Asset: CLEVELAND AF NO. 2 - QUEENS, 18-08 WILLOUGHBY AVENUE, New York, 11385 Inspection Id Inspection Type Time In Last Edited SA : Q488 Architectural - Senior 2019-11-20 12:35 PM 2019-12-02 2:12 PM AA : Q488 Architectural - Associate 2019-11-20 12:11 PM 2020-07-22 4:49 PM Asset Data Question Answer Was the building fully accessible for inspection Yes Principal(s) Information Principal Name Marc Pascente Organization Grover Cleveland High School - Queens Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal had no comments regarding the physical condition of the Athletic Field at this time. Principal Name Annette Beale Organization The Riverview School - Queens Did you meet with this Principal? No Did this Principal provide feedback? No Custodian John Sullivan Fireman Greg Bianchi Building Square Footage 5,000 Comments on the Area 282,000 SF Site Area; 156,500 SF Playing Surfaces Comments on the Stories (Floors) plus Basements 1 (No Basement) Comments on the Number of Classrooms 0 Comments on the Year Built 1967 Student Population 1732 Staff Population 2 Weather Fair Facade Photo Field House - West View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2019 - 2020 Q488 PB/A&W Print Date: 9/14/2020 Page 1 of 29

Transcript of NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected...

Page 1: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Asset: CLEVELAND AF NO. 2 - QUEENS, 18-08 WILLOUGHBY AVENUE, New York, 11385

Inspection Id Inspection Type Time In Last Edited

SA : Q488 Architectural - Senior 2019-11-20 12:35 PM 2019-12-02 2:12 PM

AA : Q488 Architectural - Associate 2019-11-20 12:11 PM 2020-07-22 4:49 PM

Asset Data

Question Answer

Was the building fully accessible for inspection Yes

Principal(s) Information

Principal Name Marc Pascente

Organization Grover Cleveland High School - Queens

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal had no comments regarding the physical condition of theAthletic Field at this time.

Principal Name Annette Beale

Organization The Riverview School - Queens

Did you meet with this Principal? No

Did this Principal provide feedback? No

Custodian John Sullivan

Fireman Greg Bianchi

Building Square Footage 5,000

Comments on the Area 282,000 SF Site Area; 156,500 SF Playing Surfaces

Comments on the Stories (Floors) plus Basements 1 (No Basement)

Comments on the Number of Classrooms 0

Comments on the Year Built 1967

Student Population 1732

Staff Population 2

Weather Fair

Facade Photo

Field House - West View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 1 of 29

Page 2: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Main Entrance Photo

Facade A - Field House

Roof Photo

Roof 1 - Southeast View

Have any Systems/Major Building Components been upgraded? Yes

Systems: Limited Roofing, Flashing and Roof Drain repairs

Year: 2018

Systems: Tennis Courts resurfaced

Year: 2017

Systems: Limited Roofing and Leader/Gutter repairs

Year: 2016

Systems: New Artificial Turf at Soccer Field; new Running TrackSurface

Year: 2015

Systems: Athletic Field restoration project including concreteRetaining Wall rebuilt, limited Artificial Turf repairs, andField House Roofing and Masonry repairs

Year: 2010

Systems: New Roofing, Windows and Exterior Guards

Year: 1984

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? No

Priority Condition

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 2 of 29

Page 3: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? No

Do any of the following spaces exist? Classroom, Art Room, Auditorium, Cafeteria,Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

No

Are ALL occupied spaces on the accessible route? Yes

Are there accessible toilets in the building? Yes

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings No No

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies Yes

Interior Elevators No

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms No

Auditorium No

Cafeteria No

Classrooms No

Computer Rooms No

Gymnasium No

Library No

Main Office No

Multi-purpose Room No

Nurse's Room No

Pool No

Science Lab No

Toilet Rooms (Boys) 1st Floor Yes Yes

Toilet Rooms (Girls) 1st Floor Yes Yes

Toilet Rooms (Staff) 1st Floor Yes Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 3 of 29

Page 4: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Does not Exist

AWNINGS AND CANOPIES Inspected

Condition 3 - Fair

Deficiency CONCRETE: MAJOR CRACKS/SPALLING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 4 of 29

Page 5: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

EXTERIOR

AWNINGS AND CANOPIES

Deficiency Photo1

Facade A

Violations No violations recorded.

