PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a...

52
PD Monitoring of MV/HV Power Cables December 2016 Malcolm Seltzer-Grant [email protected]

Transcript of PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a...

Page 1: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

PD Monitoring of MV/HV Power Cables

December 2016

Malcolm Seltzer-Grant [email protected]

Page 2: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Introduction to HVPD Ltd

Introduction to HVPD – Our global presence

•  HVPD are experts in the growing industry of on-line partial discharge (OLPD) condition monitoring and condition based maintenance (CBM) of high voltage networks.

•  We supply portable and permanent OLPD surveying, diagnostic test and continuous monitoring solutions, and a complimentary range of on-site services, monitoring services and training.

•  Over 400 customers in 100 countries trust our technology.

Page 3: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Contents

•  Introduction to partial discharge in power cables

•  Measurement equipment

•  Continuous monitoring

•  Partial discharge location methods

•  Case studies

Page 4: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Partial Discharge Detection Theory

•  PDs are incepted by the high voltage applied to cable.

•  PD pulses are short duration impulses (ns – µs) that propagate in both directions away from PD site between cable core and sheath.

•  Signals can be detected on both the core and earth screen at terminations.

End B End A

Available Waveform Display

Chan 1 Curs 1 Curs 2

Time (mSec)20191817161514131211109876543210

Chan 1

0.6

0.4

0.2

0

-0.2

-0.4

-0.6

-0.8

Page 5: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

MV/HV Cable Faults - Causes and Effects

Common Causes

•  Poor workmanship (at cable accessories)

•  Mechanical damage caused by poor installation practices (including damage to cable sheath during cable pulling and minimum cable bend radius’ being exceeded)

•  Poor quality or poorly manufactured cables and cable accessories

•  Aging of insulation

Effects

•  Electrical trees and interfacial surface tracking

•  Localised heating/moisture ingress into the cable (caused by damage to the armour/outer sheath)

•  ‘Infant Mortality’ and premature failure within the firs years of operation

Page 6: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

PD Damage to HV Cable Transformer Terminations

Tracking on 110 kV Termination

(PD detected before failure)

Failed 110 kV Termination

(same type as opposite)

Page 7: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Insufficient Mastic Around Connector in 33 kV Joint

Page 8: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Trees on 66kV paper cable

Page 9: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Why and When to Perform PD Testing

At Manufacture

•  Quality Assurance

•  Type/routine tests, e.g. IEEE/IEC standard

At Commissioning

•  To check for transport damage

•  To ensure the installation has been made to a good standard, for example attachment of terminations and joints to power cables

Service Life •  Detection of issues that emerge over time

•  Condition Based Maintenance

Page 10: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Spot Test: Surveying vs Diagnostic Testing

•  Survey - Detection –  Identify equipment with PD in network

–  Simple instrumentation – can be susceptible to noise

–  Low level of training

–  Usually only on-line

•  Diagnostic/Location Testing –  Detailed test result – more advanced instruments

–  Higher level of training to perform

–  Off-line and On-line

Use survey to identify equipment with PD and diagnostic testing only where PD is identified

Page 11: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Spot Testing vs Monitoring

•  Spot Test –  Snapshot of the condition

–  Doesn’t take into account variations with operating stress –  Labour resource to perform testing

•  Monitoring –  Continuous evaluation of the condition

–  Detect variations with operating stresses (e.g. temperature/humidity)

–  Less labour requirement after set-up

–  Usually deployed on critical plant or plant with high PD in spot test

Page 12: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Test Equipment

•  Detection –  Simple handheld detectors, give

indication if PD detected and its level

•  Diagnostic –  More advanced detector, often with

PC software

–  More information – type of PD, locations

•  Monitoring –  Portable or permanent logging of PD –  Interface to plant control system

(SCADA)

Page 13: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Aspects of Testing MV and HV Cables

•  MV

•  Equipment at primary substation and ring main units

•  Cross-bonding less common

•  Some tolerance to PD activity

•  HV

•  Strong safety motivation for sealing ends

•  Equipment and substations, cable termination, cable joints

•  Very little tolerance to PD activity

Page 14: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

PD Detection – Energies for Different Points in Cable System

Corona at metal contactsElectrical charge RF Electromagnetic radiationAcoustic UltravioletOzone

Discharges on insulator surfaceElectrical charge RF Electromagnetic radiationAcoustic UltravioletOzone

Partial discharge in termination insulation systemElectrical charge RF Electromagnetic radiation (local)Acoustic (local)

Partial discharge in cable insulation or jointElectrical charge RF Electromagnetic radiation (local)Acoustic (local)

Page 15: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

High Frequency Current Transformer (HFCT) Sensors

•  Detect PD in cables and connected plant

•  Wide bandwidth (from 100 kHz to 20 MHz)

