Job Name: System Reference: Date: Indoor Units: PEA-A12,18AA6 PEAD-A12,18AA7 PLA-A12,18BA6 PLA-A12,18EA7 PKA-A12,18 PVA-A12,18AA7 Outdoor Units: PUY/PUZ-A24,36NHA6 PUY/PUZ-A24,36NHA6-BS PUY/PUZ-A24NHA7 PUY/PUZ-A24NHA7-BS PUY/PUZ-36NKA7 PUY/PUZ-36NKA7-BS PUZ-HA36NHA5 GENERAL FEATURES Through twinning, operate two indoor units from one outdoor unit—ideal for single area and unusually shaped rooms/zones or long narrow rooms/zone applications One hard-wired, wall-mounted PAR-33MAA remote controller simultaneously controls both indoor units Supply power wiring is connected to the outdoor unit power supply terminals A-Control: Wire from S1-S2-S3 on the outdoor unit directly to indoor unit 1 and then to indoor unit 2 Control signal is transmitted between outdoor unit and both indoor units via data over the power connections Required Accessory for Combining Indoor Units: MSDD-50TR-E Distribution Pipe Kit (includes one distribution pipe each for liquid and gas, and choice of joint adapters TWINNING REQUIREMENTS AIR-CONDITIONING, HEAT PUMP & HYPER-HEAT PUMP SYSTEMS Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc. P-SERIES

Transcript of P-SERIES , TUH CEILING-CASSETTE HEA T PUMP...

Page 1: P-SERIES , TUH CEILING-CASSETTE HEA T PUMP …meus1.mylinkdrive.com/files/P-Series_Twinning_Requirements_NHA6...• Maximum total piping length for PUY/PUZ-A24,36: - with 2x PLA-A12EA7

Job Name:

System Reference: Date:

Indoor Units:

PEA-A12,18AA6 PEAD-A12,18AA7PLA-A12,18BA6 PLA-A12,18EA7 PKA-A12,18

PVA-A12,18AA7

Outdoor Units:

Job Name:

System Reference: Date:

Indoor Unit:

PLA-A30EA7

Outdoor Unit:

□ PUZ-A30NHA7

□ PUZ-A30NHA7-BS

INDOOR UNIT FEATURES• Space-efficient ductless installation • Equipped with 3D i-see SensorTM for enhanced comfort and energy efficiency• Airflow settings for high and low ceiling applications• Individual vane settings for direct/indirect airflow control or variable airflow patterns• Knockouts for outside-air intake and branch-duct run• Filter indicator signal• Easy-to-clean, washable filter (optional high-efficiency filter available - requires multi-function casement)• Built-in condensate lift mechanism• Ideal for retail shops, classrooms, office spaces, conference centers, building lobbies, and more

OUTDOOR UNIT FEATURES• Variable speed INVERTER-driven compressor• Suction accumulator pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30)• 24-hour continuous operation (cooling mode)• High pressure protection• Fast restart due to bypass valve make it ideal for equipment cooling applications, such as data centers• Superior energy and operational efficiency

SUBMITTAL DATA: PLA-A30EA7 & PUZ-A30NHA7(-BS)30,000 BTU/H CEILING-CASSETTE HEAT PUMP SYSTEM

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

P-SERIES

PUY/PUZ-A24,36NHA6PUY/PUZ-A24,36NHA6-BS

PUY/PUZ-A24NHA7PUY/PUZ-A24NHA7-BS

PUY/PUZ-36NKA7PUY/PUZ-36NKA7-BS

PUZ-HA36NHA5

GENERAL FEATURES

• Through twinning, operate two indoor units from oneoutdoor unit—ideal for single area and unusually shapedrooms/zones or long narrow rooms/zone applications

• One hard-wired, wall-mounted PAR-33MAA remotecontroller simultaneously controls both indoor units

• Supply power wiring is connected to the outdoor unitpower supply terminals

• A-Control: Wire from S1-S2-S3 on the outdoor unitdirectly to indoor unit 1 and then to indoor unit 2

• Control signal is transmitted between outdoor unit andboth indoor units via data over the power connections

• Required Accessory for Combining Indoor Units:MSDD-50TR-E Distribution Pipe Kit (includes onedistribution pipe each for liquid and gas, and choice ofjoint adapters

