Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5...

39
Operation Manual Neutralisation Systems GENO ® -Neutra NO-5 GENO ® -Neutra NO-12 GENO ® -Neutra NO-24 Edition: September 2011 Order no. 015 410 850-inter

Transcript of Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5...

Page 1: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Operation ManualNeutralisation Systems

GENO®-Neutra NO-5 GENO®-Neutra NO-12GENO®-Neutra NO-24

Edition: September 2011 Order no. 015 410 850-inter

Page 2: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

2

Table of contents

A General .......................................................................... 4 1 Preface

2 Warranty 3 General safety information 4 Shipping and storage 5 Disposal of used parts and materials

B Basic information .......................................................... 8 1 Laws, regulations, standards

2 Gas condensing technology 3 Neutralisation 4 Obligatory neutralisation as per ATV-DVWK-A 251

C Product description ....................................................... 10 1 Type designation plate

2 Designated application 3 Design 4 Function 5 Scope of supply 6 Technical specifications

D Installation .................................................................... 20 1 General installation instructions

2 Sanitary installation - Installation instructions 3 Start-up

E Troubleshooting ............................................................ 25 F Maintenance and care .................................................. 27 1 Basic information

2 Inspection 3 Maintenance

4 Spare parts list Appendix: Operation log

Page 3: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

3

EC Declaration of Conformity This is to certify that the system designated below meets the safety and health requirements of the applicable European guidelines in terms of its design, construction and execution.

If the system is modified in a way not approved by us, this certificate is void.

Manufacturer: Grünbeck Wasseraufbereitung GmbH Industriestraße 1 89420 Hoechstaedt/Germany

Responsible for documentation: Markus Pöpperl

System designation: Neutralisation system

System type: GENO®-Neutra NO-5, NO-12, NO-24

System number: 410 230, 410 240, 410 250

Applicable EC guidelines: EC Guideline EMC (2004/108/EC) EC Low Voltage Directive (2006/95/EC) RoHS (2002/95/EC)

Applied harmonised standards, in particular:

DIN EN 61000-6-2, DIN EN 61000-6-3 DIN EN 60335-1, 60335-2-102, DIN EN 62233 1st Ordinance to the Device and Product Safety Act (Ordinance on the Marketing of Electrical Operating Materials to be used within specific voltage limits – 1. GPSGV).

Applied national standard and tech-nical specifications, in particular:

ATV- DVWK-A 251 (08/03); DVGW-VP 114; E DIN 4716-2 (04/03); E DIN 4716-1 (11/98)

Date / Manufacturer signature: 07/03/2011 i. V. Markus Pöpperl Dipl.-Ing. (FH)

Function of signatory: Head of Design Department for Serial Products

Page 4: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

4

A General

1 | Preface

Thank you for opting for a Grünbeck product. Backed by decades of experience in the area of water treatment, we provide solutions for all kind of processes.

All Grünbeck systems and devices are made of high-quality materials. This ensures reliable operation over many years, provided you treat your water treatment systems with the required care. This operation manual assists you with important information. Therefore, please read the complete manual before installing, operating or maintaining your sys-tem.

Customer satisfaction is our prime objective and providing customers with qualified advice is crucial. If you have any questions concerning this device, possible extensions or general water and waste water treatment, our field staff, as well as the experts at our headquarters in Hoechstaedt, are available to help you.

Advice and assistance For advice and assistance please contact your local representative (refer

to www.gruenbeck.com). or get in touch with our service centre which can be reached during office hours: Phone: +49-9074/41-333 Fax: +49-9074/41-120 Email: [email protected] We can connect you with the appropriate expert more quickly if you provide the required system data. In order to have the required data handy at all times, please copy it from the type designation plate to the overview in chapter C-1.

2 | Warranty

All devices and systems supplied by Grünbeck Wasseraufbereitung GmbH are manufactured according to the most recent technical stand-ards and subjected to a comprehensive quality assurance system. All warranty claims are subject to our General Terms and Conditions.

Page 5: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

5

3 General safety information 3.1 Symbols and

notes Important information in this operation manual is characterised by symbols. Please pay particular attention to this information to ensure the hazard-free, safe and efficient handling of the system.

Danger! Failure to adhere to this information will cause serious or life-threatening injuries, extreme damage to property or inadmissible con-tamination of the drinking water.

Warning! Failure to adhere to this information may cause injuries, damage to property or contamination of the drinking water.

