Operating Instrution OKAN 2 Und 3 EX Eng (1)

12
Oil-Air Cooling Units Series OKAN II, OKAN II/Ex, OKAN III General view Edition 10/2004 Operating Instruction OKAN III OKAN II

description

AIR COOLER

Transcript of Operating Instrution OKAN 2 Und 3 EX Eng (1)

  • Oil-Air Cooling UnitsSeries OKAN II, OKAN II/Ex, OKAN III

    General view Edition 10/2004

    Operating Instruction

    OKAN III

    OKAN II

  • 1.1 User instructions

    This instruction relates to standard versions of the FUNKEoil-air cooling units.Supplementary operating and servicing instructions may beneeded for special versions. Please observe the order-related specifications in every case!

    Operation and servicing of FUNKE oil-air cooling units areallowed only if carried out by professionally trained andqualified operating and servicing personnel. In particular,please observe national and international specifications onpressure equipment, hazardous fluids, working in hazardousareas as well as accident prevention and operational safety(in Germany: Law on operational safety and pertinentordinances.)

    Text sections, where the working procedure andspecifications must be strictly adhered to, to avoidlife danger or system damages, are marked with thewarning triangle shown below:

    List of contents

    1.0 General

    1.1 User instructions .............................................S.2

    1.2 Intended use....................................................S.3

    1.3 Identification/name plate.................................. S.3

    2.0 Safety instructions ......................... S.4

    3.0 Design & functional description

    3.1 Design, main components, materials,

    accessories.....................................................S.5

    3.2 Operation, functional desciption.........................S.5

    4.0 Functional ranges, operation conditions

    4.1 Allow. media....................................................S.6

    4.2 Operating data.................................................S.6

    4.3 Ambient conditions.......................................... S.6

    5.0 Transportation...............................................S.7

    6.0 Installation, initial operation

    6.1 Installation....................................................S.7/8

    6.2 Initial operation................................................S.8

    6.3 Operating advice..............................................S.8

    6.4 Shutting down / dismantling..............................S.8

    7.0 Maintenance..................................................S.9

    8.0 Causes of faults / removal of faults................S.9

    9.0 Environmental protection / disposal..............S.9

    Technical data.........................................S.10/11

    Name and adress of manufacturer:

    FUNKE WRMEAUSTAUSCHER APPARATEBAU GmbHZur Dessel 1, D-31028 Gronau/Leine

    Phone: +49 (0) 5182 582-0, Telefax: +49 (0) 5182 582-48e-Mail: [email protected], Internet: www. funke.de

    Attention!

    The operator must instruct the staff appropriately before theinitial operation starts.The operating instruction must be accessible at all times.If work beyond these instructions needs to be carried out onthe oil cooling unit or if instructional texts are not understood,consult with FUNKE before beginning the work.

    Text sections, where working procedures, operatingconditions and maintenance instructions must be strictlyadhered to, to ensure proper functioning of the cooling unitas well as an economical operation, are marked with thefollowing symbol:

    1.0 General

    Important!

  • 1.3 Identification / name plate

    Each oil-air cooling unit is provided with a name-plate(figure 1).Accessibility and readability must be ensured at any time.The name plate, containing the following data is fixed laterallyon the cooler core or fan shroud:

    -Type / model- Serial number (to be mentioned on all enquiries)- Drawing number- Year of manufacture- Max. operating pressure PS- Min. operating temperature TS min. (if required)- Max. operating temperature TS max.- Volume- Test pressure- Fluid group (acc. to EU Pressure Equipment Directive (PED) 97/23/EC

    Information:

    No CE-symbol is required acc. to EU Pressure EquipmentDirective (PED) 97/23/EC for FUNKE-OKAN II/III seriesbecause of the low pressures and volumes.

    Units which are used in hazardous areas must be equippedwith a guard acc. to ATEX-directive 94/9/EC. CE-symbol isrequired.In this case the name-plate contains additional informationas follows:- CE-symbol- identification number of the notified body acc. to PED- inspection date

    - 3 -

    1.2 Intended use

    FUNKE oil-air cooling units are intended to cool oils,hydraulic fluids and mixtures of water/glycol by means ofambient air.FUNKE oil-air cooling units are unless required otherwiseby order specifications - designed for special conditions ofuse specified by the customer, concerning temperature,pressure, volumetric flow and flow media and are fabricatedin conformity with EU-pressure equipment directive(PED) 97/23.

