Performance-Based Structural-Fire Engineering...Thermal vs. Structural – Thermal criteria is...

59
1 Advanced Technology for Large Structural Systems © 2017 Spencer E. Quiel, PhD, PE Performance-Based Structural-Fire Engineering Spencer Quiel, PhD, PE P.C. Rossin Assistant Professor Lehigh University Bethlehem, PA OSEA 2017 Fall Conference Stillwater, OK September 27, 2017

Transcript of Performance-Based Structural-Fire Engineering...Thermal vs. Structural – Thermal criteria is...

  • 1

    Advanced Technology for Large Structural Systems

    © 2017 Spencer E. Quiel, PhD, PE

    Performance-Based Structural-Fire Engineering

    Spencer Quiel, PhD, PE P.C. Rossin Assistant Professor Lehigh University Bethlehem, PA

    OSEA 2017 Fall ConferenceStillwater, OKSeptember 27, 2017

  • Performance-Based Structural-Fire Engineering

    2

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    EDUCATION:– PhD, Structural Engineering, Princeton University (2009)

    DHS Graduate Fellow, 2004-2007– BS, Civil Engineering, University of Notre Dame (2004)

    EXPERIENCE:– August 2013 to Present:

    Assistant Professor, Lehigh University– July 2009 to August 2013:

    Project Engineer, Hinman Consulting Engineers, Inc.– Summer 2005: Guest Researcher

    Building and Fire Research Laboratory (BFRL), National Institute of Standards and Technology (NIST)

    PROFESSIONAL AFFILIATIONS:– ASCE Fire Protection Committee– Professionally Licensed Engineer (PA, VA)

    Spencer Quiel, PhD, PE

  • Performance-Based Structural-Fire Engineering

    3

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Structural Response to Extreme Loads: • How can we design buildings and bridges to be

    resistant to the effects of fire and blast?• How do we design structures to resist

    disproportionate, catastrophic collapse if they experience local damage?

    • How do we design for cascading hazards (i.e. for a fire following a blast or earthquake)?

    Research Approaches: • Experimental Testing at the ATLSS and Fritz

    Laboratories• High-Fidelity Computational Analysis (Finite

    Element Modeling)• Develop Improved Design Standards

    Research Interests

  • Performance-Based Structural-Fire Engineering

    4

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Fire poses a unique threat to the built environment:

    Initial extreme event = Fire as primary hazard

    Undamaged structure resists fire effects

    Following an initial extreme event = Fire as a cascading hazard

    Deformed or damaged structure resists the effects of subsequent fire

    1

    2

  • Performance-Based Structural-Fire Engineering

    5

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Fire as the Primary Hazard1

    One Meridian PlazaPhiladelphia, PA (1991)

    Delft University School of Architecture Delft, Netherlands (2008)

  • Performance-Based Structural-Fire Engineering

    6

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Fire as the Cascading Hazard2

    Oil Refinery Ichinara City, Japan

    Fire Following Tohoku Earthquake(2011)

    IRS BuildingAustin, TX

    Fire Following Aircraft Impact(2010)

  • Performance-Based Structural-Fire Engineering

    7

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Current State-of-Practice for Buildings: Resisting Fire as the Primary Hazard• Elements and subassemblies are prescribed levels of passive fire

    protection based on the results of standard fire tests

    – For generic fire protection:• International Building Code,

    UL Fire Resistance Directory, ASCE 29-05

    – For proprietary fire protection:• Products are tested according to

    appropriate standards, and a report is produced to certify the product

    • Test Standards:

    – Building Fires: ASTM E119, UL 263, ISO 834– Hydrocarbon Fires: ASTM E1529, UL 1709 Image by Exova Warrington Fire

  • Performance-Based Structural-Fire Engineering

    8

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    0

    200

    400

    600

    800

    1000

    1200

    1400

    1600

    1800

    2000

    2200

    0100200300400500600700800900

    100011001200

    0 30 60 90 120 150 180 210 240

    Temperature (°F)Te

    mpe

    ratu

    re (°

    C)

    Time (min)

    ASTM E1529UL 1709EC1 HydrocarbonASTM E119ISO 834

    What “Fire” is used for the Standard Fire Test?

