Equipment Short-Circuit Current Rating and...
Transcript of Equipment Short-Circuit Current Rating and...
8/27/2013
1
© 2013 Eaton. All rights reserved.
Equipment Short-Circuit Current Rating and Available Fault Current
Dan Neeser – Field Application Engineer
Eaton’s Bussmann Business
2© 2013 Eaton. All rights reserved.
Agenda
• Interrupting Rating & Series Rating
• Short-Circuit Current Ratings
• Maximum Fault Current Marking
• Fault Current Calculations
• UL 508A – Industrial Control Panels
Supplement SB - SCCR
8/27/2013
2
3© 2013 Eaton. All rights reserved.
Interrupting Rating
• NEC® Article 100 Definition• Highest current an OVERCURRENT DEVICE
(fuse or circuit breaker) is rated to safely interrupt.
• Self protection rating only
• NEC® 110.9 Interrupting Rating. • Requires the overcurrent device to have an
interrupting rating not less than the maximum available fault current.
• The maximum fault current must be calculated and varies based on system size/location.
• Similar Requirements in OSHA 1910.303(b)(4)
4© 2013 Eaton. All rights reserved.
Interrupting Rating
• NEC 110.9: Device interrupting rating MUST be equal to or greater than the maximum available fault current.
• Chapter 1 Video Clips - Interrupting Rating
8/27/2013
3
5© 2013 Eaton. All rights reserved.
1st
Determine available short-circuit current (Isca) at lineside
terminals of each OCPD.
2nd
Apply OCPDs with adequate Interrupting Rating.
Isca 3
MM
MSB
Isca 1
Isca 4 Isca 5
Isca 6
Isca 2
Interrupting Rating - Proper Application
6© 2013 Eaton. All rights reserved.
Must select circuit breaker with interrupting rating adequate for point of application – varies by voltage and circuit breaker type.
Interrupting Rating - Proper Application
8/27/2013
4
7© 2013 Eaton. All rights reserved.
High Interrupting rating of current-limiting fuses at full voltage reduces concerns about proper interrupting rating at point of application
I.R. - Proper Application
8© 2013 Eaton. All rights reserved.
A combination of: - Circuit breakers / circuit breakers
OR- Fuses / circuit breakers …
that can be applied at available fault levels above the interrupting rating of the load side circuit breaker, but not above that of the main
or line side device.
Downstream device will ALWAYS be a circuit breaker
Series Rated Systems
8/27/2013
5
9© 2013 Eaton. All rights reserved.
Series Rated
Combination
65,000 A.I.R.200A Circuit Breaker
65,000 A.I.R.
ISC=65,000 A
20A Circuit Breaker
ISC=65,000 A
10,000 A.I.R.
Series Rated Systems: CB-CB
10© 2013 Eaton. All rights reserved.
Series Rated
Combination
200,000 A.I.R.
ISC=200,000 A
20A Circuit Breaker
ISC=300,000 A
10,000 A.I.R.
Series Rated Systems: Fuse-CB
LPJ 400 SP
300,000 A.I.R.
8/27/2013
6
11© 2013 Eaton. All rights reserved.
Series Rated Systems
• NEC® 240.86(A) Selected Under Engineering Supervision in Existing Installations• The series rated combination devices must be selected
by licensed, professional engineer. • Requires Documentation and Stamp. • Series combination rating and upstream device must be
field marked on end use equipment. • Downstream circuit breaker must remain passive.
• NEC® 240.86(B) Tested Combinations• The combination of line side and load side devices must
be tested and marked on the end-use equipment (panelboards & switchboards).
12© 2013 Eaton. All rights reserved.
Series Rated Systems
• Additional Limitations and Requirements
• Labeling Requirements
• Manufacturer – NEC® 240.86(B)
• Field Marking – NEC® 110.22(B)&(C)
• Motor Contribution Limitations
• NEC 240.86(C)
• Motor FLA cannot exceed 1% of IR of protected CB.
