Panelboard and Switchboards Series Rating Information Manual
-
Author
mahmoud-basho -
Category
Documents
-
view
225 -
download
0
Embed Size (px)
Transcript of Panelboard and Switchboards Series Rating Information Manual

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 1/16
Panelboard and Switchboards
Series Rating Information ManualInformation Manual
Play it Safe...
Read This Manual!

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 2/16

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 3/16

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 4/16

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 5/16
Style 1C96944H02 Rev. H For more information visit: www.eaton.com
Series Rating —Panelboards andSwitchboards
Effective: January 2008 Page 3
Applying Series Ratings
The following is provided to use the series rating tableson the following pages:
Step 1.Determine the available system voltage and faultcurrent.
Step 2. Select the appropriate table using the system voltage.
Step 3.Use the appropriate “Series Equipment Rating”column equal to, or greater than, the available faultcurrent, to determine the allowable UL recognizedcombinations of main (upstream) and branch (down-stream) overcurrent devices. Main devices are shownin bold/shaded areas. Respective branch breakers areshown directly below their associated main device.If a rating is not initially found in a column, firstlook to the columns to the right for higher “SeriesEquipment Ratings” within the same table. If stillnot found, use ratings from table of a higher systemvoltage (higher numbered table).
Example 1:208Y/120 volt, 3-phase, 4-wire, ac system with availablefault current of 26,438 amperes. Main (upstream) deviceis a 3-pole, 225 ampere, EDS breaker. The branch (down-stream) breakers are single- and 2-pole, 20, 30 and 60amperes, 120 volt and 120/240 volt BAB breakers.
1. Go to the 120/240 volts table (Table 1).
2. Look down under the 22 kA column. This rating isnot shown.
3. Look to the columns to the right. This combinationrating is shown under the 42 kA column, and thereforeis valid.
Example 2:
480Y/277 volt, 3-phase, 4-wire, ac system with available faultcurrent of 62,097 amperes. Main (upstream) device is a 3-pole250 ampere, HJD breaker. The branch (downstream) break-ers are 2- and 3-pole, 60, 70 and 100 ampere EHD breakers.
1. Go to the 480Y/277 volts table (Table 4).
2. Look down under the 65 kA column. This rating isnot shown.
3. Look to the columns to the right. This rating is notshown.
4. Look at the table with the next higher system voltage.(480 volts, Table 5).
5. This combination rating is shown under the 65 kAcolumn, and therefore is valid.
Example 3:480Y/277 volt, 3-phase, 4-wire, ac system with availablefault current of 24,324 amperes. Main (upstream) device isa 3-pole, 225 ampere, FD breaker. The branch (downstream)breakers are single-pole, 20 ampere, GHQ; 2-pole, 30ampere, GHB; and 3-pole, 50 ampere, GHB devices.
1. Go to the 480Y/277 volts table (Table 4).
2. Look under the 25 kA column. This rating is not shown.Look to the columns to the right. This rating is shownunder the 35 kA column, and therefore is valid forcombinations with the 2- and 3-pole GHB breakers.
3. Go to the 277 volts table (Table 3).
4. Look under the 25 kA column. This rating is not shown.Look to the columns to the right. This rating is shownunder the 35 kA column, and therefore is validfor combinations with the single-pole GHQ breaker.
Other Applications of Series Ratings
Series ratings can also be applied under the followingguidelines:
■ Any FULLY RATED breaker can be applied upstream,downstream or in the middle of any of the series ratingsstated in the tables.
■ Any series rating stated in the tables may have additionalseries rated branch breakers of the EXACT SAME TYPEfurther downstream in that rating.
COMBINING SERIES RATINGS are allowed under certainconditions. Main and branch ratings may be combined if:
■ Breakers A, B and C are in series respectively frommain to branch. Breakers A and B series rate together.Breakers A and C series rate at the same interrupting level(or higher). It is allowable to use A, B and C together at
the A-B series rating.
It is improper to combine series ratings under the followingcondition:
■ Breakers A, B and C are in series respectively from mainto branch. Breakers A and B series rate together. BreakersB and C series rate at the Breaker B interrupting ratinglevel. It is not allowable to use A, B and C together at theA-B series rating. However, combining multiple overcur-rent devices as in this example, can be accomplished if all devices in the series combination have been testedtogether and listed in triple rating Table 13.
Note: The information contained in this manual also applies tospecifying the upstream overcurrent protective device for use withthrough-feed and sub-feed panelboards without an integral main.

