ORMOND BEACH ELEMENTARY SCHOOL BOARD SEG Project No ... › sites › default › files ›...
Transcript of ORMOND BEACH ELEMENTARY SCHOOL BOARD SEG Project No ... › sites › default › files ›...
BUILDING DATA
CONSTRUCTION DOCUMENTS - 4/20/2020NOT TO SCALE
DESCRIPTION OF WORK
SCHOOL BOARD
MEMBERS
A. SURVEY PARCEL ID XXX
B. LEGAL DESCRIPTION XXX
C. OCCUPANCY TYPE XXX
D. CONSTRUCTION TYPE TYPE XXX
E. RISK CATEGORY XXX
F. AUTOMATIC SPRINKLER XXX
G. BUILDING AREA XXX
H. BUILDING HEIGHT XXX
I. OCCUPANT LOAD XXX
LOCATION MAP
ENGINEERS & CONSULTANTS
Engineer's Statement of ComplianceTo the best of my knowledge, these drawings and the project manual are complete and comply withthe Florida Building Code.
MECHANICAL ENGINEERSABISTON ENGINEERING GROUP, INC.322 KENTUCKY BLUE CIRCLEAPOPKA, FL 32712CONTACT PHONE NUMBER: 407.884.6769PROJECT MANAGER: DON SABISTONe-mail: [email protected]
SEG Project No. 19007
Sabiston Engineering Group, Inc.
www.SabistonEngineering.comState of Florida Certificate No. 9811
P: 407.884.6769 F: 407.884.6764322 Kentucky Blue Circle, Apopka, FL 32712
PROJECT
LOCATION
ELECTRICAL ENGINEERMATERN PROFESSIONAL ENGINEERING, INC.130 CANDACE DRIVEMAITLAND, FL 32751CONTACT PHONE NUMBER: 407.740.5020PROJECT MANAGER: ADRIAN BAUSe-mail: [email protected]
FAX (407) 740-0365
PHONE (407) 740-5020
CERT. OF AUTH. No. 5096
ENG. BUS. No. EB-0005096
130 Candace Drive
Maitland, FL 32751
Replace 100% outside air unit and reconnect to existing ductwork.
THE SCHOOL BOARD OF VOLUSIA
COUNTY FLORIDA
200 North Clara Avenue
Deland, Florida 32720
VCS Project NO. 2047725
100 CORBIN AVE, ORMOND BEACH, FL 32174
UPGRADE HVAC BLDG. 1
ORMOND BEACH ELEMENTARY
VOLUSIA
COUNTY SCHOOLS
IDA D. WRIGHT
LINDA CUTHBERT
RUBEN COLON
JAIME M. HAYNES
CARL G. PERSIS
RONALD S. FRITZ
CHAIRMAN
VICE CHAIRMAN
MEMBER
MEMBER
MEMBER
SUPERINTENDENT
CS
Cover S
heet
Do
na
ld
J. S
ab
isto
n, P
.E
.
Sta
te
o
f F
lo
rid
a N
o. 5
48
89
DRAWING NO.
SHEE
T TI
TLE
AE PROJECT NUMBER
DRAWN BYDESIGNED BY
ARCH/ENGR OF RECORD
ISSUE DATE
DOCU
MENT
HIS
TORY
RE
VIS
IO
NS
VCS
Proje
ct NO
. 204
7725
UPGR
ADE
HVAC
BLD
G. 1
100 C
OR
BIN
A
VE
,
OR
MO
ND
B
EA
CH
, F
L 32174
DJS
DJS
190074/20/2020
Engineer
Donald J. Sabiston, P.E.
ORMO
ND B
EACH
ELE
MENT
ARY
NO.
DATE
DESC
RIPT
ION
SEG
Pro
ject
No.
19007
Sab
isto
n E
ngi
nee
ring
Gro
up, In
c.
ww
w.S
abis
tonE
ngin
eeri
ng.c
omS
tate
of
Flori
da C
erti
fica
te N
o. 9811
P: 407.8
84.6
769
F: 4
07.8
84.6
764
322 K
entu
cky
Blu
e C
ircl
e, A
popk
a, F
L 32712
SUMMARY OF WORK
BIDDING PROCEEDURES
ELECTRIC DUCT HEATER
FS
AFS
MANUAL DAMPER
RADIATION DAMPER
SMOKE DAMPER (FS = FIRE/SMOKE DAMPER)
FIRE DAMPER
FLEXIBLE CONNECTION
AIR FLOW STATION
S R
AD
STANDARD BRANCH, SUPPLY OR RETURN
TRANSITION, ECCENTRIC
ACCESS DOOR
TRANSITION, CONCENTRIC
RADIUS ELBOW
TURNING VANES
DUCTWORK ELBOW DOWN
MITERED ELBOW
TEE, OUTLET DOWN
VENTURI FLOWMETER
FLEXIBLE CONNECTOR
CONNECTION, BOTTOM
CONNECTION, TOP
UNION
TEE, OUTLET UP
ELBOW TURNED DOWN
ELBOW TURNED UP
PRESSURE GAGE
STRAINER WITH BLOWDOWN VALVE
MANUAL AIR VENT
AUTOMATIC AIR VENTAUTOMATIC AIR VENT
THERMOMETER
SECTION, SUPPLY DUCT
R
12X20
CHANGE OF ELEVATION (R=RISE, D=DROP)
INTERNALLY LINED OR DOUBLEWALL DUCT
DUCT SIZE IN INCHES, WIDTH X DEPTH (INSIDE)
DUCTWORK ELBOW UP
SECTION, EXHAUST DUCT
SECTION, ROUND DUCT
FLEXIBLE DUCT
SECTION, RETURN DUCT
TAG
CFM
TAG
CFM
TAG
CFM
CFM
TAG
CFM
TAG
SIDEWALL RETURN OR EXHAUST GRILLE
HVAC EQUIPMENT
ROOFTOP EXHAUST FAN
SIDEWALL SUPPLY GRILLE
EXHAUST AIR GRILLE
RETURN AIR GRILLE
RETURN AIR FLOW
SUPPLY AIR DIFFUSER
