Nivo®Guide 3100 Two-wire 4 … 20 mA/HART Rod and cable probe TDR sensor for continuous level measurement of bulk solids Technical information / Instruction manual Document ID: 58879

Transcript of Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST...

Page 1: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

Nivo®Guide 3100Two-wire 4 … 20 mA/HART

Rod and cable probe

TDR sensor for continuous level measurement of bulk solids

Technical information / Instruction manual

Document ID: 58879

Page 2: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

2

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

Contents58879-EN

-190215

Contents1 About this document ............................................................................................................... 4

1.1 Function ........................................................................................................................... 41.2 Target group ..................................................................................................................... 41.3 Symbols used................................................................................................................... 4

2 For your safety ......................................................................................................................... 52.1 Authorised personnel ....................................................................................................... 52.2 Appropriate use ................................................................................................................ 52.3 Warning about incorrect use ............................................................................................. 52.4 General safety instructions ............................................................................................... 52.5 EU conformity ................................................................................................................... 62.6 NAMUR recommendations .............................................................................................. 62.7 Installation and operation in the USA and Canada ........................................................... 6

3 Product description ................................................................................................................. 73.1 Configuration .................................................................................................................... 73.2 Principle of operation........................................................................................................ 83.3 Packaging, transport and storage ..................................................................................... 83.4 Accessories and replacement parts ................................................................................. 9

4 Mounting ................................................................................................................................. 104.1 General instructions ....................................................................................................... 104.2 Mounting instructions ..................................................................................................... 11

5 Connecting to power supply ................................................................................................. 155.1 Preparing the connection ............................................................................................... 155.2 Connecting ..................................................................................................................... 165.3 Wiring plan, single chamber housing.............................................................................. 175.4 Wiring plan, double chamber housing ............................................................................ 185.5 Switch-on phase............................................................................................................. 19

6 Set up with the display and adjustment module ................................................................ 206.1 Insert display and adjustment module ............................................................................ 206.2 Adjustment system ......................................................................................................... 216.3 Parameter adjustment - Quick setup .............................................................................. 236.4 Parameter adjustment - Extended adjustment................................................................ 236.5 Saving the parameterisation data ................................................................................... 38

7 Diagnostics and servicing .................................................................................................... 397.1 Maintenance .................................................................................................................. 397.2 Status messages ............................................................................................................ 397.3 Rectify faults ................................................................................................................... 427.4 Exchanging the electronics module ................................................................................ 457.5 Exchange or shorten cable ............................................................................................. 467.6 How to proceed if a repair is necessary .......................................................................... 47

8 Dismount................................................................................................................................. 488.1 Dismounting steps.......................................................................................................... 488.2 Disposal ......................................................................................................................... 48

9 Supplement ............................................................................................................................ 499.1 Technical data ................................................................................................................ 499.2 Dimensions .................................................................................................................... 60

Page 3: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

3

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

Contents58

879-

EN-1

9021

5

9.3 Trademark ...................................................................................................................... 65

Safety instructions for Ex areasTakenoteoftheExspecificsafetyinstructionsforExapplications.These instructions are attached as documents to each instrument with Ex approval and are part of the operating instructions.

Editing status: 2019-02-05

Page 4: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

4

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

1 About this document58879-EN

-190215

1 About this document

1.1 FunctionThis operating instructions provides all the information you need for mounting, connection and setup as well as important instructions for maintenance,faultrectification,theexchangeofpartsandthesafetyof the user. Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.

1.2 Target groupThis operating instructions manual is directed to trained personnel. Thecontentsofthismanualmustbemadeavailabletothequalifiedpersonnel and implemented.

1.3 Symbols usedInformation, tip, noteThis symbol indicates helpful additional information.Caution: If this warning is ignored, faults or malfunctions can result.Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result.Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.

Ex applicationsThis symbol indicates special instructions for Ex applications.

• ListThe dot set in front indicates a list with no implied sequence.

→ ActionThis arrow indicates a single action.

1 Sequence of actionsNumbers set in front indicate successive steps in a procedure.

Battery disposalThis symbol indicates special information about the disposal of bat-teries and accumulators.

Page 5: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

5

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

2 For your safety58

879-

EN-1

9021

5

2 For your safety

2.1 Authorised personnelAll operations described in this documentation must be carried out onlybytrained,qualifiedpersonnelauthorisedbytheplantoperator.During work on and with the device, the required personal protective equipment must always be worn.

2.2 Appropriate useNivoGuide 3100 is a sensor for continuous level measurement.Youcanfinddetailedinformationabouttheareaofapplicationinchapter "Product description".Operational reliability is ensured only if the instrument is properly usedaccordingtothespecificationsintheoperatinginstructionsmanual as well as possible supplementary instructions.

2.3 Warning about incorrect useInappropriate or incorrect use of this product can give rise to applica-tion-specifichazards,e.g.vesseloverfillthroughincorrectmountingor adjustment. Damage to property and persons or environmental contamination can result. Also, the protective characteristics of the instrument can be impaired.

2.4 General safety instructionsThis is a state-of-the-art instrument complying with all prevailing regulations and directives. The instrument must only be operated in a technicallyflawlessandreliablecondition.Theoperatorisresponsi-ble for the trouble-free operation of the instrument. When measuring aggressive or corrosive media that can cause a dangerous situation if the instrument malfunctions, the operator has to implement suitable measures to make sure the instrument is functioning properly.During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regula-tions.The safety instructions in this operating instructions manual, the na-tional installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user.For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi-traryconversionsormodificationsareexplicitlyforbidden.Forsafetyreasons,onlytheaccessoryspecifiedbythemanufacturermustbeused.To avoid any danger, the safety approval markings and safety tips on the device must also be observed and their meaning read in this oper-ating instructions manual.

Page 6: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

6

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

2 For your safety58879-EN

-190215

2.5 EU conformityThedevicefulfilsthelegalrequirementsoftheapplicableEUdirec-tives.ByaffixingtheCEmarking,weconfirmtheconformityoftheinstrument with these directives.

2.6 NAMUR recommendationsNAMUR is the automation technology user association in the process industry in Germany. The published NAMUR recommendations are acceptedasthestandardinfieldinstrumentation.ThedevicefulfilstherequirementsofthefollowingNAMURrecom-mendations:

• NE 21 – Electromagnetic compatibility of equipment• NE 43 – Signal level for fault information from measuring transduc-

ers• NE53–Compatibilityoffielddevicesanddisplay/adjustment

components• NE107–Self-monitoringanddiagnosisoffielddevicesFor further information see www.namur.de.

2.7 Installation and operation in the USA and Canada

This information is only valid for USA and Canada. Hence the follow-ing text is only available in the English language.Installations in the US shall comply with the relevant requirements of the National Electrical Code (ANSI/NFPA 70).Installations in Canada shall comply with the relevant requirements of the Canadian Electrical CodeA Class 2 power supply unit has to be used for the installation in the USA and Canada.

Page 7: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

7

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

3 Product description58

879-

EN-1

9021

5

3 Product description

3.1 ConfigurationThetypelabelcontainsthemostimportantdataforidentificationanduse of the instrument:

21

12

13

14

11

10

5

3

6

4

78

9

Fig. 1: Layout of the type label (example)1 Instrument type2 Product code3 Approvals (option)4 Power supply and signal output, electronics5 Protection rating6 Probe length (measurement accuracy optional)7 Process and ambient temperature, process pressure8 Material wetted parts9 Order number10 Serial number of the instrument11 Symbol of the device protection class12 ID numbers, instrument documentation13 CEidentification14 Approval directives (optional)

This operating instructions manual applies to the following instrument versions:

• Hardware from 1.0.0• Software from 1.3.0• OnlyforinstrumentversionswithoutSILqualification

The instrument and the electronics version can be determined via the product code on the type label as well as on the electronics.

• Standard electronics: Type FX80H.-

The scope of delivery encompasses:

• Sensor• Optional accessory• Documentation

– Quick setup guide NivoGuide 3100 – Instructions for optional instrument features – Ex-specific"Safety instructions" (with Ex versions)

Type label

Scope of this operating instructions

Versions

Scope of delivery

Page 8: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

8

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

3 Product description58879-EN

-190215

– Ifnecessary,furthercertificates

Information:In this operating instructions manual, the optional instrument features are described. The respective scope of delivery results from the order specification.

3.2 Principle of operationThe NivoGuide 3100 is a level sensor with cable or rod probe for con-tinuous level measurement, suitable for applications in bulk solids.

High frequency microwave pulses are guided along a steel cable or a rod. Upon reaching the product surface, the microwave pulses are reflected.Therunningtimeisevaluatedbytheinstrumentandoutputas level.

3.3 Packaging, transport and storageYour instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test based on ISO 4180.The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.

Transport must be carried out in due consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.

The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or con-cealed defects must be appropriately dealt with.

Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.Unless otherwise indicated, the packages must be stored only under the following conditions:

• Not in the open• Dry and dust free• Not exposed to corrosive media• Protected against solar radiation• Avoiding mechanical shock and vibration

• Storage and transport temperature see chapter "Supplement - Technical data - Ambient conditions"

• Relative humidity 20 … 85 %

With instrument weights of more than 18 kg (39.68 lbs) suitable and approved equipment must be used for lifting and carrying.

Application area

Functional principle - level measurement

Packaging

Transport

Transport inspection

Storage

Storage and transport temperature

Lifting and carrying

Page 9: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

9

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

3 Product description58

879-

EN-1

9021

5

3.4 Accessories and replacement partsThe display and adjustment module is used for measured value indi-cation, adjustment and diagnosis. It can be inserted into the sensor and removed at any time.Youcanfindfurtherinformationintheoperatinginstructions"Display and adjustment module".

Screwedflangesareavailableindifferentversionsaccordingtothefollowing standards: DIN 2501, EN 1092-1, BS 10, ASME B 16.5, JIS B 2210-1984, GOST 12821-80.Youcanfindadditionalinformationinthesupplementaryinstructionsmanual "Flanges according to DIN-EN-ASME-JIS".

The electronics module NivoGuide is a replacement part for GWR sensors of the NivoGuide series.Youcanfindfurtherinformationintheoperatinginstructionsmanual"Electronics module NivoGuide".

Display and adjustment module

Flanges

Electronics module

Page 10: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

10

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

4 Mounting58879-EN

-190215

4 Mounting

4.1 General instructionsOndeviceswithathreadedfitting,thehexagonontheprocessfittingmust be tightened with a suitable wrench.See chapter "Dimensions"forwrenchsize.

