158
ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for REM 543 and REM 545 Document ID: 1MRS751784-MTI Revision: C Description: REM 543 C 3.99 REM 543R B 3.99 REM 545 B 3.99 REM 545R B 3.99 SW build: 3.99 BIO1 version: 118001 / Rev F sw build 2.08 BIO2 version: 118002 / Rev F sw build 2.08 PS1 version: 118003 / Rev F sw build 2.08 RTD1 version: 118021 / Rev E sw build 1.17 MIMIC version: 118005 / Rev E sw build 1.15 MIP version: 118020 / MIP50E Note! This list covers the maximum set of cards and includes both the functionality levels M (Motor) and G (Generator). Page 1 of 158

Transcript of Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution...

Page 1: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Parameter List for REM 543 and REM 545Document ID: 1MRS751784-MTIRevision: CDescription: REM 543 C 3.99

REM 543R B 3.99REM 545 B 3.99REM 545R B 3.99

SW build: 3.99BIO1 version: 118001 / Rev F sw build 2.08BIO2 version: 118002 / Rev F sw build 2.08PS1 version: 118003 / Rev F sw build 2.08RTD1 version: 118021 / Rev E sw build 1.17MIMIC version: 118005 / Rev E sw build 1.15MIP version: 118020 / MIP50E

Note! This list covers the maximum set of cards and includes both the functionality levels M (Motor) and G (Generator).

Page 1 of 158

Page 2: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile ExplanationGLOVAR / Rev A GLOVAR:CH001

Rated frequency 1V10 MMI,RST General 10.00...60.00 Hz 50 Read Retain Rated frequency of the networkReset indication 1V11 RST General 1=Reset - 0 Write Volatile Resetting of operation indicationsReset outputs 1V12 RST General 1=Reset - 0 Write Volatile Resetting of operation indications & latched output signalsReset registers 1V13 RST General 1=Reset - 0 Write Volatile Resetting of operation indications, latched output signals,

registers & waveform memoryCommand timeout 1V19 MMI,RST General 0...65535 ms 100 Rd/Wr Retain Timeout for open/close requestReset energy 1V20 Internal Control setting 1=Reset - 0 Write Volatile Resetting of accumulated energy measurementFree conf. 1V21 Internal Control setting 0...1 - 0 Rd/Wr Volatile Free configuration point (F-key)Select timeout 2V1 MMI,RST General 10...600 s 30 Rd/Wr Retain Control: Object selection timeout for local and remote

selectionInterl bypass 2V4 MMI,RST General 0=Normal mode; 1=Bypass mode - 0 Rd/Wr Volatile Control: Interlocking bypass mode for all control objects

(Enables all)Control position 2V5 RST General 0=Disable; 1=Local; 2=Remote - 0 Read Volatile Control: Recent control positionControl poll 2V6 Internal Control setting 1=LON virtual inputs has been polled, 0=LON virtual

inputs hasn't been polled or the polling is going on- 0 Read Volatile Control: Virtual LON input poll status

Execute all 900V251 Internal Control setting 1=Execute - 0 Write Volatile Control: Execute all command for selected objects (global)Cancel all 900V252 Internal Control setting 1=Cancel - 0 Write Volatile Control: Cancel all command for selected objects (global)Execute 0V251 Internal Control setting 1=Execute - 0 Write Volatile Control: Execute all command for selected objects (inside

module)Cancel 0V252 Internal Control setting 1=Cancel - 0 Write Volatile Control: Cancel all command for selected objects (inside

module)JMAA-38R000 / Rev D CH000 General SPA parameters

Store 0V151 MMI General 0=OK/Done; 1=Start/Progress; 2=Error - 0 Rd/Wr Volatile Store issued settings into nonvolatile memorySoftware reset 0V250 MMI General 0=0, 1=Reset; 2=Error - 0 Rd/Wr Volatile Software reset for relaySPA address 0V200 MMI SPA 0....999 - 1 Rd/Wr Retain Slave number for communicationBaud rate 0V201 MMI SPA 0=4800; 1=9600, 2=19200 Bd 1 Rd/Wr Retain Data transfer rate for communicationRear connection 0V202 RST SPA 1=Connect - 0 Write Volatile Activate rear SPA connectionInput osc. Level 0V241 MMI,RST General 2 ... 50 1/s 50 Rd/Wr Retain Oscillation suppression for inputsInput osc. Hystr 0V242 MMI,RST General 2 ... 50 1/s 10 Rd/Wr Retain Oscillation suppression hysteresis for inputsOpen file 0M200 Internal Control setting ID/block count - - Write Volatile Open file for writeWrite data 0M201 Internal Control setting ID/data - - Write Volatile Send file blockClose file 0M202 Internal Control setting ID - - Write Volatile End of file transferOpen password 0V160 Internal Control setting 1...999 - 1 Write Volatile Opening of password for remote settingChange/close pw 0V161 Internal Control setting 0=close; 1...999=new password - 1 Write Volatile Changing and closing the password for remote settingSPAFTR block 0V203 Internal Control setting 0...100 - 18 Rd/Wr Volatile SPAFTR transfer block sizeSPAFTR coding 0V204 Internal Control setting 0=Hex coding; 1=4/5 coding - 0 Rd/Wr Volatile SPAFTR message coding

JMAA-38R001 / Rev F CH001 General parameters and analog channel parametersSerial No 1V2 MMI,RST Identification xxxxxx - 0 Rd/Wr Retain Serial number of the feeder terminalSoftware No 1V3 MMI,RST Identification 1MRSxxxxxx - 0 Rd/Wr Retain Configuration number of the softwareHardware No 1V4 MMI,RST Identification 1MRSxxxxxx - 0 Rd/Wr Retain Ordering number of the feeder terminalFinal test date 1V5 MMI,RST Identification YYYYMMDD - 19960101 Rd/Wr Retain Date of the final testsActivate IRF 1V14 MMI General 0...1 - 0 Write Volatile Activation of selfsupervision inputIRF code 1V15 MMI,RST General 0... 4294967295 - 0 Read Volatile Fault code of selfsupervision systemStart led latch 1V16 MMI,RST Display mode 0=Non-latching; 1=Latching - 0 Rd/Wr Retain Selection of latching feature for start ledTest mode 1V17 MMI General 0=Normal mode; 1=Test Mode - - Rd/Wr Volatile Test mode of binary inputsProtocol 2 1V23 MMI,RST General 0=NONE; 1=SPA; 2=Modbus - 0 Rd/Wr Retain Protocol for rear X 3.2 connectorProtocol 3 1V18 MMI,RST General 1=LON; 2=SPA; 3=IEC_103 - 1 Rd/Wr Retain Protocol for rear X 3.3 connectorOpen/read 1M200 Internal Control setting - - - Rd/Wr Volatile open file or read # data blocks

Page 2 of 158

Page 3: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Read file data 1M201 Internal Control setting - - - Read Volatile read data blockFB secur. code 1M300 Internal Control setting 1...n - 0 Write Volatile Nothing hereFB secur. status 1M301 Internal Control setting 0...n - 0 Read Volatile Nothing hereFB set request 1M302 Internal Control setting 0...n - 0 Rd/Wr Volatile Nothing hereFB set status 1M303 Internal Control setting 0...n - 0 Read Volatile Nothing hereConfig. counter 1M305 MMI,RST General 0...n - 0 Read Retain Configuration counterConfig. status 1M307 Internal Control setting 0...n - 0 Rd/Wr Volatile -Sett.file status 1M309 Internal Control setting 0...n - 0 Read Volatile -User Lib. Reset 1M310 Internal Control setting 0...n - 0 Rd/Wr Volatile -Config. capacity 1M311 MMI,RST General 000.0...200.0 % 0 Read Retain Processor execution time capacity used by the

configurationInstance count 1M313 Internal Control setting 1...255 - 1 Rd/Wr Volatile Instance count for FB locking interfaceError log status 1M314 Internal Control setting 0...255 - 0 Read Volatile Status of error logging file interfaceProtocol instant 1M315 Internal Control setting INSTTYPE - 0 Rd/Wr Retain Protocol instatiation interfaceSW build 1V503 MMI,RST CPU1 [3] ##.## - - Read Volatile Software build (##.##)SW version 1V501 MMI,RST CPU1 [3] 1MRS###### - - Read Volatile Software version (1MRS118xxx)SW revision 1V502 MMI,RST CPU1 [3] A-Z - - Read Volatile Software revision (A)Serial No 1V260 MMI,RST CPU1 [3] MR###### - MR00000 Read Volatile Serial number of CPU1 cardFactory password 1V168 Internal Control setting 0 - - Write Volatile Password for factory settingsZIP file 1V222 Internal Control setting - - - Rd/Wr Retain Zipped project fileZIP comm resp 1V223 Internal Control setting 0...3 - 0 Rd/Wr Volatile Zip file control commandCalib par locat. 1V224 Internal Control setting - - - Rd/Wr Volatile Calibration parameters location indication and control

JMAA-38R002 / Rev C CH002 Control parametersPosition setting 2V7 MMI,RST General 0=Disable;1=Local;2=Remote;3=Logic - 0 Read Retain Control position settingMIMIC file 2V8 Internal Control setting - - 0 Rd/Wr Retain MIMIC configuration fileEvent mask 1 2V101 MMI,RST General 0...55 - 55 Rd/Wr Retain Event mask 1 for event transmissionEvent mask 2 2V103 MMI,RST General 0...55 - 55 Rd/Wr Retain Event mask 2 for event transmissionEvent mask 3 2V105 MMI,RST General 0...55 - 55 Rd/Wr Retain Event mask 3 for event transmissionEvent mask 4 2V107 MMI,RST General 0...55 - 55 Rd/Wr Retain Event mask 4 for event transmissionFactory cnf 2V9 Internal Control setting Bit 0(1)=Graphical mimic - 1 Rd/Wr Retain Factory setting of mimic functionalityFile trns. stat 2V10 Internal Control setting 0=No actions; 1=File received; 2=File correct (ready for

nov-strore), 3=Erroneus file- 0 Read Volatile File transfer success status

JMAA-38R025 / Rev B CH025 LON snvt inputs/outputsCOMM_IN1 25I001 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 1COMM_IN2 25I002 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 2COMM_IN3 25I003 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 3COMM_IN4 25I004 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 4COMM_IN5 25I005 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 5COMM_IN6 25I006 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 6COMM_IN7 25I007 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 7COMM_IN8 25I008 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 8COMM_IN9 25I009 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 9COMM_IN10 25I010 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 10COMM_IN11 25I011 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 11COMM_IN12 25I012 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 12COMM_IN13 25I013 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 13COMM_IN14 25I014 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 14COMM_IN15 25I015 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 15COMM_IN16 25I016 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 16

Page 3 of 158

Page 4: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

COMM_OUT1 25O001 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 1COMM_OUT2 25O002 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 2COMM_OUT3 25O003 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 3COMM_OUT4 25O004 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 4COMM_OUT5 25O005 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 5COMM_OUT6 25O006 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 6COMM_OUT7 25O007 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 7COMM_OUT8 25O008 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 8COMM_OUT9 25O009 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 9COMM_OUT10 25O010 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 10COMM_OUT11 25O011 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 11COMM_OUT12 25O012 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 12COMM_OUT13 25O013 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 13COMM_OUT14 25O014 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 14COMM_OUT15 25O015 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 15COMM_OUT16 25O016 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 16

JMAA-38R026 / Rev B CH026 LON snvt inputs/outputsCOMM_IN17 26I001 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 17COMM_IN18 26I002 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 18COMM_IN19 26I003 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 19COMM_IN20 26I004 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 20COMM_IN21 26I005 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 21COMM_IN22 26I006 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 22COMM_IN23 26I007 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 23COMM_IN24 26I008 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 24COMM_IN25 26I009 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 25COMM_IN26 26I010 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 26COMM_IN27 26I011 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 27COMM_IN28 26I012 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 28COMM_IN29 26I013 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 29COMM_IN30 26I014 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 30COMM_IN31 26I015 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 31COMM_IN32 26I016 Internal Control setting 0 ... 65535 - 0 Rd/Wr Volatile Communication input 32COMM_OUT17 26O001 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 17COMM_OUT18 26O002 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 18COMM_OUT19 26O003 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 19COMM_OUT20 26O004 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 20COMM_OUT21 26O005 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 21COMM_OUT22 26O006 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 22COMM_OUT23 26O007 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 23COMM_OUT24 26O008 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 24COMM_OUT25 26O009 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 25COMM_OUT26 26O010 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 26COMM_OUT27 26O011 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 27COMM_OUT28 26O012 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 28COMM_OUT29 26O013 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 29COMM_OUT30 26O014 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 30COMM_OUT31 26O015 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 31COMM_OUT32 26O016 MMI Comm. outputs 0 ... 65535 - 0 Rd/Wr Volatile Communication output 32

Page 4 of 158

Page 5: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile ExplanationCH231 / Rev B CH231 LON Communication Protocol Adapter

Subnet number 231V001 MMI LON 1...255 - 1 Rd/Wr Volatile LON subnet numberNode number 231V002 MMI LON 1...127 - 1 Rd/Wr Volatile LON node number

MOD_BUS / Rev A MOD_BUS Modbus for REMUnit Address 504V001 MMI Modbus 1...247 - 1 Rd/Wr Retain Address of the unit in the Modbus networkCRC Order 504V002 MMI Modbus 0=Low/High; 1= High/Low - 0 Rd/Wr Retain The order of CRC bytes in protocol frame 0 = LO/HI, 1 =

HI/LO Not used in ASCII modeModbus Mode 504V003 MMI Modbus 0=ASCII; 1=RTU - 1 Rd/Wr Retain ASCII or RTU modePassword 504V004 MMI Modbus 0 - ' ' Rd/Wr Retain PasswordPOD entries max 504V060 Internal Control setting 0 - 0 Read Retain INTERNAL USE / POD GENERATION: Total number of

visible POD entries, parameter used by POD ToolEntr. not used 504V061 Internal Control setting 0 - 0 Read Retain INTERNAL USE / POD GENERATION: Number of POD

entries not in use, parameter used by POD ToolNo INV entries 504V062 Internal Control setting 0 - 0 Read Retain INTERNAL USE / POD GENERATION: Number of POD

entries with invalid (uncorrectable content) INV, parameter used by POD Tool

No COR entries 504V063 Internal Control setting 0 - 0 Read Retain INTERNAL USE / POD GENERATION: Number of POD entries with corrected contents( COR), parameter used by POD Tool

No NBL entries 504V064 Internal Control setting 0 - 0 Read Retain INTERNAL USE / POD GENERATION: Number of POD entries referring to nonexistent FBs (NBL), parameter used by POD Tool

No NOB entries 504V065 Internal Control setting 0 - 0 Read Retain INTERNAL USE / POD GENERATION: Number of POD entries referring to invalid objects from existent FBs (NOB), used by POD Tool

Entry to OP.POD 504V066 Internal Control setting 0 - 0 Read Retain INTERNAL USE / POD GENERATION: Number of POD entries translated into operational POD, parameter used by POD Tool

POD ID string 504V700 Internal Control setting 0 - 0 Read Retain INTERNAL USE / POD GENERATION: POD identification string used by POD Tool

POD tables 504M001 Internal Control setting 0 - 0 Read Retain Pod table upload/download parameterBaud rate 500V211 MMI Modbus 4800;9600;19200 Bd 9600 Rd/Wr Retain Communication speed of modbus protocolNo of stop bits 500V212 MMI Modbus 1..2 - 1 Rd/Wr Retain Number of stop bitsNext char. TO 500V215 MMI Modbus 0..65535 ms 0 Rd/Wr Retain Next character timeoutEnd of frame TO 500V216 MMI Modbus 2..65535 ms 10 Rd/Wr Retain End of frame timeoutParity 500V230 MMI Modbus 0=NONE; 1=ODD; 2=EVEN - 2 Rd/Wr Retain Parity settingNo of data bits 500V231 MMI Modbus 5,6,7,8 - 8 Rd/Wr Retain Number of data bitsRTS usage 500V218 Internal Control setting RTS_USAGE - 0 Rd/Wr Retain RTS usageRTS delay 500V214 Internal Control setting 0..65535 ms 0 Rd/Wr Retain RTS line delay

CCODED1 / Rev E CCODED1

Page 5 of 158

Page 6: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Ch1 meas. device 1V51 MMI,RST Analog channels 0..53[0=Not in use; 1=CT 1; 2=CT 2; 3=CT 3; 4=CT 4; 5=CT 5; 6=VT 1; 7=VT 2; 8=VT 3; 9=VT 4; 10=RS 1; 11=RS 2; 12=RS 3; 13=VD 1; 14=VD 2; 15=VD 3; 16=CT 6; 17=CT 7; 18=CT 8; 19=CT 9; 20=CT 10; 21=VT 5; 22=VT 6; 23=VT 7; 24=VT 8; 25=VT 9; 26=VT 10; 27=RS 4; 28=RS 5; 29=RS 6; 30=RS 7; 31=RS 8; 32=RS 9; 33=RS 10; 34=VD 4; 35=VD 5; 36=VD 6; 37=VD 7; 38=VD 8; 39=VD 9; 40=VD 10; 41=KS 1; 42=KS 2; 43=KS 3; 44=KS 4; 45=KS 5; 46=KS 6; 47=KS 7; 48=KS 8; 49=KS 9; 50=KS 10; 51=GE 1; 52=GE 2; 53=GE 3]

- 0 Read Retain Measuring device

Ch2 meas. device 1V53 MMI,RST Analog channels 0..53[0=Not in use; 1=CT 1; 2=CT 2; 3=CT 3; 4=CT 4; 5=CT 5; 6=VT 1; 7=VT 2; 8=VT 3; 9=VT 4; 10=RS 1; 11=RS 2; 12=RS 3; 13=VD 1; 14=VD 2; 15=VD 3; 16=CT 6; 17=CT 7; 18=CT 8; 19=CT 9; 20=CT 10; 21=VT 5; 22=VT 6; 23=VT 7; 24=VT 8; 25=VT 9; 26=VT 10; 27=RS 4; 28=RS 5; 29=RS 6; 30=RS 7; 31=RS 8; 32=RS 9; 33=RS 10; 34=VD 4; 35=VD 5; 36=VD 6; 37=VD 7; 38=VD 8; 39=VD 9; 40=VD 10; 41=KS 1; 42=KS 2; 43=KS 3; 44=KS 4; 45=KS 5; 46=KS 6; 47=KS 7; 48=KS 8; 49=KS 9; 50=KS 10; 51=GE 1; 52=GE 2; 53=GE 3]

- 0 Read Retain Measuring device

Ch3 meas. device 1V55 MMI,RST Analog channels 0..53[0=Not in use; 1=CT 1; 2=CT 2; 3=CT 3; 4=CT 4; 5=CT 5; 6=VT 1; 7=VT 2; 8=VT 3; 9=VT 4; 10=RS 1; 11=RS 2; 12=RS 3; 13=VD 1; 14=VD 2; 15=VD 3; 16=CT 6; 17=CT 7; 18=CT 8; 19=CT 9; 20=CT 10; 21=VT 5; 22=VT 6; 23=VT 7; 24=VT 8; 25=VT 9; 26=VT 10; 27=RS 4; 28=RS 5; 29=RS 6; 30=RS 7; 31=RS 8; 32=RS 9; 33=RS 10; 34=VD 4; 35=VD 5; 36=VD 6; 37=VD 7; 38=VD 8; 39=VD 9; 40=VD 10; 41=KS 1; 42=KS 2; 43=KS 3; 44=KS 4; 45=KS 5; 46=KS 6; 47=KS 7; 48=KS 8; 49=KS 9; 50=KS 10; 51=GE 1; 52=GE 2; 53=GE 3]

- 0 Read Retain Measuring device

Ch4 meas. device 1V57 MMI,RST Analog channels 0..53[0=Not in use; 1=CT 1; 2=CT 2; 3=CT 3; 4=CT 4; 5=CT 5; 6=VT 1; 7=VT 2; 8=VT 3; 9=VT 4; 10=RS 1; 11=RS 2; 12=RS 3; 13=VD 1; 14=VD 2; 15=VD 3; 16=CT 6; 17=CT 7; 18=CT 8; 19=CT 9; 20=CT 10; 21=VT 5; 22=VT 6; 23=VT 7; 24=VT 8; 25=VT 9; 26=VT 10; 27=RS 4; 28=RS 5; 29=RS 6; 30=RS 7; 31=RS 8; 32=RS 9; 33=RS 10; 34=VD 4; 35=VD 5; 36=VD 6; 37=VD 7; 38=VD 8; 39=VD 9; 40=VD 10; 41=KS 1; 42=KS 2; 43=KS 3; 44=KS 4; 45=KS 5; 46=KS 6; 47=KS 7; 48=KS 8; 49=KS 9; 50=KS 10; 51=GE 1; 52=GE 2; 53=GE 3]

- 0 Read Retain Measuring device

Page 6 of 158

Page 7: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Ch5 meas. device 1V59 MMI,RST Analog channels 0..53[0=Not in use; 1=CT 1; 2=CT 2; 3=CT 3; 4=CT 4; 5=CT 5; 6=VT 1; 7=VT 2; 8=VT 3; 9=VT 4; 10=RS 1; 11=RS 2; 12=RS 3; 13=VD 1; 14=VD 2; 15=VD 3; 16=CT 6; 17=CT 7; 18=CT 8; 19=CT 9; 20=CT 10; 21=VT 5; 22=VT 6; 23=VT 7; 24=VT 8; 25=VT 9; 26=VT 10; 27=RS 4; 28=RS 5; 29=RS 6; 30=RS 7; 31=RS 8; 32=RS 9; 33=RS 10; 34=VD 4; 35=VD 5; 36=VD 6; 37=VD 7; 38=VD 8; 39=VD 9; 40=VD 10; 41=KS 1; 42=KS 2; 43=KS 3; 44=KS 4; 45=KS 5; 46=KS 6; 47=KS 7; 48=KS 8; 49=KS 9; 50=KS 10; 51=GE 1; 52=GE 2; 53=GE 3]

- 0 Read Retain Measuring device

Ch6 meas. device 1V61 MMI,RST Analog channels 0..53[0=Not in use; 1=CT 1; 2=CT 2; 3=CT 3; 4=CT 4; 5=CT 5; 6=VT 1; 7=VT 2; 8=VT 3; 9=VT 4; 10=RS 1; 11=RS 2; 12=RS 3; 13=VD 1; 14=VD 2; 15=VD 3; 16=CT 6; 17=CT 7; 18=CT 8; 19=CT 9; 20=CT 10; 21=VT 5; 22=VT 6; 23=VT 7; 24=VT 8; 25=VT 9; 26=VT 10; 27=RS 4; 28=RS 5; 29=RS 6; 30=RS 7; 31=RS 8; 32=RS 9; 33=RS 10; 34=VD 4; 35=VD 5; 36=VD 6; 37=VD 7; 38=VD 8; 39=VD 9; 40=VD 10; 41=KS 1; 42=KS 2; 43=KS 3; 44=KS 4; 45=KS 5; 46=KS 6; 47=KS 7; 48=KS 8; 49=KS 9; 50=KS 10; 51=GE 1; 52=GE 2; 53=GE 3]

- 0 Read Retain Measuring device

Ch7 meas. device 1V63 MMI,RST Analog channels 0..53[0=Not in use; 1=CT 1; 2=CT 2; 3=CT 3; 4=CT 4; 5=CT 5; 6=VT 1; 7=VT 2; 8=VT 3; 9=VT 4; 10=RS 1; 11=RS 2; 12=RS 3; 13=VD 1; 14=VD 2; 15=VD 3; 16=CT 6; 17=CT 7; 18=CT 8; 19=CT 9; 20=CT 10; 21=VT 5; 22=VT 6; 23=VT 7; 24=VT 8; 25=VT 9; 26=VT 10; 27=RS 4; 28=RS 5; 29=RS 6; 30=RS 7; 31=RS 8; 32=RS 9; 33=RS 10; 34=VD 4; 35=VD 5; 36=VD 6; 37=VD 7; 38=VD 8; 39=VD 9; 40=VD 10; 41=KS 1; 42=KS 2; 43=KS 3; 44=KS 4; 45=KS 5; 46=KS 6; 47=KS 7; 48=KS 8; 49=KS 9; 50=KS 10; 51=GE 1; 52=GE 2; 53=GE 3]

- 0 Read Retain Measuring device

Ch8 meas. device 1V65 MMI,RST Analog channels 0..53[0=Not in use; 1=CT 1; 2=CT 2; 3=CT 3; 4=CT 4; 5=CT 5; 6=VT 1; 7=VT 2; 8=VT 3; 9=VT 4; 10=RS 1; 11=RS 2; 12=RS 3; 13=VD 1; 14=VD 2; 15=VD 3; 16=CT 6; 17=CT 7; 18=CT 8; 19=CT 9; 20=CT 10; 21=VT 5; 22=VT 6; 23=VT 7; 24=VT 8; 25=VT 9; 26=VT 10; 27=RS 4; 28=RS 5; 29=RS 6; 30=RS 7; 31=RS 8; 32=RS 9; 33=RS 10; 34=VD 4; 35=VD 5; 36=VD 6; 37=VD 7; 38=VD 8; 39=VD 9; 40=VD 10; 41=KS 1; 42=KS 2; 43=KS 3; 44=KS 4; 45=KS 5; 46=KS 6; 47=KS 7; 48=KS 8; 49=KS 9; 50=KS 10; 51=GE 1; 52=GE 2; 53=GE 3]

- 0 Read Retain Measuring device

Page 7 of 158

Page 8: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Ch9 meas. device 1V67 MMI,RST Analog channels 0..53[0=Not in use; 1=CT 1; 2=CT 2; 3=CT 3; 4=CT 4; 5=CT 5; 6=VT 1; 7=VT 2; 8=VT 3; 9=VT 4; 10=RS 1; 11=RS 2; 12=RS 3; 13=VD 1; 14=VD 2; 15=VD 3; 16=CT 6; 17=CT 7; 18=CT 8; 19=CT 9; 20=CT 10; 21=VT 5; 22=VT 6; 23=VT 7; 24=VT 8; 25=VT 9; 26=VT 10; 27=RS 4; 28=RS 5; 29=RS 6; 30=RS 7; 31=RS 8; 32=RS 9; 33=RS 10; 34=VD 4; 35=VD 5; 36=VD 6; 37=VD 7; 38=VD 8; 39=VD 9; 40=VD 10; 41=KS 1; 42=KS 2; 43=KS 3; 44=KS 4; 45=KS 5; 46=KS 6; 47=KS 7; 48=KS 8; 49=KS 9; 50=KS 10; 51=GE 1; 52=GE 2; 53=GE 3]

- 0 Read Retain Measuring device

Ch10 meas.device 1V69 MMI,RST Analog channels 0..53[0=Not in use; 1=CT 1; 2=CT 2; 3=CT 3; 4=CT 4; 5=CT 5; 6=VT 1; 7=VT 2; 8=VT 3; 9=VT 4; 10=RS 1; 11=RS 2; 12=RS 3; 13=VD 1; 14=VD 2; 15=VD 3; 16=CT 6; 17=CT 7; 18=CT 8; 19=CT 9; 20=CT 10; 21=VT 5; 22=VT 6; 23=VT 7; 24=VT 8; 25=VT 9; 26=VT 10; 27=RS 4; 28=RS 5; 29=RS 6; 30=RS 7; 31=RS 8; 32=RS 9; 33=RS 10; 34=VD 4; 35=VD 5; 36=VD 6; 37=VD 7; 38=VD 8; 39=VD 9; 40=VD 10; 41=KS 1; 42=KS 2; 43=KS 3; 44=KS 4; 45=KS 5; 46=KS 6; 47=KS 7; 48=KS 8; 49=KS 9; 50=KS 10; 51=GE 1; 52=GE 2; 53=GE 3]

- 0 Read Retain Measuring device

Ch1 signal type 1V52 MMI,RST Analog channels 0..42[0=Not in use; 1=IL1; 2=IL2; 3=IL3; 4=I0; 5=I0b; 6=U0; 7=U12; 8= U23; 9=U31; 10=U12b; 11=U12c; 12=U1; 13=U2 ; 14=U3; 15=U1b; 16=U1c; 17=IL1b; 18=IL2b; 19=IL3b; 20=GE1; 21=GE2; 22=GE3; 23=I0s; 24=U0s; 25=U23b; 26=U31b; 27=U2b; 28=U3b; 29=U0b; 30=I0bs; 31=I0cs; 32=U0bs; 33=U0cs; 34=U12s; 35=U23s; 36=U31s; 37=U12bs; 38=U23bs; 39=U31bs; 40=U12cs; 41=U23cs; 42=U31cs]

- 0 Read Retain Signal type

Ch2 signal type 1V54 MMI,RST Analog channels 0..42[0=Not in use; 1=IL1; 2=IL2; 3=IL3; 4=I0; 5=I0b; 6=U0; 7=U12; 8= U23; 9=U31; 10=U12b; 11=U12c; 12=U1; 13=U2 ; 14=U3; 15=U1b; 16=U1c; 17=IL1b; 18=IL2b; 19=IL3b; 20=GE1; 21=GE2; 22=GE3; 23=I0s; 24=U0s; 25=U23b; 26=U31b; 27=U2b; 28=U3b; 29=U0b; 30=I0bs; 31=I0cs; 32=U0bs; 33=U0cs; 34=U12s; 35=U23s; 36=U31s; 37=U12bs; 38=U23bs; 39=U31bs; 40=U12cs; 41=U23cs; 42=U31cs]

- 0 Read Retain Signal type

Ch3 signal type 1V56 MMI,RST Analog channels 0..42[0=Not in use; 1=IL1; 2=IL2; 3=IL3; 4=I0; 5=I0b; 6=U0; 7=U12; 8= U23; 9=U31; 10=U12b; 11=U12c; 12=U1; 13=U2 ; 14=U3; 15=U1b; 16=U1c; 17=IL1b; 18=IL2b; 19=IL3b; 20=GE1; 21=GE2; 22=GE3; 23=I0s; 24=U0s; 25=U23b; 26=U31b; 27=U2b; 28=U3b; 29=U0b; 30=I0bs; 31=I0cs; 32=U0bs; 33=U0cs; 34=U12s; 35=U23s; 36=U31s; 37=U12bs; 38=U23bs; 39=U31bs; 40=U12cs; 41=U23cs; 42=U31cs]

- 0 Read Retain Signal type

Page 8 of 158

Page 9: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Ch4 signal type 1V58 MMI,RST Analog channels 0..42[0=Not in use; 1=IL1; 2=IL2; 3=IL3; 4=I0; 5=I0b; 6=U0; 7=U12; 8= U23; 9=U31; 10=U12b; 11=U12c; 12=U1; 13=U2 ; 14=U3; 15=U1b; 16=U1c; 17=IL1b; 18=IL2b; 19=IL3b; 20=GE1; 21=GE2; 22=GE3; 23=I0s; 24=U0s; 25=U23b; 26=U31b; 27=U2b; 28=U3b; 29=U0b; 30=I0bs; 31=I0cs; 32=U0bs; 33=U0cs; 34=U12s; 35=U23s; 36=U31s; 37=U12bs; 38=U23bs; 39=U31bs; 40=U12cs; 41=U23cs; 42=U31cs]

- 0 Read Retain Signal type

Ch5 signal type 1V60 MMI,RST Analog channels 0..42[0=Not in use; 1=IL1; 2=IL2; 3=IL3; 4=I0; 5=I0b; 6=U0; 7=U12; 8= U23; 9=U31; 10=U12b; 11=U12c; 12=U1; 13=U2 ; 14=U3; 15=U1b; 16=U1c; 17=IL1b; 18=IL2b; 19=IL3b; 20=GE1; 21=GE2; 22=GE3; 23=I0s; 24=U0s; 25=U23b; 26=U31b; 27=U2b; 28=U3b; 29=U0b; 30=I0bs; 31=I0cs; 32=U0bs; 33=U0cs; 34=U12s; 35=U23s; 36=U31s; 37=U12bs; 38=U23bs; 39=U31bs; 40=U12cs; 41=U23cs; 42=U31cs]

- 0 Read Retain Signal type

Ch6 signal type 1V62 MMI,RST Analog channels 0..42[0=Not in use; 1=IL1; 2=IL2; 3=IL3; 4=I0; 5=I0b; 6=U0; 7=U12; 8= U23; 9=U31; 10=U12b; 11=U12c; 12=U1; 13=U2 ; 14=U3; 15=U1b; 16=U1c; 17=IL1b; 18=IL2b; 19=IL3b; 20=GE1; 21=GE2; 22=GE3; 23=I0s; 24=U0s; 25=U23b; 26=U31b; 27=U2b; 28=U3b; 29=U0b; 30=I0bs; 31=I0cs; 32=U0bs; 33=U0cs; 34=U12s; 35=U23s; 36=U31s; 37=U12bs; 38=U23bs; 39=U31bs; 40=U12cs; 41=U23cs; 42=U31cs]

- 0 Read Retain Signal type

Ch7 signal type 1V64 MMI,RST Analog channels 0..42[0=Not in use; 1=IL1; 2=IL2; 3=IL3; 4=I0; 5=I0b; 6=U0; 7=U12; 8= U23; 9=U31; 10=U12b; 11=U12c; 12=U1; 13=U2 ; 14=U3; 15=U1b; 16=U1c; 17=IL1b; 18=IL2b; 19=IL3b; 20=GE1; 21=GE2; 22=GE3; 23=I0s; 24=U0s; 25=U23b; 26=U31b; 27=U2b; 28=U3b; 29=U0b; 30=I0bs; 31=I0cs; 32=U0bs; 33=U0cs; 34=U12s; 35=U23s; 36=U31s; 37=U12bs; 38=U23bs; 39=U31bs; 40=U12cs; 41=U23cs; 42=U31cs]

- 0 Read Retain Signal type

Ch8 signal type 1V66 MMI,RST Analog channels 0..42[0=Not in use; 1=IL1; 2=IL2; 3=IL3; 4=I0; 5=I0b; 6=U0; 7=U12; 8= U23; 9=U31; 10=U12b; 11=U12c; 12=U1; 13=U2 ; 14=U3; 15=U1b; 16=U1c; 17=IL1b; 18=IL2b; 19=IL3b; 20=GE1; 21=GE2; 22=GE3; 23=I0s; 24=U0s; 25=U23b; 26=U31b; 27=U2b; 28=U3b; 29=U0b; 30=I0bs; 31=I0cs; 32=U0bs; 33=U0cs; 34=U12s; 35=U23s; 36=U31s; 37=U12bs; 38=U23bs; 39=U31bs; 40=U12cs; 41=U23cs; 42=U31cs]

- 0 Read Retain Signal type

Ch9 signal type 1V68 MMI,RST Analog channels 0..42[0=Not in use; 1=IL1; 2=IL2; 3=IL3; 4=I0; 5=I0b; 6=U0; 7=U12; 8= U23; 9=U31; 10=U12b; 11=U12c; 12=U1; 13=U2 ; 14=U3; 15=U1b; 16=U1c; 17=IL1b; 18=IL2b; 19=IL3b; 20=GE1; 21=GE2; 22=GE3; 23=I0s; 24=U0s; 25=U23b; 26=U31b; 27=U2b; 28=U3b; 29=U0b; 30=I0bs; 31=I0cs; 32=U0bs; 33=U0cs; 34=U12s; 35=U23s; 36=U31s; 37=U12bs; 38=U23bs; 39=U31bs; 40=U12cs; 41=U23cs; 42=U31cs]

- 0 Read Retain Signal type

Page 9 of 158

Page 10: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Ch10 signal type 1V70 MMI,RST Analog channels 0..42[0=Not in use; 1=IL1; 2=IL2; 3=IL3; 4=I0; 5=I0b; 6=U0; 7=U12; 8= U23; 9=U31; 10=U12b; 11=U12c; 12=U1; 13=U2 ; 14=U3; 15=U1b; 16=U1c; 17=IL1b; 18=IL2b; 19=IL3b; 20=GE1; 21=GE2; 22=GE3; 23=I0s; 24=U0s; 25=U23b; 26=U31b; 27=U2b; 28=U3b; 29=U0b; 30=I0bs; 31=I0cs; 32=U0bs; 33=U0cs; 34=U12s; 35=U23s; 36=U31s; 37=U12bs; 38=U23bs; 39=U31bs; 40=U12cs; 41=U23cs; 42=U31cs]

- 0 Read Retain Signal type

IL1 pu-scale 1V81 MMI,RST Analog scales 0...6000 A 0 Read Volatile pu-scale of IL1IL2 pu-scale 1V82 MMI,RST Analog scales 0...6000 A 0 Read Volatile pu-scale of IL2IL3 pu-scale 1V83 MMI,RST Analog scales 0...6000 A 0 Read Volatile pu-scale of IL3Io pu-scale 1V84 MMI,RST Analog scales 0...6000 A 0 Read Volatile pu-scale of IoIob pu-scale 1V85 MMI,RST Analog scales 0...6000 A 0 Read Volatile pu-scale of IobUo pu-scale 1V86 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of UoU12 pu-scale 1V87 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U12U23 pu-scale 1V88 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U23U31 pu-scale 1V89 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U31U12b pu-scale 1V90 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U12bU12c pu-scale 1V91 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U12cU1 pu-scale 1V92 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U1U2 pu-scale 1V93 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U2U3 pu-scale 1V94 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U3U1b pu-scale 1V95 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U1bU1c pu-scale 1V96 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U1cIL1b pu-scale 1V97 MMI,RST Analog scales 0...6000 A 0 Read Volatile pu-scale of IL1bIL2b pu-scale 1V98 MMI,RST Analog scales 0...6000 A 0 Read Volatile pu-scale of IL2bIL3b pu-scale 1V99 MMI,RST Analog scales 0...6000 A 0 Read Volatile pu-scale of IL3bIos pu-scale 1V100 MMI,RST Analog scales 0...6000 A 0 Read Volatile pu-scale of virtual Io channelUos pu-scale 1V111 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of virtual Uo channelU23b pu-scale 1V112 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U23bU31b pu-scale 1V113 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U31bU2b pu-scale 1V114 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U2bU3b pu-scale 1V115 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U3bUob pu-scale 1V116 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of UobIoBs pu-scale 1V117 MMI,RST Analog scales 0...6000 A 0 Read Volatile pu-scale of IoBsIoCs pu-scale 1V118 Internal Control setting 0...6000 A 0 Read Volatile pu-scale of IoCsUoBs pu-scale 1V119 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of UoBsUoCs pu-scale 1V120 Internal Control setting 0...440.000 kV 0 Read Volatile pu-scale of UoCsU12s pu-scale 1V121 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U12sU23s pu-scale 1V122 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U23sU31s pu-scale 1V123 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U31sU12Bs pu-scale 1V124 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U12BsU23Bs pu-scale 1V125 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U23BsU31Bs pu-scale 1V126 MMI,RST Analog scales 0...440.000 kV 0 Read Volatile pu-scale of U31BsU12Cs pu-scale 1V127 Internal Control setting 0...440.000 kV 0 Read Volatile pu-scale of U12CsU23Cs pu-scale 1V128 Internal Control setting 0...440.000 kV 0 Read Volatile pu-scale of U23CsU31Cs pu-scale 1V129 Internal Control setting 0...440.000 kV 0 Read Volatile pu-scale of U31CsCPU1 C1 gain 4V1 Internal Control setting 0.95 .. 9.95 ( Acceptance limits are 4.807 +/- 4% ) - 1 Rd/Wr Retain Scal. for raw data (to nominal)CPU1 C2 gain 4V2 Internal Control setting 0.95 .. 9.95 ( Acceptance limits are 4.807 +/- 4% ) - 1 Rd/Wr Retain Scal. for raw data (to nominal)

Page 10 of 158

Page 11: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

CPU1 C3 gain 4V3 Internal Control setting 0.95 .. 9.95 ( Acceptance limits are 4.807 +/- 4% ) - 1 Rd/Wr Retain Scal. for raw data (to nominal)CPU1 C4 gain 4V4 Internal Control setting 0.95 .. 9.95 ( Acceptance limits are 4.807 +/- 4% ) - 1 Rd/Wr Retain Scal. for raw data (to nominal)CPU1 C5 gain 4V5 Internal Control setting 0.95 .. 9.95 ( Acceptance limits are 4.807 +/- 4% ) - 1 Rd/Wr Retain Scal. for raw data (to nominal)CPU1 C6 gain 4V6 Internal Control setting 0.95 .. 9.95 ( Acceptance limits are 4.807 +/- 4% ) - 1 Rd/Wr Retain Scal. for raw data (to nominal)CPU1 C7 gain 4V7 Internal Control setting 0.95 .. 9.95 ( Acceptance limits are 4.807 +/- 4% ) - 1 Rd/Wr Retain Scal. for raw data (to nominal)CPU1 C8 gain 4V8 Internal Control setting 0.95 .. 9.95 ( Acceptance limits are 4.807 +/- 4% ) - 1 Rd/Wr Retain Scal. for raw data (to nominal)CPU1 C9 gain 4V9 Internal Control setting 0.95 .. 9.95 ( Acceptance limits are 4.807 +/- 4% ) - 1 Rd/Wr Retain Scal. for raw data (to nominal)CPU1 C10 gain 4V10 Internal Control setting 0.95 .. 9.95 ( Acceptance limits are 4.807 +/- 4% ) - 1 Rd/Wr Retain Scal. for raw data (to nominal)PGA 1 gain 1 4V21 Internal Control setting 6.3578288e-3 ± 5% - 6,36E-03 Rd/Wr Retain Scal. of ADC1 gainPGA 1 gain 2 4V22 Internal Control setting 1.3034737e-3 ± 5% - 1,30E-03 Rd/Wr Retain Scal. of ADC1 gainPGA 1 gain 3 4V23 Internal Control setting 2.7648995e-4 ± 5% - 2,76E-04 Rd/Wr Retain Scal. of ADC1 gainPGA 1 gain 4 4V24 Internal Control setting 6.5684820e-5 ± 5% - 6,57E-05 Rd/Wr Retain Scal. of ADC1 gainPGA 1 gain 5 4V25 Internal Control setting 1.1579783e-5 ± 5% - 1,16E-05 Rd/Wr Retain Scal. of ADC1 gainPGA 2 gain 1 4V31 Internal Control setting 6.3578288e-3 ± 5% - 6,36E-03 Rd/Wr Retain Scal. of ADC2 gainPGA 2 gain 2 4V32 Internal Control setting 1.3034737e-3 ± 5% - 1,30E-03 Rd/Wr Retain Scal. of ADC2 gainPGA 2 gain 3 4V33 Internal Control setting 2.7648995e-4 ± 5% - 2,76E-04 Rd/Wr Retain Scal. of ADC2 gainPGA 2 gain 4 4V34 Internal Control setting 6.5684820e-5 ± 5% - 6,57E-05 Rd/Wr Retain Scal. of ADC2 gainPGA 2 gain 5 4V35 Internal Control setting 1.1579783e-5 ± 5% - 1,16E-05 Rd/Wr Retain Scal. of ADC2 gainPGA 1 offset 1 4V41 Internal Control setting 0.0 ±3 - 0 Rd/Wr Retain Offs. of ADC1PGA 1 offset 2 4V42 Internal Control setting 0.0 ±4 - 0 Rd/Wr Retain Offs. of ADC1PGA 1 offset 3 4V43 Internal Control setting 0.0 ±6 - 0 Rd/Wr Retain Offs. of ADC1PGA 1 offset 4 4V44 Internal Control setting 0.0 ±25 - 0 Rd/Wr Retain Offs. of ADC1PGA 1 offset 5 4V45 Internal Control setting 0.0 ±140 - 0 Rd/Wr Retain Offs. of ADC1PGA 2 offset 1 4V51 Internal Control setting 0.0 ±3 - 0 Rd/Wr Retain Offs. of ADC2PGA 2 offset 2 4V52 Internal Control setting 0.0 ±4 - 0 Rd/Wr Retain Offs. of ADC2PGA 2 offset 3 4V53 Internal Control setting 0.0 ±6 - 0 Rd/Wr Retain Offs. of ADC2PGA 2 offset 4 4V54 Internal Control setting 0.0 ±25 - 0 Rd/Wr Retain Offs. of ADC2PGA 2 offset 5 4V55 Internal Control setting 0.0 ±140 - 0 Rd/Wr Retain Offs. of ADC2C1 sg1 (RS,VD,KS 4V61 Internal Control setting 0.0...1.1000 - 1 Rd/Wr Retain RS, VD, KS, GE gainC2 sg1 (RS,VD,KS 4V62 Internal Control setting 0.0...1.1000 - 1 Rd/Wr Retain RS, VD, KS, GE gainC3 sg1 (RS,VD,KS 4V63 Internal Control setting 0.0...1.1000 - 1 Rd/Wr Retain RS, VD, KS, GE gainC4 sg1 (RS,VD,KS 4V64 Internal Control setting 0.0...1.1000 - 1 Rd/Wr Retain RS, VD, KS, GE gainC5 sg1 (RS,VD,KS 4V65 Internal Control setting 0.0...1.1000 - 1 Rd/Wr Retain RS, VD, KS, GE gainC6 sg1 (RS,VD,KS 4V66 Internal Control setting 0.0...1.1000 - 1 Rd/Wr Retain RS, VD, KS, GE gainC7 sg1 (RS,VD,KS 4V67 Internal Control setting 0.0...1.1000 - 1 Rd/Wr Retain RS, VD, KS, GE gainC8 sg1 (RS,VD,KS 4V68 Internal Control setting 0.0...1.1000 - 1 Rd/Wr Retain RS, VD, KS, GE gainC9 sg1 (RS,VD,KS 4V69 Internal Control setting 0.0...1.1000 - 1 Rd/Wr Retain RS, VD, KS, GE gainC10 sg1(RS,VD,KS 4V70 Internal Control setting 0.0...1.1000 - 1 Rd/Wr Retain RS, VD, KS, GE gainC1 o1 (All devic 4V71 Internal Control setting ±0.03 - 0 Rd/Wr Retain Offset, all devicesC2 o1 (All devic 4V72 Internal Control setting ±0.03 - 0 Rd/Wr Retain Offset, all devicesC3 o1 (All devic 4V73 Internal Control setting ±0.03 - 0 Rd/Wr Retain Offset, all devicesC4 o1 (All devic 4V74 Internal Control setting ±0.03 - 0 Rd/Wr Retain Offset, all devicesC5 o1 (All devic 4V75 Internal Control setting ±0.03 - 0 Rd/Wr Retain Offset, all devicesC6 o1 (All devic 4V76 Internal Control setting ±0.03 - 0 Rd/Wr Retain Offset, all devicesC7 o1 (All devic 4V77 Internal Control setting ±0.03 - 0 Rd/Wr Retain Offset, all devicesC8 o1 (All devic 4V78 Internal Control setting ±0.03 - 0 Rd/Wr Retain Offset, all devicesC9 o1 (All devic 4V79 Internal Control setting ±0.03 - 0 Rd/Wr Retain Offset, all devicesC10 o1 (All devi 4V80 Internal Control setting ±0.03 - 0 Rd/Wr Retain Offset, all devicesC1 tg1 (CT, VT) 4V81 Internal Control setting 0.9...1.1000 - 1 Rd/Wr Retain Ampl. gain CT(1%*In), VT

Page 11 of 158

Page 12: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

C2 tg1 (CT, VT) 4V82 Internal Control setting 0.9...1.1000 - 1 Rd/Wr Retain Ampl. gain CT(1%*In), VTC3 tg1 (CT, VT) 4V83 Internal Control setting 0.9...1.1000 - 1 Rd/Wr Retain Ampl. gain CT(1%*In), VTC4 tg1 (CT, VT) 4V84 Internal Control setting 0.9...1.1000 - 1 Rd/Wr Retain Ampl. gain CT(1%*In), VTC5 tg1 (CT, VT) 4V85 Internal Control setting 0.9...1.1000 - 1 Rd/Wr Retain Ampl. gain CT(1%*In), VTC6 tg1 (CT, VT) 4V86 Internal Control setting 0.9...1.1000 - 1 Rd/Wr Retain Ampl. gain CT(1%*In), VTC7 tg1 (CT, VT) 4V87 Internal Control setting 0.9...1.1000 - 1 Rd/Wr Retain Ampl. gain CT(1%*In), VTC8 tg1 (CT, VT) 4V88 Internal Control setting 0.9...1.1000 - 1 Rd/Wr Retain Ampl. gain CT(1%*In), VTC9 tg1 (CT, VT) 4V89 Internal Control setting 0.9...1.1000 - 1 Rd/Wr Retain Ampl. gain CT(1%*In), VTC10 tg1 (CT, VT) 4V90 Internal Control setting 0.9...1.1000 - 1 Rd/Wr Retain Ampl. gain CT(1%*In), VTC1 tp1 (CT, VT) 4V91 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(1%*In), VTC2 tp1 (CT, VT) 4V92 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(1%*In), VTC3 tp1 (CT, VT) 4V93 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(1%*In), VTC4 tp1 (CT, VT) 4V94 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(1%*In), VTC5 tp1 (CT, VT) 4V95 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(1%*In), VTC6 tp1 (CT, VT) 4V96 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(1%*In), VTC7 tp1 (CT, VT) 4V97 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(1%*In), VTC8 tp1 (CT, VT) 4V98 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(1%*In), VTC9 tp1 (CT, VT) 4V99 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(1%*In), VTC10 tp1 (CT, VT) 4V100 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(1%*In), VTC1 tg2 (CT) 4V201 Internal Control setting 0.900...1.100 - 1 Rd/Wr Retain Ampl. gain CT(100%*In)C2 tg2 (CT) 4V202 Internal Control setting 0.900...1.100 - 1 Rd/Wr Retain Ampl. gain CT(100%*In)C3 tg2 (CT) 4V203 Internal Control setting 0.900...1.100 - 1 Rd/Wr Retain Ampl. gain CT(100%*In)C4 tg2 (CT) 4V204 Internal Control setting 0.900...1.100 - 1 Rd/Wr Retain Ampl. gain CT(100%*In)C5 tg2 (CT) 4V205 Internal Control setting 0.900...1.100 - 1 Rd/Wr Retain Ampl. gain CT(100%*In)C6 tg2 (CT) 4V206 Internal Control setting 0.900...1.100 - 1 Rd/Wr Retain Ampl. gain CT(100%*In)C7 tg2 (CT) 4V207 Internal Control setting 0.900...1.100 - 1 Rd/Wr Retain Ampl. gain CT(100%*In)C8 tg2 (CT) 4V208 Internal Control setting 0.900...1.100 - 1 Rd/Wr Retain Ampl. gain CT(100%*In)C9 tg2 (CT) 4V209 Internal Control setting 0.900...1.100 - 1 Rd/Wr Retain Ampl. gain CT(100%*In)C10 tg2 (CT) 4V210 Internal Control setting 0.900...1.100 - 1 Rd/Wr Retain Ampl. gain CT(100%*In)Factory setting 4V111 Internal Control setting 0..255[0 = Normal mode; 1 = Autocalibrate PGA and

CPU offsets; 2..11 = Channel gain calibration; 180 = Set integration time]

- 0 Rd/Wr Volatile Factory setting: mode

Factory status 4V112 Internal Control setting 0..2[0 = Idle/wait; 1 = OK; 2 = Error] - 0 Rd/Wr Volatile Factory setting: statusFactory value 4V113 Internal Control setting 0...1000.000 - 1 Rd/Wr Volatile Factory setting: valueFactory samples 4V114 Internal Control setting 0...1000.000 - 0 Rd/Wr Volatile Factory setting: inspectable dataC1 tp2 (CT) 4V121 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(100%*In)C2 tp2 (CT) 4V122 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(100%*In)C3 tp2 (CT) 4V123 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(100%*In)C4 tp2 (CT) 4V124 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(100%*In)C5 tp2 (CT) 4V125 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(100%*In)C6 tp2 (CT) 4V126 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(100%*In)C7 tp2 (CT) 4V127 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(100%*In)C8 tp2 (CT) 4V128 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(100%*In)C9 tp2 (CT) 4V129 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(100%*In)C10 tp2 (CT) 4V130 Internal Control setting -10.00...2.00 Deg. 0 Rd/Wr Retain Phase displ. CT(100%*In)CPU1 C1 offset 4V131 Internal Control setting ±0.012 - 0 Rd/Wr Retain Offset for raw dataCPU1 C2 offset 4V132 Internal Control setting ±0.012 - 0 Rd/Wr Retain Offset for raw dataCPU1 C3 offset 4V133 Internal Control setting ±0.012 - 0 Rd/Wr Retain Offset for raw dataCPU1 C4 offset 4V134 Internal Control setting ±0.012 - 0 Rd/Wr Retain Offset for raw data

Page 12 of 158

Page 13: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

CPU1 C5 offset 4V135 Internal Control setting ±0.012 - 0 Rd/Wr Retain Offset for raw dataCPU1 C6 offset 4V136 Internal Control setting ±0.012 - 0 Rd/Wr Retain Offset for raw dataCPU1 C7 offset 4V137 Internal Control setting ±0.012 - 0 Rd/Wr Retain Offset for raw dataCPU1 C8 offset 4V138 Internal Control setting ±0.012 - 0 Rd/Wr Retain Offset for raw dataCPU1 C9 offset 4V139 Internal Control setting ±0.012 - 0 Rd/Wr Retain Offset for raw dataCPU1 C10 offset 4V140 Internal Control setting ±0.012 - 0 Rd/Wr Retain Offset for raw data

CCODED2 / Rev D CCODED2Second. current 3V1 MMI,RST Current trafo1 0..3[0= 5 A; 1= 2 A; 2= 1 A; 3= 0.2 A] - 0 Rd/Wr Retain Rated secondary current of CT 1Primary current 3V2 MMI,RST Current trafo1 1...6000 A 400 Rd/Wr Retain Rated primary current of CT 1Current terminal 3V3 MMI,RST Current trafo1 0..2[0 = 5 A; 1 = 1 A; 2 = 0.2 A] - 0 Rd/Wr Retain Current terminal of relayCorr. factor 1 3V4 MMI,RST Current trafo1 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V5 MMI,RST Current trafo1 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V6 MMI,RST Current trafo1 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.01 x InDispl. error 2 3V7 MMI,RST Current trafo1 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.01 x InSecond. current 3V11 MMI,RST Current trafo2 0..3[0= 5 A; 1= 2 A; 2= 1 A; 3= 0.2 A] - 0 Rd/Wr Retain Rated secondary current of CT 2Primary current 3V12 MMI,RST Current trafo2 1...6000 A 400 Rd/Wr Retain Rated primary current of CT 2Current terminal 3V13 MMI,RST Current trafo2 0..2[0 = 5 A; 1 = 1 A; 2 = 0.2 A] - 0 Rd/Wr Retain Current terminal of relayCorr. factor 1 3V14 MMI,RST Current trafo2 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V15 MMI,RST Current trafo2 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V16 MMI,RST Current trafo2 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.01 x InDispl. error 2 3V17 MMI,RST Current trafo2 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.01 x InSecond. current 3V21 MMI,RST Current trafo3 0..3[0= 5 A; 1= 2 A; 2= 1 A; 3= 0.2 A] - 0 Rd/Wr Retain Rated secondary current of CT 3Primary current 3V22 MMI,RST Current trafo3 1...6000 A 400 Rd/Wr Retain Rated primary current of CT 3Current terminal 3V23 MMI,RST Current trafo3 0..2[0 = 5 A; 1 = 1 A; 2 = 0.2 A] - 0 Rd/Wr Retain Current terminal of relayCorr. factor 1 3V24 MMI,RST Current trafo3 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V25 MMI,RST Current trafo3 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V26 MMI,RST Current trafo3 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.01 x InDispl. error 2 3V27 MMI,RST Current trafo3 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.01 x InSecond. current 3V31 MMI,RST Current trafo4 0..3[0= 5 A; 1= 2 A; 2= 1 A; 3= 0.2 A] - 0 Rd/Wr Retain Rated secondary current of CT 4Primary current 3V32 MMI,RST Current trafo4 1...6000 A 400 Rd/Wr Retain Rated primary current of CT 4Current terminal 3V33 MMI,RST Current trafo4 0..2[0 = 5 A; 1 = 1 A; 2 = 0.2 A] - 0 Rd/Wr Retain Current terminal of relayCorr. factor 1 3V34 MMI,RST Current trafo4 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V35 MMI,RST Current trafo4 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V36 MMI,RST Current trafo4 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.01 x InDispl. error 2 3V37 MMI,RST Current trafo4 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.01 x InSecond. current 3V41 MMI,RST Current trafo5 0..3[0= 5 A; 1= 2 A; 2= 1 A; 3= 0.2 A] - 0 Rd/Wr Retain Rated secondary current of CT 5Primary current 3V42 MMI,RST Current trafo5 1...6000 A 400 Rd/Wr Retain Rated primary current of CT 5Current terminal 3V43 MMI,RST Current trafo5 0..2[0 = 5 A; 1 = 1 A; 2 = 0.2 A] - 0 Rd/Wr Retain Current terminal of relayCorr. factor 1 3V44 MMI,RST Current trafo5 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V45 MMI,RST Current trafo5 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V46 MMI,RST Current trafo5 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.01 x InDispl. error 2 3V47 MMI,RST Current trafo5 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.01 x InSecond. current 3V151 MMI,RST Current trafo6 0..3[0= 5 A; 1= 2 A; 2= 1 A; 3= 0.2 A] - 0 Rd/Wr Retain Rated secondary current of CT 6Primary current 3V152 MMI,RST Current trafo6 1...6000 A 400 Rd/Wr Retain Rated primary current of CT 6Current terminal 3V153 MMI,RST Current trafo6 0..2[0 = 5 A; 1 = 1 A; 2 = 0.2 A] - 0 Rd/Wr Retain Current terminal of relayCorr. factor 1 3V154 MMI,RST Current trafo6 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V155 MMI,RST Current trafo6 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V156 MMI,RST Current trafo6 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.01 x InDispl. error 2 3V157 MMI,RST Current trafo6 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.01 x In

Page 13 of 158

Page 14: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Second. current 3V161 MMI,RST Current trafo7 0..3[0= 5 A; 1= 2 A; 2= 1 A; 3= 0.2 A] - 0 Rd/Wr Retain Rated secondary current of CT 7Primary current 3V162 MMI,RST Current trafo7 1...6000 A 400 Rd/Wr Retain Rated primary current of CT 7Current terminal 3V163 MMI,RST Current trafo7 0..2[0 = 5 A; 1 = 1 A; 2 = 0.2 A] - 0 Rd/Wr Retain Current terminal of relayCorr. factor 1 3V164 MMI,RST Current trafo7 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V165 MMI,RST Current trafo7 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V166 MMI,RST Current trafo7 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.01 x InDispl. error 2 3V167 MMI,RST Current trafo7 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.01 x InSecond. current 3V171 MMI,RST Current trafo8 0..3[0= 5 A; 1= 2 A; 2= 1 A; 3= 0.2 A] - 0 Rd/Wr Retain Rated secondary current of CT 8Primary current 3V172 MMI,RST Current trafo8 1...6000 A 400 Rd/Wr Retain Rated primary current of CT 8Current terminal 3V173 MMI,RST Current trafo8 0..2[0 = 5 A; 1 = 1 A; 2 = 0.2 A] - 0 Rd/Wr Retain Current terminal of relayCorr. factor 1 3V174 MMI,RST Current trafo8 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V175 MMI,RST Current trafo8 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V176 MMI,RST Current trafo8 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.01 x InDispl. error 2 3V177 MMI,RST Current trafo8 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.01 x InSecond. current 3V181 MMI,RST Current trafo9 0..3[0= 5 A; 1= 2 A; 2= 1 A; 3= 0.2 A] - 0 Rd/Wr Retain Rated secondary current of CT 9Primary current 3V182 MMI,RST Current trafo9 1...6000 A 400 Rd/Wr Retain Rated primary current of CT 9Current terminal 3V183 MMI,RST Current trafo9 0..2[0 = 5 A; 1 = 1 A; 2 = 0.2 A] - 0 Rd/Wr Retain Current terminal of relayCorr. factor 1 3V184 MMI,RST Current trafo9 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V185 MMI,RST Current trafo9 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V186 MMI,RST Current trafo9 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.01 x InDispl. error 2 3V187 MMI,RST Current trafo9 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.01 x InSecond. current 3V191 MMI,RST Current tra.10 0..3[0= 5 A; 1= 2 A; 2= 1 A; 3= 0.2 A] - 0 Rd/Wr Retain Rated secondary current of CT 10Primary current 3V192 MMI,RST Current tra.10 1...6000 A 400 Rd/Wr Retain Rated primary current of CT 10Current terminal 3V193 MMI,RST Current tra.10 0..2[0 = 5 A; 1 = 1 A; 2 = 0.2 A] - 0 Rd/Wr Retain Current terminal of relayCorr. factor 1 3V194 MMI,RST Current tra.10 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V195 MMI,RST Current tra.10 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V196 MMI,RST Current tra.10 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.01 x InDispl. error 2 3V197 MMI,RST Current tra.10 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.01 x InOutput voltage 3V51 MMI,RST Rog. sensor 1 100...300 mV 150 Rd/Wr Retain Rated output voltage of RS 1Rated current 3V52 MMI,RST Rog. sensor 1 1...6000 A 80 Rd/Wr Retain Rated currentCorr. factor 3V53 MMI,RST Rog. sensor 1 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V54 MMI,RST Rog. sensor 1 -1.0000..1.0000 ° 0 Rd/Wr Retain Phase displacement errorOutput voltage 3V61 MMI,RST Rog. sensor 2 100...300 mV 150 Rd/Wr Retain Rated output voltage of RS 2Rated current 3V62 MMI,RST Rog. sensor 2 1...6000 A 80 Rd/Wr Retain Rated currentCorr. factor 3V63 MMI,RST Rog. sensor 2 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V64 MMI,RST Rog. sensor 2 -1.0000..1.0000 ° 0 Rd/Wr Retain Phase displacement errorOutput voltage 3V71 MMI,RST Rog. sensor 3 100...300 mV 150 Rd/Wr Retain Rated output voltage of RS 3Rated current 3V72 MMI,RST Rog. sensor 3 1...6000 A 80 Rd/Wr Retain Rated currentCorr. factor 3V73 MMI,RST Rog. sensor 3 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V74 MMI,RST Rog. sensor 3 -1.0000..1.0000 ° 0 Rd/Wr Retain Phase displacement errorOutput voltage 3V211 MMI,RST Rog. sensor 4 100...300 mV 150 Rd/Wr Retain Rated output voltage of RS 4Rated current 3V212 MMI,RST Rog. sensor 4 1...6000 A 80 Rd/Wr Retain Rated currentCorr. factor 3V213 MMI,RST Rog. sensor 4 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V214 MMI,RST Rog. sensor 4 -1.0000..1.0000 ° 0 Rd/Wr Retain Phase displacement errorOutput voltage 3V221 MMI,RST Rog. sensor 5 100...300 mV 150 Rd/Wr Retain Rated output voltage of RS 5Rated current 3V222 MMI,RST Rog. sensor 5 1...6000 A 80 Rd/Wr Retain Rated currentCorr. factor 3V223 MMI,RST Rog. sensor 5 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V224 MMI,RST Rog. sensor 5 -1.0000..1.0000 ° 0 Rd/Wr Retain Phase displacement errorOutput voltage 3V231 MMI,RST Rog. sensor 6 100...300 mV 150 Rd/Wr Retain Rated output voltage of RS 6

Page 14 of 158

Page 15: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Rated current 3V232 MMI,RST Rog. sensor 6 1...6000 A 80 Rd/Wr Retain Rated currentCorr. factor 3V233 MMI,RST Rog. sensor 6 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V234 MMI,RST Rog. sensor 6 -1.0000..1.0000 ° 0 Rd/Wr Retain Phase displacement errorOutput voltage 3V241 MMI,RST Rog. sensor 7 100...300 mV 150 Rd/Wr Retain Rated output voltage of RS 7Rated current 3V242 MMI,RST Rog. sensor 7 1...6000 A 80 Rd/Wr Retain Rated currentCorr. factor 3V243 MMI,RST Rog. sensor 7 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V244 MMI,RST Rog. sensor 7 -1.0000..1.0000 ° 0 Rd/Wr Retain Phase displacement errorOutput voltage 3V251 MMI,RST Rog. sensor 8 100...300 mV 150 Rd/Wr Retain Rated output voltage of RS 8Rated current 3V252 MMI,RST Rog. sensor 8 1...6000 A 80 Rd/Wr Retain Rated currentCorr. factor 3V253 MMI,RST Rog. sensor 8 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V254 MMI,RST Rog. sensor 8 -1.0000..1.0000 ° 0 Rd/Wr Retain Phase displacement errorOutput voltage 3V261 MMI,RST Rog. sensor 9 100...300 mV 150 Rd/Wr Retain Rated output voltage of RS 9Rated current 3V262 MMI,RST Rog. sensor 9 1...6000 A 80 Rd/Wr Retain Rated currentCorr. factor 3V263 MMI,RST Rog. sensor 9 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V264 MMI,RST Rog. sensor 9 -1.0000..1.0000 ° 0 Rd/Wr Retain Phase displacement errorOutput voltage 3V271 MMI,RST Rog. sensor 10 100...300 mV 150 Rd/Wr Retain Rated output voltage of RS 10Rated current 3V272 MMI,RST Rog. sensor 10 1...6000 A 80 Rd/Wr Retain Rated currentCorr. factor 3V273 MMI,RST Rog. sensor 10 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V274 MMI,RST Rog. sensor 10 -1.0000..1.0000 ° 0 Rd/Wr Retain Phase displacement error

