P roduct Catalogue · AXCLJ-TT 12/20(24) kV 66 AXQJ-TT Pure TSLI 12/20(24) kV 68 AXALJ-TT 12/20(24)...
Transcript of P roduct Catalogue · AXCLJ-TT 12/20(24) kV 66 AXQJ-TT Pure TSLI 12/20(24) kV 68 AXALJ-TT 12/20(24)...
Product CataloguePower cables
As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy and information as a primary driver in the development of communities.
With this in mind, we provide major global organisations in many industries with best-inclass cable solutions, based on state-of-the-art technology. Through two renowned commercial brands - Prysmian and Draka - based in almost 50 countries, we’re constantly close to our customers, enabling them to further develop the world’s energy and telecoms infrastructures, and achieve sustainable, profitable growth.
In our energy business, we design, produce, distribute and install cables and systems for the transmission and distribution of power at low, medium, high and extra-high voltage.
In telecoms, the Group is a leading manufacturer of all types of copper and fibre cables, systems and accessories - covering voice, video and data transmission.
Drawing on over 130 years’ experience and continuously investing in R&D, we apply excellence, understanding and integrity to everything we do, meeting and exceeding the precise needs of our customers across all continents, at the same time shaping the evolution of our industry.
Linking the Future
Taking care of the BalticsEstablishment of Keila’s plant dates back to 1968 when Keila Kaabel manufacturing plant was established and production of electrical cables in Keila started. In 1992, Nokia Cable acquired 58.8% shares of Keila Kaabel manufacturing plant. In 2003, the ownership rights were transferred to Draka Holding after acquisition of Nokia Cable.In 2011, Prysmian and Draka merged and gave birth to the cable industry’s leader worldwide. 66 % of Draka Keila Cables belonged to the Prysmian Group until 2014, when Prysmian Group finalized the acquisition of the remaining shareholding part.
As the world leader in cabling, we draw on global expertise and local presence to work in close proximity with our customers, delivering products and service platforms, built on easy contact, customised solutions and effective supply chains, meeting their specialised requirements, to help them drive the wheels of industry and achieve sustainable growth and profitability.Prysmian Group believes in the effective, efficient and sustainable supply of energy and information as a primary driver in the development of communities.
kilometers of quality cable
3 1 1 5 7
In 2016, Draka Keila Cables manufactured
Made in Keila.Due to belonging to the world’s largest cable manufacturer, Prysmian Group, we have 17 research and development centers around the world. Here in Keila we combine the world-wide expertise with local knowledge. This gives us the ability to develop solutions that not only meet required standards but also empowers us to develop tailored solutions according to specific needs.
Halogen-free cable
Low smoke emission.
Light smoke, easy to search for escape routes.
Less toxic gases, easier evacuation.
A harmless white powder is formed,
electronics- and equipment-friendly.
Easier to decontaminate, shorter production stops.
Better for the environment.
Traditional cable
Intense smoke emission.
Dense smoke, hard to find escape routes.
Toxic smoke, interferes with survival.
Emits hydrochloric acid, destroys electronics and corrodes
reinforcement bars.
Complicates decontamination, longer production stops.
Environmentally more hazardous, contains ftalates and dioxin.
A fire often entails serious financial losses due to damage to electronics, equipment and buildings. A contributing factor to these losses is the emission of hydrochloric acid from traditional PVC cables on fire. Hydrochloric acid corrodes and destroys electronics and causes metals to corrode quickly. At a fire site with halogen-free cables installed, a harmless white powder develops instead which minimizes damage to both buildings and equipment. The fire site is also significantly easier and less expensive to decontaminate which in its turn allows faster re-establishing of production.
For people present at a fire site, there are three crucial factors affecting their ability to quickly find an exit: smoke development, visibility and content of toxic substances in the inhaled air. Halogen-free and flame-retardant cables emit less and lighter smoke than PVC cables in case of a fire. The smoke also contains lower quantities of toxic substances. Consequently, people in a room exposed to fire have better visibility and more time to find exits, which increases the probability of escape and survival.
Various types of ftalates are added in the process of PVC production. Their main purpose is to make the plastic soft and mouldable. But in the recent years, research has proved that these substances may be hazardous to health and cause cancer and hormonal disturbances. Burning PVC also emits dioxins which are extremely hazardous to the environment. Above all, they are poorly degradable and remain in the fat tissue of both humans and animals for a long time. As halogen-free cables neither contain ftalates nor emit dioxins when burning, they are a good choice for our health and environment.
Saves money Saves lives Better for health & environment
Afumex– halogen free cableAfumex is a series of halogen-free flame retardant cables that can save lives and money in case
of fire. The black toxic smoke that obstructs the evacuation is gone, just as the corrosive acid that
destroys metal and electronic devices. What remain are the flexible and user-friendly qualities,
which make these cables easy to install. It’s time to choose a new path – the safe and sound one-
Afumex.
Power cables are the backbone of energy systems. Therefore, the quality of these cables are essential in ensuring continuous energy flow to consumers. Using cables with poor quality can significantly increase the probability of faults in energy systems that can be very costly or even dangerous to people.
Our cables are tested in accordance with all applicable standards and are produced according to the needs of our customers. Continuous improvement regarding materials and technology to provide the best quality on the market is our priority.
Product range covers a broad spectrum of power cables based on the market needs. Cables are available from low-voltage bare conductors to high-voltage watertight underground cables and even submarine cables.
Application, compliance with standards and important parameters regarding specific cable are shown on the product page of each cable. In addition to the products included in this catalogue, also other types of power cables are available, as agreed separately with the customer.
Power cables 24 kV 56
AXLJ-TTCL TSLF 12/20(24) kV 56
AXLJ-TTCL TSLF Triplex 12/20(24) kV 58
AHXAMK-W 12/20 (24) kV 60
AXLJ-RMF 12/20(24) kV 62
AXQJ-RMF Pure 12/20(24) kV 64
AXCLJ-TT 12/20(24) kV 66
AXQJ-TT Pure TSLI 12/20(24) kV 68
AXALJ-TT 12/20(24) kV 70
HXCMK 20 kV 72
FXLJ-TT TSLE 12/20(24)kV 74
Power cables 36 kV 76
AXLJ-TT TSLE 18/30(36) kV 76
AXLJ-TTCL TSLF 18/30(36) kV 78
AXQJ-TT Pure TSLI 18/30(36) kV 80
Power cables 42 kV 82
AXLJ-TT TSLE 20,8/36(42) kV 82
Power cables 52 kV 84
AXLJ-TTCL TSLF 26/45(52) kV 84
AXQJ-TT Pure 26/45(52)kV 86
Cable designations 89
Cable Designations used in Sweden 90
Cable Designations used in Norway 91
Cable Designations used in Finland 92
Technical data 94
General information 96
General terms and conditions of supply 96
Recommendations for cable laying 96
Sheath testing in medium voltage cables 98
Standard drums, dimensions and weights 99
Drum handling guide 100
Bare conductors 8
A 8
ACSR 10
HK 12
Aerial 14
AMKA 0,6/1(1,2) kV 14
EX 0,6/1(1,2) kV 16
SAX-W® 20 kV 18
CCST-W 20 kV 20
CCSX AL3 WK 20 kV 22
Power cables 1 kV 24
AXPK 1 core and AXPK-Plus 1 core 0,6/1(1,2) kV 24
XPK 1 core and XPK-Plus 1 core 0,6/1(1,2) kV 26
AXPK-PLUS 0,6/1(1,2) kV 28
AXPK 0,6/1(1,2) kV 30
ARLC and ARLC-PLUS 0,6/1(1,2) kV 32
Power cables 12 kV 34
AXLJ-TTCL TSLF 6/10(12) kV 34
AXQJ-TT Pure TSLI 6/10(12) kV 36
AXLJ-TTCL TSLF Triplex 6/10(12) kV 38
AXQJ-TT Pure TSLI Triplex 6/10(12) kV 40
AHXAMK-W 6/10(12) kV 42
AXLJ-RMF 6/10(12) kV 44
AXQJ-RMF Pure 6/10(12) kV 46
AXCLJ-TT 6/10(12) kV 48
AXALJ-TT 6/10(12) kV 50
FXLJ-TT 6/10(12) kV 52
FXLJ-TTCL TSLF 6/10(12) kV 54
Table of contentsPOWER CABLES
8 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 9We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product
Name
Initial modulus of
elasticity of conductor
[N/mm2]
Final modulus of
elasticity of conductor
[N/mm2]
expansion of messenger
[N/mm2]
Max DC Resistance
at +20°C [Ω/km]
Current
rating in air,
[A]
Max. permisible short
circuit current for 1 sec.,
[kA]
A 25 41000 60000 23x10-6 11,498 136 2,5
A 35 41000 60000 23x10-6 0,8347 170 3,4
A 50 41000 60000 23x10-6 0,5784 215 5,0
A 70 41000 60000 23x10-6 0,4131 265 7,0
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13
Product Name Diameter over wire
[mm]
Weight [kg/km] Number of wires Min. tensile strength of the conductor
[kN]
A 25 2,13 24,9 68 7 4,50
A 35 2,50 34,3 94 7 5,91
A 50 3,00 49,5 135 7 8,19
A 70 3,55 69,3 189 7 11,28
Standard delivery length
[m]
Delivery Package SAP Number
A 25
A 35
A 70
A 50
4000
4000
2500
3500
K8
K9
K11
K11
4741532250117
4741532250124
4741532250148
4741532250131
20074932
20074933
20074935
20074934
ApplicationBare conductor for overhead power transmission.
ApprovalCE
StandardGOST 889-80
ConstructionCable Shape Round.Conductors Stranded aluminium conductor.Conductor Insulation No insulation.Marking of cores No marking.
TemperatureMaximum operating Temperature 80°C
FeaturesFire Propagation Nothing material to burn.UV resistance Good.REACH/SVHC declaration The cable does not contain any substances on the REACH/SVHC list.RoHS declaration All substances of the cable meet the requirements of RoHS directive.
ElectricalMax. short circuit temperature [°C] 200°C
Bare conductors
A
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13
10 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 11We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product Name Number of wires
(aluminium/steel)
Conductor
dimension [mm]
Cable weight
[kg/km]
Max. permisible short
circuit current for 1 sec. **
[kA]
ACSR 34/6 SPARROW 6/1 8,1 39,5 137 3,7
ACSR 54/9 RAVEN 6/1 10,1 62,4 216 5,8
ACSR 85/14 PIGEON 6/1 12,8 99,3 344 9,2
ACSR 242/39 HAWK 26/7 21,8 281 976 26,1
ACSR 305/39 DUCK 54/7 24,1 344 1151 32,5
ACSR 565/72 FINCH 54/19 32,9 637 2123 60,1
Product Name Max DC Resistance at
+20°C [Ω/km]
Min. tensile strength
of the conductor [kN]
Initial modulus of
elasticity of conductor
[N/mm2]
Final modulus of
elasticity of conductor
[N/mm2]
expansion of
conductor [1/k]
Current rating
in air* [A]
ACSR 34/6 SPARROW 0,848 12,2 64000 78000 19,2x10-6 210
ACSR 54/9 RAVEN 0,536 17,11 64000 78000 19,2x10-6 280
ACSR 85/14 PIGEON 0,337 24,13 64000 78000 19,2x10-6 360
ACSR 242/39 HAWK 0,120 84,9 61000 75500 19,2x10-6 745
ACSR 305/39 DUCK 0,0949 96,8 50000 67000 19,3x10-6 845
ACSR 565/72 FINCH 0,0512 174 46000 63000 19,3x10-6 1250
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-09
Standard delivery length
[m]
Delivery Package SAP Number
ACSR 34/6 SPARROW
ACSR 54/9 RAVEN
ACSR 85/14 PIGEON
ACSR 242/39 HAWK
ACSR 305/39 DUCK
ACSR 565/72 FINCH
2500
2200
2000
2500
2200
1200
K9
K11
K12
K20
K26
K22
4741532250254
4741532250278
4741532250285
4741532250322
4741532250339
4741532250353
20074938
20074939
20074940
20166519
20074941
20074942
ApplicationBare conductor for overhead power transmission.
Flame retardanceFlame retardant - Not applicable
ApprovalCE
StandardIEC 61089 Overhead stranded conductorsEN 50182 Conductors for overhead linesSFS 5701 Overhead conductor wires and steel ropes.
ConstructionCable Shape Round.Conductors Conductor consists of aluminium and galvanized steel wires.Center conductor Steel.Conductor Insulation No insulation.Marking of cores No marking.
TemperatureMaximum operating Temperature 80°C
FeaturesFire Propagation Nothing material to burn.UV resistance GoodREACH/SVHC declaration The cable does not contain any substances on the REACH/SVHC list.RoHS declaration All substances of the cable meet the requirements of RoHS directive.
ElectricalMax. short circuit temperature [°C] 200°C
Bare conductors
ACSR
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-09
12 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 13We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product Name Conductor dimension
[mm]
Cross section [mm2] Number of wires Cable weight
[kg/km]
Max DC
Resistance at
+20°C [Ω/km]
Max. permisible short
circuit current for 1 sec.
* [kA]
HK 16 / 7x1,68 5,1 15,5 7 140 1,15 2,3
HK 25 / 7x2,12 6,4 24,7 7 222 0,727 3,8
HK 35 / 7x2,50 7,5 34,4 7 309 0,524 5,3
HK 50 / 19x1,77 8,9 46,8 19 422 0,387 7,2
HK 70 / 19x2,12 10,6 67,1 19 606 0,268 10,3
HK 95 / 19x2,50 12,5 93,3 19 843 0,193 14,3
HK 120 / 37x2,01 14,1 117 19 1062 0,153 18
HK 150 / 37x2,23 15,6 148 37 1338 0.124 22,6
* Initial temperature of conductor before short circuit 40°C, final temperature of conductor after short circuit 200°C
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-09
Standard delivery length
[m]
Delivery Package SAP Number
HK 16 / 7x1,68
HK 25 / 7x2,12
HK 35 / 7x2,50
HK 50 / 19x1,77
HK 70 / 19x2,12
HK 95 / 19x2,50
HK 150 / 37x2,23
HK 120 / 37x2,01
1000
500
1000
1000
1000
1000
500
500
K6
K6
K6
K7
K8
K9
K11
K9
4741532250018
4741532250025
4741532250032
4741532250049
4741532250056
4741532250063
4741532250087
4741532250070
20162343
20162344
20162345
20162346
20162347
20162348
20194993
20162349
ApplicationGrounding wire for fixed installations.
Flame retardanceFlame retardant - Not applicable
ApprovalCE
StandardIEC 60228 Conductor standard
ConstructionCable Shape RoundConductors Concentric stranded soft copper conductorConductor Insulation No insulationMarking of cores No marking
FeaturesFire Propagation Nothing material to burnUV resistance Good
ElectricalMax. short circuit temperature [°C] 200°C
Bare conductors
HK
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-09
14 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 15We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product Name Diameter over bare
conductor [mm]
Diameter over
messenger [mm] [mm]*
Conductor weight
[kg/km]
Cable weight
[kg/km]
AMKA 1x16+25 4,4 5,8 11 100 135
AMKA 3x16+25 4,4 5,8 20 185 270
AMKA 3x25+35 5,8 6,8 23 285 390
AMKA 3x35+50 6,8 8 27 390 530
AMKA 3x50+70 8,0 9,6 31 540 700
AMKA 3x70+95 9,6 11,3 36 775 1000
AMKA 3x120+95 12,7 11,3 42 1185 1500
*Circumferance divided by π (Pi).
Product Name Min. permissible
bending radius
during laying [m]
Min. permissible
bending radius at
final installation
[m]
Min.tensile strength
of the messenger
[kN]
Initial modulus of
elasticity of
messenger
[N/mm2]
Final modulus of
elasticity of
messenger
[N/mm2]
expansion
expansion of
messenger
[N/mm2]
AMKA 1x16+25 0,28 0,2 7,4 55 000 63 000 23x10-6
AMKA 3x16+25 0,42 0,3 7,4 55 000 63 000 23x10-6
AMKA 3x25+35 0,5 0,35 10,3 55 000 63 000 23x10-6
AMKA 3x35+50 0,58 0,41 14,2 55 000 63 000 23x10-6
AMKA 3x50+70 0,66 0,47 20,6 55 000 63 000 23x10-6
AMKA 3x70+95 0,78 0,55 27,9 55 000 63 000 23x10-6
AMKA 3x120+95 0,92 0,65 27,9 55 000 63 000 23x10-6
Product Name Max DC
Resistance of
phase* [Ω/km]
AC resistance of
phase** [Ω/km]
Max DC Resistance
of messenger*
[Ω/km]
Inductance
[mH/km]
Max. permisible
short circuit current
for 1 sec., phase
conductor ***[kA]
Max. permisible short
circuit current for 1 sec.,
messenger*** [kA]
AMKA 1x16+25 1,91 2,3 1,38 0,29 1,0 1,5
AMKA 3x16+25 1,91 2,3 1,38 0,35 1,0 1,5
AMKA 3x25+35 1,2 1,4 0,986 0,34 1,6 2,1
AMKA 3x35+50 0,868 1 0,720 0,34 2,3 3,0
AMKA 3x50+70 0,641 0,77 0,493 0,33 3,2 4,3
AMKA 3x70+95 0,443 0,53 0,363 0,31 4,5 5,9
AMKA 3x120+95 0,253 0,3 0,363 0,3 7,8 5,9
*** Initial temp. of conductor before short circuit - 70ºC, final temp. after short circuit - 135ºC.
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
Standard delivery length
[m]
Delivery Package SAP Number
AMKA 1x16+25
AMKA 3x16+25
AMKA 3x25+35
AMKA 3x35+50
AMKA 3x50+70
AMKA 3x70+95
AMKA 3x120+95
2000
1000
1000
1000
1000
500
500
K11
K12
K14
K16
K18
K14
K18
4741532100009
4741532100023
4741532100047
4741532100054
4741532100061
4741532100078
4741532100085
20074959
20074961
20074963
20074964
20074965
20074966
20074967
ApplicationAerial bundled power cable with aluminum conductor.
Flame retardanceFlame retardant - Not applicable
ApprovalCE
StandardSFS 2200 Aerial bundled cable AMKAHD 626 S1 Overhead distribution cablesIEC 60228 Conductor standard
ConstructionCable Shape Insulated conductors are laid up around the the messenger.Conductors 16 mm2: round and solid aluminium conductor;
25-120 mm2: round, stranded and compacted aluminium conductorConductor Insulation Black UV and weather resistant PE compoundMarking of cores Phase conductors: 2,3 or 4 longitudinal ridges
Optional conductor: no ridgesExample of marking on sheath AMKA 3x16+35 1 kV DRAKA "Production number", "Date and time", metre marked
TemperatureMaximum operating Temperature 70°CTemparatures at installation [°C] Lowest cable temperature during installation: -20 ºC , below 0 ºC special precaution is
recommended.
FeaturesUV resistance GoodMin. Bending radius at final installation 14 x DMin. Bending radius at during installation 20 x D
ElectricalMax. short circuit temperature [°C] 135°C (5s)
Covered overhead lines
AMKA 0,6/1(1,2) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
16 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 17We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Cable
diameter
[mm]
Cable
weight
Min.permissible
laying [m]
Min. permissible bending
[m]
Min.strength of
the conductor[kN]
Max. DC
resistance of
conductor
[Ω/km]
Max. permisible
short circuit current
EX 2x25, 1kV 18 205 0.4 0.28 4,1 1.2 1.8
EX 3x25, 1kV 20 305 0.5 0.35 4,1 1.2 1.8
EX 3x50, 1kV 25 525 0.44 0.31 7.3 0.641 3.6
EX 3x95, 1kV 34 1000 0.64 0.45 13.7 0.320 6.8
EX 4x16, 1kV 18 265 0.36 0.25 2.6 1.91 1.1
EX 4x25, 1kV 22 405 0.68 0.48 4,1 1.2 1.8
EX 4x35, 1kV 24 520 0.35 0.25 5.6 0.868 2.5
EX 4x50, 1kV 28 700 0.474 0.33 7.3 0.641 3.6
EX 4x50, 1kV T1000 28 700 0.56 0.39 7.3 0.641 3.6
EX 4x70, 1kV 32 1000 0.56 0.39 10.4 0.443 5.0
EX 4x95, 1kV 38 1350 0.76 0.53 13.7 0.320 6.8
EX 4x95, 1kV T1000 38 1350 0.76 0.53 13.7 0.320 6.8
*Conductor temperature 20ºC
** Initial temperature of conductor before short circuit 70ºC, final temperature of conductor after short circuit 135ºC
Standard delivery length
[m]
Delivery Package SAP Number
EX 4x25
EX 4x35
EX 4x50
EX 4x50, T1000
EX 4x70
EX 4x95
EX 4x95, T1000
500
500
500
1000
1000
500
1000
K11
K11
K11
K18
K18
K14
K20
4741532100122
4741532100153
4741532100146
4741532100221
4741532100160
4741532100184
4741532100184
20074970
20141393
20074972
20204660
20074973
20074975
20204661
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
Standard delivery length
[m]
Delivery Package SAP Number
EX 2x25
EX 3x25
EX 3x50
EX 3x95
EX 4x16
500
500
500
500
1000
K9
K9
K11
K14
K11
4741532100108
4741532100115
4741532100139
4741532100177
4741532100191
20074968
20074969
20074971
20074974
20130697
ApplicationAerial bundled power cable with aluminium conductor.
