PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato...

198
ALFREDO G. RODRIGUEZ Professional Electrical Engineer Reg. No. : 2633 PTR No. : 5913459 Date Issued : 05 January 2017 Issued at : Makati City TIN No : 119-179-390 TECHNICAL SPECIFICATION FOR ELECTRICAL SYSTEMS Prepared by: MEINHARDT PHILIPPINES, INC. 25F Chatham House 116 Valero cor. V.A. Rufino Sts Salcedo Village, Makati City 1227 Philippines 13 June 2017 PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05 Taft Avenue, Ermita, Manila, Philippines 100% CD

Transcript of PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato...

Page 1: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

ALFREDO G. RODRIGUEZ

Professional Electrical Engineer

Reg. No. : 2633 PTR No. : 5913459 Date Issued : 05 January 2017

Issued at : Makati City TIN No : 119-179-390

TECHNICAL SPECIFICATION FOR

ELECTRICAL SYSTEMS

Prepared by: MEINHARDT PHILIPPINES, INC. 25F Chatham House 116 Valero cor. V.A. Rufino Sts Salcedo Village, Makati City

1227 Philippines

13 June 2017

PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS – P05

Taft Avenue, Ermita, Manila, Philippines

100% CD

Page 2: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL

MEINHARDT PHILIPPINES INC.

TABLE OF CONTENTS

1. Section 16007 - Alternative Equipment and Suppliers

2. Section 16010 - Electrical General Provisions

3. Section 16050 - Basic Electrical Materials and Methods

4. Section 16051 - Common Works Results for Electrical

5. Section 16055 - Overcurrent Protective Device Coordination

6. Section 16060 - Grounding and Bonding

7. Section 16071 - Fire Stopping for Electrical Works

8. Section 16073 - Hangers and Supports for Electrical

Systems

9. Section 16074 - Electrical Equipment Noise Control,

Vibration, Isolation, and Seismic Restraints

10. Section 16080 - Startup, Testing, and Commissioning of

Electrical Equipment

11. Section 16120 - 600V Wire and Cable

12. Section 16130 - Raceways and Boxes

13. Section 16140 - Wiring Devices

14. Section 16145 - Lighting Control Devices

15. Section 16231 - Packaged Engine Generator System

16. Section 16410 - Enclosed Circuit Breakers and Disconnect

Switches

17. Section 16442 - Panelboards

18. Section 16511 - Interior Lighting

19. Section 16570 - Lighting Control System

Page 3: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Alternative Equipment and Suppliers SECTION 16007

MEINHARDT PHILIPPINES INC. Page 1 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16007-Alternative Equipment and Suppliers.doc

SECTION 16007 ALTERNATIVE EQUIPMENT AND SUPPLIERS

PART 1 – GENERAL INFORMATION

1.1 The Stipulated Bid Sum shall be for base Specification equipment only. Where a choice of

base bid equipment is given, indicate selection included in Stipulated Bid Sum by submitting this Section. Failure to complete and submit this section will indicate that the Contractor has agreed to provide the base bid equipment specified in each specification section, listed in each equipment schedule, and/or shown on the Drawings.

1.2 Submit the following list of base bid suppliers in accordance with Bid requirements.

Spec. Reference

Section

Materials/ Equipment

Base Bid Manufacturer or Supplier

16055 Overcurrent Protective

Device Coordination

ETAP, EDSA

16060

Grounding and Bonding Erico, Furse, Cadweld, Eritech, Kumwell

16071 Firestopping for Electrical Works

Promat, Metacaulk, Specseal, Hilti, Tremco

16073 Hangers & Supports Hilti Unistrutt Erico

16074

Vibration Control for Electrical Works

Amber/Booth California Dynamics Mason Industries

Sausse (Vibex) Kinetics Noise Control Vibration Eliminator

Siesmic-Restraint Devices Amber/Booth Cooper B-Line Inc. Kinetics Noise Control

Flexible Connections Crouse-Hinds

Emergency Generator Muffler

Nelson 400, Cowl, Maxim

Emergency Generator Noise Control

Industrial Acoustics, Ovil Ensys

Page 4: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Alternative Equipment and Suppliers SECTION 16007

MEINHARDT PHILIPPINES INC. Page 2 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16007-Alternative Equipment and Suppliers.doc

Spec. Reference

Section

Materials/ Equipment

Base Bid Manufacturer

or Supplier

16120 Conductors & Cables

Phelps Dodge American Wire, Columbia, Philflex

Fire Rated Cable Prysmian Keystone Lapp

Draka Pyrotech Sigma

Connectors and Splices

3M Burndy

16124 Medium Voltage Cables Phelps Dodge

Far East Prysmian Columbia

HV Splice Kits, Connectors, etc.

3M ITT Blackburn Burndy

Raychem Nexan

16130 Metallic Conduit and Tubing

Allied Matsushita/ Panasonic Smart Tube

Manhole Covers/Cast Iron Boxes

Crouse –Hinds Makati Foundry

Non-Metallic Conduit and Tubing

Atlanta Emerald Neltex Moldex

Metallic Wireway (Local)

Asiaphil, Fuji-Haya Electric, Total Power Box, Versa Trunk, System Powermark

Boxes, Enclosures and Cabinets

Appleton, Crouse-Hinds, Steel City

16140 Wiring Devices

MK Clipsal National/Panasonic

Toshiba Legrand

Page 5: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Alternative Equipment and Suppliers SECTION 16007

MEINHARDT PHILIPPINES INC. Page 3 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16007-Alternative Equipment and Suppliers.doc

Spec. Reference

Section

Materials/ Equipment

Base Bid Manufacturer

or Supplier

16211 Electricity Metering ABB EMH Siemens Emon-Demon EDMI Schneider

GE

16215 Electrical Power Monitoring ABB EMH Siemens Emon-demony EDMI Schneider

GE Landis Gyr

16200 Engine Generator Sets Engine Caterpillar MTU Cummins

Mitsubishi

Alternator Stamford Leroy-Sommer Marathon

Kato AVK Caterpillar

16264 Static Uninterruptible Power Supply

UPS Liebert Socomec GE

Eaton MGE Emerson

Battery Exide C & D

16271 Power Transformer Dry Type ABB

Siemens Cooper GE Trihal SGB-Germany Ritz WTW

16280 Power Factor Correction Equipment

ABB Siemens Nokia Schneider EPCOS

Page 6: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Alternative Equipment and Suppliers SECTION 16007

MEINHARDT PHILIPPINES INC. Page 4 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16007-Alternative Equipment and Suppliers.doc

Spec. Reference

Section

Materials/ Equipment

Base Bid Manufacturer

or Supplier

16289 Transient Voltage Surge Suppression

ASCO, GE, Altec, Simetaimer

16340 High Voltage Switchboards ABB GE Siemens

Schneider Ormazabal

16410 Enclosed Circuit Breakers and Disconnect Switches

ABB Siemens OEMB

16415 Transfer Switches ASCO, Zenitt, GE, Schneider

16430 Low Tension Switchgears

ABB Siemens Schneider GE Circuit Breaker

16435 Paralleling Switchgear Circuit Breaker ABB GE Siemens Schneider

Controller Woodward Cummins InteliGen

16442 Panelboards ABB

Schneider Siemens GE All distribution switchgear (locally-assembled) shall be from one of the following manufacturers:

1. Asiaphil Manufacturing Industries, Inc.

2. LJ Industrial Fabrication, Inc. 3. Fuji-Haya Electric, Inc. 4. System Powermark

16443 Motor Control Center

ABB Siemens Schneider

16450 Enclosed Bus Assemblies Siemens Schneider GE

Page 7: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Alternative Equipment and Suppliers SECTION 16007

MEINHARDT PHILIPPINES INC. Page 5 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16007-Alternative Equipment and Suppliers.doc

Spec. Reference

Section

Materials/ Equipment

Base Bid Manufacturer

or Supplier

16500 Luminaires and Accessories Architectural Lighting

BOH Area

Cooper Thorn Philips Beghelli

Fumaco Maxitech

Electronic Ballast

Philips Thorn Zumtobel Tridonic-Atco

Lamp Philips

Thorn GE Osram Toshiba

16690 Lightning Protection System

ESE/CVM Erico

EF Carrier

END OF SECTION

Page 8: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

PART 1 – GENERAL ........................................................................................................................ 1

1.1 WORK INCLUDED .............................................................................................................. 1 1.2 QUALITY ASSURANCE ........................................................................................................ 2 1.3 ABBREVIATIONS AND DEFINITIONS ....................................................................................... 3 1.4 REFERENCE STANDARDS ................................................................................................... 4 1.5 REGULATORY REQUIREMENTS ............................................................................................ 4 1.6 COORDINATION ................................................................................................................. 5 1.7 CHANGES TO CONTRACT WORK ......................................................................................... 5 1.8 PRE-PURCHASED EQUIPMENT ............................................................................................ 5 1.9 DEFECTS LIABILITY PERIOD ................................................................................................ 5 1.10 INSTRUCTIONS TO BIDDERS................................................................................................ 6 1.11 CASH ALLOWANCES: ......................................................................................................... 6 1.12 SEPARATE PRICES ............................................................................................................ 6 1.13 ALTERNATIVE MANUFACTURER AND SUPPLIERS.................................................................... 6 1.14 SAMPLES ......................................................................................................................... 7 1.15 EQUIPMENT SELECTION ..................................................................................................... 7 1.16 PACKING, STORAGE AND PROTECTION ................................................................................ 8 1.17 DRAWINGS AND APPROVAL ................................................................................................ 9 1.18 OPERATING AND MAINTENANCE MANUALS ......................................................................... 16 1.19 SEPARATION OF WORK BETWEEN THE TRADES .................................................................. 17

PART 2 - PRODUCTS .................................................................................................................... 24

2.1 EQUIPMENT AND MATERIALS ............................................................................................ 24

PART 3 – EXECUTION ................................................................................................................... 25

3.1 PROGRAMME .................................................................................................................. 25 3.2 PROGRESS REPORT ........................................................................................................ 25 3.3 INSPECTION, TESTING AND CERTIFICATES.......................................................................... 26 3.4 RESULTS OF TESTS ......................................................................................................... 26 3.5 TEMPORARY SERVICES .................................................................................................... 26 3.6 CUTTING AND PATCHING .................................................................................................. 26 3.7 PROTECTION .................................................................................................................. 27 3.8 PAINTING, LABELING AND FINISHING .................................................................................. 27 3.9 TEMPORARY AND TRIAL USE ............................................................................................ 29 3.10 COMPLETION .................................................................................................................. 29 3.11 INSTRUCTIONS TO OWNER ............................................................................................... 30 3.12 PROTECTION OF OWNER’S PREMISES ............................................................................... 30

Page 9: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 1 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

SECTION 16010

ELECTRICAL GENERAL PROVISIONS

PART 1 – GENERAL

1.1 WORK INCLUDED

A. These Specifications are an integral part of the Contract Documents. Tendering, Contract Requirements and General Requirements apply to Division 16 Specification Sections.

B. Work in the Specifications is divided into descriptive Sections which are not intended

to delegate functions or work to any specific Subcontractor or identify absolute contractual limits between Sub-Contractor, nor between the Contractor and his Sub-Contractor. The requirements of any one Section apply to all other Sections, for example: the motor service factor requirement. Refer to other Divisions and Sections to ensure a completed operational product and fully coordinated standard of work.

C. The direction to 'provide' equipment, materials, products, labour and services shall

be interpreted to 'supply, install and test' the Division 16 work indicated on the Drawings and specified in the Specifications.

D. Provide and include in the Contract Price Division 16 work including mechanical

components and normal system accessories not shown on the Drawings or stipulated in the Specifications, and required to ensure completed operational systems and a fully coordinated standard of Work acceptable to the MEEPF CONSULTANT and all authorities having jurisdiction.

E. The work essentially shall include, but shall not be limited to the following items:

1. Submission of technical specifications and samples of all supply items for approval by the MEEPF CONSULTANT.

2. Submission of shop drawings of all items for fabrication for approval by the

MEEPF CONSULTANT prior to fabrication.

3. Application and securing of required permits and licenses including facilitating inspection by governing agencies and payment of all fees levied therewith.

4. Provide labor and materials required to install, test and place into operation

the Electrical systems as called for in the Contract Documents, and in accordance with applicable codes and regulations.

5. Provide labor, materials, and accessories required to provide complete,

operating Electrical systems, including dismantling and/or relocation of existing utilities when required. Labor, materials or accessories not specifically called for in the Contract Documents, but required to provide complete, operating Electrical systems shall be provided without additional cost to the EMPLOYER.

6. Provide all electrical panelboards, distribution boards, submain switchboards

and main switchboards, isolators and disconnect switches. 7. Provide busduct systems, wiring, cables, raceway systems and all

accessories necessary to complete the system including hangers and supports, vibration isolations and seismic restraints.

8. Provide wiring devices and accessories including but not limited receptacle

Page 10: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 2 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

outlets, switches, occupancy sensors and photo sensors.

9. Provide grounding and lightning protection system to be connected to the existing earth termination network.

10. Provision for BMS interfacing. 11. Fire stopping of all vertical and/or horizontal pipe penetration to fire rated

areas. 12. Miscellaneous Works:-

a. Hacking of non-structural wall and partitions to provide opening for

pipes and sealing of opening around sleeves and pipes including provision of escutcheon plates.

b. Grouting of opening in walls after such pipes are in place and sealing

of all such openings if not used. c. Restoration/repair of existing structures damaged during installation.

d. Miscellaneous items and other provisions required to maintain

cleanliness level of adjacent areas during the entire duration of construction.

e. Full instruction after completing the job to the Maintenance Personnel regarding operation and maintenance operation of the entire installation. Provide complete printed/type instruction booklets (hardbound) covering maintenance operation and adjustment of each piece of equipment and list of each spare parts.

13. Testing and Commissioning including support for integrated system testing. 14. Submission of five (05) sets of operations and maintenance manuals and as-

built plans. 15. Training of Owner’s plant operators on the system’s maintenance and

operation. 16. Coordination with other trades for special requirements for this package.

(i.e. concrete pads, block-outs, relays, etc.). It shall be understood that the final location of equipment and devices (lighting fixtures, panelboards, outlets, etc) may be moved in the field by a distance of 5 meters from the location shown without extra cost, provided such notice is given prior to installation.

17. Provision of guarantee as specified in the Specifications.

1.2 QUALITY ASSURANCE

A. Comply with the current applicable codes, ordinances, and regulations of the authority or authorities having jurisdiction, the rules, regulations and requirements of the utility companies serving the project and the EMPLOYER’S insurance underwriter.

B. Drawings, specifications, codes and standards are minimum requirements. Where requirements differ, the more stringent apply.

Page 11: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 3 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

C. Should any change in drawings or specifications be required to comply with the governing regulations, notify the EMPLOYER’S REPRESENTATIVE prior to submitting bid.

D. All equipment and installations shall meet or exceed minimum requirements of the

Standards and Codes listed under item 1.3.

E. Execute work in strict accordance with the best practices of the trades in a thorough, substantial, workmanlike manner by competent workmen. Provide a competent, experienced, full-time Electrical Project Manager who is authorized to make decisions on behalf of the ELECTRICAL CONTRACTOR.

1.3 ABBREVIATIONS AND DEFINITIONS

A. Abbreviations: 1. PS Philippines Standard 2. PEC Philippine Electrical Code 3. ANSI American National Standards Institute 4. ASTM American Society for Testing and Materials 5. ETL Electrical Testing Laboratories 6. IEC International Electro-technical Committee 7. IEEE Institute of Electrical and Electronic Engineers 8. IES Illuminating Engineering Society 9. NEC National Electrical Code 10. NEMA National Electrical Manufacturer’s Association 11. NFPA National Fire Protection Association 12. UL Underwriters Laboratory

13. AMCA Air Moving & Conditioning Association 14. ADC Air Diffusion Council 15. ARI Air Conditioning & Refrigeration Institute

16. ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers 17. ASME American Society of Mechanical Engineers 18. AWWA American Water Works Association 19. PSME Philippine Society of Mechanical Engineering Code 20. NPCP National Plumbing Code of the Philippines 21. NBCP National Building Code of the Philippines 22. FCP Fire Code of the Philippines 23. IPC International Plumbing Code 24. IMC International Mechanical Code 25. FM Factory Mutual 26. NBS National Bureau of Standards 27. ASPE American Society of Plumbing Engineers (Handbook) 28. ANSI American National Standard Institute 29. ASTM American Society of Testing and Materials

B. Definitions

1. Where it is stated in these specifications to submit to MEEPF CONSULTANT for review, refer to Architectural General and Special Conditions for proper procedures.

2. FURNISH means to supply all materials, labor, equipment, testing apparatus, controls, tests, accessories, and all other items customarily required for the proper and complete application.

Page 12: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 4 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

3. INSTALL means to join, fasten, link, attach, set up or otherwise connect together before testing and turning over to Owner, complete and ready for regular operation.

4. PROVIDE means to FURNISH, INSTALL and TEST.

5. AS DIRECTED means as directed by the EMPLOYER’S

REPRESENTATIVE, or his representative.

6. CONCEALED means embedded in masonry or other construction, installed behind wall furring or within drywall partitions, furniture wiring management or installed within hung ceilings.

7. SUBMIT means submit to EMPLOYER’S REPRESENTATIVE for review.

8. “ARCHITECT”, “EMPLOYER’S REPRESENTATIVE”, “MEEPF

CONSULTANT”, “STRUCTURAL CONSULTANT”, “LEED CONSULTANT”, “COMMISSIONING AUTHORITY” the Party or Parties responsible for interpreting, accepting and otherwise ruling on the performance under “this Contract”.

9. “GENERAL CONTRACTOR”, the party responsible of the installation. 1.4 REFERENCE STANDARDS

A. Provide new materials and equipment of proven design and quality. Provide current

models of equipment with published ratings certified by recognized local and international testing and standards agencies.

B. Workmanship and installation methods shall conform to the best modern practice.

Employ skilled tradesmen to perform work under the direct supervision of fully qualified personnel.

C. Install equipment in strict accordance with manufacturers written recommendations. D. Meet ASTM, NEMA/ANSI, IEC, PS and other industry standards in the selection and

provision of equipment, materials, pipe and system components.

E. Meet NEMA/ANSI, IEC, PS Standards and PEC for the supply and installation of all equipment.

F. Meet the additional selection, sizing and performance criteria specified in this

Specification. 1.5 REGULATORY REQUIREMENTS

A. Meet the requirements and recommendations of local Municipal Ordinances.

1. PS Philippine Standard 2. PEC Philippine Electrical Code (2009 Edition). 3. PECE Philippine Electronics Code Vol 1 and 2. 4. R.A.9514 The Revised Fire Code of the Philippines 2008; 5. ANSI American National Standard Institute 6. ASTM American Society for Testing and Materials. 7. ETL Electrical Testing Laboratories. 8. IEC International Electro-Technical Committee 9. IEEE Institute of Electrical and Electronic Engineers. 10. IES Illuminating Engineering Society. 11. NEC National Electrical Code.

Page 13: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 5 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

12. NEMA National Electrical Manufacturer’s Association 13. NFPA National Fire Protection Association 14. UL Underwriters’ Laboratories Inc. 15. ISO International Standard Organization.

1.6 COORDINATION A. Coordinate and schedule Division 16 work with all other work in the same area or

with work which is dependent upon Division 16 work so as to facilitate mutual progress.

B. Identify and resolve interference problems prior to prefabrication and installation of

equipment. Submit interference drawings for review upon MEEPF CONSULTANT Request.

C. Examine the site and all Contract Documents prior to bid submission. No allowance

will be made for any difficulties encountered due to any features of the building, methods of construction, site or surrounding public and private property which existed up to the bid close.

1.7 CHANGES TO CONTRACT WORK

A. Do not proceed with any changes to the Work without written authority from the

Owner.

B. Follow procedures outlined in Tendering and Contract Requirements for administration and execution of Contract revisions.

C. Quotations for changes to Division 16 work shall be based on:

1. Methods either approved or directed by the MEEPF CONSULTANT.

1.8 PRE-PURCHASED EQUIPMENT A. Where equipment has been pre-purchased by the EMPLOYER for installation by

Division 16, assume complete responsibility for acceptance, delivery schedule, off-loading, storage, rigging, installation, protection, start-up and warranty of this equipment, all as if the equipment were provided by Division 16.

B. The responsibilities of the equipment supplier are delineated in the pre-purchase

documents which are available for ELECTRICAL CONTRACTOR review during the bid period.

D. The EMPLOYER’S REPRESENTATIVE shall bear the equipment and FOB job site shipping costs directly.

E. Request from the EMPLOYER’S REPRESENTATIVE, full details of the equipment

and the manufacturer's Shop Drawings. Include related information in the Operating and Maintenance Manual.

F. Assume extensions of warranties to meet specified times. 1.9 DEFECTS LIABILITY PERIOD

A. The Defects Liability Period for the purposes of this Sub-Contract shall be a period of

twelve months from the ‘Date of Practical Completion’, providing that during such period the ELECTRICAL CONTRACTOR shall have remedied and made good all faults or defects as described below, to the EMPLOYER’S REPRESENTATIVE

Page 14: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 6 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

satisfaction. B. During the Defects Liability Period, the ELECTRICAL CONTRACTOR shall at his

own cost remedy and make good with all possible speed any faults or defects in the Plant or Works due, in the opinion of the EMPLOYER’S REPRESENTATIVE, to faulty materials, workmanship or design and, shall indemnify the EMPLOYER against any damage or injury to the Building contents and/or occupants arising as a result of such faults or defects.

C. If the ELECTRICAL CONTRACTOR fails to remedy such faults or defects within a

reasonable time the Employer may proceed to do so at the risk and expense of the ELECTRICAL CONTRACTOR and without prejudice to such other rights as the Employer may have under the Sub-Contract.

D. Other requirements shall be as described in the relevant section of the Specification.

1.10 INSTRUCTIONS TO BIDDERS

A. The Bidder is invited to submit additional alternative prices not specifically requested

with the Bid.

B. Alternative prices may be used to establish the lowest Contract Price. C. The lowest or any Bid will not necessarily be accepted.

1.11 CASH ALLOWANCES:

A. Requirement set forth under Instruction to Bidders

1.12 SEPARATE PRICES A. Submit separate prices on the Bid Form and express as a credit or an extra to the

Stipulated Bid Sum.

B. Calculation of the Contract Price will include separate prices consistent with their acceptance or rejection by the Employer.

1.13 ALTERNATIVE MANUFACTURER AND SUPPLIERS

A. Equipment and materials are specifically described for the purpose of indicating standards of quality and workmanship. Base Bid on the items specified and shown on Drawings.

B. Alternatives for equipment or materials considered equal in quality and performance

may be submitted with the Bid Form. Supply with each alternative, following bid submission, upon request by MEEPF CONSULTANT, the following information: 1. Details of manufacture

2. Dimensions including required clearance

3. Performance data

4. The cost saving for piping and electrical changes imposed by the alternative

5. The effect upon and cost to other trades

C. Where alternatives are accepted, there will be no further cost allowances for subsequent changes in Division 16 work or other Contracts to make the alternative complete and equal to the specified equipment and materials.

Page 15: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 7 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

D. If alternative equipment, differing from that which is shown on Drawings is accepted,

prepare when requested, equipment layouts at no extra cost. Show clearly in plan, elevations and sections, all equipment details including dimensional changes. Show location changes to pipes and wiring and the effect of these changes on the building. Drawings shall be 1:50 scale.

E. The right is reserved to accept or reject any alternative.

1.14 SAMPLES

A. Within one month following the award of the Contract, the ELECTRICAL CONTRACTOR shall submit for review one set of labeled samples as follows:

1. Conduit and Fittings 2. Hangers and Supports 3. Wires and Cables 4. Wiring Devices

B. The EMPLOYER’S REPRESENTATIVE reserves the right to require samples which

show the fabrication techniques and workmanship of component parts, and the design of accessories and other auxiliary items, before any installation work process.

C. The ELECTRICAL CONTRACTOR shall submit to the EMPLOYER’S REPRESENTATIVE for endorsement, manufacturer’s specification and installation instructions for trade products.

1.15 EQUIPMENT SELECTION

A. All equipment supplied shall be in accordance with this Specification and the relevant

drawings and to the approval of the EMPLOYER’S REPRESENTATIVE. B. The capacities of all plant and equipment described in the Contract are minimum

capacities and the ELECTRICAL CONTRACTOR shall check them with the EMPLOYER’S REPRESENTATIVE taking into account any variations which may be made to the systems during the progress of the Contract Works.

C. The ELECTRICAL CONTRACTOR shall be required to demonstrate at site that the

duties required of the equipment are obtainable. D. Physical sizes of all plant and equipment are to be suitable for the space allocated

for the accommodation of such plant and equipment, taking into account the requirement of access for maintenance purposes.

E. In selecting makes and types of equipment, the ELECTRICAL CONTRACTOR shall

ascertain that facilities for proper maintenance, repair and replacement are provided. F. Where the ELECTRICAL CONTRACTOR proposes to use an item of equipment

other than that specified or detailed in the drawing, which requires any redesign of the system, drawings showing the layout of the equipment and such redesign as required therefore shall be prepared by the ELECTRICAL CONTRACTOR at his own expenses. Where such approved deviation necessitates a different quantity and arrangement of materials and equipment’s from that originally specified or indicated in the drawings, the ELECTRICAL CONTRACTOR shall furnish and install any such additional materials and equipment’s required by the system at no additional cost.

Page 16: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 8 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

G. Equipment catalogue and manufacturer's specifications must be submitted for examination and details shall be submitted for the approval of the EMPLOYER’S REPRESENTATIVE before any equipment is to be ordered.

This shall include all information necessary for the EMPLOYER’S

REPRESENTATIVE to ascertain the equipment comply with this Specification and drawings. Data and sales catalogue of a general nature will not be accepted.

H. Before ordering equipment, the ELECTRICAL CONTRACTOR shall provide the

EMPLOYER’S REPRESENTATIVE with full details of the weights and characteristics of the equipment for purposes of determining floor loading, power consumption etc.

1.16 PACKING, STORAGE AND PROTECTION

A. All materials, equipment, components and accessories shall be delivered to the Site

in a new condition, properly packed and protected against damage or contamination or distortion, breakage or structural weakening due to handling, adverse weather or other circumstances and, as far as practicable, they shall be kept in the packing cases or under approved protective coverings until required for use.

B. Any items suffering from damage during manufacture, or in transit, or on site whilst

in storage or during erection shall be rejected and replaced without extra cost to either the EMPLOYER’S REPRESENTATIVE or the GENERAL CONTRACTOR unless either of them, or their respective representatives, cause such damages.

C. In the case of such materials, equipment, components and accessories which

originate overseas: 1. The said items shall be adequately and securely packed for safe

transportation with due regard to the climatic conditions encountered in transit and on arrival.

2. British Standard 1133 and supplements, or other comparable and acceptable

code, shall be used as a guide for the standard of packing and package required. All bright polished or plated parts shall be treated with suitable corrosion preventative.

3. At the time of shipping, each consignment shall be documented with packing

lists and bills of lading which shall contain full statements of the packages consigned with particulars of the dimensions, weights, contents, shipping marks and approximate value of each package shall be provided in duplicate to the GENERAL CONTRACTOR.

D. Where it is stipulated in the Specification or elsewhere in the Contract that packages,

pallets, casks or other packaging or handling materials are returnable, then the ELECTRICAL CONTRACTOR shall forthwith upon receiving written notice to that effect from the GENERAL CONTRACTOR, remove the same from the site as any other place where the materials, equipment, components and accessories have been unpacked.

E. Neither the EMPLOYER’S REPRESENTATIVE nor the GENERAL CONTRACTOR

shall be liable for loss or damage to or return of any packages, pallets, casks or other packaging or handling materials where the ELECTRICAL CONTRACTOR fails to collect as notified by the GENERAL CONTRACTOR.

F. After delivery to site and prior to installation the ELECTRICAL CONTRACTOR shall

ensure that all materials and equipment are properly stored on site to avoid mechanical damage and the adverse effects of heat, humidity etc. The

Page 17: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 9 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

ELECTRICAL CONTRACTOR shall provide proper shelving and racking to support and protect the equipment and materials. All electrical equipment shall be stored covered in its original packaging or by plastic sheeting.

G. The ELECTRICAL CONTRACTOR shall apply an approved protective crating or fix

some other protective material to the materials, equipment, components and accessories so as to protect them after installation. In the event that the ELECTRICAL CONTRACTOR fails to do, the ELECTRICAL CONTRACTOR shall repair to the satisfaction of the EMPLOYER’S REPRESENTATIVE or supply free of all charge any replacement required to substitute for any part of the materials, equipment, components and accessories which may have been damaged in whole or in part as a result of such failure as directed by the Employers Representative and shall without prejudice to such other liabilities under this Sub-Contract, pay for all expenses and outgoing of the EMPLOYER’S REPRESENTATIVE or the GENERAL CONTRACTOR incurred in respect of the removal and disposal of the damaged parts and the installation of the substitute parts.

H. The ELECTRICAL CONTRACTOR shall be responsible for the off-loading and

handling of cables on site and shall ensure that cables are new and delivered to site on new drums and properly protected against mechanical damage and loss with manufacturer's seals still intact. Partly used drums of cables which have already been used elsewhere shall not be acceptable unless special approval is given by the EMPLOYER’S REPRESENTATIVE in writing.

I. Waterproof protection shall be applied to all electrical busbar and switchgears,

thermal insulation, and other materials susceptible to moisture damage during and after installation until handover to the EMPLOYER’S REPRESENTATIVE.

J. The ELECTRICAL CONTRACTOR shall be responsible for unpacking and removal

from site all temporary protective covers prior to the handover of the Installation to the Employer.

1.17 DRAWINGS AND APPROVAL

A. Interpretation of Drawings

1. The Specification and any drawings or other documents attached thereto and

issued by the Employers Representative shall be deemed to include, whether or not specifically mentioned or shown, any materials, accessories or work as may be necessary for the satisfactory completion of the Works. The ELECTRICAL CONTRACTOR shall make due allowance in his Tender for such materials or work.

2. Where a discrepancy exists between the drawings and Specification, or

where the interpretation of either is in doubt, the ELECTRICAL CONTRACTOR shall obtain written clarification on such matters before submitting his Tender. Any such clarification from the EMPLOYER’S REPRESENTATIVE to the ELECTRICAL CONTRACTOR or vice versa dated prior to the submission of the Tender, shall form part of the Sub-Contract Documents. If no clarification is requested and obtained by the ELECTRICAL CONTRACTOR the EMPLOYER’S REPRESENTATIVE reserves the right to select either option irrespective of the allowances the ELECTRICAL CONTRACTOR has made in his tender.

Page 18: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 10 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

B. Tender Drawings

1. Tender Drawings are generally diagrammatic and indicative of work to be

installed. Run and arrangement of piping and the positioning of apparatus shall be approximately as indicated.

2. The Tender Drawings are primarily intended to enable the Tender to prepare

his estimate and submit Tender. Where runs of piping, cables, conduits, etc. are shown to small scale these do not necessarily indicate exact positions, and all offsets fittings and accessories that may be required are not necessarily shown. The Tender Drawings are based on agreement with the EMPLOYER’S REPRESENTATIVE taking into account co-ordination with other services and no alteration in principle will be allowed without approval.

3. If directed by the EMPLOYER’S REPRESENTATIVE, the ELECTRICAL

CONTRACTOR shall, without extra charge, make reasonable modifications in the layout as needed to execute properly the work and prevent conflicts with the works of other trades.

4. After the award of the Sub-Contract, the EMPLOYER’S REPRESENTATIVE will, without charge, furnish two copies of the drawings and Specifications and will within a reasonable time also furnish such further drawings as are reasonably necessary to enable all the Employers Representative's Instructions to be carried out. The EMPLOYER’S REPRESENTATIVE will also provide all details which in the opinion of the EMPLOYER’S REPRESENTATIVE are necessary for the execution of any part of the work.

5. Additional copies of the drawings and the Specification can be provided to

the ELECTRICAL CONTRACTOR upon written request to the EMPLOYER’S REPRESENTATIVE, but the EMPLOYER’S REPRESENTATIVE will charge for such additional copies at current commercial rates.

C. Electrical Contractor’s Drawings

1. The ELECTRICAL CONTRACTOR shall prepare, or be responsible for

obtaining, the following drawings: a. Installation Drawings. b. Manufacturer's Shop Drawings. c. Builders Work Drawings. d. Progress Drawings e. Record Drawings and Charts.

2. The symbol notation on all drawings shall be the same as the Tender Drawings. New symbols, not previously used on the Tender Drawings shall be agreed with the EMPLOYER’S REPRESENTATIVE. All drawings shall have a stenciled title block and stenciled notes.

3. The ELECTRICAL CONTRACTOR shall be responsible for verifying the

accuracy of all dimensions abstracted from Tender Drawings and used in the preparation of his drawings.

Page 19: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 11 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

D. Installation Drawings

1. The ELECTRICAL CONTRACTOR shall, before the relevant work proceeds,

prepare and submit for approval by the EMPLOYER’S REPRESENTATIVE, all Installation Drawings showing details of his proposals for the execution of the Sub-Contract Works. The Installation Drawings shall be based on the Tender Drawings, and shall take into account any modifications, either to the building or to the installation which may have taken place, and incorporate details of the actual items of plant and equipment to be installed.

2. They shall be in such detail and with all necessary dimensions as to enable

the Sub-Contract Works to be installed, and shall indicate all piping and fittings necessary for installation, and also particular installation methods to be applied in certain instances.

3. The ELECTRICAL CONTRACTOR shall similarly prepare all necessary

Schedules of equipment, and necessary schematic diagrams, including internal diagrams for items of electrical equipment and diagrams showing the inter-connections between different items.

4. The ELECTRICAL CONTRACTOR’s Installation Drawings shall be prepared

to a scale of 1:100 for all services in the building and 1:50 or 1:20 for all plant rooms and similar spaces, unless otherwise approved by the EMPLOYER’S REPRESENTATIVE.

5. The ELECTRICAL CONTRACTOR shall produce and submit for approval

drawings detailing and dimensioning the following: a. Site distribution, feeder routes.

b. General layout drawings of all electrical plant and equipment included in the Contract.

c. Schematic distribution for main and sub-main distribution. d. Lighting and power layout and details. E. Manufacturer's Shop Drawings

1. The ELECTRICAL CONTRACTOR shall submit for review shop drawings of

any item of plant or equipment produced by a manufacturer or equipment supplier indicating principle dimensions, fixings, connections and all other relevant details. These shall include drawings of all control, and instrumentation panels, pumps and other equipment as requested by the EMPLOYER’S REPRESENTATIVE.

2. The ELECTRICAL CONTRACTOR shall provide engineering drawings

showing the construction, external and internal layout of panels and wiring diagrams comprising internal wiring, schematics of interlocking and external wiring diagrams, for the complete system in the panels. The drawings shall also show all electrical, pipework and capillary connections from the panels to external equipment.

F. GENERAL CONTRACTOR’s Approval of Manufacturer's Shop Drawings

1. All drawings, schedules or other information provided by Manufacturers,

Nominated Suppliers, Sub-Contractors Nominated Sub-Contractors or Specialist Contractors shall be approved by the GENERAL CONTRACTOR

Page 20: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 12 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

and such approval shall ensure that all requirements of the Sub-Contract documentation have been incorporated.

2. When this procedure has been completed, the ELECTRICAL

CONTRACTOR shall forward paper prints and pdf file of the approved drawings, or copies of the approved schedules or their information to the EMPLOYER’S REPRESENTATIVE in a similar manner to that described for the Installation drawings.

3. No order to a Manufacturer, Nominated Supplier, Nominated Contractor or

Specialist Contractor, to commence manufacture/installation shall be given until written approval has been given by the EMPLOYER’S REPRESENTATIVE.

4. Any costs arising from failure to meet the above conditions shall be borne by

the ELECTRICAL CONTRACTOR at no cost to the Sub-Contract.

G. Builders Work Information & Drawings

1. The GENERAL CONTRACTOR shall provide fully detailed Builders Work

drawings to show requirements for architectural or structural provisions necessary to facilitate the execution of the Sub-Contract Works, and allow their integration into the project. These drawings shall show dead and live loads of all plant, and fully dimensioned details of all plant bases, wall chases, and penetrations.

2. This information shall be prepared in sufficient time for incorporation in the

Main Building Contractors programme.

3. In cases where preliminary builders' work and structural information has already been given by the EMPLOYER’S REPRESENTATIVE, such information shall be confirmed by the GENERAL CONTRACTOR (including confirmation of weights of items of equipment, sizes of access ways, etc.) and incorporated on his drawings.

4. The GENERAL CONTRACTOR shall provide templates for, and supervise

all builders' work required, including drilling and plugging of walls, floors and ceilings for securing of brackets, and other builders work as is considered normal to the trade.

5. The details required by the Main Building Contractor are to be provided as

directed, which may require advance information to be provided by the GENERAL CONTRACTOR before the Works defined in this Specification are to commence. The GENERAL CONTRACTOR shall be responsible for checking any details that may have been given before commencement of the Works to ascertain that the said advance details are correct.

6. The GENERAL CONTRACTOR shall be liable for all costs associated with

the late submission or omission of builders work information.

H. Progress Drawings

1. The ELECTRICAL CONTRACTOR shall arrange for a full set of white prints

of Installation Drawings to be kept on the Site showing the progress of all work in connection with the Sub-Contract. Such prints shall be kept up-to-date before each site progress meeting, and all conduit, cable, pipe and trunking runs, positions of equipment and apparatus shall be recorded on the drawings as they are installed.

Page 21: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 13 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

2. The Progress Drawings shall be available for inspection at any time by the

EMPLOYER’S REPRESENTATIVE and Main Building Contractor.

3. The ELECTRICAL CONTRACTOR shall include for his representative to keep a diary recording the progress of the works and details of all instructions received. The diary shall be at the disposal of the EMPLOYER’S REPRESENTATIVE as and when required.

I. Record Drawings and Charts

1. The ELECTRICAL CONTRACTOR shall issue draft copies of Record

Drawings, showing the whole of the services as installed, to the Employers Representative one month prior to the start of commissioning.

2. Within one month of the Practical Completion of the installations, the

ELECTRICAL CONTRACTOR shall provide to the satisfaction of the EMPLOYER’S REPRESENTATIVE one durable plastic negative and one copy diskette (Autocad) and four complete final sets of white prints showing the whole of the services installed. Prior to this formal issue, the ELECTRICAL CONTRACTOR shall submit two copies of his proposed finalized Record Drawings to the EMPLOYER’S REPRESENTATIVE for approval.

3. Two sets of drawings for symbols shall be submitted, one of the same size

as the tender drawings, the other set shall be of A4 size suitable for eventual inclusion in the Operation and Maintenance Manual.

4. The complete symbol notation used for all Record Drawings shall be

computer generated. 5. The preparation of the Record Drawings shall proceed during the installation

of the Works as each section is completed. The EMPLOYER’S REPRESENTATIVE shall be allowed to inspect the drawings on request during their preparation.

5. In addition to the foregoing Record Drawings, the following charts and drawings

shall be laminated in plastic and hung in the plant rooms and switchgear rooms:

a. Plant room key Drawings: showing all plant item numbers, locations and duties.

b. Control Schematics c. Electrical system schematic diagrams

J. Submission of Drawings and Equipment for Review

1. Information for review must be submitted in accordance with the agreed

programme of work and in packages relating to complete buildings or previously agreed parts of the building.

The packages must include: a. Installation drawings. b. Builders work drawings.

Page 22: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 14 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

c. Associated Manufacturer's shop drawings. d. Technical information of proposed equipment and materials.

e. Any other relevant information required by the EMPLOYER’S REPRESENTATIVE.

Each submission must be accompanied by a letter which: a. Identifies the contents of the submission in detail.

b. Refer to previous submissions of the information and any relevant correspondence.

c. Refers to the purpose of the submission and any other requirements

of the ELECTRICAL CONTRACTOR.

K. Employer’s Representative’s Approval

1. The ELECTRICAL CONTRACTOR shall obtain the EMPLOYER’S

REPRESENTATIVEs review of his information before it is used for ordering, fabrication or installation. The form of review will be an examination of the drawings and/or samples by the EMPLOYER’S REPRESENTATIVE to ensure that the design criteria and engineering principles described in the Tender documents have been correctly interpreted and applied by the ELECTRICAL CONTRACTOR.

2. The review will not entail any checking of working dimensions on the

drawings.

3. The ELECTRICAL CONTRACTOR must carry out his own checking procedure before submitting information for review, this checking must cover not only his own work, but that of Manufacturers and Specialists for whom he is responsible.

4. The review of information by the EMPLOYER’S REPRESENTATIVE will in

no way relieve the ELECTRICAL CONTRACTOR of his responsibility for error in his work or of his other contractual responsibilities and obligations.

5. The ELECTRICAL CONTRACTOR shall allow a period of 2 weeks in his

programme for the Employers Representative to review and return the ELECTRICAL CONTRACTOR submission with comment. The ELECTRICAL CONTRACTOR shall also indicate in his programme time allowed for resubmission of drawings not allowed to be used for installation by the EMPLOYER’S REPRESENTATIVE.

L. Approval Codes of Material Submittals and Shopdrawings L.1 Each submittal will be returned to the ELECTRICAL CONTRACTOR

stamped or marked by the MEEPF CONSULTANT indicating the appropriate action as follows:

(A) APPROVED/UNALTERED means that fabrication, manufacture, or construction may proceed.

(B) APPROVED AS NOTED means that fabrication, manufacture, or construction may proceed provided submittal complies with the EMPLOYER’s or STRUCTURAL CONSULTANT’S comments.

Page 23: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 15 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

(BR) APPROVED AS NOTED RE-SUBMISSION IS REQUIRED If, for any reason, the Main Contractor cannot comply with the notations, the ELECTRICAL CONTRACTOR shall make revisions and resubmit as described in the notations made by the STRUCTURAL CONSULTANT.

(C) NOT APPROVED AND RE-SUBMISSION IS REQUIRED means

that the submittal does not comply with the Contract Documents and that fabrication, manufacture or construction shall not proceed. Submittals stamped C are not permitted on the Site of the Works and are not to be used. The ELECTRICAL CONTRACTOR shall make the required revisions and resubmit.

(D) NOT REVIEWED MORE INFORMATION IS REQUIRED means that

the submittal does not comply with the Contract Documents and incomplete. Submittals stamped D are not permitted on the Site of the Works and are not to be used. The ELECTRICAL CONTRACTOR shall make the required revisions and resubmit for STRUCTURAL CONSULTANTS’ review.

(E) NOT REVIEWED TO BE CHECK BY OTHERS means that the

submittal shall be review by other parties involved in the project. Submittals stamped E is consider for information only by the MEEPF CONSULTANT. The ELECTRICAL CONTRACTOR shall make sure that the submittals to be reviewed and approved by concern parties.

L.2 The ELECTRICAL CONTRACTOR shall be responsible for and shall bear

the cost of the preparation of all drawings necessary to provide those amplifications of drawings needed for completion of the construction. The GENERAL CONTRACTOR shall be responsible for the correct location of his works irrespective of approval by the EMPLOYER’S REPRESENTATIVE or MEEPF CONSULTANT and shall pay all costs and expenses incurred by other contractors due to improper location of his works.

L.3 The ELECTRICAL CONTRACTOR shall be responsible for and shall bear

the cost of alterations of the Works due to discrepancies, errors or omissions in the drawings and other particulars supplied by him whether such drawings and particulars have been approved by the EMPLOYER’S REPRESENTATIVE or MEEPF CONSULTANT.

