ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s /...

23
TRT-BA-TTK140-170-350-650S-TC2018-54-004-EN TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S EN ORIGINAL INSTRUCTIONS DEHUMIDIFIER

Transcript of ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s /...

Page 1: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

TRT-BA

-TTK140-170-350-650S-TC2

018-54-004-EN

TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

ENORIGINAL INSTRUCTIONSDEHUMIDIFIER

Page 2: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

2 ENdehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Table of contents

Notes regarding the instructions ..........................................  2

Safety .....................................................................................  3

Information about the device................................................  4

Transport and storage...........................................................  6

Assembly and installation.....................................................  6

Operation ...............................................................................  8

Errors and faults ..................................................................  10

Maintenance ........................................................................  11

Technical annex...................................................................  15

Disposal ...............................................................................  22

Declaration of conformity ...................................................  22

Notes regarding the instructions

Symbols

Warning of electrical voltageThis symbol indicates dangers to the life and health ofpersons due to electrical voltage.

WarningThis signal word indicates a hazard with an averagerisk level which, if not avoided, can result in seriousinjury or death.

CautionThis signal word indicates a hazard with a low risklevel which, if not avoided, can result in minor ormoderate injury.

NoteThis signal word indicates important information (e.g.material damage), but does not indicate hazards.

InfoInformation marked with this symbol helps you to carryout your tasks quickly and safely.

Follow the manualInformation marked with this symbol indicates that theinstructions must be observed.

You can download the current version of the instructions andthe EU declaration of conformity via the following link:

TTK 140 S

https://hub.trotec.com/?id=42763

TTK 170 S

https://hub.trotec.com/?id=42764

TTK 350 S

https://hub.trotec.com/?id=42765

TTK 650 S

https://hub.trotec.com/?id=42766

Page 3: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

EN 3dehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Safety

Read this manual carefully before starting or using thedevice. Always store the manual in the immediate vicinityof the device or its site of use!

WarningRead all safety warnings and all instructions.Failure to follow the warnings and instructions mayresult in electric shock, fire and / or serious injury.Save all warnings and instructions for futurereference.This appliance can be used by children aged from8 years and above and persons with reduced physical,sensory or mental capabilities or lack of experienceand knowledge if they have been given supervision orinstruction concerning use of the appliance in a safeway and understand the hazards involved.Children shall not play with the appliance. Cleaning anduser maintenance shall not be made by childrenwithout supervision.

• Do not use the device in potentially explosive rooms.

• Do not use the device in aggressive atmosphere.

• Set the device up in an upright and stable position.

• Let the device dry out after a wet clean. Do not operate itwhen wet.

• Do not use the device with wet or damp hands.

• Do not expose the device to directly squirting water.

• Never insert any objects or limbs into the device.

• Do not cover or transport the device during operation.

• Do not sit on the device.

• This appliance is not a toy! Keep away from children andanimals. Do not leave the device unattended duringoperation.

• Check accessories and connection parts for possibledamage prior to every use of the device. Do not use anydefective devices or device parts.

• Ensure that all electric cables outside of the device areprotected from damage (e.g. caused by animals). Neveruse the device if electric cables or the power connectionare damaged!

• The electrical connection must correspond to thespecifications in chapter Technical data.

• Insert the mains plug into a properly secured mainssocket.

• Observe the device's power input, cable length andintended use when selecting extensions to the powercable. Completely unroll extension cables. Avoid electricaloverload.

• Before carrying out maintenance, care or repair work onthe device, remove the mains plug from the mains socket.Hold onto the mains plug while doing so.

• Switch the device off and disconnect the power cable fromthe mains socket when the device is not in use.

• Do not under any circumstances use the device if youdetect damages on the mains plug or power cable. If the supply cord is damaged, it must be replaced by themanufacturer, its service agent or similarly qualifiedpersons in order to avoid a hazard.Defective power cables pose a serious health risk!

• When positioning the device, observe the minimumdistances from walls and other objects as well as thestorage and operating conditions specified in the Technicaldata chapter.

• Make sure that the air inlet and outlet are not obstructed.

• Make sure that the suction side is kept free of dirt andloose objects.

• Do not remove any safety signs, stickers or labels from thedevice. Keep all safety signs, stickers and labels in legiblecondition.

• Only transport the device in an upright position with anemptied condensation tank or drain hose.

• Discharge the collected condensate before transport andstorage. Do not drink it. Health hazard!

Intended useOnly use the device for drying and dehumidifying room air, whileadhering to and following the technical data.