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 6/16
For more information visit: www.eaton.com Style 1C96944H02 Rev. H
Series Rating —Panelboards andSwitchboards
Page 4 Effective: January 2008
Series Rating Tables
Table 1. 120/240 Volts ac — Breaker/Breaker Series Ratings
Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
MainBreaker
MaximumAmperes
Series Equipment Rating — kA Symmetrical
18 22 42 65 100 200
100 EHD QBHW GB, GHB FB-P FCL
BA, BABBABRPBABRSPHQPQBGFQBAFQBAG
QPHW BA, BABBABRPBABRSPHQPQBGFQPGFQBAFQBAGQBHWQPHW
BA, BABBABRPBABRSPHQPQBGFQPGFQBAFQBAGQBHWQPHWEHDFD
BA, BABBABRPBABRSPHQPQBGFQPGFQBAFQBAGQBHWQPHWGB, GHBGHQEHDFDHFD
BA, BABHQPQBGFQPGFQBAFQBAG
125 EGH
GHQ, GHB
150 FDB
BA, BABHQPQBGFQBAFQBAG
200 LA-P
BA, BABHQPQBHWQPHWEHDFD
225 EDB EDS ED, FD, FDE EDH, CHH HFD, HFDE FDC FDC
BA, BABBABRP
BABRSPHQPQBGFQPGFQBHGFQPHGFQBHWQPHWQBAFQBAG
BA, BABBABRP
BABRSPHQPQBGFQPGFQBHGFQPHGFQBHWQPHWQBAFQBAG
BA, BABBABRP
BABRSPHQPQBGFQPGFQBAFQBAGQBHWQBHGF
BA, BABBABRP
BABRSPHQPQBGFQPGFQBAFQBAG
BA, BABHQP
QBGFQBAFQBAGQBHWQPHWQBHGFGB, GHBGHQ, GHQRSPEHDFD, EGS
BA, BABHQP
QBHWQPHW
GB, GHBGHQ
GHQRSPEHDFDHFDEGSEGH

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 7/16

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 8/16
For more information visit: www.eaton.com Style 1C96944H02 Rev. H
Series Rating —Panelboards andSwitchboards
Page 6 Effective: January 2008
Table 2. 240 Volts ac — Breaker/Breaker — Series Ratings
For single- and 2-pole 120/240 volt rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 1.Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
ᕃ Valid with BAB_H only.
MainBreakerMaximumAmperes
Series Equipment Rating — kA Symmetrical
18 22 42 65 100 200
100 EHD QBHW_H GB, GHB FB-P FCL
BAB_HHQP_H
QPHW_H BAB_HHQP_HQBHW_HQPHW_H
BAB_HHQP_HEHDFDBFD
BAB_HHQP_HQBHW_HQPHW_HGB, GHBEHDFD, FDEFDBHFD, HFDE
BAB_HHQP_H
125 EGH
GHB
150 FDB
BAB_HHQP_H
200 LA-P
BAB_HHQP_HQBHW_HQPHW_HEHDFDBFDJD, JDB
225 EDB EDS ED FD, FDE EDH, EDC HFD, HFDE FDC FDC
HQP_HBAB_HQBHWQPHW
HQP_HBAB_HQBHWQPHW
BAB_HHQP_HQBHW_H
BAB_HHQP_HQBHW_HQPHW_HEHD (15 – 70 A)FDB
BAB_HHQP_H
BAB_HHQP_HQBHW_HQPHW_HGB, GHBEHDFDBFD, FDE
BAB_HHQP_HQBHW_HQPHW_H
GB, GHBEHDFDBFD, FDEHFD, HFDECHHᕃ
BAB_H
250 JD, JDB HJD HJD JDC JDCBAB_H (15 – 70 A)HQP_H (15 – 70 A)QBHW_HQPHW_HEHDFDB
BAB_H (15 – 70 A)HQP_H (15 – 70 A)QBHW_HQPHW_H
GB, GHBEHDFDFDBEDJD, JDBEGS
BAB_HHQP_HQBHW_HQPHW_H
GB, GHBEHDFD, FDEFDBHFD, EDB, EDSED, HFDEEDHJD, JDBHJD, EGS, EGH

