    ON Series User Instruction Manual

    ON Series User Instruction Manual

    ON Series

    User Instruction Manual

    IMPORTANT SAFETY INSTRUCTIONS

    SAVE THESE INSTRUCTIONS.

    Please read and save these instructions. This manual contains importantinstructions for the ON Series UPS family. Follow these instructions during theunpacking, installation and maintenance of the UPS and batteries. If you have aproblem with the UPS, please refer to this manual before calling the TechnicalSupport Department. The Troubleshooting section on page 61 addresses most

    UPS-related issues.

    Licenses and Trademarks

    ONEAC, ON Series, Virtual Kelvin Ground, Environmental Reference Groundand MopUPS are all registered trade marks and ChangeUPS, ONBoost, andONEP

    LUS

    , are trademarks of ONEAC Corporation. All other trademarks, productand corporate names are the property of their respective owners.

    Entire contents copyright 2000 ONEAC Corporation. All rights reserved. Reproduction in whole orin part without permission is prohibited. All information subject to change without notice.

    913-300-1 Rev. E 4/00

    ONEAC USA27944 North Bradley RoadLibertyville, IL 60048-9700USA

    ONEAC EUROPE18 & 20 Blacklands WayAbingdon Business ParkAbingdon, Oxfordshire OX14 1DY

    United KingdomTelephone: (847) 816-6000Toll Free: (800) 327-8801Facsimile: (847) 680-5124

    Telephone: +44 (0) 1235 534721Facsimile: +44 (0) 1235 534197

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    2/75

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    3/75

    Contents

    ii ON Series User Instruction Manual

    Runtime Estimates ......................................................................42Interface Specifications ...............................................................50

    Accessories .......................................................................................51UPS Monitoring Interfaces ..........................................................51UPS Monitoring Software ...........................................................51

    Installing and Removing Accessory Interface Cards .....................54Battery Considerations ......................................................................55

    Battery Maintenance ..................................................................55Ordering New Batteries ..............................................................55Battery Replacement ..................................................................56Installing Battery Pack in Standard, Rack Mount and Wall Mount

    Units .......................................................................................56Replacing External Battery Cabinets ............................................59Battery Disposal ..........................................................................60

    Troubleshooting ................................................................................61Checking the Size of the Load ....................................................61Technical Support .......................................................................62

    Warranty ..........................................................................................66

    Units ..........................................................................................66Batteries .....................................................................................66Limitations of Warranty ..............................................................66Exclusive Remedies .....................................................................66Return Procedure .......................................................................66

    Appendix A: Accessories Interface Capabilities ..................................67Appendix B: Operating in Power Environments Below 110V Nominal 68Appendix C: Accessing Remote Off ...................................................70

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    4/75

    Introduction

    ON Series User Instruction Manual 1

    Introduction

    Thank you for selecting this uninterruptible powersource (UPS). ONEACs ON Series offers the mostreliable protection from the harmful effects ofelectrical line disturbances for your computing andcommunications equipment.

    ONEACs ISO 9001 certification represents ourcommitment to building world-class products. Wetake pride in every unit that leaves our manufacturingfacility.

    RegisteringYour ONEACUPS

    To ensure that your ON Series model and serialnumber are registered, complete and mail theenclosed postage-paid warranty card.

    Technical

    Support

    ONEAC offers 24-hour technical support. ContactONEACs Technical Support Department:at (800) 327-8801 (extension 3),in Europe: +44 (0) 1235 534721.email: [email protected]

    NOTE:

    All calls received after 5:00 p.m. CST are

    forwarded to a beeper. An ONEAC Technical

    Support Representative will return your call within

    one half hour between 5:00 p.m. and 10:00 p.m.

    CST. Except for emergencies, calls received between

    10:00 p.m. and 7:00 a.m. will be returned during

    normal business hours.

    Please check with ONEACs Technical SupportDepartment before attempting to repair or return any

    ONEAC product. If an ONEAC UPS needs repair orreplacement, ONEACs Technical SupportDepartment issues a Return Material Authorization(RMA) number along with instructions on how toreturn the UPS.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    5/75

    FCC Compliance

    2 ON Series User Instruction Manual

    FCCCompliance

    ATTENTION:

    Changes or modifications to this unit

    not expressly approved by the party responsible or in

    FCC compliance could void the users authority to

    operate the equipment.

    This equipment was tested and complies with thelimits for a Class A digital device, pursuant to Part 15of FCC Rules. These limits are designed to providereasonable protection against harmful interferencewhen the UPS is operating in a commercialenvironment. The UPS generates, uses, and canradiate radio frequency energy. If installation and useis not in accordance with the instruction manual, itmay cause harmful interference to radiocommunications.

    ATTENTION:

    Operation of this equipment in a

    residential area may cause harmful radio

    communications interference. The user is

    responsible for correcting the interference.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    6/75

    Safety

    ON Series User Instruction Manual 3

    Safety

    (English)

    WARNING:

    This equipment services power from

    more than one source. The output receptacles may

    have voltage even when the unit is unplugged.

    UPSs present a different safety issue than mostelectrical equipment because unplugging the UPSputs it into backup mode. Unplugging the UPS doesnot remove the electrical charge. To ensure that theUPS is off, turn the power switch OFF beforeunplugging the UPS from the wall outlet.

    CAUTION:

    Operating this equipment without

    proper grounding may present a risk of electrical

    shock.

    Do not use AC adaptors with only two conductors toconnect the input line cord to the wall socket as thiswill not connect the earth ground to the equipment.

    WARNING:

    Dangerous voltages are present within

    this unit! There are no user-serviceable parts inside.

    Any repairs or modifications by the user may result

    in out-of-warranty repair charges, unsafe electrical

    conditions, or violation of electrical code.

    Do not remove the cover. All repairs should be doneby qualified service personnel. Voltages inside theUPS may be lethal. Internal components arepowered even when the power switch is in the OFFposition. Even with the battery disconnected and theunit unplugged, energy is stored in high voltagecapacitors and represents a severe shock hazard.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    7/75

    Sicherheitshinweise

    4 ON Series User Instruction Manual

    Sicherheitshinweise

    (Deutsch)

    ACHTUNG:

    Dieses Gert erhlt seinen Strom von

    mehr als einer Quelle. Die Ausgangssteckdosen

    fhren unter Umstnden Spannung, selbst wenn der

    Stecker des Gertes ausgesteckt wurde.

    Fr USVs mssen andere Sicherheitsmanahmen alsfr die meisten Elektrogerte ergriffen werden, dadie USV durch Ausstecken in den Reservebetriebgebracht wird. Wenn der Stecker der USVabgezogen wird, wird die elektrische Ladunghierdurch nicht entfernt. Um sicherzustellen, da dieUSV ausgeschaltet ist, mu der Netzschalter aufAUS (OFF) gestellt werden, bevor der Stecker derUSV aus der Wandsteckdose gezogen wird.

    VORSICHT:

    Durch Betreiben dieses Gertes ohne

    ordnungsgeme Erdung knnen Elektroschocks

    riskiert werden.

    Keine Wechselstromadapter mit nur zweiStromleitern verwenden, um das Netzkabel an dieWandsteckdose anzuschlieen, weil das Gerthierdurch nicht an die Erde angeschlossen wird.

    ACHTUNG:

    In diesem Gert sind gefhrliche

    Spannungen vorhanden! Im Inneren dieses Gertes

    befinden sich keine vom Benutzer zu wartenden Teile.

    Durch etwaige Reparaturen oder Modifikationen durch

    den Benutzer knnen nicht von der Garantie gedeckte

    Reparaturkosten, gefhrliche elektrische Zustnde oder

    Verste gegen Stromvorschriften entstehen.

    Abdeckung nicht entfernen. Alle Reparaturen solltenvon qualifizierten Wartungstechnikern durchgefhrtwerden. Die Spannungen im Inneren der USVknnen tdliche Verletzungen zur Folge haben. Dieinternen Komponenten fhren Strom, selbst wennder Stromschalter auf AUS (OFF) steht. Auch wenndie Batterie nicht angeschlossen und der Stecker desGertes ausgesteckt ist, wird Energie inHochspannungskondensatoren gespeichert, und diesbedeutet eine ernsthafte Elektroschockgefahr.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    8/75

    Mesures de scurit

    ON Series User Instruction Manual 5

    Mesures descurit

    (Franais)

    AVERTISSEMENT :

    Cet quipement est aliment

    par plus d'une source. Des tensions peuvent treprsentes aux prises de sortie, mme lorsque l'unit

    est dbranche.

    Le problme de scurit sur l'UPS diffre de celui dela plupart des quipements lectriques, car lorsqu'ilest dbranch, il se met en mode de rserve. Sondbranchement n'limine pas la charge lectrique.Pour s'assurer que l'UPS est hors tension, mettrel'interrupteur d'alimentation sur ARRT (OFF) avantde dbrancher l'UPS de la prise murale.

    ATTENTION :

    Si cet quipement fonctionne sans

    tre correctement mis la terre, un risque de choc

    lectrique peut en rsulter.

    Ne pas utiliser d'adaptateurs CA n'ayant que deuxconducteurs pour brancher le cordon d'alimentationdans la prise murale, car l'quipement ne serait pasmis la terre.

    AVERTISSEMENT :

    Cet quipement renferme des

    tensions dangereuses! Il ne contient aucune pice

    rparable par l'usager. Toutes rparations ou

    modifications effectues par l'usager peuvent

    entraner des frais de rparation non couverts par la

    garantie, un danger lectrique ou l'infraction un

    code lectrique.

