GENERAL SPECIFICATION
GSNoGBD110E-6
GasTHERMISTOR TYPE VORTEX FLOWMETER
for GAS MEASUREMENT
OVAL VORTEX FLOWMETERStandard and Gas Purge Types MODEL VF series
httpwwwovalcojpenglish
Head Office (Tokyo) Tel +81 3-3360-5121 Fax +81 3-3365-8605 International Sales Division Email SK10ovalcojpOverseas Branch Offices Beijing Seoul Singapore Taipei
GENERALThis flowmeter is a kind of vortex flowmeters which makes use of the regular and periodic characteristics of Karman vortex street A thermistor sensor picks up changes in flow velocity that come with vortex shedding in the manner - changes in thermistor temperaturerarr changes in resistance valuerarr a train of pulses proportional to the flow velocityIn the gas purge type changes in fluid velocity that come with vortex shedding are replaced by changes in fluid velocity of a purge gas (clean gas) introduced from an external sourceThanks to this arrangement the thermistor sensor constantly remains in contact with clean room temperature purge gas permitting precise flow measurement of gases containing dust and mist high or low temperature gases or others previously thought difficult to be measured
FEATURES1 The absence of mechanical moving parts and components subject to abrasion ensures long life and continuous operation with no loss of accuracy with time2 By measuring actual flowrate the measurement is insensitive to changes in fluid temperature pressure and other physical properties3 Provides pulse output proportional to the flowrate to simplify totalization4 Small pressure loss saves energy
5 Replaceable sensor facilitates maintenance and servicing without the need of interrupting the gas flow6 The converter separated from the sensor body may be located anywhere for maximum ease of maintenance irrespective of piping conditions7 Gas purge type is primarily intended for measuring gases containing dust and mist or high or low temperature gases
GENERAL SPECIFICATIONS Standard Meter Body
Item DescriptionBody style Wafer FlangeNominal size (mm) 20 25 32 (40) 50 80 100 150 200 250 300 (350) 400 (450) 500
Material (2)
Meter body SUS304 STPG370 SUS304TP STPY400 SUS304TP
Flange mdashSS400
or SFVC2A
SUSF304 SFVC2A SUSF304
Bluff body SUS304 SCS13A or SUS304
Flange ratingCompanion flangeJIS 10 20 30 K
ASMEJPI 150 300 (600)
JIS 10 20 30 KASMEJPI 150 300 (600)
JIS 10 KASMEJPI 150
Standard Connecting Pipe Sch40 Sch20Operating temp range minus20 to +130 0 to +130 minus20 to +130 0 to +130 minus20 to +130Design pressure 500MPa 189MPaAccuracy Within plusmn1 of RD or plusmn1 of FS (1)Repeatability Within plusmn02Installation Horizontal or vertical
1 For use in the high pressure range (high Reynolds number [28times106 or above]) contact OVAL2 Material may vary according to specifications3 If the connecting pipe is different from standard connecting pipe contact OVAL4 For nominal size between 200 and 300mm with flange material SFVC2A the max operating temperature ranges from 0 due to temperature limitation of the flange material5 Specifications in parentheses are non-standardmade-to-order
Converter
Wafer type
Maximum Operating PressureFlange rating JIS10K JIS16K JIS20K JIS30K ASMEJPI150 ASMEJPI300
Max operating pressure (MPa) 118 196 245 451 127 335
2
GBD110E-6OVAL VORTEX FLOWMETER
Gas Purge Type Meter Body (for measurement of gas containing dust and mist)Item Description
Body style Wafer FlangeNominal size (mm) 50 80 100 150 200 250 300 (350) 400 (450) 500
MaterialBody SUS304 STPG370 SUS304TP STPY400 SUS304TPFlanges mdash SS400 or SFVC2A SUSF304 SFVC2A SUSF304Bluff body SUS304 SCS13A or SUS304
Flange rating Companion flangeJIS10K ASMEJPI150 JIS10K ASMEJPI150
Standard connecting pipe Sch40 Sch20Operating temp range minus20 to +130 0 to +130 minus20 to +130 0 to +130 minus20 to +130Max operating pressure Less than 1MPaAccuracy Within plusmn1 of RD or plusmn1 of FSRepeatability Within plusmn02Installation Horizontal or verticalPurge gas Instrumentation air nitrogen or the same gas as the metered fluidPurge rate 05Lmin to 10Lmin at 196 to 294kPaPurge connection Rc14 fitting provided
ConverterItem Description
Model PA21 converterConfiguration Separately mountedPower source 24 to 32VDCPower consumption 32V 40mA or less (24V 54mA or less) (1)Ambienttemperature
Non-explosionproof minus20 to +60 (no condensation)Explosionproof minus20 to +55 (no condensation)
Finish Body Munsell 10B84 Cover Munsell 25PB410IP rating IP67
Transmissionlength
Sensor to converter Exclusive 5-wire cable Max 30m (Finished cable OD 107 plusmn 05mm)
Converter toreceiving instrument
For pulse output 3-wire shielded cable max 1km (See NOTE)For pulse and status output 4-wire shielded cable max 1km (See NOTE)
CEVS CVVS equivalent (Finished cable OD 101 to 13mm)
Output signal
① Pulse output Open drain (equivalent to open collector)Max applied voltage 30VDC Allowable current 50mA
Unfactored pulsePulse width 02msec or 1msec
② Status output Open drain (equivalent to open collector)Max applied voltage 30VDC Allowable current 50mA
Select from Error Error+Alarm HL alarm Error+HL alarmExplosionproofconfiguration
Converter Ex d e ⅡC T6Sensor Amplifier part Ex d [ib] ⅡC T4 Sensor part Ex ib ⅡC T4 Applicable temp range -20 to +72
Cable connectionConverter G34 (internal thread)
Sensor G12 (internal thread)Explosionproof model Union clamp of the accompanying pressure-tight packing G34 (internal thread)
Installation Mounted on 2 pipe stanchion (clamp and U-bolts furnished)
DisplayLCD display
flow rate error alarm NOTE If the wire length exceeds 250m or the cable of less than 125mm2 is used the resistance of the cable connecting the receiving instrument and the converter must satisfy the following conditions considering voltage drop① Low level of pulse output must satisfy the input condition of the receiving instrument Low level of pulse output = (If+2Ip+Is) R+05② Voltage between POWER and COMMON of the converter is within the rated voltage Converter voltage (between POWER and COMMON) = Vminus(2If+Ip+Is) RWhere
Ip Maximum current of pulse output in actual use V Supply voltageIs Maximum current of status output in actual use If Maximum current consumption of the flowmeterR Cable resistance between receiving instrument and converter
(1) To use the power supply other than manufactured by OVAL make sure its voltage capacity is 100mA or more considering the current when the power supply is turned ON
Explosionproof applied temperature range (for explosionproof models) Explosionproof applied temperature range of the instrument is -20 to +72 at the part indicated below To satisfy the requirements make sure to use the instrument within the suggested range of fluid and ambient temperature shown below
60
4050
302010
0minus10minus20minus30
minus30 minus10 10 30 50 70 90 110 130Fluid temperature ()
Ambient temperature deratingThe part subject to explosionproof
Ambi
ent t
empe
ratu
re (
)
NOTE Applicable ambient temperature range may vary with the lagging condition of the piping
3
GBD110E-6OVAL VORTEX FLOWMETER
FLOW RANGESThe OVAL VORTEX FLOWMETER measures actual flow rate (m3h[actual]) under pressure If flow rate information is given under the standard conditions (0degC 1 atmospheric pressure) (m3h[normal]) it must be converted into an actual flow rate before you refer to the flow range table below
Nom sizemm
Sp weight kgm3
AccuracyMinimum flow rate m3h [actual] Max Flow rate
m3h05 08 1 12 3 5 7 10 20 40 6020
(34Prime)plusmn1 of reading mdash mdash mdash mdash 342 206 147 103 059 042 034
125plusmn1 of full scale mdash mdash mdash mdash 205 123 099 083 059 042 034
25(1Prime)
plusmn1 of reading mdash mdash mdash mdash 435 261 187 134 095 067 055255
plusmn1 of full scale mdash mdash mdash mdash 261 189 16 134 095 067 05532
(114Prime)plusmn1 of reading mdash mdash 171 142 568 341 272 228 161 114 093
565plusmn1 of full scale mdash mdash 102 85 416 322 272 228 161 114 093
40(112Prime)
plusmn1 of reading mdash 495 396 33 166 14 125 111 878 697 60987
plusmn1 of full scale mdash 148 119 987 56 434 367 307 217 154 12650
(2Prime)plusmn1 of reading 102 633 507 422 223 188 168 149 119 938 819
185plusmn1 of full scale 303 19 159 145 916 71 6 502 355 251 205
80(3Prime)
plusmn1 of reading 151 938 751 626 416 351 314 279 221 176 154530
plusmn1 of full scale 493 39 349 318 202 156 132 111 779 551 45100(4Prime)
plusmn1 of reading 197 123 983 819 561 473 423 375 298 237 207900
plusmn1 of full scale 588 423 378 345 219 169 143 12 845 68 68150(6Prime)
plusmn1 of reading 291 182 146 131 962 812 725 644 511 406 3552100
plusmn1 of full scale 117 921 824 752 476 369 312 261 22 22 22200(8Prime)
plusmn1 of reading 385 241 204 192 142 120 107 945 75 596 523400
plusmn1 of full scale 205 162 145 132 834 646 546 51 51 51 51250
(10Prime)plusmn1 of reading 479 299 275 258 191 161 144 128 101 98 98
5200plusmn1 of full scale 317 251 224 205 130 101 98 98 98 98 98
300(12Prime)
plusmn1 of reading 573 377 350 329 243 205 183 168 168 168 1687500
plusmn1 of full scale 454 359 321 293 186 168 168 168 168 168 168400
(16Prime)plusmn1 of reading 779 616 551 503 378 378 378 378 378 378 378
12000plusmn1 of full scale 779 616 551 503 378 378 378 378 378 378 378
500(20Prime)
plusmn1 of reading 1230 966 864 789 741 741 741 741 741 741 74119000
plusmn1 of full scale 1230 966 864 789 741 741 741 741 741 741 741Type of Gas Sp weight kgNm3 Pressure of Gas MPa (gauge) Temperature 20degC
Acetylene 1175 mdash mdash mdash 0 0176 0361 0547 0824 175 360 545Argon 1785 mdash mdash mdash 0 0081 0203 0325 0508 112 234 355Carbon Monoxide 1250 mdash mdash mdash 0 0160 0334 0508 0726 164 338 512Ethane 1357 mdash mdash mdash 0 0139 0299 0460 0700 150 310 471Ethylene 1264 mdash mdash mdash 0 0157 0329 0501 0759 162 334 506Air 1293 mdash mdash mdash 0 0151 0319 0487 0740 158 326 494Oxygen 1429 mdash mdash mdash 0 0121 0279 0431 0660 142 294 446Hydrogen 00899 0503 0866 111 135 353 595 mdash mdash mdash mdash mdashCarbon Dioxide 1977 mdash mdash mdash mdash 0064 0174 0284 0449 100 210 320Nitrogen 1251 mdash mdash mdash 0 0159 0333 0507 0768 164 338 511City Gas 0802 mdash 0 0034 0061 0305 0577 0848 125 261 532 mdashNatural Gas 0828 mdash mdash 0030 0056 0293 0555 0818 121 253 515 778Propane 2020 mdash mdash mdash mdash 0060 0168 0276 0437 0975 205 313Butane 2703 mdash mdash mdash mdash 0019 0100 0180 0301 0703 151 231Methane 0717 mdash mdash 0050 0081 0354 0657 0960 142 293 597 mdash
NOTES 1 Flow ranges listed in above table is calculated based on temperature 20 and viscosity 0017mPabulls 2 If it is necessary to determine the minimum flow rate precisely contact OVAL
How to Determine Minimum Flow RateExample 1 A 200mm (8Prime) size meter is to be used for air having a pressure of 074MPa [gauge] at 20 Find the minimum flow rate [Solution] Finding the minimum flow rate for nominal size 200mm (8Prime) in Table A corresponding to 074MPa [gauge] air in Table B we obtain where accuracy is plusmn1 of reading 945m3h where accuracy is plusmn1 of full scale 51m3h
Example 2 A 250mm (10Prime) size meter is to be used for city gas having a pressure of 05MPa [gauge] at 20 with an accuracy of plusmn1 of reading Find the minimum flow rate [Solution] Finding the minimum flow rate for nominal size 250mm (10Prime ) in Table A corresponding to 0305MPa [gauge] and 0577MPa [gauge] of city gas in Table B are 191m3h and 161m3h respectively Hence at 05MPa [gauge] we obtain from the rule of proportion
0577 minus 05 Qmin= 161 + times (191minus161)≒ 170m3h 0577 minus 0305
Example 3 A 200mm (8Prime) size meter is to be used for butane gas having a pressure of 0301MPa [gauge] at 80degC with an accuracy of 1 of reading Find the minimum flow rate [Solution] Although the minimum flow rate in Table A corresponding to 0301MPa [gauge] is 945m3h the minimum flow rate should increase by the amount of decrease in specific weight due to elevated temperature (80) as follows
0101325 + 030 27315 Sp weight of butane at 80 = 2703 times times =83kgm3
0101325 27315 + 80
The minimum flow rates for the nominal size 200mm (8) corresponding to specific weights 7kgm3 and 10kgm3 in Table A are 107m3h and 945m3h respectively Hence the minimum flow rate of butane at 80 (sp weight 83kgm3) can be obtained from the rule of proportion
10 minus 83 Qmin= 945 + times (107 minus 945)≒ 102m3h 10 minus 7
Tabl
e A
Tabl
e B
Find
the
valu
e cl
oses
t to
the
pres
sure
of g
asto
be
used
(low
er v
alue
) in
Tabl
e B
and
dete
rmin
e th
e m
inim
um fl
ow ra
te in
Tab
le A
4
GBD110E-6OVAL VORTEX FLOWMETER
PERFORMANCE CHARACTERISTICS
Meter FactorsThe table below shows the nominal meter factor by each nominal size and pulse frequency at maximum flow rate
Nominal Sizemm (inch)
Nominal Meter FactorLP
Pulse Freq atMax Flow rate
Hz
Max Flow ratem3h
20 (34) 0008438 4115 125 25 (1) 001733 4087 255
32 (114) 003852 4074 565 50 (2) 01260 4078 185 80 (3) 04197 3508 530100 (4) 09432 2651 900150 (6) 3033 1923 2100200 (8) 7032 1343 3400
250 (10) 1357 1064 5200 300 (12) 2326 8957 7500 400 (16) 5238 6364 12000 500 (20) 1028 5134 19000
20 30 50 100 300 500 103 1043times103
5times103Flow rate Qm3h [actual] Flow rate Qm3h [actual]
50
10
1008060504030
20
1086543
2
1
5
1
05
011 5 10 50 100
Nominal size 20mm(frac34Prime)
Nominal size 50mm(2Prime)
80mm(3Prime)
100mm(4Prime)
150mm(6Prime)
200mm(8Prime)
250mm(10Prime)
300mm(12Prime)
400mm(16Prime)
500mm(20Prime)
25mm(1Prime)
32mm(1frac14Prime)
Pres
los
s C
oeff
[C]
Pres
los
s C
oeff
[C]
Pressure Loss
Nominal sizes 20 to 32mm Nominal sizes 50 to 500mm
C times γΔP= 100ΔP Pressure loss (kPa) γ Sp weight (kgm3)To find the pressure loss read the coefficient C at the intersection of the flow rate Q and the diagonal line of the particular size and determine ΔP by the equation above
5
GBD110E-6OVAL VORTEX FLOWMETER
OUTLINE DIMENSIONS (Standard type) (Unit in mm)
StyleNominal size mm
(inch)Flange rating L H d D
Approx Weightkg
Wafertype
20 (34)Companion Flange
JIS 10 KJIS 20 KJIS 30 K
ASMEJPI 150ASMEJPI 300
80 375 214 120 10425 (1) 80 353 272 70 59
32 (1 14) 80 351 355 70 6450 (2) 80 359 527 92 7380 (3) 80 375 781 127 105
100 (4) 86 391 1023 1572 124150 (6) 108 428 151 2159 218
Flangetype
200 (8)
JIS 10 K
350 472 200
330 61JIS 20 K 350 75JIS 30 K 370 90
ASMEJPI 150 343 71ASMEJPI 300 381 95
250 (10)
JIS 10 K
450 505 249
400 101JIS 20 K 430 126JIS 30 K 450 152
ASMEJPI 150 406 111ASMEJPI 300 445 147
300 (12)
JIS 10 K
500 545 298
445 141JIS 20 K 480 169JIS 30 K 515 214
ASMEJPI 150 483 166ASMEJPI 300 520 217
400 (16)JIS 10 K
600 595 3906560 241
ASMEJPI 150 595 366
500 (20)JIS 10 K
650 655 489675 431
ASMEJPI 150 700 591
L
φD
L
φd
φD
H
6060 85 53
φ10
3
6060 85 53
φ10
3
H
6060 5385
φ10
3
H
Lφd
Conduit Connection G12 Conduit Connection G12
Conduit Connection G12
φd
φD
Wafer type 20mm (34Prime)
Dimensions D and H depend on the connecting flange rating
Wafer type 25mm (1Prime) to 150mm (6Prime)
Flange type 200mm (8Prime) to 500mm (20Prime)
NOTE Outline dimensions of special or regulation-compliant products may be different Please refer to the approval drawing or delivery specification
6
GBD110E-6OVAL VORTEX FLOWMETER
OUTLINE DIMENSIONS (Gas purge type) (Unit in mm)
Style Nominal size mm (inch) Flange rating L H d D Approx Weight
kg
Wafertype
50 (2)Companion Flange
JIS 10 KASMEJPI 150
80 359 527 92 7380 (3) 80 375 781 127 105
100 (4) 86 391 1023 1572 124150 (6) 108 428 151 2159 218
Flangetype
200 (8)JIS 10 K
350 472 200330 61
ASMEJPI 150 343 71
250 (10)JIS 10 K
450 505 249400 101
ASMEJPI 150 406 111
300 (12)JIS 10 K
500 545 298445 141
ASMEJPI 150 483 166
400 (16)JIS 10 K
600 595 3906560 241
ASMEJPI 150 595 366
500 (20)JIS 10 K
650 655 489675 431
ASMEJPI 150 700 591
Purge gas Connection
Purge gas Connection
60 85 5360
H
φd
L
φ10
3φ
D
H
φD φd
φ10
3
60 60 85
L
53Conduit Connection G12
Conduit Connection G12
Wafer type 50mm (2Prime) to 150mm (6Prime) Flange type 200mm (8Prime) to 500mm (20Prime)
NOTE Outline dimensions of special or regulation-compliant products may be different Please refer to the approval drawing or delivery specification
Purge Box (FB0 )12 Unit in mm
570
492
Mist Separator
Purge Inlet Purge Outlet (to Flowmeter)
Pipe
Enclosure Sheet steel
Finish Light beige (5Y71)
Approx weight 4 kg
Reducing ValveRotameter
210
7
GBD110E-6OVAL VORTEX FLOWMETER
Converter (PA21)
309233
617 1715
120 110100
φ13
4
67
Conduit Connection G34 Conduit Connection G34
30 125
71
41
7411
4
WIRING DIAGRAM
(1) Wiring for converter power source and output
Do not use this conduit connection
Terminal Cover for Maintenance
