PERCENTAGE DIFFERENTIAL RELAYS - GE Grid Solutions · spring backed contact fingers mounted in...
Transcript of PERCENTAGE DIFFERENTIAL RELAYS - GE Grid Solutions · spring backed contact fingers mounted in...
INSTRUCTIONS
GEI-I-1268 J
PERCENTAGEDIFFERENTIAL RELAYS
Ty p e sIJD52A 1JD53C1iD52B IJDS3D
GENERAL’ ELECTRiC
Percentage Differential Relays Type IJD
COVER
Figure 1. (8007207) Type Type IJD53A Relay Disassembled
C
TARGET RESETBUTTON
QONNECTNO PU14i
O UT ERBLOCK
2
PERCENTAGE DIFFERENTIAL RELAYS
TYPE liD
INTRODUCTION
Type
IJD52ALTD 52 BIrD53CIJD53D
Elements
313
The Type ISD relays comprise a group that isused for differential protection of alternating current equipment. There are two general types - -thoseused for generator and reactor protection and thoseused for transformer protection. Both of these typesare available in e it he r the one -or the three -unitcases. Other variations suchas current ratings andminimum operating current will be covered byspecific model numbers under these types.
The case of these relays is suitable for eithersurface or semiulush panel mounting and an assortment of hardware is provided for either mounting.The cover attaches to the case and also carries thereset mechanism when one is required. Each coverscrew has provision for a sealing wire.
The case has studs or screw connections atboth ends or at the bottom only for the externalconnections. The electrical connections betweenthe relay units and the case studs are made throughspring backed contact fingers mounted in stationarymolded inner and outer blocks between which nestsa removable connecting plug which completes thecircuits. The outer blocks, attached to the case,have the studs for the ext e r n a 1 connections, andthe inner blocks have the terminals for the internalconnections.
The relay mechanism is mounted in a steelframework called the cradle and is a complete unitwith all leads being terminated at the inner block.This cradle is held firmly in the case withalatch atthe top and the bottom and by a guide pin at the backof the case. The cases and c r a dies are so constructedthat the relay cannot be inserted in the caseupside down. The connecting plug, besides makingthe electrical Connections between the respectiveblocks of the cradle ar.d case, also locks the latch inplace. The cover. w[ich is fastened to the case bythumbscrews. holds tie connecting plug in p!ace.
To draw out the relay unit the cover is first.r(’m.)vL-d. tad the olug drawn out. Shorting bars arepr “ideci tn the case to short the current transformer circuits. The latches are then released, andthe relay unit can be easily drawn out. To replace
the relay unit, the reverse order is followed.
Aseparatetestingplug can be inserted in placeof the connecting plug to test the relay in placeon the panel either from its own source of currentand voltage, or from other sources. Or, the relayunit can be drawn out and replaced by another whichhas been tested in the laboratory.
Figure 2. (K-6400174_o) Principle of Differential Protection
PRINCIPLE OF DIFFERENTIALPROTECTION
WhenaY-coimected a-c generator is operatingproperly the currents inthe three conductors at thejunction are, of course, equal to the currents in thecorresponding line conductors. Now, if the systemis grounded, either at this junction or at some otherpoint, then the equality of the currents will be disturbed if a ground fault occurs in one of the generatorwindings. Protectionagainst such faults can beafforded by a relay which compares the magnitudesof the twocurrents ineach phase and closes its con
tacts whenever the ratio of the larger to the smallerexceeds some predetermined value. Fig. 2 showsschematic connections for the application of such arelay. It is evident that no current will flow through
0. ton:. di not ;.‘ :‘ rt to no, .1:1 .101,, .2: s.F n,,? Ion: 5,1O’I annw,,t nor to i’Ic”ndr tar
t’.’”1j’€.,2(O’’Fl?, 1 S’t’O U,’ 00001 III 01510W, (0’ 5.111 Ins?.., ‘0? 0.?,, .11)51 St 5)71 -r IThi,ntOfl,It’O.:.l,’,uldUP’,? 1:0001 It-,k’::, n’] ..r 5c.uJ.1 ;‘zt ni. S ;.‘n.1.r’. sr. s’wlnch sr in ,,-,,-.d suit, ‘:ontiy for
‘1 :t.S;€ 0 , I’ fit (.7.001,] (1 li’ 5’ 1l1’d I ‘‘tO or L 1r,’’ .• rn
0. rps’•x F ,‘‘l.-:r 1,’’! 1,5.. ;r.n,at’. (15,0? .t.olI 17-50:11(1,’..? ,‘,oJ,’,,, p’J ,nd 5’?MA ci .:€,I,i1.is:
.55.5 Ii.- fiji b II.: 1001’’,’ sq. Vt’:I — lit t.p,’ I 1:’ 7 , Oft’:. i:.’i , .1, (1,0) ‘sO 15. . 0.), 5’?;,’i ‘.20 qrs”at 1.?