L.4 After submittals have been approved by the EMPLOYER’S

REPRESENTATIVE or MEEPF CONSULTANT they shall not be departed from, unless resubmitted and approved by the EMPLOYER’S REPRESENTATIVE or MEEPF CONSULTANT or modified by Variation Order as provided under Conditions of Contract.

M. Co-ordination

1. The Installation Drawings shall illustrate that the ELECTRICAL

CONTRACTOR design has been coordinated and integrated with that of other MEPF CONTRACTORs, the structure, and building elements, before work commences. In addition to the Works for which he is responsible, the drawings must show the structure, adjacent building elements and the zone required by other MEPF CONTRACTOR to install, operate and maintain their equipment.

2. If the ELECTRICAL CONTRACTOR deviates from the design intent of the

Tender drawings, he shall ensure that this deviation either does not involve a

Page 24: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 16 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

change in any of the other MEPF CONTRACTOR installations or that any change necessary in the other MEPF CONTRACTOR installations does not incur an additional cost to their Sub-Contract.

3. The ELECTRICAL CONTRACTOR shall be fully liable for any cost incurred

through his lack of co-ordination.

1.18 OPERATING AND MAINTENANCE MANUALS

A. Before the handover of the installation, the ELECTRICAL CONTRACTOR shall

prepare complete Operation and Maintenance Manuals which are to be printed in English for all the installations. When these manuals have been agreed in details, the ELECTRICAL CONTRACTOR shall submit to the EMPLOYER’S REPRESENTATIVE three copies thereof suitable bound. The Operating and Maintenance Manuals must be handed over before the Date of Completion.

B. Operating and Maintenance Manuals should comprise the following:

1. A hard cover giving: the name of the development the title of the document the name and address of the installation contractor

2. Inside page giving similar information to the cover but including contact

telephone numbers for normal and emergency use. 3. Contents page.

4. Description of the installation.

5. Scheduled details of all equipment and plant.

6. Operating instructions including details of any automatic control system.

7. Maintenance and fault finding instructions including composite schedule of

routine maintenance.

8. Test reports and commissioning records.

9. Recommended spare parts and lubricants.

10. List of equipment and plant with manufacturer’s name and address and local agent, if applicable.

11. Manufacturer’s literature suitably indexed to include shop drawings, wiring

diagrams, performance curves, etc.

12. List of as-installed drawings.

13. A complete valve schedule.

C. The manual should be produced on A4 size paper, all sections should be suitably separated and readily identifiable or pages should be numbered consecutively and page numbers included in the contents page.

D. The ELECTRICAL CONTRACTOR shall provide a copy diskette and video of the

complete text of the operation and maintenance manuals.

Page 25: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 17 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

1.19 SEPARATION OF WORK BETWEEN THE TRADES

A. The following summary is an outline of the work to be “Provided”, “Furnished” or “Installed” by each of the trades included in the contract, i.e., Plumbing & Sprinkler, (Div. 15) ACMV, (Div. 15), Electrical & Electronics (Div. 16) and other Divisions 1-14.

B. In the absence of more detailed information, consider the list as specific instructions

to include such work in the named contract.

C. Abbreviations are as follows:

1. “OD” - Other Division of the Contract (not Electrical or Mechanical) 2. “Plb” - Plumbing – Division 15 3. “Spr” - Sprinkler – Division 15 4. “Mech” - Mechanical – Division 15 5. “Elec” - Electrical – Division 16 6. “F” - Furnished 7. “I” - Installed 8. “P” - Provided (Furnished and Installed)

Page 26: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 18 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

ITEM OD Plb. Spr. Mech. Elec. Remarks

Motors for Mechl., Plumbing, Fire Protection Equip’t

_

P

P

P

_

Feeder Cables from Electrical Panels to Motor Controls

_

_

_

_

P

Cables to be terminated in the Motor Controls by each trade.

Motors for Mechl., Plumbing, Fire Protection Equipment

_

P

P

P

_

Specification and drawings delineate detailed exceptions.

Wiring for Mechl., Plumbing, Fire Protection Equip’t Motors including the feeder cables from motor controller

_

P

P

P

_

Wiring for Mech’l Equipment Motor Controls and Alarms

_

P

P

P

_

Specifications and drawings delineate in detail the work to be performed by each trade.

Temporary Light and Power

_

_

_

_

_

As per Contract Documents.

Temporary Water _ _ _ _ _ As per Contract Documents.

Toilets _ _ _ _ _ As per Contract Documents.

Temporary Fire Protection

_

_

_

_

_

As per Contract Documents.

Hoisting P P P P P

Rigging P P P P P

Bracing of Building for Safe Rigging

P

_

_

_

_

Page 27: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 19 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

ITEM OD Plb Spr. Mech. Elec. Remarks

Cutting, Chasing & Patching

P

_

_

_

_

Cost where due to late installation or improper coordination of work is the responsibility of the delinquent trade.

Framed Slots and Openings in Walls, Decks and Slabs

P

_

_

_

_

Includes drilling of holes when required. Cost where due to late installation or improper coordination of work is the responsibility of the delinquent trade.

Sleeves P _ _ _ _ Waterproof Sealing of Sleeves through Waterproof

Slabs, Decks and Walls

_

P

P

P

P

Fireproof Sealing of Excess Openings in Slabs, Decks and Fire Rated Walls

_

P

P

P

P

Excavation and Backfill Inside Buildings

_

P

P

P

P

Excavation and Backfill Outside Buildings

P

_

_

_

_

Coordination with the trades. Cost where due to late installation or improper coordination of work is the responsibility of the delinquent trade.

Page 28: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 20 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

ITEM OD Plb Spr. Mech. Elec. Remarks

Keep Site and Excavation Free From Surface Water During Construction

P

_

_

_

_

Fastenings _ P P P P Supports P P P P P Concrete Encasement of Conduits

_

_

_

_

P

Below Grade Drainage Inside Building

_

P

_

_

_

Base Flashing of Electric Conduits Through Roof (Pitch Pockets)

P

_

_

_

_

Cap flashing by Trade.

Electrical Handholes, and Covers

_

_

_

_

P

Finish Painting (does not include I.D. marks or color coding specified and provided by each trade)

P

P P P P

Finished Walls and Ceiling Access Doors, Panels and Supporting Frames

P

_

_

_

_

Supplying list of location of all items requiring access doors included in the Division requiring same.

Page 29: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 21 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

ITEM OD Plb Spr. Mech. Elec. Remarks

Plaster Rings and Frames

I

_

_

_

F

Plaster rings and frame furnished in electric only for lighting fittings which are so equipped.

Rubbish Removal P P P P P Where one trade furnishes

and another installs, the installing trade removes the shipping and packing materials which accumulate.

Special Tools for Equipment Maintenance

F

F

F

F

F

Electric Power Consuming Items and Controls for Other than Mechanical Equipment, e.g. Motorized Doors

P

_

_

_

_

Concrete Foundations, Pads, Pits, Curbs, and Bases Inside Buildings

P

_

_

_

_

Furnishing exact dimensions of anchors, vibration mounts and templates included in each trade providing the associated equipment.

Concrete Foundations Pads and Bases Outside Buildings

P

_

_

_

_

Furnishing exact dimensions of anchors, vibration mounts and templates included in each trade providing the associated equipment.

Masonry Pits P _ _ _ _ Furnishings of covers and

associated frames included in each trade.

Page 30: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 22 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

ITEMS OD Plb Spr Mech. Elec. Remarks

Sump Pits P _ _ _ _ Furnishing of covers and

associated frames included in each trade.

Concrete Lined Trenches inside Building Foundations

P

_

_

_

_

Prime Coat Painting

_

P

P

P

P

Fiel Touch-up Painting of Damaged Shop Coats

_

P

P

P

P

Rustproofing Field Cut and Assembled Iron Supporting Frames and Racks

_

P

P

P

P

Grating and Exterior Wall Louvers

P

_

_

_

_

Duct Connections to Louvers

_

_

_

P

_

Equipment Delivered and Set in Place

P

_

_

_

_

Except Mechanical and Electrical Equipment by Divisions 15, & 16.

Vinyl Tape or Painted Color-

Coding, Banding Arrows and Similar Identification for Mechanical and Electrical Work

P

P

P

P

P

Page 31: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 23 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

ITEM OD Plb Spr. Mech. Elec. Remarks

Under floor and Header Duct

_

_

_

_

P

Responsibility for coordination is included in this Section.

Lighting Fixtures _ _ _ _ P See Drawings. Elevators

P

_

_

_

_

Power connections to disconnect switch included in Electrical Section.

Catwalks and Ladders to Electrical Equipment

P

_

_

_

_

Food Service Equipment

P

_

_

_

_

Line connections included in each trade.

Services to Food Service Equipment

_

P

P

P

P

Equipment P _ _ _ _ Included in each trade. Services to Laundry Equipment

_

P

P

P

P

Roughing to Equipment Furnished by Others

_

P

P

P

P

D. Each Division is required to supply all necessary supervision and coordination information to any other Division supplying work to accommodate that Division.

E. For items which are to be installed but not furnished as part of this Division, the electrical

work includes: 1. Coordination of their delivery. 2. Unloading from delivery trucks driven into any point on the property line at grade

level.

3. Safe handling and field storage up to the time of permanent placement in the project.

4. Correction of any damage, defacement or corrosion to which they may have

been subjected.

5. Field make-up and internal wiring as indicated for their proper operation.

6. Mounting in place.

Page 32: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 24 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

7. Connection to building wiring, including the purchase and installation of all

termination junction boxes necessary to adapt and connect them to this wiring.

PART 2 - PRODUCTS

2.1 EQUIPMENT AND MATERIALS

A. Provide products and materials that are new, clean, free of defects, and free of

damage and corrosion.

B. Products and materials shall not contain asbestos, PCB, CFCs, Halons, or any other material which is installed considered hazardous by the authority having jurisdiction.

C. Replace materials of less than specified quality and relocate work incorrectly

installed as directed by the MEEPF CONSULTANT or by the EMPLOYER’S REPRESENTATIVE.

D. Provide name/data plates on major components of equipment with manufacturer's

name. Model number, capacity data and electrical characteristics attached in a conspicuous place.

E. Install materials and equipment with qualified trades people.

F. Maintain uniformity of manufacturer for equipment used in similar application and

sizes.

G. Fully lubricate equipment where required.

H. Follow manufacturer’s instructions for installing, connecting, and adjusting equipment. Provide a copy of such instructions at the equipment during installation.

I. Where factory testing of equipment is required to ascertain performance, and

attendance by the EMPLOYER’S REPRESENTATIVE and MEEPF CONSULTANT is required to witness such tests, associated travel costs and subsistence shall be paid for by the ELECTRICAL CONTRACTOR.

J. Equipment capacities, ratings, etc., are scheduled or specified for job site opening

conditions. Equipment sensitive to altitude shall be derated with the method of derating identified on the submittals.

K. Enclosures for electrical equipment installed in mechanical equipment rooms shall

be NEMA type 1 gasketed. Enclosures for electrical equipment installed outdoors shall be NEMA type 3R.

L. Energy consuming equipment shall meet local energy ordinances.

Page 33: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 25 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

PART 3 – EXECUTION 3.1 PROGRAMME

A. Within 2 weeks of the letter of intent or award, the ELECTRICAL CONTRACTOR shall submit a programmed showing the details of delivery and required installation period for each system.

These details shall also be forwarded to the GENERAL CONTRACTOR, and the ELECTRICAL CONTRACTOR shall work with the GENERAL CONTRACTOR to produce an overall coordinated programmed for the works.

B. The ELECTRICAL CONTRACTOR shall make such labor available at all stages of

the works to permit the programmed to be achieved and to carry out his work in accordance with the requirements of the GENERAL CONTRACTOR and Main Construction programmed.

C. The ELECTRICAL CONTRACTOR shall include all key dates into his programmed

including the dates required of all Utility submissions and also the dates that permanent power, permanent water etc will be made available for the project.

D. The ELECTRICAL CONTRACTOR shall be responsible for informing the GENERAL

CONTRACTOR of his detailed requirements in respect of fuel, water, drainage and electrical supplies, for the testing and commissioning of the plant and equipment.

The ELECTRICAL CONTRACTOR shall immediately inform the EMPLOYER’S REPRESENTATIVE of any delays caused by labor shortages, later delivery of materials and equipment, or the failure to meet programmed by any other contractor on site, which may affect his own programmed.

E. The programmed shall be updated monthly.

3.2 PROGRESS REPORT

A. The ELECTRICAL CONTRACTOR shall submit two copies of the monthly report to the EMPLOYER’S REPRESENTATIVE containing:

1. Percentage of work completed including a BOQ comparison between and

actual and contracted work. 2. Description of executed work.

3. Problems or delay (if any) and how to solve these.

4. Special occurrences, accidents, etc.

5. List of drawings, also indicating revisions.

6. List of memos and instructions ordered by the consultant.

7. List of equipment and workers at the site.

8. Color photographs of the site showing necessary views of the work at not

less than 10 locations.

Page 34: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 26 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

3.3 INSPECTION, TESTING AND CERTIFICATES

A. Periodic inspections of the work in progress will be made to check general conformity of the work to the Contract Documents. Observed deficiencies will be reported. Correct deficiencies immediately.

B. Meet the requirements of all laws, bylaws, codes, regulations and authorities having

jurisdiction.

C. Where the Contract Documents, instructions or the governing authorities require Division 15 work to be tested, inspected or approved, give sufficient notice of its readiness for inspection and schedule the date and time for such inspection.

D. Uncover Division 15 work that is covered up without consent, upon MEEPF

CONSULTANT request, for examination and restore at no extra cost to the Owner.

E. Furnish certificates and evidence that Division 15 work meets the requirements of authorities having jurisdiction.

F. Correct deficiencies immediately upon notification.

G. Operation Tests

1. The GENERAL CONTRACTOR shall perform all tests and demonstrations as called for by the local authorities.

2. Testing procedures shall be submitted two months after the approval of

major equipment to the EMPLOYER’S REPRESENTATIVE for approval.

H. Supply of Testing Equipment

1. The GENERAL CONTRACTOR shall provide all tools and instruments required to carry out the tests given in this Section.

2. All water and electricity required for testing purposes will be supplied by the

ELECTRICAL CONTRACTOR. 3.4 RESULTS OF TESTS

A. If the test results show that the plant and equipment is not functioning in a satisfactory manner nor providing the requirements of this Specification, the EMPLOYER’S REPRESENTATIVE shall decide whether this is due to incorrectness of faulty work by the ELECTRICAL CONTRACTOR and if this be the case, the ELECTRICAL CONTRACTOR shall, when called upon, carry out at his own expense such alterations, replacements and adjustments as may be required to the EMPLOYER’S REPRESENTATIVE’s complete satisfaction. The EMPLOYER’S REPRESENTATIVE decision as to what constitutes a satisfactory test shall be final.

3.5 TEMPORARY SERVICES

A. Make connections to temporary power source provided and provide extensions for

use by Division 15/16. 3.6 CUTTING AND PATCHING

A. Give notification in time to Other Contractors of openings required for Division 15/16

Work. Supply accurate details of location and size. When this requirement is not met, bear the cost of cutting and patching.

Page 35: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 27 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

B. In existing work, cutting, patching and restoration of finished work to original

condition will be carried out by Other Contractors at the expense of Division 15/16.

C. Obtain written MEEPF CONSULTANT approval before cutting openings through structure.

D. Where new work connects with existing and where existing work is altered, cut, patch

and restore to match existing work.

3.7 PROTECTION A. Protect all Division 15/16 work from damage. Keep all equipment dry and clean at

all times.

B. Cover openings in equipment, pipes with caps or heavy gauge plastic sheeting until final connections are made.

C. Repair any damage caused by improper storage, handling or installation of

equipment and materials.

D. Protect equipment, pipes and temporary services installed by Division 15/16 from weather damage.

3.8 PAINTING, LABELING AND FINISHING

A. Materials

1. All parts of the work installed under this Specification shall be painted with approved high quality enamel paints, except those items specified as being painted by others or otherwise exempted from painting in this section of the Specification.

2. Paint shall be selected to withstand the temperature on the surface which it

is applied, and shall be suitable in all respects for the environmental conditions in which it shall be located.

3. All paint used shall be of one approved manufacture, and finishes shall be

full gloss unless otherwise specified. 4. Before ordering any primer, undercoat and finishing paint, the ELECTRICAL

CONTRACTOR shall submit the color scheme to the EMPLOYER’S REPRESETATIVE for approval.

6. Before ordering any painting materials, the ELECTRICAL CONTRACTOR

shall submit the type and manufacturer of all materials for approval.

6. The ELECTRICAL CONTRACTOR shall select all finishing and painting materials from types suitable for the surfaces to which they are applied and for the environmental conditions in each area.

B. Plant, Machinery & Equipment

1. All items of plant, machinery and equipment supplied painted ex-factory shall be given one finishing coat of full gloss enamel, except where the manufacturer's standard finish is approved.

C. Exposed Metalwork

Page 36: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 28 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

1. All exposed metalwork shall be wire-brushed and cleaned from rust, scale, dirt and grease, and shall then be given one priming coat, one undercoat and one approved color finishing coat of full gloss enamel.

2. The priming coat for exposed galvanized iron shall be an approved

galvanized iron primer.

3. The priming coat for exposed non-ferrous metalwork shall be approved as suitable for the metal to which it will be applied.

D. Concealed Metalwork

1. All galvanized iron surface concealed in roof spaces, false ceilings, building

ducts etc. shall not be painted. All black iron and steel surfaces shall be wire bushed and given one coat of zinc chromate or red lead.

E. Pipe work & Metal Sheathing

1. Pipe work and metal sheathing shall be painted as for exposed or concealed metalwork as applicable.

2. Turned parts of valves, controls etc., shall be cleaned and polished to

approval.

F. Labeling

1. All plant and equipment provided under this Specification is to be labeled in English as to duty or services, all such Labeling to correspond to schedules, diagrams, etc. to be provided as part of the Record Drawings. Labels are of white Traffolyte with black engraved lettering not less than 20mm high or as otherwise required and approved.

2. Manufacturers' nameplate shall generally be provided for all plant and

equipment and shall show serial and model numbers and date of manufacture.

3. All valves, motor starters, fans, distribution boards, gauges, contactors, cable

terminals in switchboards, circuit breakers shall have labels.

4. Labels should be attached to valves (or pipe adjacent thereto) with a light gauge metal band or alternatively to be screwed to the insulated valve box where provided. These labels shall state the valve number.

5. Distribution boards, starters etc. shall be labeled to indicate the circuit

number, phase and item controlled.

6. Labels shall be screwed or riveted to sheet metal. Adhesive fixing is not acceptable.

7. Details of exact lettering shall be agreed with the Employers Representative

prior to manufacture. 8. A complete valve schedule shall be incorporated in the as-built drawings and

this schedule shall clearly indicate the valve numbers, duty, function, size, flow rate and any other relevant information necessary to allow the Employer's plant operators to safely operate each valve and to subsequently maintain or replace the valve as required.

Page 37: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 29 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

9. The valve schedule shall clearly relate to the various system schematics to enable the entire operating sequence and circuitry to be followed.

G. Application of Painting

1. All paints shall be prepared and applied in accordance with the manufacturer's recommendations.

2. All galvanized metal surfaces shall be properly etch-primed to ensure correct

adhesion of the paint to the surface. Materials for etch-priming shall be as recommended by the paint manufacturers. Subsequent painting of galvanized surfaces shall comply with this Specification.

1. Prior to painting, all metallic surfaces except galvanized surfaces shall be

thoroughly scraped and wire brushed as necessary to remove scale, rust and swarf. Surfaces shall then be solvent cleaned to remove all oil, grease and dirt.

4. When the surfaces to be painted are clean and dry, one coat of an approved primer shall be evenly applied over the entire area. After surfaces have been primed, the Sanitary ELECTRICAL CONTRACTOR shall notify the engineers so that an inspection of the primed surfaces can be made prior to the application of the undercoat and the finishing coats.

5. When the priming coat has been approved, one coat of an approved paint

flat undercoat shall be applied. Before applying the finishing coats, the ELECTRICAL CONTRACTOR shall ensure that the undercoated surface is rubbed flat and smooth. Finally, two coats of an approved high gloss finishing paint shall be applied when all dust has been removed.

6. Each successive coating shall be completely dry prior to the application of

the next coat. The minimum thickness of each layer to be 50u. 3.9 TEMPORARY AND TRIAL USE

A. Obtain written permission from Consultant to use and test permanent equipment and

systems prior to Substantial Performance acceptance by Consultant.

B. Consultant may use equipment and systems for test purposes prior to acceptance. Provide labour, fuel, material and instruments required for testing. Rectify incomplete work immediately to the satisfaction of Consultant.

C. Protect equipment and system openings from dirt, dust and other foreign materials

during temporary usage.

D. Clean and renew equipment and systems used prior to acceptance.

E. Warranty, including duration and commencement date, shall not to be affected by start-up date of equipment.

3.10 COMPLETION

A. Remove all debris from inside Division 15/16 systems and equipment.

B. Rectify deficiencies and complete work before submitting request for Substantial

Performance inspection.

C. Follow manufacturer's written instructions regarding bearing lubrication. Remove

Page 38: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 30 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

grease from pillow block type bearings and install new grease before equipment is put into operation.

D. Check and align all drives to manufacturer's acceptable tolerances.

E. Check and align all pumps to manufacturer's acceptable tolerances.

H. Remove all temporary protection and covers.

I. Remove oil and grease from equipment and bases.

J. Clean all fixtures and equipment. Polish all plated surfaces.

I. Change air and water filters.

J. Remove, clean and reinstall pipeline strainer screens.

K. Leave Division 15/16 work in as new working order.

3.11 INSTRUCTIONS TO OWNER A. Submit to Owner, check lists for each system or piece of equipment, indicating that

all components have been checked and are complete prior to instruction period.

B. Thoroughly instruct the Owner in the safe and efficient operation of the systems and equipment.

C. Arrange and pay for the services of qualified manufacturer's representatives to

instruct Owner on specialized portions of the installation, such as refrigeration machines, boilers, automatic and water treatment.

D. Submit a complete record of instructions given to the EMPLOYER. For each

instruction period, supply the following data:

1. Date 2. Duration 3. System or equipment involved 4. Names of persons giving instructions 5. Names of persons being instructed 6. Other persons present

E. Submit receipted verification of completed training to MEEPF CONSULTANT prior to

final release of retentions.

F. Carry out instructional period during a period of 5 days scheduled at Owner's convenience.

G. Video tape all instructional sessions and turn over copy of tape to Owner upon

completion of training period. 3.12 PROTECTION OF OWNER’S PREMISES

A. Adhere strictly to the EMPLOYER'S requirements. B. Confer with the EMPLOYER concerning schedule, dust and noise control prior to

commencing work in or adjacent to existing facilities where such work might affect either those facilities or their occupants.

C. Execute work with least possible interference or disturbance to occupants, public and

Page 39: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical General Provisions SECTION 16010

MEINHARDT PHILIPPINES INC. Page 31 of 31 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16010-Electrical General Provisions.doc

normal use of premises.

D. Provide temporary means to maintain security when security has been reduced by Division 15/16.

E. Only elevators assigned for Contractor's use may be used for moving men and

material within building. Protect walls of passenger elevators, to approval of Owner prior to use. Accept liability for damage, safety of equipment and overloading of existing equipment.

F. Provide temporary dust screens, barriers, warning signs in locations where

renovations and alteration work is adjacent to areas which will be operative during work.

G. Drawings indicate approximate locations of known existing underground and above

ground facilities. Avoid damage to existing services. Bear cost of repairs and replacements.

H. Immediately advise MEEPF CONSULTANT when unknown services are

encountered and await instructions.

I. Accept liability for costs incurred by the EMPLOYER in repairing and cleaning equipment, etc., resulting from failure to comply with the above requirements.

END OF SECTION

Page 40: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Basic Electrical Materials and Methods SECTION 16050

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16050-Basic Electrical Materials and Methods.doc

PART 1 - GENERAL .......................................................................................................................... 1

1.1 RELATED DOCUMENTS .......................................................................................................... 1 1.2 SUMMARY ............................................................................................................................ 1 1.3 DEFINITIONS ........................................................................................................................ 1 1.4 SUBMITTALS ........................................................................................................................ 2 1.5 QUALITY ASSURANCE ........................................................................................................... 3 1.6 COORDINATION ................................................................................................................... 3

PART 2 - PRODUCTS ........................................................................................................................... 3

2.1 MANUFACTURED PRODUCTS ................................................................................................. 3

PART 3 – EXECUTION ......................................................................................................................... 4

3.1 MANDATORY REQUIREMENTS ................................................................................................ 4 3.2 EQUIPMENT INSTALLATION AND REQUIREMENTS ...................................................................... 4 3.3 EQUIPMENT IDENTIFICATION .................................................................................................. 4 3.4 EQUIPMENT PROTECTION ...................................................................................................... 5 3.5 SINGULAR NUMBER .............................................................................................................. 5

Page 41: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Basic Electrical Materials and Methods SECTION 16050

MEINHARDT PHILIPPINES INC. Page 1 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16050-Basic Electrical Materials and Methods.doc

SECTION 16050 BASIC ELECTRICAL MATERIALS AND METHODS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. This section, basic electrical materials and methods applies to all sections of division

16, division 1 specifications and Section 16010 Electrical General Provisions.

1.2 SUMMARY

A. Furnish and install electrical wirings, systems, equipment and accessories in

accordance with the specifications and drawings. Capacities and ratings of transformers, cable, switchboards, switchgear, panelboards and other items and arrangements for the specified items are shown on the drawings.

B. Electrical service entrance equipment (arrangements for temporary and permanent

connections to the power company's system) shall conform to the power company's requirements. Coordinate fuses, circuit breakers and relays with the power company's system and obtain power company approval for sizes and settings of these devices.

C. Wiring ampacities specified or shown on the drawings are based on copper

conductors with the conduit and raceways accordingly sized. Aluminum conductors are prohibited.

1.3 DEFINITIONS

A. Listed; equipment or device of a kind mentioned which:

a. Is published by a nationally recognized laboratory which makes periodic

inspection of production of such equipment. b. States that such equipment meets nationally recognized standards or has been

tested and found safe for use in a specified manner. B. Labeled; equipment or device is when:

a. It embodies a valid label, symbol or other identifying mark of a nationally

recognized testing laboratory such as Underwriters Laboratories, Inc. b. The laboratory makes periodic inspections of the production of such equipment. c. The labeling indicates compliance with nationally recognized standards or tests to

determine safe use in a specified manner. C. Certified; equipment or product is which:

a. Has been tested and found by a nationally recognized testing laboratory to meet

nationally recognized standards or to be safe for use in a specified manner. b. Production of equipment or product is periodically inspected by a nationally

recognized testing laboratory. c. Bears a label, tag or other record of certification.

D. Nationally recognized testing laboratory; laboratory which is approved, in accordance

with OSHA regulations.

Page 42: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Basic Electrical Materials and Methods SECTION 16050

MEINHARDT PHILIPPINES INC. Page 2 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16050-Basic Electrical Materials and Methods.doc

1.4 SUBMITTALS

A. The EMPLOYER’S approval through the EMPLOYER’S CONSULTANT(S) and

representative shall be obtained for all equipment and material before delivery to the job site. Delivery, storage or installation of equipment or material; which has no approval from the EMPLOYER’S CONSULTANT(S) or representative will not be permitted at the job site.

B. All submittals shall include adequate descriptive literature, catalog cuts, shop

drawings and other data necessary for the employer to ascertain that the proposed equipment and materials comply with specification requirements. Catalog cuts submitted for approval shall be legible and clearly identify equipment being submitted.

C. Submittals for individual systems and equipment assemblies which consist of more

than one item or component shall be made for the system or assembly as a whole. Partial submittals will not be considered for approval.

1. Mark the submittals, "SUBMITTED UNDER SECTION 16000". 2. Submittals shall be marked to show specification reference including the section

and paragraph numbers. 3. Submit each section separately.

D. The submittals shall include the following:

1. Information that confirms compliance with Contract requirements. Include the manufacturer's name, model or catalog numbers, catalog information, technical data sheets, shop drawings, pictures, nameplate data and test reports as required.

2. Elementary and interconnection wiring diagrams for communication and signal systems, control system and equipment assemblies. All terminal points and wiring shall be identified on wiring diagrams.

3. Parts list which shall include those replacement parts recommended by the equipment manufacturer, quantity of parts, current price and availability of each part.

F. Manuals:

1. Maintenance and Operation Manuals: Requirement set forth under Instruction to

Bidders. G. Approvals will be based on complete submission of manuals together with shop

drawings. H. After approval and prior to installation, furnish the Engineer with one sample of each

of the following:

1. A 300 mm (12 inch) length of each type and size of wire and cable along with the tag from the coils of reels from which the samples were taken.

2. Each type of conduit coupling, bushing and termination fitting. 3. Conduit hangers, clamps and supports. 4. Duct sealing compound. 5. Each type of receptacle, toggle switch, outlet box, manual motor starter,

device plate, engraved nameplate, wire and cable splicing and terminating material and single pole molded case circuit breaker.

6. Each type of light fixture specified in Section 16500 or shown on the drawings.

Page 43: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Basic Electrical Materials and Methods SECTION 16050

MEINHARDT PHILIPPINES INC. Page 3 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16050-Basic Electrical Materials and Methods.doc

1.5 QUALITY ASSURANCE

A. All materials and equipment shall be listed, labeled or certified by a nationally

recognized testing laboratory to meet Underwriters Laboratories, Inc., standards where test standards have been established. Evidence of compliance shall include certified test reports and definitive shop drawings.

B. Manufacturers Qualifications: The manufacturer shall regularly and presently

produce, as one of the manufacturer's principal products, the equipment and material specified for this project, and shall have manufactured the item for at least three years.

C. Product Qualification:

1. Manufacturer's product shall have been in satisfactory operation, on three

installations of similar size and type as this project, for approximately fifteen (15) years, unless noted otherwise.

2. The Owner reserves the right to require the Contractor to submit a list of installations where the products have been in operation before approval.

D. Service Qualifications: There shall be a permanent service organization maintained or

trained by the manufacturer which will render satisfactory service to this installation within four hours of receipt of notification that service is needed. Submit name and address of service organizations.

1.6 COORDINATION

A. Coordinate location of equipment and conduit with other trades to minimize

interferences. See Section 16010 – Electrical General Provisions.

PART 2 - PRODUCTS

2.1 MANUFACTURED PRODUCTS

A. Materials and equipment furnished shall be of current production by manufacturers

regularly engaged in the manufacture of such items, for which replacement parts shall be available.

B. When more than one unit of the same class of equipment is required, such units shall

be the product of a single manufacturer. C. Equipment Assemblies and Components:

1. Components of an assembled unit need not be products of the same

manufacturer. 2. Manufacturers of equipment assemblies, which include components made by

others, shall assume complete responsibility for the final assembled unit. 3. Components shall be compatible with each other and with the total assembly

for the intended service. 4. Constituent parts which are similar shall be the product of a single

manufacturer. D. Factory wiring shall be identified on the equipment being furnished and on all wiring

diagrams. E. When Factory Testing Is Specified:

Page 44: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Basic Electrical Materials and Methods SECTION 16050

MEINHARDT PHILIPPINES INC. Page 4 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16050-Basic Electrical Materials and Methods.doc

1. The EMPLOYER shall have the option of witnessing factory tests. The

GENERAL CONTRACTOR shall notify the EMPLOYER through the EMPLOYER’S REPRESENATIVE a minimum of 15 working days prior to the manufacturers making the factory tests.

2. Four copies of certified test reports containing all test data shall be furnished

to the MEEPF CONSULTANT prior to final inspection and not more than 90 days after completion of the tests.

3. When equipment fails to meet factory test and re-inspection is required, the

Contractor shall be liable for all additional expenses, including expenses of the EMPLOYER/EMPLOYER’S REPRESENTATIVE.

PART 3 – EXECUTION

3.1 MANDATORY REQUIREMENTS

A. References to the Philippine Electrical Code (PEC), Underwriters Laboratories, Inc.

(UL) and National Fire Protection Association (NFPA) National Electrical Code (NEC) are minimum installation requirement standards.

B. Drawings and other specification sections shall govern in those instances where

requirements are greater than those specified in the above standards.

3.2 EQUIPMENT INSTALLATION AND REQUIREMENTS

A. Equipment location shall be as close as practical to locations shown on the drawings. B. Working spaces shall not be less than specified in the PEC for all voltages specified. C. Inaccessible Equipment:

1. Where the MEEPF CONSULTANT determines that the GENERAL

CONTRACTOR has installed equipment not conveniently accessible for operation and maintenance, the equipment shall be removed and re-installed as directed at no additional cost to the EMPLOYER.

2. "Conveniently accessible" is defined as being capable of being reached without the use of ladders, or without climbing or crawling under or over obstacles such as, but not limited to, motors, pumps, belt guards, transformers, piping, ductwork, conduit and raceways.

3.3 EQUIPMENT IDENTIFICATION

A. In addition to the requirements of the PEC, install an identification sign which clearly

indicates information required for use and maintenance of items such as panelboards, cabinets, motor controllers (starters), safety switches, separately enclosed circuit breakers, individual breakers and controllers in switchboards, switchgear and motor control assemblies, control devices and other significant equipment.

B. Nameplates shall be laminated black phenolic resin with a white core with engraved

lettering, a minimum of 6 mm (1/4-inch) high. Secure nameplates with screws. Nameplates that are furnished by manufacturer as a standard catalog item, or where other method of identification is herein specified, are exceptions.

Page 45: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Basic Electrical Materials and Methods SECTION 16050

MEINHARDT PHILIPPINES INC. Page 5 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16050-Basic Electrical Materials and Methods.doc

3.4 EQUIPMENT PROTECTION

Equipment and materials shall be protected during shipment and storage against physical

damage, dirt, moisture, cold and rain. A. During installation, enclosures, equipment, controls, controllers, circuit protective

devices and other like items, shall be protected against entry of foreign matter; and be vacuum cleaned both inside and outside before testing and operating and repainting if required.

B. Damaged equipment shall be, as determined by the MEEPF CONSULTANT, placed

in first class operating condition or be returned to the source of supply for repair or replacement.

C. Painted surfaces shall be protected with factory installed removable heavy kraft

paper, sheet vinyl or equal. D. Damaged paint on equipment and materials shall be refinished with the same quality

of paint and workmanship as used by the manufacturer so repaired areas is not obvious.

3.5 SINGULAR NUMBER

Where any device or part of equipment is referred to in these specifications in the singular

number (e.g., "the switch"), this reference shall be deemed to apply to as many such devices as are required to complete the installation as shown on the drawings.

END OF SECTION

Page 46: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Common Work Results for Electrical SECTION 16051

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16051-Common Work Results for Electrical.doc

PART 1 - GENERAL ......................................................................................................................... 1

1.1 RELATED DOCUMENTS .......................................................................................................... 1 1.2 SUMMARY ............................................................................................................................ 1 1.3 DEFINITIONS ........................................................................................................................ 1 1.4 SUBMITTALS ........................................................................................................................ 1 1.5 COORDINATION .................................................................................................................... 1

PART 2 - PRODUCTS ....................................................................................................................... 2

2.1 SLEEVES FOR RACEWAYS AND CABLES .................................................................................. 2 2.2 SLEEVE SEALS ..................................................................................................................... 2 2.3 GROUT ................................................................................................................................ 2

PART 3 - EXECUTION ...................................................................................................................... 3

3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION ....................................................... 3 3.2 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS .......................................................... 3 3.3 SLEEVE-SEAL INSTALLATION.................................................................................................. 4 3.4 FIRESTOPPING ..................................................................................................................... 4

Page 47: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Common Work Results for Electrical SECTION 16051

MEINHARDT PHILIPPINES INC. Page 1 of 4 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16051-Common Work Results for Electrical.doc

SECTION 16051 COMMON WORK RESULTS FOR ELECTRICAL

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, the following section of Division 16 and Division 1 Specification Sections, apply to this Section. 1. 16074 – Vibration Control for Electrical Systems 2. 16130 – Raceway & Boxes 3. 16120 – Conductors & Cables 4. 16410 – Disconnect Switches 5. 16442 – Panelboards

1.2 SUMMARY

A. Section Includes:

1. Electrical equipment coordination and installation. 2. Sleeves for raceways and cables. 3. Sleeve seals. 4. Grout. 5. Common electrical installation requirements.

1.3 DEFINITIONS

A. EPDM: Ethylene-propylene-diene terpolymer rubber.

B. NBR: Acrylonitrile-butadiene rubber.

1.4 SUBMITTALS

A. Product Data: For sleeve seals.

1.5 COORDINATION

A. Coordinate arrangement, mounting, and support of electrical equipment:

1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.

2. To provide for ease of disconnecting the equipment with minimum interference to other installations.

3. To allow right of way for piping and conduit installed at required slope. 4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of

obstructions and of the working and access space of other equipment.

B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.

Page 48: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Common Work Results for Electrical SECTION 16051

MEINHARDT PHILIPPINES INC. Page 2 of 4 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16051-Common Work Results for Electrical.doc

C. Coordinate location of access panels and doors for electrical items that are behind finished surfaces or otherwise concealed. Access doors and panels are specified in Division 8 Section "Access Doors and Frames."

D. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 7 Section 078413 "Penetration Firestopping".

PART 2 - PRODUCTS

2.1 SLEEVES FOR RACEWAYS AND CABLES

A. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated.

B. Sleeves for Rectangular Openings: Galvanized sheet steel.

1. Minimum Metal Thickness:

a. For sleeve cross-section rectangle perimeter less than 50 inches (1270 mm) and no side more than 16 inches (400 mm), thickness shall be 0.052 inch (1.3 mm).

b. For sleeve cross-section rectangle perimeter equal to, or more than, 50 inches (1270 mm) and 1 or more sides equal to, or more than, 16 inches (400 mm), thickness shall be 0.138 inch (3.5 mm).

2.2 SLEEVE SEALS

A. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and raceway or cable.

1. Acceptable Manufacturers: See Section 16007 “Alternative Equipment and Suppliers”

2. Sealing Elements: EPDM, NBR interlocking links shaped to fit surface of cable or conduit. Include type and number required for material and size of raceway or cable.

3. Pressure Plates: Carbon steel. Include two for each sealing element. 4. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of length

required to secure pressure plates to sealing elements. Include one for each sealing element.

2.3 GROUT

A. Nonmetallic, Shrinkage-Resistant Grout: ASTM C 1107, factory-packaged, nonmetallic aggregate grout, noncorrosive, non-staining, mixed with water to consistency suitable for application and a 30-minute working time.

Page 49: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Common Work Results for Electrical SECTION 16051

MEINHARDT PHILIPPINES INC. Page 3 of 4 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16051-Common Work Results for Electrical.doc

PART 3 - EXECUTION

3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with NECA 1.

B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.

C. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.

D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.

E. Right of Way: Give to piping systems installed at a required slope.

3.2 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS

A. Electrical penetrations occur when raceways, cables, wireways, cable trays, or busways penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall assemblies.

B. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of slabs and walls.

C. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.

D. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless openings compatible with firestop system used are fabricated during construction of floor or wall.

E. Cut sleeves to length for mounting flush with both surfaces of walls.

F. Extend sleeves installed in floors 2 inches (50 mm) above finished floor level.

G. Size pipe sleeves to provide 1/4-inch (6.4-mm) annular clear space between sleeve and raceway or cable, unless indicated otherwise.

H. Seal space outside of sleeves with grout for penetrations of concrete and masonry

1. Promptly pack grout solidly between sleeve and wall so no voids remain. Tool exposed surfaces smooth; protect grout while curing.

I. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location of joint. Comply with requirements in Division 7 Section "Joint Sealants."

J. Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at raceway and cable penetrations. Install sleeves and seal raceway and cable penetration sleeves with firestop materials. Comply with requirements in Division 7 Section "Through-Penetration Firestop Systems."

Page 50: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Common Work Results for Electrical SECTION 16051

MEINHARDT PHILIPPINES INC. Page 4 of 4 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16051-Common Work Results for Electrical.doc

K. Roof-Penetration Sleeves: Seal penetration of individual raceways and cables with flexible boot-type flashing units applied in coordination with roofing work.

L. Aboveground, Exterior-Wall Penetrations: Seal penetrations using steel pipe sleeves and mechanical sleeve seals. Select sleeve size to allow for 1-inch (25-mm) annular clear space between pipe and sleeve for installing mechanical sleeve seals.

M. Underground, Exterior-Wall Penetrations: Install cast-iron pipe sleeves. Size sleeves to allow for 1-inch (25-mm) annular clear space between raceway or cable and sleeve for installing mechanical sleeve seals.

3.3 SLEEVE-SEAL INSTALLATION

A. Install to seal exterior wall penetrations.

B. Use type and number of sealing elements recommended by manufacturer for raceway or cable material and size. Position raceway or cable in center of sleeve. Assemble mechanical sleeve seals and install in annular space between raceway or cable and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.

3.4 FIRESTOPPING

A. Apply firestopping to penetrations of fire-rated floor and wall assemblies for electrical installations to restore original fire-resistance rating of assembly. Firestopping materials and installation requirements are specified in Section 16071.

END OF SECTION

Page 51: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Overcurrent Protective Device Coordination SECTION 16055

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16055-Overcurrent Protective Device Coordination.DOC

PART 1 - GENERAL ......................................................................................................................... 1

1.1 RELATED DOCUMENTS .......................................................................................................... 1 1.2 SUMMARY ............................................................................................................................ 1 1.3 SUBMITTALS ........................................................................................................................ 1 1.4 QUALITY ASSURANCE ........................................................................................................... 1

PART 2 - PRODUCTS ....................................................................................................................... 2

2.1 COMPUTER SOFTWARE DEVELOPERS ..................................................................................... 2 2.2 COMPUTER SOFTWARE PROGRAM REQUIREMENTS .................................................................. 2

PART 3 - EXECUTION ...................................................................................................................... 2

3.1 EXAMINATION ....................................................................................................................... 2 3.2 POWER SYSTEM DATA .......................................................................................................... 2 3.3 FAULT-CURRENT STUDY ....................................................................................................... 3 3.4 COORDINATION STUDY.......................................................................................................... 4

Page 52: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Overcurrent Protective Device Coordination SECTION 16055

MEINHARDT PHILIPPINES INC. Page 1 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16055-Overcurrent Protective Device Coordination.DOC

SECTION 16055 OVERCURRENT PROTECTIVE DEVICE COORDINATION

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices shall be set based on results of the protective device coordination study.

1. Coordination of series-rated devices is permitted where indicated on Drawings.

1.3 SUBMITTALS

A. Product Data: For computer software program to be used for studies.

B. Product Certificates: For coordination-study and fault-current-study computer software programs, certifying compliance with IEEE 399.

C. Qualification Data: For coordination-study specialist.

D. Other Action Submittals: The following submittals shall be made after the approval process for system protective devices has been completed. Submittals may be in digital form.

1. Coordination-study input data, including completed computer program input data sheets.

2. Study and Equipment Evaluation Reports. 3. Coordination-Study Report.

1.4 QUALITY ASSURANCE

A. Studies shall use computer programs that are distributed nationally and are in wide use. Software algorithms shall comply with requirements of standards and guides specified in this Section. Manual calculations are not acceptable.

B. Coordination-Study Specialist Qualifications: An entity experienced in the application of computer software used for studies, having performed successful studies of similar magnitude on electrical distribution systems using similar devices.

1. Professional engineer, licensed in the state where Project is located, shall be responsible for the study. All elements of the study shall be performed under the direct supervision and control of engineer.