SHUTOFF VALVE (BS=BALANCING/SHUTOFF)
SOLENOID ACTUATOR
MOTORIZED ACTUATOR
BACKFLOW PREVENTOR ASSEMBLY
PIPE CAP
PRESSURE REDUCING VALVE
THREE-WAY VALVE
PLUG VALVE
CHECK VALVE
CHILLED WATER SUPPLY
HOT GAS REFRIGERANT PIPING
REFRIGERANT PIPING
CONDENSER WATER RETURN
C
HG
R
CWR
CONDENSER WATER SUPPLY
HOT WATER RETURN
HOT WATER SUPPLY
CHILLED WATER RETURN
CWS
HWR
HWS
CHWR
CONTROLS
ABBREVIATIONS
PIPING, VALVES AND SPECIALTIES
MECHANICAL SYMBOL LEGEND
AIR MOVING DEVICES AND COMPONENTS
UC
DRAWING REVISION INDICATOR
EXISTING TO BE DEMOLISHED
SUPPLY AIR FLOW
EXISTING TO REMAIN
EQUIPMENT TAG (X=TYPE, Y=SYSTEM, Z=NUMBER)
POINT OF CONNECTION
UNDERCUT DOOR (1" UNO)
KEYED NOTES
GENERAL
MOTORIZED CONTROL DAMPER
DUCT PRESSURE SENSOR
ENERGY MANAGEMENT SYSTEM PANEL
CHILLED WATER SUPPLYCHWS
EMS
CARBON DIOXIDE SENSOR
DUCT MOUNTED SMOKE DETECTOR
HUMIDITY SENSOR
THERMOSTAT OR TEMPERATURE SENSOR
GENERAL NOTES
ENGINEERS COMPLIANCE NOTE
1. THE WORD "PROVIDE" SHALL MEAN "FURNISH AND INSTALL".
2. ALL WORK SHALL BE PERFORMED IN A CLEAN AND WORKMANLIKE MANNER. CARE
SHALL BE EXERCISED TO MINIMIZE ANY INCONVENIENCE OR DISTURBANCE TO OTHER
AREAS OF THE FACILITY WHICH ARE TO REMAIN IN OPERATION. ISOLATE WORK AREAS
BY MEANS OF TEMPORARY PARTITIONS AND/OR TARPS TO KEEP DUST AND DIRT WITHIN
THE CONSTRUCTION AREA.
3. NO PIPING, EQUIPMENT, ETC. SHALL BE REMOVED, DISCONNECTED OR SHUT DOWN
WITHOUT PRIOR REVIEW WITH THE OWNER AND/OR ENGINEER TO CONFIRM THAT
AREAS TO REMAIN IN OPERATION WILL NOT BE AFFECTED. IF ANY AREAS NOT WITHIN
THE SCOPE OF WORK ARE AFFECTED BY ANY SHUTDOWN, REMOVAL OR
DISCONNECTION, SUFFICIENT ADVANCE NOTICE MUST BE GIVEN TO THE OWNER
INDICATING WHICH AREAS WILL BE AFFECTED, WHEN THE PROPOSED SHUTDOWN WILL
OCCUR, AND FOR HOW LONG A PERIOD OF TIME.
4. THE OWNER HAS THE RIGHT OF FIRST REFUSAL FOR ALL ITEMS REMOVED. ALL ITEMS
REFUSED BY THE OWNER SHALL BE REMOVED FROM THE SITE AND DISPOSED OF
PROPERLY BY THE CONTRACTOR.
5. THE JOB SITE SHALL BE CLEANED DAILY TO REMOVE FROM THE PREMISES ANY DIRT
AND DEBRIS CAUSED BY THE PERFORMANCE OF THE WORK INCLUDED IN THIS
CONTRACT.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFEKEEPING OF HIS OWN
PROPERTY ON THE JOB SITE. OWNER ASSUMES NO RESPONSIBILITY FOR PROTECTION
OF PROPERTIES OTHER THAN THE OWNERS.
7. EXISTING MATERIALS THAT ARE REMOVED SHALL NOT BE REUSED, EXCEPT WHERE
INDICATED AS BEING RELOCATED.
8. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO BID, FABRICATION, PURCHASE
AND INSTALLATION OF ALL WORK.
9. VISIT THE SITE AND VERIFY ALL DIMENSIONS IN THE FIELD, AND SHALL ADVISE THE
ARCHITECT/ENGINEER AND THE OWNER OF ANY DISCREPANCIES BEFORE PERFORMING
THE WORK. ALL WORK SHALL CONFORM TO ALL STATE AND LOCAL CODES, RULES AND
REGULATIONS AND ORDINANCES.
10. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE
MANUFACTURER'S WRITTEN INSTRUCTIONS.
11. PROVIDE ALL HANGERS AND SUPPORTS REQUIRED FOR A COMPLETE INSTALLATION.
12. PROVIDE ALL RIGGING, HANDLING AND PROTECTION OF MATERIALS.
13. SUBMIT SHOP DRAWINGS AND EQUIPMENT CUTS TO THE ENGINEER FOR APPROVAL
PRIOR TO ORDERING ANY MATERIALS. ALL SHOP DRAWING SUBMITTALS SHALL BE IN
ACCORDANCE WITH THE SPECIFICATIONS.
14. MAINTAIN ON-SITE A SET OF FINAL CONSTRUCTION DOCUMENTS (INCLUDING ADDENDA)
WITH MARKUP AS-BUILT INFORMATION.
15. NOTIFY THE ENGINEER PRIOR TO CONCEALING ANY WORK.
16. ALL EQUIPMENT INSTALLED SHALL PROVIDE THE MANUFACTURERS RECOMMENDED
AND CODE REQUIRED ACCESS AREAS.
17. PROVIDE ALL MODIFICATIONS RESULTING FROM USING EQUIPMENT OTHER THAN THE
BASIS OF DESIGN.
