Operating Guide VLT HVAC Drive FC 102 110–400 kWfiles.danfoss.com/download/Drives/MG16D402.pdf ·...
Transcript of Operating Guide VLT HVAC Drive FC 102 110–400 kWfiles.danfoss.com/download/Drives/MG16D402.pdf ·...
ENGINEERING TOMORROW
Operating GuideVLT® HVAC Drive FC 102110–400 kW
vlt-drives.danfoss.com
Contents
1 Introduction 3
1.1 Purpose of the Manual 3
1.2 Additional Resources 3
1.3 Document and Software Version 3
1.4 Product Overview 3
1.5 Approvals and Certifications 6
1.6 Disposal 6
2 Safety 7
2.1 Safety Symbols 7
2.2 Qualified Personnel 7
2.3 Safety Precautions 7
3 Mechanical Installation 9
3.1 Unpacking 9
3.2 Installation Environments 9
3.3 Mounting 9
4 Electrical Installation 11
4.1 Safety Instructions 11
4.2 EMC-compliant Installation 11
4.3 Grounding 12
4.4 Wiring Schematic 14
4.5 Access 15
4.6 Motor Connection 15
4.7 AC Mains Connection 32
4.8 Control Wiring 33
4.8.1 Control Terminal Types 33
4.8.2 Wiring to Control Terminals 35
4.8.3 Enabling Motor Operation (Terminal 27) 35
4.8.4 Voltage/Current Input Selection (Switches) 35
4.8.5 Safe Torque Off (STO) 36
4.9 Installation Check List 37
5 Commissioning 38
5.1 Safety Instructions 38
5.2 Applying Power 38
5.3 Local Control Panel Operation 38
5.4 Basic Programming 41
5.4.1 Commissioning with SmartStart 41
Contents Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 1
5.4.2 Commissioning via [Main Menu] 41
5.5 Checking Motor Rotation 42
5.6 Local-control Test 43
5.7 System Start-up 43
6 Application Set-up Examples 44
6.1 Introduction 44
6.2 Application Examples 44
7 Maintenance, Diagnostics, and Troubleshooting 49
7.1 Introduction 49
7.2 Maintenance and Service 49
7.3 Heat Sink Access Panel 49
7.3.1 Removing the Heat Sink Access Panel 49
7.4 Status Messages 50
7.5 Warning and Alarm Types 52
7.6 List of Warnings and Alarms 53
7.7 Troubleshooting 61
8 Specifications 63
8.1 Electrical Data 63
8.1.1 Mains Supply 3x380–480 V AC 63
8.1.2 Mains Supply 3x525–690 V AC 64
8.2 Mains Supply 66
8.3 Motor Output and Motor Data 66
8.4 Ambient Conditions 66
8.5 Cable Specifications 67
8.6 Control Input/Output and Control Data 67
8.7 Fuses 70
8.8 Connection Tightening Torques 72
8.9 Power Ratings, Weight, and Dimensions 73
9 Appendix 74
9.1 Symbols, Abbreviations, and Conventions 74
9.2 Parameter Menu Structure 74
Index 79
Contents VLT® HVAC Drive FC 102
2 Danfoss A/S © 02/2017 All rights reserved. MG16D402
1 Introduction
1.1 Purpose of the Manual
This operating guide provides information for safe instal-lation and commissioning of the frequency converter.
The operating guide is intended for use by qualifiedpersonnel.Read and follow the instructions to use the frequencyconverter safely and professionally, and pay particularattention to the safety instructions and general warnings.Always keep this operating guide available with thefrequency converter.
VLT® is a registered trademark.
1.2 Additional Resources
Other resources are available to understand advancedfrequency converter functions and programming.
• The VLT® HVAC Drive FC 102 Programming Guideprovides greater detail on working withparameters and many application examples.
• The VLT® HVAC Drive FC 102 Design Guide providesdetailed information about capabilities andfunctionality to design motor control systems.
• Instructions for operation with optionalequipment.
Supplementary publications and manuals are availablefrom Danfoss. See drives.danfoss.com/knowledge-center/technical-documentation/ for listings.
1.3 Document and Software Version
This manual is regularly reviewed and updated. Allsuggestions for improvement are welcome. Table 1.1 showsthe document version and the corresponding softwareversion.
Edition Remarks Software version
MG16D4xx Software update and editorialupdate.
4.4x
Table 1.1 Document and Software Version
1.4 Product Overview
1.4.1 Intended Use
The frequency converter is an electronic motor controllerintended for:
• Regulation of motor speed in response to systemfeedback or to remote commands from externalcontrollers. A power drive system consists of thefrequency converter, the motor, and theequipment driven by the motor.
• System and motor status surveillance.
The frequency converter can also be used for motoroverload protection.
Depending on the configuration, the frequency convertercan be used in standalone applications or form part of alarger appliance or installation.
The frequency converter is allowed for use in residential,industrial, and commercial environments in accordancewith local laws and standards.
NOTICEIn a residential environment, this product can causeradio interference, in which case supplementarymitigation measures can be required.
Foreseeable misuseDo not use the frequency converter in applications whichare non-compliant with specified operating conditions andenvironments. Ensure compliance with the conditionsspecified in chapter 8 Specifications.
Introduction Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 3
1 1
1.4.2 Interior Views
130B
E701
.10
1
2
3
4
5
67
8
9
10
11
1
15 14
8
9
12
13 (IP20/Chassis)
13 (IP21/54
NEMA 1/12)
11
10
16
1 LCP (local control panel) 9 Relay 2 (04, 05, 06)
2 RS485 fieldbus connector 10 Lifting ring
3 Digital I/O and 24 V power supply 11 Mounting holes
4 Analog I/O connector 12 Cable clamp (PE)
5 USB connector 13 Ground
6 Fieldbus terminal switch 14 Motor output terminals 96 (U), 97 (V), 98 (W)
7 Analog switches (A53, A54) 15 Mains input terminals 91 (L1), 92 (L2), 93 (L3)
8 Relay 1 (01, 02, 03) 16 TB5 (IP21/54 only). Terminal block for anti-condensation heater
Illustration 1.1 D1 Interior Components (left); Close-up View: LCP and Control Functions (right)
NOTICEFor location of TB6 (terminal block for contactor), seechapter 4.6 Motor Connection.
Introduction VLT® HVAC Drive FC 102
4 Danfoss A/S © 02/2017 All rights reserved. MG16D402
11
1.4.3 Extended Options Cabinets
If a frequency converter is ordered with 1 of the followingoptions, it is supplied with an options cabinet thatincreases the height.
• Brake chopper.
• Mains disconnect.
• Contactor.
• Mains disconnect with contactor.
• Circuit breaker.
• Oversized wiring cabinet.
• Regeneration terminals.
• Load sharing terminals.
Illustration 1.2 shows an example of a frequency converterwith an options cabinet. Table 1.2 lists the variants for thefrequency converters that include input options.
Options unitdesignations
Extension cabinets Possible options
D5h D1h enclosure withshort extension.
• Brake.
• Disconnect.
D6h D1h enclosure withtall extension.
• Contactor.
• Contactor withdisconnect.
• Circuit breaker.
D7h D2h enclosure withshort extension.
• Brake.
• Disconnect.
D8h D2h enclosure withtall extension.
• Contactor.
• Contactor withdisconnect.
• Circuit breaker.
Table 1.2 Overview of Extended Options
The D7h and D8h frequency converters (D2h plus optionscabinet) include a 200 mm (7.9 in) pedestal for floormounting.
There is a safety latch on the front cover of the optionscabinet. If the frequency converter is supplied with a mainsdisconnect or circuit breaker, the safety latch prevents thecabinet door from being opened while the frequencyconverter is energized. Before opening the door of thefrequency converter, open the disconnect or circuit breaker(to de-energize the frequency converter) and remove thecover of the options cabinet.
For frequency converters purchased with a disconnect,contactor or circuit breaker, the nameplate label includes atype code for a replacement that does not include theoption. If there is a problem with the frequency converter,it is replaced independently of the options.
130B
C539
.10
1754
[69.1]
Illustration 1.2 D7h Enclosure
Introduction Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 5
1 1
1.4.4 Block Diagram of the FrequencyConverter
Illustration 1.3 is a block diagram of the internalcomponents of the frequency converter.
Area Title Functions
1 Mains input• 3-phase AC mains supply to
the frequency converter.
2 Rectifier
• The rectifier bridge convertsthe AC input to DC current tosupply inverter power.
3 DC bus• Intermediate DC-bus circuit
handles the DC current.
4 DC reactors
• Filter the intermediate DCcircuit voltage.
• Prove mains transientprotection.
• Reduce RMS current.
• Raise the power factorreflected back to the line.
• Reduce harmonics on the ACinput.
5 Capacitor bank
• Stores the DC power.
• Provides ride-throughprotection for short powerlosses.
6 Inverter
• Converts the DC into acontrolled PWM AC waveformfor a controlled variableoutput to the motor.
7 Output to motor• Regulated 3-phase output
power to the motor.
Area Title Functions
8 Control circuitry
• Input power, internalprocessing, output, and motorcurrent are monitored toprovide efficient operationand control.
• User interface and externalcommands are monitored andperformed.
• Status output and control canbe provided.
Illustration 1.3 Block Diagram of Frequency Converter
1.4.5 Enclosure Sizes and Power Ratings
For enclosure sizes and power ratings of the frequencyconverters, refer to chapter 8.9 Power Ratings, Weight, andDimensions.
1.5 Approvals and Certifications
More approvals and certifications are available. Contact thelocal Danfoss partner. Frequency converters of enclosuresize T7 (525–690 V) are UL certified for only 525–600 V.
The frequency converter complies with UL 508C thermalmemory retention requirements. For more information,refer to the section Motor Thermal Protection in theproduct-specific design guide.
NOTICEIMPOSED LIMITATIONS ON THE OUTPUTFREQUENCYFrom software version 3.92, the output frequency of thefrequency converter is limited to 590 Hz (due to exportcontrol regulations).
1.6 Disposal
Do not dispose of equipment containingelectrical components together withdomestic waste.Collect it separately in accordance withlocal and currently valid legislation.
Introduction VLT® HVAC Drive FC 102
6 Danfoss A/S © 02/2017 All rights reserved. MG16D402
11
2 Safety
2.1 Safety Symbols
The following symbols are used in this guide:
WARNINGIndicates a potentially hazardous situation that couldresult in death or serious injury.
CAUTIONIndicates a potentially hazardous situation that couldresult in minor or moderate injury. It can also be used toalert against unsafe practices.
NOTICEIndicates important information, including situations thatcan result in damage to equipment or property.
2.2 Qualified Personnel
Correct and reliable transport, storage, installation,operation, and maintenance are required for the trouble-free and safe operation of the frequency converter. Onlyqualified personnel are allowed to install and operate thisequipment.
Qualified personnel are defined as trained staff, who areauthorized to install, commission, and maintain equipment,systems, and circuits in accordance with pertinent laws andregulations. Also, the qualified personnel must be familiarwith the instructions and safety measures described in thismanual.
2.3 Safety Precautions
WARNINGHIGH VOLTAGEFrequency converters contain high voltage whenconnected to AC mains input, DC supply, or load sharing.Failure to perform installation, start-up, and maintenanceby qualified personnel can result in death or seriousinjury.
• Only qualified personnel must perform instal-lation, start-up, and maintenance.
WARNINGUNINTENDED STARTWhen the frequency converter is connected to AC mains,DC supply, or load sharing, the motor may start at anytime. Unintended start during programming, service, orrepair work can result in death, serious injury, orproperty damage. The motor can start via an externalswitch, a fieldbus command, an input reference signalfrom the LCP, or after a cleared fault condition.
To prevent unintended motor start:• Disconnect the frequency converter from the
mains.
• Press [Off/Reset] on the LCP beforeprogramming parameters.
• Completely wire and assemble the frequencyconverter, motor, and any driven equipmentbefore connecting the frequency converter toAC mains, DC supply, or load sharing.
WARNINGDISCHARGE TIMEThe frequency converter contains DC-link capacitors,which can remain charged even when the frequencyconverter is not powered. High voltage can be presenteven when the warning LED indicator lights are off.Failure to wait the specified time after power has beenremoved before performing service or repair work canresult in death or serious injury.
• Stop the motor.
• Disconnect AC mains and remote DC-link powersupplies, including battery back-ups, UPS, andDC-link connections to other frequencyconverters.
• Disconnect or lock PM motor.
• Wait for the capacitors to discharge fully. Theminimum waiting time is 20 minutes.
• Before performing any service or repair work,use an appropriate voltage measuring device tomake sure that the capacitors are fullydischarged.
Safety Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 7
2 2
WARNINGLEAKAGE CURRENT HAZARDLeakage currents exceed 3.5 mA. Failure to ground thefrequency converter properly can result in death orserious injury.
• Ensure the correct grounding of the equipmentby a certified electrical installer.
WARNINGEQUIPMENT HAZARDContact with rotating shafts and electrical equipmentcan result in death or serious injury.
• Ensure that only trained and qualified personnelperform installation, start-up, and maintenance.
• Ensure that electrical work conforms to nationaland local electrical codes.
• Follow the procedures in this guide.
WARNINGUNINTENDED MOTOR ROTATIONWINDMILLINGUnintended rotation of permanent magnet motorscreates voltage and can charge the unit, resulting indeath, serious injury, or equipment damage.
• Ensure that permanent magnet motors areblocked to prevent unintended rotation.
CAUTIONINTERNAL FAILURE HAZARDAn internal failure in the frequency converter can resultin serious injury when the frequency converter is notproperly closed.
• Ensure that all safety covers are in place andsecurely fastened before applying power.
Safety VLT® HVAC Drive FC 102
8 Danfoss A/S © 02/2017 All rights reserved. MG16D402
22
3 Mechanical Installation
3.1 Unpacking
3.1.1 Items Supplied
Items supplied may vary according to product configu-ration.
• Make sure the items supplied and the informationon the nameplate correspond to the order confir-mation.
• Check the packaging and the frequency convertervisually for damage caused by inappropriatehandling during shipment. File any claim fordamage with the carrier. Retain damaged partsfor clarification.
130B
D60
0.11
CHASSIS/ IP20 Tamb.50 C/122 F
VLT
MADE IN DENMARK
R
P/N: 131X3537 S/N: 010122G430
0.37kW/ 0.50HP
IN: 3x200-240V 50/60Hz 2.2A
OUT: 3x0-Vin 0-590Hz 2.4Ao
CAUTION:See manual for special condition/mains fusevoir manual de conditions speclales/fusibles
WARNING:Stored charge, wait 4 min.Charge residuelle, attendez 4 min.
* 1 3 1 X 3 5 3 7 0 1 0 1 2 2 G 4 3 0 *
`
Automation Drivewww.danfoss.com
T/C: FC-302PK37T2E20H1BGXXXXSXXXXA6BKC4XXXD0
Listed 76X1 E134261 Ind. Contr. Eq.
o
`
12
4
5
6
7 8
9
10
3
1 Type code
2 Ordering number
3 Serial number
4 Power rating
5Input voltage, frequency, and current (at low/highvoltages)
6Output voltage, frequency, and current (at low/highvoltages)
7 Enclosure size and IP protection rating
8 Maximum ambient temperature
9 Certifications
10 Discharge time (Warning)
Illustration 3.1 Product Nameplate (Example)
NOTICEDo not remove the nameplate from the frequencyconverter (loss of warranty).
3.1.2 Storage
Ensure that the requirements for storage are fulfilled. Referto chapter 8.4.1 Ambient Conditions for further details.
3.2 Installation Environments
NOTICEIn environments with airborne liquids, particles, orcorrosive gases, ensure that the IP/type rating of theequipment matches the installation environment. Failureto meet requirements for ambient conditions can reducethe lifetime of the frequency converter. Ensure thatrequirements for air humidity, temperature, and altitudeare met.
Voltage [V] Altitude restrictions
380–500 At altitudes above 3000 m (9842 ft), contactDanfoss regarding PELV.
525–690 At altitudes above 2000 m (6562 ft), contactDanfoss regarding PELV.
Table 3.1 Installation at High Altitudes
For detailed ambient conditions specifications, refer tochapter 8.4.1 Ambient Conditions.
3.3 Mounting
NOTICEImproper mounting can result in overheating andreduced performance.
Cooling
• Ensure that top and bottom clearance for aircooling is provided. Clearance requirement:225 mm (9 in).
• Consider derating for temperatures startingbetween 45 °C (113 °F) and 50 °C (122 °F) andelevation 1000 m (3300 ft) above sea level. Seethe frequency converter design guide for detailedinformation.
Mechanical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 9
3 3
The frequency converter utilizes a back-channel coolingconcept that removes heat sink cooling air. The heat sinkcooling air carries approximately 90% of the heat out ofthe back channel of the frequency converter. Redirect theback-channel air from the panel or room by using:
• Duct cooling. A back-channel cooling kit isavailable to direct the heat sink cooling air out ofthe panel when an IP20/chassis frequencyconverter is installed in a Rittal enclosure. Use ofthis kit reduces the heat in the panel and smallerdoor fans can be specified on the enclosure.
• Cooling out the back (top and base covers). Theback-channel cooling air can be ventilated out ofthe room so that the heat from the back channelis not dissipated into the control room.
NOTICEOne or more door fans are required on the enclosure toremove the heat not contained in the back channel ofthe frequency converter. The fans also remove anyadditional losses generated by other components insidethe frequency converter. To select the appropriate fan,calculate the total required airflow.
Secure the necessary airflow over the heat sink. The flowrate is shown in Table 3.2.
Enclosure size Door fan/top fan Heat sink fan
D1h/D3h/D5h/D6h 102 m3/hr (60 CFM) 420 m3/hr (250 CFM)
D2h/D4h/D7h/D8h 204 m3/hr (120 CFM) 840 m3/hr (500 CFM)
Table 3.2 Airflow
LiftingAlways lift the frequency converter using the dedicatedlifting eyes. To avoid bending the lifting holes, use a liftingbar.
176FA24
5.10
Illustration 3.2 Recommended Lifting Method
WARNINGRISK OF INJURY OR DEATHThe lifting bar must be able to support the weight of thefrequency converter to ensure that it does not breakduring lifting.
• See chapter 8.9 Power Ratings, Weight, andDimensions for the weight of the differentenclosure sizes.
• Maximum diameter for bar: 25 mm (1 in).
• The angle from the top of the frequencyconverter to the lifting cable: 60° or greater.
Failure to follow recommendations could result in deathor serious injury.
Mounting
1. Ensure that the strength of the mounting locationsupports the unit weight.
2. Place the unit as near to the motor as possible.Keep the motor cables as short as possible.
3. Mount the unit vertically to a solid flat surface toprovide cooling airflow. Ensure free space forcooling.
4. Ensure the access, to open the door.
5. Ensure the cable entry from below.
Mechanical Installation VLT® HVAC Drive FC 102
10 Danfoss A/S © 02/2017 All rights reserved. MG16D402
33
4 Electrical Installation
4.1 Safety Instructions
See chapter 2 Safety for general safety instructions.
WARNINGINDUCED VOLTAGEInduced voltage from output motor cables that runtogether can charge equipment capacitors, even with theequipment turned off and locked out. Failure to runoutput motor cables separately or use shielded cablescould result in death or serious injury.
• Run output motor cables separately, or
• Use shielded cables.
CAUTIONSHOCK HAZARDThe frequency converter can cause a DC current in thePE conductor. Failure to follow the recommendationmeans that the RCD may not provide the intendedprotection.
• When a residual current-operated protectivedevice (RCD) is used for protection againstelectrical shock, only an RCD of Type B isallowed on the supply side.
Overcurrent protection• More protective equipment, such as short-circuit
protection or motor thermal protection betweenfrequency converter and motor, is required forapplications with multiple motors.
• Input fusing is required to provide short-circuitand overcurrent protection. If not factory-supplied, the installer must provide the fuses. Seemaximum fuse ratings in chapter 8.7 Fuses.
Wire type and ratings• All wiring must comply with local and national
regulations regarding cross-section and ambienttemperature requirements.
• Power connection wire recommendation:Minimum 75 °C (167 °F) rated copper wire.
See chapter 8.1 Electrical Data and chapter 8.5 Cable Specifi-cations for recommended wire sizes and types.
4.2 EMC-compliant Installation
To obtain an EMC-compliant installation, follow theinstructions provided in:
• Chapter 4.4 Wiring Schematic.
• Chapter 4.6 Motor Connection.
• Chapter 4.3 Grounding.
• Chapter 4.8.1 Control Wiring.
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 11
4 4
4.3 Grounding
WARNINGLEAKAGE CURRENT HAZARDLeakage currents exceed 3.5 mA. Failure to ground the frequency converter properly can result in death or seriousinjury.
• Ensure the correct grounding of the equipment by a certified electrical installer.
For electrical safety
• Ground the frequency converter in accordance with applicable standards and directives.
• Use a dedicated ground wire for input power, motor power, and control wiring.
• Do not ground 1 frequency converter to another in a daisy chain fashion.
• Keep the ground wire connections as short as possible.
• Follow motor manufacturer wiring requirements.
• Minimum cable cross-section: 10 mm2 (6 AWG) (or 2 rated ground wires terminated separately).
• Tighten the terminals in accordance with the information provided in chapter 8.8.1 Fastener Torque Ratings.
For EMC-compliant installation
• Establish electrical contact between the cable shield and the frequency converter enclosure by using metal cableglands or by using the clamps provided on the equipment.
• Reduce burst transient by using high-strand wire.
• Do not use pigtails.
NOTICEPOTENTIAL EQUALIZATIONThere is a risk of burst transient when the ground potential between the frequency converter and the control system isdifferent. Install equalizing cables between the system components. Recommended cable cross-section: 16 mm2
(5 AWG).
Electrical Installation VLT® HVAC Drive FC 102
12 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
130B
F152
.10
U/T1 96 V/T2 97 W/T3 98T/L3 93S/L2 92R/L1 91
FASTENER TORQUE M10 19Nm (14FT-LB), M12 35Nm (26FT-LB) FASTENER TORQUE M10 19Nm (14FT-LB), M12 35Nm (26FT-LB)
U/T1 96 V/T2 97 W/T3 98T/L3 93S/L2 92R/L1 91
FASTENER TORQUE M10 19Nm (14FT-LB), M12 35Nm (26FT-LB) FASTENER TORQUE M10 19Nm (14FT-LB), M12 35Nm (26FT-LB)
1 Ground terminal (ground terminals are marked with symbol) 2 Ground symbol
Illustration 4.1 Ground Terminals (D1h shown)
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 13
4 4
4.4 Wiring Schematic
230 V AC50/60 Hz
230 V AC50/60 Hz
TB6 Contactor
TB5R1
1
2
Brake temp (NC)
Anti-condensation heater (optional)
(optional)
91 (L1)92 (L2)93 (L3)
PE
88 (-)89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4–20 mA
12 (+24 V OUT)
13 (+24 V OUT)
18 (D IN)
20 (COM D IN)
15 mA 200 mA
(U) 96(V) 97
(W) 98(PE) 99
(COM A OUT) 39
(A OUT) 42 0/4-20 mA
03
+10 V DC
0 V DC - 10 V DC0/4–20 mA
24 V DC
02
01
05
04
06240 V AC, 2A
24 V (NPN) 0 V (PNP)
0 V (PNP)24 V (NPN)
19 (D IN)
24 V (NPN) 0 V (PNP)27
24 V
0 V
(D IN/OUT)
0 V (PNP)24 V (NPN)
(D IN/OUT)
0 V
24 V29
24 V (NPN) 0 V (PNP)
0 V (PNP)24 V (NPN)
33 (D IN)
32 (D IN)
12
ON
A53 U-I (S201)
ON2
1A54 U-I (S202)ON=0–20 mAOFF=0–10 V
95
400 V AC, 2AP 5-00
(R+) 82
(R-) 81+ - + -
(P RS485) 68
(N RS485) 69
(COM RS485) 612)
0 V
5 V
S801
RS485RS485
21 O
N
S801/Bus term.OFF-ON
3-phasepowerinput
Load share Switch modepower supply
Motor
Analog output
Interface
Relay1
Relay2
ON=TerminatedOFF=Open
Brakeresistor
(NPN) = Sink(PNP) = Source
==
=
240 V AC, 2A
400 V AC, 2A0 V DC - 10 V DC
10 V DC
37 (D IN) - option1)
130B
C548
.14
Illustration 4.2 Basic Wiring Schematic
A=Analog, D=Digital1) Terminal 37 (optional) is used for Safe Torque Off. For Safe Torque Off installation instructions, refer to the VLT® FrequencyConverters - Safe Torque Off Operating Guide.2) Do not connect cable shield.
Electrical Installation VLT® HVAC Drive FC 102
14 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
130B
E143
.10
Stop
Start
Speed Line Power Motor
Control
Illustration 4.3 Example of Proper Electrical Installation UsingConduit
NOTICEEMC INTERFERENCEUse shielded cables for motor and control wiring, andseparate cables for mains input, motor wiring, andcontrol wiring. Failure to isolate power, motor, andcontrol cables can result in unintended behavior orreduced performance. Minimum 200 mm (7.9 in)clearance between mains input, motor, and controlcables is required.
4.5 Access
All terminals to the control cables are inside the drivebelow the LCP. To access, either open the door (E1h andE2h) or remove the front panel (E3h and E4h).
4.6 Motor Connection
WARNINGINDUCED VOLTAGEInduced voltage from output motor cables that runtogether can charge equipment capacitors, even with theequipment turned off and locked out. Failure to runoutput motor cables separately or use shielded cablescould result in death or serious injury.
• Comply with local and national electrical codesfor cable sizes. For maximum wire sizes, seechapter 8.1 Electrical Data.
• Follow motor manufacturer wiring requirements.
• Motor wiring knockouts or access panels areprovided at the base of IP21 (NEMA1/12) andhigher units.
• Do not wire a starting or pole-changing device(for example Dahlander motor or slip ringasynchronous motor) between the frequencyconverter and the motor.
Procedure1. Strip a section of the outer cable insulation.
2. Position the stripped wire under the cable clampto establish mechanical fixation and electricalcontact between the cable shield and ground.
3. Connect the ground wire to the nearestgrounding terminal in accordance with thegrounding instructions provided inchapter 4.3 Grounding, see Illustration 4.4.
4. Connect the 3-phase motor wiring to terminals96 (U), 97 (V), and 98 (W), see Illustration 4.4.
5. Tighten the terminals in accordance with theinformation provided in chapter 8.8 ConnectionTightening Torques.
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 15
4 4
130B
C25
4.10
21
1 Mains connection (R, S, T)
2 Motor connection (U, V, W)
Illustration 4.4 Motor Connection
Electrical Installation VLT® HVAC Drive FC 102
16 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
A
A
B
B
33 1.3
[]
0 0.0
[]
62 2.4
[]
101 4.0
[]
140 5.5
[]
163 6.4
[]
185 7.3
[]
224 8.8
[]
263 10
.4[
]29
3 11.5
[]
GROUND 883.5[ ]
00.0[ ]
2007.9[ ]
943.7[ ]
244 9.6
[]
0 0.0
[]
272 10
.7[
]
0 0.0
[]
S U W
R T V
3X M8x20 STUDWITH NUT
SECTION A-AMAINS TERMINALS
MAINS TERMINAL
SECTION B-BMOTOR TERMINALS
MOTORTERMINAL
130B
C30
5.10
Illustration 4.5 Terminal Locations, D1h
B
B
A
A
254.
