Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air...

27
Page 1 of 27 Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com Manual : 2100-669E Supersedes: 2100-669D Date: 1-28-19 SERVICE INSTRUCTIONS WITH REPLACEMENT PARTS LIST LC6000-200 CONTROLLER Part of the Bard Cooling System NOTE: LC6000-200 controller is required for operation when multiple MULTI-TEC ® , FUSION-TEC ® WR Series and/or MEGA-TEC TM wall-mount units are used.

Transcript of Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air...

Page 1: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

Page 1 of 27

Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com

Manual : 2100-669ESupersedes: 2100-669D Date: 1-28-19

SERVICE INSTRUCTIONSWITH REPLACEMENT PARTS LIST

LC6000-200 CONTROLLERPart of the Bard Cooling System

NOTE: LC6000-200 controller is required for operation when multiple MULTI-TEC ®, FUSION-TEC® WR Series and/or MEGA-TECTM wall-mount units are used.

Page 2: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

Manual 2100-669E Page 2 of 27

FIGURES AND TABLES

Figure 1 Adjust Alarm Setpoints ...........................5Figure 2 Adjust Alarm Remote Notification Relay Output Direction ............................5Figure 3 Adjust Emergency Off, Emergency Vent or Generator Alarm Input Direction ...........6Figure 4 Adjust Alarm Remote Notification Relay Output Direction ............................7Figure 5 Adjust Units Running When Generator Is Active ................................................7Figure 6 Adjust Zone Alarm Configuration ..............9Figure 7 Adjust Humidity Alarm Setpoints ...........10Figure 8 Change Indoor Temperature Averaging Type ....................................................11Figure 9 Adjust Staging Settings .........................12Figure 10 Staging Maximum Number of Units Running ..............................................12Figure 11 Rotation ..............................................13Figure 12 Humidity Control Setpoints ....................14Figure 13 Dehumidification Types .........................14Figure 14 Enabling Humidifier ..............................14Figure 15 Continuous Blower Status ......................15Figure 16 Continuous Blower Custom Configuration .. 15 Figure 17 MULTI-TEC Unit Information Screen ......16Figure 18 FUSION-TEC WR Series Unit Information Screen ...............................16Figure 19 MEGA-TEC Unit Information Screen .......16Figure 20 Changing to Celsius ..............................17Figure 21 Clearing LC6000 Alarm Logs .................18Figure 22 Configuring Free Cooling .......................18 Figure 23 Enabling High Sensible Operation ..........19Figure 24 8403-079 Sensor .................................20Figure 25 8301-090 Sensor .................................23 Figure 26 LC6000-200 Wiring Diagram .................26

Table 1 LC6000 Passwords (Defaults) ................17Table 2 LC6000 Status Messages ......................17Table 3 8403-079 Sensor: Temperature/ Resistance ...........................................21Table 4 8403-079 Sensor: Voltage/Humidity ......22Table 5 8301-090 Sensor: Temperature/ Resistance ...........................................23Table 6 LC6000-200 Terminal Block Index ........24Table 7 LC6000-200 to Sensor Connection Index ...................................................25

General Information ...........................................3 Cooling System .....................................................3 LC6000-200 Series Controller ...............................3 Additional Publications ..........................................4Alarms ...................................................................5 Alarm Adjustment .................................................5 Acknowledging/Clearing Alarms ........................5 Low Temperature Alarm ...................................5 High Temperature Alarm ..................................5 High Temperature 2 Alarm ...............................6 Emergency Off Alarm ......................................6 Generator Alarm .............................................7 Emergency Vent Alarm ....................................8 Zone Unit Alarm .............................................8 Humidity Alarm ..............................................9

Control Operation .............................................11 Temperature Control ............................................11 Indoor Temperature Averaging ........................11 Comfort Mode ..............................................11 Staging ............................................................11 FIFO (First In First Out) .................................11 LIFO (Last In First Out) .................................11 Demand Staging ...........................................11 Staging Delay ...............................................12 Maximum Number of Units Running...............12 Rotation ......................................................12 Demand .......................................................13 Humidity Control .................................................13 Dehumidification ..........................................13 Humidification .............................................14 Enabling Humidifier ...............................14 Continuous Blower ..............................................15 Continuous Blower Custom Configuration ........15

Additional Information ....................................16 LC6000 Menus/Screens ......................................16 Main Menu ..................................................16 Status Screen ..............................................16 Quick Menu .................................................16 Data Log ...............................................16 Info ......................................................16 Setpoints ..............................................16 Menu Screens and Password Levels ................17 Additional Programming ......................................17 Changing to Celsius ......................................17 Configuring Number of Units .........................17 Calibrating Sensors .......................................18 Clearing Alarm Logs ......................................18 Configuring Free Cooling ...............................18 Enabling High Sensible Operation ..................18

Troubleshooting ................................................20 8403-079 Remote Indoor Temperature/Humidity Sensor ...............................................................20 8301-090 Outdoor Temperature/Humidity Sensor ..23

LC6000 Replacement Parts List ......................27

CONTENTS

It is important to check the software version during installation to ensure that the latest version has been installed. Current software versions, change log and installation instructions are available on the Bard website at http://www.bardhvac.com/software-download/

NOTICE

Page 3: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

Cooling SystemThis Bard cooling system is composed of MULTI-TEC, FUSION-TEC WR Series and/or MEGA-TEC wall-mounted air conditioners matched with an LC6000 controller or Bard th-Tune stand-alone controller (th-Tune can only be used with MULTI-TEC units). If only one wall-mounted air conditioner is being used, it can be matched with either the LC6000 or a th-Tune stand-alone controller (if applicable). If more than one wall-mount unit is installed, the LC6000 controller must be matched with the air conditioning units. The wall-mount units are specifically engineered for equipment cooling applications.

NOTE: The LC6000 controller and MULTI-TEC, FUSION-TEC WR Series and MEGA-TEC wall-mount units are designed specifically to work together. The controller cannot run other brands of systems, nor can other controllers run the MULTI-TEC, FUSION-TEC WR Series or MEGA-TEC wall-mount units. They are a complete system, and must be used together.

1 One remote temperature/humidity sensor is included with the LC6000 controller. If the site in which the LC6000 controller will be used has more than one zone (maximum three zones per LC6000), additional remote temperature/humidity sensors (one sensor per zone) will need to be purchased and installed in the additional zones. One additional temperature-only sensor (Bard P/N 8301-058) may also be used in Zone 1 but will also need to be purchased separately. Additional temperature/humidity sensors require field-supplied 5-wire 18 gauge shielded cable. Temperature-only sensors require field-supplied 2-wire 18 gauge shielded cable.

(1) LC6000 Programmable Logic Controller

Outside Air Temperature/Humidity Sensor

Bard P/N 8301-090

(2) Communication EMI Filters Bard P/N 8301-055

(1) TEC-EYETM Hand-Held Diagnostic Tool Bard P/N 8301-059

(1) Remote Temperature/Humidity Sensor1 Bard P/N 8403-079

(1) 35' 5-Wire 18 Gauge Shielded Cable

Remote Temperature Only Sensor

Bard P/N 8301-058

Optional Sensors:

+

Remote Temperature/Humidity Sensor1

Bard P/N 8403-079

LC6000-200 Series Controller and Accessories Included with Controller

Manual 2100-669E Page 3 of 27

GENERAL INFORMATION

Page 4: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

The equipment covered in this manual is to be installed by factory trained and certified, experienced service and installation technicians.

These instructions should be carefully read before beginning the installation. Note particularly any tags and/or labels attached to the equipment.

