OIL LEVEL INDICATOR TRIP CONTACT
-
Upload
mohamed-rafi -
Category
Documents
-
view
339 -
download
2
Transcript of OIL LEVEL INDICATOR TRIP CONTACT
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
1/34
www.precimeasure.com
PRECIMEASURE
The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.
Instruments are fully compensated for ambient temperature.
The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.
The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).
Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.
A maximum pointer facility is provided, can be reset from outside.
All switch contacts are potential free micro switches
MODEL - 1005/1005ADIAL TYPE THERMOMETER
SPECIFICATIONS Model : 1005 Model : 1005A
Temperature Range 0 -1500C, 0 -1600C, 30 -1500C,-20 to 1400C
0 -1500C, 0 -1600C, 30 -1500C,-20 to 1400C
Dial Size 150mm (6) Round 150mm (6) Round
Dial angular Sweep 2700 2700
Dial Graduation 10C 10C
Accuracy Class 1% of FSD 1% of FSD
Max. No. of Switches 5 5
Switching Range 15% - 85% 15% - 85%
Contact Rating 3A @ 250V AC/DC
Magnetic Blowout Micro switch
15A @ 250V AC
0.5A @ 250V DCStandard Micro switch
Switch Differential S1 & S2: 3C to 9C (630C)FixedS3 to S5: 8C to 400C Adjustable.
S1 & S2: 3C to 90C (630C)FixedS3 to S5: 80C to 400C Adjustable.
Switching Accuracy 2.5 0C of Set Value 2.50C of Set Value
Remote Repeater Available (Potentiometer Output) Available (Potentiometer Output)
Max. Capillary Length Up to 25 Mtrs Up to 25 Mtrs
Switch Test Knob Available Available
Electrical Connection Press Fit Wago Type Press Fit Wago Type
Degree of Protection IP 55(IEC - 60529) IP 55(IEC - 60529)
High Voltage Test 2.5 KV AC, 50Hz/60Hz for1 minute; all Terminals to ground
2.5 KV AC, 50Hz/60Hz for1 minute; all Terminals to ground
Electrical entry M20 - 3Nos M20 - 3Nos
Cable Gland Optional Optional
Thermometer Pocket Optional Optional
Remote Repeater 96 Sq
1005/1005A
General Features
STANDARD OTI / WTI
SPECIFICATIONS
Type 4 digits, 0.5 Seven Segments LEDs
Auxillary Supply 90 260V AC/DC
Resolution 0.10C
Degree of protection of enclosure IP 20
Operating Temperature Range 00C to 600C
Signal output 4 sets of 4 - 20mA DC
Optional RS 485
Cutout dimension 92 Sq. mm
DIALTYPE
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
2/34
www.precimeasure.com
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Cold and Dry Test : -40C to +70C
3. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
4. Salt Spray Test :
For polyester powder coating andSS 304 Armour for 500 Hrs as perDIN 50021 Standard
5. Micro Switch rating Test : a) ML - 1005:
3A @ 250V AC &3A @ 250V DC
b) ML - 1005A:15A @250V AC &0.5A @250V DC
Type Tested ForModel 1005 /1005A
Type of Instrument OTI / WTI
Range R1. 0 - 150CR2. 0 - 160CR3. 30 - 150CR4. -20 to140C(other ranges on request)
No. of Switches S2 - 2switchesS3 - 3switchesS4 - 4switchesS5 - 5switches
Switch Conguration L - Normally open contactL2 - Changeover contact
Capillary Length C1 - 1mtsC2 - 2mts....... upto C25 - 25mts
Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female
Repeater Y - RequriedN - Not Required
If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)
Ordering Information
Note: WTI Gradient is factory set. If required customer can adjust as per requirement.
Sample Ordering Information :1005\WTI\R3\S2\L2\C2\U1\Y\........... Amps ...............C
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
3/34
www.precimeasure.com
PRECIMEASURE
The fully sealed liquid expansion in the system provides a self powered indication and operation tothe instruments, and does not require any trimming or other periodic adjustments.
Instruments are fully compensated for ambient temperature. The WTI instruments have a built in Thermal imaging system for transformers hot spot indication. The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A). Embedded PT-100 sensors in the sensing bulb of the local OTI/ WTI provide for a master
indication. Current Converter Unit (CCU) is mounted inside the Local OTI/WTI, The output from which can be
connected to remote indicator or SCADA are a combination of both. For the WTIs additional Winding temperature simulator is provided Instrument cases are aluminium die casted and polyester powder coated. Each instrument has
anti vibration mountings and are provided with projection mounting clamps.
A maximum pointer facility is provided, can be reset from outside. All switch contacts are potential free micro switches
MODEL - 1005H/1005AHDIAL TYPE THERMOMETER
SPECIFICATIONS Model : 1005H Model : 1005AH
Temperature Range 0-1500C, 0-1600C, 30-1500C,-20 to 1400C
0-1500C, 0-1600C, 30-1500C,-20 to1400C
Dial Size 150mm (6) Round 150mm (6) Round
Dial angular Sweep 2700 2700
Dial Graduation 10C 10C
Accuracy Class 1% of FSD 1% of FSD
Max.No. of Switches 5 5
Switching Range 15% - 85% 15% - 85%
Contact Rating 3A @ 250V AC/DCMagnetic Blowout Micro switch
15A @ 250V AC0.5A @ 250V DCStandard Micro switch
Switch Differential S1 & S2: 3C to 9C (630C) FixedS3 to S5: 8C to 400C Adjustable.
S1 & S2: 3C to 90C (630C)FixedS3 to S5: 80C to 400C Adjustable.
Switching Accuracy 2.5 0C of Set Value 2.50C of Set Value
Remote indicator Available / 4 - 20mA / RS - 485 Available / 4-20mA / RS - 485
Max. Capillary Length Up to 25 Mtrs. Up to 25 Mtrs.
Switch Test Knob Available Available
Electrical Connection Press Fit Wago Type Press Fit Wago Type
Degree of Protection IP 55(IEC-60529) IP 55(IEC-60529)
High Voltage Test 2.5 KV AC, 50Hz/60Hz for 1minute; Switch connection & C.T.Terminal to ground.
CCU output 0.5 KV AC50Hz / 60Hz for 1 minute
2.5 KV AC, 50Hz/60Hz for 1minute; Switch connection & C.T.Terminal to ground.
CCU output 0.5 KV AC50Hz / 60Hz for 1 minute
Electrical entry M20 - 3Nos M20 - 3Nos
Cable Gland Optional Optional
Thermometer Pocket Optional OptionalRemote indicator 96 Sq
ML : 1005H/1005AH
General Features
Hybrid OTI / WTI
SPECIFICATIONS
Type 4 digits, 0.5 Seven Segments LEDs
Auxillary Supply 90 260V AC/DC
Resolution 0.10C
Degree of protection of enclosure IP 20
Operating Temperature Range 00
C to 600
C
Signal output 4 sets of 4 - 20mA DC
Optional RS 485
Cutout dimension 92 Sq.mm
DIALTYPE
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
4/34
www.precimeasure.com
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Cold and Dry Test : -40C to +70C
3. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
4. Salt Spray Test :
For polyster powder coating andSS 304 Armour for 500 Hrs as perDIN 50021 Standard
5. Micro Switch rating Test : a) ML - 1005H:
3A @ 250V AC &3A @ 250V DC
b) ML - 1005AH:15A @250V AC &0.5A @250V DC
Type Tested For
MODEL 1005H/1005AH
Type of Instrument OTI / WTI
Range R1. 0 - 150CR2. 0 - 160CR3. 30 - 150CR4. -20 to140C(other ranges on request)
No. of Switches S2 - 2switchesS3 - 3switchesS4 - 4switches
S5 - 5switchesSwitch Congura-tion
L - Normally open contactL2 - Changeover contact
Capillary Length C1 - 1mtsC2 - 2mts....... upto C25 - 25mts
Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female
CCU Output forindication / Scada
RI - Remote indicator - T1/T2/T3/T4 (for types, Refer Drawing)PSU - External power supply with 2 Nos. of 4-20mA output
If WTI please
specify
Transformer CT Secondary output..................(1A to 5A)
Simulated Temperature rise over top oil........... (5C to 30C)
Ordering Information
Note: WTI Gradient is factory set. If required customer can adjust as per requirment.
