Sheet 1 of 2 Status:& N U Seismic Walkdown Checklist (SWC) Equipment ID No. ODGO12 Equip. Class' 2 (17) Engine Generators Equipment Description E4 Standby Diesel Generator Location: Bldg. Diesel Generator Floor El. 127 Room, Area D/G-9 Building Manufacturer, Model, Etc. (optional but recommended) CA I Instructions for Completing Checklist This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the SWEL. The space below each of the following questions may be used to record the results of judgments and findings. Additional space is provided at the end of this checklist for documenting other comments. Anchorage 1. Is the anchorage configuration verification required (i.e., is the item one of the 50% of SWEL items requiring such verification)? 2. Is the anchorage free of bent, broken, missing or loose hardware? I Y* NEI 3. Is the anchorage free of corrosion that is more than mild surface oxidation? 4. Is the anchorage free of visible cracks in the concrete near the anchors? YEY NEI YD NEI U- N/AD Uri N/AD UD N/AEJ 5. Is the anchorage configuration consistent with plant documentation? (Note: This question only applies if the item is one of the 50% for YE No UD N/AD bA4"23 6. which qn anchorage configuratio vqrification is required.) ancag freeu of N UW Based on the above anchorage evaluations, is the ancho age free of )X ND U-1 potentially adverse seismic conditions? oCi~OOr ~1?0LT EIZE 't>'fCfjCpA)A4 poettL,-WM *~)~~~~0 ~co3 ~' qi 12 Enter the equipment class name from Appendix B: Classes of Equipment. <C-3 > Peach Bottom Atomic Power Station Unit 3 MPR-3812, Revision 3 rnrrqnnnH~nr• Nn R5-19-171 C-372

Transcript of Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I...

Page 1: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:& N U

Seismic Walkdown Checklist (SWC)

Equipment ID No. ODGO12 Equip. Class' 2 (17) Engine Generators

Equipment Description E4 Standby Diesel Generator

Location: Bldg. Diesel Generator Floor El. 127 Room, Area D/G-9Building

Manufacturer, Model, Etc. (optional but recommended) CA I

Instructions for Completing Checklist

This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on theSWEL. The space below each of the following questions may be used to record the results of judgments andfindings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item oneof the 50% of SWEL items requiring such verification)?

2. Is the anchorage free of bent, broken, missing or loose hardware?I

Y* NEI

3. Is the anchorage free of corrosion that is more than mild surfaceoxidation?

4. Is the anchorage free of visible cracks in the concrete near the anchors?

YEY NEI

YD NEI

U- N/AD

Uri N/AD

UD N/AEJ

5. Is the anchorage configuration consistent with plant documentation?(Note: This question only applies if the item is one of the 50% for

YE No UD N/AD

bA4"236.

which qn anchorage configuratio vqrification is required.)

ancag freeu of N UW

Based on the above anchorage evaluations, is the ancho age free of )X ND U-1potentially adverse seismic conditions?

oCi~OOr ~1?0LT EIZE 't>'fCfjCpA)A4 poettL,-WM *~)~~~~0 ~co3 ~' qi

12 Enter the equipment class name from Appendix B: Classes of Equipment.

<C-3 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrqnnnH~nr• Nn • R5-19-171

C-372

Page 2: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Equipment ID No. ODG012 Equip. Class12 (17) Engine Generators

Equipment Description E4 Standby Diesel Generator

Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures? YEVNEI UD N/AL]

-t1,MRri.•ttn •4 jVr OW' SMJ&7,tIYO I)IK C3OOIJLM Iv.,r OdiLL-D) &,t'MOr

4"PlACtir. L-IKAT, -q'vt 1401tl5M'00 6V1,W) CNtACR. AJu.- ior 4Pg,,-a- F4,7 MACA

8. Are overhead equipment, distribution systems, ceiling tiles and lighting, Y[efNL] UE N/AL]and masonry block walls not likely to collapse onto the equipment?

I-JOr •i •s•,'r

9. Do attached lines have adequate flexibility to avoid damage? Yf'NEI UL] N/AU

10. Based on the above seismic interaction evaluations, is equipment free Y[n/Nl- UL]of potentially adverse seismic interaction effects?

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could YEI NEI U[]adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary.)

-4)u owLv wtqI-)o9 rd~ sto~Ror QrR,40&f~t,

Evaluated by: tf;/q;41 Date:

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 C-373.nrrPqnnndrinr.. Nn • RR-19-171

Page 3: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

* LK!

1',i1~A I r T

V ~41 I

* K1..'ii:'..;-1-

1 __

i --

_Pewz jp- 1A

I ~ 1?

V IM

III

I IQ

I.......

Mge~

ks

(9(c

j, . ... 6....

3.

AtL

T14

I 1 111 ~I Ii

I 1 I l~ I11 I

I I I

I

iL~LIlJ I I II I I

111111

I 1 I I I I

I IA I I - 1III

'I-) 1

(C4'~La(e~cI

.

.1..

' F

iC-3¼ I I

WUC Ox

- -~-~ -

[Illy

Is

6'A1 ý.- 7'

.p4~1~

rAL

rv*L

0AD

-A,~cCi

1-4

ULtG$

IALLI .,

(AZI CY

(Ir.hý KY

l..c 9LL'V

Lfl, 0 1"J1L7

,..i

+I •

I

t .

30, LTý. . ... ......... F

F i

'-3

...... i

*P ach 1 Ottoi. Ati~micM PR-3ý1 2, ýevis on 31

ion L~nit 3

Page 4: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

OD6o/2-

Coarse ThreadUNC Series Coarse Thread UNC Series

efunda I Dke.(joty I Caieer I Nk,ý j Sýancjards I ýndusulaj

ýScrdwl ThIreads.

Threa~d S'ystem

ýýUnifi~ed S'crew Threads-

UNC Coarset.UNF Fine

niied Sta nda rd Series

Tap DrIll

.:on6staht'?k6c Series.

I

i .... ji , ,'

:' : -'

I-.--'- --------" ,L Materiad s

Ads by Google

Design Processes I Units FormulasMathI .j

Download sae j 1926.

Download sae j 1926 SAE International Standards - webstore.ansi~org

#1* :0.073- 64 0.0629: 0.0544 o.os61 O.00218 0.900263

TFEE Publicatiaons

..Waste Managemen t:*.

Wind Sysiems *

Chemical Engineering*

NASA Tech Brlefs *

IndUstrial Maintenance

Paint &•Coatings

Machinery Lubrication

LEDS MagazinemoreL... : :..:.-.

#2z 0.086.-#3*. 0.099.

#4 0.112

#5 0.125

#6- 0138

#8. 0.164

#10: .019

#12* 0.216

1/ .. , 0.25

.5/16 0.3125

3/8: 0.375

7/16' 0.4375

9/16 0,5625

5/8. 0.625

-¾ 0.75

7/8 0.875

"1- 1

/ 1.125

1 1.254

.56" ".48 '

.40

'40

32,-

24

24ý•'20 "

18..

16

14

.12

10

"/ " 8 "" "

0.0744,:

:0.0958

0.1088

0.1177

0.1437

0.1629

0,2175•0.2764

0.33440 .3911

0A.4.o5084

0.685

0.8028

0,9188

.00648

.0.07410.-00822

0.0952

0..1008.0:.1268:

.0'.1404,

0.1664.0.1905:

0.2464

0.3005.'

0.3525

0.4084

.0.4633

•0.5168

0.6309

0.74270.851s2

. • • .." 0.0667.

0.0764-

0.0849.,

0,0979

0. 14 .2-0.1302:-

0.1449

0.1709.

0.1959

'0.25.24:

ý0.3073

0.3602" :

0.41670.47,23'

0,5266

0.6417,

0 .7547

0.8647:

0.9704

1.0954,

0.0031

0.00406

0.00496.

0.00672

0.007450.01196

0.0145

0.0206

0.0269

0.0454.

0.0678

0.0933

0. :12570.162:

Q.202

0.302

0.419

0.693

046037

0.00487.

.0.006.04

0.00796

0.00909

0.011o40.0,175

0. 0242'

0.0318

o.0524

0.0775

0.1419 .

0.1892

0.226:

0.334

40462

.0.7606

" 0.763.

,0.969,7 1.0322 0.9549

7 . 1.1572 .1.0799

I-

http://www,eMrNhCgglff IAi•'•]pcdl ?c•-f ~c, cfm[9/1312012 4:15:32 PM]

MPR-3812, Revision 3KI

C-35-7-17C-375

Page 5: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Coarse Thread UNC Series

38 1.375

11/2 1.5

IN 1.75

2 .2

24 2.25

21/2 i .2.5

23/¾ .2.75

3 3

31/4' 3.25

31/2 .. 3.5

33/4 3.75

4 .4

6 1.2667 1.1766 1.1946 -1.054

.6

5

45:

4.5

4-

4,

4:

4.

.4

.4

1.3917

1.6201i

1.8557

2.1057

2.,3376

2.5876.

2.8376

3.0876

:3.3376

3.5876

1.3016.1.5119

1.7353

1.9853.

2:2023

2.4523

2.7023.

2.9523

3.2023.

3.4523

.1.3196

:15335

I.7594

.2.0094:

2.2294

2.24794

2.7294-

2.9794

3.2294

3.4794

3.7294

.1.294

1.74

.2.3

'3.02

3.72

4.62

5:62

6.72

7.92

19.2110.6,1

1.155

.1;405

1.9

3.25

4:

4'.93

.5.9.7

7.1

8 .33

9-.66

11.084 : 3.8376 - 3.7023

Ads by Google

MIT Engineering MS + MBADual Graduate degrees in 24 months 6-mth Internship. Fellowships Avail - LGO.MIT.edu

NJ Stainless Steel ScrewDistributor of Stainless Steel Screws. Order Online Today! - www.FordFasteners.com

Bolts, Nuts. and ToolsYou Want It, We Got It! #1 In Customer Service - BoltsNutsandTooisocom

Taps and Dies100,000 In stock specials, metric, hard to find - www;holesawsunllmlted.com,

Huarn enesi About kLiUs Pyacy~ ~Dicaimer Conta~ AdetsCopyright C 2012 eFunda, Inc.

http://www.ef kO&6%Wngsý,l rgigglqn.cfm[9/13/2012 4:15:32 PM]MPR-3812, Revision 3r.nrm.•nnnrsmrnP Nn • RR-1l-17.1

C-376

Page 6: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

=r

;D -0

* 0

0

CD

C)

0

0-A0-

Page 7: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

V~ 0M

z 0* 0

S .W

m-aCV

CD

50

C)0

N)

Page 8: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

'~o

OD 03

z -u

5'

c

.0C)S,

N)

Page 9: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status: 0 N U

Seismic Walkdown Checklist (SWC)

Equipment ID No. ODP Equif. Class12 (05) Horizontal Pumps

Thnilinment ThPientinn E4 DIG Lidye Oil Transfer Pumn

Location: Bldg. Diesel Generator Floor El. ]2/'.-14,- Room, Area D/G-9B u ild ing ."4 Z 4 -

Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist

This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on theSWEL. The space below each of the following questions may be used to record the results of judgments andfindings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item oneof the 50% of SWEL items requiring such verification)?

2. Is the anchorage free of bent, broken, missing or loose hqrdware?

3. Is the anchorage free of corrosion that is more than mild surfaceoxidation?

4. Is the anchorage free of visible cracks in the concrete near the anchors?

5. Is the anchorage configuration consistent with plant documentation?(Note: This question only applies if the item is one of the 50% forwhich an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free ofpotentially adverse seismic conditions?

YEI NX

YE3"NE] UI- N/All

Y[9"NE] UE N/AO

Y~1'NE1 UD N/A[

YEI NEI UIJ N/A

NEI U[Q

"Enter the equipment class name from Appendix B: Classes of Equipment.

<C-3 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3flnrrPnnnrli~nr'. Mn •R-19-17.

C-380

Page 10: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Equipment ID No. 0DPI'R 60 Equip. Class" (05) Horizontal Pumps

Equipment Description E4 DIG )! Oil Transfer Pump

Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures?A• WT'r TA •bT'W

8. Are overhead equipment, distribution. systems, ceiling tiles and lighting,

and masonry block walls not likely to collapse onto the equipment?

9. Do attached lines have adequate flexibility to avoid damage?

10. Based on the above seismic interaction evaluations, is equipment freeof potentially adverse seismic interaction effects?

YIt/ND UD N/AD

YIEJ'4E UD N/AD

YEI'ND UEI N/AD

Y[3ND UD

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could YM/NED UDadversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

At/A

Evaluated by:' Date: _ _ _ _ _ _

qjl'71ýAIZ

< C-4 A>

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3flnrrP-nnndPnr.P Nn • R-19-17q

C-381

Page 11: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

- -0

;p~

z o

m

-oCD

I

2CD

-50

Page 12: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status: ON U

Seismic Walkdown Checklist (SWC)

Equipment ID No. ODT40 Equip. Class12 (21) Tanks or Heat Exchangers (Vertical)

Equipment Description E4 Diesel Generator Fuel Oil Day Tank

Location: Bldg. Diesel Generator Floor El. 127 Room, Area D/G-9

Building

Manufacturer, Model, Etc. (optional but recommended) -

Instructions for Completing Checklist

This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on theSWEL. The space below each of the following questions may be used to record the results of judgments andfindings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item oneof the 50% of SWEL items requiring such verification)?

2. Is the anchorage free of bent, broken, missing or loose hardware?

3. Is the anchorage free of corrosion that is more than mild surfaceoxidation?

4. Is the anchorage free of visible cracks in the concrete near the anchors?

5. Is the anchorage configuration consistent with plant documentation?(Note: This question only applies if the item is one of the 50% forwhich an anchorage configuration verification is required.)

COA]RUIc"AV oM• ' DWTc OwO 1q9057t3, tv.7

6. Based on the above anchorage evaluations, isthe anchorage free ofpotentially adverse seismic conditions?

YR'ND

YEýNE- U0 N/AD

YEI'N[I UI1 N/AD

YE(NEI UD N/Al

YE3'NE UDl N/AD

YWfN-I UD.

12 Enter the equipment class name from Appendix B: Classes of Equipment.

<C-3 )

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3(.nrr.nnnd1.nr'.p Nn • RR-19-17. C-383

Page 13: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Equipment ID No. ODT40 Equip. Class12 (21) Tanks or Heat Exchangers (Vertical)

Equipment Description E4 Diesel Generator Fuel Oil Day Tank

Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures? Y["NEI UO] N/AOl

.8. Are overhead equipment, distribution systems, ceiling tiles and lighting, YMNI"N U-I N/AOand masonry block walls not likely to collapse:onto the equipment?

- 9. Do attached lines have adequate flexibility to avoid damage?

10. Based on the above seismic interaction evaluations, is equipment freeof potentially adverse seismic interaction effects?

YF/NI" UEI N/AO

YOI/NI-I u-1

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could Y0'/NEI- U-1adversely affect the safety functions of the equipment?

Comments (Additional pages may, be added as necessary)

NAl

Evaluated by:L.&:=v

Date: I

812?/26[2

< C-4 >Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrP-nnnr1Pnr.P Nn• RR-19-17.1

C-384

Page 14: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

,-U0

-. 0

(D

z0 0

Lcn

0:3

II

m

CD

Page 15: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status: N U

Seismic Walkdown Checklist (SWC)

Equipment ID No. AD*9t- Equip. Class12 (09) Fans

Equipment Description DIG Building Vent Supply FanLocation: Bldg. Diesel Generator Floor El. 151 Room, Area D/G-20

Building'

Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing ChecklistThis checklist may be used to document the results of the Seismic Walkdown of an item of equipment on theSWEL. The space below each of the following questions may be used to record the results of judgments andfindings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item one YI• NEIof the 50% of SWEL items requiring such verification)? V

u/erl40 d' 0 k V

2. Is the anchorage free of bent, broken, missing or loose hardware? 1; LNIUE] N/AE

UD N/AE3. Is the anchorage free of corrosion that is more than mild surface Y¶ DNE]oxidation? /ttid J c ,/c --t

4. Is the anchorage free of visible cracks in the concrete near the anchors?

5. Is the anchorage configuration consistent with plant documentation?(Note: This question only applies if the item is one of the 50% forwhich an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free ofpotentially adverse seismic conditions?

Y;NE UO N/AE

P NEI UL N/All

)NEI ULD

12 Enter the equipment class name from Appendix B: Classes of Equipment.

<C-3 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3flnrrPnnndPnr.P Nn RR-19-17.•

C-386

Page 16: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

obVOOV' 4cEquipment ID No. ODVV9- Equip. Class" (09) Fans

Equipment Description DIG Building Vent Supply Fan

Interaction Effects

7. Are soft taets free from impact b e met or structures?

8. Are overhead equipment, distribution systems, ceiling tiles and lighting,

and ma onry block walls not likely to collapse onto the equipment?

9. Do attached lines have adequate flexibility to avoid damage?

10. Based on the above seismic interaction evaluations, is equipment freeof potentially adverse seismic interaction effects?

Y/O NE] U[] N/A[U

ý9NEII UL- N/AUI

ULI N/AI-

4NIJ UE1

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could ';t "[-1 U[I]adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

Date:

A(3/

< C-4 >Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrAqnnnnrJ Nvn" RR-19-17R

C-387

Page 17: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

(D 3.

s >*pi Er~

O= 3

m30CD

C)

0)0ý

Page 18: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

-. 0

z o!.0

-~CD

-1 .

m.0C.

CD

Page 19: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

0 uCD

z T. o:30

0

T

* 0

ci,

m30

C)

CD.-06

Page 20: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:&M N U

Seismic Walkdown Checklist (SWC)

Equipment ID No. 0HT95 Equip. Class12 (21) Tanks or Heat Exchangers (Vertical)

Equipment Description E4 Diesel Generator Starting Air Reservoir

Location: Bldg. Diesel Generator Floor El. 127 Room, Area D/G-9Building

Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist

This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on the:SWEL. The space below each of the following questions may be used to record the results ofjudgments andfindings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item oneof the 50% of SWEL items requiring such verification)?

YgNEJI

2. Is the anchorage free of bent, broken, missing or loose hardware?

3. Is the anchorage free of corrosion that is more than mild surfaceoxidation?

4. Is the anchorage free of visible cracks in the concrete near the anchors?

5. Is the anchorage configuration consistent with plant documentation?L.L (Note: This question only applies if the item is one of the 50% for

K hc a anchorage configuration verifi to §required.)A~

ZW -J t-'A V."ocr6H; -5(Jý-O r

46. Based on the above anchorage evaluations, is the anchorage free ofpotentially adverse seismic conditions?

u ACCUPT'A1BLC 1- c 1I1/5-Z

EKNEI UEI N/ADZ

Y"NEI UD NIAE1

YIg'NEI UE1 N/Afl

YEI NX UEJ N/A[l

4~r~La '~ ncio- 6A4~

YNNEIUE

12 Enter the equipment class name from Appendix B: Classes of Equipment.

< C-3 >"

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrPnnnd1nr-.p Nn • R.R-I-1-71

C-391

Page 21: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Equipment ID No. 0HT95 Equip. Class"2 (21) Tanks or Heat Exchangers (Vertical)

Equipment Description E4 Diesel Generator Starting Air Reservoir

Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures?

W4 .V9j IFAF4M(?T5

8. Are overhead equipment, distribution systems, ceiling tiles.and lighting,and masonry block walls not likely to collapse onto the equipment?

Y["ND UO N/AD

Y[2NND UD N/A•

VL~jL½eer- UV~3 '~'r~OW LT ~A'es4uLWAIwP XvQ'CI -1-0

W 1 zMTLC Ck >iiIi 13:A NOT .KA~j

9. Do attached lines have adequate flexibility to avoid damage?

10. Based on the above seismic interaction evaluations, is equipment freeof potentially adverse seismic interaction effects?

YMIND UD N/AD-

YMVND UD1

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could Y["ND UD• ...adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary.)

