Outdoor package transformer substations
Ural Company for Transformer Technologies, LLC
Ural Company for Transformer Technologies, LLC
4th floor, 5 Marshala Zhukova St., Ekaterinburg, 620014
Tel/fax: +7 (343) 310-04-40E-mail: [email protected]
www.uztt.ru
UZTT branch office addresses:
office 113,. 54 Karla Marksa St., Chelyabinsk, 454091
Tel/fax: +7 (351) 240-02-84E-mail: [email protected]
www.ural-zavod.ru
office 343, 35 Kommunisticheskaya St., Novosibirsk, 630007
Tel/fax: +7 (383) 249-32-82E-mail: [email protected]
www.uztt-nsk.ru
room 6-N, 23 letter А Vladimirsky avenue, Saint-Petersburg, 191002
Tel/fax: +7 (812) 600-36-31E-mail: [email protected]
www.uztt-spb.ru
Moscow, tel. +7 (495) 661-31-01
Outdoor package transformer substation
1
ww
w.u
ztt.
ru
Ural Company for Transformer TechnologiesSince 2000 the UZTT transformer factory for high-voltage equipment, a manufacturer and ven-dor of package transformer substations (KTP substations), has its own manufacturing of Pack-age Transformer Substations, transformers and sells its products directly from the factory. The UZTT Company is specialized in manufacturing of LOW-VOLTAGE and HIGH-VOLTAGE equipment for electrical power supply systems used in industrial and civil construction, agriculture, oil and gas industries, and mining operations
The UZTT manufacturing factory offers the following range of services:
• Designing of KTP substations.• Complete cycle of manufacturing of electrical equipment, including KTP substations.• Mounting of package transformer substations, electrical installation work, substations
construction and KTP installation.• Manufacturing of oil-cooled power transformers and other components for substations.• Selling of finished electrical equipment, available and upon request.
UZTT constantly improves the technological process, searches for non-conventional solutions which allows to adapt to changing market conditions. The company is developing new model forms of package transformer substations, extending its product lines and equipment power range. Being targeted at market requirements, the factory manufactures 14 varieties of pack-age transformer substations in three options:
• “Economy” - electric power substations with hammer finish paint coating.• “Standard” - transformer substations with powder paint coating.• “Elite” - KTP with ABB; Schneider Electric, Siemens components and powder paint coat-
ing, in color to meet customer requirements. Package transformer substations of «Econ-omy» class and “Standard” substations can have components from domestic and foreign manufacturers.
Being committed to the principle “the customer comes first”, the highly skilled engineers and technicians of the UZTT Company use a professional approach in their solutions, placing high quality of customer service as a priority in their operations.
Our objective is long-term and mutually beneficial cooperation. The distinguishing feature of our products is good value for money. This aspect is highly appreciated by our regular partners, hav-ing contributed to our today’s success and our future prospects for its amplification.
Since July 2008 the UZTT electromechanical plant has been an official supplier for the Ekater-inburg Electric Grid Company. We offer our regular customers different ways of work: credit on goods, deferred payments, and customer-friendly system of discounts.
Products go through stringent quality control. The Ekaterinburg transformer factory, UZTT fac-tory, will carry out projects for transformer substation power supply, making every effort to en-hance quality of its products made with application of advanced equipment from foreign man-ufacturers. All the products are certified and comply with GOST and TU national standards.
Outdoor package transformer substation
2
ww
w.u
ztt.
ru
Table оf сontentsKtp specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Certificate of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Kiosk-type outdoor package transformer substations1. Type – single-ended air (cable)
1.1. Single-transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6General view and overall dimensions of KTP-TK substation . . . . . . . . . . . . . . . . . . 6General view and overall dimensions of KTP-TV substation . . . . . . . . . . . . . . . . . . 6General view and overall dimensions of KTP-TKu substation . . . . . . . . . . . . . . . . . 7General view and overall dimensions of KTP-TVu substation . . . . . . . . . . . . . . . . . 7Electrical schematic diagram of KTP-TK(TV) 25-400/10(6)/0,4 . . . . . . . . . . . . . . . 8Electrical schematic diagram of KTP-TK(TV) 630-1000/10(6)/0,4 . . . . . . . . . . . . . 9
1.2. Double-transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10General view and overall dimensions of 2KTP-TK substation . . . . . . . . . . . . . . . . . 10General view and overall dimensions of 2KTP-TV substation . . . . . . . . . . . . . . . . . 10Electrical schematic diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2. Type – double-ended air (cable)
2.1. Single-transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23General view and overall dimensions of KTP-PK substation . . . . . . . . . . . . . . . . . . 23General view and overall dimensions of KTP-PV substation . . . . . . . . . . . . . . . . . . 23Electrical schematic diagram of KTP-TK(TV) 25-400/10(6)/0,4 . . . . . . . . . . . . . . . 24Electrical schematic diagram of KTP-TK(TV) 630-1000/10(6)/0,4 . . . . . . . . . . . . . 25
2.2. Double-transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26General view and overall dimensions of 2KTP-TK substation . . . . . . . . . . . . . . . . . 26General view and overall dimensions of 2KTP-TV substation . . . . . . . . . . . . . . . . . 26Electrical schematic diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Pole-mountedGeneral view and overall dimensions of KTP-VS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Electrical schematic diagram of KTP-VS 25-250/10(6)/0,4 . . . . . . . . . . . . . . . . . . . . 36
Mast-mountedGeneral view and overall dimensions of KTP-VM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Electrical schematic diagram of KTP-VM 25-250/10(6)/0,4 . . . . . . . . . . . . . . . . . . . 38
Mobile (Open-pit)General view of PKTK substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Overall dimensions of PKTP substation . . . . . . . . . . . . . . . . . . . . . . . . . 40Overall dimensions of PKTP substation (kiosk) . . . . . . . . . . . . . . . . . . . . . 40
Standard components of kiosk-type, pole-mountedand mast-mounted substations
Table 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Container-type substations with maintenance corridorsGeneral view of container-type substation . . . . . . . . . . . . . . . . . . . . . . . . 42Scheme of equipment installation inside KTP (examples) . . . . . . . . . . . . . . . . 43Questionnaire for kiosk-type, pole-mounted and mast-mounted KTP . . . . . . . . . 44
I
II
III
IV
V
VI
Outdoor package transformer substation
3
ww
w.u
ztt.
ru
SpecificationsCertificate No. ROSS RU.AV28.B00803
Outdoor package transformer substation (KTP) with power of 25-1000 kVA and voltage of 10 (6) / 0,4 (0,23) kV, with cable and air input on the high-voltage side, cable or air output on the low-voltage side is intended for receiving electric power of alternating three-phase current with industrial frequency of 50 Hz, voltage of 10 (6) kV, converting it into electric power with voltage of 0.4 (0.23) kV and distributing it to consumers.
It is used to supply power to industrial, agricultural and utility facilities within loop or radial sys-tems of distribution networks.
The substation housing is metal (standard or with heat insulation). Fire resistance rating of con-struction elements is IV according to SNiP 21-09-97 “Fire safety of buildings and constructions”.
