PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt...

12
2'-0" MAX PANEL OVERHANG, TYP. 1" WALL ANGLE SEE DETAIL A1.5 PANEL BUTT JOINT SEE DETAIL A1.4 1'-0" MAX CARRIER OVERHANG, TYP. SUSPENSION REQUIREMENTS SEE DETAIL A1.2 1" WALL ANGLE SEE DETAIL A1.5 300C PANEL LENGTH 3'-0" MIN - 19'-8" MAX TYPICAL SYSTEM SECTION SEE DETAIL 'A' THIS SHEET 12 GA HANGER WIRE, BY OTHERS, NOT BY HUNTER DOUGLAS SEE DETAIL A1.2 300C PANEL WIDTH 11-13/16" NOM. 300C SYSTEM PROFILE 11 13 16 " NOM. 300C PANEL SEE DETAIL A1.1 FLOATING TRIM SEE DETAIL A1.6 TRIM NOT SHOWN FOR CLARITY 3 3 16 " NOM. 300C PANEL 300C CARRIER SEE DETAILS A1.7 THROUGH A1.10 FOR FIXTURE OPENING RECOMMENDATIONS INTERIOR INSTALLATION DETAIL 'A' 300C CARRIER SPLICE SEE DETAIL A1.3 4'-0" MAX HANGER WIRE SPACING, TYP. 4'-0" MAX CARRIER SPACING, TYP. 5015 Oakbrook Parkway, Suite 100 Norcross, GA 30093 O 800.366.4327 F 770.806.0214 CTSpecialtyCeilings.com All rights reserved. This drawing is the property of CertainTeed Ceilings Corporation. It may not be copied or multiplied, neither wholly nor partly. It may not be submitted for perusal to third parties. SPECIFICATIONS (unless noted otherwise) MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD VENEER | LUXACOTE PERFORATION: NON-PERFORATED | #160 OVERALL ISOMETRIC VIEW PROJECT: 300C PRODUCT SPECIFICATIONS DRAWING NUMBER: 300C-A1.0 SCALE: 3" = 1'-0" DRAWN BY: HD ENGINEERING DATE: 1/28/19

Transcript of PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt...

Page 1: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

2'-0" MAX

PANEL OVERHANG, TYP.

1" WALL ANGLESEE DETAIL A1.5

PANEL BUTT JOINTSEE DETAIL A1.4

1'-0" MAX CARRIER OVERHANG, TYP.

SUSPENSION REQUIREMENTSSEE DETAIL A1.2

1" WALL ANGLESEE DETAIL A1.5

300C PANEL LENGTH

3'-0" MIN - 19'-8" MAX

TYPICAL SYSTEM SECTIONSEE DETAIL 'A' THIS SHEET

12 GA HANGER WIRE,BY OTHERS, NOT BYHUNTER DOUGLASSEE DETAIL A1.2

300C PANEL WIDTH

11-13/16" NOM.

300C SYSTEM PROFILE1113

16" NOM.

300C PANELSEE DETAIL A1.1

FLOATING TRIMSEE DETAIL A1.6TRIM NOT SHOWNFOR CLARITY

33 16

" NO

M.

300C PANEL

300C CARRIER

SEE DETAILS A1.7THROUGH A1.10FOR FIXTURE OPENINGRECOMMENDATIONS

INTERIOR INSTALLATION

DETAIL 'A'

300C CARRIER SPLICESEE DETAIL A1.3

4'-0" MAX HANGER WIRE SPACING, TYP.

4'-0" MAX CARRIER SPACING, TYP.

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the proper ty

of CertainTeed Ceilings

Corporation. It may not

be copied or mult ipl ied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

OVERALL ISOMETRIC VIEW

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.0

SCALE: 3" = 1'-0"

DRAWN BY: HD ENGINEERING

DATE: 1/28/19

Page 2: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

FACTORY PANEL SIDE VIEW

13 16

"PA

NEL

HEI

GHT

33 16

" NO

M.

