Optimization of a Space Heating Solar System · 2011. 4. 18. · solar panel. We will attempt to...

30
Optimization of a Space Heating Solar System by Mashal Kara A thesis submitted in conformity with the requirements for the degree of Master of Engineering Graduate Department of Mechanical and Industrial Engineering University of Toronto © Copyright by Mashal Kara 2011

Transcript of Optimization of a Space Heating Solar System · 2011. 4. 18. · solar panel. We will attempt to...

  • Optimization of a Space Heating Solar System

    by

    Mashal Kara

    A thesis submitted in conformity with the requirements for the degree of Master of Engineering

    Graduate Department of Mechanical and Industrial Engineering University of Toronto

    © Copyright by Mashal Kara 2011

  • ii

    Optimization of a Space Heating Solar System

    Mashal Kara

    Master of Engineering

    Graduate Department of Mechanical Engineering University of Toronto

    2011

    Abstract

    With the rapid evolution of technology and globalization, our society has become highly

    dependant on the production of energy. As the threat of diminishing fossil fuels and the impact

    these technologies have on the environment, the need for renewable energy has become evident.

    In this project, we attempt to optimize an existing space heating solar technology using

    Computational Fluid Dynamics (CFD) software. Through a series of simulations and the

    construction of different predictive models, we were able to determine the optimal thickness,

    flow rate and pipe diameter for a space heating solar system. During our research we discovered

    that after optimizing the thickness of the panel we were unable improve the results by placing

    obstructions to increase the average flow paths length. These obstructions created too large of a

    resistance for the benefit they could offer. Further studies and experimental trials are needed to

    fully understand how each parameter affects the power output of the system and the power

    needed to run the system.

  • iii

    Acknowledgments

    I would like to start by thanking my supervisor Professor William L. Cleghorn, for his

    continuous support in helping this project come to life. I would also like to thank my industrial

    partner Thomas Gehring for giving me the opportunity to work on a project for the betterment of

    future generations.

    I would like to thank Donna Liu for her administrative assistance, advice and immense support

    throughout my graduate studies. I would also like to thank the University of Toronto and the

    Department of Mechanical and Industrial Engineering for creating a platform where students are

    able to work on meaningful projects.

  • iv

    Table of Contents

    Acknowledgments.......................................................................................................................... iii


    Table of Contents ........................................................................................................................... iv


    List of Symbols or Abbreviations ................................................................................................... v


    1
 Introduction ................................................................................................................................ 1


    1.1
 Background ......................................................................................................................... 1


    1.2
 Objectives and Concept ...................................................................................................... 2


    1.3
 Assumptions........................................................................................................................ 4


    2
 Calculations................................................................................................................................ 6


    3
 Results ........................................................................................................................................ 9


    4
 Parameter Optimization ........................................................................................................... 13


    4.1
 Regression analysis ........................................................................................................... 13


    4.2
 Factorial analysis of turbulent data ................................................................................... 14


    4.3
 Thickness analysis ............................................................................................................ 15


    4.4
 Flow path optimization ..................................................................................................... 17


    5
 Conclusions .............................................................................................................................. 22


    6
 Recommendations .................................................................................................................... 23


    References..................................................................................................................................... 25


  • v

    List of Symbols or Abbreviations

    A Cross sectional area

    Cp Specific heat

    D Pipe diameter

    dh Hydraulic diameter

    L Panel length

    m•

    Mass flow rate through the system

    N1 Number of fans in series

    N2 Number of fans in parallel

    P Static pressure

    Pgen Power generated by the system

    Pin Power input to the system

    Pout Power output from the system

    Q Volumetric flow rate of air through the system

    RE Reynolds number

    t Panel thickness

    Tout Temperature out of the system

    Vin Velocity in the inlet pipe

    v Kinematic viscosity

  • 1

    1 Introduction

    1.1 Background

    Energy emitted from the sun varies with altitude, as we move towards the north, the intensity and

    duration of solar radiation reduces. Solar energy can be captured in a few different ways; the

    main ones are to convert it into electricity or heat.

