 THOMAS DOUGLAS Architects Inc 196 Pleasant Street Northampton, MA 01060 phone: 413.585.0641 To: Louis Hasbrouck Delivery:  Fax: Phone: From:  Tom Douglas Date: 12/23/10 Re:  Paradise Tavern Pages:  1 floor plan Urgent  x  For Review  Please Comment  Please Reply  As Requested  Paradise Tavern Review, One Bridge Street, Northampton, MA Code: 7 th addition MA Building code, CMR 780 Constructi on type: 5B The building is fully sprinkled Allowable height and area: 2 stories, 18,000 square feet (506.3 and 504.2) (facility meets minimum requirements) Maximum travel distance (A use, sprinkled): 250 feet (facility meets minimum requirements) Existing use: A2r Restaurant Requested change (if code requirements are met): A2nc Night Club Maximum occupancy calculated: 1. By existing seat count: First floor: 86 seats existing Basement floor: 20 seats existing Total: 86 + 20 = 106 occupants

Transcript of Paradise City Tavern Compliance with State Building Code Northampton MA

Page 1: Paradise City Tavern Compliance with State Building Code Northampton MA

8/8/2019 Paradise City Tavern Compliance with State Building Code Northampton MA

http://slidepdf.com/reader/full/paradise-city-tavern-compliance-with-state-building-code-northampton-ma 1/4

 

T H O M A S D O U G L A S

Arch i tects Inc 196 Pleasant Street Northampton, MA 01060phone: 413.585.0641

To:  Louis Hasbrouck  Delivery: Fax:

Phone:

From: Tom Douglas  Date:  12/23/10 

Re:  Paradise Tavern  Pages:  1 floor plan 

Urgent  x  For 

Review Please

Comment  PleaseReply  As

Requested 

Paradise Tavern Review, One Bridge Street, Northampton, MACode: 7th addition MA Building code, CMR 780Construction type: 5BThe building is fully sprinkled

Allowable height and area:2 stories, 18,000 square feet (506.3 and 504.2) (facility meets minimumrequirements)

Maximum travel distance (A use, sprinkled): 250 feet (facility meets minimumrequirements)

Existing use: A2r RestaurantRequested change (if code requirements are met): A2nc Night Club

Maximum occupancy calculated:

1. By existing seat count:First floor: 86 seats existingBasement floor: 20 seats existingTotal: 86 + 20 = 106 occupants

Page 2: Paradise City Tavern Compliance with State Building Code Northampton MA

8/8/2019 Paradise City Tavern Compliance with State Building Code Northampton MA

http://slidepdf.com/reader/full/paradise-city-tavern-compliance-with-state-building-code-northampton-ma 2/4

 

T H O M A S D O U G L A S

Arch i tects Inc 196 Pleasant Street Northampton, MA 01060phone: 413.585.0641

2. By area: Maximum Floor Area Allowances (1004.1.2)First floor: 963 square feet

Basement floor: 381 square feet

• If occupancy is Assembly A2r without fixed seats, unconcentratedtables and chairs:First floor: 15 net s.f per person = 963/15 =64 occupantsBasement: With 1 means of egress, the occupancy is limited to 49Total: 64 + 49 = 113

• If occupancy is Assembly A2nc without fixed seats,First floor: standing space: 5 net s.f per person= 890 s.f/5 net s.f. per person = 178 occupants + 2 DJ performers =180Basement: With 1 means of egress, the occupancy is limited to 49(however, if furniture is stored here the occupancy would be further reduced)Total: 180 + 49 = 229

3. By egress capacity: Egress width per occupant served (1005.1)First floor Egress width required, with sprinkler system:.15 inches per occupant = 180 x .15 = 27 inches

• If the use is A2r, then egress width is a minimum of 36”• If the use is A2nc, then the egress width is a minimum of 72”.

