Dissolved air flotation and centrifugation as methods for ...
Optimization of a Dissolved Air Flotation System using ...
Transcript of Optimization of a Dissolved Air Flotation System using ...
Proceedings of the International Conference on Industrial Engineering and Operations Management
Dubai, UAE, March 10-12, 2020
© IEOM Society International
Optimization of a Dissolved Air Flotation System using
Factorial Experimental Design in a Water Treatment Plant
at Laguna De Bay
Aaron S. Cornista and Rianina D. Borres
School of Industrial and Engineering Management,
Mapúa University
658 Muralla St., Intramuros, Manila, 1002, Philippines
[email protected], [email protected]
Abstract
A Dissolved Air Flotation System was optimized using factorial experimental design at different turbidity conditions.
Using cluster analysis, historical water quality data was classified into low (0 – 181 NTU) and high (182 – 323 NTU)
turbidity cluster. A multiple regression analysis was performed for each of the cluster which revealed that for low
turbidity cluster eight factors are significant while only three factors were significant for the high turbidity cluster.
Using this knowledge, a factorial experiment was performed for both clusters. A model was generated with R2
adjusted = 86.25% for low turbidity cluster and R2 adjusted = 67.34% for the high turbidity cluster. The accuracy of
the models was tested on actual conditions and showed 92.60% accuracy for the low turbidity cluster and 88.12%
accuracy for the high turbidity cluster.
Keywords Dissolved air flotation system, turbidity reduction, water treatment plant, factorial experimental design
1. Introduction
Clean water is one of the basic necessities of human beings. Although there is more than enough supply of water to
support the increasing world population, access to sanitary water is limited. This is mostly caused by the pollutants
released in bodies of water through the wastes of human activities, specifically agricultural, domestic and industrial
wastes. According to Hu et al. (2014), the increase in urbanization results in the increase in the waste discharges in
the water sources. This is especially true for countries surrounded by large bodies of water such as the Philippines.
Most of its region is within the medium to high risk in terms of water quality (World Resource Institute, 2018). In
Manila, the most urbanized area in the Philippines, clean water source is scarce and could only support 6 million out
of its 12 million inhabitants (Metropolitan Waterworks and Sewerage System, n.d). This was a problem as well as an
opportunity to look for obscure water sources. One such water source is the Laguna de Bay. Laguna de Bay is located
in the southwest part of Metro Manila. It is the largest freshwater lake in Southeast Asia with an approximate surface
area of 90,000 km2, average depth of 2.8 m and maximum depth of 6.5 m (Tamayo-Zafaralla, Santos, Orozco, &
Elegado, 2010). It has a high volume ratio which makes it turbid with spikes in ammonia and manganese during the
major part of the year caused by the polluted inflows coming from various rivers. (Santos-Borja, 1994).
1902
Proceedings of the International Conference on Industrial Engineering and Operations Management
Dubai, UAE, March 10-12, 2020
© IEOM Society International
Figure1. Philippines Overall Water Risk (World Resource Institute, 2018)
Figure 2. Map of Laguna de Bay/Lake
The main pollutants in the lake are as follows: (1) ammonia, (2) manganese, (3) total dissolved solids, and (4) turbidity.
Ammonia can be reduced by nitrification/denitrification procedures aided by ammonia microbes usually on a packed
bed or stirred tank reactors (Koren, Gould, & Bedard, 2000). It can also be reduced through the use of UV/chlorination
(Zhang, Li, Blatchley, Wang, & Pengfei, 2015). Manganese can be easily removed using oxidant such as potassium
permanganate dosing (Salem, El-Awady, & Amin, 2012). High total dissolved solids content can be removed using
reverse osmosis membranes (Fotouhi & Kresic, 2010). Turbidity reduction is done using a sedimentation system or
dissolved air flotation system. Dissolved Air Flotation is generally more effective than sedimentation especially in
algae infested waters such as the Laguna de Bay (Teixeira & Rosa, 2006). It must be noted however that although
DAF is better than conventional sedimentation processes, at turbidity higher than 100 NTU, the efficiency of DAF
turbidity reduction decreases (Kwon, Ahn, & Wang, 2004). Therefore in this study, the level of turbidity must be
defined to account for the efficiency of DAF.