Intended use comprises:• dehumidifying and drying:

– living rooms, bedrooms, bathrooms and basements– laundries, holiday homes, camper vans, boats

• maintaining the dryness of:

– storage spaces, archives, laboratories, garages– bathrooms, wash rooms, changing rooms etc.

Improper use• Do not place the device on wet or flooded ground.

• Do not place any objects, e.g. clothing, on the device.

• Do not use the device outdoors.

• Any unauthorised modifications, alterations or structuralchanges to the device are forbidden.

• Any operation other than as described in this manual isprohibited. Non-observance renders all claims for liabilityand guarantee null and void.

Page 4: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

4 ENdehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Personnel qualificationsPeople who use this device must:• be aware of the dangers that occur when working with

electric devices in damp areas.

• have read and understood the instructions, especially theSafety chapter.

Maintenance tasks which require the housing to be openedmust only be carried out by specialist companies for cooling andair-conditioning or by Trotec.

Residual risks

Warning of electrical voltageWork on the electrical components must only becarried out by an authorised specialist company!

Warning of electrical voltageBefore any work on the device, remove the mains plugfrom the mains socket!Hold onto the mains plug while pulling the power cableout of the mains socket.

WarningDangers can occur at the device when it is used byuntrained people in an unprofessional or improper way!Observe the personnel qualifications!

WarningThe device is not a toy and does not belong in thehands of children.

WarningRisk of suffocation!Do not leave the packaging lying around. Children mayuse it as a dangerous toy.

NoteDo not operate the device without an inserted air filter!Without the air filter, the inside of the device will beheavily contaminated. This could reduce theperformance and result in damage to the device.

Behaviour in the event of an emergency1. Switch off the device.2. In an emergency, disconnect the device from the mains

feed-in: Hold onto the mains plug while pulling the powercable out of the mains socket.

3. Do not reconnect a defective device to the mains.

Information about the device

Description of the deviceThe device uses the principle of condensation to automaticallydehumidify rooms.

The fan sucks damp room air through the air inlet, the air filter,the evaporator and to the condenser located behind it. The air iscooled at the cold evaporator until it is below the dew point.Water vapour contained in the room air precipitates on theevaporator fins as condensation or rime. The dehumidified,cooled air is slightly warmed at the condenser and blown outagain. The drier air thus conditioned mixes with the air in theroom. The humidity in the room where the device is positionedis reduced as air constantly circulates through the device.

The condensation is fed from the device through thecondensation drain hose connected to the hose connector intoan external container or drain.

Optionally, the condensed water can also be discharged fromthe device by means of a retrofitted condensate pump (seechapter Installing the condensate pump).

For easy operation and transport, the device is fitted with anon / off switch , an operating hours counter, a transport handleand wheels. Two feet with rubber buffers prevent the devicefrom rolling away.

The device can reduce the relative humidity of a room to approx.32 %. Due to the heat radiation generated during operation, theroom temperature may rise by approx. 1–4 °C.

ModelsThe TTK S series comprises the following devices:

TTK 140 S

Page 5: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

EN 5dehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

TTK 170 S / TTK 350 S

TTK 650 S

Note!For simplification purposes the figures used in thisdocumentation only depict one device, which can deviate fromthe actual version. The factual information content remainsunaffected. If necessary in case of relevant differences therespective devices will be shown.

Device depiction

1

2

3

4

5

6

7

10

9

8

1

2

8

9

10

No. Designation

1 Air filter at air inlet

2 Fixing bar of the air filter

3 Hose connector for condensation drain hose(TTK 140 S, TTK 170 S and TTK 350 S only)

4 Condensation tank(TTK 140 S, TTK 170 S and TTK 350 S only)

5 Transport handle(TTK 170 S, TTK 350 S and TTK 650 S only)

6 Condensation drain hose(TTK 650 S only)

7 Castor (TTK 140 S)Wheel (TTK 170 S / TTK 350 S / TTK 650 S)

8 Air outlet

9 Operating elements

10 Carrying handle

Page 6: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

6 ENdehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Transport and storage

NoteIf you store or transport the device improperly, thedevice may be damaged.Note the information regarding transport and storage ofthe device.

TransportBefore transporting the device, observe the following:• Switch off the device.

• Hold onto the mains plug while pulling the power cable outof the mains socket.

• Do not use the power cable to drag the device.

• Drain the remaining condensate from the device and thecondensation drain hose (see chapter Maintenance).

• After unpacking the devices, mount the transport handle asdescribed in the chapter Assembly and installation.

After transporting the device, observe the following:• Set up the device in an upright position after transport.

• Lock the castors of the TTK 140 S.

• After having transported the device in horizontal position,leave the device to rest for 12 to 24 hours, so therefrigerant can accumulate within the compressor. Wait12 to 24 hours before switching the device back on! Actingcontrary might lead to compressor damage and amalfunctioning device. Any warranty claims will be voidedin this case.

