OpGuide WebPower Adapter

67
WebPower Adapter 2.0 356943.013 Revision 2 February 2006

Transcript of OpGuide WebPower Adapter

Page 1: OpGuide WebPower Adapter

WebPower Adapter 2.0

356943.013Revision 2

February 2006

Page 2: OpGuide WebPower Adapter

Copyright ©: ELTEK Energy 2006

Corporate Headquarters:ELTEK Energy ASP.O. Box 2340 StrømsøN-3003 DRAMMENNorway

Phone:+47 32203200Fax: +47 32203210

Americas Region Headquarters: ELTEK Energy LLC115 Erick StreetCrystal Lake, Illinois 60014USA

Phone: +1 (800) 447-3484Phone: +1 (815) 459-9100Sales FAX: +1 (815) 459-9118

24-hour domestic service helpline +1 (800) 435-487224-hour international service helpline +1 (815) 479-0682Service FAX +1 (815) 459-0453

Visit our Web site on the Internet at http://www.eltekenergy.com

Page 3: OpGuide WebPower Adapter

Table of ContentsIntroduction............................................................................................................................1Hardware Overview...............................................................................................................3WebPower General Access....................................................................................................8WebPower MCU User Interface............................................................................................10WebPower AEON User Interface..........................................................................................22WebPower Smartpack User Interface....................................................................................36Serial Utility and Telnet Access ............................................................................................49FTP Upload Information........................................................................................................58Firmware Updates..................................................................................................................60

Page 4: OpGuide WebPower Adapter

1

Chapter 1: IntroductionEltek Energy is a world leader in the development of new power supply systems, designed to meet the rapid growthwithin the field of telecommunication, as well as the increasingly stringent reliability requirements.

With the introduction of microelectronics in electronic equipment, energy distribution and telecommunication anddata systems technology require a guaranteed, uninterruptible power supply and to meet this demand, Eltek Energymake in-depth investments in all types of scientific research, technical development, and experimental mathematicalmodeling of thermal characteristics of components and systems.

The ultimate in reliability is secured through innovative new technologies and topologies, which also reduce the sizeof the power blocks and extend the operating range, thereby increasing efficiency and reducing costs. Eltek Energyinvests heavily in research and development - with highly qualified engineers and research scientists working withthe most advanced development platforms available, we are able to offer tailor-made solutions - a key factor forpenetrating new markets.

A modern power supply system must fulfill various international standards and regulations while, at the same time,meeting market requirements. Increased awareness of Electromagnetic Compatibility (EMC), especially in Europe,has resulted in Eltek's investment in an EMC test laboratory. This laboratory not only ensures that products complywith relevant standards, it is also utilized throughout product development. The EMC test laboratory forms part ofEltek's extensive in-house test facility.

Electronic equipment for data and telecommunications require supply voltages generated from the AC mains, as wellas from battery-assisted DC voltage. Intensive development work has produced power supply systems designed tomeet both present and future power requirements, and the development of control and alarm modules make ourpower supply systems a market leader. Programmed functions monitor operating conditions, load and battery. Shouldproblems be detected, the operator will be notified immediately, either via the telephone network, or via Ethernet.Shutdowns can thus be avoided for critical applications.

Eltek's software expertise is constantly expanding the remote communication capabilities of our systems, usingstandard network protocols such as SNMP and HTTP.

Eltek Energy AS accepts no responsibility for any damage or injury to the system, site or personnel caused bydrawings, instructions or procedures not prepared by Eltek Energy.

Page 5: OpGuide WebPower Adapter

2

ScopeEltek's WebPower Adapter provides the user with an affordable, easy to use, platform-independent graphicalinterface solution. Combined with one of Eltek's AEON Gold, Smartpack, or Flatpack MCU system controllers,WebPower allows remote monitoring from anywhere within a corporate LAN, WAN, or VPN, or even across theInternet.

In addition, the WebPower adapter provides an SNMP Agent, allowing Eltek power systems to be interoperable withSNMP enterprise management solutions, which are commonly in use within the Telecommunications industry.

Feature OutlineThe following are some of the features of the WebPower adapter:

� Platform independence - the monitoring PC can be Windows, Macintosh, UNIX, Linux - any modern operatingsystem and hardware platform that supports a standard Web browser capable of running Javascript. This includesmany handheld devices such as PDAs and tablet PCs.

� Freedom from software installation and version control issues at the PC. All data is exchanged using standardHTTP Internet protocol.

� Field upgrades of the WebPower adapter firmware are possible over the network connection. No specialtyhardware is required. Windows versions of the required software tools are provided free upon request toauthorized users. Remotely updating all adapters in a given enterprise is possible from a single location by use ofthese tools and associated firmware binaries provided by Eltek. Feature upgrades and improvements are easilyimplemented by this process.

� Multiple concurrent browser connections are supported. This feature may be utilized for cooperativetroubleshooting efforts, training purposes, or other collaborative, multi-user sessions.

� Access security is provided to restrict unauthorized attempts to alter system settings. Group level access control isprovided, with three access levels defined.

� A truly embedded architecture provides protection of the WebPower adapter operating software. The operatingfirmware image is compressed into WebPower's internal flash memory and decompressed into RAM at boot up.All operations are executed from RAM, so there is no file system to corrupt or damage. This RAM area is notaccessible externally, providing excellent security against malicious attacks. In the event of corrupted RAM,rebooting the device literally loads a fresh copy of the operating code.

� An embedded SNMP Agent provides standard SNMP traps upon occurrences of alarm conditions and allows GETand SET operations in order to retrieve data and perform remote operations on the power plant. Compatibility isensured by the SNMPv1 implementation and inclusion of standard SNMP variables required for device discoveryand polling. The appropriate MIB file is provided on the WebPower Companion CD-ROM shipped with eachWebPower adapter.

Globally available remote access provides many advantages to the systems operation group. The graphical userinterface built into WebPower features an environment familiar to Internet users. This document addresses in detailthe operation of the adapter and the WebPower adapter interface.

Page 6: OpGuide WebPower Adapter

3

Hardware OverviewThe WebPower adapter is either a separate external unit or an internal system component. In addition, WebPower isalso an integrated feature within the Smartconnect unit. This is determined by the system that was purchased, sincecertain systems are equipped with the internally integrated adapter, while others are not. If yours is an internal systemcomponent or is an embedded version, no wiring is necessary so you can skip the Hardware Installation sectionbelow. If you have an external adapter, you will need to perform the steps in the Hardware Installation section. Thereare no differences in the WebPower User Interface between the two versions of the adapter.

The external WebPower adapter consists of a PCB housed in a metallic enclosure that is mounted in a convenientlocation. Normally, this enclosure resides within the power system cabinet, rack, or enclosure, but it can be externallymounted. In addition, the WebPower adapter may be integrated into a system monitor panel along with other PCB-level subassemblies, in which case the connectors as described within this document may be relocated.

DimensionsThe enclosure is approximately 150 x 90 x 25 mm (6 x 3.5 x 1 inches).

Power RequirementsWebPower requires a DC voltage between 20 and 65 VDC at a maximum of 150mA to operate.

Connectors and IndicatorsSerial Ports (External adapters only)Two serial ports are available. COM0 is a female DB-9 connector and is wired as a DTE (data terminal equipment)port. COM1 is a male DB-9 connector and is wired as a DCE (data communication equipment) port.

Ethernet PortOne RJ-45 connector is provided for connection to standard UTP network cabling. Both 10Mb (10Base-T) and100Mb (100Base-T) connections are supported by the auto sensing network interface circuitry.

IndicatorsThree (3) green LED indicators are provided. These are:� 100Mb - indicates when the network connection has been auto detected as 100Mb� Link - indicates that a physical layer Ethernet connection is detected� Power - indicates that the WebPower adapter is receiving DC power and is operational

Power ConnectorA two (2) position removable connector is provided for connection of DC power to the WebPower adapter. Polaritymarking is provided adjacent to the connector and these must be observed to prevent damage to the power supplycircuitry. WebPower is internally fused and reversal of the supply polarity will open the fuse and could possiblydamage the device.

Page 7: OpGuide WebPower Adapter

4

Hardware InstallationNote: When supplied as a system component, the WebPower adapter wiring will be factory-installed. If WebPowerhas been purchased as an upgrade or system add-on, consult this section for installation information.

Connection to System ControllerConnect the correct supplied RS-232 cable to the COM1 port on the WebPower adapter. The following is a list of thecommunication cables that are supplied, depending on your region and your system type:

The cable must then be connected to a system controller port that supports the pComm protocol at 9600 baud forAeon and MCU systems and at 38400 for a Smartpack system. The Flatpack MCU and Smartpack controller bothhave a single available serial port, while the AEON controller has multiple serial ports available. For an Aeoncontroller, you must connect to the DTE Com1 port. For a Smartpack controller, you must connect to the CON3 portand the Smartpack must be equipped with the RS-232 option.

When connecting to the Flatpack MCU controller, the MCU must be configured to turn OFF the Modem Sensefunction. This is accessible through the MCU's Service Menus. See your MCU User Guide for details of this setting.If this setting is not correct, the WebPower adapter cannot communicate with the MCU.

Connection to Power� DC input power is connected to a removable terminal block.� Terminal type is Weidmuller BLZ-5.00/180, 2 positions.� Terminal accepts wire sizes of 22AWG to 12AWG

(0.5mm² to 2.5 mm²).� A small flat blade screwdriver is required to tighten the

connections.� Red wire is POSITIVE (+) and is toward the right in this photo.