    Written approval must be obtained from FUNKE for designchanges on the equipment as well as for operating methoddeviating from these instructions or the order-related productspecifications, otherwise guarantee and liability claims canbe invalidated.

    An operation with heavy temperature jumps of the medium tobe cooled as well as pressure surge can cause mechanicalor material damage and is generally not allowed!

    Abb. 1Principal structure of the name-plate

    1/1 Standard series:

    1/2 Design according to ATEX directive:

  • Works may be carried out on the oil-air cooling unit only- if the fan drive is disconnected from the power supply, ifthe hydraulic drive is disconnected from the oil pumprespectively.-if the unit is not under pressure, the temperature of themedia to be cooled does not exceed 40C and the systemis drained!

    In case of fan drive by hydraulic motor the max. allow.rotational speed of the fan shall not be exceeded!(More information are on the technical data sheet orobtainable from our specialised personnel.)

    No operation in case of partial or complete flooding!

    Boiling or freezing of the medium to be cooled shall beavoided in any case (danger of cooler core destruction)!

    Explosion protection / ATEX

    In addition the following applies for use of oil-air coolingunits in hazardous areas:

    - No operation of oil-air cooling units without explosionprotective equipment!- Oil-air cooling units explosion protected design are onlyapproved for:ATEX group II, category 3, zone 2 or 22 respectively.- Oil-air cooling units with ATEX equipment are allowed torun in hazardous areas onlywithin the temperature range of 20 to +40C.In case of special design the allowable temperature rangeof the motor must be complied with in any case!

    In case of doubt please apply to our experts before puttinginto service!

    Attention!

    FUNKE oil-air cooling units are pressure equipment andallowed to be connected, operated and maintained only bytechnically qualified operating and servicing personnel!National and international directives for pressureequipment and machinery(Europe: EU Pressure Equipment Directive (PED) 97/23/EC,machinery directive 98/37/EC),for hazardous fluids as well as on operating safety andaccident prevention must be observed.(In Germany: Law on operating safety and pertinentordinances.)

    In any case the user has to equip the plant with a controldevice for a safe stoppage of the machinery.

    Do not operate the oil-air cooling unit without guard screen!

    The operator must check that there is nothing interferinginto the fan. He also must ensure that in case of assemblynear passageways persons without protective clothingmust keep a distance of min. 1,0 m.

    Persons staying less than 1,0 m distant from the oil-aircooling unit have to wear protective clothing. Persons withlong hair have to use a hairnet or appropriate cap!

    To remove protective devices is not allowed with theexception for maintenance and servicing works isallowed only by authorised persons.

    If the oil-air cooling unit is installed in areas where aleakage of the hose or tube connection can injure persons,place a spray guard or drip cover!

    If in case of assembly near passageways operatingtemperatures are exceeding 60C, a protection againstaccidental contact should be placed or the area should beblocked!

    Be careful in case of thermostat controlled starting ofventilators! Possibly place an information sign nearpassageways!

    - 4 -

    2.0 Safety instructions

  • 1. Cooler corematerial: aluminium(optional: sea air resistantpaint coating )

    2. Motor support platematerial: steel, surface-treated

    3. Fan shroudmaterial: steel, surface-treatedor plastic (in case ofexplosion protected design:galvanised steel)

    4. Fan guardmaterial: steel, surface-treated(in case of explosion protecteddesign: galvanised steel)

    5. Fanmaterial: plastic(in case ofexplosion protected design:polyamide with electric conductivity)

    6. Fan drive(in case of explosion protecteddesign: explosion protected motor)

    Accessories (optional):- filter mats with frame- thermostat

    - 5 -

    3.2 Operation, function

    The medium to be cooled is depending on volumetric flowrate flowing through the cooler core either in one pass ormultiple passes and is cooled by the ambient air producedby the fan.The regular fan is a suction fan but can also be supplied aspressure fan if required by the order specification.To reach a high heat dissipation , oil- and air fins, fan bladesand motor power are optimally synchronised.

    3.0 Design & functional description

    3.1 Design, main components, materials, accessories

    For a most efficient application cooling to 5 6 K above theambient air temperature is recommended.To cool down to values below ambient air temperature is notpossible.

    Abb. 2

  • 4.3 Ambient conditions at set-up site

    FUNKE oil-air cooling units are allowed to be used only atambient temperatures as follows:

    In non-hazardous areas(standard design): min. 25C - max. +60C

    In hazardous areas(OKAN explosion protected acc. to ATEX directives):

    min. 25C - max. +40C

    In case of special designs the allowable temperature rangeof the motor must be complied with!