While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See Additional Publications on page 4 for information on codes and standards.

Shipping Damage

Upon receipt of equipment, the cartons should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.

Additional PublicationsThese publications can help when installing the furnace. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.

National Electrical Code ......................ANSI/NFPA 70

Standard for the Installation of Air Conditioning and Ventilating Systems ...................ANSI/NFPA 90A

Standard for Warm Air Heating and Air Conditioning Systems ............ANSI/NFPA 90B

Load Calculation for Residential Winter and Summer Air Conditioning ............. ACCA Manual J

Duct Design for Residential Winter and Summer Air Conditioning and Equipment Selection ....................................................... ACCA Manual D

For more information, contact these publishers:

Air Conditioning Contractors of America (ACCA) 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721

American National Standards Institute (ANSI) 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286

American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE) 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478

National Fire Protection Association (NFPA) Batterymarch Park P. O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057

Manual 2100-669E Page 4 of 27

ANSI Z535.5 Definitions:DANGER: Indicate[s] a hazardous situation which, if not avoided, will result in death or serious injury. The signal word “DANGER” is to be limited to the most extreme situations. DANGER [signs] should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved.

WARNING: Indicate[s] a hazardous situation which, if not avoided, could result in death or serious injury. WARNING [signs] should not be used for property damage hazards unless personal injury risk appropriate to this level is also involved.

CAUTION: Indicate[s] a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION [signs] without a safety alert symbol may be used to alert against unsafe practices that can result in property damage only.

NOTICE: [this header is] preferred to address practices not related to personal injury. The safety alert symbol shall not be used with this signal word. As an alternative to “NOTICE” the word “CAUTION” without the safety alert symbol may be used to indicate a message not related to personal injury.

Page 5: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

ALARMS

NOTE: Screenshots shown in this manual reflect default settings (when applicable).

Alarm AdjustmentAcknowledging/Clearing Alarms

Alarm conditions activate a red LED indicator that backlights the ALARM function key. As an option, an alarm condition may also be enunciated by an audible alarm signal. An alarm is acknowledged by pressing the ALARM key. This calls up alarm display screen(s) that provide a text message detailing the alarm condition(s). After an alarm condition is corrected, the alarm can be cleared by pressing the ALARM key for 3 seconds.

Low Temperature Alarm

If the lowest temperature sensor value in a zone is below the low temperature setpoint, an alarm will be generated for that zone. Additionally, a relay output will be actuated from the LC controller to provide remote notification of the event.

NOTE: This alarm is per zone. If each zone is meant to operate within the same alarm parameters, each zone will need to be set accordingly.

To adjust the low temperature alarm setpoint:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Alarm Setpoints A2-9 (Zone 1), Alarm Setpoints A3-9 (Zone 2) or Alarm Setpoints A4-9 (Zone 3).

6. Press ENTER key to scroll to the variable labeled Low Temp (see Figure 1).

7. Press UP or DOWN keys to adjust setpoint.

To change the direction of the remote notification relay output:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Digital Out Config C3.

5. Press ENTER key to scroll to the variable in the table that intersects LoTemp and Dir (see Figure 2)

6. Press UP or DOWN key to change direction.

The low temperature notification relay has dry contacts. The Dir, direction, is the position of the relay without a low temperature event. NO is normally open; NC is normally closed.

When the Val (value) is OFF, the relay is not in an alarm condition. When the Val (value) is ON, the relay is in an alarm condition. The relay connections for the low indoor temperature alarm are on the LC6000 terminal block; see Table 6 on page 24 for terminal block index.

High Temperature Alarm

If the highest temperature sensor value in a zone is above the high temperature setpoint, an alarm will be generated for that zone. When this alarm is present, emergency cooling in this zone will become active.

There are two high temperature alarm setpoints. This is the first and there is no remote notification for this alarm.

NOTE: This alarm is per zone. If each zone is meant to operate within the same alarm parameters, each zone will need to be set accordingly.

To adjust the high temperature alarm setpoint:

1. Press MENU key to go to the Main Menu screen.

FIGURE 1Adjust Alarm Setpoints

FIGURE 2Adjust Alarm Remote Notification

Relay Output Direction

Manual 2100-669E Page 5 of 27

Page 6: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Alarm Setpoints A2-8 (Zone 1), Alarm Setpoints A3-8 (Zone 2) or Alarm Setpoints A4-8 (Zone 3).

6. Press ENTER key to scroll to the variable labeled High Temp (see Figure 1).

7. Press UP or DOWN keys to adjust setpoint.

High Temperature 2 Alarm

If the highest temperature sensor value in a zone is above the high temperature 2 setpoint, an alarm will be generated for that zone. When this alarm is present, the units will emergency cool in this zone. Additionally, a relay output will be actuated from the LC to provide remote notification of the event.

NOTE: This alarm is per zone. If each zone is meant to operate within the same alarm parameters, each zone will need to be set accordingly.

To adjust the high temperature 2 alarm setpoint:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Alarm Setpoints A2-9 (Zone 1), Alarm Setpoints A3-9 (Zone 2) or Alarm Setpoints A4-9 (Zone 3).

6. Press ENTER key to scroll to the variable labeled High Temp 2 (see Figure 1).

7. Press UP or DOWN keys to adjust setpoint.

To change the direction of the remote notification relay output:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Digital Out Config C3.

5. Press ENTER key to scroll to the variable in the table that intersects HiTemp and Dir (see Figure 2).

6. Press UP or DOWN key to change direction.

When the Val (value) is OFF, the relay is not in an alarm condition. When the Val (value) is ON, the relay is in an alarm condition. The relay connections for the high indoor temperature 2 alarm are on the LC6000 terminal block; see Table 6 on page 24 for terminal block index.

Emergency Off Alarm

If the LC gets an input from a smoke detector or similar device, an alarm will be generated and all units will be shut down. Additionally, a relay output will be actuated from the LC to provide remote notification of the event.

The emergency off input can be configured to accept either normally open or normally closed inputs. The controller is defaulted to normally open and a jumper is placed across the terminals of the input (#6 and #7). When this jumper is removed, the alarm will become active.

To change the direction of the emergency off input:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Digital In Config C1.

5. Press ENTER key to scroll to the variable in the table that intersects EM Off and Dir (see Figure 3).

6. Press UP or DOWN key to change direction.

Emergency Off (EM Off) Dir (direction) is the position of the smoke detector contacts in the event of smoke. NO is normally open; NC is normally closed.

EM Off En (enable) allows the LC control to monitor the smoke detector when set to ON. When set to OFF, the LC controller ignores the smoke detector.

EM Off Val (value) of ON indicates a smoke event. A Val (value) of OFF indicates no smoke event.

Smoke detector connections (emergency off input) are on the LC6000 terminal block; see Table 6 on page 24 for terminal block index.

FIGURE 3Adjust Emergency Off, Emergency Vent or

Generator Alarm Input Direction

Manual 2100-669E Page 6 of 27

Page 7: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

Generator Alarm

If the LC detects a generator running event (through a digital input), an alarm will be generated. Additionally, a relay output will be actuated from the LC to provide remote notification of the event. The end user will be able to configure which units are permitted to run during this event. Default will be to not allow any units to run.

The generator alarm input can be configured to accept either normally open or normally closed inputs. The controller is defaulted to normally open and a jumper is placed across the terminals of the input (#10 and #11). When this jumper is removed, the alarm will become active.

To change the direction of the generator input:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Digital In Config C1.