StorageBefore storing the device, proceed as follows:• Drain the remaining condensate from the device and the

condensation drain hose (see chapter Maintenance).

• Hold onto the mains plug while pulling the power cable outof the mains socket.

• Drain any possibly remaining condensate.

When the device is not being used, observe the followingstorage conditions:• dry and protected from frost and heat

• in an upright position where it is protected from dust anddirect sunlight

• with a cover to protect it from invasive dust, if necessary

• Place no further devices or objects on top of the device toprevent it from being damaged.

Assembly and installation

Scope of delivery• 1 x Device

• 1 x Manual

Unpacking the device1. Open the cardboard box and take the device out.2. Completely remove the packaging.3. Fully unwind the power cable. Make sure that the power

cable is not damaged and that you do not damage it duringunwinding.

AssemblyUse tools suitable for the intended task.

Mounting the transport handle(TTK 170 S / TTK 350 S / TTK 650 S)Prior to initial start-up, the transport handle must be attached tothe device. To do so, please proceed as follows:

InfoAfter unpacking the device, the two lower screws mustbe unscrewed and the transport handle remountedusing only one screw (i.e. one screw remains).

A.

Page 7: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

EN 7dehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

B.

Start-upWhen positioning the device, observe the minimum distancefrom walls or other objects as described in the Technical datachapter.

A

B

CC

D

• Before restarting the device, check the condition of thepower cable. If there are doubts as to the sound condition,contact the customer service.

• Set the device up in an upright and stable position.

• Do not create tripping hazards when laying the powercable or other electric cables, especially when positioningthe device in the middle of the room. Use cable bridges.

• Make sure that extension cables are completely unrolled.

• When positioning the device, keep a sufficient distance toheat sources.

• Make sure that no curtains or other objects interfere withthe air flow.

• When positioning the device, particularly in wet areas,secure it locally with an RCD (residual current device)which complies with the respective regulations.

Inserting the air filter

NoteDo not operate the device without an inserted air filter!Without the air filter, the inside of the device will beheavily contaminated. This could reduce theperformance and result in damage to the device.

• Make sure that the air filter is installed before switchingthe device on.

Connecting the power cable• Insert the mains plug into a properly secured mains

socket.

Page 8: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

8 ENdehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Operation

Operating elements

12

13

11

TTK 650 S TTK 140/170/350 S

No. Designation Meaning

11 Condensation tank indicator light(TTK 140 S, TTK 170 S andTTK 350 S only)

Is illuminated when thecondensation tank is full ornot installed correctly.

12 On/off switch Switching the device on andoff;Is illuminated when thedevice is switched on

13 Rotary switch Selection of relative roomhumidity

Operating hours/power consumption counterThe device is optionally also available with a simple operatinghours counter or with a combined operating hours and powerconsumption counter (see fig.). Contact your Trotec customerservice.

Switching the device onOnce you have completely installed the device as described inthe Start-up chapter, you can switch it on.1. Carry out the following inspections prior to switch-on:

ð The following only applies to TTK 140 S, TTK 170 Sand TTK 350 S: Ensure that the condensation tank is empty and insertedcorrectly. Otherwise, the device will not operate!

ð The following only applies to the TTK 650 S:Ensure that the condensation drain hose has been laidand mounted properly.

2. Insert the mains plug into a properly secured mainssocket.

3. Switch on the device at the mains switch (12).4. Ensure that the mains switch (12) is lit.5. The following only applies to TTK 140 S, TTK 170 S and

TTK 350 S:Check whether the condensation tank indicator light (11) isout. Otherwise, empty the condensation tank and/or checkit for tight fit.

6. Adjust the relative room humidity level with the rotaryswitch (13).

Continuous operation modeIn continuous operation mode, the device dehumidifies the airconstantly, regardless of the humidity. To start continuousoperation mode, set the rotary switch (13) to Max.

Connecting the condensation drain hose (TTK 140 S / TTK 170 S / TTK 350 S)For continuous operation or unattended dehumidification, pleaseconnect a suitable condensation drain hose to the device.1.

Page 9: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

EN 9dehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

2.

1/2''

Connecting the condensation drain hose (TTK 650 S)For continuous operation or unattended dehumidification, pleaseconnect a suitable condensation drain hose to the device.1.

2.

Automatic defrostIf the room temperature is below 11 °C, the evaporator willfreeze during dehumidification. The device will then carry out anautomatic defrost. The duration of the defrost can vary.• Do not switch the device off during automatic defrost. Do

not remove the mains plug from the mains socket.