Warning:The housing or the electrical connection may not be used for screw-ing in! Tightening can cause damage, e. g. to the rotation mechanism of the housing.

Protect your instrument against moisture ingress through the following measures:

• Use a suitable connection cable (see chapter "Connecting to power supply")

• Tighten the cable gland or plug connector• Whenmountinghorizontally,turnthehousingsothatthecable

gland or plug connector point downward• Lead the connection cable downward in front of the cable entry or

plug connector.

This applies mainly to outdoor installations, in areas where high humidity is expected (e.g. through cleaning processes) and on cooled or heated vessels.To maintain the housing protection, make sure that the housing lid is closed during operation and locked, if necessary.Makesurethatthedegreeofcontaminationspecifiedinchapter"Technical data" meets the existing ambient conditions.

Metric threadsIn the case of instrument housings with metric thread, the cable glands are screwed in at the factory. They are sealed with plastic plugs as transport protection.You have to remove these plugs before electrical connection.

NPT threadIn the case of instrument housings with self-sealing NPT threads, it is not possible to have the cable entries screwed in at the factory. The free openings for the cable glands are therefore covered with red dust protection caps as transport protection. The dust protection caps do notprovidesufficientprotectionagainstmoisture.Prior to setup you have to replace these protective caps with ap-proved cable glands or close the openings with suitable blind plugs.

Make sure before mounting that all parts of the instrument exposed to the process are suitable for the existing process conditions.These are mainly:

• Active measuring component• Processfitting• Process seal

Screwing in

Protection against mois-ture

Cable glands

Suitability for the process conditions

Page 11: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

11

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

4 Mounting58

879-

EN-1

9021

5

Process conditions in particular are:

• Process pressure• Process temperature• Chemical properties of the medium• AbrasionandmechanicalinfluencesYoucanfinddetailedinformationontheprocessconditionsinchapter"Technical data" as well as on the type label.

The instrument is suitable for standard and extended ambient condi-tions acc. to IEC/EN 61010-1.

4.2 Mounting instructionsMount NivoGuide 3100 in such a way that the distance to vessel installations or to the vessel wall is at least 300 mm (12 in). In non-metallic vessels, the distance to the vessel wall should be at least 500 mm (19.7 in).During operation, the probe must not touch any installations or the vessel wall. If necessary, fasten the probe end.In vessels with conical bottom it can be advantageous to mount the sensor in the center of the vessel, as measurement is then possible nearly down to the lowest point of the bottom. Keep in mind that measurement all the way down to the tip of the probe may not be pos-sible. The exact value of the min. distance (lower dead band) is stated in chapter "Technical data" of the operating instructions.

Fig. 2: Vessel with conical bottom

Plastic vessel/Glass vesselThe guided microwave principle requires a metallic surface on the processfitting.Therefore,inplasticvessels,etc.,useaninstru-mentversionwithflange(fromDN50)orplaceametalsheet(ø>200mm/8in)beneaththeprocessfittingwhenscrewingitin.Makesurethattheplatehasdirectcontactwiththeprocessfitting.When using the probes without metal vessel wall, e.g. in plastic vessels,themeasuredvaluecanbeinfluencedbystrongelectromag-neticfields(emittedinterferenceaccordingtoEN61326:classA).Use a probe in coax version for applications in liquids.

Suitability for the ambient conditions

Installation position

Type of vessel

Page 12: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

12

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

4 Mounting58879-EN

-190215

1 2

Fig. 3: Mounting in non-metallic vessel1 Flange2 Metal sheet

Concrete vesselWhen mounting in thick concrete ceilings, NivoGuide 3100 should be mountedfrontflushtotheloweredge.Inconcretesilos,thedistanceto the wall should be at least 500 mm (20 in).

ø >160�mm(ø >6.3")

Fig. 4: Mounting in concrete silo

Ifpossible,avoidsockets.Mountthesensorflushwiththevesseltop.If this is not possible, use short sockets with small diameter.

Mounting socket

Page 13: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

13

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

4 Mounting58

879-

EN-1

9021

5

Higher sockets or sockets with a bigger diameter can generally be used. They can, however, increase the upper blocking distance (dead band). Check if this is relevant for your measurement.In such cases, always carry out a false signal suppression after mounting.Youcanfindfurtherinformationunder"Setup procedure".

hd

d hDN25 ... DN150

> DN150 ... DN200≤ 150 mm (5.91")≤ 100 mm (3.94")

Fig. 5: Mounting socket

Whenweldingthesocket,makesurethatthesocketisflushwiththevessel top.

1 2

Fig.6:Socketmustbeinstalledflush1 Unfavourable mounting2 Socketflush-optimummounting

Before beginning the welding work, remove the electronics module from the sensor. By doing this, you avoid damage to the electronics through inductive coupling.

Donotmounttheinstrumentsinorabovethefillingstream.Makesurethatyoudetecttheproductsurface,nottheinflowingproduct.

Welding work

Inflowingmedium

Page 14: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

14

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

4 Mounting58879-EN

-190215

Fig.7:Mountingofthesensorwithinflowingmedium

The reference plane for the measuring range of the sensors is the sealingsurfaceofthethreadorflange.Keep in mind that a min. distance must be maintained below the refer-ence plane and possibly also at the end of the probe - measurement in these areas is not possible (dead band). The length of the cable can be used all the way to the end only when measuring conductive products.Theseblockingdistancesfordifferentmediumsarelistedin chapter "Technical data". Keep in mind for the adjustment that the default setting for the measuring range refers to water.

Theprocessfittingmustbesealedifthereisgaugeorlowpressureinthe vessel. Before use, check if the seal material is resistant against the measured product and the process temperature.Themax.permissiblepressureisspecifiedinchapter"Technical data" or on the type label of the sensor.

If there is a risk of the cable probe touching the vessel wall during operation due to product movements or agitators, etc., the measuring probeshouldbesecurelyfixed.There is an inside thread (M12) in the gravity weight, e.g. for an eye-bolt (optional).Make sure that the probe cable is not completely taut. Avoid tensile loads on the cable.Avoidundefinedvesselconnections,i.e.theconnectionmustbeeithergroundedreliablyorisolatedreliably.Anyundefinedchangeofthis condition can lead to measurement errors.Keep in mind that measurement is not possible below the fastening point.

Measuring range

Pressure

Fasten

Page 15: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

15

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

5 Connecting to power supply58

879-

EN-1

9021

5

5 Connecting to power supply

5.1 Preparing the connectionAlways keep in mind the following safety instructions:

• Carryoutelectricalconnectionbytrained,qualifiedpersonnelauthorised by the plant operator

• If overvoltage surges are expected, overvoltage arresters should be installed

Warning:Connect only in the complete absence of line voltage.

Power supply and current signal are carried on the same two-wire cable.Theoperatingvoltagecandifferdependingontheinstrumentversion.Thedataforpowersupplyarespecifiedinchapter"Technical data".Provide a reliable separation between the supply circuit and the mains circuits according to DIN EN 61140 VDE 0140-1.Power the instrument via an energy-limited circuit acc. to IEC 61010-1, e.g. via Class 2 power supply unit.Keepinmindthefollowingadditionalfactorsthatinfluencetheoperat-ing voltage:

• Lower output voltage of the power supply unit under nominal load (e.g. with a sensor current of 20.5 mA or 22 mA in case of fault)

• Influenceofadditionalinstrumentsinthecircuit(seeloadvaluesinchapter "Technical data")

The instrument is connected with standard two-wire cable without screen. If electromagnetic interference is expected which is above the test values of EN 61326-1 for industrial areas, screened cable should be used.Use cable with round cross section for instruments with housing and cable gland. Use a cable gland suitable for the cable diameter to ensurethesealeffectofthecablegland(IPprotectionrating).We generally recommend the use of shielded cable for HART multidrop mode.

Metric threadsIn the case of instrument housings with metric thread, the cable glands are screwed in at the factory. They are sealed with plastic plugs as transport protection.You have to remove these plugs before electrical connection.

NPT threadIn the case of instrument housings with self-sealing NPT threads, it is not possible to have the cable entries screwed in at the factory. The free openings for the cable glands are therefore covered with red dust protection caps as transport protection.

Safety instructions

Voltage supply

Connection cable

Cable glands

Page 16: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

16

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

5 Connecting to power supply58879-EN

-190215

Prior to setup you have to replace these protective caps with ap-proved cable glands or close the openings with suitable blind plugs.On plastic housings, the NPT cable gland or the Conduit steel tube must be screwed into the threaded insert without grease.Max. torque for all housings, see chapter "Technical data".

If screened cable is required, we recommend connecting the cable screening on both ends to ground potential. In the sensor, the cable screening must be connected directly to the internal ground terminal. The ground terminal on the outside of the housing must be connected to the ground potential (low impedance).In Ex systems, the grounding is carried out according to the installa-tion regulations.

In electroplating plants as well as plants for cathodic corrosion protec-tionitmustbetakenintoaccountthatsignificantpotentialdifferencesexist. This can lead to unacceptably high currents in the cable screen if it is grounded at both ends.

Information:Themetallicpartsoftheinstrument(processfitting,sensor,concen-tric tube, etc.) are connected with the internal and external ground terminal on the housing. This connection exists either directly via the conductive metallic parts or, in case of instruments with external electronics, via the screen of the special connection cable.Youcanfindspecificationsonthepotentialconnectionsinsidetheinstrument in chapter "Technical data".

5.2 ConnectingThe voltage supply and signal output are connected via the spring-loaded terminals in the housing.Connection to the display and adjustment module or to the interface adapter is carried out via contact pins in the housing.

Information:The terminal block is pluggable and can be removed from the electronics. To do this, lift the terminal block with a small screwdriver and pull it out. When reinserting the terminal block, you should hear it snap in.

Proceed as follows:1. Unscrew the housing lid2. If a display and adjustment module is installed, remove it by turn-

ing it slightly to the left3. Loosen compression nut of the cable gland and remove blind

plug4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.

1 cm (0.4 in) of insulation from the ends of the individual wires5. Insert the cable into the sensor through the cable entry

Cable screening and grounding

Connection technology

Connection procedure

Page 17: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

17

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

5 Connecting to power supply58

879-

EN-1

9021

5

1 2

Fig. 8: Connection steps 5 and 61 Single chamber housing2 Double chamber housing

6. Insert the wire ends into the terminals according to the wiring plan

Information:Solidcoresaswellasflexiblecoreswithwireendsleevesareinsert-eddirectlyintotheterminalopenings.Incaseofflexiblecoreswithoutend sleeves, press the terminal from above with a small screwdriver, the terminal opening is then free. When the screwdriver is released, the terminal closes again.Youcanfindfurtherinformationonthemax.wirecross-sectionunder"Technical data - Electromechanical data".