18. CLEAN, PRIME, AND PAINT ALL BARE METAL SURFACES TO PREVENT RUST.
19. ALL DRAIN PIPES SHALL BE INSTALLED WITH A MINIMUM OF 1/8" PER FOOT SLOPE.
SANITARY PIPES LARGER THAN 2 1/2" REQUIRE A MINIMUM OF 1/4" PER FOOT SLOPE.
20. PROVIDE SITE UTILITY LOCATING SERVICES AS REQUIRED TO AVOID DAMAGING
EXISTING UNDERGROUND UTILITIES.
AAV AUTOMATIC AIR VENT
AC AIR CONDITIONING UNIT
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AP ACCESS PANEL
AVER AVERAGE
B BOILER
BDD BACK DRAFT DAMPER
BFP BACK FLOW PREVENTOR
BLDG BUILDING
BOB BOTTOM OF BEAM
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTU BRITISH THERMAL UNIT
CAP CAPACITY
CD CEILING DIFFUSER
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
CT COOLING TOWER
CU CONDENSING UNIT
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
DB DRY BULB
DIA DIAMETER
DIFF DIFFERENTIAL
DISCH DISCHARGE
DN DOWN
DX DIRECT EXPANSION
EA EACH
EAT ENTERING AIR TEMPERATURE
EFF EFFICIENCY
ELEC ELECTRIC
EQUIV EQUIVALENT
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETC AND SO FORTH
EWT ENTERING WATER TEMPERATURE
EWT ENTERING WATER TEMPERATURE
EXT EXTERNAL
F DEGREES FAHRENHEIT
FCU FAN COIL UNIT
FD FLOOR DRAIN
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FLR FLOOR
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPS FEET PER SECOND
FRG FILTER RETURN GRILLE
FRICT FRICTION
FT FEET
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GRS/LB GRAINS PER POUND
H2O WATER
HB HOSE BIBB
HD HEAD (SEE SCHEDULES)
HP HORSEPOWER
HR HOUR
HT HEIGHT
HTR HEATER
HX HEAT EXCHANGER
HZ HERTZ
ID INTERNAL DIAMETER
IN INCHES
INCL INCLUDING
KW KILOWATT
L LENGTH
L LOUVER
LAT LEAVING AIR TEMPERATURE
LB POUND
LBS/HR POUNDS PER HOUR (#/HR)
LD LOUVERED DOOR (24X24 UNO)
LF LINEAR FEET
LRA LOCK ROTOR AMPS
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
MBH THOUSANDS OF BTU PER HOUR
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MOD MOTOR OPERATED DAMPER
MTD MOUNTED
NC NORMALLY CLOSED
NEG NEGATIVE
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OAT OUTSIDE AIR TEMPERATURE
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
OZ OUNCE
P PUMP
PD PRESSURE DROP (SEE SCHEDULE)
PERF PERFORATED
PH PHASE
POS POSITIVE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PTAC PACKAGED TERMINAL AIR CONDITIONER
PVC POLYVINYL CHLORIDE
QUAN QUANTITY
RA RETURN AIR
RAG RETURN AIR GRILLE
RBJ RUN BETWEEN JOIST
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REQD REQUIRED
RET RETURN
RH RELATIVE HUMIDITY
RLA RATED LOAD AMPS
RM ROOM
RPM REVOLUTIONS PER MINUTE
SA SUPPLY AIR
SP STATIC PRESSURE
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
SUCT SUCTION
TEMP TEMPERATURE
TG TRANSFER GRILLE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UC UNDERCUT
UH UNIT HEATER
UNOCC UNOCCUPIED
UON UNLESS OTHERWISE NOTED
V VOLTS
VAV VARIABLE AIR VOLUME UNIT
VEL VELOCITY
VTR VENT THRU ROOF
W WIDTH
W/O WITHOUT
WB WET BULB
WC WATER COLUMN
WG WATER GAUGE
WMS WIRE MESH SCREEN
THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL LABOR AND MATERIALS AS REQUIRED AND AS INDICATED
ON THESE DRAWINGS AND NOTES. THIS WORK SHALL INCLUDE, BUT IS NOT LIMITED TO THE FOLLOWING:
1. PERFORMANCE OF ALL WORK AS DESCRIBED ON PROPOSED CONTRACT DRAWINGS AND AS REFERRED TO
IN THE SPECIFICATIONS AND NOTES AS APPLICABLE FOR EACH PARTICULAR CONSTRUCTION DISCIPLINE.
2. RESTORATION OF EXISTING SYSTEMS, DEVICES, FINISHES, ETC. DAMAGED OR ALTERED BY NEW WORK TO
ACCEPTABLE CONDITION AS DETERMINED BY THE OWNER, ARCHITECT, AND/OR ENGINEER.
3. THE DRAWINGS INDICATE DIAGRAMMATICALLY THE EXTENT, GENERAL CHARACTER AND LOCATION OF THE
WORK INCLUDED. OFFSETS AND/OR CHANGES IN ELEVATION OF PIPING AND DUCTWORK DUE TO
STRUCTURAL OR OTHER INTERFERENCES SHALL BE PROVIDED WITHOUT EXTRA COST. CONTRACTOR SHALL
VERIFY AND EVALUATE ALL EXISTING CONDITIONS PRIOR TO THE COMMENCEMENT OF WORK.
4. COORDINATE WORK WITH THE PRIME CONTRACTOR TO MEET THE CONSTRUCTION SCHEDULE AND PHASING
REQUIREMENTS.
1. SUBMISSION OF BID DIRECTLY OR INDIRECTLY IN CONNECTION WITH THIS WORK SHALL IMPLY THAT THE BIDDER HAS EXAMINED THE JOB
SITE UNDER WHICH HE WILL BE OBLIGATED TO OPERATE SHOULD HE BE AWARDED THE WORK UNDER THIS CONTRACT. NO EXTRA CHARGE
WILL BE ALLOWED FOR FAILURE OF ANY BIDDER TO EXAMINE THE SITE PRIOR TO BID.
2. REVIEW CONSTRUCTION SCHEDULE AND EQUIPMENT LEAD TIMES AND INCLUDE ALL COSTS AND QUICKSHIP CHARGES FOR ALL EQUIPMENT
NEEDED TO MEET SCHEDULE.