C. Comply with IEEE 242 for short-circuit currents and coordination time intervals.

D. Comply with IEEE 399 for general study procedures.

Page 53: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Overcurrent Protective Device Coordination SECTION 16055

MEINHARDT PHILIPPINES INC. Page 2 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16055-Overcurrent Protective Device Coordination.DOC

PART 2 - PRODUCTS

2.1 COMPUTER SOFTWARE DEVELOPERS

A. Acceptable Software: See Section 16007 “Alternative Equipment and Suppliers”

2.2 COMPUTER SOFTWARE PROGRAM REQUIREMENTS

A. Comply with IEEE 399.

B. Analytical features of fault-current-study computer software program shall include "mandatory," "very desirable," and "desirable" features as listed in IEEE 399.

C. Computer software program shall be capable of plotting and diagramming time-current-characteristic curves as part of its output. Computer software program shall report device settings and ratings of all overcurrent protective devices and shall demonstrate selective coordination by computer-generated, time-current coordination plots.

1. Optional Features:

a. Arcing faults. b. Simultaneous faults. c. Explicit negative sequence. d. Mutual coupling in zero sequence.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine Project overcurrent protective device submittals for compliance with electrical distribution system coordination requirements and other conditions affecting performance. Devices to be coordinated are indicated on Drawings.

1. Proceed with coordination study only after relevant equipment submittals have been assembled. Overcurrent protective devices that have not been submitted and approved prior to coordination study may not be used in study.

3.2 POWER SYSTEM DATA

A. Gather and tabulate the following input data to support coordination study:

1. Product Data for overcurrent protective devices specified in other Division 16 Sections and involved in overcurrent protective device coordination studies. Use equipment designation tags that are consistent with electrical distribution system diagrams, overcurrent protective device submittals, input and output data, and recommended device settings.

2. Impedance of utility service entrance. 3. Electrical Distribution System Diagram: In hard-copy and electronic-copy formats,

showing the following:

a. Circuit-breaker and fuse-current ratings and types. b. Relays and associated power and current transformer ratings and ratios.

Page 54: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Overcurrent Protective Device Coordination SECTION 16055

MEINHARDT PHILIPPINES INC. Page 3 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16055-Overcurrent Protective Device Coordination.DOC

c. Transformer kilovolt amperes, primary and secondary voltages, connection type, impedance, and X/R ratios.

d. Generator kilovolt amperes, size, voltage, and source impedance. e. Cables: Indicate conduit material, sizes of conductors, conductor material,

insulation, and length. f. Busway ampacity and impedance. g. Motor horsepower and code letter designation according to NEMA MG 1.

4. Data sheets to supplement electrical distribution system diagram, cross-referenced with tag numbers on diagram, showing the following:

a. Special load considerations, including starting inrush currents and frequent starting and stopping.

b. Transformer characteristics, including primary protective device, magnetic inrush current, and overload capability.

c. Motor full-load current, locked rotor current, service factor, starting time, type of start, and thermal-damage curve.

d. Generator thermal-damage curve. e. Ratings, types, and settings of utility company's overcurrent protective devices. f. Special overcurrent protective device settings or types stipulated by utility

company. g. Time-current-characteristic curves of devices indicated to be coordinated. h. Manufacturer, frame size, interrupting rating in amperes rms symmetrical,

ampere or current sensor rating, long-time adjustment range, short-time adjustment range, and instantaneous adjustment range for circuit breakers.

i. Manufacturer and type, ampere-tap adjustment range, time-delay adjustment range, instantaneous attachment adjustment range, and current transformer ratio for overcurrent relays.

j. Panelboards, switchboards, motor-control center ampacity, and interrupting rating in amperes rms symmetrical.

3.3 FAULT-CURRENT STUDY

A. Calculate the maximum available short-circuit current in amperes rms symmetrical at circuit-breaker positions of the electrical power distribution system. The calculation shall be for a current immediately after initiation and for a three-phase bolted short circuit at each of the following:

1. Switchgear and switchboard bus. 2. Medium-voltage controller. 3. Motor-control center. 4. Distribution panelboard. 5. Branch circuit panelboard.

B. Study electrical distribution system from normal and alternate power sources throughout electrical distribution system for Project. Include studies of system-switching configurations and alternate operations that could result in maximum fault conditions.

C. Calculate momentary and interrupting duties on the basis of maximum available fault current.

D. Calculations to verify interrupting ratings of overcurrent protective devices shall comply with IEEE 141, IEEE 241 and IEEE 242.

1. Transformers:

a. ANSI C57.12.10. b. ANSI C57.12.22. c. ANSI C57.12.40.

Page 55: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Overcurrent Protective Device Coordination SECTION 16055

MEINHARDT PHILIPPINES INC. Page 4 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16055-Overcurrent Protective Device Coordination.DOC

d. IEEE C57.12.00. e. IEEE C57.96.

2. Medium-Voltage Circuit Breakers: IEEE C37.010. 3. Low-Voltage Circuit Breakers: IEEE 1015 and IEEE C37.20.1. 4. Low-Voltage Fuses: IEEE C37.46.

E. Study Report:

1. Show calculated X/R ratios and equipment interrupting rating (1/2-cycle) fault currents on electrical distribution system diagram.

2. Show interrupting (5-cycle) and time-delayed currents (6 cycles and above) on medium- and high-voltage breakers as needed to set relays and assess the sensitivity of overcurrent relays.

F. Equipment Evaluation Report:

1. For 600-V overcurrent protective devices, ensure that interrupting ratings are equal to or higher than calculated 1/2-cycle symmetrical fault current.

2. For devices and equipment rated for asymmetrical fault current, apply multiplication factors listed in the standards to 1/2-cycle symmetrical fault current.

3. Verify adequacy of phase conductors at maximum three-phase bolted fault currents; verify adequacy of equipment grounding conductors and grounding electrode conductors at maximum ground-fault currents. Ensure that short-circuit withstand ratings are equal to or higher than calculated 1/2-cycle symmetrical fault current.

3.4 COORDINATION STUDY

A. Perform coordination study using approved computer software program. Prepare a written report using results of fault-current study. Comply with IEEE 399.

1. Calculate the maximum and minimum 1/2-cycle short-circuit currents. 2. Calculate the maximum and minimum interrupting duty (5 cycles to 2 seconds) short-

circuit currents. 3. Calculate the maximum and minimum ground-fault currents.

B. Comply with IEEE 141, IEEE 241, IEEE 242 recommendations for fault currents and time intervals.

C. Transformer Primary Overcurrent Protective Devices:

1. Device shall not operate in response to the following:

a. Inrush current when first energized. b. Self-cooled, full-load current or forced-air-cooled, full-load current, whichever is

specified for that transformer. c. Permissible transformer overloads according to IEEE C57.96 if required by

unusual loading or emergency conditions.

2. Device settings shall protect transformers according to IEEE C57.12.00, for fault currents.

D. Motors served by voltages more than 600 V shall be protected according to IEEE 620.

E. Conductor Protection: Protect cables against damage from fault currents according to ICEA P-32-382, ICEA P-45-482, and conductor melting curves in IEEE 242. Demonstrate that equipment withstands the maximum short-circuit current for a time equivalent to the tripping time of the primary relay protection or total clearing time of the fuse. To determine

Page 56: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Overcurrent Protective Device Coordination SECTION 16055

MEINHARDT PHILIPPINES INC. Page 5 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16055-Overcurrent Protective Device Coordination.DOC

temperatures that damage insulation, use curves from cable manufacturers or from listed standards indicating conductor size and short-circuit current.

F. Coordination-Study Report: Prepare a written report indicating the following results of coordination study:

1. Tabular Format of Settings Selected for Overcurrent Protective Devices:

a. Device tag. b. Relay-current transformer ratios; and tap, time-dial, and instantaneous-pickup

values. c. Circuit-breaker sensor rating; and long-time, short-time, and instantaneous

settings. d. Fuse-current rating and type. e. Ground-fault relay-pickup and time-delay settings.

2. Coordination Curves: Prepared to determine settings of overcurrent protective devices to achieve selective coordination. Graphically illustrate that adequate time separation exists between devices installed in series, including power utility company's upstream devices. Prepare separate sets of curves for the switching schemes and for emergency periods where the power source is local generation. Show the following information:

a. Device tag. b. Voltage and current ratio for curves. c. Three-phase and single-phase damage points for each transformer. d. No damage, melting, and clearing curves for fuses. e. Cable damage curves. f. Transformer inrush points. g. Maximum fault-current cutoff point.

G. Completed data sheets for setting of overcurrent protective devices.

END OF SECTION

Page 57: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Grounding and Bonding SECTION 16060

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16060-Grounding and Bonding.doc

PART 1 – GENERAL ........................................................................................................................ 1

1.1 RELATED DOCUMENTS ........................................................................................................... 1 1.2 SUMMARY ............................................................................................................................. 1 1.3 SUBMITTALS .......................................................................................................................... 1 1.4 QUALITY ASSURANCE ............................................................................................................. 2 1.5 IDENTIFICATION ..................................................................................................................... 2 1.6 COORDINATION...................................................................................................................... 2

PART 2 – PRODUCTS ...................................................................................................................... 2

2.1 GENERAL .............................................................................................................................. 2 2.2 CONDUCTORS ....................................................................................................................... 2 2.3 CONNECTORS ....................................................................................................................... 3 2.4 GROUNDING ELECTRODES ...................................................................................................... 3

PART 3 – EXECUTION ..................................................................................................................... 3

3.1 APPLICATIONS ....................................................................................................................... 3 3.2 EQUIPMENT GROUNDING ........................................................................................................ 4 3.3 CONDUCTIVE PIPING .............................................................................................................. 6 3.4 LIGHTNING PROTECTION ......................................................................................................... 6 3.5 GROUND RESISTANCE ............................................................................................................ 6 3.6 INSTALLATION ........................................................................................................................ 6 3.7 FIELD QUALITY CONTROL ....................................................................................................... 7

Page 58: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Grounding and Bonding SECTION 16060

MEINHARDT PHILIPPINES INC. Page 1 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16060-Grounding and Bonding.doc

SECTION 16060 GROUNDING AND BONDING

PART 1 – GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and

Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes methods and materials for grounding systems and equipment.

1. Common ground bonding with lightning protection system.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Shop Drawings:

1. Showing the location of system grounding electrode connections and the routing

of grounding electrode conductor. C. Other Informational Submittals: Plans showing dimensioned as-built locations of

grounding features specified in Part 3 "Field Quality Control" Article, including the following:

1. Test wells. 2. Ground rods. 3. Ground rings. 4. Grounding arrangements and connections for separately derived systems. 5. Grounding for sensitive electronic equipment.

D. Qualification Data: For testing agency and testing agency's field supervisor.

E. Field quality-control test reports.

1. Certified test reports of ground resistance.

F. Operation and Maintenance Data: For grounding to include the following in emergency, operation, and maintenance manuals:

1. Instructions for periodic testing and inspection of grounding features at test

wells based on NETA MTS. a. Tests shall be to determine if ground resistance or impedance values

remain within specified maximums, and instructions shall recommend corrective action if they do not.

b. Include recommended testing intervals.

Page 59: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Grounding and Bonding SECTION 16060

MEINHARDT PHILIPPINES INC. Page 2 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16060-Grounding and Bonding.doc

1.4 QUALITY ASSURANCE

A. Testing Agency Qualifications: An independent agency, with the experience and

capability to conduct the testing indicated, that is a member company of the InterNational Electrical Testing Association or is a nationally recognized testing laboratory (NRTL) as defined by OSHA in 29 CFR 1910.7, and that is acceptable to authorities having jurisdiction.

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in

PEC, Article 1.0, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

C. Comply with UL 467 for grounding and bonding materials and equipment.

1.5 IDENTIFICATION

A. Provide an identification nameplate for each ground bus cabinet.

1.6 COORDINATION

A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.

Concrete, reinforcement, and formwork requirements are specified in Division 3. B. Coordinate installation of roof curbs, equipment supports, and roof penetrations.

These items are specified in Division 7 Section "Roof Accessories."

PART 2 – PRODUCTS

2.1 GENERAL

A. Grounding connections shall be brazed molded exothermic welded, bolted clamp

terminal or pressure connector type.

2.2 CONDUCTORS

A. Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by applicable Code or authorities having jurisdiction.

B. Bare Copper Conductors:

1. Solid Conductors: ASTM B 3. 2. Stranded Conductors: ASTM B 8. 3. Tinned Conductors: ASTM B 33. 4. Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG conductor, 1/4 inch (6 mm) in

diameter. 5. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor. 6. Bonding Jumper: Copper tape, braided conductors, terminated with copper ferrules;

1-5/8 inches (41 mm) wide and 1/16 inch (1.6 mm) thick. 7. Tinned Bonding Jumper: Tinned-copper tape, braided conductors, terminated with

copper ferrules; 1-5/8 inches (41 mm) wide and 1/16 inch (1.6 mm) thick.

Page 60: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Grounding and Bonding SECTION 16060

MEINHARDT PHILIPPINES INC. Page 3 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16060-Grounding and Bonding.doc

C. Bare Grounding Conductor and Conductor Protector for Wood Poles:

1. No. 4 AWG minimum, soft-drawn copper. 2. Conductor Protector: Half-round PVC or wood molding. If wood, use pressure-

treated fir or cypress or cedar.

D. Grounding Bus: Rectangular bars of annealed copper, 1/4 by 2 inches (6 by 50 mm) in cross section, unless otherwise indicated; with insulators.

2.3 CONNECTORS

A. Listed and labeled by a nationally recognized testing laboratory acceptable to authorities having jurisdiction for applications in which used, and for specific types, sizes, and combinations of conductors and other items connected.

B. Bolted Connectors for Conductors and Pipes: Copper or copper alloy, bolted pressure-type, with at least two bolts.

1. Pipe Connectors: Clamp type, sized for pipe.

C. Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions.

2.4 GROUNDING ELECTRODES

A. Ground Rods: Copper-clad Stainless steel; 3/4 inch by10 feet (19 mm by 3 m) 5/8 by 96 inches (16 by 2400 mm) in diameter.

B. Chemical-Enhanced Grounding Electrodes: Copper tube, straight or L-shaped, charged with nonhazardous electrolytic chemical salts.

1. Termination: Factory-attached No. 4/0 AWG bare conductor at least 48 inches (1200 mm) long.

2. Backfill Material: Electrode manufacturer's recommended material.

PART 3 – EXECUTION

3.1 APPLICATIONS

A. Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for No. 6 AWG and larger, unless otherwise indicated.

B. Underground Grounding Conductors: Install bare tinned-copper conductor, No. 2/0 AWG minimum.

1. Bury at least 24 inches (600 mm) below grade. 2. Duct-Bank Grounding Conductor: Bury 12 inches (300 mm) above duct bank when

indicated as part of duct-bank installation.

C. Isolated Grounding Conductors: Green-colored insulation with continuous yellow stripe. On feeders with isolated ground, identify grounding conductor where visible to normal

Page 61: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Grounding and Bonding SECTION 16060

MEINHARDT PHILIPPINES INC. Page 4 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16060-Grounding and Bonding.doc

inspection, with alternating bands of green and yellow tape, with at least three bands of green and two bands of yellow.

D. Grounding Bus: Install in electrical and telephone equipment rooms, in rooms housing service equipment, and elsewhere as indicated.

1. Install bus on insulated spacers 1 inch (25 mm), minimum, from wall 6 inches (150 mm) above finished floor, unless otherwise indicated.

2. Where indicated on both sides of doorways, route bus up to top of door frame, across top of doorway, down to specified height above floor, and connect to horizontal bus.

E. Conductor Terminations and Connections:

1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors. 2. Underground Connections: Welded connectors, except at test wells and as otherwise

indicated. 3. Connections to Ground Rods at Test Wells: Bolted connectors. 4. Connections to Structural Steel: Welded connectors.

F. Primary Equipment And Circuits

1. Switchgear: Provide a bare grounding electrode conductor from the switchgear ground bus to the grounding electrode system, metal underground water pipe or driven ground rods for the grounding electrode.

2. Duct Banks and Manholes:

1. Provide a bare equipment grounding conductor in each duct containing

medium or high voltage cables. Connect the grounding conductors to the switchgear ground bus, to all manhole hardware, to the cable shielding of medium or high voltage cable splices and terminations and equipment enclosures.

2. Provide a grounding conductor having at least 50 percent ampacity of the largest phase conductor in the duct bank.

3. Connect the equipment grounding conductor to the ground rod.

3. Power Transformers:

1. Provide a driven ground rod and connect with a grounding electrode conductor to the grounding facilities at the transformer.

2. Ground the secondary neutral. 3. Connect lightning arrester grounds to the pad ground per PEC. 4. Lightning Arresters: Connect lightning arresters grounds to the equipment

ground bus or ground rods, as applicable. 5. Outdoor Fences: Connect outdoor fences around electrical equipment to the

grounding electrode system. 6. Metallic Conduit: Metallic conduits which terminate without mechanical

connection to a housing of electrical equipment by means of locknut and bushings or adapters, provided with grounding bushings. Connect bushings with a bare grounding conductor to the equipment ground bus.

3.2 EQUIPMENT GROUNDING

A. Main Bonding Jumper: Connect the secondary service neutral to the ground bus in

the service equipment. B. Water Pipe and Supplemental Electrode:

Page 62: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Grounding and Bonding SECTION 16060

MEINHARDT PHILIPPINES INC. Page 5 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16060-Grounding and Bonding.doc

1. Provide a ground conductor connection between the service equipment ground bus and the metallic water pipe system. Jumper insulating joints in the water pipe.

2. Provide a supplemental ground electrode and bond to the water pipe ground or connect to the service equipment ground bus.

C. Service Disconnect (Separate Individual Enclosure): Provide a ground bar bolted to

the enclosure with lugs for connecting the various grounding conductors. D. Switchgear, Switchboards, Unit Substations:

1. Connect the various feeder green grounding conductors to the ground bus in the enclosure with suitable pressure connectors.

2. Connect the grounding electrode conductor to the ground bus. 3. Connect the neutral to the ground bus (main bonding jumper). 4. Connect metallic conduits, which terminate without mechanical connection to

the housing, by grounding bushings and ground wire to the ground bus. E. Transformers:

1. Exterior: Exterior transformers supplying interior service equipment shall also

have the neutral grounded at the transformer secondary. Provide a grounding electrode at the transformer.

2. Separately derived systems (transformers downstream from service equipment): Ground the secondary neutral at the transformer. Provide a grounding electrode conductor from the transformer to the nearest cold water pipe.

F. Conduit Systems:

1. Ground all metallic conduit systems. 2. Non-metallic conduit systems shall contain a grounding conductor. 3. Conduit provided for mechanical protection containing only a grounding

conductor, bond to that conductor at the entrance and exit from the conduit. G. Feeders and Branch Circuits: Install green grounding conductors with feeders and

branch circuits as follows:

1. Feeders. 2. Circuits serving preparation and kitchen equipment. 3. Receptacle outlets. 4. Directly connected laboratory equipment. 5. Motors and motor controllers. 6. Fixed equipment and appliances. 7. Items of equipment where the final connection is made with flexible metal

conduit shall have grounding wire 8. Additional locations and systems as shown. 9. Provide an insulated, isolated grounding conductor for branch circuits serving

isolated ground and isolated ground surge suppressor type receptacles. Isolated grounding conductors shall be isolated from other grounding systems back to the system point of origin.

H. Boxes, Cabinets, Enclosures and Panelboards: 1. Bond the grounding wires to each pullbox, junction box, outlet box, cabinets

and other enclosures through which the ground wires pass (except for special grounding systems for intensive care units and other critical units shown).

2. Provide lugs in each box and enclosure for ground wire termination.

Page 63: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Grounding and Bonding SECTION 16060

MEINHARDT PHILIPPINES INC. Page 6 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16060-Grounding and Bonding.doc

3. Provide ground bars in panelboards, bolted to the housing, with sufficient lugs for terminating the ground wires.

I. Motors and Starters:

1. Provide lugs in motor terminal box and starter housing for ground wire

termination. 2. Make ground wire connections to ground bus in motor control centers.

J. Receptacles are not approved for grounding through their mounting screws. Ground with a ground wire from green ground terminal on the receptacle to the outlet box ground screw.

K. Ground lighting fixtures to the green grounding conductor of the wiring system when

the green ground is provided; otherwise, ground the fixtures through the conduit systems. Fixtures connected with flexible conduit shall have a green ground wire included with the power wires from the fixture through the flexible conduit to the first outlet box.

L. Fixed electrical appliances and equipment shall have ground lug installed for

termination of the green ground conductor.

3.3 CONDUCTIVE PIPING

A. Bond all conductive piping systems in the building to the electrical system ground.

Bonding connections shall be made as close as practical to the water pipe ground or service equipment ground bus.

3.4 LIGHTNING PROTECTION

Bond the lightning protection system to the electrical system grounding electrode.

3.5 GROUND RESISTANCE

A. Grounding system ground resistance must not exceed 2 ohms (1 ohm for

telecommunication systems). Final tests shall assure that this requirement is met. B. Services at power company interface points shall comply with the power company

ground resistance requirements. C. Make necessary modifications needed to the ground electrodes for compliance,

without additional cost to the Owner, including the provisions of a multi-rod system.

3.6 INSTALLATION

A. Grounding Conductors: Route along shortest and straightest paths possible, unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.

B. Common Ground Bonding with Lightning Protection System: Comply with NFPA 780 and UL 96 when interconnecting with lightning protection system. Bond electrical power system ground directly to lightning protection system grounding conductor at closest point to electrical service grounding electrode. Use bonding conductor sized same as system grounding electrode conductor, and install in conduit.

Page 64: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Grounding and Bonding SECTION 16060

MEINHARDT PHILIPPINES INC. Page 7 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16060-Grounding and Bonding.doc

C. Ground Rods: Drive rods until tops are 2 inches (50 mm) below finished floor or final grade, unless otherwise indicated.

1. Interconnect ground rods with grounding electrode conductor below grade and as otherwise indicated. Make connections without exposing steel or damaging coating, if any.

2. For grounding electrode system, install at least three rods spaced at least one-rod length from each other and located at least the same distance from other grounding electrodes, and connect to the service grounding electrode conductor.

D. Test Wells: Ground rod driven through drilled hole in bottom of handhole. Handholes are specified in Division 2 Section "Underground Ducts and Utility Structures," and shall be at least 12 inches (300 mm) deep, with cover.

1. Test Wells: Install at least one test well for each service, unless otherwise indicated. Install at the ground rod electrically closest to service entrance. Set top of test well flush with finished grade or floor.

E. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance, except where routed through short lengths of conduit.

1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate any adjacent parts.

2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install so vibration is not transmitted to rigidly mounted equipment.

3. Use exothermic-welded connectors for outdoor locations, but if a disconnect-type connection is required, use a bolted clamp.

F. Grounding and Bonding for Piping:

1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes, using a bolted clamp connector or by bolting a lug-type connector to a pipe flange, using one of the lug bolts of the flange. Where a dielectric main water fitting is installed, connect grounding conductor on street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end.

2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with a bolted connector.

3. Bond each aboveground portion of gas piping system downstream from equipment shutoff valve.

G. Bonding Interior Metal Ducts: Bond metal air ducts to equipment grounding conductors of associated fans, blowers, electric heaters, and air cleaners. Install tinned bonding jumper to bond across flexible duct connections to achieve continuity.

3.7 FIELD QUALITY CONTROL

A. Testing Agency: Owner will engage a qualified testing and inspecting agency to perform field tests and inspections and prepare test reports.

B. Testing Agency: Engage a qualified testing and inspecting agency to perform the following field tests and inspections and prepare test reports:

C. Perform the following tests and inspections and prepare test reports:

1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements.

Page 65: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Grounding and Bonding SECTION 16060

MEINHARDT PHILIPPINES INC. Page 8 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16060-Grounding and Bonding.doc

2. Test completed grounding system at each location where a maximum ground-resistance level is specified, at service disconnect enclosure grounding terminal at individual ground rods. Make tests at ground rods before any conductors are connected.

a. Measure ground resistance not less than two full days after last trace of precipitation and without soil being moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natural ground resistance.

b. Perform tests by fall-of-potential method according to IEEE 81.

3. Prepare dimensioned drawings locating each test well, ground rod and ground rod assembly, and other grounding electrodes. Identify each by letter in alphabetical order, and key to the record of tests and observations. Include the number of rods driven and their depth at each location, and include observations of weather and other phenomena that may affect test results. Describe measures taken to improve test results.

D. Report measured ground resistances that exceed the following values:

1. Power and Lighting Equipment or System with Capacity 500 kVA and Less: 5 ohms. 2. Power and Lighting Equipment or System with Capacity 500 to 1000 kVA: 5 ohms. 3. Power and Lighting Equipment or System with Capacity More Than 1000 kVA: 5

ohms. 4. Power Distribution Units or Panelboards Serving Electronic Equipment: 5 ohm(s). 5. Manhole Grounds: 5 ohms.

E. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify MEEPF CONSULTANT promptly and include recommendations to reduce ground resistance.

END OF SECTION

Page 66: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Firestopping Materials SECTION 16071

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16071-Firestopping For Electrical Works.doc

PART 1 - GENERAL ......................................................................................................................................1

1.1 DESCRIPTION OF WORK ....................................................................................................................1 1.2 RELATED DOCUMENTS ......................................................................................................................1 1.3 QUALITY ASSURANCE ........................................................................................................................1 1.4 APPLICABLE PUBLICATIONS ...............................................................................................................2 1.5 SUBMITTALS ......................................................................................................................................2 1.6 MANUFACTURERS .............................................................................................................................2

PART 2 - PRODUCTS ...................................................................................................................................3

2.1 GENERAL PRODUCT REQUIREMENTS ................................................................................................3

PART 3 - EXECUTION ..................................................................................................................................4

3.1 PREPARATION ...................................................................................................................................4 3.2 COORDINATION .................................................................................................................................4 3.3 INSTALLATION....................................................................................................................................4 3.4 FIELD QUALITY CONTROL ..................................................................................................................4 3.5 ADJUSTING AND CLEANING................................................................................................................4 3.6 CERTIFICATION .................................................................................................................................5

Page 67: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Firestopping Materials SECTION 16071

MEINHARDT PHILIPPINES INC Page 1 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16071-Firestopping For Electrical Works.doc

SECTION 16075 FIRESTOPPING MATERIALS

PART 1 - GENERAL

1.1 DESCRIPTION OF WORK Only tested firestop systems shall be used in specific locations as follows:

A. Penetrations for the passage of duct, cable, cable tray, conduit, piping, electrical busways and raceways through fire-rated vertical barriers (walls and partitions), horizontal barriers (floor/ceiling assemblies), and vertical service shaft walls and partitions.

B. Opening and penetrations in fire-rated partitions or walls containing fire doors.

C. Opening around structural members, which penetrate floors or walls.

1.2 RELATED DOCUMENTS A. All work specified in this Section is subject to the provisions of Section 16010.

B. Refer to the following sections of related work in connection with Firestopping:

16010 - Electrical General Provisions 16072 - Electrical Equipment Noise Control, Vibration Isolation, and Seismic

Restraints 16130 - Raceways and Boxes 16120 - 600V Wires and Cables 16134 - Panelboards 16420 - Disconnect Switches & Individual Motor Controllers

C. Firestopping: Material or combination of materials used to retain integrity of fire-rated

construction by maintaining an effective barrier against the spread of flame, smoke, and hot gases through penetrations in fire rated wall and floor assemblies.

D. All works specified in this Section is subject to Architectural Fire Compartmentation

plans.

E. Firestopping rating shall be as follows:

(Except as noted in fire life safety/architectural drawings). However, the more stringent applies: Zone-to-Zone 2hrs Floor-to-Floor 2hrs

Penetrations to External Wall 3hrs Critical Zone within compartmentation 1hr Penetrations to Lift stairwell shaft 2hrs & duct chases

1.3 QUALITY ASSURANCE

A. A manufacturer’s direct representative (not distributor or agent) to be on-site during initial installation of firestop systems to train appropriate contractor personnel in proper selection and installation procedures. This will be done per manufacturer’s written recommendations published in their literature and drawing details.

Page 68: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Firestopping Materials SECTION 16071

MEINHARDT PHILIPPINES INC Page 2 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16071-Firestopping For Electrical Works.doc

B. Firestop System installation must meet requirements of ASTM E-814, UL 1479 or UL

2079 tested assemblies that provide a fire rating equal to that of construction being penetrated.

C. Proposed firestop materials and methods shall conform to applicable governing codes

having local jurisdiction.

D. Firestop Systems do not re-establish the structural integrity to load bearing partitions/assemblies, or support live loads and traffic. Installer shall consult the structural engineer prior to penetrating any load bearing assembly.

E. For those firestop applications that exist for which no UL tested system is available

through a manufacturer, an engineering judgement derived from similar UL system designs or other tests will be submitted to local authorities having jurisdiction for their review and approval prior to installation.

1.4 APPLICABLE PUBLICATIONS

A. American Society for Testing and Materials (ASTM) : E 814 - Fire Tests of Through- Penetration Fire Stops

B. Underwriter’s Laboratories, Inc. (UL):

UL 1479 - Tests for Fire Resistance of Building Joint Systems UL 2079 - Fire Tests of Through -Penetration Fire Stops

1.5 SUBMITTALS

A. Submit Product Data: Manufacturer’s specifications and technical data for each material

including the composition and limitations, documentation of UL firestop systems to be used and manufacturer’s installation instructions.

B. Manufacturer’s engineering judgement identification number and drawing details when

no UL system is available for an application. Engineer judgement must include both project name and contractor’s name that will install firestop system as described in drawing.

C. Submit material safety data sheets provided with product delivered to job-site.

1.6 MANUFACTURERS

A. The acceptable manufacturers of the Firestopping Sealant shall be as per Section 16007.

B. Installer qualification

Engage an experienced Installer who is certified, licensed, or otherwise qualified by the firestopping manufacturer as having been provided the necessary training to install manufacturer’s products per specified requirements. A supplier’s willingness to sell its firestopping products to the Contractor or to an Installer engaged by the Contractor

does not in itself confer qualification on the buyer.

Page 69: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Firestopping Materials SECTION 16071

MEINHARDT PHILIPPINES INC Page 3 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16071-Firestopping For Electrical Works.doc

PART 2 - PRODUCTS

2.1 GENERAL PRODUCT REQUIREMENTS A. Provide firestopping composed of components that are compatible with each other, the

substrates forming openings, and the items, if any, penetrating the firestopping under conditions of service and application, as demonstrated by the firestopping manufacturer based on testing and field experience.

B. Provide components for each firestopping system that are needed to install fill material. Use only components specified by the firestopping manufacturer and approved by the qualified testing agency for the designated fire-resistance-rated systems.

C. Firestopping Materials are either “cast-in-place” (integral with concrete placement) or

“post installed”. Provide cast-in-place firestop devices prior to concrete placement.

D. Use only firestop products that have been UL 1479, ASTM E-814, or UL 2079 tested

for specific fire-rated construction conditions conforming to construction assembly type, penetrating item type, annular space requirements, and fire-rating involved for each separate instance.

E. Appropriate sealant shall be used in the following materials:

1. Cast-in place firestop devices for use with non-combustible plastic pipe (closed

and open piping systems) penetrating concrete floors. 2. Sealants or caulking materials for use with fire-rated construction joints and

other gaps. 3. Sealants, caulking or spray materials for use with fire-rated construction joints

and other gaps. 4. Intumescent sealants for caulking materials for use with combustible items

(penetrants consumed by high heat and flame) including insulated metal pipe, PV jacketed, flexible cable or cable bundles and plastic pipe.

5. Intumescent sealants, caulking or putty materials for use with flexible cable or cable bundles.

6. Non curing, re-penetrable intumescent sealant, caulking or putty materials for use with flexible cable or cable bundles.

7. Wall opening protective materials for use with U.L listed metallic and specified non-metallic outlet boxes.

8. Firestop collar wrap devices attached to assembly around combustible plastic

pipe (closed and open piping systems). 9. Materials used for large size/complex penetrations made to accommodate

cable trays, multiple steel and copper pipes, electrical busways in raceways. 10. Non curing, re-penetrable materials used for large size/complex penetrations

made to accommodate cable trays, multiple steel and copper pipes, electrical busways in raceways.

11. Provide a firestop system with an “F” Rating as determined by UL 1479 or

ASTM E814, which is equal to the rating of construction being penetrated. 12. Provide a firestop system with an Assembly Rating as determined by UL 2079,

which is equal to the time rating of construction being penetrated.

Page 70: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Firestopping Materials SECTION 16071

MEINHARDT PHILIPPINES INC Page 4 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16071-Firestopping For Electrical Works.doc

PART 3 - EXECUTION

3.1 PREPARATION

A. Verification of Conditions: Examine areas and conditions under which work is to be

performed and identify conditions detrimental to proper or timely completion.

1. Verify penetrations are properly size and in suitable condition for application materials.

2. Surfaces to which firestop materials will be applied shall be free of dirt,

grease, oil, rust, laitance, release agents, water repellents, and any other substances that may affect proper adhesion.

3. Provide masking and temporary covering to prevent soiling adjacent surfaces by firestopping materials.

4. Comply with manufacturer’s recommendations for temperature and humidity conditions before, during and after installation of firestopping.

5. Do not proceed until unsatisfactory conditions have been corrected.

3.2 COORDINATION A. Coordinate location and proper selection of cast-in-place Firestop Devices with trade

responsible for the work. Ensure device is installed before placement of concrete.

B. Responsible trade to provide adequate spacing of field run pipes to allow for installation of cast-in-place firestop devices without interferences.

3.3 INSTALLATION

A. Regulatory Requirements: Install firestop materials in accordance with UL Fire Resistance Directory.

B. Manufacturer’s Instructions: Comply with manufacturer’s instructions for installation of

through-penetration and construction joint materials.

1. Seal all holes or voids made by penetrations to ensure an air and water resistant seal.

2. Consult with mechanical engineer, project manager, and damper manufacturer prior to installation of UL firestop systems that might hammer the performance of fire dampers as it pertains to duct work.

3. Protect materials from damage on surfaces subjected to traffic.

3.4 FIELD QUALITY CONTROL

A. Examine sealed penetration areas to ensure proper installation before concealing areas.

B. Keep areas of work accessible until inspection by applicable code authorities.

C. Perform under this section patching and repairing of firestopping caused by cutting or penetrating of existing firestop systems already installed by other trades.

3.5 ADJUSTING AND CLEANING

A. Remove equipment, materials and debris, leaving area in undamaged, clean condition.

Page 71: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Firestopping Materials SECTION 16071

MEINHARDT PHILIPPINES INC Page 5 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16071-Firestopping For Electrical Works.doc

B. Clean all surfaces adjacent to sealed holes and joints to be free of excess firestop materials and soiling as work progresses.

3.6 CERTIFICATION

The Contractor shall secure certification from the Manufacturer (not distributor nor supplier) that the Installation done by the Contractor is in conformance set by the U.L.

END OF SECTION

Page 72: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Hangers and Supports for Electrical Systems SECTION 16073

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16073-Hangers and Supports for Electrical Systems.doc

PART 1 – GENERAL ........................................................................................................................ 1

1.1 RELATED DOCUMENTS ........................................................................................................... 1 1.2 SUMMARY ............................................................................................................................. 1 1.3 DEFINITIONS.......................................................................................................................... 1 1.4 PERFORMANCE REQUIREMENTS .............................................................................................. 1 1.5 SUBMITTALS .......................................................................................................................... 1 1.6 QUALITY ASSURANCE ............................................................................................................. 2 1.7 COORDINATION...................................................................................................................... 2

PART 2 – PRODUCTS ...................................................................................................................... 2

2.1 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS ........................................................ 2 2.2 FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES ............................................................ 3

PART 3 – EXECUTION ..................................................................................................................... 3

3.1 APPLICATION ......................................................................................................................... 3 3.2 SUPPORT INSTALLATION ......................................................................................................... 4 3.3 INSTALLATION OF FABRICATED METAL SUPPORTS ..................................................................... 4 3.4 CONCRETE BASES ................................................................................................................. 4 3.5 PAINTING .............................................................................................................................. 5

Page 73: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Hangers and Supports for Electrical Systems SECTION 16073

MEINHARDT PHILIPPINES INC. Page 1 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16073-Hangers and Supports for Electrical Systems.doc

SECTION 16073 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

PART 1 – GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and

Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Hangers and supports for electrical equipment and systems. 2. Construction requirements for concrete bases.

B. Related Sections include the following:

1. Division 16 Section "Vibration and Seismic Controls for Electrical Systems" for products and installation requirements necessary for compliance with seismic criteria.

1.3 DEFINITIONS

A. EMT: Electrical metallic tubing. B. IMC: Intermediate metal conduit.

C. RMC: Rigid metal conduit. D. NECA: National Electrical Contractor’s Association (Standard Practices for Good

Workmanship in Electrical Contracting)

1.4 PERFORMANCE REQUIREMENTS

A. Delegated Design: Design supports for multiple raceways, including comprehensive

engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.

B. Design supports for multiple raceways capable of supporting combined weight of

supported systems and its contents.

C. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.

D. Rated Strength: Adequate in tension, shear, and pullout force to resist maximum

loads calculated or imposed for this Project, with a minimum structural safety factor of five times the applied force.

1.5 SUBMITTALS

A. Product Data: For the following:

1. Steel slotted support systems. 2. Nonmetallic slotted support systems.

Page 74: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Hangers and Supports for Electrical Systems SECTION 16073

MEINHARDT PHILIPPINES INC. Page 2 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16073-Hangers and Supports for Electrical Systems.doc

B. Shop Drawings: Signed and sealed by a qualified professional engineer. Show fabrication and installation details and include calculations for the following:

1. Trapeze hangers. Include Product Data for components. 2. Steel slotted channel systems. Include Product Data for components. 3. Nonmetallic slotted channel systems. Include Product Data for components. 4. Equipment supports.

C. Welding certificates.

1.6 QUALITY ASSURANCE

A. Welding: Qualify procedures and personnel according to AWS D1.1/D1.1M,

"Structural Welding Code - Steel." B. Comply with NFPA 70.

1.7 COORDINATION

A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.

Concrete, reinforcement, and formwork requirements are specified in Division 3. B. Coordinate installation of roof curbs, equipment supports, and roof penetrations.

These items are specified in Division 7 Section "Roof Accessories."

PART 2 – PRODUCTS

2.1 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS

A. Steel Slotted Support Systems: Comply with MFMA-4, factory-fabricated

components for field assembly.

1. Acceptable Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

2. Metallic Coatings: Hot-dip galvanized after fabrication and applied according to MFMA-4.

3. Nonmetallic Coatings: Manufacturer's standard PVC, polyurethane, or polyester coating applied according to MFMA-4.

4. Channel Dimensions: Selected for applicable load criteria. B. Nonmetallic Slotted Support Systems: Structural-grade, factory-formed, glass-fiber-

resin channels and angles with 9/16-inch- (14-mm-) diameter holes at a maximum of 8 inches (200 mm) o.c., in at least 1 surface.

1. Acceptable Manufacturers: See Section 16007 “Acceptable Equipment and

Suppliers”. 2. Fittings and Accessories: Products of channel and angle manufacturer and

designed for use with those items. 3. Fitting and Accessory Materials: Same as channels and angles, except

metal items may be stainless steel. 4. Rated Strength: Selected to suit applicable load criteria.

C. Raceway and Cable Supports: As described in NECA 1 and NECA 101.

D. Conduit and Cable Support Devices: Steel and malleable-iron hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.

Page 75: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Hangers and Supports for Electrical Systems SECTION 16073

MEINHARDT PHILIPPINES INC. Page 3 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16073-Hangers and Supports for Electrical Systems.doc

E. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for non-armored electrical conductors or cables in riser conduits. Plugs shall have number, size, and shape of conductor gripping pieces as required to suit individual conductors or cables supported. Body shall be malleable iron.

F. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M, steel

plates, shapes, and bars; black and galvanized.

G. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or their supports to building surfaces include the following:

1. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened

portland cement concrete, steel, or wood, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used. a. Acceptable Manufacturers: See Section 16007 “Acceptable

Equipment and Suppliers”. 2. Mechanical-Expansion Anchors: Insert-wedge-type, zinc-coated stainless

steel, for use in hardened portland cement concrete with tension, shear, and pullout capacities appropriate for supported loads and building materials in which used. a. Acceptable Manufacturers: See Section 16007 “Acceptable

Equipment and Suppliers”. 3. Concrete Inserts: Steel or malleable-iron, slotted support system units similar

to MSS Type 18; complying with MFMA-4 or MSS SP-58. 4. Clamps for Attachment to Steel Structural Elements: MSS SP-58, type

suitable for attached structural element. 5. Through Bolts: Structural type, hex head, and high strength. Comply with

ASTM A 325. 6. Toggle Bolts: All-steel springhead type. 7. Hanger Rods: Threaded steel.

2.2 FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES

A. Description: Welded or bolted, structural-steel shapes, shop or field fabricated to fit

dimensions of supported equipment. B. Materials: Comply with requirements in Division 5 Section "Metal Fabrications" for

steel shapes and plates.

PART 3 – EXECUTION

3.1 APPLICATION

A. Comply with NECA 1 and NECA 101 for application of hangers and supports for

electrical equipment and systems except if requirements in this Section are stricter. B. Maximum Support Spacing and Minimum Hanger Rod Size for Raceway: Space

supports for EMT, IMC, and RMC as required by NFPA 70. Minimum rod size shall be 1/4 inch (6 mm) in diameter.

C. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel

slotted support system, sized so capacity can be increased by at least 25 percent in future without exceeding specified design load limits.

1. Secure raceways and cables to these supports with two-bolt conduit clamps,

single-bolt conduit clamps, single-bolt conduit clamps using spring friction action for retention in support channel.

Page 76: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Hangers and Supports for Electrical Systems SECTION 16073

MEINHARDT PHILIPPINES INC. Page 4 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16073-Hangers and Supports for Electrical Systems.doc

D. Spring-steel clamps designed for supporting single conduits without bolts may be

used for 1-1/2-inch (38-mm) and smaller raceways serving branch circuits and communication systems above suspended ceilings and for fastening raceways to trapeze supports.

3.2 SUPPORT INSTALLATION

A. Comply with NECA 1 and NECA 101 for installation requirements except as specified

in this Article. B. Raceway Support Methods: In addition to methods described in NECA 1, EMT, IMC,

and RMC may be supported by openings through structure members, as permitted in NFPA 70.

C. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static loads within specified loading limits. Minimum static design load used for strength determination shall be weight of supported components plus 200 lb (90 kg).

D. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor

and fasten electrical items and their supports to building structural elements by the following methods unless otherwise indicated by code:

1. To Wood: Fasten with lag screws or through bolts. 2. To New Concrete: Bolt to concrete inserts. 3. To Masonry: Approved toggle-type bolts on hollow masonry units and

expansion anchor fasteners on solid masonry units. 4. To Existing Concrete: Expansion anchor fasteners. 5. Instead of expansion anchors, powder-actuated driven threaded studs

provided with lock washers and nuts may be used in existing standard-weight concrete 4 inches (100 mm) thick or greater. Do not use for anchorage to lightweight-aggregate concrete or for slabs less than 4 inches (100 mm) thick.

6. To Steel: Spring-tension clamps. 7. To Light Steel: Sheet metal screws. 8. Items Mounted on Hollow Walls and Nonstructural Building Surfaces: Mount

cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices on slotted-channel racks attached to substrate by means that meet seismic-restraint strength and anchorage requirements.

E. Drill holes for expansion anchors in concrete at locations and to depths that avoid

reinforcing bars.

3.3 INSTALLATION OF FABRICATED METAL SUPPORTS

A. Comply with installation requirements in Division 5 Section "Metal Fabrications" for

site-fabricated metal supports. B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment,

and elevation to support and anchor electrical materials and equipment.

