Periodic inspection Periodic inspection 45 Glan Y Gors Inspected by Inspected by: Offaltd Date of Inspection Date of Inspection: 4th May 2016 Prepared By Prepared By: Offa Ltd Prepared for Prepared for: Jay Liptrot Tenant Tenant: Junior Buchanon & Catherine French Refers to Refers to: 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL Date Published Date Published: 10th May 2016

Transcript of Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL....

Page 1: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

Periodic inspectionPeriodic inspection45 Glan Y Gors

Inspected byInspected by:: OffaltdDate of InspectionDate of Inspection:: 4th May 2016Prepared ByPrepared By:: Offa LtdPrepared forPrepared for:: Jay LiptrotTenantTenant::Junior Buchanon & Catherine FrenchRefers toRefers to::45 Glan Y Gors, Prestatyn, DenbighshireLL19 7RLDate PublishedDate Published:: 10th May 2016

Page 2: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

GENERAL INSPECTION NOTESGENERAL INSPECTION NOTESA periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by propertymanager, Lucy Knight. Present at the inspection were the tenants, Junior Buchanon & Catherine French. The property wasclean and tidy and in a good decorative condition. Any maintenance issues have been highlighted for your attention.

CERTIFICATESCERTIFICATESSPACESSPACES

Property Front ExteriorProperty Front Exterior

04/05/2016 10:47 (UTC) at 53.33486217079063 ° ,-3.417643401774967 °

Notes:Notes:The front of the property is in good condition.

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 1 of 12

Page 3: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

Front GardenFront Garden

04/05/2016 10:55 (UTC) at 53.33484184467544 ° ,-3.417696123945916 °

04/05/2016 10:55 (UTC) at 53.33484678999831 ° ,-3.417650777849758 °

Notes:Notes:The tenant has advised that the landlord did agree to replacing the gravel in the front garden, if this correct please advisewhether you are happy to provide this.

Living RoomLiving Room

04/05/2016 10:54 (UTC) at 53.33488136534889 ° ,-3.417633008215034 °

04/05/2016 10:54 (UTC) at 53.33488044333954 ° ,-3.417701823640072 °

Notes:Notes:The living room is clean and tidy and is in good decorative condition.

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 2 of 12

Page 4: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

KitchenKitchen

04/05/2016 10:50 (UTC) at 53.33486155843625 ° ,-3.417814341463165 °

04/05/2016 10:51 (UTC) at 53.33486844052312 ° ,-3.41779528793329 °

04/05/2016 10:51 (UTC) at 53.33486667271292 ° ,-3.417742876181535 °

Notes:Notes:The kitchen is clean and tidy and is in good decorative condition.

ItemItem DescriptionDescriptionFloors UsedUsed

The flooring is non slip vinyl and is in good condition.

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 3 of 12

Page 5: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

KitchenKitchen (continued)(continued)

ItemItem DescriptionDescription

04/05/2016 10:51 (UTC) at 53.3348587907882 ° ,-3.417818891485341 °

Walls UsedUsedThe walls are wallpapered and are in a good condition.

04/05/2016 10:51 (UTC) at 53.33482453604539 ° ,-3.417741386223042 °

Cabinets FlaggedFlagged

The tenant complained that some of her work tops have chipped and also that the gap where thecooker is hasn't enough space to get out easily and asked if it could be considered to increase thisgap.

Floors(continued)

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 4 of 12

Page 6: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

KitchenKitchen (continued)(continued)

ItemItem DescriptionDescription

04/05/2016 10:50 (UTC) at 53.33484536870088 ° ,-3.417740890088031 °

04/05/2016 10:50 (UTC) at 53.33487347709884 ° ,-3.417884285325066 °

BedroomBedroom

04/05/2016 10:52 (UTC) at 53.33493358460565 ° ,-3.417767705399001 °

04/05/2016 10:52 (UTC) at 53.33494448107977 ° ,-3.417799472812021 °

Cabinets(continued)

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 5 of 12

Page 7: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

04/05/2016 10:52 (UTC) at 53.33493127958228 ° ,-3.417814224961603 °

04/05/2016 10:52 (UTC) at 53.33492407114555 ° ,-3.417815649885142 °

Notes:Notes:The bedroom is clean and tidy and is in good decorative condition.