Terminal label and descriptionLabel Description Remark
POWER 24 to 32VDC DC power 24 to 32VDC
Open drain output (equivalent of open collector output) can be connected up to 30V 50mA
STATUS Status output (open drain)
PULSE Pulse output (open drain)
COMMONDC power (0V)Status output (minus)Pulse output (minus)
EARTH Grounding
Do not use the conduit connection on the terminal cover side For wiring connection specification refer to general specifications Converter on Page 2
Unit in mm
8
GBD110E-6OVAL VORTEX FLOWMETER
CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
For details of individual receiving instruments refer to respective general specification sheets1 A digital filter (SU1301) cannot be connected (The converter is equipped with the equivalent function)2 Separate power source is required when connecting with the totalizer (EL0122)
OVAL MODEL EL4000
Line temperature and pressure are considered approximately constant and correction factor can be multiplied as constant
Line temperature and pressure are automatically compensated and total and instantaneous flow readout (or output) are obtained
Meter body
Meter body
Converter
Converter
Pulse Distributor(SU1508)
orExternal Power Source
Flow Computer(EL4001 series)
4 to 20mADC
Unfactored Pulse
Factored Pulse
Totalizer(EL0122)
Total and Instantaneous Flow rate Readout
PressureTransmitter
ResistanceThermometer
(2)
(2) Wiring between converter and sensor
Converter (PA21)
Sensor terminal box
SIG0VSUPC1C2
SHIELD
SHIE
LDC
2 C1
SUP
0V SIG
Sensor terminal box must be installed using intrinsically safe installation procedure
Terminal label and connecting cable colorConverter terminals Terminals inside sensor terminal box Connecting cable color
SIG SIG White0V 0V Black
SUP SUP RedC1 C1 GreenC2 C2 Yellow
SHIELD SHIELD Twist [RedBlackWhite] [YellowGreen] and shielded cables together and cover the bundle with the accompanying tube then connect to SHIELD terminal
Exclusive cable must be used for connecting the converter and the sensor Either the left or right conduit connection (cable entry) of the sensor terminal box can be used For wiring connection specification refer to general specifications Converter on Page 2
9
GBD110E-6OVAL VORTEX FLOWMETER
INSTALLATION CONDITIONS1 Typical Piping InstructionsIt is required that the flow pattern of the fluid flowing in and out of a vortex flowmeter be as uniform as possible for accurate metering performance Therefore proper flow straightening measures have to be applied when installing a vortex flowmeter The standard piping instructions are shown in the following table
(1) Use an OVAL flow straightener or provide a specified straight pipe (ISO-5167 compliant)
No Piping Arrangement Straight PipeLength (L) Remark
1 OVALs Flow-Straightener
8D Refer to P11
Applicable to Nominal size 25mm or above
12D Refer to GSGCF001
2 Reducer 15D Min A concentric reducer is installed at the upstream of a meter
3 Elbow
23D Min An elbow is installed at the upstream of a meter
25D Min Two elbows are installed at the upstream of a meter
40D Min Two elbows are vertically installed at the upstream of a meter
4 Fully opengate valve 15D Min A full-open gate valve is installed at the upstream of a
meter
5 Partially opengate valve 50D Min A partially open gate valve sharp orifice or something that
markedly disturbs the flow pattern is upstream of meter
Honey VanebullLFlow
L
Flow
Flow
L
L
Flow Straightener
Flow
L
Flow
L
Flow
L
Flow
L
Flow
L
Fully Open
PartiallyOpen
NOTES1 Upstream and downstream pipes adjacent to the flowmeter should be of the same internal
diameter (ID) as the flowmeter (The exclusive flow straightener Honey Vane L and downstream short pipe have the same ID as the flowmeter) The table below shows the standard ID of the flowmeter Confirm the delivery specification in case ID is non-standard
Flowmeter standard IDNominal size ID referenceunder 400mm Sch40
400mm or more Sch20
2 A short pipe section 5D or longer shall be provided downstream of the meter3 For pressure detection provide the probe downstream of the flowmeter (see the right figure)
To avoid disturbances in the flow temperature detection should be made downstream of the flowmeter and at the same time upstream of the control valve
2 Pressure PulsationIn case the flowmeter is installed in the line where instruments that can generate pressure pulsation such as roots blower or compressor is present performance of the flowmeter can be affected by flow pulsation Allowable pulsation pressure is calculated from the following equationNlt 22ρV2 (Pa)where N Pulsation pressure (Pa) ρ Density (kgm3) V Min Velocity (ms)
Even at shutdown pressure pulsation in the process fluid can produce a false output If pressure pulsation is excessive take the following measures① Locate the source of flow pulsation downstream of the flowmeter② Install a pulsation attenuator③ At shutdown of the flow shut off valves upstream and downstream of the flowmeter
2 to 7Dfrom the meter
FLOW
D Nominal size
Pressure detection point
Temperature detection point
Min 1D from pressure detection pointMin 2D from flowmeter
10
GBD110E-6OVAL VORTEX FLOWMETER
FLOW
Honey Vane S
Flowmeter
Min 8D
Honey Vane Outline Dimensions
Nominal size(mm)
Honey Vane S Honey Vane LφD (mm) t (mm) L (mm)
25 75 35 20040 90 54 32050 105 69 40080 134 102 640
100 159 133 800150 220 196 1200200 268 26 1600250 331 323 2000300 376 387 2400
Dimensions for JIS 10K
L
t
φD
t
Honey Vane S Honey Vane L
Installation of Honey Vane S ① Locate the Honey Vane S upstream of the flowmeter ② Provide a short pipe (8D or longer) between Honey Vane S and flowmeter ③ Regarding the bolts and nuts used for connecting JPI flange adopt unified screw threads If it is necessary to use metric screw threads contact OVAL
11
GBD110E-6OVAL VORTEX FLOWMETER
PRECAUTIONS ON USE1 This flowmeter is developed designed and manufactured to be used as a flowmeter for general industrial application
Therefore when it is used for the application where its operation is directly related to the safety of the relevant system or the product is important in the facilities (such as process control and custody transfer) you are requested to ensure sufficient security including safety design redundancy and duplication of the process and implementation of periodic inspection Do not use this flowmeter where its operation and performance directly affect human life
2 When used under appropriate conditions this flowmeter can demonstrate its stable performance without aging degradation of accuracy However malfunction or failure may occur due to various factors Thus examining the operating conditions operating status and importance in the process you should consider periodic maintenance of your flowmeter In order to secure long-term and safe use OVAL recommends the customer to verify the soundness of the flowmeter through periodic inspection every two years For the details of inspection contact the nearest OVAL salesservice office or representatives
3 This flowmeter is manufactured adjusted and inspected to meet the conditions of use The fluid measured flow range pressure temperature etc must be applied under the specified conditions The conditions for use are stated on the nameplate attached on the flowmeter transmitter and specification sheet supplied with the product
4 The materials used in this flowmeter are stated in this document or delivery specification sheet shipped with the equipment Supplied with all the necessary information by the customer OVAL has selected materials that best suit the customer requirements including corrosion resistance However we ask you to understand that the final judgment on the compatibility of the materials in the actual process environment lies with the customer
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
2
GBD110E-6OVAL VORTEX FLOWMETER
Gas Purge Type Meter Body (for measurement of gas containing dust and mist)Item Description
Body style Wafer FlangeNominal size (mm) 50 80 100 150 200 250 300 (350) 400 (450) 500
MaterialBody SUS304 STPG370 SUS304TP STPY400 SUS304TPFlanges mdash SS400 or SFVC2A SUSF304 SFVC2A SUSF304Bluff body SUS304 SCS13A or SUS304
Flange rating Companion flangeJIS10K ASMEJPI150 JIS10K ASMEJPI150
Standard connecting pipe Sch40 Sch20Operating temp range minus20 to +130 0 to +130 minus20 to +130 0 to +130 minus20 to +130Max operating pressure Less than 1MPaAccuracy Within plusmn1 of RD or plusmn1 of FSRepeatability Within plusmn02Installation Horizontal or verticalPurge gas Instrumentation air nitrogen or the same gas as the metered fluidPurge rate 05Lmin to 10Lmin at 196 to 294kPaPurge connection Rc14 fitting provided
ConverterItem Description
Model PA21 converterConfiguration Separately mountedPower source 24 to 32VDCPower consumption 32V 40mA or less (24V 54mA or less) (1)Ambienttemperature
Non-explosionproof minus20 to +60 (no condensation)Explosionproof minus20 to +55 (no condensation)
Finish Body Munsell 10B84 Cover Munsell 25PB410IP rating IP67
Transmissionlength
Sensor to converter Exclusive 5-wire cable Max 30m (Finished cable OD 107 plusmn 05mm)
Converter toreceiving instrument
For pulse output 3-wire shielded cable max 1km (See NOTE)For pulse and status output 4-wire shielded cable max 1km (See NOTE)
CEVS CVVS equivalent (Finished cable OD 101 to 13mm)
Output signal
① Pulse output Open drain (equivalent to open collector)Max applied voltage 30VDC Allowable current 50mA
Unfactored pulsePulse width 02msec or 1msec
② Status output Open drain (equivalent to open collector)Max applied voltage 30VDC Allowable current 50mA
Select from Error Error+Alarm HL alarm Error+HL alarmExplosionproofconfiguration
Converter Ex d e ⅡC T6Sensor Amplifier part Ex d [ib] ⅡC T4 Sensor part Ex ib ⅡC T4 Applicable temp range -20 to +72
Cable connectionConverter G34 (internal thread)
Sensor G12 (internal thread)Explosionproof model Union clamp of the accompanying pressure-tight packing G34 (internal thread)
Installation Mounted on 2 pipe stanchion (clamp and U-bolts furnished)
DisplayLCD display
flow rate error alarm NOTE If the wire length exceeds 250m or the cable of less than 125mm2 is used the resistance of the cable connecting the receiving instrument and the converter must satisfy the following conditions considering voltage drop① Low level of pulse output must satisfy the input condition of the receiving instrument Low level of pulse output = (If+2Ip+Is) R+05② Voltage between POWER and COMMON of the converter is within the rated voltage Converter voltage (between POWER and COMMON) = Vminus(2If+Ip+Is) RWhere
Ip Maximum current of pulse output in actual use V Supply voltageIs Maximum current of status output in actual use If Maximum current consumption of the flowmeterR Cable resistance between receiving instrument and converter
(1) To use the power supply other than manufactured by OVAL make sure its voltage capacity is 100mA or more considering the current when the power supply is turned ON
Explosionproof applied temperature range (for explosionproof models) Explosionproof applied temperature range of the instrument is -20 to +72 at the part indicated below To satisfy the requirements make sure to use the instrument within the suggested range of fluid and ambient temperature shown below
60
4050
302010
0minus10minus20minus30
minus30 minus10 10 30 50 70 90 110 130Fluid temperature ()
Ambient temperature deratingThe part subject to explosionproof
Ambi
ent t
empe
ratu
re (
)
NOTE Applicable ambient temperature range may vary with the lagging condition of the piping
3
GBD110E-6OVAL VORTEX FLOWMETER
FLOW RANGESThe OVAL VORTEX FLOWMETER measures actual flow rate (m3h[actual]) under pressure If flow rate information is given under the standard conditions (0degC 1 atmospheric pressure) (m3h[normal]) it must be converted into an actual flow rate before you refer to the flow range table below
Nom sizemm
Sp weight kgm3
AccuracyMinimum flow rate m3h [actual] Max Flow rate
m3h05 08 1 12 3 5 7 10 20 40 6020
(34Prime)plusmn1 of reading mdash mdash mdash mdash 342 206 147 103 059 042 034
125plusmn1 of full scale mdash mdash mdash mdash 205 123 099 083 059 042 034
25(1Prime)
plusmn1 of reading mdash mdash mdash mdash 435 261 187 134 095 067 055255
plusmn1 of full scale mdash mdash mdash mdash 261 189 16 134 095 067 05532
(114Prime)plusmn1 of reading mdash mdash 171 142 568 341 272 228 161 114 093
565plusmn1 of full scale mdash mdash 102 85 416 322 272 228 161 114 093
40(112Prime)
plusmn1 of reading mdash 495 396 33 166 14 125 111 878 697 60987
plusmn1 of full scale mdash 148 119 987 56 434 367 307 217 154 12650
(2Prime)plusmn1 of reading 102 633 507 422 223 188 168 149 119 938 819
185plusmn1 of full scale 303 19 159 145 916 71 6 502 355 251 205
80(3Prime)
plusmn1 of reading 151 938 751 626 416 351 314 279 221 176 154530
plusmn1 of full scale 493 39 349 318 202 156 132 111 779 551 45100(4Prime)
plusmn1 of reading 197 123 983 819 561 473 423 375 298 237 207900
plusmn1 of full scale 588 423 378 345 219 169 143 12 845 68 68150(6Prime)
plusmn1 of reading 291 182 146 131 962 812 725 644 511 406 3552100
plusmn1 of full scale 117 921 824 752 476 369 312 261 22 22 22200(8Prime)
plusmn1 of reading 385 241 204 192 142 120 107 945 75 596 523400
plusmn1 of full scale 205 162 145 132 834 646 546 51 51 51 51250
(10Prime)plusmn1 of reading 479 299 275 258 191 161 144 128 101 98 98
5200plusmn1 of full scale 317 251 224 205 130 101 98 98 98 98 98
300(12Prime)
plusmn1 of reading 573 377 350 329 243 205 183 168 168 168 1687500
plusmn1 of full scale 454 359 321 293 186 168 168 168 168 168 168400
(16Prime)plusmn1 of reading 779 616 551 503 378 378 378 378 378 378 378
12000plusmn1 of full scale 779 616 551 503 378 378 378 378 378 378 378
500(20Prime)
plusmn1 of reading 1230 966 864 789 741 741 741 741 741 741 74119000
plusmn1 of full scale 1230 966 864 789 741 741 741 741 741 741 741Type of Gas Sp weight kgNm3 Pressure of Gas MPa (gauge) Temperature 20degC
Acetylene 1175 mdash mdash mdash 0 0176 0361 0547 0824 175 360 545Argon 1785 mdash mdash mdash 0 0081 0203 0325 0508 112 234 355Carbon Monoxide 1250 mdash mdash mdash 0 0160 0334 0508 0726 164 338 512Ethane 1357 mdash mdash mdash 0 0139 0299 0460 0700 150 310 471Ethylene 1264 mdash mdash mdash 0 0157 0329 0501 0759 162 334 506Air 1293 mdash mdash mdash 0 0151 0319 0487 0740 158 326 494Oxygen 1429 mdash mdash mdash 0 0121 0279 0431 0660 142 294 446Hydrogen 00899 0503 0866 111 135 353 595 mdash mdash mdash mdash mdashCarbon Dioxide 1977 mdash mdash mdash mdash 0064 0174 0284 0449 100 210 320Nitrogen 1251 mdash mdash mdash 0 0159 0333 0507 0768 164 338 511City Gas 0802 mdash 0 0034 0061 0305 0577 0848 125 261 532 mdashNatural Gas 0828 mdash mdash 0030 0056 0293 0555 0818 121 253 515 778Propane 2020 mdash mdash mdash mdash 0060 0168 0276 0437 0975 205 313Butane 2703 mdash mdash mdash mdash 0019 0100 0180 0301 0703 151 231Methane 0717 mdash mdash 0050 0081 0354 0657 0960 142 293 597 mdash
NOTES 1 Flow ranges listed in above table is calculated based on temperature 20 and viscosity 0017mPabulls 2 If it is necessary to determine the minimum flow rate precisely contact OVAL
How to Determine Minimum Flow RateExample 1 A 200mm (8Prime) size meter is to be used for air having a pressure of 074MPa [gauge] at 20 Find the minimum flow rate [Solution] Finding the minimum flow rate for nominal size 200mm (8Prime) in Table A corresponding to 074MPa [gauge] air in Table B we obtain where accuracy is plusmn1 of reading 945m3h where accuracy is plusmn1 of full scale 51m3h
Example 2 A 250mm (10Prime) size meter is to be used for city gas having a pressure of 05MPa [gauge] at 20 with an accuracy of plusmn1 of reading Find the minimum flow rate [Solution] Finding the minimum flow rate for nominal size 250mm (10Prime ) in Table A corresponding to 0305MPa [gauge] and 0577MPa [gauge] of city gas in Table B are 191m3h and 161m3h respectively Hence at 05MPa [gauge] we obtain from the rule of proportion
0577 minus 05 Qmin= 161 + times (191minus161)≒ 170m3h 0577 minus 0305
Example 3 A 200mm (8Prime) size meter is to be used for butane gas having a pressure of 0301MPa [gauge] at 80degC with an accuracy of 1 of reading Find the minimum flow rate [Solution] Although the minimum flow rate in Table A corresponding to 0301MPa [gauge] is 945m3h the minimum flow rate should increase by the amount of decrease in specific weight due to elevated temperature (80) as follows