7. Check the hold of the wires in the terminals by lightly pulling on them

8. Connect the screen to the internal ground terminal, connect the external ground terminal to potential equalisation

9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable

10. Reinsert the display and adjustment module, if one was installed11. Screw the housing lid back onTheelectricalconnectionisfinished.

5.3 Wiring plan, single chamber housingThe following illustration applies to the non-Ex as well as to the Ex-ia version.

Page 18: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

18

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

5 Connecting to power supply58879-EN

-190215

51 2+( ) (-) 6 7 8

4...20mA

2

3

41

Fig. 9: Electronics and connection compartment - single chamber housing1 Voltage supply, signal output2 For display and adjustment module or interface adapter3 For external display and adjustment unit4 Ground terminal for connection of the cable screening

5.4 Wiring plan, double chamber housingThe following illustrations apply to the non-Ex as well as to the Ex-ia version.

5 6 7 8

4...20mA

1 2+( ) (-)

2

1 1

Fig. 10: Electronics compartment - double chamber housing1 Internal connection to the connection compartment2 For display and adjustment module or interface adapter

Electronics and connec-tion compartment

Electronics compartment

Page 19: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

19

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

5 Connecting to power supply58

879-

EN-1

9021

5

51 2+( ) (-) 6 7 8

4...20mA Display

2

3

41

Fig. 11: Connection compartment - double chamber housing1 Voltage supply, signal output2 For display and adjustment module or interface adapter3 For external display and adjustment unit4 Ground terminal for connection of the cable screening

5.5 Switch-on phaseAfter connecting the instrument to voltage supply or after a voltage recurrence, the instrument carries out a self-check for approx. 30 s:

• Internal check of the electronics• Indication of the instrument type, hardware and software version,

measurement loop name on the display• Indication of the status message "F 105 Determine measured

value" on the display• The output signal jumps to the set fault current

As soon as a plausible measured value is found, the corresponding current is output to the signal cable. The value corresponds to the actual level as well as the settings already carried out, e.g. factory setting.

Connection compartment

Page 20: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

20

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58879-EN

-190215

6 Set up with the display and adjustment module

6.1 Insert display and adjustment moduleThe display and adjustment module can be inserted into the sensor andremovedagainatanytime.Youcanchooseanyoneoffourdiffer-ent positions - each displaced by 90°. It is not necessary to interrupt the power supply.Proceed as follows:1. Unscrew the housing lid2. Place the display and adjustment module on the electronics in the

desired position and turn it to the right until it snaps in.3. Screw housing lid with inspection window tightly back onDisassembly is carried out in reverse order.The display and adjustment module is powered by the sensor, an ad-ditional connection is not necessary.

Fig. 12: Installing the display and adjustment module in the electronics compart-ment of the single chamber housing

Page 21: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

21

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58

879-

EN-1

9021

5

1 2

Fig. 13: Installing the display and adjustment module in the double chamber housing1 In the electronics compartment2 In the connection compartment

Note:Ifyouintendtoretrofittheinstrumentwithadisplayandadjustmentmodule for continuous measured value indication, a higher lid with an inspection glass is required.

6.2 Adjustment system

1

2

Fig. 14: Display and adjustment elements1 LC display2 Adjustment keys

• [OK] key:Key functions

Page 22: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

22

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58879-EN

-190215

– Move to the menu overview – Confirmselectedmenu – Edit parameter – Save value

• [->] key: – Change measured value presentation – Select list entry – Select editing position

• [+] key: – Change value of the parameter

• [ESC] key: – Interrupt input – Jump to next higher menu

The sensor is operated via the four keys of the display and adjustment module. The individual menu items are shown on the LC display. You canfindthefunctionoftheindividualkeysinthepreviousillustration.When the [+] and [->] keys are pressed quickly, the edited value, or the cursor, changes one value or position at a time. If the key is pressed longer than 1 s, the value or position changes continuously.When the [OK] and [ESC] keys are pressed simultaneously for more than 5 s, the display returns to the main menu. The menu language is then switched over to "English".Approx. 60 minutes after the last pressing of a key, an automatic reset tomeasuredvalueindicationistriggered.Anyvaluesnotconfirmedwith [OK] will not be saved.

After switching on, the NivoGuide 3100 carries out a short self-test where the device software is checked.The output signal transmits a fault signal during the switch-on phase.The following information is displayed on the display and adjustment module during the startup procedure:

• Instrument type• Device name• Software version (SW-Ver)• Hardware version (HW-Ver)

With the [->]keyyoucanmovebetweenthreedifferentindicationmodes.Inthefirstview,theselectedmeasuredvalueisdisplayedinlargedigits.In the second view, the selected measured value and a correspond-ing bar graph presentation are displayed.In the third view, the selected measured value as well as a second selectable value, e.g. the temperature, are displayed.

Adjustment system

Switch-on phase

Measured value indica-tion

Page 23: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

23

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58

879-

EN-1

9021

5

6.3 Parameter adjustment - Quick setupTo quickly and easily adapt the sensor to the application, select the menu item "Quick setup" in the start graphic on the display and adjustment module.

The following steps for the quick setup can be reached also in the "Extended adjustment".

• Instrument address• Measurement loop name• Medium type (optional)• Application• Max. adjustment• Min. adjustment• False signal suppression

Youcanfindthedescriptionoftheindividualmenuitemsinthefollow-ing chapter "Parameter adjustment - Extended adjustment".

6.4 Parameter adjustment - Extended adjustmentFor technically demanding measuring points, you can carry out extended settings in "Extended adjustment".

Themainmenuisdividedintofivesectionswiththefollowingfunc-tions:

Setup: Settings, e.g. measurement loop name, medium, vessel, adjustment, signal output, device unit, false signal suppression, linearizationcurveDisplay: Settings, e.g., for language, measured value display, lightingDiagnosis: Information, e.g. on instrument status, pointer, measure-ment reliability, simulation, echo curveAdditional adjustments: Reset, date/time, reset, copy function

Quick setup

Main menu

Page 24: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

24

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58879-EN

-190215

Info: Instrument name, hardware and software version, date of manu-facture, instrument features

Note:For optimum adjustment of the measuring point, the individual sub-menu items in the main menu item "Setup" should be selected one after the other and provided with the correct parameters. If possible, go through the items in the given sequence.The procedure is described below.

The following submenu points are available:

The submenu points are described below.

Here you can assign a suitable measurement loop name. Push the "OK" key to start the editing. With the "+" key you change the sign and with the "->" key you jump to the next position.You can enter names with max. 19 characters. The character set comprises:

• Capital letters from A … Z• Numbers from 0 … 9• Special characters + - / _ blanks

In this menu item you select the distance unit and the temperature unit.

For the distance units you can choose between m, mm and ft and for the temperature units °C, °F and K.

In this menu item you can enter the probe length or have the length determined automatically by the sensor system.When choosing "Yes", then the probe length will be determined automatically. When choosing "No", you can enter the probe length manually.

Setup - Measurement loop name

Setup - Units

Setup - Probe length

Page 25: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

25

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58

879-

EN-1

9021

5

In this menu item you can select which type of medium you want to measure. You can choose between liquid or bulk solid.

In this menu item you can select the application. You can choose between metallic or non-metallic vessels.

Note:Theselectionoftheapplicationhasaconsiderableinfluenceonallother menu items. Keep in mind that as you continue with the param-eter adjustment, individual menu items are only optionally available.

You have the option of choosing the demonstration mode. This mode is only suitable for test and demonstration purposes. In this mode, the sensor ignores the parameters of the application and reacts immedi-ately to any change.

Inthismenuitem,youcandefinethetypeofmedium(product).This menu item is only available if you have selected level measure-ment under the menu item "Application".

You can choose between the following medium types:

Dielectric con-stant

Medium type Examples

> 3 Cereals,flour Allkindofcereals,wheatflour

1.5 … 3 Granules, cement Lime, gypsum, cement

< 1.5 Dusts, wood chips Wood chips, sawdust

In this menu item, you can enter the max. adjustment for the level.

Adjust the requested percentage value with [+] and store with [OK].

Setup - Application - Type of medium

Setup - Application

Setup - Medium, dielec-tric constant

Setup - Max. adjustment Level

Page 26: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

26

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58879-EN

-190215

Enter the appropriate distance value in m (corresponding to the percentage value) for the full vessel. The distance refers to the sensor referenceplane(sealsurfaceoftheprocessfitting).Keepinmindthatthe max. level must lie below the dead band.

In this menu item, you can enter the min. adjustment for the level.

Adjust the requested percentage value with [+] and store with [OK].

Enter the suitable distance value in m for the empty vessel (e.g. distancefromtheflangetotheprobeend)correspondingtotheper-centage value. The distance refers tot he sensor reference plane (seal surfaceoftheprocessfitting).

Todampprocess-dependentmeasuredvaluefluctuations,setanintegration time of 0 … 999 s in this menu item.

The default setting is a damping of 0 s.

A linearisation is necessary for all vessels in which the vessel volume doesnotincreaselinearlywiththelevel-e.g.ahorizontalcylindri-cal or spherical tank, when the indication or output of the volume is required. Corresponding linearisation curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume.The linearisation applies to the measured value indication and the current output. By activating the appropriate curve, the volume per-centage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set in the menu item "Display".

Setup - Min. adjustment Level

Setup - Damping

Setup - Linearisation

Page 27: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

27

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58

879-

EN-1

9021

5

Warning:If a linearisation curve is selected, the measuring signal is no longer necessarilylineartothefillingheight.Thismustbeconsideredbytheuser especially when setting the switching point on the limit signal transmitter.In the following, you have to enter the values for your vessel, for example the vessel height and the socket correction.

For non-linear vessel forms, enter the vessel height and the socket correction.For the vessel height, you have to enter the total height of the vessel.For the socket correction you have to enter the height of the socket above the upper edge of the vessel. If the socket is lower than the up-per edge of the vessel, this value can also be negative.

+ h

D

- h

Fig. 15: Vessel height and socket correction valueD Vessel height+h Positive socket correction value-h Negative socket correction value

In the menu item "Current output mode" you determine the output characteristics and reaction of the current output in case of fault.

Setup - Current output, mode

Page 28: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

28

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58879-EN

-190215

The default setting is output characteristics 4 … 20 mA, fault mode < 3.6 mA.

In the menu item "Current output Min./Max.", you determine the reac-tion of the current output during operation.