~ee 0+{~b4J volvc~'rv

Evaluated by: Date: M OD

"i/ 1-71 V-Lriz-, -

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rlnrrA-nnndPnr.P Nn - RS-19-171

C-392

Page 22: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

i

I~i~Q L~Mj~. Li

~L<"1* ~Till

*1~-~.*') 1.....

LU

1*I I I. I.11

I I

I - -

~ fuji..

1~Ip I

I.

~

Page 23: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

VVI1 t-Coarse Thread UNC Series

Case ThedUCSre

Design. Home... ...........

Sc~~reAds,I Tirea"iSystem.Unified. ScreW Thlreads.,

UNC CoarseUNF, FineUNEF Extra Finer..

.Ufilfled Standard Series,Tap, Dril

CosatFkch Series

-Met:Nc 'cIev Threa:id S~ orque in Bolits

Jntroducticln,

TorqueCa'culator

I',Resour cesbibli-graphy

lI"ll E-7. 777: ;7 7

i 1, ý,R 1 I Maga2ines -1

0: .L Materials

Ads by Google

Design. . Processes i. Units I Formulas J Math j

Downloadsae 1926sDownload sae.j 1926 SAE International Standards - webstore.anslhorg

#1* 0.073 64 .0.0629. 0.0544 0.0561. 0.00218 "0.00263

FREE:Publications

Waste Management .Wind systems *

Chemical Engineering *NASA Tech Briefs *Industrial Maintenance.

Paint &Coatings

Machinery L ubrication

LEDs Magazine

more... . . ..

#2 0.086

#3* 0.099

#4 0.112

#5 2.525

#6 0.138

#.8 8 0.164

#10: 0i9

#12* 0.216

:.1/. . 0.25 .

5/16 .03125

3/8 0.375

7/16 0.4375

1/2. .0.5

9/16 0.5625

5/8 .0.625

3/4. 0.75

7/8 .0.875.1 1

56: 0.0744 0.0648

$8. .0.0o855" 0.0741.

60.0958 0.0822

IQ. 0. 1o88 0.0952

32: 0.1i77 0.1008.

32. 0.1437 0.1268-

24 :0.1629 0.1404

24 0. 01889 0.1664

20: 0.2175 0.1905

18. 0.2764 0.2464

16 0.3344 0.3005

14 0.39.11 0.3525

13. O.45 0.4084

12/ 0.5.084l 0 .4633

11 0,566 0.5168

10 0.685. 0.6309

9. 0.8028 0.7427

8 0.9188 .0.8512

7 1.0322 .0.9549

7 1.1572 1.0799

•0.0667.

0.0764

0.0849

0.0979

0.1042

0.1302:

0.1449.

0.,1709

0.1959

0.2524.

0.3073

0.3602.

.0.4167

" 0.47.23.

0.5266

0.6417.'

0.7547

0.8647.

0.9704.

.1.0954

0. 003.1

0..0.040.6.

0.06496

0.006.72

0.00745

0.01196

0.0145

0.l02061

0. 026.9

,"0.0454,

0.0678

0.0933

0.12 57

0.162.

0.202

0.302

0.419

0.551

0.693

0689.

0.0037

0,00487.

l0 .00604

0.;00796

0.00909

0.014

0..0175

.0.024.2

0.0318.

0.0•24

0..0775

0. 1063

0.01419

0.182.. 0.226

0.334.

0.462.

0.60 6

0.763

.0.969

1/8

11/4

1.125

1.25

1-

http://www.efunda.com/designstandards/screws/screwunc.cfm[9/13/2012 4:15:32 PMJPeach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrp.nnnrlpnrp. Nn " RR-19-171

C-394

Page 24: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Coarse Thread UNC Series

3/8

.13/

2.-2% -

.21/2

2¾"

3..

31/

31/2

3%

1.375.

1.5

1.75

.2

2.25

2.5

2.7S

3.25:

3.5

3.75

.6 1.2667 .1.1766.

'6. 1.3917' 1.3016-

5 1.6201. 1,5119

4.5:. 1.8557 1.7353,

4..5 2.-. 2.1057 .1.9853.

.4 2.3376 2.2023.

"4. .2.5876 2.4523

4 .2.8376 2.7023

4 3.0876 2.9523'4 3.3376 3.2023.

4 3.5876 3.4523

4 . 3.8376 3.7023

1.1.946.

.1.3.196'

1.5335.

" '1.7594

2.0094

2.2204

-2.4794

.2 7294

..2.97-94:

3;2294

3.4794.

3.7294

•1.054

' .1294

1.74": 2.3

3.02

: 3.72:

4.62

5.62-

67.92

9.21

1.1I55.

1.405:

1.9

:2;5

3.25

4:

.4.93

5.9.7

.7.1

8.33:

9.66

4. .14 10.161 11.08

Ads by Google

MIT Engineering MS + MBADual Graduate degrees in 24 months 6ýmth Internship. Fellowships Avail - LGO.MIT.edu

N3 Stainless Steel ScrewDistributor of Stainless Steel Screws. Order Online Today! - www.FordFasteners.com

Bolts, Nuts, and ToolsYou Want It, We Got It! #1 In Customer Service - B01tsNutsandTools.com

Iap sanLd Me100,000 In stock specials, metric, hard to find - WWwihoIesawsuniimlteci.om

Hare Memhershl About Us privacy icmer Adverse

Copyright Q 2012 eFunda, Inc.

http://www.efp gqloog•'tA~ipy&/6rMryrc.cfm[9/13/2012 4:15:32 PM]MPR-3812, Revision 3r.nrrPmnnndPnr.P. Nn • RR-1-17.

C-395

Page 25: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

CD0 a

C. 0

m30CD

-C.C2com

Page 26: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

K- 0

0

0 -u

- C/)

CA

C)

2C)-Io

Ul

Page 27: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status: C N U

Seismic Walkdown Checklist (SWC)

Equipment ID No. AO-33-0241D Equip. Class12 (07) Fluid (Air/Hyd) Valves

Equipment Description ESW Outlet Block Valve from Diesel Generator E4 CoolersLocation: Bldg. Diesel Generator Floor El. 127 Room, Area D/G-9Location: Bldg. Diesel Generator Floor El. 127 Room, Area D/G-9

Building

Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist

This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on theSWEL. The space below each of the following questions may be used to record the results of judgments andfindings. Additional space is provided at the end of this checklist for documenting other comments. ....

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item oneof the 50% of SWEL items requiring such verification)?

2. Is the anchorage free of bent, broken, missing or loose hardware?

3. Is the anchorage free of corrosion that is more than mild surfaceoxidation?

YEI ý

Y/NO UEJ N/A:.

Y0/ND UO N/ADl

4. Is the anchorage free of visible cracks in the concrete near the anchors? YI NO UE" N/AE.4~IJC16Z~b~T S LLIML .~L~l 'J'LC~ i- ~AII4g TO CRe~Ioi- EIel?

CoNlowrr;

5. Is the anchorage configuration consistent with plant documentation?(Note: This question only applies if the item is one of the 50% forwhich an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free of

potentially adverse seismic conditions?

-Soo, O+t3oIeJ (Wvol oo 'E or ac 4 a

YE NOI UO N/AX/

Yý(N U-]

er, A en+

Onc"Om~e 'Br- 0'1(- QLr

12 Enter the equipment class name from Appendix B: Classes of Equipment.

,C-3 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3

, rrp.nnnripnmrf Nn ' R.R-19-173

C-398

Page 28: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Equipment ID No. AO-33-0241D Equip. Class"2 (07) Fluid (Air/Hyd) Valves

Equipment Description ESW Outlet Block Valve from Diesel Generator E4 Coolers

Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures? Y[•NEI UD N/AD

8. Are overhead equipment, distribution systems, ceiling tiles and lighting, YE'NU UL- N/AUand masonry block walls not likely to collapse onto the equipment?

9. Do attached lines have adequate flexibility to avoid damage?

10. Based on the above seismic interaction evaluations, is equipment freeof potentially adverse seismic interaction effects?

Yd•ND UD N/AU-

YC9'NQ U[1

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could *• NE U'Uadversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

A-!A

Evaluated by: Evauatdlb: oDte

q)2 q 1 2M

< C-4 )

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3flnrrP..nnndPnr'i Nn • RR-19-17.A

C-399

Page 29: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AO-3'3- 01~,qIP

Purpose

The lateral stiffnesses of the vertical support (two structural angles) attached to the operator of Air-OperatedValve AO-0-33-0241 D and the pipe support (square structural tubing) attached downstream of the valve atthe pipe elbow are calculated. The lateral stiffnesses of the supports are compared to help judge whetherthe valve being supported at two different locations (the diesel room wall and the top of the diesel enginebase frame) could potentially cause damage to the valve during a seismic event.

Data

hangle 7ft

Langl: 3in

tangle 0.25in

Lbox. I 6in

Lbox.2 4in

tbox := 0.25in

hbox.l 3.5ft

hbox.2 2ft

angle: 1.23in4

Ibox.1 30.3in

Ibox.2 8.22in4

Est =29 x 106psi

Height of angle support above base frametop surface (from walkdown)

Length of angle leg (from walkdown)

Thickness of angle (from walkdown)

Approximate width of horizontal section ofpipe support (square cross-section) (fromwalkdown)

Approximate width of vertical section ofpipe support (square cross-section) (fromwalkdown)

Thickness of pipe supports (squarecross-section). This is a conservativeestimate.

Length of horizontal section of pipe suppol(from walkdown)

Length of vertical section of pipe support(from walkdown)

3 x 3 x 1/4 Angle area moment of inertia;AISC Shapes Database v14.0

6 x 6 x 1/4 Square tubing area moment ofinertia; AISC Shapes Database v14.0Historic

4 x 4 x 1/4 Square tubing area moment ofinertia; AISC Shapes Database v14.0Historic

Elastic modulus of carbon steel, typicalvalue.

Stiffness Calculations

3 • Est, Ianglekange- 3

hangle

lbfkangie = 180.545 inf

in

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3.nrrqnnndPnr,- Mn • R.-19-171

C-400

Page 30: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

3 Est" 'box.Ikboxl .

hbox. 1

3 Est" Ibox.2kbox.2 3

hbox.23

kbox.1 • kbox.2

kbox.l + kbox.2

kbox= 58

2 kangle

Conclusions

kbox.1 = 3.558 x 10 4Ib-.fin

kbox.2 = 5.173 x 1 4bfin

= 4 lbfkboX= 2.108x 10

in

Note that angle stiffness is multiplied bytwo since there are two supports.

The lateral stiffness of the pipe support is an order of magnitude stiffer than the support at the valveoperator. Thus, if there is any differential motion between the wall of the diesel room and the diesel enginebase frame during a seismic event, the support at the valve operator will easily displace without impartingsignificant load to the valve operator. Additionally, a structural joint was not observed between the floor ofthe diesel room and the wall of the diesel room so any differential displacement between these twolocations will be very small. The diesel engine baseframe is securely attached to the floor, and the baseframe is very stiff, so the top of the base frame (where the operator support is anchored) should displacewith the floor.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 C-401rlnrrP.nnndrnr.e Nn" RS-19-17.1

Page 31: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

~'(D

z UK E;

Lco

m

I.

06C:O

W

6

Page 32: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

C?)

CLa)EU

0

C2

Cl

0

'E - C,

0'

Cq~

C

Page 33: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

/

Sheet 1 of 2Status:0 N U

Seismic Walkdown Checklist (SWC)

Equipment ID No. N a "'- " Equip. Class1" (08a) Motor Operated Valves

Equipment Description ESW Return to Discharge Pond

Location: Bldg. Diesel Generator Floor El. .1/2-P- t" 11/2- Room, Area D/G-2Buildinge

Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist

This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on theSWEL. The space below each of the following questions may be used to record the results of judgments andfindings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

L1 Is the anchorage configuration verification required (i.e., is the item oneof the 50% of SWEL items requiring such verification)?

2, Is the anchorage free of bent, broken, missing or loose hardware?

YO NN

YP NO U NlAM0

N/A(-4

HIO

3, Is the anchorage free of corrosion that is more than mild surfaceoxidation?

4. Is the anchorage free of visible cracks in the concrete near the anchors?

5. Is the anchorage configuration consistent with plant documentation?(Note: This question only applies if the item is one of the 50% forwhich an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free ofpotentially adverse seismic conditions?

YX NO UE]

M0o

NAl/e 121QYg NEI UEJ

YO] NEI UE] N/At@

Y&NE] UO

12Enter the equipment class name from Appendix B: Classes of Equipment.

SC-3 )>.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrmnnnd1nr.P Nn • RR-19-171

C-404

Page 34: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Equipment ID No. MO-33-0498 Equip. Class12 (08a) Motor Operated Valves

Equipment Description ESW Return to Discharge Pond

Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures?nlo R-f2 4-c, rýe, /15

YjK NE UD N/AD

8. Are overhead equipment, distribution systems, ceiling tiles and lighting, Y[! NE UL N/AHland masonry block walls not likely to collapse onto the equipment?

-Tere. c-g ne t n f(i~d4 Atu tuvrl ts. vkA. - jo &'a.-() A;fs orcw bir k(-9. Do attached lines have adequate flexibility to avoid damage? Y[9 NHi UD N/A[2

10. Based on the above seismic interaction evaluations, is equipment free YRI NE UHof potentially adverse seismic interaction effects?

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could YN NEI. ULadversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

- - A0 - Ao oxqli4c , ~ V' v iS Pf-efrvtf Atbverki 'ad ý OoJe-.

Evaluated by: /c5-74bc6__

V

Date: _/2__ _ _ _-

< C-4 A>Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3(nrrP..qnnndrPnr.-. Nn • PR-19-171

C-405

Page 35: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

-~0

0

Cl,

0

m30CD

06C!O

A,,00

Page 36: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

;u1=r~3

z 033

0

0

c

m-3CD

0

C.0

D0.

00

Page 37: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status: (, N U

Seismic Walkdown Checklist (SWC)

Equipment ID No. MO-48-0501A Equip. Class"2 (08a) Motor Operated Valves

Equipment Description ESWA Inlet to ECT Reservoir

Location: Bldg. Emergenc Floor El. 114 Room, Area ECT-1

Cooling Towers

Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist

This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on theSWEL. The space below each of the following questions may be used to record the results of judgments andfindings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item oneof the 50% of SWEL items requiring such verification)?

2. Is the anchorage free of bent, broken, missing or loose hardware?

3. Is the anchorage free of corrosion that is more than mild surfaceoxidation?

4. Is the anchorage free of visible cracks in the concrete near the anchors?

5. Is the anchorage configuration consistent with plant documentation?(Note: This question only applies if the item is one of the 50% forwhich an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free ofpotentially adverse seismic conditions?

YO N~r

Y[CI NEI U[ N/AU

YY NEI UE! N/AD

Yo NEI UO N/AO

YE! NE! UO N/Aj

Yba NEI UU

12 Enter the equipment class name from Appendix B: Classes of Equipment.

<C-3 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3'.nrrmmnnnr1lnr.P Nn RR-12-173

C-408

Page 38: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Equipment ID No. MO-48-0501A Equip. Class'2 (08a) Motor Operated Valves

Equipment Description ESWA Inlet to ECT Reservoir

Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures? YP N] UI] N/A[JAJo 5o 1-

8. Are overhead equipment, distribution systems, ceiling tiles and lighting, Y)jR NLJ UEI N/AI.and masonry block walls not lik collapse onto the equipment?C-0 1 r ra-4blea fit f •j•/

~~ti1 -W 5--~f~ 4 cars

9. Do attached lines have adequate flexibility to avoid damage? Y[ NEI UO N/AI.

10. Based on the above seismic interaction evaluations, is equipment free YýQ NO UOof potentially adverse seismic interaction effects?

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could YIK NI UI]adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

Evaluated by: V Date: g./21/L-

C-;2~' /.1.

<C-4>Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrP.nnndPnr.. Nn• RR-19-17.

C-409

Page 39: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

V. 0

~CDz -:

0

m30CD

0

000

0nC)

Page 40: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

j3! 0

3~g~>

(A 3 '

m30CD

0

00

cxn

Page 41: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:O N U

Seismic Walkdown Checklist (SWC)

Equipment ID No..-______OZT -L Equip. Class"2 (10) Air Handlers

"~jl iL~~f n +•, ,n , . ,OV,-i-,it , ,- R91.M.l, " ,VaIf K. " 1A"ma tia I l&4 div. a -•-&rC

Location: Bldg. Diesel Generator Floor El. 151 Room, Area DIG-19Building

Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist

This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on theSWEL. The space below each of the following questions may be used to record the results of judgments andfindings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item oneof the 50% of SWEL items requiring such verification)?

2. Is the anchorage free of bent, broken, missing or loose hardware?

3. Is the anchorage free of corrosion that is more than mild surfaceoxidation?

4. Is the anchorage free of visible cracks in the concrete near the anchors?

5. Is the anchorage configuration consistent with plant documentation?(Note: This question only applies if the item is one of the 50% forwhich an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free ofpotentially adverse seismic conditions?

I JNJ'4

YdNEI UD N/AD

Y['NII UE-' N/A~l

YE'NEI UE N/AE[

YEI NEI UE' N/Ak

Y)ýNEI ULI

'2 Enter the equipment class name from Appendix B: Classes of Equipment.

<C-3 )0

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3CrnrrP..nnndPnr.P Nn " RR-1- -17.1

C-412

Page 42: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Equipment ID.No.entP No •_.2"- I Equip. Class' 2 (10) Air Handlers

Equipment Description Master for EI'EDG Building Vent Supply Fan Outside Air Damper

Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures? YN UEn N/AEI

8. Are overhead equipment, distribution systems, ceiling tiles and lighting, YEINQJ U-] N/A[]and masonry block walls not likely to collapse onto the equipment?

W~O OazP~7o C&LuPA4wr

9. Do attached lines have adequate flexibility to avoid damage?

10. Based on the above seismic interaction evaluations, is equipment freeof potentially adverse seismic interaction effects?

Y['NI-I ULI N/AU

YO"N UO

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could Y[YNLI ULIadversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

NI!

Evaluated by: OW Is4i~k Date: AzX

qj'? 12-01-L-- " - -1

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3CnrrP.nnnd~nr•. Nn • RR-19-171

C-413

Page 43: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

.- 0

* 0

0 3n0) -

0 ,

m

3CD

00

-n0

06C)

Page 44: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

C-0

0

;03

z

m

-o

CD

.5.

06

0

NJ4

K!

6

Page 45: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status: f9)N U

Seismic Walkdown Checklist (SWC)

p o-0-qoF-00Z ':2z- oz tl •

Equipment ID No. - -QQ 2-y Equip. Class"2 (10) Air Handlers

Thninmrne'nt fl -rmntinn M'n.vtpr fnr RP'Rl)GRuildincr V~nt ,nnlv )%n RMturn Air lnnnp...L

Location: Bldg. Diesel Generator Floor El. 151 Room, Area D/G-19

Building

Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist

This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on theSWEL. The space below each of the following questions may be used to record the results ofjudgments andfindings. Additional space is provided att the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item oneof the 50% of SWEL items requiring such verification)?

2. Is the anchorage free of bent, broken, missing or loose hardware?

3. Is the anchorage free of corrosion that is more than mild surfaceoxidation?

4. Is the anchorage free of visible cracks in the concrete near the anchors?

5. Is the anchorage configuration consistent with plant documentation?(Note: This question only applies if the item is one of the 50% forwhich an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free ofpotentially adverse seismic conditions?

YO

YIE'NO UO N/AO

Y[(N- UL N/A]

YI?(NE UD N/AO

YEI NEI UD N/Ag

YX NO UO

12 Enter the equipment class name from Appendix B: Classes of Equipment.

"(C-3 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrP--nnndP~nrP. No•- RR-19-17R

C-416

Page 46: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

po-oO-qF- OM77-0-o 1"•0"0001-0 ~~2,3yiC/212-.