Alternative Product NameCENELEC N1ED4-AR
Flame retardanceFlame retardant - Not applicable
ApprovalCE
StandardHD 626-3I Overhead distribution cablesIEC 60228 Conductor standard
ConstructionCable Shape RoundConductors Round, stranded and compacted aluminium conductorConductor Insulation Black UV and weather resistant PE compoundMarking of cores Marked with longitudinal ridges, 2-core: Neutral-conductor - no ridge, Phase 1 - 1 ridge,
3-core: Phase 1 – 1 ridge, Phase 2 – 2 ridges, Phase 3 – 3 ridges,4-core: Neutral-conductor - no ridge, Phase 1 - 1 ridge, Phase 2 - 2 ridges, Phase 3 - 3 ridges
Example of marking on sheath EX 4x50 1 kV DRAKA "Production number", "Date and time", metre marked
TemperatureMaximum operating Temperature 70°C
FeaturesUV resistance YesMin. Bending radius at final installation 14 x DMin. Bending radius at during installation 20 x DREACH/SVHC declaration Fulfills the REACH requirementsRoHS declaration Fulfills the RoHS requirements
ElectricalMax. short circuit temperature [°C] 135°C (5s)
Covered overhead lines
EX 0,6/1(1,2) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
18 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 19We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product Name Diameter over
conductor [mm]
Diameter over
covered conductor
[mm]
Cable weight
[kg/km]
Min. permissible
bending radius
during laying [m]
Min.permissible
bending radius at final
installation [m]
Min. tensile strength
of the conductor[kN]
SAX-W 35 6,9 11,5 160 0,16 0,11 11,2
SAX-W 50 8,0 12,7 200 0,18 0,13 15,5
SAX-W 70 9,7 14,3 270 0,2 0,14 22,5
SAX-W 95 11,3 16,1 350 0,22 0,16 30,4
SAX-W 120 12,8 17,6 425 0,25 0,18 38
SAX-W 150 14,2 18,9 510 0,27 0,19 47,3
Product Name Initial modulus of
elasticity of conductor
[N/mm2]
Final modulus of
elasticity of
conductor [N/mm2]
expansion
expansion of
Max. DC Resistance
of conductor*
[Ω/km]
Current rating in
air**[A]
Max. permisible
short circuit current
SAX-W 35 61 000 62 500 23x10-6 0,986 200 3,2
SAX-W 50 61 000 62 500 23x10-6 0,720 245 4,3
SAX-W 70 61 000 62 500 23x10-6 0,493 310 6,4
SAX-W 95 61 000 62 500 23x10-6 0,363 370 8,6
SAX-W 120 53 000 62 000 23x10-6 0,288 430 11,0
SAX-W 150 53 000 62 000 23x10-6 0,236 485 13,5
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-09
Standard delivery length
[m]
Delivery Package SAP Number
SAX-W 35
SAX-W 50
SAX-W 70
SAX-W 95
SAX-W 120
SAX-W 150
2000
2000
2000
2000
2000
2000
K11
K11
K12
K14
K16
K18
4741532130709
4741532130716
4741532130723
4741532130730
4741532130747
4741532130754
20074926
20074927
20074928
20074929
20074930
20074931
ApplicationAerial power cable with stranded and compacted aluminium conductor.
Alternative Product NamePAS-W / CCX-WK
ApprovalCE
Flame retardanceFlame retardant - Not applicable
StandardEN 50397-1 Covered conductors for overhead linesIEC 60228 Conductor standard
ConstructionCable Shape RoundConductors Watertight aluminium alloy, round, stranded and compactedOuter Sheath Black weather resistant XLPE compoundExample of marking on sheath Sax-W 70 20 kV DRAKA "Production number", "Date and time", metre marked
TemperatureMaximum operating Temperature 80°CTemparatures at installation [°C] Lowest cable temperature during installation -20 °C, below 0 °C special precautions are
recommended.
FeaturesUV resistance Good
ElectricalMax. short circuit temperature [°C] 200ºC
Covered overhead lines
SAX-W® 20 kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-09
20 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product Name Initial modulus of
elasticity of conductor
[N/mm2]
Final modulus of
elasticity of conductor expansion expansion of
conductor [1/k]
Max DC
Resistance of
conductor*
Current
rating in
air** [A]
Max. permisible
short circuit
current for 1
sec.*** [kA]
CCST-39 W 64000 78000 19,2 x 10-6 0.848 - 3.7
CCST-62 W 64000 78000 19,2 x 10-6 0.5355 225 5.9
CCST-99 W 64000 78000 19,2 x 10-6 0.3367 310 9.4
CCST-159 W 53000 62000 23 x 10-6 0.1923 440 15.8
CCST-241 W 53000 62000 23 x 10-6 0.1265 580 24
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-09
Product Name Diameter over
conductor [mm]
Diameter over
covered conductor
[mm]
Weight of cable
[kg/km]
Min. permissible
bending radius
during laying [m]
Min. permissible
bending radius at
final installation [m]
Min. tensile strength
of the conductor[kN]
CCST-39 W 8.1 13.1 225 0.20 0.14 12.2
CCST-62 W 10.1 15.1 309 0.23 0.16 18.64
CCST-99 W 12.8 17.8 449 0.27 0.19 29.22
CCST-159 W 16.3 21.3 575 0.32 0.22 43.61
CCST-241 W 20.1 25.1 829 0.38 0.27 61.49
Standard delivery length
[m]
Delivery Package SAP Number
CCST-39 W
CCST-62 W
CCST-99 W
CCST-159 W
CCST-241 W
2000
1500
1000
1000
1000
K12
K12
K12
K14
K18
4741532130808
4741532130839
4741532130846
4741532130860
4741532130884
20213314
20163991
20159492
20163988
20163989
ApplicationCovered conductor with a semiconductive layer for pole installation.
Alternative Product NameBLL 20 kV
Flame retardanceFlame retardant - Not applicable
ApprovalCE
StandardSS-EN 50397-1 Construction standard - Covered conductors for overhead linesIEC 60228 Conductor standard
ConstructionCable Shape RoundConductors CCST-W 39, 62 & 99: Round stranded aluminium steel reinforced conductor
CCST-W 159 & 241: Round, stranded aluminium steel reinforced conductorConductor Insulation Semiconductive compoundOuter Sheath Weather resistant PE, blackExample of marking on sheath CCST- 99W 20 kV DRAKA, "Production number", "Date and time", metre marked
TemperatureMaximum operating Temperature 70 °C.Temparatures at installation [°C] Lowest temperature -20 °C, below 0 °C extra precaution is recommended.
Covered overhead lines
CCST-W 20 kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-09
22 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 23We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product Name Initial modulus of
elasticity of
conductor
[N/mm2]
Final modulus of elasticity
of conductor[N/mm2] expansion expansion
of conductor[1/k]
Max DC
Resistance of
conductor*[Ω/km]
Current rating
in air** [A]
Max. permisible
short circuit
current for 1
CCSX 35 AL3 WK 61 000 62 500 23x10-6 0.986 200 3.2
CCSX 50 AL3 WK 61 000 62 500 23x10-6 0.72 245 4.3
CCSX 70 AL3 WK 61 000 62 500 23x10-6 0.493 310 6.4
CCSX 95 AL3 WK 61 000 62 500 23x10-6 0.363 370 8.6
CCSX 120 AL3 WK 61 000 62 500 23x10-6 0.288 430 11
CCSX 150 AL3 WK 61 000 62 500 23x10-6 0.236 485 13.5
*Conductor temperature 20ºC ** Air temperature 25ºC
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-09
Product Name Diameter over
conductor [mm]
Diameter over
covered conductor
[mm]
Cable weight
[kg/km]
Min. permissible
bending radius
during laying [m]
Min. permissible
bending radius at
final installation [m]
Min. tensile strength
of the conductor[kN]
CCSX 35 AL3 WK 6.9 12 170 0.18 0.13 11.2
CCSX 50 AL3 WK 8 13.2 220 0.20 0.14 15.5
CCSX 70 AL3 WK 9.7 14.8 290 0.22 0.16 22.5
CCSX 95 AL3 WK 11.3 16.5 370 0.25 0.17 30.4
CCSX 120 AL3 WK 12.8 18 455 0.27 0.19 38
CCSX 150 AL3 WK 14.2 19.4 545 0.29 0.20 47.3
Standard delivery length
[m]
Delivery Package SAP Number
CCSX 35 AL3 WK
CCSX 50 AL3 WK
CCSX 70 AL3 WK
CCSX 95 AL3 WK
CCSX 120 AL3 WK
CCSX 150 AL3 WK
2000
2000
2000
2000
2000
2000
K11
K12
K12
K14
K18
K18
4741532130600
4741532130617
4741532130624
4741532130631
4741532130648
4741532130655
20134348
20134349
20134350
20134351
20134352
20134353
ApplicationCovered conductor for pole installation.
Flame retardanceFlame retardant - Not applicable
StandardEN 50397-1 Covered conductors for overhead linesIEC 60228 Conductor standard
ConstructionCable Shape RoundConductors Round, stranded and compacted watertight aluminium alloy conductorInner semi-conducting layer Cross-linkable semiconductive compoundOuter Sheath Black weather resistant XLPE compoundExample of marking on sheath CCSX 70 AL3 WK DRAKA "Production number", "Date and time", metre marked
TemperatureMaximum operating Temperature 80 ˚CTemparatures at installation [°C] -20 ˚C
Covered overhead lines
CCSX AL3 WK 20 kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-09
24 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 25We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product NameCable diameter [mm]
Conductor weight[kg/km]
Cable weight [kg/km] Min.permissible bendingradius during laying [m]
Min. permissiblebending radius at finalinstallation [m]
AXPK 1x185 24 484 745 0.36 0.26
AXPK 1x240 27 635 940 0.405 0.29
AXPK 1x300 29 795 1150 0.435 0.31
AXPK 1x400 32 1020 1460 0.48 0.34
AXPK 1x500 36 1312 1850 0.54 0.38
AXPK 1x630 40 1692 2350 0.6 0.42
AXPK 1x800 44 2160 2950 0.66 0.47
AXPK-PLUS 1X300 29 795 2160 0.435 0.31
AXPK-PLUS 1X800 44 2160 2900 0.66 0.47
Product Name Max. permissible pulling forcewith a pulling grip [kN]
Max. permissible pulling forcewith a pulling eye [kN]
Max. DC resistance of conductor *[Ω/km]
AXPK 1x185 2.7 9.2 0.164
AXPK 1x240 3.6 12 0.125
AXPK 1x300 4.5 15 0.1
AXPK 1x400 6 20 0.0778
AXPK 1x500 7 20 0.0605
AXPK 1x630 8.1 20 0.0467
AXPK 1x800 8.5 20 0.0367
AXPK-PLUS 1X300 4.5 15 0.1
AXPK-PLUS 1X800 8.5 20 0.0367
*Conductor temperature 20ºC
Product Name Current rating inground* [A]; flatformation
Current rating inground* [A]; trefoilformation
Current rating in air** [A]; flat formation
Current rating in air** [A]; trefoil formation
Max. permisible shortcircuit current for 1sec.***, kA
AXPK 1x185 431 334 500 390 17.5
AXPK 1x240 511 397 600 470 22.6
AXPK 1x300 525 460 690 560 28.3
AXPK 1x400 711 558 815 640 37.6
AXPK 1x500 821 647 930 750 47
AXPK 1x630 954 754 1110 880 59.2
AXPK 1x800 1000 830 1300 1050 75.6
AXPK-PLUS 1X300 525 460 690 555 28.3
AXPK-PLUS 1X800 1000 830 1300 1040 75.6
*Conductor temperature 70ºC **Conductor temperature 90ºC
*** Initial temperature of conductor before short circuit 90ºC, final temperature of conductor after short circuit 250ºC
The ratings are based on the following conditions : maximum conductor temperature- 90ºC, ground temperature- 15ºC, air temperature- 25ºC,
thermal resistivity of soil- 1,0 ºKm/W, depth of burial-0,7m
Product Name Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
AXPK 1x185
AXPK 1x240
AXPK 1x300
AXPK 1x400
AXPK 1x500
AXPK 1x630
AXPK 1x800
AXPK 1x1000
AXPK-PLUS 1x300
AXPK-PLUS 1x800
1000
1000
1000
1000
500
500
500
500
500
500
K14
K18
K18
K18
K18
K18
K20
K22
K14
K20
4741532130006
4741532130013
4741532130020
4741532130037
4741532130044
4741532130051
4741532130068
4741532130075
6410006019311
6410006019359
20074943
20074944
20074945
20074946
20074947
20074948
20074949
20074950
20140296
20140297
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
ApplicationPower cable with round, stranded and compacted aluminium conductor. For fixed installations indoors and outdoors, perfect for ploughingdown. Suitable for cable ducts and house connections. AXPK-Plus is the halogen-free version of the cable.
Alternative Product NameAXPK-HF
Flame retardanceIEC 60332-1-2 - Vertical flame propagation for asingle insulated wire or cable
StandardSFS 4879 0.6/1 kV XLPE insulated Al and Cu wires.IEC 60502-1 Construction StandardIEC 60228 Conductor standardCENELEC HD 603 Part 5 Section D Harmonized construction standardHD 60364-5-52 Selection and erection of electrical equipment. Wiring systems.
ConstructionCable Shape Round.Conductors Round, compacted and stranded aluminium conductor.Conductor Insulation Black XLPE compound.Outer Sheath AXPK - black PVC.
AXPK-Plus - black self-extinguishing halogen-free compound.Example of marking on sheath AXPK-PLUS 1KV DRAKA "Date and time", metre marked.
TemperatureMaximum operating Temperature 90ºCTemparatures at installation [°C] Lowest cable temperature during installation: -20 ºC below 0 ºC extra precaution is
recommended.
FeaturesCPR Performance class EcaUV resistance Good.
ElectricalMax. short circuit temperature [°C] 250ºC
Power Cables 1kV
AXPK 1 core and AXPK-Plus 1 core 0,6/1(1,2) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
26 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 27We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product Name
Cable diameter
[mm]
Conductor weight
[kg/km]
Cable weight
[kg/km]
Min. permissible
bending radius
during laying [m]
Min. permissible
bending radius at
final installation
[m]
Max. permissible
pulling force with
a pulling grip [kN]
Max. permissible
pulling force with
XPK 1x185 23 1590 1900 0.35 0.24 2.7 18.5
XPK 1x240 26 2115 2400 0.39 0.27 3.6 20
XPK 1x300 29 2620 3050 0.44 0.31 4.5 20
XPK-PLUS 1x185 23 1590 1900 0.35 0.24 2.7 18.5
XPK-PLUS 1x300 29 2620 3000 0.44 0.31 4.5 20
*Conductor temperature 20ºC
Product Name Current rating in
ground* [A]; flat
formation
Current rating in
formation
Current rating in
formation
Current rating in
formation
Max. permissible
short circuit current
for 1 sec.***, kA
Maximum DC
resistance of
conductor * [Ω/km]
XPK 1x185 535 425 645 510 26.4 0.0991
XPK 1x240 625 500 790 610 34.2 0.0745
XPK 1x300 735 585 885 705 42.8 0.0601
XPK-PLUS 1x185 535 425 645 510 26.4 0.0991
XPK-PLUS 1x300 735 585 885 705 42.8 0.0601
*Conductor temperature 70ºC
**Conductor temperature 90ºC
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
Standard delivery length
[m]
Delivery Package SAP Number
XPK 1x185
XPK 1x240
XPK 1x300
XPK-PLUS 1X185
XPK-PLUS 1X300
500
500
500
500
500
K11
K12
K14
K11
K14
4741532120502
4741532120519
4741532120526
4741532120533
4741532120557
20140290
20180995
20140291
ApplicationPower cable with round, stranded and compacted copper conductor. For fixed installations indoors and outdoors, perfect for ploughing down.Suitable for cable ducts and house connections. XPK-Plus is the halogen-free version of the cable.
Alternative Product NameXPK-HF 1 core
ApprovalCE
Flame retardanceIEC 60332-1-2 - Vertical flame propagationfor a single insulated wire or cable
StandardSFS 4879 0.6/1 kV XLPE insulated Al and Cu wires.IEC 60502-1 Construction StandardCENELEC HD 603 Part 5 Section D Harmonized construction standardIEC 60228 Conductor standard
ConstructionCable Shape Round.Conductors Round, compacted and stranded copper conductor.Conductor Insulation Black XLPE compound.Outer Sheath XPK - black PVC.
XPK-PLUS - black self-extinguishing halogen-free compound.Example of marking on sheath XPK-PLUS ANNEALED 1KV DRAKA "Data ir laikas", ilgio žymuo
TemperatureMaximum operating Temperature 90ºCTemparatures at installation [°C] Lowest cable temperature during installation: -20 ºC below 0 ºC special precaution shall be
taken.
FeaturesCPR Performance class EcaUV resistance Good.
ElectricalMax. short circuit temperature [°C] 250ºC
Power Cables 1kV
XPK 1 core and XPK-Plus 1 core 0,6/1(1,2) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
28 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 29We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product name Cablediameter[mm] Conductorweight[kg/km]
Min.permissiblebendingradius duringlaying [m]
Min.permissiblebendingradius at finalinstallation[m]
Max.permissiblepullingforce with apullinggrip [kN]
Maxpermissiblepullingforce with apullingeye [kN]
AXPK-PLUS 4G16 RE 20 165 0.24 0.17 0.9 3.2
AXPK-PLUS 4G16 RM 20 165 0.24 0.17 0.9 3.2
AXPK-PLUS 5G16 RE 20 207 0.25 0.18 1.1 4.0
AXPK-PLUS 4G25 21 265 0.26 0.19 1.5 5.0
AXPK-PLUS 5G25 25 332 0.31 0.22 1.8 6.2
AXPK-PLUS 4G35 23 365 0.28 0,20 2.1 7.0
AXPK-PLUS 5G35 27 460 0.31 0.23 2.6 8.8
AXPK-PLUS 4G50 27 495 0.31 0.23 3.0 10.1
AXPK-PLUS 4G70 30 720 0.36 0.26 4.2 14.0
AXPK-PLUS 4G95 34 995 0.41 0.29 5.7 19.0
AXPK-PLUS 4G120 38 1260 0.46 0.33 7.2 20.0
AXPK-PLUS 4G150 42 1550 0.51 0.36 8.5 20.0
AXPK-PLUS 4G185 47 1950 0.57 0.40 8.5 20.0
AXPK-PLUS 4G240 53 2550 0.64 0.45 8.5 20.0
AXPK-PLUS 4G300 58 3190 0.70 0.49 8.5 20.0
*Conductor temperature 20ºC **Conductor temperature 70ºC, direct burried
Product Name Current ratinginground* [A],directburried
Current ratinginair* [A]
Current ratinginair** [A]
Max. permisibleshortcircuit currentfor 1sec.***, kA
Max. DCresistanceofconductor *[Ω/km]
Max. ACresistanceofconductor**[Ω/km]
AXPK-PLUS 4G16 RE 78 64 75 1.5 1.91 2.3
AXPK-PLUS 4G16 RM 78 64 75 1.5 1.91 2.3
AXPK-PLUS 5G16 RE 78 64 75 1.5 1.91 2.3
AXPK-PLUS 4G25 100 83 105 2.3 1.20 1.5
AXPK-PLUS 5G25 100 83 105 2.3 1.20 1.5
AXPK-PLUS 4G35 125 105 130 3.3 0.868 1.0
AXPK-PLUS 5G35 125 105 130 3.3 1.2 1.5
AXPK-PLUS 4G50 150 125 165 4,7 0.641 0.77
AXPK-PLUS 4G70 185 155 205 6.6 0.443 0.53
AXPK-PLUS 4G95 220 190 245 8.9 0.320 0.39
AXPK-PLUS 4G120 255 220 280 11.3 0.253 0.31
AXPK-PLUS 4G150 290 250 320 14.1 0.206 0.25
AXPK-PLUS 4G185 330 285 365 17.4 0.164 0.20
AXPK-PLUS 4G240 375 330 430 22.6 0.125 0.16
AXPK-PLUS 4G300 430 380 480 28.3 0.100 0.13
*Conductor temperature 70º **Conductor temperature 90ºC
***Initial temperature of conductor before short circuit 90ºC, final temperature of conductor after short circuit 250ºC
The ratings are based on the following conditions: maximum conductor temperature- 90ºC, ground temperature-- 15ºC,
air temperature- 25ºC, thermal resistivity of soil- 1,0 ºKm/W, depth of burial- 0,7m.
Product Name Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
AXPK-PLUS 4G16 RE
AXPK-PLUS 5G16 RE
AXPK-PLUS 4G16 RM
AXPK-PLUS 4G25
AXPK-PLUS 5G25
AXPK-PLUS 4G35
AXPK-PLUS 5G35
AXPK-PLUS 4G50
AXPK-PLUS 4G70
AXPK-PLUS 4G95
AXPK-PLUS 4G120
AXPK-PLUS 4G150
AXPK-PLUS 4G185
AXPK-PLUS 4G240
AXPK-PLUS 4G300
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
500
500
500
500
K12
K12
K12
K14
K14
K16
K16
K18
K20
K20
K22
K20
K22
K22
K24
4741532120106
4741532120120
4741532120090
4741532120137
4741532120281
4741532120151
4741532120274
4741532120168
4741532120175
4741532120182
4741532120199
4741532120205
4741532120212
4741532120229
4741532120236
20079318
20097601
20079317
20076250
20163987
20076251
20163932
20076252
20076253
20076254
20076255
20076256
20076257
20076258
20076259
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
ApplicationPower cable with stranded compacted aluminium conductor. The cable is halogen free. For fixed installation indoors and outdoors, perfect forploughing down. Suitable for cable ducts and house connections.
Flame retardanceIEC 60332-1-2 - Vertical flame propagationfor a single insulated wire or cable
ApprovalCE
StandardCENELEC HD 308 S2 Identification of cores in cablesIEC 60502-1 Construction StandardCENELEC HD 603 Part 5 Section D Harmonized construction standardHD 60364-5-52 Selection and erection of electrical equipment. Wiring systems.IEC 60228 Conductor standardSFS 4879 0.6/1 kV XLPE insulated Al and Cu wires.
ConstructionCable Shape Round.Conductors 16 mm² – stranded and compacted or solid round aluminium conductor;
25 mm² - stranded, compacted and annealed aluminium conductor;35–300 mm2 – stranded, compacted and annealed sector shaped aluminium conductor.
Conductor Insulation XLPE compound.Marking of cores Phase conductors: brown, black, grey, blue.
PEN conductor: yellow-green.Outer Sheath Black halogen-free self-extinguishing PE compound.Example of marking on sheath AXPK-PLUS 1KV 4G16 DRAKA "Date and time", metre marked.
TemperatureMaximum operating Temperature 90ºCTemparatures at installation [°C] Lowest cable temperature during installation: -20 ºC below 0 ºC special extra precaution is
recommended.
FeaturesCPR Performance class EcaUV resistance Good.