Connection to Ethernet� Category 5 (or higher grade) UTP cable is required for

connection.� Connector is standard RJ-45. � 10Mb and 100Mb Ethernet connections are supported.� Standard TIA/EIA 568 wiring is used.

Smartpack Eltek part no. 30801.001

AEON Eltek part no. 30801.001 or Eltek part no. 103821

MCU Eltek part no. 100359 or Eltek part no. 30616

Page 8: OpGuide WebPower Adapter

5

Software OverviewWebPower is essentially a protocol translator, where one communication protocol is "converted" into anotherprotocol. In addition, WebPower provides a physical layer conversion between an RS-232 asynchronous serial linkand a twisted pair Ethernet connection.

The Web server function provides the user interface by translating the system controller messages into a form that iseasily understood by the user. This Graphical User Interface (GUI) will be described in detail within this document.

Communication protocolsWebPower supports the following protocols:� pComm binary master-slave communication protocol, reference TE241241.000-B4. This is Eltek's Local Area

Control Network which is employed to communicate between the system controller and ancillary devices, such asWebPower. In the external WebPower adapters, serial port COM1 is dedicated to pComm communications.

� HTTP (hypertext transfer protocol) over TCP/IP (Transmission Control Protocol / Internet Protocol). Used tocommunicate with standard Web browsers. The 10/100Mb Ethernet port employs HTTP over TCP/IPcommunications.

� VT-100 serial terminal emulation protocol. In the external WebPower adapters, COM0 is dedicated to VT-100communications, which are used for diagnostic purposes and for factory WebPower configuration. Defaultcommunication parameters are 115200 baud, 8 data bits, no parity bits, 1 stop bit, and no flow control. If you havean integrated WebPower adapter in your system, the serial ports are not available.

� FTP (File Transfer Protocol): This is used to both upload and download settings to or from the WebPower via aspecially formatted delimited text file (*.csv).

� SNMP (Simple Network Management Protocol): This provides the power system with monitoring, control, andalarming features via standard GET and SET operations and via SNMP trap messages.

� Telnet: This is used for low level communication configuration via a text-based interface.

CompatibilityThe WebPower adapter firmware is interoperable with AEON, Flatpack MCU, and Smartpack controllers allowingthe WebPower adapter to address any Eltek system application using these controllers.

For additional compatibility information please see the readme.txt file on the WebPower Companion CD-ROM.

Page 9: OpGuide WebPower Adapter

6

Setting up the WebPower adapterIn order to access WebPower via the Ethernet connection, TCP/IP networking must be installed and active on theclient PC. Unless otherwise indicated, the default IP address of the WebPower adapter is 192.168.10.20. The defaultsubnet mask is 255.255.255.0. A fixed IPv4 address is required; consult your network operations or InformationTechnology group before assigning an IP address within your specific address range.

Configuration via Ethernet � Using the supplied PC Utilities

If a Windows PC is available, the IP address of the WebPower adapter may be changed using the IPSetup utility,which is provided on the WebPower adapter Companion CD-ROM. Locate the IPSetup.EXE file on the CD-ROMand launch this application. A list of all currently accessible WebPower adapters will be shown, along with theirunique physical / MAC address. Highlight the unit that you wish to reconfigure, and enter the appropriateinformation in the associated text boxes. When all the settings are entered, click the "SET'" button to change theunit's IP configuration.

Figure 1-1: IPSetup Utility

This procedure may be performed on any WebPower adapter (or any other NetBurner®-based device) on thenetwork. Be careful that the adapter you are configuring is the correct unit.

The IPSetup utility allows changing the IP configuration of a WebPower adapter without knowing the adapter'scurrent IP address. Changes may be made from any Windows client that is physically connected to the samenetwork as the WebPower adapter, regardless of the client's IP address (certain network restrictions may limitaccess by unauthorized devices). It is recommended that access to the IPSetup tool be limited and the WebPowerCompanion CD-ROM be stored in a safe, secured location.

Note that the IPSetup and AutoUpdate utilities use the same connection mechanism and cannot be runconcurrently Refer to the �Firmware Updates� section in this manual for more information.

� Using a Web Browser

If a non-Microsoft operating system must be used, or if the WebPower Companion CD-ROM is unavailable, theIP address of the browsing computer can be set to an address in the same range as the factory-configured IPaddress of the WebPower adapter (see above). The browsing computer's IP address must be within the rangeallowed by the default subnet mask (192.168.10.1 to 192.168.10.19 and 192.168.10.21 to 192.168.10.254). Ifnecessary, temporarily change the IP address of the client PC to conform to this range. Once a connection isestablished, the IP address of the WebPower adapter can be changed to the desired permanent IP address. Formore information, refer to the �Administrative Settings� section in this manual for your specific controller.

Page 10: OpGuide WebPower Adapter

7

Attention: When the WebPower adapter IP address and/or subnet mask is changed to a rangeoutside that of the client machine, WebPower will be inaccessible to any computer within theoriginal address range (before the change). After configuration of the WebPower adapter, the clientcomputer's IP address and/or subnet mask can then be changed back to its normal IP address.

� Using a Telnet ConnectionIf a Web browser is not available during configuration, or if the initial SNMP parameters must also be configured,a Telnet session can be used to access the WebPower adapter's Serial Menu. Refer to the �Using the Serial Utility�section in this manual for more information.

Configuration via a Serial ConnectionIf an Ethernet connection is not available or if it is not possible or desirable to temporarily reconfigure the PC's IPaddress, an alternative procedure for external WebPower adapters is the serial connection option. Refer to the "Usingthe Serial Utility" section in this manual for more information.

For information about connecting to the WebPower interface and accessing the information, refer to theappropriate chapter for the controller that is installed in your system.

Page 11: OpGuide WebPower Adapter

8

Page 12: OpGuide WebPower Adapter

8

Chapter 2: WebPower General AccessWebPower is best displayed on a graphic adapter/monitor capable of 1024x768 pixel resolution or better at 16-bit orhigher color depth. Lower resolutions / color depths are usable, but will result in reduced display quality and willrequire more scrolling to access some Web page contents. Turning off browser toolbars will provide additional verti-cal screen area and is suggested if a screen resolution of 800x600 must be used.

Access Levels and PasswordsThe following details are for the access/permission levels.

Table 2-1: Access Levels

Login to WebPowerIn order to connect to the WebPower adapter GUI, a browser connection to the WebPower adapter TCP/IP address isrequired. It is assumed that the user is familiar with the use of Web browsers and Web page navigation techniques.Make sure you have any pop-up blockers either disabled or that pop-ups are being allowed in this session since theWebPower utility does use some pop-up messages.

To login, start your Web browser and enter the IP address assigned to the WebPower adapter (as follows):http://192.168.10.20, substituting the actual address for the one used in this example.

The WebPower logo screen will open (all images are shown in Internet Explorer):

Figure 2-1: WebPower logo screen

Click ENTER at the bottom of the screen to begin.

User Name Factory Default Password Permissions

status status Read-only system access

control control Can change system operational settings

admin admin Can change system factory configuration settings

Page 13: OpGuide WebPower Adapter

9

A login dialog box similar to the following will then appear:

Figure 2-2: Login Dialog

After entering the username and password, click OK to continue to the WebPower home page. Incorrect loginattempts will result in an error page being displayed.

Web Page / Menu StructureThe WebPower adapter GUI uses "frames pages" (a type of HTML structure) to display related items and menus. Aframes-capable browser is required to use WebPower. All commonly used modern Web browsers support the use offrames.

Throughout the GUI, the top frame contains a menu bar with labeled buttons that link to lower-level pages. Ifapplicable, the menu bar buttons will change to match the available sub-pages within a given area. In some areas, aframe may appear along the left side with additional related information and links to sub-pages.

Sub-menus are accessible (visible) to all users, however certain sub-menus items are password-protected againstchanges. The following graphic is a hierarchal representation of the WebPower adapter menu structure. Note thatcertain menus/pages are only available to specific controllers and may not be visible.

The following chapters will show the individual Web pages within the menu structure and describe in detail the func-tion of each page / menu item below the Home Page level.

Page 14: OpGuide WebPower Adapter

10

Chapter 3: WebPower MCU User Interface

WebPower home page

Figure 3-1: WebPower Home Page

The home page includes the following information:

DC Plant Information� Customer: customer's name� Location: customer or site location� System: system controller type: MCU� Software Version: system controller software version� Date: current date yyyy/mm/dd� Time: current time hh/mm/ss� Access Level: status, control, or admin

DC Plant MeasurementsThis area shows the system status, in amperes and volts, for the AC mains input(s), rectifier current, batterycurrent, voltage, and temperature, and the load current. MCU controllers do not report an AC Mains voltagefigure, instead showing a simplified NORMAL or ALARM message instead.

Event Status This area shows a red light when a major alarm is active and a yellow light when a minor alarm is active. Agreen light will show when all alarms are inactive. Click the Event Status button to open the alarm and statesummary screen. More information about this feature is in the following section.

Make sure you have any pop-up blockers either disabled or that pop-ups are being allowed in this session sinceclicking the Event Status button will launch a pop-up screen.

Page 15: OpGuide WebPower Adapter

11

Alarm Status Page

Figure 3-2: Alarm Status page

Clicking the Event Status button (above the colored indicator on the main screen) will open a new browser windowthat displays a summary of alarms and their current states. Text labels are used to denote alarm states: Normal, MajorAlarm, Disabled, etc.