Equipment ID No. P-jQ&QZV2= Equip. Class12 (10) Air Handlers

Equipment Description Master for E."EDG Building Vent Supply Fan Return Air Damper

Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures?

t d SFr r4V4ar -

8. Are overhead equipment, distribution systems, ceiling tiles and lighting,and masonry block walls not likely to collapse onto the equipment?

9. Do attached lines have adequate flexibility to avoid damage?

10. Based on the above seismic interaction evaluations, is equipment freeof potentially adverse seismic interaction effects?

YEI'NE] urn N/AO.

YIE1'NO UD N/AD

Y["NE] UD N/AD

YOfl] UOr

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could Y[YNU1 Ul-adversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

N/A

Evaluated by:

6~4

Date: k ?i&

91li 1zoiz,- j,

<CA4>Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3C.nrrfpnnnrn•n.y Nn - R,- 9-117.

C-417

Page 47: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

0 3C.T,0

* C:

mnr-

2

0

0

'11

0

0

0

Page 48: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:.) N U

Seismic Walkdown Checklist (SWC)

Equipment ID No. TCV 52E 7239 A Equip. Class12 (07) Fluid (Air/Hyd) Valves

Equipment Description DIG Jacket Coolant 3-Way Thermostatic Control Valve

Location: Bldg. Diesel Generator Floor El. 127 Room, Area DIG-3

Building

Manufacturer, Model, Etc. (optional but recommended)

Instructions for Completing Checklist

This checklist may be used to document the results of the Seismic Walkdown of an item of equipment on theSWEL. The space below each of the following questions may be used to record the results of judgments andfindings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item one YO Ntof the 50% of SWEL items requiring such verification)?

2. Is the anchorage free of bent, broken, missing or loose hardware?

3. Is the anchorage free of corrosion that is more than mild surfaceoxidation? " '

YMJ NEI UD N/AE

Y95 NE] UD N/AOl

4. Is the anchorage free of visible cracks in the concrete near the anchors? YE NEI UO N/A[Avi4ioraed I-P0 OA6-374P Cl 0/6- n • cd- a (ooo/,q.'e ole- -

5. Is the anchorage configuration consistent with plant documentation?(Note: This question only applies if the item is one of the 50% forwhich an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free ofpotentially adverse seismic conditions?

YE NEI U- N/An.

YR NO UD

12 Enter the equipment class name from Appendix B: Classes of Equipment.

<C-3 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrPýnnnHAnr.nr Nn ' RR-1 -17.

C-419

Page 49: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2-1 C- o- P-E -7Z39' A

Equipment ID No. TV 52E 7239A Equip. Class12 (07) Fluid (Air/Hyd) Valves

Equipment Description DIG Jacket Coolant 3-Way Thermostatic Control Valve

Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures? Y% NO" U'- N/AD

8. Are overhead equipment, distribution systems, ceiling tiles and lighting, Yo NO U-. N/AO.

and masonry block walls not likely to collapse onto the equipment?

9., Do attached lines have adequate flexibility to avoid damage? Yo NOt UI' N/Al]

10. Based on the above seismic interaction evaluations, is equipment free YX NE) U .-of potentially adverse seismic interaction effects?

Other Adverse Conditions

.11. Have you looked for and found no other seismic conditions that could YI NE) UDadversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

Evaluated by:

axle

Date: 145 ,'

12-

C-4 >Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rCnrrmnnndPnr.P Nn • RR-1 9-171

C-420

Page 50: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

-. 0

23to

maC

2(D

5-IC)

0CT'r~3rn-Ir,~3Co

Page 51: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

She 1 of 2Status() N U

Seismic Walkdown Checklist (SWC)

Equipment ID No.•- 0(oO 7D Equip. ClasSl2C i9) re&,ot.,Akl, !re-f~,p-c

Equipment Description E'-/ / -"e.' , ei 5

Location: Bldg. Jf bLy- FloorEl. Room, Area A/r-•Manufacturer, Model, Etc. (optional but recommenaea)

Instructions for Completing ChecklistThis checklist may be used to document the results of the Seismic Walkdown of an item of equipment on theSWEL. The space below each of the following questions may be used to record the results of judgments andfindings. Additional space is provided at the end of this checklist for documenting other comments.

Anchorage

1. Is the anchorage configuration verification required (i.e., is the item oneof the 50% of SWEL items requiring such verifigation)?

2. Is the anchorage free of bent, broken, missing or loose hardware?

3. Is the anchorage free of corrosion that is more than mild surfaceoxidation?

4. Is the anchorage free of visible cracks in the concrete near the anchors?

5. Is the anchorage configuration consistent with plant documentation?(Note: This question only applies if the item is one of the 50% forwhich an anchorage configuration verification is required.)

6. Based on the above anchorage evaluations, is the anchorage free ofpotentially adverse seismic conditions?

YE] NJ

YqNEI UEJ N/AO

YtN1NEI UO N/AEI

NEI UE] N/AE]

YFI NEI U-I N/AV

YX NEI UI-

12 Enter the equipment class name from Appendix B: Classes of Equipment.

<C-3 >

'Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r•nrrqnnndPnr.P Nn " RR-19-17."

C-422

Page 52: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Equipment ID No. '- 5--,O 7 Equip. Class'12 6,•- ",• & "%' -A

Equipment Description /"i c/6.r-- f•-Ae. k'"?- Le,- ••- -,',z/" e -

Interaction Effects

7. Are soft targets free from impact by nearby equipment or structures?

8. Are overhead equipment, distribution systems, ceiling tiles and lighting,and masonry block walls not likely to collapse onto the equipment?

9. Do attached lines have adequate flexibility to avoid damage?

10. Based on the above seismic interaction evaluations, is equipment freeof potentially adverse seismic interaction effects?

YM NE UL N/AD

YM NEI UI' N/AD

YTS NE UM N/ADI

YEE ND UE

Other Adverse Conditions

11. Have you looked for and found no other seismic conditions that could YIý NEI U-Iadversely affect the safety functions of the equipment?

Comments (Additional pages may be added as necessary)

Evaluated by: d~ 2~2- Date: / !/// ?-

A

'< C-4 >Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrP.qnnndPnr.P Nn • RR-19-171

C-423

Page 53: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

-. 0

3

* 0~,-0

0

m30CD

co

0

0

Page 54: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

DArea Walk-By Checklists (AWCs)

Below are the names and signatures of the personnel who performed the area walk-bys.

Ben Frazier

Kevin Gantz

Mojtaba Oghbaei

Craig Swanner

James Wiggin

)c~ ~

,i. qhba~

Caroline Schlaseman

The order of the Area Walk-By Checklists (AWC) for Unit 3 is shown in Table D-1 belowand the order of the AWCs for Unit 0 (common) is shown in Table D-2.

Note: Photos for the AWCs are included in the base component SWC in Appendix C.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

D-1

Page 55: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Table D-1. Unit 3 Area Walk-By Checklists (AWCs)

AWC- Building Elevation Location ComponentUx-YY IDU3-1 Turbine 135 T3-172 3DD03

U3-2 Turbine 135 T3-74 30D37

U3-3 Pump Structure 112 P/H-9 P030223-4

U3-4 Reactor 88 R3-15 30C87

U3-5 Turbine 135 T3-171 30X133

U3-6 Reactor 91 R3-11 LS3-23-91A

U3-7 Reactor 165 R3-40 3AC65

U3-8 Reactor 88 R3-13 30P033,30P038

U3-9 Turbine 135 T3-170 3CD03

U3-10 Turbine 135 T3-169 3DD01

U3-11 Reactor 88 R3-9 3AP03730P036 &

U3-12 Reactor 88 R3-14 30P03630S038

U3-13 Reactor 135 R3-22 A03-03-33

U3-14 Reactor 135 R3-29 30Y35U3-15 Turbine 135 Recirc mg 30B324

set roomU3-16 Reactor 91 R3-5 3AP035

U3-17 Reactor 116 R3-5 3AE058

U3-18 Reactor 91 R3-7 M03-10-013C

U3-19 Reactor 116 R3-17 3CE24

U3-20 Reactor 116 R3-21 PT-5805

U3-21 Turbine 135 T3-70 3CD001

U3-22 Turbine 150 T3-81 30Y050

U3-23 Reactor 165 R3-1116 30X030

U3-24 Reactor 165 R3-41 30X033MO3-30-

U3-25 Screen House 116 S/H-4 3233A3233A

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

D-2

Page 56: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

m,9 d- a5--/Sheet 1 of 2

Status:&I•N U

Area Walk-By Checklist (AWC)

Location: Bldg.. A - Flor ' Eli . I • Room, Area13 T3 -

Instructions for Completing ChecklistThis clhecklist may be used to document the results of the Area Walk-By near one or more SWEL items.; Thespace below each of the following questions may be used to record the results of judgments and findings...Additional space is provided at the end.of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarily:.opening cabinets)? .... . - *....

NO UO N/AO..

2. Does anchorage of equipment in the area appear to be free of significant Yb$ NO, UO N/A .degradedc6nditions? ." 2,

3. Based on a visual inspection from the floor, do the cable/conduit-raceways -and HVAC ducting appearto be~free of potentially-adverseseismicn o6nditio6ns (e.g.; condition ofsupports is adequate and fillconditions of ca! le 'trays applI earto be inside acceptable limits)?

YX NEI UO N/AE.

4. Does.it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

-OPM eno~ oi Ve '6i "1V0 1 C

YO NX UO N/AOA,

ImA 'ý 4P CXO5~V

13 If the room in which the SWEL item is locateddis very.large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

SC-5 >"

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-3(rnrrP.nnnrlPnr.p Nn - RR-1 9-171

Page 57: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. .- UneL'... Fioor El. V3 S Room,' Aea 13 -•1 - -

5. Does it appear that the area is free of potentially adverse seismic Yg NO UD N/ADinteractions that could cause flooding or spray in the area?.*Iueel. -': 51 " " ( : ' ) --

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

Y' NO UO N/AD

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

4e ~

'X NO UD N/AD'

8. Have you looked for and found.noother seismic.cpnditions that could Yb NEadversely affect the safety functions of the equipment-in the area?

S9o,4 " w No.5 40 -O)-1) 171 - 19' a,-e. ,, y 'AA5 ec-+w4ýn No. iM - 1. Rev I

JUo

P 6 5

Comments.(Additional pages may be addedv asn6cessarýy)

.Oetl -hook cJ;4n *ore ~,i If~# oIL~~B~5

Evaluated by: (9ZJA"4-

tq.~Date:

L, f,20/

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3(.nrrP'nnndPnr.P Nn - RA9-1-7T

D-4

Page 58: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:K) N U

Area Walk-By Checklist (AWC)

.Location: Bldg. TuchAnk.. FloorEl. _ _5 _ Room, Area" T),- 94

Instructions for Completing Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The,space below each of the following questions, may be used-to record the results ofjudgmnents and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of )X NO UO N/A. .,potentially adverse seismic conditions (if visible without necessarilyopening c•binets)? ..

2. Does anchorage of equipment in the area appear to be free of significantdegraded conditons? .,,.:

Y)J NO Ui N/A .

...

3. Based on a visual inspection from the floor, do the cable/conduit-• --raceways and-HVAC ducting~appear to be free of'potentially-adverse, seismic cdnditions (e.g., condition of support, §is adequitedand- fill"'

conditions of cable trays appear tobe inside acceptable.limits)?:

Sc~I a4kx4ce- CowJ6 4'rays) W~ oil ry

4. Does it appear that the area is free of potentially adverse seisniic spatiainteractions with other equipment in he area (e.g., ceiling tiles andlighting)?

YNO UD N/AD-

1 Y NEIUO N/AOl

oT;.

1 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order. ofabout 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-5rnrrPmnnndP.nr.'. Inn • RS-19-171

Page 59: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AWC-U3 -7.

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. _,4 'Thc FloorEl. 135 Room, Area13 7-

5. Does it appear that the area is free of potentially adverse seismic YrI NA UEI N/ADinteractions that could cause flooding or spray in the area?

z~w -W ' I. P. V dobt-r 404lck-er-a 4 S/j r' (q f4~•..O-1 O XG. P.' j eev0t.

6. Does it appear that the area is free of potentially adverse seismic • NDI UE1 N/A"I!interactions that could cause a fire in the area?

'A-7. Does it appear that the area is free of potentially adverse seismic Y; ND UD

interactions associated with housekeeping practices, storage of portableequipment,- and temporary. installations (e.g., scaffolding, leadshielding)?

N/ArD1,1 :..i

8. Have you looked for and found no'other seismic.ce qonditions that could YX NEI UE .',, ,

adversely affect the safety functions of the equipment in the-area? .

Comments (Additional pages may be added as necessarY)• g~k Pipfe clamp ",rIJA , n~ .• e .,M60 lq1b•

Evaluated by:, i2~ Date: O /.2v,

-z91 20, I_'

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3(.nrrPqnnndimnrp. Nn R •A-19-171

D-6

Page 60: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

//1/ 1j G-- L45 _>".Sheet 1 of 2

Status:&•N U

Area Walk-By Checklist (AWC)

Location: Bldg.? vloor El. J1• .. Room, Area13 " iI -',

Instructions for Completing Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopening cabinets)?

Y) NE UD N/AJ

2. Does anchorage of equipment in the area appear to be free of significant Y•o NO UO N/AOdegraded conditions? I r_) O

tj4$V cts61a 64c " p or, ~'fU1fA

3. Based on a visual inspection from the floor, do the cable/conduitraceways and HVAC ducting appear to be free of potentially adverseseismic conditions (e.g., condition of supports is adequate and fillconditions of cable trays appear to be inside acceptable limits)?

4. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

Y•/NO UO N/AEI

Ylq NO UD N/AD

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area

selected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-7rnrrp..nnnHPnrP Nn • R5 -1T-17A

Page 61: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

ShWee -2 fj

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg.•% A 0e&Fltor1 E1. JD . Room, Area' 3

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

YX ND UD N/AD

Y) NO UD N/Al

Y•d NO UD N/Al

8. Have you looked for and found no" other seismic conditions that could YX NEI U"adversely affect the safety functions of the equipment in the area?

Comments (Additional pages may be added as necessary)

N//A

Evaluated by: (,6w Date: __________

,?[Zq1Vj7_

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3flnrrP.nnndP.nr.P Nn • RR-19-173

D-8

Page 62: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

A'Je- 60S-KSheet 1 of 2

Status/ N U

Area Walk-By Checklist (AWC)

Location:- Bldg. Floor El. > Room, Area" j? " 5Instructions for Completing Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results ofjudgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of YX NO UOI N/AOpotentially adverse seismic conditions (if visible without necessarily-openingCabinets)?, .. -

2. Does anchorage of equipment in the area appear to be free of significantdegraded onditions?

3. Based on a visual. inspection from the floor, do the cable/conduitraceways and HVACducting-appear to-be-free of potentially adverse

--.seismic cinditions'(e.g., condition 6f~suppbrts is adequate and fillconditions of cable~trays appear to be inside acceptable limits)?

YNINO UQ N/AO

'N% NO UD N/AO

4.. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

Yk(NE Un1N/AO .

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< C-5 )

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r-nrrP.nnndP.nr-.p Nn • RR-19-171

D-9

Page 63: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AVIC-U 3 - 4Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. & 6..: Floor El. 4M Room, Aread3 R• "

5. Does it appear that the area is free of potentially adverse seismic V• ND UD N/AQinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismic YJ NO UO N/ACinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismic YX NO UO N/AD ,interactions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshieldilag)?

8. Have you looked for and found no otheriseismic conditions that couldadversely affect the safety finctions ofthe, equipment in the'area?

)KNEI UO

Comments (Additional pages may. lie added as necessary)

NIA

Evaluated by: - Date:

~bO(mi -~-

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrP..qnnndrnnpJ Nn RRA-19-171

D-10

Page 64: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

RtoaC - (A 3--5Sheet I of 2

Status: N U

Area Walk-By Checklist (AWC)

Location: Bldg. "or6-X Floor El. I1 ' Room, Area" T3 I l I

Instructions for Completing Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. The:space below each of the following questions may be' used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopening cabinets)?

NO UQ N/AO

2. Does anchorage of equipment in the area appear to be free of significant YV' NOdegraded conditions? -

UO N/A " ! ..•.";. , . '' .' ,. J'

3. Based on a visual inspection from the floor, do the cable/conduitraceways andHVAC ductimg appear to be free of-potentially adverseseismic coiditions (e.g.,cbndition of supports is adequate and fill

-c biditions:of Cable trays appear to be inside acceptable limits)?'

Y NO UO N/AO

4. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

YN-NO UQ N/AO

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >,

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-11

.nrrpqnnnd1Pnr.P Nn • R5-19-17.1

Page 65: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. T Floor El. 1. -i. Room, Area'" : L .

5. Does it appear that the area is free of potentially adverse seismicinteraction$ that could cause flooding or spray in the area?

1 - - No...-v...10

* NE UO N/AQ

I (T.Oe4Aof Y4w`

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporaxy installations (e.g., scaffolding, leadshielding)?

j Noc 4ept" or e~oW~~t t' mo

YXNO UQ N/AO:

YX'NO UO N/AI:

8. Have you looked for and found no othe~r seismic conditions that couldadversely affect the safety functions of the equipment in tele are4?,

,1. 1i-401) Rev.I

VI e2t bI. W 44we-~t 4-a amv~ 556,s 4~

YX NEI 'JO

per fPISAPS ~f~eeA~ ~rV~

box :1)L4I3 :cI

Comments (Additional pages may be~added as'n~cessary)

NAl/

Evaluated by: 9aens LIK&y441 Date:m

4ZL i14I•A~L~

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3

.nrrP..nnndP*nr.P Nn • RR-19-173D-12

Page 66: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

,¢wlc - 1A -V/,Sheet 1 of 2

Status: C N U

Area Walk-By Checklist (AWC)

Location: Bldg. fc'ir FloorEl. q3L Room, Area 13 - 1

Instructions for Completing Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results ofjudgments and- findings..Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarily

" bpening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significantdegraded.coniditions?

3. Based on a visual inspection from the floor, do the cable/conduitraceways and HVAC ducting appear to be free of potentially adverseseismiiic ̀ onditions (e.g., condition of supports is adequate and fillco. .inditions- of cable trays appear to be inside acceptable limits)?

YVNEI UD" N/ADT,

YeNF- UEI N/A,;-.

24NEI U- N/AD .

4. Does it appear that the area is free of potentially. adverse seismic spatial .F ND UD N/ADIinteractions with other equipment in the area (e.g., ceiling tiles and

lighting)?

13 If the room in which the SWEL item is located is very large (e~g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

Cý5 >"

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-13

CnrrP.qnnndPnr-.p Nn • RR-19-17.1

Page 67: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AWC --V? -6Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. (foo• -- Floor El. IL Room, Area'3 -11 :115. Does it appear that the area is free of potentially adverse seismic

interactions that could cause flooding or spray in the area?YXd ND UD N/AD

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area isfree of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

Y.0 NO UO

Y)KNO UO

N/A-

N/AO2.. . . - . :

8. Have you looked for and found no.other seismic conditions that couldadversely affect the safety functions of the equipment in the area?

YVNEIUO

Comments (Additional pages may beadded as necessiry)

AJ/-/A::,. ". ...

41~6~mEvaluated by: Date:~/W

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Cnrrmnnndrnr.P Nn - RR-19-171

D-14.

Page 68: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

/ýw C - Wi- 'rSheet 1 of 2

Status: 6 N U

Area Walk-By Checklist (AWC)

Location: Bldg. FloorEl. 1 RoomArea"3 L." -

Instructionsfor Completing Checklist

Thischecklist may be used to document the results of the Area.Walk-By near one or more SWEL items. The;space below each of the following questions may be used to'record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of Yf NO UD N/A -potentially adverse seismic conditions (if visible without necessarily UC N/AC

fopening cabinets)? ""-

.Looee Lover ran'l a4•nOr4 - 30C• I '°"a aorw 0 C ...

SOW oneW A4W 614 (-)qWf) w"I 1 oiwv~ 6a~ pcwl m~kc'n-

SMA46 ADRcS5 b 1V TR-a N29-73-7, 1( 011/J-z2. Does anchorage of equipment in the% area appear to be free of significant

degrAded.1onditions? . ..