•  Attach to power cables at terminations and earthing links of HV equipment

•  Installation inside or outside of cable box

•  Temporary or permanent

Page 16: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

HFCT Sensor Attachment to Power Cables

The HFCT sensor should be attached to intercept either the conductor PD current (i+) or the earth PD current (i-)

HFCT on Earth (i-)

1

1

2

HFCT on cable with Earth

brought back through (i+)

2

HFCT around cable

(i- + i+ = 0)

3

Page 17: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

HFCT Attachment at Cross-bond Points on 132 kV Cables

Page 18: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

PD Against Phase for Power Cables – On-line Detection

Available Waveform Display

Chan 1 Curs 1 Curs 2

Time (mSec)20191817161514131211109876543210

Chan 1

0.04

0.03

0.02

0.01

0

-0.01

-0.02

-0.03

-0.04

-0.05

Available Waveform Display

Chan 1 Curs 1 Curs 2

Time (mSec)20191817161514131211109876543210

Chan 1

0.6

0.4

0.2

0

-0.2

-0.4

-0.6

-0.8

Single Core Cable Three Core Belted Cable with HFCT on Common Screen

Page 19: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Modern PD Detection Systems

Hardware Filtering/Amplification

Digitiser/DSOPD Data Analysis Software

PD Sensors

Trigger signal

Page 20: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Indicated Condition

Indicated Condition

Noise Reduction Performed with the Kronos™ Software

Raw Data PD Event

Recognition Apply Expert

De-noising Rules De-noised PD Data

1,121,068 more noise pulses are rejected.

61,924 PD pulses (0.2%) correctly identified

HVPD implements the rules on the software

21,183,018 (100%) data

point acquired over 33,941

power cycles

The Kronos™ automatically (before training) recognises

1,182,992 (6%) data points as possible PD pulses

and rejects the remainder as noise

Page 21: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Data Analysis

Data before analysis/noise rejection

Data after analysis/noise rejection

Page 22: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Data Analysis

Page 23: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Continuous Monitoring

Page 24: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Continuous PD Monitoring Aspects

Detect cyclic changes in activity •  Load varying activity on PILC cables

•  Humidity related activity from surface discharges

Detect changes that relate to incipient faults

•  Gradual rise

•  Sudden rise

•  Sudden drop

Carried out on: key circuits, circuits with suspected cyclic PD changes, circuits with high spot-test results

Page 25: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

PD and Load Relations

Although PD incepted by voltage, load can have effect •  Mostly on PILC cables •  Load variations

– Movement of oil/impregnant – Expansion of conductors

S S M T W T F S S M T W T F

Page 26: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

PD burns in a cold cable (90% of cases): fluid shrinks, voids appear, local PD in voids

0

50

100

150

200

250

300

350

400

Prozess

Datum

15.07.2009 07:30

15.07.2009 15:00

15.07.2009 22:30

16.07.2009 06:00

16.07.2009 13:30

16.07.2009 21:00

17.07.2009 04:30

17.07.2009 12:00

17.07.2009 19:30

18.07.2009 03:00

18.07.2009 10:30

18.07.2009 18:00

19.07.2009 01:30

19.07.2009 09:00

19.07.2009 16:30

20.07.2009 00:00

20.07.2009 07:30

20.07.2009 15:00

20.07.2009 22:30

21.07.2009 06:00

21.07.2009 13:30

21.07.2009 21:00

22.07.2009 04:30

22.07.2009 12:00

22.07.2009 19:30

PD burns in a hot cable: electrodes expand - possible movements inside accessories lead to increased field strengths in dielectrics – PD in accessories

10kV PILC Cables

Page 27: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Examples of PD rises to Failure

6

Number above threshold 1 (start date=12/07/99)

Time (Days)16014012010080604020

Cou

nts

abov

e th

resh

old

450,000

400,000

350,000

300,000

250,000

200,000

150,000

100,000

50,000

0

0

Thresh 1

Peak, ave, and No above thresholds (start date=29/11/00 Chan=18)

Time (Days)6050403020100

Sig

nal l

evel

s (m

V)

0

360,000340,000320,000

300,000280,000260,000240,000220,000200,000180,000160,000140,000120,000

100,00080,00060,00040,00020,000

Page 28: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

On-line Cable Mapping (PD Site Location)

Page 29: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

•  Cables act as waveguides for PD pulses and as low-pass filters.

•  PD pulses attenuate and disperse as they travel down the cable

•  PD sensor must have a good low frequency response to detect long distance PD.

•  Increasing the number of test points gives more conclusive results.

•  A study was carried out using ~500 pC calibration pulses injected into 20 km, 400 kV cable to determine attenuation and measurement range – the pulse was successfully detected 20 km from the source.