The default setting is min. current 3.8 mA and max. current 20.5 mA.

Thefollowingcircumstancescauseinterferingreflectionsandcaninfluencethemeasurement:

• High mounting sockets• Vessel internals such as struts• Deflectors,etc.Note:A false signal suppression is only recommended with liquid applica-tions.

A false signal suppression detects, marks and saves these false signals to ensure that they are ignored in the level measurement.This should be done with the lowest possible level so that all potential interferingreflectionscanbedetected.Proceed as follows:

Enter the actual distance from the sensor to the product surface.

All interfering signals in this section are detected by the sensor and stored.Keep in mind that with covered probe only false signals in the uncov-ered area of the probe are detected.

Note:Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as a false signal. The level would then no longer be detectable in this area.

If a false signal suppression has already been created in the sensor, the following menu window appears when selecting "False signal suppression":

Setup - Current output Min./Max.

Setup - False signal sup-pression

Page 29: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

29

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58

879-

EN-1

9021

5

The instrument carries out an automatic false signal suppression as soon as the probe is uncovered. The false signal suppression is always updated.The menu item "Delete" is used to completely delete an already cre-ated false signal suppression. This is useful if the saved false signal suppression no longer matches the metrological conditions in the vessel.

In the menu item "Lock/unlock adjustment", you can protect the sen-sorparametersagainstunauthorizedorinadvertentmodification.ThePIN is activated/deactivated permanently.With active PIN, only the following adjustment functions are possible without entering a PIN:

• Select menu items and show data• Read data from the sensor into the display and adjustment module

Caution:In delivery status, the PIN is 0000.CallourservicedepartmentifyouhavemodifiedandforgottenthePIN.

In the main menu point "Display", the individual submenu points should be selected one after the other and provided with the correct parameters to ensure the optimum adjustment of the display options. The procedure is described in the following.The following submenu points are available:

The submenu points are described below.

This menu item enables the setting of the requested national lan-guage.

In delivery status, the sensor is set to English.

Lock/unlock setup - Ad-justment

Display

Display - Menu language

Page 30: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

30

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58879-EN

-190215

Inthismenuitem,youdefinetheindicationofthemeasuredvalueonthedisplay.Youcandisplaytwodifferentmeasuredvalues.Inthismenuitem,youdefinemeasuredvalue1.

The default setting for the displayed value 1 is "Filling height Level".

Inthismenuitem,youdefinetheindicationofthemeasuredvalueonthedisplay.Youcandisplaytwodifferentmeasuredvalues.Inthismenuitem,youdefinemeasuredvalue2.

The default setting for the displayed value 2 is the electronics tem-perature.

Inthismenuitem,youdefinethedisplayformatofthemeasuredvalueonthedisplay.Youcandefinedifferentdisplayformatsforthetwo measured values.Youcanthusdefinethenumberofdecimalpositionsthemeasuredvalue is displayed with.

The default setting for the display format is "Automatic".

Theintegratedbackgroundlightingcanbeswitchedoffviatheadjustment menu. The function depends on the strength of the supply voltage, see "Technical data".To maintain the function of the device, the lighting is temporarily switchedoffifthepowersupplyisinsufficient.

In delivery status, the lighting is switched on.

In this menu item, the device status is displayed.When the instrument displays a failure message, you can here get detailed information on the failure reason.

Display - Displayed value 1

Display - Displayed value 2

Display - Display format

Display - Backlight

Diagnostics - Device status

Page 31: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

31

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58

879-

EN-1

9021

5

The respective min. and max. measured value is saved in the sen-sor. The two values are displayed in the menu item "Peak values, distance".

In another window you can reset the peak value.

The respective min. and max. measured values are saved in the sensor. The two values are displayed in the menu item "Peak values, measurement reliability".Themeasurementcanbeinfluencedbytheprocessconditions.Inthis menu item, the measurement reliability of the level measure-ment is displayed in mV. The higher the value, the more reliable the measurement.

In another window you can reset the peak value.

The respective min. and max. measured values are saved in the sensor. The values are displayed in the menu item "Peak values Ad-ditional".This menu item displays the peak values of the electronics tempera-ture as well as the dielectric constant.

In another window you can carry out a reset of the two peak values separately.

Information:Ifoneofthedisplayvaluesflashes,thereisactuallynovalidvalueavailable.

Diagnostics - Peak val-ues, Distance

Diagnostics - Peak values measurement reliability

Diagnostics - Peak val-ues, Additional

Page 32: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

32

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58879-EN

-190215

The menu item "Echo curve" shows the signal strength of the echoes over the measuring range in V. The signal strength enables an evalua-tion of the quality of the measurement.

Withthefollowingfunctionsyoucanzoompartsectionsoftheechocurve.

• "X-Zoom": Zoom function for the meas. distance• "Y-Zoom":1,2,5and10xsignalmagnificationin"V"• "Unzoom":Resetthepresentationtothenominalmeasuringrange

withoutmagnification

In this menu item you can simulate measured values via the current output. This allows the signal path to be tested, e.g. through down-stream indicating instruments or the input card of the control system.

Select the requested simulation variable and set the requested value.

Caution:During simulation, the simulated value is output as 4 … 20 mA current value and digital HART signal.

Push the [ESC] key to deactivate the simulation.

Information:The simulation is terminated automatically 60 minutes after the activa-tion of the simulation.

With the menu item "Setup" the echo curve it is possible to save at the time of setup. This is generally recommended; for using the Asset Management functions it is necessary. If possible, the curve should be saved with a low level in the vessel.This allows you to detect signal changes over the operating time.

Diagnostics - Echo curve

Diagnosis - Simulation

Diagnostics - Echo curve memory

Page 33: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

33

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58

879-

EN-1

9021

5

The function "Echo curve memory" enables storing echo curves of the measurement.Under the sub-menu item "Echo curve memory" you can store the current echo curve.

In this menu item, the internal clock of the sensor is set.

After a reset, certain parameter adjustments made by the user are reset.

Note:After this menu window, the reset process is carried out. No further safety inquiry follows.

The following reset functions are available:Delivery status: Restores the parameter settings at the time of ship-mentfromthefactory,incl.order-specificsettings.Anystoredfalsesignal suppression or user-programmed linearisation curve, as well as the measured value memory, are deleted.Basic settings: Restores the parameter settings, incl. special param-eters, to the default values of the respective instrument. Any stored false signal suppression or user-programmed linearisation curve, as well as the measured value memory, are deleted.The following table shows the default values of the instrument. De-pending on the instrument version or application, all menu items may notbeavailableorsomemaybedifferentlyassigned:

Additional settings - Date/Time

Additional settings - Reset

Page 34: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

34

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58879-EN

-190215

Menu - Setup

Menu Menu item Default value

Setup Lock adjustment Released

Measurement loop name Sensor

Units Distanceunit:order-specificTemperatureunit:order-specific

Probe length Länge der Messsonde factory set-ting

Type of medium Bulk solid

Application Level in the metallic vessel

Medium, dielectric constant Cereals,flour,sand/>3

Superimposed gas phase Yes

Setup Max. adjustment - Level 100 %

Max. adjustment - Level Distance: 0.000 m(d) - note block-ing distances

Min. adjustment - Level 0 %

Min. adjustment - Level Distance: Probe length - take dead band into account

Setup Integration time - Level 0.0 s

Linearisation type Linear

Linearisation - Socket correction 0 mm

Linearisation - Vessel height Probe length

Setup Scaling variable - Level Volume in l

Scaling unit - Level Litres

Scaling format - Level Without decimal positions

Scaling level - 100 % corresponds to 100

Scaling level - 0 % corresponds to 0

Setup Current output, output variableFirst HART variable (PV)

Lin. percent - Level

Current output - Output characteristics 0 … 100 % correspond to 4 … 20 mA

Current output - Reaction in case of fault ≤3.6mA

Current output - Min. 3.8 mA

Current output - Max. 20.5 mA

Current output 2 - Output variableSecond HART variable (SV)

Distance - Level

Current output 2 - Output characteristics 0 … 100 % correspond to 4 … 20 mA

Current output 2 - Reaction in case of fault ≤3.6mA

Current output - Min. 3.8 mA

Current output - Max. 20.5 mA

Page 35: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

35

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58

879-

EN-1

9021

5

Menu Menu item Default value

Setup Third HART variable (TV) Measurement reliability, level

Fourth HART variable (QV) Electronics temperature

Menu - Display

Menu Menu item Default value

Display Language Selected language

Displayed value 1 Filling height Level

Displayed value 2 Electronics temperature

Display format 1 Automatically

Display format 2 Automatically

Backlight Switched on

Menu - Additional adjustments

Menu Menu item Default value

Additional adjustments PIN 0000

Date Actual date

Time Actual time

Time - Format 24 hours

Probe type Device-specific

The instrument settings are copied with this function. The following functions are available:

• Read from sensor: Read data from sensor and save in the display and adjustment module

• Write to sensor: Save data from the display and adjustment mod-ule back into the sensor

The following data or settings for adjustment of the display and ad-justment module are saved:

• All data of the menu "Setup" and "Display"• In the menu "Additional adjustments" the items "Reset, Date/Time"• Special parameters

The copied data are permanently saved in an EEPROM memory in the display and adjustment module and remain there even in case of power failure. From there, they can be written into one or more sen-sors or kept as backup for a possible electronics exchange.

Additional settings - Copy instrument settings

Page 36: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

36

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58879-EN

-190215

Note:Before the data are stored in the sensor, a check is carried out to determineifthedatafitthesensor.Ifthedatadonotfit,afaultsignalis triggered or the function is blocked. When data are being written into the sensor, the display shows which instrument type the data originate from and which TAG-no. this sensor had.

Tip:We recommend to save the instrument adjustments. In case of an electronics exchange the saved parameter adjustment data relieve this process.

Since scaling is very extensive, scaling of the level value was divided into two menu items.

In menu item "Scaling variable"youdefinethescalingvariableandthe scaling unit for the level value on the display, e.g. volume in l.

In menu item "Scaling format"youdefinethescalingformatonthedisplay and the scaling of the measured level value for 0 % and 100 %.

Since scaling is very extensive, scaling of the level value was divided into two menu items.

In menu item "Current output, variable" you specify which measured variable the current output refers to.

Additional settings - Scal-ing level

Additional settings - Scaling level - Scaling variable

Additional settings - Scal-ing level - Scaling format

Additional settings - Cur-rent output

Additional settings - Current output - Current output, meas. variable

Page 37: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

37

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58

879-

EN-1

9021

5

In menu item "Current output, adjustment" you can assign a respec-tive measured value to the current output.

