Performance Based Design: Fire Alarm Visual Notification ... · Performance Based Design: Fire...

29
Performance Based Design: Fire Alarm Visual Notification Appliances - Mathematical Guide Ernesto Vega Jánica, EE, MSc, MEng 1

Transcript of Performance Based Design: Fire Alarm Visual Notification ... · Performance Based Design: Fire...

Performance Based Design: Fire Alarm Visual Notification

Appliances - Mathematical Guide

Ernesto Vega Jánica, EE, MSc, MEng

1

Change on Philosophy1999-2002-2007-2010-2013Prescriptive Codes Vs Performance Based Design

Performance Based Design

Introduction

2

Company

Project Owner

End-User

☐✓

Financial

Technical

$

TM R&D

Marketing

Strobe Calculations

Pros & Cons

3

‣ What is Our Goal?‣ Room Configurations & Applicable Rules‣ Performance Criteria‣ NFPA 72 Vs UL 1971‣ Critical Design Assumptions‣ Design Features‣ Method of Evaluation ‣ Mathematical Guide & Modeling Reference‣ Model Examples

15% 15%

15%

10%20%

25%

Engineer Design Brief

4

The Strobe Calculator intends to Satisfy provisions of the NFPA 72 and the UL 1971 for building room configurations not listed on the NFPA 72, 2010* Tables 18.5.4.3.1(a) and 18.5.4.3.1(b)

Performance Based Design

What is Our Goal?

*NFPA recently released the NFPA 72, 2013 Edition, but the 2010 edition still referenced in the latest editions of model building codes such as the IBC

5

NFPA 72, 2010Tables 18.5.4.3.1(a) and (b) as Prescriptive Code Points to UL 1971 as the PBD guideline

Rule of Thumb:Designs shall provide a minimum of 0.0375 lumens/ft2 (0.4036 lumens/m2) of illumination at any point

Performance Based Design

Room Configurations

6

‣ The American with Disabilities Act, ADA

‣ The National Fire Alarm Code NFPA 72

‣ The American National Standards Institute, ANSI A117.1

‣ UL Standard 1971, Signaling Devices for the Hearing Impaired

Performance Based Design

Applicable Rules

7

40’

10’

22’

30cd Strobe

30cd

15cdA=680 ft2

a1=30’x30’900ft2

a1=30’x30’900ft2

a2=20’x20’400ft2

Prescriptive Code

Strobe Coverage for Irregular Areas

8

Minimum requirements are listed by ADAAG, NFPA 72 & UL 1971:

‣ 0.0375 lumens/ft2 (0.4036 lumens/m2) of illumination at any point and,

Performance Based Design

Performance Criteria

‣ Vertical, Horizontal and Polar Output as per UL 1971

9

UL 1971 Minimum Vertical Output, Wall Mounted

Angle

α (Deg)

Vertical

Output (%)

0 1005-30 9035 6540 4645 3450 2755 2260 1865 1670 1575 1380 1285 1290 12

90°

α

Angular Derating Factor

Performance Criteria

10

Angle

α (Deg)

Horizontal

Output (%)

0 1005-25 9030-45 75

50 5555 4560 4065 3570 3575 3080 3085 2590 25

90°90°

α

UL 1971 Minimum Horizontal Output, Wall Mounted

Angular Derating Factor

Performance Criteria

11

Angle

α (Deg)

Polar

Output (%)

0 1005-25 9030-45 75

50 5555 4560 4065 3570 3575 3080 3085 2590 250°

90°90°

α

UL 1971 Minimum Polar Output, Ceiling Mounted

Angular Derating Factor

Performance Criteria

12

MINIMUM REQUIRED LIGHT OUTPUT [cd] MINIMUM REQUIRED LIGHT OUTPUT [cd] MINIMUM REQUIRED LIGHT OUTPUT [cd] MINIMUM REQUIRED LIGHT OUTPUT [cd] MINIMUM REQUIRED LIGHT OUTPUT [cd] MINIMUM REQUIRED LIGHT OUTPUT [cd]