ElectricalMax. short circuit temperature [°C] 250ºC
Power Cables 1kV
AXPK-PLUS 0,6/1(1,2) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
30 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 31We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product NameCable diameter[mm]
Conductor weight[kg/km]
Cable weight[kg/km]
Min. permissiblebending radiusduring laying [m]
Min.permissiblebending radius at finalinstallation [m]
Max. permisible shortcircuit current for 1sec.***, kA
AXPK 4G16 RE 20 165 370 0.24 0.17 1.5
AXPK 4G16 RM 20 165 370 0.24 0.17 1.5
AXPK 5G16 RE 20 207 435 0.25 0.18 1.5
AXPK 4G25 21 265 615 0,26 0,19 2,3
AXPK 5G25 25 332 670 0.31 0.22 2,3
AXPK 4G35 23 365 865 0,28 0,20 3,3
AXPK 4G50 27 495 1025 0,31 0,23 4,7
AXPK 4G70 30 720 1400 0,36 0,26 6,6
AXPK 4G95 34 995 1840 0,41 0,29 8,9
AXPK 4G120 38 1260 1900 0,46 0,33 11,3
AXPK 4G150 42 1550 2300 0,51 0,36 14,1
AXPK 4G185 47 1950 2800 0,57 0,4 17,4
AXPK 4G240 53 2550 3700 0,64 0,45 22,6
AXPK 4G300 58 3190 4600 0,7 0,49 28,3
*** Initial temperature of conductor before short circuit 90ºC, final temperature of conductor after short circuit 250ºC
Product Name Max. permissiblepulling force with apulling grip [kN]
Max. permissiblepulling force with apulling eye [kN]
Max. DCresistance ofconductor *[Ω/km]
Max. ACresistance ofconductor **[Ω/km]
Current rating inground* [A],direct burried
Current rating inair* [A]
Current rating inair** [A]
AXPK 4G16 RE 0.9 3.2 1.91 2.3 78 64 75
AXPK 4G16 RM 0.9 3.2 1.91 2.3 78 64 75
AXPK 5G16 RE 1.1 4 1.91 2.3 78 64 75
AXPK 4G25 1,5 5 1,2 1,5 100 83 105
AXPK 5G25 1.8 6.2 1,2 1,5 100 83 105
AXPK 4G35 2,1 7 0,868 1.0 125 105 130
AXPK 4G50 3 10 0,641 0,77 150 125 165
AXPK 4G70 4,2 14 0,443 0,53 185 155 205
AXPK 4G95 5,7 19 0,320 0,39 220 190 245
AXPK 4G120 7,2 20 0,253 0,31 255 220 280
AXPK 4G150 8,5 20 0,206 0,25 290 250 320
AXPK 4G185 8,5 20 0,164 0,2 330 285 365
AXPK 4G240 8,5 20 0,125 0,16 375 330 430
AXPK 4G300 8,5 20 0,125 0,13 430 380 480
*Conductor temperature 20ºC **Conductor temperature 70ºC
The ratings are based on the following conditions: maximum conductor temperature- 90ºC, ground temperature- 15ºC,
air temperature- 25ºC, thermal resistivity of soil- 1,0 ºKm/W, depth of burial- 0,7m.
Product Name Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
AXPK 4G16 RE
AXPK 4G16 RM
AXPK 5G16 RE
AXPK 4G25
AXPK 5G25
AXPK 4G35
AXPK 4G50
AXPK 4G70
AXPK 4G95
AXPK 4G120
AXPK 4G150
AXPK 4G185
AXPK 4G240
AXPK 4G300
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
500
500
500
500
K12
K12
K12
K14
K16
K16
K16
K20
K20
K22
K20
K20
K22
K24
4741532130105
4741532130112
4741532130129
4741532130136
4741532130150
4741532130167
4741532130181
4741532130204
4741532130228
4741532130235
4741532130259
4741532130266
4741532130273
4741532130280
20076220
20076221
20074980
20076222
20074981
20076224
20076226
20076228
20076230
20076231
20076233
20076234
20076235
20076236
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
ApplicationPower cable with aluminium conductor. For fixed installation indoors and outdoors, perfect for ploughing down. Suitable for cable ducts andhouse connections.
ApprovalCE
Flame retardanceEN 60332-1-2 - Vertical flame propagation for asingle insulated wire or cable
StandardCENELEC HD 308 S2 Identification of cores in cablesIEC 60502-1 Construction StandardCENELEC HD 603 Part 5 Section D Harmonized construction standardIEC 60228 Conductor standardSFS 4879 0.6/1 kV XLPE insulated Al and Cu wires.
ConstructionCable Shape Round.Conductors 16 mm² – stranded and compacted or solid round aluminium conductor;
25 mm² - stranded, compacted and annealed aluminium conductor;35–300 mm2 – stranded, compacted and annealed sector shaped aluminium conductor.
Conductor Insulation XLPE compound.Marking of cores Phase conductors: brown, black, grey, blue;
PEN conductor: yellow-green.Outer Sheath Black PVC.Example of marking on sheath AXPK 1KV 4G16 DRAKA "Date and time", metre marked.
TemperatureMaximum operating Temperature 90ºCTemparatures at installation [°C] Lowest cable temperature during installation: -15 ºC below 0 ºC special precaution is
recommended.
FeaturesCPR Performance class EcaUV resistance Good.
ElectricalMax. short circuit temperature [°C] 250 ºC
Power Cables 1kV
AXPK 0,6/1(1,2) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
32 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 33We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Product NameCable diameter [mm]
Conductor weight[kg/km]
Cable weight [kg/km] Min.permissible bendingradius during laying [m]
Min.permissible bendingradius at finalinstallation [m]
ARLC 4G16 + 2.5Cu 18.1 186 380 0.24 0.17
ARLC 4G25 + 2.5Cu 22.6 286 545 0.26 0.19
ARLC 4G35 + 2.5Cu 26.1 386 715 0.28 0,20
ARLC-PLUS 4G16 + 2.5Cu 18.1 186 355 0.24 0.17
ARLC-PLUS 4G25 + 2.5Cu 22.6 286 515 0.26 0.19
ARLC-PLUS 4G35 + 2.5Cu 26.1 386 690 0.28 0.20
Product Name Max. permissible pullingforce with a pulling grip [kN]
Max. permissible pullingforce with a pulling eye [kN]
Max. DC resistance ofconductor * [Ω/km]
Max. AC resistance ofconductor ** [Ω/km]
ARLC 4G16 + 2.5Cu 0.9 3.2 1.91 2.3
ARLC 4G25 + 2.5Cu 1.5 5 1.2 1.5
ARLC 4G35 + 2.5Cu 2.1 7 0.868 1.0
ARLC-PLUS 4G16 + 2.5Cu 0.9 3.2 1.91 2.3
ARLC-PLUS 4G25 + 2.5Cu 1.5 5 1.2 1.5
ARLC-PLUS 4G35 + 2.5Cu 2.1 7 0.868 1.0
*Conductor temperature 20ºC **Conductor temperature 70ºC
Product Name Current rating in ground*[A], direct burried
Current rating in air* [A] Current rating in air** [A] Max. permisible shortcircuit current for 1 sec.***,kA
ARLC 4G16 + 2.5Cu 78 64 75 1.5
ARLC 4G25 + 2.5Cu 100 83 105 2,3
ARLC 4G35 + 2.5Cu 125 105 130 3,3
ARLC-PLUS 4G16 + 2.5Cu 78 64 75 1.5
ARLC-PLUS 4G25 + 2.5Cu 100 83 105 2,3
ARLC-PLUS 4G35 + 2.5Cu 125 105 130 3,3
*Conductor temperature 70ºC **Conductor temperature 90ºC
*** Initial temperature of conductor before short circuit 90ºC, final temperature of conductor after short circuit 250ºC
The ratings are based on the following conditions: maximum conductor temperature - 90ºC, ground temperature - 15ºC,
air temperature - 25ºC, thermal resistivity of soil - 1,0 ºKm/W, depth of burial - 0,7m
Product Name Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
ARLC 4G16 + 2.5Cu
ARLC 4G25 + 2.5Cu
ARLC 4G35 + 2.5Cu
ARLC-PLUS 4G16 + 2.5Cu
ARLC-PLUS 4G25 + 2.5Cu
ARLC-PLUS 4G35 + 2.5Cu
1000
1000
500
1000
1000
500
K12
K14
K14
K12
K14
K14
4741532130440
4741532130457
4741532130464
4741532130471
4741532130488
4741532130495
20111654
20076248
20076249
20112072
20164811
20172988
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
ApplicationRoad lighting cable with aluminium conductor and copper signal conductor.
Alternative Product NameARLC - HF
Flame retardanceIEC 60332-1-2 - Vertical flame propagation for asingle insulated wire or cable
ApprovalCE
StandardIEC 60502-1 Construction StandardCENELEC HD 308 S2 Identification of cores in cablesCENELEC HD 603 Part 5 Section D Harmonized construction standardIEC 60228 Conductor standard
ConstructionCable Shape Round.Conductors 16 mm²: solid round aluminium conductor;
25 mm²: stranded round aluminium conductor;35 mm²: sector shaped aluminium conductor.
Center conductor 2.5 mm²: solid round insulated copper signal conductor.Conductor Insulation XLPE.Lay up / Shielding Four insulated conductors stranded together.Marking of cores Phase conductors: brown, black, grey;
PEN conductor: yellow-green;Signal conductor: black.
Outer Sheath ARLC : PVC;ARLC - Plus: black self-extinguishing halogen-free compound.
Example of marking on sheath ARLC DRAKA "Data ir laikas", ilgio žymuo
TemperatureMaximum operating Temperature 90ºCTemparatures at installation [°C] Žemiausia rekomenduojama temperatūra montuojant: ARLC -15 ºC, žemiau 0 ºC
rekomenduojama imtis atsargumo priemonių; ARLC-PLUS -20 ºC, žemiau 0 ºCrekomenduojama imtis atsargumo priemonių.
FeaturesUV resistance Good.
ElectricalMax. short circuit temperature [°C] 250ºC
Power Cables 1kV
ARLC and ARLC-PLUS 0,6/1(1,2) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
34 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 35We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductorresistance Ω/km
Screen resistance*Ω/km
Inductance in trefoil/inflat* mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
1x50/16 0,641 1,15 0,41/0,73 0,23 0,23 0,4 1,3
1x70/16 0,443 1,15 0,38/0,69 0,22 0,28 0,5 1,6
1x95/25 0,320 0,727 0,36/0,66 0,21 0,32 0,6 1,8
1x120/25 0,253 0,727 0,35/0,64 0,20 0,35 0,7 2,0
1x150/25 0,206 0,727 0,34/0,62 0,20 0,38 0,7 2,1
1x185/25 0,164 0,524 0,32/0,61 0,20 0,41 0,8 2,3
1x240/35 0,125 0,524 0,31/0,58 0,18 0,46 0,9 2,6
1x300/35 0,100 0,524 0,30/0,56 0,18 0,51 1,0 2,9
1x400/35 0,0778 0,524 0,29/0,54 0,17 0,58 1,1 3,3
1x500/35 0,0605 0,254 0,28/0,52 0,16 0,64 1,2 3,6
1x630/35 0,0469 0,524 0,28/0,51 0,16 0,72 1,4 4,1
1x800/50 0,0367 0,387 0,27/0,49 0,15 0,70 1,5 4,5
1x1000/50 0,0291 0,387 0,27/0,48 0,15 0,83 1,6 4,7
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
1x50/16 155 160 195 5,2 4,7
1x70/16 200 190 235 7,2 6,6
1x95/25 235 230 280 9,9 8,9
1x120/25 265 265 325 12,4 11,3
1x150/25 300 300 370 15,6 14,2
1x185/35 330 345 425 19,2 17,5
1x240/35 385 400 490 25,0 22,7
1x300/35 435 465 565 31,2 28,3
1x400/35 510 555 680 41,6 37,8
1x500/35 570 635 775 52,0 47,2
1x630/35 635 720 880 65,6 59,5
1x800/50 695 822 1010 83,2 75,6
1x1000/50 760 920 1130 103,7 94,5
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
1x50/16
1x70/16
1x95/25
1x120/25
1x150/25
1x185/35
1x240/35
1x300/35
1x400/35
1x500/35
1x630/35
1x800/50
1x1000/50
500
500
500
500
500
500
500
500
500
500
500
500
500
K11
K11
K12
K12
K12
K14
K14
K16
K16
K18
K20
K20
K24
7330384710664
7330384713948
7330384710671
7330384713955
7330384710688
7330384713962
7330384708920
7330384713979
7330384709651
7330384713986
7330384709316
7330384713993
7330384722049
20102173
20113259
20102174
20113260
20040268
20113271
20078241
20113272
20102175
20113273
20102176
20113274
20227891
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationSingle-core, distribution cable for outdoor use in 3-phase formation. Installation in pipes and ground/water. Both radial and longitudinal watersealed. Can be ploughed down. The outer sheath has a conductive layer that greatly extends the possibilities to do a sheath testing before,during and after installation. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N10XC7A5T5E-AR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnviromantal Declaration - AXLJ-TTCL
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section K Harmonized Construction StandardCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape RoundConductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 2,96 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminium tapeRadial water blocking Aluminum-PE laminate, bonded to sheathRipcord AramidOuter Sheath PE, natural UV-protectedExample of marking on sheath AXLJ-TTCL TSLF 12kV 1x50 AFR/16 DRAKA "Date and time", metre markedSemi-conducting layer in outer sheath Yes (facilitates sheath testing)
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 75 kV
Power Cables 12 kV
AXLJ-TTCL TSLF 6/10(12) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
36 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 37We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors andscreen area [mm2]
Conductorresistance Ω/km
Screenresistance*Ω/km
Inductance intrefoil/in flat*mH/km
Reactance intrefoil/in flat*Ω/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
1x50/16 0,641 1,15 0,40/0,72 0,13/0,23 0,25 0,5 1,4
1x70/16 0,443 1,15 0,37/0,69 0,12/0,22 0,28 0,5 1,6
1x95/25 0,320 0,727 0,36/0,66 0,11/0,21 0,32 0,6 1,8
1x120/25 0,253 0,727 0,34/0,64 0,11/0,20 0,35 0,7 2,0
1x150/25 0,206 0,727 0,33/0,62 0,10/0,20 0,38 0,7 2,1
1x185/25 0,164 0,727 0,32/0,60 0,10/0,19 0,41 0,8 2,3
1x240/35 0,125 0,524 0,31/0,58 0,10/0,18 0,46 0,9 2,6
1x300/35 0,100 0,524 0,30/0,59 0,09/0,17 0,50 1,0 3,0
1x400/35 0,0778 0,524 0,29/0,54 0,09/0,17 0,57 1,1 3,3
1x500/35 0,0605 0,524 0,28/0,52 0,09/0,16 0,58 1,1 3,3
1x630/35 0,0469 0,524 0,27/0,50 0,09/0,16 0,64 1,2 3,6
1x800/50 0,0367 0,387 0,27/0,49 0,09/0,15 0,79 1,5 4,5
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
1x50/16 155 160 195 5,2 4,7
1x70/25 200 190 235 7,2 6,6
1x95/25 235 230 280 9,9 8,9
1x120/25 265 265 325 12,4 11,3
1x150/25 300 300 370 15,6 14,2
1x185/25 330 345 425 19,2 17,5
1x240/35 385 400 490 25,0 22,7
1x300/35 435 460 565 31,0 28,3
1x400/35 510 555 680 41,6 37,8
1x500/35 570 635 775 52,0 47,2
1x630/35 635 720 880 65,6 59,5
1x800/50 695 822 1010 83,2 75,6
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
1x50/16
1x70/16
1x95/25
1x120/25
1x150/25
1x185/25
1x240/35
1x300/35
1x400/35
1x500/35
1x630/35
1x800/50
500
500
500
500
500
500
500
500
500
500
500
500
K11
K11
K12
K12
K12
K14
K14
K16
K16
K18
K20
K20
7330384720878
7330384720885
7330384720892
7330384720908
7330384720915
7330384720922
7330384720939
7330384720946
7330384720953
7330384720960
7330384720977
7330384720984
20218299
20218300
20218371
20218372
20218373
20218374
20218375
20218376
20218377
20218378
20218379
20218380
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationHalogen-free, flame retardant and self-extinguishing in case of fire. Smoke in the event of fire is limited, transparent (to facilitate evacuation) andnot harmful to electronic equipment. Radial and longitudinal water sealed distribution cable for use indoors and outdoors for 3-phaseformation. Installation in pipes and ground. Ploughing down is not recommended. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N10XC7A5Z1-AR
EnvironmentalEnviromantal Declaration - AXQJ-TT Pure TSLI
StandardCENELEC HD 620 Part 10 Section M Harmonized Construction StandardCENELEC HD 620 Part 10 Section K Harmonized Construction StandardCENELEC HD 604 Halogen free materialSS-EN 60754-1, -2 Corrosive gasesSS-EN 61034-1, -2 Smoke densityEN 50575:2014 Power, control and communication cables - Cables for general applications in construction
works subject to reaction to fire requirements
ConstructionCable Shape RoundConductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 2,96 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminum tapeRadial water blocking Aluminium laminate bonded to the sheathRipcord AramidOuter Sheath Halogen free compound, blackExample of marking on sheath AXQJ-TT Pure TSLI 12kV 1x240 AFR/35 D-s2d2a2 DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesCPR Performance class Dca-s2d2a2Bending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 75 kV
Power Cables 12 kV
AXQJ-TT Pure TSLI 6/10(12) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
38 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 39We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductorresistance Ω/km
Screen resistance*Ω/km
InductancemH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
3x1x50/16 0,641 1,15 0,40 0,13 0,25 0,5 1,4
3x1x70/16 0,443 1,15 0,38 0,12 0,28 0,5 1,6
3x1x95/25 0,320 0,727 0,36 0,11 0,32 0,6 1,8
3x1x120/25 0,253 0,727 0,35 0,11 0,35 0,7 2,0
3x1x150/25 0,206 0,727 0,34 0,11 0,38 0,7 2,1
3x1x185/35 0,164 0,524 0,32 0,10 0,41 0,8 2,3
3x1x240/35 0,125 0,524 0,31 0,10 0,46 0,9 2,6
3x1x300/35 0,100 0,524 0,30 0,09 0,51 1,0 2,9
3x1x400/35 0,0778 0,524 0,29 0,09 0,58 1,1 3,3
3x1x500/35 0,0605 0,524 0,28 0,09 0,64 1,2 3,6
*Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
3x1x50/16 155 160 195 5,2 4,7
3x1x70/16 200 190 235 7,2 6,6
3x1x95/25 235 230 280 9,9 8,9
3x1x120/25 265 265 325 12,4 11,3
3x1x150/25 300 300 370 15,6 14,2
3x1x185/35 330 345 425 19,2 17,5
3x1x240/35 385 400 490 25,0 22,7
3x1x300/35 435 460 565 31,2 28,3
3x1x400/35 510 555 680 41,6 37,8
3x1x500/35 570 635 775 52,0 47,2
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x1x50/16
3x1x70/16
3x1x95/25
3x1x120/25
3x1x150/25
3x1x185/35
3x1x240/35
3x1x300/35
3x1x400/35
3x1x500/35
500
500
500
500
500
500
500
500
500
500
K20
K20
K22
K22
K24
K24
K26
K26
K28
K28
7330384709057
7330384721851
7330384721868
7330384721875
7330384721882
7330384721899
7330384709002
7330384721905
7330384721912
7330384721929
20087880
20114706
20114707
20114708
20114709
20114710
20102177
20114711
20114712
20114713
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationSingle-core, distribution cable for outdoor use in triplex formation. Installation in pipes and ground/water. Both radial and longitudinal watersealed. Can be ploughed down. The outer sheath has a conductive layer that greatly extends the possibilities to do a sheath testing before,during and after installation. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N10XC7A5T5E-AR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnviromantal Declaration - AXLJ-TTCL
StandardCENELEC HD 620 Part 10 Section K Harmonized Construction StandardCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape RoundConductors Stranded, round, compacted aluminium acc. to IEC 60228 class 2, longitudinally watertightInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 2,96 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminum tapeRadial water blocking Aluminum-PE laminate, bonded to sheathRipcord AramidOuter Sheath PE, natural UV-protectedExample of marking on sheath AXLJ-TTCL TSLF 12kV 1x240 AFR/35 DRAKA "Date and time", metre markedSemi-conducting layer in outer sheath Yes (facilitates sheath testing)
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 75 kV
Power Cables 12 kV
AXLJ-TTCL TSLF Triplex 6/10(12) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
40 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 41We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors andscreen area [mm2]
Conductorresistance Ω/km
Screenresistance*Ω/km
Inductance intrefoil/in flat*mH/km
Reactance intrefoil/in flat*Ω/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
1x50/16 0,641 1,15 0,40/0,72 0,13/0,23 0,25 0,5 1,4
1x95/25 0,320 0,727 0,36/0,66 0,11/0,21 0,32 0,6 1,8
1x150/25 0,206 0,727 0,33/0,62 0,10/0,20 0,38 0,7 2,1
1x240/35 0,125 0,524 0,31/0,58 0,10/0,18 0,46 0,9 2,6
1x400/35 0,0778 0,524 0,29/0,54 0,09/0,17 0,57 1,1 3,3
1x500/35 0,0605 0,524 0,28/0,52 0,09/0,16 0,58 1,1 3,3
1x630/35 0,0469 0,524 0,27/0,50 0,09/0,16 0,64 1,2 3,6
1x800/50 0,0367 0,387 0,27/0,49 0,09/0,15 0,79 1,5 4,5
1x1000/50 0,0291 0,387 0,27/0,48 0,09/0,15 0,83 1,6 4,7
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
1x50/16 155 160 195 5,2 4,7
1x95/25 235 230 280 9,9 8,9
1x150/25 300 300 370 15,6 14,2
1x240/35 385 400 490 25,0 22,7
1x400/35 510 555 680 41,6 37,8
1x500/35 570 635 775 52,0 47,2
1x630/35 635 720 880 65,6 59,5
1x800/50 695 822 1010 83,2 75,6
1x1000/50 760 920 1130 103,7 94,5
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x1x50/16
3x1x70/16
3x1x95/25
3x1x120/25
3x1x150/25
3x1x185/35
3x1x240/35
3x1x300/35
3x1x400/35
3x1x500/35
500
500
500
500
500
500
500
500
500
500
K20
K20
K22
K24
K24
K24
K24
K26
K28
K28
7330384720991
7330384721004
7330384721011
7330384721028
7330384721035
7330384721042
7330384721059
7330384721066
7330384721073
7330384721080
20218381
20218382
20218383
20218384
20218385
20218386
20218387
20218388
20218389
20218390
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationHalogen-free, flame retardant and self-extinguishing in case of fire. Smoke in the event of fire is limited, transparent (to facilitate evacuation) andnot harmful to electronic equipment. Radial and longitudinal water sealed distribution cable for use indoors and outdoors for 3-phaseformation. Installation in pipes and ground. Ploughing down is not recommended. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N10XC7A5Z1-AR
EnvironmentalEnviromantal Declaration - AXQJ-TT Pure TSLI
StandardCENELEC HD 620 Part 10 Section M Harmonized Construction StandardCENELEC HD 620 Part 10 Section K Harmonized Construction StandardCENELEC HD 604 Halogen free materialSS-EN 60754-1, -2 Corrosive gasesSS-EN 61034-1, -2 Smoke densityEN 50575:2014 Power, control and communication cables - Cables for general applications in construction
works subject to reaction to fire requirements
ConstructionCable Shape RoundConductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 2,96 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminum tapeRadial water blocking Aluminium laminate bonded to the sheathRipcord AramidOuter Sheath Halogen free compound, blackExample of marking on sheath AXQJ-TT Pure TSLI 12kV 1x240 AFR/35 D-s2d2a2 DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesCPR Performance class Dca-s2d2a2Bending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 75 kV
Power Cables 12 kV
AXQJ-TT Pure TSLI Triplex 6/10(12) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
42 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 43We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductor resistanceΩ/km
Centre conductorresistance Ω/km
InductancemH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrentA/km
3x50AL+35CU 0,641 0,524 0,40 0,13 0,25 0,5 1,4
3x70AL+35CU 0,443 0,524 0,38 0,12 0,28 0,5 1,6
3x95AL+35CU 0,320 0,524 0,36 0,11 0,32 0,6 1,8
3x120AL+35CU 0,253 0,524 0,35 0,11 0,34 0,6 1,9
3x150AL+35CU 0,206 0,524 0,34 0,11 0,38 0,7 2,1
3x185AL+35CU 0,164 0,524 0,32 0,10 0,41 0,8 2,3
3x240AL+35CU 0,125 0,524 0,31 0,10 0,46 0,9 2,6
3x300AL+35CU 0,100 0,524 0,30 0,09 0,51 1,0 2,9
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
3x50AL+35CU 155 160 195 5,2 4,7
3x70AL+35CU 200 190 235 7,2 6,6
3x95AL+35CU 235 230 280 9,9 8,9
3x120AL+35CU 265 265 325 12,4 11,3
3x150AL+35CU 300 300 370 15,6 14,2
3x185AL+35CU 330 345 425 19,2 17,5
3x240AL+35CU 385 400 490 25,0 22,7
3x300AL+35CU 435 460 565 31,2 28,3
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x50AL+35CU
3x70AL+35CU
3x95AL+35CU
3x120AL+35CU
3x150AL+35CU
3x185AL+35CU
3x240AL+35CU
3x300AL+35CU
500
500
500
500
500
500
500
500
K20
K22
K24
K24
K24
K24
K26
K26
7330384715218
7330384715225
7330384710374
4705554
7330384707695
7330384705783
7330384705578
7330384709507
20118178
20118179
20088773
20078178
20102199
20102200
20102201
20102202
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationAHXAMK-W (Wiski™) is a assembled from 3-single core cables wrapped around a compact copper conductor. Each cable is radial andlongitudinal water sealed. For fixed outdoor installation, can be ploughed down.