SYST

EM H

EIGH

T

300C CARRIER

3'-0" MINIMUM PANEL LENGTH19'-8" MAXIMUM PANEL LENGTH**

*VERTICAL SUPPORT OMITTED FOR CLARITY**PANEL LENGTHS VARIABLE IN 1/8" INCREMENTS, TOLERANCE ±1/8"

112532" (11.811")

PANEL WIDTH ONLY

PERFORATION #160 ATFACTORY PANEL END

NON-PERFORATEDFACTORY PANEL END

FACTORY PANEL ENDS

13 16

"PA

NEL

HEI

GHT

*SUSPENSION OMITTED FOR CLARITY

300C PANEL MATERIAL THICKNESS

.028" ALUMINUM

300C PANEL FINISHES

PAINTED & POWDER COATED

LUXACOTE

DECORATED WOOD FINISH (POWDER COATED)

WOOD VENEER

AVAILABLE PANEL PERFORATION

PERFORATION #160PERF AREA 23% OPEN

HOLE DIAMETER 0.060"

PERFORATIONDIRECTION

112532" (11.811")

PANEL WIDTH

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the proper ty

of CertainTeed Ceilings

Corporation. It may not

be copied or mult ipl ied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

PANEL SPECIFICATIONS

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.1

SCALE: NOT TO SCALE

DRAWN BY: HD ENGINEERING

DATE: 1/28/19

Page 3: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

SIDE VIEW OF 300C CARRIER WITH PANEL

SIDE VIEW OF 300C CARRIER

END VIEW OF 300C CARRIER WITH PANEL

END VIEW OF 300C CARRIER

300C CARRIER

MATERIAL: .040" ALUMINUM

FINISH: MATTE BLACK

PART LENGTH: 16'-0"

NOTE: 300C CARRIERS ARE DIRECTIONAL, CHECKORIENTATION PRIOR TO INSTALLATION4'-0" MAX

HANGER WIRE SPACING, TYP.

1'-0" MAX

CARRIER OVERHANG, TYP.

300C PANEL

12 GA HANGER WIRE,BY OTHERS, NOT BYHUNTER DOUGLAS

2'-0" MAX PANEL OVERHANG, TYP.

4'-0" MAX CARRIER SPACING, TYP.300C CARRIER

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the property

of CertainTeed Ceilings

Corporation. It may not

be copied or multiplied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

SUSPENSION SPECIFICATIONS

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.2

SCALE: NOT TO SCALE

DRAWN BY: HD ENGINEERING

DATE: 1/28/19

Page 4: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

12 GA HANGER WIRE, NOTBY HUNTER DOUGLAS

SECTION 'A' - 'A'

CARRIER SPLICE

SNAP SPLICE TABS INTO 300CCARRIER

12" MAXIMUM ATCARRIER SPLICE

12" MAXIMUM ATCARRIER SPLICE

300C PANEL300C CARRIER 12"MAXIMUM AT

CARRIER SPLICE

12"MAXIMUM AT

CARRIER SPLICE

33 16

" NO

M.

12 GA HANGER WIRE, NOTBY HUNTER DOUGLAS

IF THE DESIRED CARRIER LENGTH EXCEEDS THE MAXIMUMOF 16'-0", USE A LUXALON CARRIER SPLICE, TO CONNECTTWO FACTORY CARRIER ENDS.

THE TABS OF THE SPLICE SNAP INTO THE HOLES IN THECARRIER AND ADDITIONAL FIXING IS NOT NECESSARY. THEMODULE IS CONTINUED AUTOMATICALLY.

'A'

'A'

INTERIOR INSTALLATION

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the proper ty

of CertainTeed Ceilings

Corporation. It may not

be copied or mult ipl ied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

CARRIER SPLICE

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.3

SCALE: 3" = 1'-0"

DRAWN BY: HD ENGINEERING

DATE: 1/28/19

Page 5: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

300C PANEL

24" MAXIMUM PANEL OVERHANG

12 GA HANGER WIREBY OTHERS, TYP.

300C CARRIER

4'-0" MAX CARRIER SPACING, TYP.

24" MAXIMUM PANEL OVERHANG

ISOMETRIC VIEW OF FACTORY PANEL ENDS AT JOINT*CARRIERS NOT SHOWN FOR CLARITY

INTERIOR INSTALLATION

NOTE: 300C PANEL ENDS MUST BUTT AT FACTORY PANEL ENDS ANDPANELS CANNOT BE SPLICED. PANEL ENDS CAN ONLY BE FIELD CUTAT PERIMETERS WHERE TRIMS ARE USED FOR TERMINATIONS.PANEL SPLICES ARE NOT REQUIRED NOR AVAILABLE.