ItemItem DescriptionDescriptionFloors UsedUsed

The flooring is carpeted in brown and is in good condition, no marks present.

04/05/2016 10:52 (UTC) at 53.33493111194421 ° ,-3.417767873037064 °

Walls UsedUsedThe walls are plastered and painted pink and are in a good condition.

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 6 of 12

Page 8: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

BedroomBedroom (continued)(continued)

ItemItem DescriptionDescription

04/05/2016 10:52 (UTC) at 53.33492482551684 ° ,-3.417770806703174 °

Bedroom 2Bedroom 2

04/05/2016 10:53 (UTC) at 53.33489138172318 ° ,-3.417782373729551 °

Notes:Notes:The bedroom is clean and tidy and is in good decorative condition.

Walls(continued)

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 7 of 12

Page 9: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

ItemItem DescriptionDescriptionFloors UsedUsed

The flooring is carpeted in brown and is in good condition, no marks present.

04/05/2016 10:53 (UTC) at 53.33488647830983 ° ,-3.41778622940501 °

Walls UsedUsedThe walls are wallpapered and are in a good condition.

04/05/2016 10:53 (UTC) at 53.33487185188879 ° ,-3.417799472812021 °

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 8 of 12

Page 10: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

Bedroom 3Bedroom 3

04/05/2016 10:53 (UTC) at 53.33486971450348 ° ,-3.417803077030384 °

04/05/2016 10:53 (UTC) at 53.33486971450348 ° ,-3.417803077030384 °

Notes:Notes:The bedroom is clean and tidy and is in good decorative condition.

ItemItem DescriptionDescriptionWalls UsedUsed

The walls are wallpapered and are in a good condition.

04/05/2016 10:53 (UTC) at 53.33489775196959 ° ,-3.417827468368614 °

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 9 of 12

Page 11: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

BathroomBathroom

04/05/2016 10:51 (UTC) at 53.33489008252819 ° ,-3.417753539982641 °

Notes:Notes:The bathroom is clean and tidy and is in good decorative condition.

ItemItem DescriptionDescriptionFloors UsedUsed

The flooring is red no slip vinyl and is in a good condition.

04/05/2016 10:52 (UTC) at 53.33489008252819 ° ,-3.417753539982641 °

Walls UsedUsedThe walls are wallpapered and in a good condition.

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 10 of 12

Page 12: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

BathroomBathroom (continued)(continued)

ItemItem DescriptionDescription

04/05/2016 10:52 (UTC) at 53.33487109751751 ° ,-3.417757563296163 °

Walls(continued)

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 11 of 12

Page 13: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

FLAGGED ADDENDUMFLAGGED ADDENDUMItemItem DescriptionDescriptionKitchen:Cabinets

FlaggedFlagged

The tenant complained that some of her work tops have chipped and also that the gap where thecooker is hasn't enough space to get out easily and asked if it could be considered to increase thisgap.

04/05/2016 10:50 (UTC) at 53.33484536870088 ° ,-3.417740890088031 °

04/05/2016 10:50 (UTC) at 53.33487347709884 ° ,-3.417884285325066 °

Periodic inspectionPeriodic inspection45 Glan Y Gors

Page 12 of 12

Page 14: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081

ELECTRICAL INSTALLATIONCONDITION REPORT

Issued in accordance with British Standard 7671 - Requirements for Electrical Installations by an Approved Contractor orConforming Body enrolled with NICEIC, Warwick House,Houghton Hall Park, Houghton Regis,Dunstable,LU5 5ZX

Contractor's Reference Number

A. DETAILS OF THE CLIENT

Client: Address:OFFA Ffordd william morganSt Asaph

Postcode:

B. PURPOSE OF THE REPORT This report must be used only for reporting on the condition of an existing installation.

Purpose for whichthis report is required:

Landlords Request

Date(s) on which inspection and testing were carried out: 10/09/2015

C. DETAILS OF THE INSTALLATION

Occupier N/A Address 45 glan y gorsPrestatyn

Postcode:

Estimated age of theelectrical installation: 25 years Description of premises:

domestic, commercial,industrial, other(Please state)

DomesticEvidence of alterations

or additions á If yes,estimatedage

5 years

Date of previousinspection:

Unknown Electrical Installation Certificate No or previousPeriodic Inspection or Condition Report No:

UNKNOWN

Records of installation available: á Records held by: NWHA

D. EXTENT OF THE INSTALLATION AND LIMITATIONS ON THE INSPECTION AND TESTING

Extent of the electrical installation covered by this report:

Atleast 10% of each circuit has been inspected during this inspection and test, no floor boards or fixed furniture have been removed to get to electrical equipment, where there are gascookers the cooker supply has only been inspected to the isolator.Only fixed wiring has been inspected and tested .Insulation resistance and R1+R2 test only where shown.

Agreed limitations (including the reasons), if any, on the inspection and testing:

Due to sensitive equipment such as fluorescents and boilers ect the insulation resistance test is only carried out at 250 volts.Tests in most cases have been carried out up to isolators, no fans, central heating systems fixed or portable appliances ect are included within the scope of the test.

Agreed with:

Operational limitations including the reasons (see page No. )

N/A

The inspection and testing have been carried out in accordance with BS 7671, as amended. Cables concealed within trunking and conduits, or cables and conduitsconcealed under floors, in inaccessible roof spaces and generally within the fabric of the building or underground, have not been visually inspected unlessspecifically agreed between the client and inspector prior to the inspection.

E. SUMMARY OF THE CONDITION OF THE INSTALLATION

General condition of the installation (in terms of electrical safety):

Unsatisfactory.

Summary of the condition of the installation continued on additional pages? No Yes Specify page No(s):áOverall assessmentof the installation: SATISFACTORY / UNSATISFACTORY

An ‘Unsatisfactory’ assessment indicates that dangerous (CODE C1) and/or potentiallydangerous (CODE C2) conditions have been identified, or that Further investigation withoutdelay (FI) is required

This report should have been reviewed and confirmed by the registered Qualified Supervisorof the Approved Contractor responsible for issuing it. (See declaration on page 2)

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

Page 1 of 8

Please see the 'Notes for Recipients'

Page 15: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081

ELECTRICAL INSTALLATIONCONDITION REPORT

Please see the 'Guidance for Recipients on theclassification codes' in the 'Notes for Recipients'

F. OBSERVATIONS AND RECOMMENDATIONS FOR ACTIONS TO BE TAKEN

Referring to the attached schedules of inspection and test results, and subject to the limitations at D:

Item No Code Ú

There are no items adversely affecting electrical safety. N/A or The following observations and recommendations forare made

á

Additional Pages? No Yesá Specify page

ÚOne of the following codes, as appropriate, has been allocated to each of theobservations made above to indicate to the person(s) responsible for the installationthe degree of urgency for remedial action:

Code C1 "Danger Present". Risk of injury. Immediate remedial action required.

Code C2 "Potentially dangerous". Urgent remedial action required.

Code C3 "Improvement recommended".

Code FI "Further investigation required without delay".

Please see the notes for recipient for guidance regarding the Classification codes.

1 Main earth is only 10mm C2

2 Main equipotential bonding conductors are only 6mm C2

3 Kitchen light had no defuser C3

4 There is no RCD protection C2

Immediate remedial actionrequired for items:

Urgent remedial actionrequired for items: 4, 1, 2

Further investigation requiredwithout delay for items:

Improvementrecommended for items: 3

G. DECLARATION

I/We, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by my/our signatures below), particulars of whichare described in page 1 (see C), having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the informationin this report, including the observations (see F) and the attached schedules (see H), provides an accurate assessment of the condition of the electricalins ta l la t ion tak ing into account the stated extent of the ins ta l la t ion and the l im i tat ions of the inspect ion and tes t ing (see D ) .I/We further declare that in my/our judgement, the overall assessment of the installation in terms of its suitability for continued use is

SATISFACTORY / UNSATISFACTORY* (see F) at the time the inspection was carried out, and that it should be further inspected as recommended (see I).