A study on the scaling of up of a dissolved air flotation pilot plant showed a significant different in their performance
because full-scale plant had long retention time and turbulent mixing conditions and higher flow rate which is not
taken into consideration in studies involving pilot plant (Chung, Choi, Choi, & Kang, 2000). Therefore in this study,
1903
Proceedings of the International Conference on Industrial Engineering and Operations Management
Dubai, UAE, March 10-12, 2020
© IEOM Society International
full-scale plant was considered instead of pilot plant to have a more accurate representation of data that can be used
by other plants so we can also see how the efficient is DAF at higher turbidity levels.
The parameters used varied from study to study. Some studies used only water quality and chemical dosing
relationship, some used DAF operating parameters and some used a mixture of both. Therefore, to account for all
possible significant parameters, the operating parameters as well as water quality parameters and chemical dosing
were used. Nominal parameter such as time was also included to account for human errors that may be caused by
morning and night shift.
From this the following output were aimed: (1) Formulate an optimization model of the DAF Performance per different
turbidity conditions. (2)Test the model on actual conditions to determine its effectiveness per different turbidity
conditions.
This study can be used as benchmark for other waste water and waste water treatment plant that uses Dissolved Air
Flotation system. The study focused on the existing Dissolved Air Flotation system of Putatan Water Treatment Plant.
The study was limited on the records and forms available from the plant. The study was performed prior and during
the Amihan season where turbidity values vary significantly to account for the low and high turbidity.
2. Methodology
In order to optimize a full scale dissolved air flotation system; there were several items that were prepared prior to the
experimental runs: (1) the scope of low and high turbidity was first defined; (2) then the factors that have significant
impact on DAF on different turbidity levels were identified. This was done by performing cluster analysis and multiple
regressions on the historical data.
2.1 Definition of Low and High Turbidity
Cluster analysis was used to group the historical data into different conditions of turbidity (High and Low). Using
historical data from June 2017 to November 2018, the variables included were only the inlet water quality parameters
that had direct relationship inlet turbidity: (a) turbidity, (b) TSS, (c) color, (d) organics (D’Sa, Hu, Muller-Karger, &
Carder, 2002). An agglomerative hierarchical algorithm was used using Minitab 18 Statistical Software and the results
were presented in the dendogram below. Square eucledian was used as the distance matrix and the method was
complete linkage.
Figure 3. Dendogram showing two clusters from the sample data
323317
308304319
280279
298288283270
301
300305286277
276
274
273
267
264278
26526926626326
126025925825525325
1232229252237
23923524
123624823423
123022822622522322222
1220219217
216187
246244247
2432 14213215212
208209203210
207
20420219
919
419
219
119
020620
119
819
619
519
320019
718
918
818
618
418
318
218
518
017
317
216
418
117
917
817
117
517
717
617
016
817
416
916
516
216
716
616
116
013
615
415
315
515
115
015
214
314
013
813
913
413
313
713
512
816
315
715
815
614
614
914
214
714
514
414
112
913
213
113
012
612
512
712
412
312
111
710
810
510
09795
116
118
120
119
115
113
112111
110
109
114
103
107
104
102
101
1069998949087
92969391
89838685848281
738880787977767475727157
5654697067665958686564636
16055524962535
15039323031
2448464745434238444
1403637
353433292627251723201828222
119161513141211910876
81.83
87.89
93.94
100.00
Observations
Sim
ilar
ity
DendrogramCentroid Linkage, Squared Euclidean Distance
1904
Proceedings of the International Conference on Industrial Engineering and Operations Management
Dubai, UAE, March 10-12, 2020
© IEOM Society International
Cluster 1 contained samples with turbidity values ranging from 6 – 181 NTU. This was tagged as the “Low Turbidity
Cluster” while Cluster 2 contained samples with turbidity values ranging from 182 – 400 NTU were tagged as “High
Turbidity Cluster”. There were no literatures showing the distinct differences between the low and high turbidity
values. However several literatures suggested that around 200 NTU turbidities were already considered high
(Palaniandy, Adlan, Aziz, & Murshed, 2010). Therefore the 181 NTU lower limit for the high turbidity cluster was
accepted. This definition of low and high turbidity was used for the rest of the experiment.