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 9/16
Style 1C96944H02 Rev. H For more information visit: www.eaton.com
Series Rating —Panelboards andSwitchboards
Effective: January 2008 Page 7
Table 2. 240 Volts ac — Breaker/Breaker — Series Ratings (Continued)
For single- and 2-pole 120/240 volt rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 1.Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.
ᕃ Valid on 2- and 3-pole breakers only. Not valid for single-pole.ᕄ Not valid with CHKD.
MainBreakerMaximumAmperes
Series Equipment Rating — kA Symmetrical
65 100 200
400 DK, KD, KDB HKD, CHKD KDC KDC LCLCKD QBHW_Hᕃ
QPHW_Hᕃ
GB, GHBEHDFDBFD, EDB, EDS, FDEEDJD, JDBDK, KD, KDBEGS ᕄ
QBHW_HQPHW_H
GB, GHBEHDFDBFD, FDEHFD, EDB, EDSED, HFDEEDHJD, JDBHJDDK, KD, KDBHKD
BAB_HHQP_HQBHW_HQPHW_HGB, GHBEHDFDBFD, HFD, EDB, EDSED, FDE, HFDEEDHJD, JDBHJDDK, KD, KDBHKD
BAB_HHQP_HQBHW_HQPHW_HEHDFDB
500 NB-P
JD, JDBKD, KDB, DKCKD
600 HLD, HLDB, CHLD LDC
GB ᕃ, GHB ᕃ
FD, EDB, EDSED, EHDJD, JDBKD, KDB, DK, CKDLD, LDB
EDB, EDS, EDEDH
800 NB-P HMDL
KD, KDB, DK EHDFD
1200 HND, CHND NDC
EDB, EDS, EDEHD
EDB, EDS, EDEDH
2500 RD RDC
EDB, EDS, ED EDB, EDS, EDEDH

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 10/16
For more information visit: www.eaton.com Style 1C96944H02 Rev. H
Series Rating —Panelboards andSwitchboards
Page 8 Effective: January 2008
Table 3. 277 Volts ac — Breaker/Breaker Series Ratings
Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.All ratings in this table apply to single-pole branch breakers only. For 2- and 3-pole branch breakers, see other tables.
ᕃ Not valid with FDE.ᕄ Not valid with HFDE.
Table 4. 480Y/277 Volts ac — Breaker/Breaker Series Ratings
Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.All ratings in this table apply to 2- and 3-pole branch breakers only. For single-pole branch breakers, see Table 3.
MainBreakerMaximumAmperes
Series Equipment Rating — kA Symmetrical
22 25 35 65 100 150
100 FCL
GHBGHQ, GHQRSPEHDFDHFD
125 EGS EGH
GHQGHB
GHQGHB
225 FD, FDE HFD, HFDE FDC
GHBGHQGHQRSPGHBGFEPᕃ
GHB, GHQRSPGHQEHDFD, GHBGFEP ᕄ
GHBEHDFDHFD
250 JD, JDB JD, JDB HJD LCL JDC
GHB GHB (15 – 50 A)GHBGFEP
GHB (15 – 50 A)EHDFDGHBGFEP
GHBS GHBEHDFDHFD
400 KD, KDB HKD KD, KDB HKD, CHKD KDC LCLCKD CHKD CKD GHB
EHDFD
GHBEHDFDHFD
GHBEHDFDHFD
GHB GHB GHB (15 – 50 A)EHDFD
MainBreakerMaximumAmperes
Series Equipment Rating — kA Symmetrical
22 25 35 65 100 150
100 FCL
GHB, GHQRSP
125 EGS EGH
GHB GHB
225 FD, FDE HFD, HFDE FDC
GHB, GHQRSP GHB, GHQRSP GHB
250 JD, JDB JD, JDB HJD JDC
GHB GHB (15 – 50 A) GHB GHB
400 KD, KDB HKD, CHKD KD, KDB HKD, CHKD KDC LCLCKD GHB CKD GHB (15 – 50 A) GHB GHB
GHB GHB (15 – 50 A)