710[
] 0.0 0[]
GROUND 143.46[ ]
0.00[ ]
GROUND 168.47[ ]
331.213[ ]
211.18[ ]
GROUND168.47[ ]
GROUND143.46[ ]
42.4 2[]
0.0 0[]
68.1 3[]
125.
85[
]18
3.5
7[]
245.
810[
]29
9.8
12[]
353.
814[
]37
7.6
15[]
284.
211[
]0.0 0[]
R
S
T
U
V
W
4X M10x20 STUDWITH NUT
SECTION B-BMOTOR TERMINALS AND
BRAKE TERMINALS
MOTOR TERMINAL
SECTION A-AMAINS TERMINALS
MAINS TERMINAL
130B
C33
2.10
Illustration 4.6 Terminal Locations, D2h
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 17
4 4
A
A
B
B
833.3[ ]
00.0[ ]
1887.4[ ]
244 9.6
[]
0 0.0
[]
290 11
.4[
]272 10
.7[
]
0 0.0
[]
22 0.9
[]
0 0.0
[]
62 2.4
[]
101 4.0
[]
145 5.7
[]
184 7.2
[]
223 8.8
[]
152 6.0
[]
217 8.5
[]
29211.5[ ]
R
S
T
U
V
W
BRAKE
SECTION A-AMAINS TERMINALS
MAINSTERMINAL
SECTION B-BMOTOR TERMINALS AND
BRAKE TERMINALS
MOTOR TERMINAL
BRAKETERMINAL
130B
C30
2.10
Illustration 4.7 Terminal Locations, D3h
1 2
130B
C533
.10
190[7.5]
75[3.0]
98[3.9]
50[2.0]
1 Front view
2 Side view
Illustration 4.8 Load Sharing and Regeneration Terminals, D3h
Electrical Installation VLT® HVAC Drive FC 102
18 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
A
A
B
B33 1.
3[
]
0 0.0
[]
91 3.6
[]
149 5.8
[]
211 8.3
[]
265 10
.4[
]31
9 12.6
[]
2007.9[ ]
00.0[ ]
31912.6[ ]
37614.8[ ]
293 11
.5[
]
255 10
.0[
]
0 0.0
[]
306 12
.1[
]
284 11
.2[
]
0 0.0
[]
236.
89[
]R
S
T
U
V
W
BRAKETERMINALS
SECTION A-AMAINS TERMINALS
MAINS TERMINAL
SECTION B-BMOTOR TERMINALS AND
BRAKE TERMINALS
TERMINALBRAKE / REGEN
MOTOR TERMINAL
130B
C33
3.10
Illustration 4.9 Terminal Locations, D4h
1
190[7.5]
75[3.0]
126[4.9]
95[3.7]
2
130B
C534
.10
1 Front view
2 Side view
Illustration 4.10 Load Sharing and Regeneration Terminals, D4h
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 19
4 4
B
B
A
A
45 1.8
[]
0 0[]
46 1.8
[]
99 3.9
[]
153
6[]
146
5.8
[]
182
7.2
[]
193
7.6
[]
249
9.8
[]
221
8.7
[]
260
10.2
[]
1184.6[ ]
00[ ]
1485.8[ ]
2218.7[ ]
903.6[ ]
1967.7[ ]
2279[ ]
113
4.4
[]
0 0[]
206
8.1
[]
A-A
RS
T
U VW
B-B
130B
C535
.11
12
3
4
1 Mains terminals
2 Brake terminals
3 Motor terminals
4 Ground terminalsIllustration 4.11 Terminal Locations, D5h with Disconnect Option
Electrical Installation VLT® HVAC Drive FC 102
20 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
33 1.3
[]
0 0[]
62 2.4
[]
101
4[]
140
5.5
[]
163
6.4
[]
185
7.3
[]
191
7.5
[]
224
8.8
[]
256
10.1
[]
263
10.4
[]
293
11.5
[]
51120.1[ ]
00[ ]
51720.4[ ]
62324.5[ ]
72728.6[ ]
246
9.7
[]
0 0[]
293
11.5
[]
274
10.8
[]
0 0[]
R
S
TU
V
W
B-B
A-A
3
4
130B
C536
.11
1
2
1 Mains terminals
2 Brake terminals
3 Motor terminals
4 Ground terminalsIllustration 4.12 Terminal Locations, D5h with Brake Option
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 21
4 4
0 [0]
0 [0]
42 [1.7
]
77 [3]
160
[6.3
]
244
[9.6
]
209
[8.2
]
126
[5]
33.8[1.3]
271[10.7]
187[7.4]
215[8.5]
0[0]
0[0]
154[6.1]
248[9.8]
233[9.2]
210[8.3]
25.83[1]
111[4.4]
224[8.8]
121[4.8]
242[9.5]
43[1.7]
15[0.6]
10[0.4]
10.3[0.4] 30
[1.2]50.5[2]
10[0.4]
16.5[0.7]
34.5[1.4]
67.5[2.7]
17.5[0.7]
M10
M8
118
[4.6
]
285
[11.
2]
35 [1.4
]
101 [4]
185
[7.3
]
285
[11.
2]
206
[8.1
]
0 [0]
0 [0]
57 [2.2
]
42 [1.7
]
123.
1[5
]17
9[7
.1]
199
[7.8
]20
9[8
.2]
285
[11.
2]
279
[11]
249
[9.8
]116
[4.6
]91 [3.6
] 151
[5.9
]17
5[6
.9]
224
[8.8
]
258
[10.
2]
Section viewMains terminalMotor terminal
Mains terminalMotor terminal
Mains terminal
Motor terminal
Brake terminal
Shieldingclamps
Shielding clamps
Mains terminal
Brake terminal
Motor terminal
4X MI0 X 20 studwith nut
5X MI0 X 20 studwith nut
Bottom view
Mains sideCable entry
Motor sideCable entry
Section viewBrake terminal
DC
DC
R
U
V W
S T
130B
E236
.11
Illustration 4.13 Oversized Wiring Cabinet, D5h
Electrical Installation VLT® HVAC Drive FC 102
22 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
B
B
A
A00.0[ ]
963.8[ ]
1957.7[ ]
2278.9[ ]
1234.8[ ]
1536.0[ ]
45818.0[ ]
0 0.0
[]
46 1.8
[]
50 2.0
[]
99 3.9
[]
147
5.8
[]
182
7.2
[]19
37.6
[]
221
8.7
[]
249
9.8
[]
260
10.2
[]
146
5.8
[]
0 0.0
[]
286
11.2
[]
0 0.0
[113
4.4
[] ]
206
8.1
[]
B-BA-A
R
S T U V W
130B
C537
.12
1
23
4
5
1 Mains terminals
2 TB6 terminal block for contactor
3 Brake terminals
4 Motor terminals
5 Ground terminalsIllustration 4.14 Terminal Locations, D6h with Contactor Option
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 23
4 4
A
A
99 3.9
[]
153 6.0
[]
00.0[ ]
2258.9[ ]
45 1.8
[]
0 0.0
[]
286 11
.2[
]
0 0.0
[]
R S T
A-A
130B
C538
.12
1
2
34
5
1 Brake terminals
2 TB6 terminal block for contactor
3 Motor terminals
4 Ground terminals
5 Mains terminalsIllustration 4.15 Terminal Locations, D6h with Contactor and Disconnect Options
Electrical Installation VLT® HVAC Drive FC 102
24 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
A
A
46718.4[ ]
00.0[ ]
52 2.1
[]
0 0.0
[]
99 3.9
[]
145 5.7
[]
163 6.4
[]
0 0.0
[]
A-A
R S T
130B
C541
.11
1
2
4
3
1 Mains terminals
2 Brake terminals
3 Motor terminals
4 Ground terminalsIllustration 4.16 Terminal Locations, D6h with Circuit Breaker Option
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 25
4 4
130B
C542
.11
B
B
A
A
37214.7[ ]
41216.2[ ] 395
15.6[ ]
51520.3[ ]
0 0[]
66 2.6
[]
95 3.7
[]
131
5.1
[]
151
5.9
[]
195.5
8[]
238
9.4
[]
292
11.5
[]
346
13.6
[]
49 1.9
[]
198
7.8
[]
368
14.5
[]
54521.4[ ]
0 0[]
119
4.7
[]
276
10.9
[]
00[ ]
B-BA-A
RS
T
U
V
W
1
2
3
4
1 Mains terminals
2 Motor terminals
3 Ground terminals
4 Brake terminalsIllustration 4.17 Terminal Locations, D7h with Disconnect Option
Electrical Installation VLT® HVAC Drive FC 102
26 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
130B
C543
.11
B
B
A
A
0 0[]
66 2.6
[]
123
4.9
[]
181
7.1
[]
243
9.6
[]
269
10.6
[]
297
11.7
[]
325
12.8
[]35
113
.8[
]
40 1.6
[]
00[ ]
100939.7[ ]
103440.7[ ]
108242.6[ ]
120247.3[ ]
126049.6[ ]
375
14.8
[]
290
11.4
[]
0 0[]
257
10.1
[]
309
12.1
[]
0 0[]
B-B
A-A
R
S
T
U
VW
1
2
3
4
1 Mains terminals
2 Brake terminals
3 Motor terminals
4 Ground terminalsIllustration 4.18 Terminal Locations, D7h with Brake Option
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 27
4 4
Section view
Section view
Mains terminalBrake terminal
Motor terminalBrake terminal
Mains terminal
Mains terminal
DC
D
C
47.2
[1.9
]
0 [0]
0 [0]
150
[5.9
]
0 [0]
120
[4.8
]
250.
2[9
.9]
651.6[25.7]
613.5[24.2]
613[24.1]
549.8[21.6]
587.1[23.1]
0[0]
0[0]
33.8[1.3]
25.3[1]
43[1.7]
222[8.7]
117.1[4.6]
337[13.3]
169[6.6]
10[0.4]
15[0.6]
16.5[0.7]
10.3[0.4]
34.5[1.4]
30[1.2]
67.5[3]
50.5[2]
17.5[0.7]
15[0.6]
107.
2[4
.2]
190.
7[7
.5]
280.
7[1
1.1]
37.4
[1.5
]
361.
1[1
4.2]
316.
1[1
2.4]
67.4
[2.7
]
107.
4[4
.2]
137.
4[5
.4]
172.
6[6
.8]
232.
6[9
.2]
48.2
[1.9
]82
.7[3
.3]
131.
7[5
.2]
166.
2[6
.5]
215.
2[8
.5]
249.
7[9
.8]
0 [0]
52.6
[2.1
]
122.
6[4
.8]
173.
6[6
.8]
208.
1[8
.2]
257.
1[1
0.1]
291.
6[1
1.5]
340.
6[1
3.4]
375.
1[1
4.8]
Shieldingclamps
Shieldingclamps
Mains sideCable entry Motor side
Cable entry
Mains terminal
4X MI0 X 20 studwith nut
6X MI0 X 20 studwith nut
Brake terminal
Brake terminal
Motor terminal
Motor terminal
Motor terminal
M10
M8
R
U V W
S T
130B
E237
.11
Illustration 4.19 Oversized Wiring Cabinet, D7h
Electrical Installation VLT® HVAC Drive FC 102
28 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
A
A B
B
69 2.7
[]
0 0[]
123 4.9
[]17
7 7[]
238
9.4
[]29
211
.5[
]34
613
.6[
]
49 1.9
[]
378
14.9
[]
198
7.8
[]
37814.9[ ]
00[ ]
41816.5[ ]
89835.3[ ]
40115.8[ ]
52120.5[ ]
95 3.7
[]
151 5.9
[]
119
4.7
[]
0 0[]
252
9.9
[]
127
5[]
0 0[]
A-A
B-B
RS
T U
V
W
130B
C544
.12
1
2
3
4
5
1 TB6 terminal block for contactor 4 Brake terminals
2 Motor terminals 5 Mains terminals
3 Ground terminals
Illustration 4.20 Terminal Locations, D8h with Contactor Option
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 29
4 4
C
C
56722.3[ ]
00[ ]
58 2.3
[]
0 0[]
123 4.9
[]
188 7.4
[]24
6 9.7
[]
0 0[]
C-C
130B
C545
.12
R
S
T
1
2
3
4
5
1 TB6 terminal block for contactor 4 Motor terminals
2 Mains terminals 5 Ground terminals
3 Brake terminals
Illustration 4.21 Terminal Locations, D8h with Contactor and Disconnect Options
Electrical Installation VLT® HVAC Drive FC 102
30 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
202 8
[]
00
[]
84.5 3
[]
00
[]
154.5
6[
]
224.5
9[
]
60523.8[ ]
00[ ]
R
S
T
130B
C546
.11
1
2
3
4
1 Mains terminals 3 Motor terminals
2 Brake terminals 4 Ground terminals
Illustration 4.22 Terminal Locations, D8h with Circuit Breaker Option
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 31
4 4
4.7 AC Mains Connection
• Size the wiring according to the input current ofthe frequency converter. For maximum wire sizes,see chapter 8.1 Electrical Data.
• Comply with local and national electrical codesfor cable sizes.
Procedure
1. Connect the 3-phase AC input power wiring toterminals R, S, and T (see Illustration 4.23).
2. Depending on the configuration of theequipment, connect the input power to themains input terminals or the input disconnect.
3. Ground the cable in accordance with thegrounding instructions provided inchapter 4.3 Grounding.
4. When supplied from an isolated mains source (ITmains or floating delta) or TT/TN-S mains with agrounded leg (grounded delta), ensure thatparameter 14-50 RFI Filter is set to [0] Off. Thissetting prevents damage to the DC link andreduces ground capacity currents.
130B
C25
4.10
21
1 Mains connection (R, S, T)
2 Motor connection (U, V, W)
Illustration 4.23 Connecting to AC Mains
Electrical Installation VLT® HVAC Drive FC 102
32 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
4.8 Control Wiring
• Isolate the control wiring from the high-powercomponents in the frequency converter.
• When the frequency converter is connected to athermistor, ensure that the thermistor controlwiring is shielded and reinforced/doubleinsulated. A 24 V DC supply voltage isrecommended.
4.8.1 Control Terminal Types
Illustration 4.24 and Illustration 4.25 show the removablefrequency converter connectors. Terminal functions anddefault settings are summarized in Table 4.1 and Table 4.2.
1
43
2
130B
B921
.12
Illustration 4.24 Control Terminal Locations
130B
B931
.11
12 13 18 19 27 29 32 33 20 37
39696861 42 50 53 54 55
1
32
Illustration 4.25 Terminal Numbers
• Connector 1 provides 4 programmable digitalinputs terminals, 2 extra digital terminalsprogrammable as either input or output, a24 V DC terminal supply voltage, and a commonfor optional customer supplied 24 V DC voltage.The frequency converter also provides a digitalinput for STO function.
• Connector 2 terminals (+)68 and (-)69 for RS485serial communication connection.
• Connector 3 provides 2 analog inputs, 1 analogoutput, 10 V DC supply voltage, and commonsfor the inputs and output.
• Connector 4 is a USB port available for use withthe MCT 10 Set-up Software.
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 33
4 4
Terminal description
Terminal ParameterDefaultsetting Description
Digital inputs/outputs
12, 13 – +24 V DC 24 V DC supplyvoltage for digitalinputs and externaltransducers. Maximumoutput current200 mA for all 24 Vloads.
18 5-10 [8] Start
Digital inputs.
19 5-11 [10] Reversing
32 5-14 [0] Nooperation
33 5-15 [0] Nooperation
27 5-12 [2] Coastinverse
For digital input oroutput. Default settingis input.29 5-13 [14] Jog
20 – Common for digitalinputs and 0 Vpotential for 24 Vsupply.
37 – STO Safe input.
Analog inputs/outputs
39 –
Common for analogoutput.
42 6-50 [0] Nooperation
Programmable analogoutput. 0–20 mA or4–20 mA at a
maximum of 500 Ω.
50 – +10 V DC 10 V DC analogsupply voltage forpotentiometer orthermistor. 15 mAmaximum.
53 6-1* Reference Analog input. Forvoltage or current.Switches A53 and A54select mA or V.
54 6-2* Feedback
55 –
Common for analoginput.
Table 4.1 Terminal Description Digital Inputs/Outputs,Analog Inputs/Outputs
Terminal description
Terminal ParameterDefaultsetting Description
Serial communication
61 –
Integrated RC-filter forcable shield forconnecting the shieldif EMC problemsoccur.
68 (+) 8-3* RS485 interface. Acontrol card switch isprovided fortermination resistance.
69 (-) 8-3*
Relays
01, 02, 03 5-40 [0][0] Nooperation
Form C relay output.For AC or DC voltageand resistive orinductive loads.
04, 05, 06 5-40 [1] [0] Nooperation
Table 4.2 Terminal Description Serial Communication
Additional terminals:
• 2 form C relay outputs. The location of theoutputs depends on the frequency converterconfiguration.
• Terminals on built-in optional equipment. See themanual provided with the equipment option.
Electrical Installation VLT® HVAC Drive FC 102
34 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
4.8.2 Wiring to Control Terminals
Control terminal connectors can be unplugged from thefrequency converter for ease of installation as shown inIllustration 4.26.
130B
D54
6.11
21
10 m
m[0
.4 in
ches
]12 13 18 19 27 29 32 33
Illustration 4.26 Connecting Control Wires
NOTICEKeep control wires as short as possible and separatethem from high-power cables to minimize interference.
1. Open the contact by inserting a small screwdriverinto the slot above the contact and push thescrewdriver slightly upwards.
2. Insert the bare control wire into the contact.
3. Remove the screwdriver to fasten the control wireinto the contact.
4. Ensure that the contact is firmly established andnot loose. Loose control wiring can be the sourceof equipment faults or reduced performance.
See chapter 8.5 Cable Specifications for control terminalwiring sizes and chapter 6 Application Set-up Examples fortypical control wiring connections.
4.8.3 Enabling Motor Operation (Terminal27)
A jumper wire may be required between terminal 12 (or13) and terminal 27 for the frequency converter to operatewhen using factory default programming values.
• Digital input terminal 27 is designed to receive a24 V DC external interlock command.
• When no interlock device is used, wire a jumperbetween control terminal 12 (recommended) or13 to terminal 27. This connection provides aninternal 24 V signal on terminal 27.
• When the status line at the bottom of the LCPreads AUTO REMOTE COAST, it indicates that theunit is ready to operate but is missing an inputsignal on terminal 27.
• When factory-installed optional equipment iswired to terminal 27, do not remove that wiring.
NOTICEThe frequency converter cannot operate without a signalon terminal 27, unless terminal 27 is reprogrammed.
4.8.4 Voltage/Current Input Selection(Switches)
The analog input terminals 53 and 54 allow setting ofinput signal to voltage (0–10 V) or current (0/4–20 mA).
Default parameter setting:• Terminal 53: Speed reference signal in open loop
(see parameter 16-61 Terminal 53 Switch Setting).
• Terminal 54: Feedback signal in closed loop (seeparameter 16-63 Terminal 54 Switch Setting).
NOTICEDisconnect power to the frequency converter beforechanging switch positions.
1. Remove the LCP (local control panel) (seeIllustration 4.27).
2. Remove any optional equipment covering theswitches.
3. Set switches A53 and A54 to select the signaltype. U selects voltage, I selects current.
130B
D53
0.10
12
N
O
VLT
BUSTER.OFF-ON
A53 A54U- I U- I
Illustration 4.27 Location of Terminal 53 and 54 Switches
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 35
4 4
4.8.5 Safe Torque Off (STO)
To run STO, extra wiring for the frequency converter isrequired. Refer to VLT® Frequency Converters Safe Torque OffOperating Guide for further information.
4.8.6 Configuring RS485 SerialCommunication
RS485 is a 2-wire bus interface compatible with multi-dropnetwork topology, and it contains the following features:
• Either Danfoss FC or Modbus RTU communicationprotocol, which are internal to the drive, can beused.
• Functions can be programmed remotely usingthe protocol software and RS485 connection or inparameter group 8-** Communications andOptions.
• Selecting a specific communication protocolchanges various default parameter settings tomatch the specifications of the protocol, makingmore protocol-specific parameters available.
• Option cards for the drive are available to providemore communication protocols. See the optioncard documentation for installation and operationinstructions.
• A switch (BUS TER) is provided on the controlcard for bus termination resistance. See Illustration 4.27.
For basic serial communication set-up, perform thefollowing steps:
1. Connect RS485 serial communication wiring toterminals (+)68 and (-)69.
1a Use shielded serial communication cable(recommended).
1b See chapter 4.3 Grounding for propergrounding.
2. Select the following parameter settings:
2a Protocol type in parameter 8-30 Protocol.
2b Drive address in parameter 8-31 Address.
2c Baud rate in parameter 8-32 Baud Rate.
61
68
69
+
130B
B489
.10
RS485
Illustration 4.28 Serial Communication Wiring Diagram
Electrical Installation VLT® HVAC Drive FC 102
36 Danfoss A/S © 02/2017 All rights reserved. MG16D402
44
4.9 Installation Check List
Before completing installation of the unit, inspect the entire installation as detailed in Table 4.3. Check and mark the itemswhen completed.
Inspect for Description Auxiliary equipment • Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers which may reside on
the input power side of the frequency converter or output side to the motor. Ensure that they are readyfor full-speed operation.
• Check the function and installation of any sensors used for feedback to the frequency converter.
• Remove any power factor correction capacitors on the motor.
• Adjust any power factor correction capacitors on the mains side and ensure that they are dampened.
Cable routing • Ensure that the motor wiring and control wiring are separated, shielded, or in 3 separate metallic conduitsfor high-frequency interference isolation.
Control wiring • Check for broken or damaged wires and loose connections.
• Check that the control wiring is isolated from power and motor wiring for noise immunity.
• Check the voltage source of the signals, if necessary.
The use of shielded cable or twisted pair is recommended. Ensure that the shield is terminated correctly.
Cooling clearance • Ensure that the top and bottom clearance is adequate to ensure proper airflow for cooling, see chapter 3.3 Mounting.
Ambient conditions • Check that requirements for ambient conditions are met.
Fusing and circuitbreakers
• Check for proper fusing or circuit breakers.
• Check that all fuses are inserted firmly and are in operational condition and that all circuit breakers are inthe open position.
Grounding • Check for sufficient ground connections and ensure that they are tight and free of oxidation.
• Grounding to conduit, or mounting the back panel to a metal surface, is not a suitable grounding.
Input and outputpower wiring
• Check for loose connections.
• Check that the motor and mains cables are in separate conduit or separated shielded cables.
Panel interior • Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion.
• Check that the unit is mounted on an unpainted, metal surface.
Switches • Ensure that all switch and disconnect settings are in the proper positions.
Vibration • Check that the unit is mounted solidly, or that shock mounts are used, as necessary.
• Check for an unusual amount of vibration.
Table 4.3 Installation Check List
CAUTIONPOTENTIAL HAZARD IN THE EVENT OF INTERNAL FAILURERisk of personal injury if the frequency converter is not properly closed.
• Before applying power, ensure that all safety covers are in place and securely fastened.
Electrical Installation Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 37
4 4
5 Commissioning
5.1 Safety Instructions
See chapter 2 Safety for general safety instructions.
WARNINGHIGH VOLTAGEFrequency converters contain high voltage whenconnected to AC mains input power. Failure to performinstallation, start-up, and maintenance by qualifiedpersonnel could result in death or serious injury.
• Installation, start-up, and maintenance must beperformed by qualified personnel only.
Before applying power:1. Verify that there is no voltage on input terminals
L1 (91), L2 (92), and L3 (93), phase-to-phase, andphase-to-ground.
2. Verify that there is no voltage on outputterminals 96 (U), 97 (V), and 98 (W), phase-to-phase, and phase-to-ground.
3. Confirm continuity of the motor by measuring Ωvalues on U-V (96–97), V-W (97–98), and W-U (98–96).
4. Check for proper grounding of the frequencyconverter and the motor.
5. Inspect the frequency converter for looseconnections on the terminals.
6. Check that all cable glands are firmly tightened.
7. Ensure that input power to the unit is OFF andlocked out. Do not rely on the frequencyconverter disconnect switches for input powerisolation.
8. Confirm that the supply voltage matches thevoltage of the frequency converter and themotor.
9. Close the door properly.
5.2 Applying Power
Apply power to the frequency converter using thefollowing steps:
1. Confirm that the input voltage is balanced within3%. If not, correct the input voltage imbalancebefore proceeding. Repeat this procedure afterthe voltage correction.
2. Ensure that any optional equipment wiringmatches the installation application.
3. Ensure that all operator devices are in the OFFposition. Close all panel doors and fasten coverssecurely.
4. Apply power to the unit. DO NOT start thefrequency converter now. For units with adisconnect switch, turn it to the ON position toapply power to the frequency converter.
5.3 Local Control Panel Operation
5.3.1 Local Control Panel
The local control panel (LCP) is the combined display andkeypad on the front of the unit.
The LCP has several user functions:
• Start, stop, and control speed when in localcontrol.
• Show operational data, status, warnings, andcautions.
• Program frequency converter functions.
• Manually reset the frequency converter after afault when auto reset is inactive.
An optional numeric LCP (NLCP) is also available. The NLCPoperates in a manner similar to the LCP. See the product-relevant programming guide for details on how to use theNLCP.
NOTICEFor commissioning via PC, install the MCT 10 Set-upSoftware. The software is available for download (basicversion) or for ordering (advanced version, orderingnumber 130B1000). For more information anddownloads, see drives.danfoss.com/downloads/pc-tools/.
5.3.2 Start-up Message
NOTICEDuring start-up, the LCP shows the message INITIALISING.When this message is no longer shown, the frequencyconverter is ready for operation. Adding or removingoptions can extend the duration of start-up.
Commissioning VLT® HVAC Drive FC 102
38 Danfoss A/S © 02/2017 All rights reserved. MG16D402
55
5.3.3 LCP Layout
The LCP is divided into 4 functional groups (seeIllustration 5.1).
A. Display area.
B. Display menu keys.
C. Navigation keys and indicator lights (LEDs).
D. Operation keys and reset.
130B
D59
8.10
AutoOn
ResetHandOn
O
Status QuickMenu
MainMenu
AlarmLog
Back
CancelInfoOK
Status 1(1)36.4 kW
Auto Remote Ramping
0.000
On
Alarm
Warn.
A
7.83 A799 RPM
B
C
D
53.2 %
1
2
3
4
5
6
78
9
10
11
12
13
14
15
16
17
18 19 20 21
Illustration 5.1 Local Control Panel (LCP)
A. Display areaThe display area is activated when the frequency converterreceives power from the mains voltage, a DC bus terminal,or a 24 V DC external supply.
The information shown on the LCP can be customized foruser application. Select options in the Quick Menu Q3-13Display Settings.
Display Parameter number Default setting
1 0-20 Speed [RPM]
2 0-21 Motor Current
3 0-22 Power [kW]
4 0-23 Frequency
5 0-24 Reference [%]
Table 5.1 Legend to Illustration 5.1, Display Area
B. Display menu keysMenu keys are used for menu access for parameter set-up,toggling through status display modes during normaloperation, and viewing fault log data.
Key Function
6 Status Shows operational information.
7 Quick Menu Allows access to programming parametersfor initial set-up instructions and manydetailed application instructions.