    Electricity generating solar panels, or photovoltaic solar panels, convert the energy from the sun

    into usable electricity. The most efficient systems feed the power generated into the grid so as to

    avoid losses due to energy transfer and storage. Most photovoltaic systems are able to generate

    on average 150-160 Watts of electricity per square meter of panel from the 1000 Watts per

    square inch emitted by the sun. This technology is less than 20% efficient [1].

    Solar thermal technologies capture the energy of the sun to heat a medium such as water or air

    before it is used. At the moment, solar water heaters are very popular as they are able to deliver

    over 300 Watts of energy per square meter of panel at an efficiency of over 30% depending on

    the size of the system. However, these systems require large hot water tanks to store the heated

    water before use. The installation of these tanks is rather expensive and reduces the payback

    period for the system. This technology is highly used in countries within 45 degrees of latitude

    from the equator. Further north, the effectiveness of this kind of system is reduced due to the

    lack of sun. The efficiency is also reduced further from the equator as cold temperatures in the

    winter increases the energy lost in storage [2].

    Solar energy can also be used to heat air and feed it to the ventilation system of the building thus

    reducing the load carried by the furnace. These systems are only useful in parts of the world

    where heating is required in the winter. They yield similar energy performances as solar water

  • 2

    heater technologies. Since the energy is used as soon as it is generated, these types of systems do

    not require any storage, and thus have very few losses due to storage and energy transfers. At the

    moment, this type of solar technology is not very popular, as it hasn’t been significantly

    promoted in the regions where it can be of value [3].

    1.2 Objectives and Concept

    The objective of this project is to design a lightweight, self-installable and efficient space heating

    solar panel. We will attempt to optimize its efficiency using ANSYS 12.1’s FLUENT module to

    simulate the flow as it enters and exits the solar collector. Each time, we will vary key

    parameters and flow paths and observe the effects on the power output and input. We will first

    optimize physical parameters by performing a set of simulations. Using the data collected during

    the simulations, we will apply statistical tools such as a Multiple Linear Regression (MLR) and a

    Factorial Analysis to model the power input and output as a factor of the three main parameters.

    This model will then be optimized to obtain the settings that yield the highest power generated.

    Then, based on the optimized settings, we will determine the best flow path by creating

    obstructions throughout the panel [4].

    Figure 1, represents a schematic diagram of how space-heating solar systems operate.

  • 3

    Figure 1: Solar space-heating system

    Air is forced by a fan from the space to be heated into the panel where it is heated and then

    returned at a higher temperature. Return air can be delivered directly into a room or fed into the

    ventilation ducts. The concept is simple enough for most homeowners to install the system on

    their own with limited craftsmanship and tools. Figure 2 shows a technical drawing of the solar

    collector panel with all critical dimensions.

    Figure 2: Technical drawing of the solar collector panel

    The critical parameters for the panel are the thickness (t), flow rate of air (Q) and pipe diameter

    (D). Each of these parameters is believed to have an impact on the performance of the system.

    Thickness: It is expected that as thickness is decreased more air will be in contact with the heat

    source thus the heat transfer will be more effective. However, as thickness is reduced, the

    All units in inches t

  • 4

    pressure loss across the system will increase thus increasing the cost of pumping the air through

    the panel.

    Flow rate: An increase in flow rate accelerates the air passing through the panel thus making the

    flow more turbulent, which leads to a higher heat transfer rate and lower head loss. However, an

    increase in flow also increases the required fan power because of the additional amount of air it

    needs to move. Increasing the flow rate also accelerates the air velocity through the panel, giving

    it less time to be in contact with the hot solar collectors, thus the temperature out of the system is

    reduced, and so is the power output.

    Pipe Diameter: A smaller pipe diameter causes the flow to be turbulent as it enters the panel, thus

    facilitating heat transfer and increasing the power output. However, as pipes get smaller, the

    pressure loss across the system increases, and more power is required from the pump [5].