YX NO UC N/A,

. . 3. Based on a visual inspection from the floor, do the cable/conduit. .......". raceways and;HVAC ducting -appear- to be free of potentially adverse.

seismiic •Cn.ditions (e.g.,. condition, of supports is adequate and fill-'-conditions of cable trays appear to be inside acceptable limits)?

YK NO O N/AO

4. Does it appear that the area is free of potentially adverse seismic spatial Y& NC UCinteractions with other equipment in the area (e.g., ceiling tiles andlighting)? LHO 4 5A1O.-JO 5AJ

N/AC

per

pBgp~S - -z4-%vn N16. /14-401~l) Peov,.V,4 -1v oreo

Temre'oy

st .Jo6i\,TC, L)80 4& 01

4-0 6r000 I eovy. ý 0,C

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-15rnrr.nnndine. Nn • R5-19-17.1

Page 69: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

r'•I%_- WP - I

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. A wc' c 'Floor<El. iiL..Room, xea13 ? -0

5. Does it appear that the area is free of potentially adverse seismic ta' NE UD N/ADinteractions that could cause flooding or spray in the area? .

VNc,~o VV~ c~be w ~f'' ~uIn5 olIP 44ja1*er

6. Does it appear that-the area is free ofpotentially adverse seismicinteractions that could cause a fire in the area?

4('NO1UO N/AO.

7. Does it appear that the. area is free of potentially adverse seismic YI'NO Ur N/ADinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?.Tfo AA and 6 M&Ao wt 4 0W.sv'IekJw~

8. Have you looked for and found no .oth~er seismic conditions that couldadversely affect the safety functions of the equipment in the area?,

NO U- A.

Commeehts (Additional. pages may be added, as neiessarý)

Iv/A

Evaluated by: &w<wlr6'Date: __________

1atut20

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrPnnnrdInr.P ln • RRA-171

D-16

Page 70: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status: & N U

Area Walk-By Checklist (AWC)

Location: Bldg. `.FloorEl. 'goo Room, Area13 R-

* Instructions for Completing.Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWELitems. Thespace below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area-appear to be free of YX NO U- N/AD..potentially adverse seismic conditions (if visible without necessarily to 1t0o_2o *, ,.opening cabinets)? ' "".6 A

-9141) .eq r pp alo*m , 6t oshuJ4" Ceti 1 "or,~V W",tv010f' ow,AAl1e o 05 0 n O aV. o J 4d OCe406W. CO~~~i~ 4flOnav

2. 4OCr)4tkft 1SrrktC Al Dt e rJ 1 Z r 1 V b' *t1j,fg* I( a/Doe anhorge f euipentin, the area appear tbefr-ee of significant. Y) NO UO N/AC

- degraded conditions?

3. Based' on avisual inspection from the floor, do the cable/conduitraceways, and HVAC ducting appear to be freeof potentially adverseseismi6 conditions (e.g., condition of supports is adequate and fill-conditi;nis of cable trays appear to be inside acceptable limits)?.

Y)4 NO UlO N/AC

4. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

YV NEI UQ N/AC .

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-17C'nrrPnnndrnrP. Nn • RR-19-17.T

Page 71: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. V Floor El. _9 _9 Room, Area'3 R -13

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is -free of potentially adverse seismicinteractions that could cause h fire in the area?.

Y)Qi"ND UD N/AQ

Y* NO UD N/AO

7. Does it appear that the area is free ofpotentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshield* •g 4. . . . .d 4

0. el:I• p, *,¢.•

YXNO UD N/A .. ,

8. Have you looked for and foud no' other seismic conditions that could X ND U"adversely affect the safety functions of the equipment in the area?

... ',

Comments (Additionýl pages may be'added as necessa), ... ." " ,

N~JIA

Evaluated by: ~rŽ4qi~ Date:

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3

.nrrsAmnnnrIPnr.P. Nn • RR-1 9-17.D-18

Page 72: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

/"JC- d5 - 9Sheet 1 of 2

Status:&ý9 N U

Area Walk-By Checklist (AWC)

Location: Bldg. _______ Floor El. A Room, Area1 "T'•-I

Instructions for Completing Checklist.

This checklist may be used to document the results of the Area Walk-By near one or more SWEL-items. The.space below each of the following questions may be used to record the results, of judgments -and findings.Additional space is provided at.the end of this checklist for. documenting other comments.

1. Does anchorage of equipment in the area appear to be free of . YK ND UD N/AC- .potentially adverse seismic conditions (if visible without necessarily

* . .:. z .:opening cabinets)?' .

2. Does anchorage of equipment in the area appear to be free of significant NO UD N/An,: .,•..•.••, de~graded-conditioins? .'- ... •. . . . .

3. Based on a visual inspection from the floor, do the cable/conduit.. -. .,raceways and HVAC ducting appear to be free of potentially adverse

. .seismic onditions•(e~g.,'conditin.of supports is adequate and fill

conditions 6f cable trays appear to be inside acceptable limits)?

4,. .Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

N UNOU N/A-

Y( NE UO N/A.

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-19

.orrPqnondnrn. Nn • RR-19-17.

Page 73: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Awc -03- qSheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg.TjrVy4' FloorEl. 13 5 Room, _AeaM T3 -10

5. Does it appear that the area is free: of potentially adverse seismic Yo ND UD N/ADinteractions that could cause flooding or spra inthe area?

:" 'T, A lb .r,. o4" re-•'e •yip(dr er OC.No. : SS) ~vI

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

Yy NO UD N/AD1

YVND Ur N/AD

8. Have you looked for and found no0other seismic conditions, that.,could YX NO UDIadversely affect the safety functions of the equipment inthe area?,

PD'AF5 Spml : Mo M- 70l1 Rev.P .

Comments(Additional pages may be added as neces'saty)

" IA

Evaluated by: a n(e

Date:

ý20_ - gVi26/26zn

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrPqnnndInrý. Nn • RR-19-17.1

D-20

Page 74: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

A4tkc- W:5-/6Sheet 1 of 2

Status: N U

Area Walk-By Checklist (AWC)

Location: Bldg. TiiU4[$i 'Floor El. S Room, Area1 3 T 3- I W

Instructionsfor Completing ChecklistThis checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results ofjudgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of .A NO UI! N/AI:1_J.potentially adverse seismic conditions (if visible without necessarilyopening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Y[' NO Ul- N/A!]degraded conditions? .

3. Based on a visual inspection from the floor, do the cable/conduit YX. NO- U!- N/A!]raceways and HAC ducting appearto be. free of potentially adverseseisnic conditiong'(e.g., condition of supports is adequate and fll ". -

conditions of cable trays appear to be inside acce table limits)?a '\ c d olo low, " " .ue

4. Does it appear that the area is free of potentially'adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

YA N!] UI- N/A[]

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-21rlnrrPqnnndPnr.A Mn R-19_173

Page 75: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AWe-eu 2 oSheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg.. Turbnc' FloOr El. f Room, Area13. T3 -10

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

NO 4wA"b orfpjy e'pmeA

*• NO UO N/AD

YbeNI UD N/A.

Yg NO U] N/AD o

8. Have.you looked forland fouidno.onther seismicoconditionsthat could YX •NO~ UEO .. ,.

rslY -t the safety functions of the-e'quipment in thearea?

POAP5 A/c f Il-r'J ) I*ev,

Comments (Additional pages may be added as nec-ssary) .

AeeA

Ic

Date: DJ2L

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrp'-nnndinr.P Nn • RR-19-173

D-22

Page 76: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Status: g N U

Area Walk-By Checklist (AWC)

Location: Bldg. Floor El. I Room, Area" 13 : -CJ

linstructions for Completing Checklist.

'This checklistimay be used to document the results of the Area Walk-By near one or more SWEL items. The.space below each of the following questions may be used to record the results ofjudgments.and, findings. -,

.Additional space is provided at the end of this checklist for documenting other comments.

I. Does anchorage of equipment in the area appear. to be free of YX NOi UC N/AC.. ..potentially adverse seismic conditions (if visible without necessarily.opening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant YpNO U[3 N/AC

dgrAd ,onditions?

3. Based on a visual inspection from the floor, do the cable/conduit-.raceways-and HVAC ducting appear tobe freeof potentially adverse'eismic**co6nnditinsdition of supports is adequate and fill

Scon'ditions of ýableltrays appear to be inside acceptable limits)?;

4•., . -Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

, e .t &.J - •

N .4

i)NO UC N/AC -

r'ND UO N/AC

Iq11

<O. non- sw

kl;

ekanw.e. W11 Qviro I&IVJ n 0 Coverel

AL c4-TI~D -a>VO Vrk-

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-23(TnrrPnnndPnr-.P Nn " PR-19-17.•

Page 77: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AWC-u3- itSheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. &tM " Floor El. L ,Ro:om, Area13 ft • "

5. Does it appear that the-area is.free of potentially adverse seismicinteractions.that could cause flooding or spray in the area?

Yg NO UO N/AO

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

Y'X NO UO N/A ,

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

-NV 4f~y oreOebt eQ1m7

Yý(NO UO N/AO I .

8. Have you looked.for and found no other seismic conditions that couldadversely affect the safety functions of the equipment in the area?,-

Yý(NO UO

Comments (Addiiional.pages'may be added as necessiry) .:. , : .... '. " " : ".. :.,

NV/A

Evaluated by:- a

Date: q~/folJAl

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrPqnnnrIinr,.P Nn • MR-19-17R

D-24

Page 78: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Area WlkB Chckist,(W)

Location:. Bidg"_____ F.,rE Room; "Area" R-'I

Thischecklist iiay be used to docu7ntthe reslt oWtý&re Walk-By' ner`eoJ oe WLies hspacebeo-,19w .each of the -followin~g ,qusinm be sdt record esis o jiigr e Is an d fnig.

Adiftioa~pc isrovid a tendof this-checkitfrdcmnig te oiet.:

-d~oextl1 &ýd:es~iii fni n (if viPl Nihu'eesrl El,

Aviil6 it6 lhc , e 19 sap

bq- .Dosanchorage of.'equip entin tjhe area appeartob fr6fsgiin

3.Based'on. a visual ispedtion from the floor,'d the cablecodut-raceways and-HVAC ductIng appear-tobeý,. fre-e ofpqteptiallyq averse

~ onhiios f ~bleK tiysapar tob nieace-ptable limii )

X~NO UON/A-.4:'

Y%-NO 15!-, NAl]

`NA......

Y~NQUQ~N/ 1.012-4. Does, it apertatteris feeb of pot Ientially 4adverse seisiic spatia

intracion itoher equipmentin h area (egcelnliIsac60ighing)

AJQ.~'ilO1 ev. I

- • If~heroom w~hjch the SWEsIvtemee',sl ocat •s earea

elcted shouldb c-d~cribed.'T6i selected area shoiildbe baue4, on judgmient ec.,o the oder, ofabout 351effoth1WL en

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision-3'" D-25r.nrrPmnnnidnrn. No.- RR-19AA7.

Page 79: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. ba'k Floor El. -fit Room, Areae3

5. Does it appear that the area is free ofpotentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7.. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

YX NO UD N/AD

Y•[ ND UD N/AD-

Y NEI UQ N/A.

8. Have you. looked for and found no other seismic conditions that could YJX ND U]adversely affect the safety functions-of the equipment in the area?

Comments (Additional pages may be added asnece=ssary)

N/VA

Evaluated by:

24m~Date: q

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrA~nnndInr.AP Nn - .R-19-173

D-26

Page 80: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status: N U

Area Walk-By Checklist (AWC)

Location:, Bldg. ...... Floor El.. 1.- Room, Area 13. /kus 5C-4e. ; ,-J.ah '.7,,•,

Instiuctions for Completing Checklist

.hig checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be- used to record the resufs of judgments and findings....

Additional space is provided at the end otftbis checklist for documenting other comments.

1. Does- anchorage of equipment in the area appear to be free of., Y, NO UI- N/Al ..potentially adverse seismic cOnditions (if visible without necessarily . -,.

opening cabinets)? .- "° v

2. Does anchorage of equipment in the area appear to be free of significant Y N"I UI- N/Al],degraded conditions? , -

3; Based on a visual inspection from the floor,.do the cable/konduit.- raceways and H-VAC ducting appear to be free-of p0enitially "adverse

" " ' eismiconditions (e.g,,condition of supports is adequate andfil

conditions of cable trays appear to be inside acceptable li.mits)?.

4. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles aindlighting)?

.# I o'"

"Y•'NO Ul] N/Al]

Y)6NO. U- N/Al]

13 If the roomin which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should.be deskribed. This selected area should be based on judgmezit, e.g.,on the order ofabout. 35 feet from the SWEL item.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-27(hnrrPaqnnnrIPnrP Nn • RR-19-17t,

Page 81: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AWC.--3 - GSheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. ' FloorEl. 3._ Room,,Aiea'•3 I1/4/' A( i V, ?k;'/ , ,,

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding . spray injthe area?:: 7/No 'o-e; ; .it 'S' •y;

6., Does it appear that the area is free of potentially adverse seismicinteractions that could cause a ffire in the area?

Yp!NDl UO N/AO

YJ!(NO UON/AO

7. Does it appear that the area is free of potentially adverse seismic yUNO JUinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)? f dc.,,t fV' ItLti 4r'%Cý' Al'W,-;apy 05* C 0V& T

N/A .

8. Have you looked for and found no other seismic conditions that couldadversely affect the safety functions of the equipment in the area?Io• :+,•, ete•,.& Ct;VIJC ,,.eW4+e,..b .- fa

YAND UE -J,

"C 4 "ok,-.r2 / 1 V **- b74i f ~

Comments (Additiohalpages may be added as necessary)"

Evaluated.by:

<C-6 >

Date: .. /,5" ---.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrqnnndPnr.P Nn • RR-19-17.

D-28

Page 82: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

/tVJu -LA:' `/I'Sheet 1 of 2

Status:"L N U

Area Walk-By Checklist (AWC)

Location: Bldg. .. Floor El. 1.., Room, iArea,3 vkhlf 3 V• 0 57:Instructidns for Completing Checklist .

This checklist may be used to document the results of the, Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the ;resUlts ofj udgments anýd findings.Additional space' is provided at the end of this checklist for documenting other comments..

1.' Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarily'opening'cabinets)? .-. ;,, +0,)

" 3 .- •051

YA~NO' UD N/AUI--,.

ýrcoq f g3q~4C /.

I.z4e- f , . M /- V ', U 0"2. Does anchorage of equi ment in the area appear to be free of significant

degraded conditions? juI vler " i.•pg•4qV/ T c..

P4ý d '0-tO 1P 4A "(-•. 'A S- , . r"

3. Based on a visual inspection from the floor, do the cable/conduit.. raceways. and HVAC ducting appear to-be free-ofpotentially adverse

ii.- ,::9eismico6diiditio6s (e.g- ,condition of supp6rts is adequate and fill• .. cciiiditioiiiýof cable trays':appear to be inside acceptable limits)?

YzI0s UD N/A[O

YJNE -U' N/AF.

• .4.. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)? %__* I/• Cl~~'i '6'",•

Y)O NO UD-E N/AQ].

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3flnrrP_,nnnd~nrPe Nn • RR-19-17.1

D-29

Page 83: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

A-S.--e -ofI"Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location:. Bldg. M, Floor El. ,3" .. Room,- Area'3 /' - •6. ,

5. Does it appear that the area is free of potentially adverse seismic 'At-NO UD N/AD -

interactions that could cause flooding or spray in the area?

6. Does it appear thar the area is.free of potentially adyerse seismic , O N JO N/A,.interactions that c6uld cause a fire in the'a'ea?

7. Doesjit appear that the area is free of potentially adv ebseismi .ifnteractions associated with housekeeping practices, storage of portable"'quipmenit, and temporary installations*(e.g. 'scaffolding, leadshielding)? ."",

YO NND UD N/AD "

.. r.

8. Have you looked for and found no other seismic conditions that couldadversely affect the safety functions of the equipment in the area?,,.

YgNEI UD

Comments (Aditi6riaf pages may be added as neeissary)" 1'

Evaluated by: Date: )S .

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3flnrrP.nnndrInri. Nn • RR-19-17.1

D-30

Page 84: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:C) N U

Area Walk-By Checklist (AWC)

A I

Location: BldZ • 10o•'El . 135 Room,'Area" 1 1____"___ _/_,___ _ý4__•~r 4I• ,1• , ;a //h- am " '..

Instructions for Completing Checklist

This checklist may be used to document the results of the.Are.a Walk-By *near one or more SWEL items. Thespace below each of the following qu'estions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopening cabinets)?, '-,

Y42-4N UD N/AD

2. Does anchorage of equipment in the area appear to be free of significant YJNEI- Ur N/AI

"degraded conditoi~s 411 .

3. Based on a visual inspection from the floor, do th4cable/conduAt Y 0N- Ut] N/AIracewaysand HVAC ducting appear to be ee of potentially adverse •, -. - . -

,seisic condiiionsz(e.g.,, :condition of suppo is ade6q4te.and fill.conditions of cable trays appear to be inside cceptable-limits)? -.

hicve. ID

4. Does it appear that the area is free of potentially adverse seismic, spatial 'YeNEI- Ut- N/ADinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

Ah, v:/a- C$.V~&,c/1V4*ofý'~ Iak

13 If the room in which the SWEL item is located is very-large (e.g., Turbine Hall), the areaselected should be described. This selected area should b'e based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrqnnndnP.nn Nn • RR-19-173

D-31

Page 85: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

r"TV %_ -LI 0 ' -"

Sheet 2 of 2

Area Walk-By Checklist (AWC) a

Location: :BldAg..,- Floor El. 1..25,. Room, e ( ' .

5. Does it appear that the area is. free of potentially adverse seismicinteyc ionsat could cause flolding or ray in.the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

NO UD N/AD

YV- UO N/AD

/

7. Does it appear that, the area'is free, of potentially adverse seismic N UD N/AED 'interactions'associated with housekeeping practices,. storage of portable.equipment, andltemporary installations g sca.folding, ead;,

ding) ..... .. .. -..... ..... ..... ...

8. Have you looked for and found no other seismic.conditions that couldadversely affect the safety functions of the equipment in the area?

Y.R NO U.

Comnimhts (Additional pages may be added as necessar/ ' ., .S ' . ; ji

Evaluated I)Y: Date: - !• -

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrmnnndr.nrn_ Nn - R.A-9-171

D-32

Page 86: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

us-U C_ t(3-16Sheet 1 of 2

Statui. U

Area Walk-By Checklist (AWC)

..Location: .Bldg.. 6b 'Fldor El. L Ro , Ardea 3. 46 e4

Instructions for Completing Checklist

Thisechecldist maybe used to document the results of the Area Walk-By near one or more SWEL items. The-"space below each of the following que.stioiis may be used to record. the results of judgments and findings.Additional space is provided at the end of this checklist' for documenting other comments. %:

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopening cabinets)? ...

YANO UD N/AD -

2. Does anchorage of equipment in the area appear to be free of significant V l-I UI] N/A[-Id degraded conditions?

3. Based on a visual inspection from the floor, do the cable/conduit.--raceways and HVAGducting appear-to be freeof potentially adverse- seismicchconditiohis (e.g., condition of supports is adequate and fill

"cbiditions-of-cabletrays appear to be inside acceptable limits)?

YPFlVWI N/ADE.

4., Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipmerPt in the area (e.,, ceilin tiles.and

VkNo uoNJA9 -

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< c-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3(.nrrPnnnndinr.. Nn • RR7-1717

D-33

Page 87: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AMC- (J3-lbSheet 2 of 2

Area Walk-By Checklist (AWC)

Location: BEdg: .ii•{• Flfoor El. • Room, Area 13

5. Does it appear that the area is free of potentially adverse seisinteractions that could causerflooting or spray in the a'a

N P A" 1v na r e a

•~~~~v f • j $

A4~-~7 All

J luoew____

mnc

6. Does it appear that.the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

YvM NO UO N/AO

YbNO U- N/AO.•

Y, NEI UO N/A'IQi .,I "

8. Have you looked for and found.no otiler seismic conditions that could YJM NI]adversely affectthe safety functions of lie equipmen.tinthoare ?

t•t ( •

UEn

r el-e_

4~ t (40" t.ý

Comments (Additional pages may be added as necessary)

Date: il/? #

7-7~

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrm.qnnndPnr.P Nn • RR-12-17.

