PERFORMANCE OF OFFICE BUILDING INTEGRATED PHOTOVOLTAIC FOR WINDOWS UNDER SEMI-ARID CLIMATE IN ALGERIA MESLOUB ABDELHAKIM A thesis submitted in fulfilment of the requirements for the award of the degree of Doctorate of Philosophy Faculty of Built Environment and Surveying Universiti Teknologi Malaysia March 2019

Transcript of PERFORMANCE OF OFFICE BUILDING INTEGRATED...

Page 1: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

PERFORMANCE OF OFFICE BUILDING INTEGRATED PHOTOVOLTAIC

FOR WINDOWS UNDER SEMI-ARID CLIMATE IN ALGERIA

MESLOUB ABDELHAKIM

A thesis submitted in fulfilment of the

requirements for the award of the degree of

Doctorate of Philosophy

Faculty of Built Environment and Surveying

Universiti Teknologi Malaysia

March 2019

Page 2: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

iii

DEDECATION

To my beloved parents, wife, my daughter Leen, sisters and friends

Page 3: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

iv

ACKNOWLEDGMENTS

In the Name of Allah, the Beneficent, the Merciful. First of all, I must give

thanks to Allah who gave me the ability, patience and has helped me to complete this

study. Peace and blessing be upon our prophet Mohammed.

I would like to express special thanks and gratitude to my supervisor Assoc.

Prof. Dr. Mohd Zin bin Kandar for his guidance, patience, dedication, and

encouragement during my study at UTM. I have the highest respect to Dr.Dodo

Yakubu and admiration for his generous support and guidance during all stages in

my PhD degree.

I would like to give further thanks to those people who supported me in

carrying out this research. Especially, my beloved parents, wife, sisters and my

Aunts for their support and constant encouragement to me during my study. They

have always asked Allah to help me in their prayers. May Allah bless and protect

them.

Page 4: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

v

ABSTRACT

Building integrated photovoltaic (BIPV) has become the most significant

alternative form of renewable energy for producing clean energy and to protect the

environment. In Algeria, some problems arise due to the high energy consumption levels

of building sector. Large amounts of this energy are lost through the external envelope

façade, because of poor window design. Therefore, this research aimed to investigate the

optimum BIPV windows performance for overall energy consumption (OEC) in typical

office buildings in the semi-arid climate. Field measurements on a tested office building

were carried out during the spring and summer seasons for the calibration and validation

of Energy-plus and Integrated Environment Solution Virtual Environment (IES-VE)

software. The data was analysed and used to develop a model for (OEC) simulation. The

results of the investigation from the site measurements show that the BIPV window

application provides a sufficient quantity of uniform daylight with only 20% Visible

Light Transmittance (VLT), plus a comfortable indoor temperature and a considerable

amount of clean energy production. The base-model and nine commercially-available

BIPV modules, with different Window Wall Ratio (WWR), cardinal orientation and tilt

angles were applied in an extensive simulation exercise. The simulation was carried out

using Energy-plus to evaluate the energy generated through simple and equivalent one-

diode models. The thermal performance used the Ideal load Air System (ILAS) model.

In addition to IES-VE for the assessment of visual comfort and daylighting

performance, through a combination of daylight control method, Useful Daylight

Illuminance (UDI) and CEI glare index (CGI) were done. The results from this study

revealed that the optimum BIPV window design differentiates in each orientation; which

is the double glazing PV modules (A) with medium WWR and 20% VLT in the

Southern facade, 30% VLT toward the East-West axis. Meanwhile, the North

orientation is not suitable the application of BIPV window. The Maximum energy

saving can be obtained with a 60% toward the South orientation by double glazing PV

module (D). On the other hand, the PV modules minimize significantly the glare index

comparing the base-model. The result established that the energy output percentages in a

3D model can be used by architects and designers in the early stages of design. Thus, the

adoption of optimum BIPV window shows a significant improvement of the overall

energy saving and visual comfort to deem them as an essential application in the semi-

arid climate.

Page 5: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

vi

ABSTRAK

Bangunan Fotovoltaik bersepadu (BIPV) telah menjadi alternatif yang paling

penting untuk tenaga boleh diperbaharui bagi menghasilkan tenaga bersih dan juga

untuk melindungi alam sekitar. Di Algeria, beberapa masalah timbul disebabkan tahap

penggunaan tenaga tinggi sektor bangunan. Sejumlah besar tenaga ini hilang melalui

permukaan luar bangunan disebabkan oleh reka bentuk tingkap yang lemah. Oleh itu,

kajian ini bertujuan untuk mengkaji prestasi tingkap BIPV yang optimum untuk

penggunaan tenaga keseluruhan (OEC) di bangunan pejabat biasa di bawah iklim separa

gersang. Ukuran lapangan bagi pejabat yang diuji telah dilakukan pada musim bunga

dan musim panas untuk tujuan kalibrasi dan validasi perisian Energy-plus dan

Integrated Environment Solution Virtual Environment (IES-VE). Data telah dianalisis

dan digunakan untuk membangunkan model untuk simulasi (OEC). Keputusan kajian

dari pengukuran di tapak menunjukkan bahawa aplikasi tetingkap BIPV menyediakan

kuantiti yang mencukupi dan pencahayaan siang seragam, dengan hanya 20%,

Transmisi Cahaya Boleh Dilihat (VLT) ditambah dengan suhu dalaman yang selesa dan

pengeluaran tenaga bersih yang banyak. Model asas dan sembilan modul BIPV yang

tersedia secara komersial, dengan Nisbah Dinding Tingkap (WWR) yang berbeza,

orientasi kardinal dan sudut condong digunakan untuk latihan simulasi yang

menyeluruh. Simulasi dijalankan menggunakan Energy-plus untuk menilai tenaga

melalui model satu-diod yang sederhana, bersamaan dengan prestasi terma

menggunakan model Sistem Udara Beban Ideal (ILAS). Sebagai tambahan kepada

Persekitaran Maya Penyelesaian Alam Sekitar Bersepadu (IES-VE) untuk penilaian

keselesaan visual dan pencahayaan siang hari, melalui gabungan kaedah kawalan siang

hari, pencahayaan siang hari yang berguna (UDI) dan CEI indeks silau (CGI),

dilaksanakan daripada kajian ini mendedahkan bahawa Reka bentuk tetingkap BIPV

optimum dibezakan mengikut, setiap orientasi; yang merupakan modul PV kaca

berganda (A) dengan WWR sederhana dan 20% di permukaan Selatan, 30% VLT ke

arah paksi Timur-Barat. Sementara itu, orientasi Utara tidak sesuai untuk penggunaan

tetingkap BIPV. Penjimatan tenaga maksimum sehingga 60% bagi orientasi Selatan

menggunakan PV kaca berganda (D). Modul PV meminimumkan secara ketara indeks

silau berbanding dengan model asas. Hasil kajian telah menetapkan bahawa peratusan

penghasilan tenaga dalam model 3D boleh digunakan oleh arkitek dan pereka pada

peringkat awal rekabentuk. Justeru, penggunaan tetingkap BIPV yang optimum

menunjukkan penambahbaikan yang ketara terhadap penjimatan tenaga dan keselesaan

visual secara keseluruhan dan ia boleh dianggap sebagai aplikasi penting di kawasan

iklim separa gersang.

Page 6: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

vii

TABLE OF CONTENTS

CHAPTER TITLE PAGE

DECLARATION ii

DEDECATION iii

ACKNOWLEDGMENTS iv

ABSTRACT v

ABSTRAK vi

TABLE OF CONTENTS vi

LIST OF TABLES xii

LIST OF FIGURES xiii

LIST OF ABBREVIATIONS xix

LIST OF APPENDICES xxi

1 INTRODUCTION 1

1.1 Background 1

1.2 Problem Statement 7

1.3 Research Gap 8

1.4 Research Aims 9

1.5 Research Objective 9

1.6 Research Questions 10

1.7 Scope of the Study 11

1.8 Significance of the Research 12

1.9 Organisation of Thesis 12

2 LITERATURE REVIEW 15

2.1 Introduction 15

2.2 Building Integrated Photovoltaic (BIPV) Technology 15

2.2.1 BIPV Definition and Concepts 16

2.2.2 Hierarchical of Photovoltaic Configurations 18

Page 7: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

viii

2.2.3 Design of Building-integrated photovoltaic

module 19

2.2.4 Potential value and economic development of

BIPV 21

2.2.5 Overview on Photovoltaic technology in Algeria

context 23

2.3 Building integrated Photovoltaic (BIPV) Window 27

2.3.1 Classification of BIPV window generations 27

2.3.2 Comparison between thin film and crystalline

silicon 31

2.4 Factors Influences on the Electrical Performance of

BIPV windows 32

2.4.1 Energy output Performance of tilted BIPV

window 34

2.5 Climatic condition factor effect on BIPV window

performance in Algeria context 36

2.5.1 The Solar radiation 36

2.5.2 The Sun path 39

2.5.3 The Sky Conditions 40

2.6 Architectural design factor effect on Overall energy

performance of BIPV window 43

2.6.1 The Window to wall ratio (WWR) 44

2.6.2 The BIPV window orientation 46

2.7 Research on BIPV Systems 46

2.7.1 The performance of Heat Transfer models of

BIPV window 47

2.7.2 Experimental application studies of Energy

Performance of BIPV window 49

2.8 Daylighting in office Building Design 51

2.8.1 Visual Comfort in Office 51

2.8.2 Visual Task in Office 52

Page 8: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

ix

2.8.3 Metrics for evaluating Daylighting availability

and quality in office 52

2.8.3.1 WorkPlane Illuminance (WPI) 52

2.8.3.2 Illuminance level 53

2.8.3.3 The daylight factor 55

2.8.3.4 Dynamic daylight metric (climate-based) 55

2.8.3.5 Uniformity 57

2.8.3.6 Related-Glare indices 57

2.8.4 Unilateral lighting mode in Algerian office 59

2.8.5 Daylighting performance of BIPV window 60

2.9 Overall Performance of BIPV Windows 62

3 Methodology 67

3.1 Introduction 67

3.2 Research framework 67

3.3 Experiment Conditions setup 69

3.3.1 Measurement Procedure 69

3.3.1.1 Location, Climate Data and general

considerations 69

3.3.1.2 Design Concept of common single office

building (Base-model) 71

3.3.1.3 PV Module selected for the experiment 72

3.3.1.4 Daylighting measurement 74

3.3.1.5 Heating transfer (heat flux) measurement 77

3.3.1.6 Monitoring of Electrical measurement‘s

instrument 78

3.3.2 Energy simulation software tools 80

3.4 Validation procedure 81

3.5 The building Simulation performance 83

3.5.1 BIPV modules selection for simulation 86

3.5.2 The Simulation Procedure 89

3.5.3 Energy output model simulation 90

3.5.4 Thermal simulation 92

Page 9: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

x

3.5.5 Daylighting simulation 94

3.5.6 The optimum design of overall energy

performance 100

3.6 Summary 101

4 RESULTS AND ANALYSIS 103

4.1 Introduction 103

4.2 Results of Experiment and Validation 103

4.2.1.1 Calibration of instruments result 103

4.2.1.2 Energy output model results and

validation 106

4.2.1.3 Thermal performance results and

validation 109

4.2.1.4 Daylighting results and validation 113

4.3 Summary of the experimental result 118

4.4 Simulation results 119

4.4.1 Analysis of vertical solar radiance (Meteonorm

Data-base) 119

4.4.2 Evaluation of the energy output of different BIPV

modules 124

4.4.2.1 Assessment of the energy output with

different tilted angle 125

4.4.2.2 Assessment of Cell temperature of BIPV

windows against energy output in

different tilt angle 130

4.4.3 Analytical Criteria for Daylight Simulation 132

4.4.3.1 Daylighting and lighting energy

performance of base-model 132

4.4.3.2 Daylighting and lighting energy

performance of BIPV windows modules 136

4.4.4 Evaluation of Cooling and Heating energy

consumption of base-model against BIPV

window modules 141

Page 10: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xi

4.4.5 Evaluation of optimum overall energy

performance of different BIPV windows against

base-model 148

4.4.5.1 Energy saving of BIPV windows modules

against base-model 160

4.5 Summary of simulation results 164

5 CONCLUSION, RECOMMENDATIONS, AND

FURTHER STUDY 167

5.1 Introduction 167

5.2 Review of Research Objectives 167

5.3 Significant findings 171

5.4 Practical Implication and Application of the Research 172

5.5 Research Limitations 172

5.6 Recommendations 173

5.7 Recommendations for Further Study 176

5.8 Review 176

5.9 Summary 177

REFERENCES 178

6 Appendix A 198

7 Appendix B 208

8 Appendix C 213

9 Appendix D 218

10 Appendix E 221

11 Appendix F 223

12 Appendix G 227

13 Appendix H 229

14 Appendix I 246

Page 11: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xii

LIST OF TABLES

TABLE NO. TITLE PAGE

Table ‎2.1: summary of add value building-integrated photovoltaic, Source: (Watt, 2001)