The Alarm Status page is automatically refreshed at the interval set in the Administrative Settings page. All fields areread-only and are reported by the system controller.

This page may be moved independently of the main page and minimized, but cannot be scrolled or resized.

If there is more than one browser page open (for different WebPower adapters), there will be only one Alarm Statuspage displayed. If you want to view the Alarm Status page for a different WebPower adapter, close the Alarm Statuswindow that you have open, navigate to the correct WebPower browser page, and then click the Event Status buttonon that page. This will open a new instance of the Alarm Status page.

In addition to the standard set of system alarms and events, the state of all enabled Programmable Events is displayed.

Page 16: OpGuide WebPower Adapter

12

Administration Settings

Figure 3-3: Administration Settings pageSystem Functions

The Auto boost checkbox will enable or disable the automatic boost (equalize) charge mode. When checked (enabled), Auto Boost will commence after any discharge event where the battery capacity has been reduced to a user-defined level. Refer to the Boost Configuration Page for details of the Auto Boost feature. If you Enable or Disable this feature, you must click �Apply� in order for the change to be implemented.

WebPower TCP/IP SettingsThe TCP/IP configuration of the WebPower adapter is performed within this page; consult your networkadministrator if you are unsure of how to adjust these settings.

Note: If the WebPower adapter physical MAC address is needed, it can be viewed in the Site Information Page.

The Refresh rate setting determines the automatic page refresh period in seconds. Clearing this box disables theauto refresh feature. Disabling the auto refresh is advised during initial setup to prevent a refresh from occurringbefore new settings can be applied in a given page.

WebPower SNMP SettingsIn this area you can specify the destination IP address(es) and the community string for SNMP traps. SNMP trapsare unsolicited messages sent to the network management system informing the manager of a network event. Ifyou make any changes in this area, click the Change Settings button for them to take effect.

WebPower Email SettingsIn this area, you can specify the e-mail settings that will be used to send pertinent information. You will need toenter your mail username, SMTP Server IP, From address, To address 1, and To address 2. If you make anychanges in this area, click the Change Settings button for them to take effect.

Page 17: OpGuide WebPower Adapter

13

Battery / Charging Settings PagesSelecting the Battery/Charging page will automatically load the Battery Test page.

Battery Test Status Page

Figure 3-4: Battery Test Status page

The Battery Test Status page is used to configure the Battery Test features of the MCU system controller, and to viewthe current status of any ongoing Battery Test. Grayed-out fields are read-only and are as reported by the MCUsystem controller.

The Test Status field displays the current condition of the Battery Test. Clicking the "Start Test" button will manuallyinitiate a Battery Test cycle, which will continue until one of the Termination Criteria parameters is met.

The following related fields are user-configurable:

Termination Criteria� End Voltage: The battery VPC (voltage per cell) at which time the test is to be terminated� Test Duration: The maximum desired battery test duration in minutes. Note that terminating a battery test

before the end voltage is reached may result in invalid battery test results.

Interval Test� Next Start Date: The initial date on which the next periodic automatic battery testing will begin. � Next Start Time: The time of day when the next automatic battery tests will occur. � Interval Period: The length of time, in days, between automatic battery tests.

General Battery Test Configuration� Guard Time: The time in days, after an AC Mains fail condition, during which a Battery Test is not allowed (to

protect the batteries and provide adequate recharge time before a Battery Test).

Clicking the "Apply" button will update the system controller with the new settings as entered on this page

Page 18: OpGuide WebPower Adapter

14

Regulation Mode / Current Limit PageWhen you click the Regulation mode/Current Limit page, the Output Control Configuration screen will be displayed.

Figure 3-5: Output Control Configuration page

The Output Control Configuration page is used to configure the rectifier voltage regulation mode and the batterycharge current limitation. The following fields are user-configurable in MCU systems:

Regulation Mode� Temperature Compensation: Rectifier voltage is determined by the battery temperature and battery parameter

tables as stored in the MCU system controller.� Output Voltage Control: Rectifier voltage is determined by the Battery Voltage level as set in the MCU System

Levels Page. This is the standard setting for systems without temperature compensation.� Default Rectifier Voltage: Rectifier voltage is determined by the front panel adjustment at the individual

rectifiers. This mode is typically used for troubleshooting purposes.

Current Limitation Mode� Maximum Battery Current: When enabled, this feature allows limiting of the battery recharge current to a safe

level. Rectifier output voltage will be reduced to limit the recharge current. When this mode is enabled,rectifier output voltage will be variable depending on battery current, and will revert to the chosen regulationmode when the charge current drops below the maximum set here.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Page 19: OpGuide WebPower Adapter

15

Boost Configuration Page

Figure 3-6: Boost (equalize) charge configuration page

The Boost (equalize) Charge Configuration page is used to configure the boost (equalize) battery charging mode andto view the current status of the Boost Charging Mode. Grayed-out fields are read-only data as reported by the systemcontroller.

Boost Mode Status This field displays the current condition of the boost charge. Clicking the "Start Boost" button will manuallyinitiate a Boost Charge cycle, which will continue for the length of time that is set in the Duration field.

Parameters� Maximum Duration: The length of the Boost Charge cycle, in minutes.

Auto Boost� Boost Factor: The amount of energy returned to the battery during an Auto Boost recharge, relative to the

energy removed during the previous discharge event.� Threshold: The depth of battery discharge which initiates an Auto Boost cycle.� Maximum Duration: Provides a timeout function that overrides the Boost Factor setting. Boost charging will

be terminated when this time, in hours, is reached, regardless of the amount of energy that has been returned tothe battery.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Page 20: OpGuide WebPower Adapter

16

Events / Inputs PagesSelecting the Events / Inputs page will automatically load the Battery Symmetry Input Monitor page.

Figure 3-7: Battery Symmetry Input Monitor page

The Battery Symmetry Input Monitor page contains information about the battery symmetry inputs to the systemcontroller. All fields are read-only. The Symmetry Monitor is used for viewing the battery symmetry channel / blockmeasurements and current status. You can also view information about the Symmetry Voltages. Refer to the manualfor the MCU controller for more detailed information regarding the fields in this area.

Page 21: OpGuide WebPower Adapter

17

General Configuration PagesSelecting the General Configuration page will automatically load the System Levels sub-page.

System Levels

Figure 3-8: System Levels Page

The System Levels page displays the System Voltages and Contactor Setup information.

System Voltages� This area displays the current settings for the Float and Boost (Equalize) charge voltages and the LVD

contactor switching points and disconnect delay times.

Contactor Setup� LVD contactors are enabled and disabled via this menu. The "control" level logon is required in order to make

changes to the System Levels page. You can change the Disconnect Voltage and the Delay (in minutes) for theLVD contactors.

ATTENTION: Make sure that the proper LVDs are enabled for your system. Incorrectly setting thesemay produce undesired results., i.e. a loss of load and/or batteries or a failure to disconnect the load and/or batteries.

Note: LVD3 is only supported by certain system configurations. Refer to the documentation for your power systemfor more information.

Clicking the "Reset" button before you click �Apply� will cancel any pending changes. If you want to remove anychanges but have already clicked �Apply�, you will need to manually re-enter the settings.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Page 22: OpGuide WebPower Adapter

18

Site Information Page

Figure 3-9: DC Plant Information page

The Site Information page contains information specific to the system in which WebPower is installed. Grayed-outfields are read-only information as provided by the system controller. Certain fields are changeable through theWinPower interface. Refer to the WinPower User's Guide for details.

The following are the fields that can be found on this page. The field naming implies the suggested usage of thefields:

� Customer: Customer name� Location: Site name and/or location� Control module s/n: Serial number of the control module (Read only)� Control module SW version: Software version of the control module (Read Only� WebPower MAC: MAC address of the WebPower adapter (Read only)� WebPower SW Version: Software version of the WebPower adapter (Read only)� Message 1: Message or text note to other users� Set DC Plant date: Date to be entered in the system controller clock� Set DC Plant time: Time to be entered in the system controller clock� Serial number: Serial number of the WebPower adapter (Read only)� Rectifiers installed: Number of rectifers detected by the controller (Read only)� Battery Install Date: Battery installation date� Last Service Date: System Maintenance / Service date � Serviced by: Maintenance / Service personnel name� Battery type: Battery model number, ampacity, etc.� Message 2: Additional message or text note to other users� Get PC Time/Date button: Used to synchronize the date and time with the monitoring PC.� Reset button: Used to revert to all of the previous settings if clicked before applying any changes.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Page 23: OpGuide WebPower Adapter

19

Password Change

Figure 3-10: Password change page

The Password change page allows users to change the access password for a given access group. Note that this newpassword is effective at a group level, but not at a user level. All users of a given access level (status, control, admin)must use the same password.

To change a password, select an Access level, enter the current password, enter the new password ,and then re-enterthe new password. When finished, click Submit.

Clicking the "Submit" button will update the system controller with the new settings as entered on this page. If thecurrent password is entered incorrectly, if the new password has not been typed the same in both lower boxes, or ifany information is missing, an error page will be displayed:

Figure 3-11: Password error message

Page 24: OpGuide WebPower Adapter

20

Relay Testing

Figure 3-12: Relay Testing page

The Relay Test page is used to verify the functionality of the MCU alarm relays and connected alarm-monitoringequipment. Clicking on one of the Event Relay buttons will toggle the state of the associated Alarm Relay.

The State fields are read-only and show the status of the relay tests.