    Ambient air:Unhindered inflow and outflow of ambient air must beensured to avoid a reduced heat dissipation (see also 6.1assembly)Furthermore, if the cooler core or the guard screen of the fanis partly or completely covered, this may cause excessivevibration of the fan or even failure of the drive.Closed rooms must be adequately ventilated.

    In case of low ambient temperatures and as a resultincreased viscosity of the medium to be cooled the functionof the system must be guaranteed by appropriate measures(e.g. pressure limiting valve, preheating).

    Attention. Dust and mist may cause a heavy drop inperformance.

    In case of aggressive or very salty air ( e.g. sea air) a specialpaint is required.

    Furthermore, in hazardous areas the ignition temperature ofdeveloped gases must be considered!FUNKE oil-air cooling units in explosion protected designare approved only for:ATEX group II, category 3, zone 2 or 22 respectively.

    No operation allowed in case of flooding (completely orpartly)!

    Special modifications are available.

    4.1 Allowed media

    - mineral oils, e.g. lubricating oil, cutting oil,converter oil

    - rapidly biodegradable oils, if not attacking aluminium

    - hydraulic fluids, e.g. HFA, HFB, HFC and HFD

    - water/glycol mixture, e.g. water/glycol 65:35

    Under no circumstances use water without anticorrosiveagent! (min 2 %)

    Contaminated oils must be filtered (grade of filtration 0,05mm) !Further media may be used only after written approval byFUNKE.

    4.2 Operating Data

    Allow. operating pressure: max. 16 bar!

    Max. operating temperature of the media to be cooled:

    Oil in hazardous areas(acc. to EU-ATEX directives): max. 100C

    Oil in non-hazardous areas: max. 120C

    Hydraulic fluids: max. 90C

    Water/glycol mixture: max. 90C

    Boiling or freezing of the medium to be cooled must beavoided in any case. Otherwise the cooler core orconnections could be destroyed.

    - 6 -

    Important!

    Attention!

    Attention!

    4.0 Functional range, operation conditions

  • 6.1 Assembly

    Before assembly of the oil-air cooling unit ensure that allbasic requirements for an unhindered operation of the plantaccording to this operating instruction are fulfilled!Safety instructions of 2.0 must be complied with!The plant operator has to assemble and start the plant instrict accordance with the valid rules for pressure equipmentand machinery (Europe: EU pressure equipment directive 97/23/EC, machinery directive 98/23/EC), hazardous fluids aswell as well as operating safety and accident prevention.Assembly of the cooling unit, especially preparation ofelectrical connections is allowed only by specialists!

    Horizontal or vertical assembly of the oil/air cooling unit ispossible. (see figure 5).In case of horizontal fitting position with the end of the motorfacing upwards, a protective shield must be placed above themotor in any case.The oil-air cooling unit must be fixed at 4 points at least on aflat foundation (figure 6).Fixing should be strainless and vibration-free (possibly usevibration isolators)Connections ( electric and hydraulic ) must also bestrainless and vibration-free.Before assembly remove protective plugs from fluidconnections!

    Unless described otherwise in the technical orderspecification, keep a distance to any foreign objects in thesuction range of at least approx. half the height of the coolingunit!

    - 7 -

    6.0 Assembly, putting into service

    5.0 Transportation instruction

    Preferably the FUNKE oil-air cooling units are transported lying on the cooler core - on wooden pallets, properlyfastened not to slip. (figure 3)Bigger oil-air cooling units series OKAN II require liftingdevices for transport and assembly.In case of hanging transport please do not use bright steelropes or chains but sheathed suspension ropes! (figure 4)Suspension ropes to be passed through both frame hoops.Lift slowly. The centre of gravity is not exactly below hangerfixtures and the cooling unit is swinging! figure 3 figure 4

    Figure 5

    Figure 6

  • Control devicesIn any case the plant must be equipped with a control devicefor a safe stoppage of the machinery!

    Plants which are approved to operate in hazardous areasmust be grounded using the corresponding earthing boss.

    Connection of the motor according to data of the motormanufacturer (see technical documentation or terminal box).Observe the direction of rotation of the motor!As standard FUNKE oil-air cooling units are designed forsuction operation.