1. TO THE BEST OF MY KNOWLEDGE, THE DRAWINGS AND SPECIFICATIONS COMPLY
WITH THE MINIMUM BUILDING CODE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
6TH EDITION (2017) AND THE FLORIDA FIRE PREVENTION CODE, 6TH EDITION (2017).
LD DOOR GRILLE (24"X24" UNO)
APPLICABLE CODES:
BUILDING CODE: FLORIDA BUILDING CODE 2017 EDITION
MECHANICAL CODE: FLORIDA MECHANICAL CODE 2017 EDITION
PLUMBING CODE: FLORIDA PLUMBING CODE 2017 EDITION
GAS CODE: FLORIDA GAS CODE 2017 EDITION
ELECTRICAL CODE: NATIONAL ELECTRIC CODE 2014 EDITION
LIFE SAFETY CODE: FLORIDA FIRE PREVENTION CODE 2017 (6th EDITION)
NFPA 101 CODE 2012
SREF: STATE REQUIREMENTS FOR EDUCATIONAL FACILITIES 2017
M0.01
Mechanical Legend and N
otes
Do
na
ld
J. S
ab
isto
n, P
.E
.
Sta
te
o
f F
lo
rid
a N
o. 5
48
89
DRAWING NO.
SHEE
T TI
TLE
AE PROJECT NUMBER
DRAWN BYDESIGNED BY
ARCH/ENGR OF RECORD
ISSUE DATE
DOCU
MENT
HIS
TORY
RE
VIS
IO
NS
VCS
Proje
ct NO
. 204
7725
UPGR
ADE
HVAC
BLD
G. 1
100 C
OR
BIN
A
VE
,
OR
MO
ND
B
EA
CH
, F
L 32174
DJS
DJS
190074/20/2020
Engineer
Donald J. Sabiston, P.E.
ORMO
ND B
EACH
ELE
MENT
ARY
NO.
DATE
DESC
RIPT
ION
SEG
Pro
ject
No.
19007
Sab
isto
n E
ngi
nee
ring
Gro
up, In
c.
ww
w.S
abis
tonE
ngin
eeri
ng.c
omS
tate
of
Flori
da C
erti
fica
te N
o. 9811
P: 407.8
84.6
769
F: 4
07.8
84.6
764
322 K
entu
cky
Blu
e C
ircl
e, A
popk
a, F
L 32712
131
113B
113
113A
122
120A
124B
122A
OAU
1
10"Ø
20X20 OVER 22X22
DOUBLE WALL DUCTS
X
20
20
10"Ø
22X22
20X20 OVER 22X22
20X20
DN
EDH
OA.1
EDH
OA.2
BELOW
ABOVE
GENERAL NOTES:
KEY NOTES:
1. DEMOLISH ALL EQUIPMENT INDICATED WITH HATCHING OR INDICATED TO BE
DEMOLISHED. DEMOLISH ALL WORK ASSOCIATED WITH THE SYSTEMS
DEMOLISHED (INCLUDING CONTROLS, PIPING AND ELECTRICAL WORK) UNLESS
NOTED OTHERWISE.
2. FIELD INVESTIGATE REQUIREMENTS FOR DEMOLITION. PROVIDE ALL LABOR
AND MATERIALS NEEDED.
3. EXISTING EQUIPMENT THAT IS TO REMAIN SHALL BE PROTECTED FROM
DAMAGE DURING CONSTRUCTION. ALL EXISTING TO REMAIN DUCTWORK
SYSTEMS SHALL BE SEALED WITH VISQUEEN DURING THE ENTIRE
CONSTRUCTION PROCESS.
1. DEMOLISH OUTSIDE AIR UNIT AND ALL ASSOCIATED EQUIPMENT.
2. DEMOLISH DUCTWORK AND SUPPORTS AS INDICATED AND PREPARE FOR
NEW DUCT CONNECTION.
3. DEMOLISH ELECTRIC DUCT HEATER AND ALL ASSOCIATED ELECTRICAL AND
CONTROLS.
MM
1
2
2
3
3
131
113B
113
113A
122
120A
124B
122A
10"Ø
EXISTING 20X20 OVER 22X22
DOUBLE WALL SA DUCTS
X
20
20
10"Ø
GENERAL NOTES:
KEY NOTES:
1. COORDINATE EXACT LOCATION OF NEW EQUIPMENT WITH EXISTING
CONDITIONS AND REQUIRED MAINTENANCE ACCESS CLEARANCES.
2. ALL DUCTWORK SHALL BE DOUBLE-WALL, PRIMED AND PAINTED.
3. DUCT SUPPORTS AND FASTENERS SHALL BE HOT DIPPED GALVANIZED AND
PLACEMENT SHALL NOT INTERFERE WITH MAINTENANCE ACCESS.
1. PROVIDE NEW UNIT PER SCHEDULE AND DETAIL.
2. CONNECT TO SA DISCHARGE. TRANSITION DUCT AND ROUTE TO EXISTING
DUCT CONNECTION POINT. SUPPORT DUCT AS INDICATED.
3. PAINT SLAB MOUNTED CONDUIT CAUTION YELLOW WITH BLACK STRIPES.
4. PROVIDE TRAP AND ROUTE 1-1/2" COPPER CONDENSATE PIPE TO DRYWELL.
ANCHOR WITH SS HARDWARE.
5. PROVIDE DRYWELL PER DETAIL.
6. NEW EMS PANEL LOCATION. PROVIDE SS UNISTRUT MOUNTING RACK WITH
SS HARDWARE.
MM
ELEC
OAU
1
1
2
3
4
5
6
TRANSITION
TO 22X30
22X30
22X58 PLENUM
DUCT SUPPORT (TYP)
SCALE:
Mechanical Elevation - OAU-1
1/4" = 1'-0"
OAU
1
TRANSITION TO 58X22 PLENUM
30X22
45 DEG SHOE IN
PROVIDE MANUAL DAMPER AND
RECONNECT TO EXISTING 20X20
PROVIDE MANUAL DAMPER AND
RECONNECT TO EXISTING 22X22
DUCT SUPPORT (TYP)
CONCRETE PAD
OAU SUPPORTS
M2.01
Mechanical P
lans B
uilding 1
Do
na
ld
J. S
ab
isto
n, P
.E
.