....................................................................................................................................21

Table ‎2.2: Latest sub-module efficiencies measured under the global AM1.5 spectrum

(1000 W/m2) at 25°C (Green, Emery, Hishikawa, Warta, & Dunlop, 2015) .................30

Table ‎2.3: Received sunlight per year in Algeria in relation to climatic regions, Source:

(Yacef et al., 2014) ......................................................................................................38

Table ‎2.4: glare discomfort indices scale of different metrics ......................................58

Table ‎3.1: Electrical and Thermo-optical characteristics of BIPV windows used in this

experiment under Standard Test Condition (STC) ........................................................74

Table ‎3.3: Room index measurement points norms......................................................76

Table ‎3.4: BIPV windows characteristics, for more details check the appendix A ........88

Table ‎3.5: description of mathematical variable used in simple model .........................90

Table ‎3.6: simulation parameter and operation condition of thermostat set point .........94

Table ‎3.7: Thermal properties of external boundary of typical office building in Algeria,

source: (Yassine & Lotfi, 2011) ...................................................................................94

Table‎4.1: MBE and RMSE of daily energy output model used in the experiment ...... 108

Table ‎4.2: Component overview (annual values) ....................................................... 125

Table ‎4.3: Summary of Performance Indicator Criteria for Daylight Simulation (ISO).

.................................................................................................................................. 132

Table ‎4.4: The useful daylight illuminance of BIPV window modules with different

transparency (10%, 20%, and 30%) against the base-model in cardinal orientations ... 139

Table ‎4.5: CIE glare index of optimum PV modules in cardinal orientation against base-

model in solstice summer, winter and equinox Spring ................................................ 159

Table ‎5.1: Summary of Findings in Relation to the objectives. .................................. 170

Page 12: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xiii

LIST OF FIGURES

FIGURE NO. TITLE PAGE

Figure ‎1.1: : The amount of solar energy could be exploited, source: (IEA, 2013) ....2

Figure ‎1.2: The average of building‘s energy consumption shown as a percentage of

national energy consumption and in relative international form, Source: (IEA online 4

Figure ‎1.3: Final energy consumption by sector in Algeria -Zone 2. under semi-arid

climate, Source: (APRUE, 2015)...............................................................................4

Figure ‎1.4: The Application of BIPV window technology in the world, Source:

(Biyik et al., 2017) ....................................................................................................7

Figure‎2.1: example of BIPV and BAPV system installation in façade (A) and the

roof (B), the BIPV presented on the left pic. Source: (A) URL:

www.onyxsolar.com/genyo-building (B)(K. Park, Kang, Kim, Yu, & Kim, 2010) .. 17

Figure ‎2.2: BIPV integration concepts, Source: (Laura Maturi, 2018). ................... 18

Figure ‎2.3: The hierarchical PV Configurations and PV elements, Source: (Geoff

Stapleton, 2013) ...................................................................................................... 18

Figure ‎2.4: locations of a building where photovoltaic elements can be integrated

into. Source: Naps Systems Oy., Photovoltaic in Buildings - a brief introduction,

2001........................................................................................................................ 19

Figure ‎2.5: Product categorization used throughout the product benchmark analysis

Source: (Verberne et al., 2015) ................................................................................ 20

Figure ‎2.6: Photovoltaic energy growth and (price) by sector, Source: (IEA, 2014)

............................................................................................................................... 23

Figure ‎2.7: R&D Institutional Framework in the REN ........................................... 24

Figure ‎2.8: installed 268MW of solar in 2015, source: (Tom Kenning, 2016) URL:

www.pv-tech.org/news/algeria-installed-268mw-of-solar-in-2015 .......................... 25

Figure ‎2.9: Contribution of Renewable Energy for power generation (PV system) in

Algeria. ................................................................................................................... 26

Page 13: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xiv

Figure ‎2.10: Example of first generation BIPV window module ............................. 28

Figure ‎2.11: Example of second and third generation BIPV windows module ........ 29

Figure ‎2.12: Photovoltaic generations based on solar cell ....................................... 29

Figure ‎2.13: comparison between the effect of thin film (a-si) and c-si under low

light intensity and high temperature. Source: (Maurus et al., 2004) ......................... 32

Figure ‎2.14: 2D energy output plots of PV arrays according to various angle-

settingsLeft: Effect of tilt angle & orientation on total yearly energy output of PV

array (east south facing)Middle: Effect of tilt angle and orientation on total yearly

energy output of PV array (W,S facing)Right: Percentage of total yearly energy

output of PV array at different tilt angles and orientations ....................................... 34

Figure ‎2.15: The annual solar radiation data in m2 for the world in 2016 (solarGis,

2016).of a typical Campbell- Stokes sunshine recorder, Source:

solargis.info/doc/free-solar-radiation-maps-DNI ..................................................... 36

Figure ‎2.16: Distribution of Direct and diffuse radiance in Tebessa (Algeria) ......... 38

Figure ‎2.17: (a) the location of Tebessa city (b) sunshine hours & solar radiance in

Tebessa (Weather station in Tebessa) ...................................................................... 39

Figure ‎2.18: Sun path of the city of Tebessa by IES-VE 2017 ................................ 40

Figure ‎2.19: Result Zoning of Daylight Availability over Algeria (Zemmouri, 2010)

............................................................................................................................... 41

Figure ‎2.20: Monthly Distribution of Extreme Conditions of Sky Mode (Dj-Rouag,

2001). ..................................................................................................................... 42

Figure ‎2.21: Window design architectural Parameters, source: (Carmody et al.,

2004) modified by researcher 43

Figure ‎2.22: BIPV façade at Bagatelos Architectural Glass Systems Inc,

Sacramento, CA, (Henson, 2012) ............................................................................ 45

Figure ‎2.23: Tthe minimum Illuminance level based on International Standard ISO

8995-1:2002 (CIE 2001/ISO 2002) for visual performance in office (A) WPI

horizontal for drawing task (B) for computer .......................................................... 55

Figure ‎2.24: Approximate Daylighting Penetration, Source: (Robertson, 2003) ...... 59

Figure ‎2.25: facade configurations used in the study 1. Base-case, 2. Half STPV and

3- Full STPV configuration. .................................................................................... 60

Figure ‎3.1: Research framework ............................................................................ 68

Page 14: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xv

Figure ‎3.2: The location and orientation of the case study being investigated (an

office building in University of Tébessa)................................................................. 70

Figure ‎3.3: Annual averagetemperature of Tebessa (Algeria), source: (Meteonorm,

2010) ...................................................................................................................... 70

Figure ‎3.4: Climate data of Tebessa city extracted from IESVE software, version

2016........................................................................................................................ 71

Figure ‎3.5: Design concept of office building chosen for experiment (interior, Plan

of typical floor, Exterior 3D model) ........................................................................ 72

Figure ‎3.6: (a) Schematic design and dimension of module (b) (pin) layers

components of module (c) structure of amorphous silicon module type used for the

experiment (d) PV module used in this experiment ................................................. 73

Figure ‎3.7: Data logger, Position of sensor and Base-U-1 & Coupler ..................... 75

Figure ‎3.8: Grids of measurements within office building ...................................... 76

Figure ‎3.9: (a) Positions for measuring heat flux and air temperature, (b) FluxTeq

data reader and heat flux sensor placed on a window surface during a cold day ....... 78

Figure ‎3.10: (A,B) system used to evaluate the maximum energy output of BIPV

windows under real conditions, (C) the recording of solar charge controller (MPPT).

............................................................................................................................... 79

Figure ‎3.11: Typical floor 3d model for Validation ................................................ 82

Figure ‎3.12: Summary of validation procedure of this study ................................... 83

Figure ‎3.13: 3D base model office building used for of daylighting validation

sketchup 2015. ........................................................................................................ 84

Figure ‎3.14: Proposed model for evaluation the energy output of BIPV windows in

different tilt angle and cardinal, intermediate orientations (Geometric A) ................ 85

Figure ‎3.15: Proposed 3D model for optimization simulation stage (Geometric B) . 86

Figure ‎3.16: BIPV windows modules types used for the simulations ...................... 88

Figure ‎3.17: A schematic diagram of the simulation methodology ......................... 89

Figure ‎3.18: schematic design of Equivalent one diode model ................................ 91

Figure ‎3.19: schedule overview heating and cooling (HVAC) system (open-studio)

............................................................................................................................... 93

Figure ‎3.20: Placement of the sensor on the centre of references office .................. 96

Figure ‎3.21: Daily Profile schedule of light control in (IESVE, 2016) ................... 96

Page 15: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xvi

Figure ‎3.22: possible cases of lighting controls vs Illuminance level (a) lower than

minimum level of illuminance (b) higher than targeted illuminance level (c) both

cases in one day. ..................................................................................................... 98

Figure ‎3.23: Example of minimum Day-lit zone of (10% WWR) ........................... 99

Figure ‎3.24: flowchart explains the part of determination the optimum BIPV

window design. ..................................................................................................... 101

Figure ‎4.1: (a) amount of Global Horizontal Irradiance (GHI), (b) Calibration of two

sensors PHFS-01type in term of (surface cell temperature) (c) Calibration of four

HOBO light meters in term of (Air temperature) used in the experiment ............... 104

Figure ‎4.2: (a) comparison of Outdoor temperature in measurement and TMY used

in simulation,(b) shelter wooden box design used to measure external air temperature

............................................................................................................................. 105

Figure ‎4.3: (a) Comparison between Monitoring data and simulated model of PV

module through the mockup model: monthly accumulated data of energy output, (b)

relationship between solar radiance and energy output in May (spring season). ..... 107

Figure ‎4.4: hourly Global and diffuse radiance of tilt angle 90 degree of Eastern

façade ................................................................................................................... 107