The substation housing is designed as a welded construction and serves as a supporting struc-ture, withstanding even the most severe dynamic loads. It provides easy access for mainte-nance and repair of high-voltage and low-voltage equipment.
Meets the requirements of regulatory documents: GOST 14695-80*, GOST 1516.3-96, TU 3412-005-96418566-09.
Structure of KTP reference designation and configuration
X1 – number of power transformers (no sign if one transformer);
KTP – product line letter designation: Package Transformer Substa-
tion;
Х2 – configuration type: P – double-ended, T – single-ended (except
mast-mounted and pole-mounted substations);
ХЗ – HV inputs configuration: V – air, K – cable;
Х4 – power of power transformer, kVA;
Х5 – rated voltage on the HV side, kV;
0,4 (0,23) – rated voltage on the LV side, kV:
U1 – climatic configuration and location category according
to GOST 15150-69.
KTP – product line letter designation:
Package Transformer Substation;
V – air;
Х1 – configuration type: M – mast-mounted, S – pole-mounted;
Х2 – power of power transformer, kVA;
ХЗ – rated voltage on the HV side, kV;
0,4 (0,23) – rated voltage on the LV side, kV;
U1 – climatic configuration and location category according
to GOST 15150-69.
KTP – V Х1 / Х2 – ХЗ / 0,4 (0,23) U1
Х1 KTP – Х2 ХЗ /Х4–Х5 / 0,4 (0,23) U1
Outdoor package transformer substation
4
ww
w.u
ztt.
ru
Normal operation of substation is provided when:
• the installation height is no more than 1000 m above sea level;• the ambient air temperature is between minus 40 C deg. and plus 40 C deg., as well as the
incidental temperature drop is up to minus the 45 C deg.;• the daily average relative air moisture is up to 80 % at plus 15 C deg.;• there is no current-conducting dust, chemically active gases and evaporations in the en-
vironment.
KTP (except PKTP) is not intended for operation in the conditions of:
• shaking, vibration, blows;• dangerously explosive places;• the ambient air shouldn’t contain acrid vapors, dust and gases in concentrations that
break the KTP operation and destroy metals and insulation.
KTP protection rating in accordance with GOST-14254 is IP-44.
Insulation resistance:
• on the LV side with respect to the housing is no less than 0.5 megohm; • on the HV side with respect to the housing• and other earthed poles – no less than 1000 megohms;
Electrodynamic endurance of VN compartment buses is 51 kA;
• for KTP-VM – 16 kА;
Short-time thermal current of VN compartment buses is 20 kA;
• for KTP-VM – 6.3 kA.
Overall dimensions and weight of KTP are specified in table 1.
KTP designationLength,
no more than, mm
Width, no more than,
mm
Height, no more than,
mm
Weight, no more than,
kg
KTP – PV 100...1000 – 10 (6)/0,4 U1 3000 2100 4000 1300
KTP – TV 25...1000 – 10 (6)0,4 U1 2000 2100 4000 1000
KTP – PK 100...1000 – 10 (6)/0,4 U1 3000 2100 2400 1300
KTP – TK 25...1000 – 10 (6)/0,4 U1 2600 2100 2400 1200
2KTP – PV 100...1000 – 10(6)/0,4 U1 3000 5000 4000 2800
2KTP – PK 100...1000 – 10(6)/0,4 U1 3000 5000 2400 2650
2KTP – TV 100...1000 – 10(6)/0,4 U1 3000 5000 4000 2700
2KTP – TK 100...1000 – 10(6)/0,4 U1 3000 5000 2400 2550
KTP – VM 25...250 – 10(6)/0,4 U1 1500 1200 2800 220
KTP – VS 25...250 – 10(6)/0,4(0,23) U1 1000 1200 6000 300
KTPu – TV 25...160 – 10 (6)/0,4 U1 1500 1800 4000 700
Table 1.
Outdoor package transformer substation
5
ww
w.u
ztt.
ru
Certificate ROSS RU.AB28.B00803
Outdoor package transformer substation
6
ww
w.u
ztt.
ru
I. Kiosk-type outdoor substations
1. Type – single-ended air (cable) 1.1. Single-transformer
Single-ended KTP with the cable input (Fig. 1) and single-ended KTP with the air input (Fig. 2) can be produced for the transformer power between 25 and 1000 kVA.
Upon request they can be produced for the transformer power of 1600 and 2500 kVA.
KTP-TK(TV) substations with power of 25-400 kVа can have a smaller-size configuration (Fig. 3,4).
Fig. 1. General view and overall dimensions of KTP-TK substation.
Fig. 2. General view and overall dimensions of KTP-TV substation
Dimensions of KTP with power more than 630 kVA are determined according to the particular order.
HousingPower transformer compartment
Air input
Housing
2100 1860
2400
4000
Power transformer compartment
Outdoor package transformer substation
7
ww
w.u
ztt.
ru
Fig. 3. General view and overall dimensions of KTP-TKu substation.
Fig. 4. General view and overall dimensions of KTP-TV substationу.
Housing Power transformer compartment
Power transformer compartment
1500
1500
1700
2600
2150
3762
2150
Air input
Housing
Outdoor package transformer substation
8
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name Quantity1 QS1 Disconnector RVZ 10(6) kV (for KTP-TK) 1 2 QSG Earthing disconnector 1 3 FV1-FV6 Overvoltage suppressor OPN a 3 4 FU1…FU3 Fuse PKT 10(6) kV 3 5 QS2 Disconnector 0.4 kV 1 6 TA1…TA3 Current transformer 3 7 QF1 Automatic circuit breaker 16 A 1 8 QF2, QF3 Automatic circuit breaker 10 A 29 Р1 Electricity meter 1 10 KL(BL) Photoswitch (photoswitch sensor) 1 11 EL Lamp E27 1 12 T1 Step-down transformer 220/12 V 1 13 PV Voltmeter 1 12 PA Ammeter 3 15 SA Switch 0.4 kV 1 16 KM Magnetic starter PM 1 17 RK1, RK2 Thermistor 2 18 XS Socket outlet 1 19 QF1- QF n Automatic circuit breaker 1-n 20 T Power transformer with power of 25-400 kVа 1
Package transformer substation ktP-tk(tv) 25-400/10(6)/0,4 Electrical schematic diagram. Diagram no. 1
Street lighting
Outgoing lines
0.4 Kv
Input 10(6) kv
Equipment list
Outdoor package transformer substation
9
ww
w.u
ztt.
ruS. No. Ref. Numeral Name Quantity
1. QW Load-break switch 10(6) kV 1 2. QSG Earthing disconnector 1 3. FV1-FV6 Overvoltage suppressor OPN 3 4. FU1...FU3 Fuse PKT 10(6) kV 3 5. QS Disconnector 0.4 kV 1 6 TA1…TA3 Current transformer 3 7. QF1 Automatic circuit breaker 16 A 1 8 QF2, QF3 Automatic circuit breaker 10 A 2 9. P1 Electricity meter 1 10. KL(BL) Photoswitch (photoswitch sensor) 1 11 EL Lamp E27 1 12. T1 Step-down transformer 220/12 V 1 13. PV Voltmeter 1 14. PA Ammeter 3 15. SA Switch 0.4 kV 1 16. KM Magnetic starter PM 1 17. RK1, RK2 Thermistor 2 18. XS Socket outlet 1 19. QF1- QFn Automatic circuit breaker 1-n 20. Т Power transformer with power of 630-100 kVa 1
Package transformer substation ktP-tk(tv) 630-1000/10(6)/0,4Electrical schematic diagram. Diagram no. 2
Street lighting
Outgoing lines
0.4 Kv
Input 10(6) kv
Equipment list
Outdoor package transformer substation
10
ww
w.u
ztt.
ru
Type – single-ended air (cable)
1.2. Double-transformerSingle-ended 2KTP with the cable input (Fig. 5) and single-ended 2KTP with the air input (Fig. 6) can be produced for the transformer power be-tween 25 and 1000 kVA.