5. Press ENTER key to scroll to the variable in the table that intersects Gen and Dir (see Figure 3).

6. Press UP or DOWN key to change direction.

Gen Dir (direction) is the position of the generator input contacts in the event of a need for generator operation. NO is normally open; NC is normally closed.

Gen En (enable) allows the LC control to monitor the generator input contacts when set to ON. When set to OFF, the LC controller ignores the generator input contacts.

Gen Val (value) of ON indicates the generator is in operation. A Val (value) of OFF indicates the generator is not operating.

Generator connections (generator run input) are on the LC6000 terminal block; see Table 5 on page 22 for terminal block index.

While the generator is running, the system will only allow selected units to run. This selection is customizable by the end user. This limitation is in place to match the unit power requirements to the shelter generator capacity.

The default is to not allow any units to run during a generator event. This can be adjusted to allow specific units to run during a generator event.

To change which units run when the generator run input is active:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.

3. Press UP or DOWN keys to scroll to Adv System Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Generator Disable B13. This screen displays units 1-6 (as applicable).

5. Press ENTER key to scroll to 01 (see Figure 5).

To change the direction of the remote notification relay output:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Digital Out Config C2.

5. Press ENTER key to scroll to the variable in the table that intersects EMG Off and Dir (see Figure 4).

6. Press UP or DOWN key to change direction.

The smoke alarm notification relay has dry contacts. The Dir (direction) is the position of the relay without a smoke event. NO is normally open; NC is normally closed.

When the Val (value) is ON, the relay is in an alarm condition. The relay connections (smoke alarm) are on the LC6000 terminal block; see Table 6 on page 24 for terminal block index.

FIGURE 4Adjust Alarm Remote Notification Relay

Output Direction

FIGURE 5Adjust Units Running When Generator Is Active

Manual 2100-669E Page 7 of 27

Page 8: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

6. Press UP or DOWN key to change Disable to Enable.

7. Press ENTER key to save the value and move cursor to 04.

8. Press UP or DOWN keys and ENTER key to change units to Enable as needed.

9. Press ENTER key to scroll back to top line.

The Generator Disable B13 screen displays units 1-6. To enable/disable units 7-14, press UP or DOWN keys to scroll to Generator Disable B14 and follow the directions provided above.

To change the direction of the remote notification relay output:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Digital Out Config C2.

5. Press ENTER key to scroll to the variable in the table that intersects Gen and Dir (see Figure 4 on page 7).

6. Press UP or DOWN key to change direction.

The generator alarm notification relay has dry contacts. The Dir (direction) is the position of the relay without generator operation. NO is normally open; NC is normally closed.

When the Val (value) is ON, the relay is in an alarm condition. The relay connections (generator alarm) are on the LC6000 terminal block; see Table 6 on page 24 for terminal block index.

Emergency Vent Alarm

If the emergency vent terminals are activated by a hydrogen detector or similar device, an alarm will be generated and the wall units will all be put into emergency ventilation by the LC. Additionally, a relay output will be actuated from the LC to provide remote notification of the event. The end user will be able to configure which zones ventilate during this event.

Units with economizers will operate in emergency vent mode. The dampers will open at 100% and the blower will come on at full speed until the alarm is reset. Units without economizers located in the same zone will only bring on the blower at full speed.

The emergency vent alarm input can be configured to accept either normally open or normally closed inputs. The controller is defaulted to normally open and a jumper is placed across the terminals of the input (#8 and #9). When this jumper is removed, the alarm will become active.

To change the direction of the emergency vent input:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Digital In Config C1.

5. Press ENTER key to scroll to the variable in the table that intersects EM Vent and Dir (see Figure 3 on page 6).

6. Press UP or DOWN key to change direction.

Emergency Vent (EM Vent) Dir (direction) is the position of the emergency vent contacts in the event of hydrogen being sensed. NO is normally open; NC is normally closed.

EM Vent En (enable) allows the LC control to monitor the hydrogen detector when set to ON. When set to OFF, the LC controller ignores the hydrogen detector.

EM Vent Val (value) of ON indicates a hydrogen event. A Val (value) of OFF indicates no hydrogen event.

Emergency vent connections (hydrogen detector input) are on the LC6000 terminal block; see Table 6 on page 24 for terminal block index.

To change the direction of the remote notification relay output:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Digital Out Config C2.

5. Press ENTER key to scroll to the variable in the table that intersects EMG Vent and Dir (see Figure 4 on page 7).

6. Press UP or DOWN key to change direction.

The emergency vent alarm notification relay has dry contacts. The Dir (direction) is the position of the relay without a hydrogen event. NO is normally open; NC is normally closed.

When the Val (value) is ON, the relay is in an alarm condition. The relay connections (emergency vent alarm) are on the LC6000 terminal block; see Table 6 on page 24 for terminal block index.

Zone Unit Alarm

By default, if any of the units communicate a high pressure or low pressure alarm to the LC, the LC will actuate a relay output to provide remote notification of the event. A relay output will be actuated from the

Manual 2100-669E Page 8 of 27

Page 9: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

FIGURE 6Adjust Zone Alarm Configuration

LC to provide remote notification of the event for each zone.

To change the direction of the remote notification relay output:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Digital Out Config C3.

5. Press ENTER key to scroll to the variable in the table that intersects Z1Alm and Dir, Z2Alm and Dir, or Z3Alm and Dir (see Figure 2 on page 5).

6. Press UP or DOWN key to change direction.

When the direction is set to NO, the relay output will be closed when the alarm is active and open when not active. When the direction is set to NC, the relay output will be open when alarm is active and closed when not active.

The zone alarms can be configured to actuate based on 15 alarms communicated from each wall unit. These items can be selected for each zone.

To select which wall unit alarms actuate zone alarms:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.

3. Press UP or DOWN keys to scroll to Adv Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone Alarm Config B4, Zone Alarm Config B5 and Zone Alarm Config B6. The 15 alarms are divided between these three screens.

5. Press ENTER key to scroll to the variable in the table that intersects with each alarm and zone number (see Figure 6).

6. Press UP or DOWN key to change value (N or Y). If a value of Y is entered, the wall unit alarm will trigger the zone alarm relay output. If a value of N is entered, the wall unit alarm will not trigger the zone alarm relay output.

NOTE: By default, only 'no temperature sensors' and high and low pressure actuate the alarms.

NOTE: Power Loss group is also affected by communication loss.

NOTE: If no temperature sensors are detected by the controller for a given zone, that zone alarm output will be actuated. This is nonconfigurable.

Humidity Alarm

When the LC detects a high indoor humidity or low indoor humidity event in a selected zone (through an analog input from a remote sensor), an alarm will be generated. Additionally, a relay output will be actuated from the LC to provide remote notification of the event. The end user can configure the alarm to be actuated when the measurement is high, low or both high and low.

To adjust the humidity alarm setpoints:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Alarm Setpoints A2-10 (Zone 1), Alarm Setpoints A3-10 (Zone 2) or Alarm Setpoints A4-10 (Zone 3).

Manual 2100-669E Page 9 of 27

Page 10: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

6. Press ENTER key to scroll to Low Humidity, High Humidity or Alarm Delay (delay in seconds from the time the alarm is sensed until the alarm is displayed). See Figure 7.

7. Press UP and DOWN keys to adjust setpoints or delay.

To adjust the direction of the remote notification relay output:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to IO Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Digital Out Config C3.

5. Press ENTER key to scroll to the variable in the table that intersects HumAl and Dir (see Figure 2 on page 5).

6. Press UP or DOWN key to change direction.

When the direction is set to NO, the relay output will be closed when the alarm is active and open when not active. When the direction is set to NC, the relay output will be open when alarm is active and closed when not active.