Inthismenuitemyoucanselectthetypeandsizeofyourprobefroma list of all possible probes. This is necessary to adapt the electronics optimally to the probe.

ThesensorofferstheHARTmodes"Analogue current output" and "Fix current (4 mA)". In this menu item you determine the HART mode and enter the address with Multidrop mode.In the mode "Fixed current output" up to 63 sensors can be operated on one two-wire cable (Multidrop operation). An address between 0 and 63 must be assigned to each sensor.If you select the function "Analogue current output" and also enter an address number, you can output a 4 … 20 mA signal in Multidrop mode.In the mode "Fixed current (4 mA)"afixed4mAsignalisoutputinde-pendently of the actual level.

The default setting is "Analogue current output" and the address 00.

In this menu item you gain access to the protected area where you can enter special parameters. In exceptional cases, individual parameterscanbemodifiedinordertoadaptthesensortospecialrequirements.Change the settings of the special parameters only after having con-tactedourservicestaff.

Additional settings - Current output - Current output, adjustment

Additional settings - Probe type

Additional settings - HART mode

Additional settings - Spe-cial parameters

Page 38: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

38

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

6 Set up with the display and adjustment module58879-EN

-190215

In this menu, you read out the instrument name and the instrument serial number.

In this menu item, the hardware and software version of the sensor is displayed.

In this menu item, the date of factory calibration of the sensor as well as the date of the last change of sensor parameters are displayed via the display and adjustment module.

In this menu item, the features of the sensor such as approval, pro-cessfitting,seal,measuringrange,electronics,housingandothersare displayed.

Example for displayed sensor features.

6.5 Saving the parameterisation dataWe recommended writing down the adjustment data, e.g. in this op-erating instructions manual, and archiving them afterwards. They are thus available for multiple use or service purposes.

If the instrument is equipped with a display and adjustment module, the parameter adjustment data can be saved therein. The procedure is described in menu item "Copy device settings".

Info - Instrument name

Info - Instrument version

Info - Factory calibration date

Info - Sensor character-istics

On paper

In the display and adjust-ment module

Page 39: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

39

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

7 Diagnostics and servicing58

879-

EN-1

9021

5

7 Diagnostics and servicing

7.1 MaintenanceIf the device is used properly, no special maintenance is required in normal operation.

The cleaning helps that the type label and markings on the instrument are visible.Take note of the following:

• Use only cleaning agents which do not corrode the housings, type label and seals

• Use only cleaning methods corresponding to the housing protec-tion rating

7.2 Status messagesThe instrument features self-monitoring and diagnostics according to NE 107 and VDI/VDE 2650. In addition to the status messages in the following tables there are more detailed error messages available under the menu item "Diagnostics" via the display and adjustment module.

The status messages are divided into the following categories:

• Failure• Function check• Outofspecification• Maintenance requirement

and explained by pictographs:

41 2 3Fig. 16: Pictographs of the status messages1 Failure - red2 Outofspecification-yellow3 Function check - orange4 Maintenance - blue

Failure: Due to a malfunction in the instrument, a fault message is output.This status message is always active. It cannot be deactivated by the user.Function check: The instrument is being worked on, the measured value is temporarily invalid (for example during simulation).This status message is inactive by default.Outofspecification: The measured value is unreliable because an instrumentspecificationwasexceeded(e.g.electronicstemperature).

Maintenance

Cleaning

Status messages

Page 40: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

40

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

7 Diagnostics and servicing58879-EN

-190215

This status message is inactive by default.Maintenance:Duetoexternalinfluences,theinstrumentfunctionislimited.Themeasurementisaffected,butthemeasuredvalueisstill valid. Plan in maintenance for the instrument because a failure is expected in the near future (e.g. due to buildup).This status message is inactive by default.

CodeText mes-sage

Cause Rectification DevSpec State in CMD 48

F013no measured value avail-able

• Sensor does not detect an echo during operation

• Process component or probe contaminated or defective

• Check for correct mounting and/or parameter settings

• Clean or exchange process component or probe

Bit 0 of Byte 0 … 5

F017Adjustment span too small

• Adjustmentnotwithinspecifi-cation

• Change adjustment accord-ingtothelimitvalues(differ-ence between min. and max. ≥10mm)

Bit 1 of Byte 0 … 5

F025Error in the linearizationtable

• Index markers are not con-tinuously rising, for example illogical value pairs

• Check values of the lineari-zationtable

• Delete/create a new lineari-zationtable

Bit 2 of Byte 0 … 5

F036No operable software

• Failed or interrupted software update

• Repeat software update• Check electronics version• Exchanging the electronics• Send instrument for repair

Bit 3 of Byte 0 … 5

F040Error in the electronics

• Hardware defect • Exchanging the electronics• Send instrument for repair

Bit 4 of Byte 0 … 5

F041Probe loss

• Probe mechanically defec-tive

• Check probe and exchange, if necessary

Bit 13 of Byte 0 … 5

F080General soft-ware error

• General software error • Disconnect operating voltage briefly

Bit 5 of Byte 0 … 5

F105Measured value is deter-mined

• The instrument is still in the start phase, the measured value could not yet be determined

• Wait for the end of the switch-on phase

• Duration depending on the version and parameter adjustment max. 5 min.

Bit 6 of Byte 0 … 5

F260Error in the calibration

• Error in the calibration car-ried out in the factory

• Error in the EEPROM

• Exchanging the electronics• Send instrument for repair

Bit 8 of Byte 0 … 5

F261Error in the instrument settings

• Error during setup• Error when carrying out a

reset• False signal suppression

faulty

• Carry out a reset• Repeat setup

Bit 9 of Byte 0 … 5

Failure

Page 41: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

41

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

7 Diagnostics and servicing58

879-

EN-1

9021

5

CodeText mes-sage

Cause Rectification DevSpec State in CMD 48

F264Installation/Setup error

• Error during setup • Check for correct mounting and/or parameter settings

• Check probe length

Bit 10 of Byte 0 … 5

F265Measurement function dis-turbed

• Sensor no longer carries out a measurement

• Carry out a reset• Disconnect operating voltage briefly

Bit 11 of Byte 0 … 5

F267No executable sensor soft-ware

• Sensor cannot start • Exchanging the electronics• Send instrument for repair

No communication possible

Tab. 5: Error codes and text messages, information on causes as well as corrective measures

CodeText mes-sage

Cause Rectification DevSpecState in CMD 48

C700Simulation ac-tive

• A simulation is active • Finish simulation• Wait for the automatic end

after 60 mins.

"Simulation Active" in "Stand-ardizedStatus0"

Tab. 6: Error codes and text messages, information on causes as well as corrective measures

CodeText message

Cause Rectification DevSpecState in CMD 48

S600Impermissible electronics tem-perature

• Temperature of the processing electronicsinthenon-specifiedsection

• Check ambient temperature• Insulate electronics• Use instrument with higher tem-

perature range

Bit 8 of Byte 14 … 24

S601Overfilling

• Level echo in the close range not available

• Reduce level• 100 % adjustment: Increase value• Check mounting socket• Remove possible interfering

signals in the close range• Use coaxial probe

Bit 9 of Byte 14 … 24

S602Level within the search range, compensation echo

• Compensation echo superim-posed by medium

• 100 % adjustment: Increase value Bit 10 of Byte 14 … 24

S603Impermissible operating voltage

• Operatingvoltagebelowspecifiedrange

• Check electrical connection• If necessary, increase operating

voltage

Bit 11 of Byte 14 … 24

Tab. 7: Error codes and text messages, information on causes as well as corrective measures

Function check

Outofspecification

Page 42: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

42

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

7 Diagnostics and servicing58879-EN

-190215

CodeText message

Cause Rectification DevSpecState in CMD 48

M500Error in the deliv-ery status

• The data could not be restored during the reset to delivery status

• Repeat reset• LoadXMLfilewithsensordata

into the sensor

Bit 0 of Byte 14 … 24

M501Error in the non-active line-arisation table

• Index markers are not continu-ously rising, for example illogical value pairs

• Check linearisation table• Delete table/Create new

Bit 1 of Byte 14 … 24

M504Error at a device interface

• Hardware defect • Exchanging the electronics• Send instrument for repair

Bit 4 of Byte 14 … 24

M505no measured val-ue available

• Sensor does not detect an echo during operation

• Check and correct mounting and/or parameter adjustment

Bit 5 of Byte 14 … 24

• Process component or probe contaminated or defective

• Clean or exchange process com-ponent or probe

M506Installation/Set-up error

• Error during setup • Check and correct mounting and/or parameter adjustment

• Check probe length

Bit 6 of Byte 14 … 24

M507Error in the in-strument settings

• Error during setup• Error when carrying out a reset• False signal suppression faulty

• Carry out reset and repeat setup Bit 7 of Byte 14 … 24

Tab. 8: Error codes and text messages, information on causes as well as corrective measures

7.3 Rectify faultsThe operator of the system is responsible for taking suitable meas-ures to rectify faults.

Thefirstmeasuresare:

• Evaluation of fault messages via the adjustment device• Checking the output signal• Treatment of measurement errors

Connect a multimeter in the suitable measuring range according to the wiring plan. The following table describes possible errors in the current signal and helps to eliminate them:

Error Cause Rectification

4 … 20 mA signal not sta-ble

• Fluctuations of the measured variable • Set damping via the display and adjustment module depending on the instrument

Maintenance

Reaction when malfunc-tion occurs

Procedure for fault recti-fication

Check the 4 … 20 mA signal

Page 43: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

43

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

7 Diagnostics and servicing58

879-

EN-1

9021

5

Error Cause Rectification

4 … 20 mA signal missing • Electrical connection faulty • Check connection according to chapter "Connection steps" and if necessary, correct according to chapter "Wiring plan"

• Voltage supply missing • Check cables for breaks; repair if necessary

• Operating voltage too low or load resistance too high

• Check, adapt if necessary

Current signal greater than 22 mA or less than 3.6 mA

• Electronics module in the sensor defective

• Exchange the instrument or send it in for repair

The below tables show typical examples for application-relevant measurement errors. There are two measurement errors:

• Constant level• Filling• Emptying

The images in column "Error pattern" show the real level as a broken line and the level displayed by the sensor as a continuous line.