    In case of horizontal installation the used air must be drawnoff upwards. In any case the technical documentation mustbe observed.In case of high heat dissipation which would result in anexcessive heating of the air in closed rooms, outdoorinstallation is advisable (observe type of protection of themotor!)Outdoors the oil-air cooling unit must be protected (e.g. byroofing) against weather damage caused by rain, snow orwindborne sand etc. If outdoor installation is not possible, anair duct should be provided to lead the used air to theoutside. Note:Supplementary equipment like air ducts for instance cancause loss of the heat dissipation or affect function of theplant if not properly fitted!

    If the oil-air cooling unit is operating with surfacetemperatures exceeding 60C protection against accidentalcontacts should be placed or the area should be blockednear passage ways!

    In case of danger of heavy temperature jumps in the systeminto which the oil-air cooling unit shall be installed (causedfor instance by control valves or shut-off valves or oscillatingpumps), appropriate measures must be taken to protect theair-oil cooling unit!

    - 8 -

    6.2 Start up

    6.3 Operating advice

    An operation with heavy temperature jumps as well aspressure surge can cause mechanical or material damageand is generally not allowed!Continuous or intermittent operation of the FUNKE oil-aircooling unit is possible!When operating the oil-air cooling units with direct-currentmotors it must be taken into consideration that service life ismuch shorter compared with three-phase motors.Frequent startings or continuous operation reduce the lifetime.In case of fan drive by means of hydraulic motor, it is notallowed to exceed the max. allowable rotational speed of thefan!(See technical data sheet or apply to our qualifiedpersonnel.)Essential operating data like pressure and temperature aswell as tightness of the system must be checked regularly,(once monthly at least) depending on conditions of use.

    Comply with safety instructions acc. to item 2.0!1.Check proper installation of all connections.2.Check filling of the oil-air cooling unit.During, after filling respectively the oil-air cooling unit must becompletely vented. Any air in the system reduces the capacityand may cause steam bubbles for instance.3.Start the motor. Check correct direction of rotation.Check that the fan is free from deposits.

    6.4 Shutting down / dismantling

    Dismantling of the oil-air cooling unit and removal of thecooler and motor connections is allowed only by qualifiedpersonnel.Follow safety instructions section 2.0!

    Works on the oil-air cooling unit are allowed only if- the fan drive has been disconnected from the electricalsupply, after the hydraulic drive has been disconnected fromthe oil pump respectively.- the unit is not under pressure, the temperature of themedium to be cooled does not exceed 40C and the unithas been drained!

    Working steps:- Switch off main power supply- Disconnect the motor- Drain fluid from the system, carefully disconnect the fluidlines, collect the fluid for reprocessing or regular disposal(see data sheet for the fluid)- Unscrew mounting bolts- Apply protective covers on connecting openings- Protect oil-air cooling unit against damage- Possibly choose appropriate transport container

    Take notice of the safety instructions section 2.0

    Important!

  • - 9 -

    7.0 Maintenance

    In case of normal operation FUNKE oil-air cooling units arenearly maintenance-free.Essential operating data like pressure and temperature aswell as tightness of the system must must be checkedregularly, (once monthly at least) depending on conditions ofuse.

    Follow safety instructions section 2.0!

    Works on the oil-air cooling unit are allowed only if- the fan drive has been disconnected from the electricalsupply, after the hydraulic drive has been disconnected from the oil pump respectively.- the unit is not under pressure, the temperature of themedium to be cooled does not exceed 40C and the unit has been drained!

    Cleaning of the oil-air cooling unitAirside dirt deposit on the suction side of the coolingelements can be removed by brushing or vacuum.In case of heavy dirt proceed as follows:

    - dismantle oil-air cooling unit as described under 6.4- remove fan and drive- clean cooler core with compressed air and/or steam jet(cold cleaner can be added) against the direction of airflow

    Caution!Do not damage or bend the core fins. This would result indrop in performance!Internal cleaning (only partly)of the cooler is depending onkind of dirt.

    Deposits as a result of insufficiently filtered oils can beremoved for instance by filling with degreasing agent. Afterreaction time rinse with clean operating liquid.

    By no means cleaning liquids may be used, which areattacking aluminium!