FIGURE 7Adjust Humidity Alarm Setpoints

Manual 2100-669E Page 10 of 27

Page 11: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

FIGURE 8Change Indoor Temperature Averaging Type

CONTROL OPERATION

NOTE: Screenshots shown in this manual reflect default settings (when applicable).

Temperature ControlIndoor Temperature Averaging

The LC has the ability to average all of the zone temperature sensors connected to the LC and the return air temperature sensors connected to the wall-mount unit, use only the zone temperature sensors, or use the LC sensors and any unit which has its blower run continuously. This can be set differently for each zone. This value will then be used as a zone indoor temperature for the LC and wall-mount unit control functions.

There are three possible sensor averaging selections:

• LC Only

This configuration only averages the zone temperature sensors connected to the LC and enabled within the specific zone.

• Blower On

This configuration averages any temperature sensors connected to the LC that are enabled and the return air temperature sensor of any wall-mount unit set to run in continuous blower within the specific zone.

• All Sensors

This configuration averages the zone temperature sensors connected to the LC that are enabled and all the return air temperature sensors of all wall-mount units within the specific zone, regardless of blower operation.

To change the indoor temperature averaging type:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Zone Temp A2-11 (Zone 1), Zone Temp A3-11 (Zone 2) or Zone Temp A4-11 (Zone 3).

6. Press ENTER key to scroll to Selection (see Figure 8).

7. Press UP and DOWN keys to adjust.

Comfort Mode

If comfort mode is activated, all of the zone setpoints will be set to 72°F for cooling and 70°F (Comfort Setoint -2) for heating. This setpoint will be active for 60 minutes.

To enable comfort mode:

1. Press UP or DOWN key while on the Status screen to select Setpoints ( ) from the Quick Menu options; press ENTER key.

2. Press ENTER key to scroll to Comfort Mode.

3. Press UP or DOWN keys to change the duration of comfort mode.

4. Press ENTER key to scroll to Comfort Setpoint.

5. Press UP and DOWN keys to change the cooling setpoint for comfort mode.

6. Press ENTER key to scroll to Comfort Enable.

7. Press UP or DOWN key to change value from OFF to ON; press ENTER key.

The system is now in comfort mode and will cool or heat to the comfort setpoint for the 60-minute duration.

StagingEach zone is capable of three different staging methods.

FIFO (First in First Out)

The unit that is first in rotation will be the first one turned off.

LIFO (Last in First Out)

The unit that is last in rotation will be the first one turned off.

Demand Staging

While in cooling operation, the unit with the highest return temperature will be brought on first. The unit with the lowest return temperature will be turned off first. While in heating mode, the unit with the lowest

Manual 2100-669E Page 11 of 27

Page 12: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

return air temperature will be brought on first and the unit with the highest return temperature will be turned off first.

To change the staging method type:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Staging A2-5 (Zone 1), A3-5 (Zone 2) or A4-5 (Zone 3).

6. Press ENTER key to scroll to the variable labeled Type (see Figure 9).

7. Press UP or DOWN keys to adjust.

Maximum Number of Units Running

The maximum number of units that will be staged on can be configured for each zone. The number is defaulted at the total number of units capable so that they are fully utilized by default. This is configurable for economizer, cooling and heating independently.

To adjust the maximum number of units running:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Staging A2-6 (Zone 1), Staging A3-6 (Zone 2) or Staging A4-6 (Zone 3).

6. Press ENTER key to scroll to the variable for Freecooling, Cooling or Heating (see Figure 10).

7. Press UP or DOWN keys to adjust number of units.

FIGURE 9Adjust Staging Settings

FIGURE 10Staging Maximum Number of Units Running

Staging Delay

A delay on and off can be set for economizer (FC), cooling (CL)and heating (HT) independently for each zone. This will limit how fast the units can be staged on or off.

To adjust the on and off delay times:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Staging A2-5 (Zone 1), Staging A3-5 (Zone 2) or Staging A4-5 (Zone 3).

6. Press ENTER key to scroll to the variable in the table that intersects FC, CL or HT and Delay On or Delay Off (see Figure 9).

7. Press UP or DOWN keys to adjust.

Rotation

The units in each zone can be rotated based on a configurable number of days (1-7). The time is defaulted to 7 days. In addition to time-based, a manual rotation can be triggered for troubleshooting.

To change the rotation variables:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Rotation A2-7 (Zone 1), Rotation A3-7 (Zone 2) or Rotation A4-7 (Zone 3).

Manual 2100-669E Page 12 of 27

Page 13: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

6. Press ENTER key to scroll to Time Based (see Figure 11). The changeover time is 12 am.

7. Press UP or DOWN key to change ON to OFF.

8. Press ENTER key to scroll to Num. of Days.

9. Press UP or DOWN keys to adjust the number of days.

10. Press ENTER key to scroll to Manual.

11. Press UP or DOWN key to change OFF to ON.

FIGURE 11Rotation

Demand

The system will compare the zone temperature (determined by zone averaging selection) to the zone cooling and heating setpoint. A demand will be calculated to determine how many units are required.

For cooling, the zone temperature will be compared to the cooling setpoint. The controller will calculate a demand based on how far above the setpoint and how long it has been above the setpoint. The demand value (0-100%) will then be split and applied to free cooling and cooling separately shown as two demands both ranged 0-100% applied to all of the available cooling methods for that zone. For example, if the demand is at 50% and there are 10 available stages of cooling in that zone, there would be 5 stages active (50% x 10 = 5). The system will prioritize free cooling stages over compressor stages. Adding to the example, if 5 of the 10 stages for cooling are economizer, 5 units would be running economizer and no compressors running. The demand is calculated for the cooling application. However, for display purposes, the demand is split so that the user can see demand separately for free cooling and compressor.

For heating, the zone temperature will be compared to the heating setpoint. The controller will calculate a demand based on how far below the setpoint and how long it has been below the setpoint. The demand value 0-100% will the be applied to all of the available stages of heating in that zone. For example, if the demand is at 50% and there are 5 available stages of heating in that zone, there would be 2 stages active (50% x 5 = 2.5 and a half of a stage cannot be turned on).

Humidity ControlThe LC can be configured to control up to three humidifiers (field supplied) with relay outputs and up to 14 units equipped with dehumidification. The indoor humidity level for each zone is compared to the dehumidification setpoint and humidification setpoint for each zone.

Dehumidification

The LC6000 controller will monitor the indoor relative humidity of each zone and compare the value to three setpoints for each zone. The three setpoints will be described as dehumidification off, passive dehumidification and active dehumidification. The default value for these setpoints will be 60%RH, 70%RH and 80%RH, respectively.

When the humidity level inside the shelter falls to the dehumidification off setpoint, the system will stop attempting to dehumidify the space.

When the humidity level rises to the passive dehumidification setpoint, all units with economizers will disable the use of economizers for cooling calls. This will act as passive dehumidification by forcing the use of compressor for space cooling. Availability for passive dehumidification will be determined by model number. All units with economizers will be considered.

When the humidity level rises to the active dehumidification setpoint, the controller will activate staged dehumidification. The controller will then calculate a dehumidification demand based on how far above the setpoint and how long the RH level has been above the setpoint. The demand will then utilize all of the units with active dehumidification capabilities to reduce the indoor humidity level. The units will be staged on based on the existing cooling rotation for the units in the zone up to an optional maximum number of units running value. Availability for active dehumidification will be determined by model number. Units with concurrent electric reheat or mechanical dehumidification will be considered. NOTE: Only one type of dehumidification unit will be considered depending upon configuration of the LC6000 controller. Unit capability is determined by the model number.