C. Field Welding: Comply with AWS D1.1/D1.1M.

3.4 CONCRETE BASES

A. Construct concrete bases of dimensions indicated but not less than 4 inches (100

mm) larger in both directions than supported unit, and so anchors will be a minimum of 10 bolt diameters from edge of the base.

Page 77: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Hangers and Supports for Electrical Systems SECTION 16073

MEINHARDT PHILIPPINES INC. Page 5 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16073-Hangers and Supports for Electrical Systems.doc

B. Anchor equipment to concrete base.

1. Place and secure anchorage devices. Use supported equipment

manufacturer's setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.

2. Install anchor bolts to elevations required for proper attachment to supported equipment.

3. Install anchor bolts according to anchor-bolt manufacturer's written instructions.

3.5 PAINTING

A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas

immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.

1. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils

(0.05 mm).

B. Touchup: Comply with requirements in Division 9 painting Sections Section "High-Performance Coatings" for cleaning and touchup painting of field welds, bolted connections, and abraded areas of shop paint on miscellaneous metal.

C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and

apply galvanizing-repair paint to comply with ASTM A 780.

END OF SECTION

Page 78: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical Equipment Noise Control, Vibration SECTION 16074 Isolation, and Seismic Restraints

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16074-Electrical Equipment Noise Control.doc

PART 1 - GENERAL ......................................................................................................................... 1

1.1 RELATED DOCUMENTS .......................................................................................................... 1 1.2 DESCRIPTION OF WORK ....................................................................................................... 1 1.3 DEFINITIONS ........................................................................................................................ 2 1.4 SUBMITTALS ........................................................................................................................ 2 1.2 QUALITY ASSURANCE ........................................................................................................... 3

PART 2 - PRODUCTS ....................................................................................................................... 3

2.1 VIBRATION ISOLATORS .......................................................................................................... 3 2.2 FLEXIBLE CONNECTIONS ....................................................................................................... 4 2.3 EMERGENCY GENERATOR MUFFLER: CRITICAL TYPE ............................................................... 4 2.4 EMERGENCY GENERATOR NOISE CONTROL ............................................................................ 4 2.5 EQUIPMENT FRAMES............................................................................................................. 4 2.6 SEISMIC-RESTRAINT DEVICES................................................................................................ 5 2.7 FACTORY FINISHES ............................................................................................................... 6

C. EXECUTION .............................................................................................................................. 6

3.1 EXAMINATION ....................................................................................................................... 6 3.2 APPLICATIONS ...................................................................................................................... 6 3.3 SEISMIC-RESTRAINT DEVICE INSTALLATION ............................................................................. 6 3.4 ACCOMMODATION OF DIFFERENTIAL SEISMIC MOTION .............................................................. 7 3.5 FIELD QUALITY CONTROL ...................................................................................................... 7 3.6 ADJUSTING .......................................................................................................................... 8 3.7 ELECTRICAL VIBRATION-CONTROL AND SEISMIC-RESTRAINT DEVICE SCHEDULE ......................... 8

Page 79: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical Equipment Noise Control, Vibration SECTION 16074 Isolation, and Seismic Restraints

MEINHARDT PHILIPPINES INC. Page 1 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16074-Electrical Equipment Noise Control.doc

SECTION 16074 VIBRATION CONTROLS FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1. Division 16 Section 16073 - "Hangers and Supports for Electrical Systems" for commonly used electrical supports and installation requirements.

2. Division 16 Section 15071 – “Mechanical Vibration and Seismic Controls”.

3. Division 16 Section 16010 – “Electrical General Provisions”.

1.2 DESCRIPTION OF WORK

A. The extent of electrical equipment noise control, vibration isolation, and seismic restraint

required for the project is indicated on the Drawings and in Division 16 of the Specifications.

B. Types of electrical equipment noise control, vibration isolation, and seismic restraint

include, but are not limited to, the following:

1. Vibration isolation of transformers 2. Flexible conduits at transformer connections 3. Flexible conduits at connections to motors and other vibrating equipment. 4. Electrical box-pads at stud partitions where sound insulation is provided. 5. Vibration isolation of the emergency generator. 6. Noise control for the emergency generator. 7. Seismic restraint for vibration isolated equipment. 8. Busway seismic restraint at seismic gaps and at vertical risers at ceiling.

C. The Contractor shall bring to the Project Manager’s attention prior to installation any

conflicts with other trades, which will result in unavoidable contact to the equipment, raceways, etc., described herein, due to inadequate space, etc. Corrective work necessitated by conflicts after installation shall be at the responsible Contractor’s expense.

D. The Contractor shall bring to the Project Manager’s attention any discrepancies between

the Specifications and field conditions, changes required to specific equipment selection, etc., prior to installation. Corrective Work necessitated by discrepancies after installation shall be at the Contractor’s expense.

E. Seismic restraint shall be furnished and installed in accordance with Section 15200,

Sound and Vibration Isolator, and local code requirements. Provide calculations signed by structural engineer licensed in the Philippines in which the work is to take place certifying that the seismic restraints will act in accordance with the relevant local codes and will maintain equipment in captive position.

Page 80: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical Equipment Noise Control, Vibration SECTION 16074 Isolation, and Seismic Restraints

MEINHARDT PHILIPPINES INC. Page 2 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16074-Electrical Equipment Noise Control.doc

F. Vibration isolation manufacturer shall have the following responsibilities:

1. Determine vibration isolation sizes and locations. 2. Provide equipment isolation system as schedule or specified. 3. Guarantee specified isolation system deflection. 4. Provide installation instructions and drawings.

1.3 DEFINITIONS

A. The IBC: International Building Code.

B. AHJ: Authority Having Jurisdiction

1.4 SUBMITTALS

A. Product Data: For the following:

1. Include rated load, rated deflection, and overload capacity for each vibration isolation device.

2. Illustrate and indicate style, material, strength, fastening provision, and finish for each

type and size of seismic-restraint component used.

a. Tabulate types and sizes of seismic restraints, complete with report numbers and rated strength in tension and shear as evaluated by AHJ.

b. Annotate to indicate application of each product submitted and compliance with requirements.

3. Restrained-Isolation Devices: Include ratings for horizontal, vertical, and combined

loads.

B. Delegated-Design Submittal: For vibration isolation and seismic-restraint details indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.

1. Design Calculations: Calculate static and dynamic loading due to equipment weight and operation, seismic forces required to select vibration isolators and seismic restraints.

a. Coordinate design calculations with wind-load calculations required for equipment mounted outdoors. Comply with requirements in other Division 16 Sections for equipment mounted outdoors.

2. Indicate materials and dimensions and identify hardware, including attachment and anchorage devices.

3. Field-fabricated supports. 4. Seismic-Restraint Details:

a. Design Analysis: To support selection and arrangement of seismic restraints. Include calculations of combined tensile and shear loads.

b. Details: Indicate fabrication and arrangement. Detail attachments of restraints to the restrained items and to the structure. Show attachment locations, methods, and spacings. Identify components, list their strengths, and indicate directions and values of forces transmitted to the structure during seismic events.

Page 81: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical Equipment Noise Control, Vibration SECTION 16074 Isolation, and Seismic Restraints

MEINHARDT PHILIPPINES INC. Page 3 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16074-Electrical Equipment Noise Control.doc

c. Preapproval and Evaluation Documentation: By AHJ, showing maximum ratings of restraint items and the basis for approval (tests or calculations).

C. Coordination Drawings: Show coordination of seismic bracing for electrical components with other systems and equipment in the vicinity, including other supports and seismic restraints.

D. Welding certificates.

E. Qualification Data: For Structural Engineer

F. Field quality-control test reports.

1.2 QUALITY ASSURANCE

A. Testing Agency Qualifications: An independent agency, with the experience and capability to conduct the testing indicated, that is a nationally recognized testing laboratory (NRTL) as defined by OSHA in 29 CFR 1910.7, and that is acceptable to authorities having jurisdiction.

B. Comply with seismic-restraint requirements in the IBC unless requirements in this Section are more stringent.

C. Welding: Qualify procedures and personnel according to AWS D1.1/D1.1M, “Structural Welding Code – Steel.”

D. Seismic-restraint devices shall have horizontal and vertical load testing and analysis and shall bear anchorage preapproval by another agency acceptable to authorities having jurisdiction, showing maximum seismic-restraint ratings. Ratings based on independent testing are preferred to ratings based on calculations. If preapproved ratings are not available, submittals based on independent testing are preferred. Calculations (including combining shear and tensile loads) to support seismic-restraint designs must be signed and sealed by a qualified professional engineer.

E. Comply with NFPA 70.

PART 2 - PRODUCTS

2.1 VIBRATION ISOLATORS

A. Acceptable Manufacturers: See Section 16007 “Alternative Equipment and Suppliers”.

B. Pads: Arrange in single or multiple layers of sufficient stiffness for uniform loading over pad area, molded with a nonslip pattern and galvanized-steel baseplates, and factory cut to sizes that match requirements of supported equipment.

1. Resilient Material: Oil- and water-resistant neoprene, rubber, hermetically sealed compressed fiberglass.

C. Spring Isolators: Freestanding, laterally stable, open-spring isolators.

1. Outside Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load.

2. Minimum Additional Travel: 50 percent of the required deflection at rated load. 3. Lateral Stiffness: More than 80 percent of rated vertical stiffness.

Page 82: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical Equipment Noise Control, Vibration SECTION 16074 Isolation, and Seismic Restraints

MEINHARDT PHILIPPINES INC. Page 4 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16074-Electrical Equipment Noise Control.doc

4. Overload Capacity: Support 200 percent of rated load, fully compressed, without deformation or failure.

5. Baseplates: Factory drilled for bolting to structure and bonded to 1/4-inch- (6-mm-) thick, rubber isolator pad attached to baseplate underside. Baseplates shall limit floor load to 500 psig (3447 kPa).

6. Top Plate and Adjustment Bolt: Threaded top plate with adjustment bolt and cap screw to fasten and level equipment.

D. Restrained Spring Isolators: Freestanding, steel, open-spring isolators with seismic or limit-stop restraint.

1. Housing: Steel with resilient vertical-limit stops to prevent spring extension due to weight being removed; factory-drilled baseplate bonded to 1/4-inch- (6-mm-) thick, neoprene or rubber isolator pad attached to baseplate underside; and adjustable equipment mounting and leveling bolt that acts as blocking during installation.

2. Restraint: Seismic or limit-stop as required for equipment and authorities having jurisdiction.

3. Outside Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load.

4. Minimum Additional Travel: 50 percent of the required deflection at rated load. 5. Lateral Stiffness: More than 80 percent of rated vertical stiffness. 6. Overload Capacity: Support 200 percent of rated load, fully compressed, without

deformation or failure.

2.2 FLEXIBLE CONNECTIONS

A. Conduit over 1 inch OD:

Make electrical connections to vibrating equipment via flexible expansion/deflection conduit coupling sized as required. Coupling shall have a flexible and watertight out-er jacket, an internal grounding strap, plastic inner sleeve to maintain smooth wire-way, and end hubs with threads to fit standard threaded metal conduit. Acceptable units include:

1. XD Expansion Deflection Coupling by Crouse-Hinds of Syracuse, N.Y. 2. Type DF Expansion and Deflection fitting by Spring City Electrical Mfg. Co. of

Spring City, PA.

B. For conduit under 1 inch OD: Use “flexible” conduit with slack at least 3 feet or 15 di-ameters long, whichever is the longer or provide a flexible coupling as defined above.

2.3 EMERGENCY GENERATOR MUFFLER: CRITICAL TYPE

A. Critical type emergency generator muffler shall be equal to Nelson 400.

2.4 EMERGENCY GENERATOR NOISE CONTROL

A. Emergency generator silencers, enclosures etc. shall be equal to Industrial Acoustics

Company.

2.5 EQUIPMENT FRAMES

A. Mounting frames and/or brackets shall be provided to carry the load of the equipment

without causing mechanical distortion or stress to the equipment.

Page 83: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical Equipment Noise Control, Vibration SECTION 16074 Isolation, and Seismic Restraints

MEINHARDT PHILIPPINES INC. Page 5 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16074-Electrical Equipment Noise Control.doc

B. Frame Types

1. Type A frame is a wide flange structural steel frame with brackets as shown on the drawings. The maximum allowable deflection of any point on the loaded frame relative to the unloaded frame shall be 0.005 inch. A wide flange section depth greater than 1/10th the length of the longest frame mem-ber will be accepted as satisfying the deflection requirement.

2. Type B frame is a channel steel structural frame with brackets as shown on the drawings. The section depth shall be greater than 1/10th the length of the longest. Frame member.

3. Type C frame is a steel bracket or gusset welded or bolted directly to the ma-chine frame in order to accommodate the isolator.

2.6 SEISMIC-RESTRAINT DEVICES

A. Acceptable Manufacturers: See Section 16007 “Alternative Equipment and Suppliers”.

B. General Requirements for Restraint Components: Rated strengths, features, and application requirements shall be as defined in reports by an agency acceptable to authorities having jurisdiction.

1. Structural Safety Factor: Allowable strength in tension, shear, and pullout force of components shall be at least four times the maximum seismic forces to which they will be subjected.

C. Channel Support System: MFMA-3, shop- or field-fabricated support assembly made of slotted steel channels with accessories for attachment to braced component at one end and to building structure at the other end and other matching components and with corrosion-resistant coating; and rated in tension, compression, and torsion forces.

D. Restraint Cables: ASTM A 492 stainless-steel cables with end connections made of steel assemblies with thimbles, brackets, swivels, and bolts designed for restraining cable service; and with a minimum of two clamping bolts for cable engagement.

E. Hanger Rod Stiffener: Steel tube or steel slotted-support-system sleeve with internally

bolted connections, Reinforcing steel angle clamped to hanger rod. Do not weld stiffeners to rods.

F. Bushings for Floor-Mounted Equipment Anchor: Neoprene bushings designed for rigid equipment mountings, and matched to type and size of anchors and studs.

G. Bushing Assemblies for Wall-Mounted Equipment Anchorage: Assemblies of neoprene elements and steel sleeves designed for rigid equipment mountings, and matched to type and size of attachment devices.

H. Resilient Isolation Washers and Bushings: One-piece, molded, oil- and water-resistant neoprene, with a flat washer face.

I. Mechanical Anchor: Drilled-in and stud-wedge or female-wedge type in zinc-coated steel for interior applications and stainless steel for exterior applications. Select anchors with strength required for anchor and as tested according to ASTM E 488. Minimum length of eight times diameter.

J. Adhesive Anchor: Drilled-in and capsule anchor system containing polyvinyl or urethane methacrylate-based resin and accelerator, or injected polymer or hybrid mortar adhesive. Provide anchor bolts and hardware with zinc-coated steel for interior applications and stainless steel for exterior applications. Select anchor bolts with strength required for anchor and as tested according to ASTM E 488.

Page 84: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical Equipment Noise Control, Vibration SECTION 16074 Isolation, and Seismic Restraints

MEINHARDT PHILIPPINES INC. Page 6 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16074-Electrical Equipment Noise Control.doc

2.7 FACTORY FINISHES

A. Finish: Manufacturer's standard prime-coat finish ready for field painting.

B. Finish: Manufacturer's standard paint applied to factory-assembled and - tested equipment before shipping.

1. Powder coating on springs and housings.

2. All hardware shall be galvanized. Hot-dip galvanize metal components for exterior use.

3. Baked enamel or powder coat for metal components on isolators for interior use.

4. Color-code or otherwise mark vibration isolation and seismic-control devices to indicate capacity range.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas and equipment to receive vibration isolation and seismic-control devices for compliance with requirements for installation tolerances and other conditions affecting performance.

B. Examine roughing-in of reinforcement and cast-in-place anchors to verify actual locations before installation.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 APPLICATIONS

A. Multiple Raceways or Cables: Secure raceways and cables to trapeze member with clamps approved for application by an agency acceptable to authorities having jurisdiction.

B. Hanger Rod Stiffeners: Install hanger rod stiffeners where indicated or scheduled on Drawings to receive them and where required to prevent buckling of hanger rods due to seismic forces.

C. Strength of Support and Seismic-Restraint Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static and seismic loads within specified loading limits.

3.3 SEISMIC-RESTRAINT DEVICE INSTALLATION

A. Equipment and Hanger Restraints:

1. Install restrained isolators on electrical equipment. 2. Install resilient, bolt-isolation washers on equipment anchor bolts where clearance

between anchor and adjacent surface exceeds 0.125 inch (3.2 mm). 3. Install seismic-restraint devices using methods approved by an agency acceptable to

authorities having jurisdiction providing required submittals for component.

Page 85: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical Equipment Noise Control, Vibration SECTION 16074 Isolation, and Seismic Restraints

MEINHARDT PHILIPPINES INC. Page 7 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16074-Electrical Equipment Noise Control.doc

B. Install bushing assemblies for mounting bolts for wall-mounted equipment, arranged to provide resilient media where equipment or equipment-mounting channels are attached to wall.

C. Attachment to Structure: If specific attachment is not indicated, anchor bracing to structure at flanges of beams, at upper truss chords of bar joists, or at concrete members.

D. Drilled-in Anchors:

1. Identify position of reinforcing steel and other embedded items prior to drilling holes for anchors. Do not damage existing reinforcing or embedded items during coring or drilling. Notify the structural engineer if reinforcing steel or other embedded items are encountered during drilling. Locate and avoid prestressed tendons, electrical and telecommunications conduit, and gas lines.

2. Do not drill holes in concrete or masonry until concrete, mortar, or grout has achieved full design strength.

3. Wedge Anchors: Protect threads from damage during anchor installation. Heavy-duty sleeve anchors shall be installed with sleeve fully engaged in the structural element to which anchor is to be fastened.

4. Adhesive Anchors: Clean holes to remove loose material and drilling dust prior to installation of adhesive. Place adhesive in holes proceeding from the bottom of the hole and progressing toward the surface in such a manner as to avoid introduction of air pockets in the adhesive.

5. Set anchors to manufacturer's recommended torque, using a torque wrench. 6. Install zinc-coated steel anchors for interior and stainless-steel anchors for exterior

applications.

3.4 ACCOMMODATION OF DIFFERENTIAL SEISMIC MOTION

A. Install flexible connections in runs of raceways, cables, wireways, cable trays, and busways where they cross seismic joints, where adjacent sections or branches are supported by different structural elements, and where they terminate with connection to equipment that is anchored to a different structural element from the one supporting them as they approach equipment.

3.5 FIELD QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to perform tests and inspections and prepare test reports.

B. Perform tests and inspections.

C. Tests and Inspections:

1. Provide evidence of recent calibration of test equipment by a testing agency acceptable to authorities having jurisdiction.

2. Schedule test with EMPLOYER’S REPRESENTATIVE, through MEEPF CONSULTANT, before connecting anchorage device to restrained component (unless postconnection testing has been approved), and with at least seven days' advance notice.

3. Obtain MEEPF CONSULTANT’S approval before transmitting test loads to structure. Provide temporary load-spreading members.

4. Test at least four of each type and size of installed anchors and fasteners selected by MEEPF CONSULTANT’S.

5. Test to 90 percent of rated proof load of device. 6. Measure isolator restraint clearance. 7. Measure isolator deflection.

Page 86: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Electrical Equipment Noise Control, Vibration SECTION 16074 Isolation, and Seismic Restraints

MEINHARDT PHILIPPINES INC. Page 8 of 8 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16074-Electrical Equipment Noise Control.doc

8. Verify snubber minimum clearances. 9. If a device fails test, modify all installations of same type and retest until satisfactory

results are achieved.

D. Remove and replace malfunctioning units and retest as specified above.

E. Prepare test and inspection reports.

3.6 ADJUSTING

A. Adjust isolators after isolated equipment is at operating weight.

B. Adjust limit stops on restrained spring isolators to mount equipment at normal operating height. After equipment installation is complete, adjust limit stops so they are out of contact during normal operation.

C. Adjust active height of spring isolators.

D. Adjust restraints to permit free movement of equipment within normal mode of operation.

3.7 ELECTRICAL VIBRATION-CONTROL AND SEISMIC-RESTRAINT DEVICE SCHEDULE

A. Supported or Suspended Equipment: As indicated on plans or as required

1. Equipment Location: As indicated on plans 2. Pads:

a. Material: Neoprene, Rubber, Hermetically sealed compressed fiberglass. b. Thickness: As per Structural recommendation c. Durometer: As per Structural recommendation d. Number of Pads: As per Structural recommendation

3. Isolator Type: As indicated on Part 2. 4. Component Importance Factor: Refer to Structural specs 5. Component Response Modification Factor: Refer to Structural specs 6. Component Amplification Factor: Refer to Structural specs

END OF SECTION

Page 87: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of SECTION 16080

Electrical Equipment

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

PART 1 – GENERAL ........................................................................................................................ 1

1.1 RELATED DOCUMENTS ........................................................................................................... 1 1.2 SUMMARY ............................................................................................................................. 1 1.3 TESTING CRITERIA ................................................................................................................. 2 1.4 QUALITY ASSURANCE, REFERENCES AND REGULATORY REQUIREMENTS ..................................... 3 1.5 QUALIFICATIONS .................................................................................................................... 4 1.6 CALIBRATION ......................................................................................................................... 5 1.7 FAILURE TO MEET TEST ......................................................................................................... 5 1.8 NOTIFICATION OF TESTING ..................................................................................................... 5

PART 2 – PRODUCTS (NOT USED) ................................................................................................ 6

PART 3 – EXECUTION ..................................................................................................................... 6

3.1 EQUIPMENT TO BE TESTED..................................................................................................... 6 3.2 DEMONSTRATION ................................................................................................................. 15

Page 88: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 1 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

SECTION 16080

STARTUP, TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENT

PART 1 – GENERAL

1.1 RELATED DOCUMENTS

A. This Section shall be used in conjunction with the following other specifications and

related Contract Documents to establish the total requirements for startup testing and

commissioning of electrical equipment:

1. Section 16051 - Common Work Results For Electrical

2. Section 16055 - Overcurrent Protective Device Coordination

3. Section16060 - Grounding and Bonding

4. Section 16073 - Hangers and Supports for Electrical Systems

5. Section 16075 - Electrical Identification

6. Section 16120 - Conductors and Cables

7. Section 16124 - Medium-Voltage Cables

8. Section 16130 - Raceways and Boxes

9. Section 16140 - Wiring Devices

10. Section 16145 - Lighting Control Devices

11. Section 16211 - Electricity Metering

12. Section 16231 - Packaged Engine Generator

13. Section 16264 - Static Uninterruptible Power Supply

14. Section 16271 - Power Transformers

15. Section 16280 - Automatic Power Factor Correction

16. Section 16289 - Transient Voltage Suppression

17. Section 16341 - High Tension Switchgear

18. Section 16410 - Circuit Breakers

19. Section 16415 - Transfer Switches

20. Section 16430 - Low Tension Switchgear

21. Section 16435 - Paralleling Switchgear

22. Section 16442 - Panelboards

23. Section 16450 - Busways

24. Section 16511 - Luminaires

B. In the event of conflict regarding startup testing and commissioning of electrical

equipment requirements between this Section and any other section, the provisions

of this Section shall govern.

C. Division 16 will be responsible to carry out the commissioning requirements specified

in Sections 17100, 17106, 17107, 17109, 17110 and other sections referenced in

17100. These include, but are not limited to, commissioning, enhanced

commissioning, preparation of a detailed O&M manual, and detailed training of the

EMPLOYER’S personnel.

1.2 SUMMARY

A. The GENERAL CONTRACTOR shall engage the services of an approved testing

organization to provide startup testing and commissioning of the electrical equipment

and/or systems listed in Section 16000, Electrical General Provisions.

Page 89: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 2 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

B. Section 16010, Basic Electrical Requirements. GENERAL CONTRACTOR refers to

electrical contractor engaged for the purposes of installing and assembling electrical

equipment.

C. It is the intent of these test to assure that all electrical equipment, both GENERAL

CONTRACTOR and EMPLOYER-Furnished, is operational within industry and the

manufacturer’s tolerances and is installed in accordance with design specifications

and the manufacturer’s recommendations.

D. Where applicable, the tests and inspections shall determine the suitability for

energization.

1.3 TESTING CRITERIA

A. General:

1. The testing company shall provide the supervision, material, equipment,

labor and technical personnel to perform all tests and inspections according

to NETA. The GENERAL CONTRACTOR shall, at his expense, furnish any

personnel necessary to assist in the testing and inspection.

2. When the tests and inspections have been completed, a label shall be

attached to all devices tested. The label shall provide the name of the

testing company, the date the tests were completed, and the initials of the

person who performed the tests.

B. Responsibilities:

1. The GENERAL CONTRACTOR shall clean the equipment, torque down all

accessible bolts according to the equipment manufacturer’s instructions,

perform routine insulation resistance tests on all branch and feeder circuits,

continuity checks on all branch and control wiring, and rotation tests for all

distribution and utilization equipment.

2. The GENERAL CONTRACTOR shall furnish a complete set of current plans

and specifications to the testing company prior to commencement of any

testing. At each test site, the GENERAL CONTRATOR shall provide any

test control power necessary to perform the tests specified. The test

organization shall be consulted as to the specific power requirements. The

GENERAL CONTRACTOR shall notify the testing organization when the

equipment and systems are ready for their inspection and testing. After

review by the testing engineer, the GENERAL CONTRACTOR shall correct

any deficiencies noted by the testing company.

3. The GENERAL CONTRACTOR shall be responsible for having the

manufacturer of each equipment and/or system provide factory-trained

representative(s) that will perform all required functional testing, checkout,

and repairs in order to pronounce the equipment and/or systems meet the

requirements of these specifications and Drawings and it is ready for startup

testing and commissioning by the testing organization as specified hereafter.

4. The GENERAL CONTRACTOR shall furnish settings of protective devices.

5. The testing organization shall notify the EMPLOYER’S RERESENTATIVE

prior to the commencement of any testing. The testing organization shall set

and adjust the protective devices and associated auxiliary timing devices in

accordance with the values furnished by the MEEPF CONSULTANT.

6. The testing organization shall maintain a written record of all tests and, upon

Page 90: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 3 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

completion of the tests, include them in a final report. The report shall detail

any deficiencies in the system material, workmanship or design. The testing

company shall, upon identification, report deficiencies to the EMPLOYER’S

REPRESENTATIVE in written form. The EMPLOYER’S

REPRESENTATIVE will report these deficiencies to the Contractor or

manufacturer to schedule remedies.

7. When directed, the testing organization shall enter “address” codes for power

monitoring devices or similar instrumentation where shown. Test monitoring

instrumentation for accuracy in combination with associated PTs and CTs.

C. Safety:

1. Safety practices shall comply with applicable state and local safety orders,

as well as with the Occupational Safety and Health Act of 1970 (OSHA) and

IEEE Standard 510. Compliance with the National Fire Protection

Association (NFPA) Standard NFPA 70E, and the Accident Prevention

Manual for Industrial Operations of the National Safety Council shall be

observed.

2. Tests shall only be performed on apparatus that is deenergized. The testing

company’s lead test engineer for the project shall be a designated safety

representative and shall supervise testing observations and safety

requirements. Work shall not proceed until he has determined that it is safe

to do so.

3. Power circuits shall have conductors shorted to ground by a hotline-

grounding device approved for the purpose. Warning signs and protective

barriers shall be provided as necessary to conduct the tests safely.

D. Reports:

1. General: Provide full documentation of all tests in the form of a report.

2. The test report shall include the following sections:

a. Scope of testing.

b. Equipment tested.

c. Description of test.

d. Test results.

e. Conclusions and recommendations.

f. Appendix, including test forms.

3. Each piece of equipment shall be recorded on a data sheet listing the

condition of the equipment as found and as left. Included shall be

recommendations for any necessary repair and/or replacement parts. The

data sheets shall indicate the name of the engineer who tested the

equipment and the date of the test completion. The EMPLOYER’S

REPRESENTATIVE shall be notified within 24 hours of any defects found

during testing.

4. Record copies of the completed test report shall be submitted to the

EMPLOYER’S REPRESENTATIVE no more than 30 days after completion

of the testing and inspection.

5. Test reports for circuit breakers shall be provided at equipment startup.

1.4 QUALITY ASSURANCE, REFERENCES AND REGULATORY REQUIREMENTS

A. The testing and inspection shall comply with all applicable sections of the applicable

Page 91: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 4 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

codes and standards listed in Division 1 of the project specifications.

B. The inspection and testing shall comply with the project plans and specifications, as

well as with the manufacturer’s drawings, instruction manuals, and other applicable

data that may be provided by the Owner, for the apparatus tested.

C. Conform to the following Standards:

1. ANSI/IEEE Standard 43-2000 – IEEE Recommended Practice for Testing

Insulation Resistance of Rotating Machinery.

2. ANSI/IEEE 112-1996 – Test Procedures for Polyphase Induction Motors and

Generators.

3. ANSI/IEEE Standard 400-1991 – IEEE Guide for Making High-Direct-Voltage

Tests On Power Cable Systems in the Field.

4. ANSI/IEEE C62.45-2002 – IEEE Guide on Surge Testing for Equipment

Connected to Low Voltage AC Power Circuits.

5. ASTM D 877-2004 – Standard Test Method for Dielectric Breakdown Voltage

of Insulating Liquids Using Disk Electrodes.

6. ICEA S-93-639 / NEMA WC74-2000 – Shielded Power Cable 5-46 kV.

7. IEEE Standard 81-1983 – IEEE Guide for Measuring Earth Resistivity,

Ground Impedance, and Earth Surface Potential of a Ground System.

8. IEEE Standard 510-1983 (R1992) – Recommended Practices For Safety In

High-Voltage And High-Power Testing.

9. IEEE Standard 576-2000 – Recommended Practice for Installation,

Termination and Testing of Insulated Power Cables as Used in Industrial and

Commercial Applications.

10. IEEE Standard C57.12.90-1999 – Standard Test Code for Liquid-Immersed

Distribution, Power, and Regulating Transformers.

11. IEEE Standard C57.12.91-2001 – Standard Test Code for Dry-Type

Distribution and Power Transformers.

12. NECA – National Electrical Contractors Association.

13. NETA – International Electrical Testing Association.

14. NETA ATS-2003 – Acceptance Testing Specifications for Electric Power

Distribution Equipment and Systems. A copy of this is in Section

16080_app.

15. NFPA 70E-2004 – Standard for Electrical Safety Requirements for Employee

Workplaces.

16. NICET – National Institute of Certification in Engineering Technologies.

1.5 QUALIFICATIONS

A. The testing organization shall be an independent, third party testing organization,

which will function as an unbiased testing authority, professionally independent of the

manufacturers, suppliers and installers of equipment or systems evaluated by the

testing organization.

B. Manufacturer’s representative or equally qualified individual shall be present during

all testing to ensure the testing is performed properly and that any deficiencies

discovered are promptly corrected.

C. The testing organization shall be a full-service company and shall be regularly

engaged in the testing of electrical equipment, devices, installations, and systems.

The testing organization shall utilize factory-trained test engineers who are regularly

employed for testing services and who are capable of troubleshooting, as well as

identifying power equipment problems.

Page 92: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 5 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

D. All work outlined shall be performed under the full-time, onsite supervision of a

graduate engineer with a minimum of 5 years of field-testing experience. Supervisor

shall hold a current registered certification in electrical testing applicable to each type

of apparatus to be inspected or tested. Certification in electrical testing shall be

issued by an independent, nationally recognized, technician certification agency.

Acceptable agencies and certifications:

1. NETA: Certified Technician/Level III or Certified Senior Technician/Level IV.

2. NICET: Engineering Technician/Level III or Senior Engineering

Technician/Level IV.

E. Upon request, the testing company shall submit proof of its qualifications.

1.6 CALIBRATION

A. Any system material or workmanship, which is found defective on the basis of

acceptance tests, shall be reported directly to the EMPLOYER’S

REPRESENTATIVE.

B. GENERAL CONTRACTOR shall replace the defective material or equipment and

have test repeated until test proves satisfactory without additional cost to the

EMPLOYER.

1.7 FAILURE TO MEET TEST

A. Any system material or workmanship, which is found defective on the basis of

acceptance tests, shall be reported directly to the EMPLOYER’S

REPRESENTATIVE.

B. Contractor shall replace the defective material or equipment and have test repeated

until test proves satisfactory without additional cost to the EMPLOYER.

1.8 NOTIFICATION OF TESTING

A. Notify the GENERAL CONTRACTOR, MEEPF CONSULTANT and the

EMPLOYER’S REPRESENTATIVE ten (10) working days before any scheduled

testing begins.

Page 93: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 6 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

PART 2 – PRODUCTS (NOT USED)

PART 3 – EXECUTION

3.1 EQUIPMENT TO BE TESTED

A. Section 16140, Wiring Devices:

1. Receptacles or Outlets

a. Ground Fault Circuit Interrupters (GFCI)

i. All GFCI outlets and protected outlets will be tested individually to

ensure they all meet protection requirements. A full GFCI test involves

the Test/Reset Button Test, Wiring Test and GFCI Circuit Challenge.

(a) Test/Reset Button Test:

(1) Ensure the energized circuit can be appropriately de-

energized.

(2) It is preferable to have a light, a fan, or a circuit tester connect

to the outlet to ensure the energization status of the circuit.

(3) Press the Test Button.

(4) The Reset Button should pop out. If it does not, proceed to

step (8).

(5) If the Reset Button pops out, check to ensure the electrical

equipment has become de-energized. If the electrical

equipment has not de-energized, proceed to step (8).

(6) If the electrical equipment has de-energized, press the Reset

Button. The Reset Button should stay reset and the electrical

equipment should re-energize. If the Reset Button does not

reset or the electrical equipment does not re-energize, proceed

to step (8).

(7) Repeat steps (3) through (6) with the light, fan, or circuit tester

plugged into the other receptacles.

(8) If the outlet fails any part of the Reset Button test, either the

outlet is miswired or needs to be replaced. If the repair cannot

be accomplished immediately and the outlet must remain in

service, place a caution label over the outlet to prevent usage

until the repairs or replacement are completed. Once repaired

or replaced the outlet must be fully tested before use is

allowed.

(9) When testing slaved outlets, repeat steps (3) through (8) with a

device plugged into the slaved outlet. Use the Test and Reset

Buttons on the GFCI that provides protection for the outlet to

perform the Test/Reset Button Test.

(b) Wiring Test:

(1) Acquire an accepted wiring test similar to the Greenlee GFCI

Circuit Tester with a wiring tester, catalog number 5708,

NAED/DCI# 78-3310/34523.

(2) If using a combination GFCI/Wiring Tester, set the nominal

leakage current knob to zero mA.

(3) Plug the tester into a receptacle on the outlet to be tested.

Page 94: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 7 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

(4) Check the tester display to ensure proper wiring.

(5) If the wiring is improper and cannot be immediately repaired,

proceed no further, cover the outlet with a caution label until

the outlet has been properly wired and then repeat the tests

prior to allowing the outlet to be used.

(c) GFCI Circuit Challenge:

(1) Test the current that causes the GFCI to trip.

(i) Turn the current selector knob to the next higher current

setting;

(ii) Wait for the test light to flash;

(iii) If the GFCI trips out;

Reset the knob to zero current;

Press the Reset Button on the GFCI the outlet the

GFCI is wired to or the GFCI circuit;

Check for test lights to indicate the circuit is re-

energized;

Remove the tester from the outlet.

(iv) If the circuit does not trip out, repeat steps (i) through

(iv).

(v) If the GFCI fails to trip within 4 to 7 mA and the GFCI

cannot be currently replaced, proceed no further, place a

caution label over the outlet, indicate faulty GFCI and

once the outlet has been replaced repeat the tests prior

to allowing the outlet to be used.

(2) After the GFCI has tripped, repeat the tests in (a), (b) and (c)

for the other receptacle (on a 2-receptacle GFCI outlet) and

all GFCI protected outlets.

(d) Placing a Test Sticker:

(1) If the outlet passes all of the above tests, place a GFCI test

sticker on the outlet cover with the following information:

(i)The test date;

(ii) The tester’s initials and company;

(iii) The current level where the interruption occurred;

(iv) The wiring status;

(v) And the number of the outlet (to distinguish the GFCI

protected outlets from each other for documentation

purposes).

B. Section 16060, Grounding and Bonding:

1. Test, in the EMPLOYER’S REPRESENTATIVE’S presence, the ground

resistance of the grounding system. Test by means of the [fall-of-potential][two

terminal or direct] method per IEEE Standard 81.

a. Testing Instrument: Battery-powered or hand-cranked AC tester.

Page 95: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 8 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

i. Indicates ground resistance in ohms from digital decade switches when

the unit’s self-contained meter indicates a null condition.

ii. Range: 0.01 ohm to 9,990 ohms in four overlapping ranges.

iii. Null condition occurs when no current flows through the potential

electrodes.

iv. Instrument Accuracy: Plus or minus 2 percent or greater.

v. Manufacturer: Biddle Instruments Model 250241 (battery powered) or

250220-2 (hand-cranked) Megger Null Balance Earth Tester.

b. Fall-of-Potential Test (Intersecting Slope Method):

i. Connect instrument as shown on the Drawings.

ii. Place Rod P2 at various locations in line between the tested electrode

and Probe C2 and plot the results on a graph (distance versus

resistance). Take sufficient readings to yield a portion of the plotted

curve as being constant (rate-of-resistance change becomes so small

with respect to distance as to be insignificant).

c. Two-Terminal Test (Direct Method):

i. Connect jumper between terminals C1 and P1 and between C2 and P2.

ii. Connect terminal P1 and C1 to the electrode under test. Connect P2

and C2 to an all metallic water pipe system extensive enough to have a

negligible resistance and metallic throughout, without insulating

couplings or flanges.

d. Conduct two separate tests on opposite sides of the grounding grid.

e. Report failure to obtain specified ground resistance to the EMPLOYER’S

REPRESENTATIVE.

f. Test report shall be in writing, and shall show temperature, humidity, and

condition of the soil at the time of the tests.

C. Section 16124, Medium-Voltage Cables:

1. Inspect exposed cable sections for physical damage.

2. Verify cable is connected according to the Drawings and shield grounding, cable

support, and terminations are properly installed.

3. DC High-Potential Test:

a. Perform high-potential tests on 5, 15, 25, and 35 kV cable after installation

in accordance with ICEA S-93-639 / NEMA WC74, ANSI/IEEE

Standard 400 and IEEE Standard 576.

b. Perform tests in the presence of the EMPLOYER’S REPRESENTATIVE.

Test each length of each phase of cable in the system after installation, with

splices and terminations in place but disconnected from equipment.

c. Use the data sheets at the end of this Section to record the results of DC

high-potential test, or if approved by the EMPLOYER’S

REPPRESENTATIVE, use the data sheets provided by the testing

company.

d. The voltage may be increased continuously or in steps to the maximum test

value. If increased continuously, apply the test voltage at a uniform rate,

increasing to maximum voltage in not less than 10 seconds or more than

60 seconds. If applied in steps, increase the test voltage from one step to

the next in approximately five to eight equal steps. Make the duration of

each step long enough for the absorption current to attain reasonable

Page 96: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 9 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

stabilization (1 minute).

4. Record current and voltage readings at the end of each step on 5, 15, 25 or 35

kV cable high-potential test data sheets included in this Section; prepare a

written copy of the test data for submission to the EMPLOYER’S

REPRESENTATIVE and include in the operations and maintenance manual.

Test company forms may be substituted for the data sheets in this Section, if

they include, at a minimum, the same information.

5. Immediately following these tests, ground the conductor to drain any charge to

earth. GENERAL CONTRACTOR shall replace cables and terminations not

passing the test.

D. Section 16231, Packaged Engine Generators:

1. Test the system per the manufacturer’s recommendation and the requirements in

Section 16231 along with the following:

1. Visual and mechanical inspection:

a. Inspect for physical damage.

b. Compare nameplate information and connection with Drawings and

Specifications.

c. Inspect for proper anchorage and grounding.

2. Electrical and mechanical tests:

a. Perform an insulation-resistance test on generator winding with respect to

ground in accordance with ANSI/IEEE Standard 43. Determine polarization

index.

b. Test protective relay devices in accordance with applicable portions of this

Section.

c. Perform phase rotation test to determine compatibility with load

requirements.

d. Functionally test engine shutdown for low oil pressure, overtemperature,

overspeed, and other features as applicable

e. Perform vibration base-line test. Plot amplitude versus frequency for each

main bearing cap.

f. Perform load bank test in accordance with the following schedule:

g. Perform a cooling system test to validate the engine cooling system.

3. Test values:

a. Perform an insulation-resistance test at minimum test voltage of 1,000

volts. Minimum insulation resistance shall be 100 megohms.

b. Vibration levels shall not exceed manufacturer’s recommendations and

specification.

c. Load test results shall demonstrate the ability of the unit to deliver rated

load for the test period.

E. Section 16264, Uninterruptible Power Supply (UPS):

1. Test the system per the manufacturer’s recommendation and the requirements in

Section 16264.

F. Section 16271, Power Transformers:

Page 97: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 10 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

1. Visual and Mechanical Inspection:

a. Check primary, secondary, and ground connections.

b. Clean and inspect bushings.

c. Check accessory devices for condition and proper operation.

d. Liquid-Filled Transformers Only:

i. Inspect bushing clamps and gaskets.

ii. Inspect cover and handhole gasket seals.

iii. Inspect tap changer seals.

iv. Check for oil leaks and external damage to radiators.

v. Check liquid level.

vi. Inspect for damaged insulators and potheads.

2. Electrical Tests:

a. Perform insulation resistance test by meggering transformer windings high

to low and ground, low to high and ground, and high and low to ground.

b. Perform turns ratio test.

c. Where cooling fans have been provided, verify proper operation of same.

d. Power factor test.

e. Liquid-Filled Transformers Only:

i. Test dielectric liquid to ASTM D877, using 25,000 volts minimum

breakdown voltage, after installation and before energizing from

system.

ii. Test transformer to IEEE C57.12.90.

iii. Perform a turns ratio test for each tap position.

f. Dry-Type Distribution and Power Transformers Only:

i. Test transformer to IEEE C57.12.91.

G. Section 16341, High Tension Switchgear:

1. Switchgear:

a. Visual and Mechanical Inspections:

i. Verify enclosure interiors are cleaned and free of accumulated dust,

dirt, films, and other foreign material.

ii. Inspect and clean all bus and support insulators.

iii. Inspect all electrical and mechanical components for condition and any

evidence of defects or failure.

iv. Check for proper travel and alignment of drawout circuit breakers.

v. Check breaker connections to bus.

vi. Inspect bolted connections. The GENERAL CONTRACTOR shall

torque wrench tighten or remake any questionable connections.

vii. Inspect for missing or loose hardware or accessories.

viii. Inspect ground bus connections.

ix. Operate key and door interlock devices to ensure proper operation.

b. Electrical Tests:

i. Insulation Resistance Test: Megger main secondary bus and feeder

Page 98: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 11 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

circuits phase-to-phase and phase-to-ground.

ii. Energize any space heater circuits to ensure proper operation.

c. Instruments and Meter Tests: Inspect panel-mounted instruments and

meters. Clean and check for calibration accuracy. Make minor

adjustments, as necessary.

2. Circuit Breakers:

a. Visual and Mechanical Inspection:

i. Remove drawout circuit breaker from cell.

ii. Clean circuit breaker and inspect for defects or damage.

iii. Inspect and check contact alignment.

iv. Inspect finger clusters on line and load stabs.

v. Check for proper mechanical operation. Lubricate where necessary.

vi. Check auxiliary devices for proper operation.

vii. Check breaker racking-device (if applicable) for alignment and friction-

free operation. Lubricate if necessary.

b. Electrical Tests:

i. Insulation Resistance Test: Megger main secondary bus and feeder

circuits phase-to-phase and phase-to-ground.

ii. Energize any space heater circuits to ensure proper operation.

c. Instruments and Meter Tests: Inspect panel-mounted instruments and

meters. Clean and check for calibration accuracy. Make minor

adjustments, as necessary.