DO NOT FASTEN PANEL ENDS TOGETHER. DOINGSO WILL CAUSE DEFORMATION IN PANEL FACE.

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the proper ty

of CertainTeed Ceilings

Corporation. It may not

be copied or mult ipl ied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

PANEL BUTT JOINT

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.4

SCALE: 3" = 1'-0"

DRAWN BY: HD ENGINEERING

DATE: 1/28/19

Page 6: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

FIELD CUT 300CPANEL SIDESFOR WIDTH

FIELD CUT 300C PANEL ENDSFOR LENGTH

1" WALL ANGLE

FACTORY PANELENDS

SECTION VIEW AT 1" WALL ANGLE & 300C PANEL SIDE

1" WALL ANGLE

12'-0" PART LENGTH

1"

1"

USE WALL ANGLE TO SECURE CUT PANELSIDE. TYPICALLY NOT REQUIRED ATFIELD CUT PANEL ENDS.

1"

FACTORY PANELENDS

USE WALL ANGLE ASHOLD DOWN CLIP

FIELD CUT 300C PANEL SIDE

SUSPENSION NOT SHOWN FOR CLARITY

DIRECT FASTEN 1" WALLANGLE TO STRUCTURE

FIELD MITER TRIMS AT CORNERS

1"

*VERTICAL SUPPORT OMITTED FOR CLARITYINTERIOR INSTALLATION

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the proper ty

of CertainTeed Ceilings

Corporation. It may not

be copied or mult ipl ied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

WALL ANGLE TRIM

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.5

SCALE: NOT TO SCALE

DRAWN BY: HD ENGINEERING

DATE: 1/28/19

Page 7: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

10'-0" PART LENGTH

1"

3-3/

16"

2-1/4"

FIELD CUT 300C PANEL SIDESFOR WIDTH

FULL 300C PANELS

1" WALL ANGLE TO SECURE FIELD CUT PANELSIDE. TYPICALLY NOT REQUIRED AT FIELDCUT PANEL ENDS & FULL PANEL EDGES.

FIELD CUT 300CPANEL ENDS

FASTENERS TO SECURE300C J-TRIM TO CARRIERBY OTHERS, TYP.

300C J-TRIM FORFLOATING CONDITION

DOUBLE-SIDEDADHESIVE TOSECURE TRIM ANGLE

300C CARRIER

FIELD CUTPANEL SIDE USE TRIM ANGLE AS

HOLD DOWN

33 16

"

214"

1"

2-1/4"

1"FIELD CUTPANEL END

3-3/

16"

12 GA HANGER WIRE,NOTCH TRIM ASNECESSARY, TYP.

FIELD MITER TRIMSAT CORNERS

INTERIOR INSTALLATION

'A'

'B'

SECTION 'A'SCALE: 6" = 1'-0"

SECTION 'B'SCALE: 6" = 1'-0"

*VERTICAL SUPPORT OMITTED FOR CLARITY

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the proper ty

of CertainTeed Ceilings

Corporation. It may not

be copied or mult ipl ied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

FLOATING TRIM

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.6

SCALE: NOT TO SCALE

DRAWN BY: HD ENGINEERING

DATE: 1/28/19

Page 8: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

300C PANEL FIELD CUT FORFIXTURE OPENING

RECOMMENDED 8" MAX WIDTHFOR FIELD CUT OPENING

CENTERED IN PANEL

8" MAX WIDTH CENTERED

IN PANEL RECOMMENDED

MAX LENGTH VARIES BASED

ON PANEL LENGTH

2" MIN FROM

PANEL END, TYP.

INTERRUPT CARRIER AT FIXTURELOCATION, TYP.

MAX

VAR

IES

BASE

DO

N P

ANEL

LEN

GTH

2" M

IN F

ROM

PAN

EL E

ND,

TYP

.

FIXTURE WITH TRIM FLANGE REQUIRED, BYOTHERS, NOT BY HUNTER DOUGLAS

FIXTURE TO BE INDEPENDENTLY SUPPORTED BY OTHERS

FIELD CUT 300C PANEL

INTERRUPT CARRIER AT FIXTURE

FIXTURE WITH TRIM FLANGE REQUIRED, BYOTHERS, NOT BY HUNTER DOUGLAS

FIELD CUT 300C PANEL

FIXTURE TO BE INDEPENDENTLYSUPPORTED BY OTHERS 300C CARRIER BEYOND

'A' 'A'

'B'

'B'

SECTION 'A' - 'A' SECTION 'B' - 'B'

NOTE: ROUND OPENINGS LESS THAN EIGHT (8) INCHES DIAMETER TYPICALLY FIELD CUT INTO PANEL FACE, TRIMFOR ALL FIXTURES BY OTHERS NOT BY HUNTER DOUGLAS

4'-6" MAX CARRIER SPACING

ALLOWABLE AT FIXTURES, TYP.