    It seems that to maximize the power generated by the system one would need to reduce the

    thickness and diameter while increasing the flow rate until no additional gain is achieved. We

    expect that as the power output increases, so would the power input. We will thus attempt to find

    the optimal point where an incremental power increase does not require a larger incremental

    power input to run the system.

    1.3 Assumptions

    For this research project, we will assume the flow is laminar when the Reynolds number is below

    2300, and fully turbulent when above. Though we are aware that the flow in question may not be

    fully turbulent, it is the only way to model it using Computational Fluid Dynamics (CFD)

    software. For the fully turbulent flow, we will be using the standard k-epsilon model in ANSYS

    FLUENT, which is governed by the following transfer functions [6]:

  • 5

    (eq 1)

    (eq 2)

    We have also made the assumption that all air properties remain constant throughout the

    simulations, regardless of temperature change. We deemed it appropriate since the ranges of

    temperatures we will be working within do not have a significant impact on air properties.

    To simplify our model, we will assume that there are no losses within our system and that the

    temperature of the solar collectors will remain constant throughout the simulation. Based on

    experimental results, we were able to determine the temperature to be 370 K in clear sunny

    weather. We will use this temperature as part of all our simulations.

  • 6

    2 Calculations Throughout our simulations, we will attempt to calculate the power output and the power input

    required for the system. In order to adequately run the simulations, FLUENT requires the

    velocity at the inlet pipe and the Reynolds number in the panel.

    The velocity of the air as it enters the intake pipe in meters per second can be calculated as

    follows [7]:

    Vin =QA

    (eq 3)

    where Vin is the velocity of the air in the inlet pipe, Q is the volumetric flow rate of air through

    the system, and A is the cross sectional area of the inlet pipe.

    We then need to calculate the Reynolds number in the panel as it will allow us to determine

    whether the flow is turbulent or laminar and select the appropriate model in FLUENT. Based on

    our assumption a Reynolds number over 2300 will be assumed to be fully turbulent and can be

    calculated as follows [7]:

    RE = wdhν

    where

    dh = 2t , and

    w = QtL

    (eq 4)

    where w is the average air velocity in the panel, dh is the hydraulic diameter, v is the kinematic

    viscosity of air, t is the thickness of the panel, Q is the volumetric flow rate of air through the

    system, and L is the length of the panel.

    Given the above information, FLUENT will then output the air temperature out of the panel, the

    pressure drop across the panel and the mass flow rate of air. From these data we need to calculate

    the power output from the panel and the power input required from the fan.

    The power output from the solar panel (Pout) can be calculated as follows [8]:

  • 7

    Pout = cp m•

    ΔT (eq 5)

    where cp is the specific heat of air,

    m•

    is the mass flow rate of air through the system, and

    ΔT is

    the change in temperature from the inlet to the outlet.

    To calculate the power input requires a more complicated procedure. We first need to map the

    system’s pressure vs flow rate curve. Then plot the different fan curves to see which ones

    intercept the system curve at the desired point. Knowing that if multiple fans are placed in series,

    the pressure they generate is to be added, and if they are placed in parallel their flow rates is to

    be added. We add multiple fans in series and sets of fans in parallel to match the flow rate and

    pressure drop required from the system. This concept is illustrated in Figure 3.

    Figure 3: Fans in parallel and series [9]

    Fans can be selected from the Digi-Key fan catalogue online [10], which provides the maximum

    flow rate and static pressure as well as the electrical power of each fan. We can model the fan

    curve for each fan using the data given on the Digi-Key database and the fan equation (eq 6)

    below:

    P = KQ2 + B (eq 6)

  • 8

    Where K and B are constants, P is the static pressure of created by the fan, Q is the volumetric

    flow rate of air through the system.

    We used fan SP101A-1123HST, which is rated to have a maximum flow rate of 105 cfm and a

    maximum pressure of 0.300 inches of water. Using these data and the fan equation (eq 6) we are

    able to come up with an expression relating static pressure and flow rate described in (eq 7).