Figure ‎4.5: Comparison of measured and simulated daily energy output of BIPV

window in East-Southeast facade under semi-arid clime Algeria, Tebessa ............. 108

Figure ‎4.6: Hourly heat gain/loss measurement data in spring and summer season

compare with simulated data. ................................................................................ 109

Figure ‎4.7: Validation of measured indoor air temperature and simulation by using

Energy-plus in summer season (1st to 15th June) .................................................. 110

Figure ‎4.8: Indoor air temperature of tested office during (a) spring season (b)

summer season ...................................................................................................... 111

Figure ‎4.9: Measurement of Surface cell temperature of BIPV module during (a)

spring season (1 may to 20 may) (b) summer season (1july to 14july) ................... 112

Figure‎4.10: Total clouds cover distribution in Tebessa city (May2017), source:

Meteoblue website ................................................................................................ 114

Figure ‎4.11: Comparaison between level of illuminance at references points (A1,

A2, B1, B2) and simulation ................................................................................... 114

Page 16: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xvii

Figure ‎4.12: The light meter reference (A2) exposed to direct sunlight at 8am,

morning period ..................................................................................................... 115

Figure ‎4.13: Uniformity of test office under clear and overcast sky ...................... 116

Figure ‎4.14: Comparaison between measured global outdoor illuminance and

simulation (IES-VE,2016) ..................................................................................... 117

Figure ‎4.15: (a) yearly global horizontal & diffuse radiance (b) Seasonally global

and diffuse tilted 90o radiance in different orientations (E, N, W, and S) ............... 121

Figure ‎4.16: Comparison between (GHI) and (DHI) with tilted 90 vertical solar

irradiance in different orientation .......................................................................... 123

Figure ‎4.17: (a) Energy output of different PV modules with various conversion

efficiency from 2.8% to 8% (b) Energy output performance in cardinal orientation (c)

Monthly Distribution of energy output PV module with conversion efficiency n=4

............................................................................................................................. 124

Figure ‎4.18: Annual energy output of BIPV window on vertical façade according to

different orientation .............................................................................................. 126

Figure ‎4.19: Annual energy output affected by different tilt angle on the southern

façade ................................................................................................................... 127

Figure ‎4.20: percentage of BIPV windows energy output performance based on tilt

angle and orientations under semi-arid region in Algeria ....................................... 128

Figure ‎4.21: The area of potential BIPV used (Roof, opaque, windows) ................ 129

Figure ‎4.22: effect of the cell temperature against energy output with different tilt

angle in design days: 21th

june, 21thdecember and 21

th September .......................... 131

Figure ‎4.23: Annual lighting energy consumption of based-model in cardinal

orientations ........................................................................................................... 133

Figure ‎4.24: hourly and means of (WPI) level with cardinal orientation of base-

model throughout the year..................................................................................... 134

Figure ‎4.25: Lighting energy consumption by using different VLT of PV modules in

cardinal orientations (a) East, (b) West, (c) South (d) North, respectively .............. 138

Figure ‎4.26: Annual cooling energy consumption of BIPV modules against base-

model .................................................................................................................... 144

Figure ‎4.27: annual heating energy consumption of BIPV modules against base-

model .................................................................................................................... 146

Page 17: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xviii

Figure ‎4.28: Monthly distribution of heating and cooling energy consumption of

base-model with WWR30% .................................................................................. 147

Figure ‎4.29: Overall energy performance and visual comfort of the PV modules

achieve the optimum design in the Southern Façade .............................................. 152

Figure ‎4.30: Overall energy performance and visual comfort of the PV modules

achieve the optimum design in the Northern Façade .............................................. 154

Figure ‎4.31 : Overall energy performance and visual comfort of the PV modules

achieve the optimum design in the Eastern Façade ................................................ 156

Figure ‎4.32 : Overall energy performance and visual comfort of PV module achieve

the optimum design in the East Façade .................................................................. 156

Figure ‎4.33 : Overall energy performance and visual comfort of the PV modules

achieve the optimum design in the Western Façade ............................................... 158

Figure ‎4.34: the maximum percentage of Energy saving of BIPV modules compared

with base-model in cardinal orientations (A) South (B) East (C) North (D) West

respectively ........................................................................................................... 162

Figure ‎4.35: the optimum WWR of PV modules and base-model in cardinal

orientation and its energy saving against optimum base-model. ............................. 163

Figure ‎5.1: The optimum design of a BIPV window (WWR, VLT, conversion

efficiency) according to each of the cardinal orientation of an office building with

vertical facades. .................................................................................................... 174

Figure ‎5.2: 3D model guideline of the energy output percentages obtained from

various tilt angles and (A) Southern hemisphere orientations (B) Northern

hemisphere, for architects and designers ............................................................... 175

Page 18: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xix

LIST OF ABBREVIATIONS

BIPV - Building Integrated Photovoltaic

BAPV - Building Added Photovoltaic

IEA - International Energy Agency

APRUE - Agency for the Promotion and Rational Use of Energy

CREDEG - Electricity & Gas R&D Center

UDTS - Unit for the development of silicium technology

CDER - Centre for Renewable Energy Development

UDES - Unit for Developing Solar Equipment

NEAL - New Energy Algeria Company Specialized in

Development of Renewable Energy

OEC - Overall Energy Consumption

STC - Standard Test Condition

UDI - Useful Daylight Illuminance

DA - Daylight Autonomy

Lux - Unit of illuminance

CEI - Commission International d‘eclairage

W - Watt

kWh - Kilo-watt Hour

IES-VE - Integrated Environment Solution Virtual Environment

FC - Foot-Candle

Ei - Exterior illuminance

ii - interior illuminance

m - meter

ȵ - Efficiency of Module

Pmax - Max power

Vpm

- Max power Voltage

Ipm

- Max power Current

WWR - Windows Wall Ratio

WPI - Work Plane Illuminance

DF - Daylight Factor

VLT - Visible Light Transmittance

SHGC - Solar Heat Gain Coefficient

N - North

S - South

E - East

W - West

S-E - South-east

S-W - South-west

N-E - North-east

N-W - North-west

MBE - Mean Bias Error

CVRMSE - Coefficient Variation of Root Means Square Error

GHI - Global Horizontal Irradiance

Page 19: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xx

DHI - Direct Horizontal Irradiance

CGI - CEI Glare Index

GVCP - Guth Visual comfort possibility

DGI - Daylight Glare Index

URG - Unified Glare index

DGP - Daylight Glare Index

CdTe - Cadmium Telluride

Mu-Si - Micro-morph Silicon

a-Si - Amorphous silicon

CIGS - Copper Indium gallium diselendide

OPV - Organic Photovoltaic

DSSCs - Dye sensitised solar cells

m-Si - Mono-crystalline

STPV - Semi-transparent Photovoltaic

PV-IGU - Photovoltaic insulated glass unit

PV-DFS - Photovoltaic Double skin facade

NEB - Net Electricity Benefit

ZEB - Zero Energy Building

Page 20: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xxi

LIST OF APPENDICES

APPENDIX TITLE PAGE

A Data sheet of BIPV modules used in (1) Experiment

(2) Simulations from manufactories

198

B The daily and monthly calculation of MBE & RMSE

of Energy output direct current by usage of MPPT

208

C Set-up of experiment measurements in tested office

building in Tebessa

213

D Algerian Solar Maps show: (1) PV power potential

(2) Global Horizontal Irradiance (3) Direct Normal

irradiance from (1994–2015) according to solar

resource data: Solargis

218

E Monthly Distribution of (Global &Diffuse)

Horizontal Solar radiance

221

F Improvement of Means CEI Glare Index evaluation of

(A) base-model against (B) optimum PV modules

designs

223

G Daily-Peak Illuminance level of base-model in

cardinal orientation with WWR20%

227

H Overall energy performance of different PV modules

balanced (cooling/heating energy consumption,

lighting energy consumption and energy output with

the percentage of UDI

229

I Yearly basis of Absolut Work plan illuminance of

different PV modules used in the simulation

246

Page 21: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

xxii

Page 22: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

1

CHAPTER 1

1 INTRODUCTION

1.1 Background

Sustainable developments in the field of architecture are turning out to be

increasingly vital which requires the utilization of renewable energy and the reduction of

energy consumption. The effect of global warming is the result of pollutant emissions

from both traditional and conventional energy resources which takes account of the

reduction of fossil fuel, intensification of oil consumption and the increment in the

energy demand (Stoppato, 2008). These concerns have led to the emergence of

significant development of renewable energy industries. Several studies show that this

new sector played a vital role and many countries such as Algeria have taken measures

to ensure sustainability of the utilization of global alternative energy resources (Hui,

1997; A Boudghene Stambouli, Khiat, Flazi, & Kitamura, 2012).

According to International Energy Agency (IEA) world council, solar energy is

natural and a clean energy source as the current availability of the energy surpasses the

annual energy demand by 400 times, whereas its potential surpasses the demand by

10,000 times. The sun will provide roughly limitless energy for the next 4-5 billion years

(IEA, 2013) as shown in the Figure1.1. Hepbasli (2008) stated that solar energy resource

such as photovoltaic is commonly used along with the leading technologies such as

geothermal, biomass and hydroelectric energy. According to the Renewable Energy

Policy Network for the 21st Century (REN21), there has been a noticeable growth by

55% in the utilization of photovoltaic (PV) as it is considered to be the most substantial

Page 23: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

2

energy resources available. In addition, study by Zahedi (2006) found that it is expected

that solar PV electric‘s capacity worldwide shown to incline tremendously by 2030 from

1,000 MW in 2000 to 140,000 MW. By 2040, the renewable electric energy may

possibly become adequate to support the base load and half of the global electricity

energy demand claimed by the European Renewable Energy Council (Teske, Zervos, &

Schäfer, 2007). Further, studies shows that the amount of solar electricity produced

surpasses the global need as projected by the solar pyramid in the case of the Algerian

Sahara with 50% of the space, 10% of the system energy efficiency and 14% PV module

coverage (A Boudghene Stambouli et al., 2012).

Figure 1.1: : The amount of solar energy could be exploited, source: (IEA, 2013)

In this decade, the ability to fully utilize renewable energy innovation in building

as well as environmental sustainability is the main topic for human societies around the

planet. Many researchers such as (Huijts, Molin, & Steg, 2012; Rogers, Simmons,

Convery, & Weatherall, 2008; Vlek & Steg, 2007; Wüstenhagen, Wolsink, & Bürer,

2007) stated that quality is taken into account of all countries in short and long term of

Page 24: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

3

natural resources, sustainable development and in addition to the technology used to

designate economic, social, and environmental dimensions of our upcoming survival.

According to Intissar Fakir (2016), low oil prices affects immensely on Algeria‘s

finances and energy use leaving the economy at struggle in 2016. Alternatively, Algeria

is interested to supplant fossil fuels and natural Gas with renewable energy resources.

However, , it is a challenge for the government to promote renewable energy to

minimize the utilization of energy in buildings as it is a new sector in the country

(Himri, Malik, Stambouli, Himri, & Draoui, 2009; A Boudghene Stambouli et al., 2012).