D-34

Page 88: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

itpod-/ M5-/7Sheet 1 of 2

Status.: N U

Area Walk-By Checklist (AWC)Ic/

-Location:. -BdI ~4 Mr,( hf o~r El. 0-6b Rom ra 13. C ,

Instructions for Completing Checklist

This checklist may be used to document the results of the AreaWalk-By near one or more SWEL items. The:space below each of the following question's nlay. be used to record the resultsofjudgmeits and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopening cabinets)? ". 5Lv.. 4 , "

YON" UQ N/A.

2. Does anchorage of equipment in the area appear to be free of significant,:degraded-conditions? :" ,', .

3. Based on a visual inspection from the floor, do the cable/conduit-raceways-and HVAC-ductingappearto be free of potentially advte, .. eismniiconditions (eg.g condition of supports'is adequate and fill

-con ditions of cable trays appear to be inside'acceptable limits)?

Yk NCi U- N/AO

Y,."2KN UEIN/A[ ,

N/AO4. Does it appear that the area is free of potentially adverse seismic spatial Y4 NO UD"Iinteractions with other equipment in the area (e.g., ceiling tiles andlighting)? No °I / • 1

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrP~nnndP.nrp. Nn " RR-19-173

D-35

Page 89: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AWe - U3-•t

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location:. Bldg.________ Floor'El. I :'omkea" Rl,€./2 .,"

5. Does it appear that the area is free of potentially adverse seismic Y-Nl] U[J N/ADinteractions that could cause flooding or spray in the area?,NO"

6. .Does.it appear that the, hrea is free, of pQtentially adverse seismicinteractions that could cause a fire in the area?

XNEI UO N/AO

7. Does it appear that the area isfree ,fpoteýtially adverse seismic , YJ NE UD N/A :"interactions associated with .housekeeping pracfices, stda6ge of portble .-equipment, and temporary installations (e.g., scaffoldig, leadshielding)? t. .Il/ OL 4 "

~t L4'~A ~ ~ b44- ~ . -pekf4% e,

- **v ~ipr

.8. Have you looked for and found no other seismic conditions that couldadversely affect the safety fInctions of the equipment in the area? ,ý"] U13. -I

Comments (Additiofial pages may b',"addedas necesaiy "

Date: . ( a

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rCnrrPqnnndrnr.P. Nn • RR-19-17.1

D-36

Page 90: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

StatusiA N U

6A44'Area Walk-By Checklist (AWC)

'Lcation: .Bldg. ! FloorEl. F o r Room,Area' 3 C i,"' • -

Instructions for Completing Checklist

This checklist may be used to document the results of the Area Wal1W-By near one or more SWEL items.: Thespace below each of the following questions may be used to record the results ofjudgments and findings..Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopeningcabibnets)?

2. Does anchorage of equipment in the area appear to be free of significantdegraded conditions

3. Based on a visual inspection from the floor, do the cable/conduit

• seismic conditions (e;g., condition of supports is adequate and fill: conditions of cable trays appear to-be inside acceptable limits)?

4. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

YND UEJ N/AD -

ND UD N/AO,,

YPNN- UEJ N/AO

YdNO UEJ N/ADO

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.•

<C-5>

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrAmnnndPnrn. Nn • R.R-19-173

D-37

Page 91: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AWC-U3-'YSheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg."j "I& FloorEl. q . [ Room, Area".40 -V-0.3C

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or splay in the area',,vi lilt~

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does.it.appear that the area is.free of potentially.adversee.seisipiic ,interactions associated with housekeepingipractices, storage ofportable

equipment, and temoar nstallations (e.g., scaffolding, leadshielding)? t Wt4|C• fO(:.

S.NI U[ N/ADI

EN" U[I N/AD.

'Iqo U[J N/AI,

8. Have you looked for and found no other seismic consditins that couldadversely affect the safety functions of the equipment in the:area?-

Yi<NO UO

Comments (Additional pages may be added as necessary) "

1* "--1 ' . "• " : , . •-' " ": i'

Evaluated by: Date:

< C-6 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrmnondnnrP. Nn RR-1.9-171

D-38

Page 92: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Statu-s: N U

Area Walk-By Checklist (AWC)

Location: Bldg. M Floor El: |LQ. Room,Area"3 R'i- c/A - C , r

Instructions for ComiipletingiChecklistThis checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of-the following questions may be, used.to i.ecord.the resultsof.judgrients and findings.

Additional space is provided at the end of this checklist for documentingother cdmmenti.

1. Does anchorage of equipment in the area appear to be free of YJ•N] UI N/Ar'D,potentially adverse seismic conditions (if visible without necessarilyopening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant Y•NII U-1 N/Ar,-degraded conditionsT'

3. Based on a visual inspection from the floor, do the cable/conduit YO' NEI UE N/AE.S .,raceways and HVAC ducting appear to be free of potentially adverse,

seismic condi:tions (eg., condition of supports is:adequate and.fill,. , -

conditions of cable trays appear to be inside acceptible limits)?-.ý.. .- "

4. Does it appear that the area is- free of potentially adverse seismic spatial Yk NOI UD N/A..

interactions with other equipment in the area (e.g., ceiling tiles andlighting)? L.kt-, d€ q,( ,

UIf the room in which the S-WEL item is located is very large (e.g.; Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< C-5 )>

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-39r.nrmq.nnnriAnr.P Nn • R.R-19-17.1

Page 93: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AWc- -113-11Sheet 2 of 2

Area Walk-By Checklist (AWC)

'"catindg U ~.fz F166t l. I (e Room,;Area'1- C-/4 A--' ,w'-443_1_ -9<:

5. Does it appear that the area is free of potentially adverse seismicinteractionsthat could cause flooding or spray in the area?

• , 4 /4e %V .- 44

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

Y19Nr' UEr N/AI-

YN'NO UEJ N/AD

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?,

XýNO UD N/AD.,"Y '. , .- : )

8. Have you looked for and found no other seismic condtions that couldadversely affect the safety. functions.of the equipment.'in the area?, Y AND U . :.

Comments (Additioinl pages may be added as ne-cessary)

N.

Evali dated by: Date:.'T Tv

< C-6 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rlnrrmnnndnP.1nr Nn - RS.-1 "-17.T

D-40

Page 94: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

4,4kdC- a3 -goSheet 1 of 2

Status.6 N U

Area Walk-By Checklist (AWC)

.Location; Bldg.: ._.___ Floor El. M& Room,, a /f Ii t4i PTL5tc"~.r II . . . . U --

-Instructions for Completing Checklist

'ThisAchecklist may be used to document the results of the Area Walk-By near one or. more SWEL items. Thespace below each of the following questions may be used to record the results ofjudgments knd findings.Additional space is provided at the endof this checldist for documenting other-comments.

-1. Does anchorage of equipment in the area appear to be free of". potentially adverse seismic conditions (if visible without necessarily

opening cabiniets)? . - "

Y NEI UEl N/A-

2. Does anchorage of equipment in the area appear to be free of significant YX NlI UI" N/A[].4eaddcnditions? "A..~. - 'egr.ded.co

3. Based on a visual inspection from the floor, do the cable/conduit.,raceways! andHVAC- ductin.g appear -to be free of potentially adverseseismictcon cition of supports is adequate and-fillconditionrs6f 'cable trays appear to be inside acceptable limits)?-',

YANI- UI N/A-

.4. Does it appear that the area is free.of potentially adverse seismic spatial Yk'Nl UI] N/AD ,interactions with other eqjipment in the area (e.g., ceiling tiles andlighting)? Alt Vd I04 Jt /Z eaO•'"

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-41.nrrP.qnnr1nrý- Nn • RR-1T-17;

Page 95: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AWC--U3- Z

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Locatiton: Bldg.%:'• Floor El. J(&- Room,'seea" P. 4-. 9" .•

5. Does, it appear that the area. is free of potentially adverse seismic Y45ND UED N/At]interactions that could cause flooding or spray in the area? .

4. .p I(•,:: C" ' ". '' I '4 -'d.

6. Does it appear that the area is free of potentially adverse seismic YV ND Ut] N/AU :interactions that couldcause a fire in the area?.

7. Does it appear that the area is free of potentially adverse seismic YO NO Ut] N/ACTinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

8. Have you looked for and foimd no other seismic conditions, that couldadversely affect the safety ,functions of the equipment in the area?

Y)ANt Ut]

Commenits (Additional pages may b• added as necessary)......................... '

/7 A7

Evaluatedby Date:

7_4"A/_

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrP.qnnndp nrP.• Nn • PR-19-17.,

D-42

Page 96: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet I of 2

Status: N U

Area Walk-By Checklist (AWC)

Location: Bldg. 7hIVR Floor El. Room, Area1 3k-A - •47'/6_c - .

Instructions for Completing -Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL.items. Thespace below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments. .,' _.. - ..

1. Does anchorage of equipment in the'area appear to be free ofpotentially adverse seismic conditions (if visible without necessarily.opehing cabinets)?

YX ND UD N/AD-,

2. Does anchorage of equipment in the area appear to be free of.significant Y)NI-! UD] N/AD

degraded conditions? : / .

-D0'-ý~ 6frZ C4

3. Based on a visual inspection from the floor, do the cable/conduitraceways-and HVAC ductingappear to be-free of-potentially. adverseseismic conditions (e.g.,& ondition of sulpports ist adequaite k.d fillconditions of cable trays appear to'be inside ac~eptablelimits)?

YX NEI U" NI/AD

4. Does it appear that the area is free of potentially adverse seismic spatial Y NDI U] N/ADinteractions with other equipment in the'area (e.g., ceiling tiles andlighting)?

~) p~ S-066R5 oL76'667-5

'3If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described.This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<-C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-43r•nrrmnnnrIP.nr.P Nn RR-1 9-171

Page 97: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

SeWL -2U -o-f

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. M24w. Floor El. 73-•" Room, Area'3 • A- 7?. W

5. Does it appear that the area is free of potentially adverse seismic YX NO UD N/ADinteractions that could cause flooding or spray in the area?

/6.-Does it appea thffit-ffie-area is optenlly evese•eismic YT D 1 N /AU :.. .W-- .

interactions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismic Yua NO UD N/AD '.interactions associated with housekeeping practices, storage of portable ("equipment, and temporary installations (e.g., scaffolding, lead,shielding)?

8. Have you looked for and found no other seismic conditions that couldadversely affect the safety functions.of the equipment in the area?.

NE UO-

Commenlts,(Additional pages may be added aidnecessary) " "

Evaluated by: Date: ___/__a,-

~fiJ.#.. /6h-89- Zc1'/i

< C-6 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrPqnnnriPnrP.• n • RR-19-171

D-44

Page 98: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet I of 2

Status:0 N U

Area Walk-By Checklist (AWC)

Location: Bldg. Floor El. I Room'Area" 13 I

Instructions for Completing Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results ofjudginents and findings.Additional space is provided at the end of this checklist for documenting other comments.

I. Does anchorageof equipment in the area appear to befree of Yj NI] U-1 N/AQI.-..potentially adverse seismic conditions (if visible without necessarilyopening cabipets)?

2. Does anchorage of equipment in the area appear to be free of significant O NO Ul N/AO.,

d"egraded conditions? .' . . .

. .. ....-Based.on-a-visual-inspection from the floor, do the cable/conduitraceways and HVAC ducting appear to be-free of potentially adverseseismic conditions (e~g., condition of supp6rts is adequate and fillconditions of cable trays appea r to be inside iic-e l

4. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)? J5I.,t S itv(d k.9 t41jj14fdt- 4/

YOiýfl UO NIAO

Y-9Nfl UOE N/AO;.

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaS :. - .",selected should be described. This selected area should be based onjudgmen4 e.g., on the order of

about 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-45flnrrPqnnnrdtnrP. NKin R5R-19-17.

Page 99: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)V3

Location: Bldgj..- .-,Floor El. 6- Room, Area3 C 4 tie IpIe4,,44 hý

5. Does it appear that the area is free of potentially adverse seismicinteraction hat could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

Ccat di f

V I_ /YONO UO N/AOI

*NE UD N/AO.

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, lead

shielding)?

YPID UQ N/AD

8. Have you looked for and found no other seismic conditions that could )fL NO UD "Oadversely affect the safety functions of the equipment in the area?

Comments (Additional pages may be added as necessary) ...

Evaluated by: Date: 54 /";L-

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrP.qnnnrIPnri• Nn RRA-17-17T

D-46

Page 100: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:•0 N U

Area Walk-By Checklist (AWC)

Location: Bldg. • Floor El. JCL5" Room, Area13. r- " 61. i I~r

Instructions for Completing Checklist

This checklist may be used to document the results of the Area. Walk-By near one or more SWELitems. Thespace below each of the following questions may be used-to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopening cabinets)?-

YEPNqI UO M/AU

I:.

2. Does anchorage of equipment in the area appear to be free of significant YJPFN[ UO N/AO].. .:,degraded conditions? . . ........- , :. - ,.. . ;

3...Based.on.a-visual inspection from the floor,.do the cable/conduit YfXNO Ut] N/AD ,raceways and HVAC ducting appear to be free of potentially adverseseismic conditions:(e.g., condition of suppOrts is adeqtite and:fill.-conditions of cable trays appear to be inside accepiable limits)? .

4. Does it appear that the area is free of potentially adverse seismic spatial YJ2asND UI- N/ADinteractions with other equipment in the area (e.g., ceiling tiles andlighting)? •C". . t ,/ 7/ 4 •,,9 -. ,.f- ,, ec r

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-47(.nrrPqnnndHnrP. Nn - RR-I19-171

Page 101: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg.'___ Floor El. JI. Room,.AreaM1 ,g ( jl• ['i"

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismic--interactions associated with housekeeping practices, storage of portableequipment, and temporary installations (eig.,.scaffolding, lead,shielding)? 10'4t t- 4- •1- -+ C -

Y) R NO UQ N/AOD

Yk NO UO N/AQ

Y•tND UD N/AO:

8. Have you looked for and found no other.seismic conditions that. couldadversely affect the safety, functions of the equipment in the area?

)%,.NEI U0

Comments (Additional paes may be added as necessary)

Evaluated by: A( Date: I 01a2

--1/3/12,-

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrs.qnnndInrP. Nn • MR-19-17.1

D-48

Page 102: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

/9wc- a3 -29Sheet I of 2

Status:(EN U

Area Walk-By Checklist (AWC)

Location: Bldg. • Floor El. 1 0,5 Room, Area,'3 k 6, 3 "o-/C

Instructions for Completing ChecklistThis checklist may be used to document the resultsof the Area Walk-By near one or more SWEL items. Thespace below each of the following questions mayý be used to record the results ofjudgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of Y4 rl& url N/AEI

potentially adverse seismic conditions (if visible without necessarilyopening cabinets)?

2. Does anchorage of equipment in the area appear to be free of significant YINEI UO N/AO-degraded conditions? 'X

3. Based on a visual inspection from the floor, do the cable/conduitraceways and HVAC ducting appear to be free of potentially adverseseismic conditions (e.g., condition of supports is adequate aud fill-conditions of cable trays appear to be inside acceptable limits)?

YA NEI UO N/AO

4. Does it appear that the area is free of potentially adverse seismic spatial YO- NI] Uil N/Al.interactions with other equipment in the area (e.g., ceiling tiles and

"If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the area

selected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3(,nrrmnnnH'ntfP Nn " R5R-1-17.1

D-49

Page 103: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

V -h.e. -2- o

:.Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. • Floor El. 1-&5 Room, Area' 3 V%.6 .' 3'3

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

)Iv, 4. + 1 44 r t f

Y•iCNO U0 N/AD

6. Does it appear that the area is free of potentially adverse seismic Y)13 ND'lUI) N/ADUinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismic Y4 NO UO N/AO,interactions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)? o;,t 44'd., *' ,,,1

8. Have you looked for and found noohther seismic conditions that could Yg NOI U0adversely affect the safety functions of the equipment in the area?

Comments (Additional pages may be'added as necessary).

Evaluated Date: 14/k/(2

/0

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrm~nnndPn(e.. Nn ' RRA -1-73

D-50

Page 104: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:,p N U

Area Walk-By Checklist (AWC)

Location: Bldg. SCMtPf t•WFloorEl. JI. Room, Area13.L/Z-L

* Instructions for Completing Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results ofjudgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

I. Does anchorage of equipment in the area appear to be free of YX NO U] N/A[Dpotentially adverse seismic conditions (if visible without necessarilyopening cabinets)?

,oL•,, Feu I olton m on 4w- -,' 4 ..oc-•,A. _.

2. Does anchorage of equipment in the area appear to be free of significant Yt NO3 UQ N/AE,de graded conditions? . . 4 u4 .... / -- _ 4: "J

..o" 4 v 4f tw-, ,

3. Based on a visual inspection from the floor, do the cable/conduitraceways -and HVAC ducting appear to be free of,potentially adversesei•mic condifionrs (e.g.; condition of supportsis adequate and fillconditions ofCible trays appear to be inside acceptable limits)?

4. Does it appear that the area is free of potentially adverse seismic spatial.interactions with other equipment in the area (e.g., ceiling tiles andlighting)? •

YW•NO UO-N/AO

YJ NO UD N/AO]

k(~, U14d~td 4w1 .ot'Q+ ra

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3 D-51

..nrrm~nnnr1P.nrP. Nn " RR 19-171

Page 105: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg.$f•ýL i, " Floor El..ALL... Room, Area'3 9/l " LI.

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

FNO UD N/AO

YX NO UO N/AO

7. Does it appear that the area is free of potentially adverse seismic Y'NdNO U- N/AQlinteractions associated with housekeeping practices, storage. of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)? - o4 .

-UnalAelJIOA 404'4 om StAe.,

8. Have you looked for and found noother seismic conditions that could YXNO U .adversely affect the safetyuýncons of the equipment in the area?

comments (dio apa i b ca ver5 A "Floor red'.

Comments (Additional pages m'ay be added as nece .ssary)

WUJANMlOReD LA06CZ 4001Z ý RI 0+ 110621'"Z

Evaluated by:NJ

Date:

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrPgnnndi.nrP Nn • R-19-171

D-52

Page 106: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Table D-2. Unit 0 Area Walk-By Checklists (AWCs)

Peach Bottom Atomic Power Station Unit 3 D-53MPR-3812, Revision 3Correspondence No.: RS-12-173

Page 107: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:Ty N U

Area Walk-By Checklist (AWC)

Location: Bldg. 3?,'asI it..Floor El. 1 12 i4'Z Room, Area'3 b--LL - 1- b&/ ,El,- K&1111

Instructions for Completing Checklist

This checklist may be usedto document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopening cabinets)T

Y09 NiO UD N/AO.

2. Does anchorage of equipment in the area appear to be free of significant YRQ NEI Ur N/AL]degraded conditions?

3. Based on a visual inspection from the floor, do the cable/conduit..raceways and HVAC ducting appearuto be free of potentially adverse

... seismic conditions (e&g., condition of supports is adequate and fillconditions-of cable trays appear to be inside acceptable limits)?

4. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

YM NI UD N/AL

/9 NO U] N/All]

One- c,,Pe, hv'k 41-1 -,''-1 11ot ve 1)H - 0 -o -.C.&'w ,,/' ,9"J•f 411• 'N t1ol/AS.7_\.. 5.l 7':•, e--,W!., .- ,• ,- , ..=.,,,f±Yi3..