    P = −(2.675 ×10−5)Q2 + 0.3 (eq 7)

    Knowing that pressure is added when multiple fans are placed in series and that the flow rate is

    added when they are placed in parallel, we came up with the following expression:

    P = N1 −(2.675 ×10−5) ⋅ Q

    N2

    2

    + 0.3

    (eq 8)

    Where N1 is the number of fans in series and N2 is the number of sets of fans in parallel.

    For each simulation we used an Excel solver to find what combination of fans in series and

    parallel could satisfy the system at the given flow rate. The power input was then calculated by

    multiplying the electrical power of each fan (18 Watts) by the number of fans required to match

    the system’s needs.

    Pin= (fan power) x (# of fans) (eq 9)

    Finally, the power generated (Pgen) is calculated by subtracting the power input from the power

    output. This is the key metric that we will try to optimize throughout our simulations.

    Pgen = Pout -Pin (eq 10)

  • 9

    3 Results We ran simulations while the three parameters were varied at the following levels:

    Thickness: 1.5, 2 and 2.5 inches

    Flow rate: 50, 100 and 200 cfm

    Pipe diameter: 4 and 6 inches

    Table 1 shows the results of a series of simulations we ran along with the necessary calculations

    needed. Table 2 shows the results of the output data from FLUENT as well as the calculated

    powers output. With the given data we were able to map the system curves and match them with

    the necessary number of fans to obtain the power input, which is displayed in Table 2.

    Table
1:
Simulation
setup
and
preliminary
calculation
results
 Parameter settings Calculated Values

    Trial no

    t [in]

    Q [cfm]

    D [in]

    Vin [m/s]

    RE number

    Model

    1 1.5 50 4 2.91 1864 Laminar 2 1.5 50 6 1.29 1864 Laminar 3 2 50 4 2.91 1864 Laminar 4 2 50 6 1.29 1864 Laminar 5 2.5 50 4 2.91 1864 Laminar 6 2.5 50 6 1.29 1864 Laminar 7 1.5 100 4 5.82 3729 turb, k-ep, std 8 1.5 100 6 2.58 3729 turb, k-ep, std 9 2 100 4 5.82 3729 turb, k-ep, std

    10 2 100 6 2.58 3729 turb, k-ep, std 11 2.5 100 4 5.82 3729 turb, k-ep, std 12 2.5 100 6 2.58 3729 turb, k-ep, std 13 1.5 200 4 11.64 7459 turb, k-ep, std 14 1.5 200 6 5.17 7459 turb, k-ep, std 15 2 200 4 11.64 7459 turb, k-ep, std 16 2 200 6 5.17 7459 turb, k-ep, std 17 2.5 200 4 11.64 7459 turb, k-ep, std 18 2.5 200 6 5.177 7459 turb, k-ep, std

    



  • 10

    Table
2:
Results
of
first
batch
of
experiments
 FLUENT output Calculated values

    Pressure loss Trial no

    m•

    [kg/s]

    Tout [K] [Pa] [in H2O]

    Power out [kW]

    Power in [kW]

    Pgen = Pout-Pin [kW]

    1 0.029 320 16.29 0.0652 0.59 0.0180 0.57 2 0.029 318 5.346 0.0214 0.53 0.0180 0.52 3 0.029 321 13.46 0.0538 0.62 0.0180 0.60 4 0.029 318 3.69 0.0148 0.52 0.0180 0.50 5 0.029 321 11.66 0.0466 0.62 0.0180 0.60 6 0.029 309 2.977 0.0119 0.26 0.0180 0.24 7 0.058 320 61.48 0.2459 1.17 0.0277 1.15 8 0.058 320 18.33 0.0733 1.15 0.0180 1.13 9 0.058 318 54.02 0.2161 1.09 0.0243 1.07

    10 0.058 318 13.79 0.0552 1.04 0.0180 1.02 11 0.058 317 49.53 0.1981 1.01 0.0223 0.99 12 0.058 316 11.31 0.0452 0.96 0.0180 0.94 13 0.115 316 240.58 0.9623 1.96 0.2167 1.74 14 0.114 316 71.56 0.2862 1.84 0.0645 1.78 15 0.115 315 205.83 0.8233 1.75 0.1854 1.57 16 0.114 314 55.63 0.2225 1.65 0.0501 1.60 17 0.115 314 195.09 0.7804 1.65 0.1758 1.48 18 0.114 312 45.44 0.1818 1.48 0.0409 1.44

    Figures 4 to 6 represent the effect each parameter has on Pout at Pin. Note that Pout is measured

    from the primary scale on the left and Pin from the secondary one on the right of each graph.

