PD30-E - b2hv · The PD diagnosis on medium and high voltage cable offers the possibility of early...

4
www.b2hv.at Features • Compact, light and portable devices • Small, light and portable units • b2 Suite ® - comprehensive diagnostic software and database • Very simple and clear measurement process • Manual and automatic diagnostic mode • Exact PD localization (PD mapping) • Phase-resolved PD display (PD Pattern) • PD Magnitude • PD inseption and extinction • PD rate • High noise suppression by filtering • Extensive reporting • Test setup according to IEC 60270 and calibration • PD measurement unit in battery operation • Extendable with Tan Delta Diagnostics (optional) The b2 electronic GmbH PDTD60-2 Partial Discharge (PD) and Tan Delta (TD) Diagnosis System for diagnosis of medium voltage cables, rotating machinery and transformers. Partial Discharge and extendable with Tan Delta Diagnostics (optional) • Diagnostics according IEEE.2-2013 and IEC 60270 Very powerful high voltage generators (optional) for very long cables. The PD diagnosis on medium and high voltage cable offers the possibility of early detection of vulnerabilities through a precise localization of PD faults in cables and their connections (joints and terminations), often caused by mechanical damage or a faulty installation process. PD30-E Partial Discharge Diagnostics System VLF DIAGNOSTICS SYSTEM

Transcript of PD30-E - b2hv · The PD diagnosis on medium and high voltage cable offers the possibility of early...

Page 1: PD30-E - b2hv · The PD diagnosis on medium and high voltage cable offers the possibility of early detection of vulnerabilities through a precise localization of PD faults in cables

www.b2hv.atFeatures

• Compact, light and portable devices • Small, light and portable units• b2 Suite® - comprehensive diagnostic software and database• Very simple and clear measurement process• Manual and automatic diagnostic mode• Exact PD localization (PD mapping)• Phase-resolved PD display (PD Pattern)• PD Magnitude• PD inseption and extinction

• PD rate• High noise suppression by filtering• Extensive reporting• Test setup according to IEC 60270 and calibration• PD measurement unit in battery operation• Extendable with Tan Delta Diagnostics (optional)

The b2 electronic GmbH PDTD60-2 Partial Discharge (PD) and Tan Delta (TD) Diagnosis System for diagnosis of medium voltage cables, rotating

machinery and transformers.

• Partial Discharge and extendable with Tan Delta Diagnostics (optional)

• Diagnostics according IEEE.2-2013 and IEC 60270

• Very powerful high voltage generators (optional) for very long cables.

The PD diagnosis on medium and high voltage cable offers the possibility of early detection of vulnerabilities through a precise localization of PD

faults in cables and their connections (joints and terminations), often caused by mechanical damage or a faulty installation process.

PD30-EPartial Discharge Diagnostics System VLFDIAGNOSTICS SYSTEM

Page 2: PD30-E - b2hv · The PD diagnosis on medium and high voltage cable offers the possibility of early detection of vulnerabilities through a precise localization of PD faults in cables

Compact, lightweight and portable solutions

From small portable units for on-site use (e.g. off-shore) to built-in solutions for „test van“ versions.

b2 Suite® software

b2 Suite® provides a comprehensive „all-in-one“ software solution for testing, dia-gnosis and management with a compre-hensive database.

Automatic Mode

In addition to the manual, incremental, and self-explanatory menu, the system also offers an automatic measurement mode.

PD30-EPartial Discharge Diagnostics System

• The only IEEE 400.2-2013 described VLF voltage shape (sinus) for PD and TD Diagnostics (optional)

• PD mapping - precise localization of partial discharge

• TE-phase resolution (PD pattern) to categorize type of fault

• Inception and extinction voltage

• Load-independent frequency

b2 electronic diagnostics system PD30E (combined with VLF generator1) provides a pure sinusoidal output voltage with stable

frequencies. This is a pre-condition of direct comparison of PD and TD diagnostics results across cables of different lengths. The

characteristics at ever-changing frequencies and varying output voltage waveforms provide no basis for reliable comparisons.

Pure sinusoidal output voltage is recommended by standards (such as IEEE400.2-2013) and therefore clear guidelines and

test procedures are provided.