CCODED3 / Rev D CCODED3Second. voltage 3V81 MMI,RST Voltage trafo1 0..4[0 = 100 V; 1 = 110 V; 2 = 115V; 3 = 120 V; 4 =

230V Direct]- 0 Rd/Wr Retain Rated secondary voltage of VT 1

Primary voltage 3V82 MMI,RST Voltage trafo1 0.100...440.000 kV 20 Rd/Wr Retain Rated primary voltageCorr. factor 3V83 MMI,RST Voltage trafo1 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x UnDispl. error 3V84 MMI,RST Voltage trafo1 -2.00...+2.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x UnSecond. voltage 3V91 MMI,RST Voltage trafo2 0..4[0 = 100 V; 1 = 110 V; 2 = 115V; 3 = 120 V; 4 =

230V Direct]- 0 Rd/Wr Retain Rated secondary voltage of VT 2

Primary voltage 3V92 MMI,RST Voltage trafo2 0.100...440.000 kV 20 Rd/Wr Retain Rated primary voltageCorr. factor 3V93 MMI,RST Voltage trafo2 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x UnDispl. error 3V94 MMI,RST Voltage trafo2 -2.00...+2.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x UnSecond. voltage 3V201 MMI,RST Voltage trafo3 0..4[0 = 100 V; 1 = 110 V; 2 = 115V; 3 = 120 V; 4 =

230V Direct]- 0 Rd/Wr Retain Rated secondary voltage of VT 3

Primary voltage 3V202 MMI,RST Voltage trafo3 0.100...440.000 kV 20 Rd/Wr Retain Rated primary voltageCorr. factor 3V203 MMI,RST Voltage trafo3 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x UnDispl. error 3V204 MMI,RST Voltage trafo3 -2.00...+2.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x UnSecond. voltage 3V111 MMI,RST Voltage trafo4 0..4[0 = 100 V; 1 = 110 V; 2 = 115V; 3 = 120 V; 4 =

230V Direct]- 0 Rd/Wr Retain Rated secondary voltage of VT 4

Primary voltage 3V112 MMI,RST Voltage trafo4 0.100...440.000 kV 20 Rd/Wr Retain Rated primary voltageCorr. factor 3V113 MMI,RST Voltage trafo4 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x UnDispl. error 3V114 MMI,RST Voltage trafo4 -2.00...+2.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x UnSecond. voltage 3V281 MMI,RST Voltage trafo5 0..4[0 = 100 V; 1 = 110 V; 2 = 115V; 3 = 120 V; 4 =

230V Direct]- 0 Rd/Wr Retain Rated secondary voltage of VT 5

Primary voltage 3V282 MMI,RST Voltage trafo5 0.100...440.000 kV 20 Rd/Wr Retain Rated primary voltageCorr. factor 3V283 MMI,RST Voltage trafo5 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x UnDispl. error 3V284 MMI,RST Voltage trafo5 -2.00...+2.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x UnSecond. voltage 3V291 MMI,RST Voltage trafo6 0..4[0 = 100 V; 1 = 110 V; 2 = 115V; 3 = 120 V; 4 =

230V Direct]- 0 Rd/Wr Retain Rated secondary voltage of VT 6

Primary voltage 3V292 MMI,RST Voltage trafo6 0.100...440.000 kV 20 Rd/Wr Retain Rated primary voltageCorr. factor 3V293 MMI,RST Voltage trafo6 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x Un

Page 15 of 158

Page 16: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Displ. error 3V294 MMI,RST Voltage trafo6 -2.00...+2.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x UnSecond. voltage 3V301 MMI,RST Voltage trafo7 0..4[0 = 100 V; 1 = 110 V; 2 = 115V; 3 = 120 V; 4 =

230V Direct]- 0 Rd/Wr Retain Rated secondary voltage of VT 7

Primary voltage 3V302 MMI,RST Voltage trafo7 0.100...440.000 kV 20 Rd/Wr Retain Rated primary voltageCorr. factor 3V303 MMI,RST Voltage trafo7 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x UnDispl. error 3V304 MMI,RST Voltage trafo7 -2.00...+2.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x UnSecond. voltage 3V311 MMI,RST Voltage trafo8 0..4[0 = 100 V; 1 = 110 V; 2 = 115V; 3 = 120 V; 4 =

230V Direct]- 0 Rd/Wr Retain Rated secondary voltage of VT 8

Primary voltage 3V312 MMI,RST Voltage trafo8 0.100...440.000 kV 20 Rd/Wr Retain Rated primary voltageCorr. factor 3V313 MMI,RST Voltage trafo8 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x UnDispl. error 3V314 MMI,RST Voltage trafo8 -2.00...+2.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x UnSecond. voltage 3V321 MMI,RST Voltage trafo9 0..4[0 = 100 V; 1 = 110 V; 2 = 115V; 3 = 120 V; 4 =

230V Direct]- 0 Rd/Wr Retain Rated secondary voltage of VT 9

Primary voltage 3V322 MMI,RST Voltage trafo9 0.100...440.000 kV 20 Rd/Wr Retain Rated primary voltageCorr. factor 3V323 MMI,RST Voltage trafo9 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x UnDispl. error 3V324 MMI,RST Voltage trafo9 -2.00...+2.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x UnSecond. voltage 3V331 MMI,RST Voltage tra.10 0..4[0 = 100 V; 1 = 110 V; 2 = 115V; 3 = 120 V; 4 =

230V Direct]- 0 Rd/Wr Retain Rated secondary voltage of VT 10

Primary voltage 3V332 MMI,RST Voltage tra.10 0.100...440.000 kV 20 Rd/Wr Retain Rated primary voltageCorr. factor 3V333 MMI,RST Voltage tra.10 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x UnDispl. error 3V334 MMI,RST Voltage tra.10 -2.00...+2.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x UnDivision ratio 3V121 MMI,RST Volt. divider1 100...20000 - 10000 Rd/Wr Retain Division ratio of VD 1Primary voltage 3V122 MMI,RST Volt. divider1 0.100...440.000 kV 20 Rd/Wr Retain Nominal phase-to-phase voltageCorr. factor 3V123 MMI,RST Volt. divider1 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V124 MMI,RST Volt. divider1 -1.0000...1.0000 ° 0 Rd/Wr Retain Phase displacement errorDivision ratio 3V131 MMI,RST Volt. divider2 100...20000 - 10000 Rd/Wr Retain Division ratio of VD 2Primary voltage 3V132 MMI,RST Volt. divider2 0.100...440.000 kV 20 Rd/Wr Retain Nominal phase-to-phase voltageCorr. factor 3V133 MMI,RST Volt. divider2 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V134 MMI,RST Volt. divider2 -1.0000...1.0000 ° 0 Rd/Wr Retain Phase displacement errorDivision ratio 3V141 MMI,RST Volt. divider3 100...20000 - 10000 Rd/Wr Retain Division ratio of VD 3Primary voltage 3V142 MMI,RST Volt. divider3 0.100...440.000 kV 20 Rd/Wr Retain Nominal phase-to-phase voltageCorr. factor 3V143 MMI,RST Volt. divider3 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V144 MMI,RST Volt. divider3 -1.0000...1.0000 ° 0 Rd/Wr Retain Phase displacement errorDivision ratio 3V341 MMI,RST Volt. divider4 100...20000 - 10000 Rd/Wr Retain Division ratio of VD 4Primary voltage 3V342 MMI,RST Volt. divider4 0.100...440.000 kV 20 Rd/Wr Retain Nominal phase-to-phase voltageCorr. factor 3V343 MMI,RST Volt. divider4 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V344 MMI,RST Volt. divider4 -1.0000...1.0000 ° 0 Rd/Wr Retain Phase displacement errorDivision ratio 3V351 MMI,RST Volt. divider5 100...20000 - 10000 Rd/Wr Retain Division ratio of VD 5Primary voltage 3V352 MMI,RST Volt. divider5 0.100...440.000 kV 20 Rd/Wr Retain Nominal phase-to-phase voltageCorr. factor 3V353 MMI,RST Volt. divider5 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V354 MMI,RST Volt. divider5 -1.0000...1.0000 ° 0 Rd/Wr Retain Phase displacement errorDivision ratio 3V361 MMI,RST Volt. divider6 100...20000 - 10000 Rd/Wr Retain Division ratio of VD 6Primary voltage 3V362 MMI,RST Volt. divider6 0.100...440.000 kV 20 Rd/Wr Retain Nominal phase-to-phase voltageCorr. factor 3V363 MMI,RST Volt. divider6 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V364 MMI,RST Volt. divider6 -1.0000...1.0000 ° 0 Rd/Wr Retain Phase displacement errorDivision ratio 3V371 MMI,RST Volt. divider7 100...20000 - 10000 Rd/Wr Retain Division ratio of VD 7Primary voltage 3V372 MMI,RST Volt. divider7 0.100...440.000 kV 20 Rd/Wr Retain Nominal phase-to-phase voltageCorr. factor 3V373 MMI,RST Volt. divider7 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V374 MMI,RST Volt. divider7 -1.0000...1.0000 ° 0 Rd/Wr Retain Phase displacement error

Page 16 of 158

Page 17: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Division ratio 3V381 MMI,RST Volt. divider8 100...20000 - 10000 Rd/Wr Retain Division ratio of VD 8Primary voltage 3V382 MMI,RST Volt. divider8 0.100...440.000 kV 20 Rd/Wr Retain Nominal phase-to-phase voltageCorr. factor 3V383 MMI,RST Volt. divider8 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V384 MMI,RST Volt. divider8 -1.0000...1.0000 ° 0 Rd/Wr Retain Phase displacement errorDivision ratio 3V391 MMI,RST Volt. divider9 100...20000 - 10000 Rd/Wr Retain Division ratio of VD 9Primary voltage 3V392 MMI,RST Volt. divider9 0.100...440.000 kV 20 Rd/Wr Retain Nominal phase-to-phase voltageCorr. factor 3V393 MMI,RST Volt. divider9 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V394 MMI,RST Volt. divider9 -1.0000...1.0000 ° 0 Rd/Wr Retain Phase displacement errorDivision ratio 3V401 MMI,RST Volt. divid.10 100...20000 - 10000 Rd/Wr Retain Division ratio of VD 10Primary voltage 3V402 MMI,RST Volt. divid.10 0.100...440.000 kV 20 Rd/Wr Retain Nominal phase-to-phase voltageCorr. factor 3V403 MMI,RST Volt. divid.10 0.9000...1.1000 - 1 Rd/Wr Retain Correction factorDispl. error 3V404 MMI,RST Volt. divid.10 -1.0000...1.0000 ° 0 Rd/Wr Retain Phase displacement error

CCODED4 / Rev D CCODED4Second. current 3V411 MMI,RST KOHU/KOKU 1 0[0 = 0.1 A] A 0 Rd/Wr Retain Rated secondary current of KS 1Primary current 3V412 MMI,RST KOHU/KOKU 1 0[0 = 400 A] A 0 Rd/Wr Retain Rated primary current of KS 1Corr. factor 1 3V413 MMI,RST KOHU/KOKU 1 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V414 MMI,RST KOHU/KOKU 1 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V415 MMI,RST KOHU/KOKU 1 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.05 x InDispl. error 2 3V416 MMI,RST KOHU/KOKU 1 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.05 x InSecond. current 3V421 MMI,RST KOHU/KOKU 2 0[0 = 0.1 A] A 0 Rd/Wr Retain Rated secondary current of KS 2Primary current 3V422 MMI,RST KOHU/KOKU 2 0[0 = 400 A] A 0 Rd/Wr Retain Rated primary current of KS 2Corr. factor 1 3V423 MMI,RST KOHU/KOKU 2 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V424 MMI,RST KOHU/KOKU 2 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V425 MMI,RST KOHU/KOKU 2 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.05 x InDispl. error 2 3V426 MMI,RST KOHU/KOKU 2 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.05 x InSecond. current 3V431 MMI,RST KOHU/KOKU 3 0[0 = 0.1 A] A 0 Rd/Wr Retain Rated secondary current of KS 3Primary current 3V432 MMI,RST KOHU/KOKU 3 0[0 = 400 A] A 0 Rd/Wr Retain Rated primary current of KS 3Corr. factor 1 3V433 MMI,RST KOHU/KOKU 3 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V434 MMI,RST KOHU/KOKU 3 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V435 MMI,RST KOHU/KOKU 3 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.05 x InDispl. error 2 3V436 MMI,RST KOHU/KOKU 3 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.05 x InSecond. current 3V441 MMI,RST KOHU/KOKU 4 0[0 = 0.1 A] A 0 Rd/Wr Retain Rated secondary current of KS 4Primary current 3V442 MMI,RST KOHU/KOKU 4 0[0 = 400 A] A 0 Rd/Wr Retain Rated primary current of KS 4Corr. factor 1 3V443 MMI,RST KOHU/KOKU 4 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V444 MMI,RST KOHU/KOKU 4 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V445 MMI,RST KOHU/KOKU 4 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.05 x InDispl. error 2 3V446 MMI,RST KOHU/KOKU 4 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.05 x InSecond. current 3V451 MMI,RST KOHU/KOKU 5 0[0 = 0.1 A] A 0 Rd/Wr Retain Rated secondary current of KS 5Primary current 3V452 MMI,RST KOHU/KOKU 5 0[0 = 400 A] A 0 Rd/Wr Retain Rated primary current of KS 5Corr. factor 1 3V453 MMI,RST KOHU/KOKU 5 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V454 MMI,RST KOHU/KOKU 5 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V455 MMI,RST KOHU/KOKU 5 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.05 x InDispl. error 2 3V456 MMI,RST KOHU/KOKU 5 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.05 x InSecond. current 3V461 MMI,RST KOHU/KOKU 6 0[0 = 0.1 A] A 0 Rd/Wr Retain Rated secondary current of KS 6Primary current 3V462 MMI,RST KOHU/KOKU 6 0[0 = 400 A] A 0 Rd/Wr Retain Rated primary current of KS 6Corr. factor 1 3V463 MMI,RST KOHU/KOKU 6 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V464 MMI,RST KOHU/KOKU 6 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V465 MMI,RST KOHU/KOKU 6 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.05 x InDispl. error 2 3V466 MMI,RST KOHU/KOKU 6 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.05 x In

Page 17 of 158

Page 18: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Second. current 3V471 MMI,RST KOHU/KOKU 7 0[0 = 0.1 A] A 0 Rd/Wr Retain Rated secondary current of KS 7Primary current 3V472 MMI,RST KOHU/KOKU 7 0[0 = 400 A] A 0 Rd/Wr Retain Rated primary current of KS 7Corr. factor 1 3V473 MMI,RST KOHU/KOKU 7 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V474 MMI,RST KOHU/KOKU 7 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V475 MMI,RST KOHU/KOKU 7 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.05 x InDispl. error 2 3V476 MMI,RST KOHU/KOKU 7 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.05 x InSecond. current 3V481 MMI,RST KOHU/KOKU 8 0[0 = 0.1 A] A 0 Rd/Wr Retain Rated secondary current of KS 8Primary current 3V482 MMI,RST KOHU/KOKU 8 0[0 = 400 A] A 0 Rd/Wr Retain Rated primary current of KS 8Corr. factor 1 3V483 MMI,RST KOHU/KOKU 8 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V484 MMI,RST KOHU/KOKU 8 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V485 MMI,RST KOHU/KOKU 8 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.05 x InDispl. error 2 3V486 MMI,RST KOHU/KOKU 8 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.05 x InSecond. current 3V491 MMI,RST KOHU/KOKU 9 0[0 = 0.1 A] A 0 Rd/Wr Retain Rated secondary current of KS 9Primary current 3V492 MMI,RST KOHU/KOKU 9 0[0 = 400 A] A 0 Rd/Wr Retain Rated primary current of KS 9Corr. factor 1 3V493 MMI,RST KOHU/KOKU 9 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V494 MMI,RST KOHU/KOKU 9 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V495 MMI,RST KOHU/KOKU 9 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.05 x InDispl. error 2 3V496 MMI,RST KOHU/KOKU 9 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.05 x InSecond. current 3V501 MMI,RST KOHU/KOKU 10 0[0 = 0.1 A] A 0 Rd/Wr Retain Rated secondary current of KS 10Primary current 3V502 MMI,RST KOHU/KOKU 10 0[0 = 400 A] A 0 Rd/Wr Retain Rated primary current of KS 10Corr. factor 1 3V503 MMI,RST KOHU/KOKU 10 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 1.00 x InDispl. error 1 3V504 MMI,RST KOHU/KOKU 10 -5.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 1.00 x InCorr. factor 2 3V505 MMI,RST KOHU/KOKU 10 0.9000...1.1000 - 1 Rd/Wr Retain Correction factor for amplitude error at 0.05 x InDispl. error 2 3V506 MMI,RST KOHU/KOKU 10 -10.00...0.00 ° 0 Rd/Wr Retain Phase displacement error at 0.05 x InCorr. factor 3V511 MMI,RST General input1 -10000.00000...10000.00000 - 1 Rd/Wr Retain Correction factor of GE 1Offset corr. 3V512 MMI,RST General input1 -10000.00000...10000.00000 - 0 Rd/Wr Retain Offset correctionCorr. factor 3V521 MMI,RST General input2 -10000.00000...10000.00000 - 1 Rd/Wr Retain Correction factor of GE 2Offset corr. 3V522 MMI,RST General input2 -10000.00000...10000.00000 - 0 Rd/Wr Retain Offset correctionCorr. factor 3V531 MMI,RST General input3 -10000.00000...10000.00000 - 1 Rd/Wr Retain Correction factor of GE 3Offset corr. 3V532 MMI,RST General input3 -10000.00000...10000.00000 - 0 Rd/Wr Retain Offset correctionCh1: scaling 3V541 MMI,RST Protected unit 0.500...3.000 - 1 Rd/Wr Retain Scaling factor for protected unitCh2: scaling 3V542 MMI,RST Protected unit 0.500...3.000 - 1 Rd/Wr Retain Scaling factor for protected unitCh3: scaling 3V543 MMI,RST Protected unit 0.500...3.000 - 1 Rd/Wr Retain Scaling factor for protected unitCh4: scaling 3V544 MMI,RST Protected unit 0.500...3.000 - 1 Rd/Wr Retain Scaling factor for protected unitCh5: scaling 3V545 MMI,RST Protected unit 0.500...3.000 - 1 Rd/Wr Retain Scaling factor for protected unitCh6: scaling 3V546 MMI,RST Protected unit 0.500...3.000 - 1 Rd/Wr Retain Scaling factor for protected unitCh7: scaling 3V547 MMI,RST Protected unit 0.500...3.000 - 1 Rd/Wr Retain Scaling factor for protected unitCh8: scaling 3V548 MMI,RST Protected unit 0.500...3.000 - 1 Rd/Wr Retain Scaling factor for protected unitCh9: scaling 3V549 MMI,RST Protected unit 0.500...3.000 - 1 Rd/Wr Retain Scaling factor for protected unitCh10: scaling 3V550 MMI,RST Protected unit 0.500...3.000 - 1 Rd/Wr Retain Scaling factor for protected unit

PS1 / Rev B PS1 PS1 (1MRS500009 & 1MRS500010) module general parametersOutput 1 state 14O001 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 1Output 2 state 14O002 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 2Output 3 state 14O003 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 3Output 4 state 14O004 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 4Output 5 state 14O005 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 5Output 6 state 14O006 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 6Input 1 state 14I001 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 1Input 2 state 14I002 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 2

Page 18 of 158

Page 19: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Input 3 state 14I003 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 3TCS 1 state 14I004 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of Trip Circuit Supervisory 1TCS 2 state 14I005 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of Trip Circuit Supervisory 2Over Tmp 14I006 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of over temperatureACfail 14I007 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of AC failInput 1 valid 14I021 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 1Input 2 valid 14I022 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 2Input 3 valid 14I023 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 3Input 1 counter 14I041 MMI,RST PS1 [4] 0 ... 2147483647 - 0 Read Volatile Count of positive transitions on input 1Input 2 counter 14I042 MMI,RST PS1 [4] 0 ... 2147483647 - 0 Read Volatile Count of positive transitions on input 2Input 3 counter 14I043 MMI,RST PS1 [4] 0 ... 2147483647 - 0 Read Volatile Count of positive transitions on input 3Input 1 preset 14V201 MMI,RST Counter settings 0 ... 2147483647 - 0 Rd/Wr Retain Set value for counter on input 1Input 2 preset 14V202 MMI,RST Counter settings 0 ... 2147483647 - 0 Rd/Wr Retain Set value for counter on input 2Input 3 preset 14V203 MMI,RST Counter settings 0 ... 2147483647 - 0 Rd/Wr Retain Set value for counter on input 3Input 1 filter 14V221 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 1Input 2 filter 14V222 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 2Input 3 filter 14V223 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 3Input 1 invert. 14V281 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 1Input 2 invert. 14V282 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 2Input 3 invert. 14V283 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 3Input 1 mode 14V301 MMI,RST Input mode 1 = Binary input;2 = Counter - 1 Read Retain Mode for input 1Input 2 mode 14V302 MMI,RST Input mode 1 = Binary input;2 = Counter - 1 Read Retain Mode for input 2Input 3 mode 14V303 MMI,RST Input mode 1 = Binary input;2 = Counter - 1 Read Retain Mode for input 3Counter trigger 14V401 MMI,RST Counter settings 0 = clear counters;1 = load updated values;2 = update all

values- 0 Write Volatile Loads the counter Preseted value(s) in to counters

SW version 14V501 MMI,RST PS1 [4] - - 0 Read Volatile Software versionSW revision 14V502 MMI,RST PS1 [4] - - 0 Read Volatile Software revisionEvent mask 1A 14V101 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E31)Event mask 1B 14V102 MMI,RST Event mask 0 ... 7 - 0 Rd/Wr Retain Event mask 1 for event transmission (E32 ... E34)Event mask 2A 14V103 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E31)Event mask 2B 14V104 MMI,RST Event mask 0 ... 7 - 0 Rd/Wr Retain Event mask 2 for event transmission (E32 ... E34)Event mask 3A 14V105 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E31)Event mask 3B 14V106 MMI,RST Event mask 0 ... 7 - 0 Rd/Wr Retain Event mask 3 for event transmission (E32 ... E34)Event mask 4A 14V107 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E31)Event mask 4B 14V108 MMI,RST Event mask 0 ... 7 - 0 Rd/Wr Retain Event mask 4 for event transmission (E32 ... E34)

BIO1 / Rev B BIO1 BIO1 (1MRS050020) module general parametersOutput 1 state 15O001 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 1Output 2 state 15O002 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 2Output 3 state 15O003 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 3Output 4 state 15O004 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 4Output 5 state 15O005 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 5Output 6 state 15O006 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 6Input 1 state 15I001 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 1Input 2 state 15I002 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 2Input 3 state 15I003 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 3Input 4 state 15I004 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 4Input 5 state 15I005 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 5Input 6 state 15I006 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 6Input 7 state 15I007 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 7

Page 19 of 158

Page 20: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Input 8 state 15I008 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 8Input 9 state 15I009 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 9Input 10 state 15I010 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 10Input 11 state 15I011 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 11Input 12 state 15I012 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 12Input 1 valid 15I021 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 1Input 2 valid 15I022 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 2Input 3 valid 15I023 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 3Input 4 valid 15I024 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 4Input 5 valid 15I025 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 5Input 6 valid 15I026 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 6Input 7 valid 15I027 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 7Input 8 valid 15I028 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 8Input 9 valid 15I029 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 9Input 10 valid 15I030 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 10Input 11 valid 15I031 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 11Input 12 valid 15I032 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 12Input 9 counter 15I041 MMI,RST BIO1 [5] 0 ... 2147483647 - 0 Read Volatile Count of positive transitions on input 9Input 10 counter 15I042 MMI,RST BIO1 [5] 0 ... 2147483647 - 0 Read Volatile Count of positive transitions on input 10Input 11 counter 15I043 MMI,RST BIO1 [5] 0 ... 2147483647 - 0 Read Volatile Count of positive transitions on input 11Input 12 counter 15I044 MMI,RST BIO1 [5] 0 ... 2147483647 - 0 Read Volatile Count of positive transitions on input 12Input 9 preset 15V201 MMI,RST Counter settings 0 ... 2147483647 - 0 Rd/Wr Retain Set value for counter on input 9Input 10 preset 15V202 MMI,RST Counter settings 0 ... 2147483647 - 0 Rd/Wr Retain Set value for counter on input 10Input 11 preset 15V203 MMI,RST Counter settings 0 ... 2147483647 - 0 Rd/Wr Retain Set value for counter on input 11Input 12 preset 15V204 MMI,RST Counter settings 0 ... 2147483647 - 0 Rd/Wr Retain Set value for counter on input 12Input 1 filter 15V221 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 1Input 2 filter 15V222 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 2Input 3 filter 15V223 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 3Input 4 filter 15V224 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 4Input 5 filter 15V225 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 5Input 6 filter 15V226 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 6Input 7 filter 15V227 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 7Input 8 filter 15V228 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 8Input 9 filter 15V229 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 9Input 10 filter 15V230 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 10Input 11 filter 15V231 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 11Input 12 filter 15V232 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 12Input 1 invert. 15V281 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 1Input 2 invert. 15V282 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 2Input 3 invert. 15V283 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 3Input 4 invert. 15V284 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 4Input 5 invert. 15V285 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 5Input 6 invert. 15V286 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 6Input 7 invert. 15V287 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 7Input 8 invert. 15V288 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 8Input 9 invert. 15V289 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 9Input 10 invert. 15V290 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 10Input 11 invert. 15V291 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 11Input 12 invert. 15V292 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 12

Page 20 of 158

Page 21: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Input 9 mode 15V309 MMI,RST Input mode 1 = Binary input;2 = Counter - 1 Read Retain Mode for input 9Input 10 mode 15V310 MMI,RST Input mode 1 = Binary input;2 = Counter - 1 Read Retain Mode for input 10Input 11 mode 15V311 MMI,RST Input mode 1 = Binary input;2 = Counter - 1 Read Retain Mode for input 11Input 12 mode 15V312 MMI,RST Input mode 1 = Binary input;2 = Counter - 1 Read Retain Mode for input 12Counter trigger 15V401 MMI,RST Counter settings 0 = clear counters;1 = load updated values;2 = update all

values- 0 Write Volatile Loads the counter Presetted value(s) in to counters

SW version 15V501 MMI,RST BIO1 [5] - - - Read Volatile Software versionSW revision 15V502 MMI,RST BIO1 [5] - - - Read Volatile Software revisionEvent mask 1A 15V101 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E31)Event mask 1B 15V102 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 1 for event transmission (E32 ... E63)Event mask 2A 15V103 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E31)Event mask 2B 15V104 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 2 for event transmission (E32 ... E63)Event mask 3A 15V105 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E31)Event mask 3B 15V106 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 3 for event transmission (E32 ... E63)Event mask 4A 15V107 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E31)Event mask 4B 15V108 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 4 for event transmission (E32 ... E63)

BIO2 / Rev B BIO2 BIO2 (1MRS050000) module general parametersOutput 1 state 17O001 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 1Output 2 state 17O002 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 2Output 3 state 17O003 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 3Output 4 state 17O004 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 4Output 5 state 17O005 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 5Output 6 state 17O006 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary output 6Input 1 state 17I001 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 1Input 2 state 17I002 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 2Input 3 state 17I003 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 3Input 4 state 17I004 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 4Input 5 state 17I005 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 5Input 6 state 17I006 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 6Input 7 state 17I007 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 7Input 8 state 17I008 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 8Input 9 state 17I009 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 9Input 10 state 17I010 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile State of binary input 10Input 1 valid 17I021 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 1Input 2 valid 17I022 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 2Input 3 valid 17I023 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 3Input 4 valid 17I024 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 4Input 5 valid 17I025 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 5Input 6 valid 17I026 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 6Input 7 valid 17I027 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 7Input 8 valid 17I028 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 8Input 9 valid 17I029 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 9Input 10 valid 17I030 Internal Control setting 0 ... 1 - 0 Rd/Wr Volatile Validity of binary input 10Input 9 counter 17I041 MMI,RST BIO2 [7] 0 ... 2147483647 - 0 Read Volatile Count of positive transitions on input 1Input 10 counter 17I042 MMI,RST BIO2 [7] 0 ... 2147483647 - 0 Read Volatile Count of positive transitions on input 2Input 9 preset 17V201 MMI,RST Counter settings 0 ... 2147483647 - 0 Rd/Wr Retain Set value for counter on input 1Input 10 preset 17V202 MMI,RST Counter settings 0 ... 2147483647 - 0 Rd/Wr Retain Set value for counter on input 2Input 1 filter 17V221 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 1Input 2 filter 17V222 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 2

Page 21 of 158

Page 22: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Input 3 filter 17V223 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 3Input 4 filter 17V224 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 4Input 5 filter 17V225 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 5Input 6 filter 17V226 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 6Input 7 filter 17V227 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 7Input 8 filter 17V228 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 8Input 9 filter 17V229 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 9Input 10 filter 17V230 MMI,RST Input filtering 1 ... 15000 ms 5 Rd/Wr Retain Debounce filter time for input 10Input 1 invert. 17V281 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 1Input 2 invert. 17V282 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 2Input 3 invert. 17V283 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 3Input 4 invert. 17V284 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 4Input 5 invert. 17V285 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 5Input 6 invert. 17V286 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 6Input 7 invert. 17V287 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 7Input 8 invert. 17V288 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 8Input 9 invert. 17V289 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 9Input 10 invert. 17V290 MMI,RST Input inversion 0 ... 1 - 0 Read Retain Invert input 10Input 9 mode 17V309 MMI,RST Input mode 1 = Binary input;2 = Counter - 1 Read Retain Mode for input 9Input 10 mode 17V310 MMI,RST Input mode 1 = Binary input;2 = Counter - 1 Read Retain Mode for input 10CountTrigg 17V401 MMI,RST Counter settings 0 = clear counters;1 = load updated values;2 = update all

values- 0 Write Volatile Loads the counter Preseted value(s) in to counters

SW version 17V501 MMI,RST BIO2 [7] - - - Read Volatile Software version (1MRS118xxx)SW revision 17V502 MMI,RST BIO2 [7] - - - Read Volatile Software revision (A)Event mask 1A 17V101 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E31)Event mask 1B 17V102 MMI,RST Event mask 0 ... 4194303 - 0 Rd/Wr Retain Event mask 1 for event transmission (E32 ... E53)Event mask 2A 17V103 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E31)Event mask 2B 17V104 MMI,RST Event mask 0 ... 4194303 - 0 Rd/Wr Retain Event mask 2 for event transmission (E32 ... E53)Event mask 3A 17V105 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E31)Event mask 3B 17V106 MMI,RST Event mask 0 ... 4194303 - 0 Rd/Wr Retain Event mask 3 for event transmission (E32 ... E53)Event mask 4A 17V107 MMI,RST Event mask 0 ... 4294967295 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E31)Event mask 4B 17V108 MMI,RST Event mask 0 ... 4194303 - 0 Rd/Wr Retain Event mask 4 for event transmission (E32 ... E53)

LocalMMI027 / Rev C LocalMMI Graphical MIMIC module (1MRS050132)Menutree 27M300 Internal Control setting 0 - 0 Read Volatile Menutree data. The structure of the menu, no language

depending data.Deutsch 27M004 MMI Languages 0 - 0 Read Volatile Menu file in GermanEnglish 27M001 MMI Languages 0 - 0 Read Volatile Menu file in EnglishSuomi 27M002 MMI Languages 0 - 0 Read Volatile Menu file in FinnishSvenska 27M003 MMI Languages 0 - 0 Read Volatile Menu file in SwedishEvent mask 1 27V101 MMI,RST MIMIC [17] 0..127 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E6)Event mask 2 27V103 MMI,RST MIMIC [17] 0..127 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E6)Event mask 3 27V105 MMI,RST MIMIC [17] 0..127 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E6)Event mask 4 27V107 MMI,RST MIMIC [17] 0..127 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E6)SW version 27V501 MMI,RST MIMIC [17] 0 - 0 Read Retain Software version (1MRSxxxxxx)SW revision 27V502 MMI,RST MIMIC [17] A..Z - 0 Read Retain Software revisioin (A-Z)Default lang. 27V400 Internal Control setting 0..255 - 0 Read Retain Current default language in relay. I.e. Index of language

which is active when relay boots.Language set 27V401 Internal Control setting 0...4294967296 - 0 Read Retain Bitmask which shows the currently loaded languages.ML Init Status 27V402 Internal Control setting 0...4294967296 - 0 Read Retain 32-bit value showing the ML init status.

Page 22 of 158

Page 23: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile ExplanationRTDMA / Rev B RTD1 RTD1 (1MRS050105) module general parameters

Output 1 value 16O001 MMI,RST Output -10000.00000..10000.00 mA 0 Read Volatile Output 1 valueOutput 2 value 16O002 MMI,RST Output -10000.00000..10000.000 mA 0 Read Volatile Output 2 valueOutput 3 value 16O003 MMI,RST Output -10000.00000..10000.000 mA 0 Read Volatile Output 3 valueOutput 4 value 16O004 MMI,RST Output -10000.00000..10000.000 mA 0 Read Volatile Output 4 valueOutput 1 invalid 16I021 MMI,RST Output 0 = Not active; 1 = Active; - 1 Read Volatile Output 1 invalid signalOutput 2 invalid 16I022 MMI,RST Output 0 = Not active; 1 = Active; - 1 Read Volatile Output 2 invalid signalOutput 3 invalid 16I023 MMI,RST Output 0 = Not active; 1 = Active; - 1 Read Volatile Output 3 invalid signalOutput 4 invalid 16I024 MMI,RST Output 0 = Not active; 1 = Active; - 1 Read Volatile Output 4 invalid signalOutput range 16V201 MMI,RST Output 1 0 = 0..20; 1 = 4..20; mA 0 Rd/Wr Retain Output 1 rangeOutput range 16V202 MMI,RST Output 2 0 = 0..20; 1 = 4..20; mA 0 Rd/Wr Retain Output 2 rangeOutput range 16V203 MMI,RST Output 3 0 = 0..20; 1 = 4..20; mA 0 Rd/Wr Retain Output 3 rangeOutput range 16V204 MMI,RST Output 4 0 = 0..20; 1 = 4..20; mA 0 Rd/Wr Retain Output 4 rangeInput 1 value 16I001 MMI,RST Input -10000.00000..10000.000 - 0 Read Volatile Measured value of input 1Input 2 value 16I002 MMI,RST Input -10000.00000..10000.000 - 0 Read Volatile Measured value of input 2Input 3 value 16I003 MMI,RST Input -10000.00000..10000.000 - 0 Read Volatile Measured value of input 3Input 4 value 16I004 MMI,RST Input -10000.00000..10000.000 - 0 Read Volatile Measured value of input 4Input 5 value 16I005 MMI,RST Input -10000.00000..10000.000 - 0 Read Volatile Measured value of input 5Input 6 value 16I006 MMI,RST Input -10000.00000..10000.000 - 0 Read Volatile Measured value of input 6Input 7 value 16I007 MMI,RST Input -10000.00000..10000.000 - 0 Read Volatile Measured value of input 7Input 8 value 16I008 MMI,RST Input -10000.00000..10000.000 - 0 Read Volatile Measured value of input 8Input 1 invalid 16I011 MMI,RST Input 0 = Not active; 1 = Active; - 1 Read Volatile Input 1 invalid signalInput 2 invalid 16I012 MMI,RST Input 0 = Not active; 1 = Active; - 1 Read Volatile Input 2 invalid signalInput 3 invalid 16I013 MMI,RST Input 0 = Not active; 1 = Active; - 1 Read Volatile Input 3 invalid signalInput 4 invalid 16I014 MMI,RST Input 0 = Not active; 1 = Active; - 1 Read Volatile Input 4 invalid signalInput 5 invalid 16I015 MMI,RST Input 0 = Not active; 1 = Active; - 1 Read Volatile Input 5 invalid signalInput 6 invalid 16I016 MMI,RST Input 0 = Not active; 1 = Active; - 1 Read Volatile Input 6 invalid signalInput 7 invalid 16I017 MMI,RST Input 0 = Not active; 1 = Active; - 1 Read Volatile Input 7 invalid signalInput 8 invalid 16I018 MMI,RST Input 0 = Not active; 1 = Active; - 1 Read Volatile Input 8 invalid signalFilter time 16V001 MMI,RST Input 1 0 = 0.4; 1 = 1; 2 = 2; 3 = 3; 4 = 4; 5 = 5; s 5 Rd/Wr Retain Input 1 filter time (step response time)Filter time 16V002 MMI,RST Input 2 0 = 0.4; 1 = 1; 2 = 2; 3 = 3; 4 = 4; 5 = 5; s 5 Rd/Wr Retain Input 2 filter time (step response time)Filter time 16V003 MMI,RST Input 3 0 = 0.4; 1 = 1; 2 = 2; 3 = 3; 4 = 4; 5 = 5; s 5 Rd/Wr Retain Input 3 filter time (step response time)Filter time 16V004 MMI,RST Input 4 0 = 0.4; 1 = 1; 2 = 2; 3 = 3; 4 = 4; 5 = 5; s 5 Rd/Wr Retain Input 4 filter time (step response time)Filter time 16V005 MMI,RST Input 5 0 = 0.4; 1 = 1; 2 = 2; 3 = 3; 4 = 4; 5 = 5; s 5 Rd/Wr Retain Input 5 filter time (step response time)Filter time 16V006 MMI,RST Input 6 0 = 0.4; 1 = 1; 2 = 2; 3 = 3; 4 = 4; 5 = 5; s 5 Rd/Wr Retain Input 6 filter time (step response time)Filter time 16V007 MMI,RST Input 7 0 = 0.4; 1 = 1; 2 = 2; 3 = 3; 4 = 4; 5 = 5; s 5 Rd/Wr Retain Input 7 filter time (step response time)Filter time 16V008 MMI,RST Input 8 0 = 0.4; 1 = 1; 2 = 2; 3 = 3; 4 = 4; 5 = 5; s 5 Rd/Wr Retain Input 8 filter time (step response time)Input mode 16V011 MMI,RST Input 1 0 = Off; 1 = Voltage measurement; 2 = Current

measurement; 3 = 2 wire resistance measurement; 4 = 3 wire resistance measurement; 5 = 2 wire temperature measurement; 6 = 3 wire temperature measurement;

- 0 Rd/Wr Retain Input 1 measurement mode

Input mode 16V012 MMI,RST Input 2 0 = Off; 1 = Voltage measurement; 2 = Current measurement; 3 = 2 wire resistance measurement; 4 = 3 wire resistance measurement; 5 = 2 wire temperature measurement; 6 = 3 wire temperature measurement;

- 0 Rd/Wr Retain Input 2 measurement mode

Input mode 16V013 MMI,RST Input 3 0 = Off; 1 = Voltage measurement; 2 = Current measurement; 3 = 2 wire resistance measurement; 4 = 3 wire resistance measurement; 5 = 2 wire temperature measurement; 6 = 3 wire temperature measurement;

- 0 Rd/Wr Retain Input 3 measurement mode

Page 23 of 158

Page 24: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Input mode 16V014 MMI,RST Input 4 0 = Off; 1 = Voltage measurement; 2 = Current measurement; 3 = 2 wire resistance measurement; 4 = 3 wire resistance measurement; 5 = 2 wire temperature measurement; 6 = 3 wire temperature measurement;

- 0 Rd/Wr Retain Input 4 measurement mode

Input mode 16V015 MMI,RST Input 5 0 = Off; 1 = Voltage measurement; 2 = Current measurement; 3 = 2 wire resistance measurement; 4 = 3 wire resistance measurement; 5 = 2 wire temperature measurement; 6 = 3 wire temperature measurement;

- 0 Rd/Wr Retain Input 5 measurement mode

Input mode 16V016 MMI,RST Input 6 0 = Off; 1 = Voltage measurement; 2 = Current measurement; 3 = 2 wire resistance measurement; 4 = 3 wire resistance measurement; 5 = 2 wire temperature measurement; 6 = 3 wire temperature measurement;

- 0 Rd/Wr Retain Input 6 measurement mode

Input mode 16V017 MMI,RST Input 7 0 = Off; 1 = Voltage measurement; 2 = Current measurement; 3 = 2 wire resistance measurement; 4 = 3 wire resistance measurement; 5 = 2 wire temperature measurement; 6 = 3 wire temperature measurement;

- 0 Rd/Wr Retain Input 7 measurement mode

Input mode 16V018 MMI,RST Input 8 0 = Off; 1 = Voltage measurement; 2 = Current measurement; 3 = 2 wire resistance measurement; 4 = 3 wire resistance measurement; 5 = 2 wire temperature measurement; 6 = 3 wire temperature measurement;

- 0 Rd/Wr Retain Input 8 measurement mode

Voltage range 16V021 MMI,RST Input 1 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 2..10; 5 = -5..5; 6 = -10..10;

V 0 Rd/Wr Retain Input 1 voltage measurement range

Voltage range 16V022 MMI,RST Input 2 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 2..10; 5 = -5..5; 6 = -10..10;

V 0 Rd/Wr Retain Input 2 voltage measurement range

Voltage range 16V023 MMI,RST Input 3 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 2..10; 5 = -5..5; 6 = -10..10;

V 0 Rd/Wr Retain Input 3 voltage measurement range

Voltage range 16V024 MMI,RST Input 4 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 2..10; 5 = -5..5; 6 = -10..10;

V 0 Rd/Wr Retain Input 4 voltage measurement range

Voltage range 16V025 MMI,RST Input 5 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 2..10; 5 = -5..5; 6 = -10..10;

V 0 Rd/Wr Retain Input 5 voltage measurement range

Voltage range 16V026 MMI,RST Input 6 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 2..10; 5 = -5..5; 6 = -10..10;

V 0 Rd/Wr Retain Input 6 voltage measurement range

Voltage range 16V027 MMI,RST Input 7 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 2..10; 5 = -5..5; 6 = -10..10;

V 0 Rd/Wr Retain Input 7 voltage measurement range

Voltage range 16V028 MMI,RST Input 8 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 2..10; 5 = -5..5; 6 = -10..10;

V 0 Rd/Wr Retain Input 8 voltage measurement range

Current range 16V031 MMI,RST Input 1 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 0..20; 5 = 4..20; 6 = -1..1; 7 = -2.5..2.5; 8 = -5..5; 9 = -10..10; 10 = -20..20;

mA 0 Rd/Wr Retain Input 1 current measurement range

Current range 16V032 MMI,RST Input 2 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 0..20; 5 = 4..20; 6 = -1..1; 7 = -2.5..2.5; 8 = -5..5; 9 = -10..10; 10 = -20..20;

mA 0 Rd/Wr Retain Input 2 current measurement range

Current range 16V033 MMI,RST Input 3 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 0..20; 5 = 4..20; 6 = -1..1; 7 = -2.5..2.5; 8 = -5..5; 9 = -10..10; 10 = -20..20;

mA 0 Rd/Wr Retain Input 3 current measurement range

Current range 16V034 MMI,RST Input 4 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 0..20; 5 = 4..20; 6 = -1..1; 7 = -2.5..2.5; 8 = -5..5; 9 = -10..10; 10 = -20..20;

mA 0 Rd/Wr Retain Input 4 current measurement range

Page 24 of 158

Page 25: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Current range 16V035 MMI,RST Input 5 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 0..20; 5 = 4..20; 6 = -1..1; 7 = -2.5..2.5; 8 = -5..5; 9 = -10..10; 10 = -20..20;

mA 0 Rd/Wr Retain Input 5 current measurement range

Current range 16V036 MMI,RST Input 6 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 0..20; 5 = 4..20; 6 = -1..1; 7 = -2.5..2.5; 8 = -5..5; 9 = -10..10; 10 = -20..20;

mA 0 Rd/Wr Retain Input 6 current measurement range

Current range 16V037 MMI,RST Input 7 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 0..20; 5 = 4..20; 6 = -1..1; 7 = -2.5..2.5; 8 = -5..5; 9 = -10..10; 10 = -20..20;

mA 0 Rd/Wr Retain Input 7 current measurement range

Current range 16V038 MMI,RST Input 8 0 = 0..1; 1 = 0..5; 2 = 1..5; 3 = 0..10; 4 = 0..20; 5 = 4..20; 6 = -1..1; 7 = -2.5..2.5; 8 = -5..5; 9 = -10..10; 10 = -20..20;

mA 0 Rd/Wr Retain Input 8 current measurement range

Resistance range 16V041 MMI,RST Input 1 0 = 0..100; 1 = 0..200; 2 = 0..500; 3 = 0..1000; 4 = 0..2000; 5 = 0..5000; 6 = 0..10000;

- 0 Rd/Wr Retain Input 1 resistance measurement range

Resistance range 16V042 MMI,RST Input 2 0 = 0..100; 1 = 0..200; 2 = 0..500; 3 = 0..1000; 4 = 0..2000; 5 = 0..5000; 6 = 0..10000;

- 0 Rd/Wr Retain Input 2 resistance measurement range

Resistance range 16V043 MMI,RST Input 3 0 = 0..100; 1 = 0..200; 2 = 0..500; 3 = 0..1000; 4 = 0..2000; 5 = 0..5000; 6 = 0..10000;

- 0 Rd/Wr Retain Input 3 resistance measurement range

Resistance range 16V044 MMI,RST Input 4 0 = 0..100; 1 = 0..200; 2 = 0..500; 3 = 0..1000; 4 = 0..2000; 5 = 0..5000; 6 = 0..10000;

- 0 Rd/Wr Retain Input 4 resistance measurement range

Resistance range 16V045 MMI,RST Input 5 0 = 0..100; 1 = 0..200; 2 = 0..500; 3 = 0..1000; 4 = 0..2000; 5 = 0..5000; 6 = 0..10000;

- 0 Rd/Wr Retain Input 5 resistance measurement range

Resistance range 16V046 MMI,RST Input 6 0 = 0..100; 1 = 0..200; 2 = 0..500; 3 = 0..1000; 4 = 0..2000; 5 = 0..5000; 6 = 0..10000;

- 0 Rd/Wr Retain Input 6 resistance measurement range

Resistance range 16V047 MMI,RST Input 7 0 = 0..100; 1 = 0..200; 2 = 0..500; 3 = 0..1000; 4 = 0..2000; 5 = 0..5000; 6 = 0..10000;

- 0 Rd/Wr Retain Input 7 resistance measurement range

Resistance range 16V048 MMI,RST Input 8 0 = 0..100; 1 = 0..200; 2 = 0..500; 3 = 0..1000; 4 = 0..2000; 5 = 0..5000; 6 = 0..10000;

- 0 Rd/Wr Retain Input 8 resistance measurement range

Temperat. range 16V051 MMI,RST Input 1 0 = Pt100 -45..150øC; 1 = Pt100 -45..600øC; 2 = Pt250 -45..150øC; 3 = Pt250 -45..600øC; 4 = Pt1000 -45..150øC; 5 = Pt1000 -45..600øC; 6 = Ni100 -45..150øC; 7 = Ni100 -45..250øC; 8 = Ni120 -45..150øC; 9 = Ni120 -45..250øC; 10 = Ni250 -45..150øC; 11 = Ni250 -45..250øC; 12 = Ni1000 -45..150øC; 13 = Ni1000 -45..250øC; 14 = Cu10 -45..150øC; 15 = Ni120US -45..150øC; 16 = Ni120US -45..250øC;

- 0 Rd/Wr Retain Input 1 temperature measurement range

Temperat. range 16V052 MMI,RST Input 2 0 = Pt100 -45..150øC; 1 = Pt100 -45..600øC; 2 = Pt250 -45..150øC; 3 = Pt250 -45..600øC; 4 = Pt1000 -45..150øC; 5 = Pt1000 -45..600øC; 6 = Ni100 -45..150øC; 7 = Ni100 -45..250øC; 8 = Ni120 -45..150øC; 9 = Ni120 -45..250øC; 10 = Ni250 -45..150øC; 11 = Ni250 -45..250øC; 12 = Ni1000 -45..150øC; 13 = Ni1000 -45..250øC; 14 = Cu10 -45..150øC; 15 = Ni120US -45..150øC; 16 = Ni120US -45..250øC;

- 0 Rd/Wr Retain Input 2 temperature measurement range

Page 25 of 158

Page 26: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Temperat. range 16V053 MMI,RST Input 3 0 = Pt100 -45..150øC; 1 = Pt100 -45..600øC; 2 = Pt250 -45..150øC; 3 = Pt250 -45..600øC; 4 = Pt1000 -45..150øC; 5 = Pt1000 -45..600øC; 6 = Ni100 -45..150øC; 7 = Ni100 -45..250øC; 8 = Ni120 -45..150øC; 9 = Ni120 -45..250øC; 10 = Ni250 -45..150øC; 11 = Ni250 -45..250øC; 12 = Ni1000 -45..150øC; 13 = Ni1000 -45..250øC; 14 = Cu10 -45..150øC; 15 = Ni120US -45..150øC; 16 = Ni120US -45..250øC;

- 0 Rd/Wr Retain Input 3 temperature measurement range

Temperat. range 16V054 MMI,RST Input 4 0 = Pt100 -45..150øC; 1 = Pt100 -45..600øC; 2 = Pt250 -45..150øC; 3 = Pt250 -45..600øC; 4 = Pt1000 -45..150øC; 5 = Pt1000 -45..600øC; 6 = Ni100 -45..150øC; 7 = Ni100 -45..250øC; 8 = Ni120 -45..150øC; 9 = Ni120 -45..250øC; 10 = Ni250 -45..150øC; 11 = Ni250 -45..250øC; 12 = Ni1000 -45..150øC; 13 = Ni1000 -45..250øC; 14 = Cu10 -45..150øC; 15 = Ni120US -45..150øC; 16 = Ni120US -45..250øC;

- 0 Rd/Wr Retain Input 4 temperature measurement range

Temperat. range 16V055 MMI,RST Input 5 0 = Pt100 -45..150øC; 1 = Pt100 -45..600øC; 2 = Pt250 -45..150øC; 3 = Pt250 -45..600øC; 4 = Pt1000 -45..150øC; 5 = Pt1000 -45..600øC; 6 = Ni100 -45..150øC; 7 = Ni100 -45..250øC; 8 = Ni120 -45..150øC; 9 = Ni120 -45..250øC; 10 = Ni250 -45..150øC; 11 = Ni250 -45..250øC; 12 = Ni1000 -45..150øC; 13 = Ni1000 -45..250øC; 14 = Cu10 -45..150øC; 15 = Ni120US -45..150øC; 16 = Ni120US -45..250øC;

- 0 Rd/Wr Retain Input 5 temperature measurement range

Temperat. range 16V056 MMI,RST Input 6 0 = Pt100 -45..150øC; 1 = Pt100 -45..600øC; 2 = Pt250 -45..150øC; 3 = Pt250 -45..600øC; 4 = Pt1000 -45..150øC; 5 = Pt1000 -45..600øC; 6 = Ni100 -45..150øC; 7 = Ni100 -45..250øC; 8 = Ni120 -45..150øC; 9 = Ni120 -45..250øC; 10 = Ni250 -45..150øC; 11 = Ni250 -45..250øC; 12 = Ni1000 -45..150øC; 13 = Ni1000 -45..250øC; 14 = Cu10 -45..150øC; 15 = Ni120US -45..150øC; 16 = Ni120US -45..250øC;

- 0 Rd/Wr Retain Input 6 temperature measurement range

Temperat. range 16V057 MMI,RST Input 7 0 = Pt100 -45..150øC; 1 = Pt100 -45..600øC; 2 = Pt250 -45..150øC; 3 = Pt250 -45..600øC; 4 = Pt1000 -45..150øC; 5 = Pt1000 -45..600øC; 6 = Ni100 -45..150øC; 7 = Ni100 -45..250øC; 8 = Ni120 -45..150øC; 9 = Ni120 -45..250øC; 10 = Ni250 -45..150øC; 11 = Ni250 -45..250øC; 12 = Ni1000 -45..150øC; 13 = Ni1000 -45..250øC; 14 = Cu10 -45..150øC; 15 = Ni120US -45..150øC; 16 = Ni120US -45..250øC;

- 0 Rd/Wr Retain Input 7 temperature measurement range

Page 26 of 158

Page 27: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Temperat. range 16V058 MMI,RST Input 8 0 = Pt100 -45..150øC; 1 = Pt100 -45..600øC; 2 = Pt250 -45..150øC; 3 = Pt250 -45..600øC; 4 = Pt1000 -45..150øC; 5 = Pt1000 -45..600øC; 6 = Ni100 -45..150øC; 7 = Ni100 -45..250øC; 8 = Ni120 -45..150øC; 9 = Ni120 -45..250øC; 10 = Ni250 -45..150øC; 11 = Ni250 -45..250øC; 12 = Ni1000 -45..150øC; 13 = Ni1000 -45..250øC; 14 = Cu10 -45..150øC; 15 = Ni120US -45..150øC; 16 = Ni120US -45..250øC;

- 0 Rd/Wr Retain Input 8 temperature measurement range

Threshold value 16V061 MMI,RST Input 1 0.1..10.0 % 0,1 Rd/Wr Retain Input 1 threshold value for updating of measured valueThreshold value 16V062 MMI,RST Input 2 0.1..10.0 % 0,1 Rd/Wr Retain Input 2 threshold value for updating of measured valueThreshold value 16V063 MMI,RST Input 3 0.1..10.0 % 0,1 Rd/Wr Retain Input 3 threshold value for updating of measured valueThreshold value 16V064 MMI,RST Input 4 0.1..10.0 % 0,1 Rd/Wr Retain Input 4 threshold value for updating of measured valueThreshold value 16V065 MMI,RST Input 5 0.1..10.0 % 0,1 Rd/Wr Retain Input 5 threshold value for updating of measured valueThreshold value 16V066 MMI,RST Input 6 0.1..10.0 % 0,1 Rd/Wr Retain Input 6 threshold value for updating of measured valueThreshold value 16V067 MMI,RST Input 7 0.1..10.0 % 0,1 Rd/Wr Retain Input 7 threshold value for updating of measured valueThreshold value 16V068 MMI,RST Input 8 0.1..10.0 % 0,1 Rd/Wr Retain Input 8 threshold value for updating of measured valueInput low limit 16V071 MMI,RST Input 1 -10000.00000..10000.000 - -4 Rd/Wr Retain Input 1 valid range low limitInput low limit 16V072 MMI,RST Input 2 -10000.00000..10000.000 - -4 Rd/Wr Retain Input 2 valid range low limitInput low limit 16V073 MMI,RST Input 3 -10000.00000..10000.000 - -4 Rd/Wr Retain Input 3 valid range low limitInput low limit 16V074 MMI,RST Input 4 -10000.00000..10000.000 - -4 Rd/Wr Retain Input 4 valid range low limitInput low limit 16V075 MMI,RST Input 5 -10000.00000..10000.000 - -4 Rd/Wr Retain Input 5 valid range low limitInput low limit 16V076 MMI,RST Input 6 -10000.00000..10000.000 - -4 Rd/Wr Retain Input 6 valid range low limitInput low limit 16V077 MMI,RST Input 7 -10000.00000..10000.000 - -4 Rd/Wr Retain Input 7 valid range low limitInput low limit 16V078 MMI,RST Input 8 -10000.00000..10000.000 - -4 Rd/Wr Retain Input 8 valid range low limitInput high limit 16V081 MMI,RST Input 1 -10000.00000..10000.000 - 104 Rd/Wr Retain Input 1 valid range high limitInput high limit 16V082 MMI,RST Input 2 -10000.00000..10000.000 - 104 Rd/Wr Retain Input 2 valid range high limitInput high limit 16V083 MMI,RST Input 3 -10000.00000..10000.000 - 104 Rd/Wr Retain Input 3 valid range high limitInput high limit 16V084 MMI,RST Input 4 -10000.00000..10000.000 - 104 Rd/Wr Retain Input 4 valid range high limitInput high limit 16V085 MMI,RST Input 5 -10000.00000..10000.000 - 104 Rd/Wr Retain Input 5 valid range high limitInput high limit 16V086 MMI,RST Input 6 -10000.00000..10000.000 - 104 Rd/Wr Retain Input 6 valid range high limitInput high limit 16V087 MMI,RST Input 7 -10000.00000..10000.000 - 104 Rd/Wr Retain Input 7 valid range high limitInput high limit 16V088 MMI,RST Input 8 -10000.00000..10000.000 - 104 Rd/Wr Retain Input 8 valid range high limitLinear. curve 16V091 MMI,RST Input 1 0 = Disabled; 1 = Enabled - 0 Rd/Wr Retain Input 1 user linearization curveLinear. curve 16V092 MMI,RST Input 2 0 = Disabled; 1 = Enabled - 0 Rd/Wr Retain Input 2 user linearization curveLinear. curve 16V093 MMI,RST Input 3 0 = Disabled; 1 = Enabled - 0 Rd/Wr Retain Input 3 user linearization curveLinear. curve 16V094 MMI,RST Input 4 0 = Disabled; 1 = Enabled - 0 Rd/Wr Retain Input 4 user linearization curveLinear. curve 16V095 MMI,RST Input 5 0 = Disabled; 1 = Enabled - 0 Rd/Wr Retain Input 5 user linearization curveLinear. curve 16V096 MMI,RST Input 6 0 = Disabled; 1 = Enabled - 0 Rd/Wr Retain Input 6 user linearization curveLinear. curve 16V097 MMI,RST Input 7 0 = Disabled; 1 = Enabled - 0 Rd/Wr Retain Input 7 user linearization curveLinear. curve 16V098 MMI,RST Input 8 0 = Disabled; 1 = Enabled - 0 Rd/Wr Retain Input 8 user linearization curveSW version 16V501 MMI,RST RTD1 [6] - - 0 Read Volatile Software versionSW revision 16V502 MMI,RST RTD1 [6] - - 0 Read Volatile Software revisionLin. data file 16M001 Internal Control setting - - - Rd/Wr Retain INTERNAL USE / POD GENERATIONLin. file set 16V601 Internal Control setting - - 0 Rd/Wr Volatile INTERNAL USE / POD GENERATIONEvent mask 1 16V101 MMI,RST Event mask 0..255 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E7)Event mask 2 16V103 MMI,RST Event mask 0..255 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E7)Event mask 3 16V105 MMI,RST Event mask 0..255 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E7)Event mask 4 16V107 MMI,RST Event mask 0..255 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E7)

Page 27 of 158

Page 28: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation100028 / Rev A MMIWAKE

Event mask 1 28V101 MMI,RST Control setting 0...2 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0...E1)Event mask 2 28V103 MMI,RST Control setting 0...2 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0...E1)Event mask 3 28V105 MMI,RST Control setting 0...2 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0...E1)Event mask 4 28V107 MMI,RST Control setting 0...2 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0...E1)

100029 / Rev A INDRESETEvent mask 1 29V101 MMI,RST Control setting 0...42 - 42 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E5)Event mask 2 29V103 MMI,RST Control setting 0...42 - 42 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E5)Event mask 3 29V105 MMI,RST Control setting 0...42 - 42 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E5)Event mask 4 29V107 MMI,RST Control setting 0...42 - 42 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E5)

100030/1 / Rev B SWGRP1Checksum 30S1 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP1Checksum 30S41 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP1Checksum 30S71 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP1Group selection 30V1 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP1

100030/2 / Rev B SWGRP2Checksum 30S2 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP2Checksum 30S42 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP2Checksum 30S72 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP2Group selection 30V2 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP2

100030/3 / Rev B SWGRP3Checksum 30S3 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP3Checksum 30S43 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP3Checksum 30S73 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP3Group selection 30V3 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP3

100030/4 / Rev B SWGRP4Checksum 30S4 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP4Checksum 30S44 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP4Checksum 30S74 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP4Group selection 30V4 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP4

100030/5 / Rev B SWGRP5Checksum 30S5 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP5Checksum 30S45 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP5Checksum 30S75 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP5Group selection 30V5 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP5

100030/6 / Rev B SWGRP6Checksum 30S6 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP6Checksum 30S46 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP6Checksum 30S76 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP6Group selection 30V6 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP6

100030/7 / Rev B SWGRP7Checksum 30S7 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP7Checksum 30S47 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP7

Page 28 of 158

Page 29: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Checksum 30S77 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP7Group selection 30V7 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP7

100030/8 / Rev B SWGRP8Checksum 30S8 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP8Checksum 30S48 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP8Checksum 30S78 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP8Group selection 30V8 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP8

100030/9 / Rev B SWGRP9Checksum 30S9 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP9Checksum 30S49 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP9Checksum 30S79 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP9Group selection 30V9 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP9

100030/10 / Rev B SWGRP10Checksum 30S10 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP10Checksum 30S50 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP10Checksum 30S80 MMI,RST Setting group2 0...255 - 0...255 Rd/Wr Retain Checksum2 of switching group SWGRP10Group selection 30V10 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP10

100030/11 / Rev B SWGRP11Checksum 30S11 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP11Checksum 30S51 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP11Checksum 30S81 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP11Group selection 30V11 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP11

100030/12 / Rev B SWGRP12Checksum 30S12 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP12Checksum 30S52 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP12Checksum 30S82 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP12Group selection 30V12 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP12

100030/13 / Rev B SWGRP13Checksum 30S13 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP13Checksum 30S53 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP13Checksum 30S83 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP13Group selection 30V13 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP13

100030/14 / Rev B SWGRP14Checksum 30S14 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP14Checksum 30S54 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP14Checksum 30S84 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP14Group selection 30V14 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP14

100030/15 / Rev B SWGRP15Checksum 30S15 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP15Checksum 30S55 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP15Checksum 30S85 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP15

Page 29 of 158

Page 30: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Group selection 30V15 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP input]

- 2 Rd/Wr Retain Checksum selection of switching group SWGRP15

100030/16 / Rev B SWGRP16Checksum 30S16 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP16Checksum 30S56 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP16Checksum 30S86 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP16Group selection 30V16 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP16

100030/17 / Rev B SWGRP17Checksum 30S17 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP17Checksum 30S57 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP17Checksum 30S87 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP17Group selection 30V17 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP17

100030/18 / Rev B SWGRP18Checksum 30S18 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP18Checksum 30S58 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP18Checksum 30S88 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP18Group selection 30V18 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP18

100030/19 / Rev B SWGRP19Checksum 30S19 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP19Checksum 30S59 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP19Checksum 30S89 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP19Group selection 30V19 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP19

100030/20 / Rev B SWGRP20Checksum 30S20 MMI,RST Actual setting 0...255 - 0 Read Volatile Ruling checksum of SWGRP20Checksum 30S60 MMI,RST Setting group1 0...255 - 0 Rd/Wr Retain Checksum1 of switching group SWGRP20Checksum 30S90 MMI,RST Setting group2 0...255 - 0 Rd/Wr Retain Checksum2 of switching group SWGRP20Group selection 30V20 MMI,RST Control setting 0..2[0 = Checksum 1; 1 = Checksum 2; 2 = GROUP

input]- 2 Rd/Wr Retain Checksum selection of switching group SWGRP20

100031 / Rev D NOC3LowOperation mode 31S1 MMI,RST Actual setting 0..15[0 = Not in use; 1 = Definite time; 2 = Extremely

inv.; 3 = Very inverse; 4 = Normal inverse; 5 = Long-timeinv.; 6 = RI-type inverse; 7 = RD-type inverse; 8 = IEEE Ext. inv.; 9 = IEEE Very inv.; 10 = IEEE Inverse; 11 = IEEE S.T. inv.; 12 = IEEE S.T.E. inv; 13 = IEEE L.T.E. inv; 14 = IEEE L.T.V. inv; 15 = IEEE L.T. inv.]

- 1 Read Volatile Selection of operate mode and inverse time characteristic

Start current 31S2 MMI,RST Actual setting 0.10...5.00 x In 0,1 Read Volatile Start currentOperate time 31S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DTmodeTime multiplier 31S4 MMI,RST Actual setting 0.05...1.00 - 0,05 Read Volatile Time multiplier at IDMT modeIEEE time dial 31S5 MMI,RST Actual setting 0.5...15.0 - 0,5 Read Volatile IEEE time dial at IDMT modeOperation mode 31S41 MMI,RST Setting group1 0..15[0 = Not in use; 1 = Definite time; 2 = Extremely

inv.; 3 = Very inverse; 4 = Normal inverse; 5 = Long-timeinv.; 6 = RI-type inverse; 7 = RD-type inverse; 8 = IEEE Ext. inv.; 9 = IEEE Very inv.; 10 = IEEE Inverse; 11 = IEEE S.T. inv.; 12 = IEEE S.T.E. inv; 13 = IEEE L.T.E. inv; 14 = IEEE L.T.V. inv; 15 = IEEE L.T. inv.]

- 1 Rd/Wr Retain Selection of operate mode and inverse time characteristic at IDMT mode

Page 30 of 158

Page 31: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Start current 31S42 MMI,RST Setting group1 0.10...5.00 x In 0,1 Rd/Wr Retain Start currentOperate time 31S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeTime multiplier 31S44 MMI,RST Setting group1 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeIEEE time dial 31S45 MMI,RST Setting group1 0.5...15.0 - 0,5 Rd/Wr Retain IEEE time dial at IDMT modeOperation mode 31S71 MMI,RST Setting group2 0..15[0 = Not in use; 1 = Definite time; 2 = Extremely

inv.; 3 = Very inverse; 4 = Normal inverse; 5 = Long-timeinv.; 6 = RI-type inverse; 7 = RD-type inverse; 8 = IEEE Ext. inv.; 9 = IEEE Very inv.; 10 = IEEE Inverse; 11 = IEEE S.T. inv.; 12 = IEEE S.T.E. inv; 13 = IEEE L.T.E. inv; 14 = IEEE L.T.V. inv; 15 = IEEE L.T. inv.]