To change the dehumidification setpoints:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Setpoints A2-2 (Zone 1), Setpoints A3-2 (Zone 2) or Setpoints A4-2 (Zone 3).

Manual 2100-669E Page 13 of 27

Page 14: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

6. Press ENTER key to scroll to Dehumidification Off, Passive On or Active On (see Figure 12).

7. Press UP and DOWN keys to change dehumidification setpoints to desired values.

FIGURE 12Humidity Control Setpoints

FIGURE 14Enabling Humidifier

FIGURE 13Dehumidification Types

Humidification

If the humidity level is below 45% RH (Humidification Setpoint), the LC will enable humidification for that zone. Once the humidity level rises to 55% RH (Humidification Setpoint plus 10% RH), the humidification for that zone will be disabled.

NOTE: Humidifiers are field supplied.

To change the humidification setpoint:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Setpoints A2-2 (Zone 1), Setpoints A3-2 (Zone 2) or Setpoints A4-2 (Zone 3).

6. Press ENTER key to scroll to Humidification (see Figure 12).

7. Press UP and DOWN keys to change humidification setpoint to desired value.

Enabling Humidifier

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to General; press ENTER key.

5. Press ENTER key to scroll to Humidifiers (see Figure 14).

6. Press UP or DOWN keys to change value to NONE, Zone 1, Z1 & Z2 or Z1, Z2, & Z3.

7. Press ENTER to scroll to Humidifier Type.

8. Press UP or DOWN keys to change value to Relay from Comm.

In addition to the setpoint configuration for dehumidification, each zone must be configured for the type of active dehumidification.

To change the dehumidification type:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Setpoints A2-3 (Zone 1), Setpoints A3-3 (Zone 2) or Setpoints A4-3 (Zone 3).

6. Press ENTER key to scroll to Type (see Figure 13).

7. Press UP and DOWN keys to change to desired value. Dehumidification type choices are None, Electric Reheat, Mechanical Reheat or Cycling Reheat. The units in the zone being configured will need to have the capability of the setting being selected (see unit model number).

Manual 2100-669E Page 14 of 27

Page 15: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

Continuous BlowerThe LC will has the option in each zone to operate in continous blower. The options are None, Lead, All and Custom. When None is selected, continuous blower will be disabled on all units in that zone. When Lead is selected, only the lead unit will have continuous blower activated. When All is selected, continuous blower will be enabled on all units in that zone. When Custom is selected, only units specifically commanded on by the end user will run in that zone.

Precedence for continuous blower will be given to the LC or stand-alone controller in instances where communication with LC is lost.

To change the continuous blower status of each zone:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Cont. Blower A2-8 (Zone 1), Cont. Blower A3-8 (Zone 2) or Cont. Blower A4-8 (Zone 3).

6. Press ENTER key to scroll to Selection (see Figure 15).

7. Press UP and DOWN keys to change to desired choice.

FIGURE 15Continuous Blower

Continuous Blower Custom Configuration

When Custom is selected, only unit specifically commanded on by the end user will run in that zone. To select the units to run in continuous blower:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter TECHNICIAN password 1313.

3. Press UP or DOWN keys to scroll to Adv Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Cont. Blower Cust. B10, Cont. Blower Cust. B11 or Cont. Blower Cust. B12. The wall-mount units are divided between these three screens.

5. Press ENTER key to scroll to the variable in the Enable column that represents the desired wall mount unit (see Figure 16).

6. Press UP or DOWN key to change value from No to Yes (to enable that unit for continuous blower) or Yes to No (to disable that unit for continuous blower).

7. Press ENTER key to save.

FIGURE 16Continuous Blower

Manual 2100-669E Page 15 of 27

Page 16: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

LC6000 Menus/ScreensMain Menu

Press the MENU key from any screen to return to the Main Menu. Press the UP or DOWN keys to scroll through the available menus. When the desired menu is highlighted, press the ENTER key to access that menu. Press the ESCAPE key or MENU key to return to the Status screen from the Main Menu.

Status Screen

The Status screen is the default start-up screen and also the return screen after 5 minutes of no activity. The screen can be accessed any time by pressing the ESCAPE button repeatedly. The LC6000 Status screen displays the current date, time, unit displayed, zone and unit status.

Quick Menu

The Quick Menu is available on the Status screen. Use UP or DOWN keys while on the Status screen to scroll between the three Quick Menu options; press ENTER key.

Data Log

The data log displays the record number, time of alarm event, date of alarm event, description of alarm event and whether the entry is the beginning or end of event. The data log will have as many screens as events occurred.

Info

The information menu groups all information by unit address. The LC6000 controller is capable of operating MULTI-TEC, FUSION-TEC WR Series and MEGA-TEC wall-mount units. The screens will automatically show the relevant information for each unit. For example, the FUSION-TEC WR Series and MEGA-TEC wall-mount units are equipped with a supply air temperature sensor while the MULTI-TEC units are not. The supply temperature measurement will only show when displaying information from a FUSION-TEC WR Seies or MEGA-TEC wall-mount unit. Additionally, FUSION-TEC WR Series units are equipped with an electronic expansion valve (EEV). When connected to a FUSION-TEC WR Series unit, an additional screen will show pressures and temperatures affecting the air conditioning system. MEGA-TEC wall-mount units are equipped with two electronic expansion valves with additional screens that show pressures and temperatures for each EEV.

The last of the wall-mount unit’s information screens will display the model number, serial number and software version of the unit (see Figures 17, 18 and 19). This information is very important and could be

ADDITIONAL INFORMATION

FIGURE 17MULTI-TEC Unit Information Screen

FIGURE 18FUSION-TEC WR Series Unit Information Screen

needed when referencing technical documentation online or contacting Bard Technical Services.

FIGURE 19MEGA-TEC Unit Information Screen

Setpoints

Setpoints allows setting and enabling of comfort mode.

Manual 2100-669E Page 16 of 27

Page 17: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

Menu Screens and Password Levels

A System Config General: User (2000) Zone 1: User (2000) Zone 2: User (2000) Zone 3: User (2000)

B Adv Sys Config: Technician (1313)

C I-O Config: Technician (1313)

D On/Off: User (2000)

E Alarm Logs: User (2000)

F Settings Date/Time: Technician (1313) Language: User (2000) Network Config: Technician (1313) Serial Ports: Technician (1313) Initialization Clear Logs: User (2000) System Default: Engineer (9254) Restart: User (2000) Parameter Config: Engineer (9254) Alarm Export: User (2000)

G Logout: Used to log out of the current password level. Entering back into the menu requires password.

Additional ProgrammingChanging to Celsius

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to General Settings (A1-1); press enter key.

5. Press ENTER key to scroll to UOM (see Figure 20).

6. Press UP and DOWN keys to change value to SI.

FIGURE 20Changing to Celsius

Configuring Number of Units

The LC is capable of operating up to 14 wall-mount units in up to 3 zones. This includes MULTI-TEC, FUSION-TEC WR Series and MEGA-TEC units. Add all units up for total number of units. Example: If there are three MULTI-TEC units in Zone 1, two FUSION-TEC WR units in Zone 2 and one MEGA-TEC unit in Zone 3, the total number of units should be set to 6.