    Used for relative benchmarking via the standard fire tests

    NOT necessarily representative of an actual fire

  • Performance-Based Structural-Fire Engineering

    9

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Standard Fire Test Procedure

    1. Subject elements to a standard temperature-time curve

    2. Measure performance based on temperature increase

    3. If loaded, evaluate performance based on load resistance and structural integrity

    4. Establish relative quantities of fire protection to achieve an hourly rating

  • Performance-Based Structural-Fire Engineering

    10

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Classifications of Standard Tests for Structural Elements

    • Loading Conditions: Loaded vs. Unloaded

    – Loaded is more realistic, but alternatives are available to perform an unloaded test which is focused on thermal performance

    – According to ASTM E119:

    “This load shall be the maximum load condition allowed under nationally recognized structural design criteria unless limited design criteria are specified and a corresponding reduced load is applied.”

    • Acceptance Criteria: Thermal vs. Structural

    – Thermal criteria is generally considered to be more conservative

    • For floor systems: Restrained vs. Unrestrained

    – Unrestrained criteria is generally considered to be more conservative

  • Performance-Based Structural-Fire Engineering

    11

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    ASTM E119: What it provides

    4.3.1 For walls, partitions, and floor or roof test specimens:

    4.3.1.1 Measurement of the transmission of heat

    4.3.1.2 Measurement of the transmission of hot gases through the test specimen

    4.3.1.3 For loadbearing elements, measurement of the load carrying ability of the test specimen during the test exposure.

    4.3.2 For individual loadbearing members such as beams and columns:

    4.3.2.1 Measurement of the load carrying ability under the test exposure with consideration for the end support conditions (that is, restrained or not restrained).

  • Performance-Based Structural-Fire Engineering

    12

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    ASTM E119: What it does NOT provide

    4.4.1 Information as to performance of test specimens constructed with components or lengths other than those tested

    4.4.2 Evaluation of the degree by which the test specimen contributes to the fire hazard by generation of smoke, toxic gases, or other products of combustion.

    4.4.3 Measurement of the degree of control or limitation of the passage of smoke or products of combustion through the test specimen.

    4.4.4 Simulation of the fire behavior of joints between building elements such as floor-wall or wall-wall, etc., connections.

    4.4.5 Measurement of flame spread over the surface of test specimens.

    4.4.6 The effect on fire-resistance of conventional openings in the test specimen, that is, electrical receptacle outlets, plumbing pipe, etc., unless specifically provided for in the construction tested. Also see Test Method E814 for testing of fire stops.

  • Performance-Based Structural-Fire Engineering

    13

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    ASTM E119 Test Criteria: Steel Elements• Columns

    – Thermal Criteria:

    • For loaded or unloaded tests

    • Acceptance Criteria: Avg. Temp. < 538°C (1000°F) Max. Temp. < 649°C (1200°F)

    – Loaded Tests:

    • Simulate the maximum-load condition per design code

    • Acceptance Criteria: Column must resist this load over the fire resistance time without collapsing

    • Floors and Roofs

    – Unrestrained Tests:

    • Can be loaded OR unloaded

    • Acceptance Criteria: Avg. Temp. < 593°C (1100°F), Max. Temp. < 704°C (1300°F), OR Max. Deflection Limits and Rate

    – Restrained Tests:

    • Simulate the maximum-load condition per design code

    • Acceptance Criteria: Assembly must resist the load without losing integrity

  • Performance-Based Structural-Fire Engineering

    14

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Passive Fire Protection for Steel Framed Buildings

    BEAM

    COLUMN

    Spray-On Fire Resistive Material (SFRM)

    Gypsum Boards

  • Performance-Based Structural-Fire Engineering

    15

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Selecting the Amount of Fire Protection

    𝑭𝑭𝑽𝑽

    =𝑯𝑯𝑯𝑯𝑯𝑯𝑯𝑯𝑯𝑯𝑯𝑯 𝑷𝑷𝑯𝑯𝑷𝑷𝑷𝑷𝑷𝑷𝑯𝑯𝑯𝑯𝑯𝑯𝑷𝑷

    𝑪𝑪𝑷𝑷𝑪𝑪𝑪𝑪𝑪𝑪 𝑺𝑺𝑯𝑯𝑺𝑺𝑯𝑯𝑷𝑷𝑪𝑪𝑺𝑺𝑯𝑯𝑺𝑺 𝑨𝑨𝑷𝑷𝑯𝑯𝑯𝑯

    Section Factor:

  • Performance-Based Structural-Fire Engineering

    16

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Intumescent Paint

    • Typical Uses:

    – Exposed Steel– Thin-Element Steelwork– Harsh Environments– Petrochemical Facilities– Offshore Facilities

    • Several coating applications are needed to ensure proper adhesion and heat activation

  • Performance-Based Structural-Fire Engineering

    17

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Passive Fire Protection: Prescriptive Tables

    IBC 2015

    UBC 1997

    What hourly rating is required?