- 1 Rd/Wr Retain Selection of operate mode and inverse time characteristic at IDMT mode

Start current 31S72 MMI,RST Setting group2 0.10...5.00 x In 0,1 Rd/Wr Retain Start currentOperate time 31S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeTime multiplier 31S74 MMI,RST Setting group2 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeIEEE time dial 31S75 MMI,RST Setting group2 0.5...15.0 - 0,5 Rd/Wr Retain IEEE time dial at IDMT modeMeasuring mode 31V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 0 Rd/Wr Retain Selection of measuring modeDrop-off time 31V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of the operate time counter at DT modeGroup selection 31V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 31V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 31V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 31V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 31V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPMinimum time 31V8 MMI,RST Control setting 0.03...10.00 s 0,03 Rd/Wr Retain Minimum operate time at IDMT modeCBFP time 31V9 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 31V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 31V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 31V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 31V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 31V101 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 31V103 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 31V105 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 31V107 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Current IL1 31I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 31I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 31I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Input BS1 31I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 31I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 31I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 31I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input DOUBLE 31I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for doubling the set start currentInput BSREG 31I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 31I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

NOC3LowOutput START 31O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 31O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput CBFP 31O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalDate 31V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 31V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 31V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 31V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1

Page 31 of 158

Page 32: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

IL2 mean 31V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 31V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 31V207 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 31V208 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 31V209 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL3BS1 31V210 MMI,RST Recorded data1 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of BS1 inputBS2 31V211 MMI,RST Recorded data1 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of BS2 inputDOUBLE 31V212 MMI,RST Recorded data1 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of DOUBLE inputActive group 31V213 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 31V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 31V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 31V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 31V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 31V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 31V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 31V307 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 31V308 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 31V309 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL3BS1 31V310 MMI,RST Recorded data2 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of BS1 inputBS2 31V311 MMI,RST Recorded data2 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of BS2 inputDOUBLE 31V312 MMI,RST Recorded data2 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of DOUBLE inputActive group 31V313 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 31V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 31V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 31V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 31V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 31V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 31V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 31V407 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 31V408 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 31V409 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL3BS1 31V410 MMI,RST Recorded data3 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of BS1 inputBS2 31V411 MMI,RST Recorded data3 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of BS2 inputDOUBLE 31V412 MMI,RST Recorded data3 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of DOUBLE inputActive group 31V413 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100032 / Rev C NOC3HighOperation mode 32S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Read Volatile Selection of operate modeStart current 32S2 MMI,RST Actual setting 0.10...40.00 x In 0,1 Read Volatile Start currentOperate time 32S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DTmodeOperation mode 32S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 32S42 MMI,RST Setting group1 0.10...40.00 x In 0,1 Rd/Wr Retain Start currentOperate time 32S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeOperation mode 32S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 32S72 MMI,RST Setting group2 0.10...40.00 x In 0,1 Rd/Wr Retain Start currentOperate time 32S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeMeasuring mode 32V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 0 Rd/Wr Retain Selection of measuringmodeDrop-off time 32V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of the operate time counterGroup selection 32V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 32V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting group

Page 32 of 158

Page 33: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Start pulse 32V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 32V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 32V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 32V8 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 32V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 32V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 32V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 32V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 32V101 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E13)Event mask 2 32V103 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E13)Event mask 3 32V105 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E13)Event mask 4 32V107 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E13)Current IL1 32I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 32I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 32I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Input BS1 32I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 32I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 32I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 32I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input DOUBLE 32I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for doubling the set start currentInput BSREG 32I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 32I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

NOC3HighOutput BSOUT 32O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of BSOUT signalOutput START 32O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 32O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput CBFP 32O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalDate 32V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 32V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 32V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 32V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 32V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 32V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 32V207 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 32V208 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 32V209 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL3BS1 32V210 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 32V211 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 32V212 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 32V213 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 32V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 32V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 32V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 32V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 32V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 32V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 32V307 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 32V308 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 32V309 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL3

Page 33 of 158

Page 34: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

BS1 32V310 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 32V311 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 32V312 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 32V313 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 32V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 32V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 32V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 32V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 32V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 32V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 32V407 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 32V408 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 32V409 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL3BS1 32V410 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 32V411 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 32V412 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 32V413 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100033 / Rev C NOC3InstOperation mode 33S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Read Volatile Selection of operation modeStart current 33S2 MMI,RST Actual setting 0.10...40.00 x In 0,1 Read Volatile Start currentOperate time 33S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DT modeOperation mode 33S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 33S42 MMI,RST Setting group1 0.10...40.00 x In 0,1 Rd/Wr Retain Start currentOperate time 33S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeOperation mode 33S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 33S72 MMI,RST Setting group2 0.10...40.00 x In 0,1 Rd/Wr Retain Start currentOperate time 33S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeMeasuring mode 33V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 0 Rd/Wr Retain Selection of measuringmodeDrop-off time 33V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of the operate time counterGroup selection 33V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 33V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 33V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 33V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 33V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 33V8 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 33V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 33V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 33V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 33V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 33V101 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E13)Event mask 2 33V103 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E13)Event mask 3 33V105 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E13)Event mask 4 33V107 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E13)Current IL1 33I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 33I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 33I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Input BS1 33I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 33I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 33I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registers

Page 34 of 158

Page 35: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Input GROUP 33I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input DOUBLE 33I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for doubling the set start currentInput BSREG 33I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 33I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

NOC3InstOutput BSOUT 33O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of BSOUT signalOutput START 33O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 33O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput CBFP 33O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalDate 33V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 33V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 33V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 33V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 33V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 33V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 33V207 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 33V208 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 33V209 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL3BS1 33V210 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 33V211 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 33V212 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 33V213 MMI,RST Recorded data1 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 33V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 33V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 33V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 33V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 33V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 33V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 33V307 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 33V308 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 33V309 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL3BS1 33V310 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 33V311 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 33V312 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 33V313 MMI,RST Recorded data2 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 33V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 33V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 33V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 33V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 33V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 33V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 33V407 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 33V408 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 33V409 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL3BS1 33V410 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 33V411 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 33V412 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 33V413 MMI,RST Recorded data3 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting group

100034 / Rev D Inrush3

Page 35 of 158

Page 36: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Operation mode 34S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Inrush mode; 2 = Start-up mode] - 1 Read Volatile Selection of operation modeRatio I2f/I1f> 34S2 MMI,RST Actual setting 5...50 % 15 Read Volatile Inrush blocking limit I2f/I1fStart current 34S3 MMI,RST Actual setting 0.10...5.00 x In 0,1 Read Volatile Motor start currentOperation mode 34S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Inrush mode; 2 = Start-up mode] - 1 Rd/Wr Retain Selection of operation modeRatio I2f/I1f> 34S42 MMI,RST Setting group1 5...50 % 15 Rd/Wr Retain Inrush blocking limit I2f/I1fStart current 34S43 MMI,RST Setting group1 0.10...5.00 x In 0,1 Rd/Wr Retain Motor start currentOperation mode 34S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Inrush mode; 2 = Start-up mode] - 1 Rd/Wr Retain Selection of operation modeRatio I2f/I1f> 34S72 MMI,RST Setting group2 5...50 % 15 Rd/Wr Retain Inrush blocking limit I2f/I1fStart current 34S73 MMI,RST Setting group2 0.10...5.00 x In 0,1 Rd/Wr Retain Motor start currentRising time 34V1 MMI,RST Control setting 20...60 ms 20 Rd/Wr Retain Rising time for phase currents (motor start-up mode)Group selection 34V2 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 34V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 34V4 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of signal STARTReset registers 34V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of registersTest START 34V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTEvent mask 1 34V101 MMI,RST Control setting 0...15 - 3 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 34V103 MMI,RST Control setting 0...15 - 3 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 34V105 MMI,RST Control setting 0...15 - 3 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 34V107 MMI,RST Control setting 0...15 - 3 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)Current IL1 34I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 34I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 34I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Input GROUP 34I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 34I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting registersOutput START 34O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of signal STARTDate 34V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 34V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 34V203 MMI,RST Recorded data1 0.0...60.0 s 0 Read Retain Duration of start situationAverage IL1 34V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Average value of IL1Average IL2 34V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Average value of IL2Average IL3 34V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Average value of IL3Min. I2f/I1f L1 34V207 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Minimum I2f/I1f of IL1Min. I2f/I1f L2 34V208 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Minimum I2f/I1f of IL2Min. I2f/I1f L3 34V209 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Minimum I2f/I1f of IL3Active group 34V210 MMI,RST Recorded data1 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 34V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 34V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 34V303 MMI,RST Recorded data2 0.0...60.0 s 0 Read Retain Duration of start situationAverage IL1 34V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Average value of IL1Average IL2 34V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Average value of IL2Average IL3 34V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Average value of IL3Min. I2f/I1f L1 34V307 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Minimum I2f/I1f of IL1Min. I2f/I1f L2 34V308 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Minimum I2f/I1f of IL2Min. I2f/I1f L3 34V309 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Minimum I2f/I1f of IL3Active group 34V310 MMI,RST Recorded data2 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 34V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 34V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 34V403 MMI,RST Recorded data3 0.0...60.0 s 0 Read Retain Duration of start situationAverage IL1 34V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Average value of IL1

Page 36 of 158

Page 37: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Average IL2 34V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Average value of IL2Average IL3 34V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Average value of IL3Min. I2f/I1f L1 34V407 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Minimum I2f/I1f of IL1Min. I2f/I1f L2 34V408 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Minimum I2f/I1f of IL2Min. I2f/I1f L3 34V409 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Minimum I2f/I1f of IL3Active group 34V410 MMI,RST Recorded data3 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting group

100035 / Rev E DOC6LowOperation mode 35S1 MMI,RST Actual setting 0..7[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.;6 = RI-type inverse; 7 = RD-type inverse]

- 1 Read Volatile Selection of operation mode and inverse time characteristic at IDMT mode

Start current 35S2 MMI,RST Actual setting 0.05...40.00 x In 0,05 Read Volatile Start currentOperate time 35S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DTmodeTime multiplier 35S4 MMI,RST Actual setting 0.05...1.00 - 0,05 Read Volatile Time multiplier at IDMT modeBasic angle ïb 35S5 MMI,RST Actual setting 0...90 ° 60 Read Volatile Basic angle jb for directional operationOper. direction 35S6 MMI,RST Actual setting 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Selection of forward/reverse operationEarth fault pr. 35S7 MMI,RST Actual setting 0..1[0 = Disabled; 1 = Enabled] - 0 Read Volatile Earth fault protectionOperation mode 35S41 MMI,RST Setting group1 0..7[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.;6 = RI-type inverse; 7 = RD-type inverse]

- 1 Rd/Wr Retain Selection of operation mode and inverse time characteristic at IDMT mode

Start current 35S42 MMI,RST Setting group1 0.05...40.00 x In 0,05 Rd/Wr Retain Start currentOperate time 35S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeTime multiplier 35S44 MMI,RST Setting group1 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeBasic angle ïb 35S45 MMI,RST Setting group1 0...90 ° 60 Rd/Wr Retain Basic angle jb for directional operationOper. direction 35S46 MMI,RST Setting group1 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Selection of forward/reverse operationEarth fault pr. 35S47 MMI,RST Setting group1 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Earth fault protectionOperation mode 35S71 MMI,RST Setting group2 0..7[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.;6 = RI-type inverse; 7 = RD-type inverse]

- 1 Rd/Wr Retain Selection of operation mode and inverse time characteristic at IDMT mode

Start current 35S72 MMI,RST Setting group2 0.05...40.00 x In 0,05 Rd/Wr Retain Start currentOperate time 35S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeTime multiplier 35S74 MMI,RST Setting group2 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeBasic angle ïb 35S75 MMI,RST Setting group2 0...90 ° 60 Rd/Wr Retain Basic angle jb for directional operationOper. direction 35S76 MMI,RST Setting group2 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Selection of forward/reverse operationEarth fault pr. 35S77 MMI,RST Setting group2 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Earth fault protectionMeasuring mode 35V1 MMI,RST Control setting 0..3[0 = Mode 1; 1 = Mode 2; 2 = Mode 3; 3 = Mode 4] - 0 Rd/Wr Retain Selection of measuring modeDrop-off time 35V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of the operate time counter at DT modeGroup selection 35V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 35V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 35V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 35V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 35V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPMinimum time 35V8 MMI,RST Control setting 0.03...10.00 s 0,03 Rd/Wr Retain Minimum operate time at IDMT modeCBFP time 35V9 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 35V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 35V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 35V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 35V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 35V101 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E13)Event mask 2 35V103 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E13)

Page 37 of 158

Page 38: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 3 35V105 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E13)Event mask 4 35V107 MMI,RST Control setting 0...16383 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E13)Current IL1 35I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 35I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 35I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Voltage U12 35I4 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U12Voltage U23 35I5 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U23Voltage U31 35I6 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U31Voltage U1 35I7 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage U1Voltage U2 35I8 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage U2Voltage U3 35I9 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage U3Phase angle ï12 35I10 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 35I11 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase-to-phase current)Phase angle ï31 35I12 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 35I13 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase current)Phase angle ï2 35I14 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase current)Phase angle ï3 35I15 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase current)Input BS1 35I16 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 35I17 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 35I18 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 35I19 MMI,RST Input data 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Signal for switching between group 1 and 2Input DOUBLE 35I20 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for doubling the set start currentInput BSREG 35I21 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 35I22 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

DOC6LowOutput DIRECTION 35O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Current direction informationOutput START 35O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 35O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput CBFP 35O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalDate 35V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 35V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 35V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 35V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 35V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 35V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 35V207 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 35V208 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 35V209 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 35V210 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage U23 35V211 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage U31 35V212 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U31Voltage U1 35V213 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U1Voltage U2 35V214 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U2Voltage U3 35V215 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U3Phase angle ï12 35V216 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 35V217 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï31 35V218 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 35V219 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï2 35V220 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)

Page 38 of 158

Page 39: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Phase angle ï3 35V221 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)DIRECTION 35V222 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DIRECTION outputBS1 35V223 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 35V224 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 35V225 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 35V226 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 35V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 35V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 35V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 35V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 35V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 35V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 35V307 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 35V308 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 35V309 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 35V310 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage U23 35V311 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage U31 35V312 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U31Voltage U1 35V313 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U1Voltage U2 35V314 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U2Voltage U3 35V315 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U3Phase angle ï12 35V316 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 35V317 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï31 35V318 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 35V319 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï2 35V320 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï3 35V321 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)DIRECTION 35V322 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DIRECTION outputBS1 35V323 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 35V324 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 35V325 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 35V326 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 35V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 35V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 35V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 35V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 35V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 35V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 35V407 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 35V408 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 35V409 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 35V410 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage U23 35V411 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage U31 35V412 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U31Voltage U1 35V413 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U1Voltage U2 35V414 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U2Voltage U3 35V415 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U3Phase angle ï12 35V416 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 35V417 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)

Page 39 of 158

Page 40: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Phase angle ï31 35V418 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 35V419 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï2 35V420 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï3 35V421 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)DIRECTION 35V422 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DIRECTION outputBS1 35V423 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 35V424 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 35V425 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 35V426 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100036 / Rev E DOC6HighCurrent IL1 36I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 36I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 36I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Voltage U12 36I4 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U12Voltage U23 36I5 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U23Voltage U31 36I6 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U31Voltage U1 36I7 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage U1Voltage U2 36I8 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage U2Voltage U3 36I9 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage U3Phase angle ï12 36I10 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 36I11 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase-to-phase current)Phase angle ï31 36I12 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 36I13 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase current)Phase angle ï2 36I14 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase current)Phase angle ï3 36I15 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase current)Input BS1 36I16 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 36I17 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 36I18 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 36I19 MMI,RST Input data 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Signal for switching between group 1 and 2Input DOUBLE 36I20 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for doubling the set start currentInput BSREG 36I21 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 36I22 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

DOC6HighOutput DIRECTION 36O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Current direction informationOutput BSOUT 36O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of BSOUT signalOutput START 36O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 36O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput CBFP 36O5 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalDate 36V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 36V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 36V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 36V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 36V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 36V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 36V207 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 36V208 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 36V209 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 36V210 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage U23 36V211 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U23

Page 40 of 158

Page 41: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Voltage U31 36V212 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U31Voltage U1 36V213 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U1Voltage U2 36V214 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U2Voltage U3 36V215 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U3Phase angle ï12 36V216 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 36V217 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï31 36V218 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 36V219 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï2 36V220 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï3 36V221 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Nondir. operat. 36V222 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of nondirectional operationBS1 36V223 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 36V224 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 36V225 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 36V226 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 36V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 36V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 36V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 36V304 MMI,RST Recorded data2 0.00...60.0 x In 0 Read Retain Filtered value of IL1IL2 mean 36V305 MMI,RST Recorded data2 0.00...60.0 x In 0 Read Retain Filtered value of IL2IL3 mean 36V306 MMI,RST Recorded data2 0.00...60.0 x In 0 Read Retain Filtered value of IL3IL1 peak 36V307 MMI,RST Recorded data2 0.00...60.0 x In 0 Read Retain Momentary peak of IL1IL2 peak 36V308 MMI,RST Recorded data2 0.00...60.0 x In 0 Read Retain Momentary peak of IL2IL3 peak 36V309 MMI,RST Recorded data2 0.00...60.0 x In 0 Read Retain Momentary peak of IL3Voltage U12 36V310 MMI,RST Recorded data2 0.00...2.0 x Un 0 Read Retain Filtered value of U12Voltage U23 36V311 MMI,RST Recorded data2 0.00...2.0 x Un 0 Read Retain Filtered value of U23Voltage U31 36V312 MMI,RST Recorded data2 0.00...2.0 x Un 0 Read Retain Filtered value of U31Voltage U1 36V313 MMI,RST Recorded data2 0.00...2.0 x Un 0 Read Retain Filtered value of U1Voltage U2 36V314 MMI,RST Recorded data2 0.00...2.0 x Un 0 Read Retain Filtered value of U2Voltage U3 36V315 MMI,RST Recorded data2 0.00...2.0 x Un 0 Read Retain Filtered value of U3Phase angle ï12 36V316 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 36V317 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï31 36V318 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 36V319 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï2 36V320 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï3 36V321 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Nondir. operat. 36V322 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of nondirectional operationBS1 36V323 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 36V324 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 36V325 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 36V326 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 36V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 36V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 36V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 36V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 36V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 36V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 36V407 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 36V408 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL2

Page 41 of 158

Page 42: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

IL3 peak 36V409 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 36V410 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage U23 36V411 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage U31 36V412 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U31Voltage U1 36V413 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U1Voltage U2 36V414 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U2Voltage U3 36V415 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U3Phase angle ï12 36V416 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 36V417 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï31 36V418 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 36V419 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï2 36V420 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï3 36V421 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Nondir. operat. 36V422 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of nondirectional operationBS1 36V423 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 36V424 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 36V425 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 36V426 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupOperation mode 36S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Read Volatile Selection of operation modeStart current 36S2 MMI,RST Actual setting 0.05...40.00 x In 0,05 Read Volatile Start currentOperate time 36S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DTmodeBasic angle ïb 36S4 MMI,RST Actual setting 0...90 ° 60 Read Volatile Basic angle jb for directional operationOper. direction 36S5 MMI,RST Actual setting 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Selection of forward/reverse operationEarth fault pr. 36S6 MMI,RST Actual setting 0..1[0 = Disabled; 1 = Enabled] - 0 Read Volatile Earth fault protectionNondir. operat. 36S7 MMI,RST Actual setting 0..1[0 = Disabled; 1 = Enabled] - 0 Read Volatile Nondirectional operation when direction cannot be

determinedOperation mode 36S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 36S42 MMI,RST Setting group1 0.05...40.00 x In 0,05 Rd/Wr Retain Start currentOperate time 36S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DTmodeBasic angle ïb 36S44 MMI,RST Setting group1 0...90 ° 60 Rd/Wr Retain Basic angle jb for directional operationOper. direction 36S45 MMI,RST Setting group1 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Selection of forward/reverse operationEarth fault pr. 36S46 MMI,RST Setting group1 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Earth fault protectionNondir. operat. 36S47 MMI,RST Setting group1 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Nondirectional operation when direction cannot be

determinedOperation mode 36S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 36S72 MMI,RST Setting group2 0.05...40.00 x In 0,05 Rd/Wr Retain Start currentOperate time 36S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DTmodeBasic angle ïb 36S74 MMI,RST Setting group2 0...90 ° 60 Rd/Wr Retain Basic angle jb for directional operationOper. direction 36S75 MMI,RST Setting group2 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Selection of forward/reverse operationEarth fault pr. 36S76 MMI,RST Setting group2 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Earth fault protectionNondir. operat. 36S77 MMI,RST Setting group2 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Nondirectional operation when direction cannot be

determinedMeasuring mode 36V1 MMI,RST Control setting 0..3[0 = Mode 1; 1 = Mode 2; 2 = Mode 3; 3 = Mode 4] - 0 Rd/Wr Retain Selection of measuring modeDrop-off time 36V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of the operate time counter at DT modeGroup selection 36V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 36V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 36V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 36V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 36V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFP

Page 42 of 158

Page 43: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

CBFP time 36V8 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 36V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 36V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 36V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 36V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 36V101 MMI,RST Control setting 0...65535 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E15)Event mask 2 36V103 MMI,RST Control setting 0...65535 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E15)Event mask 3 36V105 MMI,RST Control setting 0...65535 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E15)Event mask 4 36V107 MMI,RST Control setting 0...65535 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E15)

100037 / Rev E DOC6InstOperation mode 37S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Read Volatile Selection of operation modeStart current 37S2 MMI,RST Actual setting 0.05...40.00 x In 0,05 Read Volatile Start currentOperate time 37S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DTmodeBasic angle ïb 37S4 MMI,RST Actual setting 0...90 ° 60 Read Volatile Basic angle jb for directional operationOper. direction 37S5 MMI,RST Actual setting 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Selection of forward/reverse operationEarth fault pr. 37S6 MMI,RST Actual setting 0..1[0 = Disabled; 1 = Enabled] - 0 Read Volatile Earth fault protectionNondir. operat. 37S7 MMI,RST Actual setting 0..1[0 = Disabled; 1 = Enabled] - 0 Read Volatile Nondirectional operation when direction cannot be

determinedOperation mode 37S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 37S42 MMI,RST Setting group1 0.05...40.00 x In 0,05 Rd/Wr Retain Start currentOperate time 37S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DTmodeBasic angle ïb 37S44 MMI,RST Setting group1 0...90 ° 60 Rd/Wr Retain Basic angle jb for directional operationOper. direction 37S45 MMI,RST Setting group1 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Selection of forward/reverse operationEarth fault pr. 37S46 MMI,RST Setting group1 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Earth fault protectionNondir. operat. 37S47 MMI,RST Setting group1 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Nondirectional operation when direction cannot be

determinedOperation mode 37S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 37S72 MMI,RST Setting group2 0.05...40.00 x In 0,05 Rd/Wr Retain Start currentOperate time 37S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DTmodeBasic angle ïb 37S74 MMI,RST Setting group2 0...90 ° 60 Rd/Wr Retain Basic angle jb for directional operationOper. direction 37S75 MMI,RST Setting group2 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Selection of forward/reverse operationEarth fault pr. 37S76 MMI,RST Setting group2 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Earth fault protectionNondir. operat. 37S77 MMI,RST Setting group2 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Nondirectional operation when direction cannot be

determinedMeasuring mode 37V1 MMI,RST Control setting 0..3[0 = Mode 1; 1 = Mode 2; 2 = Mode 3; 3 = Mode 4] - 0 Rd/Wr Retain Selection of measuring modeDrop-off time 37V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of the operate time counter at DT modeGroup selection 37V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 37V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 37V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 37V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 37V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 37V8 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 37V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 37V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 37V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 37V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 37V101 MMI,RST Control setting 0...65535 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E15)Event mask 2 37V103 MMI,RST Control setting 0...65535 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E15)Event mask 3 37V105 MMI,RST Control setting 0...65535 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E15)

Page 43 of 158

Page 44: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 4 37V107 MMI,RST Control setting 0...65535 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E15)Current IL1 37I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 37I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 37I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Voltage U12 37I4 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U12Voltage U23 37I5 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U23Voltage U31 37I6 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U31Voltage U1 37I7 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage U1Voltage U2 37I8 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage U2Voltage U3 37I9 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage U3Phase angle ï12 37I10 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 37I11 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase-to-phase current)Phase angle ï31 37I12 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 37I13 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase current)Phase angle ï2 37I14 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase current)Phase angle ï3 37I15 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase difference ïb - ï(phase current)Input BS1 37I16 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 37I17 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 37I18 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 37I19 MMI,RST Input data 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Signal for switching between group 1 and 2Input DOUBLE 37I20 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for doubling the set start currentInput BSREG 37I21 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 37I22 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

DOC6InstOutput DIRECTION 37O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Current direction informationOutput BSOUT 37O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of BSOUT signalOutput START 37O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 37O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput CBFP 37O5 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalDate 37V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 37V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 37V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 37V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 37V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 37V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 37V207 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 37V208 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 37V209 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 37V210 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage U23 37V211 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage U31 37V212 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U31Voltage U1 37V213 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U1Voltage U2 37V214 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U2Voltage U3 37V215 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U3Phase angle ï12 37V216 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 37V217 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï31 37V218 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 37V219 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï2 37V220 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)

Page 44 of 158

Page 45: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Phase angle ï3 37V221 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Nondir. operat. 37V222 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of nondirectional operationBS1 37V223 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 37V224 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 37V225 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 37V226 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 37V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 37V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 37V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 37V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 37V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 37V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 37V307 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 37V308 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 37V309 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 37V310 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage U23 37V311 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage U31 37V312 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U31Voltage U1 37V313 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U1Voltage U2 37V314 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U2Voltage U3 37V315 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U3Phase angle ï12 37V316 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 37V317 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï31 37V318 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 37V319 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï2 37V320 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï3 37V321 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Nondir. operat. 37V322 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of nondirectional operationBS1 37V323 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 37V324 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 37V325 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 37V326 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 37V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 37V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 37V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 37V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 37V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 37V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 37V407 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 37V408 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 37V409 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 37V410 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage U23 37V411 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage U31 37V412 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U31Voltage U1 37V413 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U1Voltage U2 37V414 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U2Voltage U3 37V415 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U3Phase angle ï12 37V416 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï23 37V417 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)

Page 45 of 158

Page 46: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Phase angle ï31 37V418 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase-to-phase current)Phase angle ï1 37V419 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï2 37V420 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Phase angle ï3 37V421 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Phase difference ïb - ï(phase current)Nondir. operat. 37V422 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of nondirectional operationBS1 37V423 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 37V424 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputDOUBLE 37V425 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 37V426 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100038 / Rev D NEF1LowOperation mode 38S1 MMI,RST Actual setting 0..15[0 = Not in use; 1 = Definite time; 2 = Extremely

inv.; 3 = Very inverse; 4 = Normal inverse; 5 = Long-timeinv.; 6 = RI-type inverse; 7 = RD-type inverse; 8 = IEEE Ext. inv.; 9 = IEEE Very inv.; 10 = IEEE Inverse; 11 = IEEE S.T. inv.; 12 = IEEE S.T.V. inv; 13 = IEEE L.T.E. inv; 14 = IEEE L.T.V. inv; 15 = IEEE L.T. inv.]

- 1 Read Volatile Selection of operation mode and inverse time characteristic at IDMTmode

Start current 38S2 MMI,RST Actual setting 1.0...100.0 % In 1 Read Volatile Start currentOperate time 38S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DT modeTime multiplier 38S4 MMI,RST Actual setting 0.05...1.00 - 0,05 Read Volatile Time multiplier at IDMT modeIEEE time dial 38S5 MMI,RST Actual setting 0.5...15.0 - 0,5 Read Volatile IEEE time dial at IDMT modeOperation mode 38S41 MMI,RST Setting group1 0..15[0 = Not in use; 1 = Definite time; 2 = Extremely

inv.; 3 = Very inverse; 4 = Normal inverse; 5 = Long-timeinv.; 6 = RI-type inverse; 7 = RD-type inverse; 8 = IEEE Ext. inv.; 9 = IEEE Very inv.; 10 = IEEE Inverse; 11 = IEEE S.T. inv.; 12 = IEEE S.T.V. inv; 13 = IEEE L.T.E. inv; 14 = IEEE L.T.V. inv; 15 = IEEE L.T. inv.]

- 1 Rd/Wr Retain Selection of operation mode and inverse time characteristic at IDMT mode

Start current 38S42 MMI,RST Setting group1 1.0...100.0 % In 1 Rd/Wr Retain Start currentOperate time 38S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeTime multiplier 38S44 MMI,RST Setting group1 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeIEEE time dial 38S45 MMI,RST Setting group1 0.5...15.0 - 0,5 Rd/Wr Retain IEEE time dial at IDMT modeOperation mode 38S71 MMI,RST Setting group2 0..15[0 = Not in use; 1 = Definite time; 2 = Extremely

inv.; 3 = Very inverse; 4 = Normal inverse; 5 = Long-timeinv.; 6 = RI-type inverse; 7 = RD-type inverse; 8 = IEEE Ext. inv.; 9 = IEEE Very inv.; 10 = IEEE Inverse; 11 = IEEE S.T. inv.; 12 = IEEE S.T.V. inv; 13 = IEEE L.T.E. inv; 14 = IEEE L.T.V. inv; 15 = IEEE L.T. inv.]

- 1 Rd/Wr Retain Selection of operation mode and inverse time characteristic at IDMT mode

Start current 38S72 MMI,RST Setting group2 1.0...100.0 % In 1 Rd/Wr Retain Start currentOperate time 38S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeTime multiplier 38S74 MMI,RST Setting group2 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeIEEE time dial 38S75 MMI,RST Setting group2 0.5...15.0 - 0,5 Rd/Wr Retain IEEE time dialMeasuring mode 38V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 1 Rd/Wr Retain Selection of measuring modeDrop-off time 38V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of the operate time counter at DMT modeGroup selection 38V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 38V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 38V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 38V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 38V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPMinimum time 38V8 MMI,RST Control setting 0.03...10.00 s 0,03 Rd/Wr Retain Minimum operate time at IDMT modeCBFP time 38V9 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of CBFP

Page 46 of 158

Page 47: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Reset registers 38V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 38V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 38V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 38V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 38V101 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 38V103 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 38V105 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 38V107 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Current Io 38I1 MMI,RST Input data 0.0...2000.0 % In 0 Read Volatile Neutral current IoInput BS1 38I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 38I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 38I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 38I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input BSREG 38I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 38I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting trip signal and registers NEF1LowOutput START 38O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 38O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput CBFP 38O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalDate 38V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 38V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 38V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 38V204 MMI,RST Recorded data1 0.0...2000.0 % In 0 Read Retain Filtered value of IoIo peak 38V205 MMI,RST Recorded data1 0.0...2000.0 % In 0 Read Retain Momentary peak of IoBS1 38V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 38V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 38V208 MMI,RST Recorded data1 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 38V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 38V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 38V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 38V304 MMI,RST Recorded data2 0.0...2000.0 % In 0 Read Retain Filtered value of IoIo peak 38V305 MMI,RST Recorded data2 0.0...2000.0 % In 0 Read Retain Momentary peak of IoBS1 38V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 38V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 38V308 MMI,RST Recorded data2 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 38V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 38V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 38V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 38V404 MMI,RST Recorded data3 0.0...2000.0 % In 0 Read Retain Filtered value of IoIo peak 38V405 MMI,RST Recorded data3 0.0...2000.0 % In 0 Read Retain Momentary peak of IoBS1 38V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 38V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 38V408 MMI,RST Recorded data3 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting group

100039 / Rev C NEF1HighOperation mode 39S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Read Volatile Selection of operation modeStart current 39S2 MMI,RST Actual setting 0.10...12.00 x In 0,1 Read Volatile Start currentOperate time 39S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DTmodeOperation mode 39S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 39S42 MMI,RST Setting group1 0.10...12.00 x In 0,1 Rd/Wr Retain Start currentOperate time 39S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT mode

Page 47 of 158

Page 48: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Operation mode 39S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 39S72 MMI,RST Setting group2 0.10...12.00 x In 0,1 Rd/Wr Retain Start currentOperate time 39S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeMeasuring mode 39V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 1 Rd/Wr Retain Selection of measuring modeDrop-off time 39V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of the operate time counterGroup selection 39V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 39V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 39V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 39V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 39V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 39V8 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of CBFPReset registers 39V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 39V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 39V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 39V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 39V101 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 39V103 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 39V105 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 39V107 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Current Io 39I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Neutral current IoInput BS1 39I2 MMI,RST Input data 0..1[0=Not active; 1=Active] - 0 Read Volatile Block signal BS1Input BS2 39I3 MMI,RST Input data 0..1[0=Not active; 1=Active] - 0 Read Volatile Block signal BS2Input TRIGG 39I4 MMI,RST Input data 0..1[0=Not active; 1=Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 39I5 MMI,RST Input data 0..1[0=Not active; 1=Active] - 0 Read Volatile Signal for switching between group 1 and 2Input BSREG 39I6 MMI,RST Input data 0..1[0=Not active; 1=Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 39I7 MMI,RST Input data 0..1[0=Not active; 1=Active] - 0 Read Volatile Signal for resetting trip signal and registers NEF1HighOutput START 39O1 MMI,RST Output data 0..1[0=Not active; 1=Active] - 0 Read Volatile Status of start signalOutput TRIP 39O2 MMI,RST Output data 0..1[0=Not active; 1=Active] - 0 Read Volatile Status of trip signalOutput CBFP 39O3 MMI,RST Output data 0..1[0=Not active; 1=Active] - 0 Read Volatile Status of CBFP signalDate 39V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 39V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 39V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 39V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IoIo peak 39V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IoBS1 39V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status os BS1 inputBS2 39V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 39V208 MMI,RST Recorded data1 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 39V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 39V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 39V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 39V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IoIo peak 39V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IoBS1 39V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status os BS1 inputBS2 39V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 39V308 MMI,RST Recorded data2 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 39V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 39V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 39V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 39V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of Io

Page 48 of 158

Page 49: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Io peak 39V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IoBS1 39V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status os BS1 inputBS2 39V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 39V408 MMI,RST Recorded data3 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting group

100040 / Rev C DEF2LowCurrent Io 40I1 MMI,RST Input data 0.0...2000.0 % In 0 Read Volatile Neutral current IoVoltage Uo 40I2 MMI,RST Input data 0.0...120.0 % Un 0 Read Volatile Residual voltage UoPhase angle ï 40I3 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase angle jAngle ïb - ï 40I4 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase angle jb - jInput BS1 40I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 40I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input BACTRL 40I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input BACTRLInput TRIGG 40I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering he registersInput GROUP 40I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input BSREG 40I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 40I11 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Resetting of trip signal and registersOutput START 40O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 40O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput CBFP 40O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalDate 40V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 40V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 40V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 40V204 MMI,RST Recorded data1 0.0...2000.0 % In 0 Read Retain Io mean valueIo peak 40V205 MMI,RST Recorded data1 0.0...2000.0 % In 0 Read Retain Io peak valueVoltage Uo 40V206 MMI,RST Recorded data1 0.0...120.0 % Un 0 Read Retain Residual voltage UoAngle ï 40V207 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Angle between Uo & IoAngle ïb - ï 40V208 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Angle between jb & jIntermittent E/F 40V209 MMI,RST Recorded data1 0..1[0 = Not detected; 1 = Detected] - 0 Read Retain Status of intermittent E/FBS1 40V210 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 40V211 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputBACTRL 40V212 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BACTRL inputActive group 40V213 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Status of Active groupDate 40V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 40V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 40V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 40V304 MMI,RST Recorded data2 0.0...2000.0 % In 0 Read Retain Io mean valueIo peak 40V305 MMI,RST Recorded data2 0.0...2000.0 % In 0 Read Retain Io peak valueVoltage Uo 40V306 MMI,RST Recorded data2 0.0...120.0 % Un 0 Read Retain Residual voltage UoAngle ï 40V307 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Angle between Uo & IoAngle ïb - ï 40V308 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Angle between jb & jIntermittent E/F 40V309 MMI,RST Recorded data2 0..1[0 = Not detected; 1 = Detected] - 0 Read Retain Status of intermittent E/FBS1 40V310 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 40V311 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputBACTRL 40V312 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BACTRL inputActive group 40V313 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Status of Active groupDate 40V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 40V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 40V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 40V404 MMI,RST Recorded data3 0.0...2000.0 % In 0 Read Retain Io mean value

Page 49 of 158

Page 50: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Io peak 40V405 MMI,RST Recorded data3 0.0...2000.0 % In 0 Read Retain Io peak valueVoltage Uo 40V406 MMI,RST Recorded data3 0.0...120.0 % Un 0 Read Retain Residual voltage UoAngle ï 40V407 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Angle between Uo & IoAngle ïb - ï 40V408 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Angle between jb & jIntermittent E/F 40V409 MMI,RST Recorded data3 0..1[0 = Not detected; 1 = Detected] - 0 Read Retain Status of intermittent E/FBS1 40V410 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 40V411 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputBACTRL 40V412 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BACTRL inputActive group 40V413 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Status of Active groupOperation mode 40S1 MMI,RST Actual setting 0..5[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.]

- 1 Read Volatile Selection of operation mode and IDMT time characteristic

Oper. criteria 40S2 MMI,RST Actual setting 0..5[0 = BasicAng & Uo; 1 = BasicAng; 2 = IoSin/Cos & Uo; 3 = IoSin/Cos; 4 = Non-dir.Io; 5 = Non-dir. Uo]

- 0 Read Volatile Selection of operation criteria

Oper. direction 40S3 MMI,RST Actual setting 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Operation directionBasic angle ïb 40S4 MMI,RST Actual setting 0..3[0 = -90ø; 1 = -60ø; 2 = -30ø; 3 = 0ø] - 0 Read Volatile Basic angleOper. charact. 40S5 MMI,RST Actual setting 0..1[0 = IoSin(j); 1 = IoCos(j)] - 0 Read Volatile Operation characteristicStart current 40S6 MMI,RST Actual setting 1.0...25.0 % In 1 Read Volatile Start currentStart voltage 40S7 MMI,RST Actual setting 2.0...100.0 % Un 2 Read Volatile Start voltageOperate time 40S8 MMI,RST Actual setting 0.1...300.0 s 0,1 Read Volatile Operate time at DT modeTime multiplier 40S9 MMI,RST Actual setting 0.05...1.00 - 0,05 Read Volatile Time multiplier at IDMT modeIntermittent E/F 40S10 MMI,RST Actual setting 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Selection of intermittent earthfault protectionOperation mode 40S41 MMI,RST Setting group1 0..5[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.]

- 1 Rd/Wr Retain Selection of operation mode and IDMT time characteristic

Oper. criteria 40S42 MMI,RST Setting group1 0..5[0 = BasicAng & Uo; 1 = BasicAng; 2 = IoSin/Cos & Uo; 3 = IoSin/Cos; 4 = Non-dir.Io; 5 = Non-dir. Uo]

- 0 Rd/Wr Retain Selection of operation criteria

Oper. direction 40S43 MMI,RST Setting group1 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Operation directionBasic angle ïb 40S44 MMI,RST Setting group1 0..3[0 = -90ø; 1 = -60ø; 2 = -30ø; 3 = 0ø] - 0 Rd/Wr Retain Basic angleOper. charact. 40S45 MMI,RST Setting group1 0..1[0 = IoSin(j); 1 = IoCos(j)] - 0 Rd/Wr Retain Operation characteristicStart current 40S46 MMI,RST Setting group1 1.0...25.0 % In 1 Rd/Wr Retain Start currentStart voltage 40S47 MMI,RST Setting group1 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 40S48 MMI,RST Setting group1 0.1...300.0 s 0,1 Rd/Wr Retain Operate time at DT modeTime multiplier 40S49 MMI,RST Setting group1 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeIntermittent E/F 40S50 MMI,RST Setting group1 0..1[0 = Not active; 1 = Active] - 0 Rd/Wr Retain Selection of a intermittent E/F operationOperation mode 40S71 MMI,RST Setting group2 0..5[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.]

- 1 Rd/Wr Retain Selection of operation mode and IDMT time characteristic

Oper. criteria 40S72 MMI,RST Setting group2 0..5[0 = BasicAng & Uo; 1 = BasicAng; 2 = IoSin/Cos & Uo; 3 = IoSin/Cos; 4 = Non-dir.Io; 5 = Non-dir. Uo]

- 0 Rd/Wr Retain Selection of operation criteria

Oper. direction 40S73 MMI,RST Setting group2 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Operation directionBasic angle ïb 40S74 MMI,RST Setting group2 0..3[0 = -90ø; 1 = -60ø; 2 = -30ø; 3 = 0ø] - 0 Rd/Wr Retain Basic angleOper. charact. 40S75 MMI,RST Setting group2 0..1[0 = IoSin(j); 1 = IoCos(j)] - 0 Rd/Wr Retain Operation characteristicStart current 40S76 MMI,RST Setting group2 1.0...25.0 % In 1 Rd/Wr Retain Start currentStart voltage 40S77 MMI,RST Setting group2 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 40S78 MMI,RST Setting group2 0.1...300.0 s 0,1 Rd/Wr Retain Operate time at DT modeTime multiplier 40S79 MMI,RST Setting group2 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeIntermittent E/F 40S80 MMI,RST Setting group2 0..1[0 = Not active; 1 = Active] - 0 Rd/Wr Retain Selection of a intermittent E/F operationMeasuring mode 40V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 1 Rd/Wr Retain Selection of measuring mode

Page 50 of 158

Page 51: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Drop-off time 40V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of DT counterGroup selection 40V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 40V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 40V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 40V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 40V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPMinimum time 40V8 MMI,RST Control setting 0.03...10.00 s 0,03 Rd/Wr Retain Minimum operate time at IDMT modeCBFP time 40V9 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of CBFPAngle correction 40V10 MMI,RST Control setting 0.0...5.0 ° 2 Rd/Wr Retain Angle correction factor for Iosin(j) / Iocos(j)Oper. sector 40V11 MMI,RST Control setting 0..1[0 = 80ø; 1 = 88ø] - 0 Rd/Wr Retain Operation sectorReset registers 40V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 40V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 40V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 40V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 40V101 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 40V103 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 40V105 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 40V107 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)

100041 / Rev C DEF2HighOperation mode 41S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Read Volatile Selection of operation modeOper. criteria 41S2 MMI,RST Actual setting 0..5[0 = BasicAng & Uo; 1 = BasicAng; 2 = IoSin/Cos &

Uo; 3 = IoSin/Cos; 4 = Non-dir.Io; 5 = Non-dir. Uo]- 0 Read Volatile Selection of operation criteria

Oper. direction 41S3 MMI,RST Actual setting 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Operation directionBasic angle ïb 41S4 MMI,RST Actual setting 0..3[0 = -90ø; 1 = -60ø; 2 = -30ø; 3 = 0ø] - 0 Read Volatile Basic angleOper. charact. 41S5 MMI,RST Actual setting 0..1[0 = IoSin(j); 1 = IoCos(j)] - 0 Read Volatile Operation characteristicStart current 41S6 MMI,RST Actual setting 1.0...200.0 % In 1 Read Volatile Start currentStart voltage 41S7 MMI,RST Actual setting 2.0...100.0 % Un 2 Read Volatile Start voltageOperate time 41S8 MMI,RST Actual setting 0.1...300.0 s 0,1 Read Volatile Operate time at DTmodeIntermittent E/F 41S9 MMI,RST Actual setting 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Selection of intermittent earthfault protectionOperation mode 41S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeOper. criteria 41S42 MMI,RST Setting group1 0..5[0 = BasicAng & Uo; 1 = BasicAng; 2 = IoSin/Cos &

Uo; 3 = IoSin/Cos; 4 = Non-dir.Io; 5 = Non-dir. Uo]- 0 Rd/Wr Retain Selection of operation criteria

Oper. direction 41S43 MMI,RST Setting group1 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Operation directionBasic angle ïb 41S44 MMI,RST Setting group1 0..3[0 = -90ø; 1 = -60ø; 2 = -30ø; 3 = 0ø] - 0 Rd/Wr Retain Basic angleOper. charact. 41S45 MMI,RST Setting group1 0..1[0 = IoSin(j); 1 = IoCos(j)] - 0 Rd/Wr Retain Operation characteristicStart current 41S46 MMI,RST Setting group1 1.0...200.0 % In 1 Rd/Wr Retain Start currentStart voltage 41S47 MMI,RST Setting group1 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 41S48 MMI,RST Setting group1 0.1...300.0 s 0,1 Rd/Wr Retain Operate time at DT modeIntermittent E/F 41S49 MMI,RST Setting group1 0..1[0 = Not active; 1 = Active] - 0 Rd/Wr Retain Selection of a intermittent E/F operationOperation mode 41S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeOper. criteria 41S72 MMI,RST Setting group2 0..5[0 = BasicAng & Uo; 1 = BasicAng; 2 = IoSin/Cos &

Uo; 3 = IoSin/Cos; 4 = Non-dir.Io; 5 = Non-dir. Uo]- 0 Rd/Wr Retain Selection of operation criteria

Oper. direction 41S73 MMI,RST Setting group2 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Operation directionBasic angle ïb 41S74 MMI,RST Setting group2 0..3[0 = -90ø; 1 = -60ø; 2 = -30ø; 3 = 0ø] - 0 Rd/Wr Retain Basic angleOper. charact. 41S75 MMI,RST Setting group2 0..1[0 = IoSin(j); 1 = IoCos(j)] - 0 Rd/Wr Retain Operation characteristicStart current 41S76 MMI,RST Setting group2 1.0...200.0 % In 1 Rd/Wr Retain Start currentStart voltage 41S77 MMI,RST Setting group2 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 41S78 MMI,RST Setting group2 0.1...300.0 s 0,1 Rd/Wr Retain Operate time at DT modeIntermittent E/F 41S79 MMI,RST Setting group2 0..1[0 = Not active; 1 = Active] - 0 Rd/Wr Retain Selection of a intermittent E/F operation

Page 51 of 158

Page 52: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Measuring mode 41V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 1 Rd/Wr Retain Selection of measuring modeDrop-off time 41V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of DT counterGroup selection 41V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 41V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 41V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 41V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 41V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 41V8 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of CBFPAngle correction 41V9 MMI,RST Control setting 0.0...5.0 ° 2 Rd/Wr Retain Angle correction factor for Iosin(j) / Iocos(j)Oper. sector 41V10 MMI,RST Control setting 0..1[0 = 80ø; 1 = 88ø] - 0 Rd/Wr Retain Operation sectorReset registers 41V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 41V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 41V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 41V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 41V101 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 41V103 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 41V105 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 41V107 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Current Io 41I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Neutral current IoVoltage Uo 41I2 MMI,RST Input data 0.0...120.0 % Un 0 Read Volatile Residual voltage UoPhase angle ï 41I3 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase angle jAngle ïb - ï 41I4 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase angle jb - jInput BS1 41I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 41I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input BACTRL 41I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input BACTRLInput TRIGG 41I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 41I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input BSREG 41I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 41I11 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Resetting of trip signal and registersOutput START 41O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 41O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput CBFP 41O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalDate 41V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 41V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 41V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 41V204 MMI,RST Recorded data1 0.0...2000.0 % In 0 Read Retain Io mean valueIo peak 41V205 MMI,RST Recorded data1 0.0...2000.0 % In 0 Read Retain Io peak valueVoltage Uo 41V206 MMI,RST Recorded data1 0.0...120.0 % Un 0 Read Retain Residual voltage UoAngle ï 41V207 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Angle between Uo & IoAngle ïb - ï 41V208 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Angle between jb & jIntermittent E/F 41V209 MMI,RST Recorded data1 0..1[0 = Not detected; 1 = Detected] - 0 Read Retain Status of intermittent E/FBS1 41V210 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 41V211 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputBACTRL 41V212 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BACTRL inputActive group 41V213 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Status of Active groupDate 41V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 41V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 41V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 41V304 MMI,RST Recorded data2 0.0...2000.0 % In 0 Read Retain Io mean value

Page 52 of 158

Page 53: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Io peak 41V305 MMI,RST Recorded data2 0.0...2000.0 % In 0 Read Retain Io peak valueVoltage Uo 41V306 MMI,RST Recorded data2 0.0...120.0 % Un 0 Read Retain Residual voltage UoAngle ï 41V307 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Angle between Uo & IoAngle ïb - ï 41V308 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Angle between jb & jIntermittent E/F 41V309 MMI,RST Recorded data2 0..1[0 = Not detected; 1 = Detected] - 0 Read Retain Status of intermittent E/FBS1 41V310 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 41V311 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputBACTRL 41V312 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BACTRL inputActive group 41V313 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Status of Active groupDate 41V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 41V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 41V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 41V404 MMI,RST Recorded data3 0.0...2000.0 % In 0 Read Retain Io mean valueIo peak 41V405 MMI,RST Recorded data3 0.0...2000.0 % In 0 Read Retain Io peak valueVoltage Uo 41V406 MMI,RST Recorded data3 0.0...120.0 % Un 0 Read Retain Residual voltage UoAngle ï 41V407 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Angle between Uo & IoAngle ïb - ï 41V408 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Angle between jb & jIntermittent E/F 41V409 MMI,RST Recorded data3 0..1[0 = Not detected; 1 = Detected] - 0 Read Retain Status of intermittent E/FBS1 41V410 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 41V411 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputBACTRL 41V412 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BACTRL inputActive group 41V413 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Status of Active group

100042 / Rev C DEF2InstCurrent Io 42I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Neutral current IoVoltage Uo 42I2 MMI,RST Input data 0.0...120.0 % Un 0 Read Volatile Residual voltage UoPhase angle ï 42I3 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase angle jAngle ïb - ï 42I4 MMI,RST Input data -180...+180 ° 0 Read Volatile Phase angle jb - jInput BS1 42I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 42I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input BACTRL 42I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input BACTRLInput TRIGG 42I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering he registersInput GROUP 42I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input BSREG 42I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 42I11 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Resetting of trip signal and registersOutput START 42O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 42O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput CBFP 42O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalDate 42V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 42V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 42V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 42V204 MMI,RST Recorded data1 0.0...2000.0 % In 0 Read Retain Io mean valueIo peak 42V205 MMI,RST Recorded data1 0.0...2000.0 % In 0 Read Retain Io peak valueVoltage Uo 42V206 MMI,RST Recorded data1 0.0...120.0 % Un 0 Read Retain Residual voltage UoAngle ï 42V207 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Angle between Uo & IoAngle ïb - ï 42V208 MMI,RST Recorded data1 -180...+180 ° 0 Read Retain Angle between jb & jIntermittent E/F 42V209 MMI,RST Recorded data1 0..1[0 = Not detected; 1 = Detected] - 0 Read Retain Status of intermittent E/FBS1 42V210 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 42V211 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputBACTRL 42V212 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BACTRL input

Page 53 of 158

Page 54: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Active group 42V213 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Status of Active groupDate 42V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 42V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 42V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 42V304 MMI,RST Recorded data2 0.0...2000.0 % In 0 Read Retain Io mean valueIo peak 42V305 MMI,RST Recorded data2 0.0...2000.0 % In 0 Read Retain Io peak valueVoltage Uo 42V306 MMI,RST Recorded data2 0.0...120.0 % Un 0 Read Retain Residual voltage UoAngle ï 42V307 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Angle between Uo & IoAngle ïb - ï 42V308 MMI,RST Recorded data2 -180...+180 ° 0 Read Retain Angle between jb & jIntermittent E/F 42V309 MMI,RST Recorded data2 0..1[0 = Not detected; 1 = Detected] - 0 Read Retain Status of intermittent E/FBS1 42V310 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 42V311 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputBACTRL 42V312 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BACTRL inputActive group 42V313 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Status of Active groupDate 42V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 42V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 42V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 42V404 MMI,RST Recorded data3 0.0...2000.0 % In 0 Read Retain Io mean valueIo peak 42V405 MMI,RST Recorded data3 0.0...2000.0 % In 0 Read Retain Io peak valueVoltage Uo 42V406 MMI,RST Recorded data3 0.0...120.0 % Un 0 Read Retain Residual voltage UoAngle ï 42V407 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Angle between Uo & IoAngle ïb - ï 42V408 MMI,RST Recorded data3 -180...+180 ° 0 Read Retain Angle between jb & jIntermittent E/F 42V409 MMI,RST Recorded data3 0..1[0 = Not detected; 1 = Detected] - 0 Read Retain Status of intermittent E/FBS1 42V410 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 42V411 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputBACTRL 42V412 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BACTRL inputActive group 42V413 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Status of Active groupOperation mode 42S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Read Volatile Selection of operation modeOper. criteria 42S2 MMI,RST Actual setting 0..5[0 = BasicAng & Uo; 1 = BasicAng; 2 = IoSin/Cos &

Uo; 3 = IoSin/Cos; 4 = Non-dir.Io; 5 = Non-dir. Uo]- 0 Read Volatile Selection of operation criteria

Oper. direction 42S3 MMI,RST Actual setting 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Operation directionBasic angle ïb 42S4 MMI,RST Actual setting 0..3[0 = -90ø; 1 = -60ø; 2 = -30ø; 3 = 0ø] - 0 Read Volatile Basic angleOper. charact. 42S5 MMI,RST Actual setting 0..1[0 = IoSin(j); 1 = IoCos(j)] - 0 Read Volatile Operation characteristicStart current 42S6 MMI,RST Actual setting 1.0...200.0 % In 1 Read Volatile Start currentStart voltage 42S7 MMI,RST Actual setting 2.0...100.0 % Un 2 Read Volatile Start voltageOperate time 42S8 MMI,RST Actual setting 0.1...300.0 s 0,1 Read Volatile Operate time at DTmodeIntermittent E/F 42S9 MMI,RST Actual setting 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Selection of intermittent earthfault protectionOperation mode 42S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeOper. criteria 42S42 MMI,RST Setting group1 0..5[0 = BasicAng & Uo; 1 = BasicAng; 2 = IoSin/Cos &

Uo; 3 = IoSin/Cos; 4 = Non-dir.Io; 5 = Non-dir. Uo]- 0 Rd/Wr Retain Selection of operation criteria

Oper. direction 42S43 MMI,RST Setting group1 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Operation directionBasic angle ïb 42S44 MMI,RST Setting group1 0..3[0 = -90ø; 1 = -60ø; 2 = -30ø; 3 = 0ø] - 0 Rd/Wr Retain Basic angleOper. charact. 42S45 MMI,RST Setting group1 0..1[0 = IoSin(j); 1 = IoCos(j)] - 0 Rd/Wr Retain Operation characteristicStart current 42S46 MMI,RST Setting group1 1.0...200.0 % In 1 Rd/Wr Retain Start currentStart voltage 42S47 MMI,RST Setting group1 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 42S48 MMI,RST Setting group1 0.1...300.0 s 0,1 Rd/Wr Retain Operate time at DT modeIntermittent E/F 42S49 MMI,RST Setting group1 0..1[0 = Not active; 1 = Active] - 0 Rd/Wr Retain Selection of a intermittent E/F operationOperation mode 42S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation mode

Page 54 of 158

Page 55: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Oper. criteria 42S72 MMI,RST Setting group2 0..5[0 = BasicAng & Uo; 1 = BasicAng; 2 = IoSin/Cos & Uo; 3 = IoSin/Cos; 4 = Non-dir.Io; 5 = Non-dir. Uo]

- 0 Rd/Wr Retain Selection of operation criteria

Oper. direction 42S73 MMI,RST Setting group2 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Operation directionBasic angle ïb 42S74 MMI,RST Setting group2 0..3[0 = -90ø; 1 = -60ø; 2 = -30ø; 3 = 0ø] - 0 Rd/Wr Retain Basic angleOper. charact. 42S75 MMI,RST Setting group2 0..1[0 = IoSin(j); 1 = IoCos(j)] - 0 Rd/Wr Retain Operation characteristicStart current 42S76 MMI,RST Setting group2 1.0...200.0 % In 1 Rd/Wr Retain Start currentStart voltage 42S77 MMI,RST Setting group2 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 42S78 MMI,RST Setting group2 0.1...300.0 s 0,1 Rd/Wr Retain Operate time at DT modeIntermittent E/F 42S79 MMI,RST Setting group2 0..1[0 = Not active; 1 = Active] - 0 Rd/Wr Retain Selection of a intermittent E/F operationMeasuring mode 42V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 1 Rd/Wr Retain Selection of measuring modeDrop-off time 42V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of DT counterGroup selection 42V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 42V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 42V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 42V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 42V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 42V8 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of CBFPAngle correction 42V9 MMI,RST Control setting 0.0...5.0 ° 2 Rd/Wr Retain Angle correction factor for Iosin(j) / Iocos(j)Oper. sector 42V10 MMI,RST Control setting 0..1[0 = 80ø; 1 = 88ø] - 0 Rd/Wr Retain Operation sectorReset registers 42V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 42V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 42V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 42V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 42V101 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 42V103 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 42V105 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 42V107 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)

100044 / Rev D ROV1LowOperation mode 44S1 MMI,RST Actual setting 0..1[0 = Not in use; 1 = Definite time] - 1 Read Volatile Selection of operation modeStart voltage 44S2 MMI,RST Actual setting 2.0...100.0 % Un 2 Read Volatile Start voltageOperate time 44S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DTmodeOperation mode 44S41 MMI,RST Setting group1 0..1[0 = Not in use; 1 = Definite time] - 1 Rd/Wr Retain Selection of operation modeStart voltage 44S42 MMI,RST Setting group1 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 44S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeOperation mode 44S71 MMI,RST Setting group2 0..1[0 = Not in use; 1 = Definite time] - 1 Rd/Wr Retain Selection of operation modeStart voltage 44S72 MMI,RST Setting group2 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 44S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeMeasuring mode 44V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 1 Rd/Wr Retain Selection of measuring modeGroup selection 44V2 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 44V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 44V4 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 44V5 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 44V6 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIPReset registers 44V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 44V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 44V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPEvent mask 1 44V101 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 44V103 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 44V105 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)

Page 55 of 158

Page 56: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 4 44V107 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Voltage Uo 44I1 MMI,RST Input data 0.0...120.0 % Un 0 Read Volatile Residual voltage UoInput BS1 44I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 44I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 44I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 44I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 44I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting trip signal and registers ROV1LowOutput START 44O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 44O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 44V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 44V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 44V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationVoltage Uo 44V204 MMI,RST Recorded data1 0.0...120.0 % Un 0 Read Retain Filtered value of UoBS1 44V205 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 44V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 44V207 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 44V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 44V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 44V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationVoltage Uo 44V304 MMI,RST Recorded data2 0.0...120.0 % Un 0 Read Retain Filtered value of UoBS1 44V305 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 44V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 44V307 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 44V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 44V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 44V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationVoltage Uo 44V404 MMI,RST Recorded data3 0.0...120.0 % Un 0 Read Retain Filtered value of UoBS1 44V405 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 44V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 44V407 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100045 / Rev D ROV1HighOperation mode 45S1 MMI,RST Actual setting 0..1[0 = Not in use; 1 = Definite time] - 1 Read Volatile Selection of operation modeStart voltage 45S2 MMI,RST Actual setting 2.0...100.0 % Un 2 Read Volatile Start voltageOperate time 45S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DT modeOperation mode 45S41 MMI,RST Setting group1 0..1[0 = Not in use; 1 = Definite time] - 1 Rd/Wr Retain Selection of operation modeStart voltage 45S42 MMI,RST Setting group1 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 45S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeOperation mode 45S71 MMI,RST Setting group2 0..1[0 = Not in use; 1 = Definite time] - 1 Rd/Wr Retain Selection of operation modeStart voltage 45S72 MMI,RST Setting group2 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 45S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeMeasuring mode 45V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 1 Rd/Wr Retain Selection of measuring modeGroup selection 45V2 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 45V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 45V4 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 45V5 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 45V6 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIPReset registers 45V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 45V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 45V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIP

Page 56 of 158

Page 57: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 1 45V101 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 45V103 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 45V105 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 45V107 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Voltage Uo 45I1 MMI,RST Input data 0.0...120.0 % Un 0 Read Volatile Residual voltage UoInput BS1 45I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 45I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 45I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 45I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 45I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting trip signal and registers ROV1HighOutput START 45O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 45O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 45V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 45V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 45V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationVoltage Uo 45V204 MMI,RST Recorded data1 0.0...120.0 % Un 0 Read Retain Filtered value of UoBS1 45V205 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 45V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 45V207 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 45V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 45V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 45V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationVoltage Uo 45V304 MMI,RST Recorded data2 0.0...120.0 % Un 0 Read Retain Filtered value of UoBS1 45V305 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 45V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 45V307 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 45V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 45V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 45V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationVoltage Uo 45V404 MMI,RST Recorded data3 0.0...120.0 % Un 0 Read Retain Filtered value of UoBS1 45V405 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 45V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 45V407 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100046 / Rev D ROV1InstOperation mode 46S1 MMI,RST Actual setting 0..1[0 = Not in use; 1 = Definite time] - 1 Read Volatile Selection of operation modeStart voltage 46S2 MMI,RST Actual setting 2.0...100.0 % Un 2 Read Volatile Start voltageOperate time 46S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DT modeOperation mode 46S41 MMI,RST Setting group1 0..1[0 = Not in use; 1 = Definite time] - 1 Rd/Wr Retain Selection of operation modeStart voltage 46S42 MMI,RST Setting group1 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 46S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeOperation mode 46S71 MMI,RST Setting group2 0..1[0 = Not in use; 1 = Definite time] - 1 Rd/Wr Retain Selection of operation modeStart voltage 46S72 MMI,RST Setting group2 2.0...100.0 % Un 2 Rd/Wr Retain Start voltageOperate time 46S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeMeasuring mode 46V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 1 Rd/Wr Retain Selection of measuring modeGroup selection 46V2 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 46V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 46V4 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 46V5 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 46V6 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP

Page 57 of 158

Page 58: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Reset registers 46V13 RST Control setting 0..1[0 = 0; 1= Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 46V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 46V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPEvent mask 1 46V101 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 46V103 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 46V105 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 46V107 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Voltage Uo 46I1 MMI,RST Input data 0.0...120.0 % Un 0 Read Volatile Residual voltage UoInput BS1 46I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 46I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 46I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 46I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 46I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting trip signal and registers ROV1InstOutput START 46O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 46O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 46V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 46V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 46V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationVoltage Uo 46V204 MMI,RST Recorded data1 0.0...120.0 % Un 0 Read Retain Filtered value of UoBS1 46V205 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 46V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 46V207 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 46V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 46V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 46V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationVoltage Uo 46V304 MMI,RST Recorded data2 0.0...120.0 % Un 0 Read Retain Filtered value of UoBS1 46V305 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 46V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 46V307 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 46V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 46V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 46V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationVoltage Uo 46V404 MMI,RST Recorded data3 0.0...120.0 % Un 0 Read Retain Filtered value of UoBS1 46V405 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 46V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 46V407 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100048 / Rev D TOL3DevS: ç1 48S1 MMI,RST Actual setting 0.1...999.0 min 14 Read Volatile Short timeconstant for the statorS: ç2 48S2 MMI,RST Actual setting 0.1...999.0 min 69 Read Volatile Long timeconstant for the statorS: p-factor 48S3 MMI,RST Actual setting 0.00...1.00 - 0,5 Read Volatile Weighting factor of the S:ð1S: Rise(øC),I=In 48S4 MMI,RST Actual setting 50.0...350.0 °C 90 Read Volatile Temperature rise of the stator when loaded by the rated

currentS: Maximum temp 48S5 MMI,RST Actual setting 50.0...350.0 °C 155 Read Volatile Maximum temperature allowed for the statorR: ç1 48S6 MMI,RST Actual setting 0.1...999.0 min 4 Read Volatile Short timeconstant for the rotorR: ç2 48S7 MMI,RST Actual setting 0.1...999.0 min 69 Read Volatile Long timeconstant for the rotorR: p-factor 48S8 MMI,RST Actual setting 0.00...1.00 - 0,25 Read Volatile Weighting factor of the R:ð1R: Rise(øC),I=In 48S9 MMI,RST Actual setting 50.0...350.0 °C 100 Read Volatile Temperature rise of the rotor when loaded by the rated

currentR: Maximum temp 48S10 MMI,RST Actual setting 50.0...350.0 °C 200 Read Volatile Maximum temperature allowed for the rotor

Page 58 of 158

Page 59: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Starting current 48S41 MMI,RST Basic setting 0.10...10.00 x In 6 Rd/Wr Retain Starting current of the motor setted as a multiple of the rated current

Starting time 48S42 MMI,RST Basic setting 0.1...120.0 s 12 Rd/Wr Retain Maximum starting time permitted for the motorNo of starts 48S43 MMI,RST Basic setting 1...3 - 2 Rd/Wr Retain Number of the allowed starts from the cold stateDevice type 48S44 MMI,RST Basic setting 0..6[0 = MOTOR I; 1 = MOTOR II; 2 = MOTOR III; 3 =

MOTOR IV; 4 = GENERATOR I; 5 = GENERATOR II; 6 = TRANSFORMER]