ATTENTION: Make sure that you have determined the relay mapping assignments for your system in anon-intrusive manner and are completely familiar with them before attempting to change any settings onthis page. Operation of the LVD control relays will result in battery and/or load disconnection. Verifythat the correct alarm name is listed in an output line before performing a relay test.

Clicking the Refresh button will update the alarm relay State data fields.

Note: Unlike previous versions of WebPower, the relays in WebPower 2.0 will not revert back to their original stateafter a certain amount of time or when you navigate away from this page. The relays must be manually reset to theirprevious states in order to avoid any misreadings in the future.

Page 25: OpGuide WebPower Adapter

21

Alarmlog

Figure 3-13: View Alarm/Event Log page

When you click the Alarmlog button, you will see the Alarm/Event log page, which contains historical informationabout past conditions. Alarm/Event names, conditions, and timestamps are provided. A maximum of 255 events arestored.

Click �Next� at the bottom of the page to go to the next screen. On the following screens, click �Prev� or �Next� tonavigate through the log pages.

Page 26: OpGuide WebPower Adapter

22

Chapter 4: WebPower AEON User Interface

WebPower home page

Figure 4-1: WebPower Home Page

The home page includes the following information:

DC Plant Information� Customer: customer's name� Location: customer or site location� System: system controller type: AEON� Software Version: system controller software version� Date: current date yyyy/mm/dd� Time: current time hh/mm/ss� Access Level: status, control, or admin

DC Plant MeasurementsThis area shows the system status, in amperes and volts, for the AC mains input(s), rectifier current, batterycurrent, voltage, and temperature, and the load current. When connected, WebPower will display the AC inputvoltages as measured by the AEON controller.

Event Status This area shows a red light when a major alarm is active and a yellow light when a minor alarm is active. Agreen light will show when all alarms are inactive. Click the Event Status button to open the alarm and statesummary screen. More information about this feature is in the following section.

Make sure you have any pop-up blockers either disabled or that pop-ups are being allowed in this session sinceclicking the Event Status button will launch a pop-up screen.

Page 27: OpGuide WebPower Adapter

23

Alarm Status Page

Figure 4-2: Alarm Status page

Clicking the Event Status button (above the colored indicator on the main screen) will open a new browser windowthat displays a summary of alarms and their current states. Text labels are used to denote alarm states: Normal, MajorAlarm, Disabled, etc.

The Alarm Status page is automatically refreshed at the interval set in the Administrative Settings page. All fields areread-only and are reported by the system controller.

This page may be moved independently of the main page, but cannot be scrolled or resized.

If there is more than one browser page open (for different WebPower adapters), there will be only one Alarm Statuspage displayed. If you want to view the Alarm Status page for a different WebPower adapter, close the Alarm Statuswindow that you have open, navigate to the correct WebPower browser page, and then click the Event Status buttonon that page. This will open a new instance of the Alarm Status page.

In addition to the standard set of system alarms and events, the state of all enabled Programmable Inputs is displayed(in this example, twelve programmable inputs are defined and enabled).

Page 28: OpGuide WebPower Adapter

24

Administration Settings

Figure 4-3: Administration Settings pageSystem Functions

The following features can be enabled or disabled in this area: Symmetry Event, Interval Battery Test, AutoBoost, Interval Boost, and Efficiency Management. If you Enable or Disable these features, you must click"Apply" in order for the change to be implemented.

LVD Contactor SetupIn this area you can Enable/Disable and/or activate/deactivate the Normally Energized feature for the following items: Battery LVBD, Load 1 LVLD 1, Load 2 LVLD 2, Load 3 LVLD 3, or Load 4 LVLD 4. Refer to the con-troller documentation for your system.

WebPower TCP/IP SettingsThe TCP/IP configuration of the WebPower adapter is performed within this page; consult your networkadministrator if you are unsure of how to adjust these settings.

Note: If the WebPower adapter physical MAC address is needed, it can be viewed in the Site Information Page.

The Webpage Refresh rate setting determines the automatic page refresh period, in seconds. Clearing this boxdisables the auto refresh feature. Disabling the auto refresh is advised during initial setup to prevent a refreshfrom occurring before new settings can be applied in a given page.

WebPower SNMP SettingsIn this area you can specify the destination IP address(es) and the community string for SNMP traps. SNMP trapsare unsolicited messages sent to the network management system informing the manager of a network event.

WebPower Email SettingsIn this area, you can specify the e-mail settings that will be used to send pertinent information. You will need toenter your mail username, SMTP Server IP, From address, To address 1, and To address 2.

Page 29: OpGuide WebPower Adapter

25

Battery / Charging Settings PagesSelecting the Battery / Charging page will automatically load the Battery Test page.Battery Test Status Page

Figure 4-4: Battery Test Status page

The Battery Test Status page is used to configure the Battery Test features of the Aeon Gold system controller, and toview the current status of any ongoing Battery Test. Grayed-out fields are read-only and are as reported by the AeonGold system controller.

The Test Status field displays the current condition of the Battery Test. Clicking the "Start Test" button will manuallyinitiate a Battery Test cycle, which will continue until one of the Termination Criteria parameters is met.

The following related fields are user-configurable:

Termination Criteria� End Voltage: The battery VPC (voltage per cell) at which time the test is to be terminated� Test Duration: The maximum desired battery test duration in minutes. Note that terminating a battery test

before the end voltage is reached may result in invalid battery test results.� Enable: Checkbox to Allow / Disallow the Termination feature

Interval Test� Enable: Checkbox to Allow / Disallow the Interval Test feature� Next Start Date: The initial date on which the next periodic automatic battery testing will begin. � Next Start Time: The time of day when the next automatic battery tests will occur. � Interval Period: The length of time, in days, between automatic battery tests.

General Battery Test Configuration� Guard Time: The time in minutes, after an AC Mains fail condition, during which a Battery Test is not allowed

(to protect the batteries and provide adequate recharge time before a Battery Test).

Clicking the "Apply" button will update the system controller with the new settings as entered on this page

Page 30: OpGuide WebPower Adapter

26

Regulation Mode / Current Limit PageWhen you click the Regulation mode/Current Limit page, the Output Control Configuration screen will be displayed.

Output Control Configuration page

Figure 4-5: Output Control Configuration page

The Output Control Configuration page is used to configure the rectifier voltage regulation mode and the batterycharge current limitation. The following fields are user-configurable in AEON systems:

Regulation Mode� Temperature Compensation: Rectifier voltage is determined by the battery temperature and battery parameter

tables as stored in the AEON system controller.� Output Voltage Control: Rectifier voltage is determined by the Battery Voltage level as set in the AEON

System Levels Page. This is the standard setting for systems without temperature compensation.� Default Rectifier Voltage: Rectifier voltage is determined by the front panel adjustment at the individual

rectifiers. This mode is typically used for troubleshooting purposes.

Current Limitation Mode� Maximum Battery Current: When enabled, this feature allows limiting the battery recharge current to a safe

level. Rectifier output voltage will be reduced to limit the recharge current. When this mode is enabled,rectifier output voltage will be variable depending on battery current, and will revert to the chosen regulationmode when the charge current drops below the maximum set here.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Page 31: OpGuide WebPower Adapter

27

Boost Configuration Page

Figure 4-6: Boost (equalize) Charge Configuration page

The Boost (equalize) Charge Configuration page is used to configure the boost (equalize) battery charging mode andto view the current status of the Boost Charging Mode. Grayed-out fields are read-only data as reported by the systemcontroller.

Boost Mode Status This field displays the current condition of the boost charge. Clicking the "Start Boost" button will manuallyinitiate a Boost Charge cycle, which will continue for the length of time that is set in the Duration field.

Parameters� Maximum Duration: The length of the Boost Charge cycle, in minutes� Guard Time: The time in minutes, after an AC Mains fail condition, during which a Boost is not allowed (to

protect the batteries and provide adequate recharge time before a Boost).

Interval Boost� Enable: Checkbox to Allow / Disallow the Interval Boost charging feature� Next Start Date: The date the initial Interval Boost Charge is to occur� Next Start Time: The time of day that the Interval Boost Charge will occur� Interval Period: The period between Interval Boost charge cycles, in days� Maximum Duration: Boost charging will be terminated when this time is reached, regardless of the amount of

energy that has been returned to the battery.

Auto Boost� Enable: Checkbox to Allow / Disallow the Auto Boost charging feature� Boost Factor: The amount of energy returned to the battery during an Auto Boost recharge, relative to the

energy removed during the previous discharge event� Threshold: The depth of battery discharge which initiates an Auto Boost cycle

Page 32: OpGuide WebPower Adapter

28

� Maximum Duration: Provides a timeout function that overrides the Boost Factor setting. Boost charging willbe terminated when this time, is reached, regardless of the amount of energy that has been returned to thebattery.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Events / Inputs PagesSelecting the Events / Inputs page will automatically load the Battery Monitor sub-page.

Battery Monitor Page

Figure 4-7: Battery Input Monitor page

The Battery Input Monitor page contains information about the Aeon Gold controller's advanced battery healthmonitoring feature. All fields are read-only. The Battery Monitor is useful for the evaluation of existing batterycapacity and status.

Battery Monitor Status� Operational Status: Displays summary information about the battery state: float, equalize, etc.� Operation: Displays information about state and progress of battery operations, i.e. Battery Test, Boost charge,

Discharge state, Float charge, and Guard time (no text during static operation).