Attention! Failure to adhere to this information may result in damage to the system or other objects.

Note: This symbol characterises information and tips to make your work easier.

Tasks with this symbol may only be performed by qualified electrical ex-perts according to the VDE guidelines or according to the guidelines of a similar local institution.

Tasks with this symbol may only be performed by approved installation companies with appropriately trained experts or by Grünbeck’s tech-nical service/authorised service company.

3.2 Operating

personnel Only persons who have read and understood this operation manual are permitted to work with the system. The safety guidelines are to be strictly adhered to.

3.3 Designated

application The system may only be used for the purpose outlined in the product description (chapter C). The present operation manual, the applicable local guidelines as well as the guidelines on accident prevention and occupational safety must be adhered to.

In addition, appropriate application also implies that the system may only be operated when it is in proper working order. Any malfunctions must be repaired at once.

Page 6: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

6

3.4 Indication of specific dangers

Danger! Due to electrical energy! Do not touch electrical parts with wet hands! Pull out power plugs and disconnect the power supply to external system parts (e.g. voltage-free outputs) before working on electrical system parts! Have qualified experts replace damaged cables immediately.

Warning! Health risk due to acidic condensed water and alkaline neu-tralisation granulate! Avoid direct contact by means of corresponding protective measures such as protective gloves and goggles. First aid provisions in case of contact with the eyes: In case of contact with the eyes, rinse thoroughly with water and seek medical advice if irritation persists. Hygienic provisions: Do not eat, drink or smoke while working! The current safety data sheet on neutralisation granulate must be ob-served. You may order said safety data sheet from Grünbeck Was-seraufbereitung GmbH. Please indicate the corresponding product des-ignation and order number (refer to consumables – chapter C-5).

Attention! Condensed water or neutralisation granulate may damage surfaces when covering them.

4 | Shipping and storage

Attention! The system may be damaged by high temperatures. In order to avoid damage of this kind: Do not install or store the system next to objects which radiate a lot of heat.

The system may only be transported and stored in its original packing. Ensure that it is handled with care and placed down with the right side up (as indicated on the packing).

The neutralisations granulate GENO®-Neutralit Hz is not considered to be a hazardous material in the sense of the Ordinance on Hazardous Sub-stances. Please observe the current safety data sheet.

The activated carbon is not considered to be a hazardous material in the context of the Ordinance on Hazardous Substances. Please observe the current safety data sheet.

Page 7: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

7

5 | Disposal of used parts and materials Used parts and materials are to be disposed of or made available for

recycling purposes according to the applicable local guidelines.

If a material is subject to specific regulations, adhere to the instructions indicated on the packing and in the safety data sheets.

If in doubt, contact your local waste disposal authority or the manufac-turer for more information.

The used activated carbon filling of the condensate inlet filter should be disposed of under waste code number 190904 through a local waste management company.

Neutralisation granulate (waste code number 01 01 02) as delivered may be disposed of with the domestic waste after prior consultation with the responsible waste management company and the authorities and taking into consideration the applicable regulations. When cleaning the system, hydroxide sludge may be generated which has to be collected separately and disposed of in a suitable, separate container at the local point of ac-ceptance. In the declaration, it may be classified as "metal-containing hydroxide sludge” (waste code number 100121). The respective latest version of the TA- Abfall (Technical Regulation on Waste) must be ob-served.

Page 8: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

8

B Basic information

1 | Laws, regulations, standards This operation manual takes into consideration the current regulations

and stipulates information that you will need for the safe operation of your water treatment system.

Apart from the public rules and regulations, the following supporting regulations apply for the treatment of condensed water originating from condensing boilers and its discharge into the public sewage sys-tem.

Worksheet ATV-DVWK-A 251 „Condensate from condensing boil-ers“ (ATV-DVWK Body of Rules – Registered German Association for Water Management, Waste Water and Waste).

E DIN 4716-1 "Neutralisation systems – Part 1: Oil-firing systems and their flue gas systems."

E DIN 4716-2 "Neutralisation systems – Part 2: "Gas firing systems and their flue gas systems."

DVGW-VP 114 "Neutralisation systems for gas firing systems; re-quirements and testing."

2 | Gas condensing technology In case of gas condensing boilers, the residual heat still contained in the

flue gas is made use of by means of heat exchangers in order to achieve an optimum efficiency. Due to the low temperature of the ex-haust, the water contained condenses. In order to comply with the ap-plicable regulations, however, this kind of condensed water must in general be treated prior to being discharged into the public sewage system.