0101325 + 030 27315 Sp weight of butane at 80 = 2703 times times =83kgm3
0101325 27315 + 80
The minimum flow rates for the nominal size 200mm (8) corresponding to specific weights 7kgm3 and 10kgm3 in Table A are 107m3h and 945m3h respectively Hence the minimum flow rate of butane at 80 (sp weight 83kgm3) can be obtained from the rule of proportion
10 minus 83 Qmin= 945 + times (107 minus 945)≒ 102m3h 10 minus 7
Tabl
e A
Tabl
e B
Find
the
valu
e cl
oses
t to
the
pres
sure
of g
asto
be
used
(low
er v
alue
) in
Tabl
e B
and
dete
rmin
e th
e m
inim
um fl
ow ra
te in
Tab
le A
4
GBD110E-6OVAL VORTEX FLOWMETER
PERFORMANCE CHARACTERISTICS
Meter FactorsThe table below shows the nominal meter factor by each nominal size and pulse frequency at maximum flow rate
Nominal Sizemm (inch)
Nominal Meter FactorLP
Pulse Freq atMax Flow rate
Hz
Max Flow ratem3h
20 (34) 0008438 4115 125 25 (1) 001733 4087 255
32 (114) 003852 4074 565 50 (2) 01260 4078 185 80 (3) 04197 3508 530100 (4) 09432 2651 900150 (6) 3033 1923 2100200 (8) 7032 1343 3400
250 (10) 1357 1064 5200 300 (12) 2326 8957 7500 400 (16) 5238 6364 12000 500 (20) 1028 5134 19000
20 30 50 100 300 500 103 1043times103
5times103Flow rate Qm3h [actual] Flow rate Qm3h [actual]
50
10
1008060504030
20
1086543
2
1
5
1
05
011 5 10 50 100
Nominal size 20mm(frac34Prime)
Nominal size 50mm(2Prime)
80mm(3Prime)
100mm(4Prime)
150mm(6Prime)
200mm(8Prime)
250mm(10Prime)
300mm(12Prime)
400mm(16Prime)
500mm(20Prime)
25mm(1Prime)
32mm(1frac14Prime)
Pres
los
s C
oeff
[C]
Pres
los
s C
oeff
[C]
Pressure Loss
Nominal sizes 20 to 32mm Nominal sizes 50 to 500mm
C times γΔP= 100ΔP Pressure loss (kPa) γ Sp weight (kgm3)To find the pressure loss read the coefficient C at the intersection of the flow rate Q and the diagonal line of the particular size and determine ΔP by the equation above
5
GBD110E-6OVAL VORTEX FLOWMETER
OUTLINE DIMENSIONS (Standard type) (Unit in mm)
StyleNominal size mm
(inch)Flange rating L H d D
Approx Weightkg
Wafertype
20 (34)Companion Flange
JIS 10 KJIS 20 KJIS 30 K
ASMEJPI 150ASMEJPI 300
80 375 214 120 10425 (1) 80 353 272 70 59
32 (1 14) 80 351 355 70 6450 (2) 80 359 527 92 7380 (3) 80 375 781 127 105
100 (4) 86 391 1023 1572 124150 (6) 108 428 151 2159 218
Flangetype
200 (8)
JIS 10 K
350 472 200
330 61JIS 20 K 350 75JIS 30 K 370 90
ASMEJPI 150 343 71ASMEJPI 300 381 95
250 (10)
JIS 10 K
450 505 249
400 101JIS 20 K 430 126JIS 30 K 450 152
ASMEJPI 150 406 111ASMEJPI 300 445 147
300 (12)
JIS 10 K
500 545 298
445 141JIS 20 K 480 169JIS 30 K 515 214
ASMEJPI 150 483 166ASMEJPI 300 520 217
400 (16)JIS 10 K
600 595 3906560 241
ASMEJPI 150 595 366
500 (20)JIS 10 K
650 655 489675 431
ASMEJPI 150 700 591
L
φD
L
φd
φD
H
6060 85 53
φ10
3
6060 85 53
φ10
3
H
6060 5385
φ10
3
H
Lφd
Conduit Connection G12 Conduit Connection G12
Conduit Connection G12
φd
φD
Wafer type 20mm (34Prime)
Dimensions D and H depend on the connecting flange rating
Wafer type 25mm (1Prime) to 150mm (6Prime)
Flange type 200mm (8Prime) to 500mm (20Prime)
NOTE Outline dimensions of special or regulation-compliant products may be different Please refer to the approval drawing or delivery specification
6
GBD110E-6OVAL VORTEX FLOWMETER
OUTLINE DIMENSIONS (Gas purge type) (Unit in mm)
Style Nominal size mm (inch) Flange rating L H d D Approx Weight
kg
Wafertype
50 (2)Companion Flange
JIS 10 KASMEJPI 150
80 359 527 92 7380 (3) 80 375 781 127 105
100 (4) 86 391 1023 1572 124150 (6) 108 428 151 2159 218
Flangetype
200 (8)JIS 10 K
350 472 200330 61
ASMEJPI 150 343 71
250 (10)JIS 10 K
450 505 249400 101
ASMEJPI 150 406 111
300 (12)JIS 10 K
500 545 298445 141
ASMEJPI 150 483 166
400 (16)JIS 10 K
600 595 3906560 241
ASMEJPI 150 595 366
500 (20)JIS 10 K
650 655 489675 431
ASMEJPI 150 700 591
Purge gas Connection
Purge gas Connection
60 85 5360
H
φd
L
φ10
3φ
D
H
φD φd
φ10
3
60 60 85
L
53Conduit Connection G12
Conduit Connection G12
Wafer type 50mm (2Prime) to 150mm (6Prime) Flange type 200mm (8Prime) to 500mm (20Prime)
NOTE Outline dimensions of special or regulation-compliant products may be different Please refer to the approval drawing or delivery specification
Purge Box (FB0 )12 Unit in mm
570
492
Mist Separator
Purge Inlet Purge Outlet (to Flowmeter)
Pipe
Enclosure Sheet steel
Finish Light beige (5Y71)
Approx weight 4 kg
Reducing ValveRotameter
210
7
GBD110E-6OVAL VORTEX FLOWMETER
Converter (PA21)
309233
617 1715
120 110100
φ13
4
67
Conduit Connection G34 Conduit Connection G34
30 125
71
41
7411
4
WIRING DIAGRAM
(1) Wiring for converter power source and output
Do not use this conduit connection
Terminal Cover for Maintenance
Terminal label and descriptionLabel Description Remark
POWER 24 to 32VDC DC power 24 to 32VDC
Open drain output (equivalent of open collector output) can be connected up to 30V 50mA
STATUS Status output (open drain)
PULSE Pulse output (open drain)
COMMONDC power (0V)Status output (minus)Pulse output (minus)
EARTH Grounding
Do not use the conduit connection on the terminal cover side For wiring connection specification refer to general specifications Converter on Page 2
Unit in mm
8
GBD110E-6OVAL VORTEX FLOWMETER
CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
For details of individual receiving instruments refer to respective general specification sheets1 A digital filter (SU1301) cannot be connected (The converter is equipped with the equivalent function)2 Separate power source is required when connecting with the totalizer (EL0122)
OVAL MODEL EL4000
Line temperature and pressure are considered approximately constant and correction factor can be multiplied as constant
Line temperature and pressure are automatically compensated and total and instantaneous flow readout (or output) are obtained
Meter body
Meter body
Converter
Converter
Pulse Distributor(SU1508)
orExternal Power Source
Flow Computer(EL4001 series)
4 to 20mADC
Unfactored Pulse
Factored Pulse
Totalizer(EL0122)
Total and Instantaneous Flow rate Readout
PressureTransmitter
ResistanceThermometer
(2)
(2) Wiring between converter and sensor
Converter (PA21)
Sensor terminal box
SIG0VSUPC1C2
SHIELD
SHIE
LDC
2 C1
SUP
0V SIG
Sensor terminal box must be installed using intrinsically safe installation procedure
Terminal label and connecting cable colorConverter terminals Terminals inside sensor terminal box Connecting cable color
SIG SIG White0V 0V Black
SUP SUP RedC1 C1 GreenC2 C2 Yellow
SHIELD SHIELD Twist [RedBlackWhite] [YellowGreen] and shielded cables together and cover the bundle with the accompanying tube then connect to SHIELD terminal
Exclusive cable must be used for connecting the converter and the sensor Either the left or right conduit connection (cable entry) of the sensor terminal box can be used For wiring connection specification refer to general specifications Converter on Page 2
9
GBD110E-6OVAL VORTEX FLOWMETER
INSTALLATION CONDITIONS1 Typical Piping InstructionsIt is required that the flow pattern of the fluid flowing in and out of a vortex flowmeter be as uniform as possible for accurate metering performance Therefore proper flow straightening measures have to be applied when installing a vortex flowmeter The standard piping instructions are shown in the following table
(1) Use an OVAL flow straightener or provide a specified straight pipe (ISO-5167 compliant)
No Piping Arrangement Straight PipeLength (L) Remark
1 OVALs Flow-Straightener
8D Refer to P11
Applicable to Nominal size 25mm or above
12D Refer to GSGCF001
2 Reducer 15D Min A concentric reducer is installed at the upstream of a meter
3 Elbow
23D Min An elbow is installed at the upstream of a meter
25D Min Two elbows are installed at the upstream of a meter
40D Min Two elbows are vertically installed at the upstream of a meter
4 Fully opengate valve 15D Min A full-open gate valve is installed at the upstream of a
meter
5 Partially opengate valve 50D Min A partially open gate valve sharp orifice or something that
markedly disturbs the flow pattern is upstream of meter
Honey VanebullLFlow
L
Flow
Flow
L
L
Flow Straightener
Flow
L
Flow
L
Flow
L
Flow
L
Flow
L
Fully Open
PartiallyOpen
NOTES1 Upstream and downstream pipes adjacent to the flowmeter should be of the same internal
diameter (ID) as the flowmeter (The exclusive flow straightener Honey Vane L and downstream short pipe have the same ID as the flowmeter) The table below shows the standard ID of the flowmeter Confirm the delivery specification in case ID is non-standard
Flowmeter standard IDNominal size ID referenceunder 400mm Sch40
400mm or more Sch20
2 A short pipe section 5D or longer shall be provided downstream of the meter3 For pressure detection provide the probe downstream of the flowmeter (see the right figure)
To avoid disturbances in the flow temperature detection should be made downstream of the flowmeter and at the same time upstream of the control valve
2 Pressure PulsationIn case the flowmeter is installed in the line where instruments that can generate pressure pulsation such as roots blower or compressor is present performance of the flowmeter can be affected by flow pulsation Allowable pulsation pressure is calculated from the following equationNlt 22ρV2 (Pa)where N Pulsation pressure (Pa) ρ Density (kgm3) V Min Velocity (ms)
Even at shutdown pressure pulsation in the process fluid can produce a false output If pressure pulsation is excessive take the following measures① Locate the source of flow pulsation downstream of the flowmeter② Install a pulsation attenuator③ At shutdown of the flow shut off valves upstream and downstream of the flowmeter
2 to 7Dfrom the meter
FLOW
D Nominal size
Pressure detection point
Temperature detection point
Min 1D from pressure detection pointMin 2D from flowmeter
10
GBD110E-6OVAL VORTEX FLOWMETER
FLOW
Honey Vane S
Flowmeter
Min 8D
Honey Vane Outline Dimensions
Nominal size(mm)
Honey Vane S Honey Vane LφD (mm) t (mm) L (mm)
25 75 35 20040 90 54 32050 105 69 40080 134 102 640
100 159 133 800150 220 196 1200200 268 26 1600250 331 323 2000300 376 387 2400
Dimensions for JIS 10K
L
t
φD
t
Honey Vane S Honey Vane L
Installation of Honey Vane S ① Locate the Honey Vane S upstream of the flowmeter ② Provide a short pipe (8D or longer) between Honey Vane S and flowmeter ③ Regarding the bolts and nuts used for connecting JPI flange adopt unified screw threads If it is necessary to use metric screw threads contact OVAL
11
GBD110E-6OVAL VORTEX FLOWMETER
PRECAUTIONS ON USE1 This flowmeter is developed designed and manufactured to be used as a flowmeter for general industrial application
Therefore when it is used for the application where its operation is directly related to the safety of the relevant system or the product is important in the facilities (such as process control and custody transfer) you are requested to ensure sufficient security including safety design redundancy and duplication of the process and implementation of periodic inspection Do not use this flowmeter where its operation and performance directly affect human life
2 When used under appropriate conditions this flowmeter can demonstrate its stable performance without aging degradation of accuracy However malfunction or failure may occur due to various factors Thus examining the operating conditions operating status and importance in the process you should consider periodic maintenance of your flowmeter In order to secure long-term and safe use OVAL recommends the customer to verify the soundness of the flowmeter through periodic inspection every two years For the details of inspection contact the nearest OVAL salesservice office or representatives
3 This flowmeter is manufactured adjusted and inspected to meet the conditions of use The fluid measured flow range pressure temperature etc must be applied under the specified conditions The conditions for use are stated on the nameplate attached on the flowmeter transmitter and specification sheet supplied with the product
4 The materials used in this flowmeter are stated in this document or delivery specification sheet shipped with the equipment Supplied with all the necessary information by the customer OVAL has selected materials that best suit the customer requirements including corrosion resistance However we ask you to understand that the final judgment on the compatibility of the materials in the actual process environment lies with the customer
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
3
GBD110E-6OVAL VORTEX FLOWMETER
FLOW RANGESThe OVAL VORTEX FLOWMETER measures actual flow rate (m3h[actual]) under pressure If flow rate information is given under the standard conditions (0degC 1 atmospheric pressure) (m3h[normal]) it must be converted into an actual flow rate before you refer to the flow range table below
Nom sizemm
Sp weight kgm3
AccuracyMinimum flow rate m3h [actual] Max Flow rate
m3h05 08 1 12 3 5 7 10 20 40 6020
(34Prime)plusmn1 of reading mdash mdash mdash mdash 342 206 147 103 059 042 034
125plusmn1 of full scale mdash mdash mdash mdash 205 123 099 083 059 042 034
25(1Prime)
plusmn1 of reading mdash mdash mdash mdash 435 261 187 134 095 067 055255
plusmn1 of full scale mdash mdash mdash mdash 261 189 16 134 095 067 05532
(114Prime)plusmn1 of reading mdash mdash 171 142 568 341 272 228 161 114 093
565plusmn1 of full scale mdash mdash 102 85 416 322 272 228 161 114 093
40(112Prime)
plusmn1 of reading mdash 495 396 33 166 14 125 111 878 697 60987
plusmn1 of full scale mdash 148 119 987 56 434 367 307 217 154 12650
(2Prime)plusmn1 of reading 102 633 507 422 223 188 168 149 119 938 819
185plusmn1 of full scale 303 19 159 145 916 71 6 502 355 251 205
80(3Prime)
plusmn1 of reading 151 938 751 626 416 351 314 279 221 176 154530
plusmn1 of full scale 493 39 349 318 202 156 132 111 779 551 45100(4Prime)
plusmn1 of reading 197 123 983 819 561 473 423 375 298 237 207900
plusmn1 of full scale 588 423 378 345 219 169 143 12 845 68 68150(6Prime)
plusmn1 of reading 291 182 146 131 962 812 725 644 511 406 3552100
plusmn1 of full scale 117 921 824 752 476 369 312 261 22 22 22200(8Prime)
plusmn1 of reading 385 241 204 192 142 120 107 945 75 596 523400
plusmn1 of full scale 205 162 145 132 834 646 546 51 51 51 51250
(10Prime)plusmn1 of reading 479 299 275 258 191 161 144 128 101 98 98
5200plusmn1 of full scale 317 251 224 205 130 101 98 98 98 98 98
300(12Prime)
plusmn1 of reading 573 377 350 329 243 205 183 168 168 168 1687500
plusmn1 of full scale 454 359 321 293 186 168 168 168 168 168 168400
(16Prime)plusmn1 of reading 779 616 551 503 378 378 378 378 378 378 378
12000plusmn1 of full scale 779 616 551 503 378 378 378 378 378 378 378
500(20Prime)
plusmn1 of reading 1230 966 864 789 741 741 741 741 741 741 74119000
plusmn1 of full scale 1230 966 864 789 741 741 741 741 741 741 741Type of Gas Sp weight kgNm3 Pressure of Gas MPa (gauge) Temperature 20degC
Acetylene 1175 mdash mdash mdash 0 0176 0361 0547 0824 175 360 545Argon 1785 mdash mdash mdash 0 0081 0203 0325 0508 112 234 355Carbon Monoxide 1250 mdash mdash mdash 0 0160 0334 0508 0726 164 338 512Ethane 1357 mdash mdash mdash 0 0139 0299 0460 0700 150 310 471Ethylene 1264 mdash mdash mdash 0 0157 0329 0501 0759 162 334 506Air 1293 mdash mdash mdash 0 0151 0319 0487 0740 158 326 494Oxygen 1429 mdash mdash mdash 0 0121 0279 0431 0660 142 294 446Hydrogen 00899 0503 0866 111 135 353 595 mdash mdash mdash mdash mdashCarbon Dioxide 1977 mdash mdash mdash mdash 0064 0174 0284 0449 100 210 320Nitrogen 1251 mdash mdash mdash 0 0159 0333 0507 0768 164 338 511City Gas 0802 mdash 0 0034 0061 0305 0577 0848 125 261 532 mdashNatural Gas 0828 mdash mdash 0030 0056 0293 0555 0818 121 253 515 778Propane 2020 mdash mdash mdash mdash 0060 0168 0276 0437 0975 205 313Butane 2703 mdash mdash mdash mdash 0019 0100 0180 0301 0703 151 231Methane 0717 mdash mdash 0050 0081 0354 0657 0960 142 293 597 mdash
NOTES 1 Flow ranges listed in above table is calculated based on temperature 20 and viscosity 0017mPabulls 2 If it is necessary to determine the minimum flow rate precisely contact OVAL
How to Determine Minimum Flow RateExample 1 A 200mm (8Prime) size meter is to be used for air having a pressure of 074MPa [gauge] at 20 Find the minimum flow rate [Solution] Finding the minimum flow rate for nominal size 200mm (8Prime) in Table A corresponding to 074MPa [gauge] air in Table B we obtain where accuracy is plusmn1 of reading 945m3h where accuracy is plusmn1 of full scale 51m3h