TWINNING REQUIREMENTSAIR-CONDITIONING, HEAT PUMP & HYPER-HEAT PUMP SYSTEMS

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

P-SERIES

Page 2: P-SERIES , TUH CEILING-CASSETTE HEA T PUMP …meus1.mylinkdrive.com/files/P-Series_Twinning_Requirements_NHA6...• Maximum total piping length for PUY/PUZ-A24,36: - with 2x PLA-A12EA7

Outdoor Units Indoor Units X 2

PUY/PUZ-A24NHA6 PEA-A12AA6 PKA-A12HA6 PLA-A12BA6

PUY/PUZ-A36NHA6 PEA-A18AA6 PKA-A18HA6 PLA-A18BA6

PUZ-HA36NHA5 PEA-A18AA6 PKA-A18HA6 PLA-A18BA6

Outdoor Units Indoor Units X 2

PUY/PUZ-A24NHA7 PEAD-A12AA7 PKA-A12HA7 PLA-A12EA7*1 PVA-A12AA7

PUY/PUZ-A36NKA7 PEAD-A18AA7 PLA-A18EA7*1

PUZ-HA36NHA5 PEAD-A18AA7 PKA-A18HA7 PLA-A18EA7*1 PVA-A18AA7*1 Refer to the piping length limitation

Please refer to Twinning Application Piping Information for special case rules.

PIPE SIZE AND LIMIT TO REFRIGERANT PIPE

Indoor unit

Indoor unit

Outdoor unit

Distributing pipeH

h

B

C

A

(Fig. 1)

- │B - C│= 26 ft (8m)

or less

165 ft (50m)

or less H = 98 ft (30m)

or less

h = 3 ft (1m)

or less

15 or less245 ft (75m)

or less

Actual pipe length (m) Height Difference (m)Number

of bends

*2

Indoor-OutdoorIndoor-Outdoor Indoor-IndoorIndoor-IndoorA + B + C =

*2 Limit the number of bends for refrigerant pipes to 8 in each of the (A+B) and (A+C) ranges.

See the installation manual provided with the main unit for details on chargeless pipe length and refrigerant additionalcharge amount.

TWINNING REQUIREMENTS

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Page 3: P-SERIES , TUH CEILING-CASSETTE HEA T PUMP …meus1.mylinkdrive.com/files/P-Series_Twinning_Requirements_NHA6...• Maximum total piping length for PUY/PUZ-A24,36: - with 2x PLA-A12EA7

• Maximum total piping length for PUY/PUZ-A24,36:- with 2x PLA-A12EA7 is 59 ft (18m)- with 2x PLA-A18EA7 is 98 ft (30m)- All other combinations is 165 ft (50m)

• Maximum total piping length for PUZ-HA36 OutdoorUnits: 245 ft (75m)

• Maximum height difference from IDU to IDU: 3 ft (1m)Maximum length difference from IDU to IDU: 26 ft (8m)

• Maximum height difference from ODU to IDUs: 100 ft(31m); note: piping lengths to each IDU unit do not haveto be equal

• For the NHA6 generation: both IDUs must have thesame capacity, but do not have to be the same style.(PEA, PEAD, PKA, PLA, and PVA IDUs can becombined for one system.For the NH/KA7 generation, the same indoor unit typesmust be used.

• Twinned IDUs operate simultaneously only; individualIDU control is not available

• One PAR-33MAA remote controller controls both IDUssimultaneously

• Temperature setpoint is set from the PAR-33MAA,choose one of three options on the controller to set thetemperature sensing- Average of the data from both IDU return air sensors(factory setting)- Data from the return air sensor in the IDU directlyconnected to the PAR-33MAA- Data from the sensor in the PAR-33MAA only

• ODU is automatically controlled using MitsubishiElectric’s INVERTER Technology; compressor,frequency, and LEV position will be adjusted as neededto maintain selected room conditions

• Refer to P-Series Installation or Technical ServiceManuals for wiring diagrams

FORM# P-Series Twinning Requirements - 201709

1340 Satellite Boulevard, Suwanee, GA 30024Toll Free: 800-433-4822 www.mehvac.com

TWINNING APPLICATION PIPING INFORMATION

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.