Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road...
Transcript of Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road...
![Page 1: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/1.jpg)
Witt&Sohn AG Aug-11
METRO System Design
![Page 2: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/2.jpg)
Witt&Sohn AG Aug-11
Content
�Purpose �Comparison Metro – Road tunnel�Ventilation Types/ Systems�Operation Modes�Pre-/ Detailed Design�Summary
![Page 3: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/3.jpg)
Witt&Sohn AG Aug-11
Purpose
� Presentation:
� Degree of Complexity of Metro Systems
� No Design Guideline
� No Substitution for Expert’s Design
2 years:Detailed Iterative
Design Studies (SES, CFD), Iterative Fan Selection
6 months:Pre-Design
Fan-Pre-Selection
BasicConcept
![Page 4: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/4.jpg)
Witt&Sohn AG Aug-11
Purpose
� Metro Ventilation System:
� Comfort (95%)(Temperature, air quality, humidity)
� Safety (5%)(Smoke/ Fire Control)
�SAFE LIFE
![Page 5: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/5.jpg)
Witt&Sohn AG Aug-11
Comparison Metro – Road
Requirements:
low - mediumhigh → Stall
Pressure Pulse/ Piston Effect
low/nonehighComfort
lowhighSafety
low(< 300 cars = 400 persons)
high (6 coaches = 4200 persons)
Passengers/ Victims
RoadMetro
![Page 6: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/6.jpg)
Witt&Sohn AG Aug-11
Comparison Metro – Road
Q2
Topology
single tube + Longitudinal → rough
Estimation
complex System + combined Ventilation Types→ numercial Simulation
(Experience + Iteration)
Ventilation System
simple (singletube)
difficult (Interaction withother Sub-sytems)
Design
RoadMetro
Q1 Q2
Q3Qn
Qin Qout
![Page 7: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/7.jpg)
Witt&Sohn AG Aug-11
Ventilation Types - Metro
Ventilation Types:
� Longitudinal � Jet Fan, Saccardo, Push-Pull (Axial)
�Semi-Transverse
�Fully/ partly Transverse
piston
![Page 8: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/8.jpg)
Witt&Sohn AG Aug-11
Ventilation Types - Metro
Ventilation Systems:
� Tunnel Ventilation System (TVS)� Fire
� Trackway Exhaust System (TES)� Heat Release generated by the trains
� Environmental Control System (ECS)� Tunnel/ Station AC (Comfort)
![Page 9: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/9.jpg)
Witt&Sohn AG Aug-11
Ventilation Types - Metro
UPE Smoke Duct
UPE Smoke Duct
Tunnel Tube
OTE Smoke DuctFresh Air
Supply DuctFresh Air
Supply DuctOTE Smoke Duct
Smoke Extract/Fresh Air Supply Duct
Platform
Typical Ventilation Design of a Metro Station
OTE = Over Trackway ExhaustUPE = Under Platform Exhaust
![Page 10: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/10.jpg)
Witt&Sohn AG Aug-11
Operation Modes
� Normal Operation Mode:
�Train Movement � Pressure Pulse/ Piston Effect� Interaction Intermediate-shafts (complex!)
�Comfort (Temperature, humidity, air quality)
�ECS, Tunnel Cooling System, (TES)
![Page 11: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/11.jpg)
Witt&Sohn AG Aug-11
Operation Modes
� Congestion Operation Mode (Design)
�Train Stop – Tunnel/ Station � No Piston Effect
�Comfort Requirement
�ECS, Tunnel Cooling System, TES, (TVS)
![Page 12: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/12.jpg)
Witt&Sohn AG Aug-11
Operation Modes
� Emergency Operation Mode (Design)
�Smoke Control � Evacuation (Smoke-free, Time!)� Fire-Fighting
�Fire Operation � Heat Resistance
�TVS, (TES in Station)
![Page 13: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/13.jpg)
Witt&Sohn AG Aug-11
Pre-Design (Macro)
� Selection Criterias:
�Comfort Level
�Environmental Restrictions
�Traffic Capacity
�Evacuation Strategy (Fire)Civil Engineering: Construction of tunnel
�Investment Cost
�Operation & Maintenance Cost (Life Cycle Costs)
![Page 14: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/14.jpg)
Witt&Sohn AG Aug-11
Pre-Design (Macro)
� Calculation Tools:
�SES (Subway Environment Simulation)� T, Q, vcrit, input data CFD
�CFD (Computational Fluid Dynamics)� Visual Heat/ Smoke Behaviour
(steady state + unsteady state)
� Pressure Relief
![Page 15: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/15.jpg)
Witt&Sohn AG Aug-11
Pre-Design (Macro)
� Steps:
�Boundary Conditions
�Performance/ Size of Ventilation System�ΣQi in Network
�critical air speed (comfort + fire)
�∆p-Calculation(Friction, Components’ ∆pi)
![Page 16: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/16.jpg)
Witt&Sohn AG Aug-11
Pre-Design (Macro)
� Steps:
�Environmental Conditions (CFD)�Station
�Evacuation Path
�Selection of Principle vs Philosophy�Vent. Schemes (Exhaust/ Supply)�Pre-Selection of Fans
![Page 17: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/17.jpg)
Witt&Sohn AG Aug-11
Detailed Design (Micro)
� Optimisation of Ventilation System
� Iterative (Theat/ Fire, Q, ∆p, Smoke)�Matrix:�different Locations (Station/ Tunnel) vs.�different Operation Modes (Normal/ Congested/ Emergency) vs.�different Ventilation Systems (TVS, TES, ECS)�different Configurations (Supply/ Exhaust)
� by Experience
![Page 18: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/18.jpg)
Witt&Sohn AG Aug-11
Detailed Design (Micro)
� Pressure Waves (Piston Effect)
�max. 10kPa
�Benefits�Support of VS
�Bad Effects�Sound Waves
�Discomfort�Fan Stall
∆p [kPa]
t [s]
∆p development at fixed location
![Page 19: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/19.jpg)
Witt&Sohn AG Aug-11
Detailed Design (Micro)
� Energy/ Heat Balance (Normal/ Congested)� Sources to be known!