2.2 Identification of Significant Factors
Upon identification the limits of turbidity level, multiple regression was performed for both clusters in order to
determine the significant parameters. As mentioned in the previous chapter, previous studies showed that parameters
used to optimize DAF cells vary from study to study. To be able to account the effect on various factors, inlet water
quality factors, chemical dosing factors and DAF operating parameter factors were included in the multiple
regressions. To account for the difference in human behavior during morning shift and night shift, a nominal factor
which was time/shift was added in the regression. In order to account for the interaction effect of each individual
variable, they were treated separately regardless of whether they were an inlet water quality factor, chemical dosing
factor, operating parameters or nominal factor. Below is the operational framework showing each variable that was
used in the multiple regressions.
Figure 4 Operational Framework Optimization of DAF
The historical data from June 2017 to November 2018 of all the variables above were used. Stepwise multiple
regressions were used using Minitab 18 Statistical Software and the results were presented in the ANOVA table below.
Table 1. ANOVA table for the stepwise multiple regression of low turbidity cluster
Source DF Adj SS Adj MS F-Value P-Value
1905
Proceedings of the International Conference on Industrial Engineering and Operations Management
Dubai, UAE, March 10-12, 2020
© IEOM Society International
Regression 8 39.226 4.9032 460.96 0
Turbidity 1 15.5406 15.5406 1460.98 0
pH 1 1.0203 1.0203 95.92 0
Temperature 1 1.061 1.061 99.74 0
Dissolved Oxygen 1 0.3149 0.3149 29.6 0
KMnO4 1 1.5393 1.5393 144.71 0
ACH 1 1.2121 1.2121 113.95 0
Influent Flow Rate 1 0.9533 0.9533 89.62 0
Recycle Flow rate 1 0.3301 0.3301 31.04 0
Table 2. ANOVA table for the stepwise multiple regression of high turbidity cluster
Source DF Adj SS Adj MS F-Value P-Value
Regression 3 1.46997 0.48999 20.76 0
TDS 1 0.08211 0.08211 4.24 0.041
Dissolved Manganese 1 0.19584 0.19584 8.3 0.004
Influent Flow Rate 1 0.97901 0.97901 41.48 0
For the low turbidity cluster, eight (8) parameters showed significant effect on turbidity reduction and will be used for
the factorial experimental design: (a) turbidity, (b) influent flow rate, (c) pH, (d) temperature, (e) dissolved oxygen,
(f) KMnO4 dosing, (g) ACH dosing, and (i) recycle flow rate. For the high turbidity cluster, three (3) parameters
showed significant effect on turbidity reduction and will be used for the factorial experimental design: (a) TDS, (b)
dissolved Mn, and (c) influent flow rate.
2.3 Factorial Design Experimentation
For the low turbidity cluster with eight factors (28), a fractional factorial design is used with 1 replicate for each
treatment as (1) there is only limited time for the runs and (2) there are some factors that are not controlled but we
have to wait for them to happen (inlet water quality parameters). Resolution IV was chosen (1/8 fraction) with 32
runs.
For the high turbidity cluster with three factors (23), a full factorial design is used with 1 replicate for each treatment
as (1) there is only limited time for the runs (2) there are some factors that are not controlled but we have to wait for
them to happen (inlet water quality parameters) and (3) the turbidity for December 2018 is low as compared to last
year. Full factorial was chosen with 8 runs.
The experiment was performed from December 1, 2018 to January 3, 2019. The experiment was done in the actual
DAF Cell and measurements were done in the lab for the water quality and checked in the flow meter for the flow
rates. The results were then encoded in Minitab 18 for multiple regressions.
2.4 Testing the effectiveness of the model
From the mathematical model created for the dissolved air flotation system, the model was tested on actual conditions.
The prediction and actual outcome were compared using the equations below.
