Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477...
Transcript of Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477...
![Page 1: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/1.jpg)
Optimum Airborne and Droplet Precautions
Gompol Suwanpimolkul MD., M.Sc.
Assistant Professor
Infectious Diseases Division
Internal Medicine Department
King Chulalongkorn Memorial Hospital
![Page 2: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/2.jpg)
Center of Disease Control (CDC)
Precaution
- Standard isolation
- Air-borne precaution
- Droplet precaution
- Contact precaution
• Infection transmission
• Air-borne transmission
• Droplet transmission
• Contact transmission
• Vector-borne
• Blood-borne
![Page 3: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/3.jpg)
Airborne transmission
• Airborne transmission occurs only when infectious particles of < 5 µm
• Most lung infections result in droplet transmission whereby the large particles from the cough are transmitted for < 1 m and do not remain suspended in the air
![Page 4: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/4.jpg)
ขนาด (ไมโครเมตร)
เวลาทใชในการตกไกล 3 เมตร
แรงโนมถวง (เซนตเมตร/วนาท)
![Page 5: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/5.jpg)
![Page 6: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/6.jpg)
Microorganisms associated with airborne transmission
Fungi Bacteria Viruses
Numerous reports in
health-care facilities
Aspergillus spp.
Mucorales (Rhizopus
spp.)
Mycobacterium
tuberculosis
Measles
VZV
Atypical, occasional
reports
Acremonium spp.
Fusarium spp.
Pseudoallescheria boydii
Scedosporium spp.
Sporothrix cyanescens
Acinetobacter spp.
Bacillus spp.
Brucella spp.
Staphylococcus aureus
Group A Streptococcus
Smallpox
Influenza viruses
Respiratory syncytial virus
Adenoviruses
Norwalk-like virus
SARS
Airborne in nature;
airborne transmission in
health care settings not
described
Coccidioides immitis
Cryptococcus spp.
Histoplasma capsulatum
Coxiella burnetii (Q fever) Hanta virus
Lassa virus
Marburg virus
Ebola virus
Crimean-Congo viru
Under investigation PCP - -
U.S. Department of Health and Human Services
Centers for Disease Control and Prevention (CDC)
![Page 7: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/7.jpg)
Airborne transmission
• Obligate airborne: การแพรเชอผานทาง airborne เพยงอยางเดยวExample: Tuberculosis
• Preferential airborne: การแพรเชอไดหลายทาง (contact และ droplet ดวย) แตสวนใหญจะแพรแบบ airborne
Example: Chicken pox and Measles
• Opportunistic airborne: การแพรเชอมกจะเปน contact กบ droplet เปนหลก แตอาจแพรแบบ airborne ไดในบางสถานะการ เชน ระหวางการท าหตการทท าใหเกดaerosol-generating procedures
Example: Influenza, Severe Acute Respiratory Syndrome (SARS),
Middle East Respiratory Syndrome Coronavirus (MERS CoV)NEJM 2005
![Page 8: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/8.jpg)
What is an aerosol-generating procedure?