Operation with condensate pump (optional)Optionally, the condensed water can also be discharged fromthe device by means of a retrofitted condensate pump (seechapter Available accessories). With a pump performance of upto 50 m and a maximum pump height of 4 m, the condensatecan even be continuously discharged across storeys of abuilding.

Shutdown

Warning of electrical voltageDo not touch the mains plug with wet or damp hands.

• Switch off the device.

• Hold onto the mains plug while pulling the power cable outof the mains socket.

• Clean the device according to the Maintenance chapter.

• Store the device according to the Storage chapter.

Page 10: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

10 ENdehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Errors and faults

The device has been checked for proper functioning severaltimes during production. If malfunctions occur nonetheless,check the device according to the following list.

The device does not start:• Check the power connection.

• Check the power cable and mains plug for damages.

• Check the on-site fusing.

• Check the filling level of the condensation tank and emptyit if necessary. The condensation tank indicator light (11)must not light up.

The device is running, but there is no formation ofcondensate:• When using the condensate pump: Check the

condensation tank and hoses for dirt.

• Ensure that the relative room humidity complies with thetechnical data.

• Check the air filter for dirt. If necessary, clean or replacethe air filter.

• From the outside, check the condenser for dirt (seechapter Maintenance). If the condenser is dirty, have itcleaned by a specialist company or by Trotec.

• The device might carry out an automatic defrost. Duringautomatic defrost, the device does not dehumidify.

The device is loud or vibrates:• Check whether the device is set up in a stable and upright

position.

Condensate is leaking:• Check the device for leaks.

The compressor does not start:• Check the room temperature. Observe the device's

permissible operating range according to the technicaldata.

• Check whether the overheating protection of thecompressor has tripped. Disconnect the device from themains and let it cool down for approx. 10 minutes beforereconnecting it.

• The device might carry out an automatic defrost. Duringautomatic defrost, the device does not dehumidify.

The device gets very warm, is loud or loses power:• Check the air inlets and air filters for dirt. Remove external

dirt.

• From the outside, check the device for dirt (see chapterMaintenance). If the inside of the device is dirty, have itcleaned by a specialist company for cooling and air-conditioning or by Trotec.

NoteWait for at least 3 minutes after maintenance andrepair work. Only then switch the device back on.

Your device still does not operate correctly after thesechecks?Please contact the customer service. If necessary, bring thedevice to a specialist company for cooling and air-conditioningor to Trotec for repair.

Page 11: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

EN 11dehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Maintenance Maintenance intervals

Maintenance and care interval before everystart-up

as needed at least every2 weeks

at least every4 weeks

at least every6 months

at leastannually

Check the air inlets and outlets for dirtand foreign objects and clean ifnecessary

X X

Clean the exterior X X

Visually check the inside of the devicefor dirt

X X

Check the air filter for dirt and foreignobjects and clean or replace ifnecessary

X X

Replace the air filter X

Check for damage X

Check the attachment screws X X

Test run X

Empty the condensation tank and/ordrain hose

X

Maintenance and care logDevice type: ............................................. Device number: ....................................

Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Check air inlets and outlets for dirt andforeign objects and clean if necessary

Clean the exterior

Visually check the inside of the devicefor dirt

Check the air filter for dirt and foreignobjects and clean or replace ifnecessary

Replace the air filter

Check for damage

Check the attachment screws

Test run

Empty the condensation tank and/ordrain hose

Comments

1. Date: ...................................Signature: ................................

2. Date: ....................................Signature: .................................

3. Date: ....................................Signature: .................................

4. Date: ....................................Signature: .................................

5. Date: ...................................Signature: ................................

6. Date: ....................................Signature: .................................

7. Date: ....................................Signature: .................................

8. Date: ....................................Signature: .................................

9. Date: ...................................Signature: ................................

10. Date: ..................................Signature: .................................

11. Date: ..................................Signature: .................................

12. Date: ..................................Signature: .................................

13. Date: .................................Signature: ................................

14. Date: ..................................Signature: .................................

15. Date: ..................................Signature: .................................

16. Date: ..................................Signature: .................................

Page 12: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

12 ENdehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Activities required before starting maintenance

Warning of electrical voltageDo not touch the mains plug with wet or damp hands.

• Switch the device off.

• Hold onto the mains plug while pulling the power cable outof the mains socket.

Warning of electrical voltageTasks which require the housing to be openedmust only be carried out by authorised specialistcompanies or by Trotec.

Cleaning the housingClean the housing with a soft, damp and lint-free cloth. Ensurethat no moisture enters the housing. Protect electricalcomponents from moisture. Do not use any aggressive cleaningagents such as cleaning sprays, solvents, alcohol-based orabrasive cleaners to dampen the cloth.