    How much protection is needed to achieve that rating?

  • Performance-Based Structural-Fire Engineering

    18

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

  • Performance-Based Structural-Fire Engineering

    19

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

  • Performance-Based Structural-Fire Engineering

    20

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

  • Performance-Based Structural-Fire Engineering

    21

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    ASTM E119 Test Criteria: Concrete Elements• Columns

    – Thermal Criteria:

    • For loaded or unloaded tests

    • Acceptance Criteria: Avg. Temp. < 538°C (1000°F) Max. Temp. < 649°C (1200°F)

    – Loaded Tests:

    • Simulate the maximum-load condition per design code

    • Acceptance Criteria: Column must resist this load over the fire resistance time without collapsing

    • Floors and Roofs

    – Unrestrained Tests:

    • Can be loaded OR unloaded

    • Acceptance Criteria: Prestressing Steel < 427°C (800°F), Tensile Reinf. < 593°C (1100°F), OR Max. Deflection Limits and Rate

    – Restrained Tests:

    • Simulate the maximum-load condition per design code

    • Acceptance Criteria: Assembly must resist the load without losing integrity

  • Performance-Based Structural-Fire Engineering

    22

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    AC

    I 216

    -14

  • Performance-Based Structural-Fire Engineering

    23

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    ASTM E119 Test Criteria: Wood Elements• Columns

    – Thermal Criteria:

    • None

    – Loaded Tests:

    • Simulate the maximum-load condition per design code

    • Acceptance Criteria: Column must resist this load over the fire resistance time without collapsing

    • Floors and Roofs

    – Unrestrained Tests:

    • Typically, only loaded condition

    • Simulate the maximum-load condition per design code

    • Acceptance Criteria: Assembly must resist this load over the fire resistance time without collapsing

    – Restrained Tests:

    • Not allowed

  • Performance-Based Structural-Fire Engineering

    24

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    American Wood Council’s

    Design for Code Acceptance 3 (AWC DCA-3)

    *Combustible elements and assemblies are not

    permitted in some construction types

  • Performance-Based Structural-Fire Engineering

    25

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Prescriptive vs. Performance Based Design

    • Prescriptive: states how a building is to be constructed to resist fire

    – Uses furnace tests of individual members– Neglects interaction of connected members in a frame

    • Performance-Based: states how a structure is to perform in a realistic fire

    – Recommended by the NIST investigation of the WTC:

    Use realistic loads and boundary conditions

    Develop simple methods for analysis

  • Performance-Based Structural-Fire Engineering

    26

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Performance-Based Structural-Fire Engineering

    FIRE MODEL

    HEAT TRANSFER

    MODELSTRUCTURAL

    MODEL

    Fire GeometryFuel Load

    Section GeometryThermal Properties

    Boundary Layer

    Member GeometryApplied Loading

    Mechanical PropertiesEmpirical Data

    Now in Appendix E of ASCE 7-16!!

  • Performance-Based Structural-Fire Engineering

    27

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    NOW AVAILABLE COMING SOON

  • Performance-Based Structural-Fire Engineering

    28

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    • FIRE MODEL– Is the fire inside a compartment or outdoors (i.e. open-air)?– What is the fuel and associated heat release?– What is the rate of fuel consumption?

    • HEAT TRANSFER MODEL– What are the thermal boundary conditions?– What are the thermal material properties?– How do neighboring elements transfer heat to each other?

    • STRUCTURAL MODEL– How do the material properties deteriorate?– How much do the heated elements expand?– How are the elements connected and/or supported?– How are the elements loaded?

    Structural-Fire Engineering

  • Performance-Based Structural-Fire Engineering

    29

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    International Building Code 2015703.3 Alternative methods for determining fire resistance. The application of any of the alternative methods listed in this section shall be based on the fire exposure and acceptance criteria specified in ASTM E119 or UL 263. The required fire resistance of a building element, component or assembly shall be permitted to be established by any of the following methods or procedures:

    1. Fire-resistance designs documented in sources. [per the UL catalog]2. Prescriptive designs of fire-resistance-rated building elements, components or

    assemblies as prescribed in Section 721. 3. Calculations in accordance with Section 722. [per ASCE 29-05]4. Engineering analysis based on a comparison of building element, component

    or assemblies designs having fire-resistance ratings as determined by the test procedures set forth in ASTM E119 or UL 263.