3 | Neutralisation According to the worksheet ATV-DVWK-A 251, the term "neutralisa-

tion" in context with the treatment of condensed water originating from condensing boilers is defined as follows:

Increase of the pH value of the acidic condensed water to a value of more than 6.5.

Page 9: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

9

4 | Obligatory neutralisation as per ATV-DVWK-A 251 Excerpt derived from chapter 4.1.3 of the current August 2003 edition

Nominal heat output

Neutralisation for firing systems and motors without catalytic converter is required for

Gas Heating oil DIN 51603-1,

low on sulphur

Heating oil DIN 51603-1

< 25 kW no 1), 2) no 1), 2) yes 25 up to 200

kW no 1), 2),3) no 1), 2),3) yes

> 200 kW Yes yes yes However, a neutralisation is nevertheless required

1) if the domestic waste water is discharged into small sewage plants, 2) in case of buildings and lots whose drainpipes do not meet the material requirements stipulated in paragraph 5.3, 3) in case of buildings which do not meet the requirements for sufficient blending as per paragraph 4.1.1.

Page 10: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

10

C Product description

1 | Type designation plate The type designation plate is located at the housing of the neutralisa-

tion system. In order to speed up the processing of your inquiries or orders, please specify the data shown on the type designation plate when contacting Grünbeck. Please copy the indicated information to the table below in order to have it readily available whenever necessary.

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24 Serial number: /

Order no. (NO-5) 410 230

Order no. (NO-12) 410 240

Order no. (NO-24) 410 250

2 | Designated application GENO®-Neutra NO-5, NO-12 and NO-24 systems are designed for the

neutralisation (increase of the pH-value to more than 6.5) of condensed water originating from oil- and gas-fired heat generators (condensing boilers) and/or exhaust systems made of stainless steel, plastic, glass, graphite and ceramics according to ATV-DVWK-A 251, DIN 4716-1, DVGW-VP114 and DIN 4716-2 up to the specified capacity.

Concentrations of manganese, aluminium and zinc contained in the condensate may clog the neutralisation granulate and therefore consid-erably affect the function of the neutralisation system. If need be, the applicability should be checked by means of tests and if necessary, reg-ular cleaning of the system with replacement of the granulate must be arranged for.

Condensed water may also contain impurities, combustion residues and also unburnt hydrocarbons or oil, amongst other things, when operat-ing the system with oil. These are retained by the condensate inlet filter integrated into the system inlet. We recommend with a gas condensing boiler operated in gas / oil switching mode or with in-creased dirt content (e.g. the dirt ingress above the chimney) that you install an additional condensate pre-filter in the inlet hose to the neu-tralisation system.

Page 11: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

11

This is because experience has shown that with a condensing boiler operated in gas / oil switching mode, deposits may detach from pipes and other components when switching over to gas and be flushed into the neutralisation system as a result of the higher specific condensed wa-ter volume with gas (0.14 l/kWh with gas, 0.08 l/kWh with oil).

The system may only be operated if all components are installed properly. Safety devices must NEVER be removed, bridged or otherwise tampered with.

Designated application of the system also implies that the information contained in this operation manual and all safety guidelines applying at the installation site be observed. Furthermore, the maintenance and inspection intervals have to be observed.

Page 12: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

12

3 | Design

The neutralisation system consists of a neutralisation tank with hose connections for inlet and outlet. In the neutralisation tank, a sedimenta-tion zone for impurities, a zone for activated carbon filling and neutrali-sation granulate filling with an aeration device and a collection zone for condensed water are aligned in direction of the flow.

An overflow orifice is mounted above the outlet piece so that the con-densate may exit the system at a predefined place in case the conden-sate outlet is clogged. The neutralisation system can be equipped with an optional overflow warning switch - refer to accessories.

The aeration pump is fixed to the outside of the neutralisation tank with a band clamp and connected to the outlet system with a hose and non-return valve.

A siphon with a trap seal depth of 46 mm is integrated into the inlet connection for the NO-5 system.

The NO-24 consists of two NO-12 systems switched in series that are connected with a hose section.