Sample Ordering Information :1005AH\OTI\R4\S4\L\C6\U4\RI-T2 ........... Amps ...............C
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
5/34
www.precimeasure.com
PRECIMEASURE
PSU
MODEL - 1005HX / 1005AHXDIAL TYPE THERMOMETER
Remote Indicator 96 Sq
Duplex Hybrid OTI / WTI
SPECIFICATIONS MODEL : 1005HX MODEL : 1005AHX
Temperature Range 0-1500C, 0-1600C, 30-1500C,-20 to 1400C
0-1500C, 0-1600C, 30-1500C,-20 to1400C
Dial Size 150mm (6) Round 150mm (6) Round
Dial angular Sweep 2700 2700
Dial Graduation 10C 10C
Accuracy Class 1% of FSD 1% of FSD
Max.No. of Switches 5 5
Switching Range 15% - 85% 15% - 85%
Contact Rating 3A @ 250V AC/DCMagnetic Blowout Micro switch 15A @ 250V AC0.5A @ 250V DCStandard Micro switch
Switch Differential S1 & S2: 3C to 9C (630C) FixedS3 to S5: 8C to 400C Adjustable.
S1 & S2: 3C to 90C (630C)FixedS3 to S5: 80C to 400C Adjustable.
Switching Accuracy 2.5 0C of Set Value 2.50C of Set Value
Remote indicator Available / 4-20mA / RS - 485 Available / 4-20mA / RS - 485
Max. Capillary Length Up to 25 Mtrs. Up to 25 Mtrs.
Switch Test Knob Available Available
Electrical Connection Press Fit Wago Type Press Fit Wago Type
Degree of Protection IP 55(IEC-60529) IP 55(IEC-60529)
High Voltage Test 2.5 KV AC, 50Hz/60Hz for 1minute; Switch connection & C.T.Terminal to ground.CCU output 0.5 KV AC50Hz / 60Hz for 1 minute
2.5 KV AC, 50Hz/60Hz for 1minute; Switch connection & C.T.Terminal to ground.CCU output 0.5 KV AC50Hz / 60Hz for 1 minute
Electrical entry M20 - 3Nos M20 - 3Nos
Cable Gland Optional Optional
Thermometer pocket Optional Optional
ML: 1005 HX/1005 AHX
The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.
Instruments are fully compensated for ambient temperature. The WTI instruments have a built in Thermal imaging system for transformers hot spot indication. The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A). Embedded Duplex PT-100 sensors in the sensing bulb of the local OTI/ WTI provide for a
master indication. Current Converter Units (CCUs) are mounted inside the Local OTI/WTI, The output from which can be
connected to remote indicator and SCADA through external power supply units (PSUs). For the WTIs additional Winding temperature simulator is provided Instrument cases are aluminium die casted and polyester powder coated. Each instrument has
anti vibration mountings and are provided with projection mounting clamps. A maximum pointer facility is provided, can be reset from outside. All switch contacts are potential free micro switches
General Features
POWER SUPPLY UNIT - (PSU)
a. Output Voltage: 24V
b. Output Signal: Analogue output2nos. 4-20mA DC(Output - 1, Burden 250 Ohms)(Output- 2, Burden 600 Ohms)
c. Auxiliary supply: 90-260V AC/DC
REMOTE INDICATOR
a Type : 4 digits, 0.5 Seven Segment LEDs
b Auxiliary Supply : 90 260V AC/DC
d Resolution : 0.10C
e Degree of protection of enclosure : IP-20f Operating Temperature Range : 0C to 60C
g Signal output: 4sets of 4-20mA DC, OptionalRS 485
h Cutout Dimension: 92Sq.mm
DIALTYPE
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
6/34
www.precimeasure.com
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Cold and Dry Test : -40C to +70C
3. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
4. Salt Spray Test :
For polyster powder coating andSS 304 Armour for 500 Hrs as perDIN 50021 Standard
5. Micro Switchrating Test : a) ML - 1005HX:
3A @ 250V AC &3A @ 250V DC
b) ML - 1005AHX:15A @250V AC &0.5A @250V DC
Type Tested ForMODEL 1005HX/1005AHX
Type of Instrument OTI / WTI
Range R1. 0 - 150CR2. 0 - 160CR3. 30 - 150CR4. -20 to140C(other ranges on request)
No. of Switches S2 - 2switchesS3 - 3switchesS4 - 4switches
S5 - 5switchesSwitch Conguration L - Normally open contact
L2 - Changeover contact
Capillary Length C1 - 1mtsC2 - 2mts....... upto C25 - 25mts
Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female
CCU Output forindication / Scada
RI - Remote indicator - T1/T2/T3/T4 (For Types, Refer Drawing)(Connected through external powersupply PSUs)
If WTI please specify Transformer CT Secondary output..................(1A to 5A)
Simulated Temperature rise over top oil........... (5C to 30
C)
Ordering Information
Note: WTI Gradient is factory set. If required customer can adjust as per requirment.
Sample Ordering Information :1005AHX\OTI\R4\S4\L\C6\U4\RI-T1........... Amps.............C
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
7/34
www.precimeasure.com
PRECIMEASURE
The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.
Instruments are fully compensated for ambient temperature.
The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.
The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).
Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.
A maximum pointer facility is provided, can be reset from outside.
All switch contacts are potential free micro switches
MODEL - 1007DIAL TYPE THERMOMETER
Remote Repeater 96 Sq
General Features
Standard OTI / WTI
ML : 1007
PSU
SPECIFICATIONS MODEL : 1007
Temperature Range 0-1500C, 0-1600C, 30-1500C,-20 to 1400C
Dial Size 115mm, Segment Dial
Dial angular Sweep 600
Dial Graduation 20C
Accuracy Class 1.5% of FSD
Max.No. of Switches 4
Switching Range 15% - 85%
Contact Rating 15A @ 250V AC0.5A @ 250V DCStandard Micro switch
Switch Differential S1 & S2: 3C to 9C (630C) FixedS3 & S4: 8C to 400C Adjustable.
Switching Accuracy 2.5 0C of Set Value
Remote Repeater Available (Potentiometer Output)
Max. Capillary Length Up to 25 Mtrs.