%𝐴𝑐𝑐𝑢𝑟𝑎𝑐𝑦 =𝑃𝑟𝑒𝑑𝑖𝑐𝑡𝑖𝑜𝑛
𝐴𝑐𝑡𝑢𝑎𝑙
1906
Proceedings of the International Conference on Industrial Engineering and Operations Management
Dubai, UAE, March 10-12, 2020
© IEOM Society International
%𝐸𝑟𝑟𝑜𝑟 =𝐴𝑐𝑡𝑢𝑎𝑙 − 𝑃𝑟𝑒𝑑𝑖𝑐𝑡𝑖𝑜𝑛
𝐴𝑐𝑡𝑢𝑎𝑙
The experiment was performed from January 3-14, 2019. The experiment was done in the actual DAF Cell and
measurements were done in the lab for the water quality and checked in the flow meter for the flow rates.
3. Results and Discussion
3.1 Factorial Design Experimentation
The result of the experiment performed from December 1, 2018 to January 3, 2019 is shown below:
Figure 5. Pareto Chart for Standardized Effects for Low Turbidity Cluster
The top four factors (Turbidity – 46.08%; ACH-Influent Flow rate – 9.08%; ACH – dissolved oxygen – 6.71%; and,
dissolved Mn – 6.20%) constitute 68.09% contribution on the % Turbidity reduction. At low turbidity, %turbidity
reduction was more sensitive to changes in turbidity. Given the equation of turbidity reduction and that the final
turbidity was the same, increasing the initial turbidity would increase the total %turbidity reduction.
%𝑇𝑢𝑟𝑏𝑖𝑑𝑖𝑡𝑦 𝑅𝑒𝑑𝑢𝑐𝑡𝑖𝑜𝑛 =𝐼𝑛𝑖𝑡𝑖𝑎𝑙 𝑇𝑢𝑟𝑏𝑖𝑑𝑖𝑡𝑦 − 𝐹𝑖𝑛𝑎𝑙 𝑇𝑢𝑟𝑏𝑖𝑑𝑖𝑡𝑦
𝐼𝑛𝑖𝑡𝑖𝑎𝑙 𝑇𝑢𝑟𝑏𝑖𝑑𝑖𝑡𝑦
The relationship of ACH and Influent with regards to turbidity reduction was the effectiveness of coagulation through
rapid mixing. ACH was injected to the influent and coagulation was induced through the high flow rate of the influent.
A good combination of the flow and chemical dosing would lead to improvement in turbidity reduction (Kan, Huang,
& Pan, 2002).
The relationship of ACH and dissolved Oxygen with regards to turbidity reduction was the effectiveness of
coagulation and aeration. High dissolved oxygen in the system would mean that the coagulated particles can be easily
floated in the tank (Dehghani, Karimi, & Rajaei, 2016).
1907
Proceedings of the International Conference on Industrial Engineering and Operations Management
Dubai, UAE, March 10-12, 2020
© IEOM Society International
The effect of dissolved Manganese with regards to turbidity reduction was on the formation of manganese dioxide.
High dissolved manganese results in color and added in the turbidity of the system (Dvorak, 2014). The regression
model generated is as follows:
𝑇𝑢𝑟𝑏𝑖𝑑𝑖𝑡𝑦 𝑅𝑒𝑑𝑢𝑐𝑡𝑖𝑜𝑛