3. Protective Relays:

a. Visual and Mechanical Inspection:

i. Remove relay from case. Visually inspect each relay and case for

damaged or broken parts.

ii. Check contact and bearing clearances. Check hardware for tightness.

Check electrical connections for proper contact. Make minor

adjustments, as necessary.

b. Electrical Tests:

i. Insulation Resistance Test: Megger each relay circuit to relay frame.

ii. Operational Tests: Calibrate relays to settings provided by the fault

calculation and protective device coordination study provided by the

Owner.

(a) Time Overcurrent Relays

(1) Test minimum pickup.

(2) Test the minimum timing points at three times tap value and at

five times tap value unless otherwise specified.

(3) Test pickup of instantaneous trip attachment, if applicable.

(4) Check operation of target indicator.

Page 99: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 12 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

(b) Directional Overcurrent Relays:

(1) Test operation of directional units in tripping and nontripping

directions at rated current and voltage.

(2) Test time overcurrent unit as described for time overcurrent

relays above.

(c) Voltage-Controlled Overcurrent Relays:

(1) Test dropout of voltage unit.

(2) Test time overcurrent unit as described for time overcurrent

relays above.

(d) Instantaneous Overcurrent Relays:

(1) Test pickup of each coil by itself.

(2) Apply equal current to opposing coils to test for balanced or

no-trip condition.

(3) Check operation of target indicator.

(e) Differential Relays:

(1) Test pickup of relay with current in one restraint coil and

operating coil for each set of windings.

(2) Check operation of target indicator.

(3) Test current transformer connections and polarities to ensure

proper operation.

iii. After the relays have been tested, they shall be reinstalled in the relay

cases. Each relay circuit shall be tested for proper operation by applying

control power and manually closing the relay contacts to trip the breaker.

H. Section 16410, Disconnect Switches:

1. Visual and Mechanical Inspection:

a. Inspect cover and case, and check for broken or loose terminals.

b. Operate breaker to check operation.

2. Electrical Tests (all breakers with frames rated 600A and above plus 10 percent

of breakers with frames rated 250A frame to 600A frame):

a. Insulation Resistance Test: Megger main poles of breaker pole to pole, from

each pole to ground, and across the open contacts of each pole.

b. Contact Resistance Test: Measure contact resistance in microhms across

main pole contacts with breaker closed and latched to check for good, low-

resistance contact. Investigate any value exceeding 500 microhms or

deviation of 50 percent or more from adjacent contacts or similar breakers.

c. Test overcurrent trip device by primary current injection and calibrate to

settings provided on all circuit breakers 600A and larger and 10 percent of

circuit breakers 200A-599A and calibrate to settings provided by A/E.

Page 100: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 13 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

i. All trip units shall be tested by primary injection.

ii. Static overcurrent trip devices shall be tested per manufacturer’s

instructions.

iii. Test for minimum pickup current.

iv. Apply 300 percent of pickup current and measure time necessary to trip

breaker (long-time delay).

v. Where short-time delay characteristics are provided, test short-time

pickup and delay.

vi. Test instantaneous trip by passing current sufficiently high to trip breaker

instantaneously.

vii. Where ground fault protection is provided, test ground fault pickup and

delay.

viii. Check reset characteristics of trip unit.

d. For the 10 percent group of breakers tested, if one of these breakers fails the

test, then 10 more breakers shall be tested.

I. Section 16415, Transfer Switches:

1. Test the system per the manufacturer’s recommendation and the requirements in

Section 16412.

J. Section 16430, Switchgears:

1. Visual and Mechanical Inspection:

a. Verify enclosure interiors are cleaned and free of accumulated dust, dirt, oil

films, and other foreign material.

b. Inspect all electrical and mechanical components for condition and any

evidence of defect or failure.

c. Check for proper travel and alignment of any drawout or plug-in circuit

breakers.

d. Check breaker connections to bus.

e. Inspect bolted connections. The GENERAL CONTRACTOR shall torque

wrench tighten or remake any questionable connections.

f. Inspect for missing or loose hardware or accessories.

g. Inspect ground bus connections.

h. Operate key and door interlock devices to ensure proper operation.

2. Electrical Tests:

a. Insulation Resistance Test: Megger main secondary bus and feeder circuits

phase to phase and phase to ground.

b. Energize any space heater circuits to ensure proper operations.

3. Circuit Breakers:

a. Visual and Mechanical Inspection:

i. Remove each drawout type circuit breaker.

ii. Inspect arc chutes of power circuit breakers.

iii. Inspect circuit breaker for defects or damage.

iv. Inspect and check contacts. Check alignment, overtravel, and pressure.

Page 101: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 14 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

Adjust if necessary.

v. Inspect finger clusters on line and load stabs of drawout circuit breakers.

vi. Check for proper mechanical operation. Lubricate where necessary.

vii. Check auxiliary devices for proper operation.

viii. Check breaker racking-device (if applicable) for alignment and friction-

free operation. Lubricate if necessary.

b. Electrical Tests:

i. Insulation Resistance Test: Megger main poles of breaker pole to pole,

from each pole to ground, and across the open contacts of each pole.

ii. Contact Resistance Test: Measure contact resistance in microhms

across main pole contacts with breaker closed and latched to check for

good, low-resistance contact. Investigate any value exceeding

500 microhms or deviation of 50 percent or more from adjacent contacts

or similar breakers.

iii. Test overcurrent trip device by primary injection and calibrate to

settings provided by A/E. Static overcurrent trip devices shall be tested

per the manufacturer’s instructions. Test each pole of the breaker

individually. Data shall be compared with manufacturer’s published

data.

(a) Test for minimum pickup current.

(b) Apply 300 percent of pickup current and measure time necessary to

trip breaker (long-time delay).

(c) Where short-time delay characteristics are provided, test short-time

pickup and delay.

(d) Test instantaneous trip by passing current sufficiently high to trip

breaker instantaneously.

(e) Where ground fault protection is provided, test ground fault pickup

and delay.

(f) Check reset characteristics of trip unit.

c. Electrically test any auxiliary devices, such as shunt trips, undervoltage trips,

alarm contacts, and auxiliary contacts.

Section 16442, Panelboards/Section 16443, Motor Control Centers:

1. Visual and Mechanical Inspection - Circuit Breakers:

a. Inspect cover and case, and check for broken or loose terminals.

b. Operate breaker several times to check proper operation.

c. Glastic and phenolic components to be inspected for cracks.

d. Contacts, shunts, etc to be visually inspected for alignment.

2. Electrical Tests - Circuit Breakers (all breakers with frames rated 600A and

above plus 10 percent of breakers with frames rated 200A through 599A). For

CPS and emergency power switchboard and panelboards, test all main circuit

breakers regardless of size:

a. Insulation Resistance Test: Megger main poles of breaker pole to pole, from

each pole to ground, and across the open contacts of each pole.

b. Contact Resistance Test: Measure contact resistance in microhms across

main pole contacts with breaker closed and latched to check for good, low

resistance contact. Investigate any value exceeding 500 microhms or

Page 102: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Startup, Testing and Commissioning of Electrical Equipment

SECTION 16080

MEINHARDT PHILIPPINES INC. Page 15 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16080-Startup,

Testing and Commissioning of Electrical Equipment.doc

deviation of 50 percent or more from adjacent contacts or similar breakers.

c. For the 10 percent group of breakers tested, if one of these breakers fails the

test, then 10 more breakers shall be tested.

d. Test overcurrent trip device by primary current injection and calibrate to

settings provided on all circuit breakers 600A and larger and 10 percent of

circuit breakers 200A-599A.

3.2 DEMONSTRATION

A. Engage a factory authorized service representative to train EMPLOYER’S maintenance

personnel to adjust, operate, and maintain the electrical equipment and systems.

END OF SECTION

Page 103: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL 600V Wire and Cable SECTION 16120

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16120-600V Wire and Cable.doc

PART 1 - GENERAL ......................................................................................................................... 1

1.1 DESCRIPTION ........................................................................................................................ 1 1.2 STANDARDS .......................................................................................................................... 1 1.3 QUALITY ASSURANCE ............................................................................................................. 1 1.4 SUBMITTALS .......................................................................................................................... 1 1.5 FIELD TESTING ...................................................................................................................... 1

PART 2 – PRODUCTS ...................................................................................................................... 2

2.1 ACCEPTABLE MANUFACTURERS .............................................................................................. 2 2.2 WIRE AND CABLE ................................................................................................................... 2

PART 3 – EXECUTION ..................................................................................................................... 3

3.1 GENERAL .............................................................................................................................. 3

Page 104: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL 600V Wire and Cable SECTION 16120

MEINHARDT PHILIPPINES INC. Page 1 of 4 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16120-600V Wire and Cable.doc

SECTION 16120 600V WIRE AND CABLE

PART 1 - GENERAL

1.1 DESCRIPTION

A. Provide 600 volt wire and cable in accordance with the Contract Documents.

1.2 STANDARDS

A. PS B. PEC (Part 1 & Part 2) – Latest Edition. C. Rubber Insulated Wire and Cables: IPCEA S-19-81, NEMA WC 3 and UL 44. D. Thermoplastic Insulated Wire and Cables: IPCEA S-61-402, NEMA WC 3 and UL 83. E. Annealed Copper Wire for Conductors: ASTM B-3. F. Terminal Blocks: UL 1059.

1.3 QUALITY ASSURANCE

A. Wires and cables shall be of the same manufacturer.

1.4 SUBMITTALS

A. Manufacturer’s product data sheet. B. Samples C. Field test reports.

1.5 FIELD TESTING

A. Inspect splices and terminations and make mechanically and electrically tight prior to

final acceptance of the work. B. Feeder and branch circuit insulation shall be tested after installation and before

connection to fixtures, appliances and devices. 1. Tests shall be performed with a 1000 volt megger and conductors shall test free

from short circuits and grounds.

2. Conductors shall be tested phase-to-phase and phase-to-ground, phase-to-neutral.

3. Furnish the instruments, materials and labor required.

C. Demonstration: Subsequent to wire and cable installation and connection, energize circuits and demonstrate functioning in accordance with contract requirements. Correct deficiencies and retest to demonstrate compliance.

Page 105: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL 600V Wire and Cable SECTION 16120

MEINHARDT PHILIPPINES INC. Page 2 of 4 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16120-600V Wire and Cable.doc

D. All test results/records shall be endorsed by a qualified electrical engineer and submitted to the consultants for comment/approval. Approved test record shall be included into the O & M manuals for easy reference.

PART 2 – PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS

A. Wire and Cable: Refer to Section 16007.

B. Connectors: 1. Wire size 2.0mm2 through 10mm2: a. Hand or tool applied. 2. Wire size 16mm2 through 35mm2: a. Tool applied: One hole compression type. 3. Wire size 50mm2 through 240mm2: a. Tool applied: Two hole compression type. C. Electrical Tape: 1. Scotch type, 3M.

2.2 WIRE AND CABLE

A. General: 1. 600V minimum insulation rating for operation voltage of 240V and 750V/1000V

minimum insulation rating for operation voltage of 480V. B. Conductor:

1. Electrical grade, annealed copper, tinned if rubber insulated and fabricated in accordance with ASTM and IPCEA standards. Minimum size number 2.0mm2.

2. Aluminum conductors are not permitted.

C. Stranding and Number of Conductors:

1. Size 3.5mm2 and 5.5mm2 solid. 2. Larger than 5.5mm2, stranded ASTM Class B. 3. Control wires stranded in accordance with ASTM Class B stranding

designations. 4. Cables for low voltage systems shall be multi conductor type unless otherwise

noted. D. Insulated Single Conductors

Page 106: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL 600V Wire and Cable SECTION 16120

MEINHARDT PHILIPPINES INC. Page 3 of 4 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16120-600V Wire and Cable.doc

1. Type THW or THWN – Flame retardant, moisture and heat resistant thermoplastic with nylon jacket or equivalent, maximum operating, temperature

75C. Thermoplastic insulation suitable for use in wet locations up to 75oC. 2. Type THHN – Flame Retardant and Heat-resistant thermoplastic insulation,

with nylon jacket or equivalent, maximum operating temperature 90C. 3. Type XHHW – Flame Retardant and Cross linked polyethylene CPE jacketed

all throughout, maximum operating temperature 90C. E. Color Coding: 1. Wiring shall be color coded as follows: 1 phase, 2 wire + Ground Phase A – Red/Phase B-Yellow/Phase C-Blue Neutral - White Ground - Green 3 phase, 4 wire + Ground Phase A - Red Phase B - Yellow Phase C - Blue Neutral - White Ground - Green 2. Control wiring shall be color coded in accordance with manufacturer's

recommendations.

PART 3 – EXECUTION

3.1 GENERAL

A. Provide minimum 5.5mm2 wiring for 220 volt 20A, branch circuits exceeding 50 meters

in length from panel board to furthest outlet. Contractor to relocate or add DB in case there are more than two 5.5mm2 wiring for 20A CB due to voltage drop or more than 50m branch circuit run.

B. Do not install wire until raceway systems are complete. C. Provide cable supports for vertical risers. D. Wire size shall be uniform for the entire length of the circuit unless noted otherwise.

E. Do not splice feeders or dedicated branch circuits unless otherwise indicated.

F. Make connections, splices, taps and joints with solderless devices, mechanically and electrically secured.

G. Lubricate cables to facilitate pulling. Lubrication material shall be inert to cable and

raceways.

H. Install compression connectors with hydraulic die, embossing die code into connector. Connect to bus with Belleville type washers for positive pressure over complete contact area. Insulate with heat shrink tubing.

Page 107: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL 600V Wire and Cable SECTION 16120

MEINHARDT PHILIPPINES INC. Page 4 of 4 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16120-600V Wire and Cable.doc

I. Provide a separate neutral for dimmer branch circuits, ground fault interrupter branch

circuits, lighting branch circuits serving electronic ballasts and branch circuits serving isolated ground and isolated ground surge suppressor type receptacles.

END OF SECTION

Page 108: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Raceways and Boxes SECTION 16130

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16130-Raceways and Boxes.doc

PART 1 - GENERAL ......................................................................................................................... 1 1.1 RELATED DOCUMENTS .......................................................................................................... 1 1.2 SUMMARY ............................................................................................................................ 1 1.3 DEFINITIONS ........................................................................................................................ 1 1.4 SUBMITTALS ........................................................................................................................ 1 1.5 QUALITY ASSURANCE ........................................................................................................... 2

PART 2 - PRODUCTS ....................................................................................................................... 2 2.1 METAL CONDUIT AND TUBING ................................................................................................ 2 2.2 NONMETALLIC CONDUIT AND TUBING ...................................................................................... 3 2.3 METAL WIREWAYS ................................................................................................................ 3 2.4 FLUSH UNDERFLOOR DUCT ................................................................................................... 4 2.5 BOXES, ENCLOSURES AND CABINETS ..................................................................................... 4 2.6 SLEEVES FOR RACEWAYS ..................................................................................................... 5 2.7 SLEEVE SEALS ..................................................................................................................... 5 2.8 SOURCE QUALITY CONTROL FOR UNDERGROUND ENCLOSURES ............................................... 5

PART 3 - EXECUTION ...................................................................................................................... 5 3.1 RACEWAY APPLICATION ........................................................................................................ 5 3.2 INSTALLATION ...................................................................................................................... 7 3.3 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS .......................................................... 8 3.4 SLEEVE-SEAL INSTALLATION.................................................................................................. 9 3.5 FIRESTOPPING ..................................................................................................................... 9 3.6 PROTECTION ........................................................................................................................ 9

Page 109: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Raceways and Boxes SECTION 16130

MEINHARDT PHILIPPINES INC. Page 1 of 9 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16130-Raceways and Boxes.doc

SECTION 16130 RACEWAYS AND BOXES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical wiring.

B. Related Sections include the following:

1. Division 2 Section “Underground Ducts and Utility Structures” for exterior duct banks, manholes, and underground utility construction.

1.3 DEFINITIONS

A. EMT: Electrical metallic tubing.

B. ENT: Electrical nonmetallic tubing.

C. EPDM: Ethylene-propylene-diene terpolymer rubber.

D. FMC: Flexible metal conduit.

E. IMC: Intermediate metal conduit.

F. LFMC: Liquidtight flexible metal conduit.

G. LFNC: Liquidtight flexible nonmetallic conduit.

H. NBR: Acrylonitrile-butadiene rubber.

I. RNC: Rigid nonmetallic conduit.

1.4 SUBMITTALS

A. Product Data: For surface raceways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

B. Shop Drawings: For the following raceway components. Include plans, elevations, sections, details, and attachments to other work.

1. Custom enclosures and cabinets. 2. For handholes and boxes for underground wiring, including the following:

a. Duct entry provisions, including locations and duct sizes. b. Frame and cover design. c. Grounding details.

Page 110: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Raceways and Boxes SECTION 16130

MEINHARDT PHILIPPINES INC. Page 2 of 9 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16130-Raceways and Boxes.doc

d. Dimensioned locations of cable rack inserts, and pulling-in and lifting irons. e. Joint details.

C. Samples for Initial Selection: For wireways, nonmetallic wireways and surface raceways with factory-applied texture and color finishes.

D. Samples for Verification: For each type of exposed finish required for wireways nonmetallic wireways and surface raceways, prepared on Samples of sizes.

E. Coordination Drawings: Conduit routing plans, drawn to scale, on which the following items are shown and coordinated with each other, based on input from installers of the items involved:

1. Structural members in the paths of conduit groups with common supports. 2. HVAC and plumbing items and architectural features in the paths of conduit groups

with common supports.

F. Manufacturer Seismic Qualification Certification: Submit certification that enclosures and cabinets and their mounting provisions, including those for internal components, will withstand seismic forces defined in Division 16 Section 16073 "Hangers and Supports for Electrical Systems” and Section 16074 “Vibration and Seismic Controls for Electrical Systems." Include the following:

1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.

a. The term "withstand" means "the cabinet or enclosure will remain in place without separation of any parts when subjected to the seismic forces specified and the unit will retain its enclosure characteristics, including its interior accessibility, after the seismic event."

2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.

3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.

G. Qualification Data: For professional engineer and testing agency.

H. Source quality-control test reports.

1.5 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in PEC, Article 1.0, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B. Comply with PEC.

PART 2 - PRODUCTS

2.1 METAL CONDUIT AND TUBING

A. Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. Rigid Steel Conduit: ANSI C80.1.

C. Aluminum Rigid Conduit: ANSI C80.5.

Page 111: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Raceways and Boxes SECTION 16130

MEINHARDT PHILIPPINES INC. Page 3 of 9 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16130-Raceways and Boxes.doc

D. IMC: ANSI C80.6.

E. PVC-Coated Steel Conduit: PVC-coated IMC.

1. Comply with NEMA RN 1. 2. Coating Thickness: 0.040 inch (1 mm), minimum.

F. EMT: ANSI C80.3.

G. FMC: Zinc-coated steel or aluminum.

H. LFMC: Flexible steel conduit with PVC jacket.

I. Fittings for Conduit (Including all Types and Flexible and Liquidtight), EMT, and Cable: NEMA FB 1; listed for type and size raceway with which used, and for application and environment in which installed.

1. Conduit Fittings for Hazardous (Classified) Locations: Comply with UL 886. 2. Fittings for EMT: Steel, set-screw or compression type. 3. Coating for Fittings for PVC-Coated Conduit: Minimum thickness, 0.040 inch (1 mm),

with overlapping sleeves protecting threaded joints.

J. Joint Compound for Rigid Steel Conduit or IMC: Listed for use in cable connector assemblies, and compounded for use to lubricate and protect threaded raceway joints from corrosion and enhance their conductivity.

2.2 NONMETALLIC CONDUIT AND TUBING

A. Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. ENT: NEMA TC 13.

C. RNC: NEMA TC 2, Type EPC-40-PVC, unless otherwise indicated.

D. LFNC: UL 1660.

E. Fittings for ENT and RNC: NEMA TC 3; match to conduit or tubing type and material.

F. Fittings for LFNC: UL 514B.

2.3 METAL WIREWAYS

A. Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. Description: Sheet metal sized and shaped as indicated, NEMA 250, Type 1 and 3R, unless otherwise indicated.

C. Fittings and Accessories: Include couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings to match and mate with wireways as required for complete system.

D. Wireway Covers: Hinged type.

E. Finish: Manufacturer's standard enamel finish.

Page 112: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Raceways and Boxes SECTION 16130

MEINHARDT PHILIPPINES INC. Page 4 of 9 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16130-Raceways and Boxes.doc

2.4 FLUSH UNDERFLOOR DUCT

A. Manufacturers: Walker or Approved equal, See Section 16007 “Acceptable Equipment and Suppliers”.

B. Description: Body and lid manufactured from gauge 14 pre-galvanized steel, size and shape as indicated on plans. Designed with flexible multiple compartments for universal cable management catering power, voice and data services to numerous office workstations.

C. Fittings and Accessories: Include trunking connectors, fixing brackets, fasteners, joint accessories, end caps, adaptors and other fittings to match and mate with the trunking as required for complete system.

D. Trunking Cover: Quick-fix fasteners

E. Service Outlet Box: Adapts to a universal range of panel mounted accessories for power, data and telecom services.

F. Junction Box: Gauge 14 pre-galvanized steel with reinforced steel cover. Shall be configured as a four way, tee, bend or straight through connector box.

2.5 BOXES, ENCLOSURES AND CABINETS

A. Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. Sheet Metal Outlet and Device Boxes: NEMA OS 1.

C. Cast-Metal Outlet and Device Boxes: NEMA FB 1, ferrous alloy Type FD, with gasketed cover.

D. Nonmetallic Outlet and Device Boxes: NEMA OS 2.

E. Metal Floor Boxes: Cast or sheet metal rectangular.

F. Nonmetallic Floor Boxes: Nonadjustable, round.

G. Small Sheet Metal Pull and Junction Boxes: NEMA OS 1.

H. Cast-Metal Access, Pull, and Junction Boxes: NEMA FB 1, galvanized, cast iron with gasketed cover.

I. Hinged-Cover Enclosures: NEMA 250, Type 1, with continuous-hinge cover with flush latch, unless otherwise indicated.

1. Metal Enclosures: Steel, finished inside and out with manufacturer's standard enamel.

2. Nonmetallic Enclosures: Plastic, finished inside with radio-frequency-resistant paint.

J. Cabinets:

1. NEMA 250, Type 1, galvanized-steel box with removable interior panel and removable front, finished inside and out with manufacturer's standard enamel.

2. Hinged door in front cover with flush latch and concealed hinge. 3. Key latch to match panelboards. 4. Metal barriers to separate wiring of different systems and voltage. 5. Accessory feet where required for freestanding equipment.

Page 113: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Raceways and Boxes SECTION 16130

MEINHARDT PHILIPPINES INC. Page 5 of 9 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16130-Raceways and Boxes.doc

2.6 SLEEVES FOR RACEWAYS

A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.

B. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated.

C. Sleeves for Rectangular Openings: Galvanized sheet steel with minimum 0.052- or 0.138-inch (1.3- or 3.5-mm) thickness as indicated and of length to suit application.

D. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 7 Section "Through-Penetration Firestop Systems."

2.7 SLEEVE SEALS

A. Manufacturers: Subject to compliance with requirements, provide products for evaluation.

B. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and cable.

1. Sealing Elements: EPDM or NBR interlocking links shaped to fit surface of cable or conduit. Include type and number required for material and size of raceway or cable.

2. Pressure Plates: Plastic Carbon steel or Stainless steel]. Include two for each sealing element.

3. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating or Stainless steel of length required to secure pressure plates to sealing elements. Include one for each sealing element.

2.8 SOURCE QUALITY CONTROL FOR UNDERGROUND ENCLOSURES

A. Handhole and Pull-Box Prototype Test: Test prototypes of handholes and boxes for compliance with SCTE 77. Strength tests shall be for specified tier ratings of products supplied.

1. Tests of materials shall be performed by a independent testing agency. 2. Strength tests of complete boxes and covers shall be by either an independent

testing agency or manufacturer. A qualified registered professional engineer shall certify tests by manufacturer.

3. Testing machine pressure gages shall have current calibration certification complying with ISO 9000 and ISO 10012, and traceable to NIST standards.

PART 3 - EXECUTION

3.1 RACEWAY APPLICATION

A. Outdoors: Apply raceway products as specified below, unless otherwise indicated:

1. Exposed Conduit: IMC. 2. Concealed Conduit, Aboveground: IMC. 3. Underground Conduit: RNC, Type EPC-40-PVC, direct buried. 4. Connection to Vibrating Equipment (Including Transformers and Hydraulic,

Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC. 5. Boxes and Enclosures, Aboveground: NEMA 250, Type 3R. 6. Application of Handholes and Boxes for Underground Wiring:

Page 114: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Raceways and Boxes SECTION 16130

MEINHARDT PHILIPPINES INC. Page 6 of 9 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16130-Raceways and Boxes.doc

a. Handholes and Pull Boxes in Driveway, Parking Lot, and Off-Roadway Locations, Subject to Occasional, Nondeliberate Loading by Heavy Vehicles: [Polymer concrete] [Fiberglass enclosures with polymer-concrete frame and cover] [Fiberglass-reinforced polyester resin], SCTE 77, Tier 15 structural load rating.

b. Handholes and Pull Boxes in Sidewalk and Similar Applications with a Safety Factor for Nondeliberate Loading by Vehicles: [Polymer-concrete units] [Heavy-duty fiberglass units with polymer-concrete frame and cover], SCTE 77, Tier 8 structural load rating.

c. Handholes and Pull Boxes Subject to Light-Duty Pedestrian Traffic Only: Fiberglass-reinforced polyester resin, structurally tested according to SCTE 77 with 3000-lbf (13 345-N) vertical loading.

B. Comply with the following indoor applications, unless otherwise indicated:

1. Exposed, Not Subject to Physical Damage: EMT. 2. Exposed, Not Subject to Severe Physical Damage: EMT 3. Exposed and Subject to Severe Physical Damage: IMC. Includes raceways in the

following locations:

a. Loading dock. b. Corridors used for traffic of mechanized carts, forklifts, and pallet-handling

units. c. Mechanical rooms.

4. Concealed in Ceilings and Interior Walls and Partitions: EMT. 5. Connection to Vibrating Equipment (Including Transformers and Hydraulic,

Pneumatic, Electric Solenoid, or Motor-Driven Equipment): FMC, except use LFMC in damp or wet locations.

6. Damp or Wet Locations: IMC. 7. Embedded in slab – Type EPC-40 PVC, Type EPC-80 PVC. 8. Raceways for Optical Fiber or Communications Cable in Spaces Used for

Environmental Air: Plenum-type, optical fiber/communications cable raceway or EMT.

9. Raceways for Optical Fiber or Communications Cable Risers in Vertical Shafts: Riser-type, optical fiber/communications cable raceway or EMT

10. Raceways for Concealed General Purpose Distribution of Optical Fiber or Communications Cable: General-use, optical fiber/communications cable raceway or EMT.

11. Boxes and Enclosures: NEMA 250, Type 1, except use NEMA 250, Type 3R in damp or wet locations.

C. Minimum Raceway Size: PVC-20mm, IMC-15mm trade size.

D. Raceway Fittings: Compatible with raceways and suitable for use and location.

1. Rigid and Intermediate Steel Conduit: Use threaded rigid steel conduit fittings, unless otherwise indicated.

2. PVC Externally Coated, Rigid Steel Conduits: Use only fittings listed for use with that material. Patch and seal all joints, nicks, and scrapes in PVC coating after installing conduits and fittings. Use sealant recommended by fitting manufacturer.

E. Install nonferrous conduit or tubing for circuits operating above 60 Hz. Where aluminum raceways are installed for such circuits and pass through concrete, install in nonmetallic sleeve.

F. Do not install aluminum conduits in contact with concrete.

Page 115: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Raceways and Boxes SECTION 16130

MEINHARDT PHILIPPINES INC. Page 7 of 9 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16130-Raceways and Boxes.doc

3.2 INSTALLATION

A. Comply with NECA 1 for installation requirements applicable to products specified in Part 2 except where requirements on Drawings or in this Article are stricter.

B. Keep raceways at least 150 mm away from parallel runs of flues and steam or hot-water pipes. Install horizontal raceway runs above water and steam piping.

C. Complete raceway installation before starting conductor installation.

D. Support raceways as specified in Division 16 Section "Electrical Supports and Seismic Restraints."

E. Arrange stub-ups so curved portions of bends are not visible above the finished slab.

F. Install no more than the equivalent of three 90-degree bends in any conduit run except for communications conduits, for which fewer bends are allowed.

G. Conceal conduit and EMT within finished walls, ceilings, and floors, unless otherwise indicated.

H. Raceways Embedded in Slabs:

1. Run conduit larger than 25mm trade size, parallel or at right angles to main reinforcement. Where at right angles to reinforcement, place conduit close to slab support.

2. Arrange raceways to cross building expansion joints at right angles with expansion fittings.

3. Change from ENT to RNC, Type EPC-40-PVC, rigid steel conduit, or IMC before rising above the floor.

I. Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions: Apply listed compound to threads of raceway and fittings before making up joints. Follow compound manufacturer's written instructions.

J. Raceway Terminations at Locations Subject to Moisture or Vibration: Use insulating bushings to protect conductors, including conductors smaller than No. 4 AWG.

K. Install pull wires in empty raceways. Use polypropylene or monofilament plastic line with not less than 90-kg tensile strength. Leave at least 300 mm of slack at each end of pull wire.

L. Raceways for Optical Fiber and Communications Cable: Install raceways, metallic and nonmetallic, rigid and flexible, as follows:

1. 20-mm Trade Size and Smaller: Install raceways in maximum lengths of 15 m. 2. 25-mm Trade Size and Larger: Install raceways in maximum lengths of 23 m. 3. Install with a maximum of two 90-degree bends or equivalent for each length of

raceway unless Drawings show stricter requirements. Separate lengths with pull or junction boxes or terminations at distribution frames or cabinets where necessary to comply with these requirements.

M. Install raceway sealing fittings at suitable, approved, and accessible locations and fill them with listed sealing compound. For concealed raceways, install each fitting in a flush steel box with a blank cover plate having a finish similar to that of adjacent plates or surfaces. Install raceway sealing fittings at the following points:

1. Where conduits pass from warm to cold locations, such as boundaries of refrigerated spaces.

Page 116: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Raceways and Boxes SECTION 16130

MEINHARDT PHILIPPINES INC. Page 8 of 9 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16130-Raceways and Boxes.doc

2. Where otherwise required by PEC.

N. Expansion-Joint Fittings for RNC: Install in each run of aboveground conduit that is located where environmental temperature change may exceed 17 deg C, and that has straight-run length that exceeds 7.6 m.

1. Install expansion-joint fittings for each of the following locations, and provide type and quantity of fittings that accommodate temperature change listed for location:

a. Outdoor Locations Not Exposed to Direct Sunlight: 70 deg C temperature change.

b. Outdoor Locations Exposed to Direct Sunlight: 86 deg C temperature change. c. Indoor Spaces: Connected with the Outdoors without Physical Separation (70

deg C) temperature change. d. Attics: 75 deg C temperature change.

2. Install fitting(s) that provide expansion and contraction for at least (0.06 mm per meter of length of straight run per deg C) of temperature change.

3. Install each expansion-joint fitting with position, mounting, and piston setting selected according to manufacturer's written instructions for conditions at specific location at the time of installation.

O. Flexible Conduit Connections: Use maximum of 1000 mm of flexible conduit for recessed and semirecessed lighting fixtures, equipment subject to vibration, noise transmission, or movement; and for transformers and motors.

1. Use LFMC in damp or wet locations subject to severe physical damage. 2. Use LFMC or LFNC in damp or wet locations not subject to severe physical damage.

P. Recessed Boxes in Masonry Walls: Saw-cut opening for box in center of cell of masonry block, and install box flush with surface of wall.

Q. Set metal floor boxes level and flush with finished floor surface.

R. Set nonmetallic floor boxes level. Trim after installation to fit flush with finished floor

3.3 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS

A. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 7 Section "Through-Penetration Firestop Systems."

B. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of slabs and walls.

C. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.

D. Rectangular Sleeve Minimum Metal Thickness:

1. For sleeve cross-section rectangle perimeter less than 50 inches (1270 mm) and no side greater than (400 mm), thickness shall be 0.052 inch (1.3 mm).

2. For sleeve cross-section rectangle perimeter equal to, or greater than, (1270 mm) and 1 or more sides equal to, or greater than, (400 mm), thickness shall be (3.5 mm).

E. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless openings compatible with firestop system used are fabricated during construction of floor or wall.

F. Cut sleeves to length for mounting flush with both surfaces of walls.

Page 117: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Raceways and Boxes SECTION 16130

MEINHARDT PHILIPPINES INC. Page 9 of 9 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16130-Raceways and Boxes.doc

G. Extend sleeves installed in floors 50 mm above finished floor level.

H. Size pipe sleeves to provide 6.4-mm annular clear space between sleeve and raceway unless sleeve seal is to be installed or unless seismic criteria require different clearance.

I. Seal space outside of sleeves with grout for penetrations of concrete and masonry and with approved joint compound for gypsum board assemblies.

J. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and raceway, using joint sealant appropriate for size, depth, and location of joint. Refer to Division 7 Section 079200 "Joint Sealants" for materials and installation.

K. Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at raceway penetrations. Install sleeves and seal with firestop materials. Comply with Division 7 Section 078413 "Penetration Firestopping."

L. Roof-Penetration Sleeves: Seal penetration of individual raceways with flexible, boot-type flashing units applied in coordination with roofing work.

M. Aboveground, Exterior-Wall Penetrations: Seal penetrations using sleeves and mechanical sleeve seals. Select sleeve size to allow for 25-mm annular clear space between pipe and sleeve for installing mechanical sleeve seals.

N. Underground, Exterior-Wall Penetrations: Install cast-iron "wall pipes" for sleeves. Size sleeves to allow for 25-mm annular clear space between raceway and sleeve for installing mechanical sleeve seals.

3.4 SLEEVE-SEAL INSTALLATION

A. Install to seal underground, exterior wall penetrations.

B. Use type and number of sealing elements recommended by manufacturer for raceway material and size. Position raceway in center of sleeve. Assemble mechanical sleeve seals and install in annular space between raceway and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.

3.5 FIRESTOPPING

A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly. Firestopping materials and installation requirements are specified in Division 7 Section 078413 "Penetration Firestopping"

3.6 PROTECTION

A. Provide final protection and maintain conditions that ensure coatings, finishes, and cabinets are without damage or deterioration at time of Substantial Completion.

1. Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer.

2. Repair damage to PVC or paint finishes with matching touchup coating recommended by manufacturer.

END OF SECTION

Page 118: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Wiring Devices SECTION 16140

MEINHARDT PHILIPPINES, INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16140-Wiring Devices.doc/AGR/ms

PART 1 – GENERAL ........................................................................................................................ 1

1.1 DESCRIPTION ........................................................................................................................ 1 1.2 QUALITY ASSURANCE ............................................................................................................. 1 1.3 STANDARDS .......................................................................................................................... 1 1.4 SUBMITTALS .......................................................................................................................... 1 1.5 COLORS ............................................................................................................................... 1

PART 2 – PRODUCTS ...................................................................................................................... 2

2.1 ACCEPTABLE MANUFACTURERS .............................................................................................. 2 2.2 SWITCHES............................................................................................................................. 2 2.3 RECEPTACLES ....................................................................................................................... 3 2.4 WALL DIMMERS ..................................................................................................................... 4 2.5 OCCUPANCY SENSORS ........................................................................................................... 4 2.6 FLOOR BOXES AND FITTINGS .................................................................................................. 4 2.7 PLUGSTRIP ........................................................................................................................... 5 2.8 COVERPLATES ....................................................................................................................... 5 2.9 MISCELLANEOUS DEVICES ...................................................................................................... 5

PART 3 – EXECUTION ..................................................................................................................... 6

3.1 GENERAL .............................................................................................................................. 6

Page 119: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Wiring Devices SECTION 16140

MEINHARDT PHILIPPINES, INC. Page 1 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16140-Wiring Devices.doc

SECTION 16140 WIRING DEVICES

PART 1 – GENERAL

1.1 DESCRIPTION

A. Provide wiring devices in accordance with the Contract Documents.

1.2 QUALITY ASSURANCE

A. Switches and receptacles shall be of the same manufacturer. B. Occupancy sensors shall be certified for operation with specific ballasts utilized in

controlled lighting fixtures. C. Occupancy sensors shall have a three years warranty.

1.3 STANDARDS

A. PS

B. PEC (Latest Edition)

C. Switches and Receptacles: NEMA WD-1, and UL 498.

D. Ground Fault Interrupter Receptacles: UL 943 Class A.

E. Wall Dimmers: ANSI C62.41, UL 20.

1.4 SUBMITTALS

A. Manufacturer's product data sheets indicating electrical ratings, dimensions, mounting

details, construction materials, grade, and termination information. B. Sample for each wiring device and cover plate.

1.5 COLORS

A. Device and coverplate colors shall be as selected by Architect. B. Switches and receptacles connected to the UPS power system shall be red. C. Isolated ground receptacles shall be orange.

Page 120: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Wiring Devices SECTION 16140

MEINHARDT PHILIPPINES, INC. Page 2 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16140-Wiring Devices.doc

PART 2 – PRODUCTS

2.1 ACCEPTABLE MANUFACTURERS

A. Hubbell B. Pass & Saymoure

C. Legrand

2.2 SWITCHES

A. General:

1. Switches shall be of the type indicated on the Drawings. 2. Switches shall be commercial specification grade, 10A, 220V, back and side

wired, silent handle operation. 3. Switches installed in hazardous areas shall be explosion proof type in

accordance with the NEC and as shown on the drawings. 4. The switches shall be mounted on the striker plate side of doors.

B. Lighting Switches: 1. Rocker handle type:

a. Single pole b. Double pole c. Three pole d. 3 way e. 4 way

C. Illuminated Handle Switches: 1. Rocker handle type: a. Single pole. b. 3 way. D. Transfer Fan Switches: 1. Rocker handle type, single pole: Coverplate engraved FAN. E. Momentary Contact Switches: 1. Rocker handle type, center off. F. Pilot Light Switches: 1. Rocker handle type, single pole, neon pilot light. G. Key Switches: 1. Single pole. H. Weatherproof Switches: 1. Weatherproof handle/coverplate.

Page 121: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Wiring Devices SECTION 16140

MEINHARDT PHILIPPINES, INC. Page 3 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16140-Wiring Devices.doc

I. Spring Wound Timer Switches: 1. 30 minute maximum time cycle.

2.3 RECEPTACLES

A. General: 1. Receptacles shall be of the type indicated on the Drawings. 2. Receptacles shall be hospital grade (green dot identification), 220V,

grounding type. Receptacle type which have no listing as hospital grade but are listed by UL in their respective categories or receptacles indicated on the drawings as “not hospital grade”.

3. Receptacles shall have provisions for back wiring with separate metal clamp type terminals (four min.) and side wiring from four captively held binding screws.

B. Receptacles: 1. Single: 15A, 2-pole, 3-wire 2. Duplex: rating same as above.

3. Not hospital grade receptacles: rating same as above. 4. Configuration: 110 volts - NEMA 5-15R

220 volts - NEMA 6-15R C. Isolated Ground Receptacles: 1. Single: 15A, 2-pole, 3-wire 2. Duplex: rating same as above

3. Bodies shall be orange in color. 4. Shall be hospital grade and UL listed as “Isolated Ground”. 5. Configurations same as Item B.4.

D. Isolated Ground Surge Suppressor Receptacles: 1. Single: 15A 2. Duplex: 15A

3. Configurations same as item B.4. E. Ground Fault Interrupter Receptacles:

1. Single: 15A, 2-pole, 3-wire 2. Duplex: rating same as above 3. Shall be hospital grade and consist of a differential current transformer, solid

state sensing circuitry and a circuit interrupter switch. Device shall have nominal sensitivity to ground leakage current of 5mA and shall function to interrupt the current supply for any value of the device. Device shall have a minimum nominal tripping time of 1/30th of a second.

4. Configurations same as Item B.4. F. Receptacles 20, 30, and 50 Amperes, 250-volt:

1. Shall be complete with appropriate cord grip plug. G. Clock Receptacles: 1. Single: 15A

Page 122: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Wiring Devices SECTION 16140

MEINHARDT PHILIPPINES, INC. Page 4 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16140-Wiring Devices.doc

H. Weatherproof Receptacles: 1. Duplex: 15A

2. Mounted in a box with a gasketed, weatherproof, cast metal cover plate plate and cap over each receptacle opening. The cap shall be permanently attached to the cover plate by a spring hinged flap. The weatherproof integrity shall not be affected when heavy duty specification or hospital grade attachment plug caps are inserted. Cover plates on outlet boxes mounted flush in the wall shall be gasketed to the wall in a watertight manner.

2.4 WALL DIMMERS

A. Wall dimmers shall be suitable for control of the load type (incandescent, low voltage,

or fluorescent), load capacity, and branch circuit voltage of the lighting fixtures controlled.

B. Thin profile, linear slide to off control, power failure memory, front accessible service switch.

2.5 OCCUPANCY SENSORS

A. Occupancy sensors shall be suitable for control of the load type (incandescent, low

voltage, or fluorescent), load capacity, and branch circuit voltage of the lighting fixtures controlled.

B. Ultrasonic or passive infrared type, user adjustable time delay and sensitivity settings. C. Wall Switch: 1. Manual ON, manual OFF control switches. 2. Bypass override ON switch in the event of product failure. 3. 220V operation. D. Ceiling Mounted: 1. One way type. 2. Two way type. 3. Corridor type. E. Switchpacks: 1. Provide switchpacks as required for circuiting and control as shown. 2. 220V operation. 3. Isolated 15A contacts.

2.6 FLOOR BOXES AND FITTINGS

A. General:

1. Provide floor boxes and fittings of the types, ratings, and configurations as shown on the Drawings.

2. Floor boxes and fittings shall be suitable for the fire rating and thickness of the floor.

3. Combination power/telecom outlets shall have barrier to separate power and telecom wiring.

B. Poke Through Pedestal Floor Box:

Page 123: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Wiring Devices SECTION 16140

MEINHARDT PHILIPPINES, INC. Page 5 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16140-Wiring Devices.doc

1. Fire rated insert, junction box, and service fitting. Service fittings shall be diecast aluminum, satin finish.

2. Single receptacle outlet, 220V, 15A. 3. Duplex receptacle outlet, 220V, 15A. 4. Double duplex receptacle outlet, 220V, 15A. 5. Special purpose receptacle outlet: Poke through, outlet type as indicated on

the Drawings. 6. Combination duplex receptacle/telecom outlet, 220V, 15A: Poke through

fitting with grommeted hole and 2 factory installed telecom modular jacks (coordinate modular jack types with Owner).

7. Combination double duplex receptacle/telecom outlet, 220V, 15A: Poke through fitting with grommeted hole and 2 factory installed telecom modular jacks (coordinate modular jack types with Owner).

8. Telecom outlet: Grommeted hole and 2 factory installed telecom modular jacks (coordinate modular jack types with Owner).

C. Poke Through Flush Floor Box: 1. Fire rated insert, junction box, and service fitting. Combination power/telecom

outlets shall have barrier to separate power and telecom wiring. Carpet flange shall be diecast aluminum, painted or plated finish as selected by Architect.