    8.0 Cause of faults / removal of faults

    The cause for a capacity loss can be on the airside and alsoinside the oil-air cooling unit.1. Too low mass flow check or correct:

    - rotational speed of pump- rotational speed of fan- direction of rotation of fan- electric / hydraulic connection- increased pressure drop in the system

    2. Increased pressure drop Check or correct:

    - narrowed flow cross-section due to deposits / foreign matters- narrowed flow cross-section due to mechanical effect

    3. Too low inlet temperature difference Check or correct:

    - increased air inlet temperature4. Deviations between design conditions and conditions ofuse Check or correct respect:

    - temperature- mass flow- physical properties

    In case of a motor failure the user instructions of the motormanufacturer must be followed!

    9.0 Environmental protection / disposal

    FUNKE oil-air cooling units are building a closed system.Provided are proper connection and correct operating mode.However, in case of incorrect operating mode or incorrectconnections, or caused by mechanical effects, leaks cannotbe excluded.If in case of a leak at set-up site the medium to be cooled isdirectly reaching the environment (soil or water circuit), the user has to place an appropriate collecting devices (forinstance a back leakage sump). Furthermore, pertinentenvironmental protection regulations and possibly specialregulations concerning handling of the medium to be cooledmust be complied with.Disposal of the oil-air cooling units must be made inaccordance with the rules for disposal of oil and hydraulicfluids as well as for electronic components like motors andswitches.

    Important!

  • Technical Data OKAN II

    D1 ****

    D2****SAE-FL

    T3 T4

    B4

    B1

    B

    B3

    H3

    H1

    H2

    H

    102

    T28

    T1

    H4

    H5

    T

    B2

    12

    M1 **** HebeseLifting eye

    oeil porte charge

    X

    Gre / type / type 1)

    02 03 04 05 06 07 08 09 10 11 13 14Stirnflche / face / surface frontale m 0,05 0,08 0,1 0,16 0,2 0,25 0,315 0,4 0,5 0,6 0,8 1,0

    Inhalt / contents / volume l 1,6 2,7 3 5 5,5 6,2 7 8,8 9,7 11 18 20

    Gewicht / weight / poids kg 16,1 22,5 24,6 35,4 38,4 46,4 51,4 67,6 77,6 138 177 189

    Geruschpegel /noise level / *** 750 - - - - - - - - - - - - 57 / 45 58 / 46 62 / 50 66 / 54 68 / 56 71 / 59 73 / 61 77 / 65 77 / 65

    niveau bruit 1000 - - - - 59 / 47 59 / 47 64 / 52 65 / 53 70 / 58 72 / 60 77 / 65 79 / 67 81 / 69 85 / 73 86 / 74

    (1m/7m) (db(A)) 1500 61 / 49 70 / 58 70 / 58 75 / 63 75 / 63 82 / 70 81 / 69 89 / 77 90 / 78 86 / 74 - - - - - - - -1/m

    in

    3000 79 / 67 84 / 72 84 / 72 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    Luftdurchsatz/air flow / debit dair 750/900 - - - - - - - - - - - - 0,27/0,32 0,28/0,34 0,5/0,6 0,5/0,6 0,9/1,08 1/1,2 1,4/1,68 2,84/3,4 3,7/4,44

    1000/1200 - - - - 0,16/0,19 0,2/0,24 0,38/0,46 0,4/0,48 0,7/0,84 0,8/0,96 1,5/1,8 1,7/2,0 2,2/2,64 3,97/4,76 5,3/6,4

    (kg/s) 1500/1800 0,14/0,17 0,25/0,3 0,3/0,36 0,65/0,78 0,7/0,84 1,2/1,44 1,3/1,56 2,4/2,9 2,7/3,24 3,3/3,96 - - - - - - - -1/m

    in

    3000/3600 0,3/0,36 0,6/0,72 0,7/0,84 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    Motorleistung / motor power * 750/900 - - - - - - - - - - - - 0,25/0,29 0,25/0,29 0,25/0,29 0,25/0,29 0,37/0,43 0,37/0,43 0,75/0,86 2,2/3,3 2,2/3,45

    puissance motouer 1000/1200 - - - - 0,25/0,29 0,25/0,29 0,37/0,43 0,37/0,43 0,55/0,63 0,55/0,63 0,75/0,86 0,75/0,86 1,5/2,2 3,0/4,45 4,0/6,3

    (kW) 1500/1800 0,18/0,21 0,37/0,43 0,37/0,43 0,55/0,63 0,55/0,63 0,75/0,86 0,75/0,86 1,5/1,75 1,5/1,75 4,0/6,3 - - - - - - - -1/m

    in

    3000/3600 0,25/0,29 0,55/0,63 0,55/0,63 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    H 376 438 506 612 712 721 853 853 869 1022 1169 1361