8 Main Menu Allows access to all programmingparameters.
9 Alarm Log Shows a list of current warnings, the last10 alarms, and the maintenance log.
Table 5.2 Legend to Illustration 5.1, Display Menu Keys
C. Navigation keys and indicator lights (LEDs)Navigation keys are used for programming functions andmoving the display cursor. The navigation keys alsoprovide speed control in local operation. There are also 3frequency converter status indicator lights in this area.
Key Function
10 Back Reverts to the previous step or list in themenu structure.
11 Cancel Cancels the last change or command as longas the display mode has not changed.
12 Info Press for a definition of the function beingshown.
13 Navigationkeys
Use the 4 navigation keys to move betweenitems in the menu.
14 OK Use to access parameter groups or to enablea selection.
Table 5.3 Legend to Illustration 5.1, Navigation Keys
Indicator LED Function
15 On Green The ON LED activates when thefrequency converter receivespower from the mains voltage, aDC bus terminal, or a 24 V externalsupply.
16 Warn Yellow When warning conditions are met,the yellow WARN LED comes onand text appears in the displayarea identifying the problem.
17 Alarm Red A fault condition causes the redalarm LED to flash and an alarmtext is shown.
Table 5.4 Legend to Illustration 5.1, Indicator Lights (LEDs)
Commissioning Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 39
5 5
D. Operation keys and resetOperation keys are at the bottom of the LCP.
Key Function
18 Hand On Starts the frequency converter in localcontrol.
• An external stop signal by control inputor serial communication overrides thelocal hand on.
19 Off Stops the motor but does not remove powerto the frequency converter.
20 Auto On Puts the system in remote operational mode.
• Responds to an external start commandby control terminals or serial communi-cation.
21 Reset Resets the frequency converter manuallyafter a fault has been cleared.
Table 5.5 Legend to Illustration 5.1, Operation Keys and Reset
NOTICEThe display contrast can be adjusted by pressing [Status]and the []/[] keys.
5.3.4 Parameter Settings
Establishing the correct programming for applicationsoften requires setting functions in several relatedparameters. Parameter details are provided inchapter 9.2 Parameter Menu Structure.
Programming data is stored internally in the frequencyconverter.
• For back-up, upload data to the LCP memory.
• To download data to another frequencyconverter, connect the LCP to that unit anddownload the stored settings.
• Restoring factory default settings does notchange data stored in the LCP memory.
5.3.5 Uploading/Downloading Data to/fromthe LCP
1. Press [Off] to stop the motor before uploading ordownloading data.
2. Press [Main Menu], parameter 0-50 LCP Copy andpress [OK].
3. Select [1] All to LCP to upload data to the LCP, orselect [2] All from LCP to download data from theLCP.
4. Press [OK]. A progress bar shows the uploading ordownloading progress.
5. Press [Hand On] or [Auto On] to return to normaloperation.
5.3.6 Changing Parameter Settings
Parameter settings can be accessed and changed from theQuick Menu or from the Main Menu. The Quick Menu onlygives access to a limited number of parameters.
1. Press [Quick Menu] or [Main Menu] on the LCP.
2. Press [] [] to browse through the parametergroups.
3. Press [OK] to select a parameter group.
4. Press [] [] to browse through the parameters.
5. Press [OK] to select a parameter.
6. Press [] [] to change the value of a parametersetting.
7. Press [] [] to shift digit when a decimalparameter is in the editing state.
8. Press [OK] to accept the change.
9. Press either [Back] twice to enter Status, or press[Main Menu] once to enter the Main Menu.
View changesQuick Menu Q5 - Changes Made lists all parameterschanged from default settings.
• The list only shows parameters which have beenchanged in the current edit set-up.
• Parameters which have been reset to defaultvalues are not listed.
• The message Empty indicates that no parametershave been changed.
5.3.7 Restoring Default Settings
NOTICERisk of losing programming, motor data, localization, andmonitoring records by restoration of default settings. Toprovide a back-up, upload data to the LCP before initiali-zation.
Restoring the default parameter settings is done by initiali-zation of the frequency converter. Initialization is carriedout through parameter 14-22 Operation Mode(recommended) or manually.
• Initialization using parameter 14-22 OperationMode does not reset frequency converter settings,such as hours run, serial communicationselections, personal menu settings, fault log,alarm log, and other monitoring functions.
• Manual initialization erases all motor,programming, localization, and monitoring dataand restores factory default settings.
Commissioning VLT® HVAC Drive FC 102
40 Danfoss A/S © 02/2017 All rights reserved. MG16D402
55
Recommended initialization procedure viaparameter 14-22 Operation Mode
1. Press [Main Menu] twice to access parameters.
2. Scroll to parameter 14-22 Operation Mode andpress [OK].
3. Scroll to [2] Initialisation and press [OK].
4. Remove power to the unit and wait for thedisplay to turn off.
5. Apply power to the unit.
Default parameter settings are restored during start-up.The restore may take slightly longer than normal.
1. Alarm 80, Drive initialised is shown.
2. Press [Reset] to return to operating mode.
Manual initialization procedure
1. Remove power to the unit and wait for thedisplay to turn off.
2. Press and hold [Status], [Main Menu], and [OK] atthe same time while applying power to the unit.Press the keys for approximately 5 s, or until aclick is heard and the fan starts.
Factory default parameter settings are restored duringstart-up. The restore may take slightly longer than normal.
Manual initialization does not reset the followingfrequency converter information:
• Parameter 15-00 Operating hours
• Parameter 15-03 Power Up's
• Parameter 15-04 Over Temp's
• Parameter 15-05 Over Volt's
5.4 Basic Programming
5.4.1 Commissioning with SmartStart
The SmartStart wizard enables fast configuration of basicmotor and application parameters.
• SmartStart starts automatically at first power-upor after initialization of the frequency converter.
• Follow the on-screen instructions to complete thecommissioning of the frequency converter.Always reactivate SmartStart by selecting QuickMenu Q4 - SmartStart.
• For commissioning without use of the SmartStartwizard, refer to chapter 5.4.2 Commissioning via[Main Menu] or the programming guide.
NOTICEMotor data is required for the SmartStart set-up. Therequired data is normally available on the motornameplate.
5.4.2 Commissioning via [Main Menu]
Recommended parameter settings are intended for start-up and check-out purposes. Application settings may vary.
Enter data with power ON, but before operating thefrequency converter.
1. Press [Main Menu] on the LCP.
2. Press the navigation keys to scroll to parametergroup 0-** Operation/Display and press [OK].
130B
P066
.12
Keypad Set-UpParameter Data SetParameter Data CheckDrive Information
18.4% 5.22AMain Menu
1(1)
07 Motor SetupIllustration 5.2 Main Menu
3. Press the navigation keys to scroll to parametergroup 0-0* Basic Settings and press [OK].
0-**Operation / Display0.0%
0-0* Basic Settings0-1* Set-up Operations0-2* LCP Display0-3* LCP Custom Readout
0.00A 1(1)
130B
P087
.10
Illustration 5.3 Operation/Display
4. Press the navigation keys to scroll toparameter 0-03 Regional Settings and press [OK].
0-0*Basic Settings0.0%
0-03 Regional Settings
[0] International
0.00A 1(1)
130B
P088
.10
Illustration 5.4 Basic Settings
Commissioning Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 41
5 5
5. Press the navigation keys to select [0] Interna-tional or [1] North America as appropriate andpress [OK]. (This selection changes the defaultsettings for several basic parameters).
6. Press [Main Menu] on the LCP.
7. Press the navigation keys to scroll toparameter 0-01 Language.
8. Select the language and press [OK].
9. If a jumper wire is in place between controlterminals 12 and 27, leaveparameter 5-12 Terminal 27 Digital Input at factorydefault. Otherwise, select [0] No Operation inparameter 5-12 Terminal 27 Digital Input.
10. Make the application-specific settings in thefollowing parameters:
10a Parameter 3-02 Minimum Reference.
10b Parameter 3-03 Maximum Reference.
10c Parameter 3-41 Ramp 1 Ramp Up Time.
10d Parameter 3-42 Ramp 1 Ramp DownTime.
10e Parameter 3-13 Reference Site. Linked toHand/Auto Local Remote.
5.5 Checking Motor Rotation
The direction of rotation can be changed by switching 2phases in the motor cable, or by changing the setting ofparameter 4-10 Motor Speed Direction.
• Terminal U/T1/96 connected to U-phase.
• Terminal V/T2/97 connected to V-phase.
• Terminal W/T3/98 connected to W-phase.
175H
A03
6.11
U1 V1 W1
96 97 98
FC
MotorU2 V2 W2
U1 V1 W1
96 97 98
FC
MotorU2 V2 W2
Illustration 5.5 Wiring for Changing Motor Direction
Perform a motor rotation check using parameter 1-28 MotorRotation Check and follow the steps shown in the display.
Commissioning VLT® HVAC Drive FC 102
42 Danfoss A/S © 02/2017 All rights reserved. MG16D402
55
5.6 Local-control Test
1. Press [Hand On] to provide a local start commandto the frequency converter.
2. Press [] to accelerate the frequency converter tofull speed. Moving the cursor left of the decimalpoint provides quicker input changes.
3. Note any acceleration problems.
4. Press [Off]. Note any deceleration problems.
If acceleration or deceleration problems occur, seechapter 7.7 Troubleshooting. See chapter 7.6 List of Warningsand Alarms for resetting the frequency converter after atrip.
5.7 System Start-up
The procedure in this section requires user-wiring andapplication programming to be completed. The followingprocedure is recommended after application set-up iscompleted.
1. Press [Auto On].
2. Apply an external run command.
3. Adjust the speed reference throughout the speedrange.
4. Remove the external run command.
5. Check the sound and vibration levels of themotor to ensure that the system is working asintended.
If warnings or alarms occur, see chapter 7.6 List of Warningsand Alarms.
Commissioning Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 43
5 5
6 Application Set-up Examples
6.1 Introduction
The examples in this section are intended as a quickreference for common applications.
• Parameter settings are the regional default valuesunless otherwise indicated (selected inparameter 0-03 Regional Settings).
• Parameters associated with the terminals andtheir settings are shown next to the drawings.
• Where switch settings for analog terminals A53 orA54 are required, these settings are also shown.
NOTICEWhen the optional STO feature is used, a jumper wiremay be required between terminal 12 (or 13) andterminal 37 for the frequency converter to operate withfactory default programming values.
6.2 Application Examples
6.2.1 Automatic Motor Adaptation (AMA)
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130B
B929
.10 Function Setting
Parameter 1-29 Automatic MotorAdaptation(AMA)
[1] EnablecompleteAMA
Parameter 5-12 Terminal 27Digital Input
[2]* Coastinverse
* = Default value
Notes/comments:Parameter group 1-2* MotorData must be set according tomotor.D IN 37 is an option.
Table 6.1 AMA with T27 Connected
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130B
B930
.10 Function Setting
Parameter 1-29 Automatic MotorAdaptation(AMA)
[1] EnablecompleteAMA
Parameter 5-12 Terminal 27Digital Input
[0] Nooperation
* = Default value
Notes/comments:Parameter group 1–2* MotorData must be set according tomotor.D IN 37 is an option.
Table 6.2 AMA without T27 Connected
6.2.2 Speed
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
-10 - +10V
+
-
130B
B926
.10 Function Setting
Parameter 6-10 Terminal 53 LowVoltage
0.07 V*
Parameter 6-11 Terminal 53 HighVoltage
10 V*
Parameter 6-14 Terminal 53 LowRef./Feedb. Value
0 Hz
Parameter 6-15 Terminal 53 HighRef./Feedb. Value
50 Hz
* = Default value
Notes/comments:D IN 37 is an option.
Table 6.3 Analog Speed Reference (Voltage)
Application Set-up Examples VLT® HVAC Drive FC 102
44 Danfoss A/S © 02/2017 All rights reserved. MG16D402
66
Parameters
130B
B927
.10
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 VA IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
4 - 20mA
+
-
Function Setting
Parameter 6-12 Terminal 53 LowCurrent
4 mA*
Parameter 6-13 Terminal 53 HighCurrent
20 mA*
Parameter 6-14 Terminal 53 LowRef./Feedb. Value
0 Hz
Parameter 6-15 Terminal 53 HighRef./Feedb. Value
50 Hz
* = Default value
Notes/comments:D IN 37 is an option.
Table 6.4 Analog Speed Reference (Current)
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
≈ 5kΩ
130B
B683
.10 Function Setting
Parameter 6-10 Terminal 53 LowVoltage
0.07 V*
Parameter 6-11 Terminal 53 HighVoltage
10 V*
Parameter 6-14 Terminal 53 LowRef./Feedb. Value
0 Hz
Parameter 6-15 Terminal 53 HighRef./Feedb. Value
1500 Hz
* = Default value
Notes/comments:D IN 37 is an option.
Table 6.5 Speed Reference (Using a Manual Potentiometer)
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 VA IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130B
B804
.11
Function Setting
Parameter 5-10 Terminal 18Digital Input
[8]* Start
Parameter 5-12 Terminal 27Digital Input
[19] FreezeReference
Parameter 5-13 Terminal 29Digital Input
[21] Speed Up
Parameter 5-14 Terminal 32Digital Input
[22] SpeedDown
* = Default value
Notes/comments:D IN 37 is an option.
Table 6.6 Speed Up/Down
130B
B840
.12Speed
Reference
Start (18)
Freeze ref (27)
Speed up (29)
Speed down (32)
Illustration 6.1 Speed Up/Down
Application Set-up Examples Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 45
6 6
6.2.3 Start/Stop
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130B
B802
.10 Function Setting
Parameter 5-10 Terminal 18Digital Input
[8]* Start
Parameter 5-12 Terminal 27Digital Input
[0] Nooperation
Parameter 5-19 Terminal 37 SafeStop
[1] Safe StopAlarm
* = Default value
Notes/comments:If parameter 5-12 Terminal 27Digital Input is set to [0] Nooperation, a jumper wire toterminal 27 is not needed.D IN 37 is an option.
Table 6.7 Start/Stop Command with STO
130B
B805
.12
Speed
Start/Stop (18)
Illustration 6.2 Start/Stop Command with STO
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130B
B803
.10
Function Setting
Parameter 5-10 Terminal 18Digital Input
[9] LatchedStart
Parameter 5-12 Terminal 27Digital Input
[6] StopInverse
* = Default value
Notes/comments:If parameter 5-12 Terminal 27Digital Input is set to [0] Nooperation, a jumper wire toterminal 27 is not needed.D IN 37 is an option.
Table 6.8 Pulse Start/Stop
Speed
130B
B806
.10
Latched Start (18)
Stop Inverse (27)
Illustration 6.3 Latched Start/Stop Inverse
Application Set-up Examples VLT® HVAC Drive FC 102
46 Danfoss A/S © 02/2017 All rights reserved. MG16D402
66
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 VA IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
130B
B934
.11
Function Setting
Parameter 5-10 Terminal 18 DigitalInput
[8] Start
Parameter 5-11 Terminal 19 DigitalInput
[10]*Reversing
Parameter 5-12 Terminal 27 DigitalInput
[0] Nooperation
Parameter 5-14 Terminal 32 DigitalInput
[16] Presetref bit 0
Parameter 5-15 Terminal 33 DigitalInput
[17] Presetref bit 1
Parameter 3-10 Preset Reference
Preset ref. 0Preset ref. 1Preset ref. 2Preset ref. 3
25%50%75%100%
* = Default value
Notes/comments:D IN 37 is an option.
Table 6.9 Start/Stop with Reversing and 4 Preset Speeds
6.2.4 External Alarm Reset
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 VA IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130B
B928
.11
Function Setting
Parameter 5-11 Terminal 19Digital Input
[1] Reset
* = Default value
Notes/comments:D IN 37 is an option.
Table 6.10 External Alarm Reset
Application Set-up Examples Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 47
6 6
6.2.5 RS485
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
-
616869
RS-485
+
130B
B685
.10 Function Setting
Parameter 8-30 Protocol FC*
Parameter 8-31 Address
1*
Parameter 8-32 Baud Rate
9600*
* = Default value
Notes/comments:Select protocol, address, andbaud rate in these parameters.D IN 37 is an option.
Table 6.11 RS485 Network Connection
6.2.6 Motor Thermistor
WARNINGTHERMISTOR INSULATIONRisk of personal injury or equipment damage.
• Use only thermistors with reinforced or doubleinsulation to meet PELV insulationrequirements.
Parameters
130B
B686
.12
VLT
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 VA IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
D IN 37
Function Setting
Parameter 1-90 Motor ThermalProtection
[2] Thermistortrip
Parameter 1-93 Thermistor Source
[1] Analoginput 53
* = Default value
Notes/comments:If only a warning is desired, setparameter parameter 1-90 MotorThermal Protection to [1]Thermistor warning.D IN 37 is an option.
Table 6.12 Motor Thermistor
Application Set-up Examples VLT® HVAC Drive FC 102
48 Danfoss A/S © 02/2017 All rights reserved. MG16D402
66
7 Maintenance, Diagnostics, and Troubleshooting
7.1 Introduction
This chapter includes:• Maintenance and service guidelines.
• Status messages.
• Warnings and alarms.
• Basic troubleshooting.
7.2 Maintenance and Service
Under normal operating conditions and load profiles, thefrequency converter is maintenance-free throughout itsdesigned lifetime. To prevent breakdown, danger, anddamage, examine the frequency converter at regularintervals depending on the operating conditions. Replaceworn or damaged parts with original spare parts orstandard parts. For service and support, refer towww.danfoss.com/contact/sales_and_services/.
WARNINGUNINTENDED STARTWhen the frequency converter is connected to AC mains,DC supply, or load sharing, the motor can start at anytime. Unintended start during programming, service, orrepair work can result in death, serious injury, orproperty damage. The motor can start with an externalswitch, a fieldbus command, an input reference signalfrom the LCP or LOP, via remote operation using MCT 10Set-up Software, or after a cleared fault condition.
To prevent unintended motor start:• Press [Off/Reset] on the LCP before
programming parameters.
• Disconnect the frequency converter from themains.
• Completely wire and assemble the frequencyconverter, motor, and any driven equipmentbefore connecting the frequency converter toAC mains, DC supply, or load sharing.
7.3 Heat Sink Access Panel
7.3.1 Removing the Heat Sink Access Panel
The frequency converter has an optional access panel foraccessing the heat sink.
Illustration 7.1 Heat Sink Access Panel
1. Do not run the frequency converter whileremoving the heat sink access panel.
2. If the frequency converter is mounted on a wall,or its back is otherwise inaccessible, reposition itto provide full access.
3. Remove the screws (3 mm (0.12 in) internal hex)connecting the access panel to the back of theenclosure. There are 5 or 9 screws depending onthe size of the frequency converter.
Reinstall in reverse order of this procedure and tightenfasteners according to chapter 8.8 Connection TighteningTorques.
Maintenance, Diagnostics, a... Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 49
7 7
7.4 Status Messages
When the frequency converter is in status mode, statusmessages are generated automatically and appear in thebottom line of the display (see Illustration 7.2).
Status799RPM 7.83A 36.4kW
0.000
53.2%
1(1)
AutoHandO
RemoteLocal
RampingStopRunningJogging...Stand-by
130B
B037
.11
1
2
3
1 Operating mode (see Table 7.1)
2 Reference site (see Table 7.2)
3 Operation status (see Table 7.3)
Illustration 7.2 Status Display
Table 7.1 to Table 7.3 describe the status messages shown.
Off The frequency converter does not react to anycontrol signal until [Auto On] or [Hand On] ispressed.
Auto On The frequency converter is controlled from thecontrol terminals and/or the serial communi-cation.
Hand On Use the navigation keys on the LCP to controlthe frequency converter. Stop commands,reset, reversing, DC brake, and other signalsapplied to the control terminals override localcontrol.
Table 7.1 Operating Mode
Remote The speed reference is given from externalsignals, serial communication, or internalpreset references.
Local The frequency converter uses [Hand On]control or reference values from the LCP.
Table 7.2 Reference Site
AC Brake Parameter 2-16 AC brake Max. Current wasselected in parameter 2-10 Brake Function. TheAC brake overmagnetizes the motor toachieve a controlled slow-down.
AMA finish OK Automatic motor adaptation (AMA) wascarried out successfully.
AMA ready AMA is ready to start. Press [Hand On] to start.
AMA running AMA process is in progress.
Braking The brake chopper is in operation. Generativeenergy is absorbed by the brake resistor.
Braking max. The brake chopper is in operation. The powerlimit for the brake resistor defined inparameter 2-12 Brake Power Limit (kW) hasbeen reached.
Coast • Coast inverse was selected as a function fora digital input (parameter group 5-1* DigitalInputs). The corresponding terminal is notconnected.
• Coast activated by serial communication.
Ctrl. ramp-down [1] Control ramp-down was selected inparameter 14-10 Mains Failure.
• The mains voltage is below the value setin parameter 14-11 Mains Voltage at MainsFault at mains fault.
• The frequency converter ramps down themotor using a controlled ramp down.
Current High The frequency converter output current isabove the limit set in parameter 4-51 WarningCurrent High.
Current Low The frequency converter output current isbelow the limit set in parameter 4-52 WarningSpeed Low.
DC Hold [1] DC hold is selected inparameter 1-80 Function at Stop and a stopcommand is active. The motor is held by a DCcurrent set in parameter 2-00 DC Hold/PreheatCurrent.
DC Stop The motor is held with a DC current(parameter 2-01 DC Brake Current) for aspecified time (parameter 2-02 DC BrakingTime).
• The DC brake cut-in speed is reached inparameter 2-03 DC Brake Cut In Speed[RPM], and a stop command is active.
• DC brake (inverse) is selected as a functionfor a digital input (parameter group 5-1*Digital Inputs). The corresponding terminalis not active.
• The DC brake is activated via serialcommunication.
Feedback high The sum of all active feedbacks is above thefeedback limit set in parameter 4-57 WarningFeedback High.
Feedback low The sum of all active feedbacks is below thefeedback limit set in parameter 4-56 WarningFeedback Low.
Maintenance, Diagnostics, a... VLT® HVAC Drive FC 102
50 Danfoss A/S © 02/2017 All rights reserved. MG16D402
77
Freeze output The remote reference, which holds the presentspeed, is active.
• Freeze output was selected as a functionfor a digital input (parameter group 5-1*Digital Inputs). The corresponding terminalis active. Speed control is only possible viathe terminal functions speed up and speeddown.
• Hold ramp is activated via serial communi-cation.
Freeze outputrequest
A freeze output command was given, but themotor remains stopped until a run permissivesignal is received.
Freeze ref. Freeze reference was selected as a function fora digital input (parameter group 5-1* DigitalInputs). The corresponding terminal is active.The frequency converter saves the actualreference. Changing the reference is now onlypossible via terminal functions speed up andspeed down.
Jog request A jog command was given, but the motorremains stopped until a run permissive signalis received via a digital input.
Jogging The motor runs as programmed inparameter 3-19 Jog Speed [RPM].
• Jog was selected as a function for a digitalinput (parameter group 5-1* Digital Inputs).The corresponding terminal (for exampleterminal 29) is active.
• The jog function is activated via the serialcommunication.
• The jog function was selected as a reactionfor a monitoring function (for example Nosignal). The monitoring function is active.
Motor check In parameter 1-80 Function at Stop, [2] Motorcheck was selected. A stop command is active.To ensure that a motor is connected to thefrequency converter, a permanent test currentis applied to the motor.
OVC control Overvoltage control was activated inparameter 2-17 Over-voltage Control, [2]Enabled. The connected motor supplies thefrequency converter with generative energy.The overvoltage control adjusts the V/Hz ratioto run the motor in controlled mode and toprevent the frequency converter from tripping.
PowerUnit Off (Only frequency converters with a 24 Vexternal supply installed).Mains supply to the frequency converter wasremoved, and the control card is supplied bythe external 24 V.
Protection md Protection mode is active. The unit hasdetected a critical status (overcurrent orovervoltage).
• To avoid tripping, switching frequency isreduced to 4 kHz.
• If possible, protection mode ends afterapproximately 10 s.
• Protection mode can be restricted inparameter 14-26 Trip Delay at Inverter Fault.
Qstop The motor is decelerating usingparameter 3-81 Quick Stop Ramp Time.
• Quick stop inverse was selected as afunction for a digital input (parametergroup 5-1* Digital Inputs). Thecorresponding terminal is not active.
• The quick stop function was activated viaserial communication.
Ramping The motor is accelerating/decelerating usingthe active ramp up/down. The reference, alimit value, or a standstill is not yet reached.
Ref. high The sum of all active references is above thereference limit set in parameter 4-55 WarningReference High.
Ref. low The sum of all active references is below thereference limit set in parameter 4-54 WarningReference Low.
Run on ref. The frequency converter is running in thereference range. The feedback value matchesthe setpoint value.
Run request A start command was given, but the motorremains stopped until a run permissive signalis received via digital input.
Running The frequency converter drives the motor.
Sleep Mode The energy-saving function is enabled. Themotor has stopped, but restarts automaticallywhen required.
Speed high Motor speed is above the value set inparameter 4-53 Warning Speed High.
Speed low Motor speed is below the value set inparameter 4-52 Warning Speed Low.
Standby In auto-on mode, the frequency converterstarts the motor with a start signal from adigital input or serial communication.
Start delay In parameter 1-71 Start Delay, a delay startingtime was set. A start command is activatedand the motor starts after the start delay timeexpires.
Start fwd/rev Start forward and start reverse were selectedas functions for 2 different digital inputs(parameter group 5-1* Digital Inputs). Themotor starts in forward or reverse directiondepending on which corresponding terminal isactivated.
Maintenance, Diagnostics, a... Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 51
7 7
Stop The frequency converter has received a stopcommand from the LCP, digital input, or serialcommunication.
Trip An alarm occurred and the motor is stopped.Once the alarm is cleared, the frequencyconverter can be reset manually by pressing[Reset], or remotely by control terminals orserial communication.
Trip lock An alarm occurred and the motor is stopped.Once the alarm is cleared, cycle power to thefrequency converter. The frequency convertercan then be reset manually by pressing[Reset], or remotely by control terminals orserial communication.
Table 7.3 Operation Status
NOTICEIn auto/remote mode, the frequency converter requiresexternal commands to execute functions.
7.5 Warning and Alarm Types
WarningsA warning is issued when an alarm condition is impendingor when an abnormal operating condition is present. Thewarning may result in the frequency converter issuing analarm. A warning clears itself when the abnormal conditionceases.
AlarmsAn alarm indicates a fault that requires immediateattention. The fault always triggers a trip or a trip lock.Reset the system after an alarm.
TripAn alarm is issued when the frequency converter istripped, meaning that the frequency converter suspendsoperation to prevent frequency converter or systemdamage. The motor coasts to a stop. The frequencyconverter logic continues to operate and monitor thefrequency converter status. After the fault condition isremedied, the frequency converter can be reset. It is thenready to restart operation.
Resetting the frequency converter after trip/trip lock
A trip can be reset in any of 4 ways:• Press [Reset] on the LCP.
• Digital reset input command.
• Serial communication reset input command.
• Auto reset.
Trip lockInput power is cycled. The motor coasts to a stop. Thefrequency converter continues to monitor the frequencyconverter status.
1. Remove input power to the frequency converter.
2. Correct the cause of the fault.
3. Reset the frequency converter.
• A warning is shown in the LCP along with thewarning number.
• An alarm flashes along with the alarm number.
130B
P086
.12
Status0.0Hz 0.000kW 0.00A
0.0Hz0
Earth Fault [A14]Auto Remote Trip
1(1)
Illustration 7.3 Alarm Display Example
In addition to the text and alarm code in the LCP, there are3 status indicator lights (LEDs).