Electrical Connection Press Fit Wago Type
Degree of Protection IP 55 (IEC-60529)
High Voltage Test 2.5 KV AC, 50Hz/60Hz for 1 minute; all Terminalsto ground
Electrical entry M20 - 3Nos
Cable Gland Optional
Thermometer Pocket Optional
DIALTYPE
POWER SUPPLY UNIT - (PSU)
a. Output Voltage: 24V
b. Output Signal: Analogue output2nos. 4-20mA DC(Output - 1, Burden 250 Ohms)(Output- 2, Burden 600 Ohms)
c. Auxiliary supply: 90-260V AC/DC
REMOTE INDICATOR
a Type : 4 digits, 0.5 Seven Segment LEDs
b Auxiliary Supply : 90 260V AC/DC
d Resolution : 0.10C
e Degree of protection of enclosure : IP-20f Operating Temperature Range : 0C to 60C
g Signal output: 4sets of 4-20mA DC, OptionalRS 485
h Cutout Dimension: 92Sq.mm
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
8/34
www.precimeasure.com
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Cold and Dry Test : -40C to +70C
3. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
4. Salt Spray Test :
For polyster powder coating andSS 304 Armour for 500 Hrs as perDIN 50021 Standard
5. Micro Switch rating Test : 15A @250V AC &
0.5A @250V DC
Type Tested For
Model 1007
Type of Instrument OTI / WTI
Range R1. 0 - 150CR2. 0 - 160CR3. 30 - 150CR4. -20 to140C(other ranges on request)
No. of Switches S2 - 2switchesS3 - 3switchesS4 - 4switches
Switch Conguration L - Normally open contactL2 - Changeover contact
Capillary Length C1 - 1mtsC2 - 2mts....... upto C25 - 25mts
Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female
Repeater Y - Requried,N - Not Required
If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)
Ordering Information
Note: WTI Gradient is factory set. If required customer can adjust as per requirment.
Sample Ordering Information :1007\OTI\R3\S2\L2\C8\U5\Y\........... Amps ...............C
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
9/34
www.precimeasure.com
PRECIMEASURE
The fully sealed liquid expansion in the system provides a self powered indication and operation to the instruments, anddoes not require any trimming or other periodic adjustments.
Instruments are fully compensated for ambient temperature.
The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.
The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).
Embedded PT-100 sensorsin the sensing bulb of the local OTI/ WTI provide for a master indication.
Current Converter Unit (CCU) is mounted inside the Local OTI/WTI, The output from which can be connected to remoteindicator or SCADA are a combination of both.
For the WTIs additional Winding temperature simulator is provided
Instrument cases are aluminium die casted and polyester powder coated. Each instrument has anti vibration mountingsand are provided with projection mounting clamps.
A maximum pointer facility is provided, can be reset from outside.
All switch contacts are potential free micro switches
MODEL - 1007HDIAL TYPE THERMOMETER
General Features
Hybrid OTI / WTI
ML : 1007H Specifications Model : 1007HTemperature Range 0-1500C, 0-1600C, 30-1500C,-20 to 1400C
Dial Size 115mm, Segment Dial
Dial angular Sweep 600
Dial Graduation 20C
Accuracy Class 1.5% of FSD
Max.No. of Switches 4
Switching Range 15% - 85%
Contact Rating 15A @ 250V AC
0.5A @ 250V DCStandard Micro switch
Switch Differential S1 & S2: 3C to 9C (630C) FixedS3 & S4: 8C to 400C Adjustable.
Switching Accuracy 2.5 0C of Set Value
Remote Indicator Available / 4-20mA / RS - 485
Max. Capillary Length Up to 25 Mtrs
Electrical Connection Press Fit Wago Type
Degree of Protection IP 55(IEC-60529)
High Voltage Test 2.5 KV AC, 50Hz/60Hz for 1 minute; Switchconnection & C.T. Terminal to ground.CCU output 0.5 Kv Ac50Hz / 60Hz for 1 minute
Electrical entry M20 - 3Nos
Cable Gland Optional
Thermometer Packet Optional
DIALTYPE
POWER SUPPLY UNIT - (PSU)
a. Output Voltage: 24V
b. Output Signal: Analogue output2nos. 4-20mA DC(Output - 1, Burden 250 Ohms)(Output- 2, Burden 600 Ohms)
c. Auxiliary supply: 90-260V AC/DC
REMOTE INDICATOR
a Type : 4 digits, 0.5 Seven Segment LEDs
b Auxiliary Supply : 90 260V AC/DC
d Resolution : 0.10C
e Degree of protection of enclosure : IP-20f Operating Temperature Range : 0C to 60C
g Signal output: 4sets of 4-20mA DC, OptionalRS 485
h Cutout Dimension: 92Sq.mm
Remote Repeater 96 Sq
PSU
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
10/34
www.precimeasure.com
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Cold and Dry Test : -40C to +70C
3. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
4. Salt Spray Test : For polyster powder coating and
SS 304 Armour for 500 Hrs as perDIN 50021 Standard
5. Micro Switch rating Test : 15A @250V AC & 0.5A @250V DC
Type Tested For
Model 1007H
Type of Instrument OTI / WTI
Range R1. 0 - 150CR2. 0 - 160CR3. 30 - 150CR4. -20 to140C(other ranges on request)
No. of Switches S2 - 2switchesS3 - 3switchesS4 - 4switches
Switch Conguration L - Normally open contactL2 - Changeover contact
Capillary Length C1 - 1mtsC2 - 2mts....... upto C25 - 25mts
Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female
CCU Output for
indication / Scada
RI - Remote indicator - T1/T2/T3/T4 (For types, refer Drawing)
PSU - External power supply with 2 Nos. of 4-20mA outputIf WTI please specify Transformer CT Secondary output..................(1A to 5A)
Simulated Temperature rise over top oil........... (5C to 30C)
Ordering Information
Note: WTI Gradient is factory set. If required customer can adjust as per requirment.
Sample Ordering Information :1007H\OTI\R3\S2\L2\C8\U5\RI-T4........... Amps ...............C
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
11/34
www.precimeasure.com
PRECIMEASURE
The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.
Instruments are fully compensated for ambient temperature.
The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.
The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).
Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.
A maximum pointer facility is provided, can be reset from outside.
All switch contacts are potential free micro switches.
MODEL - 1006DIAL TYPE THERMOMETER
General Features
Standard OTI / WTI
ML : 1006
SPECIFICATIONS MODEL : 1006
Temperature Range 0-1500C, 0-2400C
Dial angular Sweep 2700
Dial Graduation 20C
Accuracy Class 1.5% of FSD
Max.No. of Switches 2
Switching Range 15% - 85%
Contact Rating5A @ 250V AC,
0.5A @ 220V DC
Switch Differential 10C to 50C (30C20C) Fixed
Switching Accuracy 2.50C of Set Value
Max. Capillary Length Up to 6 Mtrs.
Switch Test Knob Available
Electrical Connection 1Sq mm. Copper Cable, 1mtr LengthDegree of Protection IP 55(IEC-60529)
High Voltage Test2.5 KV AC, 50Hz / 60Hz for 1 minute ; all Terminal to ground
DIALTYPE
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
12/34
www.precimeasure.com
Model 1006
Type of Instrument OTI / WTI
Range R1. 0 - 150C.
R2. 0 - 240C
No. of Switches S2 - 2switchesSwitch Conguration L - Normally open contact
L2 - Changeover contact
Capillary Length C1 - 1mtsC2 - 2mts....... upto C6 - 6mts
Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1 BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female
If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)
Ordering Information
Note: WTI Gradient is factory set. If required customer can adjust as per requirment.
Sample Ordering Information :1006\WTI\R1\S2\L2\C5\U5 ........... Amps ...............C
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Vibration Test : Amplitude 1mm,
frequency 50Hz, 1Hr / X,Y,Z axis
3. Salt Spray Test : For polyster powder coating
and SS 304 Armour for 500 Hrsas per DIN 50021Standard
4. Micro Switch rating Test : 5A @ 250V AC, 0.5A @ 220V DC
Type Tested For
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
13/34
www.precimeasure.com
PRECIMEASURE
The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.