Battery Capacity� Total: Total calculated battery capacity, in ampere-hours.� Discharged: The amount of energy that has been transferred from the battery, in ampere-hours� Remaining: The remaining energy available in the battery.

Time until DisconnectionThis displays an approximation of the time remaining before the applicable Low Voltage Disconnect contactor isopened. This uses the either the calculated Battery Capacity and average battery discharge current or theDisconnect timer value, whichever is shorter.

Page 33: OpGuide WebPower Adapter

29

Input Monitor Page

Figure 4-8: Input Monitor page

The Input Monitor page contains readings from the Temperature Inputs, the Digital Inputs, and the Voltage andCurrent Inputs. These inputs are a mixture of analog and digital. All fields are read-only. The Input Monitor is usefulfor system diagnostics and troubleshooting purposes.

Page 34: OpGuide WebPower Adapter

30

Symmetry Monitor Page

Figure 4-9: Battery Symmetry Input Monitor page

The Battery Symmetry Input Monitor page contains information about the battery symmetry inputs to the systemcontroller. All fields are read-only. The Symmetry Monitor is used for viewing the battery symmetry channel / blockmeasurements and current status. Refer to the manual for the AEON Gold controller for more detailed informationregarding the fields in this area.

Page 35: OpGuide WebPower Adapter

31

General Configuration PagesSelecting the General Configuration page will automatically load the System Levels sub-page.

System Levels Page

Figure 4-10: System Levels page

The System Levels page displays the System Voltages and Contactor Setup information.

System VoltagesThis area displays the current settings for the Float, Boost (Equalize), and Battery Standby charge voltages.

Note: LVD3 is only supported by certain system configurations. Refer to the documentation for your power systemfor more information.

Contactor SetupIn this area, the LVD contactors can be enabled and disabled. The "control" level logon is required in order tomake changes to the System Levels page. You can change the Disconnect Voltage and the Delay (in minutes) forthe LVD contactors.

ATTENTION: Make sure that the proper LVDs are enabled for your system. Incorrectly setting thesemay produce undesired results., i.e. a loss of load and/or batteries or a failure to disconnect the loadand/or batteries.

Clicking the "Reset" button before you click �Apply� will cancel any pending changes. If you want to removeany changes but have already clicked �Apply�, you will need to manually re-enter the settings.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Page 36: OpGuide WebPower Adapter

32

Site Information Page

Figure 4-11: DC Plant Information pageThe Site Information page contains information specific to the system in which WebPower is installed. Grayed-outfields are read-only information as provided by the system controller. Certain fields are changeable through theWinPower interface, see the WinPower User's Guide for details. Clicking the "Apply" button will update the system controller with the new settings as entered on this page.The following fields are user-configurable for entry of general information. The field naming implies suggested usageof the fields:

� Customer: Customer name� Location: Site name and/or location� Control module s/n: Serial number of the control module (Read-only)� Control module SW version: Software version of the control module (Read-only)� WebPower MAC: MAC address of the WebPower adapter (Read-only)� WebPower SW Version: Software version of the WebPower adapter (Read-only)� Message 1: Message or text note to other users� Set DC Plant date: Date to be entered in the system controller clock� Set DC Plant time: Time to be entered in the system controller clock� Serial number: Serial number of the system (Read-only)� Rectifiers installed: Number of rectifers detected by the controller (Read-only)� Battery Install Date: Battery installation date� Last Service Date: System Maintenance / Service date � Serviced by: Maintenance / Service personnel name� Battery type: Battery model number, ampacity, etc. (Read-only)� Message 2: Additional message or text note to other users� Get PC Time/Date button: Used to synchronize the date and time with the monitoring PC.� Reset button: Used to revert to all of the previous settings if clicked before applying any changes.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Page 37: OpGuide WebPower Adapter

33

Password Change

Figure 4-12: Password Change page

The Password change page allows users to change the access password for a given access group. Note that this newpassword is effective at a group level, but not at a user level. All users of a given access level (status, control, admin)must use the same password.

To change a password, select an Access level, enter the current password, enter the new password ,and then re-enterthe new password. When finished, click Submit.

Clicking the "Submit" button will update the system controller with the new settings as entered on this page. If thecurrent password is entered incorrectly, if the new password has not been typed the same in both lower boxes, or ifany information is missing, an error page will be displayed:

Figure 4-13: Password error message

Page 38: OpGuide WebPower Adapter

34

Relay Testing

Figure 4-14: Relay Testing page

The Relay Test page is used to verify the functionality of the AEON alarm relays and connected alarm-monitoringequipment. Clicking on one of the Event Relay buttons will toggle the state of the associated Alarm Relay.

The State fields are read-only and show the status of the relay tests.

The Normal State and Alarm Name fields are read-only, but these parameters are changeable in the WinPower controlapplication. WinPower is normally supplied with the system controller and is also available to qualified customersdirectly from Eltek Energy.

ATTENTION: Make sure that you have determined the relay mapping assignments for your system in anon-intrusive manner and are completely familiar with them before attempting to change any settings onthis page. Operation of the LVD control relays will result in battery and/or load disconnection. Verifythat the correct alarm name is listed in an output line before performing a relay test.

Clicking the Refresh button will update the data fields.

Note: Unlike previous versions of WebPower, the relays in WebPower 2.0 will not revert back to their original stateafter a certain amount of time or when you navigate away from this page. The relays must be manually reset to theirprevious states in order to avoid any misreadings in the future.

Page 39: OpGuide WebPower Adapter

35

Alarmlog

Figure 4-15: View Alarm/Event Log page

When you click the Alarmlog button, you will see the Alarm/Event log page, which contains historical informationabout past conditions. Alarm/Event names, conditions, and timestamps are provided. A maximum of 255 events arestored.

Click �Next� at the bottom of the page to go to the next screen. On the following screens, click �Prev� or �Next� tonavigate through the log pages.

Page 40: OpGuide WebPower Adapter

36

Chapter 5: WebPower Smartpack User Interface

WebPower home page

Figure 5-1: WebPower Home Page

The home page includes the following information:

DC Plant Information� Customer: customer's name� Location: customer or site location� System: system controller type: Smartpack� Software Version: system controller software version� Date: current date yyyy/mm/dd� Time: current time hh/mm/ss� Access Level: status, control, or admin

DC Plant MeasurementsThis area shows the system status, in amperes and volts, for the AC mains input(s), rectifier current, batterycurrent, voltage, and temperature, and the load current. When connected to a Smartpack controller-based system,WebPower will display the AC input voltages as measured by the Smartpack controller (as shown in Figure 3).

Event Status This area shows a red light when a major alarm is active and a yellow light when a minor alarm is active. A greenlight will show when all alarms are inactive. Click the Event Status button to open the alarm and state summaryscreen. More information about this feature is in the following section.

Make sure you have any pop-up blockers either disabled or that pop-ups are being allowed in this session sinceclicking the Event Status button will launch a pop-up screen.

Page 41: OpGuide WebPower Adapter

37

Alarm Status Page

Figure 5-2: Alarm Status page

Clicking the Event Status button (above the colored indicator on the main screen) will open a new browser windowthat displays a summary of alarms and their current states. Text labels are used to denote alarm states: Normal, MajorAlarm, Disabled, etc.

The Alarm Status page is automatically refreshed at the interval set in the Administrative Settings page. All fields areread-only and are reported by the system controller.

This page may be moved independently of the main page, but cannot be scrolled or resized.

If there is more than one browser page open (for different WebPower adapters), there will be only one Alarm Statuspage displayed. If you want to view the Alarm Status page for a different WebPower adapter, close the Alarm Statuswindow that you have open, navigate to the correct WebPower browser page, and then click the Event Status buttonon that page. This will open a new instance of the Alarm Status page.

In addition to the standard set of system alarms and events, the state of all enabled Programmable Inputs is displayed.

Page 42: OpGuide WebPower Adapter

38

Administration Settings

Figure 5-3: Administration Settings pageSystem Functions

The following features can be enabled or disabled in this area: Symmetry Event, Interval Battery Test, AutoBoost, and Interval Boost. If you Enable or Disable these features, you must click "Apply" in order for thechange to be implemented.

WebPower TCP/IP SettingsThe TCP/IP configuration of the WebPower adapter is performed within this page; consult your networkadministrator if you are unsure of how to adjust these settings.

Note: If the WebPower adapter physical MAC address is needed, it can be viewed in the Site Information Page.

The Refresh rate setting determines the automatic page refresh period, in seconds. Clearing this box disables theauto refresh feature. Disabling the auto refresh is advised during initial setup to prevent a refresh from occurringbefore new settings can be applied in a given page.

WebPower SNMP SettingsIn this area you can specify the destination IP address(es) and the community string for SNMP traps. SNMP trapsare unsolicited messages sent to the network management system informing the manager of a network event. Ifyou make any changes in this area, click the Change Settings button for them to take effect.

WebPower Email SettingsIn this area, you can specify the e-mail settings that will be used to send pertinent information. You will need toenter your mail username, SMTP Server IP, From address, To address 1, and To address 2. If you make anychanges in this area, click the Change Settings button for them to take effect.

Page 43: OpGuide WebPower Adapter

39

Battery / Charging Settings PagesSelecting the Battery / Charging page will automatically load the Battery Test page.Battery Test Status Page

Figure 5-4: Battery Test Status page

The Battery Test Status page is used to configure the Battery Test features of the Smartpack system controller, and toview the current status of any ongoing Battery Test. Grayed-out fields are read-only and are as reported by theSmartpack system controller.