Bronchoscope
Endotracheal intubation
Positive pressure ventilation (BiPAP and CPAP)
Manual ventilation before intubation
Airway suction,
Chest physiotherapy,
Nebulizer treatment, Sputum induction
![Page 9: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/9.jpg)
Influenza may transmit via air-borne
• In has been postulated that healthcare personnel exposed to high risk cough-inducing and aerosolizationprocedures may benefit the most form higher levels of protection guidelines for influenza and MERS CoVprevention
![Page 10: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/10.jpg)
ธรรมชาตของเชอวณโรค
![Page 11: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/11.jpg)
การตดเชอวณโรค และ การปวยเปนวณโรค
1/3 ตดเชอวณโรค
2/3 ไมตดเชอวณโรค
90% ไมปวยตลอดชวต(เชอซอนอยในรางกาย และ ไมแพรเชอ)
10% ปวย
5% ปวยใน 2 ปแรก (early progression)*
5% ปวยหลงจาก 2 ป (reactivation)
*แตคนไขภมตานทานไมดมโอกาสปวยใน 2 ปแรกได > 5% เชน คนไขเอดสอาจปวยแบบ รวดเรวภายใน 2 ป ไดถง 40%
![Page 12: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/12.jpg)
HIV 20-40 50-110
CRF needing dialysis 3-4 30
TNF alpha inhibitors 7-50 10-25
Rx with steroid 2 4.9
Diabetes 3 2-3.6
Undernourished 12 2-3
Smoking 2 2-3
Alcohol use 3 1.5
Age high incidence <4 years 2-5 (young age
when infected (<4 y)
Genetic polymorphisms Gene expression
Transplantation 15-20 20-74
Overcrowding and poverty increased risk increased risk
Recent TB infection (≤ 2 years) NA 15
Apical fibronodular changes on NA 6-19
Chest radiograph
Fold risk of developing active Risk of progression to active
Tuberculosis (ปวยใน 2 ป แรกหลงรบเชอ) tuberculosis in those with
presume latent tuberculosis
Risks factors associated with tuberculosis
K Dheda, Lancet 2016;387:1211-26
![Page 13: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/13.jpg)
ปจจยทมผลตอการแพรกระจายของวณโรค
• ปจจยดานปรมาณของเชอ• การยอมเสมหะ:
• เสมหะยอมสใหผลบวก; 108-1010 ตว/วน• เสมหะยอมสใหผลลบ; < 103 ตวตอ 1
เสมหะ 1 มล.
• มโพรงหนอง หรอ ไมม• รกษาดวยยามาแลว สวนใหญ 2-4 สปดาหหลงรกษา (วณโรคทไมดอยา) เชอมกจะไมแพรแลวความถของการไอ
Clinical Infectious Diseases 1996;23:954-62
![Page 14: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/14.jpg)
โอกาสของการแพรกระจายของเชอ
• การไอ 1 ครง สามารถมเชอ 3000 infectious droplet nuclei = การพดตอเนองนาน 5 นาท และ การจาม 1 ครง สามารถมเชอ ได มากกวา 3000
infectious droplet nuclei
• โดยปกตแลว การไดรบเชอเพยง 1 droplet กสามารถตดเชอวณโรคได
• อากาศในหองทเปนระบบปด ในหองผปวยทเปนวณโรคจะมเชอวณโรครองลอยอยในอากาศไดนานกวา 120 นาทแมวาผปวยวณโรคจะออกจากหองไปแลว
![Page 15: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/15.jpg)
WHO ไดรายงานวา บคลากรทางการแพทย มภาวะเสยงตอการเกด LTBI และ TB disease สงมากกวาประชากรทวไปถง 5.7 เทา
![Page 16: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/16.jpg)
TB-Infection Controls: Simplified
• Administrative: WHO ??• Who is a TB suspect?
• Who is at risk from exposure?
• Who has infectious TB?
• Who has drug resistant TB?
• Environmental: WHERE?• Where is optimal place to minimize risk?
• Personal Respiratory Protection: Special high risk settings
![Page 17: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/17.jpg)
Administrative
1. risk assessment: data
2. Infection control plan
3. HCW training
4. Early identification and diagnosis
5. Patient education
6. Sputum collection
7. Triage of suspect TB patients
8. Reduce exposure in the laboratory.
9. Evaluating infection control interventions
![Page 18: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/18.jpg)
Environment control
![Page 19: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/19.jpg)
มาตรการดานสงแวดลอม
Prevention
Exhaustion
Dilution
Elimination
ถายงไมมการแพรกระจายของเชอไมควรใหมแหลงก าเนดเชอในพนทโดยไมจ าเปน
เมอตองมการแพรกระจายของเชอ
การควบคม ณ แหลงก าเนดเชอวณโรคภายในสงแวดลอม โดยใชระบบระบายอากาศ ณ แหลงก าเนดเชอ
ในขณะมการแพรกระจายของเชอการท าใหเชอโรคทปะปนในอากาศเจอจางโดยการใชระบบระบายอากาศ (โดยวธธรรมชาตและหรอวธกล)
เมอมการแพรกระจายของเชอแลวตองการควบคมไมใหเชอแพรกระจายจากสถานทหนงไปยงอกสถานทหนง โดยการใชอปกรณตางๆ ขอบคณ ผศ.ดร.วรภทร องคโรจนฤทธ
![Page 20: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/20.jpg)
From Theory to Application (?)