    5. Alternative protection methods as allowed by Section 104.11. [requires additional tests as proof of compliance]

    http://www.madcad.com.ezproxy.lib.lehigh.edu/library/135051/368074/#section-721http://www.madcad.com.ezproxy.lib.lehigh.edu/library/135051/368075/#section-722http://www.madcad.com.ezproxy.lib.lehigh.edu/library/135051/367984/#section-104.11

  • Performance-Based Structural-Fire Engineering

    30

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Ts

    Qin

    Qout

    >Tmax1000.00950.00900.00850.00800.00750.00700.00650.00600.00563.00

    T=920

    T=800

    T=620

    Compartment Fire Model

    FIRE MODELS HEAT TRANSFER MODELS

    Lumped Mass

    Finite Element

    STRUCTURAL MODELS

    Single Element

    Frame Subassembly

    0

    200

    400

    600

    800

    1000

    1200

    1400

    1600

    1800

    2000

    2200

    0100200300400500600700800900

    100011001200

    0 30 60 90 120 150 180 210 240

    Temperature (°F)Te

    mpe

    ratu

    re (°

    C)

    Time (min)

    ASTM E1529UL 1709EC1 HydrocarbonASTM E119ISO 834

    Standard Fire Curves

  • Performance-Based Structural-Fire Engineering

    31

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Open Questions for Performance-Based Design…• What tools should we use for each design scenario?

    – Standard Fire vs. Compartment Fire vs. CFD Model– Lumped Mass, Finite Element, etc.

    • How should we evaluate the results?

    – Does the structure collapse? Is it damaged?– Plastic behavior? Buckling? Connection failure? Compartmentation breach?

    • How can we incentivize Performance-Based Design?

    – Does it save cost? Does it improve performance? – Does it address designs that are not in the code?– Can we address structural resilience by quantifying damage?

  • Performance-Based Structural-Fire Engineering

    32

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    AISC Milek Fellowship Projectat Lehigh University

    Performance-Based Design of Passive Fire Protection for Floor Systems in Steel-Framed Buildings

    • Project Objectives:

    – Develop of a framework for performance-based design and analysis of floor systems in steel-framed buildings to resist fire

    – Adapt, rather than attempt to replace, the prescriptive design provisions that comprise the current state-of-practice

    – Enable structural engineers become an active participant in the fire resistant design of steel floor systems

    – Provide guidance for quantifying realistic restraint of floor systems in steel buildings

  • Performance-Based Structural-Fire Engineering

    33

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Mechanical Properties of Steel at Elevated Temperature

    AISC 360-10 Appendix 4

  • Performance-Based Structural-Fire Engineering

    34

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Mechanical Properties of Steel at Elevated Temperature

  • Performance-Based Structural-Fire Engineering

    35

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Project TasksTask 1: Review Existing Literature and DataTask 2: Computational Model DevelopmentTask 3: Experimental Testing and Validation Task 4: Parametric Computational Investigation Task 5: Develop Framework for Performance-Based Design

  • Performance-Based Structural-Fire Engineering

    36

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Modular Structural Testing Furnace, ATLSS Laboratory

    2 MaxonKinemax

    3” Series G Burners

  • Performance-Based Structural-Fire Engineering

    37

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Composite Floor Tests (Performed 12/12/16 and 2/23/17)

    Shear Tab Connection Composite beams designed in

    accordance with UL D902

    SPECIMEN #1: protected with 7/8” CAFCO 300 SFRM2-hr restrained rating

    SPECIMEN #2: unprotected

  • Performance-Based Structural-Fire Engineering

    38

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Composite Floor Tests (Performed 12/12/16 and 2/23/17)

  • Performance-Based Structural-Fire Engineering

    39

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Composite Floor Tests (Performed 12/12/16 and 2/23/17)

    Loading Rig for 4-Point Bending 60-kip Enerpac Jack

  • Performance-Based Structural-Fire Engineering

    40

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Finite Element Models (SAFIR)

    Column Section: W10x26Wrapped in ceramic blanketsTemperatures measured during the test are assigned to elements in the furnace

    Beam Section: W12x26 with slab (3.25” on 2” deck)