CHIMNEY Inspected

Material Type(s) Masonry

Condition 2 - Between Good and Fair

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 - CH

Violations No violations recorded.

Deficiency BRICK: MINOR CRACKS AND SPALLING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 5 of 29

Page 6: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

EXTERIOR

CHIMNEY

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1 - CH

Violations No violations recorded.

COPING Does not Exist

CORNICE Does not Exist

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 5 - Poor

Deficiency METAL: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION

Roof Plan reference

Deficiency Quantity 6

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 6 of 29

Page 7: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Deficiency Photo1

Facade C - Exit 6

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 4,000

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 3 - Fair

Instance Quantity 4,000

Instance Quantity Uom S.F.

Deficiency BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDINGCORNERS

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 7 of 29

Page 8: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REMOVE AND REBUILD

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Corner of Facades A and D

Violations No violations recorded.

Deficiency BRICK: MINOR CRACKS AND SPALLING

Roof Plan reference

Elevation

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action RESTITCH

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 8 of 29

Page 9: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

EXTERIOR

EXTERIOR WALLS

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

EXTERIOR SOFFITS Inspected

Condition 3 - Fair

Deficiency STUCCO/PLASTER: MAJOR CRACKS/SPALLING

Roof Plan reference

Elevation

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 9 of 29

Page 10: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

EXTERIOR

EXTERIOR SOFFITS Inspected

Deficiency Photo1

Facade A

Violations No violations recorded.

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Does not Exist

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 5,000

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Does not Exist

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOFING Inspected

InspectedInstance on Modified Bitumen: Roof 1

Instance Condition 4 - Between Fair and Poor

Instance Quantity 5,000

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 1984

Source of Installation Custodial Staff

Deficiency MODIFIED BITUMEN: ROOFING: DELAMINATION

Roof Plan reference

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 10 of 29

Page 11: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Center of Roof

Violations No violations recorded.

Deficiency MODIFIED BITUMEN: ROOFING: BEYOND USEFUL LIFE

Deficiency Location/Instance Modified Bitumen: Roof 1

Deficiency Quantity 5,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

ROOFING DRAINS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Specialties Inspected

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Inspected

Material Type(s) Plastic

Condition 2 - Between Good and Fair

Deficiency DAMAGED FLASHING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 11 of 29

Page 12: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

EXTERIOR

ROOF

Specialties

SKYLIGHT/ROOF VENT

Deficiency Photo1

Roof 1

Violations No violations recorded.

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Does not Exist

RAILINGS Does not Exist

STAIRS/RAMPS Inspected

Condition 3 - Fair

Deficiency STONE: CRACKS, SPALLING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade B - Exit 3

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 800

Replacement Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 12 of 29

Page 13: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

EXTERIOR

WINDOWS

EXTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Other: All Facades

Instance Condition 4 - Between Fair and Poor

Instance Quantity 800

Instance Quantity Uom S.F.

Installation Year 1984

Source of Installation Custodial Staff

Deficiency ALUMINUM - OTHER: BROKEN PANE

Roof Plan reference

Elevation

Deficiency Quantity 90

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 13 of 29

Page 14: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

EXTERIOR

WINDOWS

WINDOWS

Facade B

Violations No violations recorded.

Deficiency ALUMINUM - OTHER: BEYOND USEFUL LIFE

Deficiency Location/Instance Aluminum - Other: All Facades

Deficiency Quantity 800

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

INTERIOR Inspected

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FLOOR STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Does not Exist

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Near Exits 5,6

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 14 of 29

Page 15: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo1

Near Exit 6

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GLAZED BLOCK: CRACKS/SPALLING

Deficiency Location/Instance Near Exit 6

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Exit 6

Violations No violations recorded.