![Page 21: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/21.jpg)
General ventilation
1. Ventilation rates: Air change per hour (ACH) • Natural ventilation • Mechanical ventilation
2. Control of airflow patterns in room1. Single-pass air system: all air out 2. Recirculation: HEPA or UVGI
3. Monitor negative pressure: pressure differential should be ≥ 2.5 Pa (0.01” water gauge)
bathroom>isolation room>anteroom>corridors
![Page 22: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/22.jpg)
PD
Natural ventilation
![Page 23: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/23.jpg)
เราจะทดสอบทศทางลมอยางไร ?
![Page 24: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/24.jpg)
หองผปวยทม active TB ถกก าหนดจะตองใหมอยางนอย 12 ACH (air change per hour)
Filtration rate
![Page 25: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/25.jpg)
Minutes required for removal efficiency
ACH 99% 99.9%
2 138 207
4 69 104
6 46 69
12 23 35
15 18 28
20 7 14
50 3 6400 < 1 1
Air changes per hour (ACH) and time required for removal efficiencies of 99% and 99.9% of airborne contaminants
MMWR 2005
![Page 26: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/26.jpg)
TB clinic ควรจะเปน
Natural ventilation หรอ Mechanical ventilation??
![Page 27: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/27.jpg)
General ventilation
1. Ventilation rates: Air change per hour (ACH)
• มการศกษาท South Africa พบวาการปรบพนทของใหมการระบายอากาศทดแบบ natural ventilation สามารถปองกนการแพรกระจายของ XDR-
TB ได 33% (8-35% ขนอยกบทศทางลม)
• การศกษาทประเทศ เปร เปรยบเทยบ natural ventilation กบmechanical ventilation
![Page 28: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/28.jpg)
The study was carried out in eight hospitals in Lima,
Peru;
• 5 รพ.ทเปน ‘‘old fashioned’’ design built pre-1950,
and
• 3 รพ.ทเปน “modern’’ design, built 1970–1990
• Mechanical ventilation
A. Roderick Escombe PLoS Med 2007
![Page 29: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/29.jpg)
![Page 30: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/30.jpg)
A. Roderick Escombe PLoS Med 2007
![Page 31: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/31.jpg)
Mechanical ventilation ก าหนด air change ได 12 ACH ทายซครบวา natural ventilation ไดก ACH
1. 10
2. 20
3. 30
4. 40
5. 50
![Page 32: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/32.jpg)
Type of ventilation ACH Absolute ventilation (m3/h) Calculated risk of TB transmission (%)
All natural vent 28 18-46 2,477 1,162-4,345 16 10-30
Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16
build pre-1950
Natural ventilation 17 12-23 1,174 812-1,627 33 24-47
build 1970-1990
Mechanical vent 12 - 402 330-1,209 39 37-44
Median IQR Median IQR Median IQR
A. Roderick Escombe PLoS Med 2007
Summary statistics for measures of ventilation and calculated TB transmission risk
ACH; air change per hour
![Page 33: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/33.jpg)
General ventilation
1. Ventilation rates: Air change per hour (ACH)
2. Control of airflow patterns in room1. Single-pass air system: all air out
2. Recirculation: HEPA or UVGI
3. Monitor negative pressure: pressure differential should be ≥ 2.5 Pa (0.01” water gauge)
bathroom>isolation room>anteroom>corridors
![Page 34: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/34.jpg)
Examples of Mechanical Ventilation
• Single pass
– First choice
• Recirculating
– HEPA filtration
![Page 35: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/35.jpg)
Recirculating Central Ventilation Unit
![Page 36: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/36.jpg)
General ventilation
1. Ventilation rates: Air change per hour (ACH)
2. Control of airflow patterns in room1. Single-pass air system: all air out
2. Recirculation: HEPA or UVGI