- 0 Rd/Wr Retain Type of the device to be protected

Trip temperature 48S45 MMI,RST Basic setting 80.0...120.0 % 100 Rd/Wr Retain Tripping temperature, per cent valuePrior alarm 48S46 MMI,RST Basic setting 40.0...100.0 % 90 Rd/Wr Retain Prior alarm temperature, per cent valueRestart inhibit 48S47 MMI,RST Basic setting 40.0...100.0 % 60 Rd/Wr Retain Temperature limit for the successful restartingAmbient temp 48S48 MMI,RST Basic setting -50.0...100.0 °C 40 Rd/Wr Retain Setting value for ambient temperatureCooling ç 48S49 MMI,RST Basic setting 1.0...10.0 x ð 4 Rd/Wr Retain Cooling timeconstantGen&Trafo ç 48S50 MMI,RST Basic setting 1...999 min 20 Rd/Wr Retain Heating timeconstant for generator or transformerS: ç1 48V71 MMI,RST Advanced sett. 0.0...999.0 min 0 Rd/Wr Retain Short timeconstant for the statorS: ç2 48V72 MMI,RST Advanced sett. 0.0...999.0 min 0 Rd/Wr Retain Long timeconstant for the statorS: p-factor 48V73 MMI,RST Advanced sett. 0.00...1.00 - 0 Rd/Wr Retain Weighting factor of the S:ð1S: Rise(øC),I=In 48V74 MMI,RST Advanced sett. 0.0...350.0 °C 0 Rd/Wr Retain Temperature rise of the stator when loaded by the rated

currentS: Maximum temp 48V75 MMI,RST Advanced sett. 0.0...350.0 °C 0 Rd/Wr Retain Maximum temperature allowed for the statorR: ç1 48V76 MMI,RST Advanced sett. 0.0...999.0 min 0 Rd/Wr Retain Short timeconstant for the rotorR: ç2 48V77 MMI,RST Advanced sett. 0.0...999.0 min 0 Rd/Wr Retain Long timeconstant for the rotorR: p-factor 48V78 MMI,RST Advanced sett. 0.00...1.00 - 0 Rd/Wr Retain Weighting factor of the R:ð1R: Rise(øC),I=In 48V79 MMI,RST Advanced sett. 0.0...350.0 °C 0 Rd/Wr Retain Temperature rise of the rotor when loaded by the rated

currentR: Maximum temp 48V80 MMI,RST Advanced sett. 0.0...350.0 °C 0 Rd/Wr Retain Maximum temperature allowed for the rotorOperation mode 48V1 MMI,RST Control setting 0..3[0 = Not in use; 1 = ON: no sensors; 2 = Sensor 1; 3 =

Sensors 1&2]- 1 Rd/Wr Retain Selection of operate mode

Ambient temp 48V2 MMI,RST Control setting -50.0...100.0 °C 0 Read Volatile Ambient temperature valueTrip signal 48V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 1 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 48V7 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Minimum pulse length of TRIP and CBFPTrip delay 48V8 MMI,RST Control setting 0...60000 min 0 Rd/Wr Retain Operate time of the delayed tripCBFP time 48V9 MMI,RST Control setting 0.00...100.00 s 0 Rd/Wr Retain Operate time of the Circuit Breaker Failure Protection

CBFPTrip & Start 48V10 MMI,RST Control setting 0..1[0 = Disabled; 1 = Enabled] - 1 Rd/Wr Retain Tells if the start and the trip are enabled or notReset registers 48V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 48V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 48V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 48V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 48V101 MMI,RST Control setting 0...8388607 - 4177983 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E22)Event mask 2 48V103 MMI,RST Control setting 0...8388607 - 4177983 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E22)Event mask 3 48V105 MMI,RST Control setting 0...8388607 - 4177983 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E22)Event mask 4 48V107 MMI,RST Control setting 0...8388607 - 4177983 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E22)Current IL1 48I1 MMI,RST Input data 0.0...20000.0 A 0 Read Volatile Phase current IL1Current IL2 48I2 MMI,RST Input data 0.0...20000.0 A 0 Read Volatile Phase current IL2Current IL3 48I3 MMI,RST Input data 0.0...20000.0 A 0 Read Volatile Phase current IL3IL1 (%) 48I4 MMI,RST Input data 0.0...1000.0 % In 0 Read Volatile Phase current IL1 in percentsIL2 (%) 48I5 MMI,RST Input data 0.0...1000.0 % In 0 Read Volatile Phase current IL2 in percentsIL3 (%) 48I6 MMI,RST Input data 0.0...1000.0 % In 0 Read Volatile Phase current IL3 in percentsTemp SENSOR1 48I7 MMI,RST Input data -50.0...100.0 °C 0 Read Volatile Temperature value from sensor 1

Page 59 of 158

Page 60: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Temp SENSOR2 48I8 MMI,RST Input data -50.0...100.0 °C 0 Read Volatile Temperature value from sensor 2Input SENS_IV 48I9 MMI,RST Input data 0..1[0 = Valid; 1 = Invalid] - 0 Read Volatile Signal indicating sensor faultInput BLOCK 48I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Blocking signalInput TRIGG 48I11 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput RESET 48I12 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

TOL3DevOutput START 48O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal (prior alarm)Output TRIP 48O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput TEMP(%) 48O3 MMI,RST Output data 0000.0...1000.0 % 0 Read Volatile Calculated temperature of the device, maximum from the

stator and the rotorOutput ROTOR(%) 48O4 MMI,RST Output data 0000.0...1000.0 % 0 Read Volatile Temperature of the rotor, per cent value from the

maximum temp of the rotorOutput STATOR(%) 48O5 MMI,RST Output data 0000.0...1000.0 % 0 Read Volatile Temperature of the stator, per cent value from the

maximum temp of the statorOutput COOL_TIME 48O6 MMI,RST Output data 0...86400 s 0 Read Volatile Waiting time for the successful restartOutput TRIP_TIME 48O7 MMI,RST Output data 0...86400 s 0 Read Volatile Predicted time to the tripOutput RESTART 48O8 MMI,RST Output data 0..1[0 = Disabled; 1 = Enabled] - 0 Read Volatile Restart enable signalOutput SENSERR 48O9 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of sensor error signalDate 48V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 48V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeOutput TRIP 48V203 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP outputInput TRIGG 48V204 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGG inputTrip delay 48V205 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Elapsed Trip delay in per centsPrimary current 48V206 MMI,RST Recorded data1 0.0...20000.0 A 0 Read Retain RMS current value (maximum of IL1,IL2 & IL3)Output ROTOR(%) 48V207 MMI,RST Recorded data1 0.0...1000.0 % 0 Read Retain Temperature of the rotor, per cent value from the

maximum temp of the rotorOutput STATOR(%) 48V208 MMI,RST Recorded data1 0.0...1000.0 % 0 Read Retain Temperature of the stator, per cent value from the

maximum temp of the statorAmbient temp 48V209 MMI,RST Recorded data1 -50.0...100.0 °C 0 Read Retain The ambient temperature used for the calculation of the

thermal loadDate 48V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 48V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeOutput TRIP 48V303 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP outputInput TRIGG 48V304 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGG inputTrip delay 48V305 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Elapsed Trip delay in per centsPrimary current 48V306 MMI,RST Recorded data2 0.0...20000.0 A 0 Read Retain RMS current value (maximum of IL1,IL2 & IL3)Output ROTOR(%) 48V307 MMI,RST Recorded data2 0.0...1000.0 % 0 Read Retain Temperature of the rotor, per cent value from the

maximum temp of the rotorOutput STATOR(%) 48V308 MMI,RST Recorded data2 0.0...1000.0 % 0 Read Retain Temperature of the stator, per cent value from the

maximum temp of the statorAmbient temp 48V309 MMI,RST Recorded data2 -50.0...100.0 °C 0 Read Retain The ambient temperature used for the calculation of the

thermal loadDate 48V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 48V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeOutput TRIP 48V403 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP outputInput TRIGG 48V404 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGG inputTrip delay 48V405 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Elapsed Trip delay in per centsPrimary current 48V406 MMI,RST Recorded data3 0.0...20000.0 A 0 Read Retain RMS current value (maximum of IL1,IL2 & IL3)

Page 60 of 158

Page 61: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Output ROTOR(%) 48V407 MMI,RST Recorded data3 0.0...1000.0 % 0 Read Retain Temperature of the rotor, per cent value from the maximum temp of the rotor

Output STATOR(%) 48V408 MMI,RST Recorded data3 0.0...1000.0 % 0 Read Retain Temperature of the stator, per cent value from the maximum temp of the stator

Ambient temp 48V409 MMI,RST Recorded data3 -50.0...100.0 °C 0 Read Retain The ambient temperature used for the calculation of the thermal load

100054 / Rev F MotStartOperation mode 54S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = IIt; 2 = IIt & Stall] - 1 Read Volatile Selection of operation modeStart current 54S2 MMI,RST Actual setting 1.0...10.0 x In 2 Read Volatile Starting current for motorStart time 54S3 MMI,RST Actual setting 0.3...250.0 s 5 Read Volatile Starting time for motorTime limit 54S4 MMI,RST Actual setting 1.0...500.0 s 10 Read Volatile Time-based restart inhibit limitCountdown rate 54S5 MMI,RST Actual setting 2.0...250.0 s/h 60 Read Volatile Countdown rate for the time counterStall time 54S6 MMI,RST Actual setting 2.0...120.0 s 10 Read Volatile Permitted stalling time for rotorOperation mode 54S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = IIt; 2 = IIt & Stall] - 1 Rd/Wr Retain Selection of operation modeStart current 54S42 MMI,RST Setting group1 1.0...10.0 x In 2 Rd/Wr Retain Starting current for motorStart time 54S43 MMI,RST Setting group1 0.3...250.0 s 5 Rd/Wr Retain Starting time for motorTime limit 54S44 MMI,RST Setting group1 1.0...500.0 s 10 Rd/Wr Retain Time-based restart inhibit limitCountdown rate 54S45 MMI,RST Setting group1 2.0...250.0 s/h 60 Rd/Wr Retain Countdown rate for the time counterStall time 54S46 MMI,RST Setting group1 2.0...120.0 s 10 Rd/Wr Retain Permitted stall time for rotorOperation mode 54S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = IIt; 2 = IIt & Stall] - 1 Rd/Wr Retain Selection of operation modeStart current 54S72 MMI,RST Setting group2 1.0...10.0 x In 2 Rd/Wr Retain Starting current for motorStart time 54S73 MMI,RST Setting group2 0.3...250.0 s 5 Rd/Wr Retain Starting time for motorTime limit 54S74 MMI,RST Setting group2 1.0...500.0 s 10 Rd/Wr Retain Time-based restart inhibit limitCountdown rate 54S75 MMI,RST Setting group2 2.0...250.0 s/h 60 Rd/Wr Retain Countdown rate for the time counterStall time 54S76 MMI,RST Setting group2 2.0...120.0 s 10 Rd/Wr Retain Permitted stall time for rotorGroup selection 54V1 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 54V2 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 54V3 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 54V4 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP and STALL outputTrip pulse 54V5 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and STALLStart counter 54V6 MMI,RST Control setting 0...99999 - 0 Read Volatile Start counterTime to restart 54V7 MMI,RST Control setting 0...99999 min 0 Read Volatile Time to restart enableReset registers 54V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 54V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 54V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest STALL 54V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STALLEvent mask 1 54V101 MMI,RST Control setting 0...255 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E7)Event mask 2 54V103 MMI,RST Control setting 0...255 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E7)Event mask 3 54V105 MMI,RST Control setting 0...255 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E7)Event mask 4 54V107 MMI,RST Control setting 0...255 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E7)Current IL1 54I1 MMI,RST Input data 0.0...60.0 x In 0 Read Volatile Phase current IL1Current IL2 54I2 MMI,RST Input data 0.0...60.0 x In 0 Read Volatile Phase current IL2Current IL3 54I3 MMI,RST Input data 0.0...60.0 x In 0 Read Volatile Phase current IL3Input GROUP 54I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input STALL 54I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for motor stalling indicationInput RESET 54I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of MotStartOutput START 54O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 54O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput STALL 54O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of stall signal

Page 61 of 158

Page 62: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Output RESTART 54O4 MMI,RST Output data 0..1[0 = Disabled; 1 = Enabled] - 0 Read Volatile Restart enable signalDate 54V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 54V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeStart time 54V203 MMI,RST Recorded data1 0.0...300.0 s 0 Read Retain Duration of start-up situation in secondsDuration(IIT) 54V204 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start-up situation (IIT)Duration(STALL) 54V205 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start-up situation (STALL)Average IL1 54V206 MMI,RST Recorded data1 0.0...60.0 x In 0 Read Retain Filtered value of IL1Average IL2 54V207 MMI,RST Recorded data1 0.0...60.0 x In 0 Read Retain Filtered value of IL2Average IL3 54V208 MMI,RST Recorded data1 0.0...60.0 x In 0 Read Retain Filtered value of IL3Active group 54V209 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 54V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 54V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeStart time 54V303 MMI,RST Recorded data2 0.0...300.0 s 0 Read Retain Duration of start-up situation in secondsDuration(IIT) 54V304 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start-up situation (IIT)Duration(STALL) 54V305 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start-up situation (STALL)Average IL1 54V306 MMI,RST Recorded data2 0.0...60.0 x In 0 Read Retain Filtered value of IL1Average IL2 54V307 MMI,RST Recorded data2 0.0...60.0 x In 0 Read Retain Filtered value of IL2Average IL3 54V308 MMI,RST Recorded data2 0.0...60.0 x In 0 Read Retain Filtered value of IL3Active group 54V309 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 54V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 54V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeStart time 54V403 MMI,RST Recorded data3 0.0...300.0 s 0 Read Retain Duration of start-up situation in secondsDuration(IIT) 54V404 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start-up situation (IIT)Duration(STALL) 54V405 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start-up situation (STALL)Average IL1 54V406 MMI,RST Recorded data3 0.0...60.0 x In 0 Read Retain Filtered value of IL1Average IL2 54V407 MMI,RST Recorded data3 0.0...60.0 x In 0 Read Retain Filtered value of IL2Average IL3 54V408 MMI,RST Recorded data3 0.0...60.0 x In 0 Read Retain Filtered value of IL3Active group 54V409 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100055 / Rev C PREV3Operation mode 55S1 MMI,RST Actual setting 0..1[0 = Not in use; 1 = 2-phase; 2 = 3-phase] - 2 Read Volatile Selection of operation modeOperate time 55S2 MMI,RST Actual setting 0.1...10.00 s 0,5 Read Volatile Operate time at DT modeRotation dir. 55S3 MMI,RST Actual setting 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Selection of expected rotation directionOperation mode 55S41 MMI,RST Setting group1 0..1[0 = Not in use; 1 = 2-phase; 2 = 3-phase] - 2 Rd/Wr Retain Selection of operation modeOperate time 55S42 MMI,RST Setting group1 0.1...10.0 s 0,5 Rd/Wr Retain Operate time at DT modeRotation dir. 55S43 MMI,RST Setting group1 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Expected rotation directionOperation mode 55S71 MMI,RST Setting group2 0..1[0 = Not in use; 1 = 2-phase; 2 = 3-phase] - 2 Rd/Wr Retain Selection of operation modeOperate time 55S72 MMI,RST Setting group2 0.1...10.0 s 0,5 Rd/Wr Retain Operate time at DT modeRotation dir. 55S73 MMI,RST Setting group2 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Expected rotation directionGroup selection 55V1 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 55V2 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 55V3 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 55V4 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 55V5 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIPReset registers 55V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 55V31 MMI,RST Control setting 0..1[0 = Do not active; 1 = Active] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 55V32 MMI,RST Control setting 0..1[0 = Do not active; 1 = Active] - 0 Rd/Wr Volatile Testing of TRIPEvent mask 1 55V101 MMI,RST Control setting 0...255 - 15 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E7)Event mask 2 55V103 MMI,RST Control setting 0...255 - 15 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E7)Event mask 3 55V105 MMI,RST Control setting 0...255 - 15 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E7)

Page 62 of 158

Page 63: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 4 55V107 MMI,RST Control setting 0...255 - 15 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E7)Current IL1 55I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 55I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 55I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Angle IL1-IL2 55I4 MMI,RST Input data -180...180 ° 0 Read Volatile Phase difference of the currents L1 and L2Angle IL2-IL3 55I5 MMI,RST Input data -180...180 ° 0 Read Volatile Phase difference of the currents L2 and L3Angle IL3-IL1 55I6 MMI,RST Input data -180...180 ° 0 Read Volatile Phase difference of the currents L3 and L1Input BLOCK 55I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of BLOCK signalInput TRIGG 55I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of TRIGG signalInput GROUP 55I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of signal for switching between group 1 and 2Input RESET 55I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of signal for resetting output signals of PREV3Output START 55O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 55O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 55V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 55V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 55V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationCurrent IL1 55V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Phase current IL1Current IL2 55V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Phase current IL2Current IL3 55V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Phase current IL3Angle IL1-IL2 55V207 MMI,RST Recorded data1 -180...180 ° 0 Read Retain Phase difference of the currents L1 and L2Angle IL2-IL3 55V208 MMI,RST Recorded data1 -180...180 ° 0 Read Retain Phase difference of the currents L2 and L3Angle IL3-IL1 55V209 MMI,RST Recorded data1 -180...180 ° 0 Read Retain Phase difference of the currents L3 and L1BLOCK 55V210 MMI,RST Recorded data1 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of BLOCK inputActive group 55V211 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 55V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 55V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 55V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationCurrent IL1 55V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Phase current IL1Current IL2 55V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Phase current IL2Current IL3 55V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Phase current IL3Angle IL1-IL2 55V307 MMI,RST Recorded data2 -180...180 ° 0 Read Retain Phase difference of the currents L1 and L2Angle IL2-IL3 55V308 MMI,RST Recorded data2 -180...180 ° 0 Read Retain Phase difference of the currents L2 and L3Angle IL3-IL1 55V309 MMI,RST Recorded data2 -180...180 ° 0 Read Retain Phase difference of the currents L3 and L1BLOCK 55V310 MMI,RST Recorded data2 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of BLOCK inputActive group 55V311 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 55V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 55V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 55V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationCurrent IL1 55V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Phase current IL1Current IL2 55V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Phase current IL2Current IL3 55V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Phase current IL3Angle IL1-IL2 55V407 MMI,RST Recorded data3 -180...180 ° 0 Read Retain Phase difference of the currents L1 and L2Angle IL2-IL3 55V408 MMI,RST Recorded data3 -180...180 ° 0 Read Retain Phase difference of the currents L2 and L3Angle IL3-IL1 55V409 MMI,RST Recorded data3 -180...180 ° 0 Read Retain Phase difference of the currents L3 and L1BLOCK 55V410 MMI,RST Recorded data3 0..1[0 = Not active; 1=Active] - 0 Read Retain Status of BLOCK inputActive group 55V411 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100062 / Rev E OV3LowOperation mode 62S1 MMI,RST Actual setting 0..3[0 = Not in use; 1 = Definite time; 2 = A curve; 3 = B

curve]- 1 Read Volatile Selection of operation mode and inverse time characteristic

at IDMT mode

Page 63 of 158

Page 64: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Start voltage 62S2 MMI,RST Actual setting 0.10...1.60 x Un 1,1 Read Volatile Start voltageOperate time 62S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DT modeTime multiplier 62S4 MMI,RST Actual setting 0.05...1.00 - 0,05 Read Volatile Time multiplier at IDMT modeOperation mode 62S41 MMI,RST Setting group1 0..3[0 = Not in use; 1 = Definite time; 2 = A curve; 3 = B

curve]- 1 Rd/Wr Retain Selection of operation mode and inverse time characteristic

at IDMT modeStart voltage 62S42 MMI,RST Setting group1 0.10...1.60 x Un 1,1 Rd/Wr Retain Start voltageOperate time 62S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeTime multiplier 62S44 MMI,RST Setting group1 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeOperation mode 62S71 MMI,RST Setting group2 0..3[0 = Not in use; 1 = Definite time; 2 = A curve; 3 = B

curve]- 1 Rd/Wr Retain Selection of operation mode and inverse time characteristic

at IDMT modeStart voltage 62S72 MMI,RST Setting group2 0.10...1.60 x Un 1,1 Rd/Wr Retain Start voltageOperate time 62S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeTime multiplier 62S74 MMI,RST Setting group2 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeMeasuring mode 62V1 MMI,RST Control setting 0..2[0 = Mode 1; 1 = Mode 2; 2 = Mode 3] - 0 Rd/Wr Retain Selection of measuring modeGroup selection 62V2 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 62V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 62V4 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 62V5 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 62V6 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIPOper. hysteresis 62V7 MMI,RST Control setting 1.0...5.0 % 4 Rd/Wr Retain Operation hysteresisReset registers 62V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 62V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 62V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPEvent mask 1 62V101 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 62V103 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 62V105 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 62V107 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Voltage UL1_U12 62I1 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U12 or phase-to-earth voltage UL1

Voltage UL2_U23 62I2 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U23 or phase-to-earth voltage UL2

Voltage UL3_U31 62I3 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U31 or phase-to-earth voltage UL3

Input BS1 62I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 62I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 62I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 62I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 62I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of Output START 62O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 62O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 62V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 62V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 62V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 62V204 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 62V205 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 62V206 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 62V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 62V208 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 62V209 MMI,RST Recorded data1 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting group

Page 64 of 158

Page 65: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Date 62V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 62V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 62V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 62V304 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 62V305 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 62V306 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 62V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 62V308 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 62V309 MMI,RST Recorded data2 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 62V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 62V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 62V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 62V404 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 62V405 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 62V406 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 62V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 62V408 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 62V409 MMI,RST Recorded data3 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting group

100063 / Rev D OV3HighOperation mode 63S1 MMI,RST Actual setting 0..1[0 = Not in use; 1 = Definite time] - 1 Read Volatile Selection of operation modeStart voltage 63S2 MMI,RST Actual setting 0.10...1.60 x Un 1,1 Read Volatile Start voltageOperate time 63S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DT modeOperation mode 63S41 MMI,RST Setting group1 0..1[0 = Not in use; 1 = Definite time] - 1 Rd/Wr Retain Selection of operation modeStart voltage 63S42 MMI,RST Setting group1 0.10...1.60 x Un 1,1 Rd/Wr Retain Start voltageOperate time 63S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeOperation mode 63S71 MMI,RST Setting group2 0..1[0 = Not in use; 1 = Definite time] - 1 Rd/Wr Retain Selection of operation modeStart voltage 63S72 MMI,RST Setting group2 0.10...1.60 x Un 1,1 Rd/Wr Retain Start voltageOperate time 63S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate time at DT modeMeasuring mode 63V1 MMI,RST Control setting 0..2[0 = Mode 1; 1 = Mode 2; 2 = Mode 3] - 0 Rd/Wr Retain Selection of measuring modeGroup selection 63V2 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 63V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 63V4 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 63V5 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 63V6 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIPOper. hysteresis 63V7 MMI,RST Control setting 1.0...5.0 % 4 Rd/Wr Retain Operation hysteresisReset registers 63V13 RST Control setting 0..1[0 = 0; 1= Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 63V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 63V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPEvent mask 1 63V101 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 63V103 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 63V105 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 63V107 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Voltage UL1_U12 63I1 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage UL1 or phase-to-phase voltage U12

Voltage UL2_U23 63I2 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage UL2 or phase-to-phase voltage U23

Voltage UL3_U31 63I3 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-earth voltage UL3 or phase-to-phase voltage U31

Input BS1 63I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1

Page 65 of 158

Page 66: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Input BS2 63I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 63I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 63I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 63I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

OV3HighOutput START 63O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 63O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 63V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 63V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 63V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 63V204 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 63V205 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 63V206 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 63V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 63V208 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 63V209 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 63V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 63V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 63V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 63V304 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 63V305 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 63V306 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 63V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 63V308 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 63V309 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 63V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 63V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 63V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 63V404 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 63V405 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 63V406 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 63V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 63V408 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 63V409 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100064 / Rev D UV3LowOperation mode 64S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Definite time; 2 = C curve] - 1 Read Volatile Selection of operation mode and inverse time curve at

IDMT modeStart voltage 64S2 MMI,RST Actual setting 0.10...1.20 x Un 0,9 Read Volatile Start voltageOperate time 64S3 MMI,RST Actual setting 0.1...300.0 s 0,1 Read Volatile Operate time at DT modeTime multiplier 64S4 MMI,RST Actual setting 0.1...1.0 - 0,1 Read Volatile Time multiplier at IDMTmodeOperation mode 64S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Definite time; 2 = C curve] - 1 Rd/Wr Retain Selection of operation mode and inverse time curve at

IDMT modeStart voltage 64S42 MMI,RST Setting group1 0.10...1.20 x Un 0,9 Rd/Wr Retain Start voltageOperate time 64S43 MMI,RST Setting group1 0.1...300.0 s 0,1 Rd/Wr Retain Operate time at DT modeTime multiplier 64S44 MMI,RST Setting group1 0.1...1.0 - 0,1 Rd/Wr Retain Time multiplier at IDMT modeOperation mode 64S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Definite time; 2 = C curve] - 1 Rd/Wr Retain Selection of operation mode and inverse time curve at

IDMT modeStart voltage 64S72 MMI,RST Setting group2 0.10...1.20 x Un 0,9 Rd/Wr Retain Start voltageOperate time 64S73 MMI,RST Setting group2 0.1...300.0 s 0,1 Rd/Wr Retain Operate time at DT mode

Page 66 of 158

Page 67: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Time multiplier 64S74 MMI,RST Setting group2 0.1...1.0 - 0,1 Rd/Wr Retain Time multiplier at IDMT modeMeasuring mode 64V1 MMI,RST Control setting 0..2[0 = Mode 1; 1 = Mode 2; 2 = Mode 3] - 0 Rd/Wr Retain Selection of measuring modeVoltage select. 64V2 MMI,RST Control setting 1..7[1 = U12; 2 = U23; 3 = U12 & U23; 4 = U31; 5 =

U12 & U31; 6 = U23 & U31; 7 = U12 & U23 & U31]- 7 Rd/Wr Retain Selection of voltages

Group selection 64V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 64V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 64V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 64V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 64V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIPIntern. blocking 64V8 MMI,RST Control setting 0..1[0 = Disabled; 1 = Enabled] - 1 Rd/Wr Retain Enabling of internal undervoltage blockingOper. hysteresis 64V9 MMI,RST Control setting 1.0...5.0 % 4 Rd/Wr Retain Operation hysteresisReset registers 64V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 64V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 64V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPEvent mask 1 64V101 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 64V103 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 64V105 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 64V107 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Voltage UL1_U12 64I1 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U12 or phase-to-earth voltage UL1

Voltage UL2_U23 64I2 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U23 or phase-to-earth voltage UL2

Voltage UL3_U31 64I3 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U31 or phase-to-earth voltage UL3

Input BS1 64I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 64I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 64I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 64I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 64I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of Output START 64O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 64O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 64V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 64V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 64V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 64V204 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 64V205 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 64V206 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 64V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 64V208 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 64V209 MMI,RST Recorded data1 0..1[0=Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 64V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 64V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 64V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 64V304 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 64V305 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 64V306 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 64V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 64V308 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 64V309 MMI,RST Recorded data2 0..1[0=Group 1; 1=Group 2] - 0 Read Retain Active setting group

Page 67 of 158

Page 68: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Date 64V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 64V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 64V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 64V404 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 64V405 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 64V406 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 64V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 64V408 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 64V409 MMI,RST Recorded data3 0..1[0=Group 1; 1=Group 2] - 0 Read Retain Active setting group

100065 / Rev D UV3HighOperation mode 65S1 MMI,RST Actual setting 0..1[0 = Not in use; 1 = Definite time] - 1 Read Volatile Selection of operation modeStart voltage 65S2 MMI,RST Actual setting 0.10...1.20 x Un 0,9 Read Volatile Start voltageOperate time 65S3 MMI,RST Actual setting 0.1...300.0 s 0,1 Read Volatile Operate time at DT modeOperation mode 65S41 MMI,RST Setting group1 0..1[0 = Not in use; 1 = Definite time] - 1 Rd/Wr Retain Selection of operation modeStart voltage 65S42 MMI,RST Setting group1 0.10...1.20 x Un 0,9 Rd/Wr Retain Start voltageOperate time 65S43 MMI,RST Setting group1 0.1...300.0 s 0,1 Rd/Wr Retain Operate time at DT modeOperation mode 65S71 MMI,RST Setting group2 0..1[0 = Not in use; 1 = Definite time] - 1 Rd/Wr Retain Selection of operation modeStart voltage 65S72 MMI,RST Setting group2 0.10...1.20 x Un 0,9 Rd/Wr Retain Start voltageOperate time 65S73 MMI,RST Setting group2 0.1...300.0 s 0,1 Rd/Wr Retain Operate time at DT modeMeasuring mode 65V1 MMI,RST Control setting 0..2[0 = Mode 1; 1 = Mode 2; 2 = Mode 3] - 0 Rd/Wr Retain Selection of measuring modeVoltage select. 65V2 MMI,RST Control setting 1..7[1 = U12; 2 = U23; 3 = U12 & U23; 4 = U31; 5 =

U12 & U31; 6 = U23 & U31; 7 = U12 & U23 & U31]- 7 Rd/Wr Retain Selection of voltages

Group selection 65V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 65V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 65V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 65V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 65V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIPIntern. blocking 65V8 MMI,RST Control setting 0..1[0 = Disabled; 1 = Enabled] - 1 Rd/Wr Retain Enabling of internal undervoltage blockingOper. hysteresis 65V9 MMI,RST Control setting 1.0...5.0 % 4 Rd/Wr Retain Operation hysteresisReset registers 65V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 65V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 65V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPEvent mask 1 65V101 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 65V103 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 65V105 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 65V107 MMI,RST Control setting 0...1023 - 15 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Voltage UL1_U12 65I1 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U12 or phase-to-earth voltage UL1

Voltage UL2_U23 65I2 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U23 or phase-to-earth voltage UL2

Voltage UL3_U31 65I3 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Phase-to-phase voltage U31 or phase-to-earth voltage UL3

Input BS1 65I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 65I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 65I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 65I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 65I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

UV3HighOutput START 65O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal

Page 68 of 158

Page 69: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Output TRIP 65O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 65V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 65V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 65V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 65V204 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 65V205 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 65V206 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 65V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 65V208 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 65V209 MMI,RST Recorded data1 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 65V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 65V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 65V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 65V304 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 65V305 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 65V306 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 65V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 65V308 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 65V309 MMI,RST Recorded data2 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 65V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 65V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 65V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationVoltage UL1_U12 65V404 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U12Voltage UL2_U23 65V405 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U23Voltage UL3_U31 65V406 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Filtered value of U31BS1 65V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 65V408 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 65V409 MMI,RST Recorded data3 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting group

100066 / Rev E UE6LowCircle offset 66S1 MMI,RST Actual setting -10.00...10.00 p.u. -0,1 Read Volatile Distance of the top of the impedance circle and the R-axisCircle diameter 66S2 MMI,RST Actual setting 0.01...60.00 p.u. 2 Read Volatile Diameter of the impedance circleCir.displacem. 66S3 MMI,RST Actual setting -10.00...10.00 p.u. 0 Read Volatile Displacement of the center of the impedance circle from

the X-axisOperate time 66S4 MMI,RST Actual setting 0.06...60.00 s 5 Read Volatile Tripping timeCircle offset 66S41 MMI,RST Setting group1 -10.00...10.00 p.u. -0,1 Rd/Wr Retain Distance of the top of the impedance circle and the R-axisCircle diameter 66S42 MMI,RST Setting group1 0.01...60.00 p.u. 2 Rd/Wr Retain Diameter of the impedance circleCir.displacem. 66S43 MMI,RST Setting group1 -10.00...10.00 p.u. 0 Rd/Wr Retain Displacement of the center of the impedance circle from

the X-axisOperate time 66S44 MMI,RST Setting group1 0.06...60.00 s 5 Rd/Wr Retain Tripping timeCircle offset 66S71 MMI,RST Setting group2 -10.00...10.00 p.u. -0,1 Rd/Wr Retain Distance of the top of the impedance circle and the R-axisCircle diameter 66S72 MMI,RST Setting group2 0.01...60.00 p.u. 2 Rd/Wr Retain Diameter of the impedance circleCir.displacem. 66S73 MMI,RST Setting group2 -10.00...10.00 p.u. 0 Rd/Wr Retain Displacement of the center of the impedance circle from

the X-axisOperate time 66S74 MMI,RST Setting group2 0.06...60.00 s 5 Rd/Wr Retain Tripping timeMeasuring mode 66V1 MMI,RST Control setting 0..6[0 = Not in use; 1 = U1&I1; 2 = U12&I1&I2; 3 = 3

phase-earth; 4 = 3 phase-phase; 5 = 3 p-e pos.seq.; 6 = 3 p-p pos.seq.]

- 2 Rd/Wr Retain Selection of the meas. mode: 1 or 3 phase, phase-earth or phase-phase voltages and fund. or pos. sequence components. (6 modes)

Excit.curr.trip 66V2 MMI,RST Control setting 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Selection of the excitation current tripDrop-off time 66V3 MMI,RST Control setting 0.00...10.00 s 3 Rd/Wr Retain Drop-off time

Page 69 of 158

Page 70: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Group selection 66V4 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 66V5 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 66V6 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 66V7 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 66V8 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 66V9 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPOper. direction 66V10 MMI,RST Control setting 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Operation directionReset registers 66V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 66V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 66V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 66V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 66V101 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11, E13)Event mask 2 66V103 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11, E13)Event mask 3 66V105 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11, E13)Event mask 4 66V107 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11, E13)Impedance Z1 66I1 MMI,RST Input data 0.00...999.99 p.u. 0 Read Volatile Phase impedance Z1Impedance Z2 66I2 MMI,RST Input data 0.00...999.99 p.u. 0 Read Volatile Phase impedance Z2Impedance Z3 66I3 MMI,RST Input data 0.00...999.99 p.u. 0 Read Volatile Phase impedance Z3Angle A1 66I4 MMI,RST Input data -180...180 ° 0 Read Volatile Angle A1 of the impedance in phase 1Angle A2 66I5 MMI,RST Input data -180...180 ° 0 Read Volatile Angle A2 of the impedance in phase 2Angle A3 66I6 MMI,RST Input data -180...180 ° 0 Read Volatile Angle A3 of the impedance in phase 3Excit.cur.alarm 66I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for supervising the exitation currentExtern. BLOCK 66I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile External block signalIntern. BLOCK 66I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Internal block signalInput GROUP 66I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 66I11 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of Output START 66O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 66O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput ERR 66O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of error signalDate 66V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 66V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 66V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationZ1 66V204 MMI,RST Recorded data1 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 1Z2 66V205 MMI,RST Recorded data1 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 2Z3 66V206 MMI,RST Recorded data1 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 3A1 66V207 MMI,RST Recorded data1 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 1A2 66V208 MMI,RST Recorded data1 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 2A3 66V209 MMI,RST Recorded data1 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 3Excit.cur.alarm 66V210 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Signal for supervising the excitation current BLOCK 66V211 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 66V212 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 66V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 66V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 66V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationZ1 66V304 MMI,RST Recorded data2 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 1Z2 66V305 MMI,RST Recorded data2 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 2Z3 66V306 MMI,RST Recorded data2 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 3A1 66V307 MMI,RST Recorded data2 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 1A2 66V308 MMI,RST Recorded data2 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 2

Page 70 of 158

Page 71: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

A3 66V309 MMI,RST Recorded data2 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 3Excit.cur.alarm 66V310 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of the excitation current BLOCK 66V311 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 66V312 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 66V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 66V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 66V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationZ1 66V404 MMI,RST Recorded data3 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 1Z2 66V405 MMI,RST Recorded data3 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 2Z3 66V406 MMI,RST Recorded data3 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 3A1 66V407 MMI,RST Recorded data3 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 1A2 66V408 MMI,RST Recorded data3 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 2A3 66V409 MMI,RST Recorded data3 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 3Excit.cur.alarm 66V410 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of the excitation current BLOCK 66V411 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 66V412 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100067 / Rev E UE6HighCircle offset 67S1 MMI,RST Actual setting -10.00...10.00 p.u. -0,1 Read Volatile Distance of the top of the impedance circle and the R-axisCircle diameter 67S2 MMI,RST Actual setting 0.01...60.00 p.u. 2 Read Volatile Diameter of the impedance circleCir.displacem. 67S3 MMI,RST Actual setting -10.00...10.00 p.u. 0 Read Volatile Displacement of the center of the impedance circle from

the X-axisOperate time 67S4 MMI,RST Actual setting 0.06...10.00 s 1 Read Volatile Tripping timeCircle offset 67S41 MMI,RST Setting group1 -10.00...10.00 p.u. -0,1 Rd/Wr Retain Distance of the top of the impedance circle and the R-axisCircle diameter 67S42 MMI,RST Setting group1 0.01...60.00 p.u. 2 Rd/Wr Retain Diameter of the impedance circleCir.displacem. 67S43 MMI,RST Setting group1 -10.00...10.00 p.u. 0 Rd/Wr Retain Displacement of the center of the impedance circle from

the X-axisOperate time 67S44 MMI,RST Setting group1 0.06...10.00 s 1 Rd/Wr Retain Tripping timeCircle offset 67S71 MMI,RST Setting group2 -10.00...10.00 p.u. -0,1 Rd/Wr Retain Distance of the top of the impedance circle and the R-axisCircle diameter 67S72 MMI,RST Setting group2 0.01...60.00 p.u. 2 Rd/Wr Retain Diameter of the impedance circleCir.displacem. 67S73 MMI,RST Setting group2 -10.00...10.00 p.u. 0 Rd/Wr Retain Displacement of the center of the impedance circle from

the X-axisOperate time 67S74 MMI,RST Setting group2 0.06...10.00 s 1 Rd/Wr Retain Tripping timeMeasuring mode 67V1 MMI,RST Control setting 0..6[0 = Not in use; 1 = U1&I1; 2 = U12&I1&I2; 3 = 3

phase-earth; 4 = 3 phase-phase; 5 = 3 p-e pos.seq.; 6 = 3 p-p pos.seq.]

- 2 Rd/Wr Retain Selection of the meas. mode: 1 or 3 phase, phase-earth or phase-phase voltages and fund. or pos. sequence components. (5 modes)

Excit.curr.trip 67V2 MMI,RST Control setting 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Selection of the excitation current tripDrop-off time 67V3 MMI,RST Control setting 0.00...10.00 s 3 Rd/Wr Retain Drop-off timeGroup selection 67V4 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 67V5 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 67V6 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 67V7 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 67V8 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 67V9 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPOper. direction 67V10 MMI,RST Control setting 0..1[0 = Forward; 1 = Reverse] - 0 Rd/Wr Retain Operation directionReset registers 67V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 67V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 67V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 67V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 67V101 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11, E13)

Page 71 of 158

Page 72: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 2 67V103 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11, E13)Event mask 3 67V105 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11, E13)Event mask 4 67V107 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11, E13)Impedance Z1 67I1 MMI,RST Input data 0.00...999.99 p.u. 0 Read Volatile Phase impedance Z1Impedance Z2 67I2 MMI,RST Input data 0.00...999.99 p.u. 0 Read Volatile Phase impedance Z2Impedance Z3 67I3 MMI,RST Input data 0.00...999.99 p.u. 0 Read Volatile Phase impedance Z3Angle A1 67I4 MMI,RST Input data -180...180 ° 0 Read Volatile Angle A1 of the impedance in phase 1Angle A2 67I5 MMI,RST Input data -180...180 ° 0 Read Volatile Angle A2 of the impedance in phase 2Angle A3 67I6 MMI,RST Input data -180...180 ° 0 Read Volatile Angle A3 of the impedance in phase 3Excit.cur.alarm 67I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for supervising the exitation currentExtern. BLOCK 67I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile External block signalIntern. BLOCK 67I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Internal block signalInput GROUP 67I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 67I11 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

UE6HighOutput START 67O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 67O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput ERR 67O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of error signalDate 67V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 67V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 67V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationZ1 67V204 MMI,RST Recorded data1 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 1Z2 67V205 MMI,RST Recorded data1 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 2Z3 67V206 MMI,RST Recorded data1 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 3A1 67V207 MMI,RST Recorded data1 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 1A2 67V208 MMI,RST Recorded data1 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 2A3 67V209 MMI,RST Recorded data1 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 3Excit.cur.alarm 67V210 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Signal for supervising the excitation current BLOCK 67V211 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 67V212 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 67V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 67V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 67V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationZ1 67V304 MMI,RST Recorded data2 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 1Z2 67V305 MMI,RST Recorded data2 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 2Z3 67V306 MMI,RST Recorded data2 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 3A1 67V307 MMI,RST Recorded data2 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 1A2 67V308 MMI,RST Recorded data2 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 2A3 67V309 MMI,RST Recorded data2 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 3Excit.cur.alarm 67V310 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of the excitation current BLOCK 67V311 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 67V312 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 67V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 67V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 67V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationZ1 67V404 MMI,RST Recorded data3 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 1Z2 67V405 MMI,RST Recorded data3 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 2Z3 67V406 MMI,RST Recorded data3 0.00...999.99 p.u. 0 Read Retain Calculated impedance in phase 3A1 67V407 MMI,RST Recorded data3 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 1

Page 72 of 158

Page 73: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

A2 67V408 MMI,RST Recorded data3 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 2A3 67V409 MMI,RST Recorded data3 -180...180 ° 0 Read Retain Calculated angle of the impedance in phase 3Excit.cur.alarm 67V410 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of the excitation current BLOCK 67V411 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 67V412 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100068 / Rev E OE1LowU/f start DT 68S1 MMI,RST Actual setting 1.00...2.00 x U/f 1,4 Read Volatile Proportional overexcitation that has to be reached before

definite time operationU/f start IDMT 68S2 MMI,RST Actual setting 1.00...2.00 x U/f 1,1 Read Volatile Proportional overexictation that has to be reached before

inverse time operationU max cont. 68S3 MMI,RST Actual setting 0.80...1.60 x Un 1 Read Volatile Maximum continuous operating value without damageOperate time 68S4 MMI,RST Actual setting 0.10...600.00 s 0,5 Read Volatile Required duration of overexcitation condition before TRIP

in definite time operationK 68S5 MMI,RST Actual setting 0.1...100.0 - 3 Read Volatile Parameter for operation curve in IDMT operation,

multiplierMaximum time 68S6 MMI,RST Actual setting 500...10000 s 1000 Read Volatile Maximum operate time in IDMT mode regardless of

inverse characteristicConstant delay 68S7 MMI,RST Actual setting 0.1...120.0 s 0,8 Read Volatile Constant/minimum time parameter in IDMT operationCooling time 68S8 MMI,RST Actual setting 5...10000 s 600 Read Volatile Cooling time of the generator/transformerU/f start DT 68S41 MMI,RST Setting group1 1.00...2.00 x U/f 1,4 Rd/Wr Retain Proportional overexcitation that has to be reached before

definite time operationU/f start IDMT 68S42 MMI,RST Setting group1 1.00...2.00 x U/f 1,1 Rd/Wr Retain Proportional overexictation that has to be reached before

inverse time operationU max cont. 68S43 MMI,RST Setting group1 0.80...1.60 x Un 1 Rd/Wr Retain Maximum continuous operating value without damageOperate time 68S44 MMI,RST Setting group1 0.10...600.00 s 0,5 Rd/Wr Retain Required duration of overexcitation condition before TRIP

in definite time operationK 68S45 MMI,RST Setting group1 0.1...100.0 - 3 Rd/Wr Retain Parameter for operation curve in IDMT operation,

multiplierMaximum time 68S46 MMI,RST Setting group1 500...10000 s 1000 Rd/Wr Retain Maximum operate time in IDMT mode regardless of

inverse characteristicConstant delay 68S47 MMI,RST Setting group1 0.1...120.0 s 0,8 Rd/Wr Retain Constant/minimum time parameter in IDMT operationCooling time 68S48 MMI,RST Setting group1 5...10000 s 600 Rd/Wr Retain Cooling time of the generator/transformerU/f start DT 68S71 MMI,RST Setting group2 1.00...2.00 x U/f 1,4 Rd/Wr Retain Proportional overexcitation that has to be reached before

definite time operationU/f start IDMT 68S72 MMI,RST Setting group2 1.00...2.00 x U/f 1,1 Rd/Wr Retain Proportional overexictation that has to be reached before

inverse time operationU max cont. 68S73 MMI,RST Setting group2 0.80...1.60 x Un 1 Rd/Wr Retain Maximum continuous operating value without damageOperate time 68S74 MMI,RST Setting group2 0.10...600.00 s 0,5 Rd/Wr Retain Required duration of overexcitation condition before TRIP

in definite time operationK 68S75 MMI,RST Setting group2 0.1...100.0 - 3 Rd/Wr Retain Parameter for operation curve in IDMT operation,

multiplierMaximum time 68S76 MMI,RST Setting group2 500...10000 s 1000 Rd/Wr Retain Maximum operate time in IDMT mode regardless of

inverse characteristicConstant delay 68S77 MMI,RST Setting group2 0.1...120.0 s 0,8 Rd/Wr Retain Constant/minimum time parameter in IDMT operationCooling time 68S78 MMI,RST Setting group2 5...10000 s 600 Rd/Wr Retain Cooling time of the generator/transformerOperation mode 68V1 MMI,RST Control setting 0..3[0 = Not in use; 1 = Definite time; 2 = Inv.curve #1; 3

= Inv.curve #2]- 1 Rd/Wr Retain Selection of operation mode

Drop-off time 68V2 MMI,RST Control setting 0.05...10.00 s 0,1 Rd/Wr Retain Resetting time of the operate time counter at DT modeGroup selection 68V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting group

Page 73 of 158

Page 74: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Active group 68V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 68V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 68V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 68V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 68V8 MMI,RST Control setting 100...1000 ms 150 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 68V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 68V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 68V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 68V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 68V101 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9, E11)Event mask 2 68V103 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9, E11)Event mask 3 68V105 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9, E11)Event mask 4 68V107 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9, E11)U/f ratio 68I1 MMI,RST Input data 0.00...20.00 x U/f 0 Read Volatile Calculated U/f ratioInput BLOCK 68I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking OE1LowInput GROUP 68I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 68I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of Output START 68O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of START signalOutput TRIP 68O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of TRIP signalOutput ERR 68O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of ERR signalDate 68V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 68V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 68V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationU/f ratio 68V204 MMI,RST Recorded data1 0.00...20.00 x U/f 0 Read Retain U/f-ratio at the moment of registrationBLOCK 68V205 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK signalActive group 68V206 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 68V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 68V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 68V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationU/f ratio 68V304 MMI,RST Recorded data2 0.00...20.00 x U/f 0 Read Retain U/f-ratio at the moment of registrationBLOCK 68V305 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK signalActive group 68V306 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 68V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 68V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 68V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationU/f ratio 68V404 MMI,RST Recorded data3 0.00...20.00 x U/f 0 Read Retain U/f-ratio at the moment of registrationBLOCK 68V405 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK signalActive group 68V406 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100069 / Rev E OE1HighU/f start DT 69S1 MMI,RST Actual setting 1.00...2.00 x U/f 1,4 Read Volatile Proportional overexcitation that has to be reached before

definite time operationU/f start IDMT 69S2 MMI,RST Actual setting 1.00...2.00 x U/f 1,1 Read Volatile Proportional overexictation that has to be reached before

inverse time operationU max cont. 69S3 MMI,RST Actual setting 0.80...1.60 x Un 1 Read Volatile Maximum continuous operating value without damageOperate time 69S4 MMI,RST Actual setting 0.10...600.00 s 0,5 Read Volatile Required duration of overexcitation condition before TRIP

in definite time operationK 69S5 MMI,RST Actual setting 0.1...100.0 - 3 Read Volatile Parameter for operation curve in IDMT operation,

multiplier

Page 74 of 158

Page 75: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Maximum time 69S6 MMI,RST Actual setting 500...10000 s 1000 Read Volatile Maximum operate time in IDMT mode regardless of inverse characteristic

Constant delay 69S7 MMI,RST Actual setting 0.1...120.0 s 0,8 Read Volatile Constant/minimum time parameter in IDMT operationCooling time 69S8 MMI,RST Actual setting 5...10000 s 600 Read Volatile Cooling time of the generator/transformerU/f start DT 69S41 MMI,RST Setting group1 1.00...2.00 x U/f 1,4 Rd/Wr Retain Proportional overexcitation that has to be reached before

definite time operationU/f start IDMT 69S42 MMI,RST Setting group1 1.00...2.00 x U/f 1,1 Rd/Wr Retain Proportional overexictation that has to be reached before

inverse time operationU max cont. 69S43 MMI,RST Setting group1 0.80...1.60 x Un 1 Rd/Wr Retain Maximum continuous operating value without damageOperate time 69S44 MMI,RST Setting group1 0.10...600.00 s 0,5 Rd/Wr Retain Required duration of overexcitation condition before TRIP

in definite time operationK 69S45 MMI,RST Setting group1 0.1...100.0 - 3 Rd/Wr Retain Parameter for operation curve in IDMT operation,

multiplierMaximum time 69S46 MMI,RST Setting group1 500...10000 s 1000 Rd/Wr Retain Maximum operate time in IDMT mode regardless of

inverse characteristicConstant delay 69S47 MMI,RST Setting group1 0.1...120.0 s 0,8 Rd/Wr Retain Constant/minimum time parameter in IDMT operationCooling time 69S48 MMI,RST Setting group1 5...10000 s 600 Rd/Wr Retain Cooling time of the generator/transformerU/f start DT 69S71 MMI,RST Setting group2 1.00...2.00 x U/f 1,4 Rd/Wr Retain Proportional overexcitation that has to be reached before

definite time operationU/f start IDMT 69S72 MMI,RST Setting group2 1.00...2.00 x U/f 1,1 Rd/Wr Retain Proportional overexictation that has to be reached before

inverse time operationU max cont. 69S73 MMI,RST Setting group2 0.80...1.60 x Un 1 Rd/Wr Retain Maximum continuous operating value without damageOperate time 69S74 MMI,RST Setting group2 0.10...600.00 s 0,5 Rd/Wr Retain Required duration of overexcitation condition before TRIP

in definite time operationK 69S75 MMI,RST Setting group2 0.1...100.0 - 3 Rd/Wr Retain Parameter for operation curve in IDMT operation,

multiplierMaximum time 69S76 MMI,RST Setting group2 500...10000 s 1000 Rd/Wr Retain Maximum operate time in IDMT mode regardless of

inverse characteristicConstant delay 69S77 MMI,RST Setting group2 0.1...120.0 s 0,8 Rd/Wr Retain Constant/minimum time parameter in IDMT operationCooling time 69S78 MMI,RST Setting group2 5...10000 s 600 Rd/Wr Retain Cooling time of the generator/transformerOperation mode 69V1 MMI,RST Control setting 0..3[0 = Not in use; 1 = Definite time; 2 = Inv.curve #1; 3

= Inv.curve #2]- 1 Rd/Wr Retain Selection of operation mode

Drop-off time 69V2 MMI,RST Control setting 0.05...10.00 s 0,1 Rd/Wr Retain Resetting time of the operate time counter at DT modeGroup selection 69V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 69V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 69V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 69V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 69V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 69V8 MMI,RST Control setting 100...1000 ms 150 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 69V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 69V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 69V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 69V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 69V101 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9, E11)Event mask 2 69V103 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9, E11)Event mask 3 69V105 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9, E11)Event mask 4 69V107 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9, E11)U/f ratio 69I1 MMI,RST Input data 0.00...20.00 x Un/fn 0 Read Volatile Calculated U/f ratioInput BLOCK 69I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking OE1High

Page 75 of 158

Page 76: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Input GROUP 69I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 69I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

OE1HighOutput START 69O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of START signalOutput TRIP 69O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of TRIP signalOutput ERR 69O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of ERR signalDate 69V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 69V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 69V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationU/f ratio 69V204 MMI,RST Recorded data1 0.00...20.00 x U/f 0 Read Retain U/f-ratio at the moment of registrationBLOCK 69V205 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK signalActive group 69V206 MMI,RST Recorded data1 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 69V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 69V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 69V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationU/f ratio 69V304 MMI,RST Recorded data2 0.00...20.00 x U/f 0 Read Retain U/f-ratio at the moment of registrationBLOCK 69V305 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK signalActive group 69V306 MMI,RST Recorded data2 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 69V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 69V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 69V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationU/f ratio 69V404 MMI,RST Recorded data3 0.00...20.00 x U/f 0 Read Retain U/f-ratio at the moment of registrationBLOCK 69V405 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK signalActive group 69V406 MMI,RST Recorded data3 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting group

100070 / Rev H SCVCSt1Umax 70S1 MMI,RST Actual Setting 0.50...1.00 x Un 1 Read Volatile Upper threshold voltageUmin 70S2 MMI,RST Actual Setting 0.10...0.80 x Un 0,1 Read Volatile Lower threshold voltagedU 70S3 MMI,RST Actual Setting 0.02...0.60 x Un 0,02 Read Volatile Voltage differencedphase 70S4 MMI,RST Actual Setting 5...90 ° 5 Read Volatile Phase angle differencedf 70S5 MMI,RST Actual Setting 0.02...5.00 Hz 0,02 Read Volatile Frequency differenseUmax 70S41 MMI,RST Setting group1 0.50...1.00 x Un 1 Rd/Wr Retain Upper threshold voltageUmin 70S42 MMI,RST Setting group1 0.10...0.80 x Un 0,1 Rd/Wr Retain Lower threshold voltagedU 70S43 MMI,RST Setting group1 0.02...0.60 x Un 0,02 Rd/Wr Retain Voltage differencedphase 70S44 MMI,RST Setting group1 5...90 ° 5 Rd/Wr Retain Phase angle differencedf 70S45 MMI,RST Setting group1 0.02...5.00 Hz 0,02 Rd/Wr Retain Frequency differenseUmax 70S71 MMI,RST Setting group2 0.50...1.00 x Un 1 Rd/Wr Retain Upper threshold voltageUmin 70S72 MMI,RST Setting group2 0.10...0.80 x Un 0,1 Rd/Wr Retain Lower threshold voltagedU 70S73 MMI,RST Setting group2 0.02...0.60 x Un 0,02 Rd/Wr Retain Voltage differencedphase 70S74 MMI,RST Setting group2 5...90 ° 5 Rd/Wr Retain Phase angle differencedf 70S75 MMI,RST Setting group2 0.02...5.00 Hz 0,02 Rd/Wr Retain Frequency differenseEnergizing mode 70V1 MMI,RST Control setting 0..4[0 = Not in use; 1 = U1->U2, U2->U1; 2 = U1->U2; 3

= U2->U1; 4 = U1>U2,U2>U1,0>0]- 1 Rd/Wr Retain Selection of energizing mode

Operation mode 70V2 MMI,RST Control setting 0..1[0 = Command mode; 1 = Continuous mode] - 0 Rd/Wr Retain Selection of operation modeSynchro mode 70V3 MMI,RST Control setting 0..2[0 = Not in use; 1 = Asynchr. mode; 2 = Synchr.

mode]- 1 Rd/Wr Retain Selection of synchro mode

Operate time 70V4 MMI,RST Control setting 0.10...20.0 s 0,1 Rd/Wr Retain Operate time (dead time)Check time 70V5 MMI,RST Control setting 0.05...300.0 s 0,05 Rd/Wr Retain Check time in command mode operationClose pulse 70V6 MMI,RST Control setting 0.2...20.0 s 0,2 Rd/Wr Retain Closing signal length (command mode only)Oper.time of CB 70V7 MMI,RST Control setting 0.00...0.25 s 0,05 Rd/Wr Retain Operate time of circuit breaker

Page 76 of 158

Page 77: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Basic angle 70V8 MMI,RST Control setting -90...90 ° 0 Rd/Wr Retain Basic angle settingGroup selection 70V9 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 70V10 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupReset registers 70V11 RST Control setting 0..1[0 = 0; 1= Reset] - 0 Write Volatile Resetting of latched trip signal and registersVoltage combine 70V12 MMI,RST Control setting 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Enabling of voltage combiningEvent mask 1 70V101 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E7)Event mask 2 70V103 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E7)Event mask 3 70V105 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E7)Event mask 4 70V107 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E7)U1 70I1 MMI,RST Input data 0.00...1.30 x Un 0 Read Volatile Measurement value U1U2 70I2 MMI,RST Input data 0.00...1.30 x Un 0 Read Volatile Measurement value U2dU 70I3 MMI,RST Input data -1.30...1.30 x Un 0 Read Volatile Measurement delta value (U1-U2)f1 70I4 MMI,RST Input data 45.00...65.00 Hz 0 Read Volatile Measurement value f1f2 70I5 MMI,RST Input data 45.00...65.00 Hz 0 Read Volatile Measurement value f2df 70I6 MMI,RST Input data -20.00...20.00 Hz 0 Read Volatile Measurement delta value (f1-f2)phi1 70I7 MMI,RST Input data -180...180 ° 0 Read Volatile Measurement value phi1phi2 70I8 MMI,RST Input data -180...180 ° 0 Read Volatile Measurement value phi2dphi 70I9 MMI,RST Input data -180...180 ° 0 Read Volatile Measurement delta value (phi1-phi2)Input Command 70I10 MMI,RST Input data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of Command singnalInput BLOCK 70I11 MMI,RST Input data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of BLOCK singnalInput GROUP 70I12 MMI,RST Input data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of GROUP singnalInput RESET 70I13 MMI,RST Input data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of RESET singnalSC_DUE 70O1 MMI,RST Output data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of SC_DUE signalSC_OK 70O2 MMI,RST Output data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of SC_OK signalALARM_NC 70O3 MMI,RST Output data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of ALARM_NS signalALARM_CO 70O4 MMI,RST Output data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of ALARM_CO signalDate 70V201 MMI,RST Recorded data1 YYYY-MM-DD - 0 Read Retain Registration DateTime 70V202 MMI,RST Recorded data1 hh:mm:ss.000 - 0 Read Retain Registration TimeU1 70V203 MMI,RST Recorded data1 0.00...1.30 x Un 0 Read Retain Voltage 1 valueU2 70V204 MMI,RST Recorded data1 0.00...1.30 x Un 0 Read Retain Voltage 2 valuedU 70V205 MMI,RST Recorded data1 -1.30...1.30 x Un 0 Read Retain Voltage differencef1 70V206 MMI,RST Recorded data1 45.00... 65.00 Hz 0 Read Retain Frequency f1f2 70V207 MMI,RST Recorded data1 45.00... 65.00 Hz 0 Read Retain Frequency f2df 70V208 MMI,RST Recorded data1 -20.00... 20.00 Hz 0 Read Retain Frequency differencephi1 70V209 MMI,RST Recorded data1 -180 ... 180 ° 0 Read Retain Phase 1phi2 70V210 MMI,RST Recorded data1 -180 ... 180 ° 0 Read Retain Phase 2dphase 70V211 MMI,RST Recorded data1 -180 ...180 ° 0 Read Retain Phase differenceActive group 70V212 MMI,RST Recorded data1 0..1[0 = Setting group 1; 1 = Setting group 2] - 0 Read Retain Active setting groupDate 70V301 MMI,RST Recorded data2 YYYY-MM-DD - 0 Read Retain Registration DateTime 70V302 MMI,RST Recorded data2 hh:mm:ss.000 - 0 Read Retain Registration TimeU1 70V303 MMI,RST Recorded data2 0.00...1.30 x Un 0 Read Retain Voltage 1 valueU2 70V304 MMI,RST Recorded data2 0.00...1.30 x Un 0 Read Retain Voltage 2 valuedU 70V305 MMI,RST Recorded data2 -1.30...1.30 x Un 0 Read Retain Voltage differencef1 70V306 MMI,RST Recorded data2 45.00... 65.00 Hz 0 Read Retain Frequency f1f2 70V307 MMI,RST Recorded data2 45.00... 65.00 Hz 0 Read Retain Frequency f2df 70V308 MMI,RST Recorded data2 -20.00... 20.00 Hz 0 Read Retain Frequency differencephi1 70V309 MMI,RST Recorded data2 -180 ... 180 ° 0 Read Retain Phase 1phi2 70V310 MMI,RST Recorded data2 -180 ... 180 ° 0 Read Retain Phase 2dphase 70V311 MMI,RST Recorded data2 -180 ...180 ° 0 Read Retain Phase difference

Page 77 of 158

Page 78: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Active group 70V312 MMI,RST Recorded data2 0..1[0 = Setting group 1; 1 = Setting group 2] - 0 Read Retain Active setting groupDate 70V401 MMI,RST Recorded data3 YYYY-MM-DD - 0 Read Retain Registration DateTime 70V402 MMI,RST Recorded data3 hh:mm:ss.000 - 0 Read Retain Registration TimeU1 70V403 MMI,RST Recorded data3 0.00...1.30 x Un 0 Read Retain Voltage 1 valueU2 70V404 MMI,RST Recorded data3 0.00...1.30 x Un 0 Read Retain Voltage 2 valuedU 70V405 MMI,RST Recorded data3 -1.30...1.30 x Un 0 Read Retain Voltage differencef1 70V406 MMI,RST Recorded data3 45.00... 65.00 Hz 0 Read Retain Frequency f1f2 70V407 MMI,RST Recorded data3 45.00... 65.00 Hz 0 Read Retain Frequency f2df 70V408 MMI,RST Recorded data3 -20.00... 20.00 Hz 0 Read Retain Frequency differencephi1 70V409 MMI,RST Recorded data3 -180 ... 180 ° 0 Read Retain Phase 1phi2 70V410 MMI,RST Recorded data3 -180 ... 180 ° 0 Read Retain Phase 2dphase 70V411 MMI,RST Recorded data3 -180 ...180 ° 0 Read Retain Phase differenceActive group 70V412 MMI,RST Recorded data3 0..1[0 = Setting group 1; 1 = Setting group 2] - 0 Read Retain Active setting group

100071 / Rev G SCVCSt2Umax 71S1 MMI,RST Actual Setting 0.50...1.00 x Un 1 Read Volatile Upper threshold voltageUmin 71S2 MMI,RST Actual Setting 0.10...0.80 x Un 0,1 Read Volatile Lower threshold voltagedU 71S3 MMI,RST Actual Setting 0.02...0.60 x Un 0,02 Read Volatile Voltage differencedphase 71S4 MMI,RST Actual Setting 5...90 ° 5 Read Volatile Phase angle differencedf 71S5 MMI,RST Actual Setting 0.02...5.00 Hz 0,02 Read Volatile Frequency differenseUmax 71S41 MMI,RST Setting group1 0.50...1.00 x Un 1 Rd/Wr Retain Upper threshold voltageUmin 71S42 MMI,RST Setting group1 0.10...0.80 x Un 0,1 Rd/Wr Retain Lower threshold voltagedU 71S43 MMI,RST Setting group1 0.02...0.60 x Un 0,02 Rd/Wr Retain Voltage differencedphase 71S44 MMI,RST Setting group1 5...90 ° 5 Rd/Wr Retain Phase angle differencedf 71S45 MMI,RST Setting group1 0.02...5.00 Hz 0,02 Rd/Wr Retain Frequency differenseUmax 71S71 MMI,RST Setting group2 0.50...1.00 x Un 1 Rd/Wr Retain Upper threshold voltageUmin 71S72 MMI,RST Setting group2 0.10...0.80 x Un 0,1 Rd/Wr Retain Lower threshold voltagedU 71S73 MMI,RST Setting group2 0.02...0.60 x Un 0,02 Rd/Wr Retain Voltage differencedphase 71S74 MMI,RST Setting group2 5...90 ° 5 Rd/Wr Retain Phase angle differencedf 71S75 MMI,RST Setting group2 0.02...5.00 Hz 0,02 Rd/Wr Retain Frequency differenseEnergizing mode 71V1 MMI,RST Control setting 0..4[0 = Not in use; 1 = U1->U2, U2->U1; 2 = U1->U2; 3

= U2->U1; 4 = U1>U2,U2>U1,0>0]- 1 Rd/Wr Retain Selection of energizing mode

Operation mode 71V2 MMI,RST Control setting 0..1[0 = Command mode; 1 = Continuous mode] - 0 Rd/Wr Retain Selection of operation modeSynchro mode 71V3 MMI,RST Control setting 0..2[0 = Not in use; 1 = Asynchr. mode; 2 = Synchr.

mode]- 1 Rd/Wr Retain Selection of synchro mode

Operate time 71V4 MMI,RST Control setting 0.10...20.0 s 0,1 Rd/Wr Retain Operate time (dead time)Check time 71V5 MMI,RST Control setting 0.05...300.0 s 0,05 Rd/Wr Retain Check time in command mode operationClose pulse 71V6 MMI,RST Control setting 0.2...20.0 s 0,2 Rd/Wr Retain Closing signal length (command mode only)Oper.time of CB 71V7 MMI,RST Control setting 0.00...0.25 s 0,05 Rd/Wr Retain Operate time of circuit breakerBasic angle 71V8 MMI,RST Control setting -90...90 ° 0 Rd/Wr Retain Basic angle settingGroup selection 71V9 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 71V10 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupReset registers 71V11 RST Control setting 0..1[0 = 0; 1= Reset] - 0 Write Volatile Resetting of latched trip signal and registersVoltage combine 71V12 MMI,RST Control setting 0..1[0 = Disabled; 1 = Enabled] - 0 Rd/Wr Retain Enabling of voltage combiningEvent mask 1 71V101 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E7)Event mask 2 71V103 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E7)Event mask 3 71V105 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E7)Event mask 4 71V107 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E7)U1 71I1 MMI,RST Input data 0.00...1.30 x Un 0 Read Volatile Measurement value U1U2 71I2 MMI,RST Input data 0.00...1.30 x Un 0 Read Volatile Measurement value U2