Sta
te
o
f F
lo
rid
a N
o. 5
48
89
DRAWING NO.
SHEE
T TI
TLE
AE PROJECT NUMBER
DRAWN BYDESIGNED BY
ARCH/ENGR OF RECORD
ISSUE DATE
DOCU
MENT
HIS
TORY
RE
VIS
IO
NS
VCS
Proje
ct NO
. 204
7725
UPGR
ADE
HVAC
BLD
G. 1
100 C
OR
BIN
A
VE
,
OR
MO
ND
B
EA
CH
, F
L 32174
DJS
DJS
190074/20/2020
Engineer
Donald J. Sabiston, P.E.
ORMO
ND B
EACH
ELE
MENT
ARY
NO.
DATE
DESC
RIPT
ION
SEG
Pro
ject
No.
19007
Sab
isto
n E
ngi
nee
ring
Gro
up, In
c.
ww
w.S
abis
tonE
ngin
eeri
ng.c
omS
tate
of
Flori
da C
erti
fica
te N
o. 9811
P: 407.8
84.6
769
F: 4
07.8
84.6
764
322 K
entu
cky
Blu
e C
ircl
e, A
popk
a, F
L 32712
KEYPLAN
SCALE: N.T.S.
WORK AREA
SCALE:
Mechanical Demolition Plan - Building 1
1/8" = 1'-0"
SCALE:
Mechanical Renovation Plan - Building 1
1/8" = 1'-0"
PITCH TOWARD DRAIN
1" MIN. GAP
4"
4"
DRAIN PAN
OPEN CONDENSATE DRAIN VENT
SCALE:
3
CONDENSATE TRAP DETAIL
NOT TO SCALE
TO
DRYWELL
ZURN AIR GAP
FITTING
CLEAN OUT
(TYPICAL)
SIZE CONDENSATE DRAIN PIPE TO OAU OUTLET
PROVIDE COUPLING OR DIELECTRIC AS REQUIRED
6"-12"
12" MIN
36"
36"
GROUT AROUND PENETRATION
DRAIN LINE
SCALE:
4
VERTICAL DRYWELL DETAIL
NOT TO SCALE
36X36 QUAZITE BOX
WITH OPEN BOTTOM
GRAVEL
COURSE ROCK OR
FEATHER GRADE 24" OUT TO EDGE OF BOX
FINISHED GRADE
SET BOX APPROX 2" ABOVE GRADE
BOLT DOWN LID WITH HANDLE
NOTES:
1. BOX TO BE QUAZITE PG STYLE (STACKABLE) OR EQUAL.
2. DESIGN LOADS SHALL BE:
2.1. GRASSY AREA 8,000 LB (ANSI TIER 8) OR HIGHER.
2.2. POTENTIAL VEHICULAR TRAFFIC AREAS: 15,000 LBS (ANSI TIER 15)
LAY BRICKS AROUND ENTIRE
PERIMETER TO SUPPORT BOX
SOIL COMPACTED TO 95%
FLEXIBLE CONNECTION
SHEETMETAL RAIN SHIELD
(TOP AND SIDES) SEAL TO UNIT
SLOPE DUCT AWAY FROM UNIT
UNIT SUPPORTS
2" THICK NEOPRENE
INSULATION AROUND
FLEX CONNECTION
OUTSIDE AIR UNIT
SCALE:
OUTSIDE AIR UNIT SUPPORT DETAIL
NOT TO SCALE
1
SCALE:
OUTSIDE AIR UNIT INSTALLATION DETAIL
NOT TO SCALE
5
NOTES:
1. SUPPORTS AND HARDWARE SHALL BE HOT DIPPED GALVANIZED.
2. PAINT ALL WELD AREAS WITH COLD GALVANIZING SPRAY.
SCALE:
OUTDOOR DUCT SUPPORT DETAIL
NOT TO SCALE
2
3/16
1/4"X6"X6" PLATE
1/4"X3" SS WEDGE ANCHOR
(EACH CORNER)
DUCTWORK
< 3/16"X2"X2"
CONC PAD
3/8" BOLT WITH FENDER
WASHERS (TYP)
DOUBLEWALL DUCT
OAU
PLAN VIEW
12" LONG I-BEAM
SECTIONS (TYP)
1/2" THICK SKIRTBOARD
RUBBER ISOLATION PADS
1/2" DIA SS BOLT W/WASHER IN EACH
SUPPORT BEAM. INSTALL BOLTS THROUGH
BASE RAIL AND BEAM. SECURE WITH SS
WASHER AND NYLON INSERT SS LOCK NUT.
ALUMINUM BEAM, WFB-8.0X8.0X0.288
(If=8")x1'-0" LONG (TYP). BOLT EACH
TO SLAB AS SHOWN. PAINT W/2
COATS OF ACRYLIC PAINT. 6061-T6
ALUMINUM.
AS REQ'D BY MFG.
NTE 5'-0" O.C. MAX
1/2" DIA SS WEDGE ANCHORS AS
SHOWN. TYP 3" MIN EMBEDMENT INTO
SLAB.
ELEVATION VIEW
EXISTING CONC PAD
NOTES:
1. CENTER BEAMS UNDER BASE RAILS TO DISTRIBUTE WEIGHT EVENLY.
2. BEAM SUPPORT QUANTITY AND LOCATIONS SHALL BE AS RECOMMENDED BY THE MANUFACTURER,
NOT TO EXCEED 5' BETWEEN SUPPORTS.
3. SHIM BETWEEN BEAMS AND ISOLATION PADS TO PROVIDE SUPPORT AT ALL BEAM LOCATIONS.
CHILLER FRAME
EXISTING CONC PAD
EXISTING CONC PADEXISTING GRADE
SCALE:
SPACE MOUNTED DEVICE DIAGRAM
NOT TO SCALE
7
RM
Tem
p
RM
RelH
um
NOTES:
1. PROVIDE A MINIMUM OF ONE HUMIDITY SENSOR
PER FLOOR.