,7 A -- ,ý'44'

f ~ fy / ~,./le-/ d ~ e/oo y

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

C-5 >

Bottom Atomic Power Station Unit 3 D-54Peach EMPR-3812, Revision 3CnrrP..qnnndFnrn Nn • RR-19-171

Page 108: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

A C-2 fISheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. C"" FloorEl. .•2-1J2J Room, Area'3 J'/-t -2-13/•-lg5 Dct p t the a&oot i ll

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

YZI NEI UL N/Al

Aki 3; reA190

YIN! NEI. UL N/AL

7. Does it appear that the area is free of potentially adverse seismic YN NO UI' N/A'!interactions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

8. Have you looked for and found no other seismic conditions that could YP9 NO UOIadversely affect the safety functions of the equipment in the area?

Comments (Additional pages may be added as necessary)

Evaluated by:.L/

Date: 7/.Z/•I?,#

V~

< C-6 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrqnnndr.nrP. Nn • RR-19-17.1

D-55

Page 109: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

,40e- Uz -ZSheet 1 of 2

Status: ) N U

Area Walk-By Checklist (AWC)

Location: Bldg.. t P &(e- .Floor El. 121- I Room, Area 13 -

Instructions for Completing.Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopening cabinets)?

YN NEI UO N/AO

2. Does anchorage of equipment in the area appear to be free of significant Y6 NO] UEI N/AOdegraded conditions?

3. Based on a visual inspection from the floor, do the cable/conduit Y0 ND UD N/AOraceways and HVAC ducting appear to be free of potentially adverseseismic conditions (e.g., condition of supports is adequate and fillconditions of cable trays appear to be inside acceptable limits)?

4. Does it appear that the area is free of potentially adverse seismic spatial Y•J NEI U' N/AOinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

k cj'(t.oI-,"

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrPnnndPnr.p Nn • RR-A9-17.1

D-56

Page 110: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AVWC_-U -zSheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. bI-5c( Floor El. I-i-t27 Room, Area '

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

YK NEI U- N/AO

YO NE UD N/AEI

7. Does it appear that the area is free of potentially adverse seismic Y391 NE UD N/ADinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

fro ide~ A4- t'<.eeyF-ýL ,

8. Have you looked for and found no other seismic conditions that could YJM NE UDJadversely affect the safety functions of the equipment in the area?

Comments (Additional pages may be added as necessary)

Evaluated by:. 1-f- 0 At "'ý Date: S/_2__ __ _ 2_

3' ,~-

< C-6 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3.nrr.nnndPnn-_ Nn RR-19-171

D-57

Page 111: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

l!•14C--14-3Sheet 1 of 2

N• Status: ON U

Area Walk-By Checklist (AWC)

Location: Bldg. EC T' Floor El. t1• Room, AreaU( o,.,,, roo2 ( .- g 0)

Instructions for Completing ChecklistThis checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results ofjudgments and findings. -Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions,(if visible without necessarilyopening cabinets)?

YF NDI UE0 N/AD .

LA

2. Does anchorage of equipment in the area appear to be free of significant YI NDi U!] N/ADdegraded conditions?, ,7.' -

3. Based on a visual inspection from the floor, do the.cable/conduit...... raceways and HVAC-ducting appear to be free of potentially adverse

seismic conditions (e.g., condition of supports is adequate and fill[conditions of cable trays appear to be inside icceptable limits)?,

Y19 NEI U0] N/AD •

4. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

Y&,ND0 U!] N/AD

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >'

Peach Bottom Atomic Power Station Unit 3 D-58MPR-3812, Revision 3rnrrP;nnr1~nr.np Nn RR-1 9-1 73

Page 112: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Ave 2 -3Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. 45-e I- Floor-El. /1-s" Room, Area"3 E e•V14/ F•,/4, -T-g)

5. Does it appear that the area is free. of potentially adverse seismicinteractions that could cause flooding or spray in the,area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?.

YO NEI UUO N/AUI

YK. ND UO N/AD

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations .(e.g.,. scaffolding, leadshielding)?

Y,K NOI UD N/AEl

8. Have you looked for and found no.other seismic, conditions-that .couldadversely affect the safety functions of the equipment in-the area?

YR NE UO'-.

SComments (Additional pages maybe added'as iecesry)Cdmet as - c" ; .

Evaluated by: A"_L/

Date: .________

V/ ia// i 9 --

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrqnnndrnrP. Nn - RR-19-17T

D-59

Page 113: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:(Z)N U

Area Walk-By Checklist (AWC)

Location: Bldg. •7C< Floor El. . J z.Room, Area13.d ' -

Instiuctions for Coimpleting Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarily

- opening cabinets)?-

Yg NO UE N/A.

2. Does anchorage of equipment in the area appear to be free of significant YMk NEI UO N/AO:.degiýaded cohditions?J" ' -'-.".' ,O UD N/A<',.

.. ............

3. Based on a visual inspection from the floor, do the cable/conduit- raceways and HVAGducting-appear.to be free. of potentiallyadverse

"seismic-conditions; (e6.g:, conditionii f supports 'isi adequate and fill-conditions- f 6able traysapper to be inside acceptable limits)?

Y[F NO UC1 N/A -

4. Does it. appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

AJo ~ A'•

Y/MI NOI Ul' N/A •- •

W,' I7 -AeOVI%

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5>

Peach Bottom Atomic Power Station Unit 3 D-60MPR-3812, Revision 3CrnrrA.qennndHAnP. Nn • PS-12-171

Page 114: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AWc-uO-qSheet 2'of 2

Area Walk-By Checklist (AWC)

Location: Bldg., &:C Floor El. 1 Ii! Room, Area"3 C~ I

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

Y)XN-I UQ- N/A[I

YO ND UO N/AO,6. Does it appear that the-area is free-of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, lead

shielding)?

Yg NO UO N/A '.A

8. Hav~e you looked for and foundmno other'seis'mic' condition~s that could YI& N[I U[-3

adversely affect the safety functions of the. equipment in the area?

_Comments (Additional pages may be Add as necessairy )

Evaluated by:. Date: Z.

20 -% ?/?-/

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3"nrrP..qnnrInnr.. Nn • RR-19-173

D-61

Page 115: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

bntucin forst.4ýf thepeti Checklistr

Tliischeck~istmay, be used to documnt the eutsoh Area Wal-By near n rmr SWIEies.space beow&ahf the-following quesbtioýn's may be..used to recodkdthe; results .of judgment an d findings

Additio~had"-l space iprvi athenof-.this che&cklist. for.. docmitn tercnins

I.Dos ncorg of equipnient in- he-area4`' apetO-,be fre fN] QNApotetialy averse. seismic ýcondion(f iblwthinesaryopnncabines?

2.iDoeslanch'-o-r.age of equipm~nenit-in ~theaeia ap~pe-a-rt be fe ofsign"&Aifan Y, N DNARegde condItion's?

3~ Bse n -vsalinpetonfrmthe lor d tecable/conduitý ElN:U NIAO

seiglsnl9 .coditions'(e~g, condit'io'iY~f sip'p~ort's is'. adquate land f.'llcondctiki ofcbe f ~ppe to be inside cetbelmt)

li-httng)?o -

~b eF'em (, 'A '~'i y1 ~ , V JSNtEl

'3if the room in;hkh the. WEL. item Is doae is* v 'le(Og.,; Trbine HA),te eaSSdekcCudd&h b edds'ib TK6. selectedare 'Oiia~ldb b'di""I" jidmn;4nde th "w"f

abt3f er~r -srb 6Il~a'co u.Vg ýeg n re.. 6660 _,k ther SWitem

< -:>

Peach Bottom Atomic Power Station.Unit 3MPR-3812, Revision 3rnrrr n•nndpric-p Nn K - RsV=173

D-62

Page 116: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. EC- - Fl6orEl. /I1 Room, A-rea,3 e6 T--

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismicinteractions'associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

YY NO UD N/AQ

YNI UO N/A0

YI NO UD N/AO

8. Have you looked for and tiound no other seismic conditions that could YIZ N[D UD]adversely affect the safety functions of the equipment in the area?

Comments (Additional pages may be added as necessary)

Evaluated by: Date:

7,

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3f.nrrPqnnndPnrn- Nn " RR-917A

D-63

Page 117: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

"Sheet- lof 2Staus:~ Ni :U

Area Wlk-ByCheckht(A

'Thi !hcls ~ybe udO~cumentftheresults of.te` re Wl-Bynear one or morelSWEL items. Thev

sjpace beloweach, of the, follwing questionsýý may b 9e usd to r'ecbr'd-the results ,of judgments ý,and finidins

openar e.cainets? of

2 Dosaficho~ra of equipment-in• "~theare .a.ap..t •be free of significant

. ,.Basedona.vsualnspectionfrom, the, floor, doý'the cable/c.onduit~~~~9 mrceay Rn4V ducting-apparob freo poetal ,adverse.,

sesmcicoditio coditionof spporspq aeqae' ndflcodiiof of cal insy l',-"l

", • , ; : 4•2 ':•' '.''-'-"• , :?":¢: :- '<""•. '•"*.s ~ ~',+" V k._ it" t N `.€ "..•... , , .I••,. .,,'2 ,"-:Z- .. ..-. •'.• ,• • -'.:,;• _'.,."," 'S k n c c,..n ~ ~ n ~ .. •:co u o , s p o ,!s a~c ia • • d u ,

YJ~ 1~Q 110 PAo

Y~ NO UO N/ADC -~ . .. , ~.

-. C.-

.,:.vv

* i . C.

4. Dost09 partht0h area is 'free o'f potientiafllyadVerse seismic( spatialfinteractions, thother.equ pmentur- nthe area. (g,-;ceiigdtiles.and....ghting)?e- ..

10110l N/AONO; UC; i~b

'3 Ifth oo wictheSE cmiloat4s erylre (egTurbineHl),heaaisedec'~ed~shoulcl bdesdrib&I.a:This I:eldd areaa should be bised: donju et e:,o!,oeo:ioti!ri SW L dbe se j-dtm . .....

. . . )em

Peach Bottom Atomic Power Station',Unit 3 "-64MPR-3812, Revision 3 D i. , "rn~rr-ýnnndpmri& Nn. RA-19-173.

Page 118: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. 7e/biA Floor El. /4• Room. Area" •3 tJ4" 44/A'$x Ar 6p,&o/ .

5. Does it appear that the areais free of potentially adverse seismic.interactions that could cause flooding or spray. in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

YM NO UQ N/AO

Y$j NO UO N/AQ:

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

YX NEI U N/AO.

8. Have you looked for and found no other seismic conditions that could YM[ NOI U -adversely affect the safety.functions of the equipment in.1he area? /

comments (Additimnal pages may be added-as necessary.

Evaluated by:d

Date: 4LT/? AL_~

I t

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r•nrrP.ýnnndPnr.P. Nn • RR-12-17.1

D-65

Page 119: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

)Y6- 610- 7Sheet I of 2

Status: 0 N U

Area Walk-By Checklist (AWC)

Location: Bldg. a,,-,, ifJ'.Floor El. 16S Room, Area13 L6,h- od i

Instructions for Completing Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results ofjudgments and findings..Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopening cabinets)?

Yq-.ND UE N/AD ...

2. Does anchorage of equipment in the area appear to be free of significant Y•W N] U[]I N/AD'degraded conditions?

3. Based on a visual inspection from the floor, do the cable/conduitraceways and HVAC ducting appear to be free of potentially adverseseismic conditions (e.g., condition of supports is adequate and fillconditions of cable trays appear to be inside acceptable limits)?

4. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

~t ~cL ~&~ ~ ?-J 4~'Y(~- CL'

Y4 NEI U- N/AD.

YNl ND U N/AD!

. .. : .

cf-I'- &-(0 & / ýýee_ ZA 0 la X&

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< C-5 >

Peach Bottom Atomic Power Station Unit 3 0-66MPR-3812, Revision 3rlnrrmnnndrnrP. Nn ' RR-19-17.

Page 120: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. , IMA, Floor El. -(6 Room, Area'3 L'oWI'o 1 3oot1

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

YR NE UD N/Af

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

Y9 NE UE N/AO

YýT NO UM N/AD

8. Have you looked for and found no other seismic conditions that could YJR NE UEadversely affect the safety functions of the equipment in the area?

Comments (Additional pages may be added as necessary)

Evaluated by: 6i~>2-~ Date: / !/ V/,2-

I&'

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3rnrrP.qnnndPnrP Nn • RR-19-171

D-67

Page 121: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

/7wd -00 -IFSheet 1 of 2

Status:• N U

Area Walk-By Checklist (AWC)

Location; Bldg. 7bT/h,: Floor El. /t&- Room, Area13 F4

Instructions for Completing Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of YN[] UO] N/Al].-,,potentially adverse seismic conditions (if visible without necessarilyopening cabinets)? .

ver've- ,..rM/6 zeIr

2. Does anchorage of equipment in the area appear to be free of significant YM NEI UEI N/ADI..:,degradedconditions?. ,,.

/'D> /iOe- /y4 1ýelAxee 44'e .d'ere /Z' 4e '4,ak 45-

3. Based on a visual inspection from the floor, do the cable/conduit Y[R NEI Ul N/A[]raceways and HVAC ducting appear. to be free of potentially adverse-

* ssc conditions (ewg., condition of supports is adequ-teand fill.conditions of cable trays appear to be inside acceptable limits)?

4. Does it appear that the area is free of potentially adverse seismic spatial Yi NEI UD N/ADinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

'3 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3 D-68MPR-3812, Revision 3.nrrnnnrPnntP Mn • RR-19-171

Page 122: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. 7"w Lir.. Floor El. I65" Room, Area'313 ' ' w

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the, area is free of potentially adverse, seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, lead

shielding)?

YJR NO U- N/AU

Y/ NEI UI N/A'.

YP NO UI N/A.

8. Have you looked for and found no other seismic'€.c'nditions..that could YP• NEI UOI :..-

adversely affect-the safety functions.of the equipment iin.the area?

Comments (Additional pages may be added as necessary - .

Evaluated by:. Date: /

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrP-nnndP.nr.A Mn - MR-1 9-17.T

D-69

Page 123: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

sliet1 f 2ý

Status;O'N; Uv

Area akB hcls AC

Room, Area'6 ) l~

Istructi44s ort~omp et"n hcls

Addiionl spce uspoyced at the endo this chckis ebr doc mgte.comnsI1 .. Doe anhrg .fcupini th axes pert efe/fY N L /l

.ra.e...s.a __,-_,q c ingapp ,,ea to bpe free of poenial ad"rs

opnditgionsfcbe sry pert eisd cetbelmt)

Diq n deat~i with ote r &..., q uip met in the'di arpeaý (eg. celn ies an-~ I.

oi 1cft ii FJrt it K'C

' oii 35'ti tr~ the AVE ite

Peach wy~ad Boto Atmi Powe Stto Uni en 070aMP-1,sRevismione

coidNin app gtp 0q.7ýj

Page 124: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. .e - J. Loor El. 151 Room, Area13 r16 - 1)

5. Does it appear that the area il free of potentially adverse seismic Yd[NrI UEJ N/AI-interactions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismic Y[(NrI UI- N/AOinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismic YBNr'i url N/AL)interactions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)?

8. Have you looked for and found no other seismic conditions that could Y[ikNrI ULIadversely affect the safety functions of the equipment in the area?

Commments (Additional pages may be added as necessary)

wV/A

Evaluated by:. Date:

2- -Z7/6(

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3('nrrqnnnriPn".• Nn RR--19-171

D-71

Page 125: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

,4uoQ- Ito -Sheet 1of2

Status& N U

Area Walk-By Checklist (AWC)

Location: Bldg. Floor•.El. I S Room,.Area" gIW " ).-

Instructions for Completing Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following'questions may be usedto record the results of judgments andifindings.,Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free of YM NEIpotentially adverse seismic conditions (if visible without necessarily

-opening cabinets? .o 44 Lo

"Ur " 'r A#An -,esJ4vmk - nos

2. Does anchorage ofequipment in the area appear to be free of significant Yco o NO.: : ,>. :.'.:>.degraded conditions? ;'.iii ":,:i :•:

UO N/AO

vIa*C

UD N/AE] : , ,.,:.. .•' ..

3. Based on a visual inspection from the floor, do the cable/conduit.racewaysand HAC- ductingappear tobefree-of potentially-adverseseismic conditions (&.g., condition of supports'is adequate and fillconditions of cable trays appear to be inside acceptable limits)?T

5$-of-oI coblc' 4 0~Y5 _F1 OtO kc9 i

Y' NEI UE N/AE]

4. Does it appear that the area is free of potentially adverse seismic spatial Yk'NEIinteractions with other equipment in the area (e.g., ceiling tiles andlighting)?

UE] N/AE'

1 If the room in which the SWVEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< c-5 >"

Peach Bottom Atomic Power Station Unit 3 D-72MPR-3812, Revision 3rlnrrm..,nnnr1PnrP. Nn ' RRA -1-71

Page 126: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. • Floor El. !t5 Room, ,Area1O'3/ /c-

5. Does it appear that the area is free of potentially adverse seismic Ybd NO! UI N/A-interactions that could cause flooding or spray in the. area?

6. Does it appear that the area is free,,of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary. installations (e.g., scaffolding, leadshielding)? 4# Tool a( $strcb

Y4NOI U! N/AD

4X N[I UO N/AU.......................... .•..'..... ".-;-

8. Have you looked for and found.noother.seissmicconditions that couldadversely affect the safety functions, of the equipment in the area?

YX NO UE1

Comments (Additional pages may. be added as necessad):

NIA\

Evaluated by: (ý04 ý V - - Date: / / )

iO2Otz

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrrP..nnnldPntCP Nn • RR-19-17.

D-73

Page 127: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:& N U

Area Walk-By Checklist (AWC)pio

.I & 10/3111?.LZ

Location: Bldg.. FIcrEl. i2.." Room, Area'3 'iJ(-q bW-i,7

Instructions for Completing ChecklitThis checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopening cabinets)?

Y[Ef NO U- N/AD

Auri Izes'Rvo Oecroqs- 14A S Y2"8 '4/actMor l3LT~S A~ i - benOdt

AJVi~lgft T30OLrS' AkC 31{t6OLrb rO 7361L & ~A[~~CI ~~~7)11E I CALL 4kTkf AS x.eCfcfr-AWrC %_K~ AOZI Pqdiqd. ecC III&IhZ

2. Doe anhraeo equip~ment in the area appear to be tree of significant YLý'NI] UI] N/A[] -

degraded conditions?

3. Based on a visual inspection from the floor, do the cable/conduitraceways and HVAC ducting appear to be free of potentially adverseseismic conditions (e.g., condition of supports is adequate and fillconditions of cable trays appear to be inside acceptable limits)?

YM'NI-I UDI N/AD

4. Does it appear that the area is free of potentially adverse seismic spatial YQ( NI]interactions with other equipment in the area (e.g., ceiling tiles andlighting)?

UE- N/AEJ

tk-/4Aadb 1P Lao It tue ~sr ~*r (~J~Jcrectee butntco r~

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

< C-5 >

Peach Bottom Atomic Power Station Unit 3 D-74MPR-3812, Revision 3

..nrrPgnnnH~nr.P Nno R.0-1 9-171

Page 128: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

AwC--L)~641Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. 0', l . Ioor El. )ýIi Room, Area13 bla-4

5. Does it appear that the areas free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)? , . .. , . . .. .. . .

YEI"'N1 UEI N/AEI

YD"NFJ UEI N/Afl

YI~'NE UEl N/A[]

ý;-ATVLI;ý CAR-1 _v-M4 ý_Ou(a-v %,j(,4CqýL

8. Have you looked for and found no other seismic conditions that could Y[ET" N[1 U'-adversely affect the safety functions of the equipment in the area?

Comments (Additional pages may be added as necessary)

Iv/A

Evaluated by: Date: O/) la

-)6 --e. ,, --- 4 2 P) -201

-< C-6 >

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3r.nrmcnnnrlanr•P Nn • RR-1?-171

D-75

Page 129: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 1 of 2

Status:&•N U

Area Walk-By Checklist (AWC)

Location: Bldg. A ra." Floor:EI. ]K L Roopm,'Area 13 nl' rV 4 4-

Instructions for Completing Checklist-This checklist may be used to document the results of theArea Walk-By near one or more SWEL items. Thespace below each of the following questionsmay be used to. record the:results. of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments.