Page 13: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

13

1 Tank

2 Plugs

3 Nuts

4 Seals

5 Angle-type hose connection

6 Lid

7 Outlet system for NO-5

8 Non-return valve

9 Aeration pump

10 Band clamp

11 Clamping pin

Fig. C-1: Position drawing NO-5

Page 14: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

14

1 Tank

2 Outlet system for NO-12

3 Lid

4 Y-piece

5 Non-return valve

6 Aeration pump

7 Band clamp

8 Clamping pin

Fig. C-2: Position drawing NO-12

Page 15: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

15

1 2 x compact system NO-12

2 Hose clamp

3 Connecting hose

Fig. C-3: Position drawing NO-24

4 | Function

The condensed water flows into the sedimentation zone of the neutral-isation system. The condensed water is then distributed via the inte-grated filter plates and flows through the activated carbon and neutral-isation granulate filling. The granulate is thus solubilised and the con-densed water neutralised. The aeration device reduces iron deposits in the process. Afterwards, the condensed water flows to the drain.

The quantity of neutralisation granulate included in the scope of supply corresponds to the initial filling required at maximum capacity.

The pH value of the discharged water may be checked by means of the pH indicator strip included in the scope of supply. Neutralisation granu-late should be refilled before the pH value falls below 6.5.

Page 16: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

16

5 | Scope of supply

Standard equipment 1 Neutralisation System GENO®-Neutra NO-5, N-12 or N-24 The NO-24 consists of two NO-12 systems.

1 Plastic bag containing: 1 Pack of pH indicator strips 3 Hose clamps (for NO-12 and NO-5) 5 Hose clamps (for NO-24)

1 Connecting hose (for NO-24)

5 m hose DN 20

Activated carbon filling (filled into system for NO-5)

Neutralisation granulate GENO®-Neutralit Hz 3 kg for NO-5 (filled into system) 8 kg for NO-12 16 kg for NO-24

1 Operation manual

1 List of authorised service companies

Complete and packed in cardboard box

Page 17: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

17

Accessories Order no.

Overflow warning switch Voltage-free level switch (changeover con-tact) with attached flat pin bushing for electrical connection as well as fastening material for installation in the lid of the neutralisation system.

410 680

Alarm delay KZL 71 Alarm delay relay in the on-wall housing, e. g. to realise a parallel or delayed switch-off of the heating boiler after an alarm has occurred. Only applicable in combination with the optional accessory "overflow warning switch" of the neutralisation sys-tem.

410 285

Spiral hose DN 20, 5 m

Waste water lifting system AH-300

Oil binder mats (20 pcs)

410 764e

420 150

410 585

Consumables

Maintenance set for NO-5

Maintenance set for NO-12

Maintenance set for NO-24

GENO®-Neutralit Hz - 8 kg

pH indicator strips - 3 pieces

410 805

410 806

410 807

410 011

170 173

Page 18: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

18

6 | Technical specifications All system data is summarised in the table C-1. The data given refers to

standard neutralisation systems. Possible deviations in case of special ver-sions are listed separately, if applicable.

Table C-1: Technical specifications/Dimensions GENO®-Neutra NO-5 NO-12 NO-24 Connection data Power supply 230 V / 50 Hz Power input [W] 5 5 10 Protection/protection class IP X4/II Voltage-free fault contact (optional overflow warning switch)

Changeover contact, switching capacity 250 V / 6 A (Ohmic load) electrical connectionflat pin

bushings 6.3 x 0.8 mm Nominal diameter of inlet/outlet hose [DN] 20 Min. drain connection [DN] 40 Performance data Combustible/process (generation of condensate) Oil/gas condensing technology Max. neutralisation capacity, at 0.08 l/kWh this corresponds to a max. boiler capacity of

[l/h][kW]

4.4 55

12.8 160

25.6 320

Filling volumes and consumption data Neutralisation granulate (8 kg, order no. 410 011)

GENO®-Neutralit Hz

Filling volume neutralisation granulate [kg] 3 8 16 Service life in case of standard condensate acc. to DIN 4716-1, pH 2 Neutralisable condensate volume This corresponds to the full load operating hours of boiler

[m³][bVH]

12 months

2.9 650

12 months

8.3 650

12 months

16.6 650

Service life in case of standard condensate, however at a pH of at least 2.5 Neutralisable condensate volume This corresponds to the full load operating hours of boiler

[m³][bVH]