    Heated over entire length

  • Performance-Based Structural-Fire Engineering

    41

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Finite Element Models (SAFIR)ELEMENT SIZES:

    • Beam: 1’-0”

    • Slab Shell: 1’-0” x 1’-0”

    • Beam Shell: 1.5” x 1.5”

    BEAM beam elementsSLAB shell elementsCOLN beam elementsCNXNS pinned or fixed

    BEAM shell elementsSLAB shell elementsCOLN beam elementsCNXNS semi-rigid (discrete “bolt” elements)

  • Performance-Based Structural-Fire Engineering

    42

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Protected Composite Floor Test

    Test lasted 2 hours, 18 minutes, 45 seconds

  • Performance-Based Structural-Fire Engineering

    43

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Protected Composite Floor Test

    Top bolts sheared during the test due to large connection rotation

    Minimal hole warping

  • Performance-Based Structural-Fire Engineering

    44

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Thermal Results – Protected Test

    Ambient Temperature throughout the furnace

  • Performance-Based Structural-Fire Engineering

    45

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Thermal Results – Protected Test

    Beam Temperature Comparison

    32232432632832103212321432163218322032

    0

    200

    400

    600

    800

    1000

    1200

    0 2000 4000 6000 8000 10000 12000 14000

    Tem

    p (F

    )

    Tem

    p (c

    el)

    Time (sec)

    Web - TestBF - TestTF - TestWeb-SAFIRBF-SAFIRTF-SAFIRWeb - MatlabBF - MatlabTF - Matlab

  • Performance-Based Structural-Fire Engineering

    46

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Structural Results – Protected Test

    Beam deflection – using SAFIR beam temperatures

    Column deflection – using SAFIR beam temperatures

    Time, sec

    0 2000 4000 6000 8000 10000 12000

    Def

    lect

    ion,

    mm

    -450

    -400

    -350

    -300

    -250

    -200

    -150

    -100

    -50

    0

    500 2000 4000 6000 8000 10000 12000

    Def

    lect

    ion,

    in-20

    -15

    -10

    -5

    0

    5

    Pinned 2D

    Fixed 2D

    Pinned 3D

    Fixed 3D

    Shell

    Test Data

    Time, sec

    0 2000 4000 6000 8000 10000 12000

    Def

    lect

    ion,

    mm

    -40

    -35

    -30

    -25

    -20

    -15

    -10

    -5

    0

    50 2000 4000 6000 8000 10000 12000

    Def

    lect

    ion,

    in

    -2

    -1.5

    -1

    -0.5

    0

    0.5

    Pinned 2D

    Fixed 2D

    Pinned 3D

    Fixed 3D

    Shell

    Test Data

  • Performance-Based Structural-Fire Engineering

    47

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Concrete Structures Under Fire• Large thermal gradients due to low

    thermal conductivity

    – Lumped mass methods may not be representative of the actual temperature distribution

    – Finite element analysis or semi-empirical methods may be needed in some cases

  • Performance-Based Structural-Fire Engineering

    48

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Coping with Gradients in Concrete Sections

  • Performance-Based Structural-Fire Engineering

    49

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Siliceous Concrete Reinforcement

    Concrete Properties at Elevated Temperature (ACI 216-14)

  • Performance-Based Structural-Fire Engineering

    50

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Concrete Spalling: How do we account for it?

    1996 Channel Tunnel Firehttps://www.sandberg.co.uk/investigat

    ion-inspection/inspection/fire-damaged-concrete.html

  • Performance-Based Structural-Fire Engineering

    51

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Explosive Spalling of a Bridge Beam (test by Propex)https://www.youtube.com/watch?v=gwQfpMnSh90)

  • Performance-Based Structural-Fire Engineering

    52

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Timber or Wood Structures Under Fire

    • LIGHT TIMBER CONSTRUCTION

    – Walls, joists, and floors are smaller, conventional elements like studs, plywood, and strand board

    – Typically residential or low-rise construction with little structural fire protection requirements

    • HEAVY TIMBER CONSTRUCTION

    – Beams, columns, decks, and/or truss members are made from glue-laminated timber or large dimension sawn timber

    – “Glulam” members perform similarly as solid sawn-timber elements with the same section

    – Low- to mid-rise rise construction with a broader range of fire protection requirements

  • Performance-Based Structural-Fire Engineering

    53

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Wood Charring: How do we account for cross-section reduction?

  • Performance-Based Structural-Fire Engineering

    54

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    1 mm/min = 2.36 in/hr

    Wood Charring: How do we account for cross-section reduction?