Page 78 of 158

Page 79: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

dU 71I3 MMI,RST Input data -1.30...1.30 x Un 0 Read Volatile Measurement delta value (U1-U2)f1 71I4 MMI,RST Input data 45.00...65.00 Hz 0 Read Volatile Measurement value f1f2 71I5 MMI,RST Input data 45.00...65.00 Hz 0 Read Volatile Measurement value f2df 71I6 MMI,RST Input data -20.00...20.00 Hz 0 Read Volatile Measurement delta value (f1-f2)phi1 71I7 MMI,RST Input data -180...180 ° 0 Read Volatile Measurement value phi1phi2 71I8 MMI,RST Input data -180...180 ° 0 Read Volatile Measurement value phi2dphi 71I9 MMI,RST Input data -180...180 ° 0 Read Volatile Measurement delta value (phi1-phi2)Input Command 71I10 MMI,RST Input data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of Command singnalInput BLOCK 71I11 MMI,RST Input data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of BLOCK singnalInput GROUP 71I12 MMI,RST Input data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of GROUP singnalInput RESET 71I13 MMI,RST Input data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of RESET singnalSC_DUE 71O1 MMI,RST Output data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of SC_DUE signalSC_OK 71O2 MMI,RST Output data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of SC_OK signalALARM_NC 71O3 MMI,RST Output data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of ALARM_NS signalALARM_CO 71O4 MMI,RST Output data 0..1[0 = Not Active; 1= Active] - 0 Read Volatile Status of ALARM_CO signalDate 71V201 MMI,RST Recorded data1 YYYY-MM-DD - 0 Read Retain Registration DateTime 71V202 MMI,RST Recorded data1 hh:mm:ss.000 - 0 Read Retain Registration TimeU1 71V203 MMI,RST Recorded data1 0.00...1.30 x Un 0 Read Retain Voltage 1 valueU2 71V204 MMI,RST Recorded data1 0.00...1.30 x Un 0 Read Retain Voltage 2 valuedU 71V205 MMI,RST Recorded data1 -1.30...1.30 x Un 0 Read Retain Voltage differencef1 71V206 MMI,RST Recorded data1 45.00... 65.00 Hz 0 Read Retain Frequency f1f2 71V207 MMI,RST Recorded data1 45.00... 65.00 Hz 0 Read Retain Frequency f2df 71V208 MMI,RST Recorded data1 -20.00... 20.00 Hz 0 Read Retain Frequency differencephi1 71V209 MMI,RST Recorded data1 -180 ... 180 ° 0 Read Retain Phase 1phi2 71V210 MMI,RST Recorded data1 -180 ... 180 ° 0 Read Retain Phase 2dphase 71V211 MMI,RST Recorded data1 -180 ...180 ° 0 Read Retain Phase differenceActive group 71V212 MMI,RST Recorded data1 0..1[0 = Setting group 1; 1 = Setting group 2] - 0 Read Retain Active setting groupDate 71V301 MMI,RST Recorded data2 YYYY-MM-DD - 0 Read Retain Registration DateTime 71V302 MMI,RST Recorded data2 hh:mm:ss.000 - 0 Read Retain Registration TimeU1 71V303 MMI,RST Recorded data2 0.00...1.30 x Un 0 Read Retain Voltage 1 valueU2 71V304 MMI,RST Recorded data2 0.00...1.30 x Un 0 Read Retain Voltage 2 valuedU 71V305 MMI,RST Recorded data2 -1.30...1.30 x Un 0 Read Retain Voltage differencef1 71V306 MMI,RST Recorded data2 45.00... 65.00 Hz 0 Read Retain Frequency f1f2 71V307 MMI,RST Recorded data2 45.00... 65.00 Hz 0 Read Retain Frequency f2df 71V308 MMI,RST Recorded data2 -20.00... 20.00 Hz 0 Read Retain Frequency differencephi1 71V309 MMI,RST Recorded data2 -180 ... 180 ° 0 Read Retain Phase 1phi2 71V310 MMI,RST Recorded data2 -180 ... 180 ° 0 Read Retain Phase 2dphase 71V311 MMI,RST Recorded data2 -180 ...180 ° 0 Read Retain Phase differenceActive group 71V312 MMI,RST Recorded data2 0..1[0 = Setting group 1; 1 = Setting group 2] - 0 Read Retain Active setting groupDate 71V401 MMI,RST Recorded data3 YYYY-MM-DD - 0 Read Retain Registration DateTime 71V402 MMI,RST Recorded data3 hh:mm:ss.000 - 0 Read Retain Registration TimeU1 71V403 MMI,RST Recorded data3 0.00...1.30 x Un 0 Read Retain Voltage 1 valueU2 71V404 MMI,RST Recorded data3 0.00...1.30 x Un 0 Read Retain Voltage 2 valuedU 71V405 MMI,RST Recorded data3 -1.30...1.30 x Un 0 Read Retain Voltage differencef1 71V406 MMI,RST Recorded data3 45.00... 65.00 Hz 0 Read Retain Frequency f1f2 71V407 MMI,RST Recorded data3 45.00... 65.00 Hz 0 Read Retain Frequency f2df 71V408 MMI,RST Recorded data3 -20.00... 20.00 Hz 0 Read Retain Frequency differencephi1 71V409 MMI,RST Recorded data3 -180 ... 180 ° 0 Read Retain Phase 1phi2 71V410 MMI,RST Recorded data3 -180 ... 180 ° 0 Read Retain Phase 2

Page 79 of 158

Page 80: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

dphase 71V411 MMI,RST Recorded data3 -180 ...180 ° 0 Read Retain Phase differenceActive group 71V412 MMI,RST Recorded data3 0..1[0 = Setting group 1; 1 = Setting group 2] - 0 Read Retain Active setting group

100072 / Rev F Freq1St1Operation mode 72S1 MMI,RST Actual setting 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers;

3 = f</f> OR df/dt>; 4 = f</f>AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f>AND df/dt<]

- 1 Read Volatile Operation mode for frequency protection

Voltage limit 72S2 MMI,RST Actual setting 0.30...0.90 x Un 0,3 Read Volatile Undervoltage limit for blockingStart frequency 72S3 MMI,RST Actual setting 25.00...75.00 Hz 48,7 Read Volatile Start value for U/O frequency protectionOperate time 1 72S4 MMI,RST Actual setting 0.10...120.00 s 20 Read Volatile Operate time for U/O frequency protectionStart df/dt 72S5 MMI,RST Actual setting 0.2...10.0 Hz/s 10 Read Volatile Start value for frequency rate of change prot.Operate time 2 72S6 MMI,RST Actual setting 0.12...120.00 s 20 Read Volatile Timer for df/dt prot. or U/O frequency prot.Operation mode 72S41 MMI,RST Setting group1 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers;

3 = f</f> OR df/dt>; 4 = f</f>AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f>AND df/dt<]

- 1 Rd/Wr Retain Operation mode for frequency protection

Voltage limit 72S42 MMI,RST Setting group1 0.30...0.90 x Un 0,3 Rd/Wr Retain Undervoltage limit for blockingStart frequency 72S43 MMI,RST Setting group1 25.00...75.00 Hz 48,7 Rd/Wr Retain Start value for U/O frequency protectionOperate time 1 72S44 MMI,RST Setting group1 0.10...120.00 s 20 Rd/Wr Retain Operate time for U/O frequency protectionStart df/dt 72S45 MMI,RST Setting group1 0.2...10.0 Hz/s 10 Rd/Wr Retain Start value for frequency rate of change prot.Operate time 2 72S46 MMI,RST Setting group1 0.12...120.00 s 20 Rd/Wr Retain Timer for df/dt prot. or U/O frequency prot.Operation mode 72S71 MMI,RST Setting group2 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers;

3 = f</f> OR df/dt>; 4 = f</f>AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f>AND df/dt<]

- 1 Rd/Wr Retain Operation mode for frequency protection

Voltage limit 72S72 MMI,RST Setting group2 0.30...0.90 x Un 0,3 Rd/Wr Retain Undervoltage limit for blockingStart frequency 72S73 MMI,RST Setting group2 25.00...75.00 Hz 48,7 Rd/Wr Retain Start value for U/O frequency protectionOperate time 1 72S74 MMI,RST Setting group2 0.10...120.00 s 20 Rd/Wr Retain Operate time for U/O frequency protectionStart df/dt 72S75 MMI,RST Setting group2 0.2...10.0 Hz/s 10 Rd/Wr Retain Start value for frequency rate of change prot.Operate time 2 72S76 MMI,RST Setting group2 0.12...120.00 s 20 Rd/Wr Retain Timer for df/dt prot. or U/O frequency prot.Group selection 72V1 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 72V2 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 72V3 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalsTrip signal 72V4 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputsTrip pulse 72V5 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPReset registers 72V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START1 72V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of START1Test TRIP1 72V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIP1Test START2 72V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of START2Test TRIP2 72V34 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIP2Event mask 1 72V101 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E13)Event mask 2 72V103 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E13)Event mask 3 72V105 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E13)Event mask 4 72V107 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E13)Frequency 72I1 MMI,RST Input data 20.00...80.00 Hz 0 Read Volatile System frequencyRate of change 72I2 MMI,RST Input data -15.0...+15.0 Hz/s 0 Read Volatile Freq. rate of changeVoltage U 72I3 MMI,RST Input data 0.0...2.0 x Un 0 Read Volatile Voltage UInput BS1 72I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 72I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 72I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 72I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 72I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

Page 80 of 158

Page 81: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Output START1 72O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal 1Output TRIP1 72O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signal 1Output START2 72O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal 2Output TRIP2 72O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signal 2Date 72V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 72V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeStart1 72V203 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 72V204 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 72V205 MMI,RST Recorded data1 0...100 % 0 Read Retain Duration of start situationDuration2 72V206 MMI,RST Recorded data1 0...100 % 0 Read Retain Duration of start situationTrip1 72V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 72V208 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 72V209 MMI,RST Recorded data1 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 72V210 MMI,RST Recorded data1 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 72V211 MMI,RST Recorded data1 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 72V212 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 72V213 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 72V214 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 72V215 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 72V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 72V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeStart1 72V303 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 72V304 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 72V305 MMI,RST Recorded data2 0...100 % 0 Read Retain Duration of start situationDuration2 72V306 MMI,RST Recorded data2 0...100 % 0 Read Retain Duration of start situationTrip1 72V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 72V308 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 72V309 MMI,RST Recorded data2 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 72V310 MMI,RST Recorded data2 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 72V311 MMI,RST Recorded data2 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 72V312 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 72V313 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 72V314 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 72V315 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 72V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 72V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeStart1 72V403 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 72V404 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 72V405 MMI,RST Recorded data3 0...100 % 0 Read Retain Duration of start situationDuration2 72V406 MMI,RST Recorded data3 0...100 % 0 Read Retain Duration of start situationTrip1 72V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 72V408 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 72V409 MMI,RST Recorded data3 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 72V410 MMI,RST Recorded data3 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 72V411 MMI,RST Recorded data3 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 72V412 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 72V413 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 72V414 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 72V415 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

Page 81 of 158

Page 82: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation100073 / Rev F Freq1St2

Operation mode 73S1 MMI,RST Actual setting 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers; 3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Read Volatile Operation mode for frequency protection

Voltage limit 73S2 MMI,RST Actual setting 0.30...0.90 x Un 0,3 Read Volatile Undervoltage limit for blockingStart frequency 73S3 MMI,RST Actual setting 25.00...75.00 Hz 48,7 Read Volatile Start value for U/O frequency protectionOperate time 1 73S4 MMI,RST Actual setting 0.10...120.00 s 20 Read Volatile Operate time for U/O frequency protectionStart df/dt 73S5 MMI,RST Actual setting 0.2...10.0 Hz/s 10 Read Volatile Start value for frequency rate of change prot.Operate time 2 73S6 MMI,RST Actual setting 0.12...120.00 s 20 Read Volatile Timer for df/dt prot. or U/O frequency prot.Operation mode 73S41 MMI,RST Setting group1 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers;

3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Rd/Wr Retain Operation mode for frequency protection

Voltage limit 73S42 MMI,RST Setting group1 0.30...0.90 x Un 0,3 Rd/Wr Retain Undervoltage limit for blockingStart frequency 73S43 MMI,RST Setting group1 25.00...75.00 Hz 48,7 Rd/Wr Retain Start value for U/O frequency protectionOperate time 1 73S44 MMI,RST Setting group1 0.10...120.00 s 20 Rd/Wr Retain Operate time for U/O frequency protectionStart df/dt 73S45 MMI,RST Setting group1 0.2...10.0 Hz/s 10 Rd/Wr Retain Start value for frequency rate of change prot.Operate time 2 73S46 MMI,RST Setting group1 0.12...120.00 s 20 Rd/Wr Retain Timer for df/dt prot. or U/O frequency prot.Operation mode 73S71 MMI,RST Setting group2 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers;

3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Rd/Wr Retain Operation mode for frequency protection

Voltage limit 73S72 MMI,RST Setting group2 0.30...0.90 x Un 0,3 Rd/Wr Retain Undervoltage limit for blockingStart frequency 73S73 MMI,RST Setting group2 25.00...75.00 Hz 48,7 Rd/Wr Retain Start value for U/O frequency protectionOperate time 1 73S74 MMI,RST Setting group2 0.10...120.00 s 20 Rd/Wr Retain Operate time for U/O frequency protectionStart df/dt 73S75 MMI,RST Setting group2 0.2...10.0 Hz/s 10 Rd/Wr Retain Start value for frequency rate of change prot.Operate time 2 73S76 MMI,RST Setting group2 0.12...120.00 s 20 Rd/Wr Retain Timer for df/dt prot. or U/O frequency prot.Group selection 73V1 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 73V2 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 73V3 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalsTrip signal 73V4 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputsTrip pulse 73V5 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPReset registers 73V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START1 73V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of START1Test TRIP1 73V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIP1Test START2 73V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of START2Test TRIP2 73V34 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIP2Event mask 1 73V101 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E13)Event mask 2 73V103 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E13)Event mask 3 73V105 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E13)Event mask 4 73V107 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E13)Frequency 73I1 MMI,RST Input data 20.00...80.00 Hz 0 Read Volatile System frequencyRate of change 73I2 MMI,RST Input data -15.0...+15.0 Hz/s 0 Read Volatile Freq. rate of changeVoltage U 73I3 MMI,RST Input data 0.0...2.0 x Un 0 Read Volatile Voltage UInput BS1 73I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 73I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 73I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 73I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 73I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

Freq1St12Output START1 73O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal 1

Page 82 of 158

Page 83: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Output TRIP1 73O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signal 1Output START2 73O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal 2Output TRIP2 73O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signal 2Date 73V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 73V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeStart1 73V203 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 73V204 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 73V205 MMI,RST Recorded data1 0...100 % 0 Read Retain Duration of start situationDuration2 73V206 MMI,RST Recorded data1 0...100 % 0 Read Retain Duration of start situationTrip1 73V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 73V208 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 73V209 MMI,RST Recorded data1 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 73V210 MMI,RST Recorded data1 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 73V211 MMI,RST Recorded data1 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 73V212 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 73V213 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 73V214 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 73V215 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 73V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 73V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeStart1 73V303 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 73V304 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 73V305 MMI,RST Recorded data2 0...100 % 0 Read Retain Duration of start situationDuration2 73V306 MMI,RST Recorded data2 0...100 % 0 Read Retain Duration of start situationTrip1 73V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 73V308 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 73V309 MMI,RST Recorded data2 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 73V310 MMI,RST Recorded data2 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 73V311 MMI,RST Recorded data2 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 73V312 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 73V313 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 73V314 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 73V315 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 73V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 73V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeStart1 73V403 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 73V404 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 73V405 MMI,RST Recorded data3 0...100 % 0 Read Retain Duration of start situationDuration2 73V406 MMI,RST Recorded data3 0...100 % 0 Read Retain Duration of start situationTrip1 73V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 73V408 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 73V409 MMI,RST Recorded data3 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 73V410 MMI,RST Recorded data3 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 73V411 MMI,RST Recorded data3 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 73V412 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 73V413 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 73V414 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 73V415 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100074 / Rev F Freq1St3

Page 83 of 158

Page 84: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Operation mode 74S1 MMI,RST Actual setting 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers; 3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Read Volatile Operation mode for frequency protection

Voltage limit 74S2 MMI,RST Actual setting 0.30...0.90 x Un 0,3 Read Volatile Undervoltage limit for blockingStart frequency 74S3 MMI,RST Actual setting 25.00...75.00 Hz 48,7 Read Volatile Start value for U/O frequency protectionOperate time 1 74S4 MMI,RST Actual setting 0.10...120.00 s 20 Read Volatile Operate time for U/O frequency protectionStart df/dt 74S5 MMI,RST Actual setting 0.2...10.0 Hz/s 10 Read Volatile Start value for frequency rate of change prot.Operate time 2 74S6 MMI,RST Actual setting 0.12...120.00 s 20 Read Volatile Timer for df/dt prot. or U/O frequency prot.Operation mode 74S41 MMI,RST Setting group1 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers;

3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Rd/Wr Retain Operation mode for frequency protection

Voltage limit 74S42 MMI,RST Setting group1 0.30...0.90 x Un 0,3 Rd/Wr Retain Undervoltage limit for blockingStart frequency 74S43 MMI,RST Setting group1 25.00...75.00 Hz 48,7 Rd/Wr Retain Start value for U/O frequency protectionOperate time 1 74S44 MMI,RST Setting group1 0.10...120.00 s 20 Rd/Wr Retain Operate time for U/O frequency protectionStart df/dt 74S45 MMI,RST Setting group1 0.2...10.0 Hz/s 10 Rd/Wr Retain Start value for frequency rate of change prot.Operate time 2 74S46 MMI,RST Setting group1 0.12...120.00 s 20 Rd/Wr Retain Timer for df/dt prot. or U/O frequency prot.Operation mode 74S71 MMI,RST Setting group2 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers;

3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Rd/Wr Retain Operation mode for frequency protection

Voltage limit 74S72 MMI,RST Setting group2 0.30...0.90 x Un 0,3 Rd/Wr Retain Undervoltage limit for blockingStart frequency 74S73 MMI,RST Setting group2 25.00...75.00 Hz 48,7 Rd/Wr Retain Start value for U/O frequency protectionOperate time 1 74S74 MMI,RST Setting group2 0.10...120.00 s 20 Rd/Wr Retain Operate time for U/O frequency protectionStart df/dt 74S75 MMI,RST Setting group2 0.2...10.0 Hz/s 10 Rd/Wr Retain Start value for frequency rate of change prot.Operate time 2 74S76 MMI,RST Setting group2 0.12...120.00 s 20 Rd/Wr Retain Timer for df/dt prot. or U/O frequency prot.Group selection 74V1 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 74V2 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 74V3 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalsTrip signal 74V4 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputsTrip pulse 74V5 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPReset registers 74V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START1 74V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of START1Test TRIP1 74V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIP1Test START2 74V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of START2Test TRIP2 74V34 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIP2Event mask 1 74V101 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E13)Event mask 2 74V103 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E13)Event mask 3 74V105 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E13)Event mask 4 74V107 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E13)Frequency 74I1 MMI,RST Input data 20.00...80.00 Hz 0 Read Volatile System frequencyRate of change 74I2 MMI,RST Input data -15.0...+15.0 Hz/s 0 Read Volatile Freq. rate of changeVoltage U 74I3 MMI,RST Input data 0.0...2.0 x Un 0 Read Volatile Voltage UInput BS1 74I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 74I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 74I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 74I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 74I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of Output START1 74O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal 1Output TRIP1 74O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signal 1Output START2 74O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal 2

Page 84 of 158

Page 85: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Output TRIP2 74O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signal 2Date 74V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 74V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeStart1 74V203 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 74V204 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 74V205 MMI,RST Recorded data1 0...100 % 0 Read Retain Duration of start situationDuration2 74V206 MMI,RST Recorded data1 0...100 % 0 Read Retain Duration of start situationTrip1 74V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 74V208 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 74V209 MMI,RST Recorded data1 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 74V210 MMI,RST Recorded data1 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 74V211 MMI,RST Recorded data1 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 74V212 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 74V213 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 74V214 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 74V215 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 74V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 74V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeStart1 74V303 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 74V304 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 74V305 MMI,RST Recorded data2 0...100 % 0 Read Retain Duration of start situationDuration2 74V306 MMI,RST Recorded data2 0...100 % 0 Read Retain Duration of start situationTrip1 74V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 74V308 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 74V309 MMI,RST Recorded data2 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 74V310 MMI,RST Recorded data2 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 74V311 MMI,RST Recorded data2 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 74V312 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 74V313 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 74V314 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 74V315 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 74V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 74V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeStart1 74V403 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 74V404 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 74V405 MMI,RST Recorded data3 0...100 % 0 Read Retain Duration of start situationDuration2 74V406 MMI,RST Recorded data3 0...100 % 0 Read Retain Duration of start situationTrip1 74V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 74V408 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 74V409 MMI,RST Recorded data3 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 74V410 MMI,RST Recorded data3 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 74V411 MMI,RST Recorded data3 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 74V412 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 74V413 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 74V414 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 74V415 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100075 / Rev F Freq1St4

Page 85 of 158

Page 86: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Operation mode 75S1 MMI,RST Actual setting 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers; 3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Read Volatile Operation mode for frequency protection

Voltage limit 75S2 MMI,RST Actual setting 0.30...0.90 x Un 0,3 Read Volatile Undervoltage limit for blockingStart frequency 75S3 MMI,RST Actual setting 25.00...75.00 Hz 48,7 Read Volatile Start value for U/O frequency protectionOperate time 1 75S4 MMI,RST Actual setting 0.10...120.00 s 20 Read Volatile Operate time for U/O frequency protectionStart df/dt 75S5 MMI,RST Actual setting 0.2...10.0 Hz/s 10 Read Volatile Start value for frequency rate of change prot.Operate time 2 75S6 MMI,RST Actual setting 0.12...120.00 s 20 Read Volatile Timer for df/dt prot. or U/O frequency prot.Operation mode 75S41 MMI,RST Setting group1 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers;

3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Rd/Wr Retain Operation mode for frequency protection

Voltage limit 75S42 MMI,RST Setting group1 0.30...0.90 x Un 0,3 Rd/Wr Retain Undervoltage limit for blockingStart frequency 75S43 MMI,RST Setting group1 25.00...75.00 Hz 48,7 Rd/Wr Retain Start value for U/O frequency protectionOperate time 1 75S44 MMI,RST Setting group1 0.10...120.00 s 20 Rd/Wr Retain Operate time for U/O frequency protectionStart df/dt 75S45 MMI,RST Setting group1 0.2...10.0 Hz/s 10 Rd/Wr Retain Start value for frequency rate of change prot.Operate time 2 75S46 MMI,RST Setting group1 0.12...120.00 s 20 Rd/Wr Retain Timer for df/dt prot. or U/O frequency prot.Operation mode 75S71 MMI,RST Setting group2 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers;

3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Rd/Wr Retain Operation mode for frequency protection

Voltage limit 75S72 MMI,RST Setting group2 0.30...0.90 x Un 0,3 Rd/Wr Retain Undervoltage limit for blockingStart frequency 75S73 MMI,RST Setting group2 25.00...75.00 Hz 48,7 Rd/Wr Retain Start value for U/O frequency protectionOperate time 1 75S74 MMI,RST Setting group2 0.10...120.00 s 20 Rd/Wr Retain Operate time for U/O frequency protectionStart df/dt 75S75 MMI,RST Setting group2 0.2...10.0 Hz/s 10 Rd/Wr Retain Start value for frequency rate of change prot.Operate time 2 75S76 MMI,RST Setting group2 0.12...120.00 s 20 Rd/Wr Retain Timer for df/dt prot. or U/O frequency prot.Group selection 75V1 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 75V2 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 75V3 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalsTrip signal 75V4 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputsTrip pulse 75V5 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPReset registers 75V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START1 75V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of START1Test TRIP1 75V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIP1Test START2 75V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of START2Test TRIP2 75V34 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIP2Event mask 1 75V101 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E13)Event mask 2 75V103 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E13)Event mask 3 75V105 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E13)Event mask 4 75V107 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E13)Frequency 75I1 MMI,RST Input data 20.00...80.00 Hz 0 Read Volatile System frequencyRate of change 75I2 MMI,RST Input data -15.0...+15.0 Hz/s 0 Read Volatile Freq. rate of changeVoltage U 75I3 MMI,RST Input data 0.0...2.0 x Un 0 Read Volatile Voltage UInput BS1 75I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 75I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 75I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 75I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 75I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of Output START1 75O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal 1Output TRIP1 75O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signal 1Output START2 75O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal 2

Page 86 of 158

Page 87: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Output TRIP2 75O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signal 2Date 75V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 75V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeStart1 75V203 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 75V204 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 75V205 MMI,RST Recorded data1 0...100 % 0 Read Retain Duration of start situationDuration2 75V206 MMI,RST Recorded data1 0...100 % 0 Read Retain Duration of start situationTrip1 75V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 75V208 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 75V209 MMI,RST Recorded data1 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 75V210 MMI,RST Recorded data1 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 75V211 MMI,RST Recorded data1 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 75V212 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 75V213 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 75V214 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 75V215 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 75V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 75V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeStart1 75V303 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 75V304 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 75V305 MMI,RST Recorded data2 0...100 % 0 Read Retain Duration of start situationDuration2 75V306 MMI,RST Recorded data2 0...100 % 0 Read Retain Duration of start situationTrip1 75V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 75V308 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 75V309 MMI,RST Recorded data2 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 75V310 MMI,RST Recorded data2 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 75V311 MMI,RST Recorded data2 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 75V312 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 75V313 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 75V314 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 75V315 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 75V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 75V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeStart1 75V403 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 75V404 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 75V405 MMI,RST Recorded data3 0...100 % 0 Read Retain Duration of start situationDuration2 75V406 MMI,RST Recorded data3 0...100 % 0 Read Retain Duration of start situationTrip1 75V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 75V408 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 75V409 MMI,RST Recorded data3 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 75V410 MMI,RST Recorded data3 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 75V411 MMI,RST Recorded data3 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 75V412 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 75V413 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 75V414 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 75V415 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100076 / Rev F Freq1St5

Page 87 of 158

Page 88: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Operation mode 76S1 MMI,RST Actual setting 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers; 3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Read Volatile Operation mode for frequency protection

Voltage limit 76S2 MMI,RST Actual setting 0.30...0.90 x Un 0,3 Read Volatile Undervoltage limit for blockingStart frequency 76S3 MMI,RST Actual setting 25.00...75.00 Hz 48,7 Read Volatile Start value for U/O frequency protectionOperate time 1 76S4 MMI,RST Actual setting 0.10...120.00 s 20 Read Volatile Operate time for U/O frequency protectionStart df/dt 76S5 MMI,RST Actual setting 0.2...10.0 Hz/s 10 Read Volatile Start value for frequency rate of change prot.Operate time 2 76S6 MMI,RST Actual setting 0.12...120.00 s 20 Read Volatile Timer for df/dt prot. or U/O frequency prot.Operation mode 76S41 MMI,RST Setting group1 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers;

3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Rd/Wr Retain Operation mode for frequency protection

Voltage limit 76S42 MMI,RST Setting group1 0.30...0.90 x Un 0,3 Rd/Wr Retain Undervoltage limit for blockingStart frequency 76S43 MMI,RST Setting group1 25.00...75.00 Hz 48,7 Rd/Wr Retain Start value for U/O frequency protectionOperate time 1 76S44 MMI,RST Setting group1 0.10...120.00 s 20 Rd/Wr Retain Operate time for U/O frequency protectionStart df/dt 76S45 MMI,RST Setting group1 0.2...10.0 Hz/s 10 Rd/Wr Retain Start value for frequency rate of change prot.Operate time 2 76S46 MMI,RST Setting group1 0.12...120.00 s 20 Rd/Wr Retain Timer for df/dt prot. or U/O frequency prot.Operation mode 76S71 MMI,RST Setting group2 0..6[0 = Not in use; 1 = f</f> 1 timer; 2 = f</f> 2 timers;

3 = f</f> OR df/dt>; 4 = f</f> AND df/dt>; 5 = f</f> OR df/dt<; 6 = f</f> AND df/dt<]

- 1 Rd/Wr Retain Operation mode for frequency protection

Voltage limit 76S72 MMI,RST Setting group2 0.30...0.90 x Un 0,3 Rd/Wr Retain Undervoltage limit for blockingStart frequency 76S73 MMI,RST Setting group2 25.00...75.00 Hz 48,7 Rd/Wr Retain Start value for U/O frequency protectionOperate time 1 76S74 MMI,RST Setting group2 0.10...120.00 s 20 Rd/Wr Retain Operate time for U/O frequency protectionStart df/dt 76S75 MMI,RST Setting group2 0.2...10.0 Hz/s 10 Rd/Wr Retain Start value for frequency rate of change prot.Operate time 2 76S76 MMI,RST Setting group2 0.12...120.00 s 20 Rd/Wr Retain Timer for df/dt prot. or U/O frequency prot.Group selection 76V1 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 76V2 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 76V3 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalsTrip signal 76V4 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputsTrip pulse 76V5 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPReset registers 76V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START1 76V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of START1Test TRIP1 76V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIP1Test START2 76V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of START2Test TRIP2 76V34 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIP2Event mask 1 76V101 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E13)Event mask 2 76V103 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E13)Event mask 3 76V105 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E13)Event mask 4 76V107 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E13)Frequency 76I1 MMI,RST Input data 20.00...80.00 Hz 0 Read Volatile System frequencyRate of change 76I2 MMI,RST Input data -15.0...+15.0 Hz/s 0 Read Volatile Freq. rate of changeVoltage U 76I3 MMI,RST Input data 0.0...2.0 x Un 0 Read Volatile Voltage UInput BS1 76I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 76I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 76I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 76I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 76I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of Output START1 76O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal 1Output TRIP1 76O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signal 1Output START2 76O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal 2

Page 88 of 158

Page 89: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Output TRIP2 76O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signal 2Date 76V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 76V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeStart1 76V203 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 76V204 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 76V205 MMI,RST Recorded data1 0...100 % 0 Read Retain Duration of start situationDuration2 76V206 MMI,RST Recorded data1 0...100 % 0 Read Retain Duration of start situationTrip1 76V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 76V208 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 76V209 MMI,RST Recorded data1 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 76V210 MMI,RST Recorded data1 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 76V211 MMI,RST Recorded data1 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 76V212 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 76V213 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 76V214 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 76V215 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 76V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 76V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeStart1 76V303 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 76V304 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 76V305 MMI,RST Recorded data2 0...100 % 0 Read Retain Duration of start situationDuration2 76V306 MMI,RST Recorded data2 0...100 % 0 Read Retain Duration of start situationTrip1 76V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 76V308 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 76V309 MMI,RST Recorded data2 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 76V310 MMI,RST Recorded data2 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 76V311 MMI,RST Recorded data2 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 76V312 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 76V313 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 76V314 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 76V315 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 76V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 76V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeStart1 76V403 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START1Start2 76V404 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of START2Duration1 76V405 MMI,RST Recorded data3 0...100 % 0 Read Retain Duration of start situationDuration2 76V406 MMI,RST Recorded data3 0...100 % 0 Read Retain Duration of start situationTrip1 76V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP1Trip2 76V408 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIP2Frequency 76V409 MMI,RST Recorded data3 20.00...80.00 Hz 0 Read Retain Meas. system frequencyRate of change 76V410 MMI,RST Recorded data3 -15.0...+15.0 Hz/s 0 Read Retain Freq. rate of changeVoltage U 76V411 MMI,RST Recorded data3 0.0...2.0 x Un 0 Read Retain Meas. voltageBS1 76V412 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1BS2 76V413 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2TRIGG 76V414 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of TRIGGActive group 76V415 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100077 / Rev F NPS3LowOperation mode 77S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Definite time; 2 = Inverse time] - 1 Read Volatile Selection of operation mode (definite or inverse time

mode)

Page 89 of 158

Page 90: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Start value 77S2 MMI,RST Actual setting 0.01...0.50 x In 0,2 Read Volatile Start value of negative sequence current I2Operate time 77S3 MMI,RST Actual setting 0.1...120.0 s 1 Read Volatile Operate time in definite time modeK 77S4 MMI,RST Actual setting 5.0...100.0 - 5 Read Volatile Operating characteristic constantStart delay 77S5 MMI,RST Actual setting 0.1...60.0 s 1 Read Volatile Definite start time in inverse time modeMinimum time 77S6 MMI,RST Actual setting 0.1...120.0 s 0,1 Read Volatile Definite minimum operating timeMaximum time 77S7 MMI,RST Actual setting 500...10000 s 1000 Read Volatile Maximum operating time regardless of inverse

characteristicCooling time 77S8 MMI,RST Actual setting 5...10000 s 50 Read Volatile Time taken to cool the machineOperation mode 77S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Definite time; 2 = Inverse time] - 1 Rd/Wr Retain Selection of operation mode (definite or inverse time

mode)Start value 77S42 MMI,RST Setting group1 0.01...0.50 x In 0,2 Rd/Wr Retain Start value of negative sequence current I2Operate time 77S43 MMI,RST Setting group1 0.1...120.0 s 1 Rd/Wr Retain Operate time in definite time modeK 77S44 MMI,RST Setting group1 5.0...100.0 - 5 Rd/Wr Retain Operating characteristic constantStart delay 77S45 MMI,RST Setting group1 0.1...60.0 s 1 Rd/Wr Retain Definite start time in inverse time modeMinimum time 77S46 MMI,RST Setting group1 0.1...120.0 s 0,1 Rd/Wr Retain Definite minimum operating timeMaximum time 77S47 MMI,RST Setting group1 500...10000 s 1000 Rd/Wr Retain Maximum operating time regardless of inverse

characteristicCooling time 77S48 MMI,RST Setting group1 5...10000 s 50 Rd/Wr Retain Time taken to cool the machineOperation mode 77S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Definite time; 2 = Inverse time] - 1 Rd/Wr Retain Selection of operation mode (definite or inverse time

mode)Start value 77S72 MMI,RST Setting group2 0.01...0.50 x In 0,2 Rd/Wr Retain Start value of negative sequence current I2Operate time 77S73 MMI,RST Setting group2 0.1...120.0 s 1 Rd/Wr Retain Operate time in definite time modeK 77S74 MMI,RST Setting group2 5.0...100.0 - 5 Rd/Wr Retain Operating characteristic constantStart delay 77S75 MMI,RST Setting group2 0.1...60.0 s 1 Rd/Wr Retain Definite start time in inverse time modeMinimum time 77S76 MMI,RST Setting group2 0.1...120.0 s 0,1 Rd/Wr Retain Definite minimum operating timeMaximum time 77S77 MMI,RST Setting group2 500...10000 s 1000 Rd/Wr Retain Maximum operating time regardless of inverse

characteristicCooling time 77S78 MMI,RST Setting group2 5...10000 s 50 Rd/Wr Retain Time taken to cool the machineNum. of phases 77V1 MMI,RST Control setting 2...3 - 3 Rd/Wr Retain Selection of two phase or three phase measurementGroup selection 77V2 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 77V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupDir. selection 77V4 MMI,RST Control setting 0..2[0 = Forward; 1 = Reverse; 2 = Input rot. dir.] - 0 Rd/Wr Retain Selection of rotation directionRotation dir. 77V5 MMI,RST Control setting 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Rotation directionDrop-off time 77V6 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of the operate time counter at DT modeStart pulse 77V7 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 77V8 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 77V9 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 77V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 77V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 77V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 77V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 77V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 77V101 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11, E13)Event mask 2 77V103 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11, E13)Event mask 3 77V105 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11, E13)Event mask 4 77V107 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11, E13)Neg. seq. cur. 77I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Negative sequence current I2Current IL1 77I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 77I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2

Page 90 of 158

Page 91: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Current IL3 77I4 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Input Rot. dir. 77I5 MMI,RST Input data 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Input signal for selecting rotation direction of generatorInput BLOCK 77I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input signal for blocking FBInput GROUP 77I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 77I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

NPS3LowOutput START 77O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 77O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput BLOCK 77O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of BLOCK signal (signal for separating machine

from the power system)Output ERR 77O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of error signalDate 77V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 77V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 77V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationNeg. seq. cur. 77V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Negative sequence currentCurrent IL1 77V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1Current IL2 77V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2Current IL3 77V207 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3Rotation dir. 77V208 MMI,RST Recorded data1 0..1[0 = Forward; 1 = Reverse] - 0 Read Retain Status of rotation directionBLOCK 77V209 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 77V210 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 77V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 77V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 77V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationNeg. seq. cur. 77V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Negative sequence currentCurrent IL1 77V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL1Current IL2 77V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL2Current IL3 77V307 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL3Rotation dir. 77V308 MMI,RST Recorded data2 0..1[0 = Forward; 1 = Reverse] - 0 Read Retain Status of rotation directionBLOCK 77V309 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 77V310 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 77V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 77V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 77V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationNeg. seq. cur. 77V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Negative sequence currentCurrent IL1 77V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1Current IL2 77V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2Current IL3 77V407 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3Rotation dir. 77V408 MMI,RST Recorded data3 0..1[0 = Forward; 1 = Reverse] - 0 Read Retain Status of rotation directionBLOCK 77V409 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 77V410 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100078 / Rev F NPS3HighOperation mode 78S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Definite time; 2 = Inverse time] - 1 Read Volatile Selection of operation mode (definite or inverse time

mode)Start value 78S2 MMI,RST Actual setting 0.01...0.50 x In 0,2 Read Volatile Start value of negative sequence current I2Operate time 78S3 MMI,RST Actual setting 0.1...120.0 s 1 Read Volatile Operate time in definite time modeK 78S4 MMI,RST Actual setting 5.0...100.0 - 5 Read Volatile Operating characteristic constantStart delay 78S5 MMI,RST Actual setting 0.1...60.0 s 1 Read Volatile Definite start time in inverse time modeMinimum time 78S6 MMI,RST Actual setting 0.1...120.0 s 0,1 Read Volatile Definite minimum operating time

Page 91 of 158

Page 92: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Maximum time 78S7 MMI,RST Actual setting 500...10000 s 1000 Read Volatile Maximum operating time regardless of inverse characteristic

Cooling time 78S8 MMI,RST Actual setting 5...10000 s 50 Read Volatile Time taken to cool the machineOperation mode 78S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Definite time; 2 = Inverse time] - 1 Rd/Wr Retain Selection of operation mode (definite or inverse time

mode)Start value 78S42 MMI,RST Setting group1 0.01...0.50 x In 0,2 Rd/Wr Retain Start value of negative sequence current I2Operate time 78S43 MMI,RST Setting group1 0.1...120.0 s 1 Rd/Wr Retain Operate time in definite time modeK 78S44 MMI,RST Setting group1 5.0...100.0 - 5 Rd/Wr Retain Operating characteristic constantStart delay 78S45 MMI,RST Setting group1 0.1...60.0 s 1 Rd/Wr Retain Definite start time in inverse time modeMinimum time 78S46 MMI,RST Setting group1 0.1...120.0 s 0,1 Rd/Wr Retain Definite minimum operating timeMaximum time 78S47 MMI,RST Setting group1 500...10000 s 1000 Rd/Wr Retain Maximum operating time regardless of inverse

characteristicCooling time 78S48 MMI,RST Setting group1 5...10000 s 50 Rd/Wr Retain Time taken to cool the machineOperation mode 78S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Definite time; 2 = Inverse time] - 1 Rd/Wr Retain Selection of operation mode (definite or inverse time

mode)Start value 78S72 MMI,RST Setting group2 0.01...0.50 x In 0,2 Rd/Wr Retain Start value of negative sequence current I2Operate time 78S73 MMI,RST Setting group2 0.1...120.0 s 1 Rd/Wr Retain Operate time in definite time modeK 78S74 MMI,RST Setting group2 5.0...100.0 - 5 Rd/Wr Retain Operating characteristic constantStart delay 78S75 MMI,RST Setting group2 0.1...60.0 s 1 Rd/Wr Retain Definite start time in inverse time modeMinimum time 78S76 MMI,RST Setting group2 0.1...120.0 s 0,1 Rd/Wr Retain Definite minimum operating timeMaximum time 78S77 MMI,RST Setting group2 500...10000 s 1000 Rd/Wr Retain Maximum operating time regardless of inverse

characteristicCooling time 78S78 MMI,RST Setting group2 5...10000 s 50 Rd/Wr Retain Time taken to cool the machineNum. of phases 78V1 MMI,RST Control setting 2...3 - 3 Rd/Wr Retain Selection of two phase or three phase measurementGroup selection 78V2 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 78V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupDir. selection 78V4 MMI,RST Control setting 0..2[0 = Forward; 1 = Reverse; 2 = Input rot. dir.] - 0 Rd/Wr Retain Selection of rotation directionRotation dir. 78V5 MMI,RST Control setting 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Rotation directionDrop-off time 78V6 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of the operate time counter at DT modeStart pulse 78V7 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 78V8 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 78V9 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 78V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 78V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 78V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 78V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 78V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 78V101 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11, E13)Event mask 2 78V103 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11, E13)Event mask 3 78V105 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11, E13)Event mask 4 78V107 MMI,RST Control setting 0...12287 - 8255 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11, E13)Neg. seq. cur. 78I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Negative sequence current I2Current IL1 78I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 78I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 78I4 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Input Rot. dir. 78I5 MMI,RST Input data 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Input signal for selecting rotation direction of generatorInput BLOCK 78I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input signal for blocking FBInput GROUP 78I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2

Page 92 of 158

Page 93: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Input RESET 78I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of NPS3High

Output START 78O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 78O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput BLOCK 78O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of BLOCK signal (signal for separating machine

from the power system)Output ERR 78O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of error signalDate 78V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 78V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 78V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationNeg. seq. cur. 78V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Negative sequence currentCurrent IL1 78V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1Current IL2 78V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2Current IL3 78V207 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3Rotation dir. 78V208 MMI,RST Recorded data1 0..1[0 = Forward; 1 = Reverse] - 0 Read Retain Status of rotation directionBLOCK 78V209 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 78V210 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 78V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 78V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 78V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationNeg. seq. cur. 78V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Negative sequence currentCurrent IL1 78V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL1Current IL2 78V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL2Current IL3 78V307 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL3Rotation dir. 78V308 MMI,RST Recorded data2 0..1[0 = Forward; 1 = Reverse] - 0 Read Retain Status of rotation directionBLOCK 78V309 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 78V310 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 78V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 78V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 78V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationNeg. seq. cur. 78V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Negative sequence currentCurrent IL1 78V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1Current IL2 78V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2Current IL3 78V407 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3Rotation dir. 78V408 MMI,RST Recorded data3 0..1[0 = Forward; 1 = Reverse] - 0 Read Retain Status of rotation directionBLOCK 78V409 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 78V410 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100088 / Rev E NUC3St1Operation mode 88S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Alarm; 2 = Trip] - 2 Read Volatile Selection of operation modeOper. criteria 88S2 MMI,RST Actual setting 0..1[0 = 1,2,3-phase; 1 = 3-phase] - 0 Read Volatile Selection of operation criteriaStart current 88S3 MMI,RST Actual setting 0.10...0.99 x ln 0,5 Read Volatile Start currentOperate time 88S4 MMI,RST Actual setting 0.1...600.0 s 2 Read Volatile Operate time at ALARM and TRIP modesIntern. blocking 88S5 MMI,RST Actual setting 0..1[0 = Disable; 1 = Enable] - 1 Read Volatile Enabling of internal undercurrent blockingBlocking time 88S6 MMI,RST Actual setting 0...7200 s 0 Read Volatile Blocking time from motor start-upOperation mode 88S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Alarm; 2 = Trip] - 2 Rd/Wr Retain Selection of operation modeOper. criteria 88S42 MMI,RST Setting group1 0..1[0 = 1,2,3-phase; 1 = 3-phase] - 0 Rd/Wr Retain Selection of operation criteriaStart current 88S43 MMI,RST Setting group1 0.10...0.99 x In 0,5 Rd/Wr Retain Start currentOperate time 88S44 MMI,RST Setting group1 0.1...600.0 s 2 Rd/Wr Retain Operate time at ALARM and TRIP modesIntern. blocking 88S45 MMI,RST Setting group1 0..1[0 = Disable; 1 = Enable] - 1 Rd/Wr Retain Enabling of internal undercurrent blocking

Page 93 of 158

Page 94: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Blocking time 88S46 MMI,RST Setting group1 0...7200 s 0 Rd/Wr Retain Blocking time from motor start-upOperation mode 88S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Alarm; 2 = Trip] - 2 Rd/Wr Retain Selection of operation modeOper. criteria 88S72 MMI,RST Setting group2 0..1[0 = 1,2,3-phase; 1 = 3-phase] - 0 Rd/Wr Retain Selection of operation criteriaStart current 88S73 MMI,RST Setting group2 0.10...0.99 x In 0,5 Rd/Wr Retain Start currentOperate time 88S74 MMI,RST Setting group2 0.1...600.0 s 2 Rd/Wr Retain Operate time at ALARM and TRIP modesIntern. blocking 88S75 MMI,RST Setting group2 0..1[0 = Disable; 1 = Enable] - 1 Rd/Wr Retain Enabling of internal overcurrentBlocking time 88S76 MMI,RST Setting group2 0...7200 s 0 Rd/Wr Retain Blocking time from motor start-upMeasuring mode 88V1 MMI,RST Control setting 0..1[0 = Peak to peak; 1 = Fundam. freq.] - 0 Rd/Wr Retain Selection of measuring modeDrop-off time 88V2 MMI,RST Control setting 0.00...60.00 - 0 Rd/Wr Retain Resetting time of the operate time counterGroup selection 88V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the actiive setting groupActive group 88V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 88V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 88V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 88V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 88V8 MMI,RST Control setting 100...1000 ms 500 Rd/Wr Retain Operate time of delayed trip CBFPAlarm signal 88V9 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for ALARM outputReset registers 88V13 RST Control setting 1=Reset - 0 Write Volatile Resetting of latched alarm or trip signal and registersTest START 88V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - - Rd/Wr Volatile Testing of STARTTest TRIP 88V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - - Rd/Wr Volatile Testing of TRIPTest CBFP 88V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - - Rd/Wr Volatile Testing of CBFPTest ALARM 88V34 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - - Rd/Wr Volatile Testing of ALARMEvent mask 1 88V101 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 1 for event transmission (E0...E13)Event mask 2 88V103 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 2 for event transmission (E0...E13)Event mask 3 88V105 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 3 for event transmission (E0...E13)Event mask 4 88V107 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 4 for event tarnsmission (E0...E13)Current IL1 88I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 88I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 88I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Extern. BLOCK 88I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile External BLOCK signalIntern. BLOCK 88I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Internal BLOCK signalInput TRIGG 88I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 88I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input BSREG 88I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 88I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

NUC3St1Output START 88O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of START signalOutput TRIP 88O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of TRIP signalOutput CBFP 88O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalOutput ALARM 88O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of ALARM signalDate 88V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 88V202 MMI,RST Recorded data1 hh:mm:ss.mss - - Read Retain Recording timeDuration 88V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 88V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 88V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 88V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3Extern. BLOCK 88V207 MMI,RST Recorded data1 0=Not active, 1=Active - 0 Read Retain Status of Extern. BLOCK inputIntern. BLOCK 88V208 MMI,RST Recorded data1 0=Not active, 1=Active - 0 Read Retain Status of Intern. BLOCKB inputActive group 88V209 MMI,RST Recorded data1 0=Group 1, 1=Group 2 - 0 Read Retain Active setting groupDate 88V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording date

Page 94 of 158

Page 95: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Time 88V302 MMI,RST Recorded data2 hh:mm:ss.mss - - Read Retain Recording timeDuration 88V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 88V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 88V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 88V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL3Extern. BLOCK 88V307 MMI,RST Recorded data2 0=Not active, 1=Active - 0 Read Retain Status of Extern. BLOCK inputIntern. BLOCK 88V308 MMI,RST Recorded data2 0=Not active, 1=Active - 0 Read Retain Status of Intern. BLOCK inputActive group 88V309 MMI,RST Recorded data2 0=Group 1, 1=Group 2 - 0 Read Retain Active setting groupDate 88V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 88V402 MMI,RST Recorded data3 hh:mm:ss.mss - - Read Retain Recording timeDuration 88V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 88V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 88V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 88V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3Extern. BLOCK 88V407 MMI,RST Recorded data3 0=Not active, 1=Active - 0 Read Retain Status of Extern. BLOCK inputIntern. BLOCK 88V408 MMI,RST Recorded data3 0=Not active, 1=Active - 0 Read Retain Status of Intern. BLOCK inputActive group 88V409 MMI,RST Recorded data3 0=Group 1, 1=Group 2 - 0 Read Retain Active setting group

100089 / Rev E NUC3St2Operation mode 89S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Alarm; 2 = Trip] - 2 Read Volatile Selection of operation modeOper. criteria 89S2 MMI,RST Actual setting 0..1[0 = 1,2,3-phase; 1 = 3-phase] - 0 Read Volatile Selection of operation criteriaStart current 89S3 MMI,RST Actual setting 0.10...0.99 x ln 0,5 Read Volatile Start currentOperate time 89S4 MMI,RST Actual setting 0.1...600.0 s 2 Read Volatile Operate time at ALARM and TRIP modesIntern. blocking 89S5 MMI,RST Actual setting 0..1[0 = Disable; 1 = Enable] - 1 Read Volatile Enabling of internal undercurrent blockingBlocking time 89S6 MMI,RST Actual setting 0...7200 s 0 Read Volatile Blocking time from motor start-upOperation mode 89S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Alarm; 2 = Trip] - 2 Rd/Wr Retain Selection of operation modeOper. criteria 89S42 MMI,RST Setting group1 0..1[0 = 1,2,3-phase; 1 = 3-phase] - 0 Rd/Wr Retain Selection of operation criteriaStart current 89S43 MMI,RST Setting group1 0.10...0.99 x In 0,5 Rd/Wr Retain Start currentOperate time 89S44 MMI,RST Setting group1 0.1...600.0 s 2 Rd/Wr Retain Operate time at ALARM and TRIP modesIntern. blocking 89S45 MMI,RST Setting group1 0..1[0 = Disable; 1 = Enable] - 1 Rd/Wr Retain Enabling of internal undercurrent blockingBlocking time 89S46 MMI,RST Setting group1 0...7200 s 0 Rd/Wr Retain Blocking time from motor start-upOperation mode 89S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Alarm; 2 = Trip] - 2 Rd/Wr Retain Selection of operation modeOper. criteria 89S72 MMI,RST Setting group2 0..1[0 = 1,2,3-phase; 1 = 3-phase] - 0 Rd/Wr Retain Selection of operation criteriaStart current 89S73 MMI,RST Setting group2 0.10...0.99 x In 0,5 Rd/Wr Retain Start currentOperate time 89S74 MMI,RST Setting group2 0.1...600.0 s 2 Rd/Wr Retain Operate time at ALARM and TRIP modesIntern. blocking 89S75 MMI,RST Setting group2 0..1[0 = Disable; 1 = Enable] - 1 Rd/Wr Retain Enabling of internal overcurrentBlocking time 89S76 MMI,RST Setting group2 0...7200 s 0 Rd/Wr Retain Blocking time from motor start-upMeasuring mode 89V1 MMI,RST Control setting 0..1[0 = Peak to peak; 1 = Fundam. freq.] - 0 Rd/Wr Retain Selection of measuring modeDrop-off time 89V2 MMI,RST Control setting 0.00...60.00 s 0 Rd/Wr Retain Resetting time of the operate time counterGroup selection 89V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the actiive setting groupActive group 89V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 89V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 89V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 89V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 89V8 MMI,RST Control setting 100...1000 ms 500 Rd/Wr Retain Operate time of delayed trip CBFPAlarm signal 89V9 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for ALARM outputReset registers 89V13 RST Control setting 1=Reset - 0 Write Volatile Resetting of latched alarm or trip signal and registersTest START 89V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - - Rd/Wr Volatile Testing of STARTTest TRIP 89V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - - Rd/Wr Volatile Testing of TRIPTest CBFP 89V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - - Rd/Wr Volatile Testing of CBFP

Page 95 of 158

Page 96: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Test ALARM 89V34 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - - Rd/Wr Volatile Testing of ALARMEvent mask 1 89V101 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 1 for event transmission (E0...E13)Event mask 2 89V103 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 2 for event transmission (E0...E13)Event mask 3 89V105 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 3 for event transmission (E0...E13)Event mask 4 89V107 MMI,RST Control setting 0...16383 - 255 Rd/Wr Retain Event mask 4 for event tarnsmission (E0...E13)Current IL1 89I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 89I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 89I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Extern. BLOCK 89I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile External BLOCK signalIntern. BLOCK 89I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Internal BLOCK signalInput TRIGG 89I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 89I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input BSREG 89I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 89I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

NUC3St2Output START 89O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of START signalOutput TRIP 89O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of TRIP signalOutput CBFP 89O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalOutput ALARM 89O4 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of ALARM signalDate 89V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 89V202 MMI,RST Recorded data1 hh:mm:ss.mss - - Read Retain Recording timeDuration 89V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 89V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 89V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 89V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3Extern. BLOCK 89V207 MMI,RST Recorded data1 0=Not active, 1=Active - 0 Read Retain Status of Extern. BLOCK inputIntern. BLOCK 89V208 MMI,RST Recorded data1 0=Not active, 1=Active - 0 Read Retain Status of Intern. BLOCKB inputActive group 89V209 MMI,RST Recorded data1 0=Group 1, 1=Group 2 - 0 Read Retain Active setting groupDate 89V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 89V302 MMI,RST Recorded data2 hh:mm:ss.mss - - Read Retain Recording timeDuration 89V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 89V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 89V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 89V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL3Extern. BLOCK 89V307 MMI,RST Recorded data2 0=Not active, 1=Active - 0 Read Retain Status of Extern. BLOCK inputIntern. BLOCK 89V308 MMI,RST Recorded data2 0=Not active, 1=Active - 0 Read Retain Status of Intern. BLOCK inputActive group 89V309 MMI,RST Recorded data2 0=Group 1, 1=Group 2 - 0 Read Retain Active setting groupDate 89V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 89V402 MMI,RST Recorded data3 hh:mm:ss.mss - - Read Retain Recording timeDuration 89V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 89V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 89V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 89V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3Extern. BLOCK 89V407 MMI,RST Recorded data3 0=Not active, 1=Active - 0 Read Retain Status of Extern. BLOCK inputIntern. BLOCK 89V408 MMI,RST Recorded data3 0=Not active, 1=Active - 0 Read Retain Status of Intern. BLOCK inputActive group 89V409 MMI,RST Recorded data3 0=Group 1, 1=Group 2 - 0 Read Retain Active setting group

100090 / Rev D NEF1InstOperation mode 90S1 MMI,RST Actual setting 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Read Volatile Selection of operation modeStart current 90S2 MMI,RST Actual setting 0.10...12.00 x In 0,1 Read Volatile Start current

Page 96 of 158

Page 97: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Operate time 90S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate timeOperation mode 90S41 MMI,RST Setting group1 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 90S42 MMI,RST Setting group1 0.10...12.00 x In 0,1 Rd/Wr Retain Start currentOperate time 90S43 MMI,RST Setting group1 0.05...300.00 s 0,05 Rd/Wr Retain Operate timeOperation mode 90S71 MMI,RST Setting group2 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 1 Rd/Wr Retain Selection of operation modeStart current 90S72 MMI,RST Setting group2 0.10...12.00 x In 0,1 Rd/Wr Retain Start currentOperate time 90S73 MMI,RST Setting group2 0.05...300.00 s 0,05 Rd/Wr Retain Operate timeMeasuring mode 90V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 1 Rd/Wr Retain Selection of measuring modeDrop-off time 90V2 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Resetting time of the operate time counterGroup selection 90V3 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 90V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 90V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 90V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 90V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 90V8 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of CBFPReset registers 90V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 90V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 90V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 90V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 90V101 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 90V103 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 90V105 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 90V107 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Current Io 90I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Neutral current IoInput BS1 90I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS1Input BS2 90I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Block signal BS2Input TRIGG 90I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for triggering the registersInput GROUP 90I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input BSREG 90I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the recording functionInput RESET 90I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting trip signal and registers NEF1InstOutput START 90O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 90O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput CBFP 90O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of CBFP signalDate 90V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 90V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 90V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 90V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IoIo peak 90V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IoBS1 90V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 90V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 90V208 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 90V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 90V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 90V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 90V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IoIo peak 90V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IoBS1 90V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 90V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 90V308 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

Page 97 of 158

Page 98: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Date 90V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 90V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 90V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIo mean 90V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IoIo peak 90V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IoBS1 90V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 90V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 90V408 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100091 / Rev C VOC6LowOperation mode 91S1 MMI,RST Actual setting 0..7[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.;6 = RI-type inverse; 7 = RD-type inverse]

- 1 Read Volatile Selection of operation mode and inverse time characteristic

Start current 91S2 MMI,RST Actual setting 0.10...5.00 x In 0,1 Read Volatile Start currentOperate time 91S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DTmodeTime multiplier 91S4 MMI,RST Actual setting 0.05...1.00 - 0,05 Read Volatile Time multiplier at IDMT modeControl mode 91S5 MMI,RST Actual setting 0..2[0 = Voltage step; 1 = Voltage slope; 2 = Input step] - 0 Read Volatile Selection of mode for voltage controlVoltage limit 91S6 MMI,RST Actual setting 0.10...1.00 x Un 0,1 Read Volatile Voltage setting value for Voltage step modeVoltage limit 1 91S7 MMI,RST Actual setting 0.60...1.00 x Un 0,6 Read Volatile Upper voltage setting value for Voltage slope modeVoltage limit 2 91S8 MMI,RST Actual setting 0.10...0.59 x Un 0,1 Read Volatile Lower voltage setting value for Voltage slope modeCurr.multiplier 91S9 MMI,RST Actual setting 0.05...1.00 - 0,05 Read Volatile Multiplier for lower Start current valueOperation mode 91S41 MMI,RST Setting group1 0..7[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.;6 = RI-type inverse; 7 = RD-type inverse]

- 1 Rd/Wr Retain Selection of operate mode and inverse time characteristic

Start current 91S42 MMI,RST Setting group1 0.10...5.00 x In 0,1 Rd/Wr Retain Start currentOperate time 91S43 MMI,RST Setting group1 0.05...100.00 s 0,05 Rd/Wr Retain Operate time at DTmodeTime multiplier 91S44 MMI,RST Setting group1 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeControl mode 91S45 MMI,RST Setting group1 0..2[0 = Voltage step; 1 = Voltage slope; 2 = Input step] - 0 Rd/Wr Retain Selection of mode for voltage controlVoltage limit 91S46 MMI,RST Setting group1 0.10...1.00 x Un 0,1 Rd/Wr Retain Voltage setting value for Voltage step modeVoltage limit 1 91S47 MMI,RST Setting group1 0.60...1.00 x Un 0,6 Rd/Wr Retain Upper voltage setting value for Voltage slope modeVoltage limit 2 91S48 MMI,RST Setting group1 0.10...0.59 x Un 0,1 Rd/Wr Retain Lower voltage setting value for Voltage slope modeCurr.multiplier 91S49 MMI,RST Setting group1 0.05...1.00 - 0,05 Rd/Wr Retain Multiplier for lower Start current valueOperation mode 91S71 MMI,RST Setting group2 0..7[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.;6 = RI-type inverse; 7 = RD-type inverse]

- 1 Rd/Wr Retain Selection of operate mode and inverse time characteristic

Start current 91S72 MMI,RST Setting group2 0.10...5.00 x In 0,1 Rd/Wr Retain Start currentOperate time 91S73 MMI,RST Setting group2 0.05...100.00 s 0,05 Rd/Wr Retain Operate time at DTmodeTime multiplier 91S74 MMI,RST Setting group2 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeControl mode 91S75 MMI,RST Setting group2 0..2[0 = Voltage step; 1 = Voltage slope; 2 = Input step] - 0 Rd/Wr Retain Selection of mode for voltage controlVoltage limit 91S76 MMI,RST Setting group2 0.10...1.00 x Un 0,1 Rd/Wr Retain Voltage setting value for Voltage step modeVoltage limit 1 91S77 MMI,RST Setting group2 0.60...1.00 x Un 0,6 Rd/Wr Retain Upper voltage setting value for Voltage slope modeVoltage limit 2 91S78 MMI,RST Setting group2 0.10...0.59 x Un 0,1 Rd/Wr Retain Lower voltage setting value for Voltage slope modeCurr.multiplier 91S79 MMI,RST Setting group2 0.05...1.00 - 0,05 Rd/Wr Retain Multiplier for lower Start current valueMeasuring mode 91V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 0 Rd/Wr Retain Selection of measuring modeVoltage select. 91V2 MMI,RST Control setting 0..1[0 = Phase-to-phase; 1 = Phase-to-earth] - 0 Rd/Wr Retain Selection of phase-to-phase or phase-to-earth voltagesDrop-off time 91V3 MMI,RST Control setting 0.00...10.00 s 0 Rd/Wr Retain Resetting time of the operate time counter at DT and

IDMT modeGroup selection 91V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 91V5 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 91V6 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signal

Page 98 of 158

Page 99: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Trip signal 91V7 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 91V8 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPMinimum time 91V9 MMI,RST Control setting 0.03...10.00 s 0,03 Rd/Wr Retain Minimum operate time at IDMT modeCBFP time 91V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 91V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 91V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 91V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 91V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 91V101 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 91V103 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 91V105 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 91V107 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Current IL1 91I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Channel measuring phase current IL1Current IL2 91I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Channel measuring phase current IL2Current IL3 91I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Channel measuring phase current IL3Voltage U12 91I4 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Channel measuring voltage U12Voltage U23 91I5 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Channel measuring voltage U23Voltage U31 91I6 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Channel measuring voltage U31Input BLOCK 91I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Blocking signalInput GROUP 91I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Control input for switching between setting group 1 and

setting group 2. When GROUP is TRUE (logic 1), group 2 is active.