The main entrance/exit door shall be a pair of side hingedswinging doors without a mullion equipped with panic hardware.(1024.1.1)

Basement floor Egress width required, with sprinkler system:.15 inches per occupant = 49 x .15 = 7.35 inches

• If the use is A2r, then egress width is a minimum of 36”• If the use is A2nc, then the egress width is a minimum of 72”.

• From the basement, the path of egress is less than 72” and does not meetthe requirements for A2nc.

• On the first floor, the existing front main entrance/exit door is 60” nominalwidth.

o This door meets the A2r requirements,o This door does not meet the A2nc requirements

• On the first floor, the existing rear egress door next to the bar is 72”. (two36” nominal width doors)

o This door meets the A2r and A2nc requirements.

Page 3: Paradise City Tavern Compliance with State Building Code Northampton MA

8/8/2019 Paradise City Tavern Compliance with State Building Code Northampton MA

http://slidepdf.com/reader/full/paradise-city-tavern-compliance-with-state-building-code-northampton-ma 3/4

 

T H O M A S D O U G L A S

Arch i tects Inc 196 Pleasant Street Northampton, MA 01060phone: 413.585.0641

4. By toilet fixture count:Existing toilets: 2 women (1 basement, 1 first floor- handicapped

accessible), 1 men (first floor- handicapped accessible)

• Maximum allowable occupant count for existing toilet fixtures:For A2r: 1/60 men = 1 fixture = maximum of 60 menFor A2r: 1/30 women = 2 fixtures = maximum of 60 womenMaximum occupancy for existing bathrooms: 120 occupants

• If the occupancy is based on existing seat counts for A2r :106 occupants /2 = 53 occupants each sex

Required fixture count for occupancy of 106:1/60 men = 53/60= 1 fixtures –meets requirements1/30 women = 53/30= 1.76 fixtures–meets requirements

• If the occupancy is based on area calculation for A2r :113 occupants on 1st floor + 49 occupants basement = 113 occupants/2 =57 occupants each sex

Required fixture count for occupancy of 113:1/60 men = 57/60= 1 fixtures –meets requirements1/30 women = 57/30= 3.1 fixtures–meets requirements

• If the occupancy is based on area calculation for A2nc:180 occupants on 1st floor + 49 occupants basement = 229 occupants/2 =115 occupants each sex

Required fixture count for occupancy of 229:1/50 men = 115/50= 2.3 fixtures – does not meet requirements1/30 women = 115/30= 3.8 fixtures– does not meet requirements

5. Additional occupants not included in occupant count:Employees:2 bartenders6 kitchen staff 5 wait staff 1 manager Total: 16

Page 4: Paradise City Tavern Compliance with State Building Code Northampton MA

8/8/2019 Paradise City Tavern Compliance with State Building Code Northampton MA

http://slidepdf.com/reader/full/paradise-city-tavern-compliance-with-state-building-code-northampton-ma 4/4

 

T H O M A S D O U G L A S

Arch i tects Inc 196 Pleasant Street Northampton, MA 01060phone: 413.585.0641

6. Synopsis:For existing A2r use and existing seat count (106): The facility meets theminimum requirements.

For existing A2r use and area calculation for occupancy (113): The facility meetsthe minimum requirements.

For proposed A2nc use and area calculation for occupancy (229): The facilitydoes not meet the minimum code requirements because of inadequate toiletfixture counts and inadequate egress (front door) width.The basement level has further limitations: The path of egress is less than 72”and does not meet the minimum requirements for A2nc

Section 1024.2 allows an exception to the Main Entrance/Exit Door width bystating that where multiple main exits are provided, exits shall be permitted to bedistributed around the perimeter of the building provided that the total width of egress in not less than 100% of the required width. This means that if there wereone more 36”wide door near the front entry (within clear view of the occupants)this additional egress width may satisfy the 12” wide deficit of the front mainentry/exit door. I believe the applicability of this exception should be at thediscretion of the building official.

End of Document