Back
CancelInfoOKOn
Alarm
Warn.
130B
B467
.11
Warning LED Alarm LED
Warning On Off
Alarm Off On (flashing)
Trip lock On On (flashing)
Illustration 7.4 Status Indicator Lights (LEDs)
Maintenance, Diagnostics, a... VLT® HVAC Drive FC 102
52 Danfoss A/S © 02/2017 All rights reserved. MG16D402
77
7.6 List of Warnings and Alarms
The following warning and alarm information defines eachwarning or alarm condition, provides the probable causefor the condition, and details a remedy or troubleshootingprocedure.
WARNING 1, 10 Volts lowThe control card voltage is less than 10 V from terminal 50.Remove some of the load from terminal 50, as the 10 Vsupply is overloaded. Maximum 15 mA or minimum 590 Ω.
A short circuit in a connected potentiometer or incorrectwiring of the potentiometer can cause this condition.
Troubleshooting• Remove the wiring from terminal 50. If the
warning clears, the problem is with the wiring. Ifthe warning does not clear, replace the controlcard.
WARNING/ALARM 2, Live zero errorThis warning or alarm only appears if programmed inparameter 6-01 Live Zero Timeout Function. The signal on 1of the analog inputs is less than 50% of the minimumvalue programmed for that input. Broken wiring or a faultydevice sending the signal can cause this condition.
Troubleshooting• Check connections on all analog mains terminals.
- Control card terminals 53 and 54 forsignals, terminal 55 common.
- VLT® General Purpose I/O MCB 101terminals 11 and 12 for signals, terminal10 common.
- VLT® Analog I/O Option MCB 109terminals 1, 3, and 5 for signals,terminals 2, 4, and 6 common.
• Check that the drive programming and switchsettings match the analog signal type.
• Perform an input terminal signal test.
WARNING/ALARM 3, No motorNo motor is connected to the output of the frequencyconverter.
WARNING/ALARM 4, Mains phase lossA phase is missing on the supply side, or the mainsvoltage imbalance is too high. This message also appearsfor a fault in the input rectifier. Options are programmed inparameter 14-12 Function at Mains Imbalance.
Troubleshooting• Check the supply voltage and supply currents to
the frequency converter.
WARNING 5, DC link voltage highThe DC-link voltage (DC) is higher than the high-voltagewarning limit. The limit depends on the drive voltagerating. The unit is still active.
WARNING 6, DC link voltage lowThe DC-link voltage (DC) is lower than the low voltagewarning limit. The limit depends on the drive voltagerating. The unit is still active.
WARNING/ALARM 7, DC overvoltageIf the DC-link voltage exceeds the limit, the frequencyconverter trips after a certain time.
Troubleshooting• Connect a brake resistor.
• Extend the ramp time.
• Change the ramp type.
• Activate the functions in parameter 2-10 BrakeFunction.
• Increase parameter 14-26 Trip Delay at InverterFault.
• If the alarm/warning occurs during a power sag,use kinetic back-up (parameter 14-10 MainsFailure).
WARNING/ALARM 8, DC under voltageIf the DC-link voltage drops below the undervoltage limit,the drive checks for 24 V DC back-up supply. If no 24 V DCback-up supply is connected, the drive trips after a fixedtime delay. The time delay varies with unit size.
Troubleshooting• Check that the supply voltage matches the drive
voltage.
• Perform an input voltage test.
• Perform a soft-charge circuit test.
WARNING/ALARM 9, Inverter overloadThe frequency converter has run with more than 100%overload for too long and is about to cut out. The counterfor electronic thermal inverter protection issues a warningat 98% and trips at 100% with an alarm. The frequencyconverter cannot be reset until the counter is below 90%.
Troubleshooting• Compare the output current shown on the LCP
with the frequency converter rated current.
• Compare the output current shown on the LCPwith the measured motor current.
• Show the thermal frequency converter load onthe LCP and monitor the value. When runningabove the frequency converter continuouscurrent rating, the counter increases. Whenrunning below the frequency convertercontinuous current rating, the counter decreases.
Maintenance, Diagnostics, a... Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 53
7 7
WARNING/ALARM 10, Motor overload temperatureAccording to the electronic thermal protection (ETR), themotor is too hot.
Select 1 of these options:• The frequency converter issues a warning or an
alarm when the counter is >90% ifparameter 1-90 Motor Thermal Protection is set towarning options.
• The frequency converter trips when the counterreaches 100% if parameter 1-90 Motor ThermalProtection is set to trip options.
The fault occurs when the motor runs with more than100% overload for too long.
Troubleshooting• Check for motor overheating.
• Check if the motor is mechanically overloaded.
• Check that the motor current set inparameter 1-24 Motor Current is correct.
• Ensure that the motor data in parameters 1-20 to1-25 is set correctly.
• If an external fan is in use, check that it isselected in parameter 1-91 Motor External Fan.
• Running AMA in parameter 1-29 Automatic MotorAdaptation (AMA) tunes the frequency converterto the motor more accurately and reducesthermal loading.
WARNING/ALARM 11, Motor thermistor overtempCheck whether the thermistor is disconnected. Selectwhether the frequency converter issues a warning or analarm in parameter 1-90 Motor Thermal Protection.
Troubleshooting• Check for motor overheating.
• Check if the motor is mechanically overloaded.
• When using terminal 53 or 54, check that thethermistor is connected correctly between eitherterminal 53 or 54 (analog voltage input) andterminal 50 (+10 V supply). Also check that theterminal switch for 53 or 54 is set for voltage.Check that parameter 1-93 Thermistor Resourceselects terminal 53 or 54.
• When using terminal 18, 19, 31, 32, or 33 (digitalinputs), check that the thermistor is connectedcorrectly between the digital input terminal used(digital input PNP only) and terminal 50. Selectthe terminal to use in parameter 1-93 ThermistorResource.
WARNING/ALARM 12, Torque limitThe torque has exceeded the value inparameter 4-16 Torque Limit Motor Mode or the value inparameter 4-17 Torque Limit Generator Mode.Parameter 14-25 Trip Delay at Torque Limit can change thiswarning from a warning-only condition to a warningfollowed by an alarm.
Troubleshooting• If the motor torque limit is exceeded during
ramp-up, extend the ramp-up time.
• If the generator torque limit is exceeded duringramp-down, extend the ramp-down time.
• If torque limit occurs while running, increase thetorque limit. Make sure that the system canoperate safely at a higher torque.
• Check the application for excessive current drawon the motor.
WARNING/ALARM 13, Over currentThe inverter peak current limit (approximately 200% of therated current) is exceeded. The warning lasts approximately1.5 s, then the frequency converter trips and issues analarm. Shock loading or quick acceleration with high-inertialoads can cause this fault. If the acceleration during ramp-up is quick, the fault can also appear after kinetic back-up.If extended mechanical brake control is selected, a trip canbe reset externally.
Troubleshooting• Remove the power and check if the motor shaft
can be turned.
• Check that the motor size matches the frequencyconverter.
• Check that the motor data is correct inparameters 1-20 to 1-25.
ALARM 14, Earth (ground) faultThere is current from the output phases to ground, eitherin the cable between the frequency converter and themotor or in the motor itself.
Troubleshooting• Remove power to the frequency converter and
repair the ground fault.
• Check for ground faults in the motor bymeasuring the resistance to ground of the motorleads and the motor with a megohmmeter.
• Perform current sensor test.
Maintenance, Diagnostics, a... VLT® HVAC Drive FC 102
54 Danfoss A/S © 02/2017 All rights reserved. MG16D402
77
ALARM 15, Hardware mismatchA fitted option is not operational with the present controlcard hardware or software.
Record the value of the following parameters and contactDanfoss.
• Parameter 15-40 FC Type.
• Parameter 15-41 Power Section.
• Parameter 15-42 Voltage.
• Parameter 15-43 Software Version.
• Parameter 15-45 Actual Typecode String.
• Parameter 15-49 SW ID Control Card.
• Parameter 15-50 SW ID Power Card.
• Parameter 15-60 Option Mounted.
• Parameter 15-61 Option SW Version (for eachoption slot).
ALARM 16, Short circuitThere is short-circuiting in the motor or motor wiring.
Troubleshooting• Remove the power to the frequency converter
and repair the short circuit.
WARNINGHIGH VOLTAGEFrequency converters contain high voltage whenconnected to AC mains input, DC supply, or load sharing.Failure to use qualified personnel to install, start up, andmaintain the frequency converter can result in death orserious injury.
• Disconnect power before proceeding.
WARNING/ALARM 17, Control word timeoutThere is no communication to the frequency converter.The warning is only active when parameter 8-04 ControlWord Timeout Function is NOT set to [0] Off.If parameter 8-04 Control Word Timeout Function is set to [5]Stop and trip, a warning appears, and the frequencyconverter ramps down to a stop and shows an alarm.
Troubleshooting• Check the connections on the serial communi-
cation cable.
• Increase parameter 8-03 Control Word TimeoutTime.
• Check the operation of the communicationequipment.
• Verify that proper EMC installation wasperformed.
WARNING/ALARM 20, Temp. input errorThe temperature sensor is not connected.
WARNING/ALARM 21, Parameter errorThe parameter is out of range. The parameter number isreported in the display.
Troubleshooting• Set the affected parameter to a valid value.
WARNING/ALARM 22, Hoist mechanical brakeThe value of this warning/alarm shows the type ofwarning/alarm.0 = The torque reference was not reached before timeout(parameter 2-27 Torque Ramp Up Time).1 = Expected brake feedback was not received beforetimeout (parameter 2-23 Activate Brake Delay,parameter 2-25 Brake Release Time).
WARNING 23, Internal fan faultThe fan warning function is a protective function thatchecks if the fan is running/mounted. The fan warning canbe disabled in parameter 14-53 Fan Monitor ([0] Disabled).
For frequency converters with DC fans, a feedback sensoris mounted in the fan. If the fan is commanded to run andthere is no feedback from the sensor, this alarm appears.For frequency converters with AC fans, the voltage to thefan is monitored.
Troubleshooting• Check for proper fan operation.
• Cycle power to the frequency converter andcheck that the fan operates briefly at start-up.
• Check the sensors on the control card.
WARNING 24, External fan faultThe fan warning function is a protective function thatchecks if the fan is running/mounted. The fan warning canbe disabled in parameter 14-53 Fan Monitor ([0] Disabled).
For frequency converters with DC fans, a feedback sensoris mounted in the fan. If the fan is commanded to run andthere is no feedback from the sensor, this alarm appears.For frequency converters with AC fans, the voltage to thefan is monitored.
Troubleshooting• Check for proper fan operation.
• Cycle power to the frequency converter andcheck that the fan operates briefly at start-up.
• Check the sensors on the heat sink.
WARNING 25, Brake resistor short circuitThe brake resistor is monitored during operation. If a shortcircuit occurs, the brake function is disabled and thewarning appears. The frequency converter is stilloperational, but without the brake function.
Troubleshooting• Remove the power to the frequency converter
and replace the brake resistor (refer toparameter 2-15 Brake Check).
Maintenance, Diagnostics, a... Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 55
7 7
WARNING/ALARM 26, Brake resistor power limitThe power transmitted to the brake resistor is calculated asa mean value over the last 120 s of run time. Thecalculation is based on the DC-link voltage and the brakeresistor value set in parameter 2-16 AC brake Max. Current.The warning is active when the dissipated braking poweris higher than 90% of the brake resistor power. If option [2]Trip is selected in parameter 2-13 Brake Power Monitoring,the frequency converter trips when the dissipated brakingpower reaches 100%.
WARNING/ALARM 27, Brake chopper faultThe brake transistor is monitored during operation, and if ashort circuit occurs, the brake function is disabled, and awarning is issued. The frequency converter is stilloperational, but since the brake transistor has short-circuited, substantial power is transmitted to the brakeresistor, even if it is inactive.
Troubleshooting• Remove power to the frequency converter and
remove the brake resistor.
WARNING/ALARM 28, Brake check failedThe brake resistor is not connected or not working.
Troubleshooting• Check parameter 2-15 Brake Check.
ALARM 30, Motor phase U missingMotor phase U between the frequency converter and themotor is missing.
WARNINGHIGH VOLTAGEFrequency converters contain high voltage whenconnected to AC mains input, DC supply, or load sharing.Failure to use qualified personnel to install, start up, andmaintain the frequency converter can result in death orserious injury.
• Disconnect power before proceeding.
Troubleshooting• Remove the power from the frequency converter
and check motor phase U.
ALARM 31, Motor phase V missingMotor phase V between the frequency converter and themotor is missing.
WARNINGHIGH VOLTAGEFrequency converters contain high voltage whenconnected to AC mains input, DC supply, or load sharing.Failure to use qualified personnel to install, start up, andmaintain the frequency converter can result in death orserious injury.
• Disconnect power before proceeding.
Troubleshooting• Remove the power from the frequency converter
and check motor phase V.
ALARM 32, Motor phase W missingMotor phase W between the frequency converter and themotor is missing.
WARNINGHIGH VOLTAGEFrequency converters contain high voltage whenconnected to AC mains input, DC supply, or load sharing.Failure to use qualified personnel to install, start up, andmaintain the frequency converter can result in death orserious injury.
• Disconnect power before proceeding.
Troubleshooting• Remove the power from the frequency converter
and check motor phase W.
ALARM 33, Inrush faultToo many power-ups have occurred within a short timeperiod.
Troubleshooting• Let the unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication faultThe fieldbus on the communication option card is notworking.
WARNING/ALARM 35, Option faultAn option alarm is received. The alarm is option-specific.The most likely cause is a power-up or a communicationfault.
WARNING/ALARM 36, Mains failureThis warning/alarm is only active if the supply voltage tothe frequency converter is lost and parameter 14-10 MainsFailure is not set to [0] No function.
Troubleshooting• Check the fuses to the frequency converter and
mains supply to the unit.
ALARM 37, Phase imbalanceThere is a current imbalance between the power units.
ALARM 38, Internal faultWhen an internal fault occurs, a code number defined inTable 7.4 is shown.
Troubleshooting• Cycle power.
• Check that the option is properly installed.
• Check for loose or missing wiring.
It may be necessary to contact the Danfoss supplier orservice department. Note the code number for furthertroubleshooting directions.
Maintenance, Diagnostics, a... VLT® HVAC Drive FC 102
56 Danfoss A/S © 02/2017 All rights reserved. MG16D402
77
Number Text
0 The serial port cannot be initialized. Contact theDanfoss supplier or Danfoss service department.
256–258 The power EEPROM data is defective or too old.Replace the power card.
512–519 Internal fault. Contact the Danfoss supplier orDanfoss service department.
783 Parameter value outside of minimum/maximumlimits.
1024–1284 Internal fault. Contact the Danfoss supplier orDanfoss service department.
1299 The option software in slot A is too old.
1300 The option software in slot B is too old.
1302 The option software in slot C1 is too old.
1315 The option software in slot A is not supported/allowed.
1316 The option software in slot B is not supported/allowed.
1318 The option software in slot C1 is not supported/allowed.
1379–2819 Internal fault. Contact the Danfoss supplier orDanfoss service department.
1792 Hardware reset of digital signal processor.
1793 Motor-derived parameters not transferred correctlyto the digital signal processor.
1794 Power data not transferred correctly at power-upto the digital signal processor.
1795 The digital signal processor has received too manyunknown SPI telegrams. The frequency converteralso uses this fault code if the MCO does notpower up correctly. This situation can occur due topoor EMC protection or improper grounding.
1796 RAM copy error.
2561 Replace the control card.
2820 LCP stack overflow.
2821 Serial port overflow.
2822 USB port overflow.
3072–5122 Parameter value is outside its limits.
5123 Option in slot A: Hardware incompatible with thecontrol board hardware.
5124 Option in slot B: Hardware incompatible with thecontrol board hardware.
5125 Option in slot C0: Hardware incompatible with thecontrol board hardware.
5126 Option in slot C1: Hardware incompatible with thecontrol board hardware.
5376–6231 Internal fault. Contact the Danfoss supplier orDanfoss service department.
Table 7.4 Internal Fault Codes
ALARM 39, Heat sink sensorNo feedback from the heat sink temperature sensor.
The signal from the IGBT thermal sensor is not available onthe power card. The problem could be on the power card,on the gatedrive card, or the ribbon cable between thepower card and gatedrive card.
WARNING 40, Overload of digital output terminal 27Check the load connected to terminal 27 or remove theshort circuit connection. Check parameter 5-00 Digital I/OMode and parameter 5-01 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29Check the load connected to terminal 29 or remove theshort-circuit connection. Also check parameter 5-00 DigitalI/O Mode and parameter 5-02 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 oroverload of digital output on X30/7For terminal X30/6, check the load connected to terminalX30/6 or remove the short-circuit connection. Also checkparameter 5-32 Term X30/6 Digi Out (MCB 101) (VLT®
General Purpose I/O MCB 101).
For terminal X30/7, check the load connected to terminalX30/7 or remove the short-circuit connection. Checkparameter 5-33 Term X30/7 Digi Out (MCB 101) (VLT®
General Purpose I/O MCB 101).
ALARM 43, Ext. supplyVLT® Extended Relay Option MCB 113 is mounted withoutexternal 24 V DC. Either connect a 24 V DC external supplyor specify that no external supply is used viaparameter 14-80 Option Supplied by External 24VDC, [0] No.A change in parameter 14-80 Option Supplied by External24VDC requires a power cycle.
ALARM 45, Earth fault 2Ground fault.
Troubleshooting• Check for proper grounding and loose
connections.
• Check for proper wire size.
• Check the motor cables for short circuits orleakage currents.
ALARM 46, Power card supplyThe supply on the power card is out of range.
There are 3 supplies generated by the switch mode supply(SMPS) on the power card:
• 24 V.
• 5 V.
• ±18 V.
When powered with VLT® 24 V DC Supply MCB 107, onlythe 24 V and 5 V supplies are monitored. When poweredwith 3-phase mains voltage, all 3 supplies are monitored.
Maintenance, Diagnostics, a... Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 57
7 7
Troubleshooting• Check for a defective power card.
• Check for a defective control card.
• Check for a defective option card.
• If a 24 V DC supply is used, verify proper supplypower.
WARNING 47, 24 V supply lowThe supply on the power card is out of range.
There are 3 supplies generated by the switch mode supply(SMPS) on the power card:
• 24 V.
• 5 V.
• ±18 V.
Troubleshooting• Check for a defective power card.
WARNING 48, 1.8 V supply lowThe 1.8 V DC supply used on the control card is outside ofthe allowable limits. The supply is measured on the controlcard.
Troubleshooting• Check for a defective control card.
• If an option card is present, check forovervoltage.
WARNING 49, Speed limitThe warning is shown when the speed is outside of thespecified range in parameter 4-11 Motor Speed Low Limit[RPM] and parameter 4-13 Motor Speed High Limit [RPM].When the speed is below the specified limit inparameter 1-86 Trip Speed Low [RPM] (except when startingor stopping), the frequency converter trips.
ALARM 50, AMA calibration failedContact the Danfoss supplier or Danfoss servicedepartment.
ALARM 51, AMA check Unom and Inom
The settings for motor voltage, motor current, and motorpower are wrong.
Troubleshooting• Check the settings in parameters 1-20 to 1-25.
ALARM 52, AMA low Inom
The motor current is too low.
Troubleshooting• Check the settings in parameter 1-24 Motor
Current.
ALARM 53, AMA motor too bigThe motor is too large for the AMA to operate.
ALARM 54, AMA motor too smallThe motor is too small for the AMA to operate.
ALARM 55, AMA parameter out of rangeThe AMA cannot run because the parameter values of themotor are outside of the acceptable range.
ALARM 56, AMA interrupted by userThe AMA is manually interrupted.
ALARM 57, AMA internal faultTry to restart the AMA. Repeated restarts can overheat themotor.
ALARM 58, AMA Internal faultContact the Danfoss supplier.
WARNING 59, Current limitThe current is higher than the value inparameter 4-18 Current Limit. Ensure that the motor data inparameters 1-20 to 1-25 is set correctly. Increase the currentlimit if necessary. Ensure that the system can operate safelyat a higher limit.
WARNING 60, External interlockA digital input signal indicates a fault condition external tothe frequency converter. An external interlock hascommanded the frequency converter to trip. Clear theexternal fault condition. To resume normal operation, apply24 V DC to the terminal programmed for external interlock,and reset the frequency converter.
WARNING/ALARM 61, Feedback errorAn error between calculated speed and speedmeasurement from feedback device.
Troubleshooting• Check the settings for warning/alarm/disabling in
parameter 4-30 Motor Feedback Loss Function.
• Set the tolerable error in parameter 4-31 MotorFeedback Speed Error.
• Set the tolerable feedback loss time inparameter 4-32 Motor Feedback Loss Timeout.
WARNING 62, Output frequency at maximum limitThe output frequency has reached the value set inparameter 4-19 Max Output Frequency. Check theapplication for possible causes. Possibly increase theoutput frequency limit. Be sure that the system canoperate safely at a higher output frequency. The warningclears when the output drops below the maximum limit.
ALARM 63, Mechanical brake lowThe actual motor current has not exceeded the releasebrake current within the start delay time window.
WARNING 64, Voltage LimitThe load and speed combination demands a motorvoltage higher than the actual DC-link voltage.
WARNING/ALARM 65, Control card over temperatureThe cutout temperature of the control card is 85 °C(185 °F).
Troubleshooting• Check that the ambient operating temperature is
within the limits.
• Check for clogged filters.
• Check the fan operation.
• Check the control card.
Maintenance, Diagnostics, a... VLT® HVAC Drive FC 102
58 Danfoss A/S © 02/2017 All rights reserved. MG16D402
77
WARNING 66, Heat sink temperature lowThe frequency converter is too cold to operate. Thiswarning is based on the temperature sensor in the IGBTmodule. Increase the ambient temperature of the unit.Also, a trickle amount of current can be supplied to thefrequency converter whenever the motor is stopped bysetting parameter 2-00 DC Hold/Preheat Current to 5% andparameter 1-80 Function at Stop.
ALARM 67, Option module configuration has changedOne or more options have either been added or removedsince the last power-down. Check that the configurationchange is intentional and reset the unit.
ALARM 68, Safe Stop activatedSafe torque off (STO) has been activated. To resume normaloperation, apply 24 V DC to terminal 37, then send a resetsignal (via bus, digital I/O, or by pressing [Reset]).
ALARM 69, Power card temperatureThe temperature sensor on the power card is either toohot or too cold.
Troubleshooting• Check that the ambient operating temperature is
within limits.
• Check for clogged filters.
• Check fan operation.
• Check the power card.
ALARM 70, Illegal FC configurationThe control card and power card are incompatible. Tocheck compatibility, contact the Danfoss supplier with thetype code from the unit nameplate and the part numbersof the cards.
ALARM 71, PTC 1 safe stopSTO has been activated from the VLT® PTC Thermistor CardMCB 112 (motor too warm). Normal operation can beresumed when the MCB 112 applies 24 V DC to terminal37 again (when the motor temperature reaches anacceptable level), and when the digital input from the MCB112 is deactivated. When that happens, send a reset signal(via bus or digital I/O, or press [Reset]).
ALARM 72, Dangerous failure
STO with trip lock. An unexpected combination of STOcommands has occurred:
• VLT® PTC Thermistor Card MCB 112 enablesX44/10, but STO is not enabled.
• MCB 112 is the only device using STO (specifiedthrough selection [4] PTC 1 alarm or [5] PTC 1warning in parameter 5-19 Terminal 37 Safe Stop),STO is activated, and X44/10 is not activated.
WARNING 73, Safe Stop auto restartSTO activated. With automatic restart enabled, the motorcan start when the fault is cleared.
ALARM 74, PTC ThermistorAlarm related to VLT® PTC Thermistor Card MCB 112. ThePTC is not working.
ALARM 75, Illegal profile sel.Do not write the parameter value while the motor isrunning. Stop the motor before writing the MCO profile toparameter 8-10 Control Word Profile.
WARNING 77, Reduced power modeThe frequency converter is operating in reduced powermode (less than the allowed number of inverter sections).This warning is generated on power cycle when thefrequency converter is set to run with fewer inverters andremains on.
ALARM 78, Tracking errorThe difference between setpoint value and actual valueexceeds the value in parameter 4-35 Tracking Error.
Troubleshooting• Disable the function or select an alarm/warning
in parameter 4-34 Tracking Error Function.
• Investigate the mechanics around the load andmotor. Check feedback connections from motorencoder to frequency converter.
• Select motor feedback function inparameter 4-30 Motor Feedback Loss Function.
• Adjust the tracking error band inparameter 4-35 Tracking Error andparameter 4-37 Tracking Error Ramping.
ALARM 79, Illegal power section configurationThe scaling card has an incorrect part number or is notinstalled. The MK102 connector on the power card couldnot be installed.
ALARM 80, Drive initialised to default valueParameter settings are initialized to default settings after amanual reset. To clear the alarm, reset the unit.
ALARM 81, CSIV corruptCSIV file has syntax errors.
ALARM 82, CSIV parameter errorCSIV failed to initialize a parameter.
ALARM 83, Illegal option combinationThe mounted options are incompatible.
ALARM 84, No safety optionThe safety option was removed without applying a generalreset. Reconnect the safety option.
ALARM 88, Option detectionA change in the option layout is detected.Parameter 14-89 Option Detection is set to [0] Frozen config-uration and the option layout has been changed.
• To apply the change, enable option layoutchanges in parameter 14-89 Option Detection.
• Alternatively, restore the correct option configu-ration.
Maintenance, Diagnostics, a... Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 59
7 7
WARNING 89, Mechanical brake slidingThe hoist brake monitor detects a motor speed exceeding10 RPM.
ALARM 90, Feedback monitorCheck the connection to encoder/resolver option and, ifnecessary, replace VLT® Encoder Input MCB 102 or VLT®
Resolver Input MCB 103.
ALARM 91, Analog input 54 wrong settingsSet switch S202 in position OFF (voltage input) when aKTY sensor is connected to analog input terminal 54.
ALARM 99, Locked rotorRotor is blocked.
WARNING/ALARM 104, Mixing fan faultThe fan is not operating. The fan monitor checks that thefan is spinning at power-up or whenever the mixing fan isturned on. The mixing-fan fault can be configured as awarning or an alarm trip in parameter 14-53 Fan Monitor.
Troubleshooting• Cycle power to the frequency converter to
determine if the warning/alarm returns.
WARNING/ALARM 122, Mot. rotat. unexp.The frequency converter performs a function that requiresthe motor to be at standstill, for example DC hold for PMmotors.
WARNING 163, ATEX ETR cur.lim.warningThe frequency converter has run above the characteristiccurve for more than 50 s. The warning is activated at 83%and deactivated at 65% of the allowed thermal overload.
ALARM 164, ATEX ETR cur.lim.alarmOperating above the characteristic curve for more than60 s within a period of 600 s activates the alarm, and thefrequency converter trips.
WARNING 165, ATEX ETR freq.lim.warningThe frequency converter is running for more than 50 sbelow the allowed minimum frequency(parameter 1-98 ATEX ETR interpol. points freq.).
ALARM 166, ATEX ETR freq.lim.alarmThe frequency converter has operated for more than 60 s(in a period of 600 s) below the allowed minimumfrequency (parameter 1-98 ATEX ETR interpol. points freq.).