1. Does anchorage of equipment in-the area appearuto be free ofpotentially adverse seismic conditions (if visible without-necessarilyopening cabinets)?

YALNO uo N/AD--

2. Does anchorage of equipment inzthe area appear to be free of significantdegraded conditions?

3. Based on.a Visual inspection from the floor, do the cable/conduitraceways and HVAC ducting appear to be freeof potentiallyadverseseismic conditions (e.g., condition of supports is adequate and fill,conditions of cable trays appear totbe inside acceptable'limits)?,2

NOU- N/AD" i .,-

X NDI UQ N/AD :,;-.

4. Does it appear that the area is free of potentially adverse seismic spatial I D UO N/ADinteractions with other equipment-in the area (e.g., ceiling ti,.1sd d... -.

lighting)? Zn Nr/f c~~c-

"~ ~

V t 0ý kA a 5 +,kI4ý 9-

eV4.~ Af 4 hal

0-r13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3 D-76MPR-3812, Revision 3rnrrPqnnnd,-,nr. Nn " R-19--17.1

Page 130: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. X Floor El. • U•I Room,.Areau3 -x4I f OV3-.

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

;:"v oý 4. . • ,: -'. . . i- . le.

4Yff NEI U[I N/A[I

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire in the area?

7. Does it appear that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations :(e.g., scaffolding, leadshielding)?

SND: UQ N,/AEI

4%ZNrJ uo N

8. Have you looked for and found no other seismic conditions that~couldadversely affect the safety functions of the equipment in, the area?

ZT!CNO uo]

Comments (Additionaltiages may. be added as necessaiy)'"

- t-,'*. .

Evaluated by: Date: , 1, ? -

Ax&L

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3CrnrrPnnndlnr.P Nn • RSWZ92.171

D-77

Page 131: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

,410C-0LL-13Sheet I of 2

Status:9 N U

Area Walk-By Checklist (AWC)

Location: Bldg.. F "", Floor El. 112.. Room, Area' 3 02. HPSW Pu, J1•1a (V PH_6

Instructions for Completing Checklist

This checklist may be used to document the results of the Area Walk-By near one or more SWEL items. Thespace below each of the following questions may be used to record the results of judgments and findings.Additional space is provided at the end of this checklist for documenting other comments. .

1. Does anchorage of equipment in the area appear to be free ofpotentially adverse seismic conditions (if visible without necessarilyopening:cabinets)?

Y4I.ND UD N/AD .

2. Does anchorage of equipment in the area appear to be free of significant YRND Ul] N/Aldegraded conditions?

3. Based on a visual inspection from the floor, do the cable/conduitraceways. and HVAC ducting appear to be free of potentially adverseseismic conditions (e.g., condition of supports is adequate and fillconditions of cable trays appear to be inside acceptable limits)?

Y0ND Ul' N/Al

4. Does it appear that the area is free of potentially adverse seismic spatialinteractions with other equipment in the area (e.g., ceiling tilesAndlighting)? Nf tL-oi fOf , ,

N] UL- N/Al]

tjf%

MocJ~ &s~c/1 ;~

~cd~t C~A s~d2 e*1 ~Vttc~ ~- Cr~J"('S ~ ~ ~ Mo

6~.4

'a/tliz

13 If the room in which the SWEL item is located is very large (e.g., Turbine Hall), the areaselected should be described. This selected area should be based on judgment, e.g., on the order ofabout 35 feet from the SWEL item.

<C-5 >

Peach Bottom Atomic Power Station Unit 3 D-78MPR-3812, Revision 3CnrrP~nnnd~nrp. Nn • RR-19-17."

Page 132: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Awet. 2o- 13Sheet 2 of 2

Area Walk-By Checklist (AWC)

Location: Bldg. . S . Floor El. -' ILt . Room, Area13, 12 HCS'W

5. Does it appear that the area is free of potentially adverse seismicinteractions that could cause flooding or spray in the area?

6. Does it appear that the area is free of potentially adverse seismicinteractions that could cause a fire -in the area?

7. Does it appear.that the area is free of potentially adverse seismicinteractions associated with housekeeping practices, storage of portableequipment, and temporary installations (e.g., scaffolding, leadshielding)? A , -t4 7 , 4 •- '

v., keone

Y09ýNO UD N/AE3

YNO UEJ N/AO.

Y2NO UO N/AD

e~'4 v~v~,qAr 5e~c~ h~.

8. Have you looked for and found no'oiher seismic conditions that could Y[•NE] UE.adversely affect the safety fumctiQns ,of the.equipment-in the.area?,

Comments (Additional pages may be add'd a'sneces'siary) .... . ..

EValuated by:

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3,nrrPmnnnrIP.nr.P. Nn • RR-19-173.'

Date: ' 2

<C-6>

D-79

Page 133: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

EPlan for Walkdown of Inaccessible Equipment andAssessment of Electrical Cabinet InternalInspections

E.1. PLAN FOR WALKDOWN OF INACCESSIBLE EQUIPMENT

As shown in the SWEL for PBAPS Unit 3 in Appendix B (Table B-3), 13 items have beendeferred until the next refueling outage (RFO) or a future electrical bus outage. TableE-1 summarizes the reasons each item is inaccessible during normal plant operationand indicates the estimated milestone completion and tracking number.

Table E-1. Summary of Inaccessible Equipment

Reason for Milestone TrackingComponent ID Description Inaccessibility Completion Number

00B094 480V Bus E13A4 Requires 4KV Bus 6/2013 IROutage 01426027

30B037 480V Reactor Area MCC Requires 4KV Bus 10/2013 A1533874E234-R-B Outage

30A015 Emergency 4kV Aux Requires 4KV Bus 10/2013 A1535569Switchgear E23 Outage

30B01 1 480V Load Center E234 Requires 4KV Bus' 10/2013 A1535775Outage

A03-01-080A Inboard Main Steam Located in drywell 10/2013 Al 863615Isolation Valve A

A03-01-080C Inboard Main Steam Located in drywellIsolation Valve A

RV3-02-071 D Safety Relief Valve D Located in drywellRV3-02-071 F Safety Relief Valve F Located in drywellMO3-06-029A Feedwater Stop Valve Located in drywellMO3-23-015 HPCI Turbine Steam Line Located in drywell

Inboard Isolation ValveMO3-23-019 HPCI Discharge to Located in main

Feedwater Line Valve steam tunnel/MSIVroom

3BT540 Instrument N2 Located in drywellAccumulator

3KT545 Instrument N2 Located in drywellAccumulator

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

E-1

Page 134: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

E.2. ASSESSMENT OF ELECTRICAL CABINET INTERNAL INSPECTIONS

All electrical cabinets on the SWEL require assessment of the need for inspections toaddress the potential for "other adverse seismic conditions" internal to the cabinet. Thisassessment is required due to an NRC clarification of their expectations for seismicwalkdowns, which was received after the online seismic walkdowns were completed.Tables E-2 (for Unit 3) and E-3 (for Unit 0) list all electrical items that requireassessment. Accessibility of equipment, basis for accessibility determination,completion date of internal inspections, tracking number (if internal inspection has notyet been performed) and inspection results are provided in these tables.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

E-2

Page 135: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Table E-2. Assessment of Unit 3 Electrical Cabinet Internal Inspections

Component ID Description EPRI Equipment Class Accessible (YIN) If Not Accessible, Milestone Tracking Status IWhy? Completion Number Inspection

(IR Number) Results30B324 MO-3-23-015 Motor Control Power (01) Motor Control Centers Y N/A 10/2013 A1863615 Scheduled

Transfer Switch30B325 MO-3-13-15 Motor Control Starter Panel (01) Motor Control Centers Y N/A 10/2013 A1863615 Scheduled30B338 M03-10-16A Auto Transfer Switch (01) Motor Control Centers N Tools required for N/A N/A N/A

disassembly30B37 480V Reactor Area MCC E234-R-B (01) Motor Control Centers N Tools required for N/A N/A N/A

disassembly30B010 Emergency Aux Load Center E134 (02) Low Voltage Switchgears N Tools required for N/A N/A N/A

Switchgear disassembly30B013 Emergency Aux Load Center E434 (02) Low Voltage Switchgears N Tools required for N/A N/A N/A

Switchgear disassembly308011 480V Load Center E234 (02) Low Voltage Switchgears N Tools required for N/A N/A N/A

disassembly30A15 Emergency 4kV Aux Switchgear (03) Medium Voltage Switchgears N Tools required for N/A N/A N/A

disassembly30X030 Load Center E134 Transformer (04) Transformers N Tools required for N/A N/A N/A

disassembly30X033 Load Center E434 Transformer (04) Transformers N Tools required for N/A N/A N/A

disassembly30X133 Panel 30Y33 Transformer (04) Transformers N Tools required for N/A N/A N/A

disassembly30S703 120V Inst. Panel 30Y035 Transfer Switch (14) Distribution Panels Y N/A 7/2014 A0668950 Scheduled30Y050 120V AC Distribution Panel (14) Distribution Panels N Energized Equipment; N/A N/A N/A

never out of service(diesel backed and

battery backed)30Y35 3PPD 125V DC Distribution Panel 3C (14) Distribution Panels N Energized Equipment; N/A N/A N/A

never out of service(diesel backed, no PM)

3BD025 3B 125 VDC Distribution Panel (14) Distribution Panels N Tools required for N/A N/A N/Adisassembly

3DC068 RPS SCRAM solenoid fuse panel D (14) Distribution Panels N Tools required for N/A N/A N/Adisassembly

30D37 Static Inverter (16) Battery Chargers and Inverters N Energized Equipment; N/A N/A N/Anever out of service

(diesel backed, no PM)3CD03 Battery Charger 3C (16) Battery Chargers and Inverters Y N/A 3/2013 A1797035 Scheduled3DD03 Battery Charger 3D (16) Battery Chargers and Inverters Y N/A 4/2013 A1807622 Scheduled30C003 Reactor and Containment Cooling and (20) Control Panels & Cabinets Y N/A 9/2012 N/A SAT

Isolation30C004C RCIC Vertical Board (20) Control Panels & Cabinets Y N/A 9/2012 N/A SAT30C005A Reactor Manual Control Board (20) Control Panels & Cabinets Y N/A 9/2012 N/A SAT30C032 Egr Safeguard Sub-Sys 1 (20) Control Panels & Cabinets Y N/A 9/2012 N/A SAT30C033 Egr Safeguard Sub-Sys II (20) Control Panels & Cabinets Y N/A 9/2012 N/A SAT

Pea..h Son- Atomic Power Station Unit 3MPR-.312, Reision 3Co-espondence No.: RS-12.173

E-3

Page 136: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Table E-2. Assessment of Unit 3 Electrical Cabinet Internal Inspections

Component ID If Not Accessible, Milestone Tracking Status ICo DDescription EPRI Equipment Class Accessible (YIN) W ?Completion Number Inspection

Why? (IR Number) Results

30C034 RCIC Relay Panel (20) Control Panets & Cabinets Y N/A 9/2012 N/A SAT30C722A Accident Monitoring Instrumentation (20) Control Panels & Cabinets Y N/A 9/2012 N/A IR# 01424662

Panel30C722B Accident Monitoring Instrumentation (20) Control Panels & Cabinets Y N/A 9/2012 N/A IR# 01424692

Panel300043 HPCI Aux Lube Oil Pump Starter (20) Control Panels & Cabinets N Tools required for N/A N/A N/A

disassembly3BC270 HPCI Steam Leak Detection Cabinet (20) Control Panels & Cabinets N Tools required for N/A N/A N/A

disassemblyL13-2-3-113 Reactor Water Level (20) Control Panels & Cabinets Y N/A 9/2012 N/A SATLI-9027 Torus Water Level (20) Control Panels & Cabinets Y N/A 9/2012 N/A SATLR/TR-9123B Torus Water Level/Temperature Recorder (20) Control Panels & Cabinets Y N/A 9/2012 N/A SATP13-6-90A Reactor Wide Range Pressure Indicator (20) Control Panels & Cabinets Y N/A 9/2012 N/A SATPRrTR3-2-3-404B Reactor Pressure (20) Control Panels & Cabinets Y N/A 9/2012 N/A SATPR/TR-5805 Containment Pressure (20) Control Panels & Cabinets Y N/A 9/2012 N/A SAT

PeacSB eanolT Comk P.-e OtSon SnM 3snPR-30,2.vw ecoo3C --- pond.ne N0.: es.1 2-173

E-4

Page 137: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Table E-3. Assessment of Unit 0 Electrical Cabinet Internal Inspections

Status IMilestone Tracking Number Sau

Component ID Description EPRI Equipment Class Accessible (YIN) If Not Accessible, Why? Completion (IR Number) InspectionResults

00B061 Pump Structure MCC E224-P-A (01) Motor Control Center N Tools required for N/A N/A N/Adisassembly

00B094 480V Bus E13A4 (02) Low Voltage Switchgears N Tools required for N/A NIA N/Adisassembly

00C29B Emergency Protection Relay Board (20) Control Panels & Cabinets Y N/A 9/2012 N/A SAT0AC097 Diesel Generator OAG12 Control (20) Control Panels & Cabinets Y N/A 5/2015 A1620164 Scheduled

Panel I _IIII

Peach Bottom Atomic Power Staticn Unt 3MPRe-312, Revislon 3Correspondence No.: RS-1 2.173

E-5

Page 138: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

FPeer Review Report

This appendix includes the Peer Review Team's report, including the signed PeerReview Checklist for SWEL from Appendix F of the EPRI Seismic Walkdown Guidance(Reference 1).

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-1

Page 139: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Peer Review Report

for

Near Term Task Force (NTTF) Recommendation 2.3

Seismic Walkdown of Peach Bottom Unit 3

Peer Reviewers:

Patrick Butler (Team Leader)

Craig Swanner

Caroline Schlaseman

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-2

Page 140: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Contents

F.1 Introduction .................................................................................................... 4

F .1.1 O ve rv iew .................................................................................................. . . 4

F. 1.2 Peer Reviewers .......................................................................................... 4

F.1.3SW EL Development ................................................................................... 5

F. 1.4 Seismic W alkdown ..................................................................................... 5

F.2 Peer Review - Selection of SSCs .................................................................... 6

F .2.1 P u rp ose ................................................................................................... . . 6

F.2.2 Peer Review Activity - Selection of SSCs .................................................. 6

F.2.3 Peer Review Findings - Selection of SSCs ............................................... 7

F.2.4 Resolution of Peer Review Comments - Selection of SSCs ...................... 7

F.2.5 Conclusion of Peer Review - Selection of SSCs ....................................... 8

F.3 Review of Sample Checklist & Area Walk-Bys .............................................. 9

F.4 Review of Licensing Basis Evaluations ....................................................... 15

F.5 References .......................................................................................................... 16

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-3

Page 141: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

F.1Introduction

F.1.1 OVERVIEW

This report documents the independent peer review for the Near Term Task Force(NTTF) Recommendation 2.3 Seismic Walkdowns performed by MPR Associates, Inc.for Unit 3 of Peach Bottom Atomic Power Station (PBAPS). The peer review addressesthe following activities:

" Review of the selection of the structures, systems, and components, (SSCs)that are included in the Seismic Walkdown Equipment List (SWEL),

* Review of a sample of the checklists prepared for the Seismic Walkdowns &Walk-Bys,

* Review of any licensing basis evaluations,

" Review of the decisions for entering the potentially adverse conditions in tothe plant's Corrective Action Program (CAP), and

* Review of the final submittal report.

F.1.2 PEER REVIEWERS

The Peer Reviewers are Patrick Butler, Caroline Schlaseman and Craig Swanner.Mr. Butler is the Peer Review Team Leader, per the EPRI Seismic Walkdown Guidance(Reference 1). As Peer Review Team Leader, he was responsible for the entire peerreview process, including completion of the final peer review documentation in thisreport. The Peer Reviewers' qualifications are briefly summarized as follows:

* Mr. Butler is a degreed mechanical engineer and has over twenty-five years ofnuclear power experience. Mr. Butler and has been trained as a SeismicCapability Engineer (EPRI SQUG training) and is the primary author of EPRISQUG Guidelines for the use of the SQUG Generic ImplementationProcedure (GIP) for new and replacement components and equipment.

* Ms. Schlaseman is a degreed civil/structural engineer and has over 30 yearsof nuclear power experience. Ms. Schlaseman has been trained as a SeismicCapability Engineer and EPRI Seismic Walkdown Engineer (SWE), hasperformed USI A-46 (SQUG) seismic walkdowns for two stations, and is aprincipal investigator in (EPRI) document 1025286, "Seismic WalkdownGuidance: For Resolution of Fukushima Near-Term Task ForceRecommendation 2.3: Seismic," which is the guidance document forperforming the walkdowns documented in this report.

Peach Bottom Atomic Power Station Unit 3 F-4MPR-3812, Revision 3Correspondence No.: RS-12-173

Page 142: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Mr. Swanner is a degreed aerospace engineer with 20 years of nuclear plantexperience. Mr. Swanner has been trained as a Seismic Capability Engineerand EPRI Seismic Walkdown Engineer (SWE).

Mr. Butler, Ms. Schlaseman and Mr. Swanner are registered professional engineers.

F.1.3 SWEL DEVELOPMENT

The SWEL development was performed by Mr. Benjamin Frazier. The initial peer reviewof the SWEL development was performed by Mr. Butler and Mr. Swanner, and wasconducted between August 2, 2012 and August 16, 2012. There were no comments asnoted on the SWEL Peer Review Checklist and no findings were cited. The completedSWEL Peer Review Checklist is found in Attachment 1. The discussion for the SWELdevelopment peer review is provided in Section 2. Note that due to equipmentaccessibility including ALARA and electrical safety concerns, changes to the SWEL weremade as the walkdowns were conducted. The Peer Review Team did review changesmade during the walkdown and has reviewed the final SWEL included in Appendix B ofthe Walkdown Report. As noted in the SWEL Peer Review Checklist, there were noitems from EPRI Equipment Classes 11, Chillers; 12, Air Compressors; or 13, MotorGenerators. This was because there is no safety-related Seismic Class I equipment inthese classes at PBAPS Unit 3. Also, due to the significant number of modificationsperformed in the late 1990's as part of the USI A-46 (SQUG) and IPEEE programs,PBAPS Unit 3 has not made significant modifications to Seismic Class I equipmentwithin the last several years.

F.1.4 SEISMIC WALKDOWN

The on-site peer review of the seismic walkdowns was performed by Mr. Butler andMs. Schlaseman on August 30, 2012. The on-site and follow-up reviews includedapproximately 26% of the total SWCs and approximately 50% of the total AWCsapplicable to the equipment for Unit 3 and common, including checklists, photos, anddrawings where applicable. Interviews were conducted with both teams of SWEs toassess conduct of the walkdowns and adherence to the EPRI Seismic WalkdownGuidance (Reference 1). The discussion of the review of the sample of SeismicWalkdown Checklists (SWCs) and Area Walk-By Checklists (AWCs) is provided inSection 3.

The assessment of Issue Reports (IRs) with respect to current licensing basis isprovided in Sections 5 and 6 of the report. These assessments and their outcomes werealso discussed with the SWE inspection team in order to completely understand theissues.

Peach Bottom Atomic Power Station Unit 3 F-5MPR-3812, Revision 3Correspondence No.: RS-12-173

Page 143: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

F.2Peer Review - Selection of SSCs

F.2.1 PURPOSE

The purpose of this section is to describe the process to perform the peer review of theselected structures, systems, and components, (SSCs) that were included in the SeismicWalkdown Equipment List (SWEL).

F.2.2 PEER REVIEW ACTIVITY - SELECTION OF SSCs

The guidance in Section 3 of the EPRI Seismic Walkdown Guidance (Reference 1) wasused as the basis for this review.