*An ‘Unsatisfactory’ assessment indicates that dangerous (CODE C1) and/or potentially dangerous (CODE C2) conditions have been identified, or that Further investigationwithout delay (FI) is required.

INSPECTION, TESTING AND ASSESSMENT BY:

Signature

Name(CAPITALS) JONATHON BENBOW

Position QS

Date: 10/09/2015

REPORT REVIEWED AND CONFIRMED BY:

Signature

Name(CAPITALS) JONATHON BENBOW

(Registered Qualified Supervisor for the Approved Contractor at J)

Date: 10/09/2015

Page 2 of 8

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

Page 16: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081

ELECTRICAL INSTALLATIONCONDITION REPORT

Page 3 of 8

H. SCHEDULES AND ADDITIONAL PAGES

Inspection Schedule: Page(s) No 4,5,6 Additional pages, including additionalsource(s) data sheets: Page No(s)

Schedule of Test Results for the Installation: Page No(s) 8Schedule of Circuit Details for the Installation: Page No(s) 7

The pages identified are an essential part of this report. The report is valid only if accompanied by all the schedules and additional pages identified above.

I. NEXT INSPECTION

I/We recommend that this installation is furtherinspected and tested after an interval of not more than 5 Years (Enter interval in terms of

years, months or weeks, as appropriate)

provided that any items at F which have been attributed a Classification code C1 (danger present) are remedied immediately and that any itemswhich have been attributed a code C2 (potentially dangerous) or FI (further investigation required without delay) are remedied or investigatedrespectively as a matter of urgency. Items which have been attributed a Classification code C3 should be improved as soon aspracticable (see F).

J. DETAILS OF NICEIC APPROVED CONTRACTOR

Trading Title: 1st Class Electrical

Address: 2 Allt-y-graigDyserth

Postcode:LL18 6DE

Telephone number: 01745 571162

Email Address: [email protected]

Enrolment number:(Essential information)

600502

Branch number:(if applicable)

000

K. SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS

System Type(s) Number and Type of Live Conductors Nature of Supply Parameters

Characteristics of Primary SupplyOvercurrent Protective Device(s)

TN-S N/A

TN-C-S á

TN-C N/A

TT N/A

IT N/A

1-phase(2 wire) á2-phase(3 wire) N/A

3-phase(3 wire) N/A

1-phase(3 wire) N/A

3-phase(4 wire) N/A

a.c. á d.c. N/A

2 pole N/A

3 pole N/A

other

Other

NominalVoltage(s): Uþ 400

V230

UÒþ V

Nominalfrequency, fþ

50Hz

Prospective faultcurrent, IÙÄÅ

1.03kA

External earth faultloop impendance, Ñ Å Ç

0.22É

1Number ofsources

Notes:(1) by enquiry

(2) by enquiry or bymeasurement

(3) where more thanone supply, recordthe higher or highestvalues

(4) by measurement

BS(EN) 1361

Type 2b

Rated current 80 A

33 kAShort-circuitcapacity

Confirmation ofsupply polarity á (á)

L. PARTICULARS OF INSTALLATION AT THE ORIGINMeans of Earthing Details of Installation Earth Electrode (where applicable)

Main Switch/Switch-Fuse/Circuit-Breaker/RCD

Distributor'sfacility: á

Installationearth electrode: N/A

Type:(eg rod(s),tape(s))

Electroderesistance, RÕ: (É)

Location:

Method ofmeasurement:

* (applicable only where an RCD is suitable and is used as a main circuit-breaker)

60497-3Type:BS(EN)