WARNING 250, New spare partThe power or switch mode supply has been exchanged.Restore the frequency converter type code in the EEPROM.Select the correct type code in parameter 14-23 TypecodeSetting according to the label on the frequency converter.Remember to select Save to EEPROM at the end.
WARNING 251, New typecodeThe power card or other components are replaced, and thetype code has changed.
Maintenance, Diagnostics, a... VLT® HVAC Drive FC 102
60 Danfoss A/S © 02/2017 All rights reserved. MG16D402
77
7.7 Troubleshooting
Symptom Possible cause Test Solution
Displaydark/Nofunction
Missing input power. See Table 4.3. Check the input power source.
Missing or open fuses, or circuitbreaker tripped.
See Open power fuses and tripped circuitbreaker in this table for possible causes.
Follow the recommendations provided.
No power to the LCP. Check the LCP cable for proper connection ordamage.
Replace the faulty LCP or connectioncable.
Short circuit on control voltage(terminal 12 or 50) or at controlterminals.
Check the 24 V control voltage supply forterminal 12/13 to 20–39, or 10 V supply forterminal 50–55.
Wire the terminals properly.
Incompatible LCP (LCP from
VLT® 2800 or 5000/6000/8000/FCD or FCM).
–
Use only LCP 101 (P/N 130B1124) or LCP102 (P/N. 130B1107).
Wrong contrast setting. –Press [Status] + []/[] to adjust the
contrast.
Display (LCP) is defective. Test using a different LCP.Replace the faulty LCP or connectioncable.
Internal voltage supply fault orSMPS is defective.
– Contact supplier.
Intermittentdisplay
Overloaded supply (SMPS) dueto improper control wiring or afault within the frequencyconverter.
To rule out a problem in the control wiring,disconnect all control wiring by removing theterminal blocks.
If the display stays lit, the problem is inthe control wiring. Check the wiring forshorts or incorrect connections. If thedisplay continues to cut out, follow theprocedure for Display dark\No function.
Motor notrunning
Service switch open or missingmotor connection.
Check if the motor is connected and theconnection is not interrupted by a serviceswitch or other device.
Connect the motor and check the serviceswitch.
No mains power with 24 V DCoption card.
If the display is functioning, but there is nooutput, check that mains power is applied tothe frequency converter.
Apply mains power to run the unit.
LCP stop. Check if [Off] has been pressed.Press [Auto On] or [Hand On] (dependingon operating mode) to run the motor.
Missing start signal (Standby).Check parameter 5-10 Terminal 18 Digital Inputfor correct setting of terminal 18. Use defaultsetting.
Apply a valid start signal to start themotor.
Motor coast signal active(Coasting).
Check parameter 5-12 Terminal 27 Digital Inputfor correct setting of terminal 27 (use defaultsetting).
Apply 24 V on terminal 27 or programthis terminal to [0] No operation.
Wrong reference signal source.
Check reference signal:
• Local.
• Remote or bus reference?
• Preset reference active?
• Terminal connection correct?
• Scaling of terminals correct?
• Reference signal available?
Program correct settings. Checkparameter 3-13 Reference Site. Set presetreference active in parameter group 3-1*References. Check for correct wiring. Checkscaling of terminals. Check referencesignal.
Motorrunning inwrongdirection
Motor rotation limit.Check that parameter 4-10 Motor SpeedDirection is programmed correctly.
Program correct settings.
Active reversing signal.Check if a reversing command is programmedfor the terminal in parameter group 5-1*Digital inputs.
Deactivate reversing signal.
Wrong motor phaseconnection.
–See chapter 5.5 Checking Motor Rotation.
Maintenance, Diagnostics, a... Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 61
7 7
Symptom Possible cause Test Solution
Motor is notreachingmaximumspeed
Frequency limits set wrong.
Check output limits in parameter 4-13 MotorSpeed High Limit [RPM], parameter 4-14 MotorSpeed High Limit [Hz], and parameter 4-19 MaxOutput Frequency.
Program correct limits.
Reference input signal notscaled correctly.
Check reference input signal scaling inparameter group 6-0* Analog I/O mode andparameter group 3-1* References..
Program correct settings.
Motor speedunstable
Possible incorrect parametersettings.
Check the settings of all motor parameters,including all motor compensation settings.For closed-loop operation, check PID settings.
Check settings in parameter group 1-6*Load Depen. Setting. For closed-loopoperation, check settings in parametergroup 20-0* Feedback.
Motor runsrough
Possible overmagnetization.Check for incorrect motor settings in allmotor parameters.
Check motor settings in parameter groups1-2* Motor data, 1-3* Adv Motor Data, and1-5* Load Indep. Setting.
Motor doesnot brake
Possible incorrect settings inthe brake parameters. Ramp-down times may be too short.
Check brake parameters. Check ramp timesettings.
Check parameter groups 2-0* DC Brake and3-0* Reference Limits.
Open powerfuses
Phase-to-phase short.Motor or panel has a short phase-to-phase.Check motor and panel phases for shorts.
Eliminate any shorts detected.
Motor overload. Motor is overloaded for the application.
Perform start-up test and verify that themotor current is within specifications. Ifthe motor current exceeds the nameplatefull-load current, the motor may run onlywith reduced load. Review the specifi-cations for the application.
Loose connections. Perform pre-start-up check for looseconnections.
Tighten loose connections.
Mains currentimbalancegreater than3%
Problem with mains power (seeAlarm 4, Mains phase lossdescription).
Rotate input power leads into the 1 position:A to B, B to C, C to A.
If imbalanced leg follows the wire, it is apower problem. Check the mains supply.
Problem with the frequencyconverter.
Rotate input power leads into the frequencyconverter 1 position: A to B, B to C, C to A.
If the imbalanced leg stays on same inputterminal, it is a problem with thefrequency converter. Contact the supplier.
Motor currentimbalancegreater than3%
Problem with motor or motorwiring.
Rotate output motor leads 1 position: U to V,V to W, W to U.
If the imbalanced leg follows the wire, theproblem is in the motor or motor wiring.Check motor and motor wiring.
Problem with frequencyconverter.
Rotate output motor leads 1 position: U to V,V to W, W to U.
If the imbalanced leg stays on sameoutput terminal, it is a problem with theunit. Contact the supplier.
Frequencyconverteraccelerationproblems
Motor data is enteredincorrectly.
If warnings or alarms occur, see chapter 7.6 List of Warnings and Alarms.Check that motor data is entered correctly.
Increase the ramp-up time inparameter 3-41 Ramp 1 Ramp Up Time.Increase current limit inparameter 4-18 Current Limit. Increasetorque limit in parameter 4-16 Torque LimitMotor Mode.
Frequencyconverterdecelerationproblems
Motor data is enteredincorrectly.
If warnings or alarms occur, see chapter 7.6 List of Warnings and Alarms.Check that motor data is entered correctly.
Increase the ramp-down time inparameter 3-42 Ramp 1 Ramp Down Time.Enable overvoltage control inparameter 2-17 Over-voltage Control.
Table 7.5 Troubleshooting
Maintenance, Diagnostics, a... VLT® HVAC Drive FC 102
62 Danfoss A/S © 02/2017 All rights reserved. MG16D402
77
8 Specifications
8.1 Electrical Data
8.1.1 Mains Supply 3x380–480 V AC
N110 N132 N160 N200 N250 N315
Normal Load* NO NO NO NO NO NO
Typical shaft output at 400 V [kW] 110 132 160 200 250 315
Typical shaft output at 460 V [hp] 150 200 250 300 350 450
Typical shaft output at 480 V [kW] 132 160 200 250 315 355
Enclosure IP21 D1h D1h D1h D2h D2h D2h
Enclosure IP54 D1h D1h D1h D2h D2h D2h
Enclosure IP20 D3h D3h D3h D4h D4h D4h
Output current
Continuous (at 400 V) [A] 212 260 315 395 480 588
Intermittent (60 s overload) (at400 V)[A]
233 286 347 435 528 647
Continuous (at 460/500 V) [A] 190 240 302 361 443 535
Intermittent (60 s overload) (at460/500 V) [kVA]
209 264 332 397 487 588
Continuous kVA (at 400 V) [kVA] 147 180 218 274 333 407
Continuous kVA (at 460 V) [kVA] 151 191 241 288 353 426
Maximum input current
Continuous (at 400 V) [A] 204 251 304 381 463 567
Continuous (at 460/500 V) [A] 183 231 291 348 427 516
Maximum cable size: Mains, motor,
brake, and load share mm2 (AWG)]2 x95 (2x3/0) 2x185 (2x350)
Maximum external mains fuses [A] 315 350 400 550 630 800
Estimated power loss at 400 V [W] 2555 2949 3764 4109 5129 6663
Estimated power loss at 460 V [W] 2257 2719 3622 3561 4558 5703
Weight, enclosure IP21, IP54 [kg(lb)]
62 (135) 125 (275)
Weight, enclosure IP20 [kg (lb)] 62 (135) 125 (275)
Efficiency 0.98
Output frequency 0–590 Hz
*Normal overload=110% current for 60 s
Table 8.1 Mains Supply 3x380–480 V AC
Specifications Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 63
8 8
8.1.2 Mains Supply 3x525–690 V AC
N75K N90K N110 N132 N160 N200
Normal Load* NO NO NO NO NO NO
Typical shaft output at 550 V [kW] 55 75 90 110 132 160
Typical shaft output at 575 V [hp] 75 100 125 150 200 250
Typical shaft output at 690 V [kW] 75 90 110 132 160 200
Enclosure IP21 D1h D1h D1h D1h D1h D2h
Enclosure IP54 D1h D1h D1h D1h D1h D2h
Enclosure IP20 D3h D3h D3h D3h D3h D4h
Output current
Continuous (at 550 V) [A] 90 113 137 162 201 253
Intermittent (60 s overload) (at550 V)[A]
99 124 151 178 221 278
Continuous (at 575/690 V) [A] 86 108 131 155 192 242
Intermittent (60 s overload) (at575/690 V) [kVA]
95 119 144 171 211 266
Continuous kVA (at 550 V) [kVA] 86 108 131 154 191 241
Continuous kVA (at 575 V) [kVA] 86 108 130 154 191 241
Continuous kVA (at 690 V) [kVA] 103 129 157 185 229 289
Maximum input current
Continuous (at 550 V) [A] 89 110 130 158 198 245
Continuous (at 575 V) [A] 85 106 124 151 189 234
Continuous (at 690 V) [A] 87 109 128 155 197 240
Maximum cable size: Mains, motor,
brake, and load share [mm2 (AWG)]2x95 (2x3/0)
2x185(2x350 mcm)
Maximum external mains fuses [A] 160 315 315 315 350 350
Estimated power loss at 575 V [W] 1161 1426 1739 2099 2646 3071
Estimated power loss at 690 V [W] 1203 1476 1796 2165 2738 3172
Weight, enclosure IP21, IP54 [kg(lb)]
62 (135) 125 (275)
Weight, enclosure IP20 [kg (lb)] 62 (135) 125 (275)
Efficiency 0.98
Output frequency 0–590 Hz
Heat sink overtemperature trip 110 °C (230 °F)
Power card ambient trip 75 °C (167 °F)
*Normal overload=110% current for 60 s
Table 8.2 Mains Supply 3x525–690 V AC
Specifications VLT® HVAC Drive FC 102
64 Danfoss A/S © 02/2017 All rights reserved. MG16D402
88
N250 N315 N400
Normal Load* NO NO NO
Typical shaft output at 550 V [kW] 200 250 315
Typical shaft output at 575 V [hp] 300 350 400
Typical shaft output at 690 V [kW] 250 315 400
Enclosure IP21 D2h D2h D2h
Enclosure IP54 D2h D2h D2h
Enclosure IP20 D4h D4h D4h
Output current
Continuous (at 550 V) [A] 303 360 418
Intermittent (60 s overload) (at 550 V)[A] 333 396 460
Continuous (at 575/690 V) [A] 290 344 400
Intermittent (60 s overload) (at 575/690 V) [kVA] 319 378 440
Continuous kVA (at 550 V) [kVA] 289 343 398
Continuous kVA (at 575 V) [kVA] 289 343 398
Continuous kVA (at 690 V) [kVA] 347 411 478
Maximum input current
Continuous (at 550 V) [A] 299 355 408
Continuous (at 575 V) [A] 286 339 390
Continuous (at 690 V) [A] 296 352 400
Maximum cable size: Mains, motor, brake, and load
share, mm2 (AWG)2x185 (2x350 mcm)
Maximum external mains fuses [A] 400 500 550
Estimated power loss at 575 V [W] 3719 4460 5023
Estimated power loss at 690 V [W] 3848 4610 5150
Weight, enclosure IP21, IP54 [kg (lb)] 125 (275)
Weight, enclosure IP20 [kg (lb)] 125 (275)
Efficiency 0.98
Output frequency 0–590 Hz
Heat sink overtemperature trip 110 °C (230 °F)
Power card ambient trip 75 °C (167 °F)
*Normal overload=110% current for 60 s
Table 8.3 Mains Supply 3x525–690 V AC
• The typical power loss is at nominal load conditions and expected to be within ±15% (tolerance relates to varietyin voltage and cable conditions).
• The losses are based on the default switching frequency. The losses increase significantly at higher switchingfrequencies.
• The options cabinet adds weight to the frequency converter. The maximum weight of the D5h–D8h enclosures isshown in Table 8.4.
Enclosure size Description Maximum weight [kg] ([lb])
D5h D1h ratings+disconnect and/or brake chopper 166 (255)
D6h D1h ratings+contactor and/or circuit breaker 129 (285)
D7h D2h ratings+disconnect and/or brake chopper 200 (440)
D8h D2h ratings+contactor and/or circuit breaker 225 (496)
Table 8.4 D5h–D8h Weight
Specifications Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 65
8 8
8.2 Mains Supply
Mains supply (L1, L2, L3)Supply voltage 380–480 V ±10%, 525–690 V ±10%
Mains voltage low/mains voltage dropout:During low mains voltage or a mains drop-out, the frequency converter continues until the DC-link voltage drops below theminimum stop level. The minimum stop level corresponds typically to 15% below the frequency converter's lowest rated supplyvoltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowestrated supply voltage.
Supply frequency 50/60 Hz ±5%Maximum imbalance temporary between mains phases 3.0% of rated supply voltageTrue power factor (λ) ±0.9 nominal at rated loadDisplacement power factor (cos φ) near unity (>0.98)Switching on input supply L1, L2, L3 (power-ups) Maximum 1 time/2 minutesEnvironment according to EN60664-1 Overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 480/600 V.
8.3 Motor Output and Motor Data
Motor output (U, V, W)Output voltage 0–100% of supply voltageOutput frequency 0–590 Hz1)
Switching on output UnlimitedRamp times 0.01–3600 s
1) Dependent on voltage and power.
Torque characteristicsStarting torque (constant torque) Maximum 160% for 60 s1)
Starting torque Maximum 180% up to 0.5 s1)
Overload torque (constant torque) Maximum 160% for 60 s1)
1) Percentage relates to the frequency converter's nominal torque.
8.4 Ambient Conditions
EnvironmentEnclosure size D1h/D2h/D5h/D6h/D7h/D8h IP21/Type 1, IP54/Type12Enclosure size D3h/D4h IP20/ChassisVibration test all enclosure sizes 1.0 gRelative humidity 5–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)Aggressive environment (IEC 60068-2-43) H2S test Class KdTest method according to IEC 60068-2-43 H2S (10 days)Ambient temperature (at SFAVM switching mode)- with derating Maximum 55 °C (maximum 131 °F)1)
- with full output power of typical EFF2 motors (up to 90% output current) Maximum 50 °C (maximum 122 °F)1)
- at full continuous FC output current Maximum 45 °C (maximum 113 °F)1)
Minimum ambient temperature during full-scale operation 0 °C (32 °F)Minimum ambient temperature at reduced performance 10 °C (50 °F)Temperature during storage/transport -25 to +65/70 °C (13 to 149/158 °F)Maximum altitude above sea level without derating 1000 m (3281 ft)Maximum altitude above sea level with derating 3000 m (9842 ft)
1) For more information on derating, see section on special conditions in the design guide.
EMC standards, Emission EN 61800-3EMC standards, Immunity EN 61800-3
Specifications VLT® HVAC Drive FC 102
66 Danfoss A/S © 02/2017 All rights reserved. MG16D402
88
Energy efficiency class2) IE2
2) Determined according to EN 50598-2 at:
• Rated load.
• 90% rated frequency.
• Switching frequency factory setting.
• Switching pattern factory setting.
8.5 Cable Specifications
Cable lengths and cross-sections for control cables1)
Maximum motor cable length, shielded/armored 150 m (492 ft)Maximum motor cable length, unshielded/unarmored 300 m (984 ft)Maximum cross-section to motor, mains, load sharing, and brake See chapter 8.1 Electrical DataMaximum cross-section to control terminals, rigid wire 1.5 mm2/16 AWG (2x0.75 mm2)Maximum cross-section to control terminals, flexible cable 1 mm2/18 AWGMaximum cross-section to control terminals, cable with enclosed core 0.5 mm2/20 AWGMinimum cross-section to control terminals 0.25 mm2/23 AWG
1) For power cables, see electrical tables in chapter 8.1 Electrical Data.
8.6 Control Input/Output and Control Data
Digital inputsProgrammable digital inputs 4 (6)Terminal number 18, 19, 271), 291), 32, 33Logic PNP or NPNVoltage level 0–24 V DCVoltage level, logic 0 PNP <5 V DCVoltage level, logic 1 PNP >10 V DCVoltage level, logic 0 NPN >19 V DCVoltage level, logic 1 NPN <14 V DCMaximum voltage on input 28 V DCInput resistance, Ri Approximately 4 kΩ
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.1) Terminals 27 and 29 can also be programmed as outputs.
Analog inputsNumber of analog inputs 2Terminal number 53, 54Modes Voltage or currentMode select Switches A53 and A54Voltage mode Switch A53/A54=(U)Voltage level -10 V to +10 V (scaleable)Input resistance, Ri Approximately 10 kΩMaximum voltage ±20 VCurrent mode Switch A53/A54=(I)Current level 0/4 to 20 mA (scaleable)Input resistance, Ri Approximately 200 ΩMaximum current 30 mAResolution for analog inputs 10 bit (+ sign)Accuracy of analog inputs Maximum error 0.5% of full scaleBandwidth 100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Specifications Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 67
8 8
Mains
Functionalisolation
PELV isolation
Motor
DC-bus
Highvoltage
Control+24 V
RS485
18
37
130B
A11
7.10
Illustration 8.1 PELV Isolation
Pulse inputsProgrammable pulse inputs 2Terminal number pulse 29, 33Maximum frequency at terminal 29, 33 110 kHz (push-pull driven)Maximum frequency at terminal 29, 33 5 kHz (open collector)Minimum frequency at terminal 29, 33 4 HzVoltage level See Digital Inputs in chapter 8.6 Control Input/Output and Control DataMaximum voltage on input 28 V DCInput resistance, Ri Approximately 4 kΩPulse input accuracy (0.1–1 kHz) Maximum error: 0.1% of full scale
Analog outputNumber of programmable analog outputs 1Terminal number 42Current range at analog output 0/4-20 mAMaximum resistor load to common at analog output 500 ΩAccuracy on analog output Maximum error: 0.8% of full scaleResolution on analog output 8 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS485 serial communicationTerminal number 68 (P, TX+, RX+), 69 (N, TX-, RX-)Terminal number 61 Common for terminals 68 and 69
The RS485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from thesupply voltage (PELV).
Digital outputProgrammable digital/pulse outputs 2Terminal number 27, 291)
Voltage level at digital/frequency output 0–24 VMaximum output current (sink or source) 40 mAMaximum load at frequency output 1 kΩMaximum capacitive load at frequency output 10 nFMinimum output frequency at frequency output 0 HzMaximum output frequency at frequency output 32 kHzAccuracy of frequency output Maximum error: 0.1% of full scaleResolution of frequency outputs 12 bit
1) Terminals 27 and 29 can also be programmed as inputs.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Specifications VLT® HVAC Drive FC 102
68 Danfoss A/S © 02/2017 All rights reserved. MG16D402
88
Control card, 24 V DC outputTerminal number 12, 13Maximum load 200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digitalinputs and outputs.
Relay outputsProgrammable relay outputs 2Maximum cross-section to relay terminals 2.5 mm2 (12 AWG)Minimum cross-section to relay terminals 0.2 mm2 (30 AWG)Length of stripped wire 8 mm (0.3 in)Relay 01 terminal number 1–3 (break), 1–2 (make)Maximum terminal load (AC-1)1) on 1–2 (NO) (Resistive load)2)3) 400 V AC, 2 AMaximum terminal load (AC-15)1) on 1–2 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 AMaximum terminal load (DC-1)1) on 1–2 (NO) (Resistive load) 80 V DC, 2 AMaximum terminal load (DC-13)1) on 1–2 (NO) (Inductive load) 24 V DC, 0.1 AMaximum terminal load (AC-1)1) on 1–3 (NC) (Resistive load) 240 V AC, 2 AMaximum terminal load (AC-15)1) on 1–3 (NC) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 AMaximum terminal load (DC-1)1) on 1–3 (NC) (Resistive load) 50 V DC, 2 AMaximum terminal load (DC-13)1) on 1–3 (NC) (Inductive load) 24 V DC, 0.1 AMinimum terminal load on 1–3 (NC), 1–2 (NO) 24 V DC 10 mA, 24 V AC 2 mAEnvironment according to EN 60664-1 Overvoltage category III/pollution degree 2Relay 02 terminal number 4–6 (break), 4–5 (make)Maximum terminal load (AC-1)1) on 4–5 (NO) (Resistive load)2)3) 400 V AC, 2 AMaximum terminal load (AC-15)1) on 4–5 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 AMaximum terminal load (DC-1)1) on 4–5 (NO) (Resistive load) 80 V DC, 2 AMaximum terminal load (DC-13)1) on 4–5 (NO) (Inductive load) 24 V DC, 0.1 AMaximum terminal load (AC-1)1) on 4–6 (NC) (Resistive load) 240 V AC, 2 AMaximum terminal load (AC-15)1) on 4–6 (NC) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 AMaximum terminal load (DC-1)1) on 4–6 (NC) (Resistive load) 50 V DC, 2 AMaximum terminal load (DC-13)1) on 4–6 (NC) (Inductive load) 24 V DC, 0.1 AMinimum terminal load on 4–6 (NC), 4–5 (NO) 24 V DC 10 mA, 24 V AC 2 mAEnvironment according to EN 60664-1 Overvoltage category III/pollution degree 2
1) IEC 60947 part 4 and 5.The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).2) Overvoltage Category II.3) UL applications 300 V AC 2 A.
Control card, +10 V DC outputTerminal number 50Output voltage 10.5 V ±0.5 VMaximum load 25 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control characteristicsResolution of output frequency at 0–1000 Hz ±0.003 HzSystem response time (terminals 18, 19, 27, 29, 32, 33) ≤2 msSpeed control range (open loop) 1:100 of synchronous speedSpeed accuracy (open loop) 30–4000 RPM: Maximum error of ±8 RPM
All control characteristics are based on a 4-pole asynchronous motor.
Specifications Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 69
8 8
Control card performanceScan interval 5 ms
Control card, USB serial communicationUSB standard 1.1 (full speed)USB plug USB type B device plug
NOTICEConnection to PC is carried out via a standard host/device USB cable.The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.The USB connection is not galvanically isolated from ground. Use only isolated laptop/PC as connection to the USBconnector on the frequency converter or an isolated USB cable/converter.
8.7 Fuses
8.7.1 Fuse Selection
Use recommended fuses and/or circuit breakers on the supply side as protection if there is a component breakdown insidethe frequency converter (first fault).
NOTICEUse of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations.
Use the recommended fuses to ensure compliance with EN 50178. Use of recommended fuses and circuit breakers ensuresthat possible damage to the frequency converter is limited to damages inside the unit. For further information, seeApplication Note Fuses and Circuit Breakers.
The fuses in Table 8.5 to Table 8.7 are suitable for use on a circuit capable of delivering 100000 Arms (symmetrical),depending on the frequency converter voltage rating. With the proper fusing, the frequency converter short-circuit currentrating (SCCR) is 100000 Arms.
N110K–N315 380–500 V Type aR
N75K–N400 525–690 V Type aR
Table 8.5 Recommended Fuses
Powersize
BussmannPN
Littelfuse PN LittelfusePN
BussmannPN
Siba PN Ferraz ShawmutPN
Ferraz Shawmut PN(Europe)
Ferraz Shawmut PN(North America)
N110K 170M2619 LA50QS300-4 L50S-300 FWH-300A 20 61031.315
A50QS300-4 6,9URD31D08A0315 A070URD31KI0315
N132 170M2620 LA50QS350-4 L50S-350 FWH-350A 20 61031.350
A50QS350-4 6,9URD31D08A0350 A070URD31KI0350
N160 170M2621 LA50QS400-4 L50S-400 FWH-400A 20 61031.400
A50QS400-4 6,9URD31D08A0400 A070URD31KI0400
N200 170M4015 LA50QS500-4 L50S-500 FWH-500A 20 61031.550
A50QS500-4 6,9URD31D08A0550 A070URD31KI0550
N250 170M4016 LA50QS600-4 L50S-600 FWH-600A 20 61031.630
A50QS600-4 6,9URD31D08A0630 A070URD31KI0630
N315 170M4017 LA50QS800-4 L50S-800 FWH-800A 20 61031.800
A50QS800-4 6,9URD32D08A0800 A070URD31KI0800
Table 8.6 Fuse Options for 380–500 V Frequency Converters
Specifications VLT® HVAC Drive FC 102
70 Danfoss A/S © 02/2017 All rights reserved. MG16D402
88
Power size Bussmann PN Siba PN Ferraz Shawmut European PN Ferraz Shawmut North American PN
N75k T7 170M2616 20 610 31.160 6,9URD30D08A0160 A070URD30KI0160
N90k T7 170M2619 20 610 31.315 6,9URD31D08A0315 A070URD31KI0315
N110 T7 170M2619 20 610 31.315 6,9URD31D08A0315 A070URD31KI0315
N132 T7 170M2619 20 610 31.315 6,9URD31D08A0315 A070URD31KI0315
N160 T7 170M2619 20 610 31.315 6,9URD31D08A0315 A070URD31KI0315
N200 T7 170M4015 20 620 31.550 6,9URD32D08A0550 A070URD32KI0550
N250 T7 170M4015 20 620 31.550 6,9URD32D08A0550 A070URD32KI0550
N315 T7 170M4015 20 620 31.550 6,9URD32D08A0550 A070URD32KI0550
N400 T7 170M4015 20 620 31.550 6,9URD32D08A0550 A070URD32KI0550
Table 8.7 Fuse Options for 525–690 V Frequency Converters
For UL Compliance, use the Bussmann 170M series fuses for units supplied without a contactor-only option. See Table 8.9 forSCCR ratings and UL fuse criteria if a contactor-only option is supplied with the frequency converter.
8.7.2 Short-circuit Current Rating (SCCR)
If the frequency converter is not supplied with a mains disconnect, contactor or circuit breaker, the short-circuit currentrating (SCCR) of the frequency converters is 100000 A at all voltages (380–690 V).
If the frequency converter is supplied with a mains disconnect, the SCCR of the frequency converter is 100000 A at allvoltages (380–690 V).