PD Detection Theory PD Pulse Propagation and Attenuation

Cotton, I., O’Donnell, V,. & Christofides, N. Limitation in the application of on-line and off-line PD measurement systems CIRED 2005

Reference: S.Sutton, R. Plath and G. Shröder, “The St.Johns Wood – Elstree Experience – Testing a 20km Long 400kV XLPE-

Insulated Cable System After Installation”, Jicable 2007 - 7th International Conference on Insulated Power Cables, Paris – Versailles, 24-28 June 2007.

Page 30: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

PD Location in Power Cables

Direct pulse Reflected pulse

ΔT L

Measurement End Remote End PD event

Direct Pulse

Reflected Pulse

PD Site Location

1001% ⎟⎟⎠

⎞⎜⎜⎝

⎛⎟⎠

⎞⎜⎝

⎛ Δ−=L

TPD

ΔT = Time difference between direct and reflected pulses. L = Cable Return Time for cable

Page 31: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Single-ended Cable Mapping

•  Only possible for long distances when the tested cable’s far end impedance change is HIGH (e.g. if the end of the cable goes into a transformer and/or the circuit breaker at the far end of the cable is OPEN).

Page 32: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

OLPD Location on Power Cables

In many on-line cases reflected PD pulses are often not visible: •  Attenuation is too large to measure reflected pulses from the far end (long

cables)

•  Waveforms too difficult to interpret (noisy signals)

•  Teed or jointed cables

•  Cables with many ring main units or switches

•  Cables with no change in impedance at the far end

•  Cross-bonded cable circuits – multiple reflections

Page 33: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Double-ended Cable Mapping (Range up to 5 km or 3 RMUs)

•  Necessary when the tested cable’s far end impedance change is LOW (e.g. if the far end circuit breaker is CLOSED).

•  The HVPD Portable Transponder system amplifies PD signals, allowing the HVPD Longshot™ at the other end of the cable to receive and interpret the relative arrival times of pulses at each end of the cable to give an accurate location.

•  The cable earth strap must be accessible at both ends of the cable in order to perform double-ended mapping.

Page 34: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

On-line PD Location on Power Cables Example of Usage

Without Transponder

Reflection may not be clearly visible (e.g. due to noise)

ΔT

With Transponder

ΔT ΔTtr

The large transponder pulse removes any confusion

ΔT = Time between direct and reflected PD pulses ΔTtr = Transponder time delay

Page 35: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

On-line PD Location on Power Cables Example Results

Location (% along cable)10510095908580757065605550454035302520151050-5

All

Pha

ses

PD

(pC

)

450

400

350

300

250

200

150

100

50

0

Time (uSec)50454035302520151050

Vol

tage

(mV

)

15

10

5

0

-5

-10

-15

Direct PDPulse

Reflected PD Pulse

Transponder Pulse

Transponder Time Delay

Reflectogram showing PD and transponder pulses

PD location map for all PD pulses in cable section under test

Page 36: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

CASE STUDY: OLPD TESTING AND CABLE MAPPING OF 33 KV XLPE CABLES IN METRO NETWORK

Page 37: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

•  OLPD testing was carried out in response to a number recent faults* of 33 kV cable joints within the customer’s network.

•  The faults led to disruption of the power supply to the rail system.

•  The purpose of the testing was to measure and locate any PD activity within the cables with particular focus on the cable joints.

Case Study: Introduction

* It should be noted that this was a newly installed cable system that had been in-service for just over 12 months before the faults started to occur.

Page 38: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

•  On-line Cable PD Mapping using the HVPD Longshot™ test unit and Portable transponder.

•  Tests started with calibration testing with pulse injection HFCTs.

Case Study : OLPD Testing Equipment and Methodology

Page 39: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

•  Cable PD signals have been detected on Blue Phase with cross-talk (lower magnitude) on Red and Yellow phases.

•  The source of PD was located to Joint Number 2 (Jt2) using the on-line PD mapping technique.

•  The faulty joint on this cable was replaced and re-tested using the HVPD Longshot™ test unit to verify the repair was good

Case Study: Test Results

Page 40: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

•  Out of the 50+ circuits tested, Major PD was detected within cable accessories on the three of the circuits (6%) as shown in RED in the Table below.

•  The levels of discharges detected put these 33 kV cables into RED category, “Major concern, locate PD and then repair or replace”.

Case Study: Top 20 ‘Worst Performing Circuits’

Criticality Number Circuit Comments

Peak Cable PD Level

(pC)

Local PD Level (dB)

Cumulative Cable PD Level

(nC/cycle)

OLPD Criticality (%)

Maintenance Action

1. DUB to MPS1 C2 B Phase 25888 <10 247 97.4 Major concern, locate PD and then repair or

replace.