Example 2 A 250mm (10Prime) size meter is to be used for city gas having a pressure of 05MPa [gauge] at 20 with an accuracy of plusmn1 of reading Find the minimum flow rate [Solution] Finding the minimum flow rate for nominal size 250mm (10Prime ) in Table A corresponding to 0305MPa [gauge] and 0577MPa [gauge] of city gas in Table B are 191m3h and 161m3h respectively Hence at 05MPa [gauge] we obtain from the rule of proportion
0577 minus 05 Qmin= 161 + times (191minus161)≒ 170m3h 0577 minus 0305
Example 3 A 200mm (8Prime) size meter is to be used for butane gas having a pressure of 0301MPa [gauge] at 80degC with an accuracy of 1 of reading Find the minimum flow rate [Solution] Although the minimum flow rate in Table A corresponding to 0301MPa [gauge] is 945m3h the minimum flow rate should increase by the amount of decrease in specific weight due to elevated temperature (80) as follows
0101325 + 030 27315 Sp weight of butane at 80 = 2703 times times =83kgm3
0101325 27315 + 80
The minimum flow rates for the nominal size 200mm (8) corresponding to specific weights 7kgm3 and 10kgm3 in Table A are 107m3h and 945m3h respectively Hence the minimum flow rate of butane at 80 (sp weight 83kgm3) can be obtained from the rule of proportion
10 minus 83 Qmin= 945 + times (107 minus 945)≒ 102m3h 10 minus 7
Tabl
e A
Tabl
e B
Find
the
valu
e cl
oses
t to
the
pres
sure
of g
asto
be
used
(low
er v
alue
) in
Tabl
e B
and
dete
rmin
e th
e m
inim
um fl
ow ra
te in
Tab
le A
4
GBD110E-6OVAL VORTEX FLOWMETER
PERFORMANCE CHARACTERISTICS
Meter FactorsThe table below shows the nominal meter factor by each nominal size and pulse frequency at maximum flow rate
Nominal Sizemm (inch)
Nominal Meter FactorLP
Pulse Freq atMax Flow rate
Hz
Max Flow ratem3h
20 (34) 0008438 4115 125 25 (1) 001733 4087 255
32 (114) 003852 4074 565 50 (2) 01260 4078 185 80 (3) 04197 3508 530100 (4) 09432 2651 900150 (6) 3033 1923 2100200 (8) 7032 1343 3400
250 (10) 1357 1064 5200 300 (12) 2326 8957 7500 400 (16) 5238 6364 12000 500 (20) 1028 5134 19000
20 30 50 100 300 500 103 1043times103
5times103Flow rate Qm3h [actual] Flow rate Qm3h [actual]
50
10
1008060504030
20
1086543
2
1
5
1
05
011 5 10 50 100
Nominal size 20mm(frac34Prime)
Nominal size 50mm(2Prime)
80mm(3Prime)
100mm(4Prime)
150mm(6Prime)
200mm(8Prime)
250mm(10Prime)
300mm(12Prime)
400mm(16Prime)
500mm(20Prime)
25mm(1Prime)
32mm(1frac14Prime)
Pres
los
s C
oeff
[C]
Pres
los
s C
oeff
[C]
Pressure Loss
Nominal sizes 20 to 32mm Nominal sizes 50 to 500mm
C times γΔP= 100ΔP Pressure loss (kPa) γ Sp weight (kgm3)To find the pressure loss read the coefficient C at the intersection of the flow rate Q and the diagonal line of the particular size and determine ΔP by the equation above
5
GBD110E-6OVAL VORTEX FLOWMETER
OUTLINE DIMENSIONS (Standard type) (Unit in mm)
StyleNominal size mm
(inch)Flange rating L H d D
Approx Weightkg
Wafertype
20 (34)Companion Flange
JIS 10 KJIS 20 KJIS 30 K
ASMEJPI 150ASMEJPI 300
80 375 214 120 10425 (1) 80 353 272 70 59
32 (1 14) 80 351 355 70 6450 (2) 80 359 527 92 7380 (3) 80 375 781 127 105
100 (4) 86 391 1023 1572 124150 (6) 108 428 151 2159 218
Flangetype
200 (8)
JIS 10 K
350 472 200
330 61JIS 20 K 350 75JIS 30 K 370 90
ASMEJPI 150 343 71ASMEJPI 300 381 95
250 (10)
JIS 10 K
450 505 249
400 101JIS 20 K 430 126JIS 30 K 450 152
ASMEJPI 150 406 111ASMEJPI 300 445 147
300 (12)
JIS 10 K
500 545 298
445 141JIS 20 K 480 169JIS 30 K 515 214
ASMEJPI 150 483 166ASMEJPI 300 520 217
400 (16)JIS 10 K
600 595 3906560 241
ASMEJPI 150 595 366
500 (20)JIS 10 K
650 655 489675 431
ASMEJPI 150 700 591
L
φD
L
φd
φD
H
6060 85 53
φ10
3
6060 85 53
φ10
3
H
6060 5385
φ10
3
H
Lφd
Conduit Connection G12 Conduit Connection G12
Conduit Connection G12
φd
φD
Wafer type 20mm (34Prime)
Dimensions D and H depend on the connecting flange rating
Wafer type 25mm (1Prime) to 150mm (6Prime)
Flange type 200mm (8Prime) to 500mm (20Prime)
NOTE Outline dimensions of special or regulation-compliant products may be different Please refer to the approval drawing or delivery specification
6
GBD110E-6OVAL VORTEX FLOWMETER
OUTLINE DIMENSIONS (Gas purge type) (Unit in mm)
Style Nominal size mm (inch) Flange rating L H d D Approx Weight
kg
Wafertype
50 (2)Companion Flange
JIS 10 KASMEJPI 150
80 359 527 92 7380 (3) 80 375 781 127 105
100 (4) 86 391 1023 1572 124150 (6) 108 428 151 2159 218
Flangetype
200 (8)JIS 10 K
350 472 200330 61
ASMEJPI 150 343 71
250 (10)JIS 10 K
450 505 249400 101
ASMEJPI 150 406 111
300 (12)JIS 10 K
500 545 298445 141
ASMEJPI 150 483 166
400 (16)JIS 10 K
600 595 3906560 241
ASMEJPI 150 595 366
500 (20)JIS 10 K
650 655 489675 431
ASMEJPI 150 700 591
Purge gas Connection
Purge gas Connection
60 85 5360
H
φd
L
φ10
3φ
D
H
φD φd
φ10
3
60 60 85
L
53Conduit Connection G12
Conduit Connection G12
Wafer type 50mm (2Prime) to 150mm (6Prime) Flange type 200mm (8Prime) to 500mm (20Prime)
NOTE Outline dimensions of special or regulation-compliant products may be different Please refer to the approval drawing or delivery specification
Purge Box (FB0 )12 Unit in mm
570
492
Mist Separator
Purge Inlet Purge Outlet (to Flowmeter)
Pipe
Enclosure Sheet steel
Finish Light beige (5Y71)
Approx weight 4 kg
Reducing ValveRotameter
210
7
GBD110E-6OVAL VORTEX FLOWMETER
Converter (PA21)
309233
617 1715
120 110100
φ13
4
67
Conduit Connection G34 Conduit Connection G34
30 125
71
41
7411
4
WIRING DIAGRAM
(1) Wiring for converter power source and output
Do not use this conduit connection
Terminal Cover for Maintenance
Terminal label and descriptionLabel Description Remark
POWER 24 to 32VDC DC power 24 to 32VDC
Open drain output (equivalent of open collector output) can be connected up to 30V 50mA
STATUS Status output (open drain)
PULSE Pulse output (open drain)
COMMONDC power (0V)Status output (minus)Pulse output (minus)
EARTH Grounding
Do not use the conduit connection on the terminal cover side For wiring connection specification refer to general specifications Converter on Page 2
Unit in mm
8
GBD110E-6OVAL VORTEX FLOWMETER
CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
For details of individual receiving instruments refer to respective general specification sheets1 A digital filter (SU1301) cannot be connected (The converter is equipped with the equivalent function)2 Separate power source is required when connecting with the totalizer (EL0122)
OVAL MODEL EL4000
Line temperature and pressure are considered approximately constant and correction factor can be multiplied as constant
Line temperature and pressure are automatically compensated and total and instantaneous flow readout (or output) are obtained
Meter body
Meter body
Converter
Converter
Pulse Distributor(SU1508)
orExternal Power Source
Flow Computer(EL4001 series)
4 to 20mADC
Unfactored Pulse
Factored Pulse
Totalizer(EL0122)
Total and Instantaneous Flow rate Readout
PressureTransmitter
ResistanceThermometer
(2)
(2) Wiring between converter and sensor
Converter (PA21)
Sensor terminal box
SIG0VSUPC1C2
SHIELD
SHIE
LDC
2 C1
SUP
0V SIG
Sensor terminal box must be installed using intrinsically safe installation procedure
Terminal label and connecting cable colorConverter terminals Terminals inside sensor terminal box Connecting cable color
SIG SIG White0V 0V Black
SUP SUP RedC1 C1 GreenC2 C2 Yellow
SHIELD SHIELD Twist [RedBlackWhite] [YellowGreen] and shielded cables together and cover the bundle with the accompanying tube then connect to SHIELD terminal
Exclusive cable must be used for connecting the converter and the sensor Either the left or right conduit connection (cable entry) of the sensor terminal box can be used For wiring connection specification refer to general specifications Converter on Page 2
9
GBD110E-6OVAL VORTEX FLOWMETER
INSTALLATION CONDITIONS1 Typical Piping InstructionsIt is required that the flow pattern of the fluid flowing in and out of a vortex flowmeter be as uniform as possible for accurate metering performance Therefore proper flow straightening measures have to be applied when installing a vortex flowmeter The standard piping instructions are shown in the following table
(1) Use an OVAL flow straightener or provide a specified straight pipe (ISO-5167 compliant)
No Piping Arrangement Straight PipeLength (L) Remark
1 OVALs Flow-Straightener
8D Refer to P11
Applicable to Nominal size 25mm or above
12D Refer to GSGCF001
2 Reducer 15D Min A concentric reducer is installed at the upstream of a meter
3 Elbow
23D Min An elbow is installed at the upstream of a meter
25D Min Two elbows are installed at the upstream of a meter
40D Min Two elbows are vertically installed at the upstream of a meter
4 Fully opengate valve 15D Min A full-open gate valve is installed at the upstream of a
meter
5 Partially opengate valve 50D Min A partially open gate valve sharp orifice or something that
markedly disturbs the flow pattern is upstream of meter
Honey VanebullLFlow
L
Flow
Flow
L
L
Flow Straightener
Flow
L
Flow
L
Flow
L
Flow
L
Flow
L
Fully Open
PartiallyOpen
NOTES1 Upstream and downstream pipes adjacent to the flowmeter should be of the same internal
diameter (ID) as the flowmeter (The exclusive flow straightener Honey Vane L and downstream short pipe have the same ID as the flowmeter) The table below shows the standard ID of the flowmeter Confirm the delivery specification in case ID is non-standard
Flowmeter standard IDNominal size ID referenceunder 400mm Sch40
400mm or more Sch20
2 A short pipe section 5D or longer shall be provided downstream of the meter3 For pressure detection provide the probe downstream of the flowmeter (see the right figure)
To avoid disturbances in the flow temperature detection should be made downstream of the flowmeter and at the same time upstream of the control valve
2 Pressure PulsationIn case the flowmeter is installed in the line where instruments that can generate pressure pulsation such as roots blower or compressor is present performance of the flowmeter can be affected by flow pulsation Allowable pulsation pressure is calculated from the following equationNlt 22ρV2 (Pa)where N Pulsation pressure (Pa) ρ Density (kgm3) V Min Velocity (ms)
Even at shutdown pressure pulsation in the process fluid can produce a false output If pressure pulsation is excessive take the following measures① Locate the source of flow pulsation downstream of the flowmeter② Install a pulsation attenuator③ At shutdown of the flow shut off valves upstream and downstream of the flowmeter
2 to 7Dfrom the meter
FLOW
D Nominal size
Pressure detection point
Temperature detection point
Min 1D from pressure detection pointMin 2D from flowmeter
10
GBD110E-6OVAL VORTEX FLOWMETER
FLOW
Honey Vane S
Flowmeter
Min 8D
Honey Vane Outline Dimensions
Nominal size(mm)
Honey Vane S Honey Vane LφD (mm) t (mm) L (mm)
25 75 35 20040 90 54 32050 105 69 40080 134 102 640
100 159 133 800150 220 196 1200200 268 26 1600250 331 323 2000300 376 387 2400
Dimensions for JIS 10K
L
t
φD
t
Honey Vane S Honey Vane L
Installation of Honey Vane S ① Locate the Honey Vane S upstream of the flowmeter ② Provide a short pipe (8D or longer) between Honey Vane S and flowmeter ③ Regarding the bolts and nuts used for connecting JPI flange adopt unified screw threads If it is necessary to use metric screw threads contact OVAL
11
GBD110E-6OVAL VORTEX FLOWMETER
PRECAUTIONS ON USE1 This flowmeter is developed designed and manufactured to be used as a flowmeter for general industrial application
Therefore when it is used for the application where its operation is directly related to the safety of the relevant system or the product is important in the facilities (such as process control and custody transfer) you are requested to ensure sufficient security including safety design redundancy and duplication of the process and implementation of periodic inspection Do not use this flowmeter where its operation and performance directly affect human life
2 When used under appropriate conditions this flowmeter can demonstrate its stable performance without aging degradation of accuracy However malfunction or failure may occur due to various factors Thus examining the operating conditions operating status and importance in the process you should consider periodic maintenance of your flowmeter In order to secure long-term and safe use OVAL recommends the customer to verify the soundness of the flowmeter through periodic inspection every two years For the details of inspection contact the nearest OVAL salesservice office or representatives
3 This flowmeter is manufactured adjusted and inspected to meet the conditions of use The fluid measured flow range pressure temperature etc must be applied under the specified conditions The conditions for use are stated on the nameplate attached on the flowmeter transmitter and specification sheet supplied with the product
4 The materials used in this flowmeter are stated in this document or delivery specification sheet shipped with the equipment Supplied with all the necessary information by the customer OVAL has selected materials that best suit the customer requirements including corrosion resistance However we ask you to understand that the final judgment on the compatibility of the materials in the actual process environment lies with the customer
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
4
GBD110E-6OVAL VORTEX FLOWMETER
PERFORMANCE CHARACTERISTICS
Meter FactorsThe table below shows the nominal meter factor by each nominal size and pulse frequency at maximum flow rate
Nominal Sizemm (inch)
Nominal Meter FactorLP
Pulse Freq atMax Flow rate
Hz
Max Flow ratem3h
20 (34) 0008438 4115 125 25 (1) 001733 4087 255
32 (114) 003852 4074 565 50 (2) 01260 4078 185 80 (3) 04197 3508 530100 (4) 09432 2651 900150 (6) 3033 1923 2100200 (8) 7032 1343 3400
250 (10) 1357 1064 5200 300 (12) 2326 8957 7500 400 (16) 5238 6364 12000 500 (20) 1028 5134 19000
20 30 50 100 300 500 103 1043times103
5times103Flow rate Qm3h [actual] Flow rate Qm3h [actual]
50
10
1008060504030
20
1086543
2
1
5
1
05
011 5 10 50 100
Nominal size 20mm(frac34Prime)
Nominal size 50mm(2Prime)
80mm(3Prime)
100mm(4Prime)
150mm(6Prime)
200mm(8Prime)
250mm(10Prime)
300mm(12Prime)
400mm(16Prime)
500mm(20Prime)
25mm(1Prime)
32mm(1frac14Prime)
Pres
los
s C
oeff
[C]
Pres
los
s C
oeff
[C]
Pressure Loss
Nominal sizes 20 to 32mm Nominal sizes 50 to 500mm
C times γΔP= 100ΔP Pressure loss (kPa) γ Sp weight (kgm3)To find the pressure loss read the coefficient C at the intersection of the flow rate Q and the diagonal line of the particular size and determine ΔP by the equation above
5
GBD110E-6OVAL VORTEX FLOWMETER
OUTLINE DIMENSIONS (Standard type) (Unit in mm)
StyleNominal size mm
(inch)Flange rating L H d D
Approx Weightkg
Wafertype
20 (34)Companion Flange
JIS 10 KJIS 20 KJIS 30 K
ASMEJPI 150ASMEJPI 300
80 375 214 120 10425 (1) 80 353 272 70 59
32 (1 14) 80 351 355 70 6450 (2) 80 359 527 92 7380 (3) 80 375 781 127 105
100 (4) 86 391 1023 1572 124150 (6) 108 428 151 2159 218
Flangetype
200 (8)
JIS 10 K
350 472 200
330 61JIS 20 K 350 75JIS 30 K 370 90
ASMEJPI 150 343 71ASMEJPI 300 381 95
250 (10)
JIS 10 K
450 505 249
400 101JIS 20 K 430 126JIS 30 K 450 152
ASMEJPI 150 406 111ASMEJPI 300 445 147
300 (12)
JIS 10 K
500 545 298
445 141JIS 20 K 480 169JIS 30 K 515 214
ASMEJPI 150 483 166ASMEJPI 300 520 217
400 (16)JIS 10 K
600 595 3906560 241
ASMEJPI 150 595 366
500 (20)JIS 10 K
650 655 489675 431
ASMEJPI 150 700 591
L
φD
L
φd
φD
H
6060 85 53
φ10
3
6060 85 53
φ10
3
H
6060 5385
φ10
3
H
Lφd
Conduit Connection G12 Conduit Connection G12
Conduit Connection G12
φd
φD
Wafer type 20mm (34Prime)
Dimensions D and H depend on the connecting flange rating
Wafer type 25mm (1Prime) to 150mm (6Prime)
Flange type 200mm (8Prime) to 500mm (20Prime)
NOTE Outline dimensions of special or regulation-compliant products may be different Please refer to the approval drawing or delivery specification
6
GBD110E-6OVAL VORTEX FLOWMETER
OUTLINE DIMENSIONS (Gas purge type) (Unit in mm)
Style Nominal size mm (inch) Flange rating L H d D Approx Weight
kg
Wafertype
50 (2)Companion Flange
JIS 10 KASMEJPI 150
80 359 527 92 7380 (3) 80 375 781 127 105
100 (4) 86 391 1023 1572 124150 (6) 108 428 151 2159 218
Flangetype
200 (8)JIS 10 K
350 472 200330 61
ASMEJPI 150 343 71
250 (10)JIS 10 K
450 505 249400 101
ASMEJPI 150 406 111
300 (12)JIS 10 K
500 545 298445 141
ASMEJPI 150 483 166
400 (16)JIS 10 K
600 595 3906560 241
ASMEJPI 150 595 366
500 (20)JIS 10 K
650 655 489675 431
ASMEJPI 150 700 591
Purge gas Connection
Purge gas Connection
60 85 5360