If the frequency converter is supplied with a circuit breaker, the SCCR depends on the voltage, see Table 8.8:
415 V 480 V 600 V 690 V
D6h enclosure 120000 A 100000 A 65000 A 70000 A
D8h enclosure 100000 A 100000 A 42000 A 30000 A
Table 8.8 Frequency Converter Supplied with a Circuit Breaker
If the frequency converter is supplied with a contactor-only option and is externally fused according to Table 8.9, the SCCRof the frequency converter is as follows:
415 V
IEC1)
[A]
480 V
UL2)
[A]
600 V
UL2)
[A]
690 V
IEC1)
[A]
D6h enclosure 100000 100000 100000 100000
D8h enclosure (not including the N250T5) 100000 100000 100000 100000
D8h enclosure (N250T5 only) 100000 Consult factory Not applicable
Table 8.9 Frequency Converter Supplied with a Contactor
1) With a Bussmann type LPJ-SP or Gould Shawmut type AJT fuse. 450 A maximum fuse size for D6h, and 900 A maximum fuse size for D8h.2) Must use Class J or L branch fuses for UL Approval. 450 A maximum fuse size for D6h, and 600 A maximum fuse size for D8h.
Specifications Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 71
8 8
8.8 Connection Tightening Torques
When tightening all electrical connections, it is important to tighten with the correct torque. Too low or too high torqueresults in a bad electrical connection. To tighten the bolts and to ensure the correct torque, use a torque wrench.
Enclosure Size Terminal Torque [Nm (in-lb)] Bolt size
D1h/D3h/D5h/D6h MainsMotorLoad sharingRegen
19–40 (168–354) M10
GroundBrake
8.5–20.5 (75–181) M8
D2h/D4h/D7h/D8h MainsMotorRegenLoad sharingGround
19–40 (168–354) M10
Brake 8.5–20.5 (75–181) M8
Table 8.10 Torque for Terminals
Apply the correct torque when tightening fasteners in the locations that are listed in Table 8.11. Too low or too high torquewhen fastening an electrical connection results in a bad electrical connection. To ensure correct torque, use a torquewrench.
Location Bolt size Torque [Nm (in-lb)]
Mains terminals M10/M12 19 (168)/37 (335)
Motor terminals M10/M12 19 (168)/37 (335)
Ground terminals M8/M10 9.6 (84)/19.1 (169)
Brake terminals M8 9.6 (84)
Load sharing terminals M10/M12 19 (168)/37 (335)
Regeneration terminals (Enclosures E1h/E2h) M8 9.6 (84)
Regeneration terminals (Enclosures E3h/E4h) M10/M12 19 (168)/37 (335)
Relay terminals _ 0.5 (4)
Door/panel cover M5 2.3 (20)
Gland plate M5 2.3 (20)
Heat sink access panel M5 3.9 (35)
Serial communication cover M5 2.3 (20)
Table 8.11 Fastener Torque Ratings
Specifications VLT® HVAC Drive FC 102
72 Danfoss A/S © 02/2017 All rights reserved. MG16D402
88
8.9 Power Ratings, Weight, and Dimensions
Enclosure size D1h D2h D3h D4h D3h D4h
110–160 kW150–250 hp(380–500 V)75–160 kW75–200 hp
(525–690 V)
200–315 kW300–450 hp(380–500 V)200–400 kW300–400 hp(525–690 V)
110–160 kW150–250 hp(380–500 V)75–160 kW75–200 hp
(525–690 V)
200–315 kW300–450 hp(380–500 V)200–400 kW300–400 hp(525–690 V)
With regeneration or load sharingterminals
IPNEMA
21/54Type 1/12
21/54Type 1/12
20Chassis
20Chassis
20Chassis
20Chassis
Shippingdimensions[mm (in)]
Height 587 (23.1) 587 (23.1) 587 (23.1) 587 (23.1) 587 (23.1) 587 (23.1)
Width 997 (39.3) 1170 (46.1) 997 (39.3) 1170 (46.1) 1230 (48.4) 1430 (56.3)
Depth 460 (18.1) 535 (21.1) 460 (18.1) 535 (21.1) 460 (18.1) 535 (21.1)
Frequencyconverterdimensions[mm (in)]
Height 901 (35.5) 1060 (41.7) 909 (35.8) 1122 (44.2) 1004 (39.5) 1268 (49.9)
Width 325 (12.8) 420 (16.5) 250 (9.8) 350 (13.8) 250 (9.8) 350 (13.8)
Depth 378 (14.9) 378 (14.9) 375 (14.7) 375 (14.7) 375 (14.7) 375 (14.8)
Maximum weight [kg (lb)] 98 (216) 164 (362) 98 (216) 164 (362) 108 (238) 179 (395)
Table 8.12 Mechanical Dimensions, Enclosure Sizes D1h-D4h
Enclosure size D5h D6h D7h D8h
110–160 kW150–200 hp(380–500 V)75–160 kW75–200 hp)(525–690 V)
110–160 kW150–250 hp(380–500 V)75–160 kW75–200 hp
(525–690 V)
200–315 kW300–450 hp(380–500 V)200–400 kW300–400 hp)(525–690 V)
200–315 kW300–450 hp(380–500 V)200–400 kW300–400 hp(525–690 V)
IPNEMA
21/54Type 1/12
21/54Type 1/12
21/54Type 1/12
21/54Type 1/12
Shipping dimensions[mm (in)]
Height 660 (26) 660 (26) 660 (26) 660 (26)
Width 1820 (71.7) 1820 (71.7) 2470 (97.4) 2470 (97.4)
Depth 510 (20.1) 510 (20.1) 590 (23.2) 590 (23.2)
Frequency converterdimensions [mm (in)]
Height 1324 (52.1) 1663 (65.5) 1978 (77.9) 2284 (89.9)
Width 325 (12.8) 325 (12.8) 420 (16.5) 420 (16.5)
Depth 381 (15) 381 (15) 386 (15.2) 406 (16)
Maximum weight [kg (lb)] 116 (256) 129 (284) 200 (441) 225 (496)
Table 8.13 Mechanical Dimensions, Enclosure Sizes D5h-D8h
Specifications Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 73
8 8
9 Appendix
9.1 Symbols, Abbreviations, and Conventions
°C Degrees Celsius
°F Degrees Fahrenheit
AC Alternating current
AEO Automatic energy optimization
AWG American wire gauge
AMA Automatic motor adaptation
DC Direct current
EMC Electro magnetic compatibility
ETR Electronic thermal relay
fM,N Nominal motor frequency
FC Frequency converter
IINV Rated inverter output current
ILIM Current limit
IM,N Nominal motor current
IVLT,MAX Maximum output current
IVLT,N Rated output current supplied by the frequency converter
IP Ingress protection
LCP Local control panel
MCT Motion control tool
ns Synchronous motor speed
PM,N Nominal motor power
PELV Protective extra low voltage
PCB Printed circuit board
PM Motor Permanent magnet motor
PWM Pulse-width modulated
RPM Revolutions per minute
Regen Regenerative terminals
TLIM Torque limit
UM,N Nominal motor voltage
Table 9.1 Symbols and Abbreviations
ConventionsNumbered lists indicate procedures.Bullet lists indicate other information.Italicized text indicates:
• Cross-reference.
• Link.
• Parameter name.
• Parameter option name.
All dimensions are in [mm].
9.2 Parameter Menu Structure
Appendix VLT® HVAC Drive FC 102
74 Danfoss A/S © 02/2017 All rights reserved. MG16D402
99
0-**
Ope
ratio
n /
Dis
play
0-0*
Basi
c Se
ttin
gs0-
01La
ngua
ge0-
02M
otor
Spe
ed U
nit
0-03
Regi
onal
Set
tings
0-04
Ope
ratin
g S
tate
at
Pow
er-u
p0-
05Lo
cal M
ode
Uni
t0-
1*Se
t-up
Ope
ratio
ns0-
10Ac
tive
Set-
up0-
11Pr
ogra
mm
ing
Set
-up
0-12
This
Set
-up
Lin
ked
to
0-13
Read
out:
Lin
ked
Set
-ups
0-14
Read
out:
Pro
g. S
et-u
ps /
Cha
nnel
0-15
Read
out:
act
ual s
etup
0-2*
LCP
Dis
play
0-20
Dis
play
Lin
e 1.
1 Sm
all
0-21
Dis
play
Lin
e 1.
2 Sm
all
0-22
Dis
play
Lin
e 1.
3 Sm
all
0-23
Dis
play
Lin
e 2
Larg
e0-
24D
ispl
ay L
ine
3 La
rge
0-25
My
Pers
onal
Men
u0-
3*LC
P C
usto
m R
eado
ut0-
30Cu
stom
Rea
dout
Uni
t0-
31Cu
stom
Rea
dout
Min
Val
ue0-
32Cu
stom
Rea
dout
Max
Val
ue0-
37D
ispl
ay T
ext
10-
38D
ispl
ay T
ext
20-
39D
ispl
ay T
ext
30-
4*LC
P K
eypa
d0-
40[H
and
on]
Key
on
LCP
0-41
[Off]
Key
on
LCP
0-42
[Aut
o o
n] K
ey o
n L
CP0-
43[R
eset
] Ke
y on
LCP
0-44
[Off/Re
set]
Key
on
LCP
0-45
[Driv
e By
pass
] Ke
y on
LCP
0-5*
Copy
/Sav
e0-
50LC
P C
opy
0-51
Set-
up C
opy
0-6*
Pass
wor
d0-
60M
ain
Men
u P
assw
ord
0-61
Acce
ss t
o M
ain
Men
u w
/o P
assw
ord
0-65
Pers
onal
Men
u P
assw
ord
0-66
Acce
ss t
o P
erso
nal M
enu
w/o
Pas
swor
d0-
67Bu
s Ac
cess
Pas
swor
d0-
7*Cl
ock
Sett
ings
0-70
Dat
e an
d T
ime
0-71
Dat
e Fo
rmat
0-72
Tim
e Fo
rmat
0-73
Tim
e Zo
ne Offset
0-74
DST
/Sum
mer
time
0-76
DST
/Sum
mer
time
Star
t0-
77D
ST/S
umm
ertim
e En
d0-
79Cl
ock
Faul
t0-
81W
orki
ng D
ays
0-82
Addi
tiona
l Wor
king
Day
s0-
83Ad
ditio
nal N
on-W
orki
ng D
ays
0-89
Dat
e an
d T
ime
Read
out
1-**
Load
and
Mot
or1-
0*G
ener
al S
ettin
gs
1-00
Confi
guratio
n M
ode
1-03
Torq
ue C
hara
cter
istic
s1-
06Cl
ockw
ise
Dire
ctio
n1-
1*M
otor
Sel
ectio
n1-
10M
otor
Con
stru
ctio
n1-
1*VV
C+ P
M/S
YN R
M1-
14D
ampi
ng G
ain
1-15
Low
Spe
ed F
ilter
Tim
e Co
nst.
1-16
Hig
h S
peed
Filt
er T
ime
Cons
t.1-
17Vo
ltage
filte
r tim
e co
nst.
1-2*
Mot
or D
ata
1-20
Mot
or P
ower
[kW
]1-
21M
otor
Pow
er [H
P]1-
22M
otor
Vol
tage
1-23
Mot
or F
requ
ency
1-24
Mot
or C
urre
nt1-
25M
otor
Nom
inal
Spe
ed1-
26M
otor
Con
t. R
ated
Tor
que
1-28
Mot
or R
otat
ion
Che
ck1-
29Au
tom
atic
Mot
or A
dapt
atio
n (A
MA
)1-
3*A
dv. M
otor
Dat
a1-
30St
ator
Res
ista
nce
(Rs)
1-31
Roto
r Re
sist
ance
(Rr)
1-35
Mai
n R
eact
ance
(Xh)
1-36
Iron
Los
s Re
sist
ance
(Rfe
)1-
37d-
axis
Indu
ctan
ce (L
d)1-
38q-
axis
Indu
ctan
ce (L
q)1-
39M
otor
Pol
es1-
40Ba
ck E
MF
at 1
000
RPM
1-44
d-ax
is In
duct
ance
Sat
. (Ld
Sat)
1-45
q-ax
is In
duct
ance
Sat
. (Lq
Sat)
1-46
Posi
tion
Det
ectio
n G
ain
1-47
Torq
ue C
alib
ratio
n1-
48In
duct
ance
Sat
. Poi
nt1-
5*Lo
ad In
dep.
Set
ting
1-50
Mot
or M
agne
tisat
ion
at
Zero
Spe
ed1-
51M
in S
peed
Nor
mal
Mag
netis
ing
[RPM
]1-
52M
in S
peed
Nor
mal
Mag
netis
ing
[Hz]
1-58
Flyi
ng S
tart
Tes
t Pu
lses
Cur
rent
1-59
Flyi
ng S
tart
Tes
t Pu
lses
Fre
quen
cy1-
6*Lo
ad D
epen
. Set
ting
1-60
Low
Spe
ed L
oad
Com
pens
atio
n1-
61H
igh
Spe
ed L
oad
Com
pens
atio
n1-
62Sl
ip C
ompe
nsat
ion
1-63
Slip
Com
pens
atio
n T
ime
Cons
tant
1-64
Reso
nanc
e D
ampe
ning
1-65
Reso
nanc
e D
ampe
ning
Tim
e Co
nsta
nt1-
66M
in. C
urre
nt a
t Lo
w S
peed
1-7*
Star
t A
djus
tmen
ts1-
70PM
Sta
rt M
ode
1-71
Star
t D
elay
1-72
Star
t Fu
nctio
n1-
73Fl
ying
Sta
rt1-
77Co
mpr
esso
r St
art
Max
Spe
ed [R
PM]
1-78
Com
pres
sor
Star
t M
ax S
peed
[Hz]
1-79
Com
pres
sor
Star
t M
ax T
ime
to T
rip1-
8*St
op A
djus
tmen
ts1-
80Fu
nctio
n a
t St
op1-
81M
in S
peed
for
Func
tion
at
Stop
[RPM
]
1-82
Min
Spe
ed fo
r Fu
nctio
n a
t St
op [H
z]1-
86Tr
ip S
peed
Low
[RPM
]1-
87Tr
ip S
peed
Low
[Hz]
1-9*
Mot
or T
empe
ratu
re1-
90M
otor
The
rmal
Pro
tect
ion
1-91
Mot
or E
xter
nal F
an1-
93Th
erm
isto
r So
urce
1-94
ATEX
ETR
cur
.lim
. spe
ed re
duct
ion
1-98
ATEX
ETR
inte
rpol
. poi
nts
freq
.1-
99AT
EX E
TR in
terp
ol p
oint
s cu
rren
t2-
**Br
akes
2-0*
DC-
Brak
e2-
00D
C H
old/
Preh
eat
Curr
ent
2-01
DC
Bra
ke C
urre
nt2-
02D
C B
raki
ng T
ime
2-03
DC
Bra
ke C
ut In
Spe
ed [R
PM]
2-04
DC
Bra
ke C
ut In
Spe
ed [H
z]2-
06Pa
rkin
g C
urre
nt2-
07Pa
rkin
g T
ime
2-1*
Brak
e En
ergy
Fun
ct.
2-10
Brak
e Fu
nctio
n2-
11Br
ake
Resi
stor
(ohm
)2-
12Br
ake
Pow
er L
imit
(kW
)2-
13Br
ake
Pow
er M
onito
ring
2-15
Brak
e Ch
eck
2-16
AC b
rake
Max
. Cur
rent
2-17
Ove
r-vo
ltage
Con
trol
3-**
Refe
renc
e /
Ram
ps3-
0*Re
fere
nce
Lim
its3-
02M
inim
um R
efer
ence
3-03
Max
imum
Ref
eren
ce3-
04Re
fere
nce
Func
tion
3-1*
Refe
renc
es3-
10Pr
eset
Ref
eren
ce3-
11Jo
g S
peed
[Hz]
3-13
Refe
renc
e Si
te3-
14Pr
eset
Rel
ativ
e Re
fere
nce
3-15
Refe
renc
e 1
Sour
ce3-
16Re
fere
nce
2 So
urce
3-17
Refe
renc
e 3
Sour
ce3-
19Jo
g S
peed
[RPM
]3-
4*Ra
mp
13-
41Ra
mp
1 R
amp
Up
Tim
e3-
42Ra
mp
1 R
amp
Dow
n T
ime
3-5*
Ram
p 2
3-51
Ram
p 2
Ram
p U
p T
ime
3-52
Ram
p 2
Ram
p D
own
Tim
e3-
8*O
ther
Ram
ps3-
80Jo
g R
amp
Tim
e3-
81Q
uick
Sto
p R
amp
Tim
e3-
82St
artin
g R
amp
Up
Tim
e3-
9*D
igita
l Pot
.Met
er3-
90St
ep S
ize
3-91
Ram
p T
ime
3-92
Pow
er R
esto
re3-
93M
axim
um L
imit
3-94
Min
imum
Lim
it3-
95Ra
mp
Del
ay4-
**Li
mits
/ W
arni
ngs
4-1*
Mot
or L
imits
4-10
Mot
or S
peed
Dire
ctio
n4-
11M
otor
Spe
ed L
ow L
imit
[RPM
]4-
12M
otor
Spe
ed L
ow L
imit
[Hz]
4-13
Mot
or S
peed
Hig
h L
imit
[RPM
]4-
14M
otor
Spe
ed H
igh
Lim
it [H
z]4-
16To
rque
Lim
it M
otor
Mod
e4-
17To
rque
Lim
it G
ener
ator
Mod
e4-
18Cu
rren
t Li
mit
4-19
Max
Out
put
Freq
uenc
y4-
5*A
dj. W
arni
ngs
4-50
War
ning
Cur
rent
Low
4-51
War
ning
Cur
rent
Hig
h4-
52W
arni
ng S
peed
Low
4-53
War
ning
Spe
ed H
igh
4-54
War
ning
Ref
eren
ce L
ow4-
55W
arni
ng R
efer
ence
Hig
h4-
56W
arni
ng F
eedb
ack
Low
4-57
War
ning
Fee
dbac
k H
igh
4-58
Mis
sing
Mot
or P
hase
Fun
ctio
n4-
59M
otor
Che
ck A
t St
art
4-6*
Spee
d B
ypas
s4-
60By
pass
Spe
ed F
rom
[RPM
]4-
61By
pass
Spe
ed F
rom
[Hz]
4-62
Bypa
ss S
peed
To
[RPM
]4-
63By
pass
Spe
ed T
o [H
z]4-
64Se
mi-A
uto
Byp
ass
Set-
up5-
**D
igita
l In/
Out
5-0*
Dig
ital I
/O m
ode
5-00
Dig
ital I
/O M
ode
5-01
Term
inal
27
Mod
e5-
02Te
rmin
al 2
9 M
ode
5-1*
Dig
ital I
nput
s5-
10Te
rmin
al 1
8 D
igita
l Inp
ut5-
11Te
rmin
al 1
9 D
igita
l Inp
ut5-
12Te
rmin
al 2
7 D
igita
l Inp
ut5-
13Te
rmin
al 2
9 D
igita
l Inp
ut5-
14Te
rmin
al 3
2 D
igita
l Inp
ut5-
15Te
rmin
al 3
3 D
igita
l Inp
ut5-
16Te
rmin
al X
30/2
Dig
ital I
nput
5-17
Term
inal
X30
/3 D
igita
l Inp
ut5-
18Te
rmin
al X
30/4
Dig
ital I
nput
5-19
Term
inal
37
Safe
Sto
p5-
20Te
rmin
al X
46/1
Dig
ital I
nput
5-21
Term
inal
X46
/3 D
igita
l Inp
ut5-
22Te
rmin
al X
46/5
Dig
ital I
nput
5-23
Term
inal
X46
/7 D
igita
l Inp
ut5-
24Te
rmin
al X
46/9
Dig
ital I
nput
5-25
Term
inal
X46
/11
Dig
ital I
nput
5-26
Term
inal
X46
/13
Dig
ital I
nput
5-3*
Dig
ital O
utpu
ts5-
30Te
rmin
al 2
7 D
igita
l Out
put
5-31
Term
inal
29
Dig
ital O
utpu
t5-
32Te
rm X
30/6
Dig
i Out
(MCB
101
)5-
33Te
rm X
30/7
Dig
i Out
(MCB
101
)5-
4*Re
lays
5-40
Func
tion
Rel
ay5-
41O
n D
elay
, Rel
ay5-
42Off
Del
ay, R
elay
5-5*
Puls
e In
put
5-50
Term
. 29
Low
Fre
quen
cy5-
51Te
rm. 2
9 H
igh
Fre
quen
cy5-
52Te
rm. 2
9 Lo
w R
ef./F
eedb
. Val
ue5-
53Te
rm. 2
9 H
igh
Ref
./Fee
db. V
alue
5-54
Puls
e Fi
lter
Tim
e Co
nsta
nt #
295-
55Te
rm. 3
3 Lo
w F
requ
ency
5-56
Term
. 33
Hig
h F
requ
ency
5-57
Term
. 33
Low
Ref
./Fee
db. V
alue
5-58
Term
. 33
Hig
h R
ef./F
eedb
. Val
ue5-
59Pu
lse
Filte
r Ti
me
Cons
tant
#33
5-6*
Puls
e O
utpu
t5-
60Te
rmin
al 2
7 Pu
lse
Out
put
Varia
ble
5-62
Puls
e O
utpu
t M
ax F
req
#27
5-63
Term
inal
29
Puls
e O
utpu
t Va
riabl
e5-
65Pu
lse
Out
put
Max
Fre
q #
295-
66Te
rmin
al X
30/6
Pul
se O
utpu
t Va
riabl
e5-
68Pu
lse
Out
put
Max
Fre
q #
X30/
65-
8*I/O
Opt
ions
5-80
AH
F Ca
p R
econ
nect
Del
ay5-
9*Bu
s Co
ntro
lled
5-90
Dig
ital &
Rel
ay B
us C
ontr
ol5-
93Pu
lse
Out
#27
Bus
Con
trol
5-94
Puls
e O
ut #
27 T
imeo
ut P
rese
t5-
95Pu
lse
Out
#29
Bus
Con
trol
5-96
Puls
e O
ut #
29 T
imeo
ut P
rese
t5-
97Pu
lse
Out
#X3
0/6
Bus
Cont
rol
5-98
Puls
e O
ut #
X30/
6 Ti
meo
ut P
rese
t6-
**A
nalo
g In
/Out
6-0*
Ana
log
I/O
Mod
e6-
00Li
ve Z
ero
Tim
eout
Tim
e6-
01Li
ve Z
ero
Tim
eout
Fun
ctio
n6-
02Fi
re M
ode
Live
Zer
o T
imeo
ut F
unct
ion
6-1*
Ana
log
Inpu
t 53
6-10
Term
inal
53
Low
Vol
tage
6-11
Term
inal
53
Hig
h V
olta
ge6-
12Te
rmin
al 5
3 Lo
w C
urre
nt6-
13Te
rmin
al 5
3 H
igh
Cur
rent
6-14
Term
inal
53
Low
Ref
./Fee
db. V
alue
6-15
Term
inal
53
Hig
h R
ef./F
eedb
. Val
ue6-
16Te
rmin
al 5
3 Fi
lter
Tim
e Co
nsta
nt6-
17Te
rmin
al 5
3 Li
ve Z
ero
6-2*
Ana
log
Inpu
t 54
6-20
Term
inal
54
Low
Vol
tage
6-21
Term
inal
54
Hig
h V
olta
ge6-
22Te
rmin
al 5
4 Lo
w C
urre
nt6-
23Te
rmin
al 5
4 H
igh
Cur
rent
6-24
Term
inal
54
Low
Ref
./Fee
db. V
alue
6-25
Term
inal
54
Hig
h R
ef./F
eedb
. Val
ue6-
26Te
rmin
al 5
4 Fi
lter
Tim
e Co
nsta
nt6-
27Te
rmin
al 5
4 Li
ve Z
ero
6-3*
Ana
log
Inpu
t X3
0/11
6-30
Term
inal
X30
/11
Low
Vol
tage
6-31
Term
inal
X30
/11
Hig
h V
olta
ge6-
34Te
rm. X
30/1
1 Lo
w R
ef./F
eedb
. Val
ue6-
35Te
rm. X
30/1
1 H
igh
Ref
./Fee
db. V
alue
6-36
Term
. X30
/11
Filte
r Ti
me
Cons
tant
6-37
Term
. X30
/11
Live
Zer
o
Appendix Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 75
9 9
6-4*
Ana
log
Inpu
t X3
0/12
6-40
Term
inal
X30
/12
Low
Vol
tage
6-41
Term
inal
X30
/12
Hig
h V
olta
ge6-
44Te
rm. X
30/1
2 Lo
w R
ef./F
eedb
. Val
ue6-
45Te
rm. X
30/1
2 H
igh
Ref
./Fee
db. V
alue
6-46
Term
. X30
/12
Filte
r Ti
me
Cons
tant
6-47
Term
. X30
/12
Live
Zer
o6-
5*A
nalo
g O
utpu
t 42
6-50
Term
inal
42
Out
put
6-51
Term
inal
42
Out
put
Min
Sca
le6-
52Te
rmin
al 4
2 O
utpu
t M
ax S
cale
6-53
Term
inal
42
Out
put
Bus
Cont
rol
6-54
Term
inal
42
Out
put
Tim
eout
Pre
set
6-55
Ana
log
Out
put
Filte
r6-
6*A
nalo
g O
utpu
t X3
0/8
6-60
Term
inal
X30
/8 O
utpu
t6-
61Te
rmin
al X
30/8
Min
. Sca
le6-
62Te
rmin
al X
30/8
Max
. Sca
le6-