To configure the total number of units:

1. Press MENU key to go to the Main Menu screen.

2. Press UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to General Settings (A1-1); press enter key.

5. Press ENTER key to scroll to Total Units (see Figure 20).

6. Press UP or DOWN keys to adjust value to correct number of units.

7. Press ENTER key to save value.

User 2000

Technician 1313

Engineer 9254

Use UP or DOWN keys and ENTER key to enter password

TABLE 1LC6000 Passwords (Defaults)

Message Description

On The system is on

Off by AlarmThe system has a major fault and is

disabled

Off by BMSThe system has been disabled by

network supervisor

Off by KeypadThe system has been turned off by

local user

Emergency Cooling

The system has detected a high temperature alarm and one or more

zones are emergency cooling

Emergency VentThe system has detected hydrogen

and one or more zones are in emergency ventilation

TABLE 2LC6000 Status Messages

Manual 2100-669E Page 17 of 27

Page 18: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

FIGURE 21Clearing LC6000 Alarm Logs

Calibrating Sensors

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to I/O Config; press ENTER key.

4. Press UP or DOWN keys to scroll to sensor to be adjusted.

5. Press ENTER key to scroll to Offset.

6. Press UP or DOWN keys to add or subtract to the sensor offset value.

7. Press ENTER key to save.

Clearing Alarm Logs

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Settings; press ENTER key.

4. Press UP or DOWN keys to scroll to Initialization; press ENTER key.

5. Press ENTER key to scroll to Delete Alarm Logs? (see Figure 21).

6. Press UP or DOWN key to change value to YES; press ENTER key.

Configuring Free Cooling

Each zone can be configured to operate the economizers with different considerations. For more information on the economizer enable setpoints, please reference the most recent version of the corresponding wall-mount unit service manual. For MULTI-TEC, see Service Manual 2100-665. For FUSION-TEC WR Series, see Service Manual 2100-688. For MEGA-TEC, see Service Manual 2100-671.

The type of consideration can be changed to none, drybulb, temperature and humidity, or enthalpy. The temperature, humidity and dewpoint parameters can be changed to affect at what conditions the economizers

FIGURE 22Configuring Free Cooling

in the respective zone will operate. These settings will be communicated to the wall units while connected to the LC6000 to ensure all units operate the same.

To make changes to the free cooling settings:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

5. Press UP or DOWN keys to scroll to Zone FC Settings A2-4 (Zone 1), Zone FC Settings A3-4 (Zone 2) or Zone FC Settings A4-4 (Zone 3).

6. Press ENTER key to scroll to Type, Enable Temp, Enable Hum or Enable Dewp (see Figure 22).

7. Press UP and DOWN keys to adjust free cooling values.

Enabling High Sensible Operation

The LC6000 has the option to operate the wall units in a high sensible mode that will adjust blower speeds to enhance the sensible cooling capacity of the units. This option is not enabled by default and will automatically turn off when the indoor humidity raises to the passive dehumidification setpoint. High sensible operation will resume once the indoor humidity has lowered to the dehumidification off setpoint.

NOTE: This mode available only on the FUSION-TEC WR Series and MEGA-TEC wall-mount units. It is not available on the MULTI-TEC wall-mount units.

To enable high sensible operation:

1. Press MENU key to go to the Main Menu screen.

2. Use UP or DOWN keys and ENTER key to enter USER password 2000.

3. Press UP or DOWN keys to scroll to Sys Config; press ENTER key.

4. Press UP or DOWN keys to scroll to Zone 1, Zone 2 or Zone 3; press ENTER key.

Manual 2100-669E Page 18 of 27

Page 19: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

FIGURE 23Enabling High Sensible Operation

5. Press UP or DOWN keys to scroll to Blower Profile A2-12 (Zone 1), Blower Profile A3-12 (Zone 2) or Blower Profile A4-12 (Zone 3).

6. Press ENTER key to scroll to Enable (see Figure 23).

7. Press UP or DOWN key to change value to YES; press ENTER key.

Manual 2100-669E Page 19 of 27

Page 20: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

TROUBLESHOOTING

8403-079 Remote Indoor Temperature/Humidity Sensor

FIGURE 248403-079 Sensor

DP1DP2 0-1VDC Jumper Position

Sensor Terminals Description

M(G0) - +(G)12VDC +/–

Supplies power to the sensor

M(G0) - OUT H0-1VDC

Supplies signal for zone humidity(see Voltage/Humidity chart on page 22)

NTC OUT - NTC OUT

OhmSupplies signal for zone temperature (see Temperature/Resistance chart on

page 21)

Troubleshooting the temperature/humidity sensor is necessary if the temperature or humidity reading for a zone is inaccurate. Always start sensor troubleshooting by verifying connections at the sensor board and at the LC6000 terminal blocks. Improper connection will cause inaccurate readings. Next, verify continuity at both ends of wires running between the sensor and the LC6000. A severed or damaged wire will cause inaccurate readings. As a last step, verify voltage and resistance at the sensor and the LC6000 terminal block per the Tables 3 and 4. If the sensor is found to be malfunctioning, replace the sensor.

NOTE: Sensor jumper must be positioned for 0-1 V as shown above for sensor to function properly.