    Figure
4:
Changes
in
average
Pin
and
Pout
at
different
thicknesses


  • 11

    As we can see in Figure 4, the power output and the power input decrease as thickness increases.

    The above result confirms our hypothesis that the total heat exchange increases as the thickness

    is reduced, while the pressure drop across the system also increases. It is expected that, at the

    optimal point, if thickness is reduced, the incremental power needed to run the fan would surpass

    the incremental power generated by the system.

    Figure 5: Changes in average Pin and Pout at different flow rates

    Figure 5 confirms our hypothesis that as we increase the flow rate, the power output and the

    power input increase. We see a large difference between the slope of Pin in the laminar (under

    100 cfm) and turbulent (over 100 cfm) regions. This suggests that there may be a significant

    difference in the behaviour of the flow as it becomes turbulent. We do expect that at the optimal

    flow rate, the power needed to pass an incremental amount of flow through the system will be

    larger than the incremental power generated by the system.

  • 12

    Figure 6: Changes in average Pin and Pout as at different pipe diameters

    Figure 6 confirms that as the pipe diameter increases, the pressure drop across the system is

    reduced. However, the data also show that the power output decreases as the pipe diameter

    increases, which goes against our initial hypothesis. This can be explained by the fact that a

    larger pipe diameter will have less minor losses at the entry point, which would explain the drop

    in Pin. A larger pipe diameter also reduces the turbulence of the flow as it enters the panel, thus

    making the heat exchange less efficient and reduces Pout.

  • 13

    4 Parameter Optimization

    4.1 Regression analysis

    In order to optimize the amount of power generated by the system, we performed a Multiple

    Linear Regression (MLR) [11] with the results from our simulations. We attempted to model the

    power output and input as a function of the thickness, flow rate and pipe diameter. The MLR

    model assumes that each factor is linearly correlated to the output, which may not be the case in

    our setup. Using all parameters and interactions, Minitab was able to calculate the following

    coefficients for our model:

    Table
3:
Multiple
Linear
Regression
analysis
coefficients


    Power

    out [kW] Power in

    [kW] Constant -0.81 -0.26 t 0.66 0.030 Q 0.017 0.0043 D 0.22 0.040 t*Q -0.0047 -0.00052 t*D -0.14 -0.0030 Q*D -0.0013 -0.00062 t*Q*D 0.00068 0.000059

    R-squared values were used to evaluate the accuracy of the regressions. The regressions above

    both have R-squared values of over 85%, which makes them significant. Using the above

    coefficients, we attempted to optimize our parameters to maximize the total power generated.

    Entering the coefficients into an Excel spreadsheet and applying a solver algorithm, we were

    unable to find the optimal settings for the thickness, flow rate and pipe diameter. The model

    suggests that thickness be reduced as much as possible, while flow rate and pipe diameter be

    increased to their respective limits. It can thus be concluded that either the optimal parameter

    setting was not captured within the limits of our simulations or that the above model is flawed.

  • 14

    The simulations performed were conducted using two different FLUENT models: one for

    laminar flow and one for turbulent flow. There is a significant difference in the behaviour of the

    flow when it is laminar or turbulent. It may be that the source of our error lies in the

    incompatibility of the two different flow behaviours in a single model. At a flow rate greater than

    100 cfm, the Reynolds number is greater than 2300 and the flow is assumed to be fully turbulent.