This peer review of SWEL 1 was based on reviews of preliminary documents providedby the SWEL preparer, Mr. Benjamin Frazier. Additionally, the Peer Reviewers,Mr. Butler and Mr. Swanner, interviewed Mr. Frazier. Reference 1 Appendix F:"Checklist for Peer Review of SSC Selection," was used by the Peer Reviewers to guidetheir review.

For SWEL 1 development, the following actions were completed in the peer reviewprocess:

* Verification that the SSCs selected represented a diverse sample of the,equipment required to perform the following five safety functions:

o Reactor Reactivity Control

o Reactor Coolant Pressure Control

o Reactor Coolant Inventory Control

o Decay Heat Removal

o Containment Function

This peer review determined that the SSCs selected for the seismic walkdownsrepresent a diverse sample of equipment required to perform the five safety functions.

* Verification that the SSCs selected include an appropriate representation ofitems having the following sample selection attributes:

o Various types of systems

o Major new and replacement equipment (there are none)

o Various types of equipment

o Various environments

o Equipment enhanced based on the findings of the IPEEE (or USI A-46)

o Risk insight consideration

Peach Bottom Atomic Power Station Unit 3 F-6MPR-3812, Revision 3Correspondence No.: RS-12-173

Page 144: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

This peer review determined that the SSCs selected for the seismic walkdowns includean appropriate sample of items that represent each attribute/consideration identifiedabove. The justification for this conclusion is: a) Based on a review of the UFSAR andSWEL 1 list, it was determined that an appropriate variety of equipment and systems arerepresented (e.g., HPCI, RCIC, Core Spray, RHR, CRD Scram Hydraulic, High PressureService Water, Batteries); b) The SWEL identifies that there are no "New andReplacement" equipment; c) A variety of location environments are included (e.g., DieselRooms, Reactor Building, Drywell, Turbine Building, Screen House, Pump Structure); d)The SWEL identifies several items of equipment that were enhanced as a result ofIPEEE; and e) Risk Significant equipment items are identified on the SWEL. Additionaldetails for these conclusions are presented in Attachment 1: Peer Review Checklist forSWEL.

There are no SWEL 2 items for PBAPS Unit 3. To confirm the appropriateness of thisconclusion, the following actions were completed in the peer review process:

Verification that spent fuel pool (SFP) related Seismic Class I SSCs wereconsidered and appropriate justification was documented for why these itemswere not added to the SWEL 2.

This peer review determined that there are no spent fuel pool related items that areSeismic Class I.

Verification that the potential for rapid drain down of the SFP was consideredin accordance with the Reference 1 guidance, and appropriate justificationwas documented for no items being added to SWEL 2.

This peer review determined that appropriate consideration and justification wereprovided for there being no items identified that could result in rapid drain down. Thereare no SFP penetrations that could result in rapid draindown, and Fuel Pool Cooling andCleanup piping includes holes specifically intended to prevent siphoning and draindownof the spent fuel pool (See Section 4.3 of the Report as well as Attachment 1 to thisAppendix).

F.2.3 PEER REVIEW FINDINGS - SELECTION OF SSCs

This peer review found that the process for selecting SSCs that were added to theSWEL was consistent with the process outlined in Section 3 of Reference 1.

The Peer Review Checklist is attached to this document with additional observationsdocumented as appropriate. There were no comments or observations on the SWEL.This peer review resulted in no findings.

F.2.4 RESOLUTION OF PEER REVIEW COMMENTS - SELECTION OF SSCS

All comments requiring resolution were incorporated prior to completion of this peerreview.

Peach Bottom Atomic Power Station Unit 3 F-7MPR-3812, Revision 3Correspondence No.: RS-12-173

Page 145: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

F.2.5 CONCLUSION OF PEER REVIEW - SELECTION OF SSCs

This peer review concludes that the process for selecting SSCs to be included on theseismic walkdown equipment list appropriately followed the process outlined inReference 1, Section 3: Selection of SSCs. It is further concluded that the SWELsufficiently represents a broad population of plant Seismic Class I equipment andsystems to meet the objectives of the NRC 50.54(f) Letter.

-Vxe"-BUALPeer Reviewer: Date 10/15/2012

Peer Reviewer: Date 10/23/2012

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-8

Page 146: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

F.3Review of Sample Checklist & Area Walk-Bys

The on-site and follow-up peer reviews of the seismic walkdowns were performed forPBAPS Unit 3 by Mr. Patrick Butler, Ms. Caroline Schlaseman and Mr. Craig Swanner.The Peer Review Team reviewed Seismic Walkdown Checklists (SWC) and Area Walk-by Checklists (AWC) that were performed for Peach Bottom Unit 3 and Commonequipment, and interviewed the walkdown team members regarding details in checklists.

For Unit 3, there were two walkdown teams, which each consisted of two SeismicWalkdown Engineers (SWEs). The first team consisted of Mr. Benjamin Frazier and Mr.Mojtaba Oghbaei. The second team consisted of Mr. James Wiggin and Mr. KevinGantz. During the second week of walkdowns, Mr. Craig SwannerI replacedMr. Oghbaei.

Table F.3-1 lists the Peach Bottom Unit 3 and Common SWC and AWC sampling duringthe on-site and follow-up reviews. The SWCs and AWCs reviewed representapproximately 26% of the SWCs and approximately 50% of the AWCs applicable to thisequipment for Unit 3 and Common, which exceeds the EPRI Guidance (Reference 1)requirement of a 10% to 25% sample.

Table F.3-1. Table of SWC and AWC Samples from Seismic Walkdown

Equipment ID Description Equipment Class Location Observations(ApplicableArea Walkby)

3AC65 RPS Instrument (18) Instruments Reactor Building, No issues with the(AWC U3-7) Rack on Racks/Not on Room R3-40, El. SWC or AWC

Racks 165' applicable to thisequipment or itsconclusions wereidentified.

3AE55 RCIC Room (10) Air Handlers Reactor Building, No issues with the(AWC U3-12) Cooling Coil A Room R3-14, El. SWC orAWC

91' applicable to thisequipment or itsconclusions wereidentified.

1 Mr. Craig Swanner replaced Mr. Oghbaei on the first team for the second week of walkdowns. Ms. CarolineSchlaseman (in addition to Mr. Butler) served as the second peer reviewer for these SWCs and AWCs. Six SWCsand one AWC were prepared at the end of the second week by Mr. Ben Frazier and Ms. Schlaseman, who replacedMr. Swanner for one day. For these six SWCs and one AWC, Mr. Butler and Mr. Swanner served as the peerreviewers.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-9

Page 147: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Table F.3-1. Table of SWC and AWC Samples from Seismic Walkdown

Equipment ID Description Equipment Class Location Observations(ApplicableArea Walkby)

3AP037 Core Spray (06) Vertical Reactor Building, No issues with the(AWC U3-11) Pump A Pumps Room R3-9, El. 88' SWC or AWC

applicable to thisequipment or itsconclusions wereidentified.

3AV083 HPSW Pump (09) Fans Pump Structure, No issues with the(AWC U3-3) Room Exhaust Room P/H-9, El. SWC or AWC

Fan 112' applicable to thisequipment or itsconclusions wereidentified.

3BDO1 125 VDC (15) Batteries and Turbine Building, No issues with the(AWC U3-10) Battery 3B Racks Room T3-169, El. SWC or AWC

135' applicable to thisequipment or itsconclusions wereidentified.

3BE57 Core Spray (10) Air Handlers Reactor Building, No issues with the(AWC U3-11) Room A Cooling Room R3-9, El. 91' SWC or AWC

Coil B applicable to thisequipment or itsconclusions wereidentified.

3CD03 Battery Charger (16) Battery Turbine Building, No issues with the(AWC U3-9) 3C Chargers and Room T3-170, El. SWC or AWC

Inverters 135' applicable to thisequipment or itsconclusions wereidentified

30D043 HPCI Aux Lube (20) Control Reactor Building, No issues with the(AWC U3-8) Oil Pump Starter Panels and Room R3-13, El. SWC or AWC

Cabinets 88' applicable to thisequipment or itsconclusions wereidentified.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-1 0

Page 148: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Table F.3-1. Table of SWC and AWC Samples from Seismic Walkdown

Equipment ID Description Equipment Class Location Observations(ApplicableArea Walkby)

30X133 Panel 30Y33 (04) Transformers Turbine Building, No issues with the(AWC U3-5) Transformer T3-171, El. 135' SWC orAWC

applicable to thisequipment or itsconclusions wereidentified.

30C087 HPCI Instrument (18) Instruments Reactor Building, No issues with the(AWC U3-4) Rack on Racks Room R3-15, El. SWC orAWC

88' applicable to thisequipment or itsconclusions wereidentified.

M03-30-3233A Unit 3A Sluice (8A) Motor Screenhouse, No issues with the(AWC U3-25) Gate Operated Valves Room S/H-4, El. SWC or AWC

116' applicable to thisequipment or itsconclusions wereidentified.

H03-23C-5512 HPCI Turbine (07) Fluid Reactor Building, No issues with the(AWC U3-8) Governor (Air/Hyd) Valves Room R3-13, El. SWC or AWC

Control Valve 88' applicable to thisequipment or itsconclusions wereidentified.

RV3-23-034 HPCI Pump (07) Fluid Reactor Building, No issues with the(AWC U3-8) Suction Header (Air/Hyd) Valves Room R3-13, El. SWC or AWC

Relief Valve 88' applicable to thisequipment or itsconclusions wereidentified.

30B324 MO-3-23-015 (01) Motor Control Turbine Building, No issues with the(AWC U3-15) Motor Control Centers MG Set Room, El. SWC or AWC

Power Transfer 135' applicable to thisSwitch equipment or its

conclusions wereidentified.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.:- RS-12-173

F-11

Page 149: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Table F.3-1. Table of SWC and AWC Samples from Seismic Walkdown

Equipment ID Description Equipment Class Location Observations(ApplicableArea Walkby)

30B013 Emergency Aux (02) Low Voltage Reactor Building, No issues with the(AWC U3-24) Load Center Switchgear Room R3-41- El. SWC or AWC

E434 165' applicable to thisequipment or itsconclusions wereidentified.

30P033 & HPCI Booster (05) Horizontal Reactor Building, No issues with the30P038 Pump and HPCI Pumps Room R3-13, El. SWC orAWC(AWC U3-8) Pump 88' applicable to this

equipment or itsconclusions wereidentified.

30Y050 120V AC (14) Distribution Turbine Building, No issues with the(AWC U3-22) Distribution Panels Room T3-81, El. SWC or AWC

Panel 150' applicable to thisequipment or itsconclusions wereidentified.

0AV036 Battery Room (09) Fans Radwaste Building, No issues with the(AWC UO-10) Exhaust Fan A Room RIW-32, El. SWC or AWC

165' applicable to thisequipment or itsconclusions wereidentified.

0AP163 Emergency (05) Horizontal Diesel Generator No issues with the(AWC UO-1) Service Water Pump Building, Room SWC or AWC

Booster Pump A D/G-i, El. 121' applicable to thisequipment or itsconclusions wereidentified.

MO-0-33-0498 ESW Return to (08a) Motor Diesel Generator No issues with the(AWC U0-1) Discharge Pond Operated Valves Building, Room SWC orAWC

D/G-2, El. 121' applicable to thisequipment or itsconclusions wereidentified.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-1 2

Page 150: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Table F.3-1. Table of SWC and AWC Samples from Seismic Walkdown

Equipment ID Description Equipment Class Location Observations(ApplicableArea Walkby)

0AG012 El Standby (17) Engine Diesel Generator No issues with the(AWC UO-2) Diesel Generators Building, Room SWC or AWC

Generator D/G-3, El. 127' applicable to thisequipment or itsconclusions wereidentified.

OAP060 El D/G Fuel Oil (05) Horizontal Diesel Generator No issues with the(AWC UO-2) Transfer Pump Pumps Building, Room SWC or AWC

DIG-3, El. 127' applicable to thisequipment or itsconclusions wereidentified.

TCV-052E- D/G Jacket (07) Fluid Diesel Generator No issues with the7239A Water Coolant (Air/Hyd) Valves Building, Room SWC or AWC(AWC U0-2) 3-Way D/G-3, El. 127' applicable to this

Thermostatic equipment or itsControl Valves conclusions were

identified.

0AC097 Diesel (20) Control Diesel Generator No issues with the(AWC U0-2) Generator Panels & Cabinets Building, Room SWC orAWC

OAG12 Control D/G-3, El. 127- applicable to thisPanel equipment or its

conclusions wereidentified.

0AT096 El Diesel (21) Horizontal Diesel Generator No issues with the(AWC UO-2) Generator Lube Tanks or Heat Building, Room SWC or AWC

Oil Storage Exchangers D/G-3, El. 127' applicable to thisTank equipment or its

conclusions wereidentified.

0BK032 Emergency (09) Fans Emergency Cooling No issues with the(AWC U0-3) Cooling Tower Towers, Room SWC or AWC

Fan B ECT-6, El. 195' applicable to thisequipment or itsconclusions wereidentified.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-13

Page 151: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Table F.3-1. Table of SWC and AWC Samples from Seismic Walkdown

Equipment ID Description Equipment Class Location Observations(ApplicableArea Walkby)

MO-48-0501A ESW A Inlet to (08a) Motor Emergency Cooling No issues with the(AWC U0-4) ECT Reservoir Operated Valves Towers, Room SWC or AWC

ECT-1, El. 114' applicable to thisequipment or itsconclusions wereidentified.

SV3-3-33 Instrument Air (8b) Solenoid Reactor Building, No issues with the(AWC U3-13) Solenoid Valve Operated Valves Room R3-22, El. SWC or AWC

135' applicable to thisequipment or itsconclusions wereidentified.

-VaAt'ý& -DUALPeer Reviewer: Date 10/15/2012

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-14

Page 152: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

F.4Review of Licensing Basis Evaluations

There were no instances identified during the walkdowns where evaluated componentscould not readily be shown to meet the plant seismic licensing basis. Accordingly, nolicensing basis evaluations to determine if equipment complied with current seismiclicensing basis requirements were required. However, there were some anomalies orconditions adverse to quality identified during the walkdowns. Tables 5-2 and 5-3 in themain body of the report provide a list of the anomalies encountered during the Unit 3seismic walkdown inspections and how they were addressed.

j24~WbuAPeer Reviewer: Date 10/15/2012

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-15

Page 153: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

F.5References

1. EPRI Technical Report 1025286, Seismic Walkdown Guidance for Resolution ofFukushima Near-Term Task Force Recommendation 2.3: Seismic, dated June2012.

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-16

Page 154: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Attachment 1: Peer Review Checklist for SWEL

Peer Review Checklist for SWEL - Peach Bottom Atomic Power Station Unit 3

Instructions for Completing Checklist

This peer review checklist may be used to document the review of the Seismic WalkdownEquipment List (SWEL) in accordance with Section 6: Peer Review. The space below each questionin this checklist should be used to describe any findings identified during the peer review processand how the SWEL may have changed to address those findings. Additional space is provided at theend of this checklist for documenting other comments.

1. Were the five safety functions adequately represented in the SWEL 1 selection? YE NEiAll five safety functions were included in the SWEL Selection.

2. Does SWEL 1 include an appropriate representation of items having the following sampleselection attributes:

a. Various types of systems? YO NEA wide variety of systems were represented including Residual Heat Removal,Reactor Core Isolation Cooling, Core Spray, High Pressure Coolant Injection,Control Drive Hydraulic, High Pressure Service Water, 125 VDC, 120 VAC, 480VA C.

b. Major new and replacement equipment? YE N[lDue to the significant number of modifications performed in the late 1990's as partof the USI A-46 (SQUG) and IPEEE programs, PBAPS Unit 3 has not madesignificant modifications to Seismic Class I equipment within the last several years.Accordingly, SWEL I does not identify any new or replacement components.

c. Various types of equipment? YE NE]All of the EPRI equipment classes are represented with the exception of Classes#11 Chillers, #12 Air Compressors, and #13 Motor Generators. No Seismic Class Iequipment in these three classes were identified at PBAPS Unit 3.

d. Various environments? YED NREquipment in various environments including the Reactor Building, ControlStructure, Screen House, Pump Structure, Turbine Building, Diesel GeneratorBuilding and Drywell are included.

e. Equipment enhanced based on the findings of the IPEEE (or equivalent) YE NEIprogram?The Unit 3 SWEL includes a sample of equipment items that were enhanced basedon findings of the USI A-46 (SQUG) and IPEEE programs (see Sections 4.2 and 7of the Report).

Peach Bottom Atomic Power Station Unit 3 F-1 7MPR-3812, Revision 3Correspondence No.: RS-12-173

Page 155: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Peer Review Checklist for SWEL - Peach Bottom Atomic Power Station Unit 3

f. Were risk insights considered in the development of SWEL 1? YE NEIThe plant Probabilistic Risk Assessment (PRA) was reviewed and used to guideselection of the components on SWEL 1. Specifically, the relative risk significanceof candidate components including the Risk Achievement Worth (RAW) andFussell-Vesely importance for a Loss of Off-Site Power (LOOP) scenario from theinternal plant PRA were used (See Section 4.2 of the report).

3. For SWEL 2:

a. Were spent fuel pool related items considered, and if applicable included in Y[Z NEISWEL 2?Both parts of SWEL 2, assessment of Seismic Class I spent fuel pool (SFP) relatedequipment and equipment that could potentially result in rapid drain-down of theSFP were considered. There is no equipment in either category. Seedocumentation of SFP item review in Section 4.3 of the Report.

b. Was an appropriate justification documented for spent fuel pool related items YZ NEInot included in SWEL 2?As noted in Section 4.3 of the report, there is no Seismic Class I spent fuel poolrelated equipment.

Section 4.3 also includes appropriate justification that there are no items ofequipment that could cause rapid drain-down due to lack of penetrations withinabout 10 feet above the top of the fuel racks, and there are adequate anti-syphonfeatures included in piping that terminate within a few feet of the tops of the fuelracks.

4. Provide any other comments related to the peer review of the SWELs.

The Peer Review team had no comments on the SWEL.

5. Have all peer review comments been adequately addressed in the final SWEL? YO NEI

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-1 8

Page 156: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

Peer Review Checklist for SWEL - Peach Bottom Atomic Power Station Unit 3

Peer Reviewer#1:

Peer Reviewer#2:

Patrick Butler, P.E.

2Cf. "I•Uk 4 L Date: 10/15/2012

Craig Swanner, P.E.

4,9- Date: 10/23/2012

Peach Bottom Atomic Power Station Unit 3MPR-3812, Revision 3Correspondence No.: RS-12-173

F-1 9

Page 157: Peach Bottom, Unit 3, Report No. MPR-3812, Rev. 3, Seismic ...Design Processes I Units Formulas I Math.j Download sae j 1926. Download sae j 1926 SAE International Standards - webstore.ansi~org

U.S. Nuclear Regulatory Commission180-Day Response to 50.54(f) LetterNTTF Recommendation 2.3: SeismicNovember 19, 2012Page 7

Enclosure 3

SUMMARY OF REGULATORY COMMITMENTS

The following table identifies commitments made in this document. (Any other actionsdiscussed in the submittal represent intended or planned actions. They are described to theNRC for the NRC's information and are not regulatory commitments.)

COMMITTED COMMITMENT TYPECOMMITMENT DATE OR ONE-TIME ACTION PROGRAMMATIC

'OUTAGE' (Yes/No) (Yes/No)

1. Exelon Generation Company, LLC (EGC) will 3Q2013 Yes Nocomplete the walkdown of the one (1) (September 30,PBAPS Unit 2 item deferred due to 2013)inaccessibility.

2. EGC will complete the supplemental May 31, 2015 Yes Noinspections of the three (3) PBAPS Unit 2electrical items identified in Tables E-2 andE-3. _

3. EGC will complete the walkdown of the P3R19 Yes Nothirteen (13) PBAPS Unit 3 items deferred Fall 2013due to inaccessibility.

4. EGC will complete the supplemental May 31, 2015 Yes Noinspections of the six (6) PBAPS Unit 3electrical items identified in Tables E-2 andE-3.