For Protecting Outline & P.D. Fig.
Ge ncratorsGeneratorsTransformersTransformers
Inter.Conn. Fig.
21222122
56
1617
‘0 BUS
Percentage Differential Relays Type LTD
the operating coil as long as the CT secondary currents are equal and flow in the same direction.
In order to apply the above principle to the protection of transformers, it is necessary to providetaps on the two coils in such away as to compensatefor the inequality of the corresponding phase currents under normal conditions. This will be discussed more fully in the section on transformerrelays.
A certain amount of caution must be used inselecting current transformers for use with Type IJD
relays. if the CT error on through faults exceedsthe percentage slope characteristic of the relay thenfalse tripping may occur. For instance, if the relayhas a 10 percent slope characteristic, the two secondary currents should not differ by more than 10percent of the smaller when maximum fault currentis flowing.
To help prevent current transformer errorsfrom being excessive, it is recommended that burdens imposed be kept to a minimum. It is preferable to have no burden other than that of thedifferential relay.
RECEIVING, HANDLING AND STORAGEThese relays, when not included as a part of
a control panel, will be shipped in cartons designedto protect them against damage. Immediately uponreceipt of the relay, an examination should be madefor any damage sustained during shipment. If injuryor damage resulting from rough handling is evident,a claim should be filed at once with the transportationcompany and the nearest Sales Office of the GeneralElectric Company notified promptly.
Feasonable care should be exercised in unpack-
ing the relay in order that none of the parts areinjured or the adjustments disturbed.
if the relays are not to be installed immediately,they should be stored in their original cartons in aplace that is free from moisture, dust, and metallicchips. Foreign matter collected on the outside ofthe case may find its way inside when the cover isremoved and cause trouble in the operation of therelay.
GENERATOR AND REACTOR RELAYS
DESCRIPTI ONThe Type IJD52A relay is a single unit genera
tor differential relay. The Type IJD52B relay hasthree units, each of which is equivalent to that ofthe IJD52A. The induction unit of these relaysconsist of two coils assembled on laminated-ironU-magnets in such a way as to produce torque on adisk when current flows through them. The diskshaft carries a contact which is intended to energize the trip coils of two breakers.
A seal-in element is provided on each unit withits coil in series and its contacts in parallel with thecontacts of the induction unit. When the seal-in unitpicks up it raises a target into view. This targetlatches and remains in place until released by thereset button at the bottom of the cover.
OPERATING CHARACTERISTICSThe percentage slope characteristic of these
relays refers to the ratio Qf the differential currentto the smaller of the two phase currents, which willjust cause the relays to close its contacts. Fig. 3shows the operating characteristic for a relay with10 percent slope and 0.1 ampere minimum pickupcurrent.
The operating times for different values ofdifferential current and of load current are shownin Fig. 4. This time curve was taken with a 1/2time dial setting.
RATINGS
The restraining coils of these relays will carryfive amperes continuously without overheating. Theoperating coils of the models with 0.1-amperes minimum pickup will carry 0.6 amperes continuouslywithout overheating.
The current-closing rating of the contacts is30 amperes for voltages not exceeding 250 volts.The current-carrying ratings are affected by theselection of the tap on the target and seal-in coilsas indicated in the following table. When two tripcircuits are closed, these limits are for total current.
Amperes, AC or DC
Function 2-Amp Tap 0.2 Ampp
Tripping Duty 30 5Carry Continuously1 4 0.8
The 2-ampere tap has a d-c resistance of 0.13ohms and a 60 cycle impedance of 0.53 ohms whilethe 0.2-ampere tap has a 7 ohm d-c resistance anda 52 ohm 60 cycle impedance. The tap setting usedon the seal-in element is determined by the currentdrawn by the trip coil.
The 0.2-ampere tap is for use with trip coilsthat operate on currents ranging from 0.2 up to 2.0amperes at the minimum control voltage, If this
4
Percentage Differential Relays Type liD
tap is used with trip coils requiring more than 2amperes, there is a possibility that the 7-ohm resistance will reduce the current to so low a valuethat the breaker will not be tripped.
The 2 -ampere tap should be used with trip coilsthat take 2 amperes or more at minimum controlvoltage provided the tripping current does not exceed 3é amperes at the maximum control voltage.If the tripping current exceeds 30 amperes an auxil -
iary relay should be used, the connections beingsuch that the tripping current does not pass throughthe contacts or the target and seal-in coils of theprotective relay.
BURDENSThe burdens of the two coils at 60 cycles ar’
as follows:
r I Power 1Coil Amp Volt-amp Ohms Factj
Restraining I 5.0 17.55 0.7 0.27rating J.6 j 26.1 72.Sj 0.27
Of course there is no current flow through theoperating coil under normal conditions, hence thehigh burden is not usually objectionable.