Visual inspection of the inside of the device for dirt1. Remove the air filter.2. Use a torch to illuminate the openings of the device.3. Check the inside of the device for dirt.4. If you see a thick layer of dust, have the inside of the

device cleaned by a specialist company for cooling and air-conditioning or by Trotec.

5. Put the air filter back in.

Refrigerant circuit• The entire refrigerant circuit is a maintenance-free,

hermetically sealed system and may only be maintained orrepaired by specialist companies for cooling and air-conditioning or by Trotec.

Cleaning the air filter

NoteEnsure that the air filter is not worn or damaged. Thecorners and edges of the air filter must not bedeformed or rounded. Before reinserting the air filter,make sure that it is undamaged and dry!

The air filter has to be cleaned as soon as it is dirty. This isbrought to light e.g. by a reduced capacity (see chapter Errorsand faults).1. Remove the air filter from the device.

Page 13: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

EN 13dehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

2. Clean the filter using a slightly damp, soft, lint-free cloth. Ifthe filter is heavily contaminated, clean it with warm watermixed with a neutral cleaning agent.

3. Allow the filter to dry completely. Do not insert a wet filterinto the device!

4. Reinsert the air filter into the device.

Emptying the condensation tank(TTK 140 S / TTK 170 S / TTK 350 S)

InfoThe compressor always starts with a delay. Thisprotects the compressor and thus increases itslifetime. If you remove the condensation tank from thedevice and reinsert it after emptying, the compressorwill switch back on with a delay of approx. 3 min. Thisdelay is also enabled in optional hygrostat operation. Ifthe room humidity exceeds the setting of the selectionswitch, the compressor will only switch back on after adelay.The fan keeps running independently of thecompressor. The fan only switches off if thecondensation tank is removed.

1.

2.

Page 14: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

14 ENdehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

3.

4.

If the condensation tank is full or not installed correctly, thecondensation tank indicator light (11) will be illuminated. Thecompressor and fan will switch off.

Activities required after maintenanceIf you want to continue using the device:• Reconnect the device to the mains.

If you do not intend to use the device for a considerable time:• Store the device according to the Storage chapter.

Page 15: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

EN 15dehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Technical annex Technical data

Parameter Value

Model TTK 140 S TTK 170 S TTK 350 S TTK 650 S

Dehumidificationperformance @ 30 °C / 80 % RH

35 l / 24 h 40 l / 24 h 55 l / 24 h 125 l / 24 h

Dehumidificationperformance, max.

40 l / 24 h 50 l / 24 h 70 l / 24 h 150 l / 24 h

Operating range(temperature)

5–32 °C 5–32 °C 5–32 °C 5–32 °C

Operating range (relative humidity)

32–100 % RH 32–100 % RH 32–100 % RH 32–100 % RH

Pressure suction side 0.9 MPa 1.2 MPa 1.2 MPa 1.2 MPa

Pressure outlet side 2.5 MPa 4.2 MPa 4.2 MPa 4.2 MPa

Air volume flow 580 m3/h 580 m3/h 1000 m3/h 1000 m3/h

Power supply 230 V / 50 Hz 230 V / 50 Hz 230 V / 50 Hz 230 V / 50 Hz

Power consumption,max.

0.7 kW 0.9 kW 1.3 kW 2.5 kW

Nominal current 3.2 A 4.0 A 5.8 A 11.4 A

Water tank capacity 6 l 6 l 6 l -

Refrigerant R-407C R-410A R-410A R-410A

Amount of refrigerant 475 g 510 g 650 g 1050 g

GWP factor 1,774 2,088 2,088 2,088

CO2 equivalent 0.84 t 1.06 t 1.36 t 2.19 t

Sound pressure level LpA(1 m; complies withDIN 45635-01-KL3)

52 dB(A) 52 dB(A) 54 dB(A) 56 dB(A)

Dimensions(length x width x height) 605 x 400 x 400 mm 635 x 400 x 520 mm 745 x 415 x 520 mm 810 x 415 x 980 mm

Minimum distance towalls or other objects

top (A):rear (B):

sides (C):front (D):

50 cm50 cm50 cm50 cm

50 cm50 cm50 cm50 cm

50 cm50 cm50 cm50 cm

50 cm50 cm50 cm50 cm

Weight 29 kg 32 kg 39 kg 52 kg

Page 16: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

16 ENdehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Wiring diagram

TTK 140 S / TTK 170 S / TTK 350 S

EL

- Earthing / Erdung- Common Line / Gemeinsame

-

--

- Line / AußenleiterOn-O� Switch & Red Lamp /

Geräteschalter 0/1 & Signalleuchte “ rot “lhctiwSorciM-

- Humidistat / Hygrostat- Compressor / Kompressor

Fan motor / LüftermotorTwo Way Valve / Abtau-Magnetventil

- Running Capacitor / Motorbetriebskondensator- Time Counter /

(Tank full)(Behälter voll)