    Ne pas enlever le couvercle. Confier toutes lesrparations un personnel d'entretien qualifi. Lestensions prsentes dans l'UPS peuvent tremortelles. Les composants internes de l'unit sontsous tension, mme lorsque l'interrupteurd'alimentation est sur ARRT (OFF). Mme lorsquela batterie est dconnecte et l'unit dbranche, del'nergie est stocke dans des condensateurs hautetension et reprsente un grave risque d'lectrocution.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    9/75

    Seguridad

    6 ON Series User Instruction Manual

    Seguridad

    (Espaol)

    ADVERTENCIA:

    Este equipo suministra

    alimentacin desde ms de una fuente. Los

    tomacorrientes de salida pueden tener voltaje aun

    cuando la unidad est desenchufada.

    Las UPS (fuentes de alimentacin ininterrumpibles)cuentan con una caracterstica de seguridad diferentea la mayora de los equipos elctricos, ya que aldesenchufarse, quedan en el modo de reserva. Aldesenchufar una UPS no se elimina la cargaelctrica. Para cerciorarse de que una UPS estapagada, gire el interruptor de alimentacin a laposicin APAGADO (OFF) antes de desenchufar elUPS del tomacorriente mural.

    PRECAUCION:

    El hacer funcionar este equipo sin

    la conexin a tierra adecuada representa un riesgo

    de descargas elctricas.

    No utilice adaptadores de CA con slo dosconductores para conectar el cable de la lnea deentrada al enchufe mural debido a que ste noconectar el equipo a tierra.

    ADVERTENCIA:

    Esta unidad tiene voltajes

    peligrosos!. En su interior no hay piezas que pueda

    reparar el usuario. Las reparaciones o

    modificaciones hechas por el usuario pueden dar

    como resultado cargos de reparacin no cubiertos

    por la garanta, y producir situaciones de riesgo

    elctrico o violacin de los cdigos elctricos.

    No retire la cubierta. Todas las reparaciones debenser realizadas por personal de servicio calificado.Los voltajes del interior de las UPS pueden sermortales. Los componentes internos tienenelectricidad aun cuando el interruptor est en laposicin APAGADO (OFF). Incluso si la batera estdesconectada y la unidad desenchufada, se almacenaenerga en capacitores de alto voltaje, lo cualrepresenta un peligro grave de descarga.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    10/75

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    11/75

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    12/75

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    13/75

    Theory of Operation

    10 ON Series User Instruction Manual

    Input Protector

    A grossly overloaded UPS trips the rear panel circuitbreaker. The front panel display reads c1. To resetthe circuit breaker, push the button in.

    If the circuit breaker trips repeatedly followingreset, unplug the equipment from the UPS outputreceptacles and reset the circuit breaker onceagain.

    If operation appears to be normal, check the totalequipment load. Add your equipment to theoutput one device at a time. Check the frontpanel display after each device is powered ON.

    If the circuit breaker trips with nothing pluggedinto the output receptacles, there may be aninternal problem with the UPS. Call ONEACTechnical Support for assistance (refer topage 1).

    AuxiliaryInterface

    Port

    IEC InputConnector

    Interface Connector DIP Switches

    OutputReceptacles

    EnvironmentalReference

    Ground

    CircuitBreaker

    Model Shown: ON900A-SN

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    14/75

    Setup and Installation

    ON Series User Instruction Manual 11

    Setup andInstallation

    Inspection andUnpacking

    Previous experience with UPS operation is notrequired prior to operating ON Series units.

    Before shipment, this product was tested, inspected,and found to be free of mechanical and electricaldefects. Upon receipt of your UPS, carefullyexamine the packing containers for any sign ofphysical damage. Notify the carrier immediately ifdamage is present.

    Carefully unpack the UPS. Retain the packagingmaterials for reuse (refer to page 66, ReturnProcedure) or dispose of the materials properly.

    Once unpacked, inspect and test the unit for anyhidden damage that may have occurred in transit. Ifany damage is evident, contact ONEACs Technical

    Support Department immediately (refer to page 1) tocorrect the problem.

    CAUTION:

    Do not attach laser printers to the UPS.

    A laser printer periodically draws significantly more

    power during use and may overload the UPS.

    Testing

    Before connecting the UPS to other equipment, plugthe UPS into an AC-powered wall outlet and turn theUPS ON. When selecting a location for your UPS, be

    sure that the unit is near the wall outlet and is easilyaccessible. After the self-tests are completed, thedigital display on the front should read 00 and the% LOAD light should be on. If the digital displayreads differently, refer to System Status Codesbeginning on page 63. When the digital display reads00, the UPS is ready for use.

    NOTE:

    If the battery is not fully charged, the digital

    display may read c4. This condition may exist for

    4 12 hours if a unit has been stored.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    15/75

    Setup and Installation

    12 ON Series User Instruction Manual

    EnvironmentalReferenceGround

    The UPS provides a common ground point forsystem components and static protection devices;network cable segments that require shieldgrounding; static control devices such as floor mats,table mats, static-free work benches; or any other

    device that requires a reference ground connection.For use, remove the green screw on the back panel,attach a ground cord connector, and reinstall thescrew.

    AuxiliaryInterface

    Port

    IEC InputConnector

    Interface Connector DIP Switches

    OutputReceptacles

    EnvironmentalReference

    Ground

    CircuitBreaker

    Model Shown: ON900A-SN

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    16/75

    Setup and Installation

    ON Series User Instruction Manual 13

    Setup Precaution

    The percent of UPS capacity in use is displayed onthe front panel of the UPS. As long as the displayreads 99 or less when the AC line is present andyour equipment is running, the UPS is notoverloaded. If the front panel displays c8 or c9,

    the unit is overloaded. Remove some of the load untilthe front panel displays 99 or less.

    Long TermStorage

    Improper long-term UPS storage may damage theUPS battery and invalidate the battery warranty.Unplugging a UPS from its AC utility power sourcefor an extended period of time results in lost batterycharge. Restoration of charge to maximum capacityrequires 24 48 hours. For standard models, theSystem code may show a c4 for 2 4 hours afterutility power is restored. For extended runtimemodels, the system code c4 may show for 2 4hours per battery cabinet.

    To keep the battery enclosure fully charged and tomaximize the life of the battery, plug the UPS into anoutlet while it is in storage. If the UPS is storedwithout power access, plug it into a power source for24 hours at least once every 4 6 months.

    ATTENTION:

    If the storage temperature is greater

    than 30

    C (86

    F) plug the UPS into a power source

    for 24 hours every 2 to 3 months.

    ATTENTION:

    The UPS should not be stored at

    temperatures below -15

    C (+5

    F).

    Ventilation

    The ventilation requirement for standard ON Series

    UPSs is 2 in. (50 mm) minimum clearance on allsides. Rackmount units are vented at the front andback. Side clearance is not required.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    17/75

    Setup and Installation

    14 ON Series User Instruction Manual

    Grounding theUnit

    To eliminate shock hazard, connect the unit to aproperly grounded AC receptacle.

    Before applying power, verify that the product ratingmatches the available line voltage listed on therear-panel label.

    For CE compliance, add wire between chassis(earth) of power unit and chassis (earth) of batterycabinet(s).

    CAUTION:

    Interruption of the protective grounding

    conductor or disconnection of the protective earth

    terminal presents a potential shock hazard that could

    result in personal injury and damage to the

    equipment.

    NOTE:

    The ON2000A requires a 20 Amp circuit and

    receptacle for power.

    NOTE:

    When connecting the UPS, make sure that

    the receptacle has power available and is not

    controlled by a wall switch.

    15 A 20 A

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    18/75

    Setup and Installation

    ON Series User Instruction Manual 15

    InstallingStandardON2000 Units

    Place the power unit next to, or on top of, the batterymodule. For CE compliance, add wire betweenchassis (earth) of power unit and chassis (earth) ofbattery cabinet(s). Attach the AC line cord to thereceptacle on the back panel 24

    of the UPS, and then to a properly grounded ACwall receptacle. Connect the battery power cable asshown below. Secure the cable with screws(supplied) at each side flange.

    AuxiliaryInterface

    Port

    AC Line CordReceptacle

    Battery PowerCable

    InterfaceConnector DIP Switches

    OutputReceptacles

    Ground

    CircuitBreaker

    ON2000 (Standard Model)

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    19/75

    Setup and Installation

    16 ON Series User Instruction Manual

    InstallingON2200XAExtendedRuntime Units

    NOTE:

    The ON2200XA requires a 60 Hz, AC circuit

    providing either 208, or 220 240 Vac.

    Before plugging your ON2200XA into the AC inputcircuit, you should test the line voltage of the circuitto determine whether the feed is delivering 208 or220 240 volts rms.

    Remove the front cover of the power unit and set theinput voltage toggle switch to the position thatmatches the feed voltage. Replace the cover.

    Battery PowerCable

    Main

    BatteryUnit

    RJ Cable Ground

    Terminator

    Input VoltageSelection

    Switch

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    20/75

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    21/75

    Setup and Installation

    18 ON Series User Instruction Manual

    Connecting One Battery Enclosure

    Standard and Rack-Mount Systems

    1. Connect an RJ data cable (supplied with eachbattery unit) from the battery units eight-pin RJ

    connector (marked IN) to the six-pin RJconnector on the main unit.

    A terminating plug (with wire loop) is suppliedin each battery units six-pin RJ connector(marked OUT). Leave it in place.

    The UPSwill not operate properly with the plug removed.

    2. For CE compliance, add a ground wire betweenchassis of power unit and chassis (earth) ofbattery cabinet(s) as shown in the above diagram.

    3. Attach the AC line cord to the receptacle on theback panel of the UPS and then to a properlygrounded AC wall receptacle.

    4. Connect the battery units power cable to themain unit. Secure the cable with screws(supplied) at each side flange. The battery unitspower input is not used.