2No ofPoles

CopperPrimary supplyconductorsmaterial

16Primary supplyconductorscsa

mmâ

Voltagerating

230

Ratedcurrent,IÐ

100

RCD operatingcurrent, IÜ *

N/A

Rated timedelay*

N/A

RCD operatingtime (at IÜ )*

N/A

V

A

mA

ms

ms

Earthing conductor Main protective bonding conductors Bonding of extraneous-conductive-parts (á)

Earthing and protective bonding conductors

Conductormaterial

Copper Conductormaterial

Copper

Conductorcsa

16 mmâConductor

csa10 mmâ

Connection/ ácontinuityverified

Connection/continuityverified

(á) (á)

Waterinstallation pipes á

Oilinstallation pipes N/A

Gasinstallation pipes á

Lightningprotection N/A

Structuralsteel N/A

Other

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

Please see the 'Notes for Recipients'

Page 17: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081

ELECTRICAL INSTALLATION CONDITION REPORT

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS

Item Description Outcome* Location reference

* All Outcome boxes must be completed'á' indicates Acceptable condition'LIM' indicates a Limitation'N/A' indicates Not applicable

Unacceptable condition state C1 or C2Improvement recommended state C3Further investigation required without delaystate FI(to determine whether danger or potential danger exists)

OutcomeProvide additional comment where appropriate onattached numbered sheets. C1, C2, C3 and FI codeditems to be recorded in Section F of the report.

Page 4 of 8

1.0 Condition/adequacy of distributor's/supply intake equipmentÚ

1.1 Service cable á1.2 Service head á1.3 Distributor's earthing arrangement(s) á1.4 Meter tails - Distributor/ Consumer á1.5 Metering equipment á1.6 Means of main isolation (where present) á

2.0 Presence of adequate arrangements for parallel or switched alternative sources

2.1 Adequate arrangements where a generating set operates as a switched alternative to the public supply N/A

2.2 Adequate arrangements where a generating set operates in parallel with the public supply N/A

3.0 Automatic disconnection of supply

3.1 Main earthing and bonding arrangements

Presence and condition of distributor's earthing arrangement áPresence and condition of earth electrode arrangement N/A

Adequacy of earthing conductor size C2 1

Adequacy of earthing conductor connections áAccessibility of earthing conductor connections áAdequacy of main protective bonding conductor size(s) C2 2

Adequacy of main protective bonding conductor connections áAccessibility of main protective bonding connections áAccessibility and condition of other protective bonding connections áProvision of earthing/bonding labels at all appropriate locations á

3.2 FELV

Source providing at least simple separation N/A

Plugs, socket-outlets and the like not interchangeable with those of other systems within the premises N/A

3.3 Reduced low voltage

Adequacy of source N/A

Plugs, socket-outlets and the like not interchangeable with those of other systems within the premises N/A

4.0 Other methods of protection (where the methods of protection listed below are employed, details should be provided on separate sheets)

4.1 Double insulation á4.2 Reinforced insulation N/A

4.3 Use of obstacles á4.4 Placing out of reach N/A

4.5 Non-conducting location N/A

4.6 Earth-free local equipotential bonding N/A

4.7 Electrical separation for more than one item of equipment á

5.0 Distribution equipment

5.1 Adequacy of working space/accessibility of equipment á5.2 Security of fixing á5.3 Condition of insulation of live parts á5.4 Adequacy/security of barriers á5.5 Condition of enclosure(s) in terms of IP rating á5.6 Condition of enclosure(s) in terms of fire rating á5.7 Enclosure not damaged/deteriorated so as to impair safety á5.8 Presence of main switch(es), linked where required á5.9 Operation of main switch(es) (functional check) á5.10 Correct identification of circuit protective devices á5.11 Adequacy of protective devices for prospective fault current á5.12 RCD(s) provided for fault protection - includes RCBOs C2 4

5.13 RCD(s) provided for additional protection - includes RCBOs C2 4

Page 18: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081

ELECTRICAL INSTALLATION CONDITION REPORT

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS

Item Description Outcome* Location reference

* All Outcome boxes must be completed'á' indicates Acceptable condition'LIM' indicates a Limitation'N/A' indicates Not applicable

Unacceptable condition state C1 or C2Improvement recommended state C3Further investigation required without delaystate FI(to determine whether danger or potential danger exists)

OutcomeProvide additional comment where appropriate onattached numbered sheets. C1, C2, C3 and FI codeditems to be recorded in Section F of the report.