Alternative Product NameFI-N10XA4EC-AR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnvironmental declaration - AHXAMK-W
StandardCENELEC HD 620 Part 10 Section F Harmonized Construction Standard
ConstructionCable Shape RoundConductors Stranded, round, compacted aluminium acc. to IEC 60228 class 2, longitudinally watertightInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 2,96 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeCore assembly The cores are wrapped around a compact copper conductor. Stranded, round and compacted
copper acc. IEC 60228 class 2Radial water blocking Aluminum-PE laminate, bonded to sheathOuter Sheath PE, blackExample of marking on sheath AHXAMK-W 6/10 kV 3x150Al+35Cu DRAKA Phase 1 + "Date and time", 1 core is metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 75 kV
Power Cables 12 kV
AHXAMK-W 6/10(12) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
44 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 45We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductor resistanceΩ/km
Screen resistanceΩ/km
Inductance mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
3x50/16 0,641 1,2 0,33 0,10 0,25 0,5 1,4
3x95/25 0,320 0,8 0,30 0,09 0,32 0,6 1,8
3x150/25 0,206 0,8 0,28 0,09 0,38 0,7 2,0
3x240/35 0,125 0,6 0,23 0,09 0,46 0,8 2,5
3x300/35 0,100 0,6 0,26 0,08 0,51 1,0 2,9
Conductors andscreen area[mm2]
Current rating atcore temp. 65ºC inground A
Current rating atcore temp. 65ºC inair A
Current rating atcore temp. 90ºC inair A
Max. short circuitcurrent on the conductorduring 1s at initial temp.65ºC kA
Max. short circuitcurrent on the conductorduring 1s at initial temp.90ºC kA
Max impulse current kA
3x50/16 145 130 160 5,2 4,7 55
3x95/25 205 190 230 9,9 8,9 65
3x150/25 260 250 305 15,6 14,2 70
3x240/35 340 330 400 25,0 22,7 70
3x300/35 380 375 460 31,2 28,3 70
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x50/16
3x95/25
3x150/25
3x240/35
3x300/35
500
500
500
500
500
K18
K20
K22
K24
K26
7330384701129
7330384701143
7330384701068
7330384701099
7330384715065
20078179
20095493
20078182
20087130
20118045
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationAXLJ-RMF is a 3-core cable designed for replacement of bare overhead lines. Primary developed to be ploughed down but thanks to the robustdesign the cable can stand the stresses that appears when laid in water with moderate currents and limited depth. Ripcords for easier and saferstripping of the outer sheath.
Alternative Product NameSE-N10XC7E-AR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnviromantal Declaration - AXLJ-F, -RMFLT
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section M Harmonized Construction StandardIEC 60502-2 Construction standard
ConstructionCable Shape TriangularConductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 2,96 mmOuter semi-conducting layer BondedInner covering Conductive tapeShield / Screen Annealed copper wiresRipcord AramidOuter Sheath Composite PE, BlackExample of marking on sheath AXLJ-RMF 12kV 3x150/25 LT DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesFire Propagation Cable is not flame retardant.UV resistance GoodBending radius In fixed installation: 8 x D
When pulling-in: 12 x DWhen plowing down: 8 x D
Min. Bending radius at final installation 8 xDMin. Bending radius at during installation 12 xD
ElectricalMax. short circuit temperature [°C] 250 ºCImpulse voltage [kV] 75 kV.
Power Cables 12 kV
AXLJ-RMF 6/10(12) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
46 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 47We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductor resistanceΩ/km
Screen resistanceΩ/km
Inductance mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
3x50/16 0,641 1,2 0,34 0,11 0,23 0,5 1,4
3x70/16 0,433 1,2 0,31 0,10 0,28 0,5 1,6
3x95/25 0,320 0,8 0,31 0,10 0,30 0,6 1,8
3x120/25 0,253 0,8 0,29 0,09 0,35 0,7 2,0
3x150/25 0,206 0,8 0,29 0,09 0,35 0,7 2,0
3x185/35 0,164 0,6 0,27 0,09 0,41 0,8 2,3
3x240/35 0,125 0,6 0,27 0,09 0,43 0,8 2,5
3x300/35 0,100 0,6 0,26 0,08 0,51 1,0 2,9
Conductors andscreen area[mm2]
Current rating atcore temp. 65ºC inground A
Current rating atcore temp. 65ºC inair A
Current rating atcore temp. 90ºC inair A
Max. short circuitcurrent on the conductorduring 1s at initial temp.65ºC kA
Max. short circuitcurrent on the conductorduring 1s at initial temp.90ºC kA
Max impulse current kA
3x50/16 145 130 160 5,2 4,7 55
3x70/16 175 155 190 7,2 6,6 60
3x95/25 205 190 230 9,9 8,9 65
3x120/25 230 220 265 12,4 11,3 65
3x150/25 260 250 305 15,6 14,2 70
3x185/35 290 280 340 19,2 17,5 70
3x240/35 340 330 400 25,0 22,7 70
3x300/35 380 375 460 31,2 29,8 70
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x50/16
3x70/16
3x95/25
3x120/25
3x150/25
3x185/35
3x240/35
3x300/35
500
500
500
500
500
500
500
500
K18
K18
K20
K20
K22
K24
K24
K24
7330384720113
7330384720120
7330384720137
7330384720144
7330384720151
7330384720175
7330384720182
7330384720212
20203881
20203882
20203883
20203884
20203885
20203886
20203887
20203888
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationHalogen-free, flame retardant and self-extinguishing in case of fire. Smoke in the event of fire is limited, transparent (to facilitate evacuation) andnot harmful to electronic equipment. The cable is primarily designed for indoor installation, tunnels, etc. The cable can be installed outdoorsand in ground but ploughing is not recommended. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N10XC7Z1-AR
EnvironmentalEnvironmental Declaration - AXQJ-RMF Pure
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section M Harmonized Construction StandardIEC 60502-2 Construction standardCENELEC HD 604 Halogen free materialSS-EN 60754-1, -2 Corrosive gasesSS-EN 61034-1, -2 Smoke densityEN 50575:2014 Power, control and communication cables - Cables for general applications in construction
works subject to reaction to fire requirements
ConstructionCable Shape TriangularConductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 2,96 mmOuter semi-conducting layer BondedInner covering Conductive tapeShield / Screen Annealed copper wiresRipcord AramidOuter Sheath Halogen free compound, blackExample of marking on sheath AXQJ-RMF Pure 12kV 3x50/16 LT B2-s1d0a2 DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesCPR Performance class B2ca-s1d0a2Bending radius In fixed installation: 8 x D
When pulling-in: 12 x DWhen plowing down: 8 x D
ElectricalMax. short circuit temperature [°C] 250 ºCImpulse voltage [kV] 75 kV.
Power Cables 12 kV
AXQJ-RMF Pure 6/10(12) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
48 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 49We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors andscreen area[mm2]
Conductorresistance Ω/km
Screenresistance*Ω/km
Inductance mH/km
ReactanceΩ/km
CapacitanceµF/km
Zero sequenceimpedance Z0Ω/km
Chargingcurrent/phase A/km
Earth faultcurrentA/km
3x50/16 0,641 1,2 0,33 0,10 0,25 1,31+j0,87 0,5 1,4
3x70/16 0,443 1,2 0,31 0,10 0,28 1,06+j0,84 0,5 1,6
3x95/25 0,320 0,8 0,30 0,09 0,32 0,92+j0,72 0,6 1,8
3x120/25 0,253 0,8 0,28 0,09 0,35 0,83+j0,70 0,7 2,0
3x150/25 0,206 0,8 0,28 0,09 0,38 0,76+j0,68 0,7 2,1
3x185/35 0,164 0,6 0,27 0,09 0,41 0,71+j0,58 0,8 2,3
3x240/35 0,125 0,6 0,26 0,08 0,46 0,65+j0,56 0,9 2,6
3x300/35 0,100 0,6 0,26 0,08 0,51 0,61+j0,55 1,0 2,9
*Note! Screen resistance is the sum of copper wires and aluminum tape. The screen cross-section is made up of 60% copper.
Conductors andscreen area[mm2]
Current rating atcore temp. 65ºCin ground A
Current rating atcore temp. 65ºCin air A
Current rating atcore temp. 90ºCin air A
Max. short circuitcurrent on theconductor during 1sat initial temp. 65ºCkA
Max. short circuitcurrent on theconductor during 1sat initial temp. 90ºCkA
Max. short circuitcurrent on the screenduring 1s kA
Max impulse currentkA
3x50/16 145 130 160 5,2 4,7 3,2 55
3x70/16 175 155 190 7,2 6,6 3,2 60
3x95/25 205 190 230 9,9 8,9 5 65
3x120/25 230 220 265 12,4 11,3 5 65
3x150/25 260 250 305 15,6 14,2 5 70
3x185/35 290 280 340 19,2 17,5 7 70
3x240/35 340 330 400 25,0 22,7 7 70
3x300/35 380 375 460 31,2 28,3 7 70
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
ElectricalMax. short circuit temperature [°C] 250°CImpulse voltage [kV] 75 kV
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x50/16
3x70/16
3x95/25
3x120/16
3x150/25
3x185/35
3x240/25
3x240/35
3x300/35
500
500
500
500
500
500
500
500
500
K18
K20
K20
K22
K24
K24
K24
K24
K26
7330384721783
7330384721776
7330384721769
20206411
20206412
20206413
CA.812373200001
20206415
20206416
CA.812373230001
20206417-5
20206418
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationAXCLJ-TT is just as AXALJ-TT totally water sealed. Radial water sealed by an aluminum laminate bonded to outer sheath and longitudinally watersealed with swellable tapes. The screen is made up of circular copper wires like AXALJ-TT, water blocking tapes (replacing water blocking yarns)and the cable has been complemented with two strong ripcords for easier and safer opening of the outer sheath. The cable is primarily designedfor ploughing down in ground, but thanks to its robust design can handle the stresses resulting from installation in lakes with limited currentsand of limited depth.
Alternative Product NameSE-N10XC7A5T5E-AR
Flame retardanceFlame retardant - Not applicable
FeatureThe corresponding options with aluminumscreen. - AXALJ-TT
EnvironmentalEnvironmental declaration - AXCLJ-TT
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape TriangularConductors Stranded, round, compacted aluminum acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 2,96 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeFiller PE-profilesInner covering Conductive tapeShield / Screen Round copper wires in contact with aluminum laminateRadial water blocking Aluminum-PE laminate, bonded to sheathRipcord AramidOuter Sheath Composite PE, BlackExample of marking on sheath AXCLJ-TT 12kV 3x50/16 DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 8 x D
When pulling-in: 12 x DWhen plowing down: 8 x D
Max Pulling force - pulling grip [N/mm2] Max. pulling forse = 5 x D ^ 2 (N)D = outer diameter of cable (mm)
Max Pulling force - pulling eye [N/mm2] Max. pulling forse = 30 x S (N)S = cross-sectional area of conductor (mm^2)
Power Cables 12 kV
AXCLJ-TT 6/10(12) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
50 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 51We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductor resistanceΩ/km
Screen resistanceΩ/km
Inductance mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
3x25/25 AL 1,20 1,2 0,36 0,11 0,20 0,4 1,1
3x50/25 AL 0,641 1,2 0,33 0,10 0,25 0,5 1,4
3x75/25 AL 0,443 1,2 0,31 0,10 0,28 0,5 1,6
3x95/35 AL 0,320 0,8 0,30 0,09 0,32 0,6 1,8
3x120/35 AL 0,253 0,8 0,28 0,09 0,35 0,7 2,0
3x150/35 AL 0,206 0,8 0,28 0,09 0,38 0,7 2,1
3x185/50 AL 0,164 0,6 0,27 0,09 0,41 0,8 2,3
3x240/50 AL 0,125 0,6 0,26 0,08 0,46 0,9 2,6
3x300/50 AL 0,0778 0,6 0,26 0,08 0,51 1,0 2,9
Conductors andscreen area[mm2]
Current rating atcore temp. 65ºC inground A
Current rating atcore temp. 65ºC inair A
Current rating atcore temp. 90ºC inair A
Max. short circuitcurrent on the conductorduring 1s at initial temp.65ºC kA
Max. short circuitcurrent on the conductorduring 1s at initial temp.90ºC kA
Max impulse current kA
3x25/25 AL 100 90 110 2,6 2,3 -
3x50/25 AL 145 130 160 5,2 4,7 55
3x70/25 AL 175 155 190 7,2 6,6 60
3x95/35 AL 205 190 230 9,9 8,9 65
3x120/35 AL 230 220 265 12,4 11,3 65
3x150/35 AL 260 250 305 15,6 14,2 70
3x185/50 AL 290 280 340 19,2 17,5 70
3x240/50 AL 340 330 400 25,0 22,7 70
3x300/50 AL 380 375 460 31,2 28,3 70
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
ElectricalMax. short circuit temperature [°C] 250 ºCImpulse voltage [kV] 75 kV
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x25/25 AL
3x50/25 AL
3x70/25 AL
3x95/35 AL
3x120/35 AL
3x150/35 AL
3x185/50 AL
3x240/50 AL
3x300/50 AL
500
500
500
500
500
500
500
500
500
K16
K18
K20
K20
K22
K24
K24
K24
K26
7330384717014
7330384717021
7330384717038
7330384717045
7330384717052
7330384717069
7330384717076
7330384717144
20158257
20151640
20151641
20151642
20151643
20151644
20151645
20151646
20152032
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationAXALJ-TT is just like its predecessor AXLJ-TT, totally water sealed. Radially water sealed by an aluminium laminate bonded to the outer sheathlongitudinally water sealed with swellable tapes. The screen is made up of circular aluminium wires, water blocking tapes (replacing the waterswellable yarns) and the cable has been complemented with two strong ripcords for easier and safer opening of the outer sheath. The cable isprimarily designed for ploughing down in ground, but thanks to its robust design can handle the stresses resulting from installation in lakeswith limited currents and of limited depth.
Alternative Product NameSE-N10XA5E-AR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnviromantal Declaration - AXALJ-TT
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape TriangularConductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 2,96 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeFiller PE-profilesShield / Screen Round aluminium wires in contact with aluminium laminateRadial water blocking Aluminium laminate bonded to the sheathRipcord AramidOuter Sheath Composite PE, blackExample of marking on sheath AXALJ-TT 12kV 3x50/25 AL DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 8 x D
When pulling-in: 12 x DWhen plowing down: 8 x D
Max Pulling force - pulling grip [N/mm2] Max pulling force = 5 x D^2 (N)D = outer diameter of the cable (mm)
Max Pulling force - pulling eye [N/mm2] Max pulling force = 30 x S (N)S = cross-sectional area of the conductor (mm^2)
Power Cables 12 kV
AXALJ-TT 6/10(12) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
Conductors and screenarea [mm2]
Conductor resistanceΩ/km
Screen resistanceΩ/km
Inductance mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
3x25/25 AL 1,20 1,2 0,36 0,11 0,20 0,4 1,1
3x50/25 AL 0,641 1,2 0,33 0,10 0,25 0,5 1,4
3x75/25 AL 0,443 1,2 0,31 0,10 0,28 0,5 1,6
3x95/35 AL 0,320 0,8 0,30 0,09 0,32 0,6 1,8
3x120/35 AL 0,253 0,8 0,28 0,09 0,35 0,7 2,0
3x150/35 AL 0,206 0,8 0,28 0,09 0,38 0,7 2,1
3x185/50 AL 0,164 0,6 0,27 0,09 0,41 0,8 2,3
3x240/50 AL 0,125 0,6 0,26 0,08 0,46 0,9 2,6
3x300/50 AL 0,0778 0,6 0,26 0,08 0,51 1,0 2,9
Conductors andscreen area[mm2]
Current rating atcore temp. 65ºC inground A
Current rating atcore temp. 65ºC inair A
Current rating atcore temp. 90ºC inair A
Max. short circuitcurrent on the conductorduring 1s at initial temp.65ºC kA
Max. short circuitcurrent on the conductorduring 1s at initial temp.90ºC kA
Max impulse current kA
3x25/25 AL 100 90 110 2,6 2,3 -
3x50/25 AL 145 130 160 5,2 4,7 55
3x70/25 AL 175 155 190 7,2 6,6 60
3x95/35 AL 205 190 230 9,9 8,9 65
3x120/35 AL 230 220 265 12,4 11,3 65
3x150/35 AL 260 250 305 15,6 14,2 70
3x185/50 AL 290 280 340 19,2 17,5 70
3x240/50 AL 340 330 400 25,0 22,7 70
3x300/50 AL 380 375 460 31,2 28,3 70
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
ElectricalMax. short circuit temperature [°C] 250 ºCImpulse voltage [kV] 75 kV
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x25/25 AL
3x50/25 AL
3x70/25 AL
3x95/35 AL
3x120/35 AL
3x150/35 AL
3x185/50 AL
3x240/50 AL
3x300/50 AL
500
500
500
500
500
500
500
500
500
K16
K18
K20
K20
K22
K24
K24
K24
K26
7330384717014
7330384717021
7330384717038
7330384717045
7330384717052
7330384717069
7330384717076
7330384717144
20158257
20151640
20151641
20151642
20151643
20151644
20151645
20151646
20152032
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
52 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 53We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductor resistanceΩ/km
Screen resistanceΩ/km
Inductance mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
3x35/16 0,524 1,2 0,34 0,11 0,22 0,4 1,2
3x50/16 0,387 1,2 0,33 0,10 0,25 0,5 1,4
3x70/16 0,268 1,2 0,31 0,10 0,28 0,5 1,6
3x95/25 0,193 0,8 0,30 0,09 0,32 0,6 1,8
3x120/25 0,153 0,8 0,29 0,09 0,34 0,6 1,9
3x150/25 0,124 0,8 0,28 0,09 0,38 0,7 2,1
3x185/35 0,0991 0,6 0,27 0,09 0,41 0,8 2,3
3x240/35 0,0754 0,6 0,26 0,08 0,46 0,9 2,6
Conductors andscreen area[mm2]
Current rating atcore temp. 65ºC inground A
Current rating atcore temp. 65ºC inair A
Current rating atcore temp. 90ºC inair A
Max. short circuitcurrent on the conductorduring 1s at initial temp.65ºC kA
Max. short circuitcurrent on the conductorduring 1s at initial temp.90ºC kA
Max impulse current kA
3x35/16 140 135 165 5,5 5,0 -
3x50/16 175 165 205 7,8 7,1 55
3x70/16 210 205 250 11,0 10,0 60
3x95/25 250 240 295 14,9 13,6 65
3x120/25 285 280 340 18,9 17,2 65
3x150/25 325 320 390 23,6 21,5 70
3x185/35 360 360 435 29,1 26,5 70
3x240/35 415 420 515 37,7 34,4 70
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x35/16
3x50/16
3x70/16
3x95/25
3x120/25
3x150/25
3x185/35
3x240/35
500
500
500
500
500
500
500
500
K16
K18
K18
K20
K20
K22
K22
K24
7330384714761
7330384714778
7330384714785
7330384714792
7330384714808
7330384714815
7330384714822
7330384714839
20117462
20117463
20117464
20117465
20117491
20117497
20117513
20117514
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationFXLJ-TT is a three core cable primary developed to be ploughed down but thanks to the robust design the cable can withstand the stress thatappears when laid in water with moderate currents and limited depth. The design with water swellable yarn and aluminum foil bonded to thesheath makes the cable both radial and longitudinal water sealed, which enhances the expected life length of the cable. Ripcords for easier andsafer stripping of the outer sheath.