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 11/16
Style 1C96944H02 Rev. H For more information visit: www.eaton.com
Series Rating —Panelboards andSwitchboards
Effective: January 2008 Page 9
Table 5. 480 Volts ac — Breaker/Breaker Series Ratings
Main devices are shown centered at top, in shaded area. Respective branch devices shown directly below.All ratings in this table apply to 2- and 3-pole branch breakers only. Not valid for single-pole branch breakers.
ᕃ Not valid with HFDE.
MainBreakerMaximumAmperes
Series Equipment Rating — kA Symmetrical
25 35 65 100 150
100 FB-P FCL
EHDFDBFDHFD
EHDFDBFD, FDEHFD, HFDE
200 LA-P
EHDFDBFDHFDJD, JDBHJD
225 FD, FDE HFD, HFDE FDC
EHDFDB
EHDFDBFD, FDE
EGS ᕃ
EHD, EGS, EGHFDBFD, FDE
HFD, HFDE
250 JD, JDB HJD JDC LCL
EHDFDB
EHDFDBFD, FDEJD, JDBEGS
EHD, EGS, EGHFDBFD, FDEHFD, HFDEJD, JDBHJD
FDE, HFDE
400 KD, KDB HKD KDC LA-P LCL
EHDFDB
EHDFDBFD, FDEJD, JDBKD, KDBEGS
EHD, EGS, EGHFDBFD, FDEHFD, HFDEJD, JDBHJDKD, KDBHKD
JD, JDBHJDKD, KDBHKD
EHDFDBFD, FDEHFD, HFDEFDCJD, JDBHJDKD, KDBHKD
500 NB-P
JD, JDBHJDKD, KDBHKD
600 LD, LDB HLD, HLDBCLD CHLD
JD, JDB FD, FDEJD, JDBKD, KDBLD, LDB

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 12/16

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 13/16
Style 1C96944H02 Rev. H For more information visit: www.eaton.com
Series Rating —Panelboards andSwitchboards
Effective: January 2008 Page 11
Table 8. 240 Volts ac — Fuse/Breaker Series Ratings
For single- and 2-pole 120/240 volt rated breakers (BA, BAB, HQP, QBHW, QPHW), see Table 7.Main fuse class shown centered at top, in shaded area. Respective branch devices shown directly below.
ᕃ Valid on 2- and 3-pole breakers only. See Table 7 for single-pole.
Table 9. 277 Volts ac Fuse/Breaker Series Ratings
Main fuse class are shown centered at top, in shaded area. Respective branch devices shown directly below.All ratings in this table apply to single-pole branch breakers only. For 2- and 3-pole branch breakers, consult other tables.
MainFuseMaximumAmperes
Series Equipment Rating — kA Symmetrical
100 200
100 R
BAB_HHQP_HQBHW_HQPHW_HGBGHB
200 R J T R
GBGHB
BAB_HHQP_HQBHW_HQPHW_H
BAB_HHQP_HQBHW_HQPHW_H
GB ᕃ
GHB ᕃ
400 J T J T
BAB_HHQP_HQBHW_H
QPHW_H
BAB_HHQP_HQBHW_H
QPHW_H
GBGHB
GBGHB
4000 L
EHDFDBFD, FDEEDJD, JDBDK, KD, KDB
MainFuseMaximumAmperes
Series Equipment Rating — kA Symmetrical
65 100 200
100 J T R
GHBSGHQGHQRSP
GHBSGHQGHQRSP
GHB
200 J T J T R
GHBSGHQGHQRSP
GHBSGHQGHQRSP
EHDFDHFD
EHDFDHFD
GHB
400 J T
GHB GHB