3. Monitor negative pressure: pressure differential should be ≥ 2.5 Pa (0.01” water gauge)
bathroom>isolation room>anteroom>corridors
![Page 37: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/37.jpg)
Positive pressure room
Negative pressure room
Supply air > exhaust air
Exhaust air > Supply air
![Page 38: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/38.jpg)
Engineered specifications for positive and negative pressure room
Positive pressure areas (e.g.,
protective environments [PE])
Negative pressure areas (e.g.,
airborne infection isolation [AII])
ความแตกตางของความดน > + 2.5 Pa (0.01” water gauge) > - 2.5 Pa (0.01” water gauge)
Air changes per hour (ACH) > 12 ≥ 12 (for renovation หรอ new
construction)
ประสทธภาพของการกรอง Filtration Supply (อากาศขาเขา): HEPA (99.97%)
Return air: not required
Supply (อากาศขาเขา): 90% (dust)
Return: HEPA (99.97%)
Airflow direction ออกนอกพนทรอบๆ เขามาในหอง
การก าหนดทศทางการเดนของอากาศClean-to-dirty airflow
Away from the patient
(immunosuppressed patient)
Towards the patient (airborne
disease patient)
U.S. Department of Health and Human Services
Centers for Disease Control and Prevention (CDC)
![Page 39: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/39.jpg)
What is the usefulness of this equipment??
A. Rapid rectal swab for screening
CRE
B. Tube for testing positive or
negative pressure room
C. Novel tube suction for decreasing
rate of pneumonia
D. Special tube for oral care in ICU
patient to prevent VAP
![Page 40: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/40.jpg)
คาทอานได Inches of H2O แปลงเปน Pa
-0.01 คณดวย 249.0819 เทากบ -2.49 Pa
-0.015 คณดวย 249.0819 เทากบ -3.74 Pa
-0.02 คณดวย 249.0819 เทากบ -4.98 Pa
-0.025 คณดวย 249.0819 เทากบ -6.23 Pa
-0.03 คณดวย 249.0819 เทากบ -7.47 Pa
-0.035 คณดวย 249.0819 เทากบ -8.72 Pa
-0.04 คณดวย 249.0819 เทากบ -9.96 Pa
-0.045 คณดวย 249.0819 เทากบ -11.21 Pa
-0.05 คณดวย 249.0819 เทากบ -12.45 Pa
![Page 41: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/41.jpg)
Air-cleaning methods
1. HEPA filtration
2. Ultraviolet germicidal irradiation
![Page 42: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/42.jpg)
High-efficiency particulate air (HEPA)
• An air filter must remove (from the air that passes through) 99.97% of particles that have a size of 0.3 µm.
American Society of Mechanical Engineers, ASME AG-1a–
2004, "Addenda to ASME AG-1–2003 Code on Nuclear Air
and Gas Treatment", 2004
![Page 43: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/43.jpg)
HEPA filter
• Installed in the duct
• On the wall (Ceiling type)
• Portable air cleaner
![Page 44: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/44.jpg)
Portable HEPA filter ชวยไหม??
![Page 45: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/45.jpg)
Small HEPA filter unit
150-250 (cubic feet per minute: CFM)
Large HEPA filter unit300-1200 CFM
![Page 46: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/46.jpg)
HEPA Filter Selection Table
![Page 47: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/47.jpg)
![Page 48: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/48.jpg)
• Portable HEPA filters are used to
a) temporarily recirculate air in rooms with no general ventilation,
b) augment systems that cannot provide adequate airflow, and
c) provide increased effectiveness in airflow
Portable HEPA units are useful engineering controls that help clean the air when the central HVAC system is undergoing repairs, but these units do not satisfy fresh-air requirements
U.S. Department of Health and Human Services
Centers for Disease Control and Prevention (CDC)
![Page 49: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/49.jpg)
Ultraviolet germicidal
irradiation มประโยชนหรอไม??
![Page 50: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/50.jpg)
ทาน คดวา Ultraviolet germicidal irradiation มประโยชนในขอใดถกตอง?