12 months

6.6 1500

12 months

19.2 1500

12 months

38.4 1500

Dimensions and weights Condensate backwater height in standard operation [mm] 120 A Total height [mm] 165 B Height inlet connection [mm] 110 C Height outlet connection [mm] 110 D Length without hose connections [mm] 410 458 458 E Length with hose connections [mm] 435 469 469 F Width [mm] 268 230 460 G Overflow height (lower edge of orifice) [mm] 140 H Length with connecting hose, approx. [mm] - - 600 Operating weight, approx. [kg] 12 16 32 Shipping weight [kg] 7.5 14 28 Ambient data Condensate temperature [°C] 5 - 60 Ambient temperature [°C] 5 - 40 Test certificate/Certification mark DVGW registration number DG-4585CM0232 Order no. 410 230 410 240 410 250

Page 19: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

19

NO-5

NO-12

NO-24

Fig. C-4: Dimensional drawing

Page 20: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

20

D Installation

1 | General installation instructions

Note: When installing systems with optional accessories, also observe the operation manuals that have been supplied with the optional ac-cessories.

Attention! If no floor drain is available at the installation site, an alarm device must be installed. In case of a system failure, the alarm device must visibly indicate the alarm and, if necessary by switching the heat generator, prevent the system from overflowing and consequently pre-vent consequential damage. For an overflow warning switch, please refer to accessories.

The technical specifications of the system and the regulations for discharge to the public sewage system according to ATV- DVWK - worksheet A 251, as well as the local and general regulations must be observed.

The installation site must be frost-proof and ensure the system's protection from chemicals, dyes, solvents, high radiation tempera-tures, dust and from direct sunlight.

The installation site must provide adequate space, be level, horizon-tal and load-bearing and easily accessible for inspection and maintenance work.

The neutralisation system is fitted with a power cable that is approx. 2 metres long (2 power cables for the NO-24) with a flat Euro plug. One or two 230 v / 50 Hz socket(s) is/are required for the electrical connection.

This power connection must conduct a continuous current or be connected in parallel to the burner of the condensing boiler. Other operating modes may considerably affect the function of the neu-tralisation system.

The required connections must be provided prior to the installation.

Page 21: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

21

2 | Sanitary installation - Installation instructions

Installation and start-up may only be performed by an approved instal-lation company with appropriately trained personnel. However, you may also assign Grünbeck's technical service/authorised service company.

Take into consideration that in standard operation the condensed water is accumulated to a level of approx. the height of the outlet connection. If the condensed water shall completely drain from the heat generator or the flue gas system, the installation areas respec-tively the outlets for the condensed water must be provided for ac-cordingly.

A drain connection (min. DN 40) must be available for the discharge of the condensed water and discharge without backwater must be ensured.

If no floor drain or drain connection close to the floor is available, the water lifting system AH-300 can be installed downstream of the system (refer to accessories).

Use the hoses supplied with the system to make the connections (resp. refer to chapter C, accessories).

Should additional hoses and fittings be needed, only approved, cor-rosion-resistant materials according to ATV-worksheet - A251 (e. g. PP, PE, PVC, ...) may be used. Do not use any parts made of brass, copper or steel.

Additional condensing boilers or/and flue gas systems may be inte-grated up to the max. neutralisation capacity by using corresponding T pieces.

Page 22: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

22

GENO®-Neutra NO-12 GENO®-Neutra NO-24

GENO®-Neutra NO-12 GENO®-Neutra NO-24

GENO®-Neutra NO-5

The drain hose must not be connected directly to the drain pipe in order to prevent retroactive bacterial contamination from the drain to the neutralisation system (refer to Fig. D-1).

Direct the inlet hose with a gradient to the neutralisation system and the outlet hose with a gradient to the drain (see Fig. D-1). Do not bend the hoses!

If no siphon is available, the inlet hose must be directed to the neu-tralisation system with a backwater loop (refer to Fig. D-1) as well as a gradient.

A siphon with a trap seal depth of 46 mm is integrated into the inlet connection for the NO-5. Therefore, no additional siphon may be available here and the inlet hose must be directed with a gradient without a backwater loop (refer to Fig. D-1).

Fig. D-1: Installation example 2.1 Preliminary work

Unpack all system components and check for completeness (for the scope of supply, please refer to chapter C) and soundness.

Select an installation site where the inlet and outlet hoses can be as short as possible.

For the NO-24, connect both NO-12 systems with the enclosed con-necting hose and fasten by means of hose clamps.

Remove the lid of the neutralisation tank.