CURRFNT FROM GFN. TC BUS.
Figure 3. (K.-6375795-l) Operating Characteristics of Type IJD52A and l1D52B Relays with 10 Per Cent Slope
(zLtO
O9—
)ii
•b
ij
(11CaC)
4-.0
1—4
C)
Ui
Li
C)L
i1..
1._i
Ci
Li
—
IA
C’)
C.
aI-.
-4
I-I0)C)a)IAa)C)
IS
O-N
O.3..kV
13C—
CD‘-410
‘-1’
F—IC0)
CD
Sc
10
0I
LJ
N.l4)
CD
Co
Sc
F—
0’
0)
N1
CD
Co
Sc
0)
CI
Figure 5. (K-h2O9677-3 Type IJD52A Relay, InternalConnections (Front View)
Figure 7. (K-6154157-4) Differential Protection of aGenerator using Type IJD52A Relays
Figure 6. (K-6209678-2) Type IJD52B Relay, InternalConnections (Front View)
Figure 8. (K-6154219-3) Test Connections for theType IJDS2B Relay
Percentage DiPerential Rela’i IJD
11
RIGHT)
OPEPSI1NG (L&FT)ELEMENT
- SI’! NA) ILLli&NiS
51111Ff FING[I?
13t VOLI OLJltI
111111 FOIClIDI InlEtS
il—FuLl CIOSSIT hillEl
Si—PiIl CIICIIT INASIEIIl—LitlOil hiLt?, hill liSlE III’! liiIF—FIESSILL ItChy flPt IJISSO.-lIZILlAIY SWIRl, CLOSES Sill
CIICIIT litAtit IT CLOSESOC-,VLIATII. COIL
IC—lt3IlilIISl COILSI—II&LII tilT, hIll TLItLTTt1huPTr—TiTluTr PISILCTOSI. IF ISIS
-l
Percentage Differential Relays Type LTD
TRANSFORMER RELAYS
DESCRIPTION
The Type 11D53C is a single unit transformerdifferential relay. It is usually applied for differential protection of a single-phase transformer, orin a set of three for protection of a three-phasetransformer. The Type 1JD53D has three unitssimilar to that of the Type IJD53C, with their contacts connected in parallel. The single unit relayis shown on the cover page and in Figs. 1, 9, and 10.
The induction unit of these relays consists oftwo coils assembled on laminated U-magnets in sucha way as to produce torque on a disk when currentflows through them. The disk shaft carries a contcr which is intended to complete the trip circuitsI or two breakers.
A seal-in element is provided on each unit toprotect the main contacts. When the seal-in picksup it operates a target which remains visible untilreleased by the rest button at the bottom of the cover.
OPERATING CHARACTERISTICS
The characteristics of these relays are suchthat when the current in the two circuits are in thesan]e ratio as the two tap-plug position numbers,therc is no operatingtorque produced. A numericalexample of this statement will help to t3xplain this.
Suppose the tap plugs of a Type IJD53C relay areset in the 3.2 tap of the upper tap block and in the5.0 tap of the lower tap block. Now, with polaritiesof the currents as indicated in the diagram with thecurves of Fig. 13, assume that 3.2 amperes flow outterminalS, 5.0 amperes interminal7, andthe differ-
ence,1.8amperes,outterminal6. Under these conditions no torque will be produced by the operatingU-magnet, but considerable torque will be producedby the restrainingU-magnet. Furthermore, as longas the two currents in terminals 5 and 7 remain inthe ratio of 3.2 to 5 and are 180 degrees apart intime phase, there will be no operating torque.
These relays are built with twotypes of percent-slope characteristics; 25% slope, and 50% slope.The significance of the percent -slope characteristiccan best be understood from an extension of the example above. Takingthe25%slope relays as an example, suppose that the current into stud 7 increasesto 125% of 5.0 orto 6.25 amperes whfle the currentout of stud 5 remains at 3.2 amps, this representsa condition of 25% unbalance. The same thing wouldbe true if the 5 amp value were held constant whilethe 3.2 value was increased 25% or to 4 amperes.