1. ท าใหหองมความเปน negative pressure มากขน
2. ชวยเพม Air change per hour
3. ชวยก าหนดทศทางการไหลเวยนของอากาศ
![Page 51: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/51.jpg)
Ultraviolet germicidal irradiation (UVGI)
• Radiometer: ตรวจวดปรมาณความเขมขนของรงส (มากไป หรอ นอยไป)
• ฝ นทเกาะทหลอด UV: at least every 3mo (ผาชบน าหรอ alcohol)
• Contact time (เชอตองถก UV ในเวลาทเหมาะสม): ถาหองท air change ดอยแลว ไมเหมาะ เพราะ contact time จะสน
• ความชนสมพทธ: not recommended
for rooms in which relative
humidity > 70%
• การระคายเคองตอตา และ ผวหนง
![Page 52: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/52.jpg)
Relative humidity in Thailand
• North 74 %
• North-East 72 %
• Central 73 %
• East 76 %
• South East coast 79 %
• South west coast 80 %
• Peru 87 %
![Page 53: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/53.jpg)
UVGI
• UVGI upper room system: สามารถให air change per hour ประมาณ 10-20 ACH ในหอง ถามการวดและตดตงอยางถกหลก
• มการศกษาใน หนทดลองทประเทศแถบ African พบวา UVGI สามารถลด TB transmission ลงได จาก 35% เหลอ 9.5% และ ลดการเกด active TB ในหนได 8.6% เหลอ 3.6%
Clinical Microbiology and Infection 2016
![Page 54: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/54.jpg)
![Page 55: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/55.jpg)
PLoS Medicine 2009A. Roderick Escombe1,
![Page 56: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/56.jpg)
• Although upper-air UVGI will help dilute the overall room concentration of M. tuberculosis, it will have little beneficial effect on this near field infection risk.
![Page 57: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/57.jpg)
Ultraviolet germicidal irradiation (UVGI)
• ผลของการฆาเชอดวย UV ไมสามารถน ามาเทยบเคยงไดกบการก าหนดใหมอตราการถายเททเหมาะสม
• ถาระบบ HEPA-filtered ไดมาตราฐาน และ มการใช PPE ไดอยางถกตองและเหมาะสมแลว การน า UVGI มาใชอาจไมมผลมากนกในการชวยลดการตดเชอ
• เหมาะส าหรบน าใชในหองขนาดใหญทไมสามารถควบคมระบบไหลเวยนอากาศทด เชน homeless shelters, ER waiting room, เรอนจ า
![Page 58: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/58.jpg)
58
Ultraviolet Germicidal Irradiation (UVGI)
• Used as supplement or back-up to dilution ventilation
• Does NOT provide negative pressure
• Requires maintenance, esp. cleaning bulbs
• Not effective at high humidity (>70%)
• Occupational exposure limits: eye & skin
![Page 59: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/59.jpg)
Simple natural ventilation is better than bad mechanical ventilation
![Page 60: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/60.jpg)
แตขอจ ากดของ natural ventilation
• ไมสามารถก าหนดทศทางของ air flow ไดแนนอนขนกบทศทางลม
• ถาเปนพนททมตกบง ไมไดเปนพนทโลง จะมผลตอทศทางลมและ ACH
• ใชเครองวด air change per hour (ACH) ใหแมนย าไดยาก
• Climate dependent: หนาว ฝนตก หรอ รอนเกน
![Page 61: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/61.jpg)
TB-Infection Controls: Simplified
• Administrative: WHO ??• Who is a TB suspect?
• Who is at risk from exposure?
• Who has infectious TB?
• Who has drug resistant TB?
• Environmental: WHERE?• Where is optimal place to minimize risk?
• Personal Respiratory Protection: Special high risk settings
![Page 62: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/62.jpg)
ทานทราบหรอไมวา หนากาก respirators ชนด N95 นน ตวอกษร N และ ตวเลข 95 หมายความถงอะไร ?