    It is evident from Figure 5 that a turbulent flow yield higher performing results. In the next

    section, we will attempt to optimize the turbulent parameters using a two-level full factorial

    analysis in an attempt to achieve the optimal settings.

    4.2 Factorial analysis of turbulent data

    Using only data where the flow in the panel is turbulent (flow rate greater than 100 cfm) and

    focusing on the smaller thicknesses we developed the following parameter limits for a full-

    factorial analysis [11]:

    Table
4:
Factorial
analysis
parameter
limits
 Lower level Upper level

    Thickness [in] 1.5 2 Flow rate [cfm] 100 200

    Pipe diameter [in] 4 6

    Table 5 displays the coefficients calculated by Minitab from the above factorial analysis.

    Table
5:
Factorial
analysis
coefficients


    Power out

    [kW] Power in

    [kW] Constant -0.32 -0.56 t 0.38 0.090 Q 0.016 0.0064 D 0.15 0.082 t*Q -0.0042 -0.0011 t*D -0.075 -0.010 Q*D -0.0011 -0.00092 t*Q*D -0.00043 0.00014

  • 15

    With the calculated coefficients from Table 5, we were able to create new models for the power

    input and output. We tried to optimize thickness, flow rate and diameter to yield the highest

    power generated using an Excel solver. We were initially able to obtain an optimal diameter of

    6.8 inches while the thickness was being reduced to its lowest limit and the flow rate increased to

    its highest limit. We then decided to change the ideal diameter to the closest commercially

    available pipe size: seven inches. After setting the pipe diameter to seven inches and running the

    solver again, the flow rate converged to 200.57 cfm, while the thickness still remained at its

    lowest limit.

    This analysis has allowed the optimization of pipe diameter and flow rate to maximize the

    generated power of the system. It seems that the optimal thickness is not included within the

    limits of our simulations thus a more in depth analysis of the thickness should be implemented.

    The following section will attempt to find an optimal thickness for our system.

    4.3 Thickness analysis

    From the previous data analysis, it seemed that the optimal thickness for the system was not

    captured within the limits of our parameters. We thus ran further simulations maintaining the

    optimal flow rate (200 cfm) and pipe diameter (seven inches), while reducing the thickness in

    quarter inch increments. Table 6 shows the results obtained from the simulations.

    Table
6:
Results
of
thickness
optimization
simulations
Flow rate [cfm]

    Thickness [in]

    Diameter [in]

    Power out [kW]

    Power in [kW]

    Pgen = Pout-Pin [kW]

    200 0.25 7 3.6352 2.1712 1.4640 200 0.5 7 2.9719 0.4239 2.5480 200 0.75 7 2.5630 0.1872 2.3758 200 1 7 2.2485 0.1136 2.1349 200 1.25 7 2.0181 0.0811 1.9369 200 1.5 7 1.8604 0.0638 1.7965

  • 16

    Using Excel, we were able to plot the power output and power input versus the thickness and fit

    lines to them as shown in Figure 7.

    Figure 7: Lines of best fit for Power vs thickness

    The two best fit lines plotted in Figure 7 were selected based on their high R2 values. We then

    inputed the resulting forumulas into an Excel spreadsheet and used the solver function to find the

    optimal thickness. The optimal thickness was found to be 0.48 inches. Thus, according to our

    optimization, a panel with a thickness of 0.48 inches, flow rate of 200 cfm and pipe diameter of

    seven inches should provide a power output of 3.07 kW, an input power of 0.51 kW for a total

    power generation of 2.56 kW.

    We then conducted a verification run with a thickness of 0.5 inches, flow rate of 200 cfm and

    pipe diameter of 7 inches, which resulted in an output power of 2.94 kW and an input power of

    0.33 kW for a total power generation of 2.62 kW. The results from the verification run are fairly

    accurate when compared to those predicted from the model.

