Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of...

10
Page 1 of 10

Transcript of Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of...

Page 1: Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of 66 kv Hansot Sub-station 70 Mtr D D 75 Mtr 75 Mtr Soil Resistivity: 32.21907 ohm

Page 1 of 10

Page 2: Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of 66 kv Hansot Sub-station 70 Mtr D D 75 Mtr 75 Mtr Soil Resistivity: 32.21907 ohm

Page 2 of 10

Page 3: Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of 66 kv Hansot Sub-station 70 Mtr D D 75 Mtr 75 Mtr Soil Resistivity: 32.21907 ohm

Page 3 of 10

Page 4: Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of 66 kv Hansot Sub-station 70 Mtr D D 75 Mtr 75 Mtr Soil Resistivity: 32.21907 ohm

Page 4 of 10 TYPICAL LAP WELDING STANDARD DEISGN

Page 5: Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of 66 kv Hansot Sub-station 70 Mtr D D 75 Mtr 75 Mtr Soil Resistivity: 32.21907 ohm

Page 5 of 10

66 KV ANKLESHWAR A SUB STATION

90 Mtr

D D

75 Mtr

Soil Resistivity: 25.53

Fault Current : 2.59 kA Design Ref : Circular No 36 Sr No 3 of Annexure I

Size of mesh: 110X75 Mtr

Conductor for mesh : 50 X 6 mm GI strip 20 mm dia MS Bar ( as consideration in point No 8 of Annx 1 of circulr 36)

Horizontal Conductor: 10 Nos Vertical Conductor : 9 Nos

Distance Between Conductor : 10 Mtr ( To be revised as per size condition)

Nos of 3 mtr long MS bar spikes : 34 Nos (To be suppied by contractor)

Total length of 20 mm Dia round bar : Horizontal conductor 9 X 75 675

10 X 75 750

( 5 % extra)

Total 1425 71.25 1496.25

say 1500 Mtr

Page 6: Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of 66 kv Hansot Sub-station 70 Mtr D D 75 Mtr 75 Mtr Soil Resistivity: 32.21907 ohm

Page 6 of 10

Earthmat Layout of 66 kv Ankleshwar Urban Sub-station

86 Mtr

D D

90 Mtr

Soil Resistivity: 9.1018

Fault Current : 1.09 kA

Size of mesh: 86 X 90Mtr

Conductor for mesh :50X6 mm GI Flat/ 20 mm dia MS Bar Horizontal Conductor: 10 Nos

Vertical Conductor : 10 Nos

Distance Between Conductor : 10 Mtr ( To be revised as per size condition)

Nos of 3 mtr long MS bar spikes : 36 Nos ( To be supplied by contractor) Total length of 20 mm Dia round bar : 10 X86 860

10 X90 900

( 5 % Extra)

Total 1760 88 1848

say 1900 Mtr

Page 7: Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of 66 kv Hansot Sub-station 70 Mtr D D 75 Mtr 75 Mtr Soil Resistivity: 32.21907 ohm

Page 7 of 10

Earthmat Layout of 66 kv Panoli Sub-station

60 Mtr

10 Mtr

D D

88 Mtr

Soil Resistivity: 34.77199 ohm mtr

Fault Current : 3.60 kA

Design Ref : Circular No 36 Sr No 3 of Annexure I

Size of mesh: 88 X 60 Mtr

Conductor for mesh : 20 mm dia MS Bar

Horizontal Conductor: 5+5=10 Nos

Vertical Conductor : 7 +1=8 Nos

Distance Between Conductor ( D): 10 Mtr ( To be revised as per size condition)

Nos of 3 mtr long MS bar spikes : 32 Nos

Total length of 20 mm Dia round bar : 5X70 350

5X60 300

7X88 616

1X40 40

( 5% extra)

Total 1306 65.3 1371.3

Say 1400 Mtr

Page 8: Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of 66 kv Hansot Sub-station 70 Mtr D D 75 Mtr 75 Mtr Soil Resistivity: 32.21907 ohm

Page 8 of 10

Earthmat Layout of 66 kv Hansot Sub-station

70 Mtr

D D

75 Mtr 75 Mtr

Soil Resistivity: 32.21907 ohm mtr

Fault Current :1.48 kA

Design Ref : Circular No 36 Sr No 3 of Annexure I

Size of mesh: 70 X75 Mtr

Conductor for mesh : 20 mm dia MS Bar

Horizontal Conductor:9 Nos

Vertical Conductor : 8 Nos Distance Between Conductor ( D): 10 Mtr ( To be revised as per size condition)

Nos of 3 mtr long MS bar spikes : 30 Nos

Total length of 20 mm Dia round bar : 9X70 630

8X75 600

( 5% extra)

Total 1230 61.5 1291.5

Say

1300 Mtr

Page 9: Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of 66 kv Hansot Sub-station 70 Mtr D D 75 Mtr 75 Mtr Soil Resistivity: 32.21907 ohm

Page 9 of 10

Earth mat Lay out of 66 kV Dahej Sub Station

51.6 mtr

1 2 3 4 5 6 7 8 9 10

2

3

D D

4

5

6 62.0 Mtr

7

8

9

10

11

12

13

Soil Resistivity: 25.53963 ohm mtr

Fault Current : 3.60 kA

Design Ref : Circular No 36 Sr No 4 of Annexure I

Size of mesh: 51.6 X 62 Mtr

Conductor for mesh : 20 mm dia MS Bar

Horizontal Conductor:14 Nos

Vertical Conductor : 11 Nos

Distance Between Conductor ( D): 5 Mtr ( To be revised as per size condition)

Nos of 3 mtr long MS bar spikes : 46 Nos

Total length of 20 mm Dia round bar : 14X51.6 722.4

11X62 682

5% Extra

Total 1404.4 70.22 1474.62

Say 1500 Mtr

Page 10: Page 1 of 10 - Welcome to GUVNL Office/Bharuch Trans Circle... · Page 8 of 10 Earthmat Layout of 66 kv Hansot Sub-station 70 Mtr D D 75 Mtr 75 Mtr Soil Resistivity: 32.21907 ohm

Page 10 of 10

Earthmat Layout of 66 kv Ankleshwar B Sub-station

89 Mtr

D D

110 Mtr

Soil Resistivity :5.7562 ohm mtr

Fault Current: 3.72 kA

Design Ref : Circular No 36 Sr No 3 of Annexure I Size of mesh: 110 X 89 Mtr

Conductor for mesh : 50X6 mm GI flat/20 mm dia MS Bar

Horizontal Conductor: 12 Nos

Vertical Conductor : 10 Nos Distance Between Conductor : 10 Mtr ( To be revised as per size condition)

Nos of 3 mtr long MS bar spikes : 40 Nos Total length of 20 mm Dia round bar : 12 X89 1068

10X110 1100

5% extra

Total 2168 108.4

2276.4

Say 2300 mtr