(Tank Full) / Mikroschalter Wippe Vo lstand (Behälter voll)

)053/071()053/071((Optional) (ZZeit Zähler usätzliche)

EN

S1

S2S3M1M2YRC

L

H

N

230V /50Hz

TimeCounter(Optional)

M2M1

PCB(XGNF03)

L N

E

S2 2

1

4

S3

Y

NC NO

LS1

0/1

L N

RC

- Earthing / Erdung- Common Line / Gemeinsame- Line / Außenleiter-

--

On-O� Switch & Red Lamp /Geräteschalter 0/1 & Signalleuchte “ rot “

lhctiwSorciM-- Humidistat / Hygrostat- Compressor / Kompressor

Fan motor / LüftermotorTwo Way Valve / Abtau-Magnetventil

- Running Capacitor / Motorbetriebskondensator- Time + Energy Counter /

(Tank full)(Behälter voll)

(Tank Full) / Mikroschalter Wippe Vo lstand (Behälter voll)

)053/071()053/071(Z()lanoitpO( Zeit + Energie Zähler usätzliche)

ENLS1

S2S3M1M2YRCHE

230V /50Hz

Schuko Plug Schuko Plug

M2M1

PCB(XGNF03)

L N

E

S2 2

1

4

S3

Y

NC NO

LS1

0/1

Lin Lout N

RCTime + EnergyCounter(Optional)

H HE

Wiring diagram with Time Counter (Optional) Wiring diagram with Time & Energy Counter (Optional)

EL

N

Page 17: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

EN 17dehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

TTK 650 S

0/1 ES1

- Earthing / Erdung- Line / Außenleiter- Common Line / Gemeinsame- On-O� switch / Geräteschalter 0/1- Humidistat / Hygrostat- Compressor / Kompressor- Fan motor / Lüftermotor- Two way valve / Abtau-Magnetventil- Power Relay / Leistungsrelais- Running Capacitor / Motorbetriebskondensator

Time counter /-)053/071()053/071(

(Optional) (ZZeit Zähler usätzliche)

ELNS1S2M1M2YRRCH

EL

N

230V /50Hz

M2M1

PCB

L N

Y

NC NO

0/1S1

S2

R

- Earthing / Erdung

- Common Line / Gemeinsame--

-

- Line / Außenleiter

On-O� switch / Geräteschalter 0/1Humidistat / Hygrostat

- Compressor / KompressorFan motor / Lüftermotor

- Two way valve / Abtau-Magnetventil- Power Relay / Leistungsrelais- Running Capacitor / Motorbetriebskondensator- Time & Energy Counter /

)053/071()053/071(Z()lanoitpO( Zeit & Energie Zähler usätzliche)

ELNS1S2M1M2YRRCHE

EL

N

230V /50Hz

M2M1

PCB

L N

Y

NC NO

E

Wiring diagram with Time Counter (Optional) Wiring diagram with Time & Energy Counter (Optional)

TimeCounter(Optional)

L N

H

Lin Lout N

Time + EnergyCounter(Optional)

HE

RCRC

S2

R Schuko Plug Schuko Plug

Page 18: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

18 ENdehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Overview of spare parts and spare parts list TTK 140 S InfoThe position numbers of the spare parts differ fromthose describing the positions of the componentsmentioned in these instructions.

2827

43

4

41

40

6

32

8

7

31

3

10 34

11

21

9

35

26

12

25

36

33

2322

5

24

17

42

16

2

1

30

19

13

14 1

37

29

39

20

44

No. Spare part No. Spare part No. Spare part

1 structural element for Ø 250 fan 16 compressor's metallic bushing 31 tank base plate shaft

2 baseplate 17 compressor's rubber grommet 32 5 1/4 l PP water tank

3 air outlet ventilation grid 19 compressor's relay 33 cable gland and electric terminal block

4 air inlet ventilation grid 20 r407c compressor 34 supply cable

5 motor fan brackets 21 Ø 254 aluminium sucking fan blade 35 mechanical hygrostat

6 PVC hood 22 16 W output electric motor fan 36 hygrostat support

7 water tank base plate 23 finned pack condensing & evaporatingcoil

37 full tank helical springs

8 condensates' water pan 24 electronic printed circuit board 39 top hood thermic isolating adhesivefoam