Alternative Product NameSE-N10XC7A5T5E-R
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnviromantal Declaration - FXLJ-TT
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape TriangularConductors Stranded, round and compacted copper acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 2,96 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tape and swellable yarnShield / Screen Annealed copper wiresRadial water blocking Aluminium foil bonded to the sheathRipcord AramidOuter Sheath PE, blackExample of marking on sheath FXLJ-TT 12kV 3x95/25 DRAKA "Date", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 8 x D
When pulling-in: 12 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 75 kV
Power Cables 12 kV
FXLJ-TT 6/10(12) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
54 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 55We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors andscreen area [mm2]
Conductorresistance Ω/km
Screenresistance*Ω/km
Inductance intrefoil/in flat*mH/km
Reactance intrefoil/in flat*Ω/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
1x50/16 0,387 1,15 0,40/0,73 0,13/0,23 0,25 0,5 1,4
1x400/35 0,0470 0,524 0,29/0,54 0,09/0,17 0,58 1,1 3,3
1x500/35 0,0366 0,524 0,28/0,52 0,09/0,16 0,63 1,2 3,6
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
1x50/16 205 205 250 7,8 7,1
1x400/35 625 680 835 62,9 57,4
1x500/35 695 765 940 78,7 71,7
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
1x50/16
1x400/35
1x500/35
500
500
500
K11
K18
K20
CA. 80150421
CA. 80150429
CA. 80150430
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationSingle-core, distribution cable for outdoor use in 3-phase formation. Installation in pipes and ground/water. Both radial and longitudinal watersealed. Can be ploughed down. The outer sheath has a conductive layer that greatly extends the possibilities to do a sheath testing before,during and after installation. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N10XC7A5T5E-FR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnvironmental declaration - FXLJ-TTCLTSLF
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section K Harmonized Construction StandardCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape RoundConductors Stranded, round and compacted copper acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 2,96 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminum tapeRadial water blocking Aluminum-PE laminate, bonded to sheathRipcord AramidOuter Sheath PE, natural, UV-protectedExample of marking on sheath FXLJ-TTCL TSLF 12kV 1x50 FR/16 DRAKA "Date and time", metre markedSemi-conducting layer in outer sheath Yes (facilitates sheath testing)
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 75 kV
Power Cables 12 kV
FXLJ-TTCL TSLF 6/10(12) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
56 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 57We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductorresistance Ω/km
Screen resistance*Ω/km
Inductance in trefoil/inflat* mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
1x50/16 0,641 1,15 0,43/0,73 0,23 0,17 0,6 1,9
1x70/16 0,443 1,15 0,41/0,70 0,22 0,19 0,7 2,1
1x95/25 0,320 0,727 0,39/0,67 0,21 0,21 0,8 2,4
1x150/25 0,206 0,727 0,36/0,63 0,20 0,25 0,9 2,8
1x185/35 0,164 0,524 0,35/0,61 0,19 0,27 1,0 3,1
1x240/35 0,125 0,524 0,34/0,59 0,19 0,30 1,1 3,4
1x300/35 0,100 0,524 0,33/0,57 0,18 0,33 1,2 3,7
1x400/35 0,0778 0,524 0,30/0,55 0,17 0,37 1,4 4,2
1x500/35 0,0605 0,524 0,31/0,53 0,17 0,40 1,5 4,5
1x630/50 0,0469 0,387 0,29/0,51 0,16 0,45 1,7 5,1
1x800/50 0,0367 0,387 0,29/0,50 0,16 0,45 1,7 5,1
1x1000/50 0,0291 0,387 0,27/0,48 0,15 0,47 1,8 5,3
1x1200/50 0,0247 0,387 0,29/0,48 0,15 0,51 1,9 5,8
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
1x50/16 155 160 195 5,2 4,7
1x70/16 200 190 235 7,2 6,6
1x95/25 235 230 280 9,9 8,9
1x120/25 265 265 325 12,4 11,3
1x150/25 300 300 370 15,6 14,2
1x185/35 330 345 425 19,2 17,5
1x240/35 385 400 490 25,0 22,7
1x300/35 435 460 565 31,2 28,3
1x400/35 510 555 680 41,6 37,8
1x500/35 570 635 775 52,0 47,2
1x630/50 635 720 880 65,6 59,5
1x800/50 695 822 1010 83,2 75,6
1x1000/50 760 920 1130 103,7 94,5
1x1200/50 815 1000 1230 124,0 113,0
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
1x50/16
1x70/16
1x95/25
1x120/25
1x150/25
1x185/35
1x240/35
1x300/35
1x400/35
1x500/35
1x630/50
1x800/50
1x1000/50
1x1200/50
500
500
500
500
500
500
500
500
500
500
500
500
500
500
K12
K12
K12
K14
K14
K16
K16
K18
K18
K20
K20
K22
K24
K26
7330384707893
7330384714006
7330384707299
7330384714013
7330384707879
7330384714020
7330384707701
7330384714037
7330384707022
7330384714044
7330384709392
7330384714051
7330384720656
7330384720038
20102178
20113275
20102179
20113276
20102180
20113277
20102181
20113278
20102182
20113279
20102183
20113280
20118907
20118927
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationSingle-core, distribution cable for outdoor use in 3-phase formation. Installation in pipes and ground/water. Both radial and longitudinal watersealed. Can be ploughed down. The outer sheath has a conductive layer that greatly extends the possibilities to do a sheath testing before,during and after installation. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N20XC7A5T5E-AR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnviromantal Declaration - AXLJ-TTCL
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section M Harmonized Construction StandardCENELEC HD 620 Part 10 Section K Harmonized Construction Standard
ConstructionCable Shape RoundConductors Stranded, round, compressed aluminium acc. to IEC 60228 class 2, longitudinally watertightInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 4,85 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminum laminateRadial water blocking Aluminium laminate, bonded to sheathRipcord AramidOuter Sheath PE, natural UV protectedExample of marking on sheath AXLJ-TTCL TSLF 24kV 1x150 AFR/25 DRAKA "Date and time", metre markedSemi-conducting layer in outer sheath Yes (facilitates sheath testing)
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 125 kV
Power cables 24 kV
AXLJ-TTCL TSLF 12/20(24) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
58 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 59We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductorresistance Ω/km
Screen resistance*Ω/km
InductancemH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
3x1x50/16 0,641 1,15 0,44 0,14 0,17 0,6 1,9
3x1x70/16 0,443 1,15 0,41 0,13 0,19 0,7 2,1
3x1x95/25 0,320 0,727 0,39 0,12 0,21 0,8 2,4
3x1x120/25 0,253 0,727 0,38 0,12 0,23 0,9 2,6
3x1x150/25 0,206 0,727 0,36 0,11 0,25 0,9 2,8
3x1x185/35 0,164 0,524 0,35 0,11 0,27 1,0 3,1
3x1x240/35 0,125 0,524 0,34 0,11 0,30 1,1 3,4
3x1x300/35 0,100 0,524 0,33 0,10 0,33 1,2 3,7
3x1x400/35 0,0778 0,524 0,31 0,10 0,37 1,4 4,2
*Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
3x1x50/16 155 160 195 5,2 4,7
3x1x70/16 200 190 235 7,2 6,6
3x1x95/25 235 230 280 9,9 8,9
3x1x120/25 265 265 325 12,4 11,3
3x1x150/25 300 300 370 15,6 14,2
3x1x185/35 330 345 425 19,2 17,5
3x1x240/35 385 400 490 25,0 22,7
3x1x300/35 435 460 565 31,2 28,3
3x1x400/35 510 555 680 41,6 37,8
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x1x50/16
3x1x70/16
3x1x95/25
3x1x120/25
3x1x150/25
3x1x185/35
3x1x240/35
3x1x300/35
3x1x400/35
500
500
500
500
500
500
500
500
500
K22
K24
K24
K24
K26
K26
K28
K28
K28
7330384708999
7330384721936
7330384709019
7330384721943
7330384709125
7330384721950
7330384709026
7330384721967
7330384713320
20102184
20115022
20102185
20115023
20102186
20115024
20102187
20115025
20111044
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationSingle-core, distribution cable for outdoor use in triplex formation. Installation in pipes and ground/water. Both radial and longitudinal watersealed. Can be ploughed down. The outer sheath has a conductive layer that greatly extends the possibilities to do a sheath testing before,during and after installation. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N20XC7A5T5E-AR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnviromantal Declaration - AXLJ-TTCL
StandardCENELEC HD 620 Part 10 Section K Harmonized Construction StandardCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape RoundConductors Stranded, round and compacted aluminum acc. to IEC 60228 class 2, longitudinally watertightInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 4,85 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminum tapeRadial water blocking Aluminum-PE laminate, bonded to sheathRipcord AramidOuter Sheath PE, natural UV-protectedExample of marking on sheath AXLJ-TTCL TSLF 24kV 1x50 AFR/16 DRAKA "Date and time", 1-core is metre markedSemi-conducting layer in outer sheath Yes (facilitates sheath testing)
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 125 kV
Power cables 24 kV
AXLJ-TTCL TSLF Triplex 12/20(24) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
60 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 61We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screen area [mm2] Cable diameter [mm]Cable weight[kg/km]
Conductorresistance[Ω/km]
Centre conductorresistance[Ω/km]
Inductance/phase[mH/km] Capacitance [μF/km]
AHXAMK-W 3x50+35 64 2350 0.641 0.524 0.46 0.17
AHXAMK-W 3x95+35 71 3100 0.32 0.524 0.4 0.21
AHXAMK-W 3x120+35 74 3450 0.253 0.524 0.39 0.23
AHXAMK-W 3x150+35 76 3800 0.206 0.524 0.37 0.24
AHXAMK-W 3x185+35 80 4300 0.164 0.524 0.36 0.26
AHXAMK-W 3x240+70 89 5500 0.125 0.268 0.35 0.3
AHXAMK-W 3x300+70 94 6250 0.1 0.268 0.34 0.32
Conductors and screen area [mm2]Charging current/phase [A/km]
Earth faultcurrent [A/km]
Current ratingat core temp.65ºC in ground[A]
Current ratingat core temp.65ºC in air* [A]
Current ratingat core temp.90ºC in air*[A]
Max. short circuitcurrent on theconductor during 1s atinitial temp.*** 90ºCkA
AHXAMK-W 3x50+35 0.6 1.8 155 160 195 4.7
AHXAMK-W 3x95+35 0.8 2.3 235 230 280 8.9
AHXAMK-W 3x120+35 0.8 2.5 265 265 325 11.3
AHXAMK-W 3x150+35 0.9 2.6 300 300 370 14.1
AHXAMK-W 3x185+35 1 2.9 330 345 425 17.4
AHXAMK-W 3x240+70 1.1 3.2 385 400 510 22.6
AHXAMK-W 3x300+70 1.2 3.5 435 460 565 28.3
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –
air temperature 25ºC –thermal resistivity of soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x50+35 20kV
3x95+35 20kV
3x120+35 20kV
3x150+35 20kV
3x185+35 20kV
3x240+35 20kV
3x240+70 20kV
3x300+35 20kV
3x300+70 20kV
500
500
500
500
500
500
500
500
500
K24
K26
K26
K26
K26
K28
K28
K28
K28
6410006242504
6410006242528
6410006242535
6410006242542
6410006242559
6410006242566
6410006242566
6410006242597
6410006242573
20022490
20022491
20022492
20022493
20022495
20022499
20022498
20022502
20022501
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
ApplicationMedium voltage power cable with stranded and compacted aluminium longitudinal and radial water sealed conductor. For fixed outdoorinstallation, can be ploughed down.
Alternative Product NameWISKI®
Flame retardanceFlame retardant - Not applicable
StandardHD 620-10F Harmonized construction standardIEC 60502-2 Construction standard
ConstructionCable Shape RoundUNSPSC classification 26121629Conductors Stranded, round, compacted aluminium, longitudinally watertightCenter conductor Round, stranded and compacted copper conductorInner semi-conducting layer Semi-conducting PEXConductor Insulation PEXIndividual screen for parts Semi-conducting PEXCore assembly Three cores are stranded around the centre conductorInner covering Conductive tapeShield / Screen Aluminium foil bonded tightly to sheathOverall sheath Black PEExample of marking on sheath AHXAMK-W 12/20 kV 3x150+35 DRAKA "Date and time", 1 core is metre markedSemi-conducting layer in outer sheath Semi-conducting tape
TemperatureMaximum operating Temperature 90°CTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesMin. Bending radius at final installation 8 xDMin. Bending radius at during installation 15 xDMax Pulling force - pulling grip [N/mm2] 15 N/mm² xAMax Pulling force - pulling eye [N/mm2] 50 N/mm² xA
ElectricalMax. short circuit temperature [°C] 250°C
Power cables 24 kV
AHXAMK-W 12/20 (24) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-12-19
62 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 63We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductor resistanceΩ/km
Screen resistanceΩ/km
Inductance mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
3x50/16 0,641 1,2 0,37 0,12 0,17 0,6 1,9
3x95/25 0,320 0,8 0,34 0,11 0,21 0,8 2,4
3x150/25 0,206 0,8 0,31 0,10 0,25 0,9 2,8
3x240/35 0,125 0,6 0,29 0,09 0,30 1,1 3,4
3x300/35 0,100 0,6 0,28 0,09 0,33 1,2 3,7
Conductors andscreen area[mm2]
Current rating atcore temp. 65ºC inground A
Current rating atcore temp. 65ºC inair A
Current rating atcore temp. 90ºC inair A
Max. short circuitcurrent on the conductorduring 1s at initial temp.65ºC kA
Max. short circuitcurrent on the conductorduring 1s at initial temp.90ºC kA
Max impulse current kA
3x50/16 145 130 160 5,2 4,7 55
3x95/25 205 190 230 9,9 8,9 65
3x150/25 260 250 305 15,6 14,2 70
3x240/35 340 330 400 25,0 22,7 70
3x300/35 380 375 460 31,2 28,3 70
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x50/16
3x95/25
3x150/25
3x240/25
3x240/35
3x300/35
500
500
500
500
500
500
K20
K22
K24
K26
K26
K26
7330384701136
7330384701150
7330384701075
7330384701082
7330384714167
7330384715072
20078233
20102136
20078234
20102137
20091033
20118046
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationAXLJ-RMF is a 3-core cable designed for replacement of bare overhead lines. Primary developed to be ploughed down but thanks to the robustdesign the cable can stand the stresses that appears when laid in water with moderate currents and limited depth. Ripcords for easier and saferstripping of the outer sheath.
Alternative Product NameSE-N20XC7E-AR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnviromantal Declaration - AXLJ-F, -RMFLT
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape TriangularConductors Stranded, round, compacted aluminum acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 4,85 mmOuter semi-conducting layer BondedInner covering Conductive tapeShield / Screen Annealed copper wiresRipcord AramidOuter Sheath Composite PE, blackExample of marking on sheath AXLJ-RMF 24kV 3x150/25 LT DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 8 x D
When pulling-in: 12 x DWhen plowing down: 8 x D
ElectricalMax. short circuit temperature [°C] 250 ºCImpulse voltage [kV] 125 kV
Power cables 24 kV
AXLJ-RMF 12/20(24) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
64 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 65We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductor resistanceΩ/km
Screen resistanceΩ/km
Inductance mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
3x50/16 0,641 1,2 0,37 0,12 0,17 0,6 1,9
3x70/16 0,443 1,2 0,35 0,11 0,19 0,7 2,1
3x95/25 0,320 0,8 0,34 0,11 0,21 0,8 2,4
3x120/25 0,253 0,8 0,32 0,10 0,23 0,9 2,6
3x150/25 0,206 0,8 0,31 0,10 0,25 0,9 2,8
3x185/35 0,164 0,6 0,30 0,09 0,27 1,0 3,1
3x240/35 0,125 0,6 0,29 0,09 0,30 1,1 3,4
3x300/35 0,100 0,6 0,28 0,09 0,33 1,2 3,7
Conductors andscreen area[mm2]
Current rating atcore temp. 65ºC inground A
Current rating atcore temp. 65ºC inair A
Current rating atcore temp. 90ºC inair A
Max. short circuitcurrent on the conductorduring 1s at initial temp.65ºC kA
Max. short circuitcurrent on the conductorduring 1s at initial temp.90ºC kA
Max impulse current kA
3x50/16 145 130 160 5,2 4,7 55
3x70/16 175 155 190 7,2 6,6 60
3x95/25 205 190 230 9,9 8,9 65
3x120/25 230 220 265 12,4 11,3 65
3x150/25 260 250 305 15,6 14,2 70
3x185/35 290 280 340 19,2 17,5 70
3x240/35 340 330 400 25,0 22,7 70
3x300/35 380 375 460 31,2 29,8 70
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x50/16
3x70/16
3x95/25
3x120/25
3x150/25
3x185/35
3x240/35
3x300/35
500
500
500
500
500
500
500
500
K22
K22
K24
K24
K24
K24
K26
K26
7330384720236
7330384720243
7330384720250
7330384720267
7330384720274
7330384720281
7330384720298
7330384720311
20203889
20203890
20203891
20203892
20203893
20203894
20203895
20203896
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationHalogen-free, flame retardant and self-extinguishing in case of fire. Smoke in the event of fire is limited, transparent (to facilitate evacuation) andnot harmful to electronic equipment. The cable is primarily designed for indoor installation, tunnels, etc. The cable can be installed outdoorsand in ground but ploughing is not recommended. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N20XC7Z1-AR
EnvironmentalEnvironmental Declaration - AXQJ-RMF Pure
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section M Harmonized Construction StandardIEC 60502-2 Construction standardCENELEC HD 604 Halogen free materialSS-EN 60754-1, -2 Corrosive gasesSS-EN 61034-1, -2 Smoke densityEN 50575:2014 Power, control and communication cables - Cables for general applications in construction
works subject to reaction to fire requirements
ConstructionCable Shape TriangularConductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 4,85 mmOuter semi-conducting layer BondedInner covering Conductive tapeShield / Screen Annealed copper wiresRipcord AramidOuter Sheath Halogen free compound, blackExample of marking on sheath AXQJ-RMF Pure 24kV 3x50/16 LT B2-s1d0a2 DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesCPR Performance class B2ca-s1d0a2Bending radius In fixed installation: 8 x D
When pulling-in: 12 x DWhen plowing down: 8 x D
ElectricalMax. short circuit temperature [°C] 250 ºCImpulse voltage [kV] 125 kV
Power cables 24 kV
AXQJ-RMF Pure 12/20(24) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
66 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 67We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors andscreen area[mm2]
Conductorresistance Ω/km
Screenresistance*Ω/km
Inductance mH/km
ReactanceΩ/km
CapacitanceµF/km
Zero sequenceimpedance Z0Ω/km
Chargingcurrent/phase A/km
Earth faultcurrentA/km
3x50/16 0,641 1,2 0,37 0,12 0,17 1,30+j0,83 0,6 1,9
3x70/16 0,443 1,2 0,35 0,11 0,19 1,05+j0,80 0,7 2,1
3x95/25 0,320 0,8 0,34 0,11 0,21 0,91+j0,69 0,8 2,4
3x120/25 0,253 0,8 0,32 0,10 0,23 0,82+j0,67 0,9 2,6
3x150/25 0,206 0,8 0,31 0,10 0,25 0,75+j0,66 0,9 2,8
3x185/35 0,164 0,6 0,30 0,10 0,27 0,69+j0,56 1,0 3,1
3x240/35 0,125 0,6 0,29 0,09 0,30 0,64+j0,54 1,1 3,4
3x300/35 0,100 0,6 0,28 0,09 0,33 0,58+j0,45 1,2 3,7
*Note! Screen resistance is the sum of copper wires and aluminum tape. The screen cross-section is made up of 60% copper.
Conductors andscreen area[mm2]
Current rating atcore temp. 65ºCin ground A
Current rating atcore temp. 65ºCin air A
Current rating atcore temp. 90ºCin air A
Max. short circuitcurrent on theconductor during 1sat initial temp. 65ºCkA
Max. short circuitcurrent on theconductor during 1sat initial temp. 90ºCkA
Max. short circuitcurrent on the screenduring 1s kA
Max impulse currentkA
3x50/16 145 130 160 5,2 4,7 3,2 55
3x70/16 175 155 190 7,2 6,6 3,2 60
3x95/25 205 190 230 9,9 8,9 5 65
3x120/25 230 220 265 12,4 11,3 5 65
3x150/25 260 250 305 15,6 14,2 5 70
3x185/35 290 280 340 19,2 17,5 7 70
3x240/35 340 330 400 25,0 22,7 7 70
3x300/35 380 375 460 31,2 28,3 7 70
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
ElectricalMax. short circuit temperature [°C] 250°CImpulse voltage [kV] 125 kV
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x50/16
3x70/16
3x95/25
3x120/25
3x150/25
3x185/35
3x240/35
3x300/35
500
500
500
500
500
500
500
500
K22
K22
K24
K24
K24
K26
K26
K26
7330384721745
7330384721738
7330384721721
7330384721714
20206420
20206421
20206422
20206423
20206424
20206425
20206426
20206427
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationAXCLJ-TT is just as AXALJ-TT totally water sealed. Radial water sealed by an aluminum laminate bonded to outer sheath and longitudinally watersealed with swellable tapes. The screen is made up of circular copper wires like AXALJ-TT, water blocking tapes (replacing water blocking yarns)and the cable has been complemented with two strong ripcords for easier and safer opening of the outer sheath. The cable is primarily designedfor ploughing down in ground, but thanks to its robust design can handle the stresses resulting from installation in lakes with limited currentsand of limited depth.