2. Combination duplex receptacle/telecom outlet, 220V, 15A. D. Recessed Flush Floor Box: 1. Cast iron box, multiple gang, shallow depth, brass carpet flange and

coverplates.

2.7 PLUGSTRIP

A. Provide metallic plug strip suitable for the branch circuiting and in the length as shown

on the Drawings. B. Plugstrip shall be grounding type, painted color as selected by Architect. C. Power type: 1. Single compartment surface metal raceway with removable cover. 2. Single receptacle outlets mounted on 30 cm centers. D. Power/Telecom type: 1. Two compartment surface metal raceway with internal divider and removable

cover. 2. Duplex receptacle outlets and telecom fittings mounted on 30 cm centers.

2.8 COVERPLATES

A. Provide thermoplastic coverplates for wiring devices. Provide multiple gang

coverplates where multiple devices are installed in a common location. B. Standard NEMA design, so that products of different manufacturers can be

interchangeable. C. In psychiatric areas, wall plates shall have tamperproof screws and beveled edgaes.

2.9 MISCELLANEOUS DEVICES

A. Pushbutton

Page 124: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Wiring Devices SECTION 16140

MEINHARDT PHILIPPINES, INC. Page 6 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16140-Wiring Devices.doc

B. Buzzer C. Bell

PART 3 – EXECUTION

3.1 GENERAL

A. General: 1. Verify the exact location of wiring devices with Architect. 2. Devices mounted above counters shall be 5 cm above the top of the

backsplash to the bottom of the coverplate. 3. Provide an individual grounding conductor from the device grounding terminal

to the panelboard ground bus. 4. Switches that control devices that are connected to the emergency power

system shall be the illuminated handle type. B. Switches: 1. Mount switches vertically with the ON position on top. 2. Mount switches on the strike side of doors. C. Receptacles: 1. Mount receptacles vertically with the grounding pin on bottom. D. Occupancy Sensors: 1. In addition to occupancy sensors shown on the Drawings, provide additional

occupancy to ensure complete room coverage in accordance with manufacturer's coverage and orientation requirements.

2. Provide occupancy sensors with minimum and maximum load specifications appropriate to the load controlled.

E. Plugstrip: 1. Provide a 20 mm empty conduit home run to the nearest telecommunications

terminal board for each 3.5 linear meters of telecommunications plug strip. F. Coverplates: 1. Install device plates in full contact with wall surface. Plates shall not project

out from the wall. 2. Coverplates for multiple gang wall dimmers shall be continuous flush type

tailored to match wall dimmer physical dimensions. 3. Provide stainless steel, smooth face coverplates in equipment rooms.

Provide thermoplastic, smooth face coverplates in all other spaces. 4. Color of cover plates should be referred to Architect for approval.

END OF SECTION

Page 125: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control Devices SECTION 16145

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16145-Lighting Control Devices.doc

PART 1 - GENERAL ..................................................................................................................... 1

1.1 RELATED DOCUMENTS ...................................................................................................... 1 1.2 SUMMARY ........................................................................................................................ 1 1.3 DEFINITIONS .................................................................................................................... 1 1.4 SUBMITTALS .................................................................................................................... 1 1.5 QUALITY ASSURANCE ....................................................................................................... 1 1.6 COORDINATION ................................................................................................................ 2

PART 2 - PRODUCTS ................................................................................................................... 2

2.1 TIME SWITCHES ............................................................................................................... 2 2.2 OUTDOOR PHOTOELECTRIC SWITCHES ............................................................................... 2 2.3 INDOOR PHOTOELECTRIC SWITCHES .................................................................................. 2 2.4 INDOOR OCCUPANCY SENSORS ......................................................................................... 3 2.5 INDOOR MOTION SENSOR (PIR) ......................................................................................... 4 2.6 CONDUCTORS AND CABLES ............................................................................................... 5

PART 3 - EXECUTION .................................................................................................................. 5

3.1 SENSOR INSTALLATION ..................................................................................................... 5 3.2 CONTACTOR INSTALLATION ............................................................................................... 5 3.3 WIRING INSTALLATION....................................................................................................... 5 3.4 IDENTIFICATION ................................................................................................................ 6 3.5 FIELD QUALITY CONTROL .................................................................................................. 6 3.6 ADJUSTING ...................................................................................................................... 6 3.7 DEMONSTRATION ............................................................................................................. 6 3.8 COMMISSIONING ............................................................................................................... 6

Page 126: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control Devices SECTION 16145

MEINHARDT PHILIPPINES INC. Page 1 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16145-Lighting Control Devices.doc

SECTION 16145 LIGHTING CONTROL DEVICES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

B. Division 16 will be responsible to carry out the commissioning requirements specified in Sections 17100, 17106, 117107, 17109, 17110 and other sections referenced in 17100. These include, but are not limited to, commissioning, enhanced commissioning, preparation of a detailed O&M manual, and detailed training of the EMPLOYER’S personnel.

1.2 SUMMARY

A. This Section includes the following lighting control devices:

1. Time switches. 2. Indoor photoelectric switches. 3. Indoor occupancy sensors. 4. Lighting contactors.

1.3 DEFINITIONS

A. LED: Light-emitting diode.

B. PIR: Passive infrared.

1.4 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Shop Drawings: Show installation details for occupancy and light-level sensors.

1. Interconnection diagrams showing field-installed wiring.

C. Field quality-control test reports.

D. Operation and Maintenance Data: For each type of product to include in emergency, operation, and maintenance manuals.

1.5 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

Page 127: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control Devices SECTION 16145

MEINHARDT PHILIPPINES INC. Page 2 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16145-Lighting Control Devices.doc

1.6 COORDINATION

A. Coordinate layout and installation of ceiling-mounted devices with other construction that penetrates ceilings or is supported by them, including light fixtures, HVAC equipment, smoke detectors, fire-suppression system, and partition assemblies.

PART 2 - PRODUCTS

2.1 TIME SWITCHES

A. Acceptable Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. Electronic Time Switches: Electronic, solid-state programmable units with alphanumeric display; complying with UL 917.

1. Contact Configuration: SPST. 2. Contact Rating: 20-A ballast load, 240-V ac. 3. Program: 8 on-off set points on a 24-hour schedule and an annual holiday schedule

that overrides the weekly operation on holidays. 4. Battery Backup: For schedules and time clock.

2.2 OUTDOOR PHOTOELECTRIC SWITCHES

A. Acceptable Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. Description: Solid state, with SPST dry contacts rated for 1800-VA tungsten or 1000-VA inductive, to operate connected relay, contactor coils, or microprocessor input; complying with UL 773A.

1. Light-Level Monitoring Range: 1.5 to 10 fc (16.14 to 108 lx), with an adjustment for turn-on and turn-off levels within that range, and a directional lens in front of photocell to prevent fixed light sources from causing turn-off.

2. Time Delay: 15-second minimum, to prevent false operation. 3. Surge Protection: Metal-oxide varistor, complying with IEEE C62.41.1,

IEEE C62.41.2, and IEEE 62.45 for Category A1 locations. 4. Mounting: Twist lock complying with IEEE C136.10, with base-and-stem mounting or

stem-and-swivel mounting accessories as required to direct sensor to the north sky exposure.

C. Description: Solid state, with SPST dry contacts rated for 1800 VA to operate connected load, relay, or contactor coils; complying with UL 773.

1. Light-Level Monitoring Range: 1.5 to 10 fc (16.14 to 108 lx), with an adjustment for turn-on and turn-off levels within that range.

2. Time Delay: 30-second minimum, to prevent false operation. 3. Lightning Arrester: Air-gap type. 4. Mounting: Twist lock complying with IEEE C136.10, with base.

2.3 INDOOR PHOTOELECTRIC SWITCHES

A. Acceptable Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. Ceiling-Mounted Photoelectric Switch: Solid-state, light-level sensor unit, with separate relay unit mounted on luminaire, to detect changes in lighting levels that are perceived by the eye. Cadmium sulfide photoresistors are not acceptable.

Page 128: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control Devices SECTION 16145

MEINHARDT PHILIPPINES INC. Page 3 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16145-Lighting Control Devices.doc

1. Sensor Output: Contacts rated to operate the associated relay, complying with UL 773A. Sensor shall be powered from the relay unit.

2. Relay Unit: Dry contacts rated for 20-A ballast load at 120- and 220-V ac, for 13-A tungsten at 120-V ac, and for 1 hp at 120-V ac. Power supply to sensor shall be 24-V dc, 150-mA, Class 2 power source as defined by PEC.

3. Light-Level Monitoring Range: [10 to 200 fc (108 to 2152 lx)] [100 to 1000 fc (1080 to 10 800 lx)], with an adjustment for turn-on and turn-off levels within that range.

4. Time Delay: Adjustable from 5 to 300 seconds to prevent cycling, with deadband adjustment.

5. Indicator: Two LEDs to indicate the beginning of on-off cycles.

C. Skylight Photoelectric Sensors: Solid-state, light-level sensor; housed in a threaded, plastic fitting for mounting under skylight, facing up at skylight; with separate relay unit mounted on luminaire, to detect changes in lighting levels that are perceived by the eye. Cadmium sulfide photoresistors are not acceptable.

1. Sensor Output: Contacts rated to operate the associated relay, complying with UL 773A. Sensor shall be powered from the relay unit.

2. Relay Unit: Dry contacts rated for 20-A ballast load at 120- and 220-V ac, for 13-A tungsten at 220-V ac, and for 1hp at 120-V ac. Power supply to sensor shall be 24-V dc, 150-mA, Class 2 power source as defined by PEC.

3. Light-Level Monitoring Range: 1000 to 10,000 fc (10 800 to 108 000 lx), with an adjustment for turn-on and turn-off levels within that range.

4. Time Delay: Adjustable from 5 to 300 seconds to prevent cycling, with deadband adjustment.

5. Indicator: Two LEDs to indicate the beginning of on-off cycles.

2.4 INDOOR OCCUPANCY SENSORS

A. Acceptable Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. General Description: Wall- or ceiling-mounting, solid-state units with a separate relay unit.

1. Operation: Unless otherwise indicated, turn lights on when covered area is occupied and off when unoccupied; with a time delay for turning lights off, adjustable over a minimum range of 1 to 15 minutes.

2. Sensor Output: Contacts rated to operate the connected relay, complying with UL 773A. Sensor shall be powered from the relay unit.

3. Relay Unit: Dry contacts rated for 20-A ballast load at 220V ac, for 13-A tungsten at 220-V ac, and for 1 hp at 220-V ac. Power supply to sensor shall be 24-V dc, 150-mA, Class 2 power source as defined by PEC.

4. Mounting:

a. Sensor: Suitable for mounting in any position on a standard outlet box. b. Relay: Externally mounted through a 1/2-inch (13-mm) knockout in a standard

electrical enclosure. c. Time-Delay and Sensitivity Adjustments: Recessed and concealed behind

hinged door.

5. Indicator: LED, to show when motion is being detected during testing and normal operation of the sensor.

6. Bypass Switch: Override the on function in case of sensor failure. 7. Automatic Light-Level Sensor: Adjustable from 2 to 200 fc (21.5 to 2152 lx); keep

lighting off when selected lighting level is present.

C. PIR Type: Ceiling mounting; detect occupancy by sensing a combination of heat and movement in area of coverage.

Page 129: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control Devices SECTION 16145

MEINHARDT PHILIPPINES INC. Page 4 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16145-Lighting Control Devices.doc

1. Detector Sensitivity: Detect occurrences of 6-inch- (150-mm-) minimum movement of any portion of a human body that presents a target of not less than 36 sq. in. (232 sq. cm).

2. Detection Coverage (Room): Detect occupancy anywhere in a circular area of 1000 sq. ft. (93 sq. m) when mounted on a 96-inch- (2440-mm-) high ceiling.

3. Detection Coverage (Corridor): Detect occupancy within 90 feet (27.4 m) when mounted on a 10-foot- (3-m-) high ceiling.

D. Ultrasonic Type: Ceiling mounting; detect occupancy by sensing a change in pattern of reflected ultrasonic energy in area of coverage.

1. Detector Sensitivity: Detect a person of average size and weight moving not less than 12 inches (305 mm) in either a horizontal or a vertical manner at an approximate speed of 12 inches/s (305 mm/s).

2. Detection Coverage (Small Room): Detect occupancy anywhere within a circular area of 600 sq. ft. (56 sq. m) when mounted on a 96-inch- (2440-mm-) high ceiling.

3. Detection Coverage (Standard Room): Detect occupancy anywhere within a circular area of 1000 sq. ft. (93 sq. m) when mounted on a 96-inch- (2440-mm-) high ceiling.

4. Detection Coverage (Large Room): Detect occupancy anywhere within a circular area of 2000 sq. ft. (186 sq. m) when mounted on a 96-inch- (2440-mm-) high ceiling.

5. Detection Coverage (Corridor): Detect occupancy anywhere within 90 feet (27.4 m) when mounted on a 10-foot- (3-m-) high ceiling in a corridor not wider than 14 feet (4.3 m).

E. Dual-Technology Type: Ceiling mounting; detect occupancy by using a combination of PIR and ultrasonic detection methods in area of coverage. Particular technology or combination of technologies that controls on-off functions shall be selectable in the field by operating controls on unit.

1. Sensitivity Adjustment: Separate for each sensing technology. 2. Detector Sensitivity: Detect occurrences of 6-inch- (150-mm-) minimum movement of

any portion of a human body that presents a target of not less than 36 sq. in. (232 sq. cm), and detect a person of average size and weight moving not less than 12 inches (305 mm) in either a horizontal or a vertical manner at an approximate speed of 12 inches/s (305 mm/s).

3. Detection Coverage (Standard Room): Detect occupancy anywhere within a circular area of 1000 sq. ft. (93 sq. m) when mounted on a 96-inch- (2440-mm-) high ceiling.

2.5 INDOOR MOTION SENSOR (PIR)

A. Acceptable Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. Performance Requirements: Suitable for operation in ambient temperatures ranging from minus 40 to plus 130 deg F (minus 40 to plus 54 deg C), rated as raintight according to UL 773A.

1. Operation: Turn lights on when sensing infrared energy changes between background and moving body in area of coverage; with a time delay for turning lights off, adjustable over a minimum range of 1 to 15 minutes.

2. Mounting:

a. Sensor: Suitable for mounting in any position on a standard outdoor junction box.

b. Relay: Internally mounted in a standard weatherproof electrical enclosure. c. Time-Delay and Sensitivity Adjustments: Recessed and concealed behind

hinged door.

3. Bypass Switch: Override the on function in case of sensor failure.

Page 130: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control Devices SECTION 16145

MEINHARDT PHILIPPINES INC. Page 5 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16145-Lighting Control Devices.doc

4. Automatic Light-Level Sensor: Adjustable from 1 to 20 fc (11 to 215 lx); keep lighting off during daylight hours.

C. Detector Sensitivity: Detect occurrences of 6-inch- (150-mm-) minimum movement of any portion of a human body that presents a target of not less than 36 sq. in. (232 sq. cm).

D. Detection Coverage: Up to 35 feet (11 m), with a field of view of 360.

E. Lighting Fixture Mounted Sensor: Suitable for switching 300 W of tungsten load at 220-V ac.

F. Individually Mounted Sensor: Contacts rated to operate the connected relay, complying with UL 773A. Sensor shall be powered from the relay unit.

1. Relay Unit: Dry contacts rated for 20-A ballast load at 220-V ac, for 13-A tungsten at 220-V ac, and for 1 hp at 220-V ac. Power supply to sensor shall be 24-V dc, 150-mA, Class 2 power source as defined by PEC.

2. Indicator: LED, to show when motion is being detected during testing and normal operation of the sensor.

2.6 CONDUCTORS AND CABLES

A. Power Wiring to Supply Side of Remote-Control Power Sources: Not smaller than No. 12 AWG. Comply with requirements in Division 16 Section 16120 "Conductors and Cables."

B. Classes 2 and 3 Control Cable: Multiconductor cable with stranded-copper conductors not smaller than No. 18 AWG. Comply with requirements in Division 16 Section 16120 "Conductors and Cables."

C. Class 1 Control Cable: Multiconductor cable with stranded-copper conductors not smaller than No. 14 AWG. Comply with requirements in Division 16 Section 16120 "Conductors and Cables."

PART 3 - EXECUTION

3.1 SENSOR INSTALLATION

A. Install and aim sensors in locations to achieve not less than 90 percent coverage of areas indicated. Do not exceed coverage limits specified in manufacturer's written instructions.

3.2 CONTACTOR INSTALLATION

A. Mount electrically held lighting contactors with elastomeric isolator pads, to eliminate structure-borne vibration, unless contactors are installed in an enclosure with factory-installed vibration isolators.

3.3 WIRING INSTALLATION

A. Wiring Method: Comply with Division 16 Section 16120 "Conductors and Cables." Minimum conduit size shall be 1/2 inch (13 mm).

B. Wiring within Enclosures: Comply with NECA 1. Separate power-limited and nonpower-limited conductors according to conductor manufacturer's written instructions.

Page 131: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control Devices SECTION 16145

MEINHARDT PHILIPPINES INC. Page 6 of 6 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16145-Lighting Control Devices.doc

C. Size conductors according to lighting control device manufacturer's written instructions, unless otherwise indicated.

D. Splices, Taps, and Terminations: Make connections only on numbered terminal strips in junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures.

3.4 IDENTIFICATION

A. Identify components and power and control wiring according to Division 16 Section "Electrical Identification."

1. Identify controlled circuits in lighting contactors. 2. Identify circuits or luminaries controlled by photoelectric and occupancy sensors at

each sensor.

B. Label time switches and contactors with a unique designation.

3.5 FIELD QUALITY CONTROL

A. Perform the following field tests and inspections and prepare test reports:

1. After installing time switches and sensors, and after electrical circuitry has been energized, adjust and test for compliance with requirements.

2. Operational Test: Verify operation of each lighting control device, and adjust time delays.

B. Lighting control devices that fail tests and inspections are defective work.

3.6 ADJUSTING

A. Occupancy Adjustments: When requested within 12 months of date of Substantial Completion, provide on-site assistance in adjusting sensors to suit occupied conditions. Provide up to two visits to Project during other-than-normal occupancy hours for this purpose.

3.7 DEMONSTRATION

A. Coordinate demonstration of products specified in this Section with demonstration requirements for low-voltage, programmable lighting control system specified in Division 13 Section "Lighting Controls." Refer to Section 17100 “Commissioning.”

B. Engage a factory-authorized service representative to train EMPLOYER’S maintenance personnel to adjust, operate, and maintain lighting control devices. Refer to detailed scope matrix of the tender documents and to Section 17100 “Commissioning.”

3.8 COMMISSIONING

A. Refer to Section 17100 “Commissioning” for commissioning requirements.

END OF SECTION

Page 132: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

PART 1 - GENERAL................................................................................................................................ 1

1.1 RELATED DOCUMENTS ............................................................................................................ 1 1.2 SUMMARY ............................................................................................................................. 1 1.3 DEFINITIONS .......................................................................................................................... 1 1.4 SUBMITTALS .......................................................................................................................... 1 1.5 QUALITY ASSURANCE ............................................................................................................. 3 1.6 PROJECT CONDITIONS ............................................................................................................ 4 1.7 COORDINATION ...................................................................................................................... 4 1.8 WARRANTY ........................................................................................................................... 4 1.9 MAINTENANCE SERVICE .......................................................................................................... 4 1.10 EXTRA MATERIALS.................................................................................................................. 4

PART 2 - PRODUCTS.............................................................................................................................. 4

2.1 MANUFACTURERS .................................................................................................................. 4 2.2 ENGINE-GENERATOR SET ........................................................................................................ 5 2.3 ENGINE ................................................................................................................................. 5 2.4 FUEL OIL STORAGE ................................................................................................................. 7 2.5 CONTROL AND MONITORING .................................................................................................... 8 2.6 GENERATOR OVERCURRENT AND FAULT PROTECTION ................................................................ 9 2.7 GENERATOR, EXCITER, AND VOLTAGE REGULATOR .................................................................. 10 2.8 MOTORS ............................................................................................................................. 11 2.9 VIBRATION ISOLATION DEVICES .............................................................................................. 11 2.10 FINISHES ............................................................................................................................ 11 2.11 SOURCE QUALITY CONTROL .................................................................................................. 11

PART 3 - EXECUTION ........................................................................................................................... 12

3.1 EXAMINATION ...................................................................................................................... 12 3.2 INSTALLATION...................................................................................................................... 12 3.3 CONNECTIONS ..................................................................................................................... 13 3.4 IDENTIFICATION ................................................................................................................... 13 3.5 FIELD QUALITY CONTROL ...................................................................................................... 13 3.6 DEMONSTRATION ................................................................................................................. 15

Page 133: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 1 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

SECTION 16231 PACKAGED ENGINE GENERATOR SYSTEM

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes packaged engine-generator sets for standby power supply with the following features:

1. Diesel engine. 2. Unit-mounted cooling system. 3. Unit-mounted [control and monitoring.

B. Related Sections include the following:

1. Division 16 Section "Transfer Switches" for transfer switches including sensors and relays to initiate automatic-starting and -stopping signals for engine-generator sets.

1.3 DEFINITIONS

A. Operational Bandwidth: The total variation from the lowest to highest value of a parameter over the range of conditions indicated, expressed as a percentage of the nominal value of the parameter.

1.4 SUBMITTALS

A. Product Data: For each type of packaged engine generator indicated. Include rated capacities, operating characteristics, and furnished specialties and accessories. In addition, include the following:

1. Thermal damage curve for generator. 2. Time-current characteristic curves for generator protective device.

Page 134: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 2 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

1. Dimensioned outline plan and elevation drawings of engine-generator set and other components specified.

2. Design Calculations: Signed and sealed by a qualified professional engineer. Calculate requirements for selecting vibration isolators and seismic restraints and for designing vibration isolation bases.

3. Vibration Isolation Base Details: Signed and sealed by a qualified professional engineer. Detail fabrication, including anchorages and attachments to structure and to supported equipment. Include base weights.

4. Wiring Diagrams: Power, signal, and control wiring.

C. Manufacturer Seismic Qualification Certification: Submit certification that day tank, engine-generator set, batteries, battery racks, accessories, and components will withstand seismic forces defined in Division 16 Section "Electrical Supports and Seismic Restraints." Include the following:

1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.

a. The term "withstand" means "the unit will remain in place without separation of any

parts from the device when subjected to the seismic forces specified and the unit will be fully operational after the seismic event."

2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.

3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.

D. Qualification Data: For installer manufacturer and testing agency.

E. Source quality-control test reports.

1. Certified summary of prototype-unit test report. 2. Certified Test Reports: For components and accessories that are equivalent, but not

identical, to those tested on prototype unit. 3. Certified Summary of Performance Tests: Certify compliance with specified requirement

to meet performance criteria for sensitive loads. 4. Report of factory test on units to be shipped for this Project, showing evidence of

compliance with specified requirements. 5. Report of sound generation. 6. Report of exhaust emissions showing compliance with applicable regulations. 7. Certified Torsional Vibration Compatibility: Comply with NFPA 110.

F. Field quality-control test reports.

G. Operation and Maintenance Data: For packaged engine generators to include in emergency, operation, and maintenance manuals. In addition to items specified in Division 1 Section "Operation and Maintenance Data," include the following:

Page 135: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 3 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

1. List of tools and replacement items recommended to be stored at Project for ready access. Include part and drawing numbers, current unit prices, and source of supply.

H. Warranty: Special warranty specified in this Section.

1.5 QUALITY ASSURANCE

A. Installer Qualifications: Manufacturer's authorized representative who is trained and approved for installation of units required for this Project.

1. Maintenance Proximity: Not more than two hours' normal travel time from Installer's place of business to Project site.

2. Engineering Responsibility: Preparation of data for vibration isolators and seismic restraints of engine skid mounts, including Shop Drawings, based on testing and engineering analysis of manufacturer's standard units in assemblies similar to those indicated for this Project.

B. Manufacturer Qualifications: A qualified manufacturer. Maintain, within 100km of Project site, a service center capable of providing training, parts, and emergency maintenance repairs.

C. Testing Agency Qualifications: An independent agency, with the experience and capability to conduct the testing indicated, that is a member company of the InterNational Electrical Testing Association or is a nationally recognized testing laboratory (NRTL), and that is acceptable to authorities having jurisdiction.

1. Testing Agency's Field Supervisor: Person currently certified by the InterNational Electrical Testing Association or the National Institute for Certification in Engineering Technologies to supervise on-site testing specified in Part 3.

D. Source Limitations: Obtain packaged generator sets and auxiliary components through one source from a single manufacturer.

E. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

F. Comply with ASME B15.1.

G. Comply with NFPA 37.

H. Comply with NFPA 70.

I. Comply with NFPA 99.

J. Comply with NFPA 110 requirements for Level 2 emergency power supply system.

K. Comply with UL 2200.

L. Engine Exhaust Emissions: Comply with applicable state and local government requirements.

M. Noise Emission: Comply with applicable local government requirements for maximum noise level at adjacent property boundaries due to sound emitted by generator set including engine, engine exhaust, engine cooling-air intake and discharge, and other components of installation.

Page 136: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 4 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

1.6 PROJECT CONDITIONS

A. Environmental Conditions: Engine-generator system shall withstand the following environmental conditions without mechanical or electrical damage or degradation of performance capability:

1. Ambient Temperature: 20 to 40 deg C. 2. Relative Humidity: 0 to 99 percent. 3. Altitude: Sea level to 20.7m.

1.7 COORDINATION

A. Coordinate size and location of concrete bases for package engine generators. Cast anchor-bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in Division 3.

1.8 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of packaged engine generators and associated auxiliary components that fail in materials or workmanship within specified warranty period.

1. Warranty Period: One year from date of Substantial Completion.

1.9 MAINTENANCE SERVICE

A. Initial Maintenance Service: Beginning at Substantial Completion, provide [months' full maintenance by skilled employees of manufacturer's designated service organization. Include quarterly exercising to check for proper starting, load transfer, and running under load. Include routine preventive maintenance as recommended by manufacturer and adjusting as required for proper operation. Provide parts and supplies same as those used in the manufacture and installation of original equipment.

1.10 EXTRA MATERIALS

A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Fuses: One for every 10 of each type and rating, but no fewer than one of each. 2. Indicator Lamps: Two for every six of each type used, but no fewer than two of each. 3. Filters: One set each of lubricating oil, fuel, and combustion-air filters.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Acceptable Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers.”

Page 137: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 5 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

2.2 ENGINE-GENERATOR SET

A. Factory-assembled and -tested, engine-generator set.

B. Mounting Frame: Maintain alignment of mounted components without depending on concrete foundation; and have lifting attachments.

1. Rigging Diagram: Inscribed on metal plate permanently attached to mounting frame to indicate location and lifting capacity of each lifting attachment and generator-set center of gravity.

C. Capacities and Characteristics:

1. Power Output Ratings: 2 x 2500 kVA, 400 V, 60 Hz 2. Output Connections: Three-phase, four wire. 3. Nameplates: For each major system component to identify manufacturer's name and

address, and model and serial number of component.

D. Generator-Set Performance:

1. Steady-State Voltage Operational Bandwidth: 3 percent of rated output voltage from no load to full load.

2. Transient Voltage Performance: Not more than 20 percent variation for 50 percent step-load increase or decrease. Voltage shall recover and remain within the steady-state operating band within three seconds.

3. Steady-State Frequency Operational Bandwidth: 0.5 percent of rated frequency from no load to full load.

4. Steady-State Frequency Stability: When system is operating at any constant load within the rated load, there shall be no random speed variations outside the steady-state operational band and no hunting or surging of speed.

5. Transient Frequency Performance: Less than 5 percent variation for 50 percent step-load increase or decrease. Frequency shall recover and remain within the steady-state operating band within five seconds.

6. Output Waveform: At no load, harmonic content measured line to line or line to neutral shall not exceed 5 percent total and 3 percent for single harmonics. Telephone influence factor, determined according to NEMA MG 1, shall not exceed 50 percent.

7. Sustained Short-Circuit Current: For a 3-phase, bolted short circuit at system output terminals, system shall supply a minimum of 250 percent of rated full-load current for not less than 10 seconds and then clear the fault automatically, without damage to generator system components.

8. Start Time: Comply with NFPA 110, Type 10, system requirements.

2.3 ENGINE

A. Fuel: Fuel oil, Grade DF-2

B. Rated Engine Speed: 1800 rpm.

C. Maximum Piston Speed for Four-Cycle Engines: 2250 fpm (11.4 m/s).

D. Lubrication System: The following items are mounted on engine or skid:

1. Filter and Strainer: Rated to remove 90 percent of particles 5 micrometers and smaller while passing full flow.

Page 138: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 6 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

2. Thermostatic Control Valve: Control flow in system to maintain optimum oil temperature. Unit shall be capable of full flow and is designed to be fail-safe.

3. Crankcase Drain: Arranged for complete gravity drainage to an easily removable container with no disassembly and without use of pumps, siphons, special tools, or appliances.

E. Engine Fuel System:

1. Main Fuel Pump: Mounted on engine. Pump ensures adequate primary fuel flow under starting and load conditions.

2. Relief-Bypass Valve: Automatically regulates pressure in fuel line and returns excess fuel to source.

F. Coolant Jacket Heater: Electric-immersion type, factory installed in coolant jacket system. Comply with NFPA 110 requirements for Level 1 equipment for heater capacity.

G. Governor: Adjustable isochronous, with speed sensing.

H. Muffler/Silencer: Critical type, sized as recommended by engine manufacturer and selected with exhaust piping system to not exceed engine manufacturer's engine backpressure requirements.

1. Minimum sound attenuation of 25 dB at 500 Hz. 2. Sound level measured at a distance of 10 feet (3 m) from exhaust discharge after

installation is complete shall be 85 dBA or less.

I. Air-Intake Filter: Heavy-duty, engine-mounted air cleaner with replaceable dry-filter element and "blocked filter" indicator.

J. Starting System: 24-V electric, with negative ground.

1. Components: Sized so they will not be damaged during a full engine-cranking cycle with ambient temperature at maximum specified in Part 1 "Project Conditions" Article.

2. Cranking Motor: Heavy-duty unit that automatically engages and releases from engine flywheel without binding.

3. Cranking Cycle: As required by NFPA 110 for system level specified. 4. Battery: Adequate capacity within ambient temperature range specified in Part 1 "Project

Conditions" Article to provide specified cranking cycle at least three times without recharging.

5. Battery Cable: Size as recommended by engine manufacturer for cable length indicated. Include required interconnecting conductors and connection accessories.

6. Battery Compartment: Factory fabricated of metal with acid-resistant finish and thermal insulation. Thermostatically controlled heater shall be arranged to maintain battery above 10 deg C regardless of external ambient temperature within range specified in Part 1 "Project Conditions" Article. Include accessories required to support and fasten batteries in place.

7. Battery-Charging Alternator: Factory mounted on engine with solid-state voltage regulation and 35-A minimum continuous rating.

Page 139: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 7 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

8. Battery Charger: Current-limiting, automatic-equalizing and float-charging type. Unit shall comply with UL 1236 and include the following features:

a. Operation: Equalizing-charging rate of 10 A shall be initiated automatically after battery has lost charge until an adjustable equalizing voltage is achieved at battery terminals. Unit shall then be automatically switched to a lower float-charging mode and shall continue to operate in that mode until battery is discharged again.

b. Automatic Temperature Compensation: Adjust float and equalize voltages for variations in ambient temperature from minus 40 deg C to plus 60 deg C to prevent overcharging at high temperatures and undercharging at low temperatures.

c. Automatic Voltage Regulation: Maintain constant output voltage regardless of input voltage variations up to plus or minus 10 percent.

d. Ammeter and Voltmeter: Flush mounted in door. Meters shall indicate charging rates.

e. Safety Functions: Sense abnormally low battery voltage and close contacts providing low battery voltage indication on control and monitoring panel. Sense high battery voltage and loss of ac input or dc output of battery charger. Either condition shall close contacts that provide a battery-charger malfunction indication at system control and monitoring panel.

f. Enclosure and Mounting: NEMA 250, Type 1, wall-mounted cabinet.

2.4 FUEL OIL STORAGE

A. Comply with NFPA 30.

B. Day Tank: Comply with UL 142, freestanding, factory-fabricated fuel tank assembly, with integral, float-controlled transfer pump and the following features:

1. Containment: Integral rupture basin with a capacity of 150 percent of nominal capacity of day tank.

a. Leak Detector: Locate in rupture basin and connect to provide audible and visual alarm in the event of day-tank leak.

2. Tank Capacity: As indicated in the drawings (to provide 8 hours capacity). 3. Pump Capacity: Exceeds maximum flow of fuel drawn by engine-mounted fuel supply

pump at 110 percent of rated capacity, including fuel returned from engine. 4. Low-Level Alarm Sensor: Liquid-level device operates alarm contacts at 25 percent of

normal fuel level. 5. High-Level Alarm Sensor: Liquid-level device operates alarm and redundant fuel shutoff

contacts at midpoint between overflow level and 100 percent of normal fuel level. 6. Piping Connections: Factory-installed fuel supply and return lines from tank to engine;

local fuel fill, vent line, overflow line; and tank drain line with shutoff valve. 7. Redundant High-Level Fuel Shutoff: Actuated by high-level alarm sensor in day tank to

operate a separate motor device that disconnects day-tank pump motor. Sensor shall signal solenoid valve, located in fuel suction line between fuel storage tank and day tank, to close. Both actions shall remain in shutoff state until manually reset. Shutoff action shall initiate an alarm signal to control panel but shall not shut down engine-generator set.

Page 140: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 8 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

2.5 CONTROL AND MONITORING

A. Automatic Starting System Sequence of Operation: When mode-selector switch on the control and monitoring panel is in the automatic position, remote-control contacts in one or more separate automatic transfer switches initiate starting and stopping of generator set. When mode-selector switch is switched to the on position, generator set starts. The off position of same switch initiates generator-set shutdown. When generator set is running, specified system or equipment failures or derangements automatically shut down generator set and initiate alarms. Operation of a remote emergency-stop switch also shuts down generator set.

B. Manual Starting System Sequence of Operation: Switching on-off switch on the generator control panel to the on position starts generator set. The off position of same switch initiates generator-set shutdown. When generator set is running, specified system or equipment failures or derangements automatically shut down generator set and initiate alarms. Operation of a remote emergency-stop switch also shuts down generator set.

C. Configuration: Operating and safety indications, protective devices, basic system controls, and engine gages shall be grouped in a common control and monitoring panel mounted on the generator set. Mounting method shall isolate the control panel from generator-set vibration.

D. Configuration: Operating and safety indications, protective devices, basic system controls, and engine gages shall be grouped in a common wall-mounted control and monitoring panel.

E. Configuration: Operating and safety indications, protective devices, basic system controls, engine gages, instrument transformers, generator disconnect switch or circuit breaker, and other indicated components shall be grouped in a combination control and power panel. Control and monitoring section of panel shall be isolated from power sections by steel barriers. Panel features shall include the following:

1. Wall-Mounting Cabinet Construction: Rigid, self-supporting steel unit complying with NEMA ICS 6. Power bus shall be copper. Bus, bus supports, control wiring, and temperature rise shall comply with UL 891.

2. Switchboard Construction: Freestanding unit complying with Division 16 Section "Switchboards."

3. Switchgear Construction: Freestanding unit complying with Division 16 Section "Switchgear."

4. Current and Potential Transformers: Instrument accuracy class.

F. Indicating and Protective Devices and Controls: As required by NFPA 110 for Level 2 system, and the following:

1. AC voltmeter. 2. AC ammeter. 3. AC frequency meter. 4. DC voltmeter (alternator battery charging). 5. Engine-coolant temperature gage. 6. Engine lubricating-oil pressure gage. 7. Running-time meter. 8. Ammeter-voltmeter, phase-selector switch(es). 9. Generator-voltage adjusting rheostat. 10. Start-stop switch. 11. Overspeed shutdown device. 12. Coolant high-temperature shutdown device. 13. Coolant low-level shutdown device. 14. Oil low-pressure shutdown device.

Page 141: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 9 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

15. Fuel tank derangement alarm. 16. Fuel tank high-level shutdown of fuel supply alarm. 17. Generator overload.

G. Supporting Items: Include sensors, transducers, terminals, relays, and other devices and include wiring required to support specified items. Locate sensors and other supporting items on engine or generator, unless otherwise indicated.

H. Connection to Data Link: A separate terminal block, factory wired to Form C dry contacts, for each alarm and status indication is reserved for connections for data-link transmission of indications to remote data terminals. Data system connections to terminals are covered in Division 16 Section "Electrical Power Monitoring and Control."

I. Common Remote Audible Alarm: Comply with NFPA 110 requirements for Level 1 systems. Include necessary contacts and terminals in control and monitoring panel.

1. Overcrank shutdown. 2. Coolant low-temperature alarm. 3. Control switch not in auto position. 4. Battery-charger malfunction alarm. 5. Battery low-voltage alarm.

J. Common Remote Audible Alarm: Signal the occurrence of any events listed below without differentiating between event types. Connect so that after an alarm is silenced, clearing of initiating condition will reactivate alarm until silencing switch is reset.

1. Engine high-temperature shutdown. 2. Lube-oil, low-pressure shutdown. 3. Overspeed shutdown. 4. Remote emergency-stop shutdown. 5. Engine high-temperature prealarm. 6. Lube-oil, low-pressure prealarm. 7. Fuel tank, low-fuel level. 8. Low coolant level.

K. Remote Alarm Annunciator: Comply with NFPA 99. An LED labeled with proper alarm conditions shall identify each alarm event and a common audible signal shall sound for each alarm condition. Silencing switch in face of panel shall silence signal without altering visual indication. Connect so that after an alarm is silenced, clearing of initiating condition will reactivate alarm until silencing switch is reset. Cabinet and faceplate are surface- or flush-mounting type to suit mounting conditions indicated.

L. Remote Emergency-Stop Switch: Flush; wall mounted, unless otherwise indicated; and labeled. Push button shall be protected from accidental operation.

2.6 GENERATOR OVERCURRENT AND FAULT PROTECTION

A. Generator Circuit Breaker: Insulated-case, electronic-trip type; 100 percent rated; complying with UL 489.

1. Tripping Characteristics: Adjustable long-time and short-time delay and instantaneous. 2. Trip Settings: Selected to coordinate with generator thermal damage curve. 3. Shunt Trip: Connected to trip breaker when generator set is shut down by other

protective devices.

Page 142: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 10 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

4. Mounting: Adjacent to or integrated with control and monitoring panel.

B. Generator Disconnect Switch: Molded-case type, 100 percent rated.

1. Rating: Matched to generator output rating. 2. Shunt Trip: Connected to trip switch when signaled by generator protector or by other

protective devices.

C. Generator Protector: Microprocessor-based unit shall continuously monitor current level in each phase of generator output, integrate generator heating effect over time, and predict when thermal damage of alternator will occur. When signaled by generator protector or other generator-set protective devices, a shunt-trip device in the generator disconnect switch shall open the switch to disconnect the generator from load circuits. Protector shall perform the following functions:

1. Initiates a generator overload alarm when generator has operated at an overload equivalent to 110 percent of full-rated load for 60 seconds. Indication for this alarm is integrated with other generator-set malfunction alarms.

2. Under single or three-phase fault conditions, regulates generator to 300 percent of rated full-load current for up to 10 seconds.

3. As overcurrent heating effect on the generator approaches the thermal damage point of the unit, protector switches the excitation system off, opens the generator disconnect device, and shuts down the generator set.

4. Senses clearing of a fault by other overcurrent devices and controls recovery of rated voltage to avoid overshoot.

2.7 GENERATOR, EXCITER, AND VOLTAGE REGULATOR

A. Comply with NEMA MG 1.

B. Drive: Generator shaft shall be directly connected to engine shaft. Exciter shall be rotated integrally with generator rotor.

C. Electrical Insulation: Class F.

D. Stator-Winding Leads: Brought out to terminal box to permit future reconnection for other voltages if required.

E. Construction shall prevent mechanical, electrical, and thermal damage due to vibration, overspeed up to 125 percent of rating, and heat during operation at 110 percent of rated capacity.

F. Enclosure: Dripproof.

G. Instrument Transformers: Mounted within generator enclosure.

H. Voltage Regulator: Solid-state type, separate from exciter, providing performance as specified.

1. Adjusting rheostat on control and monitoring panel shall provide plus or minus 5 percent adjustment of output-voltage operating band.

I. Strip Heater: Thermostatically controlled unit arranged to maintain stator windings above dew point.

Page 143: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 11 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

J. Windings: Two-thirds pitch stator winding and fully linked amortisseur winding.

K. Subtransient Reactance: 12 percent, maximum.

2.8 MOTORS

A. General requirements for motors are specified in Division 15 Section "Motors."

1. Motor Sizes: Minimum size as indicated. If not indicated, large enough so driven load will not require motor to operate in service factor range above 1.0.

2. Controllers, Electrical Devices, and Wiring: Electrical devices and connections are specified in Division 16 Sections.

2.9 VIBRATION ISOLATION DEVICES

A. Elastomeric Isolator Pads: Oil- and water-resistant elastomer or natural rubber, arranged in single or multiple layers, molded with a nonslip pattern and galvanized-steel baseplates of sufficient stiffness for uniform loading over pad area, and factory cut to sizes that match requirements of supported equipment. 1. Material: Standard neoprene 2. Durometer values range from 30 to 70 and are measures of hardness or, indirectly,

deflection. Lower durometer values indicate softer material with more deflection. 3. Durometer Rating: 50 4. Number of Layers: Two

B. Restrained Spring Isolators: Freestanding, steel, open-spring isolators with seismic restraint.

1. Housing: Steel with resilient vertical-limit stops to prevent spring extension due to wind loads or if weight is removed; factory-drilled baseplate bonded to 1/4-inch- (6-mm-) thick, elastomeric isolator pad attached to baseplate underside; and adjustable equipment mounting and leveling bolt that acts as blocking during installation.

2. Outside Spring Diameter: Not less than 80 percent of compressed height of the spring at rated load.

3. Minimum Additional Travel: 50 percent of required deflection at rated load. 4. Lateral Stiffness: More than 80 percent of rated vertical stiffness. 5. Overload Capacity: Support 200 percent of rated load, fully compressed, without

deformation or failure.

2.10 FINISHES

A. Indoor and Outdoor Enclosures and Components: Manufacturer's standard finish over corrosion-resistant pretreatment and compatible primer.

2.11 SOURCE QUALITY CONTROL

A. Prototype Testing: Factory test engine-generator set using same engine model, constructed of identical or equivalent components and equipped with identical or equivalent accessories.

1. Tests: Comply with NFPA 110, Level 1 Energy Converters and with IEEE 115.

Page 144: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 12 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

B. Project-Specific Equipment Tests: Before shipment, factory test engine-generator set and other system components and accessories manufactured specifically for this Project. Perform tests at rated load and power factor. Include the following tests:

1. Test components and accessories furnished with installed unit that are not identical to those on tested prototype to demonstrate compatibility and reliability.

2. Full load run. 3. Maximum power. 4. Voltage regulation. 5. Transient and steady-state governing. 6. Single-step load pickup. 7. Safety shutdown. 8. Provide 14 days' advance notice of tests and opportunity for observation of tests by

Owner's representative. 9. Report factory test results within 10 days of completion of test.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas, equipment bases, and conditions, with Installer present, for compliance with requirements for installation and other conditions affecting packaged engine-generator performance.

B. Examine roughing-in of piping systems and electrical connections. Verify actual locations of connections before packaged engine-generator installation.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Comply with packaged engine-generator manufacturers' written installation and alignment instructions and with NFPA 110.

B. Install packaged engine generator to provide access, without removing connections or accessories, for periodic maintenance.