CONTROL SYSTEM LEGEND:
DIGITAL POINT - INPUT
DIGITAL POINT - OUTPUT
ANALOG POINT - INPUT
ANALOG POINT - OUTPUT
NO SYMBOL HARDWIRED CONTROL
SCALE:
DEDICATED OUTSIDE AIR UNIT
NOT TO SCALE
6
S/S
R
SA
R
/H
SUPPLY AIR
OAU
Alarm
R
AM
BIE
NT
SA
T
em
p
UNIT DISCHARGE SENSORS MIN 10' FROM UNIT
AV
G S
pc T
em
p
AV
G S
pc H
um
SEQUENCE OF OPERATION
1.1 GENERAL REQUIREMENTS:
A. BIDDING PROCEDURES:1. THE FOLLOWING SEQUENCE OF OPERATION OUTLINES THE GENERAL MEANS BY WHICH THE EMCS SHALL
INITIATE AND RESPOND TO EVENTS. THE REQUIREMENTS FOR THE CONTROL SYSTEM ARE SHOWN ON THEDRAWINGS, IN THE SEQUENCE OF OPERATIONS, IN THE SCHEDULES, AND IN THE SPECIFICATIONS.
2. MODIFICATIONS TO THE MEANS OF CONTROL WILL BE CONSIDERED, BUT WILL NOT BE ALLOWED IF ENERGYEFFICIENCY IS DECREASED.
B. SCOPE:1. CONTROL SYSTEM EXPANSION: THE EXISTING CONTROL SYSTEM SHALL BE EXPANDED TO INCORPORATE THE
EQUIPMENT AND SEQUENCES OF OPERATION CONTAINED IN THIS PROJECT. PROVIDE ALL LABOR, MATERIALS,AND ENGINEERING NEEDED TO PROVIDE A FULLY FUNCTIONAL CONTROL SYSTEM.a. WHERE EXISTING CENTRAL PLANT EQUIPMENT EXISTS THAT IS REQUIRED FOR NEW EQUIPMENT TO
FUNCTION, THE EMCS SHALL ACTIVATE THE CENTRAL PLANT EQUIPMENT AS NEEDED.2. FIRE ALARM SHUTDOWN: UPON A FIRE ALARM SYSTEM ACTIVATION, THE AIR HANDLING EQUIPMENT SHALL
SHUT DOWN IMMEDIATELY AND WITHOUT DELAY. THE CONTRACTOR SHALL PROVIDE A SHUTDOWN RELAY ORCONTACTOR IN CONTROL CIRCUIT. CONTROL OF CONTACTOR IS BY OTHERS.
3. FIRE ALARM INITIATION: UPON ACTIVATION, DUCT MOUNTED SMOKE DETECTORS OR HEAT DETECTORS SHALLAUTOMATICALLY SHUT DOWN THE SUPPLY FAN AND SEND A SIGNAL TO THE FIRE ALARM SYSTEM. DETECTORSARE FURNISHED, INSTALLED AND WIRED BY OTHERS. THE CONTRACTOR SHALL PROVIDE A SHUTDOWN RELAYOR CONTACTOR IN CONTROL CIRCUIT. CONTROL OF CONTACTOR IS BY OTHERS.
4. COMMUNICATIONS: EACH PIECE OF EQUIPMENT SHALL BE CONTROLLED INDEPENDENTLY BY A STAND-ALONECONTROLLER. IF COMMUNICATIONS ARE LOST WITH THE EMCS NETWORK, THE EQUIPMENT CONTROLLERSHALL CONTINUE TO OPERATE THE EQUIPMENT WITHOUT CHANGING OPERATING MODES OR REDUCINGLOCAL FUNCTIONALITY.
1.2 MISCELLANEOUS SEQUENCES:
A. MINIMUM RUN TIMES:1. EQUIPMENT SHALL BE PROGRAMMED TO PROVIDE MANUFACTURER REQUIRED MINIMUM ON AND OFF TIMES.
MINIMUMS SHALL NOT BE LESS THAN THE FOLLOWING.2. DX TYPE EQUIPMENT:
a. ON: 5 MINUTESb. OFF: 3 MINUTES
1.3 VENTILATION EQUIPMENT SEQUENCES:
A. DEDICATED OUTSIDE AIR EQUIPMENT1. ENABLE/DISABLE: THE OAU SHALL BE ENABLED BASED UPON THE TIME OF DAY VENTILATION SCHEDULE FOR
THE BUILDING.2. ONCE ENABLED, THE OAU SHALL OPERATE VIA INTERNAL CONTROLS TO PROVIDE CONDITIONED VENTILATION
AIR TO THE BUILDING BASED UPON:a. LEAVING AIR TEMPERATURE SENSORSb. BUILDING AVERAGE SPACE TEMPERATUREc. BUILDING AVERAGE RELATIVE HUMIDITY.
3. MOTORIZED DAMPER OPERATION: THE OUTSIDE AIR DAMPER IN THE OAU SHALL OPEN WHEN THE UNIT ISENABLED.
4. THE OAU SHALL PROVIDE AN 'ALARM' TO THE EMS IF PROPER OPERATION IS NOT CONFIRMED BY THE OAUINTERNAL CONTROLS.
B. BATHROOM POWER VENTILATORS:1. ENABLE/DISABLE:
a. INTERIOR BATHROOM: THE PV'S SHALL BE ENABLED BASED UPON THE BUILDING VENTILATION TIME OFDAY SCHEDULE. THE PV SHALL ONLY BE ENABLED WHEN THE AHU IS IN THE OCCUPIED MODE.
2. EXCEPTION: START/STOP OF SINGLE TOILET BATHROOMS MAY BE CONTROLLED BY THE LIGHT SWITCH OROTHER OCCUPANCY SENSOR.
M5.01
Mechanical S
chedules, D
etails, and C
ontrols
Do
na
ld
J. S
ab
isto
n, P
.E
.