Alternative Product NameSE-N20XC7A5T5E-AR
Flame retardanceFlame retardant - Not applicable
FeatureThe corresponding options with aluminumscreen. - AXALJ-TT
EnvironmentalEnvironmental declaration - AXCLJ-TT
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape TriangularConductors Stranded, round, compacted aluminum acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 4,85 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeFiller PE-profilesInner covering Conductive tapeShield / Screen Round copper wires in contact with aluminum laminateRadial water blocking Aluminum-PE laminate, bonded to sheathRipcord AramidOuter Sheath Composite PE, BlackExample of marking on sheath AXCLJ-TT 24kV 3x50/16 DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 8 x D
When pulling-in: 12 x DWhen plowing down: 8 x D
Max Pulling force - pulling grip [N/mm2] Max. pulling forse = 5 x D ^ 2 (N)D = outer diameter of cable (mm)
Max Pulling force - pulling eye [N/mm2] Max. pulling forse = 30 x S (N)S = cross-sectional area of conductor (mm^2)
Power cables 24 kV
AXCLJ-TT 12/20(24) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
68 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 69We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductorresistance Ω/km
Screen resistance*Ω/km
Inductance in trefoil/inflat* mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
1x50/16 0,641 1,15 0,43/0,73 0,14/0,23 0,17 0,6 1,9
1x95/25 0,320 0,727 0,39/0,67 0,12/0,21 0,21 0,8 2,4
1x150/25 0,206 0,727 0,36/0,63 0,11/0,20 0,25 0,9 2,8
1x240/35 0,125 0,524 0,34/0,59 0,11/0,19 0,30 1,2 3,4
1x400/35 0,0778 0,524 0,31/0,55 0,10/0,17 0,37 1,4 4,2
1x500/35 0,0605 0,524 0,30/0,53 0,09/0,17 0,40 1,5 4,5
1x630/50 0,0469 0,387 0,29/0,51 0,09/0,16 0,45 1,7 5,1
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
1x50/16 155 160 195 5,2 4,7
1x95/25 235 230 280 9,9 8,9
1x150/25 300 300 370 15,6 14,2
1x240/35 385 400 490 25,0 22,7
1x400/35 510 555 680 41,6 37,8
1x500/35 570 635 775 52,0 47,2
1x630/50 635 720 880 65,6 59,5
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
1x50/16
1x95/25
1x150/25
1x240/35
1x400/35
1x500/35
1x630/50
500
500
500
500
500
500
500
K12
K12
K14
K16
K18
K20
K20
7330384720663
7330384720687
7330384720700
7330384720724
7330384720748
7330384720755
7330384720762
20217589
20217591
20217593
20217595
20217597
20217598
20217599
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationHalogen-free, flame retardant and self-extinguishing in case of fire. Smoke in the event of fire is limited, transparent (to facilitate evacuation) andnot harmful to electronic equipment. Radial and longitudinal water sealed distribution cable for use indoors and outdoors for 3-phaseformation. Installation in pipes and ground. Ploughing down is not recommended. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N20XC7A5Z1-AR
EnvironmentalEnviromantal Declaration - AXQJ-TT Pure TSLI
StandardCENELEC HD 620 Part 10 Section M Harmonized Construction StandardCENELEC HD 620 Part 10 Section K Harmonized Construction StandardCENELEC HD 604 Halogen free materialSS-EN 60754-1, -2 Corrosive gasesSS-EN 61034-1, -2 Smoke densityEN 50575:2014 Power, control and communication cables - Cables for general applications in construction
works subject to reaction to fire requirements
ConstructionCable Shape RoundConductors Stranded, round, compressed aluminium acc. to IEC 60228 class 2, longitudinally watertightInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 4,85 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminum laminateRadial water blocking Aluminium laminate, bonded to sheathRipcord AramidOuter Sheath Halogen free compound, blackExample of marking on sheath AXQJ-TT Pure TSLI 24kV 1x120 AFR/25 D-s2d2a2 DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesCPR Performance class Dca-s2d2a2Bending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 125 kV
Power cables 24 kV
AXQJ-TT Pure TSLI 12/20(24) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
70 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 71We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductor resistanceΩ/km
Screen resistanceΩ/km
Inductance mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
3x25/25 AL 1,20 1,2 0,41 0,13 0,14 0,5 1,6
3x50/25 AL 0,641 1,2 0,37 0,12 0,17 0,6 1,9
3x70/25 AL 0,443 1,2 0,35 0,11 0,19 0,7 2,1
3x95/35 AL 0,320 0,8 0,34 0,11 0,21 0,8 2,4
3x120/35 AL 0,253 0,8 0,32 0,10 0,23 0,9 2,6
3x150/35 AL 0,206 0,8 0,31 0,10 0,25 0,9 2,8
3x185/50 AL 0,164 0,6 0,30 0,09 0,27 1,0 3,1
3x240/50 AL 0,125 0,6 0,29 0,09 0,30 1,1 3,4
3x300/50 AL 0,100 0,6 0,28 0,09 0,33 1,2 3,7
Conductors andscreen area[mm2]
Current rating atcore temp. 65ºC inground A
Current rating atcore temp. 65ºC inair A
Current rating atcore temp. 90ºC inair A
Max. short circuitcurrent on the conductorduring 1s at initial temp.65ºC kA
Max. short circuitcurrent on the conductorduring 1s at initial temp.90ºC kA
Max impulse current kA
3x25/25 AL 100 90 110 2,6 2,3 -
3x50/25 AL 145 130 160 5,2 4,7 55
3x70/25 AL 175 155 190 7,2 6,6 60
3x95/35 AL 205 190 230 9,9 8,9 65
3x120/35 AL 230 220 265 12,4 11,3 65
3x150/35 AL 260 250 305 15,6 14,2 70
3x185/50 AL 290 280 340 19,2 17,5 70
3x240/50 AL 340 330 400 25,0 22,7 70
3x300/50 AL 380 375 460 31,2 28,3 70
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
3x25/25 AL
3x50/25 AL
3x70/25 AL
3x95/35 AL
3x120/35 AL
3x150/35 AL
3x185/50 AL
3x240/50 AL
3x300/50 AL
500
500
500
500
500
500
500
500
500
K20
K22
K22
K24
K24
K24
K26
K26
K26
7330384717083
7330384717090
7330384717106
7330384717151
7330384717113
7330384717168
7330384717120
7330384717175
20158170
20151647
20151648
20151649
20152033
20151650
20152034
20151651
20152035
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationAXALJ-TT is just like its predecessor AXLJ-TT, totally water sealed. Radially water sealed by an aluminium laminate bonded to the outer sheathlongitudinally water sealed with swellable tapes. The screen is made up of circular aluminium wires, water blocking tapes (replacing the waterswellable yarns) and the cable has been complemented with two strong ripcords for easier and safer opening of the outer sheath. The cable isprimarily designed for ploughing down in ground, but thanks to its robust design can handle the stresses resulting from installation in lakeswith limited currents and of limited depth.
Alternative Product NameSE-N20XA5E-AR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnviromantal Declaration - AXALJ-TT
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape TriangularConductors Stranded, round, compacted aluminium acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 4,85 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeFiller PE-profilesShield / Screen Round aluminium wires in contact with aluminium laminateRadial water blocking Aluminium laminate, bonded to sheathRipcord AramidOuter Sheath Composite PE, BlackExample of marking on sheath AXALJ-TT 24kV 3x50/25 AL DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 8 x D
When pulling-in: 12 x DWhen plowing down: 8 x D
ElectricalMax. short circuit temperature [°C] 250 ºCImpulse voltage [kV] 125 kV
Power cables 24 kV
AXALJ-TT 12/20(24) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
72 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 73We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and
screen area [mm2]
Cable
diameter
[mm]
Cable
weight
[kg/km]
Conductor
resistance
[Ω/km]
Resistance
of phase,
core temp.
65ºC, flat
formation
[Ω/km]
Resistance of
phase, core
temp. 90ºC,
flat
formation
[Ω/km]
Resistance
of phase,
core temp.
65ºC, trefoil
formation
[Ω/km]
Resistance of
phase, core
temp. 90ºC,
trefoil
formation
[Ω/km]
Inductance
per phase,
flat
formation
[mH/km]
Inductance
per phase,
trefoil
formation
[mH/km]
Capacitance
[μF/km]
HXCMK 1x35/16 26 920 0.524 0.64 0.69 0.17 0.68 0.64 0.45 0.16
Conductors and screen
area [mm2]
Charging
current/
[A/km]
Earth fault
current
[A/km]
Current
rating in air
at core
temp. 65ºC,
flat
formation,
[A]
Current
rating in air
at core temp.
65ºC, trefoil
formation,
[A]
Current rating
in air at core
temp. 90ºC,
flat formation,
[A]
Current rating
in air at core
temp. 90ºC,
trefoil
formation, [A]
Current rating
in ground at
core temp.
65ºC, flat
formation, [A]
Current rating
in ground at
core temp.
65ºC, trefoil
formation,
[A]
Max. short
circuit current
on the
conductor
during 1s at
initial temp.***
90ºC kA
HXCMK 1x35/16 0.6 1.7 175 160 215 195 185 175 5
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –
air temperature 25ºC –thermal resistivity of soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-10
Standard delivery length
[m]
Delivery Package SAP Number
HXCMK 1x35/16 1000 K16 6410006032099 20022529
ApplicationMedium voltage power cable with stranded and compacted copper conductor. For fixed installation for the trenches and ladders indoors andoutdoors.
Flame retardanceEN 60332-1IEC 60332-1 - Fire propagation class
ApprovalCE
StandardIEC 60502-2 Construction standard
ConstructionCable Shape RoundConductors Round, compacted copper conductorInner semi-conducting layer Semi-conducting PEXConductor Insulation PEXIndividual screen for parts Semi-conducting PEXInner covering Conductive tape
Copper wire layer helix and copper contact tape counter helixOuter Sheath Black PVCExample of marking on sheath Prysmian, product name, date of manufacture, outer sheath material designation, meter
markingSemi-conducting tape
TemperatureMaximum operating Temperature 90°CTemparatures at installation [°C] Lowest cable temperature during installation is -5°C.
FeaturesUV resistance GoodBending radius 15 xDMin. Bending radius at final installation 10 xDMin. Bending radius at during installation 15 xDMax Pulling force - pulling grip [N/mm2] 15 N/mm² xAMax Pulling force - pulling eye [N/mm2] 50 N/mm² xAREACH/SVHC declaration The cable does not contain any substances on the REACH/SVHC -list.
ElectricalMax. short circuit temperature [°C] 250°C
Power cables 24 kV
HXCMK 20 kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-10
74 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 75We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors andscreen area [mm2]
Conductorresistance Ω/km
Screenresistance*Ω/km
Inductance intrefoil/in flat*mH/km
Reactance intrefoil/in flat* Ω/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
1x50/16 0,387 1,15 0,43/0,73 0,14/0,23 0,17 0,6 1,9
1x70/16 0,268 1,15 0,41/0,70 0,13/0,22 0,19 0,7 2,1
1x95/25 0,193 0,727 0,39/0,67 0,11/0,21 0,21 0,8 2,4
1x120/25 0,153 0,727 0,38/0,65 0,12/0,21 0,23 0,9 2,6
1x150/25 0,124 0,727 0,36/0,63 0,11/0,20 0,25 0,9 2,8
1x185/35 0,0991 0,524 0,35/0,61 0,11/0,19 0,27 1,0 3,1
1x240/35 0,0754 0,524 0,34/0,59 0,11/0,19 0,30 1,1 3,4
1x300/35 0,0601 0,524 0,32/0,57 0,10/0,18 0,33 1,2 3,7
1x400/35 0,0470 0,524 0,31/0,55 0,10/0,17 0,37 1,4 4,2
1x500/35 0,0366 0,524 0,30/0,53 0,09/0,17 0,40 1,5 4,5
1x630/50 0,0283 0,387 0,29/0,51 0,09/0,16 0,45 1,7 5,4
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors andscreen area [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit currenton the conductor during 1sat initial temp. 65ºC kA
Max. short circuit current on theconductor during 1s at initial temp. 90ºCkA
1x50/16 205 205 250 7,8 7,1
1x70/16 255 240 295 11,0 10,0
1x95/25 295 300 355 14,9 13,6
1x120/25 335 335 410 18,9 17,2
1x150/25 380 380 465 23,6 21,5
1x185/35 425 435 535 29,1 26,5
1x240/35 485 505 620 37,7 34,4
1x300/35 545 575 705 47,2 43,0
1x400/35 625 680 835 62,9 57,4
1x500/35 695 765 940 78,7 71,7
1x630/35 755 845 1035 99,1 90,4
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
1x50/16
1x70/16
1x95/25
1x120/25
1x150/25
1x185/35
1x240/35
1x300/35
1x400/35
1x500/35
1x630/50
1000
1000
1000
1000
1000
1000
1000
1000
500
1000
1000
K20
K20
K20
K22
K24
K24
K18
K24
K22
K18
K18
7330384714327
7330384714334
7330384714341
7330384714358
7330384714365
7330384714372
7330384714389
7330384714396
7330384714402
7330384714419
7330384714426
20117071
20117078
20117079
20117080
20117081
20117125
20117126
20117135
20117136
20117137
20117138
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationSingle-core distribution cable suitable for laying outdoors in 3-phase formation. Installation in pipes and in ground/water. Both radial andlongitudinal water sealed. Can be ploughed down.
Alternative Product NameSE-20XC7A5T5E-R
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnviromantal Declaration - FXLJ-TT
StandardCENELEC HD 620 Part 10 Section M Harmonized Construction StandardCENELEC HD 620 Part 10 Section K Harmonized Construction Standard
ConstructionCable Shape RoundConductors Stranded, round and compacted copper acc. to IEC 60228 class 2, longitudinally water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 4,85 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminum tapeRadial water blocking Aluminium laminate, bonded to sheathOuter Sheath PE, blackExample of marking on sheath FXLJ-TT TSLE 24kV 1x50 FR/16 DRAKA "Date", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation, -20 ºC below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 125 kV
Power cables 24 kV
FXLJ-TT TSLE 12/20(24)kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
76 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 77We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and Conductor
resistance ΩScreen
resistance*
Ω
Inductance in
trefoil/in flat*
Reactancein trefoil/in
ΩCapacitance Charging current/
phase A/km
Earth fault
current A/km
1x630/50 0,0469 0,387 0,31/0,52 0,10/0,16 0,33 1,9 5,9
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screen Current rating at core
temp. 65ºC in ground
Current rating at core Current rating at core Max. short circuit current on
the conductor during 1s at
initial temp. 65ºC kA
Max. short circuit current on
the conductor during 1s at
initial temp. 90ºC kA
1x630/50 635 720 880 65,5 59,5
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivity
of soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
Conductors and screen area
[mm2]
Standard delivery length
[m]
Delivery Package SAP Number
1x630/50 500 K22 CA.80140353
ApplicationSingle-core distribution cable suitable for laying outdoors in 3-phase formation. Installation in pipes and in ground/water. Both radial andlongitudinal water sealed. Can be ploughed down.
Alternative Product NameSE-N30XC7A5T5E-AR
Flame retardanceFlame retardant - Not applicable
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section K Harmonized Construction StandardCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape RoundConductors Stranded, round and compacted aluminum acc. to IEC 60228 class 2, longitudinally water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 7,1 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tape
Annealed copper wires in contact with aluminum tapeRadial water blocking Aluminium-PE laminate, bonded to sheathOuter Sheath PE, blackExample of marking on sheath AXLJ-TT TSLE 36kV 1x630 AFR/50 DRAKA "Date, metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 170 kV
Power Cables 36 kV
AXLJ-TT TSLE 18/30(36) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
78 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 79We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors andscreen area [mm2]
Conductorresistance Ω/km
Screenresistance*Ω/km
Inductance intrefoil/in flat*mH/km
Reactance intrefoil/in flat* Ω/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
1x50/25 0,641 0,727 0,47/0,75 0,15/0,24 0,13 0,7 2,2
1x70/25 0,443 0,727 0,44/0,71 0,14/0,22 0,14 0,8 2,4
1x95/25 0,320 0,727 0,42/0,68 0,13/0,21 0,16 0,9 2,7
1x120/35 0,253 0,524 0,41/0,66 0,13/0,21 0,17 1,0 2,9
1x150/35 0,206 0,524 0,39/0,64 0,12/0,20 0,19 1,1 3,2
1x185/35 0,164 0,524 0,38/0,62 0,12/0,20 0,20 1,1 3,4
1x240/35 0,125 0,524 0,36/0,60 0,11/0,19 0,22 1,2 3,7
1x300/35 0,100 0,524 0,35/0,58 0,11/0,18 0,24 1,4 4,1
1x400/35 0,0778 0,524 0,34/0,56 0,11/0,18 0,27 1,5 4,6
1x500/35 0,0605 0,524 0,32/0,54 0,10/0,17 0,29 1,6 4,9
1x630/50 0,0469 0,387 0,31/0,52 0,10/0,16 0,33 1,9 5,9
1x800/50 0,0367 0,387 0,30/0,50 0,09/0,16 0,36 2,0 6,1
1x1000/50 0,0291 0,387 0,30/0,49 0,09/0,15 0,40 2,3 6,8
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
1x50/25 155 160 195 5,2 4,7
1x70/25 200 190 235 7,2 6,6
1x95/25 235 230 280 9,9 8,9
1x120/35 265 265 325 12,4 11,3
1x150/35 300 300 370 15,6 14,2
1x185/35 330 345 425 19,2 17,5
1x240/35 385 400 490 25,0 22,7
1x300/35 435 460 565 31,2 28,3
1x400/35 510 555 680 41,6 37,8
1x500/35 570 635 775 52,0 47,2
1x630/50 635 720 880 65,6 59,5
1x800/50 695 822 1010 83,2 75,6
1x1000/50 760 920 1130 103,7 94,5
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
1x50/25
1x70/25
1x95/25
1x120/35
1x150/35
1x185/35
1x240/35
1x300/35
1x400/35
1x500/35
1x630/50
1x800/50
1x1000/50
500
500
500
500
500
500
500
500
500
500
500
500
500
K14
K14
K16
K16
K18
K18
K18
K20
K20
K22
K22
K24
K26
7330384719087
7330384719094
7330384713665
7330384719100
7330384719117
7330384713658
7330384719124
7330384713689
7330384713702
7330384713672
7330384716772
7330384718158
20114470
20114471
20102188
20114472
20114473
20102189
20114474
20102190
20102191
20102192
20114469
20114475
CA. 80160229
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationSingle-core, distribution cable for outdoor use in 3-phase formation. Installation in pipes and ground/water. Both radial and longitudinal watersealed. Can be ploughed down. The outer sheath has a conductive layer that greatly extends the possibilities to do a sheath testing before,during and after installation. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N30XC7A5T5E-AR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnvironmental declaration - AXLJ-TTCLTSLF
StandardSS 424 14 16 Construction standard 12-36 kVCENELEC HD 620 Part 10 Section K Harmonized Construction StandardCENELEC HD 620 Part 10 Section M Harmonized Construction Standard
ConstructionCable Shape RoundConductors Stranded, round and compacted aluminium acc. to IEC 60228 class 2, longitudinal water sealedInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 7,1 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminum tapeRadial water blocking Aluminium-PE laminate, bonded to sheathRipcord AramidOuter Sheath PE, natural, UV-protectedExample of marking on sheath AXLJ-TTCL TSLF 36kV 1x95 AFR/25 DRAKA "Date and time", metre markedSemi-conducting layer in outer sheath Yes (facilitates sheath testing)
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 10 x D
When pulling out: 15 x DWhen plowing down: 8 x D
ElectricalMax. short circuit temperature [°C] 250ºCImpulse voltage [kV] 170 kV
Power Cables 36 kV
AXLJ-TTCL TSLF 18/30(36) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
80 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 81We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors andscreen area [mm2]
Conductorresistance Ω/km
Screenresistance*Ω/km
Inductance intrefoil/in flat*mH/km
Reactance i intrefoil/in flat* Ω/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
1x50/25 0,641 0,727 0,47/0,74 0,15/0,23 0,13 0,7 2,2
1x70/25 0,443 0,727 0,44/0,71 0,14/0,22 0,14 0,8 2,4
1x95/25 0,320 0,727 0,42/0,68 0,13/0,21 0,16 0,9 2,7
1x120/35 0,253 0,524 0,40/0,66 0,13/0,21 0,17 1,0 2,9
1x150/35 0,206 0,524 0,39/0,64 0,12/0,20 0,19 1,1 3,2
1x185/35 0,164 0,524 0,38/0,62 0,12/0,20 0,20 1,1 3,4
1x240/35 0,125 0,524 0,36/0,60 0,11/0,19 0,22 1,2 3,7
1x300/35 0,100 0,524 0,35/0,58 0,11/0,18 0,24 1,4 4,1
1x400/35 0,0778 0,524 0,33/0,56 0,10/0,18 0,27 1,5 4,6
1x500/35 0,0605 0,524 0,32/0,54 0,10/0,17 0,29 1,6 4,9
1x630/50 0,0469 0,387 0,31/0,52 0,10/0,16 0,33 1,9 5,9
1x800/50 0,0367 0,387 0,30/0,50 0,09/0,16 0,36 2,0 6,1
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
1x50/25 155 160 195 5,2 4,7
1x70/25 200 190 235 7,2 6,6
1x95/25 235 230 280 9,9 8,9
1x120/35 265 265 325 12,4 11,3
1x150/35 300 300 370 15,6 14,2
1x185/35 330 345 425 19,2 17,5
1x240/35 385 400 490 25,0 22,7
1x300/35 435 460 565 31,2 28,3
1x400/35 510 555 680 41,6 37,8
1x500/35 570 635 775 52,0 47,2
1x630/50 635 720 880 65,6 59,5
1x800/50 695 822 1010 83,2 75,6
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
1x50/25
1x70/25
1x95/25
1x120/35
1x150/35
1x185/35
1x240/35
1x300/35
1x400/35
1x500/35
1x630/50
1x800/50
500
500
500
500
500
500
500
500
500
500
500
500
K14
K14
K16
K16
K16
K18
K18
K20
K20
K22
K22
K24
CA.81138117
CA.81138118
CA.81138119
CA.81138120
CA.81138121
CA.81138122
CA.81138123
CA.81138124
CA.81138125
CA.81138126
CA.81138127
CA.81138128
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationHalogen-free, flame retardant and self-extinguishing in case of fire. Smoke in the event of fire is limited, transparent (to facilitate evacuation) andnot harmful to electronic equipment. Radial and longitudinal water sealed distribution cable for use indoors and outdoors for 3-phaseformation. Installation in pipes and ground. Ploughing down is not recommended. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N30XC7A5Z1-AR
EnvironmentalEnviromantal Declaration - AXQJ-TT Pure TSLI
StandardCENELEC HD 620 Part 10 Section M Harmonized Construction StandardCENELEC HD 620 Part 10 Section K Harmonized Construction StandardCENELEC HD 604 Halogen free materialSS-EN 60754-1, -2 Corrosive gasesSS-EN 61034-1, -2 Smoke densityEN 50575:2014 Power, control and communication cables - Cables for general applications in construction
works subject to reaction to fire requirements
ConstructionCable Shape RoundConductors Stranded, round, compacted aluminium acc. to IEC 60228 class 2, longitudinally watertightInner semi-conducting layer ExtrudedConductor Insulation XLPE, min. thickness = 7,6 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminum laminateRadial water blocking Aluminium laminate, bonded to sheathRipcord AramidOuter Sheath Halogen free compound, blackExample of marking on sheath AXQJ-TT Pure TSLI 36kV 1x120 AFR/25 D-s2d2a2 DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesCPR Performance class Dca-s2d2a2Bending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 170 kV
Power Cables 36 kV
AXQJ-TT Pure TSLI 18/30(36) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
82 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 83We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screen Current rating at core
temp. 90ºC in ground
Current rating at core Current rating at core Max. short circuit current on
the conductor during 5s at
initial temp. 65ºC kA
Max. short circuit current on
the conductor during 5s at
initial temp. 90ºC kA
1x120/16 310 265 325 5,5 5,0
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivity
of soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-10
Conductors and screen Conductor
resistance ΩScreen resistance
ΩInductance in trefoil/in Reactance
ΩCapacitance Charging current/
phase A/km
Earth fault
current A/km
1x120/16 0,253 1,15 0,41/0,66 0,21 0,17 1,1 3,3
* Cable distance, installation in flat formation = 70 mm.