![Page 63: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/63.jpg)
Resistance to efficiency Filter efficiencies
Filter degradation 95 (95%) 99 (99%) 100 (99.97%)
N (Not resistant to oil) N95 N99 N100
R (Resistant to oil) R95 R99 R100
P (Oil proof) P95 P99 P100
Nonpowered air-purifying respirator filter ชนดตางๆ
![Page 64: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/64.jpg)
ทานเคยไดรบการทดสอบ Fit testing หรอไม ทานทราบหรอไมวา Fit testing
คออะไรและมประโยชนอยางไร?
![Page 65: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/65.jpg)
Fit testing
• Saccharin – a sweet tasting solid aerosol;
• Isoamyl acetate – a liquid that produces a sweet smelling vapor similar to bananas;
• BitrexTM – a bitter tasting solid aerosol; and
• Irritant smoke – a solid aerosol made of stannic oxychloride that produces hydrochloric acid when it comes in contact with water vapor. Exposure to the hydrochloric acid produces an involuntary cough reflex.
![Page 66: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/66.jpg)
Respirator Reuse Recommendations (N95)
• Extended use is favored over reuse because it is expected to involve less touching of the respirator and therefore less risk of contact transmission.
• Suggests limiting the number of reuses to no more than five uses per device to ensure an adequate safety margin.
• The straps stretched out so much that they no longer provide enough tension for the respirator to seal to the face
https://www.cdc.gov/niosh/topics/hcwcontrols/recommend
edguidanceextuse.html
![Page 67: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/67.jpg)
Not reuse in cases of:
• N95 respirators following use during aerosol generating procedures.
• N95 respirators contaminated with blood, respiratory or nasal secretions, or other bodily fluids from patients.
• N95 respirators following close contact with any patient co-infected with an infectious disease requiring contact precautions. (SARS)
https://www.cdc.gov/niosh/topics/hcwcontrols/rec
ommendedguidanceextuse.html
![Page 68: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/68.jpg)
Am J Respir Crit Care Med 2012 185(10); 1104–1109
![Page 69: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/69.jpg)
เมอไมใส surgical mask ท าใหหนตะเภาตดเชอ TB 69/90 ตว (76.6%)
ขณะท ผปวยใสหนากากอนามย surgical mask หนตะเภาตดเชอ TB 36/90 ตว (40%)
กลมผปวยวณโรค 2 กลม เปรยบเทยบกบหน 2 กลม
![Page 70: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/70.jpg)
สรปผลการศกษา ของ Harvard university ท าในประเทศแอฟรกาใต
หนากากอนามย สามารถลดการแพรกระจายของเชอวณโรคในอากาศได 56%
Am J
![Page 71: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/71.jpg)
ผทสมผสใกลชด
• นยามของผ ทสมผสใกลชด (Close contact) คอ
•ผ ทอยในสถานทเดยวกน เชน บานเดยวกน หองนอนเดยวกน หองเรยนเดยวกน มการสมผสใกลชดทตอเนองตงแต 8 ชวโมงขนไป
• ถาเปนการสมผสไมตอเนองใหคดเวลารวมตลอดเดอน ถามากกวา 120 ชวโมงขนไป
![Page 72: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/72.jpg)
อายทไดรบเชอกบโอกาสการตดเชอในชวงชวต
อายตอนทรบเชอ โอกาสของการเปนวณโรคในชวงชวต
< 1 ป 43%
1-5 ป 24%
11-15 ป 15%
ผใหญ 5-10%
ขนอยกบปจจยอนๆดวยเชน ระยะเวลาทอยรวมกบผปวย, ระยะการเจบปวยผปวย, มโพรงหนอง
PIDJ 1993;12:499
![Page 73: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/73.jpg)
การศกษานาน 30 ปเพอทจะยนยน วา การให ยา isoniazid (INH) เพอ
ปองกนในเดกมประโยชนในการลดภาวะปวยเปนวณโรคในเดกและวยรน
อตราการเกดวณโรค(/1,000)
ใน ให INH เทยบกบ ไมให INH
ตามไปอก 20 ป 4.2 เทยบกบ 10.1
ตามไปอก 30 ป (เฉพาะท < 3 ป) 0.5 เทยบกบ 7.5
Katharine H. K. Hsu. JAMA 1984;251:1283-5.