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LOCKER ROOM Inspected

InspectedInstance on 1st Floor - Boys (217 Lockers)

Alternative use No

InspectedInstance on 1st Floor - Girls (68 Lockers)

Alternative use No

Ceiling

InspectedInstance on 1st Floor - Boys (217 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on 1st Floor - Girls (68 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 15 of 29

Page 16: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

INTERIOR

LOCKER ROOM

Door(s)

InspectedInstance on 1st Floor - Boys (217 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on 1st Floor - Girls (68 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 1st Floor - Boys (217 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on 1st Floor - Girls (68 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Locker Room Lockers

InspectedInstance on 1st Floor - Boys (217 Lockers)

Condition 2 - Between Good and Fair

Deficiency DAMAGED UNITS

Deficiency Location/Instance Locker 17

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Locker 17

Violations No violations recorded.

Walls

InspectedInstance on 1st Floor - Girls (68 Lockers)

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Near the window

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 16 of 29

Page 17: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

INTERIOR

LOCKER ROOM

Walls

Deficiency Photo1

Near the window

Violations No violations recorded.

SHOWER ROOM Inspected

InspectedInstance on 1st Floor - Boys

Alternative use No

InspectedInstance on 1st Floor - Girls

Alternative use No

Ceiling

InspectedInstance on 1st Floor - Boys

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Not RequiredInstance on 1st Floor - Girls

Door(s)

Does not ExistInstance on 1st Floor - Boys

Does not ExistInstance on 1st Floor - Girls

Floor Finish

InspectedInstance on 1st Floor - Boys

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Not RequiredInstance on 1st Floor - Girls

Walls

InspectedInstance on 1st Floor - Boys

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Not RequiredInstance on 1st Floor - Girls

STAIRS/RAMPS: INTERIOR Does not Exist

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 3 - Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Visitors Women

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 17 of 29

Page 18: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

INTERIOR

TOILET ROOMS - STAFF

Ceiling

Deficiency Photo1

Visitors Women

Violations No violations recorded.

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 3 - Fair

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Visitors Men

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Visitors Men

Violations No violations recorded.

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GLAZED BLOCK: CRACKS/SPALLING

Deficiency Location/Instance Visitors Men

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 18 of 29

Page 19: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

INTERIOR

TOILET ROOMS - STAFF

Walls

Deficiency Photo1

Visitors Men

Violations No violations recorded.

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Does not Exist

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Girls

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Girls

Violations No violations recorded.

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ATHLETIC FIELDS Inspected

PLAYING SURFACE Inspected

Synthetic Turf Field exists? Year of Installation

Yes 2,015

Replacement Quantity 156,500

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 19 of 29

Page 20: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

ATHLETIC FIELDS

PLAYING SURFACE

Replacement Uom S.F.

InspectedInstance on Handball Courts

Instance Condition 2 - Between Good and Fair

Instance Quantity 6,500

Instance Quantity Uom S.F.

Deficiency No deficiencies recorded

InspectedInstance on Running Track

Instance Condition 1 - Good

Instance Quantity 42,000

Instance Quantity Uom S.F.

Deficiency No deficiencies recorded

InspectedInstance on Soccer Field

Instance Condition 1 - Good

Instance Quantity 79,000

Instance Quantity Uom S.F.

Deficiency No deficiencies recorded

InspectedInstance on Tennis Courts

Instance Condition 3 - Fair

Instance Quantity 29,000

Instance Quantity Uom S.F.

Deficiency ASPHALT: DAMAGED/DETERIORATED

Deficiency Location/Instance Tennis Courts 1 and 2

Roof Plan reference

Deficiency Quantity 600

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Tennis Court 1

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 20 of 29

Page 21: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

ATHLETIC FIELDS

FIXED EQUIPMENT Inspected

Basketball Backboard Does not Exist

Basketball Hoops Does not Exist

Basketball