Fill the activated carbon and neutralisation granulate acc. to Fig. D-5 and D-7. The NO-5 is already fillled acc. to D-3.

If necessary, install accessories as indicated in the operation manuals that come with these systems.

Page 23: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

23

Granulate fillinglevel max.

Inlet DN20

Outlet DN20

Activatedcarbon

Neutralisationgranulate

Fig. D-2: Granulate filling level for NO-5 Fig. D-3: NO-5 Filling areas

Granulate fillinglevel max.

Inlet DN20

Outlet DN20

Activatedcarbon

Neutralisationgranulate

Fig. D-4: Granulate filling level for NO-12 Fig. D-5: NO-12 Filling areas

Granulate fillinglevel max.

Inlet DN20

Outlet DN20

Activatedcarbon

Activatedcarbon

Neutralisationgranulate

Neutralisationgranulate

Fig. D-6: Granulate filling level for NO-24 Fig. D-7: NO-24 Filling areas

Page 24: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

24

2.2 How to connect the system

Strictly observe the direction of flow as well as the technical specifi-cations!

Connect the system according to the installation instructions and fasten the hoses by means of hose clamps.

3 | Start-up Connect the power cable of the aeration pump(s) to the designated

socket(s). This power connection must conduct a continuous current or be connected in parallel to the burner of the condensing boiler. Other operating modes may considerably affect the function of the neutralisa-tion system.

Fill the neutralisation system with water.

Check the system as well as the inlet and outlet lines for tightness.

Close the lid of the neutralisation tank.

The system is now ready for operation.

Properly instruct the user resp. the operating personnel

Fill out the operation log (refer to chapter F, operation log)

Page 25: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

25

E Troubleshooting Even carefully designed and manufactured technical systems that are

operated properly, may experience malfunctions. Table E-1 provides an overview of possible problems that may occur during the operation of the neutralisation system and indicates the causes and their elimination.

Note: Grünbeck's technical customer service/authorised service company must be notified in case of malfunctions that cannot be remedied with the information given in table E-1! When contacting Grünbeck's tech-nical service, please indicate the system designation as well as order number and serial number.

Note: Depending on the operating conditions (season, operating hours of the burner, temperature of heat supply and return, ...), the granulate consumption may vary considerably. This is normal and due to technical reasons.

Note: Clotty granulate is not considered to be a malfunction. If neces-sary, loosen up the clotty granulate. In general, the neutralisation effi-ciency is not affected by this. However, deposits of impurities contained in the condensed water may negatively affect the neutralisation effi-ciency. In general, this may be remedied by more frequent cleaning and renewal of the granulate (refer to chapter C-2). Only use genuine neu-tralisation granulate (refer to consumables)!

Page 26: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

26

Table E-1: Troubleshooting This is what you observe This is the cause This is what to do Short-term increase of the pH val-ue at the outlet to more than 10.

Longer period of standstill. No immediate action required.

Repeat the check of the pH value after a longer period of continuous operation.

pH value at the outlet is below 6.5 after a longer period of operation.

Neutralisation agent is used up. Clean the system in case of se-vere sludge deposits (refer to maintenance).

Refill granulate.

Granulate is clotty or clogged due to deposits.

Due to longer periods of stand-still, e. g. in the summer months, the granulate is caked and cured.

Loosen the granulate by adding water, perform maintenance, if necessary.

Filter plate is dirty. Clean the filter plates.

Coating on the neutralisation granulate, air inlet filter on the aeration pump are dirty.

Replace the air inlet filter on the aeration pump.

Outlet system is blocked. Clean or replace the outlet sys-tem.

pH value at the outlet is perma-nently above 10 or below 6.5.

Deviating from the reference value of the design specifica-tion, highly differentiating con-densed water types and con-densed water volumes may oc-cur in boiler and flue gas sys-tems and therefore a different system size may be required.

Adapt the system size to the inlet volume of condensed wa-ter.

Aeration pump is not running. No mains voltage available.

Electrical connection is defec-tive.

Aeration pump is defective.

Check the electrical connec-tions; replace the aeration pump if necessary.

Page 27: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

27

F Maintenance and care

1 | Basic information

Maintenance work may only be performed by Grünbeck's technical ser-vice/authorised service company or by an approved specialist company.

Danger! When performing maintenance work or when cleaning the system, pull out power plugs and disconnect the power from the inlet hose of the voltage-free contacts.