  • 17

    4.4 Flow path optimization

    After having selected the optimal parameter settings for the panel, we will attempted to

    determine the most effective flow path of air, while maintaining the optimal parameters for

    thickness, flow rate and pipe diameter. Traditionally, the concept has been to place restrictions

    on the panel to force the air to take a certain path, which will allow it to be in contact with a

    larger surface of the solar collectors thus facilitating more heat transfer. As we vary the flow

    path, we will analyze the streamline of the flow and temperature changes then compare the

    power output and input for each design.

    Looking at the base line case first, Figure 8 shows an isometric view of the model and the

    streamlined flow with a colour gradient indicating changes in the flow’s temperature.

    a) Isometric view b) Flow streamlines and temperature change

    Figure 8: Baseline case results

  • 18

    The flow throughout the panel is steady and uniform. There doesn’t seem to be any interruptions

    of flow, any abnormalities or recirculation. Temperature changes gradually as the flow

    approaches to the output. There is a concentration of warmer air closer to the borders of the

    panel, which may be caused by heat added due to wall friction. One can notice that the longer the

    length of the streamline, the higher temperature obtained at the output. It can thus be expected

    that by moving the input and output as far away from each other as possible we would be able to

    increase the efficiency of the system.

    Our first design, Design number 1, does not have any restrictions either but the input and output

    have been placed in opposite corners of the panel to increase the average distance traveled by the

    air as it enters and exits the panel. Figure 9 represents an isometric view of the model and the

    streamlined flow with a colour gradient indicating changes in the flow’s temperature.

    a) Isometric view b) Flow streamlines and temperature change

    Figure 9: Design #1 results

    Similar to the baseline design, this design displays a steady and uninterrupted flow. There is no

    presence of recirculation. The results for this design are very similar to those of the baseline. It

  • 19

    seems that, again, the majority of the flow does not undergo a significant amount of heat transfer

    as it rushes towards the exit. Presenting obstructions to the flow would reduce its velocity and

    increase the length of the average flow path thus we would expect a higher energy output. It is

    however uncertain as to how these added obstructions would affect the necessary power to

    maintain the desired flow rate.

    The next three designs present the flow with one, two, and three barriers to increase the average

    length of a streamline and facilitate more heat transfer.

    a) Isometric view b) Fluid flow and temperature change

    Figure 10: Design #2 results

  • 20

    a) Isometric view b) Flow streamlines and temperature change

    Figure 11: Design #3 results

    a) Isometric view b) Flow streamlines and temperature change

    Figure 12: Design #4 results

    Figures 10, 11 and 12 show similar flow paths as we increase the number of barriers present. The

    flow is forced to move from one end of the panel to the next making the average length of the

  • 21

    streamlines longer. However, we can see the formation of turbulence at each turn and areas

    where the flow is being recirculated. These areas of turbulence increase the static pressure of the

    system thus also increasing the power needed to run the fan.

    Table 7, summarizes the overall performance of each design.

    Table 7: Performance of different designs

    Design number

    Flow rate [cfm]

    Thickness [in]

    Diameter [in]

    Power out [kW]

    Power in [kW]

    Pgen = Pout-Pin [kW]

    Baseline 200 1.50 6.00 1.84 0.07 1.78 1 200 1.50 6.00 1.86 0.10 1.76 2 200 1.50 6.00 2.41 0.20 2.21 3 200 1.50 6.00 2.12 0.14 1.98 4 200 1.50 6.00 2.66 0.28 2.37

    Out of all the different designs, we can see that the baseline one has the lowest power output but

    the largest power generated due to its relatively low pressure rise. Though the obstructions help

    to increase the power output of the system, the sharp edges create large amounts of turbulence

    that require more power to operate the system. Making the edges of our obstructions more

    streamlined could eliminate these areas of turbulence, however the additional manufacturing cost

    associated with such changes would not justify the slight increase in performance.

    It seems that though the technique of varying the flow path is helpful in practical level, it does

    not have a significant impact once the thickness has been optimized. Adding obstacles to an

    already optimized system will lead to a larger rise in input power than output power thus making

    the fan less efficient.