= 3.375 − 0.01005[Turbidity(𝑁𝑇𝑈)] − 0.319[𝑝𝐻] − 0.000527[𝑇𝐷𝑆(𝑝𝑝𝑚)]− 0.1669[𝐷𝑖𝑠𝑠. 𝑀𝑛(𝑝𝑝𝑚)] + 0.058[𝐴𝐶𝐻(𝑝𝑝𝑚)] − 0.000189[𝐼𝑛𝑓𝑙𝑢𝑒𝑛𝑡 𝐹𝑙𝑜𝑤 𝑅𝑎𝑡𝑒(𝐿/𝑠)]+ 0.002219[𝑅𝑒𝑐𝑦𝑐𝑙𝑒 𝐹𝑙𝑜𝑤 𝑟𝑎𝑡𝑒(𝐿/𝑠)] − 0.3107[𝐷𝑖𝑠𝑠𝑜𝑙𝑣𝑒𝑑 𝑂𝑥𝑦𝑔𝑒𝑛(𝑝𝑝𝑚)]+ 0.001150[Turbidity(𝑁𝑇𝑈)][𝑝𝐻] − 0.00259[Turbidity(𝑁𝑇𝑈)][𝐴𝐶𝐻(𝑝𝑝𝑚)]− 0.000001[Turbidity(𝑁𝑇𝑈)][𝐼𝑛𝑓𝑙𝑢𝑒𝑛𝑡 𝐹𝑙𝑜𝑤 𝑅𝑎𝑡𝑒(𝐿/𝑠)]+ 0.002091[Turbidity(𝑁𝑇𝑈)][𝐷𝑖𝑠𝑠𝑜𝑙𝑣𝑒𝑑 𝑂𝑥𝑦𝑔𝑒𝑛(𝑝𝑝𝑚)] − 0.0062[𝑝𝐻][𝐴𝐶𝐻(𝑝𝑝𝑚)]+ 0.0374[𝑝𝐻][𝐷𝑖𝑠𝑠𝑜𝑙𝑣𝑒𝑑 𝑂𝑥𝑦𝑔𝑒𝑛(𝑝𝑝𝑚)] − 0.000006[𝑇𝐷𝑆(𝑝𝑝𝑚)][𝑅𝑒𝑐𝑦𝑐𝑙𝑒 𝐹𝑙𝑜𝑤 𝑟𝑎𝑡𝑒(𝐿/𝑠)]+ 0.000115[𝑇𝐷𝑆(𝑝𝑝𝑚)][𝐷𝑖𝑠𝑠𝑜𝑙𝑣𝑒𝑑 𝑂𝑥𝑦𝑔𝑒𝑛(𝑝𝑝𝑚)]+ 0.000118[𝐴𝐶𝐻(𝑝𝑝𝑚)][𝐼𝑛𝑓𝑙𝑢𝑒𝑛𝑡 𝐹𝑙𝑜𝑤 𝑅𝑎𝑡𝑒(𝐿/𝑠)]− 0.00808[𝐴𝐶𝐻(𝑝𝑝𝑚)][𝐷𝑖𝑠𝑠𝑜𝑙𝑣𝑒𝑑 𝑂𝑥𝑦𝑔𝑒𝑛(𝑝𝑝𝑚)]+ 0.000341[Turbidity(𝑁𝑇𝑈)][𝑝𝐻][𝐴𝐶𝐻(𝑝𝑝𝑚)]− 0.000264[Turbidity(𝑁𝑇𝑈)][𝑝𝐻][𝐷𝑖𝑠𝑠𝑜𝑙𝑣𝑒𝑑 𝑂𝑥𝑦𝑔𝑒𝑛(𝑝𝑝𝑚)]
Figure 6. Pareto Chart for Standardized Effects for Low Turbidity Cluster
At high turbidity, only handful parameters have effect on turbidity reduction as the capacity of DAF is already reached.
The saturators are clogged and the air could not push the solids upward which cause the sludge to sink on the floor.
The only parameter in the experiment that showed a significant effect is the joint interaction of TDS and influent flow
rate. The combination of TDS and influent flowrate accounts the rate of dosing ionic salts in DAF. At high turbidity,
the level of air to solids ratio is very much affected because during these conditions, the denominator is much higher
than the numerator. The presence of TDS has a significant effect on the solubility of air in the water. This results in a
much lower air to solids ratio and lower %turbidity reduction (Haarhoff & Edzwald, 2013). The regression model
generated is as follows:
𝑇𝑢𝑟𝑏𝑖𝑑𝑖𝑡𝑦 𝑅𝑒𝑑𝑢𝑐𝑡𝑖𝑜𝑛= 1.164 − 0.002037[𝑇𝐷𝑆(𝑝𝑝𝑚)] − 0.002776[𝐼𝑛𝑓𝑙𝑢𝑒𝑛𝑡 𝐹𝑙𝑜𝑤 𝑅𝑎𝑡𝑒(𝐿/𝑠)]+ 0.000009[Turbidity(𝑁𝑇𝑈)][𝐼𝑛𝑓𝑙𝑢𝑒𝑛𝑡 𝐹𝑙𝑜𝑤 𝑅𝑎𝑡𝑒(𝐿/𝑠)]
3.2 Testing the effectiveness of the model
After the models are generated, this was tested in actual setting. The result of the experiment performed from January
3 – 14, 2019 at the plant is shown below:
1908
Proceedings of the International Conference on Industrial Engineering and Operations Management
Dubai, UAE, March 10-12, 2020
© IEOM Society International
Figure 7. Comparison of prediction and actual values for low turbidity cluster
The model shows high accuracy in predicting the actual values with percent difference ranging from 0.42% to 14.12%
with an average of 7.40% for 70 samples. Accuracy ranges from 85.88 to 99.58% with an average of 92.60%.