Instruments are fully compensated for ambient temperature.
The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.
The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A). Embedded PT-100 sensorsin the sensing bulb of the local OTI/ WTI provide for a master indication.
Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.
A maximum pointer facility is provided, can be reset from outside.
All switch contacts are potential free micro switches.
MODEL - 1006HDIAL TYPE THERMOMETER
General Features
Hybrid OTI / WTI
ML : 1006H SPECIFICATIONS MODEL : 1006H
Temperature Range 0-1500C, 0-2400C
Dial angular Sweep 2700
Dial Graduation 20C
Accuracy Class 1.5% of FSD
Max.No. of Switches 2
Switching Range 15% - 85%
Contact Rating
5A @ 250V AC,
0.5A @ 220V DC
Switch Differential 10C to 50C (30C20C) Fixed
Switching Accuracy 2.50C of Set Value
Remote Indicator Availbale
Max. Capillary Length Up to 6 Mtrs.
Switch Test Knob Available
Electrical Connection 1Sq mm. Copper Cable, 1mtr Length
Degree of Protection IP 55(IEC-60529)
High Voltage Test
(a) Local OTI / WTI
(b) Local OTI / WTI
(c) CCU
(d) CCU
Test Voltage
2.5 KV AC, 50Hz / 60Hz
500 V AC, 50Hz / 60Hz
500 V AC, 50Hz / 60Hz
2.5 KV AC, 50Hz / 60Hz
Terminals Details
Switch connection / CT Connection
Pt 100 sensor output
Pt 100 sensor input +4-20mA Output
CT connection with power supply
ML : 2220-R2 (CCU)
Remote Indicator 96 Sq
SPECIFICATION
Type 4 digits, 0.5 Seven Segments LEDs
Auxillary Supply 90 260V AC/DC
Resolution 0.10C
Degree of protection of enclosure IP 20
Operating Temperature Range 00C to 600C
Signal output 4 sets of 4 - 20mA DC, Optional RS 485
Cutout dimension 92 Sq.mm
DIALTYPE
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
14/34
www.precimeasure.com
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
3. Salt Spray Test : For polyster powder coating and
SS 304 Armour for 500 Hrs as perDIN 50021 Standard
4. Micro Switch rating Test : 5A @ 250V AC,
0.5A @ 220V DC
Type Tested For
Model 1006H
Type of Instrument OTI / WTI
Range R1. 0 - 150C.
R2. 0 - 240C
No. of Switches S2 - 2switches
Switch Conguration L - Normally open contactL2 - Changeover contact
Capillary Length C1 - 1mtsC2 - 2mts....... upto C6 - 6mts
Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1 BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female
If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)
Ordering Information
Note: 1) WTI Gradient is factory set. If required customer can adjust as per requirment. 2) External CCU and Remote Indicator is Part of the scheme.
Sample Ordering Information :1006H\WTI\R1\S2\L\C3\U2 ........... Amps ...............C
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
15/34
www.precimeasure.com
PRECIMEASURE MODEL - 1006DHDIAL TYPE THERMOMETER for
DRY TYPE TRANSFORMER
General Features
ML : 1006DHSpecifications Model : 1006DH
Temperature Range 0-2400C
Dial angular Sweep 2700
Dial Graduation 20C
Accuracy Class 1.5% of FSD
Max.No. of Switches 2
Switching Range 15% - 85%
Contact Rating 5A @ 250V AC,
0.5A @ 220V DCSwitch Differential 10C to 50C (30C20C) Fixed
Switching Accuracy 40C of Set Value
Remote Indicator Availbale
Max. Capillary Length Up to 6 mtrs
Electrical Connection 1Sq mm. Copper Cable, 1mtr Length
Degree of Protection IP 55 (IEC-60529)
High Voltage Test
Switch Contact - 2.5KV AC,50Hz/60Hz for 1 Minutebetween Switch Terminals to ground
CCU- 500V AC,50Hz/60Hz for 1 Minute between CCUTerminals to ground
PSU
Hybrid Instrument
This is a high performance temperature Monitoring instrument with built-in PT-100 Sensor (RTD) & CurrentConverter Unit and external Remote indicator with built-in power supply unit
Winding temperatures Indicator & Controller for Dry Type Transformers / Cast-Resin Transformers with built-inRTD scheme for Independent Remote indication and 4-20mA DC output for SCADA connection.
Power Supply Unit
Signal out put 2 nos 4-20 mA DC
Aux Supply voltage 90-260V AC/DC
Burden on signal output 600 max including loop resistance
Temperature range 0-240C
Degree of protection IP-40
Temperature range 0-240C
Signal input 4-20 mA DC
Aux Supply voltage 90-260V AC/DC
Communication RS-485MODBUS RTU Communication(Optional)
Degree of protection IP 20
Cutout Dimension 92 sq.mm
Digital Remote indicator
Remote Indicator 96 Sq
The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.
Instruments are fully compensated for ambient temperature.
Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.
A maximum pointer facility is provided, can be reset from outside. All switch contacts are potential free micro switches
DIALTYPE
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
16/34
www.precimeasure.com
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
3. Salt Spray Test : For polyster powder coating and
SS 304 Armour for 500 Hrs as perDIN 50021 Standard
4. Micro Switch rating Test : 5A @ 250V AC,
0.5A @ 220V DC
Type Tested ForModel 1006DH
Type of Instrument WTI
Range R1. 0 - 240C
No. of Switches S2 - 2switches
Switch Conguration L - Normally open contactL2 - Changeover contact
Capillary Length C1 - 1mtsC2 - 2mts....... upto C6 - 6mts
Ordering Information
Note: WTI Gradient is factory set. If required customer can adjust as per requirment.
Sample Ordering Information :1006DH\WTI\R1\S2\L\C4
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
17/34
www.precimeasure.com
PRECIMEASURE MODEL - 1006HXDIAL TYPE THERMOMETER
Duplex Hybrid OTI / WTI
ML : 1006HX
SPECIFICATIONS MODEL : 1006HX
Temperature Range 0-1500C, 0-2400C
Dial angular Sweep 2700
Dial Graduation 20C
Accuracy Class 1.5% of FSD
Max.No. of Switches 2
Switching Range 15% - 85%
Contact Rating5A @ 250V AC,
0.5A @ 220V DC
Switch Differential 10C to 50C (30C20C) Fixed
Switching Accuracy 2.50C of Set Value
Remote Indicator Availbale
Max. Capillary Length Up to 6 Mtrs.
Switch Test Knob Available
Electrical Connection 1Sq mm. Copper Cable, 1mtr length
Degree of Protection IP 55(IEC-60529)
High Voltage Test
(a) Local OTI / WTI
(b) Local OTI / WTI
(c) CCU
(d) CCU
Test Voltage
2.5 KV AC, 50Hz / 60Hz
500 V AC, 50Hz / 60Hz
500 V AC, 50Hz / 60Hz
2.5 KV AC, 50Hz / 60Hz
Terminals Details
Switch connection / CT Connection
Pt 100 sensor output
Pt 100 sensor input +4-20mA Output
CT connection with power supply
The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.
Instruments are fully compensated for ambient temperature.
The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.
The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).
Embedded Duplex PT-100 sensorsin the sensing bulb of the local OTI/ WTI provide for amaster indication.
This output can be connected to Remote Indicator or SCADA or combination of both.
WTI additional Winding temperature simulator is provided.