Upon request they can be produced for the trans-former power of 1600 and 2500 kVA.
Fig. 5. General view and overall dimensions of 2KTP-TK
1. For Diagrams No. 7...10; 2. For Diagrams No. 11...14;For Diagrams No. 15...18 dimensions are determined according to particular order.
Fig. 6. Overall dimensions of 2KTP-TV
1. For Diagrams No. 7...10; 2. For Diagrams No. 11...14;For Diagrams No. 15...18 dimensions are determined according to particular order.
Housing
Housing
Power transformer compartment
Power transformer compartment
Air input
2100
2100
2100
2100
2400
4000
2400
5000
5000
27601, (3040)2
27601, (3040)2
Outdoor package transformer substation
11
ww
w.u
ztt.
ruS. No. Ref. Numeral Name Quantity
1. QS1.1, QS2.1 Disconnector RVZ 10(6) kV 2 2. QSG1.1, QSG2.l Earthing disconnector 10(6) kV 2 3. FV1- FV12 Valve arrester or OPN 12 4. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 6. TA1…TA6 Current transformer 6 7. QF1, QF4 Automatic circuit breaker 16 A 2 8. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 9. PI1, PI2 Electricity meter 2 10. KL(BL) Photoswitch (photoswitch sensor) 211. EL Lamp E27 2 12. T1 Step-down transformer 220/12 V 2 13. PV Voltmeter 2 14. PA Ammeter 6 15. SA Switch 0.4 kV 2 16. KM Magnetic starter PM 2 17. RK1, RK2 Thermistor 4 18. XS Socket outlet 2 19. QF1- QFn Automatic circuit breaker 1-n 20. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-tv(tk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 7
Street lightingStreet lighting
Outgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Equipment list
Outdoor package transformer substation
12
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name: Quantity 1. QS1.1, QS2.1 Disconnector RVZ 10(6) kV 2 2. QSG1.1, QSG2.l Earthing disconnector 10(6) kV 2 3. FV1- FV12 Valve arrester or OPN 12 4. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QF1, 1QF2, 2QF1 Automatic circuit breaker 0.4 kV 3 6. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 7. ТА1... ТА6 Current transformer 6 8. QF1, QF4 Automatic circuit breaker 16 A 2 9. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 10. PI1, PI2 Electricity meter 2 11. KL(BL) Photoswitch (photoswitch sensor) 2 12. EL Lamp E27 2 13. T1 Step-down transformer 220/12 V 2 14. PV Voltmeter 2 15. PA Ammeter 6 16. SA Switch 0.4 kV 2 17. KM Magnetic starter PM 2 18. RK1, RK2 Thermistor 4 19. XS Socket outlet 2 20. QF1- QFn Automatic circuit breaker 1-n 21. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-tv(tk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 8
Equipment list
Street lightingStreet lighting
Outgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
13
ww
w.u
ztt.
ruS. No. Ref. Numeral Name: Quantity
1. QW1.1, QW2.1 Load-break switch 10(6) kV 2 2. QSG1.1, QSG2.l Earthing disconnector 10(6) kV 2 3. FV1- FV12 Valve arrester or OPN 12 4. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 6. ТА1... ТА6 Current transformer 6 7. QF1, QF4 Automatic circuit breaker 16 A 2 8. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 9. PI1, PI2 Electricity meter 2 10. KL(BL) Photoswitch (photoswitch sensor) 2 11. EL Lamp E27 212. T1 Step-down transformer 220/12 V 2 13. PV Voltmeter 2 14. PA Ammeter 6 15. SA Switch 0.4 kV 2 16. KM Magnetic starter PM 2 17. RK1, RK2 Thermistor 4 18. XS Socket outlet 2 19. QF1- QFn Automatic circuit breaker 1-n 20. T1, T2 Power transformer 630-1000 kVа 2 21. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-tv(tk) 630-1000/10(6)/0,4Electrical schematic diagram. Diagram no. 9
Equipment list
Street lightingStreet lighting
Outgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
14
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name: Quantity 1. QW1.1, QW2.1 Load-break switch 10(6) kV 22. QSG1.1, QSG2.l Earthing disconnector 10(6) kV 23. FV1- FV12 Valve arrester or OPN 12 4. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QF1, 1QF2, 2QF1 Automatic circuit breaker 0.4 kV 3 6. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 7. ТА1... ТА6 Current transformer 6 8. QF1, QF4 Automatic circuit breaker 16 A 29. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 10. PI1, PI2 Electricity meter 211. KL(BL) Photoswitch (photoswitch sensor) 212. EL Lamp E27 213. T1 Step-down transformer 220/12 V 2. 14. PV Voltmeter 2 15. PA Ammeter 6 16. SA Switch 0.4 kV 2 17. KM Magnetic starter PM 2 18. RK1, RK2 Thermistor 4 19. XS Socket outlet 2 20. QF1- QFn Automatic circuit breaker 1-n 21. T1, T2 Power transformer 630-1000 kVа 2
Package transformer substation 2ktP-tv(tk) 630-1000/10(6)/0,4Electrical schematic diagram. Diagram no. 10
Equipment list
Street lightingStreet lighting
V VOutgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
15
ww
w.u
ztt.