12

Leve

l

time0

Fig. 17: The broken line 1 shows the real level, the continuous line 2 shows the level displayed by the sensor

Note:• Wherever the sensor displays a constant value, the reason could

also be the fault setting of the current output to "Hold value"• If the level indication is too low, the reason could be a line resist-

ance that is too high

Measurement error with constant level

Fault description Cause Rectification

1. Measured value shows a too low or too high level

Leve

l

time0

• Min./max. adjustment not correct • Adapt min./max. adjustment

• Incorrect linearisation curve • Adapt linearisation curve

• Running time error (small measure-ment error close to 100 %/serious error close to 0 %)

• Repeat setup

Treatment of measure-ment errors

Page 44: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

44

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

7 Diagnostics and servicing58879-EN

-190215

Fault description Cause Rectification

2. Measured value jumps towards 100 %

Leve

l

time0

• Due to the process, the amplitude of the product echo decreases

• A false signal suppression was not carried out

• Carry out a false signal suppression

• Amplitude or position of a false signal has changed (e.g. buildup); false sig-nal suppression no longer matches

• Determine the reason for the changed false signals, carry out false signal suppression, e.g. with buildup

Measurementerrorduringfilling

Fault description Cause Rectification

3. Measured value remains in the area of the bottom duringfilling

Leve

l

time0

• Echo from the probe end larger than the product echo, for example, with productswithεr < 2.5 oil-based, solvents, etc.

• Check parameter "Medium" and "Ves-sel height", adapt if necessary

4. Measured value remains momentarily unchanged duringfillingandthenjumpsto the correct level

Leve

l

time0

• Turbulence on the product surface, quickfilling

• Check parameters, change if neces-sary, e.g. in dosing vessel, reactor

5. Measured value jumps sporadically to 100 % dur-ingfilling

Level

time0

• Changing condensation or contamina-tion on the probe

• Carry out a false signal suppression

6. Measured value jumps to ≥100%or0mdistance

Leve

l

time0

• Level echo is no longer detected in the close range due to false signals in the close range. The sensor goes intooverfillprotectionmode.Themax.level (0 m distance) as well as the statusmessage"Overfillprotection"are output.

• Eliminate false signals in the close range

• Check installation conditions• Ifpossible,switchoffthefunction"Overfillprotection"

Page 45: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

45

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

7 Diagnostics and servicing58

879-

EN-1

9021

5

Measurement error during emptying

Fault description Cause Rectification

7. Measured value remains unchanged in the close range during emptying

Leve

l

time0

• False signal larger than the level echo• Level echo too small

• Eliminate false signals in the close range

• Remove contamination on the probe. After having removed the source of the false signals, the false signal suppres-sion must be deleted.

• Carry out a new false signal suppres-sion

8. Measured value remains reproducible in one position during emptying

Leve

l

time0

• Stored false signals in this position are larger than the level echo

• Delete false signal suppression• Carry out a new false signal suppres-

sion

Depending on the reason for the fault and the measures taken, the steps described in chapter "Setup" must be carried out again or must be checked for plausibility and completeness.

7.4 Exchanging the electronics moduleIf the electronics module is defective, it can be replaced by the user.In Ex applications, only instruments and electronics modules with ap-propriate Ex approval may be used.

If there is no electronics module available on site, the electronics module can be ordered through the agency serving you. The electron-icsmodulesareadaptedtotherespectivesensoranddifferinsignaloutput or voltage supply.The new electronics module must be loaded with the default settings of the sensor. These are the options:

• In the factory• Or on site by the user

In both cases, the serial number of the sensor is needed. The serial numbers are stated on the type label of the instrument, on the inside of the housing as well as on the delivery note.Whenloadingonsite,theorderdatamustfirstbedownloadedfromthe Internet (see operating instructions "Electronics module").

Caution:Allapplication-specificsettingsmustbeenteredagain.That'swhyyouhave to carry out a fresh setup after exchanging the electronics.Ifyousavedtheparametersettingsduringthefirstsetupofthesen-sor, you can transfer them to the replacement electronics module. A fresh setup is then not necessary.

Reaction after fault recti-fication

Page 46: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

46

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

7 Diagnostics and servicing58879-EN

-190215

7.5 Exchange or shorten cableThe cable (meas. part) of the probe can be exchanged, if necessary. To loosen the meas. cable you need a fork spanner with spanner width 13.1. Loosenthemeasuringcablebyapplyingaforkspannertotheflat

surfaces (SW 13), provide counterforce with another fork spanner (SW 13)

2. Screw out the loosened measuring cable by hand.3. Place the enclosed new double washer onto the thread.

Caution:Make sure that the two components of the double washer remain together.

4. Screw the new measuring cable carefully by hand onto the thread ontheprocessfitting.

5. Exert counterforce with the second fork spanner and tighten themeasuringcableontheflatsurfaceswithatorqueof20Nm(15 lbf ft).

Fig. 26: Exchanging the measuring cable

Information:Pleasemaintainthespecifiedtorquesothatthemax.tensilestrengthof the connection remains.

6. Enter new probe length and if necessary the new probe type and then carry out a fresh adjustment (see "Setup procedure, Carry-ing out min. adjustment - Carrying out max. adjustment").

The measuring cable of the probe can be shortened individually.1. Mark the requested length with mounted measuring cable.2. Loosen the three pins on the gravity weight

Cable ø 6: hexagon 43. Remove the pins4. Pull the cable out of the gravity weight

Exchanging the cable

Shorten cable

Page 47: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

47

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

7 Diagnostics and servicing58

879-

EN-1

9021

5

5. Shortenthecablewithacut-offwheelormetalsawatthemark-ing.Takenoteofthespecificationsinthefollowingillustrationwhen shortening the cable.

6. Shift the cable into the gravity weight (according to the drawing)Plastic coated cable: remove coating according drawing to 70 mm (2.76 in).

7. Fasten the cable with three pins, torque 20 Nm (14.75 lbf in)8. Enter new probe length and then carry out a fresh adjustment

(see "Setup procedure, Carrying out min. adjustment - Carrying out max. adjustment").

31

2 2

A B

45 m

m

(1.7

7")

150

mm

(5

.91"

)

70 m

m

(2.7

6")

150

mm

(5

.91"

)

Fig. 27: Shortening the cable probe - Cable ø 6 mm1 Threaded pins2 Thread M12 for eye-bolt

7.6 How to proceed if a repair is necessaryIf it is necessary to repair the instrument, please contact the agency serving you.

Page 48: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

48

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

8 Dismount58879-EN

-190215

8 Dismount

8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel or pipeline, high temperatures, cor-rosive or toxic products etc.

Take note of chapters "Mounting" and "Connecting to voltage supply" and carry out the listed steps in reverse order.

8.2 DisposalThe instrument consists of materials which can be recycled by spe-cialised recycling companies. We use recyclable materials and have designed the electronics to be easily separable.

WEEE directiveThe instrument does not fall in the scope of the EU WEEE directive. Article 2 of this Directive exempts electrical and electronic equipment from this requirement if it is part of another instrument that does not fall in the scope of the Directive. These include stationary industrial plants.Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points.If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal.

Page 49: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

49

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58

879-

EN-1

9021

5

9 Supplement

9.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts

Ʋ Processfitting 316L and PPS GF 40 Ʋ Process seal on the instrument side (cable/rod leadthrough)

FKM(SHSFPM70C3GLT),FFKM(Kalrez6375),EPDM (A+P 70.10-02)

Ʋ Process seal On site (instruments with thread: Klingersil C-4400 is enclosed)

Ʋ Inner conductor (up to the separation cable/rod)

316L

Ʋ Rod: ø 16 mm (0.63 in) 316L Ʋ Cable: ø 4 mm (0.157 in) 316 (1.4401) Ʋ Cable: ø 6 mm (0.236 in), PA coated Steel(galvanized),PAcoated Ʋ Cable: ø 6 mm (0.236 in) 316 (1.4401) Ʋ Cable: ø 11 mm (0.433 in), PA coated Steel(galvanized),PAcoated Ʋ Gravity weight (optionally available) 316L

Materials, non-wetted parts Ʋ Aluminium die-cast housing Aluminium die-casting AlSi10Mg, powder-coated (Basis:

Polyester) Ʋ Stainless steel housing (electropol-ished)

316L

Ʋ Second Line of Defense (optional)1) Borosilicate glass GPC 540 Ʋ Seal between housing and housing lid Silicone SI 850 R Ʋ Inspection window in housing cover (optional)

Polycarbonate (with Ex d version: glass)

Ʋ Ground terminal 316L Ʋ Cable gland PA, stainless steel, brass Ʋ Sealing, cable gland NBR Ʋ Blind plug, cable gland PA

Second Line of Defense (optional)The Second Line of Defense (SLOD) is a second level of the process separation in the form of a gas-tight feedthrough in the lower part of the housing, preventing product from penetrating into the housing.

Ʋ Supporting material 316L Ʋ Glass potting Borosilicate glass GPC 540 Ʋ Contacts Alloy C22 (2.4602) Ʋ Helium leak rate < 10-6 mbar l/s Ʋ Pressure resistance See process pressure of the sensor

1) Only with Ex-d version.

Page 50: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

50

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58879-EN

-190215

Conductive connection Betweengroundterminal,processfittingandprobeProcessfittings

Ʋ Pipe thread, cylindrical (ISO 228 T1) G¾, G1, G1½ (DIN 3852-A) Ʋ Pipe thread, conical (ASME B1.20.1) ¾ NPT, 1 NPT, 1½ NPT Ʋ Flanges DIN from DN 25, ASME from 1"

Weight Ʋ Instrument weight (depending on processfitting)

approx. 0.8 … 8 kg (0.176 … 17.64 lbs)

Ʋ Rod: ø 16 mm (0.63 in) approx.1580g/m(17oz/ft) Ʋ Cable: ø 4 mm (0.157 in) approx.78g/m(0.84oz/ft) Ʋ Cable: ø 6 mm (0.236 in), PA coated approx.180g/m(1.9oz/ft) Ʋ Cable: ø 6 mm (0.236 in) approx.80g/m(0.86oz/ft) Ʋ Cable: ø 11 mm (0.433 in), PA coated approx.320g/m(3.44oz/ft) Ʋ Gravity weight for cable ø 4 mm (0.157 in) and ø 6 mm (0.236 in), PA coated

325g(11.46oz)

Ʋ Gravity weight for cable ø 6 mm (0.236 in) and ø 11 mm (0.433 in), PA coated

780g(27.51oz)

Probe length L (from seal surface) Ʋ Rod: ø 16 mm (0.63 in) up to 6 m (19.69 ft) Ʋ Trimming accuracy (rod) ±(1 mm + 0.05 % of the rod length) Ʋ Cable: ø 4 mm (0.157 in) up to 75 m (246.1 ft) Ʋ Cable: ø 6 mm (0.236 in), PA coated up to 65 m (213.3 ft) Ʋ Cable: ø 6 mm (0.236 in) up to 75 m (246.1 ft) Ʋ Cable: ø 11 mm (0.433 in), PA coated up to 65 m (213.3 ft) Ʋ Trimming accuracy - cable ±(2 mm + 0.05 % of the cable length)

Lateral load with rod: ø 16 mm (0.63 in) 30 Nm (22.13 lbf ft)Max. tensile load

Ʋ Cable: ø 4 mm (0.157 in) 12 KN (2698 lbf) Ʋ Cable: ø 6 mm (0.236 in), PA coated 8 KN (1798 lbf) Ʋ Cable: ø 6 mm (0.236 in) 30 KN (6744 lbf) Ʋ Cable: ø 11 mm (0.433 in), PA coated 30 KN (6744 lbf)

Thetensileforceofsolidsaresubjectofanormalfluctuationrange.Forthisreason,thedetermineddiagram value of the following diagrams must be multiplied with safety factor 2.