2. ABS to AH C2 B / Y Phase 9729 <10 120 90.3 3. BUR to HCC C2 B / Y Phase 3781 <10 12.3 78.7 4. BUR to HCC C1 B / Y Phase 3245 <10 7.9 78.1 5. ABS to AH C1 B / Y Phase 2920 <10 14.4 77.4 6. NHD to QYD C2 R Phase 2849 <10 15.0 76.2 7. ALQ to AHS C2 B Phase 1733 <10 4.6 70.6 Some concern,

repeat test and regular

monitoring recommended.

8. MPS3 to BNS C2 R / B Phase 1337 <10 6.4 65.5 9. NHD to QYD C1 R Phase 887 <10 8.8 47.8

10. HCC to CRK C1 Y / B Phase 759 <10 2.5 39.2 11. AHS to SLD Y / R Phase 705 <10 3.1 38.5 12. STD to ABH Y Phase 238 <10 1.0 24.1

Re-test in 12 months.

13. ALR to BNS C1 B Phase 184 <10 0.9 18.6 14. ALR to BRJ No PD detected 0 <10 0 0 15. ALG to PMD No PD detected 0 <10 0 0 16. ALG to KBW No PD detected 0 <10 0 0 17. AQD to AQ2 No PD detected 0 <10 0 0 18. JDD to CRK No PD detected 0 <10 0 0 19. ODM to JDF C1 No PD detected 0 <10 0 0 20. ODM to JDF C2 No PD detected 0 <10 0 0

Page 41: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

CASE STUDY: OLPD Testing, Location, Monitoring with Preventative Maintenance on a 33 kV Land-

Sea Offshore Wind Farm Export Cable (UK)

Page 42: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Case Study: Circuit Details

•  1.7 km single core XLPE land cable •  9.6/11.5 km 3 core XLPE subsea cable

33kV Switching Substation

Offshore Wind farm

Land-Subsea Cable Joints

Land Cables 3 x single core

Offshore 33kVGIS Switchgear

33kV Grid Substation

3 core Subsea Cables

Circuit 1 Circuit 2

Page 43: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Case Study: OLPD Test and Mapping Data

L1 L2 L3

Cable PD

Phase of Pow er Cycle (deg)360270180900

PD

Mag

nitu

de (

pC)

0

Cable PD

Phase of Pow er Cycle (deg)360270180900

PD

Mag

nitu

de (

pC)

0

Cable PD

Phase of Pow er Cycle (deg)360270180900

PD M

agni

tude

(pC

) 10,000

5,000

0

-5,000

-10,000

High levels of PD (of up to 10,000 pC / 10 nC) measured on Circuit B, Phase L3.

Page 44: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Location (meters) 1,600 1,400 1,200 1,000 800 600 400 200 0

Case Study: PDMap© Graph Showing PD Location

Land-sea Transition

Joint Joint Pit 7

Switching Substation

Page 45: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Case Study: PD Signals Before and After Joint Replacement

Joint 7 with PD removed and replacement cable section installed

Location (meters) 1,600 1,400 1,200 1,000 800 600 400 200 0

High PD detected on L3

PD Located

Lower-level sporadic PD signals from different site after joint replacement

BEFORE

AFTER

Page 46: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Case Study: Circuit B – Evidence of Surface Degradation Due to Bad Fitting Heatshrink Stress Control

Page 47: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Case Study: OLPD testing of 110 kV XLPE cables and terminations for oil refinery client (Slovakia)

Page 48: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Following the failure of two 110 kV transformer cable terminations, OLPD testing on the other cable terminations of same type was carried out.

Condition Assessment

Page 49: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Failed 110 kV Transformer Cable Termination

Page 50: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Test Set-up and Results

HFCT L1 Earth Strap HFCT L2 Earth Strap HFCT L3 Earth Strap

Cable PD

Phase of Pow er Cycle (deg)360270180900

PD M

agni

tude

(pC

)

0

Cable PD

Phase of Pow er Cycle (deg)360270180900

PD

Mag

nitu

de (

pC)

0

Cable PD

Phase of Pow er Cycle (deg)360270180900

PD

Mag

nitu

de (

pC)

400

300200100

0-100-200-300

-400

Significant levels of PD activity (of up to 400 pC) were detected on Phase L2.

Cable PD Segment Waveform

Time us3210

Vol

ts (

mV

)

10

5

0

-5

-10

Page 51: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

Forensic Investigation

•  L2 termination was eventually replaced 15 months after the initial tests were made.

•  Investigation showed evidence of severe tracking.

•  The cable had not yet failed i.e. the OLPD testing gave a very good ‘early warning’ of 15 months against the incipient fault.

Page 52: PD Monitoring of MV/HV Power Cables - Supergen … Monitoring of MV/HV Power Cables ... and a complimentary range of on-site services, ... Use survey to identify equipment with PD

End of Presentation

Thank you for your time Any Questions?

Malcolm Seltzer-Grant [email protected]