It should not be inferred from this discussionthat the relay will necessarily close its contactsunderthe conditions dscribedas 25% unbalance. Atlow current values considerable more unbalance isnecessary to overcome the effect of the spring.However, at current values of twice tap value andabove, the unbalance required for operation will notgreatly exceed 25%. Fig. 11 and 12 show these relationships graphically for currents several timesrated values. In explaining these graphs, the sametap ratio of 3.2/5willbe used. If 12 were 50 amperesthere would be no operating torque developed if
= 3.2 X 50 = 32 amperes. This relationship is
shown by the dotted lines running diagonally acrossthe graphs in Fig. ii and 12. If I were to increaseabove the no torque condition by 25%, it would now
UPPER TAP PLATE
UPPER PIVOTTSP SELECTOR COIL
SEAL- INELEMENT
TAR DC’
STATIONARY:sNTACTS
MOVAB_E —-
CONTACTAS SEM BLY
-FMAINSTATIONAR’CONTACTS
CRADLE
LOWER TAPPLATE
DISK S,IAFT
MAIN MOVINGCONTACT
CONTROLSPRING ANOSOJUSTINGRING
OPERATINGMAGNET AND
COIL ASSEMBLY
_.ORAG MAGNE1
RESTRAININGMAGNETSNO COILASSEMBLY
Figure 10. (8007208) Type IJD53C Relay Mounted inCradle (Rear View)
Figure 9. (8007205) Type IJD53C Relay Mounted inCradle (Front View)
UT0
0
OT
0
0a
0
LI..
8
Percent age Dif[i.rcntial Relays Tyc [in
be 1.25 x 32 = 40 amps. Fig. ii shows this condition for values of 12 between 0 and 70 amps. 11 onthe other hand, Ii were to r e main constant at 32amps and 2 were to increase 25%, 12 would go to50X1.25= 62.5 amps. Fig. 12 shows this conditionfor values of I between 0 and 70 amperes. Thesecurves show the i - n i ni u rn current on the ordinal.e to close the relay contacts for a given current on the abscissa when the various tap ratiosshown are used. The time characteristic is shownin Fig. 13.
-e
-
1
H
Fig. 14 and 15 show curves for the relays with50% slope characteristics.
MINIMUM PICKUP
These relays are adjusted at the factory to closetheir ront acts at 40 percent of tap value in one circult with no current in the other. This pickup maybe increased by means of the control spring to 125per cent of tap value as described under ‘Adjustments.
TAPS
11 12
5. 0—4 .6
Fuure 11. (64O1h9,Sh.l 2fl Jperatin$ Characteristics of Type L1T)53C and IJD53D RelaysWith 25 alope When I is Excessive.
CURRENT DIFFERENTIAL RELAY1JD5381 FOR TWO—WINDINGTRANF.__PROTECTION.UINIMU’.Y VALJ[S OF lj 10CLOSE CONTACTS wITH EXCESSCURRENT IN t CIRCUIT TORARE RATIO CF 1 TO 1225GREATER THAN NORRAL
±
4-.-c
H :a[E1U TLi ±,1!
I /
‘ I 1 251 TA2 BLOCK CTTIN6 - - ——0 I 2 LOWLP bLOCK 3.iT;N0 1 — -
— 3 54—I--- -
I / / 1/ 3.8-1.(r
-—F--——--- -;--
--- - --
5C± ±:IZ E E—-—
- : : .4.2+5.7
40-: — - - -
-
-
‘c Y / - — U L
J__ P
-
BIOCK>P A—-——---i/ E C
\ R R
2( - — — — IV - , - -— NORMAL SALANCE - —
li “l/’ ‘ ‘ .. - . \ON 3.-a.OTAPS
;T\-1 — — 4’ / — - - — - — OPERA]HNG - —
± POINT
CK) 10 20 40 50 50 70 80
I? — CuORNT IN LO.’:EI T[e’NAL
‘3
Percentage Differential }eIays Type 1JD
RATINGSThe standard models of these relays have a tap
range of 3.2 to 8.7 amperes. Any of the circuits
will carry twice the tap setting or 10 amperes,whichever is less, continuously on any current tap
100
90
80
U) r.fl_ F-I
I— 1___-I. (;
PER
TAP
B
0CK
II’
without overheating.
The current ratings of the contact circuits arediscussed fully in the section on generator relays.This discussion applies to the transformer relaysalso.
Figure 12. (K (54O0lO9Sh23l) iperating Characteristics of Type IJD53C and 1J1053D Relays
With 25 Slope When 12 is Excessive.
—1I
U,
I—
In in
‘0
DI
UI
<‘4
o ,o
In
‘0 (‘4
IT
U)
In U)
L0wIR
IAP
BL0CII
TA PS11 2
.3.8 4.6
:Ii ‘c
zi i =
—:
= : =I,
-
I,‘
I
/ ,
Ti
‘-I
-J
LX;
IX;
0-J
I
-II-)
(N
:z:7 z:ZiZ2i .‘ , ,
- --
-- --1 ii- — - — - - -
1’- : NORMAL BALANCE ON
II / / i 7 3.2—5.O AMP.TAP----
--
‘1 77/ , / N.
‘ 0[RATlNG
7 ‘ en- OIFFERE’4TIAL RELAY— -
— ) ) 7 T , 7 1105301 FOR TAO—WINDING TRANSEPROTECTION.