Sta
te
o
f F
lo
rid
a N
o. 5
48
89
DRAWING NO.
SHEE
T TI
TLE
AE PROJECT NUMBER
DRAWN BYDESIGNED BY
ARCH/ENGR OF RECORD
ISSUE DATE
DOCU
MENT
HIS
TORY
RE
VIS
IO
NS
VCS
Proje
ct NO
. 204
7725
UPGR
ADE
HVAC
BLD
G. 1
100 C
OR
BIN
A
VE
,
OR
MO
ND
B
EA
CH
, F
L 32174
DJS
DJS
190074/20/2020
Engineer
Donald J. Sabiston, P.E.
ORMO
ND B
EACH
ELE
MENT
ARY
NO.
DATE
DESC
RIPT
ION
SEG
Pro
ject
No.
19007
Sab
isto
n E
ngi
nee
ring
Gro
up, In
c.
ww
w.S
abis
tonE
ngin
eeri
ng.c
omS
tate
of
Flori
da C
erti
fica
te N
o. 9811
P: 407.8
84.6
769
F: 4
07.8
84.6
764
322 K
entu
cky
Blu
e C
ircl
e, A
popk
a, F
L 32712
SHEETNO. ELECTRICAL SHEET INDEX SCALE
E0.01 GENERAL NOTES & ABBREVIATIONS NONE
E0.02 SYMBOL LEGENDS NONE
E2.01 ELECTRICAL PLANS BUILDING 1 1/8" = 1'-0"
E7.01 MECHANICAL FEEDER SCHEDULE AND DETAILS NONE
DRAWING NO.
SHEE
TTI
TLE
AE PROJECT NUMBER
DRAWN BYDESIGNED BY
ARCH/ENGR OF RECORD
ISSUE DATE
DOCU
MENT
HIST
ORY
REV
ISIO
NS
1900704/20/2020
EngineerAdrian Baus, P.E.
NO.
DATE
DESC
RIPT
ION
130 Candace DriveMaitland, FL 32751
VCS
Proje
ctNO
.204
7725
UPGR
ADE
HVAC
BLDG
.1
100
CO
RBI
NAV
E,O
RM
ON
DBE
ACH
,FL
3217
4
ORMO
NDBE
ACH
ELEM
ENTA
RY
AWB AWB
E0.01
DRAWING NO.
SHEE
TTI
TLE
AE PROJECT NUMBER
DRAWN BYDESIGNED BY
ARCH/ENGR OF RECORD
ISSUE DATE
DOCU
MENT
HIST
ORY
REV
ISIO
NS
1900704/20/2020
EngineerAdrian Baus, P.E.
NO.
DATE
DESC
RIPT
ION
130 Candace DriveMaitland, FL 32751
VCS
Proje
ctNO
.204
7725
UPGR
ADE
HVAC
BLDG
.1
100
CO
RBI
NAV
E,O
RM
ON
DBE
ACH
,FL
3217
4
ORMO
NDBE
ACH
ELEM
ENTA
RY
AWB AWB
E0.02
DN
BELOW
ABOVE
ELEC
DRAWING NO.
SHEE
TTI
TLE
AE PROJECT NUMBER
DRAWN BYDESIGNED BY
ARCH/ENGR OF RECORD
ISSUE DATE
DOCU
MENT
HIST
ORY
REV
ISIO
NS
1900704/20/2020
EngineerAdrian Baus, P.E.
NO.
DATE
DESC
RIPT
ION
130 Candace DriveMaitland, FL 32751
VCS
Proje
ctNO
.204
7725
UPGR
ADE
HVAC
BLDG
.1
100
CO
RBI
NAV
E,O
RM
ON
DBE
ACH
,FL
3217
4
ORMO
NDBE
ACH
ELEM
ENTA
RY
KEYPLAN
WORK AREA
AWB AWB
E2.01
6FT. MIN.
COPPER GROUND WIRE (TYP.)
N.T.S.
FINISHED GRADECONDUIT, TYP.
120V CIRCUIT
6" X 6" (MINIMUM) CONCRETE POST
HEIG
HTAS
REQU
IRED
FOR
EQUI
PMEN
T(12
'MIN
IMUM
)
60" MIN.
DRM3
NOTE:COVERS ON RACK MOUNTED RECEPTACLES TO BE WEATHERPROOF WHEN IN USE TYPE.1)
PROVIDE CONCRETEAROUND POST IFREQUIRED FORSUBSTANTIATION OFSOIL, ETC.
DISCONNECTS AS CALLEDFOR ON DRAWINGS
6" X 6" (MINIMUM)CONCRETE POST
GROUND LUG WITHCRIMP CONNECTION
1-1/2" X 1-1/2" STAINLESS STEELCHANNEL HORIZONTAL BRACESAS REQUIRED FOR EQUIPMENTAND CONDUIT
DUPLEX W.P. GFIRECEPTACLE
DISCONNECT RACK (DOUBLE) -FREESTANDING/GRADE MOUNTED
CHILLER CH-1HEAT TAPE 20 AMP 120V 1PH 2W
FED FROM1L1-73 LOCATED IN
BUILDING 1 ROOM 01-142
MECHANICAL EQUIPMENT FEEDER SCHEDULE FOR (9): ORMOND BEACH ELEMENTARY - UPGRADE HVAC BUILDING 1 COPYRIGHT ME, LLC Version : W17f REVISED: September 30, 2019 DATE: April 20, 2020
EQUIPMENT DESCRIPTION VOLTS PH NEUTRALY/N
LARGEST MOTOR COMPRESSOR ADD'L MOTORS HEAT STRIPS MISCAMPS
TOTALFLA
MCA(10)
MOCP(10)
VFDIRC
PANELCB (5)
DISCONNECT SWITCH STARTER WIRE PERPHASE (6)
NEUTRALWIRE (7)
GROUNDWIRE
WIREMATERIAL
# OFRUNS
CONDUITSIZE % VD NOTES
(SEE BELOW)HP FLA LRA FLA(11) LRA FLA LRA KW AMPS CODE SIZE (1) FUSE (2) TYPE (3) CODE TYPE
OAU-1 (FROM MDP TO DISCONNECT) 208 3 N 7.50 24.2 140.0 60.0 166.5 191 240 250 250 2 400 250 4SS #250 KCMIL #4 COPPER 1 3.00 0.47OAU-1 (DISCONNECT TO UNIT) 208 3 N 7.50 24.2 140.0 60.0 166.5 191 240 250 250 #250 KCMIL #4 COPPER 1 2.00
NOTES ( ) NOTES:(A)=CONNECT VIA LINE VOLTAGE T'STAT BY DIV. 23 CONTRACTOR.