    H1 204,5 235,5 269,5 320,5 370,5 370,5 436,5 436,5 436,5 513 592,5 688,5

    H2 62 62,5 62,5 66 66 62 62 62 53 53 81 81

    H3 285 346 414 509 609 617 749 749 767 920 1023 1215

    H4 50 50 50 50 50 55 55 55 55 55 70 70

    H5 309 371 439 541 641 631 763 763 763 916 1045 1237

    B 293 348 348 454 454 548 548 658 818 818 971 971

    B1 20 40 40 45 45 51 51 51 55 55 68 68

    B2 224 268 268 322 322 408 408 544 696 696 824 824

    B3 155 166 166 200 200 260 260 360 360 360 420 420

    B4 213 224 224 258 258 318 318 418 418 440 510 510

    T MAX 450 500 500 550 550 600 600 650 650 750 900 900

    T1 240 240 240 275 275 319 319 319 319 355 580,5 580,5

    T2 108 108 108 148,5 148,5 185 185 185 185 220 215x2 215x2

    T3 109 112 112 112 112 115 115 115 115 115 135 135

    T4 94 93 93 128 128 156 156 156 156 187 215 215

    D1 / M1 **** 9 / M8 9 / M8 9 / M8 9 / M8 9 / M8 11 / M10 11 / M10 11 / M10 11 / M10 11 / M10 13 / M12 13 / M12

    D2 **** 9 9 9 9 9 11 11 11 11 11 14 14

    X 130 130 130 130 130 130 250 350 350 900 1200 1500

    SAE-Flansch/ -falnge/ -bride 1 flu / pass / pass ** 1 1 1 1 1 1 1 2 2 S73x73 S73x73

    SAE-Flansch/ -falnge/ -bride 3 flu / pass / pass ** 1 1 - - - - - - - -

    Betriebstemp. / working temp. / temp. de travail 120C

    Betriebsdruck / working press. / press. de travail 16 bar

    Spannungen / Frequenzen Normspannungen

    Voltages / Frequencies Standard voltages

    Voltages / Frequences Voltages standard

    110 690 V A.C. / 50 /60 Hz 12 V, 24 V D.C.

    * U.p.m / r.p.m. / r.p.m. 50 Hz / 60 Hz ** bei Gre 02 keine SAE-Flansche / no SAE-flanges on type 02 / pour type 02 pas de connexion SAE

    *** bei / at / au 60 Hz + 4 dB(A) **** Befestigungspunkte / Fixing points / Point de fixation

    1) 2.78XX.2. ...

    Gre / type / type

  • M14x1,5

    B2

    B1

    H

    B3

    H3

    H1

    H2

    Tmax

    275

    41 108 12

    Xmin

    H1

    B464 100

    Gre / type / type III-1 III-2 III-3 III-4Stirnflche / face / surface frontale m 0,077 0,11 0,15 0,209Inhalt / contents / volume l 2 2,5 3 4Gewicht / weight / poids kg 16 21 25 31Geruschpegel /noise level / *** 1000 - - 58 / 45 62 / 48 65 / 52 niveau bruit 1500 63 / 51 68 / 54 72 / 58 76 / 63(1m/7m) (db(A))

    1/m

    in

    3000 78 / 66 85 / 70 87 / 74 - -Luftdurchsatz/air flow / debit dair 1000 - - 0,20 0,28 0,55

    1500 0,19 0,33 0,42 0,80 (kg/s)

    1/m

    in

    3000 0,43 0,55 0,84 - -Motorleistung / motor power * 1000 - - 0,25 0,25 0,37 puissance motouer 1500 0,18 0,37 0,37 0,55 (kW)

    1/m

    in

    3000 0,25 0,55 0,55 - -

    H 426 478 548 611

    H1 339 394 464 524

    H2 44 41 41 44

    H3 213 238 273 306

    B1 335 378 430 510

    B2 309 356 403 481

    B3 213 224 224 258

    B4 36 50 50 57

    Tmax 380 424 424 490

    Xmin 200 200 240 240

    Betriebstemp. / working temp. / temp. detravail

    120C

    Betriebsdruck / working press. / press. detravail

    16 bar

    Spannungen / Frequenzen Normspannungen

    Voltages / Frequencies Standard voltages

    Voltages / Frequences Voltages standard

    230 400 V A.C. / 50 /60 Hz 12 V, 24 V D.C.

    Technical Data OKAN III