One Box – Multi Options! - · One Box – Multi Options! 2 ... Production facility for fans and...
Transcript of One Box – Multi Options! - · One Box – Multi Options! 2 ... Production facility for fans and...
Systemair | 1Fans | Air Handling Units | Air Distribution Products | Fire Safety | Air Curtains and Heating Products | Tunnel Fans
Thermo fan Multibox/T
One Box – Multi Options!
2 | Systemair
Systemair worldwide
Skinnskatteberg, Sweden: Systemair AB, the Systemair group head office in Skinnskatteberg, Sweden. The production is virtually fully automated with modern machin-ery featuring advanced computer support. Also located here is the company's most advanced test installation for measuring technical data.
Windischbuch, Germany: Production facility for fans and modular air han-dling units, specialized on engineered products (e.g. tunnel and jet fans). Distribution center.
Hässleholm, Sweden: VEAB is the leading European manufacturer of electric duct heaters. Production of heating and cooling coils, electric and water based.
Ukmerge, Lithuania :Production of smaller air handling units with energy recovery systems.
Maribor, Slovenia: Specialized in centrifugal smoke extract fans, EN certified.
Hasselager, Denmark: Production of air handling units.
2 | Systemair
Systemair | 3
Save energy, lower running cost!Our label "Green Ventilation" features products with a high energy saving potential.All products labelled with "Green Ventilation" combine energy economy with energy efficiency.
Quality:Systemair is certified in accordance with ISO 9001; ISO 14001 and ATEX. Our research and develop-ment laboratories are one of the most modern in Europe; measurements are made in accordance with international standards like AMCA and ISO.
Bratislava, Slovakia: The factory in Bratislava manufactures air distribution products and EN certified fire and smoke dampers.
Kuala Lumpur, Malaysia :Manufacturing of products for the Asian market.
Madrid, Spain: Production of air handling units.
Dal, Eidsvoll, Norway: Production of air handling units for the Norwegian market.
New Delhi, India: The factories in New Delhi and Noida manufac-ture grilles and diffusers. Systemair Software is also based here.
Bouctouche, Canada: Our main North American production facility of air handling units and inline fans for commercial and residential applications is located in Bouctouche.
Kansas City, USA: Production of fans for the US market. Norwegian market.
Kuala Lumpur, Malaysia
Skinnskatteberg, Sweden Hässleholm, Sweden
Ukmerge, Lithuania
Bratislava, Slovakia
Maribor, Slovenia
Windischbuch, Germany
Madrid, Spain
Hasselager, Denmark
Kansas City, USA
Dal, Eidsvoll, Norway
Bouctouche, Canada
Systemair | 3
New Delhi, India
Hyderabad, India
4 | Systemair
Thermo fan Multibox/THigh performance and extreme flexibility
Protection guardMotor protection guard available as accessory.
Isolator switchAn isolator switch is pre-installed as standard.
Drain pipeIsolated and integrated fat drain tray including 1“ drain pipe.
Nozzle CCM/CCMIRound nozzle (CCM), sound isolated (CCMI). Available as accessory.
Whenever higher requirements are needed, the new Multibox/T can play to its strength. For example, it can handle polluted and hot exhaust air up to 100 °C in industrial areas or kitchens.
This new fan sets standards for flexibility and functionali-ty. During product development, great attention was paid to a fast and flexible installation on site as well as easy maintenance.
The results are impressive and will convince you as well as your customers:• The exhaust direction can be modified on site by sim-
ply changing the side panel positions. The location of the MUB/T can therefore be chosen freely and easily.
• The motor and impeller section can be removed as one section for maintenance. Practical handles allow an easy extraction.
• A condensate drain is pre-installed as standard.• Short time of delivery: MUB/T is available from stock.