Instrument cases are aluminium die casted and polyester powder coated. Each instrument has
anti vibration mountings and are provided with projection mounting clamps. A maximum pointer facility is provided, can be reset from outside.
All switch contacts are potential free micro switches.
General Features
PSU
Remote Indicator 96 Sq
POWER SUPPLY UNIT - (PSU)
a. Output Voltage: 24V
b. Output Signal: Analogue output2nos. 4-20mA DC(Maximum burden 600 OhmsIncluding Loop resistantance)
c. Auxiliary supply: 90-260V AC/DC
REMOTE INDICATOR
a Type : 4 digits, 0.5 Seven Segment LEDs
b Auxiliary Supply : 90 260V AC/DC
d Resolution : 0.10C
e Degree of protection of enclosure : IP-20
f Operating Temperature Range : 0C to 60C
g Signal output: 4sets of 4-20mA DC, OptionalRS 485
h Cutout Dimension: 92Sq.mm
DIALTYPE
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
18/34
www.precimeasure.com
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
3. Salt Spray Test : For polyster powder coating and
SS 304 Armour for 500 Hrs as perDIN 50021 Standard
4. Micro Switch rating Test : a) ML - 1006HX:
5A @ 250V AC,
0.5A @ 220V DC
Type Tested ForModel 1006HX
Type of Instrument OTI / WTI
Range R1. 0 - 150C.
R2. 0 - 240C
No. of Switches S2 - 2switches
Switch Conguration L - Normally open contactL2 - Changeover contact
Capillary Length C1 - 1mtsC2 - 2mts....... upto C6 - 6mts
Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1 BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female
CCU Output forindication / Scada
RI - Remote indicator - T1/T2/T3/T4 (For types, Refer Drawing(Connected through external powersupply PSUs)
If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)
Ordering Information
Note: WTI Gradient is factory set. If required customer can adjust as per requirment.
Sample Ordering Information :1006HX\OTI\R2\S2\L\C4\U1\RI-T3 ........... Amps ...............C
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
19/34
www.precimeasure.com
PRECIMEASURE
The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.
Instruments are fully compensated for ambient temperature.
The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.
The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A).
Instrument cases are aluminium die casted and polyester powder coated. Each instrument has antivibration mountings and are provided with projection mounting clamps.
A maximum pointer facility is provided, can be reset from outside.
All switch contacts are potential free micro switches.
MODEL - 1031DIAL TYPE THERMOMETER
General Features
Standard OTI / WTI
ML : 1031
SPECIFICATIONS Model : 1031
Temperature Range 0-1500C
Dial size 115mm, Segment Dial
Dial angular Sweep 600
Dial Graduation 20C
Accuracy Class 1.5% of FSD
Max.No. of Switches 2
Switching Range 15% - 85%
Contact Rating5A @ 250V AC
0.5A @ 220V DC
Switch Differential 10C to 50C (30C20C) Fixed
Switching Accuracy 2.50C of Set Value
Max. Capillary Length Up to 6 Mtrs.Electrical Connection 1Sq mm. Copper Cable, 1mtr Length
Degree of Protection IP 55(IEC-60529)
High Voltage Test 2.5KV AC, 50Hz/60Hz for 1 minute; All terminal to ground
DIALTYPE
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
20/34
www.precimeasure.com
Model 1031
Type of Instrument OTI / WTI
Range R1. 0 - 150C.
No. of Switches S2 - 2switches
Switch Conguration L - Normally open contactL2 - Changeover contact
Capillary Length C1 - 1mtsC2 - 2mts....... upto C6 - 6mts
Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1 BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female
If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)
Ordering Information
Note: WTI Gradient is factory set. If required customer can adjust as per requirment.
Sample Ordering Information :1031\OTI\R1\S2\L2\C6\U2 ........... Amps ...............C
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
3. Salt Spray Test : For polyster powder coating and
SS 304 Armour for 500 Hrs as perDIN 50021 Standard
4. Micro Switch rating Test : 5A @ 250V AC,
0.5A @ 220V DC
Type Tested For
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
21/34
www.precimeasure.com
PRECIMEASURE
The fully sealed liquid expansion in the system provides a self powered indication and operation to theinstruments, and does not require any trimming or other periodic adjustments.
Instruments are fully compensated for ambient temperature.
The WTI instruments have a built in Thermal imaging system for transformers hot spot indication.
The WTIs are provided with gradient adjustment through a shunt for CT secondary input (1A to 5A). Embedded PT-100 sensorsin the sensing bulb of the local OTI/ WTI provide for a master indication.
Instrument cases are aluminium die casted and polyester powder coated. Each instrument hasanti vibration mountings and are provided with projection mounting clamps.
A maximum pointer facility is provided, can be reset from outside.
All switch contacts are potential free micro switches.
MODEL - 1031HDIAL TYPE THERMOMETER
General Features
Hybrid OTI / WTI
ML : 1031H SPECIFICATIONS MODEL : 1031H
Temperature Range 0-1500C
Dial Size 115mm, Segment Dial
Dial angular Sweep 600
Dial Graduation 20C
Accuracy Class 1.5% of FSD
Max.No. of Switches 2
Switching Range 15% - 85%
Contact Rating5A @ 250V AC,
0.5A @ 220V DC
Switch Differential 10C to 50C (30C20C) Fixed
Switching Accuracy 2.50C of Set Value
Remote Indicator Availbale
Max. Capillary Length Up to 6 Mtrs.
Electrical Connection 1Sq mm. Copper Cable, 1mtr Lenght
Degree of Protection IP 55(IEC-60529)ML : 2220-R2 (CCU)
Remote Indicator
SPECIFICATIONS
Type 4 digits, 0.5 Seven Segments LEDs
Auxillary Supply 90 260V AC/DC
Resolution 0.10C
Degree of protection of enclosure IP 20
Operating Temperature Range 00C to 600C
Signal output 4 sets of 4 - 20mA DC, Optional RS 485Cutout dimension 92 Sq.mm
High Voltage Test
(a) Local OTI / WTI
(b) Local OTI / WTI
(c) CCU
(d) CCU
Test Voltage
2.5 KV AC, 50Hz / 60Hz
500 V AC, 50Hz / 60Hz
500 V AC, 50Hz / 60Hz
2.5 KV AC, 50Hz / 60Hz
Terminals Details
Switch connection / CT Connection
Pt 100 sensor output
Pt 100 sensor input +4-20mA Output
CT connection with power supply
DIALTYPE
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
22/34
www.precimeasure.com
Model 1031H
Type of Instrument OTI / WTI
Range R1. 0 - 150C.
No. of Switches S2 - 2switches
Switch Conguration L - Normally open contact
L2 - Changeover contactCapillary Length C1 - 1mts
C2 - 2mts....... upto C6 - 6mts
Union Type U1 - 1/2 BSP MaleU2 - 3/4 BSP MaleU3 - 1 BSP MaleU4 - 1/2 BSP FemaleU5 - 3/4 BSP Female
If WTI please specify Transformer CT Secondary output..................(1A to 5A)Simulated Temperature rise over top oil........... (5C to 30C)
Ordering Information
Sample Ordering Information :1031H\WTI\R1\S2\L\C3\U2 ........... Amps ...............C
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
3. Salt Spray Test : For polyster powder coating and
SS 304 Armour for 500 Hrs as perDIN 50021 Standard
4. Micro Switch rating Test : 5A @ 250V AC,
0.5A @ 220V DC
Type Tested For
Note: 1) WTI Gradient is factory set. If required customer can adjust as per requirment. 2) External CCU and Remote Indicator is Part of the scheme.