ruS. No. Ref. Numeral Name: Quantity
1. QW1.1, QW2.1 Load-break switch 10(6) kV 2 2. QSG1.1- QSG1.3, QSG2.1- QSG2.3 Earthing disconnector 10(6) kV 6 3. QS1.1, QS1.2, QS2.1, QS2.2 Disconnector 10(6) kV 4 4. FV1- FV12 Valve arrester or OPN 12 5. FU1…FU6 Fuse PKT 10(6) kV 6 6. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 7. ТА1... ТА6 Current transformer 68. QF1, QF4 Automatic circuit breaker 16 A 2 9. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 10. PI1, PI2 Electricity meter 2 11. KL(BL) Photoswitch (photoswitch sensor) 2 12. EL Lamp E27 2 13. T1 Step-down transformer 220/12 V 2 14. PV Voltmeter 2 15. PA Ammeter 6 16. SA Switch 0.4 kV 2 17. KM Magnetic starter PM 2 18. RK1, RK2 Thermistor 4 19. XS Socket outlet 2 20. QF1- QFn Automatic circuit breaker 1-n 21. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-tv(tk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 11
Equipment list
Street lightingStreet lighting
V VOutgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
16
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name: Quantity 1. QW1.1, QW2.1 Load-break switch 10(6) kV 2 2. QSG1.1- QSG1.3, QSG2.1- QSG2.3 Earthing disconnector 10(6) kV 6 3. QS1.1, QS1.2, QS2.1, QS2.2 Disconnector 10(6) kV 4 4. FV1- FV12 Valve arrester or OPN 12 5. FU1…FU6 Fuse PKT 10(6) kV 6 6. 1QF1, 1QF2, 2QF1 Automatic circuit breaker 0.4 kV 3 7. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 8. ТА1... ТА6 Current transformer 6 9. QF1, QF4 Automatic circuit breaker 16 A 2 10. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 11. PI1, PI2 Electricity meter 2 12. KL(BL) Photoswitch (photoswitch sensor) 2 13. EL Lamp E27 2 14. T1 Step-down transformer 220/12 V 2 15. PV Voltmeter 2 16. PA Ammeter 6 17. SA Switch 0.4 kV 2 18. KM Magnetic starter PM 2 19. RK1, RK2 Thermistor 4 20. XS Socket outlet 2 21. QF1- QFn Automatic circuit breaker 1-n 22. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-tv(tk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 12
Equipment list
Street lightingStreet lighting
V VOutgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
17
ww
w.u
ztt.
ruS. No. Ref. Numeral Name: Quantity
1. QW1.1-QW1.3, QW2.1-QW2.3 Load-break switch 10(6) kV 6 2. QSG1.1- QSG1.3, QSG2.1- QSG2.3 Earthing disconnector 10(6) kV 6 3. FV1- FV12 Valve arrester or OPN 12 4. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 6. ТА1... ТА6 Current transformer 6 7. QF1, QF4 Automatic circuit breaker 16 A 2 8. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 9. PI1, PI2 Electricity meter 2 10. KL(BL) Photoswitch (photoswitch sensor) 2 11. EL Lamp E27 2 12. T1 Step-down transformer 220/12 V 2 13. PV Voltmeter 2 14. PA Ammeter 6 15. SA Switch 0.4 kV 2 16. KM Magnetic starter PM 2 17. RK1, RK2 Thermistor 4 18. XS Socket outlet 2 19. QF1- QFn Automatic circuit breaker 1-n 20. T1, T2 Power transformer 630-1000 kVа 2 21. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-tv(tk) 630-1000/10(6)/0,4Electrical schematic diagram. Diagram no. 13
Equipment list
Street lightingStreet lighting
V VOutgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
18
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name Quantity 1. QW1.1-QW1.3, QW2.1-QW2.3 Load-break switch 10(6) kV 6 2. QSG1.1- QSG1.3, QSG2.1- QSG2.3 Earthing disconnector 10(6) kV 6 3. FV1- FV12 Valve arrester or OPN 124. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QF1, 1QF2, 2QF1 Automatic circuit breaker 0.4 kV 3 6. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 7. ТА1... ТА6 Current transformer 6 8. QF1, QF4 Automatic circuit breaker 16 A 2 9. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 10. PI1, PI2 Electricity meter 2 11. KL(BL) Photoswitch (photoswitch sensor) 2 12. EL Lamp E27 2 13. T1 Step-down transformer 220/12 V 2 14. PV Voltmeter 2 15. PA Ammeter 6 16. SA Switch 0.4 kV 2 17. KM Magnetic starter PM 2 18. RK1, RK2 Thermistor 4 19. XS Socket outlet 2 20. QF1- QFn Automatic circuit breaker 1-n 21. T1, T2 Power transformer 630-1000 kVа 2
Package transformer substation 2ktP-tv(tk) 630-1000/10(6)/0,4Electrical schematic diagram. Diagram no. 14
Equipment list
Street lightingStreet lighting
V VOutgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
19
ww
w.u
ztt.
ruS. No. Ref. Numeral Name Quantity
1. QW1.1 Load-break switch 10(6) kV 1 2. QSG1.1- QSG1.3, QSG2.3 Earthing disconnector 10(6) kV 4 3. QS1.1, QS1.2, QS2.2 Disconnector 10(6) kV 3 4. FV1- FV12 Valve arrester or OPN 12 5. FU1…FU6 Fuse PKT 10(6) kV 6 6. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 7. ТА1... ТА6 Current transformer 6 8. QF1, QF4 Automatic circuit breaker 16 A 2 9. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 10. PI1, PI2 Electricity meter 2 11. KL(BL) Photoswitch (photoswitch sensor) 2 12. EL Lamp E27 2 13. T1 Step-down transformer 220/12 V 2 14. PV Voltmeter 2 15. PA Ammeter 6 16. SA Switch 0.4 kV 2 17. KM Magnetic starter PM 2 18. RK1, RK2 Thermistor 4 19. XS Socket outlet 2 20. QF1- QFn Automatic circuit breaker 1-n 21. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-tv(tk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 15
Equipment list
Street lightingStreet lighting
V VOutgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv
Outdoor package transformer substation
20
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name Quantity 1. QW1.1 Load-break switch 10(6) kV 1 2. QSG1.1- QSG1.3, QSG2.3 Earthing disconnector 10(6) kV 4 3. QS1.1, QS1.2, QS2.2 Disconnector 10(6) kV 3 4. FV1- FV12 Valve arrester or OPN 12 5. FU1…FU6 Fuse PKT 10(6) kV 6 6. 1QF1, 1QF2, 2QF1 Automatic circuit breaker 0.4 kV 3 7. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 8. ТА1... ТА6 Current transformer 6 9. QF1, QF4 Automatic circuit breaker 16 A 2 10. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 11. PI1, PI2 Electricity meter 2 12. KL(BL) Photoswitch (photoswitch sensor) 2 13. EL Lamp E27 2 14. T1 Step-down transformer 220/12 V 2 15. PV Voltmeter 2 16. PA Ammeter 6 17. SA Switch 0.4 kV 2 18. KM Magnetic starter PM 2 19. RK1, RK2 Thermistor 4 20. XS Socket outlet 2 21. QF1- QFn Automatic circuit breaker 1-n 22. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-tv(tk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 16
Equipment listStreet lightingStreet lighting
V VOutgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv
Outdoor package transformer substation
21
ww
w.u
ztt.
ruS. No. Ref. Numeral Name Quantity
1. QW1.1-QW1.3, QW2.3 Load-break switch 10(6) kV 4 2. QSG1.1-QSG1.3, QSG2.3 Earthing disconnector 10(6) kV 4 3. FV1- FV12 Valve arrester or OPN 12 4. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 6. ТА1... ТА6 Current transformer 6 7. QF1, QF4 Automatic circuit breaker 16 A 2 8. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 9. PI1, PI2 Electricity meter 2 10. KL(BL) Photoswitch (photoswitch sensor) 2 11. EL Lamp E27 2 12. T1 Step-down transformer 220/12 V 2 13. PV Voltmeter 2 14. PA Ammeter 6 15. SA Switch 0.4 kV 2 16. KM Magnetic starter PM 2 17. RK1, RK2 Thermistor 4 18. XS Socket outlet 2 19. QF1- QFn Automatic circuit breaker 1-n 20. T1, T2 Power transformer 630-1000 kVа 2
Package transformer substation 2ktP-tv(tk) 630-1000/10(6)/0,4Electrical schematic diagram. Diagram no. 17
Equipment list
Street lightingStreet lighting
V VOutgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv
Outdoor package transformer substation
22
ww
w.u
ztt.