Across all nations, the sector of energy consumption in buildings alone consumes

around 20% to 60% of the overall account that is used by all sectors, and an average of

about 31% worldwide. Algeria, a standout amongst the most nations on the planet‘s

energy utilization assessed 42% more than the average by more than 10% as shown in

the figure 1.2. However, according to latest statistic of the Algerian agency for the

promotion and rational use of energy (APRUE) in 2015, this percentage varies from

zone to others, the Zone 2 and 7 represent the context of this study (Semi-arid climate)

include Tebessa city. Subsequently, Figure 1.3 shows the final energy consumption by

35% in transport sector, 16% industrial sector, 6% agricultural sector and 45%

residential & office building sector as shown in Figure.1.3. The utilization creates 25%

of the national CO2 outflow as these measurements are liable to ascend over the later

because of the developing interest for convenience in building sector (Sotehi, Chaker,

Benamra, & Ramoul, 2015b). This major consumption level warrants a point by point

comprehension of the building sector's consumption elements to formulate and guide the

sector‘s energy consumption in the attainment to stimulate efficiency, conservation,

technology implementation and energy source substituting such as to on-site renewable

energy.

Page 25: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

4

Figure 1.2: The average of building‘s energy consumption shown as a percentage of

national energy consumption and in relative international form, Source: (IEA online

Figure 1.3: Final energy consumption by sector in Algeria -Zone 2. under semi-arid

climate, Source: (APRUE, 2015).

Page 26: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

5

The building sector is the largest consumer of energy, with a share of almost

50% of the entire energy consumption for all types of buildings, according to experts at

Bayer, the German company that facilitated a meeting on the topic of energy efficiency

on 29 May 2012 (the German-Algerian Chamber of Commerce). Approximately, 60% to

80% of this energy is lost. Up to 60% of the energy loss is attributed to air-conditioning

and heating acquired through external envelopes (openings, roofs, walls and grounds).

This percentage is in line with a recent study carried out by Missoum and Draoui in

(2016). According to an APRUE report in 2013, the demand for electricity in Algeria

has been increasing at a normal rate of 9.5% over the past five years, with 42% of the

energy consumption being accounted for by residential and offices buildings, where

58% of the energy is from gas and 61% from electricity. According to studies by Bélaïd

and Abderrahmani in (2013), electricity production is estimated to double in the next

decade in order to maintain the economic growth and demographic expansion. On the

other hand, a vital portion of the energy consumption in the building sector is marked by

a solid annual growth rate of 6.28%, thereby making it necessary to consider energy

saving measures (Ferhat & Boutrahi, 2014).

From another perspective, a study showed that there are no building regulations

or any recommendations for daylighting and window-to-wall ratios (WWR) for public

buildings. Thus, poor window designs and the absence of regulations in Algeria will lead

to higher energy consumption (A. Belakehal, 2014). However, electric lighting now

makes up 25% of the total energy consumption, making it one of the main consumers of

electricity in buildings (Amirat & El Hassar, 2005).

There are concerns about the incorporation of PV on buildings, as the experience

of various disadvantages has prevented the building sector from understanding the

capability of this advancement in Algeria‘s building envelope. The main problems

blocking improvements in solar technology have been identified as being in relation to

financial issues, the extremely high cost of equipment and the time taken for returns on

the capital invested for such innovations. In addition, householders are not interested in

Page 27: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

6

enhancing their energy efficiency by installing building-integrated photovoltaics (BIPV)

in their homes to keep energy costs low. According to (Maafi, 2000; Semache, Hamidat,

& Benchatti), and the APRUE report (2010), PV power is used for rural electrification,

pumping, telecommunication repeaters, refrigeration and ventilation. The report

published in APRUE (2010) by the European Commission on the 6th framework

program on research uncovered the deficiency of the policy regarding building-

integrated PVs, while construction grants for both public and private buildings do not

include any regulations with regard to the utilization of energy by buildings in this

country. The awareness and doubts of households with regard to the installation of

photovoltaics in residential buildings also need to be considered. In addition, studies by

(Chaurey & Kandpal, 2010; Haw, Sopian, & Sulaiman, 2009) have stated that these are

some of the fundamental limitations that need more attention in most countries as with

other concerns arising from limitations in the system design (Heinstein, Ballif, & Perret-

Aebi, 2013). In particular, these new technologies, such as BIPV systems (Goh, Goh,

Yap, Masrom, & Mohamed, 2017; R. J. Yang & Zou, 2016), which can substitute

historical building elements and can achieve additional purposes needed for the

building‘s envelope (Maturi, 2013). Lately, it has been popular to produce electrical

energy from windows and glass (Li, Lam, Chan, & Mak, 2009). This has been made

possible by employing photovoltaic (PV) panels combined within windows. Such

technology is created to aid several functions. In addition to the basic task of generating

electricity, the multiple-use of BIPV window indicates that it is able to give glare

protection and reduce heat gain and loss to save energy (Attoye, Tabet Aoul, & Hassan,

2017). However, there are insufficient researches and analyses in this domain, thereby

making the development of this technology an urgent task in Algeria.

Page 28: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

7

1.2 Problem Statement

In Algeria, the energy consumption levels for buildings are very high. A large

amount of this energy is lost through the external envelope façade of buildings

(claddings, openings), while energy demands for both heating and cooling are high in

summer and winter respectively due to the nature of the Algerian climate. Since mid-rise

buildings (4-11story) are the dominant typology in Algeria (Senouci et al., 2012), it has

been suggested that window glazing should play a significant role as a building material,

for which BIPV windows can be an alternative.

It has been noticed that literature exhibited a significant lack of BIPV windows

energy support and performance in Algerian building sector (Maafi, 2000; A Boudghene

Stambouli et al., 2012). Besides, the integration of BIPV windows into the façade of

mid-rise buildings instead of conventional windows is almost non-existent as shown in

figure 1.4, even though Algeria has an enormous potential in solar energy in addition to

an obvious drop in PV prices in the market over the last few years.

Figure 1.4: The Application of BIPV window technology in the world, Source: (Biyik et

al., 2017)

Page 29: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

8

The on-going research into energy consumption in the building sector in Algeria

is mainly concentrated on several areas including the output efficiency of PV plants that

are connected to an installed grid. This application was implemented on the site of the

Centre for Development of Renewable Energy in Bouzaréah (Algiers) (Cherfaa et al.).

This technology is considered to be the first of its kind in Algeria. In addition, the

research has also been focused on minimising energy consumption by utilizing thermal

insulation technology. The most common application is the usage of adobe (mud bricks)

building material. Other techniques that have been given extensive importance in

researches and practical applications in Algeria are the application of BIPVT systems

(Sotehi, Chaker, Benamra, & Ramoul, 2015a) and the manipulation of the orientation of

the building or natural ventilation in summer to obtain optimum performance (Hacene &

Sari, 2013; Zemmouri & Schiler, 2005).

For all the reasons mentioned above, this research attempted to make use of the

enormous solar energy potential of Algeria by utilizing the BIPV windows technology.

This aim was accomplished by investigating the optimum performance of BIPV

windows as an alternative solution for minimizing energy consumption in the building

sector. The outcome of this research, if implemented, will positively impact energy

savings for the occupants and beneficiaries of office buildings, as they comprise the

most common category of energy consumers.

1.3 Research Gap

Architectural practices in Algeria generally do not keep pace with the use of the

aspects of sustainability and technology to reduce energy in the building sector. Based

on the literature and the observations of this researcher as an architect, the use of

renewable solar energy panels in buildings is limited, except for those installed on the

roofs of a few houses. The installation of BIPV windows in the vertical façade of mid-

Page 30: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

9

rise buildings is completely scarce even though the use of BIPV windows is linked with

the huge vertical façade areas compared to roof areas. The solar radiation supplied by

the vertical installations might not be at a maximum, but the energy savings could be

compensated by the use of a huge façade such as in mid-rise and high-rise buildings.

The majority of the studies that focused on the overall energy performance of BIPV

windows targeted the climate of Asian countries, while no study has been performed in

countries with a similar climate to Algeria. Consequently, in order to fill the gap, this

research targeted the overall energy performance of BIPV windows in relation to the

WWR, and the orientation and tilt angles in terms of four factors: visual comfort with

energy output, utilization of day lighting, and heat gain and loss to achieve the optimum

performance of a BIPV window façade in a semi-arid climate.

1.4 Research Aims

This research was aimed in determining the optimum performance of BIPV

windows in a typical office building while maximizing daylighting and minimizing the

heat gain/ heat loss into the interior in order to obtain a visually comfortable internal

micro climate and energy savings in a semi-arid climate.

1.5 Research Objective

1. To investigate a level of the overall energy (Energy output, Heat gain/loss

and Daylighting) of BIPV windows performance of a typical office

building under Semi-arid climate in Algeria.

2. To evaluate the performance of different BIPV windows types based on

(conversion Efficiency, visible Transparency, Solar Heat gain Coefficient

Page 31: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

10

SHGC and U-value) orientations, Window to Wall Ratio (WWR) for

assessment of overall energy use.

a. To determine the optimum tilt angle design of BIPV window in

term of energy output.

b. To compare the overall energy performance of base-model with

different BIPV window modules

3. To recommend an optimum design model of BIPV windows in cardinal

orientations to improve energy saving and visual comfort in Algeria.

1.6 Research Questions

After reviewing the past literature, and in line with the above-mentioned

objectives, this study will seek answers to the following research questions:

1. What are the influences of applying BIPV windows technology on

overall energy performance under a Semi-arid climate of Algeria?

2. Does modifying the configuration of BIPV windows design

(Orientations, types of PV, WWR) affect reducing the quantity of energy

output?

3. What is the optimum tilt angle to maximise the energy output?

4. What is the optimum WWR and orientation of BIPV windows modules

according to Algeria climate in the office buildings in view to optimise

day lighting and maximise energy output?

5. Is it possible that the use of BIPV window as an alternative to

conventional window could lead to zero energy saving?

Page 32: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

11

1.7 Scope of the Study

The scope of this study covered the following points:

i. Building sector, including residential and public buildings, which is comprised

of different activities such as for tourism (hotels, restaurants), education, health,

administration, offices (financial institutions and other private services).

However, this study focused on office buildings.

ii. Office building structures contain many spaces such as individual or open

offices, laboratories, meeting rooms, and conference rooms. An individual office

was chosen for this study because it is considered to be the most important

element in an office building; however, a computer used as (electrical

equipment) always has constant energy consumption for all scenarios.

iii. This study focused on second-generation PV modules (thin film technology) that

are available in the market rather than on first-generation modules (silicon

wafer-based technology).

iv. Algeria is a large country with four different climatic zones. The overall energy

performance analysis of this study was limited to the Haut-plateau region of

Algeria, where the majority of the offices are concentrated (the region is located

between latitudes 34°-36° and is within a semi-arid climate zone).

v. This study focused on the effect on the overall energy performance of a BIPV

window installed on the vertical façade rather than on the roof area of a building

mainly because the roof area is relatively small compared to the external façade

of a high-rise and mid-rise building. Furthermore, a large portion of the roof

area is usually occupied by various building service installations such as water

tanks, chillers, cooling towers, a lift machine room, etc.

vi. The EnergyPlus and IES-VE (Integration Environment Solution Virtual

Environment) simulation software were chosen from several simulation

software, including Design-builder, Ecotec, Velux, and Revit. Energy-Plus was

chosen for its ability to simulate the BIPV window application accurately and to

provide all the necessary details. At the same time, IES-VE was selected for its

Page 33: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

12

many properties and its accurate annual calculation of daylight through the WPI

data, useful daylight illuminates and glare index metrics, and diminished light

control (IES, 1993; IES-VE. 2006;(CF Reinhart & Breton, 2009).