Figure 8. Comparison of prediction and actual values for high turbidity cluster
The model shows high accuracy in predicting the actual values with percent difference ranging from 7.78% to 16.77%
with an average of 11.88% for 8 samples. Accuracy ranges from 83.23 to 92.22% with an average of 88.12%
4. Conclusion
The study confirms the difference in the efficiency of dissolved air flotation system at different turbidity levels. Using
cluster analysis, water quality data from June 2017 to November 2018 was separated into two groups: Low Turbidity
cluster containing influent with turbidity values ranging from 0 – 181 NTU and High Turbidity cluster containing
influent with turbidity values ranging from 182 – 323 NTU.
Using multiple regressions on historical data, 8 significant factors were identified to have an effect on the %turbidity
reduction for low turbidity cluster: a) turbidity, (b) influent flow rate, (c) pH, (d) temperature, (e) dissolved oxygen,
(f) KMnO4 dosing, (g) ACH dosing, and (i) recycle flow rate. For the high turbidity cluster, three (3) parameters
showed significant effect on turbidity reduction: (a) TDS, (b) dissolved Mn, and (c) influent flow rate.
1909
Proceedings of the International Conference on Industrial Engineering and Operations Management
Dubai, UAE, March 10-12, 2020
© IEOM Society International
All of their effects were furthered scrutinized and identified as a factorial experiment was performed on the significant
factors for both turbidity clusters. For the low turbidity cluster, five main factors, six 2-way interaction and 2 3-way
interactions show significant effect in the %turbidity reduction. The regression model generated has an r2 = 95.12%.
For the high turbidity cluster only 1 2-way interactions show significant effect in the %turbidity reduction. The
regression model generated has an r2 = 81.34%.
The models were tested on actual conditions. Low turbidity cluster showed 92.60% accuracy on the predictions and
high turbidity cluster showed 88.12% accuracy on the predictions.
Overall, this paper proved that at a certain level of inlet turbidity, the dissolved air flotation system would not be as
effective. At lower turbidity levels, the system had many options or factors that it could control or adjust to get the
optimum turbidity reduction. At higher turbidity level, the maximum reduction that can be achieved was 69%.
Adjusting other factors would only increase the operational cost.
References
Chung, Y., Choi, Y. C., Choi, Y. H., & Kang, H. S. (2000). A demonstration scaling-up of the dissolved air flotation.
Water Research, 817-824.
D’Sa, E. J., Hu, C., Muller-Karger, F. E., & Carder, K. L. (2002). Estimation of colored dissolved organic matter and
salinity fields in case 2 waters using SeaWiFS: Examples from Florida Bay and Florida Shelf. Journal of Earth
System Science, 111(3), 197–207.
Dehghani, M., Karimi, B., & Rajaei, M. S. (2016). The effect of aeration on advanced coagulation, flotation and
advanced oxidation processes for color removal from wastewater. Journal of Molecular Liquids, 223, 75-80.
Dvorak, B. I. (2014). The relationship of ACH and dissolved Oxygen with regards to turbidity reduction is the
effectiveness of coagulation. NebGuide.
Fotouhi, F., & Kresic, N. (2010). Springwater treatment. Groundwater Hydrology of Springs, 269-304.
Haarhoff, J., & Edzwald, J. K. (2013). Adapting dissolved air flotation for the clarification of seawater. Desalination,
311, 90-94.
Hu, F., Tan, D., & Lavareza, I. (2014, March 12). 8 Facts on China’s Wastewater. Retrieved from China Water Risk
Review: http://chinawaterrisk.org/resources/analysis-reviews/8-facts-on-china-wastewater/
Kan, C., Huang, C., & Pan, J. R. (2002, April 25). Time requirement for rapid-mixing in coagulation. Colloids and
Surfaces A: Physicochemical and Engineering Aspects, 203(1-3), 1-9.