The Test Status field displays the current condition of the Battery Test. Clicking the "Start Test" button will manuallyinitiate a Battery Test cycle, which will continue until one of the Termination Criteria parameters is met.

Simplified Test� Enable: Checkbox to Allow / Disallow the Simplified Test feature This type of test will check the basic voltage

parameters once and will not automatically repeat.

Battery Test Termination Criteria� Enable: Checkbox to Allow / Disallow the Termination feature� End Voltage: The battery VPC (voltage per cell) at which time the test is to be terminated� Test Duration: The maximum desired battery test duration in minutes. Note that terminating a battery test

before the end voltage is reached may result in invalid battery test results.

Interval Test� Enable: Checkbox to Allow / Disallow the Interval Test feature. This type of test is initiated at a defined date

and time and is repeated after a number of days.� Next Start Date: The initial date on which the next periodic automatic battery testing will begin. � Next Start Time: The time of day when the next automatic battery tests will occur. � Interval: The length of time, in days, between automatic battery tests.

General Battery Test Configuration� Guard Time: The time in hours, after an AC Mains fail condition, during which a Battery Test is not allowed

(to protect the batteries and provide adequate recharge time before a Battery Test).

Clicking the "Apply" button will update the system controller with the new settings as entered on this page

Page 44: OpGuide WebPower Adapter

40

Regulation Mode / Current Limit PageWhen you click the Regulation mode/Current Limit page, the Output Control Configuration screen will be displayed.

Figure 5-5: Output Control Configuration pageThe Output Control Configuration page is used to configure the rectifier voltage regulation mode and the batterycharge current limitation. The following fields are user-configurable in MCU systems:

Regulation Mode� No Temperature Compensation/Temperature Compensation: Rectifier voltage is determined by the battery

temperature and battery parameter tables as stored in the MCU system controller.� Output Voltage Control: Rectifier voltage is determined by the Battery Voltage level as set in the MCU System

Levels Page. This is the standard setting for systems without temperature compensation.� Default Rectifier Voltage: Rectifier voltage is determined by the front panel adjustment at the individual

rectifiers. This mode is typically used for troubleshooting purposes.

Current Limitation Mode� Maximum Battery Current: When enabled, this feature allows limiting of the battery recharge current to a safe

level. Rectifier output voltage will be reduced to limit the recharge current. When this mode is enabled,rectifier output voltage will be variable depending on battery current, and will revert to the chosen regulationmode when the charge current drops below the maximum set here.

System Current Alarm� Current Alarm Trip Point: If the system current exceeds the level specified in this field, an alarm will be

triggered.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Page 45: OpGuide WebPower Adapter

41

Boost Configuration Page

Figure 5-6: Boost (Equalize) Charge Configuration page

The Boost (equalize) Charge Configuration page is used to configure the boost (equalize) battery charging mode andto view the current status of the Boost Charging Mode. Grayed-out fields are read-only data as reported by the systemcontroller.

Boost Mode Status This field displays the current condition of the boost charge. Clicking the "Start Boost" button will manuallyinitiate a Boost Charge cycle,

Manual Boost� Maximum Duration: This determines the length of time in minutes for a manual boost charge cycle.

Interval Boost� Enable: Checkbox to Allow / Disallow the Interval Boost charging feature� Next Start Date: The date the initial Interval Boost Charge is to occur� Next Start Time: The time of day that the Interval Boost Charge will occur� Interval Period: The period between Interval Boost charge cycles, in days� Maximum Duration: Boost charging will be terminated when this time is reached, regardless of the amount of

energy that has been returned to the battery.

Auto Boost� Enable: Checkbox to Allow / Disallow the Automatic Boost charging feature� Charge Factor: The amount of energy returned to the battery during an Auto Boost recharge, relative to the

energy removed during the previous discharge event� Threshold: The depth of battery discharge which initiates an Auto Boost cycle� Maximum Duration: Provides a timeout function that overrides the Boost Factor setting. Boost charging will

be terminated when this time is reached, regardless of the amount of energy that has been returned to thebattery.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Page 46: OpGuide WebPower Adapter

42

Events / Inputs PagesSelecting the Events / Inputs page will automatically load the Battery Input Monitor sub-page.

Battery Input Monitor Page

Figure 5-7: Battery Input Monitor page

The Battery Input Monitor page contains information about the Smartpack controller's advanced battery healthmonitoring feature. All fields are read-only. The Battery Monitor is useful for the evaluation of existing batterycapacity and status.

Battery Monitor Status� Operational Status: Displays summary information about the battery state; normal, warning, or alarm.� Operation: Displays information about state and progress of battery operations, i.e. Battery Test, Boost charge,

Discharge state, Float charge, and Guard time (no text during static operation).

Battery Capacity� Total: Total calculated battery capacity, in ampere-hours.� Discharged: The amount of energy that has been transferred from the battery, in ampere-hours� Remaining: The remaining energy available in the battery.

Time until Disconnection� This displays an approximation of the time remaining before the applicable Low Voltage Disconnect contactor

is opened. This uses the calculated Battery Capacity and the average battery discharge current, or theDisconnect timer value, whichever is shorter.

Page 47: OpGuide WebPower Adapter

43

Battery Symmetry Input Monitor page

Figure 5-8: Battery Symmetry Input Monitor page

The Battery Symmetry Input Monitor page contains information about the battery symmetry inputs to the systemcontroller. All fields are read-only. The Symmetry Monitor is used for viewing the battery symmetry channel / blockmeasurements and current status. You can also view information about the Symmetry Voltages. Refer to the manualfor the Smartpack controller for more detailed information regarding the fields in this area.

Page 48: OpGuide WebPower Adapter

44

General Configuration PagesSelecting the General Configuration page will automatically load the System Levels sub-page.

System Levels

Figure 5-9: System Levels page

The System Levels page displays the System Voltages and Contactor Setup information.

System VoltagesThis area displays the current settings for the Float, Boost (Equalize), and Battery Standby charge voltages.

ATTENTION: Make sure that the proper LVDs are enabled for your system. Incorrectly setting thesemay produce undesired results., i.e. a loss of load and/or batteries or a failure to disconnect the load and/or batteries.

Contactor SetupIn this area, the LVD contactors can be enabled and disabled. The "control" level logon is required in order tomake changes to the System Levels page. You can change the Disconnect Voltage and the Delay (in minutes) forthe LVD contactors.

If you change the values in the Disconnect Voltage areas, the Reconnect Voltage values will be changed by thesame amount. If you do not want these corresponding changes, you can change the Reconnect Voltage valuesindependently.

Clicking the "Reset" button before you click �Apply� will cancel any pending changes. If you want to removeany changes but have already clicked �Apply�, you will need to manually re-enter the settings.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Page 49: OpGuide WebPower Adapter

45

Site Information Page

Figure 5-10: DC Plant Information - date and time page

The Site Information page contains information specific to the system in which WebPower is installed. Grayed-outfields are read-only information as provided by the system controller. Certain fields are changeable through thePowersuite. Clicking the "Apply" button will update the system controller with the new settings as entered on this page.The following fields are user-configurable for entry of general information. The field naming implies suggested usageof the fields:

� Customer: Customer name� Location: Site name and/or location� Control module s/n: Serial number of the control module (Read-only)� Control module SW version: Software version of the control module (Read-only)� WebPower MAC: MAC address of the WebPower adapter (Read-only)� WebPower SW Version: Software version of the WebPower adapter (Read-only)� Message 1: Message or text note to other users� Set DC Plant date: Date to be entered in the system controller clock� Set DC Plant time: Time to be entered in the system controller clock� Serial number: Serial number of the WebPower adapter (Read-only)� Rectifiers installed: Number of rectifers detected by the controller (Read-only)� Battery Install Date: Battery installation date� Last Service Date: System Maintenance / Service date � Serviced by: Maintenance / Service personnel name� Battery type: Battery model number, ampacity, etc. � Message 2: Additional message or text note to other users� Get PC Time/Date button: Used to synchronize the date and time with the monitoring PC.� Reset button: Used to revert to all of the previous settings if clicked before applying any changes.

Clicking the "Apply" button will update the system controller with the new settings as entered on this page.

Page 50: OpGuide WebPower Adapter

46

Password Change

Figure 5-11: Password Change page

The Password change page allows users to change the access password for a given access group. Note that this newpassword is effective at a group level, but not at a user level. All users of a given access level (status, control, admin)must use the same password.

To change a password, select an Access level, enter the current password, enter the new password ,and then re-enterthe new password. When finished, click Submit.

Clicking the "Submit" button will update the system controller with the new settings as entered on this page. If thecurrent password is entered incorrectly, if the new password has not been typed the same in both lower boxes, or ifany information is missing, an error page will be displayed:

Figure 5-12: Password error message

Page 51: OpGuide WebPower Adapter

47

Relay Testing

Figure 5-13: Relay Testing page

The Relay Test page is used to verify the functionality of the Smartpack alarm relays and connected alarm-monitoringequipment. Clicking on one of the Output buttons will toggle the state of the associated Alarm Relay.

The State fields are read-only.

The Normal State and Alarm Name fields are read-only, but these parameters are changeable in the WinPower controlapplication. WinPower is normally supplied with the system controller and is also available to qualified customersdirectly from Eltek Energy.

ATTENTION: Make sure that you have determined the relay mapping assignments for your system in anon-intrusive manner and are completely familiar with them before attempting to change any settings onthis page. Operation of the LVD control relays will result in battery and/or load disconnection. Verifythat the correct alarm name is listed in an output line before performing a relay test.