Maximum Room Size

Wall Mount as per NFPA (cd)

Wall Mount as per UL (cd)

Maximum Ceiling Height

Ceiling Mount as per NFPA (cd)

Ceiling Mount as per UL (cd)

20’x20’ 15 30 10’,20’,30’ 15, 30, 55 15, 30, 75

30’x30’ 34 75 10’,20’,30’ 30, 45, 75 75, 75, 75

40’x40’ 60 110 10’,20’,30’ 60, 75, 95 75, 75, 75

50’x50’ 94 177 10’,20’,30’ 95, 95, 95 110, 110, 110

60’x60’ 135 OVER 177 10’,20’,30’ 150, 150, 150 177, 177, 177

UL 1971 (PBD: Strobe Calculations)Vs

Performance Based Design

NFPA 72 (Prescriptive)

13

MINIMUM REQUIRED LIGHT OUTPUT [cd]

MINIMUM REQUIRED LIGHT OUTPUT [cd]

MINIMUM REQUIRED LIGHT OUTPUT [cd]

Maximum Room Size

Wall Mount as per NFPA (cd)

Wall Mount as per UL (cd)

10’x10’ NA (15) 3015’x15’ NA (15) 3018’x10’ NA (15) 3020’x20’ 15 3025’x30’ NA (34) 7530’x30’ 34 7538’x35’ NA (60) 7540’x40’ 60 11044’x44’ NA (75) 17748’x50’ NA (94) 17750’x50’ 94 177

WallMounted Strobes

New Scenarios no listed in NFPA 72

Add Value !

UL 1971

NFPA 72

Performance Based Design

Vs

14

MINIMUM REQUIRED LIGHT OUTPUT [cd] MINIMUM REQUIRED LIGHT OUTPUT [cd] MINIMUM REQUIRED LIGHT OUTPUT [cd] MINIMUM REQUIRED LIGHT OUTPUT [cd]

Maximum Room Size

Maximum Ceiling Height

Ceiling Mount as per NFPA (cd)

Ceiling Mount as per UL (cd)

10’x10’ 10’,12’,15’ 15, 30, 30 15, 15, 1510’x15’ 10’,12’,25’ 15, 30, 55 15, 15, 3020’x20’ 10’,20’,30’ 15, 30, 55 15, 30, 7520’x20’ 12’,18’,24’ 15, 30, 55 15, 30, 3025’x25’ 12’,18’,24’ 45, 45, 75 30, 30, 7530’x30’ 10’,20’,30’ 30, 45, 75 75, 75, 7540’x40’ 10’,20’,30’ 60, 75, 95 75, 75, 7544’x44’ 12’,24’,30’ 75, 95, 95 75, 75, 7550’x50’ 10’,20’,30’ 95, 95, 95 110, 110, 11060’x60’ 10’,20’,30’ 150, 150, 150 177, 177, 177

New Scenarios ! New Savings!

Add Value !

CeilingMounted Strobes

UL 1971

NFPA 72

Performance Based Design

Vs

15

‣Distance from Strobe to most remote point

‣Inverse Square Law

‣Vertical, Horizontal & Polar distribution as per UL 1971

Add Value !

Performance Based Design

Critical Design Assumptions

16

Keep it Simple!

P = I / D2 P = Illuminance (lumens/ft2)

I = Effective Intensity (candela)

D = Distance (ft)

Strobe(Source)

D1

D2

P1

P2

Inverse Square law

17

80”-96” ADA80”-96” NFPA 72

Sync more than 2 Strobes in a field view

6” In rooms with Low Ceilings

Sect. 18.5.4.1

Sect. 18.5.4.3.2.(4)Sect. 18.5.4.4.7

Sect. 18.5.4.2

Prescriptive Code

Design Features

Middle of Lens

NFPA 72, 201018

‣ Scenarios Not Listed in prescriptive tables

‣ Wall Mounted: Horizontal & Vertical Outputs Ceiling Mounted: Polar Outputs

‣ The Strobe Calculator will recommend the next commercially available strobe

‣ Equivalent Facilitation Letter

15cd 30cd 75cd 110cd 177cd

Add Value !