ru
S. No. REF. NUMERAL NAME QUANtItY 1. QW1.1-QW1.3, QW2.3 Load-break switch 10(6) kV 4 2. QSG1.1-QSG1.3, QSG2.3 Earthing disconnector 10(6) kV 4 3. FV1- FV12 Valve arrester or OPN 12 4. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QF1, 1QF2, 2QF1 Automatic circuit breaker 0.4 kV 3 6. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 7. ТА1... ТА6 Current transformer 6 8. QF1, QF4 Automatic circuit breaker 16 A 2 9. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 10. PI1, PI2 Electricity meter 2 11. KL(BL) Photoswitch (photoswitch sensor) 2 12. EL Lamp E27 2 13. T1 Step-down transformer 220/12 V 2 14. PV Voltmeter 2 15. PA Ammeter 6 16. SA Switch 0.4 kV 2 17. KM Magnetic starter PM 2 18. RK1, RK2 Thermistor 4 19. XS Socket outlet 2 20. QF1- QFn Automatic circuit breaker 1-n 21. T1, T2 Power transformer 630-1000 kVа 2
Package transformer substation 2ktP-tv(tk) 630-1000/10(6)/0,4Electrical schematic diagram. Diagram no. 18
Equipment list
Street lightingStreet lighting
V VOutgoing linesOutgoing lines
0.4 Kv 0.4 Kv
Input 10(6) kv
Outdoor package transformer substation
23
ww
w.u
ztt.
ru
2. Type – double-ended air (cable)
2.1. Single-transformerDouble-ended KTP with the cable input (Fig. 7) and dou-ble-ended KTP with the air input (Fig. 8) can be produced for the transformer power between 25 and 1000 kVA.
Upon request they can be produced for the transformer power of 1600 and 2500 kVA.
Fig. 7. Overall dimensions of KTP-PK substation.
Fig. 8. Overall dimensions of KTP-PV substation.
Dimensions of KTP with power more than 630 kVA are determined according to the particular order.
Housing
Housing
Power transformer compartment
Power transformer compartment
Air input
2100
2100
3040
3040
2400
4000
2400
Outdoor package transformer substation
24
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name Quantity 1. QS1 Disconnector 10(6) kV 1 2. QSG Earthing disconnector 1 3. QW1, QW2 Load-break switch 10(6) kV 2 4. QSG1, QSG2 Earthing disconnector 2 5. FV1-FV6 Valve arrester or OPN 10(6) kV 3 6. FU1…FU3 Fuse PKT 10(6) kV 3 7. QS2 Disconnector 0.4 kV 1 8. TA1…TA3 Current transformer 3 9. QF1 Automatic circuit breaker 16 A 1 10. QF2, QF3 Automatic circuit breaker 10 A 2 11. PI Electricity meter 1 12. KL(BL) Photoswitch (photoswitch sensor) 1 13. EL Lamp E27 1 14. T1 Step-down transformer 220/12 V 1 15. PV Voltmeter 1 16. PA Ammeter 3 17. SA Switch 0.4 kV 1 18. KM Magnetic starter PM 1 19. RK1, RK2 Thermistor 2 20. XS Socket outlet 1 21. QF1- QFn Automatic circuit breaker 1-n 22. T Power transformer with power of 25-400 kVа 1
Package transformer substation ktP-Pv(Pk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 3
Equipment listStreet lighting
VOutgoing lines
Outgoing line
0.4 Kv
Input 10(6) kv
Outdoor package transformer substation
25
ww
w.u
ztt.
ruS. No. Ref. Numeral Name Quantity
1. QW, QW1, QW2 Load-break switch 10(6) kV 2 2. QSG, QSG1, QSG2 Earthing disconnector 2 3. FV1-FV6 Valve arrester or OPN 10(6) kV 3 4. FU1...FU3 Fuse PKT 10(6) kV 3 5. QS Disconnector 0.4 kV 1 6. TA1…TA3 Current transformer 3 7. QF1 Automatic circuit breaker 16 A 1 8. QF2, QF3 Automatic circuit breaker 10 A 2 9. PI Electricity meter 1 10. KL(BL) Photoswitch (photoswitch sensor) 1 11. EL Lamp E27 1 12. T1 Step-down transformer 220/12 V 1 13. PV Voltmeter 1 14. PA Ammeter 3 15. SA Switch 0.4 kV 1 16. KM Magnetic starter PM 1 17. RK1, RK2 Thermistor 2 18. XS Socket outlet 1 19. QF1- QFn Automatic circuit breaker 1-n 20. T Power transformer with power of 630-1000 kVа 1
Package transformer substation ktP-Pv(Pk) 630-1000/10(6)/0,4Electrical schematic diagram. Diagram no. 4
Equipment list
Street lighting
VOutgoing lines
Outgoing line
0.4 Kv
Input 10(6) kv
Outdoor package transformer substation
26
ww
w.u
ztt.
ru
Type – double-ended air (cable)
2.2. Double-transformerDouble-ended 2KTP with the cable input (Fig. 9) and double-ended 2KTP with the air input (Fig. 10) can be produced for the transformer power between 25 and 1000 kVA.
Upon request they can be produced for the trans-former power of 1600 and 2500 kVA.
Fig. 9. Overall dimensions of 2KTP-PK for Diagrams No. 19...22,
For Diagrams No. 24…26 dimensions are determined according to the particular order.
Fig. 10. Overall dimensions of 2KTP-PV
Dimensions of KTP with power more than 630 kVA are determined according to the particular order.
Housing
Housing
Power transformer compartment
Power transformer compartment
Air input
21002100
2100 2100
3040
3040
5000
5000
2400
4000
2400
Outdoor package transformer substation
27
ww
w.u
ztt.
ruS. No. Ref. Numeral Name Quantity
1. QW1.1, QW1.4, QW2.1, QW2.4 Load-break switch 10(6) kV 4 2. QSG1.1- QSG1.3, QSG2.1- QSG2.3 Earthing disconnector 10(6) kV 6 3. QS1.2, QS2.2 Disconnector 10(6) kV 2 4. FV1- FV12 Valve arrester or OPN 12 5. FU1…FU6 Fuse PKT 10(6) kV 6 6. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 7. ТА1... ТА6 Current transformer 6 8. QF1, QF4 Automatic circuit breaker 16 A 2 9. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 10. PI1, PI2 Electricity meter 2 11. KL(BL) Photoswitch (photoswitch sensor) 2 12. EL Lamp E27 2 13. T1 Step-down transformer 220/12 V 2 14. PV Voltmeter 2 15. PA Ammeter 6 16. SA Switch 0.4 kV 2 17. KM Magnetic starter PM 2 18. RK1, RK2 Thermistor 4 19. XS Socket outlet 2 20. QF1- QFn Automatic circuit breaker 1-n 21. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-Pv(Pk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 19
Equipment list
Street lighting Street lighting
V VOutgoing lines Outgoing lines
Outgoing line 2Outgoing line 1
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
28
ww
w.u
ztt.