1.8 Significance of the Research

There is no specific design of BIPV window in Algerian office buildings in

relation to its orientation, sunlight permissible in office, and visual comfort of occupant

through regulations to achieve the maximum energy saving and environmental needs.

The Authorities of Algeria has not put in place a proper design procedure for office

building energy consumption and visual comfort for users. Therefore, this research aims

to generate significant information to serve as a platform for overall energy performance

requirements for office building design. Subsequently, the requirements would form a

basis for future overall energy and visual comfort recommendations for Algerian office

building design.

1.9 Organisation of Thesis

Chapter Two reviews the state-of-the-art BIPV technology in the world and,

particularly, in Algeria. This is followed by an explanation on the concept of the BIPV

window and its classification and design. Furthermore, this chapter presents the

electrical, climatic and architectural factors that influence the performance of the BIPV

window technology. In addition, it reviews the experimental applications and heat

transfer model of the BIPV window. It also provides an explanation of the visual

comfort in offices and the metrics used to evaluate the quantity and quality of day

lighting using the BIPV window. Furthermore, this chapter presents the performance of

Page 34: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

13

the BIPV window within an office building. It concludes with an examination of the

relevant researches on this topic.

Chapter Three explains the research methodology, which is a combination of two

methods. The first consists of a site visitation and experimental measurements in a

selected Algerian office building, followed by computer simulations using EnergyPlus

and IES-VE Integrated Environment Solution Virtual Environment.

Chapter Four presents the results of the field measurements in a tested office in

Tebessa during critical time periods, and compares these results with the international

standard. This chapter also presents the results from a simulated overall energy model of

a base model and different BIPV window modules in the office in order to determine the

maximum energy saved and to meet the criteria of visual comfort.

Chapter Five reviews the research objectives highlighted in Chapter one and

examines the impact of the findings revealed through the outlined objectives. The

practical implications and recommendations are highlighted, and the limitations of the

study are discussed, with suggestions offered for further research.

Page 35: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

178

REFERENCES

A. Belakehal, A. B. a. K. A. (2014). Office Buildings Daylighting Design in Hot Arid

Regions: Forms, Codes and Occupants‘ Point of View. International Engineering

Conference on Hot Arid Regions (IECHAR 2010).

Abdeladim, K., Bouchakour, S., Arab, A. H., Cherfa, F., Chouder, A., & Kerkouche, K.

Contribution for assessment and mapping in Algeria using appropriate models

Abdelhakeem, M., Aminu, D. Y., & Kandar, M. Z. (2015). Investigating use of daylight

in a typical algerian public classroom typology. JURNAL TEKNOLOGI, 77(15),

21-30.

Alexandri, E., Papastefanakis, D., & Damasiotis, M. (2008). Integration of solar

technologies into buildings in Mediterranean communities. Centre for Renewable

Energy Sources, Athens.

Alonso-Garcia, M., Ruiz, J., & Chenlo, F. (2006). Experimental study of mismatch and

shading effects in the I–V characteristic of a photovoltaic module. Solar Energy

Materials and Solar Cells, 90(3), 329-340.

Amar, H.-A. (2015). Quantification of solar radiation in Algeria, application to the

sizing of photovoltaic systems. Université de Tlemcen.

Amirat, M., & El Hassar, S. (2005). Economies d'energie dans le secteur de l'habitat

consommation electrique des ménages: Cas d'un foyer algérien typique en

période d'hiver. Revue des énergies renouvelables, 8(1), 27-37.

Andenæs, E., Jelle, B. P., Ramlo, K., Kolås, T., Selj, J., & Foss, S. E. (2018). The

influence of snow and ice coverage on the energy generation from photovoltaic

solar cells. Solar Energy, 159, 318-328.

Andersen, D., & Foldbjerg, R. (2012). Daylight, Energy and Indoor Climate–Basic

Book. Editorial team: Daylight Energy and Indoor Climate (DEIC), VELUX

A/S.

Anderson, A.-L., Chen, S., Romero, L., Top, I., & Binions, R. (2016). Thin films for

advanced glazing applications. Buildings, 6(3), 37.

Page 36: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

179

APRUE. (2010). International Exhibition of Renewable Energy and Energy

Management. Algeria: The National Agency for the Promotion and

Rationalization of the Use of Energy Retrieved from

http://www.aprue.org.dz/publications.html.

APRUE. (2015). Regional energy situation. Retrieved 10-9-2018, from The National

Agency for the Promotion and Rationalization of the Use of Energy

http://www.aprue.org.dz/publications.html

Aries, M. B., Veitch, J. A., & Newsham, G. R. (2010). Windows, view, and office

characteristics predict physical and psychological discomfort. Journal of

Environmental Psychology, 30(4), 533-541.

Aristizabal, A., & Gordillo, G. (2008). Performance monitoring results of the first grid-

connected BIPV system in Colombia. Renewable Energy, 33(11), 2475-2484.

Attoye, D. E., Tabet Aoul, K. A., & Hassan, A. (2017). A Review on Building

Integrated Photovoltaic Façade Customization Potentials. Sustainability, 9(12),

2287.

Barman, S., Chowdhury, A., Mathur, S., & Mathur, J. (2018). Assessment of the

efficiency of window integrated CdTe based semi-transparent photovoltaic

module. Sustainable Cities and Society, 37, 250-262.

Basak, O. D., & Sazak, B. S. (2013). Effect of developments on a PV system efficiency.

Paper presented at the Electrical and Electronics Engineering (ISEEE), 2013 4th

International Symposium on.

Bayrak, F., Ertürk, G., & Oztop, H. F. (2017). Effects of partial shading on energy and

exergy efficiencies for photovoltaic panels. Journal of cleaner production, 164,

58-69.

Bélaïd, F., & Abderrahmani, F. (2013). Electricity consumption and economic growth in

Algeria: A multivariate causality analysis in the presence of structural change.

Energy Policy, 55, 286-295.

Bellia, L., Cesarano, A., Iuliano, G. F., & Spada, G. (2008). Daylight glare: a review of

discomfort indexes.

Bellini, E. (2017). Aurés Solaire commissions Algeria‘s second module factory. PV

magazine.

Page 37: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

180

Bellini, E. (2018). Engie, Sonatrach officialize partnership for solar and renewables. PV

magazine.

Bendel, C. (2003). Multifunktionale Nutzung photovoltaischer Anlagen. Photovoltaik–

Neue Horizonte, 76.

Biyik, E., Araz, M., Hepbasli, A., Shahrestani, M., Yao, R., Shao, L., . . . Rico, E.

(2017). A key review of building integrated photovoltaic (BIPV) systems.

Engineering science and technology, an international journal, 20(3), 833-858.

Cantin, F., & Dubois, M.-C. (2011). Daylighting metrics based on illuminance,

distribution, glare and directivity. Lighting Research & Technology, 43(3), 291-

307.

Carlos, J. S., & Corvacho, H. (2015). Evaluation of the performance indices of a

ventilated double window through experimental and analytical procedures:

SHGC-values. Energy and Buildings, 86, 886-897.

Carlucci, S., Causone, F., De Rosa, F., & Pagliano, L. (2015). A review of indices for

assessing visual comfort with a view to their use in optimization processes to

support building integrated design. Renewable and Sustainable Energy Reviews,

47, 1016-1033.

CDER. (2016). Photovoltaic solar energy Division Retrieved 03-28-2016, 2016, from

http://www.cder.dz/spip.php?rubrique213

Chaurey, A., & Kandpal, T. C. (2010). Assessment and evaluation of PV based

decentralized rural electrification: An overview. Renewable and Sustainable

Energy Reviews, 14(8), 2266-2278.

Chegaar, M., & Chibani, A. (2001). Global solar radiation estimation in Algeria. Energy

conversion and management, 42(8), 967-973.

Chen, F., Wittkopf, S. K., Ng, P. K., & Du, H. (2012). Solar heat gain coefficient

measurement of semi-transparent photovoltaic modules with indoor calorimetric

hot box and solar simulator. Energy and Buildings, 53, 74-84.

Chen, W., Shen, H., & Liu, Y. (2009). Performance evaluation of PV arrays at different

tilt angles and orientations in BIPV. Taiyangneng Xuebao. Acta Energiae Solaris

Sinica, 30, 206-210.

Page 38: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

181

Cherfaa, F., Araba, A. H., Oussaidb, R., Abdeladima, K., Bouchakoura, S., &

Kerkouchea, K. Performance evaluation of the first grid connected PV system in

Algeria. Paper presented at the 28th European Photovoltaic Solar Energy

Conference and Exhibition. Paris.

Chiang, C.-M., & Lai, C.-M. (2002). A study on the comprehensive indicator of indoor

environment assessment for occupants‘ health in Taiwan. Building and

Environment, 37(4), 387-392.

Commission, C. o. t. E. (2010). Directive 2010/31/EU of the European Parliament and of

the council of 19 May 2010 on the energy performance of buildings. Off. J. Eur.

Union L, 153, 13-35.

Cornaro, C., Basciano, G., Puggioni, V. A., & Pierro, M. (2017). Energy saving

assessment of semi-transparent photovoltaic modules integrated into NZEB.

Buildings, 7(1), 9.

Corporation, O. C. (2009). HOBO Pendant,Temperature/Light Data Logger:

Specifications and Light measurement

Retrieved 01-03-2015 www.onsetcomp.com

Crawley, D. B., Hand, J. W., Kummert, M., & Griffith, B. T. (2008). Contrasting the

capabilities of building energy performance simulation programs. Building and

Environment, 43(4), 661-673.

Cuce, E. (2016). Toward multi-functional PV glazing technologies in low/zero carbon

buildings: Heat insulation solar glass–Latest developments and future prospects.

Renewable and Sustainable Energy Reviews, 60, 1286-1301.

De Carli, M., De Giuli, V., & Zecchin, R. (2008). Review on visual comfort in office

buildings and influence of daylight in productivity. Paper presented at the 11th

International Conference Indoor Air, Copenhagen.

Didoné, E. L., & Wagner, A. (2013). Semi-transparent PV windows: a study for office

buildings in Brazil. Energy and Buildings, 67, 136-142.

Dinçer, İ., Midilli, A., & Kucuk, H. (2014). Progress in Sustainable Energy

Technologies: Generating Renewable Energy (Vol. 1): Springer.

Page 39: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

182

Djalel, D., & Moatezbillah, G. (2014). Optimal Exploitation of a Solar Power System for

a Semi-Arid Zone (Case Study: Ferkène, Algeria). International Journal of

Renewable Energy Research (IJRER), 4(2), 389-400.

Djamel, Z., & Noureddine, Z. (2017). The Impact of Window Configuration on the

Overall Building Energy Consumption under Specific Climate Conditions.

Energy Procedia, 115, 162-172. doi:

https://doi.org/10.1016/j.egypro.2017.05.016

Dubey, S., Sarvaiya, J. N., & Seshadri, B. (2013). Temperature dependent photovoltaic

(PV) efficiency and its effect on PV production in the world–a review. Energy

Procedia, 33, 311-321.

Duffie, J. A., & Beckman, W. A. (2013). Solar engineering of thermal processes: John

Wiley & Sons.

Eiffert, P., & Kiss, G. J. (2000). Building-integrated photovoltaic designs for

commercial and institutional structures: a sourcebook for architects: DIANE

Publishing.