Input DOUBLE 91I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input signal used for doubling the set start current value temporarily at magnetizing inrush or start-up situation

Input CONTROL 91I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input signal used for lower current setting in Input Step Control mode

Input RESET 91I11 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input signal for resetting the trip signal and registers of VOC6Low

Output START 91O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 91O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput ERR 91O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of ERR signalDate 91V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 91V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 91V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 91V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 91V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 91V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 91V207 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 91V208 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 91V209 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 91V210 MMI,RST Recorded data1 0.0...2.0 x Un 0 Read Retain Filtered value of U12Voltage U23 91V211 MMI,RST Recorded data1 0.0...2.0 x Un 0 Read Retain Filtered value of U23Voltage U31 91V212 MMI,RST Recorded data1 0.0...2.0 x Un 0 Read Retain Filtered value of U31BLOCK 91V213 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputDOUBLE 91V214 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 91V215 MMI,RST Recorded data1 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 91V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 91V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 91V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situation

Page 99 of 158

Page 100: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

IL1 mean 91V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 91V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 91V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 91V307 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 91V308 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 91V309 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 91V310 MMI,RST Recorded data2 0.0...2.0 x Un 0 Read Retain Filtered value of U12Voltage U23 91V311 MMI,RST Recorded data2 0.0...2.0 x Un 0 Read Retain Filtered value of U23Voltage U31 91V312 MMI,RST Recorded data2 0.0...2.0 x Un 0 Read Retain Filtered value of U31BLOCK 91V313 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputDOUBLE 91V314 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 91V315 MMI,RST Recorded data2 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting groupDate 91V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 91V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 91V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 91V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 91V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 91V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 91V407 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 91V408 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 91V409 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 91V410 MMI,RST Recorded data3 0.0...2.0 x Un 0 Read Retain Filtered value of U12Voltage U23 91V411 MMI,RST Recorded data3 0.0...2.0 x Un 0 Read Retain Filtered value of U23Voltage U31 91V412 MMI,RST Recorded data3 0.0...2.0 x Un 0 Read Retain Filtered value of U31BLOCK 91V413 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputDOUBLE 91V414 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 91V415 MMI,RST Recorded data3 0..1[0 = Group 1; 1=Group 2] - 0 Read Retain Active setting group

100092 / Rev D OPOW6St1Active power P 92I1 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated active powerReactive powerQ 92I2 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated reactive powerInput BLOCK 92I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the functionInput GROUP 92I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 92I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

OPOW6St1Output START 92O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 92O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 92V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 92V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 92V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 92V204 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 92V205 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 92V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 92V207 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 92V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 92V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 92V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 92V304 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 92V305 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 92V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK input

Page 100 of 158

Page 101: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Active group 92V307 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 92V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 92V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 92V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 92V404 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 92V405 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 92V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 92V407 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupPower setting 92S1 MMI,RST Actual setting 1.0...200.0 % Sn 100 Read Volatile Start powerAngle 92S2 MMI,RST Actual setting -90...90 ° 0 Read Volatile Power directionOperate time 92S3 MMI,RST Actual setting 0.04...300.00 s 0,5 Read Volatile Operate timePower setting 92S41 MMI,RST Setting group1 1.0...200.0 % Sn 100 Rd/Wr Retain Start powerAngle 92S42 MMI,RST Setting group1 -90...90 ° 0 Rd/Wr Retain Power directionOperate time 92S43 MMI,RST Setting group1 0.04...300 s 0,5 Rd/Wr Retain Operate timePower setting 92S71 MMI,RST Setting group2 1.0...200.0 % Sn 100 Rd/Wr Retain Start powerAngle 92S72 MMI,RST Setting group2 -90...90 ° 0 Rd/Wr Retain Power directionOperate time 92S73 MMI,RST Setting group2 0.04...300 s 0,5 Rd/Wr Retain Operate timeOPOW6St1 92V1 MMI,RST Control setting 0=Not in use; 1=In use - 1 Rd/Wr Retain Protection block in use or not in useDrop-off time 92V2 MMI,RST Control setting 0.00...60.00 s 1 Rd/Wr Retain Resetting time of the operate time counterMeasuring mode 92V3 MMI,RST Control setting 0 = Not in use; 1= U1,U2,U3 & I1,I2,I3; 2 =

U12,U23,U0 & I1,I2,I3; 3 = U23,U31,U0 & I1,I2,I3; 4 = U12,U31,U0 & I1,I2,I3; 5 = U12,U23 & I1,I2,I3;

- 0 Read Volatile Power measurement mode

Power direction 92V4 MMI,RST Control setting 0= Forward; 1= Reverse - 0 Rd/Wr Retain Direction of power flowGroup selection 92V5 MMI,RST Control setting 0=Group 1; 1=Group 2; 2=GROUP input - 0 Rd/Wr Retain Selection of the active setting groupActive group 92V6 MMI,RST Control setting 0=Group 1; 1=Group 2 - 0 Read Volatile Active setting groupStart pulse 92V7 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 92V8 MMI,RST Control setting 0=Non-latching; 1=Latching - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 92V9 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 92V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 92V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 92V31 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of STARTTest TRIP 92V32 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 92V33 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 92V101 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 92V103 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 92V105 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 92V107 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)

100093 / Rev D OPOW6St2Power setting 93S1 MMI,RST Actual setting 1.0...200.0 % Sn 100 Read Volatile Start powerAngle 93S2 MMI,RST Actual setting -90...90 ° 0 Read Volatile Power directionOperate time 93S3 MMI,RST Actual setting 0.04...300.00 s 0,5 Read Volatile Operate timePower setting 93S41 MMI,RST Setting group1 1.0...200.0 % Sn 100 Rd/Wr Retain Start powerAngle 93S42 MMI,RST Setting group1 -90...90 ° 0 Rd/Wr Retain Power directionOperate time 93S43 MMI,RST Setting group1 0.04...300 s 0,5 Rd/Wr Retain Operate timePower setting 93S71 MMI,RST Setting group2 1.0...200.0 % Sn 100 Rd/Wr Retain Start powerAngle 93S72 MMI,RST Setting group2 -90...90 ° 0 Rd/Wr Retain Power directionOperate time 93S73 MMI,RST Setting group2 0.04...300 s 0,5 Rd/Wr Retain Operate timeOPOW6St2 93V1 MMI,RST Control setting 0=Not in use; 1=In use - 1 Rd/Wr Retain Protection block in use or not in useDrop-off time 93V2 MMI,RST Control setting 0.00...60.00 s 1 Rd/Wr Retain Resetting time of the operate time counter

Page 101 of 158

Page 102: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Measuring mode 93V3 MMI,RST Control setting 0 = Not in use; 1= U1,U2,U3 & I1,I2,I3; 2 = U12,U23,U0 & I1,I2,I3; 3 = U23,U31,U0 & I1,I2,I3; 4 = U12,U31,U0 & I1,I2,I3; 5 = U12,U23 & I1,I2,I3;

- 0 Read Volatile Power measurement mode

Power direction 93V4 MMI,RST Control setting 0= Forward; 1= Reverse - 0 Rd/Wr Retain Direction of power flowGroup selection 93V5 MMI,RST Control setting 0=Group 1; 1=Group 2; 2=GROUP input - 0 Rd/Wr Retain Selection of the active setting groupActive group 93V6 MMI,RST Control setting 0=Group 1; 1=Group 2 - 0 Read Volatile Active setting groupStart pulse 93V7 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 93V8 MMI,RST Control setting 0=Non-latching; 1=Latching - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 93V9 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 93V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 93V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 93V31 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of STARTTest TRIP 93V32 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 93V33 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 93V101 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 93V103 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 93V105 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 93V107 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Active power P 93I1 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated active powerReactive powerQ 93I2 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated reactive powerInput BLOCK 93I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the functionInput GROUP 93I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 93I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

OPOW6St2Output START 93O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 93O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 93V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 93V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 93V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 93V204 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 93V205 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 93V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 93V207 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 93V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 93V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 93V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 93V304 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 93V305 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 93V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 93V307 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 93V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 93V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 93V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 93V404 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 93V405 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 93V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 93V407 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100094 / Rev D OPOW6St3Power setting 94S1 MMI,RST Actual setting 1.0...200.0 % Sn 100 Read Volatile Start power

Page 102 of 158

Page 103: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Angle 94S2 MMI,RST Actual setting -90...90 ° 0 Read Volatile Power directionOperate time 94S3 MMI,RST Actual setting 0.04...300.00 s 0,5 Read Volatile Operate timePower setting 94S41 MMI,RST Setting group1 1.0...200.0 % Sn 100 Rd/Wr Retain Start powerAngle 94S42 MMI,RST Setting group1 -90...90 ° 0 Rd/Wr Retain Power directionOperate time 94S43 MMI,RST Setting group1 0.04...300 s 0,5 Rd/Wr Retain Operate timePower setting 94S71 MMI,RST Setting group2 1.0...200.0 % Sn 100 Rd/Wr Retain Start powerAngle 94S72 MMI,RST Setting group2 -90...90 ° 0 Rd/Wr Retain Power directionOperate time 94S73 MMI,RST Setting group2 0.04...300 s 0,5 Rd/Wr Retain Operate timeOPOW6St3 94V1 MMI,RST Control setting 0=Not in use; 1=In use - 1 Rd/Wr Retain Protection block in use or not in useDrop-off time 94V2 MMI,RST Control setting 0.00...60.00 s 1 Rd/Wr Retain Resetting time of the operate time counterMeasuring mode 94V3 MMI,RST Control setting 0 = Not in use; 1= U1,U2,U3 & I1,I2,I3; 2 =

U12,U23,U0 & I1,I2,I3; 3 = U23,U31,U0 & I1,I2,I3; 4 = U12,U31,U0 & I1,I2,I3; 5 = U12,U23 & I1,I2,I3;

- 0 Read Volatile Power measurement mode

Power direction 94V4 MMI,RST Control setting 0= Forward; 1= Reverse - 0 Rd/Wr Retain Direction of power flowGroup selection 94V5 MMI,RST Control setting 0=Group 1; 1=Group 2; 2=GROUP input - 0 Rd/Wr Retain Selection of the active setting groupActive group 94V6 MMI,RST Control setting 0=Group 1; 1=Group 2 - 0 Read Volatile Active setting groupStart pulse 94V7 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 94V8 MMI,RST Control setting 0=Non-latching; 1=Latching - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 94V9 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 94V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 94V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 94V31 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of STARTTest TRIP 94V32 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 94V33 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 94V101 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 94V103 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 94V105 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 94V107 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Active power P 94I1 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated active powerReactive powerQ 94I2 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated reactive powerInput BLOCK 94I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the functionInput GROUP 94I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 94I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

OPOW6St3Output START 94O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 94O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 94V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 94V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 94V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 94V204 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 94V205 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 94V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 94V207 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 94V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 94V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 94V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 94V304 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 94V305 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 94V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK input

Page 103 of 158

Page 104: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Active group 94V307 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 94V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 94V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 94V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 94V404 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 94V405 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 94V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 94V407 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100095 / Rev E UPOW6St1Power setting 95S1 MMI,RST Actual setting 1.0...200.0 % Sn 1 Read Volatile Start powerOperation mode 95S2 MMI,RST Actual setting 0=Under power ; 1=Reverse power - 1 Read Volatile Selection of under power or reverse powerOperate time 95S3 MMI,RST Actual setting 0.04...300.00 s 0,5 Read Volatile Operate timeWait time 95S4 MMI,RST Actual setting 0.0...60 s 0 Read Volatile Waiting time after closing circuit breakerDisable mode 95S5 MMI,RST Actual setting 0=OFF; 1=ON - 1 Read Volatile Disable input in use or not in usePower setting 95S41 MMI,RST Setting group1 1.0...200.0 % Sn 1 Rd/Wr Retain Start powerOperation mode 95S42 MMI,RST Setting group1 0=Under power ; 1=Reverse power - 1 Rd/Wr Retain Selection of under power or reverse powerOperate time 95S43 MMI,RST Setting group1 0.04...300.00 s 0,5 Rd/Wr Retain Operate timeWait time 95S44 MMI,RST Setting group1 0.0...60.0 s 0 Rd/Wr Retain Waiting time after closing circuit breakerDisable mode 95S45 MMI,RST Setting group1 0=OFF; 1=ON - 1 Rd/Wr Retain Disable input in use or not in usePower setting 95S71 MMI,RST Setting group2 1.0...200.0 % Sn 1 Rd/Wr Retain Start powerOperation mode 95S72 MMI,RST Setting group2 0=Under power ; 1=Reverse power - 1 Rd/Wr Retain Selection of under power or reverse powerOperate time 95S73 MMI,RST Setting group2 0.04...300.00 s 0,5 Rd/Wr Retain Operate timeWait time 95S74 MMI,RST Setting group2 0.0...60.0 s 0 Rd/Wr Retain Waiting time after closing circuit breakerDisable mode 95S75 MMI,RST Setting group2 0=OFF; 1=ON - 1 Rd/Wr Retain Disable input in use or not in useUPOW6St1 95V1 MMI,RST Control setting 0=Not in use; 1=In use - 1 Rd/Wr Retain UPOWSt1 in use or not in useDrop-off time 95V2 MMI,RST Control setting 0.00...60.00 s 1 Rd/Wr Retain Resetting time of the operate time counterMeasuring mode 95V3 MMI,RST Control setting 0 = Not in use; 1= U1,U2,U3 & I1,I2,I3; 2 =

U12,U23,U0 & I1,I2,I3; 3 = U23,U31,U0 & I1,I2,I3; 4 = U12,U31,U0 & I1,I2,I3; 5 = U12,U23 & I1,I2,I3;

- 0 Read Volatile Power measurement mode

Power direction 95V4 MMI,RST Control setting 0= Forward; 1= Reverse - 0 Rd/Wr Retain Direction of power flowGroup selection 95V5 MMI,RST Control setting 0=Group 1; 1=Group 2; 2=GROUP input - 0 Rd/Wr Retain Selection of the active setting groupActive group 95V6 MMI,RST Control setting 0=Group 1; 1=Group 2 - 0 Read Volatile Active setting groupStart pulse 95V7 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 95V8 MMI,RST Control setting 0=Non-latching; 1=Latching - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 95V9 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 95V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 95V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 95V31 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of STARTTest TRIP 95V32 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 95V33 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 95V101 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 95V103 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 95V105 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 95V107 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Active power P 95I1 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated active powerReactive powerQ 95I2 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated reactive powerInput BLOCK 95I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the functionInput GROUP 95I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2

Page 104 of 158

Page 105: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Input RESET 95I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of UPOW6St1

Input DISABLE 95I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for disabling UPOW to operate when generator is not synchronized

Output START 95O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 95O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 95V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 95V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 95V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 95V204 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 95V205 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 95V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 95V207 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 95V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 95V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 95V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 95V304 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 95V305 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 95V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 95V307 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 95V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 95V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 95V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 95V404 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 95V405 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 95V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 95V407 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100096 / Rev E UPOW6St2Power setting 96S1 MMI,RST Actual setting 1.0...200.0 % Sn 1 Read Volatile Start powerOperation mode 96S2 MMI,RST Actual setting 0=Under power ; 1=Reverse power - 1 Read Volatile Selection of under power or reverse powerOperate time 96S3 MMI,RST Actual setting 0.04...300.00 s 0,5 Read Volatile Operate timeWait time 96S4 MMI,RST Actual setting 0.0...60 s 0 Read Volatile Waiting time after closing circuit breakerDisable mode 96S5 MMI,RST Actual setting 0=OFF; 1=ON - 1 Read Volatile Disable input in use or not in usePower setting 96S41 MMI,RST Setting group1 1.0...200.0 % Sn 1 Rd/Wr Retain Start powerOperation mode 96S42 MMI,RST Setting group1 0=Under power ; 1=Reverse power - 1 Rd/Wr Retain Selection of under power or reverse powerOperate time 96S43 MMI,RST Setting group1 0.04...300.00 s 0,5 Rd/Wr Retain Operate timeWait time 96S44 MMI,RST Setting group1 0.0...60.0 s 0 Rd/Wr Retain Waiting time after closing circuit breakerDisable mode 96S45 MMI,RST Setting group1 0=OFF; 1=ON - 1 Rd/Wr Retain Disable input in use or not in usePower setting 96S71 MMI,RST Setting group2 1.0...200.0 % Sn 1 Rd/Wr Retain Start powerOperation mode 96S72 MMI,RST Setting group2 0=Under power ; 1=Reverse power - 1 Rd/Wr Retain Selection of under power or reverse powerOperate time 96S73 MMI,RST Setting group2 0.04...300.00 s 0,5 Rd/Wr Retain Operate timeWait time 96S74 MMI,RST Setting group2 0.0...60.0 s 0 Rd/Wr Retain Waiting time after closing circuit breakerDisable mode 96S75 MMI,RST Setting group2 0=OFF; 1=ON - 1 Rd/Wr Retain Disable input in use or not in useUPOW6St2 96V1 MMI,RST Control setting 0=Not in use; 1=In use - 1 Rd/Wr Retain UPOWSt2 in use or not in useDrop-off time 96V2 MMI,RST Control setting 0.00...60.00 s 1 Rd/Wr Retain Resetting time of the operate time counterMeasuring mode 96V3 MMI,RST Control setting 0 = Not in use; 1= U1,U2,U3 & I1,I2,I3; 2 =

U12,U23,U0 & I1,I2,I3; 3 = U23,U31,U0 & I1,I2,I3; 4 = U12,U31,U0 & I1,I2,I3; 5 = U12,U23 & I1,I2,I3;

- 0 Read Volatile Power measurement mode

Power direction 96V4 MMI,RST Control setting 0= Forward; 1= Reverse - 0 Rd/Wr Retain Direction of power flow

Page 105 of 158

Page 106: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Group selection 96V5 MMI,RST Control setting 0=Group 1; 1=Group 2; 2=GROUP input - 0 Rd/Wr Retain Selection of the active setting groupActive group 96V6 MMI,RST Control setting 0=Group 1; 1=Group 2 - 0 Read Volatile Active setting groupStart pulse 96V7 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 96V8 MMI,RST Control setting 0=Non-latching; 1=Latching - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 96V9 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 96V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 96V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 96V31 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of STARTTest TRIP 96V32 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 96V33 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 96V101 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 96V103 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 96V105 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 96V107 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Active power P 96I1 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated active powerReactive powerQ 96I2 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated reactive powerInput BLOCK 96I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the functionInput GROUP 96I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 96I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

UPOW6St2Input DISABLE 96I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for disabling UPOW to operate when generator is

not synchronizedOutput START 96O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 96O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 96V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 96V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 96V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 96V204 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 96V205 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 96V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 96V207 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 96V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 96V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 96V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 96V304 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 96V305 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 96V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 96V307 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 96V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 96V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 96V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 96V404 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 96V405 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 96V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 96V407 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100097 / Rev E UPOW6St3Power setting 97S1 MMI,RST Actual setting 1.0...200.0 % Sn 1 Read Volatile Start powerOperation mode 97S2 MMI,RST Actual setting 0=Under power ; 1=Reverse power - 1 Read Volatile Selection of under power or reverse powerOperate time 97S3 MMI,RST Actual setting 0.04...300.00 s 0,5 Read Volatile Operate time

Page 106 of 158

Page 107: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Wait time 97S4 MMI,RST Actual setting 0.0...60 s 0 Read Volatile Waiting time after closing circuit breakerDisable mode 97S5 MMI,RST Actual setting 0=OFF; 1=ON - 1 Read Volatile Disable input in use or not in usePower setting 97S41 MMI,RST Setting group1 1.0...200.0 % Sn 1 Rd/Wr Retain Start powerOperation mode 97S42 MMI,RST Setting group1 0=Under power ; 1=Reverse power - 1 Rd/Wr Retain Selection of under power or reverse powerOperate time 97S43 MMI,RST Setting group1 0.04...300.00 s 0,5 Rd/Wr Retain Operate timeWait time 97S44 MMI,RST Setting group1 0.0...60.0 s 0 Rd/Wr Retain Waiting time after closing circuit breakerDisable mode 97S45 MMI,RST Setting group1 0=OFF; 1=ON - 1 Rd/Wr Retain Disable input in use or not in usePower setting 97S71 MMI,RST Setting group2 1.0...200.0 % Sn 1 Rd/Wr Retain Start powerOperation mode 97S72 MMI,RST Setting group2 0=Under power ; 1=Reverse power - 1 Rd/Wr Retain Selection of under power or reverse powerOperate time 97S73 MMI,RST Setting group2 0.04...300.00 s 0,5 Rd/Wr Retain Operate timeWait time 97S74 MMI,RST Setting group2 0.0...60.0 s 0 Rd/Wr Retain Waiting time after closing circuit breakerDisable mode 97S75 MMI,RST Setting group2 0=OFF; 1=ON - 1 Rd/Wr Retain Disable input in use or not in useUPOW6St3 97V1 MMI,RST Control setting 0=Not in use; 1=In use - 1 Rd/Wr Retain UPOWSt3 in use or not in useDrop-off time 97V2 MMI,RST Control setting 0.00...60.00 s 1 Rd/Wr Retain Resetting time of the operate time counterMeasuring mode 97V3 MMI,RST Control setting 0 = Not in use; 1= U1,U2,U3 & I1,I2,I3; 2 =

U12,U23,U0 & I1,I2,I3; 3 = U23,U31,U0 & I1,I2,I3; 4 = U12,U31,U0 & I1,I2,I3; 5 = U12,U23 & I1,I2,I3;

- 0 Read Volatile Power measurement mode

Power direction 97V4 MMI,RST Control setting 0= Forward; 1= Reverse - 0 Rd/Wr Retain Direction of power flowGroup selection 97V5 MMI,RST Control setting 0=Group 1; 1=Group 2; 2=GROUP input - 0 Rd/Wr Retain Selection of the active setting groupActive group 97V6 MMI,RST Control setting 0=Group 1; 1=Group 2 - 0 Read Volatile Active setting groupStart pulse 97V7 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 97V8 MMI,RST Control setting 0=Non-latching; 1=Latching - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 97V9 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 97V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 97V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 97V31 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of STARTTest TRIP 97V32 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 97V33 MMI,RST Control setting 0=Do not activate; 1=Activate - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 97V101 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 97V103 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 97V105 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 97V107 MMI,RST Control setting 0...4095 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Active power P 97I1 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated active powerReactive powerQ 97I2 MMI,RST Input data -1000.0...1000.0 % Sn 0 Read Volatile Calculated reactive powerInput BLOCK 97I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for blocking the functionInput GROUP 97I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 97I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of

UPOW6St3Input DISABLE 97I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for disabling UPOW to operate when generator is

not synchronizedOutput START 97O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 97O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalDate 97V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 97V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 97V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 97V204 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 97V205 MMI,RST Recorded data1 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 97V206 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 97V207 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

Page 107 of 158

Page 108: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Date 97V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 97V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 97V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 97V304 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 97V305 MMI,RST Recorded data2 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 97V306 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 97V307 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 97V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 97V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 97V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationActive power P 97V404 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated active powerReactive powerQ 97V405 MMI,RST Recorded data3 -1000.0...1000.0 % Sn 0 Read Retain Calculated reactive powerBLOCK 97V406 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 97V407 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100099 / Rev C Diff6GBasic setting 99S1 MMI,RST Actual setting 5...50 % 5 Read Volatile The lowest ratio of differential and nominal current to

cause a tripStarting ratio 99S2 MMI,RST Actual setting 10...50 % 10 Read Volatile Slope of the second line of the operation characteristicsTurn-point 1 99S3 MMI,RST Actual setting 0.0...1.0 x In 0,5 Read Volatile Turn-point between the first and the second line of the

operation characteristicsTurn-point 2 99S4 MMI,RST Actual setting 1.0...3.0 x In 1,5 Read Volatile Turn-point between the second and the third line of the

operation characteristicsInst. setting 99S5 MMI,RST Actual setting 5...30 x In 5 Read Volatile Trip value of the instantaneous stageBasic setting 99S41 MMI,RST Setting group1 5...50 % 5 Rd/Wr Retain The lowest ratio of differential and nominal current to

cause a tripStarting ratio 99S42 MMI,RST Setting group1 10...50 % 10 Rd/Wr Retain Slope of the second line of the operation characteristicsTurn-point 1 99S43 MMI,RST Setting group1 0.0...1.0 x In 0,5 Rd/Wr Retain Turn-point between the first and the second line of the

operation characteristicsTurn-point 2 99S44 MMI,RST Setting group1 1.0...3.0 x In 1,5 Rd/Wr Retain Turn-point between the second and the third line of the

operation characteristicsInst. setting 99S45 MMI,RST Setting group1 5...30 x In 5 Rd/Wr Retain Trip value of the instantaneous stageBasic setting 99S71 MMI,RST Setting group2 5...50 % 5 Rd/Wr Retain The lowest ratio of differential and nominal current to

cause a tripStarting ratio 99S72 MMI,RST Setting group2 10...50 % 10 Rd/Wr Retain Slope of the second line of the operation characteristicsTurn-point 1 99S73 MMI,RST Setting group2 0.0...1.0 x In 0,5 Rd/Wr Retain Turn-point between the first and the second line of the

operation characteristicsTurn-point 2 99S74 MMI,RST Setting group2 1.0...3.0 x In 1,5 Rd/Wr Retain Turn-point between the second and the third line of the

operation characteristicsInst. setting 99S75 MMI,RST Setting group2 5...30 x In 5 Rd/Wr Retain Trip value of the instantaneous stageDiff6G 99V1 MMI,RST Control setting 0=Not in use; 1=In use - 1 Rd/Wr Retain Protection block in use or not in useGroup selection 99V2 MMI,RST Control setting 0=Group 1; 1=Group 2; 2=GROUP input - 0 Rd/Wr Retain Selection of the active setting groupActive group 99V3 MMI,RST Control setting 0=Group 1; 1=Group 2 - 0 Read Volatile Active setting groupTrip signal 99V4 MMI,RST Control setting 0=Non-latching; 1=Latching - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 99V5 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 99V6 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPCT connection 99V7 MMI,RST Control setting 0=type I; 1=type II - 0 Rd/Wr Retain Determined by the directions of the connected current

transformersReset registers 99V13 RST Control setting 1=Reset - 0 Write Volatile Resetting of latched trip signal and registersTest TRIP 99V32 MMI,RST Control setting 0=Do not activate; 1=Activate - - Rd/Wr Volatile Testing of TRIP

Page 108 of 158

Page 109: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Test CBFP 99V33 MMI,RST Control setting 0=Do not activate; 1=Activate - - Rd/Wr Volatile Testing of CBFPEvent mask 1 99V101 MMI,RST Control setting 0...16383 - 8255 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E13)Event mask 2 99V103 MMI,RST Control setting 0...16383 - 8255 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E13)Event mask 3 99V105 MMI,RST Control setting 0...16383 - 8255 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E13)Event mask 4 99V107 MMI,RST Control setting 0...16383 - 8255 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E13)Current IL1 99I1 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 99I2 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 99I3 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Phase current IL3Current IL1b 99I4 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Phase current IL1bCurrent IL2b 99I5 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Phase current IL2bCurrent IL3b 99I6 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Phase current IL3bCurrent Id1 99I7 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Differential current of phase 1Current Id2 99I8 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Differential current of phase 2Current Id3 99I9 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Differential current of phase 3Current Ib1 99I10 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Bias current of phase 1Current Ib2 99I11 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Bias current of phase 2Current Ib3 99I12 MMI,RST Input data1 0.00...60.00 x In 0 Read Volatile Bias current of phase 3Angle IL1-IL2 99I13 MMI,RST Input data2 -180...180 ° 0 Read Volatile Phase difference of the currents L1 and L2Angle IL2-IL3 99I14 MMI,RST Input data2 -180...180 ° 0 Read Volatile Phase difference of the currents L2 and L3Angle IL3-IL1 99I15 MMI,RST Input data2 -180...180 ° 0 Read Volatile Phase difference of the currents L3 and L1Angle IL1b-IL2b 99I16 MMI,RST Input data2 -180...180 ° 0 Read Volatile Phase difference of the currents L1b and L2bAngle IL2b-IL3b 99I17 MMI,RST Input data2 -180...180 ° 0 Read Volatile Phase difference of the currents L2b and L3bAngle IL3b-IL1b 99I18 MMI,RST Input data2 -180...180 ° 0 Read Volatile Phase difference of the currents L3b and L1bAngle IL1-IL1b 99I19 MMI,RST Input data2 -180...180 ° 0 Read Volatile Phase difference of the currents L1 and L1bAngle IL2-IL2b 99I20 MMI,RST Input data2 -180...180 ° 0 Read Volatile Phase difference of the currents L2 and L2bAngle IL3-IL3b 99I21 MMI,RST Input data2 -180...180 ° 0 Read Volatile Phase difference of the currents L3 and L3bInput BS1 99I22 MMI,RST Input data2 0=Not active, 1=Active - 0 Read Volatile Status of BS1 signalInput BS2 99I23 MMI,RST Input data2 0=Not active, 1=Active - 0 Read Volatile Status of BS2 signalInput GROUP 99I24 MMI,RST Input data2 0=Not active, 1=Active - 0 Read Volatile Status of signal for switching between group 1 and 2Input RESET 99I25 MMI,RST Input data2 0=Not active, 1=Active - 0 Read Volatile Status of signal for resetting output signals of Diff6GOutput TRIP 99O1 MMI,RST Output data 0=Not active, 1=Active - 0 Read Volatile Status of trip signalOutput ERR 99O2 MMI,RST Output data 0=Not active, 1=Active - 0 Read Volatile Status of configuration error signalDate 99V201 MMI,RST Recorded data1A YYYY-MM-DD - - Read Retain Recording dateTime 99V202 MMI,RST Recorded data1A hh:mm:ss.mss - - Read Retain Recording timeCurrent IL1 99V203 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Phase current IL1Current IL2 99V204 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Phase current IL2Current IL3 99V205 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Phase current IL3Current IL1b 99V206 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Phase current IL1bCurrent IL2b 99V207 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Phase current IL2bCurrent IL3b 99V208 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Phase current IL3bCurrent Id1 99V209 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Differential current of phase 1Current Id2 99V210 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Differential current of phase 2Current Id3 99V211 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Differential current of phase 3Current Ib1 99V212 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Bias current of phase 1Current Ib2 99V213 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Bias current of phase 2Current Ib3 99V214 MMI,RST Recorded data1A 0.00...60.00 x In 0 Read Retain Bias current of phase 3Angle IL1-IL2 99V215 MMI,RST Recorded data1B -180...180 ° 0 Read Retain Phase difference of the currents L1 and L2Angle IL2-IL3 99V216 MMI,RST Recorded data1B -180...180 ° 0 Read Retain Phase difference of the currents L2 and L3Angle IL3-IL1 99V217 MMI,RST Recorded data1B -180...180 ° 0 Read Retain Phase difference of the currents L3 and L1

Page 109 of 158

Page 110: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Angle IL1b-IL2b 99V218 MMI,RST Recorded data1B -180...180 ° 0 Read Retain Phase difference of the currents L1b and L2bAngle IL2b-IL3b 99V219 MMI,RST Recorded data1B -180...180 ° 0 Read Retain Phase difference of the currents L2b and L3bAngle IL3b-IL1b 99V220 MMI,RST Recorded data1B -180...180 ° 0 Read Retain Phase difference of the currents L3b and L1bAngle IL1-IL1b 99V221 MMI,RST Recorded data1B -180...180 ° 0 Read Retain Phase difference of the currents L1 and L1bAngle IL2-IL2b 99V222 MMI,RST Recorded data1B -180...180 ° 0 Read Retain Phase difference of the currents L2 and L2bAngle IL3-IL3b 99V223 MMI,RST Recorded data1B -180...180 ° 0 Read Retain Phase difference of the currents L3 and L3bBS1 99V224 MMI,RST Recorded data1B 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 99V225 MMI,RST Recorded data1B 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 99V226 MMI,RST Recorded data1B 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupReg. reason 99V227 MMI,RST Recorded data1B 0..2[0 = TRIP >; 1 = TRIP >>; 2 = TRIGG] - 0 Read Retain Reason for registration ( TRIP >, TRIP >> or TRIGG)Date 99V301 MMI,RST Recorded data2A YYYY-MM-DD - - Read Retain Recording dateTime 99V302 MMI,RST Recorded data2A hh:mm:ss.mss - - Read Retain Recording timeCurrent IL1 99V303 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Phase current IL1Current IL2 99V304 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Phase current IL2Current IL3 99V305 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Phase current IL3Current IL1b 99V306 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Phase current IL1bCurrent IL2b 99V307 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Phase current IL2bCurrent IL3b 99V308 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Phase current IL3bCurrent Id1 99V309 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Differential current of phase 1Current Id2 99V310 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Differential current of phase 2Current Id3 99V311 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Differential current of phase 3Current Ib1 99V312 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Bias current of phase 1Current Ib2 99V313 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Bias current of phase 2Current Ib3 99V314 MMI,RST Recorded data2A 0.00...60.00 x In 0 Read Retain Bias current of phase 3Angle IL1-IL2 99V315 MMI,RST Recorded data2B -180...180 ° 0 Read Retain Phase difference of the currents L1 and L2Angle IL2-IL3 99V316 MMI,RST Recorded data2B -180...180 ° 0 Read Retain Phase difference of the currents L2 and L3Angle IL3-IL1 99V317 MMI,RST Recorded data2B -180...180 ° 0 Read Retain Phase difference of the currents L3 and L1Angle IL1b-IL2b 99V318 MMI,RST Recorded data2B -180...180 ° 0 Read Retain Phase difference of the currents L1b and L2bAngle IL2b-IL3b 99V319 MMI,RST Recorded data2B -180...180 ° 0 Read Retain Phase difference of the currents L2b and L3bAngle IL3b-IL1b 99V320 MMI,RST Recorded data2B -180...180 ° 0 Read Retain Phase difference of the currents L3b and L1bAngle IL1-IL1b 99V321 MMI,RST Recorded data2B -180...180 ° 0 Read Retain Phase difference of the currents L1 and L1bAngle IL2-IL2b 99V322 MMI,RST Recorded data2B -180...180 ° 0 Read Retain Phase difference of the currents L2 and L2bAngle IL3-IL3b 99V323 MMI,RST Recorded data2B -180...180 ° 0 Read Retain Phase difference of the currents L3 and L3bBS1 99V324 MMI,RST Recorded data2B 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 99V325 MMI,RST Recorded data2B 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 99V326 MMI,RST Recorded data2B 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupReg. reason 99V327 MMI,RST Recorded data2B 0..2[0 = TRIP >; 1 = TRIP >>; 2 = TRIGG] - 0 Read Retain Reason for registration ( TRIP >, TRIP >> or TRIGG)Date 99V401 MMI,RST Recorded data3A YYYY-MM-DD - - Read Retain Recording dateTime 99V402 MMI,RST Recorded data3A hh:mm:ss.mss - - Read Retain Recording timeCurrent IL1 99V403 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Phase current IL1Current IL2 99V404 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Phase current IL2Current IL3 99V405 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Phase current IL3Current IL1b 99V406 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Phase current IL1bCurrent IL2b 99V407 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Phase current IL2bCurrent IL3b 99V408 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Phase current IL3bCurrent Id1 99V409 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Differential current of phase 1Current Id2 99V410 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Differential current of phase 2Current Id3 99V411 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Differential current of phase 3Current Ib1 99V412 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Bias current of phase 1

Page 110 of 158

Page 111: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Current Ib2 99V413 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Bias current of phase 2Current Ib3 99V414 MMI,RST Recorded data3A 0.00...60.00 x In 0 Read Retain Bias current of phase 3Angle IL1-IL2 99V415 MMI,RST Recorded data3B -180...180 ° 0 Read Retain Phase difference of the currents L1 and L2Angle IL2-IL3 99V416 MMI,RST Recorded data3B -180...180 ° 0 Read Retain Phase difference of the currents L2 and L3Angle IL3-IL1 99V417 MMI,RST Recorded data3B -180...180 ° 0 Read Retain Phase difference of the currents L3 and L1Angle IL1b-IL2b 99V418 MMI,RST Recorded data3B -180...180 ° 0 Read Retain Phase difference of the currents L1b and L2bAngle IL2b-IL3b 99V419 MMI,RST Recorded data3B -180...180 ° 0 Read Retain Phase difference of the currents L2b and L3bAngle IL3b-IL1b 99V420 MMI,RST Recorded data3B -180...180 ° 0 Read Retain Phase difference of the currents L3b and L1bAngle IL1-IL1b 99V421 MMI,RST Recorded data3B -180...180 ° 0 Read Retain Phase difference of the currents L1 and L1bAngle IL2-IL2b 99V422 MMI,RST Recorded data3B -180...180 ° 0 Read Retain Phase difference of the currents L2 and L2bAngle IL3-IL3b 99V423 MMI,RST Recorded data3B -180...180 ° 0 Read Retain Phase difference of the currents L3 and L3bBS1 99V424 MMI,RST Recorded data3B 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS1 inputBS2 99V425 MMI,RST Recorded data3B 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BS2 inputActive group 99V426 MMI,RST Recorded data3B 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupReg. reason 99V427 MMI,RST Recorded data3B 0..2[0 = TRIP >; 1 = TRIP >>; 2 = TRIGG] - 0 Read Retain Reason for registration ( TRIP >, TRIP >> or TRIGG)

100100 / Rev B Diff3Basic setting 100S1 MMI,RST Actual setting 0.5...50.0 % 0,5 Read Volatile Lowest ratio of differential and nominal current to cause a

tripOperate time 100S2 MMI,RST Actual setting 0.03...0.50 s 0,03 Read Volatile Operate timeBasic setting 100S41 MMI,RST Setting group1 0.5...50.0 % 0,5 Rd/Wr Retain Lowest ratio of differential and nominal current to cause a

tripOperate time 100S42 MMI,RST Setting group1 0.03...0.50 s 0,03 Rd/Wr Retain Operate timeBasic setting 100S71 MMI,RST Setting group2 0.5...50.0 % 0,5 Rd/Wr Retain Lowest ratio of differential and nominal current to cause a

tripOperate time 100S72 MMI,RST Setting group2 0.03...0.50 s 0,03 Rd/Wr Retain Operate timeOperation mode 100V1 MMI,RST Control setting 0..2[0 = Not in use; 1 = Definite time; 2 = Instantaneous] - 2 Rd/Wr Retain Selection of operation modeGroup selection 100V2 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 100V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupTrip signal 100V4 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 100V5 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 100V6 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPStart pulse 100V7 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalReset registers 100V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 100V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 100V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 100V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 100V101 MMI,RST Control setting 0...1023 - 783 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 100V103 MMI,RST Control setting 0...1023 - 783 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 100V105 MMI,RST Control setting 0...1023 - 783 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 100V107 MMI,RST Control setting 0...1023 - 783 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Current Id1 100I1 MMI,RST Input data 0.000...60.000 x In 0 Read Volatile Differential current of phase L1Current Id2 100I2 MMI,RST Input data 0.000...60.000 x In 0 Read Volatile Differential current of phase L2Current Id3 100I3 MMI,RST Input data 0.000...60.000 x In 0 Read Volatile Differential current of phase L3Input BLOCK 100I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of block signalInput GROUP 100I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of signal for switching between group 1 and 2Input RESET 100I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of signal for resetting output signals of Diff3Output TRIP 100O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput ERR 100O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of configuration error signalOutput START 100O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signal

Page 111 of 158

Page 112: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Date 100V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 100V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeCurrent Id1 100V203 MMI,RST Recorded data1 0.000...60.000 x In 0 Read Retain Differential current of phase L1Current Id2 100V204 MMI,RST Recorded data1 0.000...60.000 x In 0 Read Retain Differential current of phase L2Current Id3 100V205 MMI,RST Recorded data1 0.000...60.000 x In 0 Read Retain Differential current of phase L3Active group 100V206 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDuration 100V207 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationDate 100V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 100V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeCurrent Id1 100V303 MMI,RST Recorded data2 0.000...60.000 x In 0 Read Retain Differential current of phase L1Current Id2 100V304 MMI,RST Recorded data2 0.000...60.000 x In 0 Read Retain Differential current of phase L2Current Id3 100V305 MMI,RST Recorded data2 0.000...60.000 x In 0 Read Retain Differential current of phase L3Active group 100V306 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDuration 100V307 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationDate 100V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 100V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeCurrent Id1 100V403 MMI,RST Recorded data3 0.000...60.000 x In 0 Read Retain Differential current of phase L1Current Id2 100V404 MMI,RST Recorded data3 0.000...60.000 x In 0 Read Retain Differential current of phase L2Current Id3 100V405 MMI,RST Recorded data3 0.000...60.000 x In 0 Read Retain Differential current of phase L3Active group 100V406 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDuration 100V407 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situation

100102 / Rev B REF1ABasic setting 102S1 MMI,RST Actual setting 0.5...50 % 0,5 Read Volatile Lowest ratio of differential and nominal current to cause a

tripBasic setting 102S41 MMI,RST Setting group1 0.5...50 % 0,5 Rd/Wr Retain Lowest ratio of differential and nominal current to cause a

tripBasic setting 102S71 MMI,RST Setting group2 0.5...50 % 0,5 Rd/Wr Retain Lowest ratio of differential and nominal current to cause a

tripREF1A 102V1 MMI,RST Control setting 0..1[0 = Not in use; 1 = In use] - 1 Rd/Wr Retain Protection block in use or not in useGroup selection 102V2 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 102V3 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupTrip signal 102V4 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 102V5 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 102V6 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 102V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest TRIP 102V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 102V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 102V101 MMI,RST Control setting 0...255 - 15 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E7)Event mask 2 102V103 MMI,RST Control setting 0...255 - 15 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E7)Event mask 3 102V105 MMI,RST Control setting 0...255 - 15 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E7)Event mask 4 102V107 MMI,RST Control setting 0...255 - 15 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E7)Current Ido 102I1 MMI,RST Input data 0.000...60.000 x In 0 Read Volatile Neutral differential currentInput BLOCK 102I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of block signalInput GROUP 102I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of signal for switching between group 1 and 2Input RESET 102I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of signal for resetting output signals of REF1AOutput TRIP 102O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput ERR 102O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of configuration error signalDate 102V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 102V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording time

Page 112 of 158

Page 113: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Current Ido 102V203 MMI,RST Recorded data1 0.000...60.000 x In 0 Read Retain Neutral differential currentActive group 102V204 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 102V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 102V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeCurrent Ido 102V303 MMI,RST Recorded data2 0.000...60.000 x In 0 Read Retain Neutral differential currentActive group 102V304 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 102V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 102V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeCurrent Ido 102V403 MMI,RST Recorded data3 0.000...60.000 x In 0 Read Retain Neutral differential currentActive group 102V404 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100107 / Rev C VOC6HighOperation mode 107S1 MMI,RST Actual setting 0..7[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.;6 = RI-type inverse; 7 = RD-type inverse]

- 1 Read Volatile Selection of operation mode and inverse time characteristic

Start current 107S2 MMI,RST Actual setting 0.10...5.00 x In 0,1 Read Volatile Start currentOperate time 107S3 MMI,RST Actual setting 0.05...300.00 s 0,05 Read Volatile Operate time at DTmodeTime multiplier 107S4 MMI,RST Actual setting 0.05...1.00 - 0,05 Read Volatile Time multiplier at IDMT modeControl mode 107S5 MMI,RST Actual setting 0..2[0 = Voltage step; 1 = Voltage slope; 2 = Input step] - 0 Read Volatile Selection of mode for voltage controlVoltage limit 107S6 MMI,RST Actual setting 0.10...1.00 x Un 0,1 Read Volatile Voltage setting value for Voltage step modeVoltage limit 1 107S7 MMI,RST Actual setting 0.60...1.00 x Un 0,6 Read Volatile Upper voltage setting value for Voltage slope modeVoltage limit 2 107S8 MMI,RST Actual setting 0.10...0.59 x Un 0,1 Read Volatile Lower voltage setting value for Voltage slope modeCurr.multiplier 107S9 MMI,RST Actual setting 0.05...1.00 - 0,05 Read Volatile Multiplier for lower Start current valueOperation mode 107S41 MMI,RST Setting group1 0..7[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.;6 = RI-type inverse; 7 = RD-type inverse]

- 1 Rd/Wr Retain Selection of operate mode and inverse time characteristic

Start current 107S42 MMI,RST Setting group1 0.10...5.00 x In 0,1 Rd/Wr Retain Start currentOperate time 107S43 MMI,RST Setting group1 0.05...100.00 s 0,05 Rd/Wr Retain Operate time at DTmodeTime multiplier 107S44 MMI,RST Setting group1 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeControl mode 107S45 MMI,RST Setting group1 0..2[0 = Voltage step; 1 = Voltage slope; 2 = Input step] - 0 Rd/Wr Retain Selection of mode for voltage controlVoltage limit 107S46 MMI,RST Setting group1 0.10...1.00 x Un 0,1 Rd/Wr Retain Voltage setting value for Voltage step modeVoltage limit 1 107S47 MMI,RST Setting group1 0.60...1.00 x Un 0,6 Rd/Wr Retain Upper voltage setting value for Voltage slope modeVoltage limit 2 107S48 MMI,RST Setting group1 0.10...0.59 x Un 0,1 Rd/Wr Retain Lower voltage setting value for Voltage slope modeCurr.multiplier 107S49 MMI,RST Setting group1 0.05...1.00 - 0,05 Rd/Wr Retain Multiplier for lower Start current valueOperation mode 107S71 MMI,RST Setting group2 0..7[0 = Not in use; 1 = Definite time; 2 = Extremely inv.;

3 = Very inverse; 4 = Normal inverse; 5 = Long-time inv.;6 = RI-type inverse; 7 = RD-type inverse]

- 1 Rd/Wr Retain Selection of operate mode and inverse time characteristic

Start current 107S72 MMI,RST Setting group2 0.10...5.00 x In 0,1 Rd/Wr Retain Start currentOperate time 107S73 MMI,RST Setting group2 0.05...100.00 s 0,05 Rd/Wr Retain Operate time at DTmodeTime multiplier 107S74 MMI,RST Setting group2 0.05...1.00 - 0,05 Rd/Wr Retain Time multiplier at IDMT modeControl mode 107S75 MMI,RST Setting group2 0..2[0 = Voltage step; 1 = Voltage slope; 2 = Input step] - 0 Rd/Wr Retain Selection of mode for voltage controlVoltage limit 107S76 MMI,RST Setting group2 0.10...1.00 x Un 0,1 Rd/Wr Retain Voltage setting value for Voltage step modeVoltage limit 1 107S77 MMI,RST Setting group2 0.60...1.00 x Un 0,6 Rd/Wr Retain Upper voltage setting value for Voltage slope modeVoltage limit 2 107S78 MMI,RST Setting group2 0.10...0.59 x Un 0,1 Rd/Wr Retain Lower voltage setting value for Voltage slope modeCurr.multiplier 107S79 MMI,RST Setting group2 0.05...1.00 - 0,05 Rd/Wr Retain Multiplier for lower Start current valueMeasuring mode 107V1 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 0 Rd/Wr Retain Selection of measuring modeVoltage select. 107V2 MMI,RST Control setting 0..1[0 = Phase-to-phase; 1 = Phase-to-earth] - 0 Rd/Wr Retain Selection of phase-to-phase or phase-to-earth voltagesDrop-off time 107V3 MMI,RST Control setting 0.00...10.00 s 0 Rd/Wr Retain Resetting time of the operate time counter at DT and

IDMT modeGroup selection 107V4 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting group

Page 113 of 158

Page 114: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Active group 107V5 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 107V6 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 107V7 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 107V8 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPMinimum time 107V9 MMI,RST Control setting 0.03...10.00 s 0,03 Rd/Wr Retain Minimum operate time at IDMT modeCBFP time 107V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 107V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 107V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 107V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 107V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 107V101 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 107V103 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 107V105 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 107V107 MMI,RST Control setting 0...1023 - 63 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Current IL1 107I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Channel measuring phase current IL1Current IL2 107I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Channel measuring phase current IL2Current IL3 107I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Channel measuring phase current IL3Voltage U12 107I4 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Channel measuring voltage U12Voltage U23 107I5 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Channel measuring voltage U23Voltage U31 107I6 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Channel measuring voltage U31Input BLOCK 107I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Blocking signalInput GROUP 107I8 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Control input for switching between setting group 1 and

setting group 2. When GROUP is TRUE (logic 1), group 2 is active.

Input DOUBLE 107I9 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input signal used for doubling the set start current value temporarily at magnetizing inrush or start-up situation

Input CONTROL 107I10 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input signal used for lower current setting in Input Step Control mode

Input RESET 107I11 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input signal for resetting the trip signal and registers of VOC6High

Output START 107O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 107O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput ERR 107O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of ERR signalDate 107V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 107V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 107V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 107V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 107V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 107V206 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 107V207 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 107V208 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 107V209 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 107V210 MMI,RST Recorded data1 0.0...2.0 x Un 0 Read Retain Filtered value of U12Voltage U23 107V211 MMI,RST Recorded data1 0.0...2.0 x Un 0 Read Retain Filtered value of U23Voltage U31 107V212 MMI,RST Recorded data1 0.0...2.0 x Un 0 Read Retain Filtered value of U31BLOCK 107V213 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputDOUBLE 107V214 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 107V215 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 107V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording date

Page 114 of 158

Page 115: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Time 107V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 107V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 107V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 107V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 107V306 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 107V307 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 107V308 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 107V309 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 107V310 MMI,RST Recorded data2 0.0...2.0 x Un 0 Read Retain Filtered value of U12Voltage U23 107V311 MMI,RST Recorded data2 0.0...2.0 x Un 0 Read Retain Filtered value of U23Voltage U31 107V312 MMI,RST Recorded data2 0.0...2.0 x Un 0 Read Retain Filtered value of U31BLOCK 107V313 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputDOUBLE 107V314 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 107V315 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 107V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 107V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 107V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationIL1 mean 107V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL1IL2 mean 107V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL2IL3 mean 107V406 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Filtered value of IL3IL1 peak 107V407 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL1IL2 peak 107V408 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL2IL3 peak 107V409 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Momentary peak of IL3Voltage U12 107V410 MMI,RST Recorded data3 0.0...2.0 x Un 0 Read Retain Filtered value of U12Voltage U23 107V411 MMI,RST Recorded data3 0.0...2.0 x Un 0 Read Retain Filtered value of U23Voltage U31 107V412 MMI,RST Recorded data3 0.0...2.0 x Un 0 Read Retain Filtered value of U31BLOCK 107V413 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputDOUBLE 107V414 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of DOUBLE inputActive group 107V415 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100110 / Rev D UI6LowZ-setting 110S1 MMI,RST Actual setting 0.01...60.00 p.u. 0,07 Read Volatile Start impedanceOperate time 110S2 MMI,RST Actual setting 0.04...300.00 s 0,2 Read Volatile Operate timeZ-setting 110S41 MMI,RST Setting group1 0.01...60.00 p.u. 0,07 Rd/Wr Retain Start impedanceOperate time 110S42 MMI,RST Setting group1 0.04...300.00 s 0,2 Rd/Wr Retain Operate timeZ-setting 110S71 MMI,RST Setting group2 0.01...60.00 p.u. 0,07 Rd/Wr Retain Start impedanceOperate time 110S72 MMI,RST Setting group2 0.04...300.00 s 0,2 Rd/Wr Retain Operate timeUI6Low 110V1 MMI,RST Control setting 0..1[0 = Not in use; 1 = In use] - 1 Rd/Wr Retain UI6Low in use or not in useMeas. signals 110V2 MMI,RST Control setting 0..11[0 = Not selected; 1 = 2-ph, ph-e 1&2; 2 = 2-ph, ph-

e 2&3; 3 = 2-ph, ph-e 3&1; 4 = 3-ph, ph-e; 5 = 2-ph, ph-ph 1&2; 6 = 2-ph, ph-ph 2&3; 7 = 2-ph, ph-ph 3&1;

- 11 Rd/Wr Retain Selection of the measuring signal conbination

Measuring mode 110V3 MMI,RST Control setting 0..1[0 = Peak-to-peak; 1 = Fundam.freq.] - 1 Rd/Wr Retain Selection of measuring mode (peak-to-peak or fund.freq.)Drop-off time 110V4 MMI,RST Control setting 0.00...10.00 s 1 Rd/Wr Retain Drop-off timeGroup selection 110V5 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 110V6 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 110V7 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 110V8 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 110V9 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 110V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 110V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registers

Page 115 of 158

Page 116: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Test START 110V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 110V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 110V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 110V101 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9, E11)Event mask 2 110V103 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9, E11)Event mask 3 110V105 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9, E11)Event mask 4 110V107 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9, E11)Impedance Z1 110I1 MMI,RST Input data 0.00...99999.99 p.u. 99999,99 Read Volatile Phase impedance Z1Impedance Z2 110I2 MMI,RST Input data 0.00...99999.99 p.u. 99999,99 Read Volatile Phase impedance Z2Impedance Z3 110I3 MMI,RST Input data 0.00...99999.99 p.u. 99999,99 Read Volatile Phase impedance Z3Input BLOCK 110I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile External block signalInput GROUP 110I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input DOUBLE 110I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input signal used for reducing the Z-setting value by factor

0.5 temporarilyInput RESET 110I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of UI6LowOutput START 110O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 110O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput ERR 110O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of error signalDate 110V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 110V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 110V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationZ1 110V204 MMI,RST Recorded data1 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 1Z2 110V205 MMI,RST Recorded data1 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 2Z3 110V206 MMI,RST Recorded data1 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 3BLOCK 110V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 110V208 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 110V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 110V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 110V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationZ1 110V304 MMI,RST Recorded data2 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 1Z2 110V305 MMI,RST Recorded data2 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 2Z3 110V306 MMI,RST Recorded data2 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 3BLOCK 110V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 110V308 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 110V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 110V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeDuration 110V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationZ1 110V404 MMI,RST Recorded data3 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 1Z2 110V405 MMI,RST Recorded data3 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 2Z3 110V406 MMI,RST Recorded data3 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 3BLOCK 110V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 110V408 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100111 / Rev D UI6HighZ-setting 111S1 MMI,RST Actual setting 0.01...60.00 p.u. 0,04 Read Volatile Start impedanceOperate time 111S2 MMI,RST Actual setting 0.04...300.00 s 0,1 Read Volatile Operate timeZ-setting 111S41 MMI,RST Setting group1 0.01...60.00 p.u. 0,04 Rd/Wr Retain Start impedanceOperate time 111S42 MMI,RST Setting group1 0.04...300.00 s 0,1 Rd/Wr Retain Operate timeZ-setting 111S71 MMI,RST Setting group2 0.01...60.00 p.u. 0,04 Rd/Wr Retain Start impedanceOperate time 111S72 MMI,RST Setting group2 0.04...300.00 s 0,1 Rd/Wr Retain Operate time

Page 116 of 158

Page 117: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

UI6High 111V1 MMI,RST Control setting 0..1[0 = Not in use; 1 = In use] - 1 Rd/Wr Retain UI6High in use or not in useMeas. signals 111V2 MMI,RST Control setting 0..11[0 = Not selected; 1 = 2-ph, ph-e 1&2; 2 = 2-ph, ph-

e 2&3; 3 = 2-ph, ph-e 3&1; 4 = 3-ph, ph-e; 5 = 2-ph, ph-ph 1&2; 6 = 2-ph, ph-ph 2&3; 7 = 2-ph, ph-ph 3&1;

- 11 Rd/Wr Retain Selection of the measuring signal conbination

Measuring mode 111V3 MMI,RST Control setting MEASMODE_1 - 1 Rd/Wr Retain Selection of measuring mode (peak-to-peak or fund.freq.)Drop-off time 111V4 MMI,RST Control setting 0.00...10.00 s 1 Rd/Wr Retain Drop-off timeGroup selection 111V5 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 111V6 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupStart pulse 111V7 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 111V8 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 111V9 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIP and CBFPCBFP time 111V10 MMI,RST Control setting 100...1000 ms 100 Rd/Wr Retain Operate time of the delayed trip CBFPReset registers 111V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 111V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of STARTTest TRIP 111V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of TRIPTest CBFP 111V33 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of CBFPEvent mask 1 111V101 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9, E11)Event mask 2 111V103 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9, E11)Event mask 3 111V105 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9, E11)Event mask 4 111V107 MMI,RST Control setting 0...3071 - 2111 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9, E11)Impedance Z1 111I1 MMI,RST Input data 0.00...99999.99 p.u. 99999,99 Read Volatile Phase impedance Z1Impedance Z2 111I2 MMI,RST Input data 0.00...99999.99 p.u. 99999,99 Read Volatile Phase impedance Z2Impedance Z3 111I3 MMI,RST Input data 0.00...99999.99 p.u. 99999,99 Read Volatile Phase impedance Z3Input BLOCK 111I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile External block signalInput GROUP 111I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input DOUBLE 111I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input signal used for reducing the Z-setting value by factor

0.5 temporarilyInput RESET 111I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of UI6HighOutput START 111O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 111O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput ERR 111O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of error signalDate 111V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 111V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration 111V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situationZ1 111V204 MMI,RST Recorded data1 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 1Z2 111V205 MMI,RST Recorded data1 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 2Z3 111V206 MMI,RST Recorded data1 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 3BLOCK 111V207 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 111V208 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 111V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 111V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration 111V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situationZ1 111V304 MMI,RST Recorded data2 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 1Z2 111V305 MMI,RST Recorded data2 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 2Z3 111V306 MMI,RST Recorded data2 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 3BLOCK 111V307 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 111V308 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 111V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 111V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording time

Page 117 of 158

Page 118: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Duration 111V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situationZ1 111V404 MMI,RST Recorded data3 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 1Z2 111V405 MMI,RST Recorded data3 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 2Z3 111V406 MMI,RST Recorded data3 0.00...99999.99 p.u. 0 Read Retain Calculated impedance 3BLOCK 111V407 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 111V408 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100112 / Rev C PSV3St1Operation mode 112S1 MMI,RST Actual setting 0..7[0 = Not in use; 1 = U1< & U2> & U1>; 2 = U1< &

U2>; 3 = U2> & U1>; 4 = U1< & U1>; 5 = U2>; 6 = U1<; 7 = U1>]

- 1 Read Volatile Selection of operation mode

Start value U2> 112S2 MMI,RST Actual setting 0.01...1.00 x Un 0,03 Read Volatile Start voltage of negative phase sequence overvoltage operation

Start value U1< 112S3 MMI,RST Actual setting 0.01...1.20 x Un 0,9 Read Volatile Start voltage of positive phase sequence undervoltage operation

Start value U1> 112S4 MMI,RST Actual setting 0.80...1.60 x Un 1,1 Read Volatile Start voltage of positive phase sequence overvoltage operation

Operate time U2> 112S5 MMI,RST Actual setting 0.04...60.00 s 0,04 Read Volatile Operate time of negative phase sequence overvoltage operation

Operate time U1< 112S6 MMI,RST Actual setting 0.04...60.00 s 0,04 Read Volatile Operate time of positive phase sequence undervoltage operation

Operate time U1> 112S7 MMI,RST Actual setting 0.04...60.00 s 0,04 Read Volatile Operate time of positive phase sequence overvoltage operation

Operation mode 112S41 MMI,RST Setting group1 0..7[0 = Not in use; 1 = U1< & U2> & U1>; 2 = U1< & U2>; 3 = U2> & U1>; 4 = U1< & U1>; 5 = U2>; 6 = U1<; 7 = U1>]

- 1 Rd/Wr Retain Selection of operation mode

Start value U2> 112S42 MMI,RST Setting group1 0.01...1.00 x Un 0,03 Rd/Wr Retain Start voltage of negative phase sequence overvoltage operation

Start value U1< 112S43 MMI,RST Setting group1 0.01...1.20 x Un 0,9 Rd/Wr Retain Start voltage of positive phase sequence undervoltage operation

Start value U1> 112S44 MMI,RST Setting group1 0.80...1.60 x Un 1,1 Rd/Wr Retain Start voltage of positive phase sequence overvoltage operation

Operate time U2> 112S45 MMI,RST Setting group1 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of negative phase sequence overvoltage operation

Operate time U1< 112S46 MMI,RST Setting group1 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of positive phase sequence undervoltage operation

Operate time U1> 112S47 MMI,RST Setting group1 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of positive phase sequence overvoltage operation

Operation mode 112S71 MMI,RST Setting group2 0..7[0 = Not in use; 1 = U1< & U2> & U1>; 2 = U1< & U2>; 3 = U2> & U1>; 4 = U1< & U1>; 5 = U2>; 6 = U1<; 7 = U1>]

- 1 Rd/Wr Retain Selection of operation mode

Start value U2> 112S72 MMI,RST Setting group2 0.01...1.00 x Un 0,03 Rd/Wr Retain Start voltage of negative phase sequence overvoltage operation

Start value U1< 112S73 MMI,RST Setting group2 0.01...1.20 x Un 0,9 Rd/Wr Retain Start voltage of positive phase sequence undervoltage operation

Start value U1> 112S74 MMI,RST Setting group2 0.80...1.60 x Un 1,1 Rd/Wr Retain Start voltage of positive phase sequence overvoltage operation

Operate time U2> 112S75 MMI,RST Setting group2 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of negative phase sequence overvoltage operation

Page 118 of 158

Page 119: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Operate time U1< 112S76 MMI,RST Setting group2 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of positive phase sequence undervoltage operation

Operate time U1> 112S77 MMI,RST Setting group2 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of positive phase sequence overvoltage operation

Group selection 112V1 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 112V2 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupDir. selection 112V3 MMI,RST Control setting 0..2[0 = Forward; 1 = Reverse; 2 = Input ROT_DIR] - 0 Rd/Wr Retain Selection of rotation directionRotation dir. 112V4 MMI,RST Control setting 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Rotation directionStart pulse 112V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 112V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 112V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIPIntern. blocking 112V8 MMI,RST Control setting 0..1[0 = Disabled; 1 = Enabled] - 1 Rd/Wr Retain Enabling of internal positive phase sequence undervoltage

blockingReset registers 112V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 112V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Retain Testing of STARTTest TRIP 112V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Retain Testing of TRIPEvent mask 1 112V101 MMI,RST Control setting 0...196607 - 135167 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E15, E17)Event mask 2 112V103 MMI,RST Control setting 0...196607 - 135167 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E15, E17)Event mask 3 112V105 MMI,RST Control setting 0...196607 - 135167 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E15, E17)Event mask 4 112V107 MMI,RST Control setting 0...196607 - 135167 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E15, E17)Pos. seq. volt. 112I1 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Positive phase sequence voltageNeg. seq. volt. 112I2 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Negative phase sequence voltageInput ROT_DIR 112I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between forward and reverse rotationInput BLOCK 112I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input for blocking he functionInput GROUP 112I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 112I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of Output START 112O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 112O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput ERR 112O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of error output signalDate 112V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 112V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration U2> 112V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situation of U2> stageDuration U1< 112V204 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situation of U1< stageDuration U1> 112V205 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situation of U1> stagePos. seq. volt. 112V206 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Positive sequence voltageNeg. seq. volt. 112V207 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Negative sequence voltageBLOCK 112V208 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 112V209 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 112V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 112V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration U2> 112V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situation of U2> stageDuration U1< 112V304 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situation of U1< stageDuration U1> 112V305 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situation of U1> stagePos. seq. volt. 112V306 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Positive sequence voltageNeg. seq. volt. 112V307 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Negative sequence voltageBLOCK 112V308 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 112V309 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 112V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 112V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording time

Page 119 of 158

Page 120: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Duration U2> 112V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situation of U2> stageDuration U1< 112V404 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situation of U1< stageDuration U1> 112V405 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situation of U1> stagePos. seq. volt. 112V406 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Positive sequence voltageNeg. seq. volt. 112V407 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Negative sequence voltageBLOCK 112V408 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 112V409 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100113 / Rev C PSV3St2Operation mode 113S1 MMI,RST Actual setting 0..7[0 = Not in use; 1 = U1< & U2> & U1>; 2 = U1< &

U2>; 3 = U2> & U1>; 4 = U1< & U1>; 5 = U2>; 6 = U1<; 7 = U1>]

- 1 Read Volatile Selection of operation mode

Start value U2> 113S2 MMI,RST Actual setting 0.01...1.00 x Un 0,03 Read Volatile Start voltage of negative phase sequence overvoltage operation

Start value U1< 113S3 MMI,RST Actual setting 0.01...1.20 x Un 0,9 Read Volatile Start voltage of positive phase sequence undervoltage operation

Start value U1> 113S4 MMI,RST Actual setting 0.80...1.60 x Un 1,1 Read Volatile Start voltage of positive phase sequence overvoltage operation

Operate time U2> 113S5 MMI,RST Actual setting 0.04...60.00 s 0,04 Read Volatile Operate time of negative phase sequence overvoltage operation

Operate time U1< 113S6 MMI,RST Actual setting 0.04...60.00 s 0,04 Read Volatile Operate time of positive phase sequence undervoltage operation

Operate time U1> 113S7 MMI,RST Actual setting 0.04...60.00 s 0,04 Read Volatile Operate time of positive phase sequence overvoltage operation

Operation mode 113S41 MMI,RST Setting group1 0..7[0 = Not in use; 1 = U1< & U2> & U1>; 2 = U1< & U2>; 3 = U2> & U1>; 4 = U1< & U1>; 5 = U2>; 6 = U1<; 7 = U1>]

- 1 Rd/Wr Retain Selection of operation mode

Start value U2> 113S42 MMI,RST Setting group1 0.01...1.00 x Un 0,03 Rd/Wr Retain Start voltage of negative phase sequence overvoltage operation

Start value U1< 113S43 MMI,RST Setting group1 0.01...1.20 x Un 0,9 Rd/Wr Retain Start voltage of positive phase sequence undervoltage operation

Start value U1> 113S44 MMI,RST Setting group1 0.80...1.60 x Un 1,1 Rd/Wr Retain Start voltage of positive phase sequence overvoltage operation

Operate time U2> 113S45 MMI,RST Setting group1 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of negative phase sequence overvoltage operation

Operate time U1< 113S46 MMI,RST Setting group1 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of positive phase sequence undervoltage operation

Operate time U1> 113S47 MMI,RST Setting group1 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of positive phase sequence overvoltage operation

Operation mode 113S71 MMI,RST Setting group2 0..7[0 = Not in use; 1 = U1< & U2> & U1>; 2 = U1< & U2>; 3 = U2> & U1>; 4 = U1< & U1>; 5 = U2>; 6 = U1<; 7 = U1>]

- 1 Rd/Wr Retain Selection of operation mode

Start value U2> 113S72 MMI,RST Setting group2 0.01...1.00 x Un 0,03 Rd/Wr Retain Start voltage of negative phase sequence overvoltage operation

Start value U1< 113S73 MMI,RST Setting group2 0.01...1.20 x Un 0,9 Rd/Wr Retain Start voltage of positive phase sequence undervoltage operation

Start value U1> 113S74 MMI,RST Setting group2 0.80...1.60 x Un 1,1 Rd/Wr Retain Start voltage of positive phase sequence overvoltage operation

Operate time U2> 113S75 MMI,RST Setting group2 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of negative phase sequence overvoltage operation

Page 120 of 158

Page 121: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Operate time U1< 113S76 MMI,RST Setting group2 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of positive phase sequence undervoltage operation

Operate time U1> 113S77 MMI,RST Setting group2 0.04...60.00 s 0,04 Rd/Wr Retain Operate time of positive phase sequence overvoltage operation