Attention! Danger of water damage! Clean resp. replace damaged, old or silted hose connections. Check system for tightness.

In order to guarantee the reliable function of the neutralisation systems over a long period of time, some maintenance work has to be per-formed at regular intervals. All regulations and guidelines which apply at the installation site must be strictly adhered to.

The regular inspections can be performed by the operator or by a trained expert contracted by him. Initially, we recommend inspecting the system at shorter intervals and later on as required. However, an inspection is compulsory at least every six months.

Depending on the impurities contained as well as the volume and the pH value of the condensed water, maintenance work has to be performed at regular intervals, at least, however, once a year, other-wise the warranty will be void. Maintenance must be performed by an approved installation com-pany with appropriately trained experts or by Grünbeck’s technical service/authorised service company.

In order to document the inspection and maintenance work, an op-eration log must be kept (for the operation log, see appendix). In the case of system failure, the operation log helps to identify possible sources of error. In addition the log documents the proper system supervision.

Note: A maintenance contract ensures that all the required mainte-nance work will be performed in due time.

Note: Only use genuine neutralisation granulate and activated carbon (refer to chapter C, consumables)!

Page 28: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

28

2 | Inspection

Note: Inspection work is sensible and necessary to ensure the function of the system and to identify maintenance requirements at an early stage.

A minimum of the following components should be kept in stock for carrying out an inspection (refer to spare parts).

Air inlet filter for the aeration pump

Oil binder mats

Inspection work

Check the pH value at the condensate outlet. The pH value meas-ured must be higher than 6.5.

Check the inlet and outlet lines for deposits and clean them, if nec-essary.

Check whether there is a film of oil on the surface of the water in the neutralisation tank (not necessary when operating the system with gas). If this is the case, remove the film of oil by means of an oil binder mat. Immediately inform or consult the technical service re-sponsible for the condensing boiler about the film of oil. Do not use any loose oil binding agents! These can lead to a blockage of the neutralisation system.

Check the air inlet filter on the aeration pump for any impurities and replace if necessary.

If required, refill the neutralisation granulate or perform mainte-nance.

Check the water level in the neutralisation system and if necessary, fill with water up to the outlet level.

Check the system as well as the inlet and outlet lines for tightness.

Record the inspection in the operation log (refer to chapter F, opera-tion log).

3 | Maintenance

A minimum of the following components should be kept in stock for

performing maintenance (refer to spare parts)

Maintenance set

Oil binder mats

Outlet system (recommended)

Page 29: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

29

Maintenance work

1. Stop the occurrence of condensed water or redirect it to a suitable collecting tank.

2. Pull the power plug on the aeration pump out of the socket.

3. If the accessory "overflow warning switch" is available, de-energise it and remove it from the system together with the lid.

4. Check whether there is a film of oil on the surface of the water in the neutralisation tank (not necessary when operating the system with gas). If this is the case, remove the film of oil by means of an oil binder mat. Immediately inform or consult the technical service responsible for the condensing boiler about the film of oil. Do not use any loose oil binding agents! These can lead to a blockage of the neutralisation system.

5. Detach the air hose on the aeration pump and remove the aeration pump from the system by lifting the band clamp.

6. Remove the granulate and activated carbon separately from the system, preferably with a wet suction device, fill the plastic bag in-cluded in the maintenance set and dispose of this as specified in chapter A-5.

7. Clean the outlet system and replace it if necessary (refer to spare parts)

8. Clean the tank.

9. Check the inlet and outlet lines for deposits and clean them, if necessary.

10. Install the outlet system again.

11. Replace the connecting hose between the non-return valve and aer-ation pump.

12. Replace the inlet filter and aeration pump feet.

13. Install the aeration pump and connect the air hose.

14. Insert the power plug on the aeration pump into the socket.

15. Fill activated carbon and neutralisation granulate into the corre-sponding areas (refer to chapter D-2.1).

Page 30: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

30

16. Fill the system with water and check the system as well as the inlet and outlet lines for tightness.

17. Close the lid of the neutralisation system again. If the accessory "overflow warning switch" is available, energise it and check the function of the alarm signal (simulate backwater). Lift the outlet hose for a short time and fill the tank with water to the level of the overflow orifice. Close the lid - the overflow warning switch must be completely inserted in the terminal screw connection.

