    Okoguard is Okonites trade name for its eth-

    ylene propylene based insulation. Okoguard

    insulation is heat resistant, mechanically rug-

    ged, and exceptionally moisture resistant.

    This insulation provides an excellent balance

    of properties for a low voltage power cable.

    For use in branch circuits up to 600V. Rated

    90C wet or dry for use in conduits, under-ground ducts and aerial circuits in accor-

    dance with the National Electric Code. It is

    applicable for cable tray use on sizes 4/0 and

    larger and is sunlight resistant. This con-

    struction combines the high dielectric and

    flexibility characteristics of EPR and PVC to

    resist the hostile oil environments in refinery

    use and permits ease of low friction installa-

    tion. The jacket is UL rated Oil Resistant II.

    Uncoated soft copper per ASTM

    B-3. Sizes smaller than #8 are compress

    stranded per ASTM B-8. Sizes #8 and larger

    are compact stranded per ASTM B-496.

    Okoguard (EPR) meets or ex-

    ceeds all requirements of ICEA S-95-658,

    NEMA WC70 and UL Standard 44.

    Okoseal (PVC) meets or exceeds

    the requirements of ICEA S-95-658, NEMA

    WC70 and UL 1581, Class 43 (90C rated

    PVC jacket).

    Listed by Underwriters Laboratories, Inc. un-

    der miscellaneous wire category as

    RHW-2/PVC. Sizes 4/0 & larger are also

    marked for CT-Use.

    Sizes 4/0 AWG and larger pass the Vertical Tray Flame Test requirements of UL

    1581 for use in cable tray.

    Heat resistance; 90C continuous rat-ing; 130C emergency overload rating;

    250C short circuit rating

    Rated 90C wet or dry.

    Resistant to deformation at high tem-perature.

    Stable electrical properties.

    Low SIC and power factor.

    Low moisture absorption.

    Mechanically rugged.

    Resistant to weather, most oils, acidsand alkalies.

    More flexible, easier to install and termi-

    nate than XLPE insulation.

    UL Listed.

    Constructions also available rated 2kV.

    Okoguard-Okoseal

    Type RHW-2/PVC

    Copper Conductor/90C Wet or Dry

    Stranded Copper Conductor

    Insulation - Okoguard

    Jacket - Okoseal

    ULR

    B

    A

    C

  • 7/23/2019 OKONITE 600V RHW-2.pdf

    2/2

    112-24-3071

    112-24-3111

    112-24-3151

    14

    12

    10

    45

    45

    45

    15

    15

    15

    0.20

    0.22

    0.24

    29

    39

    54

    34

    44

    59

    15

    20

    30

    15

    20

    30

    24

    24

    30

    112-24-3231

    112-24-3271

    112-24-3311

    8

    6

    4

    60

    60

    60

    30

    30

    30

    0.33

    0.36

    0.41

    92

    127

    182

    103

    138

    205

    55

    75

    95

    50

    65

    85

    55

    75

    97

    112-24-3371

    112-24-3421

    112-24-3441

    2

    1/0

    2/0

    60

    80

    80

    30

    45

    45

    0.46

    0.61

    0.65

    267

    438

    532

    290

    470

    564

    130

    170

    195

    115

    150

    175

    130

    179

    204

    112-24-3481

    112-24-3541

    112-24-3581

    112-24-3641

    4/0

    350

    500

    750

    80

    95

    95

    110

    45

    65

    65

    65

    0.75

    0.96

    1.08

    1.27

    795

    1314

    1804

    2649

    834

    1369

    1881

    2749

    260

    350

    430

    535

    230

    310

    380

    475

    272

    384

    477

    598

    Visit Okonite's web site, www.okonite.com, for the most up to date dimensions.

    Ampacities are based on Table 310.16 of the National Electrical Code for

    these 90C rated conductors at an ambient temperature of 30C. The 75Cwet column is provided for additional information.

    The ampacities shown apply to open runs of cable, installation in any approvedraceway, direct burial in the earth, or as aerial cable on a messenger. Deratingfor more than three current carrying conductors within a raceway is in accor-dance with NEC Section 310.15.B.2.

    Based on three (3) conductors in a single enclosed or exposed conduit. Ca-pacities based on 40C air ambient using ICEA methods. For 30C ambientmultiply values by 1.10; for 50C multiply by .90. For other ambients or installa-tion conditions refer to Engineering Data Book EHB.

    For ampacities in cable tray, see NEC Section 392.11.B.

    B\14050308

    Okoguard-Okoseal

    Type RHW-2/PVC

    Copper Conductor/90C Wet or Dry

    II

    To order a color other than black, change the last digit of thecatalog number as follows:

    White 2 Orange 5

    Red 3 Blue 6

    Green 4 Yellow 7

    Example: To order #14 - Red, the catalog number would be112-24-3073

    ULR

    Ramsey, New Jersey 07446

    THE OKONITE COMPANY