�Energyout
�by Air Exchange inside Metro System� external (cool)
� intermediate
�by AC-System (ECS)� Optimisation
![Page 20: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/20.jpg)
Witt&Sohn AG Aug-11
Detailed Design (Micro)
�Energyin
�by Train� AC
� Power Consumpt.� Aerodynamic Losses
�by Air Exchange� external (hot)
� intermediate
T [°C]
s [km]
I II
![Page 21: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/21.jpg)
Witt&Sohn AG Aug-11
Detailed Design (Micro)
� Fire Scenario (Emergency):
�Fire Size/ Heat Amount
�Heat/ Smoke Distribution�different Scenarios/ Locations
�Determine Performance TVS
�Heat at Fans
�Evacuation Time Lines
![Page 22: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/22.jpg)
Witt&Sohn AG Aug-11
Summary
� Metro Systems Design � complex:
�Detailed Calculation (2 years) for�3 Operation Modes (Normal/ Congested/ Emergency)�different Ventilation Types (longitudinal, semi transverse, full/part
transverse) �different Ventilation Systems (TVS, etc.)�different Configurations (Smoke/ Comfort)�different Locations
� Estimations NOT possible !!
![Page 23: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/23.jpg)
Witt&Sohn AG Aug-11
Summary
� Requirement for Metro tunnels are more stringent than Road tunnels� Design of ventilation system is very complex� Different type of ventilation systems are required in Metro applications
(TVS, TES, ECS)
� SES/CFD has to be conducted by experienced consultants� Special fan design to enable operation of fans despite piston effect
(pressure waves) generated by the trains
� Therefore: Design of Metro Systems should be only done by:�Consultants
� Not done by reputable Fan Makers !!
![Page 24: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/24.jpg)
Witt&Sohn AG Aug-11
Annex with further informations
![Page 25: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/25.jpg)
Witt&Sohn AG Aug-11
Boundary Conditions
� Given project facts:
� Tunnel System� 1 Station (Extension) or Network� Tunnel or Station segment (Constructive)� Tunnel or Station Dimensions:
Lengths, Areas, Gradients� Type (1- or 2-Track/ Separate Walls/ Platform)� Type and Quantity of
Shafts/ Openings/ Cross-Passages
![Page 26: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/26.jpg)
Witt&Sohn AG Aug-11
Boundary Conditions
� Train
�Dimension�Performance (speed)�Operation Scheme/ Frequency�Heat Release (Normal/ Congested)�Fire Size
![Page 27: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/27.jpg)
Witt&Sohn AG Aug-11
Boundary Conditions
�Ambient Conditions (summer/ winter)
�Environmental Restrictions/ Impacts
�Safety Strategy� Evacuation Path/ Scenario
� Min. Survival Conditions
![Page 28: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/28.jpg)
Witt&Sohn AG Aug-11
Boundary Conditions
�Comfort (Limits)� Air Quality
� Humidity� Temperature
� Pressure Pulse
![Page 29: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/29.jpg)
Witt&Sohn AG Aug-11
Boundary Samples
Tunnel and Station
Details
Ventilation System
Details
Train
Details
Temperatures
Volume flow at
platform
Air speeds
in Tunnel
![Page 30: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/30.jpg)
Witt&Sohn AG Aug-11
Tunnel Scheme
Sample
Configuration
of Stations
![Page 31: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/31.jpg)
Witt&Sohn AG Aug-11
Tunnel Scheme
Station Shaft
Configuration
![Page 32: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/32.jpg)
Witt&Sohn AG Aug-11
Pressure Drop Calculation
AREA PERIM.
78080
860
![Page 33: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/33.jpg)
Witt&Sohn AG Aug-11
Pressure Pulse (CFD)
Grid
Pressure pulsePressure pulse
![Page 34: Part2.1 Metro design - wittfan.de · Witt&Sohn AG Aug-11 Content Purpose Comparison Metro – Road tunnel Ventilation Types/ Systems Operation Modes Pre-/ Detailed Design Summary](https://reader031.fdocuments.in/reader031/viewer/2022022016/5b644bc07f8b9a0e428d34e4/html5/thumbnails/34.jpg)
Witt&Sohn AG Aug-11
Pressure Pulse
Tympanic membrane rupture> 13300
Severe ear pain, tinitus8000 - 10700
Increased discomfort (ear ringing, painful cracking, dizziness)
2000 - 4000
Disinct feeling of fullness in the ear; decreasedsound intensity
1300 - 2000
Increased feeling of fullness in the ear700 - 1300
Perceptible feeling of fullness in the ear400 - 700
Typical Symptom (human ear)
Pressure Pulse Magnitude [Pa]