    Battery PowerCable

    Main

    Battery

    Unit

    RJ Cable Ground Wire

    Terminator

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    22/75

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    23/75

    Setup and Installation

    20 ON Series User Instruction Manual

    Model Shown: ON2000XA-SN

    Battery PowerCable

    Main

    BatteryUnits

    RJ CableGround Wire

    Terminator

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    24/75

    Setup and Installation

    ON Series User Instruction Manual 21

    MountingWallmountExtendedRuntime Unitsand BatteryEnclosures

    Mount the power unit and battery enclosure(s) to a3/4-in. plywood (minimum) backboard. Use theenclosed four 1/4-in. x 1-in. slotted-hex,washer-head wood screws.

    1. Draw a straight, level, horizontal 8-in. line on thebackboard.

    2. Mark two screw locations, on the line, 7-3/8 in.apart.

    3. Drill a 3/16-in. diameter hole at each screwlocation.

    4. Drive the screws into the backboard at the screwlocations. Allow a 1/8-in. gap.

    5. Slide the keyhole slots, located on the back of theunit, over the screws.

    6. Check to ensure that the unit is level.

    7. When the unit is level, drive the remaining two

    screws through the holes in the mounting tabs atthe bottom of the unit.

    NOTE:

    When mounting the power unit and battery

    enclosure, make sure that cables can reach the

    connection points without twisting, pinching, or

    stressing the cables or connectors.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    25/75

    Setup and Installation

    22 ON Series User Instruction Manual

    InstallingWallmountExtendedRuntime Units

    To install an extended runtime unit there are two orthree connections that need to be made: the batterypower cable, the RJ cable, and the ground wire.

    The six-pin RJ cable allows the power unit to countthe number of battery enclosures connected. If theconnection is incorrect or incomplete, runtimereporting and assessment of the batteries will beinaccurate.

    For CE compliance, add a ground wire betweenchassis of power unit and chassis (earth) of batterycabinet(s).

    Connecting One Battery Enclosure

    Wall-Mount Systems

    1. Connect an RJ data cable (supplied with eachbattery unit) from the battery units eight-pin RJ

    connector (marked IN) to the six-pin RJconnector on the main unit.

    A terminating plug (with wire loop) is supplied ineach battery units six-pin RJ connector (markedOUT). Leave it in place. The UPS will not operateproperly with the plug removed.

    2. Attach the AC line cord to the receptacle on theback panel of the UPS and then to a properlygrounded AC wall receptacle.

    3. Connect a power cable (supplied with eachbattery unit) from either of the battery unitspower connectors to the main unit. Theremaining battery unit power connector is notused.

    NOTE:On the wall mounted units, the back panel is

    the bottom panel.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    26/75

    Setup and Installation

    ON Series User Instruction Manual 23

    Wallmount Extended Runtime Power Unit

    Wallmount Extended Runtime Battery Enclosure

    OutputReceptacles

    DIP SwitchesInterface

    Connector

    RJ Connector

    AuxiliaryInterface

    PortEnvironmental

    Reference

    Mate-n-Lock

    Connector

    IECInput

    Connector

    CircuitBreaker

    Ground

    RJ

    OutIn

    Mate-n-LockConnectors

    Connectors

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    27/75

    Setup and Installation

    24 ON Series User Instruction Manual

    Connecting Multiple BatteryEnclosures

    1. Remove the terminating plug (with wire loop)from the six-pin RJ connector on all but the last

    battery unit. Set these aside. Only oneterminating plug is required for the system.

    2. Connect an RJ data cable (supplied with eachbattery unit) from the closest battery unitseight-pin RJ connector (marked IN) to thesix-pin RJ connector on the main unit.

    3. Connect another RJ data cable from the nextbattery units eight-pin RJ connector (markedIN) to the closest battery units six-pin RJconnector (marked OUT). Continue thisprocess until RJ cables connect all battery unitsin a chain.

    NOTE:Leave the terminating plug installedin the

    last battery units six-pin RJ connector (marked

    OUT). The UPS will not operate properly with the

    plug removed.

    4. For CE compliance, add a ground wire betweenchassis of power unit and chassis (earth) ofbattery cabinet(s) as shown in the followingdiagram.

    5. Attach the AC line cord to the receptacle on theback panel of the UPS and then to a properlygrounded AC wall receptacle.

    6. Connect a power cable (supplied with eachbattery unit) from either of the closest battery

    units power connectors to the main unit.7. Connect a power cable from the closest battery

    units other power connector to either of the nextclosest battery units power connectors. Continuethis process until power cables connect ALLbattery units in a chain. The last battery unitsextra connector is not used.

    NOTE:On the wall mounted units, the back panel is

    the bottom panel.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    28/75

    Setup and Installation

    ON Series User Instruction Manual 25

    RJCable

    BatteryPower CableAC Line CordReceptacle

    Terminator

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    29/75

    Setup and Installation

    26 ON Series User Instruction Manual

    InstallingRackmount Units

    Install Rackmount UPSs as low as possible in therack. Do not install the UPS near heat sources.

    The Rackmount UPS draws cooling air from back tofront. If the rack has a door on the front, make sure

    that there is some clearance between the vents andthe rack door.

    Model Shown: ON600-RM-SN

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    30/75

    Setup and Installation

    ON Series User Instruction Manual 27

    Front PanelFeatures andControls

    Once the UPS is correctly installed, the front paneldisplay provides all necessary operatinginformation. To operate an ON Series UPS:

    1. Plug the unit into an AC power source.

    2. Plug the load equipment into the UPS.3. Turn the front-panel switch ON.

    Power ON/OFF Switch

    With the UPS plugged in, operate the ON ( | ) switchup to supply power to the loads. The loads areimmediately powered.

    To turn OFF the UPSs output power, press the OFF( O ) power switch down. The UPS ON/OFF switchcan be used as a master ON/OFF switch for theprotected equipment.

    NOTE:This switch controls output power only. The

    unit will continue to operate the battery charger and

    control circuits even when front panel switch is in

    OFF position.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    31/75

    Setup and Installation

    28 ON Series User Instruction Manual

    Front Panel Display

    Three display lights operate in conjunction with adigital display on the front panel to show systemstatus:

    NOTE:Place the enclosed peel-n-stick label

    (located on the warranty registration card on the last

    page of this manual) on or near the UPS for futurereference. This label provides a quick reference for

    interpretation of the system status codes.

    1 % LOAD

    When the % LOAD light is on, the digital display shows the

    percentage of capacity in use, in one percent increments,

    with full load displayed as 99.

    2 % BATTERY

    When the % BATTERY light is on, the digital display

    indicates the relative amount of battery runtime available, in

    five percent increments, during an AC line power failure.

    3 SYS. CODE

    When the SYS. CODE light is on, an unusual condition

    exists. Refer to pages 63 and 64 for the System Status Code

    labels included in the rear of this manual to interpret the

    reading.

    % BATTERY

    % LOAD

    SYS. CODE

    1

    2

    3

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    32/75

    Setup and Installation

    ON Series User Instruction Manual 29

    Back Panel DIPSwitch Settings

    DIP Switch Settings

    DIP switches are located on the rear panel of theUPS.

    The following table describes the switch settings andtheir corresponding configurations.

    Table 1. DIP Switches

    Switches 1 and 2: Units are shipped with theinterface preset to Advanced and 9600 to

    support ONEACs most popular UPS monitoringsoftware accessory kits. Follow the specialinstructions in the accessory kit, or refer toAppendix A for information on supporting thirdparty interface software.

    *Switch 3: This switch is only applicable to the50/60Hz switchable models. Its setting has no affecton the 120V, 60Hz A models.

    1 2

    3 4

    ON

    OFF

    Switch Description Down (Off) Up (On)

    1 Interface port configuration ADVANCED BASIC

    2 Interface port baud rate 1200 9600

    3* UPS frequency 50 Hz 60 Hz

    4 Reserved

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    33/75

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    34/75

    Features

    ON Series User Instruction Manual 31

    The ON Series product family was designed forvarious power environments. Each part numberincludes a letter. This letter identifies the powerenvironment. Please specify the part number andletter when ordering

    120 or 208/240V, 60Hz applications=A.Example: ON400A-SN.

    230V, 50/60Hz applications=I.Example: ON400I-SN.

    120V, 50/60Hz applications (which are110 120V nominal)=J.Example: ON400J-SN.

    NOTE:Two models, the ON400 and ON900, are

    offered for the 120V, 50/60Hz power environment.

    For information on models operating in power

    environments below 110V, refer toAppendix B:

    Operating in Power Environments Below 110V

    Nominal on page 68.

    Features Full output isolation and powerconditioningwith Virtual KelvinGroundoutput filtering

    Five-year warranty on power andcontrol systems

    Two-year warranty on battery enclosure

    Sinusoidal inverter wave form, loadregulated

    Intelligent battery management system:

    Battery condition monitoring and status alerts Low battery indication

    ONBoost, low line voltage compensationwithout battery depletion

    Inverter shutdown control

    Hot Swap, user replaceable battery enclosure

    Battery charge indicator

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    35/75

    Features

    32 ON Series User Instruction Manual

    Agency approvals: UL, cUL, FCC, GS,CE Approved

    System intelligence andcommunications:

    Basic Interface supports Novell, BANYAN, LanServer, and Windows NT

    Advanced RS-232 UPS control language supportinformation required for IETF UPS MIBconformance

    Auxiliary interface expansion port

    Programmable switchover thresholds

    Intelligent runtime estimates

    Unit identification stored in memory for remoteasset management

    Digital load meter with output overloadprotection and recovery indication

    Options The ON Series units can be customized to suit yourparticular computing environment. Special types ofreceptacles, such as hospital grade and countryspecific, are available.

    Auxiliary Interface Port

    The auxiliary interface port is located on the backpanel of the UPS. ONEAC offers optional interfaceswhich may be plugged into this port to connect it toa computer system or network. Refer to page 54 forspecial notes on installing interface cards. Seepage 51 for available accessories.