Group selection 113V1 MMI,RST Control setting 0..2[0 = Group 1; 1 = Group 2; 2 = GROUP input] - 0 Rd/Wr Retain Selection of the active setting groupActive group 113V2 MMI,RST Control setting 0..1[0 = Group 1; 1 = Group 2] - 0 Read Volatile Active setting groupDir. selection 113V3 MMI,RST Control setting 0..2[0 = Forward; 1 = Reverse; 2 = Input ROT_DIR] - 0 Rd/Wr Retain Selection of rotation directionRotation dir. 113V4 MMI,RST Control setting 0..1[0 = Forward; 1 = Reverse] - 0 Read Volatile Rotation directionStart pulse 113V5 MMI,RST Control setting 0...1000 ms 0 Rd/Wr Retain Minimum pulse length of START signalTrip signal 113V6 MMI,RST Control setting 0..1[0 = Non-latching; 1 = Latching] - 0 Rd/Wr Retain Selection of self-holding for TRIP outputTrip pulse 113V7 MMI,RST Control setting 40...1000 ms 40 Rd/Wr Retain Minimum pulse length of TRIPIntern. blocking 113V8 MMI,RST Control setting 0..1[0 = Disabled; 1 = Enabled] - 1 Rd/Wr Retain Enabling of internal positive phase sequence undervoltage

blockingReset registers 113V13 RST Control setting 0..1[0 = 0; 1 = Reset] - 0 Write Volatile Resetting of latched trip signal and registersTest START 113V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Retain Testing of STARTTest TRIP 113V32 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Retain Testing of TRIPEvent mask 1 113V101 MMI,RST Control setting 0...196607 - 135167 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E15, E17)Event mask 2 113V103 MMI,RST Control setting 0...196607 - 135167 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E15, E17)Event mask 3 113V105 MMI,RST Control setting 0...196607 - 135167 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E15, E17)Event mask 4 113V107 MMI,RST Control setting 0...196607 - 135167 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E15, E17)Pos. seq. volt. 113I1 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Positive phase sequence voltageNeg. seq. volt. 113I2 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Negative phase sequence voltageInput ROT_DIR 113I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between forward and reverse rotationInput BLOCK 113I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input for blocking he functionInput GROUP 113I5 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for switching between group 1 and 2Input RESET 113I6 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting output signals and registers of Output START 113O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of start signalOutput TRIP 113O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of trip signalOutput ERR 113O3 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of error output signalDate 113V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 113V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeDuration U2> 113V203 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situation of U2> stageDuration U1< 113V204 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situation of U1< stageDuration U1> 113V205 MMI,RST Recorded data1 0.0...100.0 % 0 Read Retain Duration of start situation of U1> stagePos. seq. volt. 113V206 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Positive sequence voltageNeg. seq. volt. 113V207 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Negative sequence voltageBLOCK 113V208 MMI,RST Recorded data1 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 113V209 MMI,RST Recorded data1 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 113V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 113V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeDuration U2> 113V303 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situation of U2> stageDuration U1< 113V304 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situation of U1< stageDuration U1> 113V305 MMI,RST Recorded data2 0.0...100.0 % 0 Read Retain Duration of start situation of U1> stagePos. seq. volt. 113V306 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Positive sequence voltageNeg. seq. volt. 113V307 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Negative sequence voltageBLOCK 113V308 MMI,RST Recorded data2 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 113V309 MMI,RST Recorded data2 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting groupDate 113V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 113V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording time

Page 121 of 158

Page 122: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Duration U2> 113V403 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situation of U2> stageDuration U1< 113V404 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situation of U1< stageDuration U1> 113V405 MMI,RST Recorded data3 0.0...100.0 % 0 Read Retain Duration of start situation of U1> stagePos. seq. volt. 113V406 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Positive sequence voltageNeg. seq. volt. 113V407 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Negative sequence voltageBLOCK 113V408 MMI,RST Recorded data3 0..1[0 = Not active; 1 = Active] - 0 Read Retain Status of BLOCK inputActive group 113V409 MMI,RST Recorded data3 0..1[0 = Group 1; 1 = Group 2] - 0 Read Retain Active setting group

100118 / Rev C FuseFailRatio U2/U1 > 118S41 MMI,RST Settings 10...50 % 25 Rd/Wr Retain Minimum ratio of negative sequence voltage to positive

sequence voltage to allow blockingRatio I2/I1 < 118S42 MMI,RST Settings 10...50 % 20 Rd/Wr Retain Maximum ratio of negative sequence current to positive

sequence current to allow blockingFuseFail 118V1 MMI,RST Control setting 0..1[0 = Not in use; 1 = In use] - 0 Rd/Wr Retain Function block in use or not in useTest BSOUT 118V2 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - - Rd/Wr Volatile Testing BSOUTEvent mask 1 118V101 MMI,RST Control setting 0...1023 - 527 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E7 and E9)Event mask 2 118V103 MMI,RST Control setting 0...1023 - 527 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E7 and E9)Event mask 3 118V105 MMI,RST Control setting 0...1023 - 527 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E7 and E9)Event mask 4 118V107 MMI,RST Control setting 0...1023 - 527 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E7 and E9)Input BLOCK 118I1 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of signal for blocking the function blockInput MCB 118I2 MMI,RST Input data 0..1[0 = Open; 1 = Closed] - 1 Read Volatile Position of the miniature circuit breaker contactsOutput BSOUT 118O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of blocking signal for protection functionsOutput ERR 118O2 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of configuration error signal

100120 / Rev A COCB1Fixed pulse 120S1 MMI,RST Actual setting 0=Variable pulse;1=Fixed pulse - 0 Rd/Wr Retain Selection of fixed pulse lengthForced pulse 120S2 MMI,RST Actual setting 0=Single pulse;1=Forced pulse - 1 Rd/Wr Retain Execution of control command regardless the recent state

(repeated command)Event delay 120S3 MMI,RST Actual setting 0.000...60.000 s 0,2 Rd/Wr Retain Event delay for undefined stateOpen pulse 120S6 MMI,RST Actual setting 0.04...100.000 s 0,1 Rd/Wr Retain Opening time pulse lengthOpen alarm 120S7 MMI,RST Actual setting 0.00...100.000 s 0,1 Rd/Wr Retain Opening time alarm limitClose pulse 120S8 MMI,RST Actual setting 0.04...100.000 s 0,1 Rd/Wr Retain Closing time pulse lengthClose alarm 120S9 MMI,RST Actual setting 0.00...100.000 s 0,1 Rd/Wr Retain Closing time alarm limitInactive alarm 120S10 MMI,RST Actual setting 0...1825 days 1825 Rd/Wr Retain Inactive time alarm limitCycle alarm 120S11 MMI,RST Actual setting 0...10000 - 5000 Rd/Wr Retain Cycle count alarm limitOpen compens 120S12 MMI,RST Actual setting 0.000...0.020 s 0,007 Rd/Wr Retain Output relay delay compensation parameter for opening

time measurementsClose compens 120S13 MMI,RST Actual setting 0.000...0.020 s 0,007 Rd/Wr Retain Output relay delay compensation parameter for closing

time measurementsObject state 120V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined(00);3=Undefined

(11)- 0 Read Volatile 2-bit value of the object state

Interlock close 120V30 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Close command interlockingInterlock open 120V31 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Open command interlockingDirect open 120V4 Internal Control setting 1=Direct open - 0 Write Volatile Direct open commandDirect close 120V5 Internal Control setting 1=Direct close - 0 Write Volatile Direct close commandOpen select 120V6 Internal Control setting 1=Open select - 0 Write Volatile Open operation selection of the secured controlClose select 120V7 Internal Control setting 1=Close select - 0 Write Volatile Close operation selection of the secured controlCancel 120V10 Internal Control setting 1=Cancel - 0 Write Volatile Cancel of the secured commandExecute 120V11 Internal Control setting 1=Execute - 0 Write Volatile Execute of the secured commandCycle count 120V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueInactive time 120V13 MMI,RST Control setting 0...3650 days 0 Rd/Wr Retain Inactive time

Page 122 of 158

Page 123: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Alarm time 120V40 MMI,RST Control setting 0.00...23.59 - 8 Rd/Wr Retain Inactive time alarm time settingLast open 120V14 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last opening timeMax open 120V15 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum opening timeLast close 120V17 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last closing timeMax close 120V18 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum closing timeIV state 120V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalBlock state 120V35 MMI,RST Input data 0=Inactive;1=Active - 0 Read Volatile Object block signal stateSummarized stat 120V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV;

B4(16)=CLOSEENA; B5(32)=OPENENA; B8(256)=BLOCK; B9(512)=reserved

- 0 Read Volatile Summarized status of the object

Regist clear 120V98 MMI,RST Control setting 1=Clear - 0 Write Volatile Clear internal registrations (last and maximum)Alarm ack 120V99 MMI,RST Control setting 1=Acknowledge - 0 Write Volatile Acknowlege alarmsEvent mask 1 120V101 MMI,RST Control setting 0...536870911 - 145403647 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E28)Event mask 2 120V103 MMI,RST Control setting 0...536870911 - 145403647 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E28)Event mask 3 120V105 MMI,RST Control setting 0...536870911 - 145403647 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E28)Event mask 4 120V107 MMI,RST Control setting 0...536870911 - 145403647 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E28)Last change 120V41 Internal Control setting 0...2000000000 - 2000000000 Read Retain Object state change time (internally used)Open alarm 120O3 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Opening time alarm statusClose alarm 120O4 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Closing time alarm statusInactive alarm 120O5 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Inactive time alarm statusCycle alarm 120O6 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Cycle count alarm status

100121 / Rev A COCB2Fixed pulse 121S1 MMI,RST Actual setting 0=Variable pulse;1=Fixed pulse - 0 Rd/Wr Retain Selection of fixed pulse lengthForced pulse 121S2 MMI,RST Actual setting 0=Single pulse;1=Forced pulse - 1 Rd/Wr Retain Execution of control command regardless the recent state

(repeated command)Event delay 121S3 MMI,RST Actual setting 0.000...60.000 s 0,2 Rd/Wr Retain Event delay for undefined stateOpen pulse 121S6 MMI,RST Actual setting 0.04...100.000 s 0,1 Rd/Wr Retain Opening time pulse lengthOpen alarm 121S7 MMI,RST Actual setting 0.00...100.000 s 0,1 Rd/Wr Retain Opening time alarm limitClose pulse 121S8 MMI,RST Actual setting 0.04...100.000 s 0,1 Rd/Wr Retain Closing time pulse lengthClose alarm 121S9 MMI,RST Actual setting 0.00...100.000 s 0,1 Rd/Wr Retain Closing time alarm limitInactive alarm 121S10 MMI,RST Actual setting 0...1825 days 1825 Rd/Wr Retain Inactive time alarm limitCycle alarm 121S11 MMI,RST Actual setting 0...10000 - 5000 Rd/Wr Retain Cycle count alarm limitOpen compens 121S12 MMI,RST Actual setting 0.000...0.020 s 0,007 Rd/Wr Retain Output relay delay compensation parameter for opening

time measurementsClose compens 121S13 MMI,RST Actual setting 0.000...0.020 s 0,007 Rd/Wr Retain Output relay delay compensation parameter for closing

time measurementsObject state 121V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined(00);3=Undefined

(11)- 0 Read Volatile 2-bit value of the object state

Interlock close 121V30 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Close command interlockingInterlock open 121V31 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Open command interlockingDirect open 121V4 Internal Control setting 1=Direct open - 0 Write Volatile Direct open commandDirect close 121V5 Internal Control setting 1=Direct close - 0 Write Volatile Direct close commandOpen select 121V6 Internal Control setting 1=Open select - 0 Write Volatile Open operation selection of the secured controlClose select 121V7 Internal Control setting 1=Close select - 0 Write Volatile Close operation selection of the secured controlCancel 121V10 Internal Control setting 1=Cancel - 0 Write Volatile Cancel of the secured commandExecute 121V11 Internal Control setting 1=Execute - 0 Write Volatile Execute of the secured commandCycle count 121V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueInactive time 121V13 MMI,RST Control setting 0...3650 days 0 Rd/Wr Retain Inactive timeAlarm time 121V40 MMI,RST Control setting 0.00...23.59 - 8 Rd/Wr Retain Inactive time alarm time setting

Page 123 of 158

Page 124: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Last open 121V14 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last opening timeMax open 121V15 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum opening timeLast close 121V17 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last closing timeMax close 121V18 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum closing timeIV state 121V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalBlock state 121V35 MMI,RST Input data 0=Inactive;1=Active - 0 Read Volatile Object block signal stateSummarized stat 121V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV;

B4(16)=CLOSEENA; B5(32)=OPENENA; B8(256)=BLOCK; B9(512)=reserved

- 0 Read Volatile Summarized status of the object

Regist clear 121V98 MMI,RST Control setting 1=Clear - 0 Write Volatile Clear internal registrations (last and maximum)Alarm ack 121V99 MMI,RST Control setting 1=Acknowledge - 0 Write Volatile Acknowlege alarmsEvent mask 1 121V101 MMI,RST Control setting 0...536870911 - 145403647 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E28)Event mask 2 121V103 MMI,RST Control setting 0...536870911 - 145403647 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E28)Event mask 3 121V105 MMI,RST Control setting 0...536870911 - 145403647 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E28)Event mask 4 121V107 MMI,RST Control setting 0...536870911 - 145403647 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E28)Last change 121V41 Internal Control setting 0...2000000000 - 2000000000 Read Retain Object state change time (internally used)Open alarm 121O3 MMI,RST Output data 1=Forced pulse - 0 Read Volatile Opening time alarm statusClose alarm 121O4 MMI,RST Output data 1=Forced pulse - 0 Read Volatile Closing time alarm statusInactive alarm 121O5 MMI,RST Output data 1=Forced pulse - 0 Read Volatile Inactive time alarm statusCycle alarm 121O6 MMI,RST Output data 1=Forced pulse - 0 Read Volatile Cycle count alarm status

100122 / Rev A CODC1Fixed pulse 122S1 MMI,RST Actual setting 0=Variable pulse;1=Fixed pulse - 0 Rd/Wr Retain Selection of fixed pulse lengthForced pulse 122S2 MMI,RST Actual setting 0=Single pulse;1=Forced pulse - 1 Rd/Wr Retain Execution of control command regardless the recent state

(repeated command)Event delay 122S3 MMI,RST Actual setting 0.000...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateOpen pulse 122S6 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Opening time pulse lengthOpen alarm 122S7 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Opening time alarm limitClose pulse 122S8 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Closing time pulse lengthClose alarm 122S9 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Closing time alarm limitObject state 122V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(11);3=Undefine

d2(00)- 0 Read Volatile 2-bit state of the object

Interlock close 122V30 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Close command interlockingInterlock open 122V31 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Open command interlockingDirect open 122V4 Internal Control setting 1=Direct open - 0 Write Volatile Direct open commandDirect close 122V5 Internal Control setting 1=Direct close - 0 Write Volatile Direct close commandOpen select 122V6 Internal Control setting 1=Open select - 0 Write Volatile Open operation selection of the secured controlClose select 122V7 Internal Control setting 1=Close select - 0 Write Volatile Close operation selection of the secured controlCancel 122V10 Internal Control setting 1=Cancel - 0 Write Volatile Deselection of the secured controlExecute 122V11 Internal Control setting 1=Execute - 0 Write Volatile Execution of the secured controlCycle count 122V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueLast open 122V14 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last opening timeMax open 122V15 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum opening timeLast close 122V17 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last closing timeMax close 122V18 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum closing timeIV state 122V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalBlock state 122V35 MMI,RST Input data 0=Inactive;1=Active - 0 Read Volatile Object block signal stateSummarized stat 122V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV;

B4(16)=CLOSEENA; B5(32)=OPENENA; B8(256)=BLOCK; B9(512)=reserved

- 0 Read Volatile Summarized status of the object

Page 124 of 158

Page 125: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Regist clear 122V98 MMI,RST Control setting 1=Clear - 0 Write Volatile Clear internal registrations (last maximum)Alarm ack 122V99 MMI,RST Control setting 1=Acknowledge - 0 Write Volatile Acknowlege alarmEvent mask 1 122V101 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E28)Event mask 2 122V103 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E28)Event mask 3 122V105 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E28)Event mask 4 122V107 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E28)Open alarm 122O3 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Opening time alarm statusClose alarm 122O4 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Closing time alarm status

100123 / Rev A CODC2Fixed pulse 123S1 MMI,RST Actual setting 0=Variable pulse;1=Fixed pulse - 0 Rd/Wr Retain Selection of fixed pulse lengthForced pulse 123S2 MMI,RST Actual setting 0=Single pulse;1=Forced pulse - 1 Rd/Wr Retain Execution of control command regardless the recent state

(repeated command)Event delay 123S3 MMI,RST Actual setting 0.000...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateOpen pulse 123S6 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Opening time pulse lengthOpen alarm 123S7 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Opening time alarm limitClose pulse 123S8 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Closing time pulse lengthClose alarm 123S9 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Closing time alarm limitObject state 123V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(11);3=Undefine

d2(00)- 0 Read Volatile 2-bit state of the object

Interlock close 123V30 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Close command interlockingInterlock open 123V31 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Open command interlockingDirect open 123V4 Internal Control setting 1=Direct open - 0 Write Volatile Direct open commandDirect close 123V5 Internal Control setting 1=Direct close - 0 Write Volatile Direct close commandOpen select 123V6 Internal Control setting 1=Open select - 0 Write Volatile Open operation selection of the secured controlClose select 123V7 Internal Control setting 1=Close select - 0 Write Volatile Close operation selection of the secured controlCancel 123V10 Internal Control setting 1=Cancel - 0 Write Volatile Deselection of the secured controlExecute 123V11 Internal Control setting 1=Execute - 0 Write Volatile Execution of the secured controlCycle count 123V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueLast open 123V14 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last opening timeMax open 123V15 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum opening timeLast close 123V17 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last closing timeMax close 123V18 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum closing timeIV state 123V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalBlock state 123V35 MMI,RST Input data 0=Inactive;1=Active - 0 Read Volatile Object block signal stateSummarized stat 123V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV;

B4(16)=CLOSEENA; B5(32)=OPENENA; B8(256)=BLOCK; B9(512)=reserved

- 0 Read Volatile Summarized status of the object

Regist clear 123V98 MMI,RST Control setting 1=Clear - 0 Write Volatile Clear internal registrations (last maximum)Alarm ack 123V99 MMI,RST Control setting 1=Acknowledge - 0 Write Volatile Acknowlege alarmEvent mask 1 123V101 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E28)Event mask 2 123V103 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E28)Event mask 3 123V105 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E28)Event mask 4 123V107 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E28)Open alarm 123O3 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Opening time alarm statusClose alarm 123O4 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Closing time alarm status

100124 / Rev A CODC3Fixed pulse 124S1 MMI,RST Actual setting 0=Variable pulse;1=Fixed pulse - 0 Rd/Wr Retain Selection of fixed pulse lengthForced pulse 124S2 MMI,RST Actual setting 0=Single pulse;1=Forced pulse - 1 Rd/Wr Retain Execution of control command regardless the recent state

(repeated command)

Page 125 of 158

Page 126: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event delay 124S3 MMI,RST Actual setting 0.000...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateOpen pulse 124S6 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Opening time pulse lengthOpen alarm 124S7 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Opening time alarm limitClose pulse 124S8 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Closing time pulse lengthClose alarm 124S9 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Closing time alarm limitObject state 124V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(11);3=Undefine

d2(00)- 0 Read Volatile 2-bit state of the object

Interlock close 124V30 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Close command interlockingInterlock open 124V31 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Open command interlockingDirect open 124V4 Internal Control setting 1=Direct open - 0 Write Volatile Direct open commandDirect close 124V5 Internal Control setting 1=Direct close - 0 Write Volatile Direct close commandOpen select 124V6 Internal Control setting 1=Open select - 0 Write Volatile Open operation selection of the secured controlClose select 124V7 Internal Control setting 1=Close select - 0 Write Volatile Close operation selection of the secured controlCancel 124V10 Internal Control setting 1=Cancel - 0 Write Volatile Deselection of the secured controlExecute 124V11 Internal Control setting 1=Execute - 0 Write Volatile Execution of the secured controlCycle count 124V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueLast open 124V14 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last opening timeMax open 124V15 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum opening timeLast close 124V17 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last closing timeMax close 124V18 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum closing timeIV state 124V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalBlock state 124V35 MMI,RST Input data 0=Inactive;1=Active - 0 Read Volatile Object block signal stateSummarized stat 124V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV;

B4(16)=CLOSEENA; B5(32)=OPENENA; B8(256)=BLOCK; B9(512)=reserved

- 0 Read Volatile Summarized status of the object

Regist clear 124V98 MMI,RST Control setting 1=Clear - 0 Write Volatile Clear internal registrations (last maximum)Alarm ack 124V99 MMI,RST Control setting 1=Acknowledge - 0 Write Volatile Acknowlege alarmEvent mask 1 124V101 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E28)Event mask 2 124V103 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E28)Event mask 3 124V105 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E28)Event mask 4 124V107 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E28)Open alarm 124O3 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Opening time alarm statusClose alarm 124O4 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Closing time alarm status

100125 / Rev A CODC4Fixed pulse 125S1 MMI,RST Actual setting 0=Variable pulse;1=Fixed pulse - 0 Rd/Wr Retain Selection of fixed pulse lengthForced pulse 125S2 MMI,RST Actual setting 0=Single pulse;1=Forced pulse - 1 Rd/Wr Retain Execution of control command regardless the recent state

(repeated command)Event delay 125S3 MMI,RST Actual setting 0.000...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateOpen pulse 125S6 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Opening time pulse lengthOpen alarm 125S7 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Opening time alarm limitClose pulse 125S8 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Closing time pulse lengthClose alarm 125S9 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Closing time alarm limitObject state 125V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(11);3=Undefine

d2(00)- 0 Read Volatile 2-bit state of the object

Interlock close 125V30 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Close command interlockingInterlock open 125V31 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Open command interlockingDirect open 125V4 Internal Control setting 1=Direct open - 0 Write Volatile Direct open commandDirect close 125V5 Internal Control setting 1=Direct close - 0 Write Volatile Direct close commandOpen select 125V6 Internal Control setting 1=Open select - 0 Write Volatile Open operation selection of the secured control

Page 126 of 158

Page 127: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Close select 125V7 Internal Control setting 1=Close select - 0 Write Volatile Close operation selection of the secured controlCancel 125V10 Internal Control setting 1=Cancel - 0 Write Volatile Deselection of the secured controlExecute 125V11 Internal Control setting 1=Execute - 0 Write Volatile Execution of the secured controlCycle count 125V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueLast open 125V14 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last opening timeMax open 125V15 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum opening timeLast close 125V17 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last closing timeMax close 125V18 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum closing timeIV state 125V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalBlock state 125V35 MMI,RST Input data 0=Inactive;1=Active - 0 Read Volatile Object block signal stateSummarized stat 125V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV;

B4(16)=CLOSEENA; B5(32)=OPENENA; B8(256)=BLOCK; B9(512)=reserved

- 0 Read Volatile Summarized status of the object

Regist clear 125V98 MMI,RST Control setting 1=Clear - 0 Write Volatile Clear internal registrations (last maximum)Alarm ack 125V99 MMI,RST Control setting 1=Acknowledge - 0 Write Volatile Acknowlege alarmEvent mask 1 125V101 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E28)Event mask 2 125V103 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E28)Event mask 3 125V105 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E28)Event mask 4 125V107 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E28)Open alarm 125O3 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Opening time alarm statusClose alarm 125O4 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Closing time alarm status

100126 / Rev A CODC5Fixed pulse 126S1 MMI,RST Actual setting 0=Variable pulse;1=Fixed pulse - 0 Rd/Wr Retain Selection of fixed pulse lengthForced pulse 126S2 MMI,RST Actual setting 0=Single pulse;1=Forced pulse - 1 Rd/Wr Retain Execution of control command regardless the recent state

(repeated command)Event delay 126S3 MMI,RST Actual setting 0.000...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateOpen pulse 126S6 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Opening time pulse lengthOpen alarm 126S7 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Opening time alarm limitClose pulse 126S8 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Closing time pulse lengthClose alarm 126S9 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Closing time alarm limitObject state 126V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(11);3=Undefine

d2(00)- 0 Read Volatile 2-bit state of the object

Interlock close 126V30 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Close command interlockingInterlock open 126V31 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Open command interlockingDirect open 126V4 Internal Control setting 1=Direct open - 0 Write Volatile Direct open commandDirect close 126V5 Internal Control setting 1=Direct close - 0 Write Volatile Direct close commandOpen select 126V6 Internal Control setting 1=Open select - 0 Write Volatile Open operation selection of the secured controlClose select 126V7 Internal Control setting 1=Close select - 0 Write Volatile Close operation selection of the secured controlCancel 126V10 Internal Control setting 1=Cancel - 0 Write Volatile Deselection of the secured controlExecute 126V11 Internal Control setting 1=Execute - 0 Write Volatile Execution of the secured controlCycle count 126V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueLast open 126V14 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last opening timeMax open 126V15 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum opening timeLast close 126V17 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last closing timeMax close 126V18 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum closing timeIV state 126V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalBlock state 126V35 MMI,RST Input data 0=Inactive;1=Active - 0 Read Volatile Object block signal state

Page 127 of 158

Page 128: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Summarized stat 126V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV; B4(16)=CLOSEENA; B5(32)=OPENENA; B8(256)=BLOCK; B9(512)=reserved

- 0 Read Volatile Summarized status of the object

Regist clear 126V98 MMI,RST Control setting 1=Clear - 0 Write Volatile Clear internal registrations (last maximum)Alarm ack 126V99 MMI,RST Control setting 1=Acknowledge - 0 Write Volatile Acknowlege alarmEvent mask 1 126V101 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E28)Event mask 2 126V103 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E28)Event mask 3 126V105 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E28)Event mask 4 126V107 MMI,RST Control setting 0...521142271 - 134917887 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E28)Open alarm 126O3 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Opening time alarm statusClose alarm 126O4 MMI,RST Output data 0=Inactive; 1=Active - 0 Read Volatile Closing time alarm status

100127 / Rev A COIND1Event delay 127S3 MMI,RST Actual setting 0.0...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateObject state 127V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(00);3=Undefine

d2(11)- 0 Read Volatile 2-bit state of the object

Cycle count 127V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueIV state 127V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalSummarized stat 127V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV - 0 Read Volatile Summarized status of the objectEvent mask 1 127V101 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 127V103 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 127V105 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 127V107 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)

100128 / Rev A COIND2Event delay 128S3 MMI,RST Actual setting 0.0...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateObject state 128V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(00);3=Undefine

d2(11)- 0 Read Volatile 2-bit state of the object

Cycle count 128V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueIV state 128V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalSummarized stat 128V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV - 0 Read Volatile Summarized status of the objectEvent mask 1 128V101 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 128V103 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 128V105 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 128V107 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)

100129 / Rev A COIND3Event delay 129S3 MMI,RST Actual setting 0.0...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateObject state 129V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(00);3=Undefine

d2(11)- 0 Read Volatile 2-bit state of the object

Cycle count 129V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueIV state 129V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalSummarized stat 129V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV - 0 Read Volatile Summarized status of the objectEvent mask 1 129V101 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 129V103 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 129V105 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 129V107 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)

100130 / Rev A COIND4Event delay 130S3 MMI,RST Actual setting 0.0...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateObject state 130V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(00);3=Undefine

d2(11)- 0 Read Volatile 2-bit state of the object

Cycle count 130V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process value

Page 128 of 158

Page 129: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

IV state 130V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalSummarized stat 130V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV - 0 Read Volatile Summarized status of the objectEvent mask 1 130V101 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 130V103 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 130V105 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 130V107 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)

100131 / Rev A COIND5Event delay 131S3 MMI,RST Actual setting 0.0...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateObject state 131V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(00);3=Undefine

d2(11)- 0 Read Volatile 2-bit state of the object

Cycle count 131V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueIV state 131V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalSummarized stat 131V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV - 0 Read Volatile Summarized status of the objectEvent mask 1 131V101 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 131V103 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 131V105 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 131V107 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)

100132 / Rev A COIND6Event delay 132S3 MMI,RST Actual setting 0.0...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateObject state 132V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(00);3=Undefine

d2(11)- 0 Read Volatile 2-bit state of the object

Cycle count 132V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueIV state 132V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalSummarized stat 132V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV - 0 Read Volatile Summarized status of the objectEvent mask 1 132V101 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 132V103 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 132V105 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 132V107 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)

100133 / Rev A COIND7Event delay 133S3 MMI,RST Actual setting 0.0...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateObject state 133V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(00);3=Undefine

d2(11)- 0 Read Volatile 2-bit state of the object

Cycle count 133V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueIV state 133V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalSummarized stat 133V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV - 0 Read Volatile Summarized status of the objectEvent mask 1 133V101 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 133V103 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 133V105 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 133V107 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)

100134 / Rev A COIND8Event delay 134S3 MMI,RST Actual setting 0.0...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateObject state 134V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined1(00);3=Undefine

d2(11)- 0 Read Volatile 2-bit state of the object

Cycle count 134V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process valueIV state 134V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalSummarized stat 134V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN; B3(8)=IV - 0 Read Volatile Summarized status of the objectEvent mask 1 134V101 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 134V103 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 134V105 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)

Page 129 of 158

Page 130: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 4 134V107 MMI,RST Control setting 0...783 - 527 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)100135 / Rev B COSW1

Nonvolatile 135S1 MMI,RST Actual setting 0..1[0 = Inactive; 1 = Active] - 1 Rd/Wr Retain Setting will be stored in a non-volatile memoryON state 135V1 MMI,RST Control setting 0..1[0 = Inactive; 1 = Active] - 0 Rd/Wr Volatile Object output stateEvent mask 1 135V101 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E1)Event mask 2 135V103 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E1)Event mask 3 135V105 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E1)Event mask 4 135V107 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E1)

100136 / Rev B COSW2Nonvolatile 136S1 MMI,RST Actual setting 0..1[0 = Inactive; 1 = Active] - 1 Rd/Wr Retain Setting will be stored in a non-volatile memoryON state 136V1 MMI,RST Control setting 0..1[0 = Inactive; 1 = Active] - 0 Rd/Wr Volatile Object output stateEvent mask 1 136V101 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E1)Event mask 2 136V103 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E1)Event mask 3 136V105 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E1)Event mask 4 136V107 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E1)

100137 / Rev B COSW3Nonvolatile 137S1 MMI,RST Actual setting 0..1[0 = Inactive; 1 = Active] - 1 Rd/Wr Retain Setting will be stored in a non-volatile memoryON state 137V1 MMI,RST Control setting 0..1[0 = Inactive; 1 = Active] - 0 Rd/Wr Volatile Object output stateEvent mask 1 137V101 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E1)Event mask 2 137V103 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E1)Event mask 3 137V105 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E1)Event mask 4 137V107 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E1)

100138 / Rev B COSW4Nonvolatile 138S1 MMI,RST Actual setting 0..1[0 = Inactive; 1 = Active] - 1 Rd/Wr Retain Setting will be stored in a non-volatile memoryON state 138V1 MMI,RST Control setting 0..1[0 = Inactive; 1 = Active] - 0 Rd/Wr Volatile Object output stateEvent mask 1 138V101 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E1)Event mask 2 138V103 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E1)Event mask 3 138V105 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E1)Event mask 4 138V107 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E1)

100139 / Rev A CO3DC1Open alarm 139O5 MMI,RST Output data 0=Inactive;1=Active - 0 Read Volatile Opening time alarm statusClose alarm 139O6 MMI,RST Output data 0=Inactive;1=Active - 0 Read Volatile Closing time alarm statusEarth alarm 139O7 MMI,RST Output data 0=Inactive;1=Active - 0 Read Volatile Earthing time alarm statusFree alarm 139O8 MMI,RST Output data 0=Inactive;1=Active - 0 Read Volatile Freeing time alarm statusFixed pulse 139S1 MMI,RST Actual setting 0=Variable pulse;1=Fixed pulse - 0 Rd/Wr Retain Selection of fixed pulse lengthForced pulse 139S2 MMI,RST Actual setting 0=Single pulse;1=Forced pulse - 1 Rd/Wr Retain Execution of control command regardless the recent state

(repeated command)Event delay 139S3 MMI,RST Actual setting 0.000...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateOpen pulse 139S6 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Opening time pulse lengthOpen alarm 139S7 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Opening time alarm limitClose pulse 139S8 MMI,RST Actual setting 0.04...100.000 s 0,1 Rd/Wr Retain Closing time pulse lengthClose alarm 139S9 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Closing time alarm limitEarth pulse 139S20 MMI,RST Actual setting 0.04...100.000 s 0,1 Rd/Wr Retain Earthing time pulse lengthEarth alarm 139S21 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Earthing time alarm limitFree pulse 139S22 MMI,RST Actual setting 0.04...100.000 s 0,1 Rd/Wr Retain Freeing time pulse lengthFree alarm 139S23 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Freeing time alarm limitObject state oc 139V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined(00);3=Undefined

(11)- 0 Read Volatile Open/Close state of the object

Page 130 of 158

Page 131: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Object state fe 139V2 MMI,RST Input data 1=Earth(01);2=Free(10);0=Undefined(00);3=Undefined(11)

- 0 Read Volatile Free/Earth state of the object

Interlock close 139V30 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Close command interlockingInterlock open 139V31 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Open command interlockingInterlock earth 139V32 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Earth command interloockingInterlock free 139V33 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Free command interlockingDirect open 139V4 Internal Control setting 1=Direct open - 0 Write Volatile Direct open commandDirect close 139V5 Internal Control setting 1=Direct close - 0 Write Volatile Direct close commandDirect earth 139V20 Internal Control setting 1=Direct earth - 0 Write Volatile Direct earth commandDirect free 139V21 Internal Control setting 1=Direct free - 0 Write Volatile Direct free commandOpen select 139V6 Internal Control setting 1=Open select - 0 Write Volatile Open operation selection of the secured controlClose select 139V7 Internal Control setting 1=Close select - 0 Write Volatile Close operation selection of the secured controlEarth select 139V22 Internal Control setting 1=Earth select - 0 Write Volatile Earth operation selection of the secured controlFree select 139V23 Internal Control setting 1=Free select - 0 Write Volatile Free operation selection of the secured controlCancel 139V10 Internal Control setting 1=Cancel - 0 Write Volatile Deselection of the secured controlExecute 139V11 Internal Control setting 1=Execute - 0 Write Volatile Execution of the secured controlOpen cycles 139V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process value between opening and closingLast open 139V14 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last opening timeMax open 139V15 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum opening timeLast close 139V17 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last closing timeMax close 139V18 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum closing timeLast earth 139V24 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last earthing timeMax earth 139V25 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum earthing timeLast free 139V26 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last freeing timeMax free 139V27 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum freeing timeEarth cycles 139V28 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process value between earth and free stateIV state 139V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalBlock state 139V35 MMI,RST Input data 0=Inactive;1=Active - 0 Read Volatile Object block signal stateSummarized stat 139V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN;

B2(4)=BINEARTH; B3(8)=IV; B4(16)=CLOSEENA; B5(32)=OPENENA; B6(64)=EARTHENA; B7(128)=FREEENA; B8(256)=BLOCK; B9(512)=reserved

- 0 Read Volatile Summarized status of the object

Regist clear 139V98 MMI,RST Control setting 1=Clear - 0 Write Volatile Clear internal registrations (last maximum)Alarm ack 139V99 MMI,RST Control setting 1=Acknowledge - 0 Write Volatile Acknowlege alarmEvent mask 1A 139V101 MMI,RST Control setting 0...3742367743 - 2282401535 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E31)Event mask 1B 139V102 MMI,RST Control setting 0...16383 - 16362 Rd/Wr Retain Event mask 1 for event transmission (E32 ... E45)Event mask 2A 139V103 MMI,RST Control setting 0...3742367743 - 2282401535 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E31)Event mask 2B 139V104 MMI,RST Control setting 0...16383 - 16362 Rd/Wr Retain Event mask 2 for event transmission (E32 ... E45)Event mask 3A 139V105 MMI,RST Control setting 0...3742367743 - 2282401535 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E31)Event mask 3B 139V106 MMI,RST Control setting 0...16383 - 16362 Rd/Wr Retain Event mask 3 for event transmission (E32 ... E45)Event mask 4A 139V107 MMI,RST Control setting 0...3742367743 - 2282401535 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E31)Event mask 4B 139V108 MMI,RST Control setting 0...16383 - 16362 Rd/Wr Retain Event mask 4 for event transmission (E32 ... E45)

100140 / Rev A CO3DC2Fixed pulse 140S1 MMI,RST Actual setting 0=Variable pulse;1=Fixed pulse - 0 Rd/Wr Retain Selection of fixed pulse lengthForced pulse 140S2 MMI,RST Actual setting 0=Single pulse;1=Forced pulse - 1 Rd/Wr Retain Execution of control command regardless the recent state

(repeated command)Event delay 140S3 MMI,RST Actual setting 0.000...60.000 s 0,1 Rd/Wr Retain Event delay for undefined stateOpen pulse 140S6 MMI,RST Actual setting 0.04...100.00 s 0,1 Rd/Wr Retain Opening time pulse length

Page 131 of 158

Page 132: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Open alarm 140S7 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Opening time alarm limitClose pulse 140S8 MMI,RST Actual setting 0.04...100.000 s 0,1 Rd/Wr Retain Closing time pulse lengthClose alarm 140S9 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Closing time alarm limitEarth pulse 140S20 MMI,RST Actual setting 0.04...100.000 s 0,1 Rd/Wr Retain Earthing time pulse lengthEarth alarm 140S21 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Earthing time alarm limitFree pulse 140S22 MMI,RST Actual setting 0.04...100.000 s 0,1 Rd/Wr Retain Freeing time pulse lengthFree alarm 140S23 MMI,RST Actual setting 0.00...100.000 s 10 Rd/Wr Retain Freeing time alarm limitObject state oc 140V1 MMI,RST Input data 1=Close(01);2=Open(10);0=Undefined(00);3=Undefined

(11)- 0 Read Volatile Open/Close state of the object

Object state fe 140V2 MMI,RST Input data 1=Earth(01);2=Free(10);0=Undefined(00);3=Undefined(11)

- 0 Read Volatile Free/Earth state of the object

Interlock close 140V30 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Close command interlockingInterlock open 140V31 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Open command interlockingInterlock earth 140V32 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Earth command interloockingInterlock free 140V33 MMI,RST Input data 1=Interlocked; 0=Enabled - 1 Read Volatile Free command interlockingDirect open 140V4 Internal Control setting 1=Direct open - 0 Write Volatile Direct open commandDirect close 140V5 Internal Control setting 1=Direct close - 0 Write Volatile Direct close commandDirect earth 140V20 Internal Control setting 1=Direct earth - 0 Write Volatile Direct earth commandDirect free 140V21 Internal Control setting 1=Direct free - 0 Write Volatile Direct free commandOpen select 140V6 Internal Control setting 1=Open select - 0 Write Volatile Open operation selection of the secured controlClose select 140V7 Internal Control setting 1=Close select - 0 Write Volatile Close operation selection of the secured controlEarth select 140V22 Internal Control setting 1=Earth select - 0 Write Volatile Earth operation selection of the secured controlFree select 140V23 Internal Control setting 1=Free select - 0 Write Volatile Free operation selection of the secured controlCancel 140V10 Internal Control setting 1=Cancel - 0 Write Volatile Deselection of the secured controlExecute 140V11 Internal Control setting 1=Execute - 0 Write Volatile Execution of the secured controlOpen cycles 140V12 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process value between opening and closingLast open 140V14 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last opening timeMax open 140V15 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum opening timeLast close 140V17 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last closing timeMax close 140V18 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum closing timeLast earth 140V24 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last earthing timeMax earth 140V25 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum earthing timeLast free 140V26 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Last freeing timeMax free 140V27 MMI,RST Recorded data1 0.000...100.000 s 0 Read Retain Maximum freeing timeEarth cycles 140V28 MMI,RST Control setting 0...10000 - 0 Rd/Wr Retain Cycle count process value between earth and free stateIV state 140V34 MMI,RST Input data 0=Valid;1=Invalid - 0 Read Volatile Object state validitity from IV-signalBlock state 140V35 MMI,RST Input data 0=Inactive;1=Active - 0 Read Volatile Object block signal stateSummarized stat 140V50 RST Input data B0(1)=BINCLOSE; B1(2)=BINOPEN;

B2(4)=BINEARTH; B3(8)=IV; B4(16)=CLOSEENA; B5(32)=OPENENA; B6(64)=EARTHENA; B7(128)=FREEENA; B8(256)=BLOCK; B9(512)=reserved

- 0 Read Volatile Summarized status of the object

Regist clear 140V98 MMI,RST Control setting 1=Clear - 0 Write Volatile Clear internal registrations (last maximum)Alarm ack 140V99 MMI,RST Control setting 1=Acknowledge - 0 Write Volatile Acknowlege alarmEvent mask 1A 140V101 MMI,RST Control setting 0...3742367743 - 2282401535 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E31)Event mask 1B 140V102 MMI,RST Control setting 0...16383 - 16362 Rd/Wr Retain Event mask 1 for event transmission (E32 ... E45)Event mask 2A 140V103 MMI,RST Control setting 0...3742367743 - 2282401535 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E31)Event mask 2B 140V104 MMI,RST Control setting 0...16383 - 16362 Rd/Wr Retain Event mask 2 for event transmission (E32 ... E45)Event mask 3A 140V105 MMI,RST Control setting 0...3742367743 - 2282401535 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E31)

Page 132 of 158

Page 133: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 3B 140V106 MMI,RST Control setting 0...16383 - 16362 Rd/Wr Retain Event mask 3 for event transmission (E32 ... E45)Event mask 4A 140V107 MMI,RST Control setting 0...3742367743 - 2282401535 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E31)Event mask 4B 140V108 MMI,RST Control setting 0...16383 - 16362 Rd/Wr Retain Event mask 4 for event transmission (E32 ... E45)Open alarm 140O5 MMI,RST Output data 0=Inactive;1=Active - 0 Read Volatile Opening time alarm statusClose alarm 140O6 MMI,RST Output data 0=Inactive;1=Active - 0 Read Volatile Closing time alarm statusEarth alarm 140O7 MMI,RST Output data 0=Inactive;1=Active - 0 Read Volatile Earthing time alarm statusFree alarm 140O8 MMI,RST Output data 0=Inactive;1=Active - 0 Read Volatile Freeing time alarm status

100141 / Rev B COCBDIRPulse width 141S1 MMI,RST Actual setting 0.1...300.0 s 0,1 Rd/Wr Retain Output pulse widthOutput pulse 141V1 RST Control setting 0..1[0 = 0; 1 = Activate] - 0 Write Volatile Remote trigger for output pulseEvent mask 1 141V101 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E1)Event mask 2 141V103 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E1)Event mask 3 141V105 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E1)Event mask 4 141V107 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E1)

100142 / Rev A COLOCATLogic setting 142V1 RST Control setting 0=Inactive;1=Active - 0 Read Volatile Reset logic position settingBinary position 142V2 RST Control setting 0=Disable state, 1=Local state (BINLOCAL active),

2=Remote state (BINREMOTE active)- 0 Read Volatile Recent binary input position (to be validated by the system

software)Event mask 1 142V101 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E1)Event mask 2 142V103 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E1)Event mask 3 142V105 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E1)Event mask 4 142V107 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E1)

100157 / Rev A MMIDATA1Data value 157V1 RST Control setting -999.9...9999.9 - 0 Read Volatile Dynamic data point valueData visibility 157V2 RST Control setting 1=Visible, 0=Invisible - 0 Read Volatile Dynamic data point visibility

100158 / Rev A MMIDATA2Data value 158V1 RST Control setting -999.9...9999.9 - 0 Read Volatile Dynamic data point valueData visibility 158V2 RST Control setting 1=Visible, 0=Invisible - 0 Read Volatile Dynamic data point visibility

100159 / Rev A MMIDATA3Data value 159V1 RST Control setting -999.9...9999.9 - 0 Read Volatile Dynamic data point valueData visibility 159V2 RST Control setting 1=Visible, 0=Invisible - 0 Read Volatile Dynamic data point visibility

100160 / Rev A MMIDATA4Data value 160V1 RST Control setting -999.9...9999.9 - 0 Read Volatile Dynamic data point valueData visibility 160V2 RST Control setting 1=Visible, 0=Invisible - 0 Read Volatile Dynamic data point visibility

100161 / Rev A MMIDATA5Data value 161V1 RST Control setting -999.9...9999.9 - 0 Read Volatile Dynamic data point valueData visibility 161V2 RST Control setting 1=Visible, 0=Invisible - 0 Read Volatile Dynamic data point visibility

100162 / Rev B MMIALAR1Object mode 162V1 MMI,RST Control setting 0..4[0 = Nonlatched steady; 1 = Latched steady; 2 =

Latched blinking; 4 = Uninitialized]- 4 Read Retain Object mode from mimic file

Object status 162V2 RST Control setting 0..7[B0 = ON-signal state; B1 = Alarm latched; B2 = Alarm or state (non-latched) acknowledged]

- 0 Read Volatile Object status

Alarm ack 162V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowlege alarmEvent mask 1 162V101 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 162V103 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 162V105 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 162V107 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)ON-state 162I1 RST Input data 0..1[0 = 0; 1 = ON] - 0 Read Volatile ON-signals state

100163 / Rev B MMIALAR2

Page 133 of 158

Page 134: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Object mode 163V1 MMI,RST Control setting 0..4[0 = Nonlatched steady; 1 = Latched steady; 2 = Latched blinking; 4 = Uninitialized]

- 4 Read Retain Object mode from mimic file

Object status 163V2 RST Control setting 0..7[B0 = ON-signal state; B1 = Alarm latched; B2 = Alarm or state (non-latched) acknowledged]

- 0 Read Volatile Object status

Alarm ack 163V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowlege alarmEvent mask 1 163V101 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 163V103 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 163V105 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 163V107 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)ON-state 163I1 RST Input data 0..1[0 = 0; 1 = ON] - 0 Read Volatile ON-signals state

100164 / Rev B MMIALAR3Object mode 164V1 MMI,RST Control setting 0..4[0 = Nonlatched steady; 1 = Latched steady; 2 =

Latched blinking; 4 = Uninitialized]- 4 Read Retain Object mode from mimic file

Object status 164V2 RST Control setting 0..7[B0 = ON-signal state; B1 = Alarm latched; B2 = Alarm or state (non-latched) acknowledged]

- 0 Read Volatile Object status

Alarm ack 164V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowlege alarmEvent mask 1 164V101 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 164V103 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 164V105 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 164V107 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)ON-state 164I1 RST Input data 0..1[0 = 0; 1 = ON] - 0 Read Volatile ON-signals state

100165 / Rev B MMIALAR4Object mode 165V1 MMI,RST Control setting 0..4[0 = Nonlatched steady; 1 = Latched steady; 2 =

Latched blinking; 4 = Uninitialized]- 4 Read Retain Object mode from mimic file

Object status 165V2 RST Control setting 0..7[B0 = ON-signal state; B1 = Alarm latched; B2 = Alarm or state (non-latched) acknowledged]

- 0 Read Volatile Object status

Alarm ack 165V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowlege alarmEvent mask 1 165V101 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 165V103 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 165V105 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 165V107 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)ON-state 165I1 RST Input data 0..1[0 = 0; 1 = ON] - 0 Read Volatile ON-signals state

100166 / Rev B MMIALAR5Object mode 166V1 MMI,RST Control setting 0..4[0 = Nonlatched steady; 1 = Latched steady; 2 =

Latched blinking; 4 = Uninitialized]- 4 Read Retain Object mode from mimic file

Object status 166V2 RST Control setting 0..7[B0 = ON-signal state; B1 = Alarm latched; B2 = Alarm or state (non-latched) acknowledged]

- 0 Read Volatile Object status

Alarm ack 166V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowlege alarmEvent mask 1 166V101 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 166V103 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 166V105 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 166V107 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)ON-state 166I1 RST Input data 0..1[0 = 0; 1 = ON] - 0 Read Volatile ON-signals state

100167 / Rev B MMIALAR6Object mode 167V1 MMI,RST Control setting 0..4[0 = Nonlatched steady; 1 = Latched steady; 2 =

Latched blinking; 4 = Uninitialized]- 4 Read Retain Object mode from mimic file

Object status 167V2 RST Control setting 0..7[B0 = ON-signal state; B1 = Alarm latched; B2 = Alarm or state (non-latched) acknowledged]

- 0 Read Volatile Object status

Alarm ack 167V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowlege alarm

Page 134 of 158

Page 135: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 1 167V101 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 167V103 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 167V105 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 167V107 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)ON-state 167I1 RST Input data 0..1[0 = 0; 1 = ON] - 0 Read Volatile ON-signals state

100168 / Rev B MMIALAR7Object mode 168V1 MMI,RST Control setting 0..4[0 = Nonlatched steady; 1 = Latched steady; 2 =

Latched blinking; 4 = Uninitialized]- 4 Read Retain Object mode from mimic file

Object status 168V2 RST Control setting 0..7[B0 = ON-signal state; B1 = Alarm latched; B2 = Alarm or state (non-latched) acknowledged]

- 0 Read Volatile Object status

Alarm ack 168V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowlege alarmEvent mask 1 168V101 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 168V103 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 168V105 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 168V107 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)ON-state 168I1 RST Input data 0..1[0 = 0; 1 = ON] - 0 Read Volatile ON-signals state

100169 / Rev B MMIALAR8Object mode 169V1 MMI,RST Control setting 0..4[0 = Nonlatched steady; 1 = Latched steady; 2 =

Latched blinking; 4 = Uninitialized]- 4 Read Retain Object mode from mimic file

Object status 169V2 RST Control setting 0..7[B0 = ON-signal state; B1 = Alarm latched; B2 = Alarm or state (non-latched) acknowledged]

- 0 Read Volatile Object status

Alarm ack 169V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowlege alarmEvent mask 1 169V101 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 169V103 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 169V105 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 169V107 MMI,RST Control setting 0...11 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)ON-state 169I1 RST Input data 0..1[0 = 0; 1 = ON] - 0 Read Volatile ON-signals state

100181 / Rev C CMCU3Operation mode 181V1 MMI,RST Control setting 0..1[0 = Not in use; 1 = In use] - 1 Rd/Wr Retain Switching between the modes: 'In use' and 'Not in use'Current select. 181V2 MMI,RST Control setting 1..4[1 = L1 & L2 & L3; 2 = L1 & L2; 3 = L1 & L3; 4 =

L2 & L3]- 1 Rd/Wr Retain Selection of phase currents used for supervision

High limit 181V3 MMI,RST Control setting 10...20 % In 12 Rd/Wr Retain Set high limit for phase current supervisionLow limit 181V4 MMI,RST Control setting 2...8 % In 6 Rd/Wr Retain Set low limit for phase current supervisionAlarm delay 181V5 MMI,RST Control setting 3.00...60.00 s 15 Rd/Wr Retain Set alarm operate time delayTest ALARM 181V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of alarm outputEvent mask 1 181V101 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E1)Event mask 2 181V103 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E1)Event mask 3 181V105 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E1)Event mask 4 181V107 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E1)Current IL1 181I1 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL1Current IL2 181I2 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL2Current IL3 181I3 MMI,RST Input data 0.00...60.00 x In 0 Read Volatile Phase current IL3Output ALARM 181O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of alarm signalDate 181V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 181V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeCurrent IL1 181V203 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Value of current IL1Current IL2 181V204 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Value of current IL2Current IL3 181V205 MMI,RST Recorded data1 0.00...60.00 x In 0 Read Retain Value of current IL3Date 181V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording date

Page 135 of 158

Page 136: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Time 181V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeCurrent IL1 181V303 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Value of current IL1Current IL2 181V304 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Value of current IL2Current IL3 181V305 MMI,RST Recorded data2 0.00...60.00 x In 0 Read Retain Value of current IL3Date 181V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 181V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeCurrent IL1 181V403 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Value of current IL1Current IL2 181V404 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Value of current IL2Current IL3 181V405 MMI,RST Recorded data3 0.00...60.00 x In 0 Read Retain Value of current IL3

100182 / Rev C CMVO3Operation mode 182V1 MMI,RST Control setting 0..1[0 = In use; 1 = Not in use] - 1 Rd/Wr Retain Switching between the modes: 'In use' and 'Not in use'Voltage select. 182V2 MMI,RST Control setting 1..4[1 = L1 & L2 & L3; 2 = L1 & L2; 3 = L1 & L3; 4 =

L2 & L3]- 1 Rd/Wr Retain Selection of voltages used for supervision

High limit 182V3 MMI,RST Control setting 10...110 % Un 12 Rd/Wr Retain Set high limit for voltage supervisionLow limit 182V4 MMI,RST Control setting 2...90 % Un 6 Rd/Wr Retain Set low limit for voltage supervisionAlarm delay 182V5 MMI,RST Control setting 3...60 s 15 Rd/Wr Retain Set alarm operate time delayTest ALARM 182V31 MMI,RST Control setting 0..1[0 = Do not activate; 1 = Activate] - 0 Rd/Wr Volatile Testing of alarm outputEvent mask 1 182V101 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E1)Event mask 2 182V103 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E1)Event mask 3 182V105 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E1)Event mask 4 182V107 MMI,RST Control setting 0...3 - 3 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E1)Voltage UL1_U12 182I1 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Voltage UL1 / U12Voltage UL2_U23 182I2 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Voltage UL2 / U23Voltage UL3_U31 182I3 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Voltage UL3 / U31Output ALARM 182O1 MMI,RST Output data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Status of alarm signalDate 182V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Recording dateTime 182V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Recording timeVoltage U1_12 182V203 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Voltage U1Voltage U2_23 182V204 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Voltage U2Voltage U3_31 182V205 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Voltage U3Date 182V301 MMI,RST Recorded data2 YYYY-MM-DD - - Read Retain Recording dateTime 182V302 MMI,RST Recorded data2 hh:mm:ss.000 - - Read Retain Recording timeVoltage U1_12 182V303 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Voltage U1Voltage U2_23 182V304 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Voltage U2Voltage U3_31 182V305 MMI,RST Recorded data2 0.00...2.00 x Un 0 Read Retain Voltage U3Date 182V401 MMI,RST Recorded data3 YYYY-MM-DD - - Read Retain Recording dateTime 182V402 MMI,RST Recorded data3 hh:mm:ss.000 - - Read Retain Recording timeVoltage U1_12 182V403 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Voltage U1Voltage U2_23 182V404 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Voltage U2Voltage U3_31 182V405 MMI,RST Recorded data3 0.00...2.00 x Un 0 Read Retain Voltage U3

100184 / Rev B CMTIME1Max hours 184S1 MMI,RST Actual setting 0...87600 hours 0 Rd/Wr Retain Maximum accumulated time alarm limit hoursMax mins 184S2 MMI,RST Actual setting 0...59 min 0 Rd/Wr Retain Maximum accumulated time alarm limit minutesAccum. hours 184V1 MMI,RST Control setting 0...87600 hours 0 Rd/Wr Retain Accumulated time hoursAccum. min 184V2 MMI,RST Control setting 0...59 min 0 Rd/Wr Retain Accumulated time minutesAlarm ack 184V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowledge alarmEvent mask 1 184V101 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 184V103 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 184V105 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)

Page 136 of 158

Page 137: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 4 184V107 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)BININP state 184I1 MMI,RST Input data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Binary input stateAlarm state 184O1 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Alarm state

100185 / Rev B CMTIME2Max hours 185S1 MMI,RST Actual setting 0...87600 hours 0 Rd/Wr Retain Maximum accumulated time alarm limit hoursMax mins 185S2 MMI,RST Actual setting 0...59 min 0 Rd/Wr Retain Maximum accumulated time alarm limit minutesAccum. hours 185V1 MMI,RST Control setting 0...87600 hours 0 Rd/Wr Retain Accumulated time hoursAccum. min 185V2 MMI,RST Control setting 0...59 min 0 Rd/Wr Retain Accumulated time minutesAlarm ack 185V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowledge alarmEvent mask 1 185V101 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 185V103 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 185V105 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 185V107 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)BININP state 185I1 MMI,RST Input data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Binary input stateAlarm state 185O1 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Alarm state

100186 / Rev B CMGAS1Alarm delay 186S1 MMI,RST Actual setting 0.000...300.000 s 0 Rd/Wr Retain Alarm delayAlarm ack 186V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowledge alarmEvent mask 1 186V101 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 186V103 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 186V105 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 186V107 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)Gas pressure 186I1 MMI,RST Input data 0..1[0 = Invalid; 1 = Valid] - 0 Read Volatile Indication of valid gas pressureAlarm state 186O1 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Alarm state

100187 / Rev B CMBWEAR1Alarm limit 187S1 MMI,RST Actual setting 1.00...10000.00 - 5000 Rd/Wr Retain Breaker wear alarm limit for accumulated breaker wearWear L1 187V1 MMI,RST Control setting 0.00...10000.00 - 0 Rd/Wr Retain Accumulated breaker wear at pole 1Wear L2 187V2 MMI,RST Control setting 0.00...10000.00 - 0 Rd/Wr Retain Accumulated breaker wear at pole 2Wear L3 187V3 MMI,RST Control setting 0.00...10000.00 - 0 Rd/Wr Retain Accumulated breaker wear at pole 3Alarm ack 187V99 MMI,RST Control setting 0..1[0 = 0; 1=Acknowledge] - 0 Write Volatile Acknowledge alarmEvent mask 1 187V101 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E1)Event mask 2 187V103 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E1)Event mask 3 187V105 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E1)Event mask 4 187V107 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E1)Current 1/16 187V13 RST Control setting 0.00...1000.00 kA 0 Rd/Wr Retain Current value in breaker wear table (1/16)Wear 1/16 187V14 RST Control setting 0.00...10000.00 - 0 Rd/Wr Retain Wear value in breaker wear table (1/16)Current 2/16 187V15 RST Control setting 0.00...1000.00 kA 4 Rd/Wr Retain Current value in breaker wear table (2/16)Wear 2/16 187V16 RST Control setting 0.00...10000.00 - 4 Rd/Wr Retain Wear value in breaker wear table (2/16)Current 3/16 187V17 RST Control setting 0.00...1000.00 kA 8 Rd/Wr Retain Current value in breaker wear table (3/16)Wear 3/16 187V18 RST Control setting 0.00...10000.00 - 33 Rd/Wr Retain Wear value in breaker wear table (3/16)Current 4/16 187V19 RST Control setting 0.00...1000.00 kA 12 Rd/Wr Retain Current value in breaker wear table (4/16)Wear 4/16 187V20 RST Control setting 0.00...10000.00 - 92 Rd/Wr Retain Wear value in breaker wear table (4/16)Current 5/16 187V21 RST Control setting 0.00...1000.00 kA 16 Rd/Wr Retain Current value in breaker wear table (5/16)Wear 5/16 187V22 RST Control setting 0.00...10000.00 - 164 Rd/Wr Retain Wear value in breaker wear table (5/16)Current 6/16 187V23 RST Control setting 0.00...1000.00 kA 20 Rd/Wr Retain Current value in breaker wear table (6/16)Wear 6/16 187V24 RST Control setting 0.00...10000.00 - 256 Rd/Wr Retain Wear value in breaker wear table (6/16)Current 7/16 187V25 RST Control setting 0.00...1000.00 kA 24 Rd/Wr Retain Current value in breakerwear table (7/16)Wear 7/16 187V26 RST Control setting 0.00...10000.00 - 369 Rd/Wr Retain Wear value in breaker wear table (7/16)Current 8/16 187V27 RST Control setting 0.00...1000.00 kA 28 Rd/Wr Retain Current value in breaker wear table (8/16)

Page 137 of 158

Page 138: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Wear 8/16 187V28 RST Control setting 0.00...10000.00 - 502 Rd/Wr Retain Wear value in breaker wear table (8/16)Current 9/16 187V29 RST Control setting 0.00...1000.00 kA 32 Rd/Wr Retain Current value in breaker wear table (9/16)Wear 9/16 187V30 RST Control setting 0.00...10000.00 - 655 Rd/Wr Retain Wear value in breaker wear table (9/16)Current 10/16 187V31 RST Control setting 0.00...1000.00 kA 36 Rd/Wr Retain Current value in breaker wear table (10/16)Wear 10/16 187V32 RST Control setting 0.00...10000.00 - 829 Rd/Wr Retain Wear value in breaker wear table (10/16)Current 11/16 187V33 RST Control setting 0.00...1000.00 kA 40 Rd/Wr Retain Current value in breaker wear table (11/16)Wear 11/16 187V34 RST Control setting 0.00...10000.00 - 1024 Rd/Wr Retain Wear value in breaker wear table (11/16)Current 12/16 187V35 RST Control setting 0.00...1000.00 kA 44 Rd/Wr Retain Current value in breaker wear table (12/16)Wear 12/16 187V36 RST Control setting 0.00...10000.00 - 1239 Rd/Wr Retain Wear value in breaker wear table (12/16)Current 13/16 187V37 RST Control setting 0.00...1000.00 kA 48 Rd/Wr Retain Current value in breaker wear table (13/16)Wear 13/16 187V38 RST Control setting 0.00...10000.00 - 1475 Rd/Wr Retain Wear value in breaker wear table (13/16)Current 14/16 187V39 RST Control setting 0.00...1000.00 kA 52 Rd/Wr Retain Current value in breaker wear table (14/16)Wear 14/16 187V40 RST Control setting 0.00...10000.00 - 1731 Rd/Wr Retain Wear value in breaker wear table (14/16)Current 15/16 187V41 RST Control setting 0.00...1000.00 kA 56 Rd/Wr Retain Current value in breaker wear table (15/16)Wear 15/16 187V42 RST Control setting 0.00...10000.00 - 2007 Rd/Wr Retain Wear value in breaker wear table (15/16)Current 16/16 187V43 RST Control setting 0.00...1000.00 kA 60 Rd/Wr Retain Current value in breaker wear table (16/16)Wear 16/16 187V44 RST Control setting 0.00...10000.00 - 2304 Rd/Wr Retain Wear value in breaker wear table (16/16)Alarm state 187O1 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Breaker wear alarm state

100188 / Rev B CMBWEAR2Alarm limit 188S1 MMI,RST Actual setting 1.00...10000.00 - 5000 Rd/Wr Retain Breaker wear alarm limit for accumulated breaker wearWear L1 188V1 MMI,RST Control setting 0.00...10000.00 - 0 Rd/Wr Retain Accumulated breaker wear at pole 1Wear L2 188V2 MMI,RST Control setting 0.00...10000.00 - 0 Rd/Wr Retain Accumulated breaker wear at pole 2Wear L3 188V3 MMI,RST Control setting 0.00...10000.00 - 0 Rd/Wr Retain Accumulated breaker wear at pole 3Alarm ack 188V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowledge alarmEvent mask 1 188V101 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E1)Event mask 2 188V103 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E1)Event mask 3 188V105 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E1)Event mask 4 188V107 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E1)Current 1/16 188V13 RST Control setting 0.00...1000.00 kA 0 Rd/Wr Retain Current value in breaker wear table (1/16)Wear 1/16 188V14 RST Control setting 0.00...10000.00 - 0 Rd/Wr Retain Wear value in breaker wear table (1/16)Current 2/16 188V15 RST Control setting 0.00...1000.00 kA 4 Rd/Wr Retain Current value in breaker wear table (2/16)Wear 2/16 188V16 RST Control setting 0.00...10000.00 - 4 Rd/Wr Retain Wear value in breaker wear table (2/16)Current 3/16 188V17 RST Control setting 0.00...1000.00 kA 8 Rd/Wr Retain Current value in breaker wear table (3/16)Wear 3/16 188V18 RST Control setting 0.00...10000.00 - 33 Rd/Wr Retain Wear value in breaker wear table (3/16)Current 4/16 188V19 RST Control setting 0.00...1000.00 kA 12 Rd/Wr Retain Current value in breaker wear table (4/16)Wear 4/16 188V20 RST Control setting 0.00...10000.00 - 92 Rd/Wr Retain Wear value in breaker wear table (4/16)Current 5/16 188V21 RST Control setting 0.00...1000.00 kA 16 Rd/Wr Retain Current value in breaker wear table (5/16)Wear 5/16 188V22 RST Control setting 0.00...10000.00 - 164 Rd/Wr Retain Wear value in breaker wear table (5/16)Current 6/16 188V23 RST Control setting 0.00...1000.00 kA 20 Rd/Wr Retain Current value in breaker wear table (6/16)Wear 6/16 188V24 RST Control setting 0.00...10000.00 - 256 Rd/Wr Retain Wear value in breaker wear table (6/16)Current 7/16 188V25 RST Control setting 0.00...1000.00 kA 24 Rd/Wr Retain Current value in breakerwear table (7/16)Wear 7/16 188V26 RST Control setting 0.00...10000.00 - 369 Rd/Wr Retain Wear value in breaker wear table (7/16)Current 8/16 188V27 RST Control setting 0.00...1000.00 kA 28 Rd/Wr Retain Current value in breaker wear table (8/16)Wear 8/16 188V28 RST Control setting 0.00...10000.00 - 502 Rd/Wr Retain Wear value in breaker wear table (8/16)Current 9/16 188V29 RST Control setting 0.00...1000.00 kA 32 Rd/Wr Retain Current value in breaker wear table (9/16)Wear 9/16 188V30 RST Control setting 0.00...10000.00 - 655 Rd/Wr Retain Wear value in breaker wear table (9/16)Current 10/16 188V31 RST Control setting 0.00...1000.00 kA 36 Rd/Wr Retain Current value in breaker wear table (10/16)Wear 10/16 188V32 RST Control setting 0.00...10000.00 - 829 Rd/Wr Retain Wear value in breaker wear table (10/16)Current 11/16 188V33 RST Control setting 0.00...1000.00 kA 40 Rd/Wr Retain Current value in breaker wear table (11/16)