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
23/34
www.precimeasure.com
PRECIMEASURE DIAL TYPE BI - METALLICTHERMOMETER
Bi-metallic type thermometer consists of Helical Bimetal Coil, which will expand or contract according to thetemperature changes, which in turn operates indicating pointer.
General Featuresa No external power supply required for indication or operation.
a Sealed system which requires no trimming or periodic site adjustments
a Directly mounted on the Transformer & Other Process Control Equipments.
a A maximum pointer facility is provided, can be reset from outside.
a The instruments are capable of working at an ambient temperature range of 00C to +600C.
MODEL 1070 (THERMOMETER WITHOUT CONTACT, TOP MOUNTING)
SPECIFICATIONS
Dial Segment Dial
Angular Sweep 1050
Range 0-1200C (Other ranges on request)
Accuracy 40C Between 400C & 1100C
Graduation 20C per division
Instrument Case PDC Aluminum Casting with Polyester Powder Coated.
ML :1070
ML :1071
MODEL 1071 (THERMOMETER WITH 2 CONTACT, TOP MOUNTING)
SPECIFICATIONS
Dial Segment Dial
Angular Sweep 1050
Range 0-1200C (Other ranges on request)
Accuracy 40C Between 400C & 1100C
Graduation 20C per division
Instrument Case PDC Aluminum Casting with Polyester Powder Coated.
Max. Number of Switches 2
Switch Type Micro Switch
Switch Rating 5A at 240V AC
Switches Normally Open Type or Changeover Type
Adjustable Range 200C 1050C
Accuracy of switch setting 40C of Set Value
Switch Differential Range 60C30C
Contact Type Potential Free
Cable Gland (Polyamide / Brass) Cable Gland Size PG16
High Voltage Test 2KV AC, 50/60 Hz for 1 Minute, All terminals to ground
BI-METALLIC
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
24/34
www.precimeasure.com
MODEL 1068 (4" DIAL THERMOMETER WITH 2 CONTACT, HORIZONTAL MOUNTING)
SPECIFICATIONS
Dial Round Dial 4
Angular Sweep 1350
Range 0-1200C (Other ranges on request)
Accuracy 40C Between 400C & 1100C
Graduation 20C per division
Instrument Case PDC Aluminum Casting with Polyester Powder Coated
* The WTI instruments have a built in Thermal imaging system for transformers hotspot indication.
* WTI Gradient calibration is factory set as per customer specication. If required, aprovision is made for small adjustment at site.
MODEL 1071 WTI (THERMOMETER WITH 2 CONTACT, TOP MOUNTING)WINDING TEMPERATURE INDICATOR :
SPECIFICATIONS
Dial Segment Dial
Angular Sweep 1050
Range 0-1200C (Other ranges on request)
Accuracy 40C Between 400C & 1100C
Graduation 20C per division
Instrument Case PDC Aluminum Casting with Polyester Powder Coated
Max. Number of Switches 2
Switch Type Micro Switch
Switch Rating 5A at 240V AC
Switches Normally Open Type or Changeover Type
Adjustable Range 200C 1050C
Switching Accuracy 40C of Set Value
Switch Differential 60C30C
Contact Type Potential Free
Cable Gland (Polyamide / Brass) Cable Gland Size PG11-2Nos
High Voltage Test 2KV AC, 50Hz for 1 Minute, All terminals to ground
ML :1071-WTI
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
Max. Number of Switches 2
Switch Type Micro Switch
Switch Rating 5A at 240V AC
Switches Normally Open Type or Changeover Type
Adjustable Range 400C 1050C
Accuracy of switch setting 40C of Set Value
Switch Differential Range 60C30CContact Type Potential Free
Cable Gland (Polyamide / Brass) Cable Gland Size PG16
High Voltage Test 2KV AC, 50/60 Hz for 1 Minute, All terminals to ground
ML :1068
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
25/34
www.precimeasure.com
PRECIMEASURE
ML :1075
DIAL TYPE BI - METALLICTHERMOMETER
MODEL 1075 (3 DIAL HORIOZONTAL MOUNTING WITHMAXIMUM POINTER)
SPECIFICATIONS
Dial Round Dial 3
Angular Sweep 2400
Range 0-1200C (Other ranges on request)
Accuracy 40C Between 400C & 1100C
Graduation 20C per divisionInstrument Case SS-304 Case (Natural Finish).
MODEL 1073 (4 DIAL TOP MOUNTING WITH MAXIMUM POINTER)
SPECIFICATIONS
Dial Round Dial 4
Angular Sweep 2400
Range 0-1200C (Other ranges on request)
Accuracy 40C Between 400C & 1100C
Graduation 20C per division
Instrument Case SS-304 Case (Natural Finish)
MODEL 1074 (6 DIAL TOP MOUNTING WITH MAXIMUM POINTER)
SPECIFICATIONS
Dial Round Dial 6
Angular Sweep 2400
Range 0-1200C (Other ranges on request)
Accuracy 40C Between 400C & 1100C
Graduation 20C per division
Instrument Case SS-304 Case (Natural Finish).
ML :1073 / 1074
BI-METALLIC
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
26/34
www.precimeasure.com
ML :1078
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Salt Spray Test : Model-1068 / 1070 / 1071 For polyster powder coating
500 Hrs as per DIN 50021Standard
All the Models Type Tested For :
MODEL 1078 (3 DIAL TOP MOUNTING WITH MAXIMUM POINTER)
SPECIFICATIONS
Dial Round Dial 3
Angular Sweep 2400
Range 0 -1200C (Other ranges on request)
Accuracy 40C Between 400C & 1100C
Graduation 20C per division
Instrument Case SS-304 Case (Natural Finish).
ML :1079
MODEL 1079 (3 DIAL ENTRY AT ANGLE 450WITH MAXIMUM POINTER)
SPECIFICATIONS
Dial Round Dial 3
Angular Sweep 2400
Range 0 -1200C ( Other ranges on request)
Accuracy 40C Between 400C & 1100C
Graduation 20C per division
Instrument Case SS-304 Case (Natural Finish).
Registered Office & Works :No. 168/C Industrial Suburb,
Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :No. 27,28,30, Block-II, 2ndFloor,
Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
27/34
www.precimeasure.com
PRECIMEASURE
ML :2241B
MODEL 2241B & 2242 WINDING TEMPERATURE INDICATOR / CONTROLLER FOR DRY TYPE TRANSFORMERS
APPLICATION :MODEL 2241B/2242/2244T3 is designed for monitoring the temperatures of L.V. windings of the Dry-Type Transformer / Cast ResinTransformers. It will display winding temperatures and take necessary control action as per set and differential values programmedby the user. The protection system also records maximum temperatures and will display the same along with corresponding channelnumber whenever relevant push button is pressed.
SALIENT FEATURES :
a Power line lter with Fuse is incorporated in the input of the power supply to protect the equipment from High Energy Surgeand Electrical Fast Transient.
a High Scanning Speed
a Remote Indication & Data Acquisition facility with burden upto 600 ohms.
a Optional RS-485 MODBUS RTU Communication
ML :2242
SPECIFICATIONS Model 2241B Model 2242
Temperature Sensorinput
RTD (Pt-100 DIN 43760) K Type thermocouples
No. of Sensor inputs Four, Eight & Twelve Three
No. of Set-points Three (Fan, Alarm and Trip) Four (Alarm, Trip, Fan1,Fan2)
Range 00C -3000C 00C 2500C
Resolution 0.10C 10C
Accuracy 10C 0.8%, one count undernormal conditions.