Page 5 of 8

5.14 RCD(s) provided for protection against fire - includes RCBOs C2 4

5.15 Manual operation of circuit-breakers and RCDs to prove disconnection C2 4

5.16 Presence of RCD retest notice at or near equipment where required á5.17 Presence of diagrams, charts or schedules at or near equipment, where required á5.18 Presence of non-standard (mixed) cable colour warning notice at or near equipment where required á5.19 Presence of alternative/additional supply arrangement warning notice(s) at or near equipment where required á5.20 Presence of replacement next inspection recommendation label á5.21 Presence of other required labelling (specify) á5.22 Examination of protective device(s) and base(s); correct type and rating (no signs of unacceptable thermal damage,

arcing or overheating)á

5.23 Single-pole switching or protective devices in line conductors only á5.24 Protection against mechanical damage where cables enter equipment á5.25 Protection against electromagnetic effects where cables enter metallic enclosures N/A

6.0 Distribution/final circuits

6.1 Identification of conductors á6.2 Cables correctly supported throughout their length á6.3 Condition of insulation of live parts á6.4 Non-sheathed cables protected by enclosure in conduit, ducting or trunking á6.5 Suitability of containment systems for continued use (including flexible conduit) á6.6 Cables correctly terminated in enclosures (indicate extent of sampling in Section D of report) á6.7 Confirmation of indication that SPD(s) are functional á6.8 Confirmation that ALL conductor connections, including connections to busbars are correctly located in terminals and

are tight and secureá

6.9 Examination of cables for signs of unacceptable thermal and mechanical damage/deterioration á6.10 Adequacy of cables for current-carrying capacity with regard to the type and nature of installation á6.11 Adequacy of protective devices; type and rated current for fault protection á6.12 Presence and adequacy of circuit protective conductors á6.13 Co-ordination between conductors and overload protective devices á6.14 Cable installation methods/practices appropriate to the type and nature of installation and external influences á6.15 Cables where exposed to direct sunlight, of a suitable type á6.16 Cables installed under floors, above ceilings, in walls / partitions, adequately protected against damage

installed in prescribed zones (see Section D. Extent and limitations) áincorporating earthed armour or sheath, or installed within earthed wiring system, or otherwise protected against mechanical damage by nails, screws and the like (see Section D. Extent and limitations)

N/A

6.17 Provision of additional protection by 30 mA RCD

Ú for mobile equipment not exceeding a rating of 32 A for use outdoors C2 4

Ú for all socket-outlets of rating 20 A or less, unless exempt C2 4

Ú for cables installed in walls / partitions at a depth of less than 50 mm C2 4

Ú for cables installed in walls / partitions containing metal parts regardless of depth C2 4

6.18 Provision of fire barriers, sealing arrangements and protection against thermal effects á6.19 Band II cables segregated/separated from Band I cables á6.20 Cables segregated/separated from non-electrical services á6.21 Termination of cables at enclosures (identify numbers and locations of items inspected in Section D)

Connections under no undue strain áNo basic insulation of a conductor visible outside an enclosure áConnections of live conductors adequately enclosed áAdequacy of connection at point of entry to enclosure (gland, bush or similar) á

6.22 General condition of wiring systems á6.23 Temperature rating of cable insulation á6.24 Condition of accessories including socket-outlets, switches and joint boxes á6.25 Suitability of accessories for external influences á6.26 Single-pole switching or protective devices in line conductors only á6.27 Adequacy of connections, including cpcs, within accessories and to fixed and stationary equipment - identify /record

numbers and locations of items inspectedá

Page 19: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081

ELECTRICAL INSTALLATION CONDITION REPORT

This report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS

Item Description Outcome* Location reference

* All Outcome boxes must be completed'á' indicates Acceptable condition'LIM' indicates a Limitation'N/A' indicates Not applicable

Unacceptable condition state C1 or C2Improvement recommended state C3Further investigation required without delaystate FI(to determine whether danger or potential danger exists)

OutcomeProvide additional comment where appropriate onattached numbered sheets. C1, C2, C3 and FI codeditems to be recorded in Section F of the report.