    Ethernet SNMP Interface Card

    An SNMP interface card is available for individualswho need direct access and control of every criticaldevice on the network through a commonSNMP-based management console. A user canreceive notifications of conditions that require/meritattention. ONEACs SNMP solution also enablesremote control, remote testing, and informationretrieval on networked ON Series UPSs.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    36/75

    Features

    ON Series User Instruction Manual 33

    Physical andElectricalSpecifications

    Performance Characteristics For AllModels (Tables 2 5)

    Surge voltage withstand capability: ANSI/IEEEC62.41 Category A&B, 6kV/200 & 500 Amp, 100kHz Ringwave

    Surge voltage let-through (max): less than 10VNormal mode (L-N), less than 0.5 V Common mode(N-G) when subjected to 6kV ANSI/IEEE C62.41Cat. A

    Normal & common mode clamping response

    time: instantaneous

    Transfer time (typical/max): < 3.0 / 3.5milliseconds

    ONBoost: boosts output voltage 11% above inputvoltage if between -21% & -15% of nominal

    Load power factor range (crest factor): UPS .65 to1.0 (3) will support loads rated 0.5 to 1.0 (

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    37/75

    Features

    34 ON Series User Instruction Manual

    Table 2A. Standard A Unit Specifications

    ON400 ON600 ON900 ON1300 ON2000

    Input connector IEC 320 IEC 320/C20

    Output sockets: NEMA 5-15R

    for 120V4 4 6 8 8

    120V units include 6-foot detachable input cord with a 5-15P plug, except for the

    ON2000 which has a 5-20P plug. Other plugs and sockets are available on request.

    Power Battery

    Maximum Dimensions-inches

    (cm): (H)

    (W)

    (D)

    Net weight-lbs. (kg.)

    Shipping weight-lbs. (kg.)

    7.5

    (19.1)

    8.5

    (21.6)

    15.5

    (39.4)

    30 (14)

    35 (16)

    7.5

    (19.1)

    8.5

    (21.6)

    18.5

    (47.0)

    41 (18)

    46 (21)

    12

    (30.5)

    8.5

    (21.6)

    18.5

    (47.0)

    59 (26)

    64 (29)

    12

    (30.5)

    8.5

    (21.6)

    21

    (53.3)

    78 (35)

    83 (37)

    12

    (30.5)

    8.5

    (21.6)

    18.5

    (47.0)

    58 (26)

    63 (28)

    7.5

    (19.1)

    8.5

    (21.6)

    18.5

    (47.0)

    70 (32)

    75 (34)

    Nominal input voltage: 120Vac 60Hz

    On battery output voltage: Sinewave 120Vac

    Maximum capacity (volt-amps)

    (watts)

    400

    280

    600

    400

    900

    600

    1300

    900

    1850

    1300

    Batteries: Sealed,

    maintenance-free lead acid,

    36 yr. typical life

    Two,

    12V,

    4AH

    Two,

    12V,

    7AH

    Four,

    6V,

    10AH

    Two,

    12V,

    17AH

    Four, 12V,

    17AH

    Efficiency (%) on utility, 100%

    load90% 83% 83% 87% 83%

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    38/75

    Features

    ON Series User Instruction Manual 35

    Table 2I. Standard I and J Unit Specifications

    ON400 ON600 ON900 ON1300 ON2000

    Input connector IEC 320

    Output sockets: IEC 320

    female for 230V 4 4 4 8 8

    230V units include IEC320 M/F detachable output cord(s). Other plugs and sockets

    are available on request.

    Power Battery

    Maximum Dimensions-inches

    (cm):

    (H)

    (W)

    (D)

    Net weight-lbs. (kg.)

    Shipping weight-lbs. (kg.)

    7.5

    (19.1)

    8.5

    (21.6)

    15.5

    (39.4)

    33 (15)

    38 (17)

    7.5

    (19.1)

    8.5

    (21.6)

    18.5

    (47.0)

    44 (20)

    50 (23)

    12

    (30.5)

    8.5

    (21.6)

    18.5

    (47.0)

    64 (29)

    69 (31)

    12

    (30.5)

    8.5

    (21.6)

    21

    (53.3)

    88 (40)

    92 (41)

    12

    (30.5)

    8.5

    (21.6)

    18.5*

    (47.0)

    60 (27)

    66 (31)

    7.5

    (19.1)

    8.5

    (21.6)

    18.5*

    (47.0)

    70 (32)

    75 (34)

    Nominal input voltage: I models: 230Vac 50/60Hz J models:120Vac 50/60Hz

    On battery output voltage: "I" models: 230Vac "J" models: 120Vac

    Maximum capacity (volt-amps)

    (watts)

    400

    280

    600

    400

    900

    600

    1300

    900

    2000

    1400

    Batteries: Sealed,

    maintenance-free lead acid,

    36 yr. typical life

    Two,

    12V,

    4AH

    Two,

    12V,

    7AH

    Four,

    6V,

    10AH

    Two,

    12V,

    17AH

    Four, 12V,

    17AH

    Efficiency (%) on utility, 100%

    load90% 83% 83% 87% 83%

    * Length of chassis, allow an additional 10 in. (25.40 cm.) at rear of unit to

    accommodate external battery cable connection.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    39/75

    Features

    36 ON Series User Instruction Manual

    Table 3A. Rackmount "A" Unit Specifications

    ON600 ON900 ON1300 ON2000

    Input connector IEC 320/C20 IEC 320/C20

    Output sockets: NEMA 5-15R for 120V 6 6 8 8

    120V units include 6-foot detachable input cord with a 5-15P plug, except for the

    ON2000 which has a 5-20P plug. Other plugs and sockets are available on request.

    Power Battery

    Maximum Dimensions-inches (cm): (H)

    (W)

    (D)

    Net weight-lbs. (kg.)

    Shipping weight-lbs. (kg.)

    6.9

    (17.5)

    19

    (48.3)

    15

    (38.1)

    46 (21)

    50 (23)

    6.9

    (17.5)

    19

    (48.3)

    15

    (38.1)

    65 (30)

    69 (31)

    10.5

    (26.7)

    19

    (48.3)

    15

    (38.1)

    92 (41)

    101 (46)

    10.5

    (26.7)

    19

    (48.3)

    15*

    (38.1)

    66 (30)

    72 (33)

    10.5

    (26.7)

    19

    (48.3)

    9*

    (22.9)

    76 (35)

    82 (37)

    Height 4U 4U 6U 6U 6U

    Nominal input voltage: 120Vac 60Hz

    On battery output voltage: Sinewave 120Vac Maximum capacity (volts-amps)

    (watts)

    600

    400

    900

    600

    1300

    900

    1850

    1300

    Batteries: Sealed, maintenance-free

    lead acid, 36 yr. typical life

    Two,

    12V,

    7AH

    Four, 6V,

    10AH

    Two,

    12V,

    17AH

    Four, 12V,

    17AH

    Efficiency (%) on utility, 100% load 83% 83% 87% 83%

    * Length of chassis, allow an additional 10 in. (25.40 cm.) at rear of unit to

    accommodate external battery cable connection.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    40/75

    Features

    ON Series User Instruction Manual 37

    Table 3I. Rackmount "I" Unit Specifications

    ON600 ON900 ON1300 ON2000

    Input connector IEC320

    Output sockets: IEC 320 female for

    230V 4 4 8 8

    230V units include IEC320 M/F detachable output cord(s). Other plugs and sockets

    are available on request.

    Power Battery

    Maximum Dimensions-inches (cm): (H)

    (W)

    (D)

    Net weight-lbs. (kg.)

    Shipping weight-lbs. (kg.)

    6.9

    (17.5)

    19

    (48.3)

    15

    (38.1)

    48 (22)

    52 (24)

    6.9

    (17.5)

    19

    (48.3)

    15

    (38.1)

    68 (31)

    73 (33)

    10.5

    (26.7)

    19

    (48.3)

    15

    (38.1)

    101 (45)

    108 (49)

    10.5

    (26.7)

    19

    (48.3)

    15*

    (38.1)

    66 (30)

    72 (33)

    10.5

    (26.7)

    19

    (48.3)

    9*

    (22.9)

    76 (35)

    82 (37)

    Height 4U 4U 6U 6U 6U

    Nominal input voltage: 230Vac 50/60Hz

    On battery output voltage: Sinewave 230Vac

    Maximum capacity (volts-amps)

    (watts)

    600

    400

    900

    600

    1300

    900

    2000

    1400

    Batteries: Sealed, maintenance-free

    lead acid, 36 yr. typical life

    Two,

    12V,

    7AH

    Four, 6V,

    10AH

    Two,

    12V,

    17AH

    Four, 12V,

    17AH

    Efficiency (%) on utility, 100% load 83% 83% 87% 83%

    * Length of chassis, allow an additional 10 in. (25.40 cm.) at rear of unit to

    accommodate external battery cable connection.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    41/75

    Features

    38 ON Series User Instruction Manual

    Table 4A. Standard "A" Unit Extended Runtime Specifications

    ON600 ON900 ON2000 ON2200

    External

    Battery

    Cabinet

    for AllUnits

    Input connector IEC 320 IEC 320/C20

    Output sockets: NEMA 5-15R for

    120V:

    NEMA 5-20R for 115V:

    NEMA L6-30R for 230V:

    4

    -

    -

    6

    -

    -

    8

    -

    -

    -

    4

    2

    120V units include 6-foot

    detachable input cord with:5-15P Plug

    5-20P

    Plug

    L6-30P

    Plug

    Maximum Dimensions-inches (cm):

    (H)

    (W)

    (D)

    Net weight-lbs. (kg.)

    Shipping weight-lbs. (kg.)