Koren, D. W., Gould, W. D., & Bedard, P. (2000). Biological removal of ammonia and nitrate from simulated mine
and mill effluents. Hydrometallurgy, 127-244.
Kwon, S. B., Ahn, H. W., Ahn, C. J., & Wang, C. K. (2004). A case study of dissolved air flotation for seasonal high
turbidity water in Korea. Water Science Technology, 50(12), 245-253.
Metropolitan Waterworks and Sewerage System. (n.d.). Metro Manila Water Supply System. Retrieved from
http://mwss.gov.ph/learn/metro-manila-water-supply-system/
Palaniandy, P., Adlan, M. N., Aziz, H. A., & Murshed, M. F. (2010, March). Application of dissolved air flotation
(DAF) in semi-aerobic leachate treatment. Chemical Engineering Journal, 157(2-3), 316-322.
Salem, M. G., El-Awady, M., & Amin, E. (2012). Enhanced Removal of Dissolved Iron and Manganese from
Nonconventional Water Resources in Delta District, Egypt. Energy Procedia, 983-993.
Santos-Borja, A. C. (1994). The Control of Saltwater Intrusion into Laguna de Bay: Socioeconomic and Ecological
Significance.
Tamayo-Zafaralla, M., Santos, R., Orozco, R., & Elegado, G. (2010). The Ecological Status of Lake Laguna de Bay,
Philippines.
Teixeira, M. R., & Rosa, M. J. (2006). Comparing dissolved air flotation and conventional sedimentation to remove
cyanobacterial cells of Microcystis aeruginosa. Separation and Purification Technology, 84-94.
World Resource Institute. (2018, August). Aqueduct Water Risk Atlas Current Conditions. Retrieved from
http://www.wri.org/applications/maps/aqueduct-
atlas/#x=121.24&y=13.04&s=ws!20!28!c&t=waterrisk&w=def&g=0&i=BWS-16!WSV-4!SV-2!HFO-4!DRO-
4!STOR-8!GW-8!WRI-4!ECOS-2!MC-4!WCG-8!ECOV-2!&tr=ind-1!prj-1&l=4&b=terrain&m=group
Zhang, X., Li, W., Blatchley, E. R., Wang, X., & Pengfei, R. (2015). UV/chlorine process for ammonia removal and
disinfection by-product reduction: Comparison with chlorination. Water Research, 804-811.
1910
Proceedings of the International Conference on Industrial Engineering and Operations Management
Dubai, UAE, March 10-12, 2020
© IEOM Society International
Biographies
Rianiña D. Borres is an Assistant Professor of School of Industrial Engineering and Engineering Management at
Mapua University in Intramuros, Manila, Philippines. She has earned her B.S degree in Industrial Engineering and
Masters of Engineering Program major in IE from Mapua University, Intramuros, Manila, Philippines. She is a
Professional Industrial Engineer (PIE) with over 15 years of experience. She has taught courses in Probability and
Statistics, Operations Research and Computer Integrated Manufacturing. She has done research projects in operations
research and human factors and ergonomics. She is a member of Philippine Institute of Industrial Engineers (PIIE).
Aaron S. Cornista graduated with a degree of Chemical Engineering (cum laude) at the University of the Philippines
Los Baños. He recently obtained his master's degree in Engineering Management and is taking his doctorate in
Environmental Engineering at the Mapua University. He is currently working as a Process and Applications Manager
in Promark Process International Corporation. His work involves designing water and waste water system to help
various industries in their water supply and sewage discharge issues. He previously worked in Maynilad as a Water
Supply Operations Officer of Putatan Water Treatment Plant Operations and works on ensuring proper water supply
to the community. Prior to that he worked in a food manufacturing industry as a process engineer who deals with
design and commissioning of complex food process flows. Prior to that, he was a project engineer who was responsible
for the construction of new manufacturing plants and rehabilitation of old factories. His research undergraduate and
master’s research focuses on wastewater and water treatment respectively.
1911