Page 51: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

51

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58

879-

EN-1

9021

5

1

2A B

1

2

34

5

6

3

4

5

6

6

12

10

8

4

2

0

3

6

5

4

2

1

00 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35

Fig. 28: Max. tensile load with cereals and plastic granules - Cable: ø 4 mm (0.157 in)A CerealsB Plastic granules1 Tensile force in kN (the determined value must be multiplied with safety factor 2)2 Cable length in m3 Vessel diameter 12 m (39.37 ft)4 Vessel diameter 9 m (29.53 ft)5 Vessel diameter 6 m (19.69 ft)6 Vessel diameter 3 m (9.843 ft)

1

2C D

1

2

3

4

5

6

3

4

5

6

20

18

16

14

12

10

8

6

4

2

20

18

16

14

12

10

8

6

4

2

0 00 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35

Fig. 29: Max. tensile load with sand and cement - Cable: ø 4 mm (0.157 in)C SandD Cement1 Tensile force in kN (the determined value must be multiplied with safety factor 2)2 Cable length in m3 Vessel diameter 12 m (39.37 ft)4 Vessel diameter 9 m (29.53 ft)5 Vessel diameter 6 m (19.69 ft)6 Vessel diameter 3 m (9.843 ft)

Page 52: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

52

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58879-EN

-190215

1

2A B

1

2

34

5

6

3

4

5

6

12

18

16

14

10

8

6

4

2

0

6

9

8

7

5

4

3

2

1

00 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35

Fig. 30: Max. tensile load with cereals and plastic granules - Cable: ø 6 mm, ø 11 mm, PA coatedA CerealsB Plastic granules1 Tensile force in kN (the determined value must be multiplied with safety factor 2)2 Cable length in m3 Vessel diameter 12 m (39.37 ft)4 Vessel diameter 9 m (29.53 ft)5 Vessel diameter 6 m (19.69 ft)6 Vessel diameter 3 m (9.843 ft)

1

2C D

3

4

5

6

2

3

4

5

6

130

25

20

15

10

5

00 5 10 15 20 25 30 35

30

25

20

15

10

5

00 5 10 15 20 25 30 35

Fig. 31: Max. tensile load with sand and cement - Cable: ø 6 mm, ø 11 mm, PA coatedC SandD Cement1 Tensile force in kN (the determined value must be multiplied with safety factor 2)2 Cable length in m3 Vessel diameter 12 m (39.37 ft)4 Vessel diameter 9 m (29.53 ft)5 Vessel diameter 6 m (19.69 ft)6 Vessel diameter 3 m (9.843 ft)

Thread in gravity weight, e.g. for eye-bolt (cable version)

M 12

Torqueforexchangeablecableorrodprobe(intheprocessfitting) Ʋ Cable: ø 4 mm (0.157 in) 8 Nm (5.9 lbf ft)

Page 53: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

53

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58

879-

EN-1

9021

5

Ʋ Cable: ø 6 mm (0.236 in), PA coated 8 Nm (5.9 lbf ft) Ʋ Cable: ø 6 mm (0.236 in) 20 Nm (14.75 lbf ft) Ʋ Cable: ø 11 mm (0.433 in), PA coated 20 Nm (14.75 lbf ft) Ʋ Rod: ø 16 mm (0.63 in) 20 Nm (14.75 lbf ft)

Torque for NPT cable glands and Conduit tubes Ʋ Aluminium/Stainless steel housing max. 50 Nm (36.88 lbf ft)

Input variableMeasured variable Level of solidsMin. dielectric constant of the medium εr≥1.5

Output variableOutput signal 4 … 20 mA/HARTRange of the output signal 3.8 … 20.5 mA/HART (default setting)FulfilledHARTspecification 7Signal resolution 0.3 µAFault signal, current output (adjustable) Lastvalidmeasuredvalue,≥21mA,≤3.6mAMax. output current 21.5 mAStarting current ≤10mAfor5msafterswitchingon,≤3.6mALoad see load under Power supplyDamping (63 % of the input variable), adjustable

0 … 999 s

HART output values according to HART 7 (default setting)2)

Ʋ First HART value (PV) Linearised percentage value, level Ʋ Second HART value (SV) Distance to the level Ʋ Third HART value (TV) Measurement reliability, level Ʋ Fourth HART value (QV) Electronics temperature

Indication value - Display and adjustment module3)

Ʋ Displayed value 1 Filling height Level Ʋ Displayed value 2 Electronics temperature

Resolution, digital < 1 mm (0.039 in)

Measurement accuracy (according to DIN EN 60770-1)Process reference conditions according to DIN EN 61298-1

Ʋ Temperature +18 … +30 °C (+64 … +86 °F) Ʋ Relative humidity 45 … 75 % Ʋ Air pressure +860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)Mounting, reference conditions

Ʋ Min. distance to internal installations > 500 mm (19.69 in)

2) The output values can be assigned individually.3) The indication values can be assigned individually.

Page 54: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

54

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58879-EN

-190215

Ʋ Vessel metallic,ø1m(3.281ft),centricmounting,processfit-tingflushwiththevesselceiling

Ʋ Reflector metallic, ø 1 m Ʋ Medium Bulksolids-cereals,flour,cement(dielectriccon-

stant ~2.0) Ʋ Mounting Probe end does not touch the vessel bottom

Sensor parameter adjustment No gating out of false signals carried out

4

5

3

1

2

4

5

3

1

2

Fig. 32: Measuring ranges - NivoGuide 31001 Reference plane2 Probe length L3 Measuring range4 Upper dead band (see following diagrams - grey section)5 Lower dead band (see following diagrams - grey section)

Typical deviation4) See following diagrams

4) Depending on the installation conditions, deviations may occur which can be corrected by adapting the adjust-ment.

Page 55: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

55

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58

879-

EN-1

9021

5

L

0-2�mm

(-0.079")

2�mm (0.079")

15�mm(0.591")

-10�mm (-0.394")

0,3 m(11.811")

0,08 m(3.15")

0,02 m(0.787")

1

Fig. 33: Deviation NivoGuide 3100 in rod version1 Dead band (no measurement possible in this area)L Probe length

0

2�mm(0.079")

-2�mm(-0.079")

15�mm(0.591")

10�mm(0.394")

0,08 m(3.15")

0,3 m(11.811")

0,1 m(3.94")

L

1

Fig. 34: Deviation NivoGuide 3100 in cable version in water1 Dead band (no measurement possible in this area)L Probe length

Repeatability ≤±1mm

VariablesinfluencingmeasurementaccuracySpecificationsforthedigitalmeasuredvalueTemperature drift - Digital output ±3 mm/10 K relating to the max. measuring range or

max. 10 mm (0.394 in)Additional deviation through electromag-netic interference acc. to EN 61326

< ±10 mm (< ±0.394 in)

Specificationsapplyalsotothecurrentoutput5)

Temperature drift - Current output ±0.03 %/10 K relating to the 16 mA span or max. ±0.3 %

5) Also for the additional current output (optional).

Page 56: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

56

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58879-EN

-190215

Deviation in the current output due to digital/analogue conversion Ʋ Non-Ex and Ex-ia version < ±15 µA

Additional deviation through electromag-netic interference acc. to EN 61326

< ±150 µA

InfluenceofthesuperimposedgasandpressureonmeasurementaccuracyThe propagation speed of the radar impulses in gas or vapour above the medium is reduced by highpressure.Thiseffectdependsonthesuperimposedgasorvapours.Thefollowingtableshowstheresultingdeviationforsometypicalgasesandvapours.Thespecifiedvalues refer to the distance. Positive values mean that the measured distance is too large, negative values that the measured distance is too small.

Gas phase Temperature Pressure

1 bar (14.5 psig) 10 bar (145 psig) 50 bar (725 psig)

Air 20 °C (68 °F) 0 % 0.22 % 1.2 %

200 °C (392 °F) -0.01 % 0.13 % 0.74 %

400 °C (752 °F) -0.02 % 0.08 % 0.52 %

Hydrogen 20 °C (68 °F) -0.01 % 0.1 % 0.61 %

200 °C (392 °F) -0.02 % 0.05 % 0.37 %

400 °C (752 °F) -0.02 % 0.03 % 0.25 %

Steam (saturated steam)

100 °C (212 °F) 0.26 % - -

180 °C (356 °F) 0.17 % 2.1 % -

264 °C (507 °F) 0.12 % 1.44 % 9.2 %

366 °C (691 °F) 0.07 % 1.01 % 5.7 %

Characteristics and performance dataMeasuring cycle time < 500 msStep response time6) ≤3sMax.filling/emptyingspeed 1 m/min

Products with high dielectric constant (>10) up to 5 m/min.

Ambient conditionsAmbient, storage and transport tempera-ture

-40 … +80 °C (-40 … +176 °F)

Process conditionsFortheprocessconditions,pleasealsonotethespecificationsonthetypelabel.Thelowestvaluealways applies.Themeasurementerrorthroughtheprocessconditionsinthespecifiedpressureandtemperaturerange is < 1 %.

6) Time span after a sudden measuring distance change by max. 0.5 m in liquid applications, max 2 m with bulk solidsapplications,untiltheoutputsignalhastakenforthefirsttime90%ofthefinalvalue(IEC61298-2).