Clicking the Refresh button will update the data fields.

Note: Unlike previous versions of WebPower, the relays in WebPower 2.0 will not revert back to their original stateafter a certain amount of time or when you navigate away from this page. The relays must be manually reset to theirprevious states in order to avoid any misreadings in the future.

Page 52: OpGuide WebPower Adapter

48

Alarmlog

Figure 5-14: View Alarm/Event Log page

When you click the Alarmlog button, you will see the Alarm/Event log page, which contains historical informationabout past conditions. Alarm/Event names, conditions, and timestamps are provided. A maximum of 255 events arestored.

Click �Next� at the bottom of the page to go to the next screen. On the following screens, click �Prev� or �Next� tonavigate through the log pages.

Page 53: OpGuide WebPower Adapter

49

Chapter 6: Serial Utility and Telnet AccessThe Serial Utility and Telnet Interface provide alternative methods for setting various WebPower configurationoptions, such as the parameters of the embedded SNMP Agent.

The Serial Utility instructions only apply to customers with an external WebPower Adapter; integrated WebPoweradapters do not expose this serial port. If your system has an integrated WebPower adapter, you will need to use anEthernet connection and the Telnet Interface of the WebPower adapter. Note that a Telnet connection can be used foreither type of WebPower adapter, but some options require a serial connection.

Refer to the individual controller chapters in this guide for configuration information. It is assumed that the user isfamiliar with the operation of a Telnet client. Use the following section as a guide when using Telnet to configure theWebPower adapter and/or embedded SNMP Agent.

ATTENTION: CONCURRENT TELNET AND SERIAL CONNECTIONS OR MULTIPLECONCURRENT TELNET SESSIONS, TO THE WEBPOWER ADAPTER ARE TO BE AVOIDED.ATTEMPTING TO ALTER SETTINGS UNDER SUCH CONDITIONS MAY CAUSEUNPREDICTABLE RESULTS. CLOSE ALL BROWSER WINDOWS BEFORE CREATING ATELNET OR SERIAL CONNECTION.

Serial Utility Requirements� Any PC hardware and operating system capable of communicating on an RS-232 serial port at 115200-baud rate,

with a standard DTE serial port connector. � A terminal emulation program capable of VT-100 terminal emulation. Examples are HyperTerminal, TeraTerm,

and others.� A standard DTE to DCE serial cable. This is a "straight-through" wired cable. The DCE end of the cable must be

DB-9; the DTE end of the cable is determined by the PC hardware.

Getting Connected - Serial Utility1. With DC power removed from the WebPower Adapter, attach the serial cable between the PC / terminal and the

WebPower adapter's COM0 port. 2. Launch a terminal emulator, such as HyperTerminal, and configure the necessary port settings per above.3. Apply DC power to the WebPower adapter. A message should appear on the terminal almost immediately (do

not press "A" when prompted). A subset of the current TCP/IP parameters will be displayed, followed by a loginprompt. Type in the "admin" username and the password, pressing Enter after each entry. By default, admin willbe both the correct Username and Password.

Telnet Interface Requirements� Any PC with a Network Interface Card or built-in Ethernet adapter� TCP/IP networking configured with a static IP address on the same subnet (standalone WebPower adapter without

router). For router-equipped systems (i.e. Smartconnect), use DHCP to automatically acquire an IP address. � A standard RJ-45 Ethernet cable (Smartconnect with router) or 568A to 568B crossover cable (WebPower

standalone, without router).� Telnet client application

Page 54: OpGuide WebPower Adapter

50

Getting Connected - Telnet Access1. Attach one end of the appropriate Ethernet cable into the Ethernet port on your computer and the other end to the

craft port on the Smartconnect unit or the Ethernet port of the WebPower adapter.2. Assuming you are using a Windows operating system, open a Command Prompt window (example: in the

Accessories area of the Windows Program Menu). In the Command Prompt window, type telnet 192.168.10.20and then press Enter. Make sure you include the space between telnet and the IP address. Note that192.168.10.20 is the default IP address of the WebPower or Smartconnect unit; if you have changed this IPaddress to a custom address, that new address must be entered instead.

3. You will then be prompted to log in. Type in the "admin" username and the password, pressing Enter after eachentry. By default, admin will be both the correct Username and Password.

Menu OptionsAfter successfully logging in, the main menu should be displayed. The six menu selection options are describedbelow.

Setup Network Addresses If you are using the Serial Utility, you have the option in this area to change any or all of the following networksettings for the WebPower adapter: the IP Address, the Netmask, the Default Gateway, and the DNS Server. Theseparameters should be determined in cooperation with the network administration / Information Technology staff.Note that router-equipped WebPower solutions (Smartconnect) may have particular factory settings necessary foroperation; do not alter these settings without fully understanding the implications. If you are using the TelnetInterface, you will not be able to change certain settings.

Serial Utility Telnet Interface

Page 55: OpGuide WebPower Adapter

51

pComm Driver InfoSelecting this option will display the name, description, part number, version number, and release information for thepComm Driver. This information may be required by factory personnel during service correspondence.

WebPower InfoSelecting this option will display the version information for WebPower. This information may be required byfactory personnel during service correspondence.

SNMP: Trap Host ConfigurationIf you select this option, you will be presented with three suboptions: Set IP Addresses & Community, Set TrapRepeat Rate, and Set Off Trap. SNMP traps are unsolicited messages sent to the network management systeminforming the manager of an event that has occurred, as monitored by the embedded Agent.

Page 56: OpGuide WebPower Adapter

52

Set Trap IP Addresses & Community StringIf you select this option, you will need to specify the number of the table entry that you want to modify.

You will then need to enter the new trap client IP address and community string for the chosen table entry. TheCommunity String can be a combination of 19 characters, numbers, or spaces. Valid characters are A-Z, a-z, 0-9, andthe special characters ~@#%^&_-+=:,. Do not use the asterisk or any other special character not shown. Note thatspaces are valid characters, but leading spaces are ignored.

Page 57: OpGuide WebPower Adapter

53

Set Trap repeat rate configIf you select this option, you will need to set the repeat rate between 0 and 10 minutes. Choosing 0 will turn thisfeature off. The number specified will determine how often Trap messages are resent to the NMS, while a givenevent/alarm remains in the "active" (alarm) condition. Changing this setting requires the WebPower to be rebooted.

Set Off Trap configWithin this option, you can enable the Send Off Trap feature. This feature will send a trap message whenever anevent or alarm condition has cleared. Changing this setting requires the WebPower to be rebooted.

SNMP: NMS ConfigurationThere are two options within this section: Set Read Community string and Set Write Community string. All OIDswithin the MIB construct support the GET ("read") operation. Certain OIDs also support the SET ("write") operation.

Set Read Community stringThis is the Community String name that is used to determine NMS read-only level access to the SNMP Agent, forOIDs that support the GET operation.

Page 58: OpGuide WebPower Adapter

54

Set Write Community stringThis is basically the Community String name that is used to determine NMS read-write level access to the SNMPAgent, for OIDs that also support the SET operation.

Note: See the "SNMP: Trap Host Configuration" section for Community String limitations.

Set pComm BaudrateIf you have an integrated Webpower adapter in your system, you should not need to change this setting. If you havean external WebPower adapter, you should select the option that matches the type of system that you have. Selecteither 1 for Smartpack/eNexus (38400bps) or 2 for AEON or MCU (9600bps).

Page 59: OpGuide WebPower Adapter

55

SNMP MIB InformationDetails of SNMP MIBs. NMS configuration, and of SNMP in general, are beyond the scope of this document. Thissection is provided for the convenience of personnel knowledgeable in the application of SNMP devices.

The appropriate SNMP MIB (ELTEK-DCSYSTEM-MIB) is provided on the WebPower Companion CD-ROM andis required for configuration of the SNMP Network Management Station (NMS).

Eltek's unique Enterprise ID is 12148.

Standard OIDs required for Agent discovery are provided under the iso.org.dod.internet.mgmt.mib.system(1.3.6.1.2.1.1) namespace. Examples are as follows:

sysDescr.0="Eltek Energy SNMP Agent"

sysObjectID.0=enterprise.12148.4.2

sysUpTime.0=05:37:47

[email protected]

sysName.0="Eltek WebPower Demo"

sysLocation.0="Crystal Lake Illinois U.S.A"

sysContact, sysName, and sysLocation are Read-Write variables and may be GET and SET via the NMS. It isrecommended that the sysDescr or sysObjectID be used for discovery and polling purposes.

The header of the MIB file provides userful information such as MIB import dependencies, namespaces, etc. asfollows:-- Description:-- Eltek DC power system MIB-- Numerical: .1.3.6.1.4.1.12148.4-- ASN1: .iso.org.dod.internet.private.enterprises.eltek.dcSystem

IMPORTS TRAP-TYPE FROM RFC-1215 DisplayString FROM RFC1213-MIBOBJECT-TYPE FROM RFC-1212 enterprises FROM RFC1155-SMI;

eltekOBJECT IDENTIFIER ::= { enterprises 12148 }dcSystemOBJECT IDENTIFIER ::= { eltek 4 }dcTrapGroupOBJECT IDENTIFIER ::= { dcSystem 2 }

� (MIB file continues)�

Page 60: OpGuide WebPower Adapter

56

Known IssuesThe following list of items represent known issues that exist in version xxx of WebPower 2.0 and are beingaddressed. Future releases of firmware updates will address and resolve these issues.