— - - - .4 - — -
I / 7 . MINIMUM VALUES OF I TO CLOSE- -
- 1 1 7 /- — - CONTACTS WITH EXCE CURRENT
-
- 1 1 i /7 - l - —
- IN 12 CIRCUIT O MAKE RATIO- - < ‘ - -
- — - - -
— OF I- TO I 25% GREATFR THAN-- /l/ N0RML.
1
liii,’11 /1
- - - — — — 1- - -
iOwER Tp BLOCK SETTING
1’ i — —2 11PpFR IA ULCCK SETTINGjç
50
40
30
20
10
00 10 20 30
Ii — CURRENT40 50 60 70 80IN LlPPR TERMINAL
10
Pc rceritage Differential Rel.iy Type [.rD
C,
Figure 13. (K-6400171-4) Typical Time-Current Characteristics of Type 1J1153C and IJD53D Relays.
BURDENSBurdens for the standard toils at five amperes
and rated frequency are given in the table on theright. Operating coil burdens are for the minimumcurrent tap, 3.2 amperes, while restraint coil burdens are withthe 5.0 ampere tap on both tap blocks.
Impedance of the operating coil on any other tapis inversely proportional to the square of the tapvalue. The impedance of the restraint circuit withunequal tap settings is difficult to calculate, but ingeneral will be quite low.
Freq. Coil Volt-amp Imp. Ohms PF60 Operating 20.5 0.82 0.33
Restraining 1.1 0.043 0.94
50 Operating 17.5 0.70 0.35Restraining 1.0 0.041 0.96
25 Operating 10.5 0.42 0.41Restraining 0.9 0.037 0.98
ii
Perceitage Differential Relays Type IJD
Figure 24. (K-6400379,Sh.l [1)) Dperating Characteristics of Type IJD53C and IJES3D Relays
With 5O Slope When lis Excessive.
INSTALLATION
Cl)
FC.,cCD
L1
LOCATION
T1e lcca. ion should be clean and dry, free from
dust a !d I-(rssi c vibration, and we 11 lighted to
facjl’.ite inspection and testing.
MOUNTING
The relay should be mounted on a vertical sur
face. The outline and panel diagrams are shown in
Fig. 21 and 22.
12
Percentage Differential Relays Type lID
0
Figure 15. - 4u037l3,Sh.2 31) )perating Characteristics of Type LJD53C and IJD53D belaysWith 50 blOpE When 19 is Excesjv.
CONNECTIONSGNERATOR RELAYS
Internal connections for the Type IJD52A areshown in Fig. , and for the Type IJD52B in Fig. 6.
Typical external connect ions for the Type11D52A are shown in Fig. 7. It will be noted thatcontacts are provided for closing two trip circuits,namely the line breaker andthe field breaker. Connections for the Type IJD52fl will correspond tothese except that the stud numbers will be different.
13
Percentiwe Differential Relays Type IJD
TRANSFORMER RELAYS
Internal connections for the Type 13D53C are
shown in Fig. 16 and for the Type IJD53D in Fig. 17.
Typical external connections forthe type IJD53D
are shown in Fig. 18 and 19. It will be noted that
this figure shows connections to be used when the
transformer bank is Delta-Wye, or Wye-Delta. IS
the hank is Wye-Wye with grounded neutrals, then
the connections shown in Fig. 7 for the generator
relay can be applied to the transformer relay pro
vided the transformer consists of three, single—
phase transformers. This connection cannotbeused
if a three-phase core-type transformer is used since
the case acts in a manner similar to the delta insofar
as it is a source of zero-phase sequence current.
Also, the wye.-wye arrangement cannot have a delta
winding, even though that winding is not used for
load purposes, for the same reason.
External connections for the Type IJD53C relay
should correspond to the connections for phase 2
in Fig. 18.
In each case, the smaller of the two secondary
current should pass through the right-hand stud on
the relay (back view), that is, stud 2, 5, or 8.
There ,is a useful rule which can be applied to
determine whether delta orwye current-trans
former connections should be used for differential
re1ayin of a 3-phase transformer bank composed of
three similar single -phase transformers, each hay-
trig two or more windings. This rule is as follows:
The current transformers in [he leads to a wye
connected winding should be connected in delta;
current transformers in the leads to a delta-con
nected winding should be connected in wye.
Since there are several ways of connecting the
current transformers in wye or delta, the following
additional rule should be noted: Make the delta
connection of the current transformers a replica of
the delta connection othe power transformers; the
wye connections of the current transformers should
be a reversal of the wye connection of the power
transformers.
GROUND CONNECTIONS
One of the mounting studs or screws should be
permanently grounded by a conductor not less than
No. 128 FS gage copper wire or its equivalent.