63Te
rmin
al X
30/8
Out
put
Bus
Cont
rol
6-64
Term
inal
X30
/8 O
utpu
t Ti
meo
ut P
rese
t6-
7*A
nalo
g O
utpu
t X4
5/1
6-70
Term
inal
X45
/1 O
utpu
t6-
71Te
rmin
al X
45/1
Min
. Sca
le6-
72Te
rmin
al X
45/1
Max
. Sca
le6-
73Te
rmin
al X
45/1
Bus
Con
trol
6-74
Term
inal
X45
/1 O
utpu
t Ti
meo
ut P
rese
t6-
8*A
nalo
g O
utpu
t X4
5/3
6-80
Term
inal
X45
/3 O
utpu
t6-
81Te
rmin
al X
45/3
Min
. Sca
le6-
82Te
rmin
al X
45/3
Max
. Sca
le6-
83Te
rmin
al X
45/3
Bus
Con
trol
6-84
Term
inal
X45
/3 O
utpu
t Ti
meo
ut P
rese
t8-
**Co
mm
. and
Opt
ions
8-0*
Gen
eral
Set
tings
8-01
Cont
rol S
ite8-
02Co
ntro
l Sou
rce
8-03
Cont
rol T
imeo
ut T
ime
8-04
Cont
rol T
imeo
ut F
unct
ion
8-05
End-
of-T
imeo
ut F
unct
ion
8-06
Rese
t Co
ntro
l Tim
eout
8-07
Dia
gnos
is T
rigge
r8-
08Re
adou
t Fi
lterin
g8-
09Co
mm
unic
atio
n C
hars
et8-
1*Co
ntro
l Set
tings
8-10
Cont
rol P
rofile
8-13
Confi
gurable
Stat
us W
ord
STW
8-3*
FC P
ort
Sett
ings
8-30
Prot
ocol
8-31
Addr
ess
8-32
Baud
Rat
e8-
33Pa
rity
/ St
op B
its8-
34Es
timat
ed c
ycle
tim
e8-
35M
inim
um R
espo
nse
Del
ay8-
36M
axim
um R
espo
nse
Del
ay8-
37M
axim
um In
ter-
Char
Del
ay8-
39Pr
otoc
ol F
irmw
are
vers
ion
8-4*
FC M
C p
roto
col s
et8-
40Te
legr
am S
elec
tion
8-42
PCD
Writ
e Co
nfigu
ratio
n
8-43
PCD
Rea
d Con
figuration
8-5*
Dig
ital/B
us8-
50Co
astin
g S
elec
t8-
52D
C B
rake
Sel
ect
8-53
Star
t Se
lect
8-54
Reve
rsin
g S
elec
t8-
55Se
t-up
Sel
ect
8-56
Pres
et R
efer
ence
Sel
ect
8-7*
BACn
et8-
70BA
Cnet
Dev
ice
Inst
ance
8-72
MS/
TP M
ax M
aste
rs8-
73M
S/TP
Max
Info
Fra
mes
8-74
"I-A
m"
Serv
ice
8-75
Initi
alis
atio
n P
assw
ord
8-8*
FC P
ort
Dia
gnos
tics
8-80
Bus
Mes
sage
Cou
nt8-
81Bu
s Er
ror
Coun
t8-
82Sl
ave
Mes
sage
s Rc
vd8-
83Sl
ave
Erro
r Co
unt
8-84
Slav
e M
essa
ges
Sent
8-85
Slav
e Ti
meo
ut E
rror
s8-
89D
iagn
ostic
s Co
unt
8-9*
Bus
Jog
/ F
eedb
ack
8-90
Bus
Jog
1 S
peed
8-91
Bus
Jog
2 S
peed
8-94
Bus
Feed
back
18-
95Bu
s Fe
edba
ck 2
8-96
Bus
Feed
back
39-
**PR
OFI
driv
e9-
00Se
tpoi
nt9-
07Ac
tual
Val
ue9-
15PC
D W
rite Co
nfigu
ratio
n9-
16PC
D R
ead
Con
figuration
9-18
Nod
e Ad
dres
s9-
22Te
legr
am S
elec
tion
9-23
Para
met
ers
for
Sign
als
9-27
Para
met
er E
dit
9-28
Proc
ess
Cont
rol
9-44
Faul
t M
essa
ge C
ount
er9-
45Fa
ult
Code
9-47
Faul
t N
umbe
r9-
52Fa
ult
Situ
atio
n C
ount
er9-
53Profi
bus
War
ning
Wor
d9-
63Ac
tual
Bau
d R
ate
9-64
Dev
ice Iden
tificatio
n9-
65Profi
le N
umbe
r9-
67Co
ntro
l Wor
d 1
9-68
Stat
us W
ord
19-
70Pr
ogra
mm
ing
Set
-up
9-71
Profi
bus
Save
Dat
a Va
lues
9-72
Profi
busD
riveR
eset
9-75
DO
Iden
tificatio
n9-
80Defi
ned
Par
amet
ers
(1)
9-81
Defi
ned
Par
amet
ers
(2)
9-82
Defi
ned
Par
amet
ers
(3)
9-83
Defi
ned
Par
amet
ers
(4)
9-84
Defi
ned
Par
amet
ers
(5)
9-85
Defi
ned
Par
amet
ers
(6)
9-90
Chan
ged
Par
amet
ers
(1)
9-91
Chan
ged
Par
amet
ers
(2)
9-92
Chan
ged
Par
amet
ers
(3)
9-93
Chan
ged
Par
amet
ers
(4)
9-94
Chan
ged
Par
amet
ers
(5)
9-99
Profi
bus
Revi
sion
Cou
nter
10-*
*CA
N F
ield
bus
10-0
*Co
mm
on S
ettin
gs10
-00
CAN
Pro
toco
l10
-01
Baud
Rat
e Se
lect
10-0
2M
AC ID
10-0
5Re
adou
t Tr
ansm
it E
rror
Cou
nter
10-0
6Re
adou
t Re
ceiv
e Er
ror
Coun
ter
10-0
7Re
adou
t Bu
s Off
Cou
nter
10-1
*D
evic
eNet
10-1
0Pr
oces
s D
ata
Type
Sel
ectio
n10
-11
Proc
ess
Dat
a Co
nfig
Writ
e10
-12
Proc
ess
Dat
a Co
nfig
Rea
d10
-13
War
ning
Par
amet
er10
-14
Net
Ref
eren
ce10
-15
Net
Con
trol
10-2
*CO
S Fi
lters
10-2
0CO
S Fi
lter
110
-21
COS
Filte
r 2
10-2
2CO
S Fi
lter
310
-23
COS
Filte
r 4
10-3
*Pa
ram
eter
Acc
ess
10-3
0A
rray
Inde
x10
-31
Stor
e D
ata
Valu
es10
-32
Dev
icen
et R
evis
ion
10-3
3St
ore
Alw
ays
10-3
4D
evic
eNet
Pro
duct
Cod
e10
-39
Dev
icen
et F
Par
amet
ers
11-*
*Lo
nWor
ks11
-0*
LonW
orks
ID11
-00
Neu
ron
ID11
-1*
LON
Fun
ctio
ns11
-10
Driv
e Profi
le11
-15
LON
War
ning
Wor
d11
-17
XIF
Revi
sion
11-1
8Lo
nWor
ks R
evis
ion
11-2
*LO
N P
aram
. Acc
ess
11-2
1St
ore
Dat
a Va
lues
12-*
*Et
hern
et12
-0*
IP S
ettin
gs12
-00
IP A
ddre
ss A
ssig
nmen
t12
-01
IP A
ddre
ss12
-02
Subn
et M
ask
12-0
3D
efau
lt G
atew
ay12
-04
DH
CP S
erve
r12
-05
Leas
e Ex
pire
s12
-06
Nam
e Se
rver
s12
-07
Dom
ain
Nam
e12
-08
Hos
t N
ame
12-0
9Ph
ysic
al A
ddre
ss12
-1*
Ethe
rnet
Lin
k Pa
ram
eter
s12
-10
Link
Sta
tus
12-1
1Li
nk D
urat
ion
12-1
2Au
to N
egot
iatio
n12
-13
Link
Spe
ed
12-1
4Li
nk D
uple
x12
-18
Supe
rvis
or M
AC12
-19
Supe
rvis
or IP
Add
r.12
-2*
Proc
ess
Dat
a12
-20
Cont
rol I
nsta
nce
12-2
1Pr
oces
s D
ata Co
nfig
Writ
e12
-22
Proc
ess
Dat
a Co
nfig
Rea
d12
-27
Prim
ary
Mas
ter
12-2
8St
ore
Dat
a Va
lues
12-2
9St
ore
Alw
ays
12-3
*Et
herN
et/IP
12-3
0W
arni
ng P
aram
eter
12-3
1N
et R
efer
ence
12-3
2N
et C
ontr
ol12
-33
CIP
Rev
isio
n12
-34
CIP
Pro
duct
Cod
e12
-35
EDS
Para
met
er12
-37
COS
Inhi
bit
Tim
er12
-38
COS
Filte
r12
-4*
Mod
bus
TCP
12-4
0St
atus
Par
amet
er12
-41
Slav
e M
essa
ge C
ount
12-4
2Sl
ave
Exce
ptio
n M
essa
ge C
ount
12-7
*BA
Cnet
12-7
0BA
Cnet
Sta
tus
12-7
1BA
Cnet
Dat
alin
k12
-72
BACn
et U
DP
Por
t12
-75
BBM
D IP
Add
ress
12-7
6BB
MD
Por
t12
-77
BBM
D R
eg. I
nter
val
12-7
8D
evic
e ID
Con
flict
Det
ectio
n12
-79
Mes
sage
Cou
nter
12-8
*O
ther
Eth
erne
t Se
rvic
es12
-80
FTP
Ser
ver
12-8
1H
TTP
Ser
ver
12-8
2SM
TP S
ervi
ce12
-83
SNM
P A
gent
12-8
4Ad
dres
s Co
nflict
Det
ectio
n12
-85
ACD
Las
t Co
nflict
12-8
9Tr
ansp
aren
t So
cket
Cha
nnel
Por
t12
-9*
Adv
ance
d E
ther
net
Serv
ices
12-9
0Ca
ble
Dia
gnos
tic12
-91
Auto
Cro
ss O
ver
12-9
2IG
MP
Sno
opin
g12
-93
Cabl
e Er
ror
Leng
th12
-94
Broa
dcas
t St
orm
Pro
tect
ion
12-9
5In
activ
ity t
imeo
ut12
-96
Port
Con
fig12
-97
QoS
Prio
rity
12-9
8In
terf
ace
Coun
ters
12-9
9M
edia
Cou
nter
s13
-**
Smar
t Lo
gic
13-0
*SL
C S
ettin
gs13
-00
SL C
ontr
olle
r M
ode
13-0
1St
art
Even
t13
-02
Stop
Eve
nt13
-03
Rese
t SL
C13
-1*
Com
para
tors
13-1
0Co
mpa
rato
r O
pera
nd
13-1
1Co
mpa
rato
r O
pera
tor
13-1
2Co
mpa
rato
r Va
lue
13-2
*Ti
mer
s13
-20
SL C
ontr
olle
r Ti
mer
13-4
*Lo
gic
Rule
s13
-40
Logi
c Ru
le B
oole
an 1
13-4
1Lo
gic
Rule
Ope
rato
r 1
13-4
2Lo
gic
Rule
Boo
lean
213
-43
Logi
c Ru
le O
pera
tor
213
-44
Logi
c Ru
le B
oole
an 3
13-5
*St
ates
13-5
1SL
Con
trol
ler
Even
t13
-52
SL C
ontr
olle
r Ac
tion
13-9
*U
ser Defi
ned
Ale
rts
13-9
0A
lert
Trig
ger
13-9
1A
lert
Act
ion
13-9
2A
lert
Tex
t13
-9*
Use
r Defi
ned
Rea
dout
s13
-97
Ale
rt A
larm
Wor
d13
-98
Ale
rt W
arni
ng W
ord
13-9
9A
lert
Sta
tus
Wor
d14
-**
Spec
ial F
unct
ions
14-0
*In
vert
er S
witc
hing
14-0
0Sw
itchi
ng P
atte
rn14
-01
Switc
hing
Fre
quen
cy14
-03
Ove
rmod
ulat
ion
14-0
4PW
M R
ando
m14
-1*
Mai
ns On/Off
14-1
0M
ains
Fai
lure
14-1
1M
ains
Vol
tage
at
Mai
ns F
ault
14-1
2Fu
nctio
n a
t M
ains
Imba
lanc
e14
-16
Kin.
Bac
kup
Gai
n14
-2*
Rese
t Fu
nctio
ns14
-20
Rese
t M
ode
14-2
1Au
tom
atic
Res
tart
Tim
e14
-22
Ope
ratio
n M
ode
14-2
3Ty
peco
de S
ettin
g14
-25
Trip
Del
ay a
t To
rque
Lim
it14
-26
Trip
Del
ay a
t In
vert
er F
ault
14-2
8Pr
oduc
tion
Set
tings
14-2
9Se
rvic
e Co
de14
-3*
Curr
ent
Lim
it C
trl.
14-3
0Cu
rren
t Li
m C
trl,
Prop
ortio
nal G
ain
14-3
1Cu
rren
t Li
m C
trl,
Inte
grat
ion
Tim
e14
-32
Curr
ent
Lim
Ctr
l, Fi
lter
Tim
e14
-4*
Ener
gy O
ptim
isin
g14
-40
VT L
evel
14-4
1A
EO M
inim
um M
agne
tisat
ion
14-4
2M
inim
um A
EO F
requ
ency
14-4
3M
otor
Cos
phi
14-5
*En
viro
nmen
t14
-50
RFI F
ilter
14-5
1D
C L
ink
Com
pens
atio
n14
-52
Fan
Con
trol
14-5
3Fa
n M
onito
r14
-55
Out
put
Filte
r14
-59
Actu
al N
umbe
r of
Inve
rter
Uni
ts14
-6*
Aut
o D
erat
e14
-60
Func
tion
at
Ove
r Te
mpe
ratu
re
Appendix VLT® HVAC Drive FC 102
76 Danfoss A/S © 02/2017 All rights reserved. MG16D402
99
14-6
1Fu
nctio
n a
t In
vert
er O
verlo
ad14
-62
Inv.
Ove
rload
Der
ate
Curr
ent
14-8
*O
ptio
ns14
-80
Opt
ion
Sup
plie
d b
y Ex
tern
al 2
4VD
C14
-88
Opt
ion
Dat
a St
orag
e14
-89
Opt
ion
Det
ectio
n14
-9*
Faul
t Se
ttin
gs14
-90
Faul
t Le
vel
15-*
*D
rive
Info
rmat
ion
15-0
*O
pera
ting
Dat
a15
-00
Ope
ratin
g h
ours
15-0
1Ru
nnin
g H
ours
15-0
2kW
h C
ount
er15
-03
Pow
er U
p's
15-0
4O
ver
Tem
p's
15-0
5O
ver
Volt'
s15
-06
Rese
t kW
h C
ount
er15
-07
Rese
t Ru
nnin
g H
ours
Cou
nter
15-0
8N
umbe
r of
Sta
rts
15-1
*D
ata
Log
Set
tings
15-1
0Lo
ggin
g S
ourc
e15
-11
Logg
ing
Inte
rval
15-1
2Tr
igge
r Ev
ent
15-1
3Lo
ggin
g M
ode
15-1
4Sa
mpl
es B
efor
e Tr
igge
r15
-2*
His
tori
c Lo
g15
-20
His
toric
Log
: Eve
nt15
-21
His
toric
Log
: Val
ue15
-22
His
toric
Log
: Tim
e15
-23
His
toric
log:
Dat
e an
d T
ime
15-3
*A
larm
Log
15-3
0A
larm
Log
: Err
or C
ode
15-3
1A
larm
Log
: Val
ue15
-32
Ala
rm L
og: T
ime
15-3
3A
larm
Log
: Dat
e an
d T
ime
15-4
*D
rive
Iden
tificatio
n15
-40
FC T
ype
15-4
1Po
wer
Sec
tion
15-4
2Vo
ltage
15-4
3So
ftw
are
Vers
ion
15-4
4O
rder
ed T
ypec
ode
Strin
g15
-45
Actu
al T
ypec
ode
Strin
g15
-46
Freq
uenc
y Co
nver
ter
Ord
erin
g N
o15
-47
Pow
er C
ard
Ord
erin
g N
o15
-48
LCP
Id N
o15
-49
SW ID
Con
trol
Car
d15
-50
SW ID
Pow
er C
ard
15-5
1Fr
eque
ncy
Conv
erte
r Se
rial N
umbe
r15
-53
Pow
er C
ard
Ser
ial N
umbe
r15
-54
Confi
g F
ile N
ame
15-5
5Ve
ndor
URL
15-5
6Ve
ndor
Nam
e15
-58
Smar
t Se
tup
File
nam
e15
-59
File
nam
e15
-6*
Opt
ion
Iden
t15
-60
Opt
ion
Mou
nted
15-6
1O
ptio
n S
W V
ersi
on15
-62
Opt
ion
Ord
erin
g N
o15
-63
Opt
ion
Ser
ial N
o
15-6
4A
pplic
atio
n V
ersi
on15
-70
Opt
ion
in S
lot
A15
-71
Slot
A O
ptio
n S
W V
ersi
on15
-72
Opt
ion
in S
lot
B15
-73
Slot
B O
ptio
n S
W V
ersi
on15
-74
Opt
ion
in S
lot
C0/E
015
-75
Slot
C0/
E0 O
ptio
n S
W V
ersi
on15
-76
Opt
ion
in S
lot
C1/E
115
-77
Slot
C1/
E1 O
ptio
n S
W V
ersi
on15
-8*
Ope
ratin
g D
ata
II15
-80
Fan
Run
ning
Hou
rs15
-81
Pres
et F
an R
unni
ng H
ours
15-9
*Pa
ram
eter
Info
15-9
2Defi
ned
Par
amet
ers
15-9
3Mod
ified
Par
amet
ers
15-9
8D
rive Iden
tificatio
n15
-99
Para
met
er M
etad
ata
16-*
*D
ata
Read
outs
16-0
*G
ener
al S
tatu
s16
-00
Cont
rol W
ord
16-0
1Re
fere
nce
[Uni
t]16
-02
Refe
renc
e [%
]16
-03
Stat
us W
ord
16-0
5M
ain
Act
ual V
alue
[%]
16-0
9Cu
stom
Rea
dout
16-1
*M
otor
Sta
tus
16-1
0Po
wer
[kW
]16
-11
Pow
er [h
p]16
-12
Mot
or V
olta
ge16
-13
Freq
uenc
y16
-14
Mot
or c
urre
nt16
-15
Freq
uenc
y [%
]16
-16
Torq
ue [N
m]
16-1
7Sp
eed
[RPM
]16
-18
Mot
or T
herm
al16
-20
Mot
or A
ngle
16-2
2To
rque
[%]
16-2
3M
otor
Sha
ft P
ower
[kW
]16
-24
Calib
rate
d S
tato
r Re
sist
ance
16-2
6Po
wer
Filt
ered
[kW
]16
-27
Pow
er F
ilter
ed [h
p]16
-3*
Dri
ve S
tatu
s16
-30
DC
Lin
k Vo
ltage
16-3
1Sy
stem
Tem
p.16
-32
Brak
e En
ergy
/s
16-3
3Br
ake
Ener
gy A
vera
ge16
-34
Hea
tsin
k Te
mp.
16-3
5In
vert
er T
herm
al16
-36
Inv.
Nom
. Cur
rent
16-3
7In
v. M
ax. C
urre
nt16
-38
SL C
ontr
olle
r St
ate
16-3
9Co
ntro
l Car
d T
emp.
16-4
0Lo
ggin
g Buff
er F
ull
16-4
1Lo
ggin
g Buff
er F
ull
16-4
3Ti
med
Act
ions
Sta
tus
16-4
9Cu
rren
t Fa
ult
Sour
ce16
-5*
Ref.
& F
eedb
.16
-50
Exte
rnal
Ref
eren
ce16
-52
Feed
back
[Uni
t]
16-5
3D
igi P
ot R
efer
ence
16-5
4Fe
edba
ck 1
[Uni
t]16
-55
Feed
back
2 [U
nit]
16-5
6Fe
edba
ck 3
[Uni
t]16
-58
PID
Out
put
[%]
16-5
9Ad
just
ed S
etpo
int
16-6
*In
puts
& O
utpu
ts16
-60
Dig
ital I
nput
16-6
1Te
rmin
al 5
3 Sw
itch
Set
ting
16-6
2A
nalo
g In
put
5316
-63
Term
inal
54
Switc
h S
ettin
g16
-64
Ana
log
Inpu
t 54
16-6
5A
nalo
g O
utpu
t 42
[mA
]16
-66
Dig
ital O
utpu
t [b
in]
16-6
7Pu
lse
Inpu
t #2
9 [H
z]16
-68
Puls
e In
put
#33
[Hz]
16-6
9Pu
lse
Out
put
#27
[Hz]
16-7
0Pu
lse
Out
put
#29
[Hz]
16-7
1Re
lay
Out
put
[bin
]16
-72
Coun
ter
A16
-73
Coun
ter
B16
-75
Ana
log
In X
30/1
116
-76
Ana
log
In X
30/1
216
-77
Ana
log
Out
X30
/8 [m
A]
16-7
8A
nalo
g O
ut X
45/1
[mA
]16
-79
Ana
log
Out
X45
/3 [m
A]
16-8
*Fi
eldb
us &
FC
Por
t16
-80
Fiel
dbus
CTW
116
-82
Fiel
dbus
REF
116
-84
Com
m. O
ptio
n S
TW16
-85
FC P
ort
CTW
116
-86
FC P
ort
REF
116
-9*
Dia
gnos
is R
eado
uts
16-9
0A
larm
Wor
d16
-91
Ala
rm W
ord
216
-92
War
ning
Wor
d16
-93
War
ning
Wor
d 2
16-9
4Ex
t. S
tatu
s W
ord
16-9
5Ex
t. S
tatu
s W
ord
216
-96
Mai
nten
ance
Wor
d18
-**
Info
& R
eado
uts
18-0
*M
aint
enan
ce L
og18
-00
Mai
nten
ance
Log
: Ite
m18
-01
Mai
nten
ance
Log
: Act
ion
18-0
2M
aint
enan
ce L
og: T
ime
18-0
3M
aint
enan
ce L
og: D
ate
and
Tim
e18
-1*
Fire
Mod
e Lo
g18
-10
Fire
Mod
e Lo
g:Ev
ent
18-1
1Fi
re M
ode
Log:
Tim
e18
-12
Fire
Mod
e Lo
g: D
ate
and
Tim
e18
-3*
Inpu
ts &
Out
puts
18-3
0A
nalo
g In
put
X42/
118
-31
Ana
log
Inpu
t X4
2/3
18-3
2A
nalo
g In
put
X42/
518
-33
Ana
log
Out
X42
/7 [
V]
18-3
4A
nalo
g O
ut X
42/9
[V
]18
-35
Ana
log
Out
X42
/11
[V]
18-3
6A
nalo
g In
put
X48/
2 [m
A]
18-3
7Te
mp.
Inpu
t X4
8/4
18-3
8Te
mp.
Inpu
t X4
8/7
18-3
9Te
mp.
Inpu
t X4
8/10
18-5
*Re
f. &
Fee
db.
18-5
0Se
nsor
less
Rea
dout
[uni
t]18
-57
Air
Pre
ssur
e to
Flo
w A
ir F
low
18-6
*In
puts
& O
utpu
ts 2
18-6
0D
igita
l Inp
ut 2
18-7
*Re
ctifier
Sta
tus
18-7
0M
ains
Vol
tage
18-7
1M
ains
Fre
quen
cy18
-72
Mai
ns Im
bala
nce
18-7
5Re
ctifier
DC
Vol
t.20
-**
Dri
ve C
lose
d L
oop
20-0
*Fe
edba
ck20
-00
Feed
back
1 S
ourc
e20
-01
Feed
back
1 C
onve
rsio
n20
-02
Feed
back
1 S
ourc
e U
nit
20-0
3Fe
edba
ck 2
Sou
rce
20-0
4Fe
edba
ck 2
Con
vers
ion
20-0
5Fe
edba
ck 2
Sou
rce
Uni
t20
-06
Feed
back
3 S
ourc
e20
-07
Feed
back
3 C
onve
rsio
n20
-08
Feed
back
3 S
ourc
e U
nit
20-1
2Re
fere
nce/
Feed
back
Uni
t20
-13
Min
imum
Ref
eren
ce/F
eedb
.20
-14
Max
imum
Ref
eren
ce/F
eedb
.20
-2*
Feed
back
/Set
poin
t20
-20
Feed
back
Fun
ctio
n20
-21
Setp
oint
120
-22
Setp
oint
220
-23
Setp
oint
320
-3*
Feed
b. A
dv. C
onv.
20-3
0Re
frig
eran
t20
-31
Use
r Defi
ned
Ref
riger
ant
A1
20-3
2U
ser Defi
ned
Ref
riger
ant
A2
20-3
3U
ser Defi
ned
Ref
riger
ant
A3
20-3
4D
uct
1 A
rea
[m2]
20-3
5D
uct
1 A
rea
[in2]
20-3
6D
uct
2 A
rea
[m2]
20-3
7D
uct
2 A
rea
[in2]
20-3
8A
ir D
ensi
ty F
acto
r [%
]20
-6*
Sens
orle
ss20
-60
Sens
orle
ss U
nit
20-6
9Se
nsor
less
Info
rmat
ion
20-7
*PI
D A
utot
unin
g20
-70
Clos
ed L
oop
Typ
e20
-71
PID
Per
form
ance
20-7
2PI
D O
utpu
t Ch
ange
20-7
3M
inim
um F
eedb
ack
Leve
l20
-74
Max
imum
Fee
dbac
k Le
vel
20-7
9PI
D A
utot
unin
g20
-8*
PID
Bas
ic S
ettin
gs20
-81
PID
Nor
mal
/ In
vers
e Co
ntro
l20
-82
PID
Sta
rt S
peed
[RPM
]20
-83
PID
Sta
rt S
peed
[Hz]
20-8
4O
n R
efer
ence
Ban
dwid
th20
-9*
PID
Con
trol
ler
20-9
1PI
D A
nti W
indu
p20
-93
PID
Pro
port
iona
l Gai
n
20-9
4PI
D In
tegr
al T
ime
20-9
5PI
D Differen
tiatio
n T
ime
20-9
6PI
D Diff. G
ain
Lim
it21
-**
Ext.
Clo
sed
Loo
p21
-0*
Ext.
CL
Aut
otun
ing
21-0
0Cl
osed
Loo
p T
ype
21-0
1PI
D P
erfo
rman
ce21
-02
PID
Out
put
Chan
ge21
-03
Min
imum
Fee
dbac
k Le
vel
21-0
4M
axim
um F
eedb
ack
Leve
l21
-09
PID
Aut
otun
ing
21-1
*Ex
t. C
L 1
Ref./
Fb.
21-1
0Ex
t. 1
Ref
./Fee
dbac
k U
nit
21-1
1Ex
t. 1
Min
imum
Ref
eren
ce21
-12
Ext.
1 M
axim
um R
efer
ence
21-1
3Ex
t. 1
Ref
eren
ce S
ourc
e21
-14
Ext.
1 F
eedb
ack
Sour
ce21
-15
Ext.
1 S
etpo
int
21-1
7Ex
t. 1
Ref
eren
ce [U
nit]
21-1
8Ex
t. 1
Fee
dbac
k [U
nit]
21-1
9Ex
t. 1
Out
put
[%]
21-2
*Ex
t. C
L 1
PID
21-2
0Ex
t. 1
Nor
mal
/Inve
rse
Cont
rol
21-2
1Ex
t. 1
Pro
port
iona
l Gai
n21
-22
Ext.
1 In
tegr
al T
ime
21-2
3Ex
t. 1
Differen
tatio
n T
ime
21-2
4Ex
t. 1
Dif.
Gai
n L
imit
21-3
*Ex
t. C
L 2
Ref./
Fb.
21-3
0Ex
t. 2
Ref
./Fee
dbac
k U
nit
21-3
1Ex
t. 2
Min
imum
Ref
eren
ce21
-32
Ext.
2 M
axim
um R
efer
ence
21-3
3Ex
t. 2
Ref
eren
ce S
ourc
e21
-34
Ext.
2 F
eedb
ack
Sour
ce21
-35
Ext.
2 S
etpo
int
21-3
7Ex
t. 2
Ref
eren
ce [U
nit]
21-3
8Ex
t. 2
Fee
dbac
k [U
nit]
21-3
9Ex
t. 2
Out
put
[%]
21-4
*Ex
t. C
L 2
PID
21-4
0Ex
t. 2
Nor
mal
/Inve
rse
Cont
rol
21-4
1Ex
t. 2
Pro
port
iona
l Gai
n21
-42
Ext.
2 In
tegr
al T
ime
21-4
3Ex
t. 2
Differen
tatio
n T
ime
21-4
4Ex
t. 2
Dif.
Gai
n L
imit
21-5
*Ex
t. C
L 3
Ref./
Fb.