7/31/2019 Panelboard and Switchboards Series Rating Information Manual
http://slidepdf.com/reader/full/panelboard-and-switchboards-series-rating-information-manual 14/16
For more information visit: www.eaton.com Style 1C96944H02 Rev. H
Series Rating —Panelboards andSwitchboards
Page 12 Effective: January 2008
Table 10. 480Y/277 Volts ac — Fuse/Breaker Series Ratings
Main fuse class shown centered at top, in shaded area.Respective branch devices shown directly below. All ratingsin this table apply to 2- and 3-pole branch breakers only.For single-pole branch breakers, see Table 9.
Table 11. 480 Volts ac — Fuse/Breaker Series Ratings
Main fuse class shown centered at top, in shaded area.Respective branch devices shown directly below. All ratingsin this table apply to 2- and 3-pole branch breakers only.Not valid for single-pole branch breakers.
Table 12. 600 Volts ac — Fuse/Breaker Series Ratings
Main fuse class shown centered at top, in shaded area.Respective branch devices shown directly below. All ratingsin this table apply to 2- and 3-pole branch breakers only.Not valid for single-pole branch breakers.
Table 13. Triple Series Ratings
ᕃ Valid on 2- and 3-pole breakers only. Not valid for single-pole.
Cutler-Hammer is a federally registered trademark of Eaton Corporation.National Electrical Code and NEC are registered trademarks of the National FireProtection Association, Quincy, Mass. UL is a registered trademark of UnderwritersLaboratories Inc. NFPA is a registered trademark of the National Fire ProtectionAssociation.
Main
FuseMaximumAmperes
Series Equipment Rating — kA Symmetrical
65 100 200
100 J T R
GHBS GHBS GHB
200 J T R
GHBS GHBS GHB
400 J T
GHB GHB
600 J T
EHDFD, FDEHFD, HFDEFDC
GHBEHDFD, FDEHFD, HFDEFDCJD
HJDJDC
MainFuseMaximumAmperes
Series Equipment Rating — kA Symmetrical
100 200
100 R
EHD
200 J T
EHDFDHFDFDC
EHDFDHFDFDC
Main
FuseMaximumAmperes
Series Equipment Rating — kA Symmetrical
100 200
100 R
FD, FDEHFD, HFDEFDC
200 J T R
FD, FDEHFD, HFDEFDC
FD, FDEHFD, HFDEFDC
JDHJDJDC
400 J T R
JDHJDJDC
JDHJDJDC
KDHKDKDC
600 J T
KDHKDKDC
KDHKDKDC
Main FuseClass andMaximumAmperes
Tenant MainType
BranchType
SystemVoltage
ShortCircuitSeriesRating(kA, Sym.)
L-6000 DK, KD, KDB GB, GHB, EHD ᕃ 240 100
L-6000 DK, KD, KDB GB, GHB 120/240 100
L-6000 DK, KD, KDB FD ᕃ, FDB 240 100
L-6000 DK, KD, KDB JD, JDB 240 100
L-6000 JD, JDB GB, GHB 240 100
L-6000 JD, JDB GB, GHB 120/240 100
L-6000 FD GB, GHB 240 100
L-6000 FD GB, GHB 120/240 100
L-6000 FD, FDB BAB_H, HQP_HQBHW_H, QPHW_H
240 100
L-6000 FD, FDB BA, BABHQP (15 – 70 A)
120/240 100
L-6000 EHD BAB_H, HQP_H 240 100
L-6000 EHD BA, BAB, HQP 120/240 100