ROUND OPENINGS FORCAN LIGHTS, SPEAKERS,SPRINKLERS, ETC.

4'-6

" MAX

CAR

RIER

SPAC

ING

ALLO

WAB

LEAT

FIX

TURE

S, T

YP.

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the property

of CertainTeed Ceilings

Corporation. It may not

be copied or multiplied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

FIELD CUT PANEL FOR FIXTURE OPENINGS

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.7

SCALE: 3" = 1'-0"

DRAWN BY: HD ENGINEERING

DATE: 1/28/19

Page 9: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

VARIES TO ACCOMMODATE FIXTURE WIDTH

11.811" MAX WIDTH TO REMAIN ON MODULE

MAX LENGTH VARIES BASED

ON PANEL LENGTH

FACTORY 300C PANELS

INTERRUPT CARRIER AT FIXTURELOCATION, TYP.

'A' 'A'

'B'

'B'11.811" MAX WIDTH

TO REMAIN ON MODULE

MAX

VAR

IES

BASE

DO

N P

ANEL

LEN

GTH

FIXTURE WITH TRIM FLANGE REQUIRED, BYOTHERS, NOT BY HUNTER DOUGLAS

FIXTURE TO BE INDEPENDENTLY SUPPORTED BY OTHERS

FIELD CUT 300C PANEL

INTERRUPT CARRIER AT FIXTURE

FULL 300C PANEL

FIXTURE TO BE INDEPENDENTLYSUPPORTED BY OTHERS 300C CARRIER BEYOND

SECTION 'A' - 'A'

FIXTURE WITH TRIM FLANGE REQUIRED, BYOTHERS, NOT BY HUNTER DOUGLAS

FULL 300C PANEL

SECTION 'B' - 'B'

NOTE: FIXTURE WITH TRIM FLANGE NOT BY HUNTER DOUGLAS

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the proper ty

of CertainTeed Ceilings

Corporation. It may not

be copied or mult ipl ied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

INTERRUPTED PANEL FOR FIXTURE OPENINGS

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.8

SCALE: 3" = 1'-0"

DRAWN BY: HD ENGINEERING

DATE: 1/28/19

Page 10: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

FIXTURE CUT IN 300C PANEL FACE

MAX WIDTH VARIES BASED

ON PANEL LENGTH

MAX LENGTH VARIES

2" MIN FROM

PANEL SIDE, TYP.

'A'

'B'

'B'

'A'

FIXTURE TO BE INDEPENDENTLY SUPPORTED BY OTHERSCONTINUOUS 300CCARRIER BEYOND

FIXTURE WITH TRIM FLANGE REQUIRED, BYOTHERS, NOT BY HUNTER DOUGLAS

FIELD CUT 300C PANEL

SECTION 'A' - 'A'

FIXTURE WITH TRIM FLANGE REQUIRED, BYOTHERS, NOT BY HUNTER DOUGLAS

FIELD CUT 300C PANEL

300C CARRIER

FIXTURE TO BE INDEPENDENTLYSUPPORTED BY OTHERS

SECTION 'B' - 'B'

MAX WIDTH VARIES2" MIN FROM

PANEL SIDE, TYP.

4'-6

" MAX

CAR

RIER

SPA

CIN

GAL

LOW

ABLE

AT

FIXT

URE

S, T

YP.

MAX

WID

TH V

ARIE

S BA

SED

ON

PAN

EL L

ENGT

H

NOTE: ROUND OPENINGS LESS THAN EIGHT (8) INCHES DIAMETER TYPICALLY FIELD CUT INTO PANEL FACE, TRIMFOR ALL FIXTURES BY OTHERS NOT BY HUNTER DOUGLAS

4'-6" MAX CARRIER SPACING

ALLOWABLE AT FIXTURES, TYP.

4'-6" MAX CARRIER SPACING ALLOWABLE AT FIXTURES, TYP.