Ellis, P. G., Torcellini, P. A., & Crawley, D. B. (2008). Energy Design Plugin: An

EnergyPlus Plugin for SketchUp; Preprint: National Renewable Energy

Lab.(NREL), Golden, CO (United States).

Falk, A., Durschner, C., & Remmers, K.-H. (2013). Photovoltaics for professionals:

solar electric systems marketing, design and installation: Routledge.

Fedail, H. H. A. (2015). Design and Implementation of a Microcontroller–Based Solar

Panel Tracking System. Sudan University of Science and Technology.

Ferhat, S., & Boutrahi, M. (2014). The Residential Built Heritage Of Algiers And Its

Energy Behaviour: Case Study Of The Building Number 3 Flats Of The Aero-

habitat District. WIT Transactions on Ecology and the Environment, 186, 39-53.

Fesharaki, V. J., Dehghani, M., Fesharaki, J. J., & Tavasoli, H. (2011). The effect of

temperature on photovoltaic cell efficiency. Paper presented at the Proceedings

of the 1stInternational Conference on Emerging Trends in Energy Conservation–

ETEC, Tehran, Iran.

Flodberg, K., Blomsterberg, Å., & Dubois, M.-C. (2012). Low-energy office buildings

using existing technology: simulations with low internal heat gains. International

Journal of Energy and Environmental Engineering, 3(1), 19.

Page 40: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

183

Fung, T. Y., & Yang, H. (2008). Study on thermal performance of semi-transparent

building-integrated photovoltaic glazings. Energy and Buildings, 40(3), 341-350.

Gairaa, K., & Bakelli, Y. (2013). Solar energy potential assessment in the Algerian south

area: case of Ghardaïa region. Journal of Renewable Energy, 2013.

Gassim, O. A. O. (2015). Improvement of Performance of Conjugated Polymer Solar

Cells Coated. Sudan University of Science and Technology.

Geoff Stapleton, S. N., Geoff Milne (2013). Photovoltaic systems. Retrieved 9/2/2018

http://www.yourhome.gov.au

Ghezloun, A., Oucher, N., & Chergui, S. (2012). Energy policy in the context of

sustainable development: Case of Algeria and Tunisia. Energy Procedia, 18, 53-

60.

Goel, S., Rosenberg, M. I., & Eley, C. (2017). ANSI/ASHRAE/IES Standard 90.1-2016

Performance Rating Method Reference Manual: Pacific Northwest National

Lab.(PNNL), Richland, WA (United States).

Goh, K. C., Goh, H. H., Yap, A. B. K., Masrom, M. A. N., & Mohamed, S. (2017).

Barriers and drivers of Malaysian BIPV application: Perspective of developers.

Procedia Eng, 180, 1585-1595.

Green, M. A. (2003). Crystalline and thin-film silicon solar cells: state of the art and

future potential. Solar Energy, 74(3), 181-192.

Green, M. A., Emery, K., Hishikawa, Y., Warta, W., & Dunlop, E. D. (2015). Solar cell

efficiency tables (Version 45). Progress in Photovoltaics: Research and

applications, 23(1), 1-9.

Griffith, B. T., & Ellis, P. G. (2004). Photovoltaic and Solar Thermal Modeling with the

EnergyPlus Calculation Engine: Preprint: National Renewable Energy Lab.,

Golden, CO (US).

Grynning, S., Gustavsen, A., Time, B., & Jelle, B. P. (2013). Windows in the buildings

of tomorrow: Energy losers or energy gainers? Energy and Buildings, 61, 185-

192.

Gulagi, A. (2015). Characterization and Investigation on Material Compatibilities of

Building Integrated Photovoltaic Module Components.

Page 41: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

184

Hacene, M. E. A. B., & Sari, N. E. C. (2013). Algerian Strategy in the Context of

Sustainable Development: The Case of Green Building. Int. J. of Thermal &

Environmental Engineering, 6(1), 1-6.

Hachem, C., Fazio, P., & Athienitis, A. (2013). Solar optimized residential

neighborhoods: Evaluation and design methodology. Solar Energy, 95, 42-64.

Hamakawa, Y. (2013). Thin-film solar cells: next generation photovoltaics and its

applications (Vol. 13): Springer Science & Business Media.

Hammad, B., Al–Abed, M., Al–Ghandoor, A., Al–Sardeah, A., & Al–Bashir, A. (2017).

Modeling and analysis of dust and temperature effects on photovoltaic systems‘

performance and optimal cleaning frequency: Jordan case study. Renewable and

Sustainable Energy Reviews.

Han, J., Lu, L., Peng, J., & Yang, H. (2013). Performance of ventilated double-sided PV

façade compared with conventional clear glass façade. Energy and Buildings, 56,

204-209.

Han, J., Lu, L., & Yang, H. (2009). Thermal behavior of a novel type see-through

glazing system with integrated PV cells. Building and Environment, 44(10),

2129-2136.

Haselbach, L. (2008). The engineering guide to LEED-new construction: sustainable

construction for engineers: McGraw-Hill.

Haw, L., Sopian, K., & Sulaiman, Y. (2009). Public response to residential building

integrated photovoltaic system (BIPV) in Kuala Lumpur urban area. Paper

presented at the Proceedings of the 4th IASME/WSEAS International

Conference on Energy and Environment, Cambridge, UK.

Haysom, J. E., Hinzer, K., & Wright, D. (2016). Impact of electricity tariffs on optimal

orientation of photovoltaic modules. Progress in Photovoltaics: Research and

applications, 24(2), 253-260.

He, W., Zhang, Y., Sun, W., Hou, J., Jiang, Q., & Ji, J. (2011). Experimental and

numerical investigation on the performance of amorphous silicon photovoltaics

window in East China. Building and Environment, 46(2), 363-369.

Heinstein, P., Ballif, C., & Perret-Aebi, L.-E. (2013). Building integrated photovoltaics

(BIPV): review, potentials, barriers and myths. Green, 3(2), 125-156.

Page 42: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

185

Hensen, J. L., & Lamberts, R. (2012). Building performance simulation for design and

operation: Routledge.

Henson, J. W. C. (2012). BIPV FAÇADES RECONSIDERED: MID-RISE AND HIGH

RISE APPLICATIONS. Paper presented at the Building Enclosure Science &

Technology (BEST3) Conference.

Hepbasli, A. (2008). A key review on exergetic analysis and assessment of renewable

energy resources for a sustainable future. Renewable and Sustainable Energy

Reviews, 12(3), 593-661.

Himri, Y., Malik, A. S., Stambouli, A. B., Himri, S., & Draoui, B. (2009). Review and

use of the Algerian renewable energy for sustainable development. Renewable

and Sustainable Energy Reviews, 13(6), 1584-1591.

Hui, S. C. (1997). From renewable energy to sustainability: the challenge for Hong

Kong. Hong Kong Institution of Engineers, 351-358.

Huijts, N. M., Molin, E., & Steg, L. (2012). Psychological factors influencing

sustainable energy technology acceptance: A review-based comprehensive

framework. Renewable and Sustainable Energy Reviews, 16(1), 525-531.

Husnaina, I., Mushtaqa, W., & Khana, Z. S. (2016). Comparison of thin film versus

crystalline PV modules for utility-scale electric power production in Pakistan.

Ibarra, D., & Reinhart, C. F. (2009). Daylight factor simulations–how close do

simulation beginners ‗really‘get? Paper presented at the Building simulation.

IEA. (2013). World Energy Resources Survey. 468. www.worldenergy.org

Ihm, P., Nemri, A., & Krarti, M. (2009). Estimation of lighting energy savings from

daylighting. Building and Environment, 44(3), 509-514.

Index, G. B., & Malaysia, G. (2013). Green Building Index: Retrieved.

Infield, D., Eicker, U., Fux, V., Mei, L., & Schumacher, J. (2006). A simplified

approach to thermal performance calculation for building integrated

mechanically ventilated PV facades. Building and Environment, 41(7), 893-901.

Intissar Fakir, D. g.-y. (2016). Running Low: Algeria‘s Fiscal Challenges and

Implications for Stability. http://carnegie-mec.org/2016/02/11/running-low-

algeria-s-fiscal-challenges-and-implications-for-stability/itu8

Page 43: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

186

ISO, I. (2002). 8995-1: 2002 (CIE S 008/E: 2001). Lighting of indoor work places.

Geneva: ISO Organización Internacional de Normalización.

Jakubiec, J., & Reinhart, C. (2011). DIVA-FOR-RHINO 2.0: Environmental parametric

modeling in Rhinoceros/Grasshopper using RADIANCE, Daysim and

EnergyPlus. Paper presented at the Conference proceedings of building

simulation.

Jarić, M., Budimir, N., Pejanovic, M., & Svetel, I. (2013). A review of energy analysis

simulation tools.

Kacira, M., Simsek, M., Babur, Y., & Demirkol, S. (2004). Determining optimum tilt

angles and orientations of photovoltaic panels in Sanliurfa, Turkey. Renewable

Energy, 29(8), 1265-1275.

Kapsis, K., & Athienitis, A. K. (2011). Building integrated semi-transparent

photovoltaics: energy and daylighting performance. Paper presented at the

Photonics North 2011.

Kapsis, K., Dermardiros, V., & Athienitis, A. (2015). Daylight performance of perimeter

office façades utilizing semi-transparent photovoltaic windows: a simulation

study. Energy Procedia, 78, 334-339.

Kazem, H. A., Chaichan, M. T., Alwaeli, A. H., & Mani, K. (2017). Effect of Shadows

on the Performance of Solar Photovoltaic, Cham.

Khatib, T., Kazem, H., Sopian, K., Buttinger, F., Elmenreich, W., & Albusaidi, A. S.

(2013). Effect of dust deposition on the performance of multi-crystalline

photovoltaic modules based on experimental measurements. International

Journal of Renewable Energy Research (IJRER), 3(4), 850-853.

Kibria, M. T., Ahammed, A., Sony, S., Hossain, F., & Islam, S. (2014). A Review:

Comparative studies on different generation solar cells technology. Paper

presented at the Proc. of 5th International Conference on Environmental Aspects

of Bangladesh.

Krarti, M., Erickson, P. M., & Hillman, T. C. (2005). A simplified method to estimate

energy savings of artificial lighting use from daylighting. Building and

Environment, 40(6), 747-754.

Page 44: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

187

Kurayama, C. (2006). Developement of a Measurement Sysem for SHGC and U-

VALUE: Study on SHGC and U-value for fenestration and shading system Part

1. Journal of Environmental Engineering (Transactions of AIJ), 71(604), 15-22.

Lam, T., Ge, H., & Fazio, P. (2016). Energy positive curtain wall configurations for a

cold climate using the Analysis of Variance (ANOVA) approach. Paper

presented at the Building Simulation.

Laura Maturi, J. A. (2018). Building Integrated Photovoltaic In Trentino Alto Adige

Springer International PU.

Lee, T. D., & Ebong, A. U. (2017). A review of thin film solar cell technologies and

challenges. Renewable and Sustainable Energy Reviews, 70, 1286-1297.

Li, D. H. (2010). A review of daylight illuminance determinations and energy

implications. Applied Energy, 87(7), 2109-2118.

Li, D. H., Lam, T. N., Chan, W. W., & Mak, A. H. (2009). Energy and cost analysis of

semi-transparent photovoltaic in office buildings. Applied Energy, 86(5), 722-

729.