C. Install packaged engine generator with restrained spring isolators having a minimum deflection of 25 mm < on 4-inch- (100-mm-) high concrete base. Secure sets to anchor bolts installed in concrete bases. Concrete base construction is specified in Division 16 Section "Electrical Supports and Seismic Restraints."

D. Install Schedule 40, black steel piping with welded joints and connect to engine muffler. Install thimble at wall. Piping shall be same diameter as muffler outlet. Flexible connectors and steel piping materials and installation requirements are specified in Division 15 Section "Hydronic Piping."

1. Install condensate drain piping to muffler drain outlet full size of drain connection with a shutoff valve, stainless-steel flexible connector, and Schedule 40, black steel pipe with welded joints. Flexible connectors and piping materials and installation requirements are specified in Division 15 Section "Hydronic Piping."

Page 145: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 13 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

E. Electrical Wiring: Install electrical devices furnished by equipment manufacturers but not specified to be factory mounted.

3.3 CONNECTIONS

A. Piping installation requirements are specified in Division 15 Sections. Drawings indicate general arrangement of piping and specialties.

B. Connect fuel, cooling-system, and exhaust-system piping adjacent to packaged engine generator to allow service and maintenance.

C. Connect engine exhaust pipe to engine with flexible connector.

D. Connect fuel piping to engines with a gate valve and union and flexible connector.

1. Diesel storage tanks, tank accessories, piping, valves, and specialties for fuel systems outside the building are specified in Division 2 Section "Fuel Oil Distribution."

2. Diesel fuel piping, valves, and specialties inside the building are specified in Division 15 Section "Fuel Oil Piping."

3. Natural- and LP-gas piping, valves, and specialties for gas distribution outside the building are specified in Division 2 Section "Natural Gas Distribution."

4. Natural- and LP-gas piping, valves, and specialties for gas piping inside the building are specified in Division 15 Section "Fuel Gas Piping."

E. Ground equipment according to Division 16 Section "Grounding and Bonding."

F. Connect wiring according to Division 16 Section "Conductors and Cables."

3.4 IDENTIFICATION

A. Identify system components according to Division 15 Section "Mechanical Identification" and Division 16 Section "Electrical Identification."

3.5 FIELD QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to perform tests and inspections and prepare test reports.

B. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections. Report results in writing.

C. Perform tests and inspections and prepare test reports.

1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.

D. Tests and Inspections:

Page 146: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 14 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

1. Perform tests recommended by manufacturer and each electrical test and visual and mechanical inspection for "AC Generators and for Emergency Systems" specified in NETA Acceptance Testing Specification. Certify compliance with test parameters.

2. NFPA 110 Acceptance Tests: Perform tests required by NFPA 110 that are additional to those specified here including, but not limited to, single-step full-load pickup test.

3. Battery Tests: Equalize charging of battery cells according to manufacturer's written instructions. Record individual cell voltages.

a. Measure charging voltage and voltages between available battery terminals for full-charging and float-charging conditions. Check electrolyte level and specific gravity under both conditions.

b. Test for contact integrity of all connectors. Perform an integrity load test and a capacity load test for the battery.

c. Verify acceptance of charge for each element of the battery after discharge. d. Verify that measurements are within manufacturer's specifications.

4. Battery-Charger Tests: Verify specified rates of charge for both equalizing and float-charging conditions.

5. System Integrity Tests: Methodically verify proper installation, connection, and integrity of each element of engine-generator system before and during system operation. Check for air, exhaust, and fluid leaks.

6. Exhaust-System Back-Pressure Test: Use a manometer with a scale exceeding 40-inch wg (120 kPa). Connect to exhaust line close to engine exhaust manifold. Verify that back pressure at full-rated load is within manufacturer's written allowable limits for the engine.

7. Exhaust Emissions Test: Comply with applicable government test criteria. 8. Voltage and Frequency Transient Stability Tests: Use recording oscilloscope to measure

voltage and frequency transients for 50 and 100 percent step-load increases and decreases, and verify that performance is as specified.

9. Harmonic-Content Tests: Measure harmonic content of output voltage under 25 percent

and at 100 percent of rated linear load. Verify that harmonic content is within specified limits.

10. Noise Level Tests: Measure A-weighted level of noise emanating from generator-set installation, including engine exhaust and cooling-air intake and discharge, at four location on the property line and compare measured levels with required values.

E. Coordinate tests with tests for transfer switches and run them concurrently.

F. Test instruments shall have been calibrated within the last 12 months, traceable to standards of NIST, and adequate for making positive observation of test results. Make calibration records available for examination on request.

G. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.

H. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation.

I. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

J. Remove and replace malfunctioning units and retest as specified above.

Page 147: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Packaged Engine Generator System SECTION 16231

MEINHARDT PHILIPPINES INC. Page 15 of 15 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16231-Packaged Engine Generator System.doc

K. Retest: Correct deficiencies identified by tests and observations and retest until specified requirements are met.

L. Report results of tests and inspections in writing. Record adjustable relay settings and measured insulation resistances, time delays, and other values and observations. Attach a label or tag to each tested component indicating satisfactory completion of tests.

M. Infrared Scanning: After Substantial Completion, but not more than 60 days after Final Acceptance, perform an infrared scan of each power wiring termination and each bus connection. Remove all access panels so terminations and connections are accessible to portable scanner.

1. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan 11 months after date of Substantial Completion.

2. Instrument: Use an infrared scanning device designed to measure temperature or to detect significant deviations from normal values. Provide calibration record for device.

3. Record of Infrared Scanning: Prepare a certified report that identifies terminations and connections checked and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action.

3.6 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain packaged engine generators. Refer to Division 1 Section "Demonstration and Training."

END OF SECTION

Page 148: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Enclosed Circuit Breakers and Disconnect Switches SECTION 16410

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16410-Enclosed Circuit Breakers and Disconnect Switches.doc

PART 1 - GENERAL ......................................................................................................................... 1

1.1 RELATED DOCUMENTS .......................................................................................................... 1 1.2 SUMMARY ............................................................................................................................ 1 1.3 DEFINITIONS ........................................................................................................................ 1 1.4 SUBMITTALS ........................................................................................................................ 1 1.5 QUALITY ASSURANCE ........................................................................................................... 2 1.6 PROJECT CONDITIONS .......................................................................................................... 2 1.7 COORDINATION .................................................................................................................... 2 1.8 EXTRA MATERIALS ............................................................................................................... 3

PART 2 - PRODUCTS ....................................................................................................................... 3

2.1 MOLDED-CASE SWITCHES ..................................................................................................... 3 2.2 ENCLOSURES ....................................................................................................................... 3

PART 3 - EXECUTION ...................................................................................................................... 4

3.1 EXAMINATION ....................................................................................................................... 4 3.2 INSTALLATION ...................................................................................................................... 4 3.3 IDENTIFICATION .................................................................................................................... 4 3.4 FILED QUALITY CONTROL ...................................................................................................... 4 3.5 ADJUSTING .......................................................................................................................... 5

Page 149: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Enclosed Circuit Breakers and Disconnect Switches SECTION 16410

MEINHARDT PHILIPPINES INC. Page 1 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16410-Enclosed Circuit Breakers and Disconnect Switches.doc

SECTION 16410 ENCLOSED CIRCUIT BREAKERS AND DISCONNECT SWITCHES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Disconnect Switches 2. Individually mounted, enclosed circuit breakers. 3. Molded-case switches.

1.3 DEFINITIONS

A. NC: Normally closed.

B. NO: Normally open.

C. SPDT: Single pole, double throw.

1.4 SUBMITTALS

A. Product Data: For each type of enclosed switch, circuit breaker, accessory, and component indicated. Include dimensioned elevations, sections, weights, and manufacturers' technical data on features, performance, electrical characteristics, ratings, accessories, and finishes.

1. Enclosure types and details for types other than NEMA 250, Type 1. 2. Current and voltage ratings. 3. Short-circuit current ratings (interrupting and withstand, as appropriate). 4. Include evidence of NRTL listing for series rating of installed devices. 5. Detail features, characteristics, ratings, and factory settings of individual overcurrent

protective devices, accessories, and auxiliary components. 6. Include time-current coordination curves (average melt) for each type and rating of

overcurrent protective device; include selectable ranges for each type of overcurrent protective device.

B. Shop Drawings: For enclosed switches and circuit breakers. Include plans, elevations, sections, details, and attachments to other work.

1. Wiring Diagrams: For power, signal, and control wiring.

C. Qualification Data: For qualified testing agency.

D. Field quality-control reports.

1. Test procedures used. 2. Test results that comply with requirements.

Page 150: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Enclosed Circuit Breakers and Disconnect Switches SECTION 16410

MEINHARDT PHILIPPINES INC. Page 2 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16410-Enclosed Circuit Breakers and Disconnect Switches.doc

3. Results of failed tests and corrective action taken to achieve test results that comply with requirements.

E. Manufacturer's field service report.

F. Operation and Maintenance Data: For enclosed switches and circuit breakers to include in emergency, operation, and maintenance manuals. In addition to items specified in Division 1 Section 01782 "Operation and Maintenance Data," include the following:

1. Manufacturer's written instructions for testing and adjusting enclosed switches and circuit breakers.

2. Time-current coordination curves (average melt) for each type and rating of overcurrent protective device; include selectable ranges for each type of overcurrent protective device.

1.5 QUALITY ASSURANCE

A. Testing Agency Qualifications: Member company of NETA or an NRTL.

1. Testing Agency's Field Supervisor: Currently certified by NETA to supervise on-site testing.

B. Source Limitations: Obtain enclosed switches and circuit breakers, overcurrent protective devices, components, and accessories, within same product category, from single source from single manufacturer.

C. Product Selection for Restricted Space: Drawings indicate maximum dimensions for enclosed switches and circuit breakers, including clearances between enclosures, and adjacent surfaces and other items. Comply with indicated maximum dimensions.

D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

E. Comply with NFPA 70.

1.6 PROJECT CONDITIONS

A. Environmental Limitations: Rate equipment for continuous operation under the following conditions unless otherwise indicated:

1. Ambient Temperature: Not less than minus 22 deg F (minus 30 deg C) and not exceeding 104 deg F (40 deg C).

2. Altitude: Not exceeding 6600 feet (2010 m).

1.7 COORDINATION

A. Coordinate layout and installation of switches, circuit breakers, and components with equipment served and adjacent surfaces. Maintain required workspace clearances and required clearances for equipment access doors and panels.

Page 151: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Enclosed Circuit Breakers and Disconnect Switches SECTION 16410

MEINHARDT PHILIPPINES INC. Page 3 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16410-Enclosed Circuit Breakers and Disconnect Switches.doc

1.8 EXTRA MATERIALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Fuses: Equal to 10 percent of quantity installed for each size and type, but no fewer than three of each size and type.

2. Fuse Pullers: Two for each size and type.

PART 2 - PRODUCTS

2.1 MOLDED-CASE SWITCHES

A. Acceptable Manufacturers: See Section 16007 “Alternative Equipment and Suppliers”.

B. General Requirements: MCCB with fixed, high-set instantaneous trip only, and short-circuit withstand rating equal to equivalent breaker frame size interrupting rating.

C. Features and Accessories:

1. Standard frame sizes and number of poles. 2. Lugs: Mechanical type, suitable for number, size, trip ratings, and conductor material. 3. Ground-Fault Protection: Comply with UL 1053; remote-mounted and powered type

with mechanical ground-fault indicator; relay with adjustable pickup and time-delay settings, push-to-test feature, internal memory, and shunt trip unit; and three-phase, zero-sequence current transformer/sensor.

4. Shunt Trip: Trip coil energized from separate circuit, with coil-clearing contact. 5. Undervoltage Trip: Set to operate at 35 to 75 percent of rated voltage without

intentional time delay. 6. Auxiliary Contacts: Two SPDT switches with "a" and "b" contacts; "a" contacts mimic

switch contacts, "b" contacts operate in reverse of switch contacts. 7. Alarm Switch: One NC contact that operates only when switch has tripped. 8. Key Interlock Kit: Externally mounted to prohibit switch operation; key shall be

removable only when switch is in off position. 9. Zone-Selective Interlocking: Integral with ground-fault shunt trip unit; for interlocking

ground-fault protection function. 10. Electrical Operator: Provide remote control for on, off, and reset operations. 11. Accessory Control Power Voltage: Integrally mounted, self-powered 240-V ac.

2.2 ENCLOSURES

A. Enclosed Switches and Circuit Breakers: NEMA AB 1, NEMA KS 1, NEMA 250, and UL 50, to comply with environmental conditions at installed location.

1. Indoor, Dry and Clean Locations: NEMA 250, Type 1. 2. Outdoor Locations: NEMA 250, Type 4X. 3. Kitchen and Wash-Down Areas: NEMA 250, Type 4X, stainless steel. 4. Other Wet or Damp, Indoor Locations: NEMA 250, Type 4. 5. Indoor Locations Subject to Dust, Falling Dirt, and Dripping Noncorrosive Liquids:

NEMA 250, Type 12. 6. Hazardous Areas Indicated on Drawings: NEMA 250, Type 9.

Page 152: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Enclosed Circuit Breakers and Disconnect Switches SECTION 16410

MEINHARDT PHILIPPINES INC. Page 4 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16410-Enclosed Circuit Breakers and Disconnect Switches.doc

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine elements and surfaces to receive enclosed switches and circuit breakers for compliance with installation tolerances and other conditions affecting performance of the Work.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Install individual wall-mounted switches and circuit breakers with tops at uniform height unless otherwise indicated.

B. Comply with mounting and anchoring requirements specified in Division 16 Section 16074 "Vibration and Seismic Controls for Electrical Systems."

C. Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and temporary blocking of moving parts from enclosures and components.

D. Install fuses in fusible devices.

E. Comply with NECA 1.

3.3 IDENTIFICATION

A. Comply with requirements in Division 16 Section 16075 "Electrical Identification."

1. Identify field-installed conductors, interconnecting wiring, and components; provide warning signs.

2. Label each enclosure with engraved metal or laminated-plastic nameplate.

3.4 FILED QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.

B. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections.

C. Perform tests and inspections.

1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.

D. Acceptance Testing Preparation:

1. Test insulation resistance for each enclosed switch and circuit breaker, component, connecting supply, feeder, and control circuit.

2. Test continuity of each circuit.

Page 153: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Enclosed Circuit Breakers and Disconnect Switches SECTION 16410

MEINHARDT PHILIPPINES INC. Page 5 of 5 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16410-Enclosed Circuit Breakers and Disconnect Switches.doc

E. Tests and Inspections:

1. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.

2. Correct malfunctioning units on-site, where possible, and retest to demonstrate compliance; otherwise, replace with new units and retest.

3. Perform the following infrared scan tests and inspections and prepare reports:

a. Initial Infrared Scanning: After Substantial Completion, but not more than 60 days after Final Acceptance, perform an infrared scan of each enclosed switch and circuit breaker. Remove front panels so joints and connections are accessible to portable scanner.

b. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan of each enclosed switch and circuit breaker 11 months after date of Substantial Completion.

c. Instruments and Equipment: Use an infrared scanning device designed to measure temperature or to detect significant deviations from normal values. Provide calibration record for device.

4. Test and adjust controls, remote monitoring, and safeties. Replace damaged and malfunctioning controls and equipment.

F. Enclosed switches and circuit breakers will be considered defective if they do not pass tests and inspections.

G. Prepare test and inspection reports, including a certified report that identifies enclosed switches and circuit breakers and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action.

3.5 ADJUSTING

A. Adjust moving parts and operable components to function smoothly, and lubricate as recommended by manufacturer.

B. Set field-adjustable circuit-breaker trip ranges as specified in Division 16 Section 16055 "Overcurrent Protective Device Coordination".

END OF SECTION

Page 154: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

PART 1 - GENERAL ..................................................................................................................... 1

1.1 RELATED DOCUMENTS ...................................................................................................... 1 1.2 SUMMARY ........................................................................................................................ 1 1.3 DEFINITIONS .................................................................................................................... 1 1.4 PERFORMANCE REQUIREMENTS......................................................................................... 1 1.5 SUBMITTALS .................................................................................................................... 1 1.6 QUALITY ASSURANCE ....................................................................................................... 2 1.7 DELIVERY, STORAGE, AND HANDLING ................................................................................. 3 1.8 PROJECT CONDITIONS ...................................................................................................... 3 1.9 COORDINATION ................................................................................................................ 3 1.10 WARRANTY ...................................................................................................................... 3 1.11 EXTRA MATERIALS ........................................................................................................... 3

PART 2 - PRODUCTS ................................................................................................................... 4

2.1 GENERAL REQUIREMENTS FOR PANELBOARDS .................................................................... 4 2.2 DISTRIBUTION PANELBOARDS ............................................................................................ 5 2.3 LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS ................................................. 5 2.4 LOAD CENTERS ................................................................................................................ 6 2.5 DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICES ................................................. 6 2.6 ACCESSORY COMPONENTS AND FEATURES......................................................................... 9

PART 3 - EXECUTION .................................................................................................................. 9

3.1 EXAMINATION ................................................................................................................... 9 3.2 INSTALLATION .................................................................................................................. 9 3.3 IDENTIFICATION .............................................................................................................. 10 3.4 FIELD QUALITY CONTROL ................................................................................................ 10 3.5 ADJUSTING .................................................................................................................... 11 3.6 PROTECTION .................................................................................................................. 12

Page 155: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 1 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

SECTION 16442 PANELBOARDS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

1.3 DEFINITIONS

A. SVR: Suppressed voltage rating.

B. TVSS: Transient voltage surge suppressor.

1.4 PERFORMANCE REQUIREMENTS

A. Seismic Performance: Panelboards shall withstand the effects of earthquake motions determined according to SEI/ASCE 7.

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified and the unit will be fully operational after the seismic event."

1.5 SUBMITTALS

A. Product Data: For each type of panelboard, switching and overcurrent protective device, transient voltage suppression device, accessory, and component indicated. Include dimensions and manufacturers' technical data on features, performance, electrical characteristics, ratings, and finishes.

B. Shop Drawings: For each panelboard and related equipment.

1. Include dimensioned plans, elevations, sections, and details. Show tabulations of installed devices, equipment features, and ratings.

2. Detail enclosure types and details for types other than NEMA 250, Type 1. 3. Detail bus configuration, current, and voltage ratings. 4. Short-circuit current rating of panelboards and overcurrent protective devices. 5. Include evidence of NRTL listing for series rating of installed devices. 6. Detail features, characteristics, ratings, and factory settings of individual overcurrent

protective devices and auxiliary components. 7. Include wiring diagrams for power, signal, and control wiring.

Page 156: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 2 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

8. Include time-current coordination curves for each type and rating of overcurrent protective device included in panelboards. Submit on translucent log-log graft paper; include selectable ranges for each type of overcurrent protective device.

C. Qualification Data: For qualified testing agency.

D. Seismic Qualification Certificates: Submit certification that panelboards, overcurrent protective devices, accessories, and components will withstand seismic forces defined in Division 16 Section Sections 16073 and 16074 "Hangers and Supports for Electrical Systems and Vibration and Seismic controls for Electrical Systems" respectively. Include the following:

1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.

2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.

3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.

E. Field Quality-Control Reports:

1. Test procedures used. 2. Test results that comply with requirements. 3. Results of failed tests and corrective action taken to achieve test results that comply

with requirements.

F. Panelboard Schedules: For installation in panelboards. Submit final versions after load balancing.

G. Operation and Maintenance Data: For panelboards and components to include in emergency, operation, and maintenance manuals. In addition to items specified in Division 1 Section 01782 "Operation and Maintenance Data," include the following:

1. Manufacturer's written instructions for testing and adjusting overcurrent protective devices.

2. Time-current curves, including selectable ranges for each type of overcurrent protective device that allows adjustments.

1.6 QUALITY ASSURANCE

A. Testing Agency Qualifications: Member company of NETA or an NRTL.

1. Testing Agency's Field Supervisor: Currently certified by NETA to supervise on-site testing.

B. Source Limitations: Obtain panelboards, overcurrent protective devices, components, and accessories from single source from single manufacturer.

C. Product Selection for Restricted Space: Drawings indicate maximum dimensions for panelboards including clearances between panelboards and adjacent surfaces and other items. Comply with indicated maximum dimensions.

D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

E. Comply with NEMA PB 1.

F. Comply with NFPA 70.

Page 157: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 3 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

1.7 DELIVERY, STORAGE, AND HANDLING

A. Handle and prepare panelboards for installation according to NECA 407 or NEMA PB 1.

1.8 PROJECT CONDITIONS

A. Environmental Limitations:

1. Do not deliver or install panelboards until spaces are enclosed and weathertight, wet work in spaces is complete and dry, work above panelboards is complete, and temporary ACMV system is operating and maintaining ambient temperature and humidity conditions at occupancy levels during the remainder of the construction period.

2. Rate equipment for continuous operation under the following conditions unless otherwise indicated:

a. Ambient Temperature: Not exceeding 23 deg F (minus 5 deg C) to plus 104 deg F (plus 40 deg C).

b. Altitude: Not exceeding 6600 feet (2000 m).

B. Service Conditions: NEMA PB 1, usual service conditions, as follows:

1. Ambient temperatures within limits specified. 2. Altitude not exceeding 6600 feet (2000 m).

1.9 COORDINATION

A. Coordinate layout and installation of panelboards and components with other construction that penetrates walls or is supported by them, including electrical and other types of equipment, raceways, piping, encumbrances to workspace clearance requirements, and adjacent surfaces. Maintain required workspace clearances and required clearances for equipment access doors and panels.

B. Coordinate sizes and locations of concrete bases with actual equipment provided. Cast anchor-bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in Division 3.

1.10 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace transient voltage suppression devices that fail in materials or workmanship within specified warranty period.

1. Warranty Period: Five years from date of Substantial Completion.

1.11 EXTRA MATERIALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Keys: Two spares for each type of panelboard cabinet lock. 2. Circuit Breakers Including GFCI and Ground Fault Equipment Protection (GFEP)

Types: Two spares for each panelboard. 3. Fuses for Fused Switches: Equal to 10 percent of quantity installed for each size and

type, but no fewer than three of each size and type.

Page 158: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 4 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

4. Fuses for Fused Power-Circuit Devices: Equal to 10 percent of quantity installed for each size and type, but no fewer than three of each size and type.

PART 2 - PRODUCTS

2.1 GENERAL REQUIREMENTS FOR PANELBOARDS

A. Fabricate and test panelboards according to IEEE 344 to withstand seismic forces defined in Division 16 Sections 16073 and 16074 "Hangers and Supports for Electrical Systems and Vibration and Seismic controls for Electrical Systems" respectively.

B. Enclosures: Flush, Surface, Flush- and surface-mounted cabinets.

1. Rated for environmental conditions at installed location.

a. Indoor Dry and Clean Locations: NEMA 250, Type 1. b. Outdoor Locations: NEMA 250, Type 3R. c. Kitchen and Wash-Down Areas: NEMA 250, Type 4X, stainless steel. d. Other Wet or Damp Indoor Locations: NEMA 250, Type 4. e. Indoor Locations Subject to Dust, Falling Dirt, and Dripping Noncorrosive

Liquids: NEMA 250, Type 5 or Type 12.

2. Front: Secured to box with concealed trim clamps. For surface-mounted fronts, match box dimensions; for flush-mounted fronts, overlap box.

3. Hinged Front Cover: Entire front trim hinged to box and with standard door within hinged trim cover.

4. Skirt for Surface-Mounted Panelboards: Same gage and finish as panelboard front with flanges for attachment to panelboard, wall, and ceiling or floor.

5. Gutter Extension and Barrier: Same gage and finish as panelboard enclosure; integral with enclosure body. Arrange to isolate individual panel sections.

6. Finishes:

a. Panels and Trim: Steel and galvanized steel, factory finished immediately after cleaning and pretreating with manufacturer's standard two-coat, baked-on finish consisting of prime coat and thermosetting topcoat.

b. Back Boxes: Galvanized steel Same finish as panels and trim. c. Fungus Proofing: Permanent fungicidal treatment for overcurrent protective

devices and other components.

7. Directory Card: Inside panelboard door, mounted in transparent card holder metal frame with transparent protective cover.

C. Incoming Mains Location: Top or Bottom.

D. Phase, Neutral, and Ground Buses:

1. Material: Hard-drawn copper, 98 percent conductivity. 2. Equipment Ground Bus: Adequate for feeder and branch-circuit equipment

grounding conductors; bonded to box. 3. Neutral Bus: 100 percent of phase bus 4. Extra-Capacity Neutral Bus: Neutral bus rated 200 percent of phase bus and UL

listed as suitable for nonlinear loads.

E. Conductor Connectors: Suitable for use with conductor material and sizes.

1. Material: Hard-drawn copper, 98 percent conductivity.

Page 159: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 5 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

2. Main and Neutral Lugs: Mechanical type. 3. Ground Lugs and Bus-Configured Terminators: Mechanical type. 4. Feed-Through Lugs: Mechanical type, suitable for use with conductor material.

Locate at opposite end of bus from incoming lugs or main device. 5. Subfeed (Double) Lugs: Mechanical type suitable for use with conductor material.

Locate at same end of bus as incoming lugs or main device. 6. Gutter-Tap Lugs: Mechanical type suitable for use with conductor material. Locate at

same end of bus as incoming lugs or main device. 7. Extra-Capacity Neutral Lugs: Rated 200 percent of phase lugs mounted on extra-

capacity neutral bus.

F. Service Equipment Label: NRTL labeled for use as service equipment for panelboards or load centers with one or more main service disconnecting and overcurrent protective devices.

G. Future Devices: Mounting brackets, bus connections, filler plates, and necessary appurtenances required for future installation of devices.

H. Panelboard Short-Circuit Current Rating: Fully rated to interrupt symmetrical short-circuit current available at terminals.

I. Panelboard Short-Circuit Current Rating: Rated for series-connected system with integral or remote upstream overcurrent protective devices and labeled by an NRTL. Include size and type of allowable upstream and branch devices, listed and labeled for series-connected short-circuit rating by an NRTL.

2.2 DISTRIBUTION PANELBOARDS

A. Acceptable Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. Panelboards: NEMA PB 1, power and feeder distribution type.

C. Doors: Secured with vault-type latch with tumbler lock; keyed alike.

1. For doors more than 36 inches 914 mm high, provide two latches, keyed alike.

D. Mains: Circuit breaker.

E. Branch Overcurrent Protective Devices for Circuit-Breaker Frame Sizes 125 A and Smaller: Bolt-on circuit breakers.

F. Branch Overcurrent Protective Devices for Circuit-Breaker Frame Sizes Larger Than 125 A: Bolt-on circuit breakers; plug-in circuit breakers where individual positive-locking device requires mechanical release for removal.

G. Branch Overcurrent Protective Devices: Fused switches.

H. Contactors in Main Bus: NEMA ICS 2, Class A, electrically or mechanically held, general-purpose controller, with same short-circuit interrupting rating as panelboard.

1. Internal Control-Power Source: Control-power transformer, with fused primary and secondary terminals, connected to main bus ahead of contactor connection.

2. External Control-Power Source: 220-V branch circuit 24-V control circuit.

2.3 LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS

A. Acceptable Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

Page 160: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 6 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

B. Panelboards: NEMA PB 1, lighting and appliance branch-circuit type.

C. Mains: Circuit breaker.

D. Branch Overcurrent Protective Devices: Bolt-on circuit breakers, replaceable without disturbing adjacent units.

E. Contactors in Main Bus (Not used): NEMA ICS 2, Class A, electrically or mechanically held, general-purpose controller, with same short-circuit interrupting rating as panelboard.

1. Internal Control-Power Source: Control-power transformer, with fused primary and secondary terminals, connected to main bus ahead of contactor connection.

2. External Control-Power Source: 220-V branch circuit, 24-V control circuit.

F. Doors: Concealed hinges; secured with flush latch with tumbler lock; keyed alike.

G. Column-Type Panelboards: Narrow gutter extension, with cover, to overhead junction box equipped with ground and neutral terminal buses.

2.4 LOAD CENTERS

A. Acceptable Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. Load Centers: Comply with UL 67.

C. Mains: Circuit breaker.

D. Branch Overcurrent Protective Devices: Plug-in circuit breakers, replaceable without disturbing adjacent units.

E. Conductor Connectors: Mechanical type for main, neutral, and ground lugs and buses.

2.5 DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICES

A. Acceptbale Manufacturers: See Section 16007 “Acceptable Equipment and Suppliers”.

B. Molded-Case Circuit Breaker (MCCB): Comply with UL 489, to meet available fault currents.

1. Thermal-Magnetic Circuit Breakers: Inverse time-current element for low-level overloads, and instantaneous magnetic trip element for short circuits. Adjustable magnetic trip setting for circuit-breaker frame sizes 250 A and larger.

2. Adjustable Instantaneous-Trip Circuit Breakers: Magnetic trip element with front-mounted, field-adjustable trip setting.

3. Electronic trip circuit breakers with rms sensing; field-replaceable rating plug or field-replicable electronic trip; and the following field-adjustable settings:

a. Instantaneous trip. b. Long- and short-time pickup levels. c. Long- and short-time time adjustments. d. Ground-fault pickup level, time delay, and I2t response.

4. Current-Limiting Circuit Breakers: Frame sizes 400 A and smaller; let-through ratings less than NEMA FU 1, RK-5.

5. GFCI Circuit Breakers: Single- and two-pole configurations with Class A ground-fault protection (6-mA trip).

Page 161: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 7 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

6. Ground-Fault Equipment Protection (GFEP) Circuit Breakers: Class B ground-fault protection (30-mA trip).

7. Arc-Fault Circuit Interrupter (AFCI) Circuit Breakers: Comply with UL 1699; 120/240-V, single-pole configuration.

Page 162: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 8 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

8. Molded-Case Circuit-Breaker (MCCB) Features and Accessories:

a. Standard frame sizes, trip ratings, and number of poles. b. Lugs: Mechanical style, suitable for number, size, trip ratings, and conductor

materials. c. Application Listing: Appropriate for application; Type SWD for switching

fluorescent lighting loads; Type HID for feeding fluorescent and high-intensity discharge (HID) lighting circuits.

d. Ground-Fault Protection: Integrally mounted or Remote-mounted relay and trip unit with adjustable pickup and time-delay settings, push-to-test feature, and ground-fault indicator.

e. Communication Capability: Circuit-breaker-mounted, Universal-mounted Integral or Din-rail-mounted communication module with functions and features compatible with power monitoring and control system specified in Division 16 Section "Electrical Power Monitoring and Control."

f. Shunt Trip: 220V trip coil energized from separate circuit, set to trip at [55] [75] percent of rated voltage.

g. Undervoltage Trip: Set to operate at 35 to 75 percent of rated voltage with field-adjustable 0.1- to 0.6-second time delay.

h. Auxiliary Contacts: Two SPDT switches with "a" and "b" contacts; "a" contacts mimic circuit-breaker contacts and "b" contacts operate in reverse of circuit-breaker contacts.

i. Alarm Switch: Single-pole, normally open contact that actuates only when circuit breaker trips.

j. Key Interlock Kit: Externally mounted to prohibit circuit-breaker operation; key shall be removable only when circuit breaker is in off position.

k. Zone-Selective Interlocking: Integral with electronic trip unit; for interlocking ground-fault protection function with other upstream or downstream devices.

l. Multipole units enclosed in a single housing or factory assembled to operate as a single unit.

m. Handle Padlocking Device: Fixed attachment, for locking circuit-breaker handle in on or off position.

n. Handle Clamp: Loose attachment, for holding circuit-breaker handle in on position.

C. Fused Switch: NEMA KS 1, Type HD; clips to accommodate specified fuses; lockable handle.

1. Fuses, and Spare-Fuse Cabinet: 2. Fused Switch Features and Accessories: Standard ampere ratings and number of

poles. 3. Auxiliary Contacts: Two normally open and normally closed contact(s) that operate

with switch handle operation.

Page 163: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 9 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

2.6 ACCESSORY COMPONENTS AND FEATURES

A. Accessory Set: Include tools and miscellaneous items required for overcurrent protective device test, inspection, maintenance, and operation.

B. Portable Test Set: For testing functions of solid-state trip devices without removing from panelboard. Include relay and meter test plugs suitable for testing panelboard meters and switchboard class relays.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Receive, inspect, handle, and store panelboards according to NECA 407 or NEMA PB 1.1.

B. Examine panelboards before installation. Reject panelboards that are damaged or rusted or have been subjected to water saturation.

C. Examine elements and surfaces to receive panelboards for compliance with installation tolerances and other conditions affecting performance of the Work.

D. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Install panelboards and accessories according to NECA 407 or NEMA PB 1.1.

B. Equipment Mounting: Install panelboards on concrete bases, 4-inch (100-mm) nominal thickness. Comply with requirements for concrete base specified in Division 3 Section "Cast-in-Place Concrete."

1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch (450-mm) centers around full perimeter of base.

2. For panelboards, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor.

3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.

4. Install anchor bolts to elevations required for proper attachment to panelboards. 5. Attach panelboard to the vertical finished or structural surface behind the panelboard.

C. Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and temporary blocking of moving parts from panelboards.

D. Comply with mounting and anchoring requirements specified in Division 16 Section "Vibration and Seismic Controls for Electrical Systems."

E. Mount top of trim 90 inches (2286 mm) above finished floor unless otherwise indicated.

F. Mount panelboard cabinet plumb and rigid without distortion of box. Mount recessed panelboards with fronts uniformly flush with wall finish and mating with back box.

G. Install overcurrent protective devices and controllers not already factory installed.

Page 164: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 10 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

1. Set field-adjustable, circuit-breaker trip ranges.

H. Install filler plates in unused spaces.

I. Stub four 1-inch (27-GRC) empty conduits from panelboard into accessible ceiling space or space designated to be ceiling space in the future. Stub four 1-inch (27-GRC) empty conduits into raised floor space or below slab not on grade.

J. Arrange conductors in gutters into groups and bundle and wrap with wire ties after completing load balancing.

K. Comply with NECA 1.

3.3 IDENTIFICATION

A. Identify field-installed conductors, interconnecting wiring, and components; provide warning signs complying with Division 16 Section 16075 "Electrical Identification."

B. Create a directory to indicate installed circuit loads after balancing panelboard loads; incorporate Owner's final room designations. Obtain approval before installing. Use a computer or typewriter to create directory; handwritten directories are not acceptable.

C. Panelboard Nameplates: Label each panelboard with a nameplate complying with requirements for identification specified in Division 16 16075 Section"Electrical Identification."

D. Device Nameplates: Label each branch circuit device in distribution panelboards with a nameplate complying with requirements for identification specified in Division 16 Section 16075 "Electrical Identification."

3.4 FIELD QUALITY CONTROL

A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.

B. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections.

Page 165: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 11 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

C. Perform tests and inspections.

1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.

D. Acceptance Testing Preparation:

1. Test insulation resistance for each panelboard bus, component, connecting supply, feeder, and control circuit.

2. Test continuity of each circuit.

E. Tests and Inspections:

1. Perform each visual and mechanical inspection and electrical test stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.

2. Correct malfunctioning units on-site, where possible, and retest to demonstrate compliance; otherwise, replace with new units and retest.

3. Perform the following infrared scan tests and inspections and prepare reports:

a. Initial Infrared Scanning: After Substantial Completion, but not more than 60 days after Final Acceptance, perform an infrared scan of each panelboard. Remove front panels so joints and connections are accessible to portable scanner.

b. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan of each panelboard 11 months after date of Substantial Completion.

c. Instruments and Equipment:

1) Use an infrared scanning device designed to measure temperature or to detect significant deviations from normal values. Provide calibration record for device.

F. Panelboards will be considered defective if they do not pass tests and inspections.

G. Prepare test and inspection reports, including a certified report that identifies panelboards included and that describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations after remedial action.

3.5 ADJUSTING

A. Adjust moving parts and operable component to function smoothly, and lubricate as recommended by manufacturer.

B. Set field-adjustable circuit-breaker trip ranges as specified in Division 16 Section 16055 "Overcurrent Protective Device Coordination."

C. Load Balancing: After Substantial Completion, but not more than 60 days after Final Acceptance, measure load balancing and make circuit changes.

1. Measure as directed during period of normal system loading.

Page 166: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Panelboards SECTION 16442

MEINHARDT PHILIPPINES INC. Page 12 of 12 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16442-Panelboards.doc

2. Perform load-balancing circuit changes outside normal occupancy/working schedule of the facility and at time directed. Avoid disrupting critical 24-hour services such as fax machines and on-line data processing, computing, transmitting, and receiving equipment.

3. After circuit changes, recheck loads during normal load period. Record all load readings before and after changes and submit test records.

4. Tolerance: Difference exceeding 20 percent between phase loads, within a panelboard, is not acceptable. Rebalance and recheck as necessary to meet this minimum requirement.

3.6 PROTECTION

A. Temporary Heating: Apply temporary heat to maintain temperature according to manufacturer's written instructions.

END OF SECTION

Page 167: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

PART 1 - GENERAL ......................................................................................................................... 1

1.1 RELATED DOCUMENTS .......................................................................................................... 1 1.2 SUMMARY ............................................................................................................................ 1 1.3 DEFINITIONS ........................................................................................................................ 1 1.4 SUBMITTALS ........................................................................................................................ 2 1.5 QUALITY ASSURANCE ........................................................................................................... 3 1.6 COORDINATION .................................................................................................................... 4 1.7 WARRANTY .......................................................................................................................... 4 1.8 EXTRA MATERIALS ............................................................................................................... 4

PART 2 - PRODUCTS ....................................................................................................................... 4 2.1 MANUFACTURERS................................................................................................................. 4 2.2 GENERAL REQUIREMENTS FOR LIGHTING FIXTURES AND COMPONENTS ..................................... 4 2.3 BALLASTS FOR LINEAR FLUORESCENT LAMPS.......................................................................... 5 2.4 BALLASTS FOR COMPACT FLUORESCENT LAMPS...................................................................... 6 2.5 EMERGENCY FLUORESCENT POWER UNIT............................................................................... 6 2.6 BALLASTS FOR HID LAMPS..................................................................................................... 8 2.7 EXIT SIGNS .......................................................................................................................... 8 2.8 EMERGENCY LIGHTING UNITS ................................................................................................ 9 2.9 FLUORESCENT LAMPS ........................................................................................................... 9 2.10 LIGHTING FIXTURE SUPPORT COMPONENTS .......................................................................... 10 2.11 RETROFIT KIT FOR FLUORESCENT LIGHTING FIXTURES .......................................................... 10 2.12 PERFORMANCE SPECIFICATION OF LIGHT EMITTING DIODE (LED) LUMINAIRES ......................... 11

PART 3 - EXECUTION .................................................................................................................... 13 3.1 INSTALLATION .................................................................................................................... 13 3.2 IDENTIFICATION .................................................................................................................. 13 3.3 FIELD QUALITY CONTROL .................................................................................................... 14 3.4 STARTUP SERVICE .............................................................................................................. 14 3.5 ADJUSTING ........................................................................................................................ 14

Appendix 1 Illumination Criteria (Lighting Levels) Appendix 2 Luminaire Efficacy Appendix 3 Correlated Color Temperature (CCT) and Tolerance Limit of LED Luminaire

Page 168: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 1 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

SECTION 16511 INTERIOR LIGHTING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Interior lighting fixtures, lamps, and ballasts. 2. Emergency lighting units. 3. Exit signs. 4. Lighting fixture supports. 5. Retrofit kits for fluorescent lighting fixtures.

B. Related Sections:

1. Division 16 Section 16140 "Wiring Devices" for manual wall-box dimmers for

incandescent lamps.

1.3 DEFINITIONS

A. BF: Ballast factor.

B. CCT: Correlated color temperature.

C. CRI: Color-rendering index.

D. HID: High-intensity discharge.

E. LER: Luminaire efficacy rating.

F. Lumen: Measured output of lamp and luminaire, or both.

G. Luminaire: Complete lighting fixture, including ballast housing if provided.

Page 169: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 2 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

1.4 SUBMITTALS

A. Product Data: For each type of lighting fixture, arranged in order of fixture designation. Include data on features, accessories, finishes, and the following:

1. Physical description of lighting fixture including dimensions. 2. Emergency lighting units including battery and charger. 3. Ballast, including BF. 4. Energy-efficiency data. 5. Life, output (lumens, CCT, and CRI), and energy-efficiency data for lamps. 6. Photometric data and adjustment factors based on laboratory tests, complying with

IESNA Lighting Measurements Testing & Calculation Guides, of each lighting fixture type. The adjustment factors shall be for lamps, ballasts, and accessories identical to those indicated for the lighting fixture as applied in this Project.

a. Testing Agency Certified Data: For indicated fixtures, photometric data shall be certified by a qualified independent testing agency. Photometric data for remaining fixtures shall be certified by manufacturer.

b. Manufacturer Certified Data: Photometric data shall be certified by a manufacturer's laboratory with a current accreditation under the National Voluntary Laboratory Accreditation Program for Energy Efficient Lighting Products.

7. “Dialux” software simulation with IES/LDT plug-in files shall be provided to meet the lighting level requirement per Appendix 1.

B. Shop Drawings: For nonstandard or custom lighting fixtures. Include plans, elevations, sections, details, and attachments to other work.

1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

2. Wiring Diagrams: For power, signal, and control wiring.

C. Samples: For each lighting fixture indicated in the Drawings. Each Sample shall include the following:

1. Lamps and ballasts, installed. 2. Cords and plugs. 3. Pendant support system.

D. Installation instructions.

E. Coordination Drawings: Reflected ceiling plan(s) and other details, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:

1. Lighting fixtures. 2. Suspended ceiling components. 3. Partitions and millwork that penetrate the ceiling or extends to within 12 inches (305

mm) of the plane of the luminaires. 4. Ceiling-mounted projectors. 5. Structural members to which suspension systems for lighting fixtures will be attached. 6. Other items in finished ceiling including the following:

a. Air outlets and inlets. b. Speakers.

Page 170: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 3 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

c. Sprinklers. d. Smoke and fire detectors. e. Occupancy sensors. f. Access panels.

7. Perimeter moldings.

F. Qualification Data: For qualified agencies providing photometric data for lighting fixtures.

G. Product Certificates: For each type of ballast for bi-level and dimmer-controlled fixtures, from manufacturer.

H. Field quality-control reports.

I. Operation and Maintenance Data: For lighting equipment and fixtures to include in emergency, operation, and maintenance manuals.

1. Provide a list of all lamp types used on Project; use ANSI and manufacturers' codes.

J. Illumination Simulation using Dialux, Relux or other lighting softwares.

K. Warranty: Sample of special warranty.

1.5 QUALITY ASSURANCE

A. Luminaire Photometric Data Testing Laboratory Qualifications: Provided by manufacturers' laboratories that are accredited under the National Volunteer Laboratory Accreditation Program for Energy Efficient Lighting Products.

B. Luminaire Photometric Data Testing Laboratory Qualifications: Provided by an independent agency, with the experience and capability to conduct the testing indicated, that is an NRTL as defined by OSHA in 29 CFR 1910, complying with the IESNA Lighting Measurements Testing & Calculation Guides.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in PEC, by a qualified testing agency, and marked for intended location and application.

D. Comply with PEC.

E. FM Global Compliance: Lighting fixtures for hazardous locations shall be listed and labeled for indicated class and division of hazard by FM Global.

F. Mockups: Provide interior lighting fixtures for room or module mockups, complete with power and control connections.

1. Obtain ARCHITECT’S and MEEPF CONSULTANT’S approval of fixtures for mockups before starting installations.

2. Maintain mockups during construction in an undisturbed condition as a standard for judging the completed Work.

3. Approved fixtures in mockups may become part of the completed Work if undisturbed at time of Substantial Completion.

Page 171: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 4 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

1.6 COORDINATION

A. Coordinate layout and installation of lighting fixtures and suspension system with other construction that penetrates ceilings or is supported by them, including HVAC equipment, fire-suppression system, and partition assemblies.