• Lack of Selective Coordination
8/27/2013
7
13© 2013 Eaton. All rights reserved.
Current Limitation
• A current limiting fuse will clear a fault within one half of a cycle.• Thermal energy is
proportionate to the square of “RMS” current multiplied by the time (Irms2t)
• Mechanical stresses are proportionate to the square of “peak” current multiplied by the time (Ip2t)
14© 2013 Eaton. All rights reserved.
Current Limitation
• Conductor protection for fault of 45kA/480V (26kA with conductor) with non-current-limiting device (1 cycle) vs. current-limiting device (>1/2 cycle)
8/27/2013
8
15© 2013 Eaton. All rights reserved.
Short-Circuit Current Ratings
• NEC® Article 100 Definition• The highest current EQUIPMENT can withstand without extensive
damage (fire or shock hazard).
• Also known as component protection
• May be based on a specific type of overcurrent device
• NEC® 110.10 Circuit Impedance, Short-Circuit Current Ratings, and Other Characteristics.
• Requires the equipment to have a short circuit current rating not less than the maximum available fault current.
• The maximum fault current must be calculated and varies based on system size/location.
• Similar Requirements in OSHA 1910.303(b)(5)
16© 2013 Eaton. All rights reserved.
Motor Starter - SCCR
• High Fault Test: starter protected by an instantaneous trip circuit breaker (MCP) that only provides Type 1 protection
• High Fault Test: starter protected by Low-Peak® fuses that provides Type 2 (No Damage) protection
Fault
480V - 22,000A
Fault
480V - 22,000A
8/27/2013
9
17© 2013 Eaton. All rights reserved.
• 430.8 – Marked on motor controllers• 440.4(B) – Marked on HVAC equipment• 409.110(3) – Marked on industrial control panels
• 409.22 – Fault current cannot exceed marked SCCR
• 670.3(A)(4) – Marked on industrial machinery control panel• 670.5 – Fault current cannot exceed marked SCCR
• UL 508A, Supplement SB is an approved method to determine SCCR for industrial control panels and industrial machinery control panels
SCCR Marking Requirements
18© 2013 Eaton. All rights reserved.
Fault Current Marking Requirement
• 110.24 Available Fault Current.
• (A) Service equipment must be marked with
the maximum available fault current and
date of calculation
• (B) If fault current increases due to system
modification, the marking must be updated.
8/27/2013
10
19© 2013 Eaton. All rights reserved.
How to Comply?
Service Equipment
Isc = 60,142 A
Isc = 27,532 AIsc = 42,153 A
Max Avail. Fault Current = 58,524 A
Date Determined/Calculated: 9/2010
Isc = 18,752 AIsc = 38,525 A
Required per NEC 110.24
Motor ControllerSCCR = 25kA
Industrial Control PanelSCCR = 30kA
Industrial Machinery PanelSCCR = 65kA
HVACSCCR = 40kA
All equipment must comply with: NEC 110.9 (IR) &110.10 (SCCR)
Engineer – Calculate
Contractor – Label
20© 2013 Eaton. All rights reserved.
IR/SCCR Inspection Check-List
8/27/2013
11
21© 2013 Eaton. All rights reserved.
Fault Current Calculations
• To determine the fault current:• Draw the one-line diagram
• Identify sources of short-circuit current (utility, generation, motors)
• Include system component information (tranformers, conductors, busway, overcurrent devices are not considered)
• Use calculation method (ohmic, per unit, point-to-point, software)
• Use “typical” fault current values as a reference only.
22© 2013 Eaton. All rights reserved.
Typical Short-Circuit Current Values
• Short-Circuit Current at service entrance equipment varies by type/size of system:• Small residential systems (100A to 200A) – 10,000A to
15,000A or less• Small commercial building systems (400A to 800A) –
20,000A to 30,000A• Larger commercial and manufacturing building systems
(2,000A to 3,000A) - 50,000A to 65,000A• Higher short-circuit currents are possible where low
impedance (energy-efficient) transformers are used (or where larger transformers (kVA) feed multiple services.