H
φd
L
φ10
3φ
D
H
φD φd
φ10
3
60 60 85
L
53Conduit Connection G12
Conduit Connection G12
Wafer type 50mm (2Prime) to 150mm (6Prime) Flange type 200mm (8Prime) to 500mm (20Prime)
NOTE Outline dimensions of special or regulation-compliant products may be different Please refer to the approval drawing or delivery specification
Purge Box (FB0 )12 Unit in mm
570
492
Mist Separator
Purge Inlet Purge Outlet (to Flowmeter)
Pipe
Enclosure Sheet steel
Finish Light beige (5Y71)
Approx weight 4 kg
Reducing ValveRotameter
210
7
GBD110E-6OVAL VORTEX FLOWMETER
Converter (PA21)
309233
617 1715
120 110100
φ13
4
67
Conduit Connection G34 Conduit Connection G34
30 125
71
41
7411
4
WIRING DIAGRAM
(1) Wiring for converter power source and output
Do not use this conduit connection
Terminal Cover for Maintenance
Terminal label and descriptionLabel Description Remark
POWER 24 to 32VDC DC power 24 to 32VDC
Open drain output (equivalent of open collector output) can be connected up to 30V 50mA
STATUS Status output (open drain)
PULSE Pulse output (open drain)
COMMONDC power (0V)Status output (minus)Pulse output (minus)
EARTH Grounding
Do not use the conduit connection on the terminal cover side For wiring connection specification refer to general specifications Converter on Page 2
Unit in mm
8
GBD110E-6OVAL VORTEX FLOWMETER
CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
For details of individual receiving instruments refer to respective general specification sheets1 A digital filter (SU1301) cannot be connected (The converter is equipped with the equivalent function)2 Separate power source is required when connecting with the totalizer (EL0122)
OVAL MODEL EL4000
Line temperature and pressure are considered approximately constant and correction factor can be multiplied as constant
Line temperature and pressure are automatically compensated and total and instantaneous flow readout (or output) are obtained
Meter body
Meter body
Converter
Converter
Pulse Distributor(SU1508)
orExternal Power Source
Flow Computer(EL4001 series)
4 to 20mADC
Unfactored Pulse
Factored Pulse
Totalizer(EL0122)
Total and Instantaneous Flow rate Readout
PressureTransmitter
ResistanceThermometer
(2)
(2) Wiring between converter and sensor
Converter (PA21)
Sensor terminal box
SIG0VSUPC1C2
SHIELD
SHIE
LDC
2 C1
SUP
0V SIG
Sensor terminal box must be installed using intrinsically safe installation procedure
Terminal label and connecting cable colorConverter terminals Terminals inside sensor terminal box Connecting cable color
SIG SIG White0V 0V Black
SUP SUP RedC1 C1 GreenC2 C2 Yellow
SHIELD SHIELD Twist [RedBlackWhite] [YellowGreen] and shielded cables together and cover the bundle with the accompanying tube then connect to SHIELD terminal
Exclusive cable must be used for connecting the converter and the sensor Either the left or right conduit connection (cable entry) of the sensor terminal box can be used For wiring connection specification refer to general specifications Converter on Page 2
9
GBD110E-6OVAL VORTEX FLOWMETER
INSTALLATION CONDITIONS1 Typical Piping InstructionsIt is required that the flow pattern of the fluid flowing in and out of a vortex flowmeter be as uniform as possible for accurate metering performance Therefore proper flow straightening measures have to be applied when installing a vortex flowmeter The standard piping instructions are shown in the following table
(1) Use an OVAL flow straightener or provide a specified straight pipe (ISO-5167 compliant)
No Piping Arrangement Straight PipeLength (L) Remark
1 OVALs Flow-Straightener
8D Refer to P11
Applicable to Nominal size 25mm or above
12D Refer to GSGCF001
2 Reducer 15D Min A concentric reducer is installed at the upstream of a meter
3 Elbow
23D Min An elbow is installed at the upstream of a meter
25D Min Two elbows are installed at the upstream of a meter
40D Min Two elbows are vertically installed at the upstream of a meter
4 Fully opengate valve 15D Min A full-open gate valve is installed at the upstream of a
meter
5 Partially opengate valve 50D Min A partially open gate valve sharp orifice or something that
markedly disturbs the flow pattern is upstream of meter
Honey VanebullLFlow
L
Flow
Flow
L
L
Flow Straightener
Flow
L
Flow
L
Flow
L
Flow
L
Flow
L
Fully Open
PartiallyOpen
NOTES1 Upstream and downstream pipes adjacent to the flowmeter should be of the same internal
diameter (ID) as the flowmeter (The exclusive flow straightener Honey Vane L and downstream short pipe have the same ID as the flowmeter) The table below shows the standard ID of the flowmeter Confirm the delivery specification in case ID is non-standard
Flowmeter standard IDNominal size ID referenceunder 400mm Sch40
400mm or more Sch20
2 A short pipe section 5D or longer shall be provided downstream of the meter3 For pressure detection provide the probe downstream of the flowmeter (see the right figure)
To avoid disturbances in the flow temperature detection should be made downstream of the flowmeter and at the same time upstream of the control valve
2 Pressure PulsationIn case the flowmeter is installed in the line where instruments that can generate pressure pulsation such as roots blower or compressor is present performance of the flowmeter can be affected by flow pulsation Allowable pulsation pressure is calculated from the following equationNlt 22ρV2 (Pa)where N Pulsation pressure (Pa) ρ Density (kgm3) V Min Velocity (ms)
Even at shutdown pressure pulsation in the process fluid can produce a false output If pressure pulsation is excessive take the following measures① Locate the source of flow pulsation downstream of the flowmeter② Install a pulsation attenuator③ At shutdown of the flow shut off valves upstream and downstream of the flowmeter
2 to 7Dfrom the meter
FLOW
D Nominal size
Pressure detection point
Temperature detection point
Min 1D from pressure detection pointMin 2D from flowmeter
10
GBD110E-6OVAL VORTEX FLOWMETER
FLOW
Honey Vane S
Flowmeter
Min 8D
Honey Vane Outline Dimensions
Nominal size(mm)
Honey Vane S Honey Vane LφD (mm) t (mm) L (mm)
25 75 35 20040 90 54 32050 105 69 40080 134 102 640
100 159 133 800150 220 196 1200200 268 26 1600250 331 323 2000300 376 387 2400
Dimensions for JIS 10K
L
t
φD
t
Honey Vane S Honey Vane L
Installation of Honey Vane S ① Locate the Honey Vane S upstream of the flowmeter ② Provide a short pipe (8D or longer) between Honey Vane S and flowmeter ③ Regarding the bolts and nuts used for connecting JPI flange adopt unified screw threads If it is necessary to use metric screw threads contact OVAL
11
GBD110E-6OVAL VORTEX FLOWMETER
PRECAUTIONS ON USE1 This flowmeter is developed designed and manufactured to be used as a flowmeter for general industrial application
Therefore when it is used for the application where its operation is directly related to the safety of the relevant system or the product is important in the facilities (such as process control and custody transfer) you are requested to ensure sufficient security including safety design redundancy and duplication of the process and implementation of periodic inspection Do not use this flowmeter where its operation and performance directly affect human life
2 When used under appropriate conditions this flowmeter can demonstrate its stable performance without aging degradation of accuracy However malfunction or failure may occur due to various factors Thus examining the operating conditions operating status and importance in the process you should consider periodic maintenance of your flowmeter In order to secure long-term and safe use OVAL recommends the customer to verify the soundness of the flowmeter through periodic inspection every two years For the details of inspection contact the nearest OVAL salesservice office or representatives
3 This flowmeter is manufactured adjusted and inspected to meet the conditions of use The fluid measured flow range pressure temperature etc must be applied under the specified conditions The conditions for use are stated on the nameplate attached on the flowmeter transmitter and specification sheet supplied with the product
4 The materials used in this flowmeter are stated in this document or delivery specification sheet shipped with the equipment Supplied with all the necessary information by the customer OVAL has selected materials that best suit the customer requirements including corrosion resistance However we ask you to understand that the final judgment on the compatibility of the materials in the actual process environment lies with the customer
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
5
GBD110E-6OVAL VORTEX FLOWMETER
OUTLINE DIMENSIONS (Standard type) (Unit in mm)
StyleNominal size mm
(inch)Flange rating L H d D
Approx Weightkg
Wafertype
20 (34)Companion Flange
JIS 10 KJIS 20 KJIS 30 K
ASMEJPI 150ASMEJPI 300
80 375 214 120 10425 (1) 80 353 272 70 59
32 (1 14) 80 351 355 70 6450 (2) 80 359 527 92 7380 (3) 80 375 781 127 105
100 (4) 86 391 1023 1572 124150 (6) 108 428 151 2159 218
Flangetype
200 (8)
JIS 10 K
350 472 200
330 61JIS 20 K 350 75JIS 30 K 370 90
ASMEJPI 150 343 71ASMEJPI 300 381 95
250 (10)
JIS 10 K
450 505 249
400 101JIS 20 K 430 126JIS 30 K 450 152
ASMEJPI 150 406 111ASMEJPI 300 445 147
300 (12)
JIS 10 K
500 545 298
445 141JIS 20 K 480 169JIS 30 K 515 214
ASMEJPI 150 483 166ASMEJPI 300 520 217
400 (16)JIS 10 K
600 595 3906560 241
ASMEJPI 150 595 366
500 (20)JIS 10 K
650 655 489675 431
ASMEJPI 150 700 591
L
φD
L
φd
φD
H
6060 85 53
φ10
3
6060 85 53
φ10
3
H
6060 5385
φ10
3
H
Lφd
Conduit Connection G12 Conduit Connection G12
Conduit Connection G12
φd
φD
Wafer type 20mm (34Prime)
Dimensions D and H depend on the connecting flange rating
Wafer type 25mm (1Prime) to 150mm (6Prime)
Flange type 200mm (8Prime) to 500mm (20Prime)
NOTE Outline dimensions of special or regulation-compliant products may be different Please refer to the approval drawing or delivery specification
6
GBD110E-6OVAL VORTEX FLOWMETER
OUTLINE DIMENSIONS (Gas purge type) (Unit in mm)
Style Nominal size mm (inch) Flange rating L H d D Approx Weight
kg
Wafertype
50 (2)Companion Flange
JIS 10 KASMEJPI 150
80 359 527 92 7380 (3) 80 375 781 127 105
100 (4) 86 391 1023 1572 124150 (6) 108 428 151 2159 218
Flangetype
200 (8)JIS 10 K
350 472 200330 61
ASMEJPI 150 343 71
250 (10)JIS 10 K
450 505 249400 101
ASMEJPI 150 406 111
300 (12)JIS 10 K
500 545 298445 141
ASMEJPI 150 483 166
400 (16)JIS 10 K
600 595 3906560 241
ASMEJPI 150 595 366
500 (20)JIS 10 K
650 655 489675 431
ASMEJPI 150 700 591
Purge gas Connection
Purge gas Connection
60 85 5360
H
φd
L
φ10
3φ
D
H
φD φd
φ10
3
60 60 85
L
53Conduit Connection G12
Conduit Connection G12
Wafer type 50mm (2Prime) to 150mm (6Prime) Flange type 200mm (8Prime) to 500mm (20Prime)
NOTE Outline dimensions of special or regulation-compliant products may be different Please refer to the approval drawing or delivery specification
Purge Box (FB0 )12 Unit in mm
570
492
Mist Separator
Purge Inlet Purge Outlet (to Flowmeter)
Pipe
Enclosure Sheet steel
Finish Light beige (5Y71)
Approx weight 4 kg
Reducing ValveRotameter
210
7
GBD110E-6OVAL VORTEX FLOWMETER
Converter (PA21)
309233
617 1715
120 110100
φ13
4
67
Conduit Connection G34 Conduit Connection G34
30 125
71
41
7411
4
WIRING DIAGRAM
(1) Wiring for converter power source and output
Do not use this conduit connection
Terminal Cover for Maintenance
Terminal label and descriptionLabel Description Remark
POWER 24 to 32VDC DC power 24 to 32VDC
Open drain output (equivalent of open collector output) can be connected up to 30V 50mA
STATUS Status output (open drain)
PULSE Pulse output (open drain)
COMMONDC power (0V)Status output (minus)Pulse output (minus)
EARTH Grounding
Do not use the conduit connection on the terminal cover side For wiring connection specification refer to general specifications Converter on Page 2
Unit in mm
8
GBD110E-6OVAL VORTEX FLOWMETER
CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
For details of individual receiving instruments refer to respective general specification sheets1 A digital filter (SU1301) cannot be connected (The converter is equipped with the equivalent function)2 Separate power source is required when connecting with the totalizer (EL0122)
OVAL MODEL EL4000
Line temperature and pressure are considered approximately constant and correction factor can be multiplied as constant
Line temperature and pressure are automatically compensated and total and instantaneous flow readout (or output) are obtained
Meter body
Meter body
Converter
Converter
Pulse Distributor(SU1508)
orExternal Power Source
Flow Computer(EL4001 series)
4 to 20mADC
Unfactored Pulse
Factored Pulse
Totalizer(EL0122)
Total and Instantaneous Flow rate Readout
PressureTransmitter
ResistanceThermometer
(2)
(2) Wiring between converter and sensor
Converter (PA21)
Sensor terminal box
SIG0VSUPC1C2
SHIELD
SHIE
LDC
2 C1
SUP
0V SIG
Sensor terminal box must be installed using intrinsically safe installation procedure
Terminal label and connecting cable colorConverter terminals Terminals inside sensor terminal box Connecting cable color
SIG SIG White0V 0V Black
SUP SUP RedC1 C1 GreenC2 C2 Yellow
SHIELD SHIELD Twist [RedBlackWhite] [YellowGreen] and shielded cables together and cover the bundle with the accompanying tube then connect to SHIELD terminal
Exclusive cable must be used for connecting the converter and the sensor Either the left or right conduit connection (cable entry) of the sensor terminal box can be used For wiring connection specification refer to general specifications Converter on Page 2
9
GBD110E-6OVAL VORTEX FLOWMETER
INSTALLATION CONDITIONS1 Typical Piping InstructionsIt is required that the flow pattern of the fluid flowing in and out of a vortex flowmeter be as uniform as possible for accurate metering performance Therefore proper flow straightening measures have to be applied when installing a vortex flowmeter The standard piping instructions are shown in the following table
(1) Use an OVAL flow straightener or provide a specified straight pipe (ISO-5167 compliant)
No Piping Arrangement Straight PipeLength (L) Remark
1 OVALs Flow-Straightener
8D Refer to P11
Applicable to Nominal size 25mm or above
12D Refer to GSGCF001
2 Reducer 15D Min A concentric reducer is installed at the upstream of a meter
3 Elbow
23D Min An elbow is installed at the upstream of a meter
25D Min Two elbows are installed at the upstream of a meter
40D Min Two elbows are vertically installed at the upstream of a meter
4 Fully opengate valve 15D Min A full-open gate valve is installed at the upstream of a
meter
5 Partially opengate valve 50D Min A partially open gate valve sharp orifice or something that
markedly disturbs the flow pattern is upstream of meter
Honey VanebullLFlow
L
Flow
Flow
L
L
Flow Straightener
Flow
L
Flow
L
Flow
L
Flow
L
Flow
L
Fully Open
PartiallyOpen
NOTES1 Upstream and downstream pipes adjacent to the flowmeter should be of the same internal
diameter (ID) as the flowmeter (The exclusive flow straightener Honey Vane L and downstream short pipe have the same ID as the flowmeter) The table below shows the standard ID of the flowmeter Confirm the delivery specification in case ID is non-standard
Flowmeter standard IDNominal size ID referenceunder 400mm Sch40
400mm or more Sch20
2 A short pipe section 5D or longer shall be provided downstream of the meter3 For pressure detection provide the probe downstream of the flowmeter (see the right figure)
To avoid disturbances in the flow temperature detection should be made downstream of the flowmeter and at the same time upstream of the control valve
2 Pressure PulsationIn case the flowmeter is installed in the line where instruments that can generate pressure pulsation such as roots blower or compressor is present performance of the flowmeter can be affected by flow pulsation Allowable pulsation pressure is calculated from the following equationNlt 22ρV2 (Pa)where N Pulsation pressure (Pa) ρ Density (kgm3) V Min Velocity (ms)
Even at shutdown pressure pulsation in the process fluid can produce a false output If pressure pulsation is excessive take the following measures① Locate the source of flow pulsation downstream of the flowmeter② Install a pulsation attenuator③ At shutdown of the flow shut off valves upstream and downstream of the flowmeter
2 to 7Dfrom the meter
FLOW
D Nominal size
Pressure detection point
Temperature detection point