  • 22

    5 Conclusions From the research explained in this report, we were able to determine that the optimal thickness,

    flow rate and pipe diameter for a four feet by four feet space heating solar panel. The optimal

    parameters being a thickness of 0.5 inches, a flow rate of 200 cfm and a pipe diameter of four

    inches. These parameters are optimal as they maximize the amount of power one can generate

    given the size of the solar panel. Should we modify any of these parameters, the total power

    generation would decrease.

    After optimizing the three key parameters, we discovered that there was no benefit in placing

    obstructions along the flow, as it would only decrease the amount of power generated.

    Obstructions along the flow do help getting a better heat transfer but also create additional

    turbulences, which increase the amount of energy needed to maintain the desired flow rate. We

    can thus say with confidence that it is of more value to optimize the key parameters, mainly the

    thickness, to generate the maximum amount of power from a solar panel.

  • 23

    6 Recommendations Though we were able to obtain optimal parameter settings through a series of simulations, a gap

    still remains to optimize this green technology. Here are a few suggestions for future

    development:

    • Physical verification of results: All our data were based on simulations developed

    using Computational Fluid Dynamics (CFD) software. As is well known, the realities

    of the physical world differ greatly from the idealized computer simulated algorithms.

    It would be of immense value to verify the performance of the said optimized

    parameters.

    • Attempt to achieve similar results at different thicknesses: In our research, we have

    optimized the thickness first thus leaving no room for additional optimization using

    different flow paths. It would be of value to run various simulations at larger, non-

    optimal, thicknesses while testing different flow paths to achieve similar if not greater

    results. One may find that such results are possible or that the added turbulence from

    the non-streamline flow would cause a significant increase in static pressure.

    • Varying pipe diameter: Throughout our study, though we varied the size of the pipes,

    we always maintained the same diameter for input and output pipes. We are aware,

    however that the velocity of the air at the exit is higher due to the increase in

    temperature. It may be of value to analyze the effects of having larger pipes at the

    output so as to accommodate the flow and determine the optimal ratio between input

    and output pipe size.

  • 24

    • In depth study of all parameters: In this research we made the assumption that the

    relationships between the power output or power input and each parameter were

    linear. Due to time constraints, we were only able to perform a detailed analysis of

    the thickness parameter since we believed it had the greatest impact on the output. It

    would be of value to analyze each of the two other parameters (flow rate and pipe

    diameter) in more depth individually so as to gain a better understanding of their

    relationship with the power output and input.

  • 25

    References

    [1] Kreith, Fran & Kreider Jan F. “Principles of Solar Engineering”. Second Edition. Taylor &

    Francis, 2000

    [2] Howell, John R. & Bannerot, Richard B & Vliet, Gary C. “Solar-Thermal Energy Systems”.

    McGraw-Hill, 1982

    [3] Wallace, James S. “MIE515: Alternative Energy Systems”. Course notes. 2010

    [4] Jones, David “Solar Sponge”. [Online]. Available: http://www.solarsponge.com/ [Accessed

    December 10th, 2010]

    [5] Tiwade, P.C & Pathare, N.R. “Performance Analysis of Solar Air Heater by Extended Heat

    Transfer Surfaces, G.H. Raisoni College of Engineering

    [6] Digi-Key, [Online]. Available: http://www.digikey.com/?curr=USD [Accessed December

    15th, 2010]

    [7] White, Frank M. “Fluid Mechanics”. Fifth Edition, McGraw-Hill, 2003

    [8] Cengel, Yunus A. & Boles, Michael A., “Thermodynamics – An Engineering Approach”.

    Fourth Edition. McGraw-Hill, 2002

    [9] Comair Rotron. “Establishing Cooling Requirements”. [Online]. Available:

    http://www.comairrotron.com/engineering_notes_02.asp [Accessed December 10th, 2010]

    [10] Bardina, J.E., Huang, P.G., Coakley, T.J. (1997), "Turbulence Modeling Validation,

    Testing, and Development", NASA Technical Memorandum 110446.

    [11] Nacson, David. “MIE540: Product Design”. Course notes, utpprint, 2009.