1.7 WARRANTY

A. Special Warranty for Emergency Lighting Batteries: Manufacturer's standard form in which manufacturer of battery-powered emergency lighting unit agrees to repair or replace components of rechargeable batteries that fail in materials or workmanship within specified warranty period.

1. Warranty Period for Emergency Lighting Unit Batteries: 10 years from date of Substantial Completion. Full warranty shall apply for first year, and prorated warranty for the remaining nine years.

2. Warranty Period for Emergency Fluorescent Ballast and Self-Powered Exit Sign Batteries: Seven years from date of Substantial Completion. Full warranty shall apply for first year, and prorated warranty for the remaining six years.

1.8 EXTRA MATERIALS

A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Lamps: 10 for every 100 of each type and rating installed. Furnish at least one of each type.

2. Plastic Diffusers and Lenses: One for every 100 of each type and rating installed. Furnish at least one of each type.

3. Fluorescent-fixture-mounted, emergency battery pack: One for every 50 emergency lighting unit.

4. Ballasts: One for every 100 of each type and rating installed. Furnish at least one of each type.

5. Globes and Guards: One for every 20 of each type and rating installed. Furnish at least one of each type.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Acceptable Manufacturers: Refer to Section 16007.

2.2 GENERAL REQUIREMENTS FOR LIGHTING FIXTURES AND COMPONENTS

A. Recessed Fixtures: Comply with NEMA LE 4 for ceiling compatibility for recessed fixtures.

B. Incandescent Fixtures: Comply with UL 1598. Where LER is specified, test according to NEMA LE 5A.

C. Fluorescent Fixtures: Comply with UL 1598. Where LER is specified, test according to NEMA LE 5 and NEMA LE 5A as applicable.

Page 172: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 5 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

D. HID Fixtures: Comply with UL 1598. Where LER is specified, test according to NEMA LE 5B.

E. Metal Parts: Free of burrs and sharp corners and edges.

F. Sheet Metal Components: Steel unless otherwise indicated. Form and support to prevent warping and sagging.

G. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage under operating conditions, and designed to permit relamping without use of tools. Designed to prevent doors, frames, lenses, diffusers, and other components from falling accidentally during relamping and when secured in operating position.

H. Diffusers and Globes:

1. Acrylic Lighting Diffusers: 100 percent virgin acrylic plastic. High resistance to yellowing and other changes due to aging, exposure to heat, and UV radiation.

a. Lens Thickness: At least 0.125 inch (3.175 mm) minimum unless otherwise indicated.

b. UV stabilized.

2. Glass: Annealed crystal glass unless otherwise indicated.

I. Factory-Applied Labels: Comply with UL 1598. Include recommended lamps and ballasts. Labels shall be located where they will be readily visible to service personnel, but not seen from normal viewing angles when lamps are in place.

1. Label shall include the following lamp and ballast characteristics:

a. "USE ONLY" and include specific lamp type. b. Lamp diameter code (T-4, T-5 etc.), tube configuration (twin, quad, triple, etc.),

base type, and nominal wattage for fluorescent and compact fluorescent luminaires.

c. Lamp type, wattage, bulb type (ED17, BD56, etc.) and coating (clear or coated) for HID luminaires.

d. Start type (preheat, rapid start, instant start, etc.) for fluorescent and compact fluorescent luminaires.

e. ANSI ballast type (M98, M57, etc.) for HID luminaires. f. CCT and CRI for all luminaires.

J. Electromagnetic-Interference Filters: Factory installed to suppress conducted electromagnetic interference as required by MIL-STD-461E. Fabricate lighting fixtures with one filter on each ballast indicated to require a filter.

2.3 BALLASTS FOR LINEAR FLUORESCENT LAMPS

A. General Requirements for Electronic Ballasts:

1. Comply with UL 935 and with ANSI C82.11. 2. Designed for type and quantity of lamps served. 3. Ballasts shall be designed for full light output unless another BF, dimmer, or bi-level

control is indicated. 4. DSI/DALI Compatible 5. Sound Rating: Class A. 6. Total Harmonic Distortion Rating: Less than 10 percent. 7. Transient Voltage Protection: IEEE C62.41.1 and IEEE C62.41.2, Category A or

better.

Page 173: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 6 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

8. Operating Frequency: 20 kHz or higher. 9. Lamp Current Crest Factor: 1.7 or less. 10. BF: 0.90 or higher. 11. Power Factor: 0.95 or higher. 12. Parallel Lamp Circuits: Multiple lamp ballasts shall comply with ANSI C82.11 and

shall be connected to maintain full light output on surviving lamps if one or more lamps fail.

B. Electronic Programmed-Start Ballasts for T5 Lamps: Comply with ANSI C82.11 and the following:

1. Lamp end-of-life detection and shutdown circuit for T5 diameter lamps. 2. Automatic lamp starting after lamp replacement.

C. Single Ballasts for Multiple Lighting Fixtures: Factory wired with ballast arrangements and bundled extension wiring to suit final installation conditions without modification or rewiring in the field.

2.4 BALLASTS FOR COMPACT FLUORESCENT LAMPS

A. Description: Electronic-programmed rapid-start type, complying with UL 935 and with ANSI C 82.11, designed for type and quantity of lamps indicated. Ballast shall be designed for full light output unless dimmer or bi-level control is indicated:

1. Lamp end-of-life detection and shutdown circuit. 2. Automatic lamp starting after lamp replacement. 3. Sound Rating: Class A. 4. Total Harmonic Distortion Rating: Less than 20 percent. 5. Transient Voltage Protection: IEEE C62.41.1 and IEEE C62.41.2, Category A or

better. 6. Operating Frequency: 20 kHz or higher. 7. Lamp Current Crest Factor: 1.6 or less. 8. BF: 0.95 or higher unless otherwise indicated. 9. Power Factor: 0.95 or higher. 10. Interference: Comply with 47 CFR 18, Ch. 1, Subpart C, for limitations on

electromagnetic and radio-frequency interference for nonconsumer equipment.

2.5 EMERGENCY FLUORESCENT POWER UNIT

A. Internal Type: Self-contained, modular, battery-inverter unit, factory mounted within lighting fixture body and compatible with ballast. Comply with UL 924.

1. Emergency Connection: Operate one fluorescent lamp(s) continuously at an output of 1100 lumens each. Connect unswitched circuit to battery-inverter unit and switched circuit to fixture ballast.

2. Nightlight Connection: Operate one fluorescent lamp continuously. 3. Test Push Button and Indicator Light: Visible and accessible without opening fixture

or entering ceiling space.

a. Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability.

b. Indicator Light: LED indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle.

Page 174: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 7 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

4. Battery: Sealed, maintenance-free, nickel-cadmium type. 5. Charger: Fully automatic, solid-state, constant-current type with sealed power

transfer relay. 6. Remote Test: Switch in hand-held remote device aimed in direction of tested unit

initiates coded infrared signal. Signal reception by factory-installed infrared receiver in tested unit triggers simulation of loss of its normal power supply, providing visual confirmation of either proper or failed emergency response.

7. Integral Self-Test: Factory-installed electronic device automatically initiates code-required test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing red LED.

Page 175: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 8 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

2.6 BALLASTS FOR HID LAMPS

A. High-Pressure Sodium Ballasts: Electromagnetic type, with solid-state igniter/starter. Igniter/starter shall have an average life in pulsing mode of 10,000 hours at an igniter/starter-case temperature of 90 deg C.

1. Instant-Restrike Device: Integral with ballast, or solid-state potted module, factory installed within fixture and compatible with lamps, ballasts, and mogul sockets up to 150 W.

2. Minimum Starting Temperature: Minus 40 deg F (Minus 40 deg C).

2.7 EXIT SIGNS

A. General Requirements for Exit Signs: Comply with UL 924; for sign colors, visibility, luminance, and lettering size, comply with authorities having jurisdiction.

B. Internally Lighted Signs:

1. Lamps for AC Operation: LEDs, 50,000 hours minimum rated lamp life. 2. Self-Powered Exit Signs (Battery Type): Integral automatic charger in a self-

contained power pack.

a. Battery: Sealed, maintenance-free, nickel-cadmium type. b. Charger: Fully automatic, solid-state type with sealed transfer relay. c. Operation: Relay automatically energizes lamp from battery when circuit

voltage drops to 80 percent of nominal voltage or below. When normal voltage is restored, relay disconnects lamps from battery, and battery is automatically recharged and floated on charger.

d. Test Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability.

e. LED Indicator Light: Indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle.

f. Remote Test: Switch in hand-held remote device aimed in direction of tested unit initiates coded infrared signal. Signal reception by factory-installed infrared receiver in tested unit triggers simulation of loss of its normal power supply, providing visual confirmation of either proper or failed emergency response.

g. Integral Self-Test: Factory-installed electronic device automatically initiates code-required test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing red LED.

3. Master/Remote Sign Configurations:

a. Master Unit: Comply with requirements above for self-powered exit signs, and provide additional capacity in LED power supply for power connection to remote unit.

b. Remote Unit: Comply with requirements above for self-powered exit signs, except omit power supply, battery, and test features. Arrange to receive full power requirements from master unit. Connect for testing concurrently with master unit as a unified system.

C. Self-Luminous Signs: Powered by tritium gas, with universal bracket for flush-ceiling, wall, or end mounting. Signs shall be guaranteed by manufacturer to maintain the minimum brightness requirements in UL 924 for 10 years.

Page 176: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 9 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

D. Self-Luminous Signs: Using strontium oxide aluminate compound to store ambient light and release the stored energy when the light is removed. Provide with universal bracket for flush-ceiling, wall, or end mounting.

2.8 EMERGENCY LIGHTING UNITS

A. General Requirements for Emergency Lighting Units: Self-contained units complying with UL 924.

1. Battery: Sealed, maintenance-free, lead-acid type. 2. Charger: Fully automatic, solid-state type with sealed transfer relay. 3. Operation: Relay automatically turns lamp on when power-supply circuit voltage

drops to 80 percent of nominal voltage or below. Lamp automatically disconnects from battery when voltage approaches deep-discharge level. When normal voltage is restored, relay disconnects lamps from battery, and battery is automatically recharged and floated on charger.

4. Test Push Button: Push-to-test type, in unit housing, simulates loss of normal power and demonstrates unit operability.

5. LED Indicator Light: Indicates normal power on. Normal glow indicates trickle charge; bright glow indicates charging at end of discharge cycle.

6. Wire Guard: Heavy-chrome-plated wire guard protects lamp heads or fixtures. 7. Integral Time-Delay Relay: Holds unit on for fixed interval of 15 minutes when power

is restored after an outage. 8. Remote Test: Switch in hand-held remote device aimed in direction of tested unit

initiates coded infrared signal. Signal reception by factory-installed infrared receiver in tested unit triggers simulation of loss of its normal power supply, providing visual confirmation of either proper or failed emergency response.

9. Integral Self-Test: Factory-installed electronic device automatically initiates code-required test of unit emergency operation at required intervals. Test failure is annunciated by an integral audible alarm and a flashing red LED.

2.9 FLUORESCENT LAMPS

A. T5 rapid-start lamps, rated 28 W maximum, nominal length of 45.2 inches (1150 mm), 2900 initial lumens (minimum), CRI 85 (minimum), color temperature 3000 K, and average rated life of 20,000 hours unless otherwise indicated.

B. T5HO rapid-start, high-output lamps, rated 54 W maximum, nominal length of 45.2 inches (1150 mm), 5000 initial lumens (minimum), CRI 85 (minimum), color temperature 4100 K, and average rated life of 20,000 hours unless otherwise indicated.

Page 177: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 10 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

C. Compact Fluorescent Lamps: 4-Pin, CRI 80 (minimum), color temperature 3500 K, average rated life of 10,000 hours at three hours operation per start, and suitable for use with dimming ballasts unless otherwise indicated.

1. 13 W: T4, double or triple tube, rated 900 initial lumens (minimum). 2. 18 W: T4, double or triple tube, rated 1200 initial lumens (minimum). 3. 26 W: T4, double or triple tube, rated 1800 initial lumens (minimum). 4. 32 W: T4, triple tube, rated 2400 initial lumens (minimum). 5. 42 W: T4, triple tube, rated 3200 initial lumens (minimum). 6. 57 W: T4, triple tube, rated 4300 initial lumens (minimum). 7. 70 W: T4, triple tube, rated 5200 initial lumens (minimum).

2.10 LIGHTING FIXTURE SUPPORT COMPONENTS

A. Comply with Division 16 Section 16073 "Hangers and Supports for Electrical Systems" for channel- and angle-iron supports and nonmetallic channel and angle supports.

B. Single-Stem Hangers: 1/2-inch (13-mm) steel tubing with swivel ball fittings and ceiling canopy. Finish same as fixture.

C. Twin-Stem Hangers: Two, 1/2-inch (13-mm) steel tubes with single canopy designed to mount a single fixture. Finish same as fixture.

D. Wires: ASTM A 641/A 641M, Class 3, soft temper, zinc-coated steel, 12 gage (2.68 mm).

E. Wires for Humid Spaces: ASTM A 580/A 580M, Composition 302 or 304, annealed stainless steel, 12 gage (2.68 mm).

F. Rod Hangers: 3/16-inch (5-mm) minimum diameter, cadmium-plated, threaded steel rod.

G. Hook Hangers: Integrated assembly matched to fixture and line voltage and equipped with threaded attachment, cord, and locking-type plug.

2.11 RETROFIT KIT FOR FLUORESCENT LIGHTING FIXTURES

A. A. Reflector Kit: UL 1598, Type I. Suitable for two- to four-lamp, surface-mounted or recessed lighting fixtures by improving reflectivity of fixture surfaces.

B. Ballast and Lamp Change Kit: UL 1598, Type II. Suitable for changing existing ballast, lamps, and sockets.

Page 178: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 11 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

2.12 PERFORMANCE SPECIFICATION OF LIGHT EMITTING DIODE (LED) LUMINAIRES

A. General Requirements

1. The “Light Emitting Diode” (LED) luminaires, including the electronic driver and LED module shall be suitable for operation at 220V ± 6%, 60 Hz ± 2%, single phase, a.c. supply.

2. The LED luminaires shall be fully assembled and tested before shipment from factory. The LED luminaires shall comply both in manufacturing and testing with the following international standards and their manufacturing process shall conform to the relevant quality standard of ISO 9000:2005:

Luminaires : IEC 60598-1:2008 for general requirements and tests; and IEC 60598-2-1:1987 for general purpose luminaires or IEC 60598-2- 2:1997 for recessed luminaires. Type test certificate shall be provided to demonstrate the compliance with the above standards issued by an accredited test laboratory for the LED luminaires. The LED luminaires shall be marked in accordance with the requirements of IEC 60598-2-1:1987 for general-purpose luminaires or IEC 60598-2-2:1997 for recessed luminaires.

3. The LED luminaires shall be rated for continuous service at an ambient temperature of 40ºC without affecting the performance requirements as stated in clause 4 of this specification. The Contractor shall be responsible to advise the Architect if the performance of the LED luminaires will be affected due to the installation conditions affecting the thermal dissipation from the LED luminaires.

4. The LED luminaires shall be “Restriction of Hazardous Substances (RoHS) Compliance”. RoHS Compliance certificate issues by an accredited test laboratory shall be submitted.

5. The LED luminaires shall have a full set of photometric data prepared to CIBSE TM5

or IES format for general lighting design purpose. IES/LDT plug-in files shall be provided together with the “Dialux” simulation files.

B. Electronic Driver for LED Module 1. The electronic driver for LED module (driver) shall be the unit, inserted between the

power supply and one or more LED modules, which serves to supply the LED module(s) with its constant rated voltage or rated current. The driver shall include the components of power factor correction, radio interferences suppression and also dimming facility if it is specified.

2. The driver shall conform to the following international standards:

(i) IEC 61347-1:2007 Lamp controlgear – Part 1: General and safety requirements;

(ii) IEC 61347-2-13:2006 Lamp controlgear – Part 2-13: Particular requirements for d.c. or a.c. supplied electronic controlgear for LED modules;

(iii) IEC 62384:2006 DC or AC supplied electronic control gear for LED modules – Performance requirements;

Page 179: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 12 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

(iv) IEC 61000-3-2:2009 Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits for harmonic current emissions (equipment input current O 16A per

phase);

(v) IEC 61547:2000 Equipment for general lighting purposes – EMC immunity requirements; and

(vi) EN 55015:2009 Limits and methods of measurement of radio disturbance

characteristics of electrical lighting and similar equipment.

3. Certificates of compliance with the above standards shall be issued by an accredited test laboratory for different ratings of drivers.

B. LED Module

The “LED module” contains one or more LEDs are to supply the light source and it may also include the optical, electrical and electronic components, but excluding the electronic driver. For the “self-ballasted LED module”, the electronic driver integrates with one or more LEDs as a unit for direct connection to a.c. supply. If the self-ballasted LED module is equipped with a lamp camp, it is regarded as “self-ballasted LED lamp”. The LED module, self-ballasted LED module or self-ballasted LED lamp shall be manufactured and tested to comply with IEC 62031:2008: LED modules for general lighting – Safety specifications. Certificate of compliance with the above standard shall be issued by an accredited test laboratory or the manufacturer.

C. Performance Requirements (Note: Project officer shall add any particular performance requirements to meet the project specific needs if necessary).

Each model of LED luminaire shall comply with the following performance requirements:

a. Luminaire efficacy (lumen/watt): Refer to Appendix 2 for the minimum requirement.

b. Lumen maintenance (L70):

The lumen output shall deliver at least 70% of its initial lumen output after operating 50,000 hours and 25,000 hours for LED module and self-ballasted LED lamp respectively.

c. Colour Rendering Index (CRI):

CRI shall be minimum 75 for colour temperature from 2700 – 6500K for indoor luminaires and minimum 80 for self-ballasted LED lamp.

d. Power factor:

The power factor of the LED luminaire circuit and self-ballasted LED lamp shall be minimum 0.9 and minimum 0.7 respectively.

Refer to Appendix 3 for the requirement.

D. Testing Standards for Compliance with Performance Requirements

The performance requirements as stated in Clause D of each model of LED luminaire shall be tested and certified by the accredited laboratories. The test reports shall be submitted for approval. If the test reports of the above performance requirements from the accredited laboratories are not available for the model of LED luminaire, the test reports certifying their compliance with the other recognized international or national standards or other standards on similar performance requirements shall be submitted for approval.

Page 180: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 13 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

PART 3 - EXECUTION

3.1 INSTALLATION

A. Lighting fixtures:

1. Set level, plumb, and square with ceilings and walls unless otherwise indicated. 2. Install lamps in each luminaire.

B. Temporary Lighting: If it is necessary, and approved by Architect, to use permanent luminaires for temporary lighting, install and energize the minimum number of luminaires necessary. When construction is sufficiently complete, remove the temporary luminaires, disassemble, clean thoroughly, install new lamps, and reinstall.

C. Remote Mounting of Ballasts: Distance between the ballast and fixture shall not exceed that recommended by ballast manufacturer. Verify, with ballast manufacturers, maximum distance between ballast and luminaire.

D. Lay-in Ceiling Lighting Fixtures Supports: Use grid as a support element.

1. Install ceiling support system rods or wires, independent of the ceiling suspension devices, for each fixture. Locate not more than 6 inches (150 mm) from lighting fixture corners.

2. Support Clips: Fasten to lighting fixtures and to ceiling grid members at or near each fixture corner with clips that are UL listed for the application.

3. Fixtures of Sizes Less Than Ceiling Grid: Install as indicated on reflected ceiling plans or center in acoustical panel, and support fixtures independently with at least two 3/4-inch (20-mm) metal channels spanning and secured to ceiling tees.

4. Install at least one independent support rod or wire from structure to a tab on lighting fixture. Wire or rod shall have breaking strength of the weight of fixture at a safety factor of 3.

E. Suspended Lighting Fixture Support:

1. Pendants and Rods: Where longer than 48 inches (1200 mm), brace to limit swinging.

2. Stem-Mounted, Single-Unit Fixtures: Suspend with twin-stem hangers. 3. Continuous Rows: Use tubing or stem for wiring at one point and tubing or rod for

suspension for each unit length of fixture chassis, including one at each end. 4. Do not use grid as support for pendant luminaires. Connect support wires or rods to

building structure.

F. Connect wiring according to Division 16 Section 16120 "Conductors and Cables."

3.2 IDENTIFICATION

A. Install labels with panel and circuit numbers on concealed junction and outlet boxes. Comply with requirements for identification specified in Division 16 Section 16075 "Electrical Identification."

Page 181: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 14 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

3.3 FIELD QUALITY CONTROL

A. Test for Emergency Lighting: Interrupt power supply to demonstrate proper operation. Verify transfer from normal power to battery and retransfer to normal.

B. Verify that self-luminous exit signs are installed according to their listing and the requirements in NFPA 101.

C. Prepare a written report of tests, inspections, observations, and verifications indicating and interpreting results. If adjustments are made to lighting system, retest to demonstrate compliance with standards.

3.4 STARTUP SERVICE

A. Burn-in all lamps that require specific aging period to operate properly, prior to occupancy by Owner. Burn-in fluorescent and compact fluorescent lamps intended to be dimmed, for at least 100 hours at full voltage.

3.5 ADJUSTING

A. Occupancy Adjustments: When requested within 12 months of date of Substantial Completion, provide on-site assistance in adjusting aimable luminaires to suit actual occupied conditions. Provide up to two visits to Project during other-than-normal occupancy hours for this purpose. Some of this work may be required after dark.

1. Adjust aimable luminaires in the presence of Architect.

Page 182: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 15 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

Appendix 1 – Illumination Criteria (Lighting Levels)

A. Hotel Casino

Location Illumination Level

(lux)

Entrance Lobby (1)

Living (1)

Bedroom (1)

Kitchen (1)

Bathrooms (1)

Lift Lobby (1)

Management Office 500

Security Room 500

Club Room (1)

Gymnasium (1)

MEPF Plantrooms 150

Loading / Unloading 150

Internal Staircase 150

Fire Lift Lobby 200

Common Toilet 150

Notes to Design Criteria:

To comply with the specialist lighting designer’s requirements.

Uniformity of lighting level will be designed at 0.7.

Page 183: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 16 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

B. Retail & Carpark

Location Illumination Level

(lux)

Entrance Lobby (1)

Retail Unit (2)

Restaurant (2)

Kitchen (2)

Public Lift Lobby (1)

Service Lift Lobby 200

Offices 500

Public Area 150

MEP Plantrooms 150

Loading / Unloading 150

Internal Staircase 150

Fire Lift Lobby 200

Carpark 50

Carpark Ramp 200

Carpark Entrance / Exit zones

200

Toilet 150

Notes to Design Criteria:

To comply with the specialist lighting designer’s and operator’s requirements

By Tenant and operator requirement.

General Notes:

Unformity of lighting level will be designed at 0.7.

Page 184: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 17 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

C. Hotel Tower

Location Illumination Level

(lux)

Guest Room (1)

Circulation Spaces 150

Stairs 150

Reception / Main Lobby (1)

Meeting Room (1)

Bar Lounge (1)

Pub (1)

Restaurant (1)

Kitchen 500

Guest Lift Lobby (1)

Service Lift Lobby 200

House keeping 500

Office 500

Business Centre (1)

Staff Toilets & Changing Room 150

Spa /Gym (2)

Ballroom (1)

Pre Function (1)

Public Toilets 150

Plantrooms 150

Loading / Unloading 150

Laundry 300

Notes to Design Criteria:

To comply with the specialist lighting designer’s and operator’s requirements

By Tenant and operator requirement.

Page 185: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 18 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

General Notes:

Unformity of lighting level will be designed at 0.7.

D. Shopping Mall

Location Illumination Level

(lux)

Restaurant (1)

Staff Toilets & Changing Room 150

Public Toilets 150

Plantrooms 150

Corridors 200

Notes to Design Criteria:

To comply with the specialist lighting designer’s and operator’s requirements

By Tenant and operator requirement.

General Notes:

Unformity of lighting level will be designed at 0.7.

Page 186: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Interior Lighting SECTION 16511

MEINHARDT PHILIPPINES INC. Page 19 of 19 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16511-Interior Lighting.doc

Appendix 2 – Luminaire Efficacy

The Luminaire efficacy of some typical luminaires is listed below for reference:

Luminaire Type Luminaire Efficacy

(i) recessed/surface/pendant-mounted downlight min. 35 lumen/watt (ii) wall washer (min. 575 lumens) min. 40 lumen/watt

(The luminaire efficacy shall be reviewed to match with the prevailing LED lighting technology).

Appendix 3 – The correlated colour temperature (CCT) and tolerance limit of LED luminaire

Nominal CCT Target CCT and tolerance

2700 K 2725 ± 145 K

3000 K 3045 ± 175 K

3500 K 3465 ± 245 K

4000 K 3985 ± 275 K

4500 K 4503 ± 243 K

5000 K 5028 ± 283 K

5700 K 5665 ± 355 K

6500 K 6530 ± 510 K

END OF SECTION

Page 187: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

PART 1 - GENERAL ......................................................................................................................... 1

1.1 INTRODUCTION ......................................................................................................................... 1

1.2 EQUIPMENT DESCRIPTIONS AND APPLICATION: ............................................................................ 1

1.3 RELATED SECTIONS .................................................................................................................. 2

1.4 REFERENCES ........................................................................................................................... 3

1.5 SUBMITTALS ............................................................................................................................. 3

1.6 PROJECT RECORD DOCUMENTS ................................................................................................. 3

1.7 PROJECT RECORD DOCUMENTS ................................................................................................. 3

1.8 MANUFACTURER ....................................................................................................................... 3

1.9 REGULATORY REQUIREMENTS .................................................................................................... 4

1.10 MAINTENANCE SERVICE............................................................................................................. 4

PART 2 - PRODUCTS ...................................................................................................................... 5

2.1 DIMMER RACKS OR PANELS ....................................................................................................... 5

2.2 STACKER ASSEMBLY ................................................................................................................. 5

2.3 DIMMER MODULE ...................................................................................................................... 6

2.4 RELAY MODULES ...................................................................................................................... 7

2.5 SCENESET LIGHTING ROUTERS .................................................................................................. 7

2.6 SCENE COMMANDER CONTROL STATIONS ................................................................................... 8

2.7 SOFTWARE REQUIREMENT......................................................................................................... 9

2.8 CABLE ..................................................................................................................................... 9

PART 3 - EXECUTION ................................................................................................................... 10

3.1 EXAMINATION ......................................................................................................................... 10

3.2 INSTALLATION ......................................................................................................................... 10

3.3 FIELD QUALITY CONTROL ........................................................................................................ 10

3.4 ADJUSTING ............................................................................................................................ 10

3.5 CLEANING .............................................................................................................................. 10

3.6 DEMONSTRATION .................................................................................................................... 11

Page 188: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. Page 1 of 11 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

SECTION 16570

LIGHTING CONTROL SYSTEM (DIMMING SYSTEM)

PART 1 - GENERAL

1.1 INTRODUCTION

A. Provide centralized lighting control system for the areas of as mentioned in the

drawing & in LP schedule.

B. The Addressable Lighting Control system / Dimming System shall provide different

Preset controls of Lighting as required. The system shall permit the user to turn ON /

OFF and dimming control of Individual load and group of loads and to set

preprogrammed Lighting pattern via Manual preset push button scene commander.

The system programming shall be implemented via a computer interface, and shall

be designed for centralized system with full automatic control and local control self-

contained within the lighting management system for which a dedicated computer

need not to be supplied by the supplier.

C. The system shall be completely programmable using advanced Lighting control

software operating under Windows to enable the lighting operation to be centrally

programmed and adapted. The system shall incorporate virtual wiring software,

enabling lighting switching patterns to be set up and instantly altered from the PC

without the need to access equipment or disruptive wiring alterations. The entire

system shall be centrally monitored in real time both On line and Off line.

D. The system shall be provided with multi sensors in order to maximize on energy

saving using daylight sensing to have constant lighting, Lighting control using hand

held remote control, presence detection etc and at the same time extend the life of

lamps within each of the required areas like corridor, car park, stair case, plant

room etc where ever applicable and as required by the client.

E. All luminaries shall be suitable for dimming control and will be equipped with high

frequency dimmable electronic ballast with variable output analogue control HF 0 -

10V DC interface when applicable where fluorescent lamps / compact fluorescent

lamps are utilized.

F. The system shall comprise rack / panel housings stackers, plug in type Dual channel

hard fired Thyristor dimmer modules, Lighting Router, local scene commander

control stations, programming sockets…etc.

G. The dimming systems Racks shall be suitable for operating at 400V/230V Ac – 60HZ

supply, and integrated with suitably rated TPN ISOLATOR, COELCB, and 10A/15A

MCB’S for output circuit protection.

H. The plug in type Thyristor dimmer modules shall be rated for 10A / 20Amps load as

Required and as per the load (LP) Schedule.

I. The dimming system shall be suitable for continuous 24 Hr. operation at a maximum

ambient temperature of 40 centigrade and 90 % humidity (non condensing).

J. The dimming system shall be guaranteed for a period of not less than 24 months

from the date of commissioning.

1.2 EQUIPMENT DESCRIPTIONS AND APPLICATION:

Page 189: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. Page 2 of 11 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

A. The dimmer rack shall consist of 10A / 20Amps dual channel plug in type, Thyristor

dimmer module as per the load requirement, Lighting Router etc with an incomer

TPN Isolator and COELCB. A facility shall be provided to isolate any individual

circuit as required, by providing an auxiliary housing / in the extended dimmer rack

with the rated MCB’s for out going circuits protection.

B. Output level override facility shall be provided to allow illumination for cleaning and

maintenance of the area incase of any defect in the lighting control system.

C. All the dimming & switching operation of lighting circuits mentioned in the load

schedule shall be considered for programming with the same type of dimming push

button control panel.

D. All the required areas as mentioned in the drawing shall be provided with 4 scenes

and Off Preset push button control scene commander panels with inbuilt infra red

receiver and Raise/Lower facility as shown in the Block Schematic Drawing. Where

ever double entrances are available, two way operation scene commander push

button control panels shall be provided.

E. All the push button control panels should be provided with polished brass or brushed

stainless steel fascia plate with a led tell back in the push buttons, in coordination

with other switch/sockets finishes.

F. A lighting router shall be provided to store the programmed Lighting scenes and all

the other programmed data and keep them in memory for ever.

1.3 RELATED SECTIONS

A. Section 16130 Raceways and Boxes

B. Section 16010 Basic Electrical Materials and Methods

C. Section 16145 Lighting Control Devices

D. Section 16511 Interior Lighting

Page 190: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. Page 3 of 11 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

1.4 REFERENCES

A. The equipment shall comply with all relevant proposed and current national,

European and inter -national safety and technical standards for electrical and

electronic dimming system. These will include strict compliance with electro

magnetic conduction (EMC) standards EN50 081-1 and EN50 082-1, safety standard

EN60 950 and RFI suppression standard EN50 014.

B. The equipment shall be fabricated in accordance with all procedures for quality

assurance to ISO 9002.

1.5 SUBMITTALS

A. Shop drawings: provide working drawings and schematic diagrams.

B. Manufacturers instruction:

C. Indicate instructions for storage, handling, protection, examination, installation &

wiring of equipment.

1.6 PROJECT RECORD DOCUMENTS

A. Submit Under Provisions Of Division 1.

B. Accurately record actual locations of each item of equipment.

1.7 PROJECT RECORD DOCUMENTS

A. Submit under provision of Division 1.

B. Maintenance Data: Include recommended spare parts list as recommended by the

manufacturer.

1.8 MANUFACTURER

A. The Dimming system equipment specified shall be manufactured, supplied and

commissioned by one of the following complying with the specification.

1. Clipsal

2. Cooper

3. Lutron.

B. Main Contractor to provide three (3) separate proposals for the different brands

mentioned.

Page 191: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. Page 4 of 11 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

1.9 REGULATORY REQUIREMENTS

A. Furnish products listed and classified as suitable for purpose specified and shown.

All the equipment & accessories should be manufactured by one manufacturer & any

deviation from the specification will not be accepted.

B. The system supplier should have minimum 10 years of documentary evidence of

continuous supply, installation, testing and commissioning experience in major

projects, local technical support for maintenance and spare parts availability.

C. Submit Projects reference list executed in Kuwait in order to prove the ability of the

local authorized agent to give a reliable service and maintenance support to the

client.

D. The supplier should have qualified engineering team for installation, testing and

commissioning and technical support to the client for maintenance and trouble

shooting.

1.10 MAINTENANCE SERVICE

A. Furnish service and maintenance of the system for 24 months from the date of

substantial completion.

Page 192: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. Page 5 of 11 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

PART 2 - PRODUCTS

2.1 DIMMER RACKS OR PANELS

A. The rack(s) shall be factory assembled, pre-wired and fitted with 3-phase and neutral

incoming power distribution and output load connections. All power and low voltage

wiring shall be distance segregated.

B. The rack shall be fabricated from 16 gauge sheet steel, suitable for wall or floor

mounting with front access and painted semi matt finish.

C. Cable entry shall be provided top and bottom with separate detachable side panels

for contractor’s access.

D. The rack shall be fitted with a removable hinged (reversible) lockable front cover.

The cover shall be pierced to provide ventilation and sight of the dimmer status.

E. The Dimmer rack shall be available in two sizes, and the modules shall be provided

in the Dimmer Rack as required.

F. The rack shall be fitted and wired with either single or double stacker assemblies

according to size.

G. The terminal connectors for the Lighting circuit loads and the low voltage

connections shall be at one side of the Dimmer Rack and should not be behind the

Dimmer modules.

H. The Dimmer rack shall have a separate Low voltage Break out module for inter

connections of Dimmer racks, connecting to lighting router etc.

I. Pressure pad terminals shall be provided grouped in a L.N.E. arrangement to

accommodate incoming load cables up to 16 sq.mm line, 35 sq.mm neutral and

earth and 4 sq.mm for output load wiring.

J. Each dimmer module shall be protected by a suitably rated Double pole MCB.

K. The dimmer rack shall be fitted & wired with suitable TPN incomer isolator, and

COELCB as mentioned in the DB schedule of points. Above the dimmer rack, an

auxiliary housing / in the extended dimmer rack, shall have required number of

10A/15A MCB’s for outgoing load circuits protection.

2.2 STACKER ASSEMBLY

A. A stacker assembly shall be provided within the dimmer rack to accommodate

dimmer modules & break out unit.

Page 193: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. Page 6 of 11 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

B. The stacker shall be of sheet steel fabrication constructed with a unique 45 high

density support framework for dimmer modules to ensure good ventilation. A rear air

chimney shall be formed to provide an optimized cooling airflow over the dimmer

modules irrespective of the number of modules in either natural or force ventilated

operation.

C. The stacker assembly fitted and wired within the dimmer rack shall also be suitable

for use in other electrical assemblies such as distribution boards and switch panels

subject to local safety and electrical regulations.

D. The stacker assembly shall be suitable for double mounting by removal of a simple

baffle.

E. The stacker shall be fitted with a flexible low voltage motherboard for ease of

assembly.

F. A continuously operating low noise fan shall be available as a simple addition to

maintain air flow efficiency with 20A loads in ambient conditions above 35

centigrade.

2.3 DIMMER MODULE

A. The dimmer module units shall be of plug in hard fired thyristor type and shall

comprise of a two part encapsulated module, universally suitable for all types of

incandescent, halogen, low voltage halogen, compact fluorescent and fluorescent

lamps (with appropriate electronic or wire wound devices where required) and shall

be suitable to interchange with any other dimmer module within a system.

B. Each dimmer module shall contain strictly two independent dimming channels

incorporating 12 bit hard firing Opto-isolated Thyristors with low Q suppression

filtering in a high temperature (130 centigrade) ABS-Polycarbonate molded

enclosure with VO flammability.

C. Each dimmer channel shall be capable of controlling minimum up to 10A load with

convection cooling or 20A load with forced ventilation.

D. Each dimmer channel shall incorporate up to 10 dimming curves including a

switched output, which shall be selected at module face.

E. Each dimmer shall be capable of self-sensing voltage and frequency fluctuations

without affecting light output. Fluctuations in supply frequency shall range between

45 and 56 Hz and supply voltage such that a 10% change will affect light output by a

maximum of 1%.

F. Each dimmer module shall incorporate self-sensing thermal overload protection,

which shall reduce load outputs upon internal temperature rising to 70C and auto

shutdown at 90 centigrade. After the temperature returns to the normal, the lighting

level automatically should come back to the previous preset level.

Page 194: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. Page 7 of 11 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

G. Each dimmer shall be capable of either reducing or shutting down output in the event

of overload being undetected by the input MCB.

H. Each dimmer channel shall be suitable for either serial digital SDim RS485 serial or

0 - 10V analogue signal.

I. Each dimmer shall be fully programmable to allow the soft patching of any output to

any addressed channel.

J. Each module shall incorporate an integral three digits, seven segments red led

display with four operational push buttons. This shall enable the display adjustment

and setting on a cycle menu of the following: Light output status in 10% increments,

raising and lower of light output (also default status), soft patching of two 10A

channels to the same control channel, selection of dimmer response curves, defining

of switch ON and OFF Hysterisis, defining of fall back watch-dog light output levels,

display of error messages owing to over temperature or over current, auto reverse to

default status.

K. All programmed information shall be retained in the Lighting router for minimum of

twenty five years.

L. Maximum heat dissipation from the dimmer module shall not be greater than 3W at

zero load 35W with 2 x 10A dimmers fully loaded and 100w with 2 x 20A dimmers

fully loaded.

M. The dimmer channels shall strictly comply with emission standard EN50 081 Part 1,

immunity standard EN50 082 Part 1, RFI suppression EN50 014, safety standard

EN60 950 and ingress protection rating of IP 30.

2.4 RELAY MODULES

A. Where ever required, Provide addressable relay modules an economical means of

controlling switched (ON / OFF) loads like Metal Halide Lamps, Motor operated

curtains etc. In case of metal halide lamps and inductive loads are to be switched

ON there shall be required rating contactors, through these relay modules. The relay

modules shall be designed for wall mounted or Din rail mounted type fixed in a wall

mounted cabinet for installation in electrical rooms. The relay modules shall be of 8

channels, each with 1X10A changeover contact and shall meet the following

technical specification:

Operating Conditions:

Supply Voltage : 180V – 260V AC

Relay load : Max 10A

Protective Device : self resetting thermal cut-off for electronics

Ambient Temperature : 0 - 40˚C in operation, -10 to + 70˚C in store

Relative Humidity : 0 – 90%(non-condensing

2.5 SCENESET LIGHTING ROUTERS

A. Lighting Router shall be provided to have a central system controller which shall be

capable of storing, generating and coordinating all system stimuli and resultant

actions.

B. The Lighting Router shall have the complete working database of the system.

Page 195: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. Page 8 of 11 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

C. The Lighting router shall directly accept a DMX I/P to offer interactive control of the

Dimmer channels and multiple routers connect via Ethernet, which also provides

general TCP/IP access and system programming, monitoring and scheduling using

the lighting system software.

D. A single Phase power supply shall be provided for the Lighting router and for

Ethernet switch.

E. The Lighting router shall strictly comply with emission standard EN55 015, immunity

standard EN61 547, safety standard EN60 950, IP rating IP10, Isolation 4kV, Storage

temperature -10 to 70 Centigrade and shall be suitable for continuous operation at

40 centigrade.

F. The system shall be programmed using Laptop computer through the Lighting

Routers

G. Ethernet Switch shall be provided near to Lighting router and wired for programming

sockets where ever required.

2.6 SCENE COMMANDER CONTROL STATIONS

A. Local control stations shall be provided to select programmed lighting scene either

manually by means of a scene commander push button station or against timed

commands from a scene scheduler.

B. The control station shall feature a low profile construction and shall comprise of two

elements, a mounting base with wiring access and a decorative polished brass/

brushed stainless steel control fascia plate without the fixing screws on the facia

plate.

C. Scene commander control stations shall be 4 scene and OFF with raise and lower

scene modifiers facility as required. Push buttons shall have variable back

illumination tell back according to light level selected.

D. For switching operation provide ON / OFF Control stations.

E. The scene commander control stations shall be provided with in built infra red

receiver.

Page 196: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. Page 9 of 11 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

2.7 SOFTWARE REQUIREMENT

A. The system Programming, monitoring and scheduling shall be Performed using a

Lighting control software based on windows NT/2000/XP via the Ethernet Link.

B. The system programming access can be from any Ethernet connection point in the

lighting control system. The Lighting system can be a part of an existing Ethernet

installation.

C. Lighting Software shall employ a tree structure to facilitate access and manipulation

of all the system components. The system shall allow offline / online simulation of

program operation and make online control more intuitive.

D. The Lighting system software shall have the capability of Automatic Recognition of

the field components installed in the network.

E. The system programming shall be through a Laptop computer.

F. The Lap top computer shall be plugged in to the Lighting router or Ethernet switch or

Programming socket for programming the system.

G. The programmer shall provide the capability to pre-set all lighting scene

requirements such as light levels, fade times, Scenes naming and circuit numbering

with the aid of the graphical presentation of programming entries, database setting,

pop up menus, job windows and help screens at all stages.

H. The Software shall have the facility of monitoring the status of the circuits that are

connected to the system, which facilitates to find out if the lamps are present / fused.

The system software should have the feature to monitor the dimmer module

temperature.

I. Provide RJ 45 sockets for programming the system and shall be installed in the

location as required by the engineer at site.

2.8 CABLE

Data cable and Ethernet cable shall be provided for the system as recommended by the

manufacturer.

Page 197: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. Page 10 of 11 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine end luminaries to determine suitability for lighting control by means of a

high frequency dimmable electronic ballast with variable output. Analogue control HF

0-10 V DC suitable for operation in ambient temperature up to 35 centigrade.

B. Examine subs rate and supporting grids where any controls are to be fixed.

3.2 INSTALLATION

A. Install in accordance with manufacturers instructions.

B. Install connections to all luminaries in a tidy manner and no wiring shall be left coiled

up.

C. Ensure all items are earth bonded.

D. Location and equipment main incoming power supply etc. shall be coordinated with

electrical contractor.

E. Install dimmer racks and relay panels as mentioned in drawing.

3.3 FIELD QUALITY CONTROL

Operate each luminaries after installation of controls and for proper connection and

operation.

3.4 ADJUSTING

Adjust work under provisions of division 1.

3.5 CLEANING

A. Clean work under provisions of division 1.

B. Clean electrical parts to remove conductive and detritus materials.

C. Remove dirt and debris from any enclosure or item of equipment.

D. Clean photometric control surfaces as recommended by manufacturers.

E. Clean all finishes.

Page 198: PHILIPPINE GENERAL HOSPITAL VARIOUS PROJECTS P05...Alternator Stamford Leroy-Sommer Marathon Kato AVK Caterpillar 16264 Static Uninterruptible Power Supply UPS Liebert Socomec GE Eaton

DIVISION 16 – ELECTRICAL Lighting Control System SECTION 16570

MEINHARDT PHILIPPINES INC. Page 11 of 11 S:\admin\mpi\MP1626_Philippine General Hospital Various Projects\000 - ACTIVE DOCUMENTS\09 - SPECS\2017-06-13_100% CD\P05\Electrical\16570-Lighting

Control System.doc

3.6 DEMONSTRATION

A. Provide systems demonstration under provisions of Division 1.

B. Provide minimum of 24 hours demonstration of system operation.

END OF SECTION