Min 1D from pressure detection pointMin 2D from flowmeter
10
GBD110E-6OVAL VORTEX FLOWMETER
FLOW
Honey Vane S
Flowmeter
Min 8D
Honey Vane Outline Dimensions
Nominal size(mm)
Honey Vane S Honey Vane LφD (mm) t (mm) L (mm)
25 75 35 20040 90 54 32050 105 69 40080 134 102 640
100 159 133 800150 220 196 1200200 268 26 1600250 331 323 2000300 376 387 2400
Dimensions for JIS 10K
L
t
φD
t
Honey Vane S Honey Vane L
Installation of Honey Vane S ① Locate the Honey Vane S upstream of the flowmeter ② Provide a short pipe (8D or longer) between Honey Vane S and flowmeter ③ Regarding the bolts and nuts used for connecting JPI flange adopt unified screw threads If it is necessary to use metric screw threads contact OVAL
11
GBD110E-6OVAL VORTEX FLOWMETER
PRECAUTIONS ON USE1 This flowmeter is developed designed and manufactured to be used as a flowmeter for general industrial application
Therefore when it is used for the application where its operation is directly related to the safety of the relevant system or the product is important in the facilities (such as process control and custody transfer) you are requested to ensure sufficient security including safety design redundancy and duplication of the process and implementation of periodic inspection Do not use this flowmeter where its operation and performance directly affect human life
2 When used under appropriate conditions this flowmeter can demonstrate its stable performance without aging degradation of accuracy However malfunction or failure may occur due to various factors Thus examining the operating conditions operating status and importance in the process you should consider periodic maintenance of your flowmeter In order to secure long-term and safe use OVAL recommends the customer to verify the soundness of the flowmeter through periodic inspection every two years For the details of inspection contact the nearest OVAL salesservice office or representatives
3 This flowmeter is manufactured adjusted and inspected to meet the conditions of use The fluid measured flow range pressure temperature etc must be applied under the specified conditions The conditions for use are stated on the nameplate attached on the flowmeter transmitter and specification sheet supplied with the product
4 The materials used in this flowmeter are stated in this document or delivery specification sheet shipped with the equipment Supplied with all the necessary information by the customer OVAL has selected materials that best suit the customer requirements including corrosion resistance However we ask you to understand that the final judgment on the compatibility of the materials in the actual process environment lies with the customer
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
6
GBD110E-6OVAL VORTEX FLOWMETER
OUTLINE DIMENSIONS (Gas purge type) (Unit in mm)
Style Nominal size mm (inch) Flange rating L H d D Approx Weight
kg
Wafertype
50 (2)Companion Flange
JIS 10 KASMEJPI 150
80 359 527 92 7380 (3) 80 375 781 127 105
100 (4) 86 391 1023 1572 124150 (6) 108 428 151 2159 218
Flangetype
200 (8)JIS 10 K
350 472 200330 61
ASMEJPI 150 343 71
250 (10)JIS 10 K
450 505 249400 101
ASMEJPI 150 406 111
300 (12)JIS 10 K
500 545 298445 141
ASMEJPI 150 483 166
400 (16)JIS 10 K
600 595 3906560 241
ASMEJPI 150 595 366
500 (20)JIS 10 K
650 655 489675 431
ASMEJPI 150 700 591
Purge gas Connection
Purge gas Connection
60 85 5360
H
φd
L
φ10
3φ
D
H
φD φd
φ10
3
60 60 85
L
53Conduit Connection G12
Conduit Connection G12
Wafer type 50mm (2Prime) to 150mm (6Prime) Flange type 200mm (8Prime) to 500mm (20Prime)
NOTE Outline dimensions of special or regulation-compliant products may be different Please refer to the approval drawing or delivery specification
Purge Box (FB0 )12 Unit in mm
570
492
Mist Separator
Purge Inlet Purge Outlet (to Flowmeter)
Pipe
Enclosure Sheet steel
Finish Light beige (5Y71)
Approx weight 4 kg
Reducing ValveRotameter
210
7
GBD110E-6OVAL VORTEX FLOWMETER
Converter (PA21)
309233
617 1715
120 110100
φ13
4
67
Conduit Connection G34 Conduit Connection G34
30 125
71
41
7411
4
WIRING DIAGRAM
(1) Wiring for converter power source and output
Do not use this conduit connection
Terminal Cover for Maintenance
Terminal label and descriptionLabel Description Remark
POWER 24 to 32VDC DC power 24 to 32VDC
Open drain output (equivalent of open collector output) can be connected up to 30V 50mA
STATUS Status output (open drain)
PULSE Pulse output (open drain)
COMMONDC power (0V)Status output (minus)Pulse output (minus)
EARTH Grounding
Do not use the conduit connection on the terminal cover side For wiring connection specification refer to general specifications Converter on Page 2
Unit in mm
8
GBD110E-6OVAL VORTEX FLOWMETER
CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
For details of individual receiving instruments refer to respective general specification sheets1 A digital filter (SU1301) cannot be connected (The converter is equipped with the equivalent function)2 Separate power source is required when connecting with the totalizer (EL0122)
OVAL MODEL EL4000
Line temperature and pressure are considered approximately constant and correction factor can be multiplied as constant
Line temperature and pressure are automatically compensated and total and instantaneous flow readout (or output) are obtained
Meter body
Meter body
Converter
Converter
Pulse Distributor(SU1508)
orExternal Power Source
Flow Computer(EL4001 series)
4 to 20mADC
Unfactored Pulse
Factored Pulse
Totalizer(EL0122)
Total and Instantaneous Flow rate Readout
PressureTransmitter
ResistanceThermometer
(2)
(2) Wiring between converter and sensor
Converter (PA21)
Sensor terminal box
SIG0VSUPC1C2
SHIELD
SHIE
LDC
2 C1
SUP
0V SIG
Sensor terminal box must be installed using intrinsically safe installation procedure
Terminal label and connecting cable colorConverter terminals Terminals inside sensor terminal box Connecting cable color
SIG SIG White0V 0V Black
SUP SUP RedC1 C1 GreenC2 C2 Yellow
SHIELD SHIELD Twist [RedBlackWhite] [YellowGreen] and shielded cables together and cover the bundle with the accompanying tube then connect to SHIELD terminal
Exclusive cable must be used for connecting the converter and the sensor Either the left or right conduit connection (cable entry) of the sensor terminal box can be used For wiring connection specification refer to general specifications Converter on Page 2
9
GBD110E-6OVAL VORTEX FLOWMETER
INSTALLATION CONDITIONS1 Typical Piping InstructionsIt is required that the flow pattern of the fluid flowing in and out of a vortex flowmeter be as uniform as possible for accurate metering performance Therefore proper flow straightening measures have to be applied when installing a vortex flowmeter The standard piping instructions are shown in the following table
(1) Use an OVAL flow straightener or provide a specified straight pipe (ISO-5167 compliant)
No Piping Arrangement Straight PipeLength (L) Remark
1 OVALs Flow-Straightener
8D Refer to P11
Applicable to Nominal size 25mm or above
12D Refer to GSGCF001
2 Reducer 15D Min A concentric reducer is installed at the upstream of a meter
3 Elbow
23D Min An elbow is installed at the upstream of a meter
25D Min Two elbows are installed at the upstream of a meter
40D Min Two elbows are vertically installed at the upstream of a meter
4 Fully opengate valve 15D Min A full-open gate valve is installed at the upstream of a
meter
5 Partially opengate valve 50D Min A partially open gate valve sharp orifice or something that
markedly disturbs the flow pattern is upstream of meter
Honey VanebullLFlow
L
Flow
Flow
L
L
Flow Straightener
Flow
L
Flow
L
Flow
L
Flow
L
Flow
L
Fully Open
PartiallyOpen
NOTES1 Upstream and downstream pipes adjacent to the flowmeter should be of the same internal
diameter (ID) as the flowmeter (The exclusive flow straightener Honey Vane L and downstream short pipe have the same ID as the flowmeter) The table below shows the standard ID of the flowmeter Confirm the delivery specification in case ID is non-standard
Flowmeter standard IDNominal size ID referenceunder 400mm Sch40
400mm or more Sch20
2 A short pipe section 5D or longer shall be provided downstream of the meter3 For pressure detection provide the probe downstream of the flowmeter (see the right figure)
To avoid disturbances in the flow temperature detection should be made downstream of the flowmeter and at the same time upstream of the control valve
2 Pressure PulsationIn case the flowmeter is installed in the line where instruments that can generate pressure pulsation such as roots blower or compressor is present performance of the flowmeter can be affected by flow pulsation Allowable pulsation pressure is calculated from the following equationNlt 22ρV2 (Pa)where N Pulsation pressure (Pa) ρ Density (kgm3) V Min Velocity (ms)
Even at shutdown pressure pulsation in the process fluid can produce a false output If pressure pulsation is excessive take the following measures① Locate the source of flow pulsation downstream of the flowmeter② Install a pulsation attenuator③ At shutdown of the flow shut off valves upstream and downstream of the flowmeter
2 to 7Dfrom the meter
FLOW
D Nominal size
Pressure detection point
Temperature detection point
Min 1D from pressure detection pointMin 2D from flowmeter
10
GBD110E-6OVAL VORTEX FLOWMETER
FLOW
Honey Vane S
Flowmeter
Min 8D
Honey Vane Outline Dimensions
Nominal size(mm)
Honey Vane S Honey Vane LφD (mm) t (mm) L (mm)
25 75 35 20040 90 54 32050 105 69 40080 134 102 640
100 159 133 800150 220 196 1200200 268 26 1600250 331 323 2000300 376 387 2400
Dimensions for JIS 10K
L
t
φD
t
Honey Vane S Honey Vane L
Installation of Honey Vane S ① Locate the Honey Vane S upstream of the flowmeter ② Provide a short pipe (8D or longer) between Honey Vane S and flowmeter ③ Regarding the bolts and nuts used for connecting JPI flange adopt unified screw threads If it is necessary to use metric screw threads contact OVAL
11
GBD110E-6OVAL VORTEX FLOWMETER
PRECAUTIONS ON USE1 This flowmeter is developed designed and manufactured to be used as a flowmeter for general industrial application
Therefore when it is used for the application where its operation is directly related to the safety of the relevant system or the product is important in the facilities (such as process control and custody transfer) you are requested to ensure sufficient security including safety design redundancy and duplication of the process and implementation of periodic inspection Do not use this flowmeter where its operation and performance directly affect human life
2 When used under appropriate conditions this flowmeter can demonstrate its stable performance without aging degradation of accuracy However malfunction or failure may occur due to various factors Thus examining the operating conditions operating status and importance in the process you should consider periodic maintenance of your flowmeter In order to secure long-term and safe use OVAL recommends the customer to verify the soundness of the flowmeter through periodic inspection every two years For the details of inspection contact the nearest OVAL salesservice office or representatives
3 This flowmeter is manufactured adjusted and inspected to meet the conditions of use The fluid measured flow range pressure temperature etc must be applied under the specified conditions The conditions for use are stated on the nameplate attached on the flowmeter transmitter and specification sheet supplied with the product
4 The materials used in this flowmeter are stated in this document or delivery specification sheet shipped with the equipment Supplied with all the necessary information by the customer OVAL has selected materials that best suit the customer requirements including corrosion resistance However we ask you to understand that the final judgment on the compatibility of the materials in the actual process environment lies with the customer
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
7
GBD110E-6OVAL VORTEX FLOWMETER
Converter (PA21)
309233
617 1715
120 110100
φ13
4
67
Conduit Connection G34 Conduit Connection G34
30 125
71
41
7411
4
WIRING DIAGRAM
(1) Wiring for converter power source and output
Do not use this conduit connection
Terminal Cover for Maintenance
Terminal label and descriptionLabel Description Remark
POWER 24 to 32VDC DC power 24 to 32VDC
Open drain output (equivalent of open collector output) can be connected up to 30V 50mA
STATUS Status output (open drain)
PULSE Pulse output (open drain)
COMMONDC power (0V)Status output (minus)Pulse output (minus)
EARTH Grounding
Do not use the conduit connection on the terminal cover side For wiring connection specification refer to general specifications Converter on Page 2
Unit in mm
8
GBD110E-6OVAL VORTEX FLOWMETER
CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
For details of individual receiving instruments refer to respective general specification sheets1 A digital filter (SU1301) cannot be connected (The converter is equipped with the equivalent function)2 Separate power source is required when connecting with the totalizer (EL0122)
OVAL MODEL EL4000
Line temperature and pressure are considered approximately constant and correction factor can be multiplied as constant
Line temperature and pressure are automatically compensated and total and instantaneous flow readout (or output) are obtained
Meter body
Meter body
Converter
Converter
Pulse Distributor(SU1508)
orExternal Power Source
Flow Computer(EL4001 series)
4 to 20mADC
Unfactored Pulse
Factored Pulse
Totalizer(EL0122)
Total and Instantaneous Flow rate Readout
PressureTransmitter
ResistanceThermometer
(2)
(2) Wiring between converter and sensor
Converter (PA21)
Sensor terminal box
SIG0VSUPC1C2
SHIELD
SHIE
LDC
2 C1
SUP
0V SIG
Sensor terminal box must be installed using intrinsically safe installation procedure
Terminal label and connecting cable colorConverter terminals Terminals inside sensor terminal box Connecting cable color
SIG SIG White0V 0V Black
SUP SUP RedC1 C1 GreenC2 C2 Yellow
SHIELD SHIELD Twist [RedBlackWhite] [YellowGreen] and shielded cables together and cover the bundle with the accompanying tube then connect to SHIELD terminal
Exclusive cable must be used for connecting the converter and the sensor Either the left or right conduit connection (cable entry) of the sensor terminal box can be used For wiring connection specification refer to general specifications Converter on Page 2
9
GBD110E-6OVAL VORTEX FLOWMETER
INSTALLATION CONDITIONS1 Typical Piping InstructionsIt is required that the flow pattern of the fluid flowing in and out of a vortex flowmeter be as uniform as possible for accurate metering performance Therefore proper flow straightening measures have to be applied when installing a vortex flowmeter The standard piping instructions are shown in the following table
(1) Use an OVAL flow straightener or provide a specified straight pipe (ISO-5167 compliant)
No Piping Arrangement Straight PipeLength (L) Remark
1 OVALs Flow-Straightener
8D Refer to P11
Applicable to Nominal size 25mm or above
12D Refer to GSGCF001
2 Reducer 15D Min A concentric reducer is installed at the upstream of a meter
3 Elbow
23D Min An elbow is installed at the upstream of a meter
25D Min Two elbows are installed at the upstream of a meter
40D Min Two elbows are vertically installed at the upstream of a meter
4 Fully opengate valve 15D Min A full-open gate valve is installed at the upstream of a
meter
5 Partially opengate valve 50D Min A partially open gate valve sharp orifice or something that
markedly disturbs the flow pattern is upstream of meter
Honey VanebullLFlow
L
Flow
Flow
L
L
Flow Straightener
Flow
L
Flow
L
Flow
L
Flow
L
Flow
L
Fully Open
PartiallyOpen
NOTES1 Upstream and downstream pipes adjacent to the flowmeter should be of the same internal
diameter (ID) as the flowmeter (The exclusive flow straightener Honey Vane L and downstream short pipe have the same ID as the flowmeter) The table below shows the standard ID of the flowmeter Confirm the delivery specification in case ID is non-standard
Flowmeter standard IDNominal size ID referenceunder 400mm Sch40
400mm or more Sch20
2 A short pipe section 5D or longer shall be provided downstream of the meter3 For pressure detection provide the probe downstream of the flowmeter (see the right figure)
To avoid disturbances in the flow temperature detection should be made downstream of the flowmeter and at the same time upstream of the control valve