Liao, W., & Xu, S. (2015). Energy performance comparison among see-through

amorphous-silicon PV (photovoltaic) glazings and traditional glazings under

different architectural conditions in China. Energy, 83, 267-275.

López, C. S. P., & Sangiorgi, M. (2014). Comparison assessment of BIPV façade semi-

transparent modules: further insights on human comfort conditions. Energy

Procedia, 48, 1419-1428.

Lu, L., & Law, K. M. (2013). Overall energy performance of semi-transparent single-

glazed photovoltaic (PV) window for a typical office in Hong Kong. Renewable

Energy, 49, 250-254.

Lu, L., & Yang, H. (2004). A study on simulations of the power output and practical

models for building integrated photovoltaic systems. Journal of Solar Energy

Engineering, 126(3), 929-935.

Luo, Y., Feng, Z., Han, Y., & Li, H. (2010). Design of compact and smooth free-form

optical system with uniform illuminance for LED source. Optics express, 18(9),

9055-9063.

Page 45: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

188

Maafi, A. (2000). A survey on photovoltaic activities in Algeria. Renewable Energy,

20(1), 9-17.

Mahato, N., Ansari, M. O., & Cho, M. H. (2015). Production of Utilizable Energy from

Renewable Resources: Mechanism, Machinery and Effect on Environment.

Paper presented at the Advanced Materials Research.

Maile, T., Fischer, M., & Bazjanac, V. (2007). Building energy performance simulation

tools-a life-cycle and interoperable perspective.

Mardaljevic, J., Andersen, M., Roy, N., & Christoffersen, J. (2012). Daylighting metrics:

is there a relation between useful daylight illuminance and daylight glare

probability. Paper presented at the Proceedings of the building simulation and

optimization conference (BSO12), Loughborough, UK.

Maturi, L. (2013). Building skin as energy supply: Prototype development of a wooden

prefabricated BiPV wall. University of Trento.

Maurus, H., Schmid, M., Blersch, B., Lechner, P., & Schade, H. (2004). PV for

buildings: benefits and experiences with amorphous silicon in BIPV applications.

Refocus, 5(6), 22-27.

McCluney, R. (1991). The death of the shading coefficient. ASHRAE journal, 33(3), 36-

45.

McNeil, A., & Burrell, G. (2016). Applicability of DGP and DGI for evaluating glare in

a brightly daylit space. Proceedings of SimBuild, 6(1).

Mehleri, E., Zervas, P., Sarimveis, H., Palyvos, J., & Markatos, N. (2010).

Determination of the optimal tilt angle and orientation for solar photovoltaic

arrays. Renewable Energy, 35(11), 2468-2475.

Meral, M. E., & Dinçer, F. (2011). A review of the factors affecting operation and

efficiency of photovoltaic based electricity generation systems. Renewable and

Sustainable Energy Reviews, 15(5), 2176-2184.

Missoum, A., Elmir, M., Bouanini, M., & Draoui, B. (2016). Numerical simulation of

heat transfer through the building facades of buildings located in the city of

Bechar. International Journal of Multiphysics, 10(4).

Page 46: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

189

Miyazaki, T., Akisawa, A., & Kashiwagi, T. (2005). Energy savings of office buildings

by the use of semi-transparent solar cells for windows. Renewable Energy, 30(3),

281-304.

Mondol, J. D., Yohanis, Y. G., & Norton, B. (2007). The impact of array inclination and

orientation on the performance of a grid-connected photovoltaic system.

Renewable Energy, 32(1), 118-140.

Montoro, D., Vanbuggenhout, P., & Ciesielska, J. (2011). Building Integrated

Photovoltaics: An overview of the existing products and their fields of

application. Report Prepared in the Framework of the European Funded Project;

SUNRISE: Saskatoon, Canada.

Moscoso, C. P. (2016). Daylighting and Architectural Quality: Aesthetic Perception of

Daylit Indoor Environments.

Motuziene, V., & Juodis, E. S. (2010). Simulation based complex energy assessment of

office building fenestration. Journal of civil Engineering and management, 16(3),

345-351.

Motuziene, V., & Valancius, K. (2015). Multi-criteria assesment of building integrated

photovoltaics. Mokslas: Lietuvos Ateitis, 7(4), 499.

Mousavi, S. M., Khan, T. H., & Lim, Y.-W. (2018). Impact of Furniture Layout on

Indoor Daylighting Performance in Existing Residential Buildings in Malaysia.

Journal of Daylighting, 5(1), 1-13.

Nabil, A., & Mardaljevic, J. (2005). Useful daylight illuminance: a new paradigm for

assessing daylight in buildings. Lighting Research & Technology, 37(1), 41-57.

Nabil, A., & Mardaljevic, J. (2006). Useful daylight illuminances: A replacement for

daylight factors. Energy and Buildings, 38(7), 905-913.

Ng, P. K., Mithraratne, N., & Kua, H. W. (2013). Energy analysis of semi-transparent

BIPV in Singapore buildings. Energy and Buildings, 66, 274-281.

Nikpour, M., Kandar, M., & Roshan, M. (2013). Empirical vof IES< VE> simulation in

term of daylight in self-shading office room in Malaysia. Journal of Basic

Applied Science Research, 3(10), 106-112.

Page 47: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

190

Nordmann, T., & Clavadetscher, L. (2003). Understanding temperature effects on PV

system performance. Paper presented at the Photovoltaic Energy Conversion,

2003. Proceedings of 3rd World Conference on.

Norton, B., Eames, P. C., Mallick, T. K., Huang, M. J., McCormack, S. J., Mondol, J.

D., & Yohanis, Y. G. (2011). Enhancing the performance of building integrated

photovoltaics. Solar Energy, 85(8), 1629-1664.

Olivieri, L., Caamaño-Martín, E., Moralejo-Vázquez, F. J., Martín-Chivelet, N., Olivieri,

F., & Neila-Gonzalez, F. (2014). Energy saving potential of semi-transparent

photovoltaic elements for building integration. Energy, 76, 572-583.

Olivieri, L., Caamaño-Martin, E., Olivieri, F., & Neila, J. (2014). Integral energy

performance characterization of semi-transparent photovoltaic elements for

building integration under real operation conditions. Energy and Buildings, 68,

280-291.

Osman, M. M., & Alibaba, A. P. D. H. Z. (2015). Comparative Studies on Integration of

Photovoltaic in Hot and Cold Climate.

Özakın, A., Karsli, S., Kaya, F., & Güllüce, H. (2016). The heat recovery with heat

transfer methods from solar photovoltaic systems. Paper presented at the Journal

of Physics: Conference Series.

Park, K.-W., & Athienitis, A. K. (2003). Workplane illuminance prediction method for

daylighting control systems. Solar Energy, 75(4), 277-284.

Park, K., Kang, G., Kim, H., Yu, G., & Kim, J. (2010). Analysis of thermal and

electrical performance of semi-transparent photovoltaic (PV) module. Energy,

35(6), 2681-2687.

Pasini, I. (2002). Daylighting Guide for Canadian Commercial Buildings. 86.

Paulescu, M., Paulescu, E., Gravila, P., & Badescu, V. (2012). Weather modeling and

forecasting of PV systems operation: Springer Science & Business Media.

Peng, C., Huang, Y., & Wu, Z. (2011). Building-integrated photovoltaics (BIPV) in

architectural design in China. Energy and Buildings, 43(12), 3592-3598.

Peng, J., Lu, L., Yang, H., & Ma, T. (2015a). Comparative study of the thermal and

power performances of a semi-transparent photovoltaic façade under different

ventilation modes. Applied Energy, 138, 572-583.

Page 48: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

191

Peng, J., Lu, L., Yang, H., & Ma, T. (2015b). Validation of the Sandia model with

indoor and outdoor measurements for semi-transparent amorphous silicon PV

modules. Renewable Energy, 80, 316-323.

Pidwirny, M. (2014). Introduction to the Biosphere: Single chapter from the eBook

Understanding Physical Geography: Our Planet Earth Publishing.

Rasul, M. G., & Doring, C. (2017). Performance Assessment of Desiccant air

Conditioning System in an Institutional Building in Subtropical Climate. Energy

Procedia, 110, 486-491.

Reinhart, C. (2011). Tutorial on the Use of Daysim Simulations for Sustainable Design,

2010. Harvard Design School.

Reinhart, C., & Breton, P.-F. (2009). Experimental validation of 3ds Max® Design 2009

and Daysim 3.0. Draft manuscript submitted to Building Simulation.

Reinhart, C., & Fitz, A. (2006). Findings from a survey on the current use of daylight

simulations in building design. Energy and Buildings, 38(7), 824-835.

Reinhart, C. F., & Walkenhorst, O. (2001). Validation of dynamic RADIANCE-based

daylight simulations for a test office with external blinds. Energy and Buildings,

33(7), 683-697.

Remund, J., Müller, S., Schilter, C., & Rihm, B. (2010). The use of Meteonorm weather

generator for climate change studies. Paper presented at the 10th EMS Annual

Meeting, 10th European Conference on Applications of Meteorology (ECAM)

Abstracts, held Sept. 13-17, 2010 in Zürich, Switzerland. http://meetings.

copernicus. org/ems2010/, id. EMS2010-417.

Remund, J., & Müller, S. C. (2011). Solar radiation and uncertainty information of

Meteonorm 7. Paper presented at the Proceedings of 26th European Photovoltaic

Solar Energy Conference and Exhibition.

Robertson, K. (2003). guide on daylighting of buildings. 24.

Robinson, L., & Athienitis, A. (2009). Design methodology for optimization of

electricity generation and daylight utilization for façade with semi-transparent

photovoltaics. Paper presented at the Proc. Building Simulation.

Page 49: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

192

Rogers, J. C., Simmons, E. A., Convery, I., & Weatherall, A. (2008). Public perceptions

of opportunities for community-based renewable energy projects. Energy Policy,

36(11), 4217-4226.

Rouag, D. S. (2001). Sunlight problems within new primary school classrooms in

Constantine (Algeria). (PHD), University of Mentouri, Constantine -Algeria-.

Rustemli, S., & Dincer, F. (2011). Modeling of photovoltaic panel and examining effects

of temperature in Matlab/Simulink. Elektronika ir Elektrotechnika, 109(3), 35-

40.

Salem, T., & Kinab, E. (2015). Analysis of Building-integrated Photovoltaic Systems: A

Case Study of Commercial Buildings under Mediterranean Climate. Procedia

Engineering, 118, 538-545.

Sampaio, P. G. V., & González, M. O. A. (2017). Photovoltaic solar energy: Conceptual

framework. Renewable and Sustainable Energy Reviews, 74, 590-601.

Sankaranarayanan, K., Van Der Kooi, H. J., & de Swaan Arons, J. (2010). Efficiency

and sustainability in the energy and chemical industries: scientific principles and

case studies: Crc Press.

Schoen, T., Prasad, D., Ruoss, D., Eiffert, P., & Sørensen, H. (2001). Task 7 of the IEA

PV power systems program–achievements and outlook. Paper presented at the

Proceedings of the 17th European Photovoltaic Solar Conference.

Scognamiglio, A., & Røstvik, H. N. (2013). Photovoltaics and zero energy buildings: a

new opportunity and challenge for design. Progress in Photovoltaics: Research

and applications, 21(6), 1319-1336.