ru
S. No. REF. NUMERAL NAME QUANtItY 1. QW1.1, QW1.4, QW2.1, QW2.4 Load-break switch 10(6) kV 4 2. QSG1.1- QSG1.3, QSG2.1- QSG2.3 Earthing disconnector 10(6) kV 6 3. QS1.2, QS2.2 Disconnector 10(6) kV 2 4. FV1- FV12 Valve arrester or OPN 12 5. FU1…FU6 Fuse PKT 10(6) kV 6 6. 1QF1, 1QF2, 2QF1 Automatic circuit breaker 0.4 kV 3 7. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 8. ТА1... ТА6 Current transformer 6 9. QF1, QF4 Automatic circuit breaker 16 A 2 10. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 11. PI1, PI2 Electricity meter 212. KL(BL) Photoswitch (photoswitch sensor) 2 13. EL Lamp E27 2 14. T1 Step-down transformer 220/12 V 2 15. PV Voltmeter 2 16. PA Ammeter 6 17. SA Switch 0.4 kV 2 18. KM Magnetic starter PM 2 19. RK1, RK2 Thermistor 4 20. XS Socket outlet 2 21. QF1- QFn Automatic circuit breaker 1-n 22. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-Pv(Pk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 20
Equipment list
Street lighting Street lighting
V VOutgoing lines Outgoing lines
Outgoing line 2Outgoing line 1
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
29
ww
w.u
ztt.
ru
S. No. REF. NUMERAL NAME QUANtItY 1. QW1.1, QW1.3, QW1.4, QW2.1,
QW2.3, QW2.4Load-break switch 10(6) kV
6
2. QSG1.1- QSG1.3, QSG2.1- QSG2.3 Earthing disconnector 10(6) kV 6 3. FV1- FV12 Valve arrester or OPN 12 4. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 6. ТА1...ТА6 Current transformer 6 7. QF1, QF4 Automatic circuit breaker 16 A 2 8. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 9. PI1, PI2 Electricity meter 2 10. KL(BL) Photoswitch (photoswitch sensor) 2 11. EL Lamp E27 2 12. T1 Step-down transformer 220/12 V 213. PV Voltmeter 2 14. PA Ammeter 6 15. SA Switch 0.4 kV 2 16. KM Magnetic starter PM 2 17. RK1, RK2 Thermistor 4 18. XS Socket outlet 2 19. QF1- QFn Automatic circuit breaker 1-n 20. T1, T2 Power transformer 630-1000 kVа 2 21. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-Pv(Pk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 21
Equipment list
Street lighting Street lighting
V VOutgoing lines Outgoing lines
Outgoing line 2Outgoing line 1
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
30
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name Quantity 1. QW1.1, QW1.3, QW1.4, QW2.1,
QW2.3, QW2.4Load-break switch 10(6) kV
6
2. QSG1.1- QSG1.3, QSG2.1- QSG2.3 Earthing disconnector 10(6) kV 6 3. FV1- FV12 Valve arrester or OPN 12 4. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QF1, 1QF2, 2QF1 Automatic circuit breaker 0.4 kV 3 6. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 7. ТА1...ТА6 Current transformer 6 8. QF1, QF4 Automatic circuit breaker 16 A 2 9. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 10. PI1, PI2 Electricity meter 2 11. KL(BL) Photoswitch (photoswitch sensor) 2 12. EL Lamp E27 2 13. T1 Step-down transformer 220/12 V 2 14. PV Voltmeter 2 15. PA Ammeter 6 16. SA Switch 0.4 kV 2 17. KM Magnetic starter PM 2 18. RK1, RK2 Thermistor 4 19. XS Socket outlet 2 20. QF1- QFn Automatic circuit breaker 1-n 21. T1, T2 Power transformer 630-1000 kVа 2
Package transformer substation 2ktP-Pv(Pk) 630-1000/10(6)/0,4Electrical schematic diagram. Diagram no. 22
Equipment list
Street lighting Street lighting
V V
Outgoing lines Outgoing lines
Outgoing line 2Outgoing line 1
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
31
ww
w.u
ztt.
ruS. No. Ref. Numeral Name Quantity
1. QW1.1, QW1.4, QW2.1, QW2.4 Load-break switch 10(6) kV 4 2. QSG1.1- QSG1.4, QSG2.1- QSG2.4 Earthing disconnector 10(6) kV 8 3. QS1.1, QS1.2, QS2.1, QS2.2 Disconnector 10(6) kV 4 4. FV1- FV12 Valve arrester or OPN 12 5. FU1…FU6 Fuse PKT 10(6) kV 6 6. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 7. ТА1...ТА6 Current transformer 6 8. QF1, QF4 Automatic circuit breaker 16 A 2 9. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 10. PI1, PI2 Electricity meter 2 11. KL(BL) Photoswitch (photoswitch sensor) 2 12. EL Lamp E27 2 13. T1 Step-down transformer 220/12 V 2 14. PV Voltmeter 2 15. PA Ammeter 6 16. SA Switch 0.4 kV 2 17. KM Magnetic starter PM 2 18. RK1, RK2 Thermistor 4 19. XS Socket outlet 2 20. QF1- QFn Automatic circuit breaker 1-n 21. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-Pv(Pk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 23
Equipment list
Street lighting Street lighting
V VOutgoing lines Outgoing lines
Outgoing line 2Outgoing line 1
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
32
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name Quantity 1. QW1.1, QW1.4, QW2.1, QW2.4 Load-break switch 10(6) kV 4 2. QSG1.1- QSG1.4, QSG2.1- QSG2.4 Earthing disconnector 10(6) kV 8 3. QS1.1, QS1.2, QS2.1, QS2.2 Disconnector 10(6) kV 4 4. FV1- FV12 Valve arrester or OPN 12 5. FU1…FU6 Fuse PKT 10(6) kV 6 6. 1QF1, 1QF2, 2QF1 Automatic circuit breaker 0.4 kV 3 7. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 8. ТА1...ТА6 Current transformer 6 9. QF1, QF4 Automatic circuit breaker 16 A 2 10. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 11. PI1, PI2 Electricity meter 2 12. KL(BL) Photoswitch (photoswitch sensor) 2 13. EL Lamp E27 2 14. T1 Step-down transformer 220/12 V 2 15. PV Voltmeter 2 16. PA Ammeter 6 17. SA Switch 0.4 kV 2 18. KM Magnetic starter PM 2 19. RK1, RK2 Thermistor 4 20. XS Socket outlet 2 21. QF1- QFn Automatic circuit breaker 1-n 22. T1, T2 Power transformer 25-400 kVа 2
Package transformer substation 2ktP-Pv(Pk) 25-400/10(6)/0,4Electrical schematic diagram. Diagram no. 24
Equipment list
Street lighting Street lighting
V VOutgoing lines Outgoing lines
Outgoing line 2Outgoing line 1
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
33
ww
w.u
ztt.