    7.5

    (19.1)

    8.5

    (21.6)

    18.5*

    (47.0)30 (14)

    35 (16)

    12

    (30.5)

    8.5

    (21.6)

    18.5*

    (47.0)45 (20)

    50 (23)

    12

    (30.5)

    8.5

    (21.6)

    18.5*

    (47.0)58 (26)

    63 (28)

    12

    (30.5)

    8.5

    (21.6)

    21.5*

    (54.6)77 (35)

    82 (37)

    7.5

    (19.1)

    8.5

    (21.6)

    18.5*

    (47.0)70 (32)

    75 (34)

    Nominal input voltage 120Vac 60Hz

    208Vac or

    220x

    240Vac

    On battery output voltage Sinewave 120Vac

    Sinewave:

    230/

    115Vacx

    Maximum capacity (volt-amps)

    (watts)600

    400

    900

    600

    1850

    1300

    2200

    1500

    Batteries: Sealed, maintenance-free lead acid, 36 yr. typical life

    Four,

    12V,17AH

    Efficiency (%) on utility, 100% load 83% 83% 83% 88%

    * Length of chassis, allow an additional 10 in. (25.40 cm.) at rear of unit to

    accommodate external battery cable connection.x See page 17 for details on input and output voltages under various conditions.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    42/75

    Features

    ON Series User Instruction Manual 39

    Table 4I. Standard "I" Unit Extended Runtime Specifications

    ON600 ON900 ON2000

    ExternalBatteryCabinetfor All

    Units

    Input connector IEC 320

    Output sockets: IEC 320 female for 230V 4 8 8

    230V units include IEC320 M/F detachable output cord(s). Other plugs and

    sockets are available on request.

    Maximum Dimensions-inches (cm)): (H)

    (W)

    (D)

    Net weight-lbs. (kg.)

    Shipping weight-lbs. (kg.)

    7.5

    (19.1)

    8.5

    (21.6)

    18.5*

    (47.0)

    34 (16)

    39 (17)

    12

    (30.5)

    8.5

    (21.6)

    18.5*

    (47.0)

    50 (23)

    55 (26)

    12

    (30.5)

    8.5

    (21.6)

    18.5*

    (47.0)

    61 (27)

    66 (29)

    7.5

    (19.1)

    8.5

    (21.6)

    18.5*

    (47.0)

    70 (32)

    75 (34)

    Nominal input voltage: 230Vac 50/60Hz

    On battery output voltage: Sinewave 120VAC/230VacMaximum capacity for 230V

    (volt-amps, watts)

    600

    400

    900

    600

    2000

    1400

    Batteries:

    Sealed, maintenance-free

    lead acid, 36 yr. typical

    life

    Four,

    12V,

    17AH

    Efficiency (%) on utility, 100% load 83% 83% 83%

    * Length of chassis, allow an additional 10 in. (25.40 cm.) at rear of unit to

    accommodate external battery cable connection.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    43/75

    Features

    40 ON Series User Instruction Manual

    Table 5A. Wall Mount "A" Unit Extended Runtime Specifications

    ON400 ON600

    ExternalBatteryCabinetfor All

    UnitsInput connector IEC320

    Output sockets: NEMA 5-15R for 120V 4 4

    120V units include 6-foot detachable input cord with a 5-15P plug.

    Maximum Dimensions-inches (cm): (H)

    (W)

    (D)

    Net weight-lbs. (kg.)

    Shipping weight-lbs. (kg.)

    15

    (38.1)

    8.5

    (21.6)

    9

    (22.9)

    25 (11)

    30 (14)

    15

    (38.1)

    8.5

    (21.6)

    9

    (22.9)

    29 (13)

    34 (15)

    7.5

    (19.1)

    8.5

    (21.6)

    9

    (22.9)

    35 (16)

    40 (18)

    Nominal input voltage 120Vac 60Hz

    On battery output voltage Sinewave 120Vac

    Maximum capacity (volt-amps):(watts):

    400280

    600400

    Batteries: Sealed, maintenance-free lead acid, 36 yr. typical life

    Two,

    12V,

    17AH

    Efficiency (%) on uti li ty, 100% load 90% 83%

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    44/75

    Features

    ON Series User Instruction Manual 41

    Table 5I. Wall Mount "I" Unit Extended Runtime Specifications

    ON400 ON600

    ExternalBatteryCabinetfor All

    UnitsInput connector IEC 320 female

    Output sockets: IEC 320 female 4 4

    230V units include IEC 320 M/F detachable output cord(s). Other plugs and sockets

    are available on request.

    Maximum Dimensions-inches (cm): (H)

    (W)

    (D)

    Net weight-lbs. (kg.)

    Shipping weight-lbs. (kg.)

    15

    (38.1)

    8.5

    (21.6)

    9

    (22.9)

    28 (13)

    33 (15)

    15

    (38.1)

    8.5

    (21.6)

    9

    (22.9)

    33 (15)

    38 (17)

    7.5

    (19.1)

    8.5

    (21.6)

    9

    (22.9)

    35 (16)

    40 (18)

    Nominal input voltage 230Vac 50/60Hz

    On battery output voltage Sinewave 230VacMaximum capacity (volt-amps):

    (watts):

    400

    280

    600

    400

    Batteries: Sealed, maintenance-free lead acid, 36 yr. typical life

    Two,

    12V,

    17AH

    Efficiency (%) on uti li ty, 100% load 90% 83%

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    45/75

    Features

    42 ON Series User Instruction Manual

    RuntimeEstimates

    Table 6. Standard and Rackmount Unit Runtimes

    NOTE:Runtimes in the above chart are based on

    tests using 0.65 PF switched mode power supply.

    Percent of Capacity ON400 ON600 ON900 ON1300ON2000

    (A)

    ON2000

    (I)

    Runtimes are expressed in hours:minutes.Typical runtimes based on fully charged, new batteries operating under typical load conditions.Runtimes are affected by battery age, ambient temperature, site specific UPS usage patterns andload characteristics.Your actual runtime may be different.

    10 1:33 1:45 1:59 2:32 3:00 2:48

    20 0:43 0:52 0:58 1:11 1:36 1:29

    30 0:27 0:34 0:37 0:45 1:05 1:00

    40 0:19 0:25 0:27 0:33 0:49 0:45

    50 0:15 0:20 0:21 0:25 0:39 0:36

    60 0:12 0:17 0:17 0:20 0:32 0:29

    70 0:10 0:14 0:14 0:17 0:27 0:24

    80 0:09 0:13 0:12 0:14 0:23 0:21

    90 0:08 0:11 0:10 0:12 0:20 0:18

    100 0:07 0:10 0:09 0:11 0:17 0:15

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    46/75

    Features

    ON Series User Instruction Manual 43

    Table 7. ON600 Extended Runtime Unit Runtimes

    NOTE:Runtimes shown are based on calculated

    values.

    Percent of CapacityNumber of Battery Enclosures

    1 2 3 4 5 6 7 8

    Runtimes are expressed in hours:minutes.Typical runtimes based on fully charged, new batteries operating under typical load conditions.Times estimated assuming a switch mode power supply with a power factor of 0.65.Runtimes are affected by battery age, ambient temperature, site specific UPS usage patterns andload characteristics.

    15 6:16 11:48

    20 5:15 10:06 - - - - - -

    30 3:50 7:39 11:54

    40 2:55 6:01 9:24 - - - - -

    50 2:18 4:54 7:40 10:52

    60 1:52 4:07 6:27 9:07 - - - -

    70 1:34 3:33 5:33 7:51 9:53 -

    80 1:21 3:08 4:54 6:53 8:39 - - -

    90 1:11 2:48 4:23 6:10 7:43 9:24 -

    100 1:04 2:34 3:60 5:36 6:58 8:28 - -

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    47/75

    Features

    44 ON Series User Instruction Manual

    Table 8. ON900 Extended Runtime Unit Runtimes

    NOTE:Runtimes shown are based on calculated

    values.

    Percent of CapacityNumber of Battery Enclosures

    1 2 3 4 5 6 7 8

    Runtimes are expressed in hours:minutes.Typical runtimes based on fully charged, new batteries operating under typical load conditions.Times estimated assuming a switch mode power supply with a power factor of 0.65.Runtimes are affected by battery age, ambient temperature, site specific UPS usage patterns andload characteristics.

    10 6:16 11:48

    20 3:50 7:39 11:54 - - - - -

    30 2:34 5:24 8:27

    40 1:52 4:07 6:27 9:07 - - - -

    50 1:27 3:19 5:12 7:20 9:14

    60 1:11 2:48 4:23 6:10 7:43 9:24 - -

    70 1:01 2:27 3:50 5:21 6:39 8:05 -

    80 0:53 2:12 3:25 4:47 5:53 7:06 8:32 -

    90 0:47 2:01 3:07 4:20 5:17 6:20 7:39 9:07

    100 0:42 1:51 2:51 3:59 4:47 5:43 6:55 8:16

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    48/75

    Features

    ON Series User Instruction Manual 45

    Table 9A. ON2000 A Extended Runtime Unit Runtimes

    NOTE:Runtimes shown are based on calculated

    values.

    Percent of CapacityNumber of Battery Enclosures

    1 2 3 4 5 6 7 8

    Runtimes are expressed in hours:minutes.Typical runtimes based on fully charged, new batteries operating under typical load conditions.Times estimated assuming a switch mode power supply with a power factor of 0.65.Runtimes are affected by battery age, ambient temperature, site specific UPS usage patterns andload characteristics.