ADJUSTMENTS
TARGET AND SEAL-IN ELEMENT FOR BOTH
TYPES
For trip coils operating on currents ranging
from 0.2 up to 2.0 amperes at the minimum control
voltage, set the target and seal-in tap plug in the
O.2-ampere tap.
For trip coils operating on currents ranging
from 2 to 30 amperes at the minimum control volt
age, place the tap plug in the 2-ampere tap.
The tap plug is the screw holding the right-hand
stationary contact of the seal-in element. To change
the tap setting, first remove the connecting plug.
Then, take a screw from the left-hand stationary
contact and place it inthedesiredtap. Next remove
the screw from the other tap, and place it in the
left-hand contact. This proced’ire is necessary to
prevent the right-hand stationary contact from
getting out of adjustment. Screws should not be in
both taps at the same time as pickup for d-c will
be the highter tap value and a-c pickup will be in
creased.
GENERATOR RELAYS
No adjustment of the relay is necessary other
than the setting of the target and seal-in element
tapplugdescribedabove. Howevei-,the relay should
be inspected for any loosening of the screws that
may have occurred during shipment.
TRANSFORMER RELAYS
These relays have been adjusted at the factory
to operate as indicated by the characteristic curves.
However, it is necessary to make the proper tap
selections for the particular application. The taps
chosen should be such that the ratio of tap settings
lsequaltothe ratio of currents to the corresponding
tap blocks. Itis also desirable that the tap settings
should be equal as nearly as possible to the respec
tive currents which will flow under normal condi
tions. The normal currents at the relay terminals
can be readily calculated from the current trans
former ratio and the normal load on the power trans -
formers.
The tap settingswill, of course, usually be made
before the relay is energized initscircuit. If, how
ever, it isnecessaryto change the tap settings after
the relay has been installed, the connection plugs
shouldberemovedfrom the case before proceeding.
When the tap plugs are inserted into the tap blocks,
caution should be exercised to screw them all the
way down until the lock washer is flattened between
the plug and plate. These precautions are necessary
to avoid opening the current transformer secondary
circuits.
A further adjustment that may be necessary at
the time of installation is the setting of minimum
pickup current. The relays are adjusted at the
factory so that with no current in one circuit, 40 per
cent of tap current is required in the other circuit
to close the contacts. This value can be increased
by turning the c o nt r aT spring adjusting ring (see
Fig. 9) in a counter-clockwise direction. Pickup
should not be increased to more than 125 percent
of tap value, or the control spring may be damaged.
At the time of installation, the relay should be
inspected for any loosening of the screw that may
have resulted from vibration or rough handling
during shipment.
14
I’Figure 16. (K—6556496.-3) Type IJD53C Relay, Internal
Connections (Front View)Figure 17. (K-6556497-2) Type IJD53D Relay, Internal
Connections (Front View)
Figure 18. (K-6142O7-4) Differential Protection of Power Transformer Using a Type 1J053D Relay.
RESrRAININGELL(Efi1S
Percentage Differential Relays Tupe IJL)
SEAL -LIIIN IT
U,U,to
(0
U
0,
(0U,U,
tC
RESTRAINIERGLLEMENTS
k SHORT FINGLRSSIORT FINGERS
GERICI FLCTICN NLfl.18(RS— PLH[R CIRCLIT RREAKflA. PMARY
5.1—C — PLWfR CIRCIJLT RAEA S[CO’DARYLOCROL RELAY. RAND R[CT. TY PR
b7 —D!FFt!TLL FLA, V[ IJI3s3— IUX.. S*I H, CLC(3 WHII, CIXCIJ:T RREXXIX
AC — J’FD4IIRG CALRC _R1’TRAIN INS COILSI — YXAL—IN UNITCC — rFIp COIL
15
Percentage Differential Relays Type IJD
r
!iF’‘
______
1 P f; T
b
t _i
I IL
L 1.
I OICOt MiIOfl
__________
[Yr 7cTiWrT
{iiT I DIUIILMT A; ti1AVTAYLill ‘ _nL_Drt E_Zj_ -;-Ai 11t JP O)lFcAlT C.AP Lila
loS 159 TOP 2ihlb45 .lsIciL_______.311 TPFIffii a2CFt0I.3 A 11JFt14t1 IASICLAI’OIL tililit DAlofO tillS AfiPLO
iLT ID SIFLIt IFIAIL 1,1115. r TILhI Fti&5A fllMP5. TRAA5ICMLII
taA(PIMI IIAGWW & ISTOAIA1hiJ 111141141 loSIGIAIIOKS APPlY.