9 grip 25 ABS hygrostat adjusting knob 40 3/8" water hose, 0.45 m length

10 spinning castor with brake 26 control panel sticker 41 threaded hose connector for 3/4" hose

11 loose spinning castor 27 air filter 42 hour counter gap cover

12 combined power switch, tank fullwarning lamp, silicon cover

28 filter support 43 defrosting system temperature probe

13 defrosting system solenoid valve 29 ABS full tank micro switch protectioncase

44 water tank's bail handle

14 compressor's overload protection 30 full tank micro switch

Page 19: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

EN 19dehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Overview of spare parts and spare parts list TTK 170 S InfoThe position numbers of the spare parts differ fromthose describing the positions of the componentsmentioned in these instructions.

2

9 4 17 18

16

10

15 48

47

22

13

8

5

51

7

20

333446

31

30

39

45

44

14

43

12

49

24

25

40

3

1

11

26

23

21

27

19

38 6

50

29

28

37

No. Spare part No. Spare part No. Spare part

1 structural element for Ø 250 fan 17 air filter 37 defrosting system solenoid valve

2 baseplate 18 filter support 38 top hood thermic isolating adhesive foam

3 air outlet ventilation grid 19 full tank micro switch protection case 39 35 μF running capacitor

4 air inlet ventilation grid 20 full tank micro switch 40 r407c compressor

5 motor fan brackets 21 tank base plate shaft 43 compressor's overload protection

6 PVC hood 22 5 1/4 l PP water tank 44 compressor's rubber grommet

7 water tank base plate 23 cable gland and electric terminal block 45 compressor's metallic bushing

8 condensates' water pan 24 supply cable 46 PA 3 mm saddle spacer for wheels' shaft

9 grip 25 mechanical hygrostat 47 3/8" water hose, 0.45 m length

10 combined power switch, tank full warninglamp, silicon cover

26 hygrostat support 47 Ø 250 wheel

11 Ø 254 aluminium sucking fan blade 27 full tank helical springs 48 threaded hose connector for 3/4" hose

12 16 W output electric motor fan 28 tubular foot 49 hour counter gap cover

13 finned pack condensing & evaporating coil 29 tubular handle 50 defrosting system temperature probe

14 electronic printed circuit board 30 clamping plastic saddle foot 51 water tank's bail handle

15 ABS hygrostat adjusting knob 31 PA 6 mm saddle spacer for tubular handle

16 control panel sticker 34 Ø 20 wheel shaft

Page 20: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

20 ENdehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Overview of spare parts and spare parts list TTK 350 S InfoThe position numbers of the spare parts differ fromthose describing the positions of the componentsmentioned in these instructions.

2

9 4 17 18

16

10

15 48

47

22

13

8

5

51

7

20

333446

31

30

39

45

44

14

43

12

49

24

25

40

3

1

11

26

23

21

27

19

38 6

50

29

28

37

No. Spare part No. Spare part No. Spare part

1 structural element for Ø 300 fan 17 air filter 37 defrosting system solenoid valve

2 baseplate 18 filter support 38 top hood thermic isolating adhesive foam

3 air outlet ventilation grid 19 full tank micro switch protection case 39 35 μF running capacitor

4 air inlet ventilation grid 20 full tank micro switch 40 r407c compressor

5 motor fan brackets 21 tank base plate shaft 43 compressor's overload protection

6 PVC hood 22 5 1/4 l PP water tank 44 compressor's rubber grommet

7 water tank base plate 23 cable gland and electric terminal block 45 compressor's metallic bushing

8 condensates' water pan 24 supply cable 46 PA 3 mm saddle spacer for wheels' shaft

9 grip 25 mechanical hygrostat 47 3/8" water hose, 0.45 m length

10 combined power switch, tank full warninglamp, silicon cover

26 hygrostat support 47 Ø 250 wheel

11 Ø 300 aluminium sucking fan blade 27 full tank helical springs 48 threaded hose connector for 3/4" hose

12 25 W output electric motor fan 28 tubular foot 49 hour counter gap cover

13 finned pack condensing & evaporating coil 29 tubular handle 50 defrosting system temperature probe

14 electronic printed circuit board 30 clamping plastic saddle foot 51 water tank's bail handle

15 ABS hygrostat adjusting knob 31 PA 6 mm saddle spacer for tubular handle

16 control panel sticker 34 Ø 20 wheel shaft

Page 21: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

EN 21dehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Overview of spare parts and spare parts list TTK 650 S InfoThe position numbers of the spare parts differ fromthose describing the positions of the componentsmentioned in these instructions.