• Commercial buildings directly connected to utility “grid system” – 200,000A or greater
8/27/2013
12
23© 2013 Eaton. All rights reserved.
Short-Circuit Current Factors
• Typically highest at service point
• Decreases in downstream equipment (due to impedance of transformers and conductors)
24© 2013 Eaton. All rights reserved.
Calculation Example
• 480V/3000A Service supplied from 2500 kVA Transformer
• Find Isc at Transformer Secondary & Service Equipment
480V, 3000A Service EquipmentService Transformer
2500 kVA
13.2kV – 480V
5% Impedance
7 – 600 Cu kcmil/phase
25 Feet in PVC
Isc = 60,142 A
Isc = 58,524A
8/27/2013
13
25© 2013 Eaton. All rights reserved.
IFLA =KVA X 1000
EL-L X 1.732
KVA = KVA of Transformer
EL-L = Secondary Phase to Phase voltage
Calculation Example
• Step One: Calculate Secondary FLA of Transformer (3 phase)
26© 2013 Eaton. All rights reserved.
2500 KVA Transformer
13.2kV - 480V, 3 Phase
Z = 5%
ISC
IFLA =2500 X 1000
480 X 1.732
IFLA = 3007 A
Calculation Example
8/27/2013
14
27© 2013 Eaton. All rights reserved.
Mult =100
% Z
Mult =100
5
Mult = 20
Calculation Example
• Step Two: Calculate Multiplier• Z = Impedance of Transformer, refer to transformer
nameplate or manufacturer data
28© 2013 Eaton. All rights reserved.
ISC = IFLA X Mult
ISC = 3007 X 20
ISC = 60,140 A
Calculation Example
• Step Three: Calculate Secondary Short Circuit Current
8/27/2013
15
29© 2013 Eaton. All rights reserved.
480V
Switchgear
7 – 600 Cu kcmil/phase
25 Feet in PVCISC = 60,140A
Calculation Example
• Calculate Short Circuit Current at 480V Switchgear
30© 2013 Eaton. All rights reserved.
ISC 480V SWGR = ISC X Mult
Calculation Example
• Isc known from previous calculation• Calculate multiplier for Cable
• Step One: Calculate f value
8/27/2013
16
31© 2013 Eaton. All rights reserved.
f =1.732 X L X ISC
C X EL-L
L = Length of conductor
ISC = Short-circuit current at beginning of circuit
C = “C” Value Constant for Cable
From Table. Multiply by # of runs
EL-L = Phase to Phase Voltage
Calculation Example
• Step One: Calculate f value
32© 2013 Eaton. All rights reserved.
Calculation Example
• C Value – 600 kcmil, CU, PVC = 28,033
8/27/2013
17
33© 2013 Eaton. All rights reserved.
f =1.732 X 25 X 60,140
7 X 28,033 X 480= 0.0276
Calculation Example
• Step One: Calculate f Value• L = 25 Feet
• ISC = 60,140 A
• C = 7 X 28,033 - See “C” Value Table
• EL-L = 480V
34© 2013 Eaton. All rights reserved.
Mult =1
1 + f
• Step Two: Use Calculated f Value• Calculate Multiplier
Calculation Example
Mult = = 0.97311
1 + 0.0276
8/27/2013
18
35© 2013 Eaton. All rights reserved.
ISC 480V SWGR = ISC X Mult
ISC 480V SWGR = 60,140 X .9731
ISC 480V SWGR = 58,522 A*
* Add motor contribution if present
Calculation Example
• Calculate Short Circuit Current at 480V Switchgear
36© 2013 Eaton. All rights reserved.
What if the System Changes?