(1) PROVIDE DISC SW AT ALL PIECES OF EQUIPMENT AS REQUIRED BY THE N.E.C. AND AHJ UNLESS PROVIDED BY OTHERS (INCLUDING AT MOTORS AND AT STARTERS. MCP = MOTOR CIRCUIT PROTECTOR W/COMBINATION STARTER (B)=CONNECT VIA CONTROL DEVICES BY DIV. 23 CONTRACTOR.
(2) FUSES SHOWN FOR REFERENCE ONLY, PROVIDE FUSES AS RECOMMENDED BY EQUIPMENT MANUFACTURER. MMS = MANUAL MOTOR STARTER SWITCH WITH OVERLOADS AND PILOT LIGHT (C)=CONNECT MOTOR(S) VIA VFD/AFD WITH INTEGRAL DISC. SW.
(3) PROVIDE NEMA OUTDOOR RATED ENCLOSURES FOR ALL DISC SWS MOUNTED OUTDOORS. I = NEMA I ENCLOSURE (D)=CONNECT VIA COMBINATION DISC/STARTER BY DIV. 23 CONTRACTOR.
(4) COORDINATE STARTER TYPE WITH MECH EQUIP INSTALLER . 3R = NEMA 3R ENCLOSURE (E)=CONNECT VIA DISC SWITCH AT EQUIP. BY DIV. 23 CONTRACTOR.
(5) CONTRACTOR TO VERIFY THAT C.B. FOR COMPRESSORS IS SUFFICIENT TO ALLOW STARTING OF UNIT, IF REQUIRED FOR STARTING C.B. TO BE INCREASED TO A MAX ALLOWED BYN.E.C. CB TO BE HACR RATED. 4SS = NEMA 4 WATER TIGHT STAINLESS STEEL ENCLOSURE (F)=PROVIDE FULL SIZE NEUTRAL.
(6) #12 FEEDERS SHOWN AND OVER 50FT. LONG TO BE #10 FOR 120V CIRCUITS. #12 FEEDERS SHOWN AND OVER 100 FT. LONG TO BE #10 FOR 277 V CIRCUITS. 4 = NEMA 4 WATER TIGHT NON-CORROSIVE ENCLOSURE (G)=MMS WITHOUT OVERLOADS.
(7) NEUTRAL CONDUCTOR TO BE SAME SIZE AS PHASE CONDUCTORS. VFD/AFD = VARIABLE (ADJUSTABLE-AFD) FREQ DRIVE UNIT (H)=CONNECT VIA STARTER IN MCC (BY DIV 26).
(8) MOTOR CB IS SIZED BASED ON NEMA CODE 'F' OR HIGHER. CHANGE CB SIZE IF REQUIRED DUE TO NEMA CODE OF MOTOR PER N.E.C. NF = NON-FUSED. WHERE ACCEPTABLE TO AHJ, CONTRACTOR MAY USEPROPERLY RATED MOTOR SWITCH FOR DISCONNECT SWITCH
(I)=2 SPEED,1 WINDING MOTOR/STARTER.
(9) ALL FEEDERS 100 AMP AND LESS ARE BASED ON 60 DEGREE CONDUCTOR/TERMINATION RATING. ALL OTHER FEEDERS ARE BASED ON 75 DEGREE CONDUCTOR TERMINATIONS.PROVIDE AND INSTALL PROPER TERMINATIONS ON ALL EQUIPMENT PROVIDED BY ANY DIVISION AND/OR SECTION OF THE CONTRACT DOCUMENTS. PROPER TERMINATIONS TO BE ASREQUIRED TO MATCH CONDUCTOR WITH REQUIRED AMPACITY.
AHJ = AUTHORITY HAVING JURISDICTION. (J)=COORDINATE WITH DIV.15 TO BALANCE LOAD OF 1 PHASE FTB MOTORS.
(10) BASED ON MANUFACTURER'S RECOMMENDATION. FNVR = FULL VOLTAGE NON-REVERSING (K)=PROVIDE NEW STARTER IN MCC TO MATCH EXISTING. SEE MCC SCHED.
(11) OR BRANCH CIRCUIT SELECTION CURRENT WHEN AVAILABLE. DFNVR = DUAL VOLTAGE NON-REVERSING (L)=WHERE MOTOR IS FED FROM MCC, PANEL CB NOT REQUIREDFVC = FULL VOLTAGE CONTACTOR (M)=CONNECT EXIST DISC SWITCH AT MOTOR. MODIFY AS NOTED ON DRWGS
(N)= PROVIDE SHUNT TRIP OPERATED CIRCUIT BREAKER FOR ELEVATOR MOTORS.(O)=(P)=
DRAWING NO.
SHEE
TTI
TLE
AE PROJECT NUMBER
DRAWN BYDESIGNED BY
ARCH/ENGR OF RECORD
ISSUE DATE
DOCU
MENT
HIST
ORY
REV
ISIO
NS
1900704/20/2020
EngineerAdrian Baus, P.E.
NO.
DATE
DESC
RIPT
ION
130 Candace DriveMaitland, FL 32751
VCS
Proje
ctNO
.204
7725
UPGR
ADE
HVAC
BLDG
.1
100
CO
RBI
NAV
E,O
RM
ON
DBE
ACH
,FL
3217
4
ORMO
NDBE
ACH
ELEM
ENTA
RY
AWB AWB
E7.01