![Page 74: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/74.jpg)
• เดกทมอายต ากวา 5 ป จะถอวามความเสยงสงสดทจะปวยเปนวณโรค และถาเปนแลวกจะมโอกาสกระจายทวรางกาย และเปนวณโรคในเยอหมสมองไดสง (การฉดวคซน BCG จะชวยลดอบตการณการเปนวณโรคทวรางกายและวณโรคในเยอหมสมองไดมาประมาณรอยละ 60)
• ในทางปฏบตเดกทอายนอยกวา 5 ปทมประวตสมผสใกลชดกบผ ปวยวณโรคโดยทวไปแลวแนะน าใหรบประทาน ยา isoniazid เพอปองกนการเปนวณโรค 6-9 เดอนทกราย
• แตตองตรวจสอบใหแนชดกอนใหยาปองกนวาเดกไมไดเปนวณโรคอยกอนแลว (ควรถายภาพเอกซเรยปอดกอนใหยาปองกน)
• สวนเดกทอายมากกวาหรอเทากบ 5 ปใหพจารณาเปนรายๆไปตามผลการทดสอบ Tuberculin skin test
![Page 75: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/75.jpg)
การท า tuberculin skin test ในการทดสอบวามเชอวณโรคซอนอยในรางกายหรอไม??
• การท า tuberculin skin test ในการทดสอบวามเชอ
Cut-off 15 10
กลมเสยง 10 10
กลมภมต า 5 5
BCG+ BCG -
![Page 76: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/76.jpg)
FAST for TB Settings
• Finding TB Patients
• Actively: cough surveillance and rapid molecular sputum testing
• Separating safely
• Treatment
INT J TUBERC LUNG DIS 2016;19(4):381–38
![Page 77: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/77.jpg)
Take home messages
• การแพรกระจายของผ ปวยวณโรค ขนอยกบ ปรมาณเชอ (grading AFB smear), ผ ปวยมอาการไอ??, กอนหรอหลงไดรบยา anti-TB, contact time, air change per hour ของหอง เปนตน
• วณโรคไมไดเปนโรคทนารงเกยจ หรอตดงายอยางทคดคนทแขงแรงด รางกายกจะสามารถก าจดเชอทเขามาในปอดได หรอ cell เมดเลอดขาวสามารถโอบลอม ไมใหเชอ active (latent infection)
• หลกการส าคญของ environment control คอ การให air change per hour > 12
ACH, Control of airflow patterns in room, negative pressure
• การใช Natural ventilation เปดหนาตาง ในตกทมการระบายอากาศไดด กยงสามารถท าเปน TB clinic ไดในประเทศไทย ถาไมสามารถใช mechanical ventilation ไดอยางถกตอง และ maintenance อยางเหมาะสม
![Page 78: Optimum Airborne and Droplet Precautions · TB transmission (%) All natural vent 28 18-46 2,477 1,162-4,345 16 10-30 Natural ventilation 40 26-52 3,769 2,477-5,104 11 7.9-16](https://reader036.fdocuments.in/reader036/viewer/2022062917/5ecebefbebc4355d0440b9e8/html5/thumbnails/78.jpg)
Take home messages
• ถาผปวย admit หองแยกโรคทดทสดควรจะท าเปน AII room (negative
pressure with anti-room) แตมอยางจ ากด กควรท าเปนหองแยกโรคทมการระบายอากาศ ตดพดลมดดอากาศ และมการปลอยอากาศเสยทงออกไปอยางเหมาะสม (HEPA, UV duct, ตอ duct สงขนไป > 3 m เหนอระดบทมผคนเดนไปมา)
• Ultraviolet germicidal irradiation (UVGI) อาจน ามาชวยเสรมในการชวยเพม ACH เหมาะส าหรบน าใชในหองทไมสามารถควบคมระบบไหลเวยนอากาศทด เชน homeless shelters, ER waiting room, เรอนจ า และราคาไมแพงเมอเทยบกบ portable HEPA filter
• อยาลมใหคนไขใสหนากากอนามย หนากากอนามย สามารถลดการแพรกระจายของเชอวณโรคในอากาศได