  • Performance-Based Structural-Fire Engineering

    55

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Wood Material Properties at Elevated Temperature

    Summarized by Buchanan, A.H. (2002). Structural Design for Fire Safety. Wiley.

    Tensile Strength Modulus of Elasticity

  • Performance-Based Structural-Fire Engineering

    56

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Case Study: SOM’s Tall Timber Tower Design Concept

  • Performance-Based Structural-Fire Engineering

    57

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Timber Tower: Fire Design Challenges• Tall timber construction cannot comply within the current US prescriptive code

    (since the structural system is COMBUSTIBLE)

    – Intent of the code must be understood and translated to equivalent requirements via PERFORMANCE-BASED DESIGN

    • Fire Design Approaches:

    1) Protect structure with non-combustible materials2) Prevent ignition under all possible fire conditions3) Design the structure so the members will self-extinguish and remain fully functional after

    charring4) Fire “burn out time” should be considered in developing fire assemblies

    • Tests and studies are needed to:

    1) Verify that timber elements will self-extinguish2) Establish exposure time for timber elements (i.e. charring rates)

  • Performance-Based Structural-Fire Engineering

    58

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    Moving Forward• Develop new tests with additional modes of realistic restraint and exposure

    • Conduct parametric studies

    – Section sizes, lengths, loading scenarios– Refine boundary conditions– Introduce realistic or probabilistic fire exposure

    • Develop simpler design-basis models

    – Compare to test results and FE models– Decrease computational effort to enhance usability

    • Develop a performance-based framework which leverages the standard test

    – Use the standard test for model benchmarking– Use calibrated models to calculate damage (and resilience) to fire

  • Performance-Based Structural-Fire Engineering

    59

    OSEA 2017 Fall Conference

    © 2017 Spencer E. Quiel, PhD, PE

    THANK YOU

    Any Questions?

    Special thanks to: AISC Milek Fellowship Lehigh University Amy Kordosky (Degenkolb, San Francisco) Matt Hoehler and Matt Bundy (BFRL-NIST)

    Slide Number 1Spencer Quiel, PhD, PEResearch InterestsSlide Number 4 Fire as the Primary Hazard Fire as the Cascading HazardCurrent State-of-Practice for Buildings: �Resisting Fire as the Primary HazardWhat “Fire” is used for the Standard Fire Test?Standard Fire Test ProcedureClassifications of Standard Tests for Structural ElementsASTM E119: What it providesASTM E119: What it does NOT provideASTM E119 Test Criteria: Steel ElementsPassive Fire Protection for Steel Framed BuildingsSelecting the Amount of Fire ProtectionIntumescent PaintPassive Fire Protection: �Prescriptive TablesSlide Number 18Slide Number 19Slide Number 20ASTM E119 Test Criteria: Concrete ElementsACI 216-14ASTM E119 Test Criteria: Wood ElementsAmerican Wood Council’s �Design for Code Acceptance 3 (AWC DCA-3)Prescriptive vs. Performance Based DesignPerformance-Based Structural-Fire EngineeringSlide Number 27Structural-Fire EngineeringInternational Building Code 2015Slide Number 30Open Questions for Performance-Based Design…AISC Milek Fellowship Project�at Lehigh UniversityMechanical Properties of Steel at Elevated TemperatureMechanical Properties of Steel at Elevated TemperatureProject TasksModular Structural Testing Furnace, ATLSS LaboratoryComposite Floor Tests (Performed 12/12/16 and 2/23/17)Composite Floor Tests (Performed 12/12/16 and 2/23/17)Slide Number 39Finite Element Models (SAFIR)Finite Element Models (SAFIR)Protected Composite Floor TestProtected Composite Floor TestThermal Results – Protected TestThermal Results – Protected TestStructural Results – Protected TestConcrete Structures Under FireCoping with Gradients in Concrete SectionsSiliceous ConcreteConcrete Spalling: How do we account for it?Explosive Spalling of a Bridge Beam (test by Propex)�https://www.youtube.com/watch?v=gwQfpMnSh90)Timber or Wood Structures Under FireWood Charring: How do we account for cross-section reduction?Wood Charring: How do we account for cross-section reduction?Wood Material Properties at Elevated TemperatureCase Study: SOM’s Tall Timber Tower Design ConceptTimber Tower: Fire Design ChallengesMoving ForwardTHANK YOU��Any Questions?