480V, 4000A Service EquipmentService Transformer
3000 kVA
13.2kV – 480V
5% Impedance
9 – 600 Cu kcmil/phase
25 Feet in PVC
Isc = 72,171 A
Isc = 70,587A
480V, 3000A Service EquipmentService Transformer
2500 kVA
13.2kV – 480V
4% Impedance
7 – 600 Cu kcmil/phase
25 Feet in PVC
Isc = 75,178 A
Isc = 72,667A
8/27/2013
19
37© 2013 Eaton. All rights reserved.
Cooper Bussmann Short-Circuit Calculator
• New version• Apple or Android Apps
• Web (run from homepage)
• Old version• Download for Window XP
38© 2013 Eaton. All rights reserved.
• Choose three phase or single phase system
Calculating available fault current and creating 110.24 labels has never been easier!
1 2 3
• Click on Add to my
System
• Select a component
you want to add
Create a System
8/27/2013
20
39© 2013 Eaton. All rights reserved.
• Select Add Transformer
Calculating available fault current and creating 110.24 labels has never been easier!
1 2 3
• If you have a known primary fault
current you can add it here. If not,
select assume infinite
• Enter values into the appropriate fields
Add a Transformer
40© 2013 Eaton. All rights reserved.
• After adding a Transformer,
you will be asked if you want
to add motor contribution
Calculating available fault current and creating 110.24 labels has never been easier!
1 2 3
• You can complete a quick calculation
by selecting a % of your
transformer’s FLA or add it manually
• Add these calculations to your
system
Add Motor Contribution
8/27/2013
21
41© 2013 Eaton. All rights reserved.
• Select Add To My System
Calculating available fault current and creating 110.24 labels has never been easier!
1 2 3
• Add Conductor Run or Buss Run
• Add the correct values and Add To System
Add Other Components
42© 2013 Eaton. All rights reserved.
• View system one‐line
diagram
Calculating available fault current and creating 110.24 labels has never been easier!
1 2 3
• Email one‐line
diagram
• Select a specific fault to create a label
System Summary
8/27/2013
22
43© 2013 Eaton. All rights reserved.
• Select a fault and click on Create Label
Calculating available fault current and creating 110.24 labels has never been easier!
1 2
• Enter the email address, project name,
fault name, and label size, then Send Label
Create a Label
44© 2013 Eaton. All rights reserved.
• Tap on Fuse Sizing Diagram
Sizing fuses for mains, feeders, and branch circuits has never been easier!
1 2 3
• Tap on the circuit to protect
• Review each section and the fuse suggestions for the selected location
Fuse Sizing
8/27/2013
23
45© 2013 Eaton. All rights reserved.
Calculating available fault current and creating 110.24 labels has never been easier!
• The User guide provides useful
information about FC2
• There is a user guide selection at the bottom
if each page
• Based on where you are in the app, you will
be provided a specific
overview of FC2’s
functionality
• While the FC2 is very
intuitive, there may be
additional questions
• There is a Contact Us selection at the
bottom of each page
• From this location,
you can select to send
an email for technical
assistance or
customer service
support
User Guide & Contact Us
46© 2013 Eaton. All rights reserved.
Cooper Bussmann FC2 Web Version - Example
8/27/2013
24
47© 2013 Eaton. All rights reserved.
How to Determine SCCR?
• Short-Circuit Current Rating (SCCR)• Can be established by testing during the listing
and labeling process
OR
• Can be determined using an approved (calculation) method
• UL 508A Supplement SB is an approved method (industrial control panels and industrial machinery control panel)
• AHJ Approved Method
• NRTL field evaluation can also be used.
48© 2013 Eaton. All rights reserved.
Industrial Control Panel SCCR
• Industrial Control Panel. An assembly of two or more components consisting of one of the following:
1)power circuit components only, such as motor controllers, overload relays, fused disconnect switches, and circuit breakers;
2)control circuit components only, such as push buttons, pilot lights, selector switches, timers, switches, and control relays;
3)a combination of power and control circuit components. These components, with associated wiring and terminals, are mounted on, or contained within, an enclosure or mounted on a subpanel.
The industrial control panel does not include the controlled equipment.
48
8/27/2013
25
49© 2013 Eaton. All rights reserved.