Page 57: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

57

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58

879-

EN-1

9021

5

Process pressure -1 … +40 bar/-100 … +4000 kPa (-14.5 … +580 psig), dependingontheprocessfitting

Vesselpressurerelatingtotheflangenominal pressure stage

see supplementary instructions manual "Flanges ac-cording to DIN-EN-ASME-JIS"

Process temperature - Cable versions with PA coating

-40 … +80 °C (-40 … +176 °F)

Processtemperature(threadorflangetemperature)withprocessseals Ʋ FKM (SHS FPM 70C3 GLT) -40 … +150 °C (-40 … +302 °F) Ʋ EPDM (A+P 70.10-02) -40 … +150 °C (-40 … +302 °F) Ʋ FFKM(Kalrez6375)-withtempera-ture adapter

-20 … +200 °C (-4 … +392 °F)

1

2

A

B0°C / 32°F

-40°C / -40°F

80°C / 176°F

30°C / 86°F

60°C / 140°F

150°C302°F

100°C212°F

50°C122°F

80°C176°F

-40°C-40°F

Fig. 35: Ambient temperature - process temperature, standard versionA Ambient temperatureB Process temperature (depending on the seal material)1 Aluminium housing2 Stainless steel housing, electropolished

Page 58: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

58

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58879-EN

-190215

0°C / 32°F

-40°C / -40°F

80°C / 176°F

40°C / 104°F

60°C / 140°F

200°C392°F

150°C302°F

100°C212°F

50°C122°F

80°C176°F

-20°C-4°F

1

2

A

B

Fig. 36: Ambient temperature - process temperature, version with temperature adapterA Ambient temperatureB Process temperature (depending on the seal material)1 Aluminium housing2 Stainless steel housing, electropolished

Vibration resistance Ʋ Rod probe 1gwith5…200HzaccordingEN60068-2-6(vibration

at resonance) with rod length 50 cm (19.69 in)Shock resistance

Ʋ Rod probe 25 g, 6 ms according to EN 60068-2-27 (mechanical shock) with rod length 50 cm (19.69 in)

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable entry

Ʋ M20 x 1.5 1 x cable gland M20 x 1.5 (cable: ø 6 … 12 mm), 1 x blind plug M20 x 1.5

Ʋ ½ NPT 1 x blind plug NPT, 1 x closing cap (red) ½ NPTWire cross-section (spring-loaded terminals)

Ʋ Massive wire, stranded wire 0.2 … 2.5 mm² (AWG 24 … 14) Ʋ Stranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16)

Electromechanical data - version IP 66/IP 68 (1 bar)Connection cable

Ʋ Configuration four wires, one suspension cable, braiding, metal foil, cover

Ʋ Wire cross-section 0.5 mm² (AWG 20) Ʋ Wire resistance <0.036Ω/m Ʋ Tensile strength < 1200 N (270 lbf) Ʋ Standard length 5 m (16.4 ft)

Page 59: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

59

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58

879-

EN-1

9021

5

Ʋ Max. length 180 m (590.6 ft) Ʋ Min. bending radius 25 mm (0.984 in) with 25 °C (77 °F) Ʋ Diameter approx. 8 mm (0.315 in) Ʋ Colour - Non-Ex version Black Ʋ Colour - Ex-version Blue

Display and adjustment moduleDisplay element Display with backlightMeasured value indication

Ʋ Number of digits 5Adjustment elements

Ʋ 4 keys [OK], [->], [+], [ESC]Protection rating

Ʋ unassembled IP 20 Ʋ Mounted in the housing without lid IP 40

Materials Ʋ Housing ABS Ʋ Inspection window Polyester foil

Functional safety SIL non-reactive

Integrated clockDate format Day.Month.YearTime format 12 h/24 hTimezone,factorysetting CETMax. rate deviation 10.5 min/year

Additional output parameter - Electronics temperatureRange -40 … +85 °C (-40 … +185 °F)Resolution < 0.1 KDeviation ±3 KOutput of the temperature values

Ʋ Indication Via the display and adjustment module Ʋ Analogue Via the current output

Voltage supplyOperating voltage UB

Ʋ Non-Ex instrument 9.6 … 35 V DC Ʋ Ex-ia instrument 9.6 … 30 V DC

Operating voltage UB with lighting switched on Ʋ Non-Ex instrument 16 … 35 V DC Ʋ Ex-ia instrument 16 … 30 V DC

Reverse voltage protection Integrated

Page 60: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

60

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58879-EN

-190215

Permissible residual ripple - Non-Ex, Ex-ia instrument Ʋ for 9.6 V< UB < 14 V ≤0.7Veff(16…400Hz) Ʋ for 18 V< UB < 36 V ≤1.0Veff(16…400Hz)

Load resistor Ʋ Calculation (UB - Umin)/0.022 A Ʋ Example - Non-Ex instrument with UB= 24 V DC

(24V-9.6V)/0.022A=655Ω

Potential connections and electrical separating measures in the instrumentElectronics Notnon-floatingReference voltage7) 500 V ACConductive connection Betweengroundterminalandmetallicprocessfitting

Electrical protective measures

Housing material Version Protection acc. to IEC 60529

Protection acc. to NEMA

Aluminium Single chamber IP 66/IP 68 (0.2 bar) Type 6P

Double chamber IP 66/IP 68 (0.2 bar) Type 6P

Stainless steel (electro-pol-ished)

Single chamber IP 66/IP 68 (0.2 bar) Type 6P

Connection of the feeding power supply unit

Networks of overvoltage category III

Altitude above sea level Ʋ by default up to 2000 m (6562 ft) Ʋ with connected overvoltage protection up to 5000 m (16404 ft)

Pollutiondegree(withfulfilledhousingprotection)

4

Protection rating (IEC 61010-1) III

ApprovalsInstruments with approvals can have deviating technical data (depending on the version). For such instruments, the corresponding approval documents must be noted.

9.2 DimensionsThe following dimensional drawings are only an extract of the possible versions.

7) Galvanic separation between electronics and metal housing parts

Page 61: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

61

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58

879-

EN-1

9021

5

Aluminium housing

21

ø 84 mm(3.31")

~ 116 mm(4.57")

116

mm

(4.5

7")

M20x1,5M20x1,5/½ NPT

~ 87 mm(3.43")

M16x1,5

ø 84 mm(3.31")

120

mm

(4.7

2")

M20x1,5/½ NPT

Fig. 37: Housing versions with protection rating IP 66/IP 68 (0.2 bar), (with integrated display and adjustment module the housing is 9 mm/0.35 in higher)1 Aluminium - single chamber2 Aluminium - double chamber

Stainless steel housing

~ 59 mm(2.32")

ø 80 mm(3.15")

112

mm

(4.4

1")

M20x1,5/½ NPT

Fig. 38: Housing versions with protection rating IP 66/IP 68 (0.2 bar), (with integrated display and adjustment module the housing is 9 mm/0.35 in higher)1 Stainless steel single chamber (electropolished)

Page 62: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

62

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58879-EN

-190215

NivoGuide 3100, cable version ø 4 mm (0.157 in), ø 6 mm (0.236 in), PA coated

L

46 m

m(1

.81"

)22

mm

(0.8

7")

ø 20 mm(0.79")

150

mm

(5.9

1")

ø 4 mm(0.16")

G ¾

SW 36 mm(1.42")

ø 6 mm(0.24")

3

1 2

Fig. 39: NivoGuide 3100, cable ø 4 mm (0.157 in), ø 6 mm (0.236 in) threaded version with gravity weight (all grav-ity weights with thread M12 for eye-bolt)L Sensor length, see chapter "Technical data"1 Cable ø 4 mm (0.157 in)2 Cable ø 6 mm (0.236 in), PA coated3 Joint - cable

Page 63: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

63

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58

879-

EN-1

9021

5

NivoGuide 3100, cable version ø 6 mm (0.236 in), ø 11 mm (0.433 in), PA coated

80 m

m(3

.15"

)L

30 m

m(1

.18"

)

ø 30 mm(1.18")

SW 55 mm(2.17")

G1½15

0 m

m (5

.91"

)

ø 6 mm(0.24")

ø 11 mm(0.43")

1 2

3

Fig. 40: NivoGuide 3100, cable ø 6 mm (0.236 in), ø 11 mm (0.433 in) threaded version with gravity weight (all gravity weights with thread M12 for eye-bolt)L Sensor length, see chapter "Technical data"1 Cable ø 6 mm (0.236 in)2 Cable ø 11 mm (0.433 in), PA coated3 Joint - cable

Page 64: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

64

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58879-EN

-190215

NivoGuide 3100, rod version ø 16 mm (0.63 in)

80 m

m(3

.15"

)L

30 m

m(1

.18"

)

ø 16 mm(0.63")

SW 55 mm(2.17")

G1½

1

Fig. 41: NivoGuide 3100, rod ø 16 mm (0.63 in), threaded versionL Sensor length, see chapter "Technical data"1 Joint - rod

Page 65: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

65

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

9 Supplement58

879-

EN-1

9021

5

9.3 TrademarkAll the brands as well as trade and company names used are property of their lawful proprietor/originator.

Page 66: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

66

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

INDEX58879-EN

-190215

INDEX

AAdjustment

– Max. adjustment 25 – Min. adjustment 26

Adjustment system 22Application 25Application area 8

BBacklight 30

CCheck output signal 42Copy sensor settings 35Current output 36Current output, adjustment 37Current output, meas. variable 36Current output, min./max. 28Current output mode 27Curve display

– Echo curve 32

DDamping 26Date of manufacture 38Date/Time 33Default values 33Deviation 43Display format 30

EEcho curve of the setup 32Electrical connection 15, 16Electronics and connection compartment 18Electronics compartment - double chamber housing 18Error codes 41

FFactory calibration date 38False signal suppression 28Faultrectification42Functional principle 8

GGrounding 16

HHART address 37

IInflowingmedium13Installation position 11

KKey function 21

LLanguage 29Linearisation 26Lock adjustment 29

MMain menu 23Measured value indication 30Measurement loop name 24Measurement reliability 31

NNAMUR NE 107

– Failure 40 – Maintenance 42 –Outofspecification41

PPeak value indicator 31Probe length 24Probe type 37

QQuick setup 23

RRead out info 38Repair 47Replacement parts

– Electronics module 9Reset 33

SScaling measured value 36Sensor characteristics 38Sensor status 30Simulation 32Special parameters 37Status messages - NAMUR NE 107 39

TType label 7Type of medium 25

Page 67: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual

67

Nivo®Guide 3100 • Two-wire 4 … 20 mA/HART

INDEX58

879-

EN-1

9021

5

UUnits 24

Page 68: Operating Instructions - Nivo®Guide 3100 - Two-wire 4 … 20 ...€¦ · JIS B 2210-1984, GOST 12821-80. You can find additional information in the supplementary instructions manual