    10 3:44 7:29 11:39 16:30

    20 1:49 4:00 6:17 8:53 - - - -

    30 1:09 2:44 4:17 6:00 7:31 9:09 -

    40 0:51 2:10 3:21 4:40 5:44 6:55 8:19 -

    50 0:41 1:49 2:47 3:53 4:40 5:34 6:44 8:04

    60 0:34 1:32 2:21 3:18 3:52 4:33 5:32 6:42

    70 0:27 1:16 1:56 2:47 3:12 3:42 4:32 5:33

    80 0:22 1:02 1:34 2:19 2:37 2:66 3:40 4:34

    90 0:18 0:49 1:16 1:56 2:09 2:28 3:02 3:48

    100 0:16 0:41 1:03 1:39 1:52 2:09 2:39 3:20

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    49/75

    Features

    46 ON Series User Instruction Manual

    Table 9I. ON2000 I Extended Runtime Unit Runtimes

    NOTE:Runtimes shown are based on calculated

    values.

    Percent of CapacityNumber of Battery Enclosures

    1 2 3 4 5 6 7 8

    Runtimes are expressed in hours:minutes.Typical runtimes based on fully charged, new batteries operating under typical load conditions.Times estimated assuming a switch mode power supply with a power factor of 0.65.Runtimes are affected by battery age, ambient temperature, site specific UPS usage patterns andload characteristics.

    10 3:29 7:02 10:57 -

    20 1:40 3:43 5:49 8:14 - - - -

    30 1:00 1:54 3:60 5:36 6:58 8:28 -

    40 0:48 2:02 3:09 4:23 5:21 6:25 7:44 9:13

    50 0:38 1:42 2:36 3:38 4:20 5:07 6:13 7:28

    60 0:30 1:24 2:08 3:03 3:32 4:07 5:02 6:07

    70 0:24 1:08 1:43 2:31 2:51 3:17 4:01 4:58

    80 0:19 0:53 1:21 2:03 2:18 2:38 3:14 4:02

    90 0:17 0:43 1:06 1:43 1:55 2:13 2:44 3:26

    100 0:17 0:37 0:59 1:34 1:47 2:06 2:37 3:15

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    50/75

    Features

    ON Series User Instruction Manual 47

    Table 9. ON2200 Extended Runtime Unit Runtimes

    NOTE:Runtimes shown are based on calculated

    values.

    Percent of CapacityNumber of Battery Enclosures

    1 2 3 4 5 6 7 8

    Runtimes are expressed in hours:minutes.Typical runtimes based on fully charged, new batteries operating under typical load conditions.Times estimated assuming a switch mode supply with a power factor of 0.65.Runtimes are affected by battery age, ambient temperature, site specific UPS usage patterns andload characteristics.

    10 3:10 6:29 10:08 -

    20 1:30 3:23 5:19 7:30 9:26 - - -

    30 0:58 2:22 3:41 5:09 6:22 7:43 9:15

    40 0:43 1:53 2:54 4:03 4:54 5:51 7:04 -

    50 0:34 1:33 2:22 3:20 3:55 4:36 5:36 6:46

    60 0:27 1:14 1:53 2:43 3:07 3:36 4:24 5:24

    70 0:21 0:57 1:27 2:11 2:27 2:48 3:26 4:17

    80 0:17 0:44 1:08 1:46 1:59 2:17 2:48 3:31

    90 0:17 0:38 1:00 1:34 1:47 2:06 2:36 3:15

    100 0:13 0:28 0:45 1:16 1:26 1:41 2:00 2:40

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    51/75

    Features

    48 ON Series User Instruction Manual

    Table 10. ON400 Wall Mount Extended Runtime Unit Runtimes

    NOTE:Runtimes shown are based on calculated

    values.

    Percent of CapacityNumber of Battery Enclosures

    1 2 3 4 5 6 7 8

    Runtimes are expressed in hours:minutes.Typical runtimes based on fully charged, new batteries operating under typical load conditions.Times estimated assuming a switch mode supply with a power factor of 0.65.Runtimes are affected by battery age, ambient temperature, site specific UPS usage patterns andload characteristics.

    10 5:58 12:33 - - - - - -

    20 3:48 7:54 11:42

    30 2:51 5:53 8:52 - - - - -

    40 2:16 4:43 7:11 10:02 - - - -

    50 1:53 3:56 6:03 8:25 10:24

    60 1:36 3:21 5:13 7:14 8:55 - - -

    70 1:22 2:54 4:34 6:20 7:47 9:30

    80 1:12 2:33 4:03 5:36 6:52 8:20 - -

    90 1:03 2:15 3:38 5:00 6:01 7:22 8:52

    100 0:55 2:00 3:16 4:29 5:29 6:33 7:54 9:05

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    52/75

    Features

    ON Series User Instruction Manual 49

    Table 11. ON600 Wall Mount Extended Runtime Unit Runtimes

    NOTE:Runtimes shown are based on calculated

    values.

    Percent of CapacityNumber of Battery Enclosures

    1 2 3 4 5 6 7 8

    Runtimes are expressed in hours:minutes.Typical runtimes based on fully charged, new batteries operating under typical load conditions.Times estimated assuming a switch mode supply with a power factor of 0.65.Runtimes are affected by battery age, ambient temperature, site specific UPS usage patterns andload characteristics.

    15 3:30 7:16 10:49

    20 2:51 5:53 8:52 12:25 15:24 19:25 23:29 27:06

    30 2:04 4:17 6:34 9:09 11:19

    40 1:36 3:21 5:13 7:14 8:55 10:59 13:12 15:08

    50 1:17 2:43 4:18 5:57 7:18 8:53 10:41

    60 1:03 2:15 3:38 5:00 6:07 7:22 8:52 10:10

    70 0:52 1:54 3:06 4:16 5:12 6:11 7:28 8:36

    80 0:43 1:37 2:41 3:41 4:28 5:15 6:22 7:20

    90 0:36 1:23 2:21 3:12 3:52 4:29 5:27 6:19

    100 0:29 1:11 2:03 2:47 3:22 3:50 4:42 5:28

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    53/75

    Features

    50 ON Series User Instruction Manual

    InterfaceSpecifications

    For the RS-232 advanced interface port, pins 2 and 3are receive and transmit, respectively, and pin 7 is thesignal ground.

    Pins 5 and 8 are RS-232 static levels (typically+/-12V DC) indicate a not true condition (e.g., linefail = -12 indicates that the line has not failed). +12VDC indicates a true condition (e.g., line fail = +12indicates that the line has failed).

    Pins 1, 10, 18, and 25 (simulated relay closures) areopen collector transistor outputs which must bepulled up to a common reference supply no greaterthan +40V DC (See Accessories on page 53 forIsolated Contacts Interface Card). The transistors areNPN type 2N2222A capable of a maximumnoninductive load of 25mA DC. Pin 11 is thecommon for all of the relay closure pins and isconnected to the UPS chassis ground.

    Pin 20 is used to shut down the UPS when it isoperating on battery. A positive signal (3 to 24V DC)with respect to pin 7 shuts down the UPS. A signal ator below ground allows the UPS to keep running.

    The shell of the interface connector is connected tothe UPS chassis ground.

    Pin # Signal

    1 Low battery normally open

    2 Rx

    3 Tx5 Line fail RS-232 static levels

    7 Signal ground

    8 Low battery RS-232 static levels

    10 Line fail normally open

    11 Common for simulated relay closures

    18 Line fail normally closed

    20 Shutdown (to UPS)

    25 Low Battery normally closed

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    54/75

    Accessories

    ON Series User Instruction Manual 51

    Accessories

    UPS MonitoringInterfaces

    ONEAC UPS monitoring interfaces are powerfulnetwork management tools. They enhance systemsfault tolerance by providing automatic shutdown andrestart, and allow network managers to access vitalpower and UPS status information. Basic interfacingprovides signals to shutdown Lan Manager, LanServer, and Windows NT environments.

    UPS MonitoringSoftware

    MopUPSfor Netware

    MopUPS provides unattended system shutdowncapability for NetWare and operating environments.It offers remote pager capability, a GUI-basedmonitoring utility, and can broadcast alert conditionsthat are logged into the System Error Log file.

    MopUPS/RM advanced software provides all

    features of MopUPS plus the ability to reviewsystem error messages. MopUPS/RM also providesmultiple server support to execute unattendedshutdown of two servers sharing a single UPS andlocal access to remote servers or workstationsrunning MopUPS/RM.

    MopUPS for Windows NT

    MopUPS installs as a Service under Windows NT. Itconstantly monitors your UPS and gracefully shutsdown the NT operating system in the event of aprolonged power outage. An intuitive GUI interfacesteps you through configuration of various automaticevent responses such as network, e-mail and pageralerts, event logging and command file execution. Anintegrated utility lets you view UPS front panelinformation and configure UPS operatingparameters from anywhere on your network.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    55/75

    Accessories

    52 ON Series User Instruction Manual

    MopUPS for UNIX

    MopUPS for UNIX provides automatic systemshutdown and status code messaging capability inUNIX environments, including SCO, UnixWare,Sun Solaris, IBM-AIX, HP-UX, NCR, SGI, DigitalUNIX, and Motorola System V/88.

    ChangeUPS (Windows NT, 95 and3.11)

    ChangeUPS is an intuitive, user friendly utility thatenables you to view real time changes in your powerenvironments and change how your ON UPSresponds to changes in the environment (includescomplete online documentation).

    The Main screen provides easy viewing andinterpretation of all front panel displays, productidentifiers, and line voltage statistics.

    A Configuration Wizard walks through theconfigurable options with ample context-sensitivehelp also allows one button reset to factorydefaults.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    56/75

    Accessories

    ON Series User Instruction Manual 53

    ONEPLUS Multi-Server Y CableAccessory

    ONEPlus Y cable accessory kit allows the sharingof communications from a single ON UPS, to initiateunattended system shutdown sequences on two ormore servers when AC power fails and the serversare operating from UPS battery power.

    Isolated Contacts Interface Card

    This optional interface card provides an isolated,Form C contact closure signal mechanism, forsystems not compatible with the simulated contactclosures described on page 50. Unit must be set toBasic communications mode to operate the IsolatedContacts Interface card. See page 29.