7

48

514116

44

31

13

46

10

19

30

54

22

34

25

40

8

2

36

41

3

5

42

21

37

58

33

9

14

182

28

47

15

24

23

35

56

57

26

49

32

43

16

17

No. Spare part No. Spare part No. Spare part

1 baseplate 18 Ø250 wheel 37 compressor's rubber grommet

2 structural element for Ø300 fan 19 Ø20 wheel shaft 40 compressor overload protector

3 air outlet ventilation grid 21 plastic feet for handle 41 50μF running capacitor

4 air inlet ventilation grid 22 PA shaft 3mm spacer 42 electronic printed circuit board

5 back panel 23 hour counter gap cover 43 power relay

6 Pre-coated PVC hood 24 motor fan brackets 44 defrosting system temperature probe

7 tubular handle 25 25 W output electric motor fan 46 cable gland and electric terminal block

8 tubular foot 26 Ø 300 aluminium sucking fan blade 47 supply cable

9 threaded condensates' water pan 28 1/2" to 3/8" reduction pipe bushing 48 thermostatic expansion valve

10 PA 1/2" nut 30 power switch, transparent silicon cover 49 defrosting system solenoid valve

11 air filter 31 ABS hygrostat adjusting knob 51 filter support

13 PA 6 mm saddle spacer 32 control panel sticker 54 turn lock

14 grip 33 finned pack condensing. evaporating coil 56 mechanical hygrostat

15 threaded hose connector 34 top hood thermic isolating adhesive foam 57 hygrostat support

16 3/8" hexagonal threaded plug 35 r407c compressor 58 9/16" water hose, 0.45 m length

17 2x18x25 rubber washer 36 compressor's metallic bushing

Page 22: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

22 ENdehumidifier TTK 140 S / TTK 170 S / TTK 350 S / TTK 650 S

Disposal

The icon with the crossed-out waste bin on wasteelectrical or electronic equipment stipulates that this equipmentmust not be disposed of with the household waste at the end ofits life. You will find collection points for free return of wasteelectrical and electronic equipment in your vicinity. Theaddresses can be obtained from your municipality or localadministration. For further return options provided by us pleaserefer to our website www.trotec24.com.

The separate collection of waste electrical and electronicequipment aims to enable the re-use, recycling and other formsof recovery of waste equipment as well as to prevent negativeeffects for the environment and human health caused by thedisposal of hazardous substances potentially contained in theequipment.

The device is operated with fluorinated greenhouse gas whichcan be dangerous for the environment and contribute to globalwarming when emitted to the atmosphere.

Further information is provided on the nameplate.

Dispose of the refrigerant appropriately and according to thenational regulations.

Declaration of conformity

The text below sets out the contents of the declaration ofconformity. The signed declaration of conformity can be foundat https://hub.trotec.com/?id=42763.

Declaration of conformityIn accordance with the EC Machinery Directive 2006/42/EC,

Annex II, part 1, Section A

Herewith, we – Trotec GmbH & Co. KG – declare that themachinery designated below was developed, constructed andproduced in compliance with the requirements of theEC Machinery Directive in the version 2006/42/EC.

Product model / product: TTK 140 S, TTK 170 S, TTK 350 S, TTK 650 S

Product type: dehumidifier

Year of manufacture as of: 2018

Relevant EU directives:• 2011/65/EU: 1 July 2011

• 2014/30/EU: 29 March 2014

Applied harmonised standards:• EN 55014-2:2015

• EN 55014-1:2017

• EN 60335-1:2012

• EN 60335-1:2012/A11:2014

• EN 60335-2-40:2003

• EN 60335-2-40:2003/A11:2004

• EN 60335-2-40:2003/A12:2005

• EN 60335-2-40:2003/A1:2006

• EN 60335-2-40:2003/A2:2009

• EN 60335-2-40:2003/A13:2012

• EN 61000-3-2:2014

• EN 61000-3-3:2013

Applied national standards and technical specifications:• None

Manufacturer and name of the authorised representative ofthe technical documentation:Trotec GmbH & Co. KG

Grebbener Straße 7, D-52525 Heinsberg

Phone: +49 2452 962-400

E-mail: [email protected]

Place and date of issue:

Heinsberg, 05.09.2018

Detlef von der Lieck, Managing Director

Page 23: ORIGINAL INSTRUCTIONS EN - Ceresol€¦ · trt-ba-ttk140-170-350-650s-tc2018-54-004-en ttk 140 s / ttk 170 s / ttk 350 s / ttk 650 s en original instructions dehumidifier

Trotec GmbH & Co. KG

Grebbener Str. 7D-52525 Heinsberg

+49 2452 962-400+49 2452 962-200

[email protected]