ruS. No. Ref. Numeral Name Quantity
1. QW1.1-QW1.4, QW2.1-QW2.4 Load-break switch 10(6) kV 8 2. QSG1.1-QSG1.3, QSG2.1-QSG2.3 Earthing disconnector 10(6) kV 8 3. FV1- FV12 Valve arrester or OPN 124. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 6. ТА1...ТА6 Current transformer 6 7. QF1, QF4 Automatic circuit breaker 16 A 2 8. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 9. PI1, PI2 Electricity meter 2 10. KL(BL) Photoswitch (photoswitch sensor) 2 11. EL Lamp E27 2 12. T1 Step-down transformer 220/12 V 2 13. PV Voltmeter 2 14. PA Ammeter 6 15. SA Switch 0.4 kV 2 16. KM Magnetic starter PM 2 17. RK1, RK2 Thermistor 4 18. XS Socket outlet 2 19. QF1- QFn Automatic circuit breaker 1-n 20. T1, T2 Power transformer 630-1000 kVа 2
Package transformer substation 2ktP-Pv(Pk) 630-1000/10(6)/0,4Electrical schematic diagram. Diagram no. 25
Equipment list
Street lighting Street lighting
V VOutgoing lines Outgoing lines
Outgoing line 2Outgoing line 1
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
34
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name Quantity 1. QW1.1-QW1.4, QW2.1-QW2.4 Load-break switch 10(6) kV 8 2. QSG1.1-QSG1.3, QSG2.1-QSG2.3 Earthing disconnector 10(6) kV 8 3. FV1- FV12 Valve arrester or OPN 12 4. FU1…FU6 Fuse PKT 10(6) kV 6 5. 1QF1, 1QF2, 2QF1 Automatic circuit breaker 0.4 kV 3 6. 1QS1, 1QS2, 2QS1, 2QS2 Disconnector 0.4 kV 4 7. ТА1...ТА6 Current transformer 6 8. QF1, QF4 Automatic circuit breaker 16 A 2 9. QF2, QF3, QF5, QF6 Automatic circuit breaker 10 A 4 10. PI1, PI2 Electricity meter 2 11. KL(BL) Photoswitch (photoswitch sensor) 2 12. EL Lamp E27 2 13. T1 Step-down transformer 220/12 V 2 14. PV Voltmeter 2 15. PA Ammeter 6 16. SA Switch 0.4 kV 2 17. KM Magnetic starter PM 2 18. RK1, RK2 Thermistor 4 19. XS Socket outlet 2 20. QF1- QFn Automatic circuit breaker 1-n 21. T1, T2 Power transformer 630-1000 kVа 2
Package transformer substation 2ktP-Pv(Pk) 630-1000/10(6)/0,4Electrical schematic diagram. Diagram no. 26
Equipment list
Street lighting Street lighting
V VOutgoing lines Outgoing lines
Outgoing line 2Outgoing line 1
0.4 Kv 0.4 Kv
Input 10(6) kv Input 10(6) kv
Outdoor package transformer substation
35
ww
w.u
ztt.
ru
II. Pole-mountedPole-mounted KTP (Fig. 11) can be produced for the transformer power between 25 and 250 kVA.
Pole-mounted package transformer substations - KTP-VS (agricul-tural) - are used to supply electric power to cottages, industrial, ag-ricultural and utility facilities within loop or radial systems of distri-bution networks.
Pole-mounted package transformer substations (KTP-VS) do not have common outer shell. Each compartment of the substation is mounted on a special-purpose frame on a power line pole.
Fig. 11. General view and overall dimensions of KTP-VS.
High-voltage disconnector (RLND)
High-voltage fuse
Transformer
LV switchgear cabinet
Arrester (overvoltage suppressor)
PTL (power transmission line) 6(10) kV
1700
max
6000
max
Outdoor package transformer substation
36
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name Quantity 1. FV1-FV6 Valve arrester or OPN 3 2. FU1...FU3 Fuse PKT 10(6) kV 3 3. QS2 Disconnector 0.4 kV 1 4. TA1…TA3 Current transformer 3 5. QF1 Automatic circuit breaker 16 A 1 6. QF2, QF3 Automatic circuit breaker 10 A 2 7. PI Electricity meter 1 8. KL(BL) Photoswitch (photoswitch sensor) 1 9. EL Lamp E27 1 10. T1 Step-down transformer 220/12 V 1 11. PV Voltmeter 1 12. PA Ammeter 3 13. SA Switch 0.4 kV 1 14. KM Magnetic starter PM 115. RK1, RK2 Thermistor 2 16. XS Socket outlet 1 17. QF1- QFn Automatic circuit breaker 1-n 18. T Power transformer with power of 25-250 kVа 1
Package transformer substation ktP-vS 25-250/10(6)/0,4Electrical schematic diagram. Diagram no. 5
Equipment list
Street lighting
V
Outgoing lines
0.4 Kv
Outdoor package transformer substation
37
ww
w.u
ztt.
ruHV gear cabinet
Transformer
cabinetLV switchgear
III. MAST-MOUNTEDMast-mounted KTP (Fig. 12) can be produced for the transformer power between 25 and 1000 kVA.
Fig. 12. General view and overall dimensions of KTP-VM substation.
1000 max 1100 max
2780
max
Outdoor package transformer substation
38
ww
w.u
ztt.
ru
S. No. Ref. Numeral Name Quantity 1. FV1-FV6 Valve arrester or OPN 3 2. FU1...FU3 Fuse PKT 10(6) kV 3 3. QS2 Disconnector 0.4 kV 1 4. TA1…TA3 Current transformer 3 5. QF1 Automatic circuit breaker 16 A 1 6. QF2, QF3 Automatic circuit breaker 10 A 2 7. PI Electricity meter 1 8. KL(BL) Photoswitch (photoswitch sensor) 1 9. EL Lamp E27 1 10. T1 Step-down transformer 220/12 V 1 11. PV Voltmeter 1 12. PA Ammeter 3 13. SA Switch 0.4 kV 1 14. KM Magnetic starter PM 115. RK1, RK2 Thermistor 2 16. XS Socket outlet 1 17. QF1- QFn Automatic circuit breaker 1-n 18. T Power transformer with power of 25-250 kVа 1
Package transformer substation ktp-vm 25-250/10(6)/0,4 Electrical schematic diagram. Diagram no. 6
Equipment list
Street lighting
V
Outgoing lines
0.4 Kv
Outdoor package transformer substation
39
ww
w.u
ztt.
ru
IV. MOBILE (OPEN-PIT)Mobile transformer substations (Fig. 13) are designed to receive three-phase ac electric power with industrial 50 Hz frequency and 10 (6) kV voltage, to convert it into electric power with 0.4 kV voltage and to distribute it to consumers.
It is used to supply ac electricity to portable current collectors for surface coal mines, ore and other mines (open pits) with open-cast mining operations; they can be also used to supply elec-tricity to underground mine consumers through pit-holes and boreholes, construction sites and other temporary facilities.
Comply with TU 3412-005-96418566-09.
PKTR packaging is made according to Customer Questionnaire.
Fig. 13. General view of PKTR substation.