    SNMP Network Interface Card

    For integrated, in-band manageability of dedicatedcommunications switching systems, the SNMPinterface card with SNMP-based networkmanagement utilities supports in-band monitoring ofremote UPSs over wide-area TCP/IP networks.

    SNMP interface cards house the UPS agent ethernetcontroller. Both network and RS-232 ports are activeconcurrently allowing in-band SNMP-basedmonitoring, and local monitoring/auto shutdown ofCPUs running MopUPS or MopUPS for UNIX.When attached to a modem, the interface portenables remote monitoring and Agent configuration.

    An embedded SNMP Agent (MIB II compliant)supports Subset, Basic, and Advanced compliancegroups defined in the May 1994 Internet ProposedStandard UPS MIB.

    The ethernet card has an RJ-45 connector for10BaseT ethernet networks.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    57/75

    Accessories

    54 ON Series User Instruction Manual

    Installing andRemovingAccessoryInterface Cards

    To install an optional interface card in an ON SeriesUPS:

    1. Shut down all UPS-powered systems. Turn theUPS OFF and unplug it.

    2. Identify the interface port on the back panel of

    the UPS. Remove the plate if the UPS does nothave an interface card. Set the two screws aside.The plate will not be used.

    NOTE:This port may already have an interface card

    in it. If so, carefully remove it to make room for the

    new interface card.

    3. Carefully slide the interface card into the UPSguide rails. Reinstall the plate screws.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    58/75

    Battery Considerations

    ON Series User Instruction Manual 55

    4. Refer to specific instructions provided in theAccessory Kit.

    5. Plug the UPS in and turn it ON.

    NOTE:All ONEAC interfaces are designed to

    connect to signaling systems which comply withNational Electrical Code Class 2 limits.

    BatteryConsiderations

    The UPS must be adequately cooled to preventsystem overheating and enhance battery life. The ONSeries UPSs must be installed with a minimum 2 in.(50 mm) clearance on all sides. Do not place otherequipment or supplies on top of the UPS.

    To preserve the performance and warranty of yourON Series UPS, use only original equipmentreplacement batteries.

    ATTENTION:The batteries in this UPS are

    recyclable. Dispose of the batteries properly.

    BatteryMaintenance

    Customer maintenance of the ON Series UPS islimited to battery enclosure replacement. ContactONEACs Technical Support Department (refer topage 1, Technical Support) with any other servicingneeds.

    The UPS uses sealed, leak-proof, lead-acid batteriesthat do not emit corrosive gasses.

    Ordering NewBatteries

    To ensure optimal performance and battery life,ONEAC selects premium quality batteries and tunesthe UPS battery charger and test circuits to thecharacteristics of these batteries. With safety inmind, ONEAC uses patented, insulated batteryenclosure assemblies to ensure safe handling andinstallation.

    Original equipment replacement batteries may beordered directly from ONEAC at (800) 327-8801(extension 3), email: [email protected], in Europe, at+44 (0) 1235 534721, or from your local authorizedrepresentative or reseller.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    59/75

    Battery Considerations

    56 ON Series User Instruction Manual

    BatteryReplacement

    Battery replacement is a safe procedure that isisolated from electrical hazards. You can leave theUPS and attached loads powered on during theprocedure.

    If the unit is on, it will beep when the battery isdisconnected and the front panel will display c2.Remove the old battery pack by pulling it away fromthe UPS.

    Installing BatteryPack inStandard, RackMount and WallMount Units

    Standard Units: ON400, ON600,ON900, ON1300

    To replace a battery pack in a Standard UPS, removethe front cover of the unit by pushing down on the

    front panel approximately 1/8 in. (3 mm) and tiltingthe top away from the unit. Squeeze and unlatch thewire retainer from the upper casing. Squeeze bothsides of the plug to unplug the battery enclosure(s).

    Insert the new battery pack into the UPS with themolded cover facing into the unit. Rest the wiresover the top of the battery with the plug kept towardthe front. Once the battery pack is in place, insert theplug and attach the wire retainer and front cover.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    60/75

    Battery Considerations

    ON Series User Instruction Manual 57

    Rackmount Units

    To replace the battery pack in a Rackmount Unit,remove the battery cover by pushing down on theindented latch approximately 1/8 in. (3 mm). Tilt thecover away from the front panel.

    Squeeze and unlatch the wire retainer from thecasing. Squeeze both sides of the plug to unplug thebattery pack(s).

    Insert the new battery pack into the UPS with themolded cover toward the front. Once the battery packis in place, insert the plug and attach the wire retainerand front cover.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    61/75

    Battery Considerations

    58 ON Series User Instruction Manual

    Wall Mount Units

    To replace the battery pack in the Wall Mount batteryenclosure, remove the front cover of the unit bypushing down on the front panel approximately1/8 in. (3 mm) and tilting the top away from the unit.Remove the screw from the inside cover and remove

    the inside cover by lifting it away from the UPS.Squeeze both sides of the plug to unplug the batterypack.

    Insert the new battery pack into the UPS with themolded cover at the top. Rest the wires at the frontand to the left of the battery. Once the battery pack isin place, insert the plug and refit the inside coverwith the screw. Attach the front cover.

    Battery Pack

    CoverInside Cover

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    62/75

    Battery Considerations

    ON Series User Instruction Manual 59

    ReplacingExternal BatteryCabinets

    ON2000 and Extended Runtime versions of theON600, ON900, ON2000, and ON2200 use batterieshoused in a separate enclosure. The UPS powermodule and battery module(s) are shippedseparately.

    The batteries inside the Extended Runtimeenclosures are not user-replaceable. The entirebattery enclosure must be replaced or the enclosuremay be returned to ONEAC for battery replacement.For details, refer to Connecting Multiple BatteryEnclosures on page 19.

    ATTENTION:Place the Main Power Unit on the top

    or to the side of the stackable configuration.

    Battery PowerCable

    Main

    BatteryUnits

    RJ CableGround

    Terminator

    Extended Runtime Unit

    Model Shown:

    ON900XA-SN

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    63/75

    Battery Considerations

    60 ON Series User Instruction Manual

    Battery Disposal UPS batteries contain toxic and acidic materials.Disposal method must adhere to local/nationalrecycling laws. Dispose of the battery in one of threeways:

    1. Return batteries prepaid to ONEAC for properrecycling. Contact ONEAC Technical SupportDepartment (847) 816-6000, (call toll free,(800) 327-8801), for a Return MaterialAuthorization (RMA) number. In Europe,contact ONEAC Technical Support at +44 (0)1235 534721. Mark the RMA number on thepacking slip and shipping carton.

    2. Phone ONEAC Corporation for the number of alocal battery collection site (US only).

    3. Make arrangements with a local auto shop thatcollects automotive batteries for reprocessing.

    CAUTION:DO NOT dispose of batteries in a fire.

    The battery may explode. Do not open or mutilate thebattery or battery enclosure. Released electrolyte is

    harmful to the skin and eyes and is toxic.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    64/75

    Troubleshooting

    ON Series User Instruction Manual 61

    Troubleshooting Three display lights aid in digital displayinterpretation. % LOAD (top) indicates the UPSload. % BATTERY (middle) indicates thepercentage of battery charge available while in thebattery backup mode. SYS. CODE (bottom) is a

    message to the user.

    Checking theSize of the Load

    When all equipment is connected and the UPS is on,the digital display should read 99 or less. If itdisplays c8 the UPS is overloaded. Remove someof the equipment or purchase a higher capacity UPS.If there is no display, ensure that the circuit breakerlocated on the rear panel is pushed in. Refer topage 10, Input Protector, for more information onresetting and troubleshooting the circuit breaker.

    % BATTERY

    % LOAD

    SYS. CODE

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    65/75

    Troubleshooting

    62 ON Series User Instruction Manual

    TechnicalSupport

    ONEAC offers 24-hour technical support. If youhave questions or problems regarding your ONSeries UPS:

    1. Refer to the troubleshooting table onpage 63 andpage 65 for corrective or recommended action.

    2. If you are unable to troubleshoot the problem,contact ONEACs Technical SupportDepartment. Refer to page 1, Technical Support,for the correct telephone number in your area.Our Technical Support Department will ask youto describe the problem. We will help solve theproblem over the telephone or issue a ReturnMaterial Authorization (RMA) number alongwith instructions on how to return the UPS.

    NOTE:You will need to supply the service

    representative with the UPS part number and serial

    number. You can access these numbers in two places

    on your UPS: On the back panel of the unit on a labellocated near the receptacles, and behind the front

    battery cover.

    Always check with our Technical SupportDepartment before attempting to repair or return anyONEAC product.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    66/75

    Troubleshooting

    ON Series User Instruction Manual 63

    Table 12. System Status Codes

    System status codes are displayed for two seconds,alternating with normal % LOAD or% BATTERY displays. If multiple alarmconditions exist, the system status code display

    cycles through all active alarm condition codesbefore returning to % LOAD or % BATTERY

    When your UPS is on inverter it sounds a toneevery 60 seconds. When your UPS reaches lowbattery, a continuous tone is sounded.

    System

    Status

    Codes

    Description Corrective Action

    c0 Battery test in progress. (no sound) None required.

    c1

    Rear panel input circuit breaker

    open. (tone sounds every 60seconds)

    Reset breaker on back panel.

    c2

    Battery disconnected. Or battery

    fuse blown. (tone sounds every 60

    seconds)

    Check battery is plugged in, if still c2

    call the ONEAC Technical Support

    Department.

    c3Over temperature, unit is too hot.

    (continuous tone)Provide adequate ventilation.

    c4AC line returned, battery charging.