18. Record the maintenance in the operation log (see chapter F, opera-tion log).

19. Hand over the operation manual to the operator.

4 | Spare parts

Note: For accessories and consumables refer to chapter C.

Note: You may order spare parts, accessories and consumables from your local Grünbeck representative.

Wearing parts:

Various components are subject to a certain wear and tear or ageing and therefore are considered to be wearing parts.

Note: Although these are wearing parts, we grant a limited warranty period of 6 months. The same applies for electrical components. The wearing parts are indicated below (refer to the table for Fig. F-1, F-2, F-3).

Aeration pump The proper function of the aeration pump depends on environmental parameters (temperature, air humidity, air pollution, etc.), whereby the wearing parts or parts in which impurities may occur need to be re-newed as required. These include the membranes, filter felt and possi-bly the pump head if it is dirty.

As extensive repair work does not generally make sense and requires expert knowledge, we recommend that the entire aeration pump is replaced in the event of system failure.

We generally recommend that the aeration pump is replaced every 4 - 5 years to prevent any malfunctions.

As a general rule, the air inlet filter must be replaced as part of a general maintenance.

Page 31: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

31

Fig. F-1 Wearing parts on the GENO®-Neutra NO-5 Pos. Notes 1 Plugs 2 Angle-type hose connection 3 Seals 4 Overflow warning switch Accessories 5 * Outlet system for NO-5 6 * Non-return valve 7 * Air inlet filter and rubber feet 8 * Hose section 9 * Aeration pump 10 * Band clamp 11 Clamping pin w/o item no.

* Hose DN 20

*Wearing parts

Page 32: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

32

Fig. F-2: Wearing parts on the GENO®-Neutra NO-12 Pos. Notes 1 * Outlet system for NO-12 2 Overflow warning switch Accessories 3 * Non-return valve 4 * Hose section 5 * Aeration pump 6 * Band clamp 7 * Air inlet filter and rubber feet 8 Clamping pin 9 * Connecting hose Only for NO-24 w/o item no.

* Hose DN 20 5 m

*Wearing parts

Page 33: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

33

Fig. F-3: Wearing parts for the GENO®-Neutra NO-24

Note: The GENO®-Neutra NO-24 consists of two GENO®-Neutra NO-12 systems connected in series. Therefore the same parts can be used.

Page 34: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

34

Page 35: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

35

Operation log Customer

Name: ..........................................................

Address: ......................................................

...................................................................

...................................................................................

Neutralisation system

System type .................................................

Order no. ....................................................

Serial number: .............................................

Installation: Date: .............................................................................. ......................................................................................

Company: .......................................................................

Phone: ............................................................................

Start-up: Date: .............................................................................. ......................................................................................

Company: .......................................................................

Phone: ............................................................................ Connection data/

condensing boiler: Manufacturer: .................................................................

Type: ........................ Capacity [kW]: ..............................

Combustible: .................................................................

Material(s) of boiler: ........................................................

Material(s) of heat exchanger: .........................................

Material(s) of flue gas system: .........................................

Page 36: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

36

Log of proof for inspection, maintenance and repair work

System type: ..................................... Order no. ................................. Serial no.: ..................................

Work performed Execution confirmed

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Page 37: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

37

Log of proof for inspection, maintenance and repair work

System type: ..................................... Order no. ................................. Serial no.: ..................................

Work performed Execution confirmed

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Page 38: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation Systems GENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

38

Log of proof for inspection, maintenance and repair work

System type: ..................................... Order no. ................................. Serial no.: ..................................

Work performed Execution confirmed

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Page 39: Operation Manual Neutralisation Systems GENO … Manual Neutralisation Systems GENO ®-Neutra NO-5 GENO®-Neutra NO-12 GENO®-Neutra NO-24 Edition: September 2011 Order no. 015 410

Neutralisation SystemsGENO®-Neutra NO-5, NO-12, NO-24

Order no. 015 410 850 Edited by: KONS-gme-rg G:\BA-410850-INTER_GENO-NEUTRA NO-5_NO-12_NO-24.DOC.DOC

39

Log of proof for inspection, maintenance and repair work

System type: ..................................... Order no. ................................. Serial no.: ..................................

Work performed Execution confirmed

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................

Inspection

Maintenance

Repair

Description _____________________________________________________

__________________________________________________________________

__________________________________________________________________

__________________________________________________________________

Company: ......................................................................................

Name: ............................................................................................ Date/ Signature: .......................................................................................