*111 - -III; FLP 1 F 111111515 APPlY ID JFO’D. 05110 STill lt.UPJ1S FIFtY TO
IIOYl. 511.3 4jA5 5 A I Ill ;PX31 1440 Ft ItIYtfliAY ,N 11111,141
11,1111 II ht&&MPl TO 1140)1 (1,110115 In AlLAY TArS. fl( 5114 APPIlIS
III flIt lit (10 OFLIIIP 01 SOFT, 4—7_Ill lit .11413 7-5—lI ill 1.0131(1
tOll 3; 0.30111 7; 7 11111,1.31 IlL PT 1411 111.30140 1(01 114)4 TOIJICt il
llhIUl HI Omit 1RA1l5l14H 11FF II 114.311111
Figure 19. (0264B0449-3) Differential Protection of a Power Transformer Using a Type IJD53D Relay
With Desensitizing Equipment.
OPERATION
Under certain circumstances, false operationmay occur when large external fault currents arecleared. This would be due to the sudden releaseof reverse torque on the relay shaft. If this troubleis encountered it probably can be corrected by oneor more of the following adjustments.
I. Increasing the disk travel by loosening thetwo set screws and turning the Textolite dial,mounted at the top of the shaft, counter-clockwise.The dial should not be turned beyond the numbertwo setting inscribed in the dial or to a positionwhere the slot in the disk is allowed to pass underthe pole of the operating coil. The relay will notoperate properly when the slot is under the polesince the two fluxes from the pole cannot inter-actin the disk because of the slotted separation.
The Type IJD relays have the time dial set andlocked at the factory. The types IJD52A and IJD52Bare set at the 0.5 time dial setting and the TypesIJD53C and 1J053D are set at the 0.8 time dialsetting. The 0.8 time dial setting is equivalent toa three-quarter inch travel at the periphery of thedisk.
2. Moving the drag magnet out from the centerof the shaft.
3. Increasing the wind-up of the spiral controlspring. This should not be increased more than90 deg. over the original factory setting.
DESENSITIZATIONAny of these adjustments will increase the
operating time on internal faults, and the third alsowill increase the minimum current required foroperation.
In some instances it may be that the maximumcurrent setting of these relays will not be highenough to prevent them from operating on magnetizing inrush current. If such a condition should exist,it is recommended that the IJO relay be used with anauxiliary desensitizing equipment consisting of anauxiliary relay, a potential transformer, and threeexternal resistors connected as shown in Fig. 19.
To facilitate the connection of the desensitizingequipment the relay is provided with an extra studwhich terminates at the junction of the two 5.0 amp.taps.
This permits the external connection of au.xiiary desensitizing equipment to the operating coilonly, without affecting the restraining torque. Whenthe desensitizing equipment is connected in thismanner, the pick-up value ol the relay is raisedthe same amount regardless of the direction fromwhich the transformer is energized.
The following table shows the factor by which
the nominal pickup must be multiplied when the de
sensitizing resistor 579A121 G—2 is connected as
described above. Fig. 19A shows the wiring
diagram and mounting outline for the resistor.
-- —
:j1 11111H(0 I
l;{I iH-- L:_
tn4L
FlJI1
fV1L
57-li
52-li
16
Percentage Differential Relays Type LID
.15 .15 .15 .15 .15 .15
REQUIRED JUMPER CONNECT TOOHMS RELAY
0.05 1 TO 3 2 TO4 1 AND 4
0.10 1T05 3T07 IAND70.20 1 TO 7 1. AND3
0.30 NONE 1 AND 3CONNECTIONS REFER TO ONE RESISTOR ONLY
Figure 19A. (O418AO999-3 Wiring Diagram and Mounting Outline for External Resistor
MOUNTING FIXTURE-1OWN IS FOR THREERESISTORS, ELECTRIC—ALLY SEPARATE
17
Percentage IDifferential R’1avs ‘l’vije IJD
RESISTOR OHMS J0.057 0.1 ro.2 0.3
MULTIPLIER 8.0 2.1 1.65
Since the resistance shui:tiug the operating coil
determines the pick—up value of the relay, it is im
portant that the lead resistance from the relay to the
desensitizing resistor be kept as low as possible.The auxiliary relay is time opening and instantaneousclosing, and its contacts are closed when the relay
is energized. The external resistors are connected
across the operating cods of the IJD relays throughthe contacts of the auxiliary relay. When thefirst transformer breaker is closed, the auxiliary
relay is energized from the potential transformersecondary, but does not open its contact immethately.
This permits a momentary raising of the IJD relaysetting as part of the current, which would normally
flow through the operating coils, is shunted through
the external resistors. When the contacts of theauxiliary relay open, the shunt circuit is removedand the IJD relay functions at normal rating.
The Type HDD Percentage Differential Relay,
with harmonic restraint is available for transformer
protection and is inherently Insensitive to inrush
current owing to its harmonic restraint feature.