Page 138 of 158

Page 139: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Wear 11/16 188V34 RST Control setting 0.00...10000.00 - 1024 Rd/Wr Retain Wear value in breaker wear table (11/16)Current 12/16 188V35 RST Control setting 0.00...1000.00 kA 44 Rd/Wr Retain Current value in breaker wear table (12/16)Wear 12/16 188V36 RST Control setting 0.00...10000.00 - 1239 Rd/Wr Retain Wear value in breaker wear table (12/16)Current 13/16 188V37 RST Control setting 0.00...1000.00 kA 48 Rd/Wr Retain Current value in breaker wear table (13/16)Wear 13/16 188V38 RST Control setting 0.00...10000.00 - 1475 Rd/Wr Retain Wear value in breaker wear table (13/16)Current 14/16 188V39 RST Control setting 0.00...1000.00 kA 52 Rd/Wr Retain Current value in breaker wear table (14/16)Wear 14/16 188V40 RST Control setting 0.00...10000.00 - 1731 Rd/Wr Retain Wear value in breaker wear table (14/16)Current 15/16 188V41 RST Control setting 0.00...1000.00 kA 56 Rd/Wr Retain Current value in breaker wear table (15/16)Wear 15/16 188V42 RST Control setting 0.00...10000.00 - 2007 Rd/Wr Retain Wear value in breaker wear table (15/16)Current 16/16 188V43 RST Control setting 0.00...1000.00 kA 60 Rd/Wr Retain Current value in breaker wear table (16/16)Wear 16/16 188V44 RST Control setting 0.00...10000.00 - 2304 Rd/Wr Retain Wear value in breaker wear table (16/16)Alarm state 188O1 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Breaker wear alarm state

100189 / Rev C CMSCHEDAlarm interval 189S1 MMI,RST Actual setting 1...3650 days 1825 Rd/Wr Retain Interrupt interval at daysAlarm time 189S2 MMI,RST Actual setting 00.00...23.59 hh.mm 8 Rd/Wr Retain Interrupt clock time at format hh.mmElapsed time 189V1 MMI,RST Control setting 0...3650 days 0 Read Retain Elapsed time at daysAlarm ack 189V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowledge alarmEvent mask 1 189V101 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E1)Event mask 2 189V103 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E1)Event mask 3 189V105 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E1)Event mask 4 189V107 MMI,RST Control setting 0...3 - 2 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E1)Start time 189V2 Internal Control setting - - 0 Read Retain Internal variableAlarm state 189O1 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Scheduled maintenance alarm state

100190 / Rev B CMSPRC1Fixed pulse 190S1 MMI,RST Actual setting 0..1[0 = Fixed pulse; 1 = Variable pulse] - 0 Rd/Wr Retain Selection of fixed pulse length or variable pulse lengthCharge time 190S2 MMI,RST Actual setting 0.00...100.00 s 20 Rd/Wr Retain Spring charging timeCharge max 190S3 MMI,RST Actual setting 0.00...100.00 s 20 Rd/Wr Retain Spring charging maximum alarm limitCharge min 190S4 MMI,RST Actual setting 0.00...100.00 s 5 Rd/Wr Retain Spring charging minimum alarm limitLast charge 190V1 MMI,RST Control setting 0.00...100.00 s 0 Read Retain Last charging timeRegist clear 190V98 MMI,RST Control setting 0..1[0 = 0; 1 = Clear] - 0 Write Volatile Clear internal registrationsAlarm ack 190V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowledge alarmEvent mask 1 190V101 MMI,RST Control setting 0...959 - 682 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 190V103 MMI,RST Control setting 0...959 - 682 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 190V105 MMI,RST Control setting 0...959 - 682 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 190V107 MMI,RST Control setting 0...959 - 682 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Charge status 190I2 MMI,RST Input data 0..1[0 = Uncharged; 1 = Charged] - 0 Read Volatile Spring charge statusAlarm max 190O2 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Alarm status of maximum alarm pulseAlarm min 190O3 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Alarm status of minumum alarm pulse

100191 / Rev B CMTCS1Alarm delay 191S1 MMI,RST Actual setting 0...300.000 s 3 Rd/Wr Retain Alarm delayActivation 191S2 MMI,RST Actual setting 0..1[0 = Inactive; 1 = Active] - 1 Rd/Wr Retain Activation of TCS functionEvent mask 1 191V101 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 191V103 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 191V105 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 191V107 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)BS state 191I2 MMI,RST Input data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Blocking signal stateAlarm state 191O1 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Alarm state

100192 / Rev B CMTCS2Alarm delay 192S1 MMI,RST Actual setting 0...300.000 s 3 Rd/Wr Retain Alarm delay

Page 139 of 158

Page 140: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Activation 192S2 MMI,RST Actual setting 0..1[0 = Inactive; 1 = Active] - 1 Rd/Wr Retain Activation of TCS functionEvent mask 1 192V101 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 192V103 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 192V105 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 192V107 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)BS state 192I2 MMI,RST Input data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Blocking signal stateAlarm state 192O1 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Alarm state

100193 / Rev B CMTRAV1Open alarm lim. 193S1 MMI,RST Actual setting 0...100.000 s 0,01 Rd/Wr Retain Alarm limit for openingClose alarm lim. 193S2 MMI,RST Actual setting 0...100.000 s 0,01 Rd/Wr Retain Alarm limit for closingLast open 193V1 MMI,RST Control setting 0...100.000 s 0 Read Retain Last open travel timeLast close 193V2 MMI,RST Control setting 0...100.000 s 0 Read Retain Last close travel timeRegist clear 193V98 MMI,RST Control setting 0..1[0 = 0; 1 = Clear] - 0 Write Volatile Clear internal registrationsAlarm ack 193V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowledge alarmEvent mask 1 193V101 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E3)Event mask 2 193V103 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E3)Event mask 3 193V105 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E3)Event mask 4 193V107 MMI,RST Control setting 0...15 - 10 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E3)Open alarm 193O1 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Alarm signal status for openClose alarm 193O2 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Alarm signal status for close

100194 / Rev A CMGAS3Alarm delay 194S1 MMI,RST Actual setting 0...300.000 s 0 Rd/Wr Retain Alarm delayAlarm ack 194V99 MMI,RST Control setting 0..1[0 = 0; 1 = Acknowledge] - 0 Write Volatile Acknowledge alarmEvent mask 1 194V101 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E7)Event mask 2 194V103 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E7)Event mask 3 194V105 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E7)Event mask 4 194V107 MMI,RST Control setting 0...255 - 170 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E7)Gas pressure L1 194I1 MMI,RST Input data 0..1[0 = Invalid; 1 = Valid] - 0 Read Volatile Indication of valid gas pressure in pole L1Gas pressure L2 194I2 MMI,RST Input data 0..1[0 = Invalid; 1 = Valid] - 0 Read Volatile Indication of valid gas pressure in pole L2Gas pressure L3 194I3 MMI,RST Input data 0..1[0 = Invalid; 1 = Valid] - 0 Read Volatile Indication of valid gas pressure in pole L3Alarm state 194O1 MMI,RST Output data 0..1[0 = Inactive; 1 = Active] - 0 Read Volatile Low gas pressure alarm

100200 / Rev C MECU3APhase selection 200V1 MMI,RST Control setting 0..6[0 = L1,L2,L3; 1 = L1,L2; 2 = L2,L3; 3 = L1,L3; 4 =

L1; 5 = L2; 6 = L3]- 0 Rd/Wr Retain Selection of phase currents to be measured

Demand interval 200V2 MMI,RST Control setting 0..5[0 = 1 min; 1 = 5 min; 2 = 10 min; 3 = 15 min; 4 = 30 min; 5 = 60 min]

- 1 Rd/Wr Retain Time interval for demand supervision

Threshold select 200V3 MMI,RST Control setting 0..2[0 = Not in use; 1= Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 200V4 MMI,RST Control setting 0.1...25.0 % In 1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 200V5 MMI,RST Control setting 0..9[0 = Not in use; 1= HW, HA, LW, LA; 2 = HW, HA;

3 = LW, LA; 4 = HW, LW; 5 = HA, LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of monitored limits

High warning 200V6 MMI,RST Control setting 80.0...500.0 % In 100 Rd/Wr Retain High warning limit valueHigh alarm 200V7 MMI,RST Control setting 80.0...500.0 % In 120 Rd/Wr Retain High alarm limit valueLow warning 200V8 MMI,RST Control setting 0.0...80.0 % In 0 Rd/Wr Retain Low warning limit valueLow alarm 200V9 MMI,RST Control setting 0.0...80.0 % In 0 Rd/Wr Retain Low alarm limit valueEvent mask 1 200V101 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E29)Event mask 2 200V103 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E29)Event mask 3 200V105 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E29)Event mask 4 200V107 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E29)

Page 140 of 158

Page 141: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

IL1 200I1 MMI,RST Input data 0.0...20000.0 A 0 Read Volatile Current IL1 in amperesIL2 200I2 MMI,RST Input data 0.0...20000.0 A 0 Read Volatile Current IL2 in amperesIL3 200I3 MMI,RST Input data 0.0...20000.0 A 0 Read Volatile Current IL3 in amperesIL1 200I4 MMI,RST Input data 0.0...1000.0 % In 0 Read Volatile Current IL1 in percentsIL2 200I5 MMI,RST Input data 0.0...1000.0 % In 0 Read Volatile Current IL2 in percentsIL3 200I6 MMI,RST Input data 0.0...1000.0 % In 0 Read Volatile Current IL3 in percentsIL1 demand 200I7 MMI,RST Input data 0.0...20000.0 A 0 Read Volatile IL1 demand in amperesIL2 demand 200I8 MMI,RST Input data 0.0...20000.0 A 0 Read Volatile IL2 demand in amperesIL3 demand 200I9 MMI,RST Input data 0.0...20000.0 A 0 Read Volatile IL3 demand in amperesIL1 demand 200I10 MMI,RST Input data 0.0...1000.0 % In 0 Read Volatile IL1 demand in percentsIL2 demand 200I11 MMI,RST Input data 0.0...1000.0 % In 0 Read Volatile IL2 demand in percentsIL3 demand 200I12 MMI,RST Input data 0.0...1000.0 % In 0 Read Volatile IL3 demand in percentsInput RESET 200I13 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting demand values and registers of

MECU3AIL1 Maximum Date 200V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of IL1 max demandIL1 Maximum Time 200V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of IL1 max demandIL1 Maximum (A) 200V203 MMI,RST Recorded data1 0.0...20000.0 A 0 Read Retain Maximum demand for IL1 in amperesIL1 Maximum (%) 200V204 MMI,RST Recorded data1 0.0...1000.0 % In 0 Read Retain Maximum demand for IL1 in percentsIL2 Maximum Date 200V205 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of IL2 max demandIL2 Maximum Time 200V206 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of IL2 max demandIL2 Maximum (A) 200V207 MMI,RST Recorded data1 0.0...20000.0 A 0 Read Retain Maximum demand for IL2 in amperesIL2 Maximum (%) 200V208 MMI,RST Recorded data1 0.0...1000.0 % In 0 Read Retain Maximum demand for IL2 in percentsIL3 Maximum Date 200V209 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of IL3 max demandIL3 Maximum Time 200V210 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of IL3 max demandIL3 Maximum (A) 200V211 MMI,RST Recorded data1 0.0...20000.0 A 0 Read Retain Maximum demand for IL3 in amperesIL3 Maximum (%) 200V212 MMI,RST Recorded data1 0.0...1000.0 % In 0 Read Retain Maximum demand for IL3 in percents

100201 / Rev C MECU1AThreshold select 201V1 MMI,RST Control setting 0..2[0=Not in use; 1=Absolute alg.; 2=Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 201V2 MMI,RST Control setting 0.1...25.0 % In 1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 201V3 MMI,RST Control setting 0..3[0= Not in use; 1= HW,HA; 2= HW; 3= HA] - 0 Rd/Wr Retain Selection of monitored limitsHigh warning 201V4 MMI,RST Control setting 0.0...80.0 % In 0 Rd/Wr Retain High warning limit valueHigh alarm 201V5 MMI,RST Control setting 0.0...80.0 % In 0 Rd/Wr Retain High alarm limit valueEvent mask 1 201V101 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E5)Event mask 2 201V103 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E5)Event mask 3 201V105 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E5)Event mask 4 201V107 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E5)Io 201I1 MMI,RST Input data 0.0...20000.0 A 0 Read Volatile Current Io in amperesIo 201I2 MMI,RST Input data 0.0...80.0 % In 0 Read Volatile Current Io in percentsInput RESET 201I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting demand values and registers of

MECU1AIo Peak Date 201V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of Io peakIo Peak Time 201V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of Io peakIo Peak Amps 201V203 MMI,RST Recorded data1 0.0...20000.0 A 0 Read Retain Io peak in amperesIo Peak % 201V204 MMI,RST Recorded data1 0.0...80.0 % In 0 Read Retain Io peak in percents

100203 / Rev C MECU1BThreshold select 203V1 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 203V2 MMI,RST Control setting 0.1...25.0 % In 1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 203V3 MMI,RST Control setting 0..3[0 = Not in use; 1 = HW,HA; 2 = HW; 3 = HA] - 0 Rd/Wr Retain Selection of monitored limitsHigh warning 203V4 MMI,RST Control setting 0.0...80.0 % In 0 Rd/Wr Retain High warning limit value

Page 141 of 158

Page 142: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

High alarm 203V5 MMI,RST Control setting 0.0...80.0 % In 0 Rd/Wr Retain High alarm limit valueEvent mask 1 203V101 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E5)Event mask 2 203V103 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E5)Event mask 3 203V105 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E5)Event mask 4 203V107 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E5)Io 203I1 MMI,RST Input data 0.0...20000.0 A 0 Read Volatile Current Io in amperesIo 203I2 MMI,RST Input data 0.0...80.0 % In 0 Read Volatile Current Io in percentsInput RESET 203I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting demand values and registers of

MECU1BIo Peak Date 203V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of Io peakIo Peak Time 203V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of Io peakIo Peak Amps 203V203 MMI,RST Recorded data1 0.0...20000.0 A 0 Read Retain Io peak in amperesIo Peak % 203V204 MMI,RST Recorded data1 0.0...80.0 % In 0 Read Retain Io peak in percents

100204 / Rev D MEVO3APhase selection 204V1 MMI,RST Control setting 0..6[0 = Uch1, Uch2, Uch3; 1 = Uch1, Uch2; 2 = Uch2,

Uch3; 3 = Uch1, Uch3; 4 = Uch1; 5 = Uch2; 6 = Uch3]- 0 Rd/Wr Retain Selection of channels to be measured

Average interval 204V2 MMI,RST Control setting 0..5[0 = 1 min; 1 = 5 min; 2 = 10 min; 3 = 15 min; 4 = 30 min; 5 = 60 min]

- 1 Rd/Wr Retain Time interval for average value

Threshold select 204V3 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 204V4 MMI,RST Control setting 0.01...1.00 x Un 0,01 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 204V5 MMI,RST Control setting 0..9[0 = Not in use; 1 = HW, HA, LW, LA; 2 = HW, HA;

3 = LW, LA; 4 = HW, LW; 5 = HA, LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of monitored limits

High warning 204V6 MMI,RST Control setting 0.80...1.50 x Un 1 Rd/Wr Retain High warning limit valueHigh alarm 204V7 MMI,RST Control setting 0.80...1.50 x Un 1,1 Rd/Wr Retain High alarm limit valueLow warning 204V8 MMI,RST Control setting 0.00...0.99 x Un 0 Rd/Wr Retain Low warning limit valueLow alarm 204V9 MMI,RST Control setting 0.00...0.99 x Un 0 Rd/Wr Retain Low alarm limit valueEvent mask 1A 204V101 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E29)Event mask 1B 204V102 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 1 for event transmission (E32 ... E61)Event mask 2A 204V103 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E29)Event mask 2B 204V104 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 2 for event transmission (E32 ... E61)Event mask 3A 204V105 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E29)Event mask 3B 204V106 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 3 for event transmission (E32 ... E61)Event mask 4A 204V107 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E29)Event mask 4B 204V108 MMI,RST Control setting 0...721420287 - 0 Rd/Wr Retain Event mask 4 for event transmission (E32 ... E61)UL1_U12 204I1 MMI,RST Input data 0.00...999.99 kV 0 Read Volatile Voltage UL1_U12 in voltagesUL2_U23 204I2 MMI,RST Input data 0.00...999.99 kV 0 Read Volatile Voltage UL2_U23 in voltagesUL3_U31 204I3 MMI,RST Input data 0.00...999.99 kV 0 Read Volatile Voltage UL3_U31 in voltagesUL1_U12 204I4 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Voltage UL1_U12 in percentsUL2_U23 204I5 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Voltage UL2_U23 in percentsUL3_U31 204I6 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Voltage UL3_U31 in percentsUL1_U12 average 204I7 MMI,RST Input data 0.00...999.99 kV 0 Read Volatile Average value of UL1_U12 in voltagesUL2_U23 average 204I8 MMI,RST Input data 0.00...999.99 kV 0 Read Volatile Average value of UL2_U23 in voltagesUL3_U31 average 204I9 MMI,RST Input data 0.00...999.99 kV 0 Read Volatile Average value of UL3_U31 in voltagesUL1_U12 average 204I10 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Average value of UL1_U12 in percentsUL2_U23 average 204I11 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Average value of UL2_U23 in percentsUL3_U31 average 204I12 MMI,RST Input data 0.00...2.00 x Un 0 Read Volatile Average value of UL3_U31 in percentsInput RESET 204I13 MMI,RST Input data 0..1[0=Not active; 1=Active] - 0 Read Volatile Signal for resetting demand values and registers of

MEVO3A

Page 142 of 158

Page 143: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

U1_12 Max Date 204V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of UL1_U12 maximum average voltageU1_12 Max Time 204V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of UL1_U12 maximum average voltageU1_12 Max (kV) 204V203 MMI,RST Recorded data1 0.00...999.99 kV 0 Read Retain Maximum average of UL1_U12 in voltagesU1_12 Max (pu) 204V204 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Maximum average of UL1_U12 in percentsU2_23 Max Date 204V205 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of UL2_U23 maximum average voltageU2_23 Max Time 204V206 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of UL2_U23 maximum average voltageU2_23 Max (kV) 204V207 MMI,RST Recorded data1 0.00...999.99 kV 0 Read Retain Maximum average of UL2_U23 in voltagesU2_23 Max (pu) 204V208 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Maximum average of UL2_U23 in percentsU3_31 Max Date 204V209 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of UL3_U31 maximum average voltageU3_31 Max Time 204V210 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of UL3_U31 maximum average voltageU3_31 Max (kV) 204V211 MMI,RST Recorded data1 0.00...999.99 kV 0 Read Retain Maximum average of UL3_U31 in voltagesU3_31 Max (pu) 204V212 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Maximum average of UL3_U31 in percentsU1_12 Min Date 204V213 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of UL1_U12 minimum average voltageU1_12 Min Time 204V214 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of UL1_U12 minimum average voltageU1_12 Min (kV) 204V215 MMI,RST Recorded data1 0.00...999.99 kV 0 Read Retain Minimum average of UL1_U12 in voltagesU1_12 Min (pu) 204V216 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Minimum average of UL1_U12 in percentsU2_23 Min Date 204V217 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of UL2_U23 minimum average voltageU2_23 Min Time 204V218 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of UL2_U23 minimum average voltageU2_23 Min (kV) 204V219 MMI,RST Recorded data1 0.00...999.99 kV 0 Read Retain Minimum average of UL2_U23 in voltagesU2_23 Min (pu) 204V220 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Minimum average of UL2_U23 in percentsU3_31 Min Date 204V221 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of UL3_U31 minimum average voltageU3_31 Min Time 204V222 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of UL3_U31 minimum average voltageU3_31 Min (kV) 204V223 MMI,RST Recorded data1 0.00...999.99 kV 0 Read Retain Minimum average of UL3_U31 in voltagesU3_31 Min (pu) 204V224 MMI,RST Recorded data1 0.00...2.00 x Un 0 Read Retain Minimum average of UL3_U31 in percents

100205 / Rev D MEVO1AThreshold select 205V1 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 205V2 MMI,RST Control setting 0.1...25.0 % Un 1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 205V3 MMI,RST Control setting 0..3[0 = Not in use; 1 = HW,HA; 2 = HW; 3 = HA] - 0 Rd/Wr Retain Selection of monitored limitsHigh warning 205V4 MMI,RST Control setting 2.0...100.0 % Un 2 Rd/Wr Retain High warning limit valueHigh alarm 205V5 MMI,RST Control setting 2.0...100.0 % Un 10 Rd/Wr Retain High alarm limit valueEvent mask 1 205V101 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E5)Event mask 2 205V103 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E5)Event mask 3 205V105 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E5)Event mask 4 205V107 MMI,RST Control setting 0...47 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E5)Uo 205I1 MMI,RST Input data 0...150000 V 0 Read Volatile Residual voltage Uo in voltagesUo 205I2 MMI,RST Input data 0.0...120.0 % Un 0 Read Volatile Residual voltage Uo in percentsInput RESET 205I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting demand values and registers of

MEVO1AUo Peak Date 205V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of Uo peakUo Peak Time 205V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of Uo peakUo Peak Volts 205V203 MMI,RST Recorded data1 0...150000 V 0 Read Retain Uo peak in voltsUo Peak % 205V204 MMI,RST Recorded data1 0.0...120.0 % Un 0 Read Retain Uo peak in percents

100207 / Rev E MEPE7Power direction 207V1 MMI,RST Control setting 0..1[0 = Forward; 1= Reverse] - 0 Rd/Wr Retain Direction of power flowDemand interval 207V2 MMI,RST Control setting 0..5[0 = 1 min; 1 = 5 min; 2 = 10 min; 3 = 15 min; 4 = 30

min; 5 = 60 min]- 3 Rd/Wr Retain Time interval for demand supervision

Energy interval 207V3 MMI,RST Control setting 0..6[0 = 1 min; 1 = 5 min; 2 = 10 min; 3 = 15 min; 4 = 30 min; 5 = 60 min; 6 = 120 min]

- 3 Rd/Wr Retain Time interval for energy calculation

Page 143 of 158

Page 144: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Threshold select 207V4 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.; 3 = Time interval]

- 0 Rd/Wr Retain Selection of threshold supervision algorithm

P3 threshold 207V5 MMI,RST Control setting 1...999999 kW 999999 Rd/Wr Retain Threshold value for active powerQ3 threshold 207V6 MMI,RST Control setting 1...999999 kvar 999999 Rd/Wr Retain Threshold value for reactive powerP3 limit select. 207V7 MMI,RST Control setting 0..8[0 = Not in use; 1 = HW,HA,LW,LA; 2 = HW,HA; 3

= LW,LA; 4 = HW,LW; 5 = HA,LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of active power limits to be monitored

Q3 limit select. 207V8 MMI,RST Control setting 0..8[0 = Not in use; 1 = HW,HA,LW,LA; 2 = HW,HA; 3 = LW,LA; 4 = HW,LW; 5 = HA,LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of reactive power limits to be monitored

P3 high warning 207V9 MMI,RST Control setting -999999...999999 kW 0 Rd/Wr Retain High warning limit value for active powerP3 high alarm 207V10 MMI,RST Control setting -999999...999999 kW 0 Rd/Wr Retain High alarm limit value for active powerP3 low warning 207V11 MMI,RST Control setting -999999...999999 kW 0 Rd/Wr Retain Low warning limit value for active powerP3 low alarm 207V12 MMI,RST Control setting -999999...999999 kW 0 Rd/Wr Retain Low alarm limit value for active powerQ3 high warning 207V13 MMI,RST Control setting -999999...999999 kvar 0 Rd/Wr Retain High warning limit value for reactive powerQ3 high alarm 207V14 MMI,RST Control setting -999999...999999 kvar 0 Rd/Wr Retain High alarm limit value for reactive powerQ3 low warning 207V15 MMI,RST Control setting -999999...999999 kvar 0 Rd/Wr Retain Low warning limit value for reactive powerQ3 low alarm 207V16 MMI,RST Control setting -999999...999999 kvar 0 Rd/Wr Retain Low alarm limit value for reactive powerEnergy meas. 207V17 MMI,RST Control setting 0..1[0 = No energy reg.; 1 = Energy reg. on] - 0 Rd/Wr Retain Parameter for enable energy measurement and registrationMEPEmode 207V18 MMI,RST Control setting 0..13[0 = Not in use; 1= U1,U2,U3 & I1,I2,I3; 2 =

U12,U23,U0 & I1,I2,I3; 3 = U23,U31,U0 & I1,I2,I3; 4 = U12,U31,U0 & I1,I2,I3; 5 = U12,U23 & I1,I2,I3; 6 = U23,U31 & I1,I2,I3; 7 = U12,U31 & I1,I2,I3; 8 = U1 & I1; 9 = U2 & I2; 10 = U3 & I3; 11 = U12 & I3; 12 = U23 & I1; 13 = U31 & I2]

- 0 Read Volatile Power measurement mode

Time interval 207V19 MMI,RST Control setting 1...600 s 1 Rd/Wr Retain Time interval for threshold supervisionPF Threshold 207V20 MMI,RST Control setting 0.01...0.50 - 0,5 Rd/Wr Retain Threshold value for power factorEvent mask 1 207V101 MMI,RST Control setting 0...2863333375 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E31)Event mask 2 207V103 MMI,RST Control setting 0...2863333375 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E31)Event mask 3 207V105 MMI,RST Control setting 0...2863333375 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E31)Event mask 4 207V107 MMI,RST Control setting 0...2863333375 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E31)P3 (kW) 207I1 MMI,RST Input data -999999...999999 kW 0 Read Volatile 3-phase active powerQ3 (kvar) 207I2 MMI,RST Input data -999999...999999 kvar 0 Read Volatile 3-phase reactive powerPower factor DPF 207I3 MMI,RST Input data -1.00...1.00 - 0 Read Volatile Displacement power factor cos(j)Power factor PF 207I4 MMI,RST Input data -1.00...1.00 - 0 Read Volatile Power factorP3 demand (kW) 207I5 MMI,RST Input data -999999...999999 kW 0 Read Volatile Active power demandQ3 demand (kvar) 207I6 MMI,RST Input data -999999...999999 kvar 0 Read Volatile Reactive power demandInput RESET 207I7 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting demand values and registers of MEPE7P3 Maximum Date 207V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of P3 max demandP3 Maximum Time 207V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of P3 max demandP3 Maximum 207V203 MMI,RST Recorded data1 -999999...999999 kW -999999 Read Retain Maximum demand for P3Q3 Maximum Date 207V204 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of Q3 max demandQ3 Maximum Time 207V205 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of Q3 max demandQ3 Maximum 207V206 MMI,RST Recorded data1 -999999...999999 kvar -999999 Read Retain Maximum demand for Q3Energy kWh 207V207 MMI,RST Recorded data1 0...999999999 kWh 0 Read Retain Active energy in kWh (Accumulated)Reverse kWh 207V208 MMI,RST Recorded data1 0...999999999 kWh 0 Read Retain Reversed active energy in kWh (Accumulated)Energy kvarh 207V209 MMI,RST Recorded data1 0...999999999 kvarh 0 Read Retain Reactive energy in kvarh (Accumulated)Reverse kvarh 207V210 MMI,RST Recorded data1 0...999999999 kvarh 0 Read Retain Reversed reactive energy in kvarh (Accumulated)Ener. kWh (1) 207V211 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)

Page 144 of 158

Page 145: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Ener. kWh (2) 207V212 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (3) 207V213 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (4) 207V214 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (5) 207V215 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (6) 207V216 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (7) 207V217 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (8) 207V218 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (9) 207V219 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (10) 207V220 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (11) 207V221 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (12) 207V222 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (13) 207V223 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (14) 207V224 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (15) 207V225 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (16) 207V226 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (17) 207V227 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (18) 207V228 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (19) 207V229 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (20) 207V230 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (21) 207V231 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (22) 207V232 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (23) 207V233 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (24) 207V234 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (25) 207V235 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (26) 207V236 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (27) 207V237 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (28) 207V238 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (29) 207V239 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (30) 207V240 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (31) 207V241 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (32) 207V242 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (33) 207V243 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (34) 207V244 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (35) 207V245 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (36) 207V246 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (37) 207V247 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (38) 207V248 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (39) 207V249 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (40) 207V250 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (41) 207V251 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (42) 207V252 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (43) 207V253 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (44) 207V254 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (45) 207V255 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (46) 207V256 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (47) 207V257 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (48) 207V258 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (49) 207V259 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)Ener. kWh (50) 207V260 RST Recorded data2 0...999999 kWh 0 Read Volatile Active energy in kWh (50 latest)

Page 145 of 158

Page 146: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Rev. kWh (1) 207V261 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (2) 207V262 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (3) 207V263 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (4) 207V264 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (5) 207V265 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (6) 207V266 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (7) 207V267 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (8) 207V268 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (9) 207V269 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (10) 207V270 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (11) 207V271 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (12) 207V272 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (13) 207V273 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (14) 207V274 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (15) 207V275 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (16) 207V276 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (17) 207V277 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (18) 207V278 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (19) 207V279 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (20) 207V280 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (21) 207V281 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (22) 207V282 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (23) 207V283 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (24) 207V284 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (25) 207V285 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (26) 207V286 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (27) 207V287 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (28) 207V288 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (29) 207V289 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (30) 207V290 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (31) 207V291 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (32) 207V292 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (33) 207V293 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (34) 207V294 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (35) 207V295 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (36) 207V296 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (37) 207V297 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (38) 207V298 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (39) 207V299 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (40) 207V300 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (41) 207V301 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (42) 207V302 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (43) 207V303 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (44) 207V304 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (45) 207V305 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (46) 207V306 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (47) 207V307 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (48) 207V308 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Rev. kWh (49) 207V309 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)

Page 146 of 158

Page 147: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Rev. kWh (50) 207V310 RST Recorded data3 0...999999 kWh 0 Read Volatile Reversed active energy in kWh (50 latest)Ener. kvarh (1) 207V311 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (2) 207V312 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (3) 207V313 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (4) 207V314 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (5) 207V315 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (6) 207V316 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (7) 207V317 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (8) 207V318 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (9) 207V319 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (10) 207V320 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (11) 207V321 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (12) 207V322 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (13) 207V323 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (14) 207V324 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (15) 207V325 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (16) 207V326 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (17) 207V327 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (18) 207V328 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (19) 207V329 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (20) 207V330 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (21) 207V331 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (22) 207V332 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (23) 207V333 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (24) 207V334 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (25) 207V335 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (26) 207V336 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (27) 207V337 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (28) 207V338 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (29) 207V339 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (30) 207V340 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (31) 207V341 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (32) 207V342 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (33) 207V343 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (34) 207V344 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (35) 207V345 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (36) 207V346 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (37) 207V347 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (38) 207V348 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (39) 207V349 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (40) 207V350 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (41) 207V351 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (42) 207V352 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (43) 207V353 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (44) 207V354 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (45) 207V355 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (46) 207V356 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (47) 207V357 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (48) 207V358 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)

Page 147 of 158

Page 148: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Ener. kvarh (49) 207V359 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Ener. kvarh (50) 207V360 RST Recorded data4 0...999999 kvarh 0 Read Volatile Reactive energy in kvarh (50 latest)Rev. kvarh (1) 207V361 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (2) 207V362 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (3) 207V363 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (4) 207V364 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (5) 207V365 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (6) 207V366 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (7) 207V367 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (8) 207V368 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (9) 207V369 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (10) 207V370 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (11) 207V371 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (12) 207V372 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (13) 207V373 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (14) 207V374 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (15) 207V375 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (16) 207V376 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (17) 207V377 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (18) 207V378 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (19) 207V379 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (20) 207V380 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (21) 207V381 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (22) 207V382 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (23) 207V383 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (24) 207V384 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (25) 207V385 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (26) 207V386 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (27) 207V387 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (28) 207V388 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (29) 207V389 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (30) 207V390 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (31) 207V391 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (32) 207V392 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (33) 207V393 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (34) 207V394 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (35) 207V395 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (36) 207V396 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (37) 207V397 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (38) 207V398 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (39) 207V399 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (40) 207V400 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (41) 207V401 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (42) 207V402 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (43) 207V403 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (44) 207V404 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (45) 207V405 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (46) 207V406 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (47) 207V407 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)

Page 148 of 158

Page 149: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Rev. kvarh (48) 207V408 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (49) 207V409 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Rev. kvarh (50) 207V410 RST Recorded data5 0...999999 kvarh 0 Read Volatile Rev. reactive energy in kvarh (50 latest)Last save Date 207V411 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of last registered energy valuesLast save Time 207V412 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of last registered energy valuesLast save Pos. 207V413 RST Recorded data1 0...50 - 0 Read Volatile Position of last registered energy values (1...50, 0=No

registered values)Last Ener. kWh 207V414 MMI,RST Recorded data1 0...999999 - 0 Read Retain Last registered active energyLast Rev. kWh 207V415 MMI,RST Recorded data1 0...999999 - 0 Read Retain Last registered reversed active energy Last Ener. kvarh 207V416 MMI,RST Recorded data1 0...999999 - 0 Read Retain Last registered reactive energy Last Rev. kvarh 207V417 MMI,RST Recorded data1 0...999999 - 0 Read Retain Last registered reversed reactive energy Reset flag 207V418 RST Recorded data1 0..1[0 = Valid; 1 = Invalid] - 1 Read Volatile Indication of valid energy history; 0= All values valid, 1=

'Last save Pos.' values valid100208 / Rev C MEFR1

Average interval 208V1 MMI,RST Control setting 0..5[0 = 1 min; 1 = 5 min; 2 = 10 min; 3 = 15 min; 4 = 30 min; 5 = 60 min]

- 1 Rd/Wr Retain Time interval for average supervision

Threshold select 208V2 MMI,RST Control setting 0..2[0 = Not in use; 1= Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 208V3 MMI,RST Control setting 0.01...5.00 Hz 0,1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 208V4 MMI,RST Control setting 0..9[0 = Not in use; 1= HW,HA,LW,LA; 2 = HW,HA; 3

= LW,LA; 4 = HW,LW; 5 = HA,LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of monitored limits

High warning 208V5 MMI,RST Control setting 15.00...75.00 Hz 55 Rd/Wr Retain High warning limit valueHigh alarm 208V6 MMI,RST Control setting 15.00...75.00 Hz 60 Rd/Wr Retain High alarm limit valueLow warning 208V7 MMI,RST Control setting 10.00...60.00 Hz 45 Rd/Wr Retain Low warning limit valueLow alarm 208V8 MMI,RST Control setting 10.00...60.00 Hz 40 Rd/Wr Retain Low alarm limit valueVoltage limit 208V9 MMI,RST Control setting 0.30...0.90 x Un 0,3 Rd/Wr Retain Undervoltage limit for blockingEvent mask 1 208V101 MMI,RST Control setting 0...767 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 208V103 MMI,RST Control setting 0...767 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 208V105 MMI,RST Control setting 0...767 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)Event mask 4 208V107 MMI,RST Control setting 0...767 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Frequency 208I1 MMI,RST Input data 10.00...75.00 Hz 0 Read Volatile System frequency in HertzsAverage Freq. 208I2 MMI,RST Input data 10.00...75.00 Hz 0 Read Volatile Average system frequency in HertzsVoltage U 208I3 MMI,RST Input data 0.0...2.0 x Un 0 Read Volatile Voltage UInput RESET 208I4 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting demand values and registers of MEFR1Freq Max Date 208V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of maximum average frequencyFreq Max Time 208V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of maximum average frequencyFrequency Max 208V203 MMI,RST Recorded data1 10.00...75.00 Hz 50 Read Retain Maximum average frequencyFreq Min Date 208V204 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Date of minimum average frequencyFreq Min Time 208V205 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Time of minimum average frequencyFrequency Min 208V206 MMI,RST Recorded data1 10.00...75.00 Hz 50 Read Retain Minimum average frequency

100213 / Rev A MEAI1Threshold select 213V001 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 213V002 MMI,RST Control setting 0...10.0000 - 1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 213V003 MMI,RST Control setting 0..9[0 = Not in use; 1 = HW, HA, LW, LA; 2 = HW, HA;

3 = LW, LA; 4 = HW, LW; 5 = HA, LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of monitored limits

High warning 213V004 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High warning limit valueHigh alarm 213V005 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High alarm limit valueLow warning 213V006 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low warning limit value

Page 149 of 158

Page 150: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Low alarm 213V007 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low alarm limit valueHW start delay 213V008 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high warning signalHW reset delay 213V009 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high warning signalHA start delay 213V010 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high alarm signalHA reset delay 213V011 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high alarm signalLW start delay 213V012 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low warning signalLW reset delay 213V013 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low warning signalLA start delay 213V014 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low alarm signalLA reset delay 213V015 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low alarm signalLimit hysteresis 213V016 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Hysteresis for limit supervisionMeasuring mode 213V017 MMI,RST Control setting 0..1[0 = DC; 1 = AC] - 0 Rd/Wr Retain Measurement modeZero force limit 213V018 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Zero value supervision thresholdEvent mask 1 213V101 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 213V103 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 213V105 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 213V107 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Input value 213I1 MMI,RST Input data -10000.00000...10000.00000 - 0 Read Volatile Measurement valueInput invalid 213I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input validity signalInput RESET 213I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting registers of MEAI1Max value date 213V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Maximum value dateMax value time 213V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Maximum value timeMaximum value 213V203 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Maximum valueMin value date 213V204 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Minimujm value dateMin value time 213V205 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Minimum value timeMinimum value 213V206 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Minimum value

100214 / Rev A MEAI2Threshold select 214V001 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 214V002 MMI,RST Control setting 0...10.0000 - 1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 214V003 MMI,RST Control setting 0..9[0 = Not in use; 1 = HW, HA, LW, LA; 2 = HW, HA;

3 = LW, LA; 4 = HW, LW; 5 = HA, LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of monitored limits

High warning 214V004 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High warning limit valueHigh alarm 214V005 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High alarm limit valueLow warning 214V006 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low warning limit valueLow alarm 214V007 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low alarm limit valueHW start delay 214V008 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high warning signalHW reset delay 214V009 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high warning signalHA start delay 214V010 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high alarm signalHA reset delay 214V011 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high alarm signalLW start delay 214V012 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low warning signalLW reset delay 214V013 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low warning signalLA start delay 214V014 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low alarm signalLA reset delay 214V015 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low alarm signalLimit hysteresis 214V016 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Hysteresis for limit supervisionMeasuring mode 214V017 MMI,RST Control setting 0..1[0 = DC; 1 = AC] - 0 Rd/Wr Retain Measurement modeZero force limit 214V018 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Zero value supervision thresholdEvent mask 1 214V101 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E9)Event mask 2 214V103 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E9)Event mask 3 214V105 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E9)

Page 150 of 158

Page 151: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 4 214V107 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E9)Input value 214I1 MMI,RST Input data -10000.00000...10000.00000 - 0 Read Volatile Measurement valueInput invalid 214I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input validity signalInput RESET 214I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting registers of MEAI2Max value date 214V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Maximum value dateMax value time 214V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Maximum value timeMaximum value 214V203 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Maximum valueMin value date 214V204 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Minimujm value dateMin value time 214V205 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Minimum value timeMinimum value 214V206 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Minimum value

100215 / Rev A MEAI3Threshold select 215V001 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 215V002 MMI,RST Control setting 0...10.0000 - 1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 215V003 MMI,RST Control setting 0..9[0 = Not in use; 1 = HW, HA, LW, LA; 2 = HW, HA;

3 = LW, LA; 4 = HW, LW; 5 = HA, LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of monitored limits

High warning 215V004 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High warning limit valueHigh alarm 215V005 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High alarm limit valueLow warning 215V006 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low warning limit valueLow alarm 215V007 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low alarm limit valueHW start delay 215V008 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high warning signalHW reset delay 215V009 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high warning signalHA start delay 215V010 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high alarm signalHA reset delay 215V011 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high alarm signalLW start delay 215V012 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low warning signalLW reset delay 215V013 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low warning signalLA start delay 215V014 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low alarm signalLA reset delay 215V015 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low alarm signalLimit hysteresis 215V016 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Hysteresis for limit supervisionMeasuring mode 215V017 MMI,RST Control setting 0..1[0 = DC; 1 = AC] - 0 Rd/Wr Retain Measurement modeZero force limit 215V018 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Zero value supervision thresholdEvent mask 1 215V101 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E911)Event mask 2 215V103 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 215V105 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 215V107 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Input value 215I1 MMI,RST Input data -10000.00000...10000.00000 - 0 Read Volatile Measurement valueInput invalid 215I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input validity signalInput RESET 215I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting registers of MEAI3Max value date 215V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Maximum value dateMax value time 215V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Maximum value timeMaximum value 215V203 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Maximum valueMin value date 215V204 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Minimujm value dateMin value time 215V205 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Minimum value timeMinimum value 215V206 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Minimum value

100216 / Rev A MEAI4Threshold select 216V001 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 216V002 MMI,RST Control setting 0...10.0000 - 1 Rd/Wr Retain Threshold value for threshold supervision

Page 151 of 158

Page 152: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Limit selection 216V003 MMI,RST Control setting 0..9[0 = Not in use; 1 = HW, HA, LW, LA; 2 = HW, HA; 3 = LW, LA; 4 = HW, LW; 5 = HA, LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of monitored limits

High warning 216V004 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High warning limit valueHigh alarm 216V005 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High alarm limit valueLow warning 216V006 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low warning limit valueLow alarm 216V007 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low alarm limit valueHW start delay 216V008 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high warning signalHW reset delay 216V009 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high warning signalHA start delay 216V010 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high alarm signalHA reset delay 216V011 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high alarm signalLW start delay 216V012 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low warning signalLW reset delay 216V013 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low warning signalLA start delay 216V014 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low alarm signalLA reset delay 216V015 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low alarm signalLimit hysteresis 216V016 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Hysteresis for limit supervisionMeasuring mode 216V017 MMI,RST Control setting 0..1[0 = DC; 1 = AC] - 0 Rd/Wr Retain Measurement modeZero force limit 216V018 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Zero value supervision thresholdEvent mask 1 216V101 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 216V103 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 216V105 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 216V107 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Input value 216I1 MMI,RST Input data -10000.00000...10000.00000 - 0 Read Volatile Measurement valueInput invalid 216I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input validity signalInput RESET 216I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting registers of MEAI4Max value date 216V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Maximum value dateMax value time 216V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Maximum value timeMaximum value 216V203 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Maximum valueMin value date 216V204 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Minimujm value dateMin value time 216V205 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Minimum value timeMinimum value 216V206 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Minimum value

100217 / Rev A MEAI5Threshold select 217V001 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 217V002 MMI,RST Control setting 0...10.0000 - 1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 217V003 MMI,RST Control setting 0..9[0 = Not in use; 1 = HW, HA, LW, LA; 2 = HW, HA;

3 = LW, LA; 4 = HW, LW; 5 = HA, LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of monitored limits

High warning 217V004 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High warning limit valueHigh alarm 217V005 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High alarm limit valueLow warning 217V006 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low warning limit valueLow alarm 217V007 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low alarm limit valueHW start delay 217V008 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high warning signalHW reset delay 217V009 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high warning signalHA start delay 217V010 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high alarm signalHA reset delay 217V011 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high alarm signalLW start delay 217V012 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low warning signalLW reset delay 217V013 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low warning signalLA start delay 217V014 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low alarm signalLA reset delay 217V015 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low alarm signal

Page 152 of 158

Page 153: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Limit hysteresis 217V016 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Hysteresis for limit supervisionMeasuring mode 217V017 MMI,RST Control setting 0..1[0 = DC; 1 = AC] - 0 Rd/Wr Retain Measurement modeZero force limit 217V018 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Zero value supervision thresholdEvent mask 1 217V101 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 217V103 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 217V105 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 217V107 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Input value 217I1 MMI,RST Input data -10000.00000...10000.00000 - 0 Read Volatile Measurement valueInput invalid 217I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input validity signalInput RESET 217I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting registers of MEAI5Max value date 217V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Maximum value dateMax value time 217V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Maximum value timeMaximum value 217V203 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Maximum valueMin value date 217V204 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Minimujm value dateMin value time 217V205 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Minimum value timeMinimum value 217V206 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Minimum value

100218 / Rev A MEAI6Threshold select 218V001 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 218V002 MMI,RST Control setting 0...10.0000 - 1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 218V003 MMI,RST Control setting 0..9[0 = Not in use; 1 = HW, HA, LW, LA; 2 = HW, HA;

3 = LW, LA; 4 = HW, LW; 5 = HA, LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of monitored limits

High warning 218V004 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High warning limit valueHigh alarm 218V005 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High alarm limit valueLow warning 218V006 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low warning limit valueLow alarm 218V007 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low alarm limit valueHW start delay 218V008 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high warning signalHW reset delay 218V009 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high warning signalHA start delay 218V010 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high alarm signalHA reset delay 218V011 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high alarm signalLW start delay 218V012 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low warning signalLW reset delay 218V013 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low warning signalLA start delay 218V014 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low alarm signalLA reset delay 218V015 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low alarm signalLimit hysteresis 218V016 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Hysteresis for limit supervisionMeasuring mode 218V017 MMI,RST Control setting 0..1[0 = DC; 1 = AC] - 0 Rd/Wr Retain Measurement modeZero force limit 218V018 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Zero value supervision thresholdEvent mask 1 218V101 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 218V103 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 218V105 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 218V107 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Input value 218I1 MMI,RST Input data 10000.00000...10000.00000 - 0 Read Volatile Measurement valueInput invalid 218I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input validity signalInput RESET 218I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting registers of MEAI6Max value date 218V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Maximum value dateMax value time 218V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Maximum value timeMaximum value 218V203 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Maximum valueMin value date 218V204 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Minimujm value dateMin value time 218V205 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Minimum value time

Page 153 of 158

Page 154: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Minimum value 218V206 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Minimum value100219 / Rev A MEAI7

Threshold select 219V001 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 219V002 MMI,RST Control setting 0...10.0000 - 1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 219V003 MMI,RST Control setting 0..9[0 = Not in use; 1 = HW, HA, LW, LA; 2 = HW, HA;

3 = LW, LA; 4 = HW, LW; 5 = HA, LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of monitored limits

High warning 219V004 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High warning limit valueHigh alarm 219V005 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High alarm limit valueLow warning 219V006 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low warning limit valueLow alarm 219V007 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low alarm limit valueHW start delay 219V008 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high warning signalHW reset delay 219V009 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high warning signalHA start delay 219V010 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high alarm signalHA reset delay 219V011 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high alarm signalLW start delay 219V012 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low warning signalLW reset delay 219V013 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low warning signalLA start delay 219V014 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low alarm signalLA reset delay 219V015 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low alarm signalLimit hysteresis 219V016 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Hysteresis for limit supervisionMeasuring mode 219V017 MMI,RST Control setting 0..1[0 = DC; 1 = AC] - 0 Rd/Wr Retain Measurement modeZero force limit 219V018 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Zero value supervision thresholdEvent mask 1 219V101 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 219V103 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 219V105 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 219V107 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Input value 219I1 MMI,RST Input data -10000.00000...10000.00000 - 0 Read Volatile Measurement valueInput invalid 219I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input validity signalInput RESET 219I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting registers of MEAI7Max value date 219V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Maximum value dateMax value time 219V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Maximum value timeMaximum value 219V203 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Maximum valueMin value date 219V204 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Minimujm value dateMin value time 219V205 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Minimum value timeMinimum value 219V206 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Minimum value

100220 / Rev A MEAI8Threshold select 220V001 MMI,RST Control setting 0..2[0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.] - 0 Rd/Wr Retain Selection of threshold supervision algorithmThreshold value 220V002 MMI,RST Control setting 0...10.0000 - 1 Rd/Wr Retain Threshold value for threshold supervisionLimit selection 220V003 MMI,RST Control setting 0..9[0 = Not in use; 1 = HW, HA, LW, LA; 2 = HW, HA;

3 = LW, LA; 4 = HW, LW; 5 = HA, LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA]

- 0 Rd/Wr Retain Selection of monitored limits

High warning 220V004 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High warning limit valueHigh alarm 220V005 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain High alarm limit valueLow warning 220V006 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low warning limit valueLow alarm 220V007 MMI,RST Control setting -10000.00000...10000.00000 - 0 Rd/Wr Retain Low alarm limit valueHW start delay 220V008 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high warning signalHW reset delay 220V009 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high warning signalHA start delay 220V010 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the high alarm signalHA reset delay 220V011 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the high alarm signal

Page 154 of 158

Page 155: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

LW start delay 220V012 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low warning signalLW reset delay 220V013 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low warning signalLA start delay 220V014 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Starting delay of the low alarm signalLA reset delay 220V015 MMI,RST Control setting 1.0..300.0 s 1 Rd/Wr Retain Resetting delay of the low alarm signalLimit hysteresis 220V016 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Hysteresis for limit supervisionMeasuring mode 220V017 MMI,RST Control setting 0..1[0 = DC; 1 = AC] - 0 Rd/Wr Retain Measurement modeZero force limit 220V018 MMI,RST Control setting 0...10.0000 - 0 Rd/Wr Retain Zero value supervision thresholdEvent mask 1 220V101 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E11)Event mask 2 220V103 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E11)Event mask 3 220V105 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E11)Event mask 4 220V107 MMI,RST Control setting 0...4095 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E11)Input value 220I1 MMI,RST Input data -10000.00000...10000.00000 - 0 Read Volatile Measurement valueInput invalid 220I2 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Input validity signalInput RESET 220I3 MMI,RST Input data 0..1[0 = Not active; 1 = Active] - 0 Read Volatile Signal for resetting registers of MEAI8Max value date 220V201 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Maximum value dateMax value time 220V202 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Maximum value timeMaximum value 220V203 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Maximum valueMin value date 220V204 MMI,RST Recorded data1 YYYY-MM-DD - - Read Retain Minimujm value dateMin value time 220V205 MMI,RST Recorded data1 hh:mm:ss.000 - - Read Retain Minimum value timeMinimum value 220V206 MMI,RST Recorded data1 -100000.000000 ... 100000.000000 - 0 Read Retain Minimum value

100225 / Rev G MEDREC16Periodic time 225V1 MMI,RST Trg settings 0...604800 s 0 Rd/Wr Retain Time between periodic triggeringsExclusion time 225V2 MMI,RST Control setting 0...86400 s 0 Rd/Wr Retain Time how long triggerings from same reason ar ignoredOperation mode 225V3 MMI,RST Control setting 0..2 [0 = Saturation; 1 = Overwrite; 2 = Extension] - 0 Rd/Wr Retain Operation mode of the recorderPre-trg time 225V5 MMI,RST Control setting 0...100 % 50 Rd/Wr Retain Length of record preceding the triggeringBI enable 225V6 MMI,RST Trg settings 0...65535 - 0 Rd/Wr Retain Binary channel triggering enable bit maskBI mode 225V7 MMI,RST Trg settings 0...65535 - 0 Rd/Wr Retain Binary channel triggering mode bit maskOver lim. enab. 225V8 MMI,RST Trg settings 0...65535 - 0 Rd/Wr Retain Analog channel over limit triggering bit maskUnder lim. enab 225V9 MMI,RST Trg settings 0...65535 - 0 Rd/Wr Retain Analog channel under limit triggering bit maskOver limit ILx 225V10 MMI,RST Trg limits 0.00...40.00 x In 10 Rd/Wr Retain Over limit for IL1, IL2 and IL3Over limit Io 225V11 MMI,RST Trg limits 0.00...40.00 x In 10 Rd/Wr Retain Over limit for IoOver limit Iob 225V12 MMI,RST Trg limits 0.00...40.00 x In 10 Rd/Wr Retain Over limit for IobOver limit Uo 225V13 MMI,RST Trg limits 0.00...2.00 x Un 2 Rd/Wr Retain Over limit for UoOver limit Ux 225V14 MMI,RST Trg limits 0.00...2.00 x Un 2 Rd/Wr Retain Over limit for U1, U2 and U3Over limit Uxy 225V15 MMI,RST Trg limits 0.00...2.00 x Un 2 Rd/Wr Retain Over limit for U12, U23 and U31Over limit U12b 225V16 MMI,RST Trg limits 0.00...2.00 x Un 2 Rd/Wr Retain Over limit for U12bOver limit ILxb 225V17 MMI,RST Trg limits 0.00...40.00 x In 10 Rd/Wr Retain Over limit for IL1b, IL2b and IL3bUnder limit Ux 225V18 MMI,RST Trg limits 0.00...2.00 x Un 0 Rd/Wr Retain Under limit for U1, U2 and U3Under limit Uxy 225V19 MMI,RST Trg limits 0.00...2.00 x Un 0 Rd/Wr Retain Under limit for U12, U23 and U31AI filter time 225V20 MMI,RST Trg settings 0.000...60.000 s 0,05 Rd/Wr Retain Filtering time for analogue channel limit triggeringsHeader file 225V30 Internal Control setting - - - Read Volatile LON file object for recording headerData file 225V31 Internal Control setting - - - Read Volatile LON file object for recording dataTransfer data va 225V32 Internal Control setting 0...1 - 0 Read Volatile Tells to the upload SW that the data is valid in transfer

bufferTransfer data lo 225V33 Internal Control setting 0...1 - 0 Write Volatile The upload SW tells to the FB that it is not allowed to

write to the transfer bufferEvent mask 1 225V101 MMI,RST Event masks 0...2147483691 - 2147483691 Rd/Wr Retain Event mask 1 for event transmissionEvent mask 2 225V103 MMI,RST Event masks 0...2147483691 - 2147483691 Rd/Wr Retain Event mask 2 for event transmissionEvent mask 3 225V105 MMI,RST Event masks 0...2147483691 - 2147483691 Rd/Wr Retain Event mask 3 for event transmission

Page 155 of 158

Page 156: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Event mask 4 225V107 MMI,RST Event masks 0...2147483691 - 2147483691 Rd/Wr Retain Event mask 4 for event transmissionRecorder channel 0M10 Internal Control setting - - 225 Read Volatile Channel number of the internal disturbance recorderData format 225M12 Internal Control setting - - 2 Read Volatile Data format of the recordingTransfer format 225M17 Internal Control setting - - 0 Read Volatile The protocol of the file transmissionRemote trigger 225M1 MMI,RST Control setting 0..1 [0 = 0; 1 = Trigger] - 0 Write Volatile Remote triggeringReset memory 225M2 MMI,RST Control setting 0..1 [0 = 0; 1 = Reset] - 0 Write Volatile Resetting of recording memoryRecord length 225M11 MMI,RST Control setting 10...65535 cyc. 50 Rd/Wr Retain Size of the recording memory in cyclesMax # records 225M3 MMI,RST Control setting 0...65535 - 0 Read Volatile Maximum number of recordings# records 225M16 MMI,RST Control setting 0...65535 - 0 Read Volatile Number of recordings in memoryAI chs used 225M13 MMI,RST General info 0...65535 - 65535 Rd/Wr Retain Bit mask of recorded analog channelsBI chs used 225M14 MMI,RST General info 0...65535 - 65535 Read Volatile Bit mask of recorded binary channelsSampling rate 225M15 MMI,RST General info 400...2400 Hz 2000 Read Volatile Sampling frequency (Hz)Line frequency 225M19 MMI,RST General info 10.00...60.00 Hz 50 Read Volatile Nominal system frequencyIdentification 225M18 MMI,RST General info 0...10000 - 0 Rd/Wr Retain Station identification or unit numberMain header 225M20 MMI,RST General info Default header - Default header Rd/Wr Retain Main header for recordingsText of BI1 225M40 MMI,RST BI texts BI1 - BI1 Rd/Wr Retain Text of binary input BI1Text of BI2 225M41 MMI,RST BI texts BI2 - BI2 Rd/Wr Retain Text of binary input BI2Text of BI3 225M42 MMI,RST BI texts BI3 - BI3 Rd/Wr Retain Text of binary input BI3Text of BI4 225M43 MMI,RST BI texts BI4 - BI4 Rd/Wr Retain Text of binary input BI4Text of BI5 225M44 MMI,RST BI texts BI5 - BI5 Rd/Wr Retain Text of binary input BI5Text of BI6 225M45 MMI,RST BI texts BI6 - BI6 Rd/Wr Retain Text of binary input BI6Text of BI7 225M46 MMI,RST BI texts BI7 - BI7 Rd/Wr Retain Text of binary input BI7Text of BI8 225M47 MMI,RST BI texts BI8 - BI8 Rd/Wr Retain Text of binary input BI8Text of BI9 225M48 MMI,RST BI texts BI9 - BI9 Rd/Wr Retain Text of binary input BI9Text of BI10 225M49 MMI,RST BI texts BI10 - BI10 Rd/Wr Retain Text of binary input BI10Text of BI11 225M50 MMI,RST BI texts BI11 - BI11 Rd/Wr Retain Text of binary input BI11Text of BI12 225M51 MMI,RST BI texts BI12 - BI12 Rd/Wr Retain Text of binary input BI12Text of BI13 225M52 MMI,RST BI texts BI13 - BI13 Rd/Wr Retain Text of binary input BI13Text of BI14 225M53 MMI,RST BI texts BI14 - BI14 Rd/Wr Retain Text of binary input BI14Text of BI15 225M54 MMI,RST BI texts BI15 - BI15 Rd/Wr Retain Text of binary input BI15Text of BI16 225M55 MMI,RST BI texts BI16 - BI16 Rd/Wr Retain Text of binary input BI16Text of AI1 225M60 MMI,RST AI texts IL1 - IL1 Read Volatile Text of analog input channel 1 (IL1)Text of AI2 225M61 MMI,RST AI texts IL2 - IL2 Read Volatile Text of analog input channel 2 (IL2)Text of AI3 225M62 MMI,RST AI texts IL3 - IL3 Read Volatile Text of analog input channel 3 (IL3)Text of AI4 225M63 MMI,RST AI texts Io - Io Read Volatile Text of analog input channel 4 (Io)Text of AI5 225M64 MMI,RST AI texts Iob - Iob Read Volatile Text of analog input channel 5 (Iob)Text of AI6 225M65 MMI,RST AI texts Uo - Uo Read Volatile Text of analog input channel 6 (Uo)Text of AI7 225M66 MMI,RST AI texts U1 - U1 Read Volatile Text of analog input channel 7 (U1)Text of AI8 225M67 MMI,RST AI texts U2 - U2 Read Volatile Text of analog input channel 8 (U2)Text of AI9 225M68 MMI,RST AI texts U3 - U3 Read Volatile Text of analog input channel 9 (U3)Text of AI10 225M69 MMI,RST AI texts U12 - U12 Read Volatile Text of analog input channel 10 (U12)Text of AI11 225M70 MMI,RST AI texts U23 - U23 Read Volatile Text of analog input channel 11 (U23)Text of AI12 225M71 MMI,RST AI texts U31 - U31 Read Volatile Text of analog input channel 12 (U31)Text of AI13 225M72 MMI,RST AI texts U12b - U12b Read Volatile Text of analog input channel 13 (U12b)Text of AI14 225M73 MMI,RST AI texts IL1b - IL1b Read Volatile Text of analog input channel 14 (IL1b)Text of AI15 225M74 MMI,RST AI texts IL2b - IL2b Read Volatile Text of analog input channel 15 (IL2b)Text of AI16 225M75 MMI,RST AI texts IL3b - IL3b Read Volatile Text of analog input channel 16 ((IL3b)IL1 pu-scale 225M80 Internal Control setting 0...6000 A 1 Read Volatile Conversion factor for IL1 from pu to AIL2 pu-scale 225M81 Internal Control setting 0...6000 A 1 Read Volatile Conversion factor for IL2 from pu to A

Page 156 of 158

Page 157: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

IL3 pu-scale 225M82 Internal Control setting 0...6000 A 1 Read Volatile Conversion factor for IL3 from pu to AIo pu-scale 225M83 Internal Control setting 0...6000 A 1 Read Volatile Conversion factor for Io from pu to AIob pu-scale 225M84 Internal Control setting 0...6000 A 1 Read Volatile Conversion factor for Iob from pu to AUo pu-scale 225M85 Internal Control setting 0...440.000 kV 1 Read Volatile Conversion factor for Uo from pu to kVU1 pu-scale 225M86 Internal Control setting 0...440.000 kV 1 Read Volatile Conversion factor for U1 from pu to kVU2 pu-scale 225M87 Internal Control setting 0...440.000 kV 1 Read Volatile Conversion factor for U2 from pu to kVU3 pu-scale 225M88 Internal Control setting 0...440.000 kV 1 Read Volatile Conversion factor for U3 from pu to kVU12 pu-scale 225M89 Internal Control setting 0...440.000 kV 1 Read Volatile Conversion factor for U12 from pu to kVU23 pu-scale 225M90 Internal Control setting 0...440.000 kV 1 Read Volatile Conversion factor for U23 from pu to kVU31 pu-scale 225M91 Internal Control setting 0...440.000 kV 1 Read Volatile Conversion factor for U31 from pu to kVU12b pu-scale 225M92 Internal Control setting 0...440.000 kV 1 Read Volatile Conversion factor for U12b from pu to kVIL1b pu-scale 225M93 Internal Control setting 0...6000 A 1 Read Volatile Conversion factor for IL1b from pu to AIL2b pu-scale 225M94 Internal Control setting 0...6000 A 1 Read Volatile Conversion factor for IL2b from pu to AIL3b pu-scale 225M95 Internal Control setting 0...6000 A 1 Read Volatile Conversion factor for IL3b from pu to AConv. factor uni 225M100 Internal Control setting 0...65535 - 57375 Read Volatile Units of the conversion factors of each analog channel, bit

mask, 0 = kV, 1 = ATime to trigger 225O1 MMI,RST Output data 0...604800 s 0 Read Volatile Remaining time of periodic triggeringExclusion time 225O2 MMI,RST Output data 0...86400 s 0 Read Volatile Remaining time of exclusion time

100230 / Rev B EVENT230Event mask 1A 230V101 MMI,RST Control setting 0...4294967295 - 0 Rd/Wr Retain Event mask 1 for event transmission (E0 ... E31)Event mask 1B 230V102 MMI,RST Control setting 0...4294967295 - 0 Rd/Wr Retain Event mask 1 for event transmission (E32 ... E63)Event mask 2A 230V103 MMI,RST Control setting 0...4294967295 - 0 Rd/Wr Retain Event mask 2 for event transmission (E0 ... E31)Event mask 2B 230V104 MMI,RST Control setting 0...4294967295 - 0 Rd/Wr Retain Event mask 2 for event transmission (E32 ... E63)Event mask 3A 230V105 MMI,RST Control setting 0...4294967295 - 0 Rd/Wr Retain Event mask 3 for event transmission (E0 ... E31)Event mask 3B 230V106 MMI,RST Control setting 0...4294967295 - 0 Rd/Wr Retain Event mask 3 for event transmission (E32 ... E63)Event mask 4A 230V107 MMI,RST Control setting 0...4294967295 - 0 Rd/Wr Retain Event mask 4 for event transmission (E0 ... E31)Event mask 4B 230V108 MMI,RST Control setting 0...4294967295 - 0 Rd/Wr Retain Event mask 4 for event transmission (E32 ... E63)

100456 / Rev A MEAO1Output range 456V001 MMI,RST Control setting 0..1[0 = 0..20; 1 = 4..20] mA 0 Rd/Wr Retain Output rangeThreshold value 456V002 MMI,RST Control setting 0.01..1.00 - 1 Rd/Wr Retain Threshold value for threshold supervisionInput low limit 456V003 MMI,RST Control setting -10000.00000..10000.00000 - 0 Rd/Wr Retain Input low limitInput high limit 456V004 MMI,RST Control setting -10000.00000..10000.00000 - 1 Rd/Wr Retain Input high limitOutput value 456O001 MMI,RST Output data 0.00...20.00 mA 0 Read Volatile Output value

100457 / Rev A MEAO2Output range 457V001 MMI,RST Control setting 0..1[0 = 0..20; 1 = 4..20] mA 0 Rd/Wr Retain Output rangeThreshold value 457V002 MMI,RST Control setting 0.01..1.00 - 1 Rd/Wr Retain Threshold value for threshold supervisionInput low limit 457V003 MMI,RST Control setting -10000.00000..10000.00000 - 0 Rd/Wr Retain Input low limitInput high limit 457V004 MMI,RST Control setting -10000.00000..10000.00000 - 1 Rd/Wr Retain Input high limitOutput value 457O001 MMI,RST Output data 0.00...20.00 mA 0 Read Volatile Output value

100458 / Rev A MEAO3Output range 458V001 MMI,RST Control setting 0..1[0 = 0..20; 1 = 4..20] mA 0 Rd/Wr Retain Output rangeThreshold value 458V002 MMI,RST Control setting 0.01..1.00 - 1 Rd/Wr Retain Threshold value for threshold supervisionInput low limit 458V003 MMI,RST Control setting -10000.00000..10000.00000 - 0 Rd/Wr Retain Input low limitInput high limit 458V004 MMI,RST Control setting -10000.00000..10000.00000 - 1 Rd/Wr Retain Input high limitOutput value 458O001 MMI,RST Output data 0.00...20.00 mA 0 Read Volatile Output value

100459 / Rev A MEAO4Output range 459V001 MMI,RST Control setting 0..1[0 = 0..20; 1 = 4..20] mA 0 Rd/Wr Retain Output rangeThreshold value 459V002 MMI,RST Control setting 0.01..1.00 - 1 Rd/Wr Retain Threshold value for threshold supervisionInput low limit 459V003 MMI,RST Control setting -10000.00000..10000.00000 - 0 Rd/Wr Retain Input low limit

Page 157 of 158

Page 158: Parameter List for REM 543 and REM 545 Document ID: … · 2018. 5. 9. · ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004 Parameter List for

ABB Oy Distribution Automation Parameter List for REM 543 and REM 545 August 25 2004Module Parameter Code Visiblity Menu Value range Unit Default Access Volatile Explanation

Input high limit 459V004 MMI,RST Control setting -10000.00000..10000.00000 - 1 Rd/Wr Retain Input high limitOutput value 459O001 MMI,RST Output data 0.00..20.00 mA 0 Read Volatile Output value