Standard delivery length
[m]
Delivery Package SAP Number
AXLJ-TT TSLE1x120/16 AFR42kV
1000 K22 CA.80140189
ApplicationSingle-core, distribution cable for outdoor use in 3-phase formation. Installation in pipes and ground/water. Both radial and longitudinal waterblocked. Can be ploughed down.
Alternative Product NameSE-N36XC7A5T5E-AR
Flame retardanceFlame retardant - Not applicable
ConstructionCable Shape RoundConductors Stranded, round, compacted aluminium acc. to IEC 60228 class 2, longitudinally watertightInner semi-conducting layer ExtrudedConductor Insulation XLPE, nom. thickness = 8,0 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tape
Annealed copper wiresRadial water blocking Aluminum-PE laminate, bonded to sheathOuter Sheath PE, black, resistant to weather an UVExample of marking on sheath AXLJ-TT TSLE 42kV 1x120 AFR/16 DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken. Fixed installed -35ºC/ +35ºC
FeaturesThe dielectric loss factor (tg δ) at 50 Hz, between 20 ° C to 90 ° C < 0,6x10^-350 Hz voltage value, which keeps the device for 1 min. period: 70 kV
Bending radius In fixed installation: 10 x DWhen pulling-in: 15 x DWhen plowing down: 8 x D
Max Pulling force - pulling eye [N/mm2] Max. pulling forse = 30 x S (N)S = cross-sectional area of conductor (mm^2)
ElectricalMax. short circuit temperature [°C] (5s) 250 ºCImpulse voltage [kV] 200 kV
Power Cables 42 kV
AXLJ-TT TSLE 20,8/36(42) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-10
84 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 85We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screenarea [mm2]
Conductorresistance Ω/km
Screen resistance*Ω/km
Inductance in trefoil/inflat* mH/km
ReactanceΩ/km
CapacitanceµF/km
Charging current/phase A/km
Earth faultcurrent A/km
1x50/25 0,641 0,727 0,49/0,75 0,24 0,12 1,0 2,9
1x70/25 0,443 0,727 0,46/0,72 0,23 0,13 1,1 3,2
1x95/25 0,320 0,727 0,44/0,69 0,22 0,14 1,1 3,4
1x120/35 0,253 0,524 0,42/0,67 0,21 0,16 1,3 3,9
1x150/35 0,206 0,524 0,41/0,65 0,20 0,17 1,4 4,2
1x185/35 0,164 0,524 0,39/0,63 0,20 0,18 1,5 4,4
1x240/35 0,125 0,524 0,38/0,61 0,19 0,19 1,6 4,7
1x300/35 0,100 0,524 0,36/0,59 0,19 0,21 1,7 5,1
1x400/35 0,0778 0,524 0,35/0,56 0,18 0,24 2,0 5,9
1x500/35 0,0605 0,524 0,34/0,55 0,17 0,26 2,1 6,4
1x630/50 0,0469 0,387 0,33/0,53 0,17 0,28 2,3 6,9
1x800/50 0,0367 0,387 0,32/0,51 0,16 0,31 2,5 7,6
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screenarea [mm2]
Current rating at coretemp. 65ºC in ground*A
Current rating at coretemp. 65ºC in air *A
Current rating at coretemp. 90ºC in air *A
Max. short circuit current onthe conductor during 1s atinitial temp. 65ºC kA
Max. short circuit current onthe conductor during 1s atinitial temp. 90ºC kA
1x50/25 155 160 195 5,2 4,7
1x70/25 200 190 235 7,2 6,6
1x95/25 235 230 280 9,9 8,9
1x120/35 265 265 325 12,4 11,3
1x150/35 300 300 370 15,6 14,2
1x180/35 330 345 425 19,2 17,5
1x240/35 385 400 490 25,0 22,7
1x300/35 435 460 565 31,2 28,3
1x400/35 510 555 680 41,6 37,8
1x500/50 570 635 775 52,0 47,2
1x630/50 635 720 880 65,6 59,5
1x800/50 695 822 1010 83,2 75,6
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivityof soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
Conductors and screen area[mm2]
Standard delivery length[m]
Delivery Package EAN/GTIN number SAP Number
1x50/25
1x70/25
1x95/25
1x120/35
1x150/35
1x185/35
1x240/35
1x300/35
1x400/35
1x500/50
1x630/50
1x800/50
500
500
500
500
500
500
500
500
500
500
500
500
K16
K16
K16
K16
K18
K18
K20
K20
K22
K22
K24
K24
7330384713580
7330384718325
7330384718042
7330384719384
7330384714075
7330384719070
CA.80140194
CA.80140193
CA.80140192
CA.80140191
CA.80140128
CA.80140129
20111047
20165484
20159537
20183095
20113584
20173864
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
ApplicationSingle-core, distribution cable for outdoor use in 3-phase formation. Installation in pipes and ground/water. Both radial and longitudinal watersealed. Can be ploughed down. The outer sheath has a conductive layer that greatly extends the possibilities to do a sheath testing before,during and after installation. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N45XC7A5T5E-AR
Flame retardanceFlame retardant - Not applicable
EnvironmentalEnvironmental declaration - AXLJ-TTCLTSLF
StandardIEC 60840 Construction standard
ConstructionCable Shape RoundConductors Stranded, round, compressed aluminium acc. to IEC 60228 class 2, longitudinally watertightInner semi-conducting layer ExtrudedConductor Insulation XLPE, nom. thickness = 9,0 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tapeShield / Screen Annealed copper wires in contact with aluminum tapeRadial water blocking Aluminium-PE laminate, bonded to sheathRipcord AramidOuter Sheath PE, natural UV protectedExample of marking on sheath AXLJ-TTCL TSLF 52kV 1x50 AFR/25 DRAKA "Date and time", metre markedSemi-conducting layer in outer sheath Yes (facilitates sheath testing)
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation -20 ºC, below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 250 kV
Power Cables 52 kV
AXLJ-TTCL TSLF 26/45(52) kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
86 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 87We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Conductors and screen Conductor
resistance ΩScreen resistance*
ΩInductance in trefoil/in Reactance
ΩCapacitance Charging current/
phase A/km
Earth fault
current A/km
1x50/16 0,641 1,15 0,40/0,72 0,23 0,25 0,5 1,4
1x95/25 0,320 0,727 0,36/0,66 0,21 0,32 0,6 1,8
1x150/25 0,206 0,727 0,33/0,62 0,20 0,38 0,7 2,1
1x240/35 0,125 0,524 0,31/0,58 0,18 0,46 0,9 2,6
1x400/35 0,0778 0,524 0,29/0,54 0,17 0,57 1,1 3,3
1x500/35 0,0605 0,524 0,28/0,52 0,16 0,58 1,1 3,3
1x630/35 0,0469 0,524 0,27/0,50 0,16 0,64 1,2 3,6
* Cable distance, installation in flat formation = 70 mm. Note screen resistance is the sum of copper wires and aluminum tape.
Conductors and screen Current rating at core
temp. 65ºC in ground
Current rating at core Current rating at core Max. short circuit current on
the conductor during 1s at
initial temp. 65ºC kA
Max. short circuit current on
the conductor during 1s at
initial temp. 90ºC kA
1x50/16 155 160 195 5,2 4,7
1x95/25 235 230 280 9,9 8,9
1x150/25 300 300 370 15,6 14,2
1x240/35 385 400 490 25,0 22,7
1x400/35 510 555 680 41,6 37,8
1x500/35 570 635 775 52,0 47,2
1x630/35 635 720 880 65,6 59,5
* Trefoil with screen grounded in both end.
The ratings are based on the following conditions –maximum conductor temperature 90ºC –ground temperature 15ºC –air temperature 25ºC –thermal resistivity
of soil 1,0 ºKm/W –depth of burial 0,65 m –frequency 50Hz
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
Conductors and screen area
[mm2]
Standard delivery length
[m]
Delivery Package SAP Number
1x150/35
1x240/35
1x500/50
1x800/50
500
500
500
500
K18
K20
K22
K24
CA.80140261
CA.80140263
CA.80140266
CA.80160083
ApplicationHalogen-free, flame retardant and self-extinguishing in case of fire. Smoke in the event of fire is limited, transparent (to facilitate evacuation) andnot harmful to electronic equipment. Radial and longitudinal water sealed distribution cable for use indoors and outdoors for 3-phaseformation. Installation in pipes and ground. Ploughing down is not recommended. Ripcords for easier and safer stripping of the outer sheath.
Alternative Product NameSE-N45XC7A5Z1-AR
EnvironmentalEnviromantal Declaration - AXQJ-TT TSLI
StandardIEC 60840 Construction standard
ConstructionCable Shape RoundConductors Stranded, round, compressed aluminium acc. to IEC 60228 class 2, longitudinally watertightInner semi-conducting layer ExtrudedConductor Insulation XLPE, nom. thickness = 9,0 mmOuter semi-conducting layer BondedLongitudinal water tightness Semi conducting water blocking tape
Annealed copper wires in contact with aluminum tapeRadial water blocking Aluminium laminate adhering to outer sheathRipcord AramidOuter Sheath Halogen free compound, blackExample of marking on sheath AXQJ-TT Pure TSLI 52kV 1x150 AFR/35 DRAKA "Date and time", metre marked
TemperatureMaximum operating Temperature 90 ºCTemparatures at installation [°C] Lowest cable temperature during installation: -20 ºC below 0 ºC special precaution shall be
taken.
FeaturesBending radius In fixed installation: 10 x D
When pulling-in: 15 x DWhen plowing down: 8 x D
ElectricalImpulse voltage [kV] 250 kV
Power Cables 52 kV
AXQJ-TT Pure 26/45(52)kV
We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-16
88 89We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
General Information
Prysmian Group. We reserve the right to change as a result of product development and/or changes in standard.
49
Cable designations – CENELEC coding systemThe new type designations according to HD361, which are intended eventually to replace the earlier system entirely, are often referred to as "CENELEC designations". They have been accepted as a
common system within CENELEC which is a European standardisation organisation with the EC andEFTA countries as members. The designation is made up of groups of letters and numbers as shown below.
1) The symbol CC is to be superseded by the code for country orgin according to CENELEC International Regulations. The code for Sweden is SE.
2) The symbol S is used for special type of cables. This code does not comply with the CENELEC document HD 361 S2.
3) Rated voltage in brackets is not yet standard in CENELEC.
Example: SE-N10XC7E-AR
AXLJ-RMF 12 kV
Standardand ratedvoltage
Cable design(from insula-
tion outwards)
Number and cross-section of condutors
Type of standard
Rated voltage
Insulation
Metallic covering
Sheath
Conductor form
Number of conductors
Conductor cross-section
Protection coreA Accepted national standardCC-N ¹) Other national standardH Established standardS ²) Special standard
00 (<100/100V)³)01 (≥100/100,<300/300 V)03 300/300 V05 300/500 V07 450/750 V1 (0,6/1 kV)3 (1,7/3 kV)6 (3,5/6 kV)10 (7/12 kV)20 (14/20 kV)30 (18/30 kV)60 (36/60 kV)
B EP rubber, max 90°CE Ethylene plastics, PEG EVA rubberM Mineral materialN2 Special polychloroprene compoundN4 Hypalon CSMR EP rubber, natural rubber, max 60°CS Silicone rubberV PVCV2 PVC, For max. 90°CV3 PVC, Fors installation at low temperaturesX XLPEZ Polyolefine, cross-linked LSZHZ1 Polyolefine, thermoplastic LSZH
A4 Aluminium sheat on each coreA5 Concentric aluminiumC Concentric copper conductors, spiral-shapedC4 Copper braid over cable bodyC6 Concentric copper conductors, wave-shapedC7 Copper wire screenC8 Copper screen as C7, on each core
G With protection coreX Without protection core
-D Flexible conductor for welding cable-F Flexible conductor of a flexible cable or cord. Class 5-H Highly flexible conductor of a flexible cable or cord. Class 6-K Flexible conductor of a cable for fixed installation-R Rigid, round conductor, stranded. Class 2-S Rigid, sector shaped, stranded. Class 2-U Rigid, round conductor, solid. Class 1-W Rigid, sector shaped. solid. Class 1-AR Al, Rigid, round conductor, stranded Class 2-AS Al, Rigid, sector shaped, stranded. Class 2-AU Al, Rigid, round conductor, solid. Class 1-AW Al, Rigid, sector shaped. solid. Class 1
B EP rubber, max 90°CE Ethylene plastics, PEG EVA rubberJ Glass fibre braidN Polychloroprene or similar materialQ PolyurethaneQ4 Polyamide (Nylon)R EP rubber, natural rubber, max 60°CT3 Textile layer (wrapping or tape), imptegnated or notV PVCV5 PVC, extra oil-resistantZ Polyolefine, cross-linked LSZHZ1 Polyolefine, thermoplastic LSZH
General information_eng.fm Page 49 Thursday, March 13, 2014 10:48 AM
90 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 91We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Cable Designations used in SwedenExtracts from SS 424 17 01
Letter 1st letterCore
2nd letterInsulation
3rd letterSheath or otherdesign detail
4th letterDesign detail or usage
5th letterDesign detail or usage
A Aluminium Screen of aluminiumfoil and/or aluminium wire
B Aluminium alloy Flame retardant thermo-
free, low smoke)
Flame retardant thermoplastic
smoke)
Vehicle cable
Lead sheath Connection wire
Lead sheath
C Impregnated paper Concentric copper screen Concentric copper screen
D Rubber with outerrubber sheath
E Copper, solid(class 1)
Ethylene propylenerubber
Reinforced design Reinforced design
F Copper, stranded (class 2)
Braid of copper wire Braid of copper or steel wire
H Silicon rubber Lift cable Suspension cable
I Polyurethane Polyurethane
J Steel wire Steel tape armouring For laying in ground
K PVC PVC PVC PVC
L Polyethylene (PE) Screen of plastic coatedaluminium tape ev. together with screen of copper
Polyethylene (PE) Polyethylene (PE)
Polyethylene (PE)
M Copper, stranded
O Chloroprene rubber Chloroprene rubber Oil cable
P Galvanised steel tapearmouring
Galvanised steel tape armouring
Q Halogen free plastic Flame retardant thermoplastic
smoke)
Flame retardant thermo-
gen free, low smoke)
R5)
Plastic coated aluminium tape armouring
Control cable
S(class 6)
Self-supporting
T Heavy connection cable or galvanised steel wire armouring
Steel wire armouring
U Without outer sheath
V Rubber without outer sheath
Ethylene propylene rubber For laying in water For laying in water
X Cross-linkedpolyethylene (XLPE)
PVC, oval cross-section
Z Flame retardant cross-linked
low smoke)
Flame retardant cross-linked
smoke)
Cable for neon equipment
Cable Designations used in NorwayA cable code of 2 - 4 letters is used to descriebe the construction.Additional abbrevation for instrumentation cables: Collective screen = (c) Individual pair or triple screen = (i)The interpretation (per letter) can be read from the table below:
1st. letter:Insulation
2nd. letterBedding / inner sheath
3rd. letterArmouring / screen
4th. letterOuter sheath
A Fibre, tight cladded A Aluminium (optional with cor-rosion protection)
A Strength member yarn A Yarn + bitumen
B Fire resistant tape + insulation (Halogen-free)
B Corrogated aluminium (o.w.c.p.)
B Steel tapes, 2 B Hydrocarbon resistant sehath
C Polychloroprene (Neoprene) PCP, or chlorinated polyethyl-ene - CPE
C Polychloroprene (Neoprene) PCP, or chlorinated polyethyl-ene - CPE
C Galvanized steel wire braid C Polychloroprene (Neoprene) PCP, or chlorinated polyethyl-ene - CPE
D Impregnated paper Drip free
D Aluminium + Plastics D Oil filled cable reinforcement (Longitudinal / Transverse)
D
E Polyethylene - PEPolypropylene - PP
E Polyethylene - PEPolypropylene - PP
E Oil filled cable reinforcement(Transverse only)
E Polyethylene - PEPolypropylene - PP
F PE or PP + F Bedding or taping F Flat steel wire armour F Semi-conducting PE
filling compound (Halogen-free)
G Polyamid - PA GGG PE + PA
H Chlorosulphonated polyethylene - CSP
H Chlorosulphonated polyethylene - CSP
H Steel tape + steel wires
H Chlorosulphonated polyethylene - CSP
I Thermoplastic compound (Hal-ogen-free)
I Thermoplastic compound (Hal-ogen-free)
I Steel tapes, 4 o I Thermoplastic compound (Hal-ogen-free)
K Paper K Lead K Steel wire, plastics or rubber coated
K Lead
L Air + plastics (Coaxial cable)
L Aluminium laminate + plastics sheath
L Aluminium (laminated to outer jacket)
L
M Expanded PE or PP +filling compound
M Polyester MM Polyester
N Impregnated paper N Polyurethane N Steel (laminated to outer jacket)
N Polyurethane
O Impregnated paper,oilfilled cable
O Lead + Plastics O Copper wire braid(Tinned or bare)
O
P Polyvinylchloride - PVC P Polyvinylchloride - PVC P Phosphorbronze wire braid P Polyvinylchloride - PVC
Q Fibre in loose tube QQ Steel wires + counter steel tape (optional)
Q
R Ethylenepropylene rubber - EPR
R Ethylenepropylene rubber - EPR
R Steel wires (round) + filling compound
R Ethylenepropylene rubber - EPR
S Silicone rubber S Bedding or taping +concentric conductor
S Concentric conductor (Screen) S Silicone rubber
T Cross-linked polyethylene XLPE T PE + aluminium wire + steel tape
TT Cross-linked polyethylene XLPE
U Halogen-free thermoset com-pound EMA or EVA
U Halogen-free thermoset com-pound EMA or EVA
UU Halogen-free thermoset com-pound EMA or EVA
V Fibre, slotted core V Aluminium screen V Double wire armour (two layers)
V Other halogen-free thermoset materials
W Other materials W Other materials W Catenary wire W Other materials
X No insulation X No bedding or equivalent X No armour X No sheath
YY Screen YY
Z Flour plastics PTFE / FEP Z Flour plastics ZZ Flour plastics
- J Earth conductor
- O Optical fiber
- OJ Optical fiber and earth conductor
92 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 93We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Cable Designations used in FinlandDesignations in the cross-section:
The most common letters used in domestic products (current product selection):
x Separating the number of phase cores and the cross-section (mm²), for example AXMK 1x300 1 kV
+ Product having an external conductor (centre conductor, messenger or auxiliary phase core), for example AHXAMK-W 3x240+70 20 kV, AHXAMK-WM 3x95+62I 20kV, AMKA 4x25+35 1 kV
/ Separating numbers or letters from each other.- separates the cross-section of the concentric conductor (metallic screen) from the phase core, for example MCMK 3x25/16 1kV, AHXCMK-WTC 3x240/35 20kV- separates the cross-section of the aluminium and the steel core in overhead conductors, for example ACSR 54/9 RAVEN
A Aluminium or aluminium alloy (for alumiini in Finnish)- in the beginning of the type designation means Al conductor, for example AXMK (excep-tion: SAX-W means Al alloy)- in the middle of the type designation means Al foil laminate, for example AHXAMK-W- aluminium alloy messenger, for example AMKA- aluminium alloy armouring, for example AHXLKAJ-W
Copper conductor (no A letter in the beginning), for example MCMK, XMK, HXCMK-WTC
M - plastic insulation (general expression), for example MCMK, AMKA.. Usually plastic insu-lation is either PVC or PE (for muovi in Finnish)- plastic sheath (general expression), for example MCMK, AHXAMK-W. Plastic sheath can be PVC, PE or fire-retardant and halogen-free thermoplastic compound.
K Cable, for example XMK, AHXAMK-W (for kaapeli in Finnish)
X XLPE insulation, for example AXMK, AHXAMK-W, AMKA-X, SAX-W (for PEX in Finnish)
H - extruded semi-conducting layer below and over the insulation (in MV and HV cables), for example AHXAMK-W (for hohtosuoja in Finnish)- sheath made of special material, for example TASH having heat resistant sheath
C - concentric layer of copper wires (metallic screen), for example MCMK, AHXCMK-WTC- uniform copper layer (Cu helical tape or Cu foil laminate) MCCMK, HXCCMK
S Copper braid, for example LSM-HF
L - lead sheath, for example AHXLMK-W (for lyijy in Finnish)- marine cable (the 1st letter in the type designation), for example LM-HF (for laiva in Finnish)
P Round steel wire armouring, for example AHXAMKPJ-W
J - a conductor or a lead, for example MMJ, LJST-HF (for johdin in Finnish)- jute tape layer, for example AHXAMKPJ-W
O Control cable, for example MMO (for ohjaus in Finnish)
CHB Metallic screen having Cu wires, semi-conducting tape layer and Al foil laminate, for example HXCHBMK. The cross-section of the metallic screen given in type designation is solely based on the cross-section of Cu wires.
CA Metallic screen having Cu wires, semi-conducting tape layer and Al foil laminate, for example AHXCAMK-W. The cross-section of the metallic screen given in the type designa-tion is a total cross-section of Cu wires and Al foil laminate combined.
Y Each phase core having a separate metallic screen (in a 3-core cable), for example HXYL-MKPJ-W 3x95 10kV. This letter is not used with 3-core cables having Al foil laminate only (AHXAMK-W).