Manual 2100-669E Page 20 of 27

Page 21: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

Temperature Resistance

C F KΩ-18 0 61.52

-17 1 58.66

-16 3 55.95

-15 5 53.39

-14 7 50.96

-13 9 48.65

-12 10 46.48

-11 12 44.41

-10 14 42.25

-9 16 40.56

-8 18 38.76

-7 19 37.05

-6 21 35.43

-5 23 33.89

-4 25 32.43

-3 27 31.04

-2 28 29.72

-1 30 28.47

TABLE 38403-079 Sensor: Temperature/Resistance

Temperature Resistance

C F KΩ0 32 27.28

1 34 26.13

2 36 25.03

3 37 23.99

4 39 22.99

5 41 22.05

6 43 21.15

7 45 20.29

8 46 19.40

9 48 18.70

10 50 17.96

11 52 17.24

12 54 16.55

13 55 15.90

14 57 15.28

15 59 14.68

16 61 14.12

17 63 13.57

Temperature Resistance

C F KΩ18 64 13.06

19 66 12.56

20 68 12.09

21 70 11.63

22 72 11.20

23 73 10.78

24 75 10.38

25 77 10.00

26 79 9.63

27 81 9.28

28 82 8.94

29 84 8.62

30 86 8.31

31 88 8.01

32 90 7.72

33 91 7.45

34 93 7.19

35 95 6.94

Temperature Resistance

C F KΩ36 97 6.69

37 99 6.46

38 100 6.24

39 102 6.03

40 104 5.82

41 106 5.63

42 108 5.43

43 109 5.25

44 111 5.08

45 113 4.91

46 115 4.74

47 117 4.59

48 118 4.44

49 120 4.30

50 122 4.16

51 124 4.02

52 126 3.90

Manual 2100-669E Page 21 of 27

Page 22: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

Voltage DC RH%

1 100

0.99 99

0.98 98

0.97 97

0.96 96

0.95 95

0.94 94

0.93 93

0.92 92

0.91 91

0.90 90

0.89 89

0.88 88

0.87 87

0.86 86

0.85 85

0.84 84

0.83 83

0.82 82

0.81 81

0.79 79

0.78 78

0.77 77

0.76 76

0.75 75

Voltage DC RH%

0.49 49

0.48 48

0.47 47

0.46 46

0.45 45

0.44 44

0.43 43

0.42 42

0.41 41

0.40 40

0.39 39

0.38 38

0.37 37

0.36 36

0.35 35

0.34 34

0.33 33

0.32 32

0.31 31

0.30 30

0.29 29

0.28 28

0.27 27

0.26 26

0.25 25

TABLE 48403-079 Sensor: Voltage/Humidity

Voltage DC RH%

0.74 74

0.73 73

0.72 72

0.71 71

0.70 70

0.69 69

0.68 68

0.67 67

0.66 66

0.65 65

0.64 64

0.63 63

0.62 62

0.61 61

0.60 60

0.59 59

0.58 58

0.57 57

0.56 56

0.55 55

0.54 54

0.53 53

0.52 52

0.51 51

0.50 50

Voltage DC RH%

0.24 24

0.23 23

0.22 22

0.21 21

0.20 20

0.19 19

0.18 18

0.17 17

0.16 16

0.15 15

0.14 14

0.13 13

0.12 12

0.11 11

0.10 10

0.09 9

0.08 8

0.07 7

0.06 6

0.05 5

0.04 4

0.03 3

0.02 2

0.01 1

0.00 0

Manual 2100-669E Page 22 of 27

Page 23: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

8301-090 Outdoor Temperature/Humidity Sensor

Troubleshooting the temperature/humidity sensor is necessary if the temperature or humidity reading is inaccurate. Always start sensor troubleshooting by verifying connections at the sensor board and at the LC6000 terminal blocks. Improper connection will cause inaccurate readings. Next, verify continuity at both ends of wires running between the sensor and the LC6000. A severed or damaged wire will cause inaccurate readings. As a last step, verify voltage and resistance at the sensor and the LC6000 terminal block per the provided table. If the sensor is found to be malfunctioning, replace the sensor.