2 Pressure PulsationIn case the flowmeter is installed in the line where instruments that can generate pressure pulsation such as roots blower or compressor is present performance of the flowmeter can be affected by flow pulsation Allowable pulsation pressure is calculated from the following equationNlt 22ρV2 (Pa)where N Pulsation pressure (Pa) ρ Density (kgm3) V Min Velocity (ms)
Even at shutdown pressure pulsation in the process fluid can produce a false output If pressure pulsation is excessive take the following measures① Locate the source of flow pulsation downstream of the flowmeter② Install a pulsation attenuator③ At shutdown of the flow shut off valves upstream and downstream of the flowmeter
2 to 7Dfrom the meter
FLOW
D Nominal size
Pressure detection point
Temperature detection point
Min 1D from pressure detection pointMin 2D from flowmeter
10
GBD110E-6OVAL VORTEX FLOWMETER
FLOW
Honey Vane S
Flowmeter
Min 8D
Honey Vane Outline Dimensions
Nominal size(mm)
Honey Vane S Honey Vane LφD (mm) t (mm) L (mm)
25 75 35 20040 90 54 32050 105 69 40080 134 102 640
100 159 133 800150 220 196 1200200 268 26 1600250 331 323 2000300 376 387 2400
Dimensions for JIS 10K
L
t
φD
t
Honey Vane S Honey Vane L
Installation of Honey Vane S ① Locate the Honey Vane S upstream of the flowmeter ② Provide a short pipe (8D or longer) between Honey Vane S and flowmeter ③ Regarding the bolts and nuts used for connecting JPI flange adopt unified screw threads If it is necessary to use metric screw threads contact OVAL
11
GBD110E-6OVAL VORTEX FLOWMETER
PRECAUTIONS ON USE1 This flowmeter is developed designed and manufactured to be used as a flowmeter for general industrial application
Therefore when it is used for the application where its operation is directly related to the safety of the relevant system or the product is important in the facilities (such as process control and custody transfer) you are requested to ensure sufficient security including safety design redundancy and duplication of the process and implementation of periodic inspection Do not use this flowmeter where its operation and performance directly affect human life
2 When used under appropriate conditions this flowmeter can demonstrate its stable performance without aging degradation of accuracy However malfunction or failure may occur due to various factors Thus examining the operating conditions operating status and importance in the process you should consider periodic maintenance of your flowmeter In order to secure long-term and safe use OVAL recommends the customer to verify the soundness of the flowmeter through periodic inspection every two years For the details of inspection contact the nearest OVAL salesservice office or representatives
3 This flowmeter is manufactured adjusted and inspected to meet the conditions of use The fluid measured flow range pressure temperature etc must be applied under the specified conditions The conditions for use are stated on the nameplate attached on the flowmeter transmitter and specification sheet supplied with the product
4 The materials used in this flowmeter are stated in this document or delivery specification sheet shipped with the equipment Supplied with all the necessary information by the customer OVAL has selected materials that best suit the customer requirements including corrosion resistance However we ask you to understand that the final judgment on the compatibility of the materials in the actual process environment lies with the customer
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
8
GBD110E-6OVAL VORTEX FLOWMETER
CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
For details of individual receiving instruments refer to respective general specification sheets1 A digital filter (SU1301) cannot be connected (The converter is equipped with the equivalent function)2 Separate power source is required when connecting with the totalizer (EL0122)
OVAL MODEL EL4000
Line temperature and pressure are considered approximately constant and correction factor can be multiplied as constant
Line temperature and pressure are automatically compensated and total and instantaneous flow readout (or output) are obtained
Meter body
Meter body
Converter
Converter
Pulse Distributor(SU1508)
orExternal Power Source
Flow Computer(EL4001 series)
4 to 20mADC
Unfactored Pulse
Factored Pulse
Totalizer(EL0122)
Total and Instantaneous Flow rate Readout
PressureTransmitter
ResistanceThermometer
(2)
(2) Wiring between converter and sensor
Converter (PA21)
Sensor terminal box
SIG0VSUPC1C2
SHIELD
SHIE
LDC
2 C1
SUP
0V SIG
Sensor terminal box must be installed using intrinsically safe installation procedure
Terminal label and connecting cable colorConverter terminals Terminals inside sensor terminal box Connecting cable color
SIG SIG White0V 0V Black
SUP SUP RedC1 C1 GreenC2 C2 Yellow
SHIELD SHIELD Twist [RedBlackWhite] [YellowGreen] and shielded cables together and cover the bundle with the accompanying tube then connect to SHIELD terminal
Exclusive cable must be used for connecting the converter and the sensor Either the left or right conduit connection (cable entry) of the sensor terminal box can be used For wiring connection specification refer to general specifications Converter on Page 2
9
GBD110E-6OVAL VORTEX FLOWMETER
INSTALLATION CONDITIONS1 Typical Piping InstructionsIt is required that the flow pattern of the fluid flowing in and out of a vortex flowmeter be as uniform as possible for accurate metering performance Therefore proper flow straightening measures have to be applied when installing a vortex flowmeter The standard piping instructions are shown in the following table
(1) Use an OVAL flow straightener or provide a specified straight pipe (ISO-5167 compliant)
No Piping Arrangement Straight PipeLength (L) Remark
1 OVALs Flow-Straightener
8D Refer to P11
Applicable to Nominal size 25mm or above
12D Refer to GSGCF001
2 Reducer 15D Min A concentric reducer is installed at the upstream of a meter
3 Elbow
23D Min An elbow is installed at the upstream of a meter
25D Min Two elbows are installed at the upstream of a meter
40D Min Two elbows are vertically installed at the upstream of a meter
4 Fully opengate valve 15D Min A full-open gate valve is installed at the upstream of a
meter
5 Partially opengate valve 50D Min A partially open gate valve sharp orifice or something that
markedly disturbs the flow pattern is upstream of meter
Honey VanebullLFlow
L
Flow
Flow
L
L
Flow Straightener
Flow
L
Flow
L
Flow
L
Flow
L
Flow
L
Fully Open
PartiallyOpen
NOTES1 Upstream and downstream pipes adjacent to the flowmeter should be of the same internal
diameter (ID) as the flowmeter (The exclusive flow straightener Honey Vane L and downstream short pipe have the same ID as the flowmeter) The table below shows the standard ID of the flowmeter Confirm the delivery specification in case ID is non-standard
Flowmeter standard IDNominal size ID referenceunder 400mm Sch40
400mm or more Sch20
2 A short pipe section 5D or longer shall be provided downstream of the meter3 For pressure detection provide the probe downstream of the flowmeter (see the right figure)
To avoid disturbances in the flow temperature detection should be made downstream of the flowmeter and at the same time upstream of the control valve
2 Pressure PulsationIn case the flowmeter is installed in the line where instruments that can generate pressure pulsation such as roots blower or compressor is present performance of the flowmeter can be affected by flow pulsation Allowable pulsation pressure is calculated from the following equationNlt 22ρV2 (Pa)where N Pulsation pressure (Pa) ρ Density (kgm3) V Min Velocity (ms)
Even at shutdown pressure pulsation in the process fluid can produce a false output If pressure pulsation is excessive take the following measures① Locate the source of flow pulsation downstream of the flowmeter② Install a pulsation attenuator③ At shutdown of the flow shut off valves upstream and downstream of the flowmeter
2 to 7Dfrom the meter
FLOW
D Nominal size
Pressure detection point
Temperature detection point
Min 1D from pressure detection pointMin 2D from flowmeter
10
GBD110E-6OVAL VORTEX FLOWMETER
FLOW
Honey Vane S
Flowmeter
Min 8D
Honey Vane Outline Dimensions
Nominal size(mm)
Honey Vane S Honey Vane LφD (mm) t (mm) L (mm)
25 75 35 20040 90 54 32050 105 69 40080 134 102 640
100 159 133 800150 220 196 1200200 268 26 1600250 331 323 2000300 376 387 2400
Dimensions for JIS 10K
L
t
φD
t
Honey Vane S Honey Vane L
Installation of Honey Vane S ① Locate the Honey Vane S upstream of the flowmeter ② Provide a short pipe (8D or longer) between Honey Vane S and flowmeter ③ Regarding the bolts and nuts used for connecting JPI flange adopt unified screw threads If it is necessary to use metric screw threads contact OVAL
11
GBD110E-6OVAL VORTEX FLOWMETER
PRECAUTIONS ON USE1 This flowmeter is developed designed and manufactured to be used as a flowmeter for general industrial application
Therefore when it is used for the application where its operation is directly related to the safety of the relevant system or the product is important in the facilities (such as process control and custody transfer) you are requested to ensure sufficient security including safety design redundancy and duplication of the process and implementation of periodic inspection Do not use this flowmeter where its operation and performance directly affect human life
2 When used under appropriate conditions this flowmeter can demonstrate its stable performance without aging degradation of accuracy However malfunction or failure may occur due to various factors Thus examining the operating conditions operating status and importance in the process you should consider periodic maintenance of your flowmeter In order to secure long-term and safe use OVAL recommends the customer to verify the soundness of the flowmeter through periodic inspection every two years For the details of inspection contact the nearest OVAL salesservice office or representatives
3 This flowmeter is manufactured adjusted and inspected to meet the conditions of use The fluid measured flow range pressure temperature etc must be applied under the specified conditions The conditions for use are stated on the nameplate attached on the flowmeter transmitter and specification sheet supplied with the product
4 The materials used in this flowmeter are stated in this document or delivery specification sheet shipped with the equipment Supplied with all the necessary information by the customer OVAL has selected materials that best suit the customer requirements including corrosion resistance However we ask you to understand that the final judgment on the compatibility of the materials in the actual process environment lies with the customer
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
9
GBD110E-6OVAL VORTEX FLOWMETER
INSTALLATION CONDITIONS1 Typical Piping InstructionsIt is required that the flow pattern of the fluid flowing in and out of a vortex flowmeter be as uniform as possible for accurate metering performance Therefore proper flow straightening measures have to be applied when installing a vortex flowmeter The standard piping instructions are shown in the following table
(1) Use an OVAL flow straightener or provide a specified straight pipe (ISO-5167 compliant)
No Piping Arrangement Straight PipeLength (L) Remark
1 OVALs Flow-Straightener
8D Refer to P11
Applicable to Nominal size 25mm or above
12D Refer to GSGCF001
2 Reducer 15D Min A concentric reducer is installed at the upstream of a meter
3 Elbow
23D Min An elbow is installed at the upstream of a meter
25D Min Two elbows are installed at the upstream of a meter
40D Min Two elbows are vertically installed at the upstream of a meter
4 Fully opengate valve 15D Min A full-open gate valve is installed at the upstream of a
meter
5 Partially opengate valve 50D Min A partially open gate valve sharp orifice or something that
markedly disturbs the flow pattern is upstream of meter
Honey VanebullLFlow
L
Flow
Flow
L
L
Flow Straightener
Flow
L
Flow
L
Flow
L
Flow
L
Flow
L
Fully Open
PartiallyOpen
NOTES1 Upstream and downstream pipes adjacent to the flowmeter should be of the same internal
diameter (ID) as the flowmeter (The exclusive flow straightener Honey Vane L and downstream short pipe have the same ID as the flowmeter) The table below shows the standard ID of the flowmeter Confirm the delivery specification in case ID is non-standard
Flowmeter standard IDNominal size ID referenceunder 400mm Sch40
400mm or more Sch20
2 A short pipe section 5D or longer shall be provided downstream of the meter3 For pressure detection provide the probe downstream of the flowmeter (see the right figure)
To avoid disturbances in the flow temperature detection should be made downstream of the flowmeter and at the same time upstream of the control valve
2 Pressure PulsationIn case the flowmeter is installed in the line where instruments that can generate pressure pulsation such as roots blower or compressor is present performance of the flowmeter can be affected by flow pulsation Allowable pulsation pressure is calculated from the following equationNlt 22ρV2 (Pa)where N Pulsation pressure (Pa) ρ Density (kgm3) V Min Velocity (ms)
Even at shutdown pressure pulsation in the process fluid can produce a false output If pressure pulsation is excessive take the following measures① Locate the source of flow pulsation downstream of the flowmeter② Install a pulsation attenuator③ At shutdown of the flow shut off valves upstream and downstream of the flowmeter
2 to 7Dfrom the meter
FLOW
D Nominal size
Pressure detection point
Temperature detection point
Min 1D from pressure detection pointMin 2D from flowmeter
10
GBD110E-6OVAL VORTEX FLOWMETER
FLOW
Honey Vane S
Flowmeter
Min 8D
Honey Vane Outline Dimensions
Nominal size(mm)
Honey Vane S Honey Vane LφD (mm) t (mm) L (mm)
25 75 35 20040 90 54 32050 105 69 40080 134 102 640
100 159 133 800150 220 196 1200200 268 26 1600250 331 323 2000300 376 387 2400
Dimensions for JIS 10K
L
t
φD
t
Honey Vane S Honey Vane L
Installation of Honey Vane S ① Locate the Honey Vane S upstream of the flowmeter ② Provide a short pipe (8D or longer) between Honey Vane S and flowmeter ③ Regarding the bolts and nuts used for connecting JPI flange adopt unified screw threads If it is necessary to use metric screw threads contact OVAL
11
GBD110E-6OVAL VORTEX FLOWMETER
PRECAUTIONS ON USE1 This flowmeter is developed designed and manufactured to be used as a flowmeter for general industrial application
Therefore when it is used for the application where its operation is directly related to the safety of the relevant system or the product is important in the facilities (such as process control and custody transfer) you are requested to ensure sufficient security including safety design redundancy and duplication of the process and implementation of periodic inspection Do not use this flowmeter where its operation and performance directly affect human life
2 When used under appropriate conditions this flowmeter can demonstrate its stable performance without aging degradation of accuracy However malfunction or failure may occur due to various factors Thus examining the operating conditions operating status and importance in the process you should consider periodic maintenance of your flowmeter In order to secure long-term and safe use OVAL recommends the customer to verify the soundness of the flowmeter through periodic inspection every two years For the details of inspection contact the nearest OVAL salesservice office or representatives
3 This flowmeter is manufactured adjusted and inspected to meet the conditions of use The fluid measured flow range pressure temperature etc must be applied under the specified conditions The conditions for use are stated on the nameplate attached on the flowmeter transmitter and specification sheet supplied with the product
4 The materials used in this flowmeter are stated in this document or delivery specification sheet shipped with the equipment Supplied with all the necessary information by the customer OVAL has selected materials that best suit the customer requirements including corrosion resistance However we ask you to understand that the final judgment on the compatibility of the materials in the actual process environment lies with the customer
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
10
GBD110E-6OVAL VORTEX FLOWMETER
FLOW
Honey Vane S
Flowmeter
Min 8D
Honey Vane Outline Dimensions
Nominal size(mm)
Honey Vane S Honey Vane LφD (mm) t (mm) L (mm)
25 75 35 20040 90 54 32050 105 69 40080 134 102 640
100 159 133 800150 220 196 1200200 268 26 1600250 331 323 2000300 376 387 2400
Dimensions for JIS 10K
L
t
φD
t
Honey Vane S Honey Vane L
Installation of Honey Vane S ① Locate the Honey Vane S upstream of the flowmeter ② Provide a short pipe (8D or longer) between Honey Vane S and flowmeter ③ Regarding the bolts and nuts used for connecting JPI flange adopt unified screw threads If it is necessary to use metric screw threads contact OVAL
11
GBD110E-6OVAL VORTEX FLOWMETER
PRECAUTIONS ON USE1 This flowmeter is developed designed and manufactured to be used as a flowmeter for general industrial application
Therefore when it is used for the application where its operation is directly related to the safety of the relevant system or the product is important in the facilities (such as process control and custody transfer) you are requested to ensure sufficient security including safety design redundancy and duplication of the process and implementation of periodic inspection Do not use this flowmeter where its operation and performance directly affect human life
2 When used under appropriate conditions this flowmeter can demonstrate its stable performance without aging degradation of accuracy However malfunction or failure may occur due to various factors Thus examining the operating conditions operating status and importance in the process you should consider periodic maintenance of your flowmeter In order to secure long-term and safe use OVAL recommends the customer to verify the soundness of the flowmeter through periodic inspection every two years For the details of inspection contact the nearest OVAL salesservice office or representatives
3 This flowmeter is manufactured adjusted and inspected to meet the conditions of use The fluid measured flow range pressure temperature etc must be applied under the specified conditions The conditions for use are stated on the nameplate attached on the flowmeter transmitter and specification sheet supplied with the product
4 The materials used in this flowmeter are stated in this document or delivery specification sheet shipped with the equipment Supplied with all the necessary information by the customer OVAL has selected materials that best suit the customer requirements including corrosion resistance However we ask you to understand that the final judgment on the compatibility of the materials in the actual process environment lies with the customer
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
11
GBD110E-6OVAL VORTEX FLOWMETER
PRECAUTIONS ON USE1 This flowmeter is developed designed and manufactured to be used as a flowmeter for general industrial application
Therefore when it is used for the application where its operation is directly related to the safety of the relevant system or the product is important in the facilities (such as process control and custody transfer) you are requested to ensure sufficient security including safety design redundancy and duplication of the process and implementation of periodic inspection Do not use this flowmeter where its operation and performance directly affect human life
2 When used under appropriate conditions this flowmeter can demonstrate its stable performance without aging degradation of accuracy However malfunction or failure may occur due to various factors Thus examining the operating conditions operating status and importance in the process you should consider periodic maintenance of your flowmeter In order to secure long-term and safe use OVAL recommends the customer to verify the soundness of the flowmeter through periodic inspection every two years For the details of inspection contact the nearest OVAL salesservice office or representatives
3 This flowmeter is manufactured adjusted and inspected to meet the conditions of use The fluid measured flow range pressure temperature etc must be applied under the specified conditions The conditions for use are stated on the nameplate attached on the flowmeter transmitter and specification sheet supplied with the product
4 The materials used in this flowmeter are stated in this document or delivery specification sheet shipped with the equipment Supplied with all the necessary information by the customer OVAL has selected materials that best suit the customer requirements including corrosion resistance However we ask you to understand that the final judgment on the compatibility of the materials in the actual process environment lies with the customer
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
12
GBD110E-6OVAL VORTEX FLOWMETER
⑯ Regulations0 Standard No applicable law and regulations
G High Pressure Gas Safety Act(Approved product) wMaterial test certificate
H High Pressure Gas Safety Act(Individual test)
wMaterial test certificate (Designed on PO issued)
L Gas Business Act(Approved product)
wMaterial test certificate (Designed on PO issued)
M Gas Business Act wMaterial test certificate
Q Electricity Business Act(Certificate required)
wMaterial test certificate (Designed on PO issued)
R Electricity Business Act wMaterial test certificateT Fire Service Act wMaterial test certificateF wMaterial test certificate⑰ mdash⑱ Converter (Power supply)5 PA21 External power supply (24 to 32VDC)9 Special⑲ Converter configuration2 Separately mounted⑳ Display0 Digital indicator ( instantaneous flow indication) PulseG Open drain pulse Communication interfaceN Always N Version codeB Version code B mdash Sensor configuration1 External sensor Sensor type1 Standard (Nominal Size 20 to 500mm)2 Gas-purge (Nominal Size 50 to 500mm) Max operating pressure 1MPa at max3 Gas-purge (For low temp or high temp) (Designed on PO issued)4 Double sensor (Designed on PO issued)5 Double sensor wMagnet filter (Designed on PO issued)9 Special Accompanied cable length0 10m (Standard)9 Specific cable length (Max 30m) Special0 StandardZ When Special or Designed on PO issued is chosen
1 Flange face to fit with the gasket is RF Flange serration according to ASME standard complies with ASME B 165minus20032 Make sure to use the dedicated explosionproof cable gland supplied with the flowmeter
PRODUCT CODE EXPLANATION
Main code
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
① ② ③ Model V F W OVAL VORTEX FLOWMETER Wafer type (Nominal Size 20 to 150mm)
V F Y OVAL VORTEX FLOWMETER Wafer type spigot joint type(Nominal Size 25 to 150mm)
V F F OVAL VORTEX FLOWMETER Flanged type (Nominal Size 200 to 500mm)④ ⑤ ⑥ Nominal Size0 2 0 20mm (34Prime)0 2 5 25mm (1Prime)0 3 2 32mm (114Prime)0 4 0 40mm (112Prime) (Designed on PO issued)0 5 0 50mm (2Prime)0 8 0 80mm (3Prime)1 0 0 100mm (4Prime)1 5 0 150mm (6Prime)2 0 0 200mm (8Prime)2 5 0 250mm (10Prime)3 0 0 300mm (12Prime)3 5 0 350mm (14Prime) (Designed on PO issued)4 0 0 400mm (16Prime)4 5 0 450mm (18Prime) (Designed on PO issued)5 0 0 500mm (20Prime)⑦ mdash⑧ Fluid categoryG Gas⑨ Temp category0 Standard Max fluid temperature 130⑩ Major Parts Material
DSUS304 or SUS304 equivalent Allowed lowest temp -20(Nominal Size 20 to 500mm)
GCarbon steel (STPG370SFVC2ASS400) Allowed lowest temp 0(Nominal Size 200 to 500mm)
Z Special⑪ ⑫ Process connection 1J 0 JIS10K FFJ 1 JIS10K RF For wafer type FF is also availableJ B JIS16K RF For wafer type FF is also availableJ 2 JIS20K RF For wafer type FF is also availableJ 3 JIS30K RF For wafer type FF is also availableP 1 JPI150 RF For wafer type FF is also availableP 3 JPI300 RF For wafer type FF is also availableP 6 JPI600 RF (Designed on PO issued)A 1 ASME150 RF For wafer type FF is also availableA 3 ASME300 RF For wafer type FF is also availableA 6 ASME600 RF (Designed on PO issued)Z 9 Special⑬ mdash⑭ ⑮ Explosion-proof0 0 Non-explosionproofJ 4 TIIShellipsensor T4 (transmitter T6) 2
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
13
GBD110E-6OVAL VORTEX FLOWMETER
Additional codeCategory of High Pressure GasH P 0 Other than High Pressure GasH P 1 Toxic gas and flammable gasH P 2 Toxic gasH P 3 Flammable gasH P 4 Other than toxic or flammable gasAccuracyF 1 0 plusmn100 RDF 1 0 plusmn100 FSSpecial test (instrumental error)
A 0 1 Actual flow test B (Certificate) Witnessed accuracy test not applicable
A 0 3 Actual flow test A (Report) Witnessed accuracy test applicableA 1 0 Taxed custody transferA 2 0 By certified measurer
A 9 9 Designation of instrumentalerror test method
Designation of test point andor addition etc
Direction of sensor terminal box
F L 1 Flow direction and entry of electric conduit are in verticalwith the long lid on flow inlet side
F L 2 Direction of flow and entry of electric conduit is samewith the long lid is in front when LrarrR
F L 3 Flow direction and entry of electric conduit are in verticalwith the long lid on flow outlet side
F L 4 Direction of flow and entry of electric conduit is samewith the long lid is behind when LrarrR
Designated special paint on bodyB C 0 Corrosion proofB A 0 Salinity and acid tolerance Limited to 120 and lowerB X 0 Customer designationDesignated special paint on transmitterS F 0 Corrosion proof SpecialS D 0 Salinity toleranceS E 0 Acid tolerance SpecialS X 0 Customer designated paint SpecialCleansingT W 0 Non-oil and non-water treatment
1 Need not choose the item when required to implement in Japan law and regulation Only for items other than the legal requirement customer can choose as special requirement
DocumentD S J DWG and specifications for approval (Japanese)D S E DWG and specifications for approval (English)D R 0 Re-submission of DWG with specificationsD C J Final DWG (Japanese)D C E Final DWG (English)D P J Calculation sheet (Japanese)D P E Calculation sheet (English) Unavailable for the Japan law compliantS E J Instrumental error test report (Japanese)S E E Instrumental error test report (English)S T J Pressure test report (Japanese)S T E Pressure test report (English)S A J Airtight test report (Japanese)S A E Airtight test report (English)D D J Dimensional check record (Japanese)D D E Dimensional check record (English)S P J Penetrant test report (Japanese) Welded part of pressure resistant vesselS P E Penetrant test report (English) Welded part of pressure resistant vesselS M J Magnetic particle inspection (Japanese) Welded part of pressure resistant vesselS M E Magnetic particle inspection (English) Welded part of pressure resistant vesselS R J Radiographic inspection (Japanese) Welded part of pressure resistant vesselS R E Radiographic inspection (English) Welded part of pressure resistant vesselS U J Ultrasonic inspection (Japanese) Welded part of pressure resistant vesselS U E Ultrasonic inspection (English) Welded part of pressure resistant vesselS X J PMI test report (Japanese)S X E PMI test report (English)S S J Impact test report (Japanese)S S E Impact test report (English)D Y J WPSPQR (Japanese)D Y E WPSPQR (English)D 9 J Photo (Japanese)D 9 E Photo (English)D T J Inspection procedure (Japanese)D T E Inspection procedure (English)C A J Inspection certificate A set Only JapaneseC B J Inspection certificate B set Only JapaneseC C J Inspection certificate C set Only JapaneseC D J Inspection certificate D set Only JapaneseWitnessed by customerV 1 0 Required
PRODUCT CODE EXPLANATION
⑧-⑥⑤④③②① ⑯⑮⑭-⑫⑪⑩⑨ - ㉒㉑⑳ -㉓ ㉕⑲⑱Model
Temp category
Nominal SizeFluid category
Converter configuration
Version codeSensor configuration
Sensor typeAccompanied cable length
Special
Communication interfacePulse
DisplayConverter (Power supply)
Major Parts Material
Explosion-proofProcess connection
Main code
Regulations
㉗㉖ ㉘ Additional code
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
14
GBD110E-6OVAL VORTEX FLOWMETER
FORMER PRODUCT CODE EXPLANATIONThe new product code has been implemented since April 2017
Therefore the product code explanation of the old product code will not be updated after April 2017Contact OVAL if you wish to order with the old product code for reasons such as type approval
Item Product Code Description① ② ③ ④ ⑤ ⑥ minus ⑦ ⑧ ⑨ ⑩ ⑪ minus ⑫ ⑬ ⑭ minus ⑮ ⑯ ⑰ ⑱ ⑲ ⑳ minus
ModelV F W Wafer type (Nominal size 20mm to 150mm)V F Y Wafer spigot joint type (Nominal size 25mm to 150mm)V F F Flange type (Nominal size 200mm to 500mm)
Nominal size
0 2 0 20mm0 2 5 25mm0 3 2 32mm0 4 0 40mm (made-to-order)0 5 0 50mm0 8 0 80mm1 0 0 100mm1 5 0 150mm2 0 0 200mm2 5 0 250mm3 0 0 300mm3 5 0 350mm (made-to-order)4 0 0 400mm4 5 0 450mm (made-to-order)5 0 0 500mm
minusFluid category G GasTemperature category 0 Standard Max fluid temperature 130
Major parts material
D SUS304 or SUS304 equivalent Allowable temp low limit minus20(Nominal size 20mm to 500mm)
G Carbon steel (STPG370STPY400SFVC2ASS400) Allowable temp low limit 0(Nominal size 200mm to 500mm)
Z Other than above
Process connection
J 1 JIS 10K
Flange face of the flange type model is RF
J B JIS 16KJ 2 JIS 20KJ 3 JIS 30KA 1 ASME 150A 3 ASME 300A 6 ASME 600 (made-to-order)P 1 JPI 150P 3 JPI 300P 6 JPI 600 (made-to-order)Z 9 Other than above
minus
Explosionproof rating0 Non-explosionproofJ TIIS
Explosionproof temperature class0 Non-explosionproof4 Sensor T4 (Converter T6)
Regulations
0 Standard (No regulation applied)
G High Pressure Gas Safety Act wMaterial test report(Approved product)
H High Pressure Gas Safety Act wMaterial test report (made-to-order)(Equipment test accepted product)
L Gas Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
M Gas Business Act wMaterial test report (made-to-order)
Q Electricity Business Act wMaterial test report (made-to-order)(Subject to Japan Welding Engineering Standards)
R Electricity Business Act wMaterial test report (made-to-order)F w Material test report
minusConverter (power source) 5 PA21 (24 to 32VDC)Converter construction 2 Separately mountedDisplay 0 w Digital indicator ( instantaneous flow rate display)Output G Open drain pulseCommunication specification NVersion B
minusSensor configuration 1 Externally installed sensor
Sensor type
1 Standard (Nominal size 20mm to 500mm)
2 Gas purge type (Nominal size 50mm to 500mm) Max operating pressure under 1MPa
4 Double sensor (made-to-order)9 Other than above
Accompanied cable length0 10m9 Specific cable length (Max 30m)
Special0 StandardZ Special (meter ID flange-to-flange dimension etc is non-standard)
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
15
GBD110E-6OVAL VORTEX FLOWMETER
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-
初版 改訂 印刷1601 1812
GSNoGBD110E
The specification as of December 2018 is stated in this GS Sheet Specifications and design are subject to change without notice
Sales Representative
GBD110E-6OVAL VORTEX FLOWMETER
PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIREFill in the blanks Tick the boxes that apply
Item Description
1 Name of gas
2 Application
3 Flow range Max Normal Min m3h [normal] m3h [actual]
4 Temperature range Max Normal Min
5 Pressure range Max Normal Min MPa [gauge]
6 Compensation reference Temperature ref Pressure ref MPa [gauge]
7 Compression coefficient Z Z0
8 Density or specific gravity Density kgm3 [normal] kgm3 [actual] Specific gravity (Air=I)
9 Viscosity Viscosity mPabulls mm2s at
10 ConnectionsNominal size mm inch Flange rating JIS K RF ASME RFSch FF JPI RF
11 Flow straightening pipeRequired (Flow straightener Honey Vane S Honey Vane L and downstream short pipe)Not required (Please supply straight pipe of appropriate length ID and Sch No)
12 Compensation range Temperature to Pressure to MPa [gauge]
13 Accuracy test Required Not required
14 Receiving instrument Specify the model and specification referring to P8 CONNECTION TO RECEIVING INSTRUMENTS on P8
15 Compensation Not required
16 Explosionproof Required Not required
17 Regulations Required Not required
18 Cable length Standard 10m Specific length m
19 Other considerations
- GENERAL
- FEATURES
- GENERAL SPECIFICATIONS
- FLOW RANGES
- PERFORMANCE CHARACTERISTICS
- OUTLINE DIMENSIONS (Standard type)
- OUTLINE DIMENSIONS (Gas purge type)
- WIRING DIAGRAM
- CONNECTION TO RECEIVING INSTRUMENTS (EXAMPLE)
- INSTALLATION CONDITIONS
- PRECAUTIONS ON USE
- PRODUCT CODE EXPLANATION Main code
- PRODUCT CODE EXPLANATION Additional code
- FORMER PRODUCT CODE EXPLANATION
- PLEASE SUPPLY THE FOLLOWING INFORMATION WHEN YOU INQUIRE
-