UL 508A Supplement SB
• What Needs to be Analyzed per UL 508A, Supplement SB?• All power circuit components (SB 4.1)
• Feeder and branch circuit components that supply power to loads (motors, lighting, heating and appliances)
• Includes disconnect switches, fuses, circuit breakers, load controllers, overload relays, power distribution/terminal blocks, bus bars, etc.
• Control circuit components are not required to be analyzed
• Pushbuttons, pilot lights, selector switches, timers, control relays, etc.
50© 2013 Eaton. All rights reserved.
Power vs. Control Circuits
Control circuit components don’t have to be analyzed
Power Transformer
Control Transformer
*
*Control Circuit, but affects SCCR
8/27/2013
26
51© 2013 Eaton. All rights reserved.
UL 508A Supplement SB
• How to Determine Component SCCR (SB4.2.2)?• The SCCR marked on the component or on instructions.• The SCCR determined by the voltage rating of the
component and the assumed short circuit current from Table SB4.1.
• or• The SCCR for a load controller, motor overload relay, or
combination motor controller that has been investigated in accordance with the performance requirements, including short circuit test requirements for standard fault currents or high fault currents specified in the Standard for Industrial Control Equipment, UL 508, and described in the manufacturer’s procedure.
52© 2013 Eaton. All rights reserved.
UL 508A Supplement SB
• What are the Rules (Sweep 1)?
• Lowest component SCCR limits assembly SCCR unless:
• Combination ratings can be used to increase branch circuit component ratings (SB 4.2.2)
• Component with marked/specified OCPD
• Check with component manufacturer for combination ratings
8/27/2013
27
53© 2013 Eaton. All rights reserved.
Combination Ratings - Branch
• Use combination ratings with specified/marked OCPD to fix low rated branch components
Component SCCR OCPD I.R.
Combination ratings of overcurrent protective devices and components can be used
Nameplate
480
SCCR:
Voltage:
100kA
54© 2013 Eaton. All rights reserved.
Combination Ratings - Contactor
8/27/2013
28
55© 2013 Eaton. All rights reserved.
Combination Ratings - MMP
• OL Protection Only
• Fuse or Circuit Breaker Required for SC Protection
• Suitable for Group Installations
• Straight Ratings (480V)
56© 2013 Eaton. All rights reserved.
Combination Ratings – Type E/F
• Combination Motor Controller
• SC & OL Protection
• Line Side Adapters Required
• Slash Ratings (480/277V)
8/27/2013
29
57© 2013 Eaton. All rights reserved.
Combination Ratings - ASD
• 200kA with Class CC/J/T Fuse
• Suitable for Group Installations
• 65kA with Type E CMC (480/277V)
58© 2013 Eaton. All rights reserved.
Combination Ratings - Feeder
• Use UL Listed power distribution block with high SCCR when used with specified fuses or circuit breakers and required load side conductors
• Must have feeder circuit spacing (Listed PDB) if in feeder circuit
Nameplate
480
SCCR:
Voltage:
100kA
Component SCCR OCPD I.R.
Combination ratings of PDBs is cost effective fix
8/27/2013
30
59© 2013 Eaton. All rights reserved.59
Combination Ratings - PDBs
PDBFS220 (4 – 14 Load Side Conductors) – 100kA with 175A Class J fuse or less
60© 2013 Eaton. All rights reserved.
UL 508A Supplement SB
• What are the Rules (Sweep 1)?
• Lowest component SCCR limits assembly
SCCR unless:
• Feeder components are used that limit the short-
circuit current reducing the need for higher branch
circuit component SCCR (SB 4.3)
• Current limiting overcurrent protective devices
• Transformers rated 10kVA or less
8/27/2013
31
61© 2013 Eaton. All rights reserved.
Feeder Circuit
Branch Circuit
Branch Circuit
Feeder vs. Branch Circuits
62© 2013 Eaton. All rights reserved.