Page 6 of 8

7.0 Isolation and switching

7.1 Isolators

presence and condition of appropriate devices áacceptable location (state if local or remote) ácapable of being secured in the OFF position ácorrect operation verified áclearly identified by position and/or durable marking(s) áWarning label posted in situations where live parts cannot be isolated by the operation of a single device á

7.2 Switching off for mechanical maintenance

presence and condition of appropriate devices áacceptable location ácapable of being secured in the OFF position ácorrect operation verified áclearly identified by position and/or durable marking(s) á

7.3 Emergency switching/stopping

presence and condition of appropriate devices áreadily accessible for operation where danger might occur ácorrect operation verified áclearly identified by position and/or durable marking(s) á

7.4 Functional switching

presence and condition of appropriate devices ácorrect operation verified á

8.0 Current-using equipment (permanently connected)

8.1 Condition of equipment in terms of IP rating á8.2 Equipment does not constitute a fire hazard á8.3 Enclosure not damaged/deteriorated so as to impair safety á8.4 Suitability for the environment and external influences á8.5 Security of fixing á8.6 Cable entry holes in ceiling above luminaires, sized or sealed so as to restrict the spread of fire (indicate extent of

sampling in Section D of report)8.7 Recessed luminaires (e.g. downlighters)

correct type of lamps fitted N/A

installed to minimise build-up of heat by use of "fire rated" fittings, insulation displacement box or similar N/A

no signs of overheating to surrounding building fabric N/A

no signs of overheating to conductors/terminations N/A

9.0 Location(s) containing a bath or shower

9.1 Additional protection by RCD not exceeding 30 mA

for low voltage circuits serving the location C2 4

for low voltage circuits passing through Zone 1 and Zone 2 not serving the location C2 4

9.2 Where used as a protective measure, requirements for SELV or PELV are met N/A

9.3 Shaver sockets comply with BS EN 61558-2-5 or BS 3535 N/A

9.4 Presence of supplementary bonding conductors unless not required by BS 7671: 2008 á9.5 Low voltage (e.g. 230 volts) socket-outlets sited at least 3 m from zone 1 á9.6 Suitability of equipment for external influences for installed location in terms of IP rating á9.7 Suitability of equipment for installation in a particular zone á9.8 Suitability of current-using equipment for a particular position within the location á

10.0 Other special installations or locations

List special locations present, if any. List the results of particular inspections applied (a separate page is required for each location). N/A

N/A

N/A

N/A

N/A

N/A

Page 20: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

Page 7 of 8

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081

SCHEDULE OF CIRCUIT DETAILSFOR THE PRIMARY DISTRIBUTION BOARD

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

TO BE COMPLETED IN EVERY CASE TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN OF THE INSTALLATION*

Location ofdistribution board:

Hallway

Distributionboard designation: DB001---

Supply to distributionboard is from:

No ofphases:

Nominalvoltage: V

Overcurrent protective device for the distribution circuit:Associated

RCD (if any): BS(EN)

Type:BS(EN) Rating: A RCD No

of poles: IÜ mA

Þ See Table 4A2 of Appendix 4 of BS 7671

CODES FOR TYPE OF WIRINGA B C D E F G H

Thermoplasticinsulated/

sheathed cables

Thermoplasticcables in

metallic conduit

Thermoplasticcables in non

metallic conduit

Thermoplasticcables in

metallic trunking

Thermoplasticcables in non

metallic trunking

Thermoplastic/SWA cables

Thermosetting/SWA cables

Mineral-insulated

cables

O (Other - please state)

* In such cases, details of the distribution (sub-main) circuit(s), together with the test results for the circuit(s), must also be provided, on continuation schedules.