The comprehensive control and diagnostics software b2 Suite® makes the process of diagnostics easy as never before, guiding

the operator step by step through the entire process. The b2 Suite® Data Base allows your data to be processed, stored and

made available for future reference in just a few clicks.

1 VLF (0.1 Hz) high voltage generator (required) with integrated Tan Delta Diagnostics (option) is not

in scope of delivery.

Page 3: PD30-E - b2hv · The PD diagnosis on medium and high voltage cable offers the possibility of early detection of vulnerabilities through a precise localization of PD faults in cables

Database

Comprehensive b2 Suite® database enab-les easy analysis and evaluation of the PD measurement. A fast search function for archived measurements and easy repro-ducibility of a measurement are among the key features.

Reporting

Reporting by a mouse click – simple or comprehensive. Individual design for reporting and easy integration of data and files.

Algorithms for detection of PD activities

The b2 Suite® distinguishes between valid and invalid PD signals, and then separates them.This facilitates easy interpretation of results for the user.

b2 Suite®Diagnostics and Data Base Software

• Automatic or manual modes for testing and

PD diagnostics

• Guided Diagnostics Process - leads the

operator through diagnostics step by

step

• Automatic & manual gain and trigger setting

• Comprehensive Data Base

• Sets or recommends measuring parameters

• Reporting by a mouse-click

• Recommended by Standards (CENELEC & IEEE),

with guidance for interpretation in literature

• Precise location of PD events on cable insu-

lation, terminations and joints

• Algorithms for PD detection

• Analog and digital frequency filters

• Phase-resolved presentation (pattern) of PD

• Measurement in as little as 15 min incl.

reporting

• Presentation of PD events over total cable

length

• PD mapping

• Direct Mapping of cable trace in OpenStreet-

Map®

• Display of parasitic frequencies (bandpass

and bandstop for parasitic frequencies)

Page 4: PD30-E - b2hv · The PD diagnosis on medium and high voltage cable offers the possibility of early detection of vulnerabilities through a precise localization of PD faults in cables

Partial Discharge Diagnostics (PD)Article number SH0234

Input supply voltage 110 - 240 V AC, 50/60Hz

Operating voltagesine wave 1 - 24 kV rms / 34 kV peak

frequency 0.01 - 0.1 Hz in steps of 0.01 Hz (default 0.1 Hz) - auto frequency

CapacitanceHV Coupling Capacitor ~ 1 nF

HV Filter 4 nF

Dimensions L 300 x W 250 x H 486mm

Weight 29 kg

Filter analog & digital

Velocity Range (v/2) 10 - 150 m/µs

Measuring Range 100 km

PD background level < 10 pC

PD localization accuracy 1%

PD resolution 0.1 pC | 0.1 m

Sample rate 125 MHz (Version 2 - 200 MHz)

Input impedance 10 kΩ / 50 pF

Bandwidth 100 MHz | analog filter

Signal Amplification 0 - 52 dB (1 channel) | 0 - 72 dB (2 channel)

Environmentalconditions

storage - 20°C to + 65°C

operating - 5°C to + 45°C

Control and Diagnostics Software b2 Suite®

Features • Automatic or manual modes for PD Diagnostics• Guided Diagnostics Process • Comprehensive Data Base

Control b2 VLF generator control and b2 Suite® Software

Measurement Cable length with PD activities, PD Location, PD Mapping, Background Noise, PD Magnitude, Sine Wave Imposed display, PDIV and PDEV, etc…

System requirements MS Windows 7 / 8, 64 Bit Operating System

Scope of delivery Unit , Calibrator, HV Cable, Power and earthing cable, Corona Shields, Transport Boxes (2), b2 Suite Software (1 licence), Operating Manual, Data Base

NOT in scope of delivery of delivery

Computer / PC, VLF (0.1 Hz) Generator (Voltage Source)

Please note: VLF (0.1 Hz) high voltage generator (required) is not in scope of delivery.

DH

V130

9 Re

v03

- EN

GLI

SH -

Subj

ect t

o al

tern

atio

ns. E

rror

s ex

cept

ed. I

llust

ratio

ns a

re n

ot b

indi

ng.

Riedstrasse 1 | A-6833 Klaus | +43 (0) 5523 57373 | [email protected]

PD30-E