Strobe Calculations

Method of Evaluation

19

Add Value !

‣ Department of Community Affairs -DCA-

‣ Authority Having Jurisdiction -AHJ-

‣ Explain Evaluation Procedure & Results

Strobe Calculations

Code Compliance Facilitation Letter

20

Wall

x=Wide

y=Deep

h=Height

Strobe Location:

Ceiling

h =

Room Dimensions:

x =

y =

☐☐✓

12’

44’

44’

75cd

Recommended Strobe:

75cd

Performance Based Design

Model Interface

21

80cd StrobeA=1600 SqFt

Super eXtra Outlet Mall

NFPA 72Prescriptive 75cd Strobe

A=1936 SqFt

Performance Based Design

44’x44’

40’x40’

Ceilings at 12’ AFF

Performance Based Design

Model Examples

22

Sports

Food

Movies

Home

Retail

Over 300 Stores $ 8,500

$ 15,000

$ 22,000

$ 21,000

$ 13,500$ 80,000

ACHIEVE14%

SAVINGSSuper eXtra Outlet Mall

Performance Based Design

Model Examples

23

Equivalent Facilitation Letter

24

Performance Based Design

Model Examples

What about existing buildings?

‣ Existing Strobes not in compliance with proper coverage?

‣ Limited Wire, Circuit Runs and Power Supplies?

‣ Landmark or Sensitive Areas or Buildings?

‣ What would be the Maximum Coverage if...?

Add Value !

25

MINIMUM REQUIRED LIGHT OUTPUT [cd] MINIMUM REQUIRED LIGHT OUTPUT [cd] MINIMUM REQUIRED LIGHT OUTPUT [cd] MINIMUM REQUIRED LIGHT OUTPUT [cd]

Maximum Room Size

Maximum Ceiling Height

Ceiling Mount as per NFPA (cd)

Ceiling Mount as per UL (cd)

10’x10’ 10’,12’,15’ 15, 30, 30 15, 15, 1510’x15’ 10’,12’,25’ 15, 30, 55 15, 15, 3020’x20’ 10’,20’,30’ 15, 30, 55 15, 30, 7520’x20’ 12’,18’,24’ 15, 30, 55 15, 30, 3025’x25’ 12’,18’,24’ 45, 45, 75 30, 30, 7530’x30’ 10’,20’,30’ 30, 45, 75 75, 75, 7540’x40’ 10’,20’,30’ 60, 75, 95 75, 75, 7544’x44’ 12’,24’,30’ 75, 95, 95 75, 75, 7550’x50’ 10’,20’,30’ 95, 95, 95 110, 110, 11060’x60’ 10’,20’,30’ 150, 150, 150 177, 177, 177

New Scenarios ! New Savings!

Where do we see more add Value?

CeilingMounted Strobes

Performance Based Design

Discard non-commercially available ( )26

any?

27

[email protected]

any?

[email protected]

Ernesto Vega Jánica. EE, MSc, MEng

28

References

ADAAG Visible Notification Sections 4.28.3 and 2,2 Equivalent FacilitationNFPA 72, National Fire Alarm Code, 1999, 2002, 2007, 2010 & 2013 Editions

UL Standard for Safety 1971, Signaling Devices for the Hearing ImpairedSFPE Handbook of Fire Protection Engineering, 3rd Edition

SFPE Engineering Guide to Performance-Based Fire Protection, 2nd Edition

Credits

Dr. James Milke. University of MarylandRolf Jensen & Associates. New York City

Thank You!

29