Semache, A., Hamidat, A., & Benchatti, A. Impacts Study of The Solar Energy On The

Energy Performance of The Rural Housing In Algeria

Senouci, A., Taibim, A., Nedjar, D., Ramdane, A., Farsi, M. N., Bard, P.-Y., . . . Cartier,

S. (2012). Classification of buildings of Oran city (Algeria) based on their

seismic vulnerability. Paper presented at the 15th World Conference on

Earthquake Engineering.

Sfaelou, S., & Lianos, P. (2016). Photoactivated Fuel Cells (PhotoFuelCells). An

alternative source of renewable energy with environmental benefits.

Page 50: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

193

Shah, A. (2017). Thin-film silicon solar cells McEvoy's Handbook of Photovoltaics

(Third Edition) (pp. 235-307): Elsevier.

Shaheen, S. E., Ginley, D. S., & Jabbour, G. E. (2005). Organic-based photovoltaics:

toward low-cost power generation. MRS bulletin, 30(01), 10-19.

Simson, R., Kurnitski, J., & Kuusk, K. (2017). Experimental validation of simulation

and measurement-based overheating assessment approaches for residential

buildings. Architectural Science Review, 60(3), 192-204.

Siong, C. T., & Janssen, P. (2013). Semi-Transparent Building Integrated Photovoltaic

Facades–Maximise Energy Savings Using Evolutionary Multi-Objective

Optimisation.

Skandalos, N., & Karamanis, D. (2016). Investigation of thermal performance of semi-

transparent PV technologies. Energy and Buildings, 124, 19-34.

Skoplaki, E., & Palyvos, J. A. (2009). On the temperature dependence of photovoltaic

module electrical performance: A review of efficiency/power correlations. Solar

Energy, 83(5), 614-624.

Song, J.-H., An, Y.-S., Kim, S.-G., Lee, S.-J., Yoon, J.-H., & Choung, Y.-K. (2008).

Power output analysis of transparent thin-film module in building integrated

photovoltaic system (BIPV). Energy and Buildings, 40(11), 2067-2075.

Sopian, K., Cheow, S., & Zaidi, S. (2017). An overview of crystalline silicon solar cell

technology: Past, present, and future. Paper presented at the AIP Conference

Proceedings.

Sotehi, O., Chaker, A., Benamra, M. L., & Ramoul, E. (2015a). Theoretical

Investigation on a Building-Integrated PV/T (BiPVT) System for Electrical and

Thermal Energy Saving Case Study: Integrated Solar Village of Bou Saada. In I.

Dincer, O. C. Colpan, O. Kizilkan & A. M. Ezan (Eds.), Progress in Clean

Energy, Volume 2: Novel Systems and Applications (pp. 433-448). Cham:

Springer International Publishing.

Sotehi, O., Chaker, A., Benamra, M. L., & Ramoul, E. (2015b). Theoretical

Investigation on a Building-Integrated PV/T (BiPVT) System for Electrical and

Thermal Energy Saving Case Study: Integrated Solar Village of Bou Saada

Progress in Clean Energy, Volume 2 (pp. 433-448): Springer.

Page 51: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

194

Stambouli, A. B. (2011). Promotion of renewable energies in Algeria: strategies and

perspectives. Renewable and Sustainable Energy Reviews, 15(2), 1169-1181.

Stambouli, A. B., Khiat, Z., Flazi, S., & Kitamura, Y. (2012). A review on the renewable

energy development in Algeria: current perspective, energy scenario and

sustainability issues. Renewable and Sustainable Energy Reviews, 16(7), 4445-

4460.

Stoppato, A. (2008). Life cycle assessment of photovoltaic electricity generation.

Energy, 33(2), 224-232.

Stouffs, R., Janssen, P., Roudavski, S., & Tunçer, B. (2013). Semi-transparent building

integrated photovoltaic facades. Paper presented at the Conference on Computer-

Aided Architectural Design Research in Asia (CAADRIA 2013).

Sun, L., Lu, L., & Yang, H. (2012). Optimum design of shading-type building-integrated

photovoltaic claddings with different surface azimuth angles. Applied Energy,

90(1), 233-240.

Teske, S., Zervos, A., & Schäfer, O. (2007). Energy Revolution: A Sustainable World

Energy Outlook: Greenpeace International and European Renewable Energy

Council.

Verberne, G., Bonomo, P., Frontini, F., Donker, M., Chatzipanagi, A., Sinapis, K., &

Folkerts, W. (2015). BIPV products for facades and roof: a market analysis.

Solar Energy, 2014, 2013.

Vlek, C., & Steg, L. (2007). ⊡ Human Behavior and Environmental Sustainability:

Problems, Driving Forces, and Research Topics. Journal of social issues, 63(1),

1-19.

Wah, W. P., Shimoda, Y., Nonaka, M., Inoue, M., & Mizuno, M. (2005). Field study

and modeling of semi-transparent PV in power, thermal and optical aspects.

Journal of Asian Architecture and Building Engineering, 4(2), 549-556.

Wang, C., Peng, J., Li, N., Wang, M., & Li, X. (2017). Study on the Operation Strategy

of Ventilated Photovoltaic Windows in Hot-Summer and Cold-Winter Zone in

China. Procedia Engineering, 205, 2092-2099.

Wang, M., Peng, J., Li, N., Lu, L., & Yang, H. (2017). Experimental Study on Thermal

Performance of Semi-transparent PV Window in Winter in Hong Kong. Energy

Procedia, 105, 864-868.

Page 52: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

195

Wang, M., Peng, J., Li, N., Yang, H., Wang, C., Li, X., & Lu, T. (2017). Comparison of

energy performance between PV double skin facades and PV insulating glass

units. Applied Energy, 194, 148-160.

Wang, Y., Tian, W., Ren, J., Zhu, L., & Wang, Q. (2006). Influence of a building‘s

integrated-photovoltaics on heating and cooling loads. Applied Energy, 83(9),

989-1003.

Watt, M. (2001). Added Values of Photovoltaic Power Systems, Report IEA - PVPS T1

- 09 : 2001. Australia

Weicht, J., Rasch, R., Behrens, G., & Hamelmann, F. (2016). Performance

characterization of thin-film-silicon based solar modules under clouded and clear

sky conditions in comparison to crystalline silicon modules. Electronic Materials

Letters, 12(4), 468-471.

Wong, L. (2017). A review of daylighting design and implementation in buildings.

Renewable and Sustainable Energy Reviews, 74, 959-968.

Wong, P. W., Shimoda, Y., Nonaka, M., Inoue, M., & Mizuno, M. (2008). Semi-

transparent PV: Thermal performance, power generation, daylight modelling and

energy saving potential in a residential application. Renewable Energy, 33(5),

1024-1036.

Wright, J. A., Brownlee, A., Mourshed, M. M., & Wang, M. (2014). Multi-objective

optimization of cellular fenestration by an evolutionary algorithm. Journal of

Building Performance Simulation, 7(1), 33-51.

Wüstenhagen, R., Wolsink, M., & Bürer, M. J. (2007). Social acceptance of renewable

energy innovation: An introduction to the concept. Energy Policy, 35(5), 2683-

2691.

Xu, S., Liao, W., Huang, J., & Kang, J. (2014). Optimal PV cell coverage ratio for semi-

transparent photovoltaics on office building façades in central China. Energy and

Buildings, 77, 130-138.

Xue, G., Liu, K., Chen, Q., Yang, P., Li, J., Ding, T., . . . Zhou, J. (2017). Robust and

Low-Cost Flame-Treated Wood for High-Performance Solar Steam Generation.

ACS Applied Materials & Interfaces, 9(17), 15052-15057.

Yacef, R., Mellit, A., Belaid, S., & Şen, Z. (2014). New combined models for estimating

daily global solar radiation from measured air temperature in semi-arid climates:

Page 53: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

196

application in Ghardaïa, Algeria. Energy conversion and management, 79, 606-

615.

Yadav, D. P., Bajracharya, S. B., & Bhattrai, S. (2017). Energy Saving Assessment for

Building Envelope of Supermarket Based on EnergyPlus and Openstudio.

American Journal of Civil Engineering, 5(3), 141.

Yang, H., & Lu, L. (2007). The optimum tilt angles and orientations of PV claddings for

building-integrated photovoltaic (BIPV) applications. Journal of Solar Energy

Engineering, 129(2), 253-255.

Yang, J.-h., Mao, J.-j., & Chen, Z.-h. (2002). Calculation of solar radiation on variously

oriented tilted surface and optimum tilt angle. JOURNAL-SHANGHAI

JIAOTONG UNIVERSITY-CHINESE EDITION-, 36(7), 1032-1036.

Yang, R. J., & Zou, P. X. (2016). Building integrated photovoltaics (BIPV): Costs,

benefits, risks, barriers and improvement strategy. International Journal of

Construction Management, 16(1), 39-53.

Yassine, M., & Lotfi, D. (2011). Technical Document and regulation; Thermal

Regulations of Building. Algeria: National Center for Studies and Integrated

Research of the Building Retrieved from

https://www.scribd.com/doc/171884035/Reglement-algerien-sur-les-thermiques-

des-batiments-version-de-05-09-2011.

Yoon, J.-H., Song, J., & Lee, S.-J. (2011). Practical application of building integrated

photovoltaic (BIPV) system using transparent amorphous silicon thin-film PV

module. Solar Energy, 85(5), 723-733.

Yoshikawa, K., Kawasaki, H., Yoshida, W., Irie, T., Konishi, K., Nakano, K., . . . Uzu,

H. (2017). Silicon heterojunction solar cell with interdigitated back contacts for a

photoconversion efficiency over 26%. Nature Energy, 2, 17032.

Zahedi, A. (2006). Solar photovoltaic (PV) energy; latest developments in the building

integrated and hybrid PV systems. Renewable Energy, 31(5), 711-718.

Zemmouri, N. (2010). Achieving Environmental Security: Ecosystem Services and

Human Welfare (W. G. K. P. H. Liotta Ed.). Department of architecture,

University of Biskra, Algeria.

Page 54: PERFORMANCE OF OFFICE BUILDING INTEGRATED …eprints.utm.my/id/eprint/84184/1/MesloubAbdelhakimPFAB... · 2019-12-04 · penting untuk tenaga boleh diperbaharui bagi menghasilkan

197

Zemmouri, N., & Schiler, M. E. (2005). Modelling Energy Efficient Windows in hot

arid zones. Paper presented at the The 22nd Conference On Passive and Low

Energy Architecture-PLEA.

Zhang, W., Lu, L., Peng, J., & Song, A. (2016). Comparison of the overall energy

performance of semi-transparent photovoltaic windows and common energy-

efficient windows in Hong Kong. Energy and Buildings, 128, 511-518.

Zhang, X., & Du, J. (2015). Lighing Performance In Office Buildings with BIPV

Facades: Visual and Non-visual Effects.

Zhou, C., Liang, R., Zhang, J., & Riaz, A. (2017). Experimental Study on Dynamic

Thermal Response of Building Attached Photovoltaic (BAPV) Curtain Wall

System. Procedia Engineering, 205, 314-320.

Zhu, D., Hong, T., Yan, D., & Wang, C. (2013). A detailed loads comparison of three

building energy modeling programs: EnergyPlus, DeST and DOE-2.1 E. Paper

presented at the Building Simulation.

Zinßer, B., Makrides, G., Schubert, M., Georghiou, G., & Werner, J. H. (2008).

Temperature and intensity dependence of twelve photovoltaic technologies.

Paper presented at the Proceedings of the 23rd European photovoltaic solar

energy conference.