See next page for

Schedule of Test ResultsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

CIRCUIT DETAILS

Cir

cuit

num

ber

and

line

Circuit designationT

ype

of w

irin

g(s

ee c

ode

belo

w)

Ref

eren

ce

Þ

met

hod

Num

ber

ofpo

ints

ser

ved Live

(mmâ)

Circuitconductors: csa

cpc

(mmâ)

Max

. dis

conn

ecti

onti

me

perm

itte

dby

BS

767

1

(s)

BS (EN)

Typ

e

Rat

ing

(A)

Overcurrent protective devices

Sho

rt-c

ircu

itca

paci

ty

(kA)

RCD

Ope

rati

ngcu

rren

t, IÜ

(mA)

Max

imum

Öpe

rmit

ted

by B

S 7

671

(É)

1 Shower A B 2 6 2.5 0.4 60898 B 40 6 0.92

2 Cooker A B 2 6 2.5 0.4 60898 B 32 6 1.15

3 Sockets A B 14 2.5 1.5 0.4 60898 B 32 6 1.15

4 Immersion A B 2 4 2.5 0.4 60898 B 16 6 2.3

5 Lights A B 7 1 1 0.4 60898 B 6 6 6.13

Page 21: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection

Page 8 of 8

Ori

gin

al

(To

the

pers

on o

rder

ing

the

wor

k)

This certificate is not valid if the serialnumber has been defaced or altered IPN4/0304081

SCHEDULE OF TEST RESULTSFOR THE PRIMARY DISTRIBUTION BOARD

TO BE COMPLETED ONLY IF THE DISTRIBUTION BOARD IS NOT CONNECTEDDIRECTLY TO THE ORIGIN OF THE INSTALLATION

Characteristics at this distribution board

Confirmation of supply polarity* See note below

Ö É

IÙ kA

*

*

At IÜ ms

At 5IÜ ms

Operating timesof associated

RCD (if any)

Phase sequence confirmed (where appropriate) N/A

Test instruments (serial numbers) used:

Earth fault loopimpedance 5988

Insulationresistance 5988

Continuity 5988

RCD 5988

Multifunction

Other

* Note: Where the installation can be supplied by more than one source, such as a primary source (eg public supply) and a secondary source (eg standby generator), the higher or highestvalues must be recorded.

TESTED BY

Signature:

Date oftesting: 10/09/2015Name:

(CAPITALS) JONATHON BENBOW

Position: QS

See previous page for

Schedule of Circuit DetailsThis report is based on the model forms shown in Appendix 6 of BS7671Published by Certsure LLP. Certsure LLP operates the ELECSA & NICEIC brands. Copyright Certsure LLP (January 2015)©

TEST RESULTS

Cir

cuit

num

ber

and

line

rã(Line)

rÐ(Neutral)

Ring final circuits only(measured end to end)

rå(cpc) Rã + Rå

Circuit impedances(É)

All circuits(At least one column

to be completed)

Line/Line Ú

(MÉ)

Line/Neutral Ú

(MÉ)

Line/Earth Ú

(MÉ)

Insulation resistance

Neutral/Earth

(MÉ)

Polarity

(á)

Maximummeasured earth

fault loopimpedance, Ö

(É)

at IÜ

(ms)

RCD operatingtimes

at 5IÜ

(if applicable)

(ms)

Testbutton

operation

(á)

1 N/A N/A N/A 999 999 999 á 0.36

2 N/A N/A N/A 999 999 999 á N/A

3 0.44 0.50 0.87 N/A N/A N/A 999 999 999 á 0.71

4 N/A N/A N/A 999 999 999 á 0.45

5 N/A N/A N/A 999 999 999 á 0.95

Page 22: Periodic inspection · A periodic inspection on 45 Glan Y Gors, Prestatyn, Denbighshire LL19 7RL. Conducted on 4th May 2016 by property manager, Lucy Knight. Present at the inspection