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the proper ty

of CertainTeed Ceilings

Corporation. It may not

be copied or mult ipl ied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

FIELD CUT PANEL FOR FIXTURE OPENINGS

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.9

SCALE: 3" = 1'-0"

DRAWN BY: HD ENGINEERING

DATE: 1/28/19

Page 11: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

MAX LENGTH VARIES BASED

ON 11.811" INCREMENTS

(PANEL WIDTH)

MAX WIDTH VARIES

FACTORY FULL 300C PANELS

'A' 'A'

MAX WIDTH VARIES BASEDON 11.811" INCREMENTS

(PANEL WIDTH) OPE

NIN

G W

IDTH

VAR

IES

SECTION 'A' - 'A'

FIXTURE WITH TRIM FLANGE REQUIRED, BYOTHERS, NOT BY HUNTER DOUGLAS

FULL 300C PANEL

SECTION 'B' - 'B'

FIXTURE WITH TRIM FLANGE REQUIRED, BYOTHERS, NOT BY HUNTER DOUGLAS

FULL 300C PANEL

FIXTURE TO BE INDEPENDENTLY SUPPORTED BY OTHERSCONTINUOUS 300CCARRIER BEYOND

'B'

'B'

NOTE: FIXTURE WITH TRIM FLANGE NOT BY HUNTER DOUGLAS

PANEL LENGTHS FACTORYFABRICATED TO MAINTAINPANEL SEAM MODULE

4'-6

" MAX

CAR

RIER

SPA

CIN

GAL

LOW

ABLE

AT

FIXT

URE

S, T

YP.

4'-6" MAX CARRIER SPACING

ALLOWABLE AT FIXTURES, TYP.

300C CARRIER

FIXTURE TO BE INDEPENDENTLYSUPPORTED BY OTHERS

4'-6" MAX CARRIER SPACING ALLOWABLE AT FIXTURES, TYP.

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the proper ty

of CertainTeed Ceilings

Corporation. It may not

be copied or mult ipl ied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

INTERRUPTED PANEL FOR FIXTURE OPENINGS

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.10

SCALE: 3" = 1'-0"

DRAWN BY: HD ENGINEERING

DATE: 1/28/19

Page 12: PANEL OVERHANG, TYP. INTERIOR INSTALLATION · interior installation note: 300c panel ends must butt at factory panel ends and panels cannot be spliced. panel ends can only be field

N

S

SPLAYED 12 GA HANGERWIRE, BY OTHERS, TYP.

300C PANEL

COMPRESSION STRUT

E

300C CARRIER

INTERIOR INSTALLATION

W

45°

45°

45°

45°

LATERAL BRACING: BRACE WITH HANGER WIRES AND STRUTS PER ASTM E-580 AND INACCORDANCE WITH LOCAL CODE REQUIREMENTS.

(4) #12 GAUGE WIRES SPLAYED 90° FROM EACH OTHER AT ANGLE NOT EXCEEDING 45°FROM PLANE OF CEILING. A STRUT FASTENED TO MAIN RUNNER SHALL BE EXTENDED TOAND FASTENED TO STRUCTURE ABOVE. SPLAYED WIRE AND STRUT BRACING TO BE PLACEDNOT MORE THAN 12 FEET ON CENTER IN EACH DIRECTION, WITH THE FIRST POINT WITHIN6 FEET FROM EACH WALL.

5015 Oakbrook Parkway, Suite 100

Norcross, GA 30093

O 800.366.4327

F 770.806.0214

CTSpecialtyCeilings.com

All r ights reserved. This

drawing is the proper ty

of CertainTeed Ceilings

Corporation. It may not

be copied or mult ipl ied,

n e i t h e r w h o l l y n o r

par t l y . I t may not be

submitted f or perusal to

t h i r d p a r t i e s .

SPECIFICATIONS

(unless noted otherwise)

MATERIAL: .028" ALUMINUM 300C PANEL | .040" ALUMINUM 300C CARRIER

FINISH: PAINT | POWDER COAT | DECORATED WOOD FINISH | WOOD

VENEER | LUXACOTE

PERFORATION: NON-PERFORATED | #160

SEISMIC SPECIFICATIONS

PROJECT: 300C PRODUCT SPECIFICATIONS

DRAWING NUMBER: 300C-A1.11

SCALE: NOT TO SCALE

DRAWN BY: HD ENGINEERING

DATE: 1/28/19