FR Fire Resistant cable remaining functional during fire, for example FRHF
T Heat resistant, for example TASH, AMKA-T
E Cable having a special feature compared to standard cable, for example XMKE 1x300 1kV having a flexible Class 5 conductor (for erikoinen in Finnish)
General information_eng.fm Page 53 Thursday, March 13, 2014 10:48 AM
Exceptions to the previous, trademarks:
Exceptions to the previous, bare conductors, overhead conductors, etcTypical Finnish cable with trade name Wiski™
SAX™ -W .SAP si tcudorp siht rof eman hsinniF dezidradnats A .rotcudnoc derevoC
SAXKA® -W Aerial bundled MV cable, completely watertight
AFUMEX® Fire retardant halogen-free cable (or material)
ATON® Flexible, cold resistant (-50°C) rubber insulated cable
Wiski™ The nickname and trademark of AHXAMK-W
Multi-Wiski™ The nickname and trademark of AHXAMK-WM
Wiski Plain™ The nickname and trademark of AHXAMK-WP
ACSR Aluminium conductor steel reinforced. These overhead conductors have often nickname of bird, city etc, for example Sparrow, Duck, Savo
AACSR Aluminium alloy conductor steel reinforced (overhead conductor)
AAC All aluminium conductor (overhead conductor)
HK )hsinniF ni irapuk uttetukheh rof( seriw delaenna htiw rotcudnoc reppoC
FE Steel conductor
TRL Overhead contact conductor for electric locomotives and trolleys
MA 84:01 4102 ,31 hcraM ,yadsruhT 45 egaP mf.gne_noitamrofni lareneG
94 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 95We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Rated area mm2
Min number of wires per conductorMax conductor resistance at 20°C
Copper conductor Aluconduc-tors
Round conductors, non-compr. Round conductors Shaped conductors Uncoated
wires Ω/kmTinned wires Ω/km
Uncoated,plated Ω/kmCu Al Cu Al Cu Al
0.5 7 - - - - - 36.0 36.7 -
0.75 7 - - - - - 24.5 24.8 -
1 7 - - - - - 18.1 18.2 -
1.5 7 - 6 - - - 12.1 12.2 -
2.5 7 - 6 - - - 7.41 7.56 -
4 7 7 6 - - - 4.61 4.70 7.41
6 7 7 6 - - - 3.08 3.11 4.61
10 7 7 6 - - - 1.83 1.84 3.08
16 7 7 6 6 - - 1.15 1.16 1.91
25 7 7 6 6 6 6 0.727 0.734 1.20
35 7 7 6 6 6 6 0.524 0.529 0.868
50 19 19 6 6 6 6 0.387 0.391 0.641
70 19 19 12 12 12 12 0.268 0.270 0.443
95 19 19 15 15 15 15 0.193 0.195 0.320
120 37 37 18 15 18 15 0.153 0.154 0.253
150 37 37 18 15 18 15 0.124 0.126 0.206
185 37 37 30 30 30 30 0.0991 0.100 0.164
240 61 61 34 30 34 30 0.0754 0.0762 0.125
300 61 61 34 30 34 30 0.0601 0.0607 0.100
400 61 61 53 53 53 53 0.0470 0.0475 0.0778
500 61 61 53 53 53 53 0.0366 0.0369 0.0605
630 91 91 53 53 53 53 0,0283 0,0286 0,0469
800 91 91 53 53 - - 0,0221 0,0224 0,0367
1000 91 91 53 53 - - 0,0176 0,0177 0,0291
1200 1) 0,0151 0,0151 0,0247
1) The minimum number of wires is not specified for these conductor areas. These areas may be designed with 4, 5 or 6 segments of equal size (Milliken).
Stranded conductors, Class 2
Rated area mm2
Max conductor resistance at 20 °C
Round copper conductors Round aluminum conductors
Uncoated Ω/km Tinned Ω/km Ω/km
0.5 36.0 36.7 -
0.75 24.5 24.8 -
1 18.1 18.2 -
1.5 12.1 12.2 18.1
2.5 7.41 7.56 12.1
4 4.61 4.70 7.41
6 3.08 3.11 4.61
10 1.83 1.84 3.08
16 1.15 1.16 1.91
25 0.727 - 1.20
35 0.524 - 0.868
50 0.387 - 0.641
70 0.268 - 0.443
95 0.193 - 0.320
120 0.153 - 0.253
150 0.124 - 0.206
185 - - 0.164
240 - - 0.125
300 - - 0.100
Conductor resistances in installation cables and power cables pursuant to EN 50228Solid conductors, Class 1
Flexible conductors, Class 6
Flexible conductors, Class 5
Rated area mm2 Max wire diameter in the conductor mm
Max conductor resistance at 20°C
Uncoated wires Ω/km Tinned wires Ω/km
0.5 0.21 39.0 40.1
0.75 0.21 26.0 26.7
1 0.21 19.5 20.0
1.5 0.26 13.3 13.7
2.5 0.26 7.98 8.21
4 0.31 4.95 5.09
6 0.31 3.30 3.39
10 0.41 1.91 1.95
16 0.41 1.21 1.24
25 0.41 0.780 0.795
35 0.41 0.554 0.565
50 0.41 0.386 0.393
70 0.51 0.272 0.277
95 0.51 0.206 0.210
120 0.51 0.161 0.164
150 0.51 0.129 0.132
185 0.51 0.106 0.108
240 0.51 0.0801 0.0817
300 0.51 0.0641 0.0654
400 0.51 0.0486 0.0495
500 0.61 0.0384 0.0391
Rated area mm22 Max wire diameter in the conductor mm
Max conductor resistance at 20°C
Uncoated wires Ω/km Tinned wires Ω/km
0.5 0.16 39.0 40.0
0.75 0.16 26.0 26.7
1 0.16 19.5 20.0
1.5 0.16 13.3 13.7
2.5 0.16 7.98 8.21
4 0.16 4.95 5.09
6 0.21 3.30 3.39
10 0.21 1.91 1.95
16 0.21 1.21 1.24
25 0.21 0.780 0.795
35 0.21 0.554 0.565
50 0.31 0.386 0.393
70 0.31 0.272 0.277
95 0.31 0.206 0.210
120 0.31 0.161 0.164
150 0.31 0.129 0.132
185 0.41 0.106 0.108
240 0.41 0.0801 0.0817
300 0.41 0.0641 0.0654
96 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 97We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
General terms and conditions of supplyUnless agreed otherwise, the ”General Terms and Conditions of Supply NL09” are applied.
Length tolerances
Installation cables, standard length: ± 3% Rubber cables, standard length: ± 5% Power cables, standard length: + 3% –2%
Reel label
The reel label is supplied with large, distinctive text and a bar code for faster and safer handling of goods, also at the clients’ sites. The bar code system chosen by us (code 39) is an alphanumeric bar code with a high safety level. The image below shows an example of a reel label. The actual labels are at least 160 mm wide.
Recommendations for cable layingGeneral
Cable laying environments and cable types vary widely. This section provides brief advice and recommendations for different operations during cable laying. The cable weight often determines the laying method. In case of cable laying in ground, one can choose between pulling, driving and ploughing. If the area is easily accessible for vehicles, driving is an easier and more cable-friendly method. Tractor excavator is often used for reel weights of up to approx. 1 tons, where the cable reel hangs from the bucket. Heavier cables are driven with crane truck or a vehicle for lift dumpers. For cable pulling, cable reels are placed evenly distributed along the cable route so that the cable runs freely. Pulling can be performed manually or with a machine. The reel shall be possible to brake during cable laying, driving as well as pulling. There are detailed manuals for ground installation indicating the installation depth, cable protection, marking and combined laying with telecommunication cables in SEK Manual 429. The organization EBR (El Byggnads Rationalisering, Rational Electrical Installation) has issued a manual for cable laying for max 145 kV (KJ41:09). Another norm, SS 424 14 38, regulates cable laying in buildings and culverts. Sharp bends can be critical moments during pulling and permanent installation, high tensile stresses and laying at low temperatures.
Marine cable laying
Standard cables are normally used in shallow water with good bottom conditions and low level of water movement. The worst risk of operation disturbances in these installations is external mechanical damage to land fixtures and anchor. Therefore, the cable shall always be marked with signs and protected mechanically at the land fixtures. In deeper water or unfavourable or unknown bottom conditions where better mechanical protection is desired, the cable should be reinforced. Additional fixing may also be necessary to keep the cable in place in areas with strong currents, using e.g. sandbags or similar.
Cable ploughing
Cable ploughing methods have been developed within the latest years and entail that cable installation costs have decreased compared to traditional cable laying with trenching. Observe the following for successful cable ploughing installation:
Cable ploughing is generally considered to be a “rough” installation method for cables. Uncautious handling may damage the cables due to rocks and other sharp objects in the ground pressed into cable sheaths. The planned installation route shall always be ploughed in advance to ensure that cable installation is possible along the planned route. Choose a cable type intended for cable ploughing. Generally, cables with polyethylene (PE) outer sheath has the required mechanical strength. Halogen-free, fire-retardant sheath can be ploughed if required caution is observed. Outer sheaths have different mechanical characteristics at different temperatures which can be crucial for whether a cable installation will
be good or less good. A cable installed on a warm summer day at +30°C ambient temperature can show different performance from the same cable installed at an ambient temperature of +10°C. The choice of machines and equipment is also crucial for the final result. Experience has shown that machines and equipment used for cable laying require similar service and maintenance as all other equipment. Faulty or damaged equipment can easily destroy many metres of cable.
Other
Cable ladders are practical aids for cable laying both indoors and outdoors. Power cables are preferably installed with a slight distance between cables for efficient cooling. Lashing wire should be used with caution to avoid any cuts
in the sheath, especially in case of vertical cable laying. Sheath damage may also occur in long horizontal cable connections fixed with lashing wire, due to temperature changes. Clamps are less harmful to cable sheaths and should therefore be preferred for somewhat heavier cables and sheaths that can reach very high temperatures. Heat may originate both from the environment and from load losses in the cable. XLPE cables installed on ladders with uninhibited air circulation achieve a conductor temperature of +90°C and a sheath
General information.
temperature of approx. +70°C at the rated current. If cooling of the cable is complicated by a heat-insulating layer such as sawdust or pulp, the conductor and sheath temperatures can reach +125°C and +100°C, respectively. At this point, there is a risk of deformation of the insulation and sheath layers which leads to disruptive discharge in the cable.
In case of open laying of single-conductor cables, the cables shall be bound together and fixed to the base surface to avoid them being thrown apart at short-circuiting. Otherwise, thick cables exposed to high short-circuit currents may be damaged or damage their surroundings. Single-conductor cables are normally laid close together in a triangle form which both facilitates the “trussing” and reduces shield losses which in its turn affects the load capacity. In order to improve the load capacity in connections with single-conductor cables, shield losses can be minimized in exceptional cases with various methods. The simplest way is to only earth the metal shields of the cables in one end of the connection, open shield. Instead of an induced shield current which causes losses, an induced voltage is achieved between the insulated shield end and earth. This voltage is directly proportional to the length of the connection and the conductor current and can be dangerous to people. Therefore, open shield is only recommended for short connections (< 100 m) and preferably in protected areas (substations, equipment rooms etc.). Note that in case of single-point earthing, the insulation between the shield and the system earth shall be checked prior to commissioning.Earth faults may cause electric arcs and fire hazard.
Fire sealing
Fire sealing of lead-throughs is necessary in order to reduce the
risk of fire spreading between different parts of the building
through cable connections.
This also applies during the entire construction period. A proper
fire sealing should prevent fire from spreading between fire
compartments during the whole course of the fire – fire
development and extinguishing – i.e. it shall
• Meet the requirements of the fire class: be type approved.
• Withstand smoke, gas and extinguishing media during the
fire.
• Withstand fire restoration after the fire
• Be easily installed and allow modifications.
• Withstand loads normally occurring in the installation, during
both operation and standby
1. Minimum cable temperature during cable laying
Cable type Temperature °C
AXQJ, FXQJ, N1XZ1, AXALJ-TT, AXLJ-RMF, AXQJ-RMF, AXLJ-TT TSLF
-10-20
5. Maximum permissible surge current in three-phase cables (kA)
Areamm2
Rated voltage Areamm2
Rated voltage
1kV 12-24kV 1kV 12-24kV
50 45 55 150 60 70
70 50 60 185 60 70
95 55 65 240 60 70
120 55 65 300 60 70
6. Testing voltage for 12-36 kV cables after laying
Voltage kV Insulation typeAC
kV Time
New cable installation12 PEX 12
75 min24 h
24 PEX2414
5 min 24 h
36 PEX3618
5 min24 h
3. Sealing of cable ends
The cable ends shall be sealed against moisture after each cutting. The cut length shall alsi be sealed if it is not installed immediately.
2. Minimum bending radius
Cable typeAt
layingAt ploughing
At fixing
AXQJ, FXQJ-EMC, FKKJ, N1XE / -Z1Single-conductor 1kVMulticonductor
AXQJ, FXQJ, AXALJ-TT, AXLJ-TTCL TSLF, AXLJ-RMFSingle-conductor 12 - 36kV Multiconductor
15 x D15 x D
15 x D 12 x D
8 x D8 x D
8 x D 8 x D
10 x D8 x D
10 x D 8 x D
D = Outer diameter of the cable Dr
4. Maximum pulling force
Pulling equipment Pulling force
Immediate connection in all conductors Cable grip on the cover
Aluminium P = 30 N/mm2
Copper P = 50 N/mm2
P = 5 x D2 Newton
98 drakakeila.ee We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 99We reserve the right to change as a result of product development and/or changes in product standard. Data from 2017-10-13 drakakeila.ee
Testing after cable laying
All cables are subjected to routine testing according to the applicable standard at the factory before the reels are delivered to the client. In order to check the dielectric strength after transport and cable laying, a new test shall be conducted by the installer or the owner of the installation prior to commissioning of the cable. The test standard SS 424 14 17 for PEX cables indicates the method, voltage and time that can be applied in testing. Tests may also prove necessary in technical assessment of older installations. Ensure that a reasonable test voltage is chosen, taking the general condition of the installation into account. Prior to testing, it is important to ensure that the parts of the installation which are not to be tested are disconnected and earthed. Then the voltage test is performed with the voltage indicated in the regulations. After testing, it is important to earth the installation to ensure that the installation and testing equipment are properly discharged. Maintain earthing until the cable is commissioned or for at least 3 hours.
Sheath testing in medium voltage cablesNetwork owners set high requirements on the quality of execution of cable installations. Many power plants require improved quality assurance for this work. The possibility of checking the sheath on medium voltage cables both before and after installation has therefore come into focus. This contributes to better safety for the network owner as well as the external contractors often used for laying cables and installing them in the ground.
The advantage of the semiconductive outer layer is that the cable can be tested for sheath faults before the cable trench is closed. If a fault is detected, it can be repaired in an early stage, saving both time and money. Cable testing of cables installed in pipes is another positive side of choosing this cable.
Measurement of sheath current
Required instrument: high voltage generator (DC) with a precise ammeter for measuring the output current. The voltage shall be adjusted gradually from 0 to the maximum of 5 kV to avoid indication of several sheath faults at the same time. The largest faults are then detected first. The measurement voltage depends on the type of sheath material. For our AXLJ-TTCL with PE (Polyethylene), the maximum measurement voltage is 5 kV.
Sheath current can also be identified with a megger. The formula for sheath current is then:
I = U / (RxL)
where I is the sheath current per length unit (A/km), U is the applied voltage (V), R is the detected sheath resistance (Ω) and L is the cable length (km).
Sheath test, measurement setup
• Strip 10 cm of the semiconductive sheath from both the inner and the outer end of the sheath.
• Connect the instrument between the semiconductive layer of the sheath and the copper shield.
• Adjust the instrument to read the leakage current ”I”.
• Start by applying 100 V.
• Increase the test voltage gradually.
• Discontinue the test if a fault is detected.
• If no fault is detected during the voltage increase, continue to the test voltage within a minute.
Note! When measuring a cable on reel, ensure that the inner end is freed, dry and stripped to at least 10 cm to avoid conduction due to moisture/water.
Interpretation of measurement results
Suitable test voltages and acceptable leakage currents for different sheath materials are indicated below. An aged sheath may show up to 1000 times higher leakage currents than a new one without being faulty, and still be approved, depending on the installation conditions.
SELCABLE, 2012, / Available at: [www] http://www.selcable.se/$-1/file/-
selc-11-005-mantelprovning.pdf [2015-07-20]
Repairing sheath damage
When repairing sheath damage, 10 cm of the conductive layer shall be stripped from each side of the edges of the hole/damage. This ensures that no erroneous indications are received during repeated testing after the repair. To maintain the special function of the conductive layer after repair and testing, a temporary connection should be made over the non-conductive repair with e.g. a copper net.
Always consult your supplier of joint/repair sets for recommendations.
10 cm 10 cm
Sheath material
Test voltage (kV, DC)
Newly installed cable Max leakage current, repeat measurementRec. max leak-
age currentMax leakage, note
PE 5 10 μA/km 1 mA/km 1 mA/km
PVC 2 0,5 μA/km 10 mA/km 50 mA/km
LSZH* 2 2 mA/km 50 mA/km 500 mA/km
* LSZH halogen-free and flame-retardant sheath
Drum Dimensions, mm Weight Carrying capacity
type A B C D E kg/drum kg
K6 600 468 250 400 75 12 300
K7 700 580 325 500 75 20 400
K8 800 580 375 500 75 25 500
K9 900 630 425 550 75 34 600
9FV 900 675 425 550 82 50 700
K10 1000 712 500 600 75 54 800
K11 1100 762 575 650 106 55 850
11GV 1100 755 500 600 82 85 1000
K12 1200 982 675 850 106 90 1500
13G 1300 760 600 600 82 105 1600
K14 1400 982 800 850 106 115 2000
15G 1500 760 700 600 82 150 2000
K16 1600 1018 950 850 106 195 2500
K18 1800 1075 1100 850 132 230 3000
K20 2000 1190 1300 1000 132 340 3500
K22 2200 1190 1400 1000 132 410 4500
K24 2400 1205 1400 1000 132 450 5000
K26 2600 1448 1500 1200 132 900 10000
K28 2800 1610 1500 1300 132 1180 12000
K30 3000 1800 1500 1500 132 1500 13000
Drum dimensions and weights
100 101
Drum handling guideThe right way to transport, handle and move drums
A cable is a valuable product. The cable transportation package is usually a drum. The battens on the drum seem thick enough to remain unbroken. But, with a cable weighing more than 4 tons, it becomes very vulnerable. If the handling is done correctly, the drum will protect the cable from transportation damages. If the drum is damaged, the cable can also be damaged. The damage might not be discovered until after installation, when repairs can be extremely expensive.
The purpose of these instructions is to tell you how damages can be avoided by correct drum handling.
Roll in direction of arrows only
Always roll the drum in direction of the arrow. This way the cable will not unwind and loosen on the drum. But, this does not mean that the drum can be rolled freely. When the drum must be rolled for some reason or other, roll it in the direction of arrow over a distance not exceeding 5 meters. If it is rolled beyond the 5 m limit, the cable wind will come too tight and cut o the rope holding the cable end. This will deform the cable and make it unfit for use.
drum. Keep the drum from touching other drums and well balanced. Take care not to give any impact to the drum being lowered. In case a cable drum must be temporarily in a waiting position above the deck for reason of cargo handling, keep it hoisted and do not put it down on the deck.
Keep the drum upright
Always store and move the drum in an upright position. The drum is constructed to be handled in an upright position - it will not stand up to being lifted lying flat. When kept upright, the cable layers will not entangle and cause problems when the cable is laid. Keep the cable protected until the cable is used.
Handling with fork-lift truck
The forks of the truck must be longer than the width of the drum, so that the lagging is not damaged. Dierent widths of drums should be painted on the forks enabling the operator to select the correct position for the drum size. When moving the drum, tilt the truck mast so that the drum remains in the fork and the points don’t touch the ground. Raise the forks of the forklift suciently 15-20 cm abovethe ground. Insucient raising may cause the drum to be dragged on the ground and eventually damaged or dropped o the forks if the ground surface is uneven. Don’t release the drum until the truck has sopped completely. Don’t push the drum with the truck. Leave
age
sucient room between each drum so that the fork doesn’t damage the drum.
Nail with caution
In case the planks have to be refastened, the nailing should be done carefully in the middle of the drum flange. If label or something similar is attached to the drum with nails, make sure that they don’t touch the cable.
Lift the drum without damage
When lifting the drum, use a shaft through the centre of the drum and a wire spreader. If these are not available, lift with as long a wire as possible, so that the sides of the drum are not damaged. Make sure that the cable head is not pinched between wire and
Secure the drums firmly
The round-shaped cable drum rolls easily. It is an a very unstable state because its center section is vacant and the whole weight rests on its peripheral section. Make sure to use drags to prevent drums from rolling during storage. Large drums should be lifted from the base onto triangular or square wedges. The wedges should be posi-tioned by the flanges or the full width of drum. Sideways movement is eliminated by planks attached to the side of the drum. In case smaller drums are placed between larger ones, each drum has to be supported separately to prevent damages.
Avoid stacking
Stacking of drums should be avoided. If, however, one is forced to do this, same size of drums should be positioned exactly on top of each other.If smaller drums are stacked on larger drums, planks of the size of the larger drum is placed in between to protect the flanges. Above method is recommended even when same size drums are stacked.
Fasten the drums firmly
The drum is fastened to the base through the centre hole or across the flanges with wires or ropes.
Secure drums to be transported
To prevent movement of drums, a combination of wedges and transportation support should be used and tied down front and rear. Higher drums should be tied in side direction as high up as possible.
The drums loaded first should rest against the front board (observ-ing shaft weight). If the last drum doesn’t lean against the end board or the board is not strong enough, the drum must be secured.
Don’t drop drums
The drum must not be dropped from the vehicle. The drum is to be lifted either by winch of fork-lift truck as mentioned in “lifting the drum”. If above mentioned equipment is not available, best possible conditions must be created to unload the drums from the vehicle. A platform of the same height as the vehicle or a point in the terrain will guarantee that no damage will occur. Make sure when unloading that the drum doesn’t strike another drum.
Draka Keila Cables AS
Paldiski road 31
76606 Keila
Estonia
T +372 674 7466
www.drakakeila.ee
© by Draka Keila Cables AS 2017
Issue: December 2017
The preparation of text and illustration has been carried out with great care. Nevertheless mistakes can not be excluded. All photographs are the exclusive property of Prysmian Group.
Prysmian Group does not accept any liability for casual or consequential damage in connection with the use of this catalog. Improvement proposals and advices are to be sent to the above address.
All rights reserved. This document may not be copied in whole or in part, be reproduced, translated into another language or stored on electronic media.
Please note: Prysmian Group herewith warrants that the delivery items contained in this catalogue will be of the agreed nature and quality upon passing of the risk. Aforementioned nature of the delivered items shall be exclusively rated and measured by the sales and purchase agreements made in writing between Prysmian Group and the purchaser about nature and quality, properties and characteristic performance features of the respective delivery item. Illustrations and information contained in catalogues, price lists and other information material disclosed to the purchaser by Prysmian Group as well as any information describing the product shall be only legally binding, if expressly being referred to as binding information. Under no circumstances, such information shall be taken as guarantee for the special quality or nature of the delivery item. Such quality guarantees must be explicitly agreed upon in writing. Prysmian Group herewith reserves the right to modify the content of the catalog at any time.