MAINTENANCE
The relays are adjusted at the factory and it isadvisable not to disturb the adjustments. If, for anyreason, they have been disturbed, the following points
should be observed in restoring them:
DISK AND BEARINGS
The lower jewel may be tested for cracks byexploring its surface with the point of a fine needle.If it is necessary to replace the jewel a new pivotshould be screwed into the bottom of the shaft at thesame time. A very small drop of General Electricmeter-jewel oil, or fine watch oil, should be placedon the new jewel before ii is inserted. The jewelshouldbe turned up until the disk is centered in theair gaps, after which it should be locked in thisposition by the set screw provided for this purpose.The upper bearing pin should next be adjusted untilvery little end play can be felt; about .015 inch iscorrect.
CONTACT CLEANING
For cleaning fine silver contacts, a flexibleburnishing tool should be used. This consists of a
flexible strip of metal with an etched roughenedsurface, resembling in effect a superfine file. Thepolishing a c t i on is so delicate that no scratchesare left, yet corroded material will be removedrapidly and thoroughly. The flexibility of the toolinsures the cleaning of the actual points of contact.Sometimes an ordinary file cannot reach the actualpoints of contact because of some obstruction fromsome other part of the relay.
Fine silv.’r contacts should not be cleaned with
230
1 --- -
4 s-f,’ j2 0Pf0 ->
.
..P010 lOp 05,1
——____
‘I All 1*0 .011
:EJ—,) tj—•0.LV,111ll .-
——
—
— -
Figure 20. (K-6154218-1) Test Connections for the
Middle Unit of the Type 13D53B Relay.
knives, files, or abrasive paper or cloth. Knivesor files may leave scratches which increase arcingand deterioration of the contacts. Abrasive paper
or cloth may leave minute particles of insulatingabrasive material in the contacts and thus prevent
closing.
The burnishing tool described above can be
obtained from the factory.
PERIODIC TESTING
An operation test and inspection of the relay at
least once every six months are recommended. Test
connections are shown in Fig. 8 and Fig. 20.
RENEWAL PARTS
It is rrcommcnded t hat sufficient quantities
of renewal parts be carried in stock to enable theprompt replacenwnt of any that are worn, broken,or damaged.
When ordering renewal parts. address the near-
est Sales Office of the General Electric Company,
specify quantity required, name of part wanted, and
give complete name plate data, including serial
number. If possible, give the Ge tie ral Electric
Company requisition number on which the relay
was furnished.
Since the last edition, changes have been made in Figures 21 and 22.
13
Percentage Differential Relays Type IJD
9. 125232MM
PANEL DRILLINGFOR SEMI-FLUSH MOUNTING
FRONT VIEWPANEL DRILLING
FOR SURFACE MOUNTINGFRONT VIEW
TYPICAL DIM.INCHES
MM
Figure 21. (K—6209271 18)) Outline and Panel Drilling Diiriensions for Type IJD52A and IJD53C Relays
_____
6 625
____
•• 168MM ‘
(2) 5/16—18 STUDSFOR SURFACE MTG.
riAss
-j
___
I. 12529MM1/4 DRILL
4 HOLES6MM
STUDNUMBERING
975310 C) 000
0000010 8 6 4 2
BACK VIEW
5/8 DRILL2 HOLES
15MM—
--;---
4.406112MM
I-CU iiUT
CUTOUT MAY REPLACEDRILLED HOLES
8.812224MM
1 1 5629MM
172MM1
5 687144MM
.50012MM
(TYPICAL)
CASE-
VIEWFOR
5/16-18 STUD
19
Percentage Differential Relays Type IJO
A9 97525iMM
6 75171MM
PANEL DRILLINGFOR SEMI-FLUSH MOUNTING
FRONT VIEW
TP1CAL DM.INCHES
MM
.50012MM
(TYPICAL)
PA1[L DRILLINGFUR SURFACE MOUNTING
FPINT VIEW
Figure 22. (I(—6209276 f5J) Outline and Panel Drilling Dimensions for Type IJD52B and LJD53D Relays
____
C 625 SEMI-FLUSH
168MM -
PANEL LOCATION
1 0-324) 5/16—18 STuBSOR SURFACE MTG.
1917 15 131100000
20,312
516MM
CLASS
I_L - -
U 0
(.6) iO-3, X 3/EMTG. SCREWS
00018 16 24
012
STUDNUMBER INS
9753100000
0000010 8 6 4 2
BACK VIEW
CUTOUTS MAY REPLACEDRILLED HOLES
T19. 3255MM
19875504MM
2185MM
19. 7550
——
1 ,46837MM
-3/4 DRILL20 HOLES19MM
CASE
--4
_
VIEW SHOWING ASSEMBLY OF HARDWAREFOR SURFACE MTG. ON STEEL PANELS
5/16-18 STUD
BC-7197(200) GENERAL ELECTRIC METER AND CONTROL BUSINESS DEPT., MALVERN, PA 19355