    (no sound)

    Normal, allow battery to charge

    (4 12 hours).

    c5Backup time is significantly

    degraded.(tone sounds hourly)

    Contact ONEACs Technical Support

    Department to order a replacement

    battery.

    c6

    Battery failure detected. Replace

    battery! (tone sounds every 60

    seconds)

    Contact ONEACs Technical Support

    Department to order a replacement

    battery.

    c7

    On inverter due to sustained

    overvoltage.(tone sounds every 60

    seconds)

    Contact your building facilities

    manager.

    c8

    Output overload Inverter

    disabled. (tone sounds every 60

    seconds)

    Unplug devices until unit is loaded to

    99 percent or less.

    c9

    Output will shut down due to severe

    overload. (continuous tone until

    output off)

    Reduce load, turn the unit OFF, then

    ON to reset.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    67/75

    Troubleshooting

    64 ON Series User Instruction Manual

    NOTE:The tone can be controlled through the Serial

    Port. Select On, Off, or Mute.

    Table 12. System Status Codes, continued

    NOTE:The tone can be controlled through the Serial

    Port. Select On, Off, or Mute.

    SystemStatus

    Codes

    Description Corrective Action

    u0Manual restart as requested by

    the user (no sound).

    Turn front panel switch OFF then ON, or

    issue proper reset command to interface

    port.

    u1

    Internal charger fuse blown

    (tone sounds every 60

    seconds).

    Call ONEACs Technical Support

    Department.

    u2System restart is pending

    (no sound).

    Wait for user configured delay to expire

    or turn the front panel switch OFF then

    ON to reset.

    u3System is counting a WAKEUP

    delay (no sound).

    Wait for delay to expire or turn the front

    panel switch OFF then ON to reset.

    u4System is counting a

    SHUTDOWN delay. (no sound).

    Normal but may be stopped using

    control language or turn the front panel

    power switch OFF then ON to reset.

    u5Back feed relay failure detected

    (no sound).

    Possible system fault. Contact ONEACs

    Technical Support Department.

    [ ] No output (no sound).Plug in terminator or check RJ cables on

    the battery cabinet(s). (See page 18.)

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    68/75

    Troubleshooting

    ON Series User Instruction Manual 65

    Table 13. Troubleshooting Guide

    Problem Recommended Action

    The UPS will not do anything.

    The wall outlet may not have power

    available. The UPS will not start unless it

    is plugged into a working electrical outlet.

    Make sure the outlet has power and the

    terminator is in place on extended

    battery cabinet.

    The UPS front panel is active, but there

    is no output.

    Check the System Status Code on the

    digital display. Refer to the chart on

    page 63.

    The UPS works, but an alarm sounds.

    May be a normal indication of AC line

    failure if front panel display indicates

    normal. Check the System Status Code

    on the digital display. Refer to the chart

    on page 63.

    The UPS works, but the shutdown/

    monitoring software is not working.

    Check the DIP switch settings on the rear

    panel of the UPS. Make sure they match

    the software requirements.

    None of the above, but things are still not

    right.

    Contact ONEACs Technical Support

    Department.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    69/75

    Warranty

    66 ON Series User Instruction Manual

    Warranty

    Units ONEAC products are warranted free from defects inmaterials and workmanship for five years. Thiswarranty is limited to repairing or replacing, at

    ONEACs option, any defective component, circuitboard, or module contained within the product onlywhen it is returned with an ONEAC Return MaterialAuthorization (RMA) number to ONEAC or to anONEAC-designated repair facility. In all cases, thecustomer is responsible for shipping charges to andfrom ONEAC or the ONEAC-designated repairfacility.

    Batteries Certain modules or peripherals included with theproduct but not manufactured by ONEAC, includingbut not limited to batteries or battery enclosures, arewarranted for two years or the extent of themanufacturers warranty, whichever is longer.

    Limitations ofWarranty

    This limited warranty does not cover any losses ordamage resulting from shipment to or from thecustomer, or from improper installation,inappropriate environment, abuse, modifications,adjustments, or unauthorized repair.

    For full details of the warranty, see ONEACWarranty, Policy and Procedures (part number955-053).

    ExclusiveRemedies

    Except as set forth herein and except as to title, thereare no warranties, express or implied, or anyaffirmations of fact or promises by ONEAC for theproducts, their merchantability, or fitness for anyparticular purpose. In no event shall ONEAC beliable for lost profits, goodwill, or any other specialor consequential damages.

    ReturnProcedure

    To return an uninterruptible power supply (UPS),contact ONEAC for a Return Material Authorization(RMA) number. This number must be marked on theshipping carton and packing slip of the unit returned.The customer is responsible for repair charges fordamages incurred in shipment that result frominadequate or improper packing of the product.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    70/75

    Appendix A: Accessories Interface Capabilities

    ON Series User Instruction Manual 67

    Appendix A:AccessoriesInterfaceCapabilities

    BASIC Communications Capability

    BASIC interface capability allows for automaticsystem shutdown in the event of a power failure.Rear panel DIP switches enable the BASIC interface

    capability (refer to Back Panel DIP Switch Settingson page 29). Two output signals, power failure,and low battery, and one input signal, UPSshutdown, are active in the BASIC interface mode.

    Signals are provided both as simulated Form C(see Accessories on page 53 for Isolated ContactsInterface Card) relay contacts and RS-232 voltagelevels on RS-232 handshake pins. These simplesignals support automatic system shutdown for UPSmonitoring modules provided in NetWare,BANYAN, Lan Manager, Lan Server, andWindows NT environments.

    Interface kits for each operating environment include

    appropriate cable and documentation.

    ADVANCED CommunicationsCapability

    ADVANCED interface capability allows access tovital power and UPS status information and enablesunattended system shutdown. Advanced featuresinclude AC line voltage reporting, UPS statuscondition alerting, and capacity and runtimeestimates.

    Installing ONEAC Software

    Use rear panel DIP switches to select the desiredinterface capability. ONEAC UPS control protocol(ASCII characters) communicates with ONEACUPS monitoring software that you install on yoursystem. Refer to Back Panel DIP Switch Settings onpage 29.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    71/75

    Appendix B: Operating in Power Environments Below

    68 ON Series User Instruction Manual

    Appendix B:Operating inPowerEnvironments

    Below 110VNominal

    Minimum and maximum allowedoutput voltages

    The J models are set at the factory to anticipate anominal input line voltage of 110 120V rms. The

    default setting for Minimum output volts allowed(Min-Allow) is 95V rms. The default setting formaximum output volts allowed (Max-Allow) is138V rms. If necessary, these settings can bechanged in the field through the UPS serialcommunications port. The Min-Allow can be set to aminimum value of 90V rms. The Max-Allow can beset to a minimum value 20 volts higher than theMin-Allow settings.

    Operation of low voltage boost and ACinverter systems

    The output voltage boost circuit raises output voltage

    by 11% without depleting battery charge. Thiscircuit is engaged whenever the incoming linevoltage reaches the value set for Min-Allow. At thefactory default setting, the boost circuit is engaged at95V and remains engaged until the line drops to 86Vrms or rises to 102V rms. At 102V the boost circuitis disengaged and output volts will match input volts.At 86V rms, the battery and inverter system isengaged and supports the load as if a line failure hasoccurred. The battery and inverter system is alsoengaged whenever the incoming line voltageexceeds the Max-Allow setting (138V rms default),protecting the load from unusually high line

    conditions by running the load from the battery andinverter system. The inverter is disengaged when theinput AC line drops 7 volts below the Max-Allowsetting (default at 131V rms).

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    72/75

    Appendix B: Operating in Power Environments Below

    ON Series User Instruction Manual 69

    Changing the min-allow andmax-allow settings

    To change the min/max output voltage settings youwill need to connect an ASCII terminal to the UPSserial communications port on the back of the unit.The communications setting should be (9600,N,8,1)9600 baud, No Parity, 8 Data Bits, 1 Stop Bit.

    If you need to change the UPS min/max settings, usethe change UPS utility pictured below. Refer topage 52 for further information on ChangeUPS.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    73/75

    Appendix C: Accessing Remote Off

    70 ON Series User Instruction Manual

    Appendix C:AccessingRemote Off

    Accessing Remote Off Functions for ShuntTrip EMO

    These reference instructions offer a suggestedmethod for integration into a shunt trip EMO

    scheme. A more complete discussion of EMO issueswhen a UPS power source is involved is offered inONEAC Tech Tips document Emergency MainsOff Circuitry - July 1999.

    Control of the UPS inverter is available through thestandard UPS communications port (see pagepage 50). Setting the inverter OFF effectivelyallows UPS AC output to be controlled remotelythrough interconnection with a work-cell or facilityEMO scheme. When Inverter Off is assertedremotely via the EMO mechanism, the normalbattery backup operation of the UPS is disabled inthe event of an EMO-activated AC input failure.

    Inverter Off To Set

    Dip switch #1 (left most when you look at the backpanel) must be set in the UP or BASIC position.(The default is down, ADVANCED.) (See pagepage 29.)

    A positive DC voltage of at least 3 volts but not morethan 24 volts must be applied to pin 20 with respectto pin 7 on the 25-pin communications port. Thevoltage needs to be present for 20 milliseconds inorder to prevent the inverter from starting.

    The inverter will remain off and the logic will stay

    that way until one of two events occur: AC returns -This restarts the UPS logic and the

    UPS will now control the inverter as undernormal operations.

    A person holds the cold start button in with thepoint of a pen or paperclip and toggles the frontpanel switch to ON. Cold start is anundocumented capability that is enabled thru thesmall hole near the front panel switch.

  • 7/31/2019 OneAC1300 UPS Battery for ACE Chemistry

    74/75

    Appendix C: Accessing Remote Off

    ON Series User Instruction Manual 71

    NOTE:When AC returns, the UPS will supply AC

    power. The UPS will not supply inverter power when

    needed if the inverter control voltage is left in a

    positive 3-24V state. So, the EMO needs to reset the

    voltage in order for the UPS to operate as expected

    during a natural AC failure