Display Speed User Settable (1-99 Seconds) 5 Seconds
Display Six Nos. 0.5 Seven Segment LEDs Four nos 0.5 Seven Seg-ment LEDs
Auxiliary Supply Voltage 90-260 V AC/DC 0-20V AC or 0-240V AC
Output Analogue output DC 4-20mA(Maximum burden 600 Ohms)
Analogue O/P DC0-1mA (10000 Ohms)4-20mA(600 Ohmsburden)
Communication Isolated RS-485 MODBUS RTUCommunication (Optional).
RS-485 & RS-232Communication
Contact Rating @Resistive Load
5A @ 220 VAC / 5A @ 30 DC Alarm & Trip 10A@120VAC & 8A@240 VAC, Fan1& Fan2 30A@120/240VAC
Power Consumption 5 Watts 8 Watts
Weight 2Kgs. Approx without packing box 2kgs Approx. withoutpacking box
Enclosure Aluminium Pressure Diecastingenclosure, powder coated all sideswith acrylic viewing window, IP-55
Panel Mount thru CutoutIndoor Mounting only
Operating conditions Temp:-300C to 700C Temp : -300C to 550C
Electronic TemperatureControllers
Model: 2241B
1. Cold and Dry Test : -30C to +70C
2. Vibration Test : Amplitude 1mm,frequency 50Hz, 1Hr / X,Y,Z axis
Model: 2242
1. Shock Test : 11ms/15g Procedure as per the
IS: 13779 (12 shots)2. Vibration Test : Amplitude 0.5mm,
Frequency 05 to 50Hz,02 sweeps / X,Y,Z axis
Type Tested For
ELECTRONIC
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
28/34
www.precimeasure.com
SPECIFICATIONS
Temperature Sensor input RTD (PT-100 DIN 43760)
No. of Sensor inputs one
No. of Set-points Two (Alarm,Trip)
Range 00C 2000C (Other Ranges on Request)
Resolution 10C
Accuracy 1%
Display Speed -
Display Three nos 0.5 Seven Segment LEDs
Auxiliary Supply Voltage 90-260V AC/DC (Other voltages on Request)
Output Analogue output DC 4-20mA (Maximum burden 600 Ohms)
Communication -
Contact Rating @ Resistive Load 5A@220 VAC / 5A@30 VDC
Power Consumption 2 Watts
Weight 0.5kgs Approx. without packing box.
Enclosure 96 Sq mm ABS Box Enclosure Panel Mount through Cutout,
IP-20Operating conditions Temp : 00C to 600C
SPECIFICATIONS
Temperature Sensor input RTD (PT-100 DIN 43760)
No. of Sensor inputs Four
No. of Set-points Three (Fan, Alarm and Trip)
Range -20 to+3000C / 0 - 3000C
Resolution 10C
Accuracy 20C
Display Speed User Settable (1- 30 Seconds)
Display 4 Nos. 0.5 Seven Segment LEDs
Auxiliary Supply Voltage 90-260 V AC/DC
Output Analogue output DC 4-20mA (Maximum burden 600 Ohms)
Communication RS-485 MODBUS RTU Communication (Optional)
Contact Rating @ Resistive Load 5A @ 220 VAC / 5A @ 30 VDC
Power Consumption 5 Watts
Weight 0.5Kgs Approx without packing
Enclosure 96 Sq mm ABS Box Enclosure Panel Mount through Cutout,IP-20
Operating conditions Temp: 00C to 600C
ML : 2253
ML : 2244T3
MODEL 2244T3 & 2253 WINDING TEMPERATURE INDICATOR / CONTROLLER FOR DRY TYPE TRANSFORMERS
APPLICATION :
MODEL 2244T3 & 2253 is designed for monitoring the temperatures of L.V. windings of the Dry-Type Transformer / Cast ResinTransformers. It will display winding temperatures and take necessary control action as per set and differential values programmedby the user. The protection system also records maximum temperatures and will display the same along with correspondingchannel number whenever relevant push button is pressed.
SALIENT FEATURES :
a Power line lter with Fuse is incorporated in the input of the power supply to protect the equipment from High Energy Surgeand Electrical Fast Transient.
a High Scanning Speed
a Remote Indication & Data Acquisition facility with burden upto 600 ohms.
a Optional RS-485 MODBUS RTU Communication
Electronic TemperatureControllers
Registered Office & Works :
No. 168/C Industrial Suburb,Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :
No. 27,28,30, Block-II, 2nd
Floor,Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
29/34
www.precimeasure.com
PRECIMEASURE Electronic TemperatureControllers
SPECIFICATION :
DESCRIPTION DETAILS
Temperature Sensor input RTD (Pt 100 DIN 43760)
No. of sensor inputs ONE
CT Sec Current Input 1.0A to 5.0A (User Selectable)
Temperature Rise 10C to 450C (User Selectable)
No. of Set-points OTI Two Relays for Alarm and Trip (1C/O SPDT Relay
contacts)No. of Set-points WTI Four Relays for Alarm, Trip, Fan 1 and Fan 2
(1C/O SPDT Relay contacts)
Contact Rating 5A @ 220 VAC / 5A @ 30 VDC Resistive Load
Range 0-1500C
Resolution 0.10C
Accuracy 10C
Display 0.5 Seven Segment LED Display
Auxiliary Supply Voltage 90-260 V AC/DC
Signal Outputs Two analogue Outputs (4-20mA Suitable for 600Ohms Burdon) Each 1 No.
Power Consumption 5 Watts (Max.)
Weight 2 Kgs Approx. without packing
Enclosure Aluminium Pressure Die Casting enclosure,powder coated with acrylic viewing window, IP-55
Communication RS-485 MODBUS RTU (Optional)
Operating Temperature -300C to 700C
MODEL 2243A OTI / WTI TEMPERATURE INDICATOR / CONTROLLER
APPLICATION :
This scheme is used to Indicate Oil & Winding Temperature of the oil immersed transformers. Relays are provided for Alarm, Trip
and Cooler Duties, are operated as per the set value. 4-20mA DC signal outputs are provided separately for OTI & WTI for RemoteIndication or SCADA Purpose. The System has the facility to store the maximum temperature attained.
SCHEME CONSISTS OF :1. PT -100 Sensor 1 No. 2. Electronic Temperature Controller 1 No. 3. Thermometer Pocket 1 No. (Optional)
ML : 2243A
ML : 2246
Model: 2243A
1. Cold and Dry Test : -30C to +70C
2. Vibration Test : Amplitude 1mm,
frequency 50Hz, 1Hr / X,Y,Z axis
Type Tested For
MODEL 2246 TAP POSITION INDICATOR
SPECIFICATIONS MODEL 2246
Signal Input Resistance (1Kohms per step)
Range 1-39 Position (User settable)
Display 3 nos. 0.5 7 Segment LEDS
Auxiliary Supply Voltage 90-260 V AC/DC
Out put Four sets of 4-20 mA DC ( MaximumBurndon 600 Ohms)
Communication RS - 485 Modbus RTU Communication(Optional)
Power Consumption 5 Watts (Max.)
Weight 0.5Kgs Approx. without packing
Enclosure 96 sq mm ABS Box Enclousure PanelMount through cutout IP-20
Operating Temperature 00C to 600C
ELECTRONIC
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
30/34
www.precimeasure.com
Electronic TemperatureControllers
ELECTRONIC TYPE
MODEL 2220-R1 & 2220-R2 TEMPERATURE INDICATOR
APPLICATION : PRECIMEASURE Electronic Instruments are designed to indicatethe Top Oil Temperature / Winding Temperature of the oil-immersed transformersin remote control room. This scheme has 2 Nos of 4-20 mA DC Signal outputsproportional to the temperature range. Signal OUTPUT 1 is connected to anindicator for indicating temperature at remote and OUTPUT 2 can be connectedto Recorder or Data Acquisition System.