21-5
0Ex
t. 3
Ref
./Fee
dbac
k U
nit
21-5
1Ex
t. 3
Min
imum
Ref
eren
ce21
-52
Ext.
3 M
axim
um R
efer
ence
21-5
3Ex
t. 3
Ref
eren
ce S
ourc
e21
-54
Ext.
3 F
eedb
ack
Sour
ce21
-55
Ext.
3 S
etpo
int
21-5
7Ex
t. 3
Ref
eren
ce [U
nit]
21-5
8Ex
t. 3
Fee
dbac
k [U
nit]
21-5
9Ex
t. 3
Out
put
[%]
21-6
*Ex
t. C
L 3
PID
21-6
0Ex
t. 3
Nor
mal
/Inve
rse
Cont
rol
21-6
1Ex
t. 3
Pro
port
iona
l Gai
n21
-62
Ext.
3 In
tegr
al T
ime
21-6
3Ex
t. 3
Differen
tatio
n T
ime
21-6
4Ex
t. 3
Dif.
Gai
n L
imit
Appendix Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 77
9 9
22-*
*A
ppl.
Func
tions
22-0
*M
isce
llane
ous
22-0
0Ex
tern
al In
terlo
ck D
elay
22-0
1Po
wer
Filt
er T
ime
22-1
*A
ir P
res.
to
Flo
w22
-10
Air
Pre
ssur
e to
Flo
w S
igna
l sou
rce
22-1
1A
ir P
ress
ure
to F
low
Fan
k-fa
ctor
22-1
2A
ir P
ress
ure
to F
low
Air
den
sity
22-1
3A
ir P
ress
ure
to F
low
Fan
flow
uni
t22
-2*
No-
Flow
Det
ectio
n22
-20
Low
Pow
er A
uto
Set
-up
22-2
1Lo
w P
ower
Det
ectio
n22
-22
Low
Spe
ed D
etec
tion
22-2
3N
o-Fl
ow F
unct
ion
22-2
4N
o-Fl
ow D
elay
22-2
6D
ry P
ump
Fun
ctio
n22
-27
Dry
Pum
p D
elay
22-3
*N
o-Fl
ow P
ower
Tun
ing
22-3
0N
o-Fl
ow P
ower
22-3
1Po
wer
Cor
rect
ion
Fac
tor
22-3
2Lo
w S
peed
[RPM
]22
-33
Low
Spe
ed [H
z]22
-34
Low
Spe
ed P
ower
[kW
]22
-35
Low
Spe
ed P
ower
[HP]
22-3
6H
igh
Spe
ed [R
PM]
22-3
7H
igh
Spe
ed [H
z]22
-38
Hig
h S
peed
Pow
er [k
W]
22-3
9H
igh
Spe
ed P
ower
[HP]
22-4
*Sl
eep
Mod
e22
-40
Min
imum
Run
Tim
e22
-41
Min
imum
Sle
ep T
ime
22-4
2W
ake-
up S
peed
[RPM
]22
-43
Wak
e-up
Spe
ed [H
z]22
-44
Wak
e-up
Ref
./FB
Differen
ce22
-45
Setp
oint
Boo
st22
-46
Max
imum
Boo
st T
ime
22-5
*En
d o
f Cu
rve
22-5
0En
d o
f Cu
rve
Func
tion
22-5
1En
d o
f Cu
rve
Del
ay22
-52
End
of
Curv
e To
lera
nce
22-6
*Br
oken
Bel
t D
etec
tion
22-6
0Br
oken
Bel
t Fu
nctio
n22
-61
Brok
en B
elt
Torq
ue22
-62
Brok
en B
elt
Del
ay22
-7*
Shor
t Cy
cle
Prot
ectio
n22
-75
Shor
t Cy
cle
Prot
ectio
n22
-76
Inte
rval
bet
wee
n S
tart
s22
-77
Min
imum
Run
Tim
e22
-78
Min
imum
Run
Tim
e O
verr
ide
22-7
9M
inim
um R
un T
ime
Ove
rrid
e Va
lue
22-8
*Fl
ow C
ompe
nsat
ion
22-8
0Fl
ow C
ompe
nsat
ion
22-8
1Sq
uare
-line
ar C
urve
App
roxi
mat
ion
22-8
2W
ork
Poin
t Ca
lcul
atio
n22
-83
Spee
d a
t N
o-Fl
ow [R
PM]
22-8
4Sp
eed
at
No-
Flow
[Hz]
22-8
5Sp
eed
at
Des
ign
Poi
nt [R
PM]
22-8
6Sp
eed
at
Des
ign
Poi
nt [H
z]22
-87
Pres
sure
at
No-
Flow
Spe
ed
22-8
8Pr
essu
re a
t Ra
ted
Spe
ed22
-89
Flow
at
Des
ign
Poi
nt22
-90
Flow
at
Rate
d S
peed
23-*
*Ti
me-
base
d F
unct
ions
23-0
*Ti
med
Act
ions
23-0
0O
N T
ime
23-0
1O
N A
ctio
n23
-02
OFF
Tim
e23
-03
OFF
Act
ion
23-0
4O
ccur
renc
e23
-0*
Tim
ed A
ctio
ns S
ettin
gs23
-08
Tim
ed A
ctio
ns M
ode
23-0
9Ti
med
Act
ions
Rea
ctiv
atio
n23
-1*
Mai
nten
ance
23-1
0M
aint
enan
ce It
em23
-11
Mai
nten
ance
Act
ion
23-1
2M
aint
enan
ce T
ime
Base
23-1
3M
aint
enan
ce T
ime
Inte
rval
23-1
4M
aint
enan
ce D
ate
and
Tim
e23
-1*
Mai
nten
ance
Res
et23
-15
Rese
t M
aint
enan
ce W
ord
23-1
6M
aint
enan
ce T
ext
23-5
*En
ergy
Log
23-5
0En
ergy
Log
Res
olut
ion
23-5
1Pe
riod
Sta
rt23
-53
Ener
gy L
og23
-54
Rese
t En
ergy
Log
23-6
*Tr
endi
ng23
-60
Tren
d V
aria
ble
23-6
1Co
ntin
uous
Bin
Dat
a23
-62
Tim
ed B
in D
ata
23-6
3Ti
med
Per
iod
Sta
rt23
-64
Tim
ed P
erio
d S
top
23-6
5M
inim
um B
in V
alue
23-6
6Re
set
Cont
inuo
us B
in D
ata
23-6
7Re
set
Tim
ed B
in D
ata
23-8
*Pa
ybac
k Co
unte
r23
-80
Pow
er R
efer
ence
Fac
tor
23-8
1En
ergy
Cos
t23
-82
Inve
stm
ent
23-8
3En
ergy
Sav
ings
23-8
4Co
st S
avin
gs24
-**
App
l. Fu
nctio
ns 2
24-0
*Fi
re M
ode
24-0
0Fi
re M
ode
Func
tion
24-0
1Fi
re M
ode Co
nfigu
ratio
n24
-02
Fire
Mod
e U
nit
24-0
3Fi
re M
ode
Min
Ref
eren
ce24
-04
Fire
Mod
e M
ax R
efer
ence
24-0
5Fi
re M
ode
Pres
et R
efer
ence
24-0
6Fi
re M
ode
Refe
renc
e So
urce
24-0
7Fi
re M
ode
Feed
back
Sou
rce
24-0
9Fi
re M
ode
Ala
rm H
andl
ing
24-1
*D
rive
Byp
ass
24-1
0D
rive
Bypa
ss F
unct
ion
24-1
1D
rive
Bypa
ss D
elay
Tim
e24
-9*
Mul
ti-M
otor
Fun
ct.
24-9
0M
issi
ng M
otor
Fun
ctio
n24
-91
Mis
sing
Mot
or Coe
fficien
t 1
24-9
2M
issi
ng M
otor
Coe
fficien
t 2
24-9
3M
issi
ng M
otor
Coe
fficien
t 3
24-9
4M
issi
ng M
otor
Coe
fficien
t 4
24-9
5Lo
cked
Rot
or F
unct
ion
24-9
6Lo
cked
Rot
or Coe
fficien
t 1
24-9
7Lo
cked
Rot
or Coe
fficien
t 2
24-9
8Lo
cked
Rot
or Coe
fficien
t 3
24-9
9Lo
cked
Rot
or Coe
fficien
t 4
25-*
*Ca
scad
e Co
ntro
ller
25-0
*Sy
stem
Set
tings
25-0
0Ca
scad
e Co
ntro
ller
25-0
2M
otor
Sta
rt25
-04
Pum
p C
yclin
g25
-05
Fixe
d L
ead
Pum
p25
-06
Num
ber
of P
umps
25-2
*Ba
ndw
idth
Set
tings
25-2
0St
agin
g B
andw
idth
25-2
1O
verr
ide
Band
wid
th25
-22
Fixe
d S
peed
Ban
dwid
th25
-23
SBW
Sta
ging
Del
ay25
-24
SBW
Des
tagi
ng D
elay
25-2
5O
BW T
ime
25-2
6D
esta
ge A
t N
o-Fl
ow25
-27
Stag
e Fu
nctio
n25
-28
Stag
e Fu
nctio
n T
ime
25-2
9D
esta
ge F
unct
ion
25-3
0D
esta
ge F
unct
ion
Tim
e25
-4*
Stag
ing
Set
tings
25-4
0Ra
mp
Dow
n D
elay
25-4
1Ra
mp
Up
Del
ay25
-42
Stag
ing
Thr
esho
ld25
-43
Des
tagi
ng T
hres
hold
25-4
4St
agin
g S
peed
[RPM
]25
-45
Stag
ing
Spe
ed [H
z]25
-46
Des
tagi
ng S
peed
[RPM
]25
-47
Des
tagi
ng S
peed
[Hz]
25-5
*A
ltern
atio
n S
ettin
gs25
-50
Lead
Pum
p A
ltern
atio
n25
-51
Alte
rnat
ion
Eve
nt25
-52
Alte
rnat
ion
Tim
e In
terv
al25
-53
Alte
rnat
ion
Tim
er V
alue
25-5
4A
ltern
atio
n Prede
fined
Tim
e25
-55
Alte
rnat
e if
Load
< 5
0%25
-56
Stag
ing
Mod
e at
Alte
rnat
ion
25-5
8Ru
n N
ext
Pum
p D
elay
25-5
9Ru
n o
n M
ains
Del
ay25
-8*
Stat
us25
-80
Casc
ade
Stat
us25
-81
Pum
p S
tatu
s25
-82
Lead
Pum
p25
-83
Rela
y St
atus
25-8
4Pu
mp
ON
Tim
e25
-85
Rela
y O
N T
ime
25-8
6Re
set
Rela
y Co
unte
rs25
-9*
Serv
ice
25-9
0Pu
mp
Inte
rlock
25-9
1M
anua
l Alte
rnat
ion
26-*
*A
nalo
g I/
O O
ptio
n26
-0*
Ana
log
I/O
Mod
e
26-0
0Te
rmin
al X
42/1
Mod
e26
-01
Term
inal
X42
/3 M
ode
26-0
2Te
rmin
al X
42/5
Mod
e26
-1*
Ana
log
Inpu
t X4
2/1
26-1
0Te
rmin
al X
42/1
Low
Vol
tage
26-1
1Te
rmin
al X
42/1
Hig
h V
olta
ge26
-14
Term
. X42
/1 L
ow R
ef./F
eedb
. Val
ue26
-15
Term
. X42
/1 H
igh
Ref
./Fee
db. V
alue
26-1
6Te
rm. X
42/1
Filt
er T
ime
Cons
tant
26-1
7Te
rm. X
42/1
Liv
e Ze
ro26
-2*
Ana
log
Inpu
t X4
2/3
26-2
0Te
rmin
al X
42/3
Low
Vol
tage
26-2
1Te
rmin
al X
42/3
Hig
h V
olta
ge26
-24
Term
. X42
/3 L
ow R
ef./F
eedb
. Val
ue26
-25
Term
. X42
/3 H
igh
Ref
./Fee
db. V
alue
26-2
6Te
rm. X
42/3
Filt
er T
ime
Cons
tant
26-2
7Te
rm. X
42/3
Liv
e Ze
ro26
-3*
Ana
log
Inpu
t X4
2/5
26-3
0Te
rmin
al X
42/5
Low
Vol
tage
26-3
1Te
rmin
al X
42/5
Hig
h V
olta
ge26
-34
Term
. X42
/5 L
ow R
ef./F
eedb
. Val
ue26
-35
Term
. X42
/5 H
igh
Ref
./Fee
db. V
alue
26-3
6Te
rm. X
42/5
Filt
er T
ime
Cons
tant
26-3
7Te
rm. X
42/5
Liv
e Ze
ro26
-4*
Ana
log
Out
X42
/726
-40
Term
inal
X42
/7 O
utpu
t26
-41
Term
inal
X42
/7 M
in. S
cale
26-4
2Te
rmin
al X
42/7
Max
. Sca
le26
-43
Term
inal
X42
/7 B
us C
ontr
ol26
-44
Term
inal
X42
/7 T
imeo
ut P
rese
t26
-5*
Ana
log
Out
X42
/926
-50
Term
inal
X42
/9 O
utpu
t26
-51
Term
inal
X42
/9 M
in. S
cale
26-5
2Te
rmin
al X
42/9
Max
. Sca
le26
-53
Term
inal
X42
/9 B
us C
ontr
ol26
-54
Term
inal
X42
/9 T
imeo
ut P
rese
t26
-6*
Ana
log
Out
X42
/11
26-6
0Te
rmin
al X
42/1
1 O
utpu
t26
-61
Term
inal
X42
/11
Min
. Sca
le26
-62
Term
inal
X42
/11
Max
. Sca
le26
-63
Term
inal
X42
/11
Bus
Cont
rol
26-6
4Te
rmin
al X
42/1
1 Ti
meo
ut P
rese
t30
-**
Spec
ial F
eatu
res
30-2
*A
dv. S
tart
Adj
ust
30-2
2Lo
cked
Rot
or D
etec
tion
30-2
3Lo
cked
Rot
or D
etec
tion
Tim
e [s
]30
-5*
Uni
t Co
nfigu
ratio
n30
-50
Hea
t Si
nk F
an M
ode
31-*
*By
pass
Opt
ion
31-0
0By
pass
Mod
e31
-01
Bypa
ss S
tart
Tim
e D
elay
31-0
2By
pass
Trip
Tim
e D
elay
31-0
3Te
st M
ode
Activ
atio
n31
-10
Bypa
ss S
tatu
s W
ord
31-1
1By
pass
Run
ning
Hou
rs31
-19
Rem
ote
Bypa
ss A
ctiv
atio
n35
-**
Sens
or In
put
Opt
ion
35-0
*Te
mp.
Inpu
t M
ode
35-0
0Te
rm. X
48/4
Tem
pera
ture
Uni
t
35-0
1Te
rm. X
48/4
Inpu
t Ty
pe35
-02
Term
. X48
/7 T
empe
ratu
re U
nit
35-0
3Te
rm. X
48/7
Inpu
t Ty
pe35
-04
Term
. X48
/10
Tem
pera
ture
Uni
t35
-05
Term
. X48
/10
Inpu
t Ty
pe35
-06
Tem
pera
ture
Sen
sor
Ala
rm F
unct
ion
35-1
*Te
mp.
Inpu
t X4
8/4
35-1
4Te
rm. X
48/4
Filt
er T
ime
Cons
tant
35-1
5Te
rm. X
48/4
Tem
p. M
onito
r35
-16
Term
. X48
/4 L
ow T
emp.
Lim
it35
-17
Term
. X48
/4 H
igh
Tem
p. L
imit
35-2
*Te
mp.
Inpu
t X4
8/7
35-2
4Te
rm. X
48/7
Filt
er T
ime
Cons
tant
35-2
5Te
rm. X
48/7
Tem
p. M
onito
r35
-26
Term
. X48
/7 L
ow T
emp.
Lim
it35
-27
Term
. X48
/7 H
igh
Tem
p. L
imit
35-3
*Te
mp.
Inpu
t X4
8/10
35-3
4Te
rm. X
48/1
0 Fi
lter
Tim
e Co
nsta
nt35
-35
Term
. X48
/10
Tem
p. M
onito
r35
-36
Term
. X48
/10
Low
Tem
p. L
imit
35-3
7Te
rm. X
48/1
0 H
igh
Tem
p. L
imit
35-4
*A
nalo
g In
put
X48/
235
-42
Term
. X48
/2 L
ow C
urre
nt35
-43
Term
. X48
/2 H
igh
Cur
rent
35-4
4Te
rm. X
48/2
Low
Ref
./Fee
db. V
alue
35-4
5Te
rm. X
48/2
Hig
h R
ef./F
eedb
. Val
ue35
-46
Term
. X48
/2 F
ilter
Tim
e Co
nsta
nt35
-47
Term
. X48
/2 L
ive
Zero
43-*
*U
nit
Read
outs
43-0
*Co
mpo
nent
Sta
tus
43-0
0Co
mpo
nent
Tem
p.43
-01
Auxi
liary
Tem
p.43
-1*
Pow
er C
ard
Sta
tus
43-1
0H
S Te
mp.
ph.
U43
-11
HS
Tem
p. p
h.V
43-1
2H
S Te
mp.
ph.
W43
-13
PC F
an A
Spe
ed43
-14
PC F
an B
Spe
ed43
-15
PC F
an C
Spe
ed43
-2*
Fan
Pow
.Car
d S
tatu
s43
-20
FPC
Fan
A S
peed
43-2
1FP
C F
an B
Spe
ed43
-22
FPC
Fan
C S
peed
43-2
3FP
C F
an D
Spe
ed43
-24
FPC
Fan
E S
peed
43-2
5FP
C F
an F
Spe
ed
Appendix VLT® HVAC Drive FC 102
78 Danfoss A/S © 02/2017 All rights reserved. MG16D402
99
Index
AAbbreviation........................................................................................... 74
AC mains............................................................................................. 6, 32
AC waveform............................................................................................ 6
Additional resources.............................................................................. 3
AlarmsAlarm log............................................................................................. 39Alarms.................................................................................................. 52List of.................................................................................................... 53
AMAAMA...................................................................................................... 50with T27 connected........................................................................ 44without T27 connected................................................................. 44Automatic motor adaptation (AMA)......................................... 44
AMA........................................................................................................... 58see also Automatic motor adaptation
Ambient conditions............................................................................. 66
Analogspeed reference................................................................................ 44
Analog input.......................................................................................... 33
Analog output....................................................................................... 33
Approvals................................................................................................... 6
Auto on................................................................................ 40, 43, 50, 51
Automatic motor adaptationWarning............................................................................................... 58
Auto-reset................................................................................................ 38
Auxiliary equipment............................................................................ 37
BBlock diagram........................................................................................... 6
Brakeresistor................................................................................................. 53Terminal torque rating................................................................... 72
Brake resistorWarning............................................................................................... 56
Braking..................................................................................................... 50
Burst transient....................................................................................... 12
Bus termination switch....................................................................... 36
CCable routing......................................................................................... 37
CablesCable length and cross-section.................................................. 67Specifications.................................................................................... 67
Certifications............................................................................................. 6
Circuit breaker................................................................................ 37, 70
Clearance requirement......................................................................... 9
Closed loop............................................................................................. 35
Conduct................................................................................................... 37
Controlterminal............................................................................................... 52Signal.................................................................................................... 50Terminal................................................................................. 40, 42, 50Wiring.............................................................................. 12, 15, 35, 37
Control cardRS485.................................................................................................... 68Specifications.................................................................................... 70Warning............................................................................................... 58
Control input/outputSpecifications.................................................................................... 67
Control wiring........................................................................................ 15
Convention............................................................................................. 74
Cooling........................................................................................................ 9
Cooling clearance................................................................................. 37
CurrentDC............................................................................................................. 6Leakage............................................................................................... 12Limit...................................................................................................... 62Motor............................................................................................... 6, 39RMS.......................................................................................................... 6
DDC current.................................................................................... 6, 11, 50
Default setting....................................................................................... 40
Digital input..................................................................................... 35, 51
Dimensions shipping.......................................................................... 73
Discharge time......................................................................................... 7
Disconnect switch................................................................................ 38
Door/panel coverTorque rating..................................................................................... 72
EEMC............................................................................................................ 11
EMC interference.................................................................................. 15
Energy efficiency class........................................................................ 66
Extended options cabinet.................................................................... 5
External alarm reset............................................................................. 47
External command.......................................................................... 6, 52
External controller.................................................................................. 3
FFans
Warning............................................................................................... 60
Fault log................................................................................................... 39
Feedback.................................................................................... 35, 37, 50
Floating delta......................................................................................... 32
Fuse....................................................................................... 11, 37, 56, 70
Index Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 79
GGland plate
Torque rating..................................................................................... 72
Groundconnection......................................................................................... 37Grounding..................................................................... 15, 32, 37, 38Terminal torque rating................................................................... 72Warning............................................................................................... 57
Ground wire............................................................................................ 12
Grounded delta..................................................................................... 32
HHand on............................................................................................. 40, 50
Harmonics.................................................................................................. 6
Heat sinkAccess panel torque rating........................................................... 72Warning........................................................................................ 57, 59
High voltage...................................................................................... 7, 38
IInitialization............................................................................................ 41
InputAC...................................................................................................... 6, 32Analog.................................................................................................. 33Current................................................................................................. 32Digital................................................................................................... 35Disconnect.......................................................................................... 32Power............................................................ 6, 12, 15, 32, 37, 38, 52Power wiring...................................................................................... 37Signal.................................................................................................... 35Terminal................................................................................. 32, 35, 38Voltage................................................................................................. 38
Installation....................................................................................... 35, 37
Installation environment...................................................................... 9
Intended use............................................................................................. 3
Interference isolation.......................................................................... 37
Interior view.............................................................................................. 4
Isolated mains........................................................................................ 32
JJumper...................................................................................................... 35
LLeakage current................................................................................ 8, 12
Lifting........................................................................................................ 10
Load shareTerminal torque rating................................................................... 72
Load sharing...................................................................................... 7, 73
Local control............................................................................. 38, 40, 50
Local control panel (LCP)................................................................... 38
MMain menu.............................................................................................. 39
Mainssupply (L1, L2, L3)............................................................................. 66voltage.......................................................................................... 39, 50Terminal torque rating................................................................... 72
Maintenance.......................................................................................... 49
Manual initialization............................................................................ 41
MCT 10............................................................................................... 33, 38
Menu key................................................................................................. 39
Menu structure...................................................................................... 39
MotorCable..................................................................................................... 15Connection......................................................................................... 15current............................................................................................. 6, 39data....................................................................................................... 62Output (U, V, W)................................................................................ 66Overheating....................................................................................... 54Power............................................................................................. 12, 39Protection.............................................................................................. 3Rotation check.................................................................................. 42Speed.................................................................................................... 41Status...................................................................................................... 3Terminal torque rating................................................................... 72Thermal protection......................................................................... 48Thermistor.......................................................................................... 48Unintended motor rotation............................................................ 8Warning........................................................................................ 54, 56Wiring............................................................................................ 15, 37
Mounting.......................................................................................... 10, 37
NNameplate................................................................................................. 9
Navigation key......................................................................... 39, 41, 50
OOpen loop
Open loop........................................................................................... 35Speed accuracy................................................................................. 69
Operation key........................................................................................ 39
Optional equipment..................................................................... 35, 38
Outputcurrent.................................................................................................. 50power wiring...................................................................................... 37terminal............................................................................................... 38
Overcurrent protection...................................................................... 11
Overvoltage..................................................................................... 51, 62
PParameter menu structure................................................................ 75
PELV........................................................................................................... 48
Phase loss................................................................................................ 53
Index VLT® HVAC Drive FC 102
80 Danfoss A/S © 02/2017 All rights reserved. MG16D402
Potential equalization......................................................................... 12
Power cardWarning............................................................................................... 59
Power connection................................................................................ 11
Power factor....................................................................................... 6, 37
Programming.................................................................... 35, 38, 39, 40
Pulse start/stop..................................................................................... 46
QQualified personnel................................................................................ 7
Quick menu............................................................................................ 39
RRamp-down time.................................................................................. 62
Ramp-up time........................................................................................ 62
Reference............................................................................ 39, 44, 50, 51
RegenerationTerminal torque rating................................................................... 72
Regeneration.......................................................................................... 73
RelaysOutput specifications..................................................................... 69
Remote command.................................................................................. 3
Remote reference................................................................................. 51
Reset....................................................................... 38, 39, 40, 41, 52, 59
RFI filter.................................................................................................... 32
RMS current............................................................................................... 6
RS485................................................................................................. 36, 48
Run command....................................................................................... 43
Run permissive...................................................................................... 51
SSafe Torque Off
Safe Torque Off................................................................................. 36Warning............................................................................................... 59
Safety........................................................................................................... 8
Serial communication.................................................................. 33, 50
Serial communicationCover torque rating......................................................................... 72Serial communication...................................................... 40, 51, 52
Service...................................................................................................... 49
Setpoint.................................................................................................... 51
Set-up................................................................................................ 39, 43
Shielded cable................................................................................ 15, 37
Short circuit............................................................................................ 55
Short circuit current rating (SCCR)................................................. 71
Sleep mode............................................................................................. 51
SmartStart............................................................................................... 41
SpeedMotor.................................................................................................... 41reference........................................................................ 35, 43, 44, 50reference, analog............................................................................. 44
Start/stop command........................................................................... 46
Start-up.................................................................................................... 41
Status display......................................................................................... 50
Status mode........................................................................................... 50
STO............................................................................................................. 36
Storage........................................................................................................ 9
Supply voltage.................................................................. 33, 38, 56, 68
Switch....................................................................................................... 35
SwitchesBus termination................................................................................ 36
Switching frequency........................................................................... 51
Symbol...................................................................................................... 74
System feedback..................................................................................... 3
TTerminal
Control terminal............................................................................... 52Input..................................................................................................... 35Location, D1h.................................................................................... 17Location, D2h.................................................................................... 17Location, D3h.................................................................................... 18Location, D4h.................................................................................... 1953........................................................................................................... 3554........................................................................................................... 35
Thermal protectionMotor.................................................................................................... 48Thermal protection............................................................................ 6
ThermistorThermistor.......................................................................................... 33control wiring.................................................................................... 33Warning............................................................................................... 59
TorqueFastener rating.................................................................................. 72Limit...................................................................................................... 54characteristic..................................................................................... 66limit....................................................................................................... 62
Torque, terminals.................................................................................. 72
Transient protection............................................................................... 6
Trip............................................................................................................. 48
Trip lock.................................................................................................... 52
Trips........................................................................................................... 52
TroubleshootingTroubleshooting............................................................................... 62Warnings and alarms...................................................................... 53
UUnintended start.............................................................................. 7, 49
USBSpecifications.................................................................................... 70
Index Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 81
VVoltage imbalance............................................................................... 53
WWarnings
List of.................................................................................................... 53Warnings............................................................................................. 52
Weight...................................................................................................... 73
Windmilling............................................................................................... 8
Wire size............................................................................................ 11, 15
WiringControl................................................................................... 15, 35, 37Motor............................................................................................. 15, 37
Index VLT® HVAC Drive FC 102
82 Danfoss A/S © 02/2017 All rights reserved. MG16D402
Index Operating Guide
MG16D402 Danfoss A/S © 02/2017 All rights reserved. 83
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies toproducts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are propertyof the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/SUlsnaes 1DK-6300 Graastenvlt-drives.danfoss.com
*MG16D402*130R0290 MG16D402 02/2017