Use of CL Devices - OCPD
• CL Device must be in the feeder circuit• For CL Fuses or Circuit Breakers
• Use PEAK Let-through, Not RMS Let-Through (more conservative)
• Fuses - cannot use manufacturer specific fuse data –only tables based on performance requirements from UL 248 (more conservative - apply to all manufacturers)
• Circuit Breakers - must be Listed and marked “current-limiting” and use published let-thru curves (most circuit breakers are not CL)
• Can only raise downstream BRANCH circuit components (not overcurrent protective devices –fuses/circuit breaker IR or Combination motor controllers SCCR)
8/27/2013
32
63© 2013 Eaton. All rights reserved.
Fuse LT – UL vs Manufacturer
• LPJ-100SP
• UL Limits• 50kA = 12kA• 100kA = 14kA• 200kA = 20kA
• Manufacturer Let Through Curves• Ip LT:
• 50kA = 9kA• 100kA = 12kA• 200kA = 14kA
• Irms LT:• 50kA = 4kA• 100kA = 5kA• 200kA = 6kA
64© 2013 Eaton. All rights reserved.
• Current limiting feeder OCPD can be used to increase branchcomponent SCCR.
Component SCCR OCPD I.R.
Use of CL OCPD can only fix components
F
B
Use of CL Devices - OCPD
Nameplate
480
SCCR:
Voltage:
14kA
8/27/2013
33
65© 2013 Eaton. All rights reserved.
Use of CL Devices - Transformers
• CL Device must be in the feeder circuit
• For Transformers• If 10kVA with secondary devices (components and
overcurrent devices) of 5kA or higher, apply the IR of the primary overcurrent protective device
• If 5kVA (120V Secondary) with secondary devices (Components and overcurrent devices) of 2kA or higher, apply the IR of the primary overcurrent protective device
66© 2013 Eaton. All rights reserved.
Component SCCR OCPD I.R.
10 kVA
Use of CL Devices - Transformers
• Transformers can be used to limit the short-circuit current available• If 10kVA & sec comp = 5kA+• If 5kVA/120V & sec comp = 2kA+• Then assign entire circuit I.R. of
primary overcurrent device
Use of Small Transformers (10kVA or less) can increase secondary component/OCPD ratings
Nameplate
480
SCCR:
Voltage:
200kA
8/27/2013
34
67© 2013 Eaton. All rights reserved.
UL 508A Supplement SB
• What are the Rules (Sweep 2)?• Lowest overcurrent protective device interrupting
rating (or SCCR for some devices) always limits assembly SCCR
• All Feeder and branch circuit overcurrent devices
• Tested series combination ratings or series ratings (fuse-circuit breaker or circuit breaker-circuit breaker) are NOT allowed.
• Branch circuit overcurrent devices tapped from the feeder circuit supplying a control circuit.
• Supplemental protective devices protecting the control circuit transformer in a motor branch circuit.
68© 2013 Eaton. All rights reserved.
Overcurrent Protection Devices
• Branch Circuit Protective Devices• Fuses
• Circuit Breakers
• Application Limited Devices
• Supplemental Protectors/Fuses• Not suitable for branch circuit
protection (protecting a load)
• Can only be used in control circuits
8/27/2013
35
69© 2013 Eaton. All rights reserved.
Why High SCCR?
• NEC & Equipment standards only require the SCCR to be marked
• NEC requires the marked value to be adequate for the maximum available fault current
• Although not required, high SCCR is often preferred• Flexibility of application
• Multiple installations
• Fault current unknown
• Insufficient SCCR can delay installation
70© 2013 Eaton. All rights reserved.
Fix It - Solutions
• High I.R. Protective Devices• Class R
• Class J
• Class J Drive Fuse
• Class T
• Class CC
• CubeFuse
• High Speed
• High IR/CL CBs
8/27/2013
36
71© 2013 Eaton. All rights reserved.
Fix It - Solutions
• High SCCR Components
© 2013 Eaton. All rights reserved.
Questions?