SensorTerminal

Description

1 Remote Outdoor Humidity Sensor: 0-10 VDC

2 +VDC

3 Ground

4 Remote Outdoor Temperature Sensor

5 Ground

FIGURE 258301-090 Sensor

Temperature Resistance

C F Ω-32 -25.6 151,200

-31 -23.8 142,900

-30 -22.0 135,200

-29 -20.2 127,900

-28 -18.4 121,100

-27 -16.6 114,600

-26 -14.8 108,600

-25 -13.0 102,900

-24 -11.2 97,490

-23 -9.4 92,420

-22 -7.6 87,650

-21 -5.8 83,150

-20 -4.0 78,910

-19 -2.2 74,910

-18 -0.4 71,130

-17 1.4 67,570

-16 3.2 64,200

-15 5.0 61,020

-14 6.8 58,010

-13 8.6 55,170

-12 10.4 52,490

-11 12.2 49,950

TABLE 58301-090 Sensor: Temperature/Resistance

Temperature Resistance

C F Ω-10 14.0 47,540

-9 15.8 45,270

-8 17.6 43,110

-7 19.4 41,080

-6 21.2 39,140

-5 23.0 37,310

-4 24.8 35,580

-3 26.6 33,930

-2 28.4 32,370

-1 30.2 30,890

0 32.0 29,490

1 33.8 28,160

2 35.6 26,890

3 37.4 25,690

4 39.2 24,540

5 41.0 23,460

6 42.8 22,430

7 44.6 21,440

8 46.4 20,510

9 48.2 19,620

10 50.0 18,780

11 51.8 17,980

Temperature Resistance

C F Ω12 53.6 17,210

13 55.4 16,480

14 57.2 15,790

15 59.0 15,130

16 60.8 14,500

17 62.6 13,900

18 64.4 13,330

19 66.2 12,780

20 68.0 12,260

21 69.8 11,770

22 71.6 11,290

23 73.4 10,840

24 75.2 10,410

25 77.0 10,000

26 78.8 9602

27 80.6 9226

28 82.4 8866

29 84.2 8522

30 86.0 8194

31 87.8 7879

32 89.6 7579

33 91.4 7291

Temperature Resistance

C F Ω34 93.2 7016

35 95.0 6752

36 96.8 6500

37 98.6 6258

38 100.4 6027

39 102.2 5805

40 104.0 5592

41 105.8 5389

42 107.6 5194

43 109.4 5007

44 111.2 4827

45 113.0 4655

46 114.8 4490

47 116.6 4331

48 118.4 4179

49 120.2 4033

50 122.0 3893

51 123.8 3758

52 125.6 3629

Manual 2100-669E Page 23 of 27

Page 24: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

TABLE 6LC6000-200 Terminal Block Index

TB# WireMark Description

1 - 120 VAC Input

2 - 208 VAC Input

3 - 230 VAC Input

4 - Power Input Common

5 - Power Input Ground

6 DI1 Emergency Off Input

7 GND Emergency Off Common

8 DI2 Emergency Vent Input

9 GND Emergency Vent Common

10 DI3 Generator Run Input

11 GND Generator Run Common

12 B2 Zone 1 Indoor Remote Humidity Sensor

13 GND Ground

14 B3 Zone 2 Indoor Remote Humidity Sensor

15 GND Ground

16 B4 Zone 3 Indoor Remote Humidity Sensor

17 GND Ground

18 B6 Zone 1 Indoor Temperature Sensor

19 GND Ground

20 B7 Zone 1 Indoor Remote Temperature Sensor

21 GND Ground

22 VDC+ Power for B2 (Z1 Humidity)

23 VDC+ Power for B3 (Z2 Humidity)

24 VDC+ Power for B4 (Z3 Humidity)

25 VDC+ Power for B10 (Pressure)

26 B8 Zone 2 Indoor Remote Temperature Sensor

27 GND Ground

28 B9 Zone 3 Indoor Remote Temperature Sensor

29 GND Ground

30 B10 Indoor Space Pressure

31 GND Ground

32 NO1 Humidifier 1

33 C1 Common

34 NO2 Humidifier 2

35 C1 Common

36 NO3 Humidifier 3

37 C1 Common

38 NO4 Emergency Off Alarm

TB# WireMark Description

39 C2 Common

40 NO5 Emergency Vent Alarm

41 C2 Common

42 NO6 Generator Run Alarm

43 C2 Common

44 NO7 Indoor Humidity Alarm

45 C7 Common

46 NO8 High Indoor Temperature Alarm

47 C8 Common

48 NO9 Low Indoor Temperature Alarm

49 C8 Common

50 NO10 Zone 1 Unit Alarm

51 C8 Common

52 NO11 Zone 2 Unit Alarm

53 C8 Common

54 NO12 Zone 3 Unit Alarm

55 C8 Common

56 FB1R-RS485 RX- / TX- (Fieldbus 1) UNIT CONNECTION

57 FB1R+RS485 RX+ / TX- (Fieldbus 1) UNIT CONNECTION

58 FB2R- RS485 RX- / TX- (Fieldbus 2)

59 FB2R+ RS485 RX+ / TX- (Fieldbus 2)

60 -- Power Input Ground

61 24 VAC+ 24 VAC Supply

62 -- Not Used

63 24 VAC+ 24 VAC Supply

64 24 VAC- 24 VAC Ground

65 24 VAC+ 24 VAC Supply for Outdoor Humidity Sensor

66 24 VAC- 24 VAC Ground for Outdoor Humidity Sensor

67 B11 Signal for Outdoor Humidity Sensor

68 24 VAC+ 24 VAC Supply

69 D14 Bard Guard Alarm Signal

70 B12 Signal for Outdoor Temperature Sensor

71 GND Ground for Outdoor Temperature Sensor

72 GND Ground for Bard Guard Alarm Signal

73 G Orange Power Connector

74 24 VAC+ 24 VAC Supply

75 G0 Orange Power Connector

76 24 VAC- 24 VAC Ground

Manual 2100-669E Page 24 of 27

Page 25: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

TABLE 7LC6000-200 to Sensor Connection Index

LC6000Sensor Terminal Description

TB# Wire Mark

12 B2 8403-079 (Indoor Temp/Hum) OUT H Zone 1 Indoor Remote Humidity Sensor

13 GND 8403-079 (Indoor Temp/Hum) M (GO) Ground

14 B3 8403-079 (Indoor Temp/Hum) OUT H Zone 2 Indoor Remote Humidity Sensor

15 GND 8403-079 (Indoor Temp/Hum) M (GO) Ground

16 B4 8403-079 (Indoor Temp/Hum) OUT H Zone 3 Indoor Remote Humidity Sensor

17 GND 8403-079 (Indoor Temp/Hum) M (GO) Ground

18 B6 8403-079 (Indoor Temp/Hum) NTC OUT Zone 1 Indoor Temperature Sensor

19 GND 8403-079 (Indoor Temp/Hum) NTC OUT Ground

20 B7 8301-058 (Indoor Temp Only) NTC OUT Zone 1 Indoor Remote Temperature Sensor

21 GND 8301-058 (Indoor Temp Only) NTC OUT Ground

22 VDC+ 8403-079 (Indoor Temp/Hum) + (G) Power for B2 (Z1 Humidity)

23 VDC+ 8403-079 (Indoor Temp/Hum) + (G) Power for B3 (Z2 Humidity)

24 VDC+ 8403-079 (Indoor Temp/Hum) + (G) Power for B4 (Z3 Humidity)

26 B8 8403-079 (Indoor Temp/Hum) NTC OUT Zone 2 Indoor Remote Temperature Sensor

27 GND 8403-079 (Indoor Temp/Hum) NTC OUT Ground

28 B9 8403-079 (Indoor Temp/Hum) NTC OUT Zone 3 Indoor Remote Temperature Sensor

29 GND 8403-079 (Indoor Temp/Hum) NTC OUT Ground

65 24 VAC+ 8301-090 (Outdoor Temp/Hum) 2 24 VAC Supply for Outdoor Humidity Sensor

66 24 VAC- 8301-090 (Outdoor Temp/Hum) 3 24 VAC Ground for Outdoor Humidity Sensor

67 B11 8301-090 (Outdoor Temp/Hum) 1 Signal for Outdoor Humidity Sensor

69 D14 Bard Guard 14 Bard Guard Alarm Signal

70 B12 8301-090 (Outdoor Temp/Hum) 4 Signal for Outdoor Temperature Sensor

71 GND 8301-090 (Outdoor Temp/Hum) 5 Ground for Outdoor Temperature Sensor

72 GND Bard Guard 15 Ground for Bard Guard Alarm Signal

Manual 2100-669E Page 25 of 27

Page 26: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

FIGURE 26LC6000-200 Wiring Diagram

GN

DR

X+TX+R

X-TX-

43

21

TB 6

120V IN

208V IN

230V IN

COMMON IN BLACK

RED

ORANGE

WHITE

5GND

TB 57TB 56

BLUEYELLOW

TB 37TB 32TB 34TB 36

TB 45TB 44

GREEN

GG0

GN

DR

X+T X+R

X-TX-

TB 59TB 58

6 7 8 9

10 1112 13

14 1516 17

18 1920 21

22 2324 25

26 2728 29

30 3132 33

34 3536 37

38 3940 41

42 4344 45

46 4748 49

50 5152 53

54 5556 57

58 59

TB 8TB 10

DI1RED

DI2RED

DI3RED

B2RED

B3RED

B4RED

B6RED

B7RED

GN

D

GREEN

GN

D

BLK/RED TB 12 TB 14 TB 16

TB 18 TB 20

+Vdc

TB 26

TB 30

B9RED

B10RED

C1BLACK

C2BLACK

NO1BLUE/BLK

NO2BLUE/BLK

NO3BLUE/BLK

NO4BLUE/BLK

NO5BLUE/BLK

NO6BLUE/BLK

TB 43TB 38TB 40TB 42

TB 55TB 46TB 48TB 50TB 52TB 54

NO7BLUE/BLK

NO8BLUE/BLK

NO9BLUE/BLK

NO10BLUE/BLK

NO11BLUE/BLK

NO12BLUE/BLK

1-RX+TX+

C7BLACK

C8BLACK

2-RX+TX+

1-RX-TX-

2-RX-TX-

GREEN

TB 28

B8RED

SMKJUMPER

HYDJUMPER

GENJUMPER

ORANGE

BROWN

ORANGE/BLK

BROWN/BLK

62 6164 63

66 6568 67

70 6972 71

G 24 VAC TB74YELLOWG0 24 VAC TB76BLUE

B11B12

TB 67 TB 70

DI4

TB 69

REDREDREDGREEN

GN

D

YELLOW

BLUE

EMPTY

60GROUND

TB76TB74

74 7376 75

TB 61

TB 64G

G0

NOTE:

Wire indexes are identified such that even numbered index numbers are on the lower wire entries of the terminal block and odd numbered index numbers are on the top wire entries. Since terminal block 60 is a ground block, terminal blocks 61 thru 72 shift while still maintaining the same top and bottom configuration.

(L1) 120V IN

(L1) 208V IN

(L1) 230V IN

(L2 OR N) COMMON INPOWER GND

LC6000 TERMINAL BLOCK

TRANSFORMER

120V/208V/230VAC

24VAC

24VACINPUT

TOBOARD

PLC BOARD

UNITMODBUS

CONNECTORS

Manual 2100-669E Page 26 of 27

Page 27: Part of the Bard Cooling System - Bard HVACE).pdfANSI/NFPA 90A Standard for Warm Air Heating and Air Conditioning Systems ..... ANSI/NFPA 90B Load Calculation for Residential Winter

LC6000 REPLACEMENT PARTS LIST

Replacement part will have a letter attached to the end of the part number to designate software version (Example: 8301-076-001A). A software upgrade of all PLCs onsite (units and controllers) should accompany any PLC replacement. Latest revisions of software, change log and instructions are available on the Bard website at http://www.bardhvac.com/software-download/

uPC3 PLC board digital output ratings. Type: A (SPST) with a rating of AC 230V 3(1)A 100k cycles, 250 Vac FLA 1A, LRA 6A Definite Purpose 30k cycles, 250 Vac, 3A resistive, 50k cycles, C300 pilot duty, 30k cycles. (EN60730-1, UL60730)

Batteries for the control boards are field supplied. Supplier part number is BR2032.

Optional NS – Not Shown

Manual 2100-669E Page 27 of 27

Dwg. No. Part No. Description

1 8407-074 Transformer X

2 8301-076-001 UPC3-LC6000 1.1.0 X

3 8301-053 pGDEvolution Panel Display X

4 8607-052 Grounded Terminal Block 2

5 8614-059 1.0 Amp Fuse 4

6 8607-039 Fused Terminal Block 4

7 8607-057 Terminal Block Double Level 54

8 8611-144 End Clamp (for Din Rail) 6

9 8301-075 USB Micro Cable Female to Male X

NS 8301-055 EMI Ferrite Filter 2

NS 8403-079 Remote Temperature/Humidity Sensor X

NS 8301-058 Remote Temperature Sensor X

NS 8301-090 Outdoor Temperature/Humidity Sensor X

NS 8301-059 TEC-EYE (Service Tool), 5' Telephone Cable X

321

4568

9

7