SNMP Agent

1. Recursive GET (MIB "walk") operations are unsupported by the current SNMP Agent implementation; use theGET NEXT method instead.

2. batteryHighMajorAlarmVoltageConfig.AEON Gold also automatically sets a 0,25Volt hysteresis.

3. batteryHighMinorAlarmVoltageConfig.AEON Gold does not contain this minor alarm, so this will always appear as 0Volts

4. batteryLowMajorAlarmVoltageConfig.AEON Gold also automatically sets a 0,25Volt hysteresis.

5. batteryLowMinorAlarmVoltageConfig.AEON Gold does not contain this minor alarm, so this will always appear as 0Volts

6. batteryMidpointDeltaLimitVoltageNot writable in AEON, appears as read only in AEON even if the mib states 'read/write'

7. batteryMidpointControlTable Not writable in AEON, appears as read only in AEON even if the mib states 'read/write'

8. loadLVD1Status, loadLVD2Status, loadLVD3StatusThese are the same status. AEON Gold have one common LVD status visible from the outside. When any of theLVDs changes state, all these flags changes at once.

9. rectifierUtilizationFor future use. Not yet implemented in the AEON, MCU, or Smartpack versions.

10. rectifiersStatusTablesrectifiers Status Tables is not implemented for AEON systems.

11. Alarms that cover two levels may skip the 'minor' step when an abrupt change in the source status occur. Whenthe source status of a two-level alarm goes directly from 'normal' to 'major', the traps perform the same change.

12. Node 3 (alarmMinorHighBattVoltAlarm), Node 4 (alarmMinorLowBattVoltAlarm), and Node 6(alarmMinorBatteryHighTempAlarm) are not implemented in AEON and will always remain off.

13. Node 18 (alarmBatteryLifeEnded) is not implemented in either AEON or MCU and will always remain off.14. The Read and Write Community Strings do not work properly. When the SNMP device is set for "Read

Community: Public" and "Write Community: Private", NMS must be set for "Read Community: Public" and"Write Community: Public" in order to read and write properly to any OID.

15. Midpoint Indexes and ID are read-only in SNMP. There is nowhere to enable these in WebPower.

WebPower GUI1. In an MCU system, there is no timer that resets the relay to its original state after testing. The individual relays

must be set manually to their original positions before leaving this page, otherwise, they will remain in their teststate.

2. Within the WebPower interface of an MCU system, the following voltage alarm set-points cannot be set:Battery Voltage Major-HighBattery Voltage Minor-HighBattery Voltage Major-LowBattery Voltage Minor-Low

3. The Disconnect/Reconnect LVD voltages can be changed through SNMP, but there is no way to control theirstate directly through SNMP (like a relay test function or Remote Battery Disconnect).

4. When values are changed through the controller front panel, the Webpower and SNMP values remainunchanged for up to 2 - 3 minutes while the controller communicates with the various components of the system.The updated values will then be displayed. Some examples of screens where this is the case are the MaximumCurrent, HighVolt1, HighVolt2, LowVolt1, and LowVolt2 settings.

5. For the Boost features, there is no SNMP OID for Max. Boost interval.

Page 61: OpGuide WebPower Adapter

57

Abbreviations

AC Alternating CurrentAWG American Wire GageCO Central OfficeDC Direct CurrentDHCP Dynamic Host Configuration ProtocolEIA Electronic Industries AllianceEMT Electrical Metallic TubingEPO Emergency Power OffFP2 Flatpack2; Eltek digital rectifierGUI Graphical User InterfaceHTTP HyperText Transfer ProtocolHVS High Voltage ShutdownIT Information TechnologyLAN Local Area NetworkLCD Liquid Crystal DisplayLED Light Emitting DiodeLMP Lithium Metal PolymerLVBD Low Voltage Battery DisconnectLVLD Low Voltage Load DisconnectLVD Low Voltage DisconnectMIB Management Information BaseNMS Network Management StationNEC National Electrical CodePC Portable ComputerRU Rack UnitSNMP Simple Network Messaging ProtocolTB Terminal BlockVAC Volts ACVDC Volts DCVPC Volts Per CellVRLA Valve Regulated Lead AcidWAN Wide Area Network

Page 62: OpGuide WebPower Adapter

58

Chapter 7: FTP Upload InformationThe following information pertains to the option of uploading information for your system via an FTP client. Thisoption is only available to Smartpack users. A common settings file is available for uploading from Eltek. If you arelogged in to PowerSuite, click �Tools�, �Configurator�, and then �Read from Smartpack� to view additionaldatapoint locations. To use the FTP upload option, perform the following steps:

1. Launch Internet Explorer, type FTP://192.168.10.20 in the address line, and then press ENTER. This assumes you are utilizing a connection via the local Craft Port. If you are connecting from the WAN side of the router, use the WAN side IP address instead of 192.168.10.20.

2. When prompted, log in with the �admin� user account and password (this is the same as WebPower�s �admin� user account).

3. After logging in, the following screen will be displayed. Notice that the SETUP.CSV file does not appear in the remote directory.

4. Open a file browsing session and navigate to the location of the SETUP.CSV file that is to be uploaded. Select the file, right-click, and then click Copy.

Page 63: OpGuide WebPower Adapter

59

5. Next, right-click in the browser session that is connected to the WebPower FTP server and click Paste.

6. During the file transfer, a dialog box showing the progress of the transfer will be displayed.

7. Once the transfer is complete, the remote directory will show that the SETUP.CSV file has been transferred. Refreshing this window will show that the file does not physically persist on the FTP server.

Page 64: OpGuide WebPower Adapter

60

Chapter 8: Firmware UpdatesUpdating the WebPower adapter operating code ("firmware") is easily achieved. WebPower's hardware platformprovides flash program storage for simple code updates - over a network connection from any Windows PC that canaccess WebPower. Using the PC utilities provided on the WebPower Companion CD-ROM, this loading process canbe conducted across an entire network from a single location. This remote update capability is a major advantage tothe WebPower hardware platform.

Recognizing the platform-independence of WebPower, a serial update procedure is included here for users of non-Windows operating systems. This serial update process cannot be conducted remotely.

Firmware binary files are available from Eltek Energy whenever feature improvements are released. In most cases,Eltek sales agents are able to provide these updates free of charge to existing users.

Updates using the PC utilitiesAfter obtaining the firmware binary from Eltek, save the file to your PC. Browse the WebPower Companion CD-ROM and locate the AutoUpdate.exe file. This application provides the means to remotely load a new operatingimage into the WebPower adapter. Launch the application; the following screen should be displayed:

Click the "Reboot when complete" checkbox, as shown above. Use the "Browse" button to select the firmware filepreviously saved to your PC. Note that the file must follow the syntax "xxxxx_app.s19"; where "xxxxx" can be anycharacter string. The utility will not recognize files that do not conform to this naming convention.

The IP address field will be populated with the first WebPower adapter discovered by the application. By using theFind button, a list of all WebPower adapters will be displayed, as follows:

Highlight the adapter to be updated and click the OK button. The screen will close and revert to the main screen.Click the "Update" button and wait until the process is completed, as indicated by a progress bar and message box.The WebPower adapter has now been updated, rebooted, and is running the new application code.

Note: The IPSetup and AutoUpdate utilities use the same connection mechanism and cannot be run concurrently.

Page 65: OpGuide WebPower Adapter

61

Updates via a serial connectionA serial terminal emulation application (client) is required on your PC. The WebPower adapter has an embedded bootloader that provides a flash loading capability over a serial connection. The following process employs the serialloader to allow updates to adapters when an Ethernet connection and/or Windows PC is not available. It is assumedthat the user is somewhat familiar with the operation of a terminal emulator application (example: Hyperterm forWindows platform).

Requirements� Any PC hardware and operating system capable of communicating on an RS-232 serial port at 115200-baud rate,

with a standard DTE serial port connector. � A terminal emulation program capable of VT-100 terminal emulation and binary file transfer.� A standard DTE to DCE serial cable. This is a "straight-through" wired cable. The DCE end of the cable must be

DB-9, while the DTE end of the cable is determined by the PC hardware.

Procedure1. With DC power removed, attach the serial cable between the PC and the WebPower adapter's COM0 port. 2. Launch the terminal emulator, as applicable, and configure the port settings as needed.3. Apply DC power to the WebPower adapter.4. A message should appear on the terminal almost immediately stating the following: "Waiting 2 sec to start 'A' to

abort". Before the 2 seconds expires, press "A" (capital A) and the Boot Monitor Prompt "NB>" should appear Ifthe time elapses, WebPower will start and it will be necessary to cycle power to the adapter and begin again.

5. At the NB> prompt, type FLA and press ENTER. FLA stands for Flash Application.6. Send the firmware (.S19) file by selecting the Transfer->Send File option from the terminal application (if a

"binary" mode is provided, use binary mode).7. As the download progresses, a "*" character will appear in the terminal window and the progress bar in the lower

left hand side of the window will move towards the right. 8. Upon completion of the transfer, the WebPower adapter is updated. It will then reboot and will be running the

new application code.

If errors are reported during the serial transfer, it may be necessary to add "line pacing" in the terminal settings.Typically, this is not required, but in some cases an additional 1 millisecond per line pacing will prevent errors wherelong serial cables are involved.

Page 66: OpGuide WebPower Adapter
Page 67: OpGuide WebPower Adapter

Copyright ©: ELTEK Energy 2006