Systemair | 5
F E D B
1 Zoll
A
C
MUB/T A B C D ⌀E ⌀F
042 400DV 670 670 590 548 404 253
042 400E4 670 670 590 548 404 253
042 450D4-IE2 670 670 590 548 454 286
042 450E4 670 670 590 548 454 286
042 500D4-IE2 670 670 590 548 504 321
062 560D4-IE2 800 800 720 678 564 361
062 630D4-IE2 800 800 720 678 635 407
Dimensions:
Technical data:MUB/T 042 400DV 042 400E4 042 450D4-IE2 042 450E4 042 500D4-IE2 062 560D4-IE2 062 630D4-IE2
item no. 33655 33656 33657 33658 33622 33659 33660
Voltage/Frequency V/50Hz 400 230 400 230 400 400 400
Phase ~ 3 1 3 1 3 3 3
Shaft power W 370 370 750 750 1500 2200 4000
Current A 1,4 2,1 1,78 5,3 3,39 4,2 8,12
Max. air volume m³/h 4082 3992 6188 6037 8042 11704 14843
RPM min-1 1370 1370 1400 1430 1400 1445 1450
Max. medium temperature °C 100 100 100 100 100 100 100
Sound pressure level at 1 m dB(A) 47 47 49 50 53 55 67
Weight kg 48 50 61 63 62 132 137
Motor isolation class F F F F F F F
Motor protection class IP 54 54 55 54 55 55 55
Additional benefits of the MUB/T:• Air volume optimized motor support• High efficiency motors placed outside air flow,
IE2 efficiency class for all 3~motors of 0.75 kW and higher
• Free-running, backward curved impeller ma-nufactured from aluminium
• Frame profile from corrosion-resistant alumini-um and plastic corners
• Housing equipped with 20 mm mineral wool for optimal sound and heat insulation
• Extensive range of accessories suitable for circular and rectangular ducts
• Sizes from 400 to 630• Air volume up to 15.000 m³/h
6 | Systemair
dB(A) Tot Medium frequency, Hz
63 125 250 500 1k 2k 4k 8k
LwA inlet 70 57 59 63 65 64 61 56 51
LwA outlet 72 59 61 65 67 66 63 58 51
LwA surrounding 54 41 43 47 49 48 45 40 33
Measurement conditions: qv = 0,6 m3/s, Ps = 385 Pa
dB(A) Tot Medium frequency, Hz
63 125 250 500 1k 2k 4k 8k
LwA inlet 70 57 59 63 65 64 61 56 49
LwA outlet 72 59 61 65 67 66 63 58 51
LwA surrounding 54 41 43 47 49 48 45 40 33
Measurement conditions: qv = 0,59 m3/s, Ps = 340 Pa
dB(A) Tot Medium frequency, Hz
63 125 250 500 1k 2k 4k 8k
LwA inlet 71 58 60 64 66 65 62 47 50
LwA outlet 73 60 62 66 68 67 64 59 52
LwA surrounding 56 43 45 49 51 50 47 42 35
Measurement conditions: qv = 0,8 m3/s, Ps = 500 Pa
dB(A) Tot Medium frequency, Hz
63 125 250 500 1k 2k 4k 8k
LwA inlet 72 59 61 65 67 66 63 48 51
LwA outlet 74 61 63 67 69 68 65 60 53
LwA surrounding 57 44 46 50 52 51 48 43 36
Measurement conditions: qv = 0,88 m3/s, Ps = 470 Pa
Systemair | 7
dB(A) Tot Medium frequency, Hz
63 125 250 500 1k 2k 4k 8k
LwA inlet 75 62 64 68 70 69 66 61 54
LwA outlet 77 64 66 70 72 71 68 63 56
LwA surrounding 60 47 49 53 55 54 51 46 39
Measurement conditions: qv = 1,26 m3/s, Ps = 550 Pa
Accessories:
FGVFlexible duct collar
SRKGDamper
UGSAdaptor, flexible
WSGWeather protection guard
WSD MUBWeather roof
CCMNozzle, square to round
CCMINozzle, square to round, sound isolated,
CCMNozzle, for duct connection
dB(A) Tot Medium frequency, Hz
63 125 250 500 1k 2k 4k 8k
LwA inlet 78 65 67 71 73 72 69 64 57
LwA outlet 80 67 69 73 75 74 71 66 59
LwA surrounding 63 50 52 56 58 57 54 49 42
Measurement conditions: qv = 2,25 m3/s, Ps = 565 Pa
dB(A) Tot Medium frequency, Hz
63 125 250 500 1k 2k 4k 8k
LwA inlet 86 73 75 79 81 80 77 72 65
LwA outlet 88 75 77 81 83 82 79 74 67
LwA surrounding 75 62 64 68 70 69 66 61 54
Measurement conditions: qv = 2,00 m3/s, Ps = 1100 Pa
8 | Systemair
Syst
emai
r Gm
bH ∙
Dez
embe
r 201
1 ∙
E300
1