SCHEME CONSISTS OF :
1. PT -100 Sensor 1 No.
2. Current Converter Unit 1 No.
3. Remote Indicator 1 No.
4. Thermometer Pocket 1 No. (Optional)
SPECIFICATIONS :
SL. DESCRIPTION MODEL 2220 R1 MODEL 2220 R2
1 PT 100 SENSOR ASSEMBLY
a. Element : Simplex, 3 wire system / Duplex, 6 Wire System
b. Tolerance : DIN 43760, Class B
2 CURRENT CONVERTER UNIT WITH POWER SUPPLY UNIT
a Signal Input : PT 100 RTD, Simplex 3 wire
b Auxiliary Supply : 90 260V AC/DC
c Signal Outputs : 4 20mA DC corresponding to temperature range
d Burden on Output Signal : 600 Ohms maximum including loop resistance
e Accuracy of Signal Output : 1% of F.S.D.
f Degree of protection of enclosure IP-55 IP-40
g Casing Aluminium Casting. ABS, DIN Enclosure Box.
3 REMOTE INDICATOR
a Type : 4 digits, 0.5 Seven Segment LEDs
b Auxiliary Supply : 90 260V AC/DC
c Temperature indicator range : 0-1500C (Other ranges on request)
d Resolution : 0.10C
e Degree of protection of enclosure : IP-20
Model: 2220-R1& 2220-R21. 2220-R1, Protection class :
IP55 as per IEC 60529 CAT 2.
2. 2220-R2, Protection class:IP40 as per IEC 60529 CAT 2
3.Cold and Dry Teast :-30C to +70C
4.Vibration Test :Amplitude 1mm, frequency50Hz,1Hr / X,Y,Z axis
5. EMI / EMC Test :a) Electrostatic Discharge
Immunity Test as perIEC61000-4-2, 2001
b) Electrical Fast TransientImmunity Test as perIEC61000-4-4, 2004
c) High Energy SurgeImmunity Test as perIEC61000-45, 2005
Type Tested For
Registered Office & Works :
No. 168/C Industrial Suburb,Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :
No. 27,28,30, Block-II, 2nd
Floor,Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
31/34
www.precimeasure.com
PRECIMEASURE
Ordering Information
Model 1080 - 4" & 6"
MODEL: 1090SIZE: 1 B.S.P MALE
SPECIFICATIONS :
Liquid in Tank Transformer oil to IS 335 and or any other Oil
Working Temperature -30 to 100C of oil
Working Pressure 0 to 4 Kg / Cm2
Working Environment Indoor or Outdoor
INDICATION :
Dial size 4" & 6" RoundColor Black marking on white background orany other combination as required. Standard
Red Line Indication for Min. to Empty LevelAngular Sweep 300
FLOAT (SENSOR) AND ARM :
Material Float :Polyurethane Foam/Brass
Float Arm : Brass
Float-Arm Length Fixed Length as given by Customer
Travel Max. 45 Below & Above from the centre
Margin Leave Min. 40 mm beyond lower & higherlimit markings to avoid striking of oat tobottom & top of conservator.
SWITCH :
Type Micro switchContact Rating 5A @ 240V AC, 0.25A 220V DC
MAGNETIC OIL LEVELGUAGE
APPLICATION:
Magnetic Oil Level Gauge (MOG) is used to Measure Oil Level of oil lled Transformers & Oil lled Tanks.
Model No 1080/4
Float Arm Length
Conservator Diameter
Mounting Vertical/Inclined
If Inclined Mention Angle
And other Specications if any
Type Tested For
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
PRESSURE RELIEF DEVICE
APPLICATION:PRD is a safety device for the distribution transformer up to 5000KVA, OLTC and other similarequipments. This PRD is used to prevent heavy damages of the tank in case of sudden rise ofinternal pressure.
OPERATING PRESSURE :Operating Pressure range available from 0.2 to 0.7 kg/sq.cm with tolerance0.05 kg/sq.cm.
Safe spring loaded design that does not require external power supply for operation
Positive downward directional ow limits horizontal spraying of hot oil on adjacent equipment
Large diameter top cover with improved operating force providing better protection
Transport safety clip to prevent oil spillage during transportation of oil lled transformers
Available in brass or Zamak body construction
General Features
OTHERS
-
8/9/2019 OIL LEVEL INDICATOR TRIP CONTACT
32/34www.precimeasure.com
PRECIMEASUREBEARING / AIR
TEMPERATURE INDICATOR /CONTROLLER
APPLICATION :
This Instruments is used for monitoring and controlling the Bearing/ Air Temperature of the Motor and Generators
Model 1006 - BTD/ATD
SPECIFICATIONS :
Temperature Range 0-150C (Other Rangeson request)
Dial Size 150mm (6") Round
Dial Angular Sweep 270
Dial Graduations 2C per Division
Accuracy Class 1.5% of F.S.D
Max. No. of Switches 2
Switch Setting 15% to 85%
Switch Contact Rating 5A at 250 V AC & 0.5Aat 220V DC
Switch Differential 3 C 2 C (Fixed)
Accuracy of Switch Setting 2.5C of Set Value
Max. Capillary Length Up to 15 Meters
Mounting Flush / Projection
1. Protection class : IP55 as per IEC 60529 CAT 2.
2. Vibration Test : Amplitude 1mm, frequency 50Hz,
1Hr / X,Y,Z axis
3. Micro Switch rating Test :
5A @ 250V AC &0.5A @ 220V DC
Type Tested For
Registered Office & Works :
No. 168/C Industrial Suburb,Peenya 3rd Phase, Bangalore - 560058. INDIA
Phone : + 91-80-4260 2705 / 08
Fax : + 91-80-4155 2205
E-Mail : [email protected]
Branch Office & Works :
No. 27,28,30, Block-II, 2nd
Floor,Sidco Electronics Complex, Guindy, Chennai - 600032. INDIA
Phone : + 91-44-2250 0191 / 2250 0175
Fax : + 91-44-2250 0175
E-Mail : [email protected]
PRECIMEASURE CONTROLS PVT. LTD.
Western India Region Office :Mobile : 09377561070
E-Mail : [email protected]
PORTABLE OIL BATH
Model HOB -180For OTI & WTI Caliberation
DISPLAY SPECIFICATION
Range Ambient +5C To 180C
Display Dual 4 Digit Display
Disply Resolution 0.1C
Temp-Setting With Push Button Data Entry
GENERAL SPECIFICATION
System Acuracy Better Then 0.5% Of Reading Or 0.5%C(Which Ever Is Higher)
Stability Better Then 0.5%C
Set Point Archive Time Approx. 30 Minutes
Stabilization Time Approx. 20 Minutes After Reaching Set Value
ELECTRICAL SPECIFICATION
Power Consumption 300 Watts Approx.
Power Supply 230Vac, 50Hz
PHYSICAL SPECIFICATIONDimensions 6 (W) X 14 (H) X 9(L)
Weight 5.5 Kgs Approx.
Heating Media Silicon Oil / Transformer Oil
Oil Volume 1.5 Ltr Approx
Well Depth 160 mm
Accessories Drain Locking O Ring
Stirring By Mechanical Stirrer Of Ig Motor
-