PKTR – product line letter designation:
Mobile Package Transformer Substation;
Х1 – configuration type: P – double-ended, T – single-ended;
Х2 – HV inputs configuration: V – air, K – cable;
ХЗ – power of power transformer, kVA;
Х4 – rated voltage on the HV side. kV:
0,4 – rated voltage on the LV side, kV;
U1 – climatic configuration and location category according to
GOST 15150-69.
PKTR – Х1 Х2/ХЗ–Х4/0,4 U1
Outdoor package transformer substation
40
ww
w.u
ztt.
ru
шкаф ВН трансформаторшкаф РУНН Салазки HV cabinettransformerLV switchgear cabinet Slide railsКорпусСалазки Отсек силового трансформатора Slide rails
Fig. 14. Overall dimensions of PKTP substation (type 1).
Fig. 15. Overall dimensions of PKTP substation (type 2 - kiosk)
Dimensions of KTP with power more than 630 kVA are determined according to the particular order.
HV cabinet
Transformer
Slide rails
Slide rails
Housing
cabinet
compartment
LV switchgear
Power transformer
1380
2100
2000
2400
2200
max
2600
max
3000 max
3000
3000 max
500 500
Outdoor package transformer substation
41
ww
w.u
ztt.
ru
V. Standard components of kiosk-type, pole-mounted and mast-mounted substations
For 2KTP-type substations the number of outgoing lines and their specifications are taken in accordance with the table for each KTP.
Table 2.
Substation type
Parameter name Parameter value
KTP-VS (single-phase)
MTPO
Transformer power (kVA)
1.25 2.5 4 6 10
Outgoing lines
L.1 2.5 4.0 10 16 25ВА47-29
L.2 2.5 6.3 6.3 10 16
KTP-VS (three-phase)
Transformer power (kVA)
25 40 63 100 160 250 Type of
automaton OF
Outgoing lines
L.1 16 25 40 100 100 100
VA-88L.2 16 25 40 100 100 100
L.3 25 40 63 160 160 200
L.4 - - - - 200 200
KTP-VM
mast-mounted
Transformer power (kVA)
25 40 63 100 160 250 Type of
automaton OF
Outgoing lines
L.1 16 25 40 100 100 100
VA-88L.2 16 25 40 100 100 100
L.3 25 40 63 160 160 200
L.4 - - - - 200 200
Kiosk-type:
KTP-TV,
KTP-TK,
KTP-PV,
KIP-PK
Transformer power (kVA)
25 40 63 100 160 250 400 630 1000Type of
automaton OF
Outgoing lines
L.1 16 25 40 80 80 80 100 250 250
VA-88
(VA-99)
L.2 16 25 40 80 80 100 100 250 250
L.3 25 40 63 100 100 160 160 250 250
L.4 160 160 160 250 400
L.5 250 250 400
Outdoor package transformer substation
42
ww
w.u
ztt.
ru
VI. Container-type substations with maintenance corridorsContainer-type substations (KTRN) have maintenance corridors. Equipment maintenance is carried out di-rectly from transformer substation rooms (compartments).
Each KTRN has three (or four – for double-transformer substations) compartments: HV compartment, LV compartment, power transformer(s) compartment (or compartments– for double-transformer substa-tions). Switchgears and protection devices and other electrical equipment are installed in high-voltage and low-voltage compartments (rooms) in chambers and cabinets, which type is determined according to the order - generally, they are:
• on the HV side – KSO 366 cells (КSО385), КSО292 • on the LV side – panels ShchO 70.
HV-side input – cable, LV-side output – cable. Upon request can be produced with the air input.
Transformer substation is equipped with lighting, has 220 and 12В outlet circuit, internal ground loop with outside-mounted “bosses” for connection to the external ground loop. Substation can be equipped with electric heating, which is operated both in automatic and manual mode.
The substation housing is metal (standard or with heat insulation). Fire resistance rating of construction elements is IV according to SNiP 21-09-97 “Fire safety of buildings and constructions”.
Substations can be produced both in standard UZTT overall dimensions (three dimension-types) and cus-tomized dimensions.
Number of transport units for double-transformer substations – 3:• HV switchgear compartment (with installed equipment)• LV switchgear compartment (with installed equipment)• Compartments of transformers No.1 and No.2.
Power transformers should be transported in accordance with rules for carriage of goods or regulations applicable for this type of transport. Number of transport groups for single-transformer substations is de-termined on an individual basis and depends on the equipment kit.
Questionnaire for KTRN with maintenance corridor shall contain:• Questionnaire for HV switchgear, specifying type of installed cells, as well as type and specifica-
tions of equipment, installed inside them, scheme of equipment installation;• Questionnaire for LV switchgear, specifying type of installed panels, as well as type and specifica-
tions of equipment, installed inside them, scheme of equipment installation;• Questionnaire for transformers;• Questionnaire for package condensing units.
Outdoor package transformer substation
43
ww
w.u
ztt.
ruList of cells RU 10(6) kv inside ktRN (example)
Panel number at the scheme
Initials Panel function Qty Remarks
2, 6 KSO-366M 3n-630 Cable input 21, 7 KSO-366M 3н-630 Outgoing line 23, 5 KSO-366M 4n-630 Power transformer 2
4 KSO-366M 13-630 Sectionalizer 1
List of board panels 0.4 kv inside ktRN (example)
Panel number at the scheme
Initials Panel function Qty Remarks
1,5 ShchO70-3M-12U3 Bus input 2
2,4 ShchO70-3M-03U3 Line with the knife switch 23 ShchO70-3M-39U3 Section with the knife switch 1
5t ShchO70-3M-58U3 Side panel right 2
1t ShchO70-3M-59U3 Side panel left 2
Зa False panel 1 dimensions to be determined at equipment installation
Scheme of equipment installation inside KTP (example)
RU 0.4 kv
trasformer No.1
RU 10(6) kv
trasformer No.2
Outdoor package transformer substation
44
ww
w.u
ztt.
ru
QuestionnaireFor making an order for kiosk-type, pole-mounted and mast-mounted KTP
URAL COMPANY FOR TRANSFORMER TECHNOLOGIES
Substation type: Quantity:
UZTT
Equipment reference designationTo be filled in by the Customer
Remarks
Substation design
stationarymobile1-transformer, double-ended1-transformer, single-ended2-transformer (single-ended/double-ended)
HV input configurationaircable
LV outputaircable
Rated voltage, kV 6 10
High-voltage switchgear
ArresterRVOOPN
DisconnectorRLNDRVZVNR
TransformerType (TM, TMZ, TMG, TMF, TSZ) Power Phase displacement groupQuantity
Low-voltage switchgear
Input switching unitautomatic circuit breaker - VAdisconnector RE-19
Section deviceautomatic circuit breaker - VAdisconnector RE-19
ArresterRVOOPN
Electricity meter activereactive
ControlsVoltmeter
QtyAmmeter
Street lighting:
Outgoing linesAutomatic circuit breaker - VAknife switch with fuse - RPS
Rated current of outgoing line protection devices/rated current of releases or fuse links (1n/ 1nr), A
Line 1 Line 2 Line.3 Line 4 Line 5 Line 6
Additional equipment
HV switchgear Reserve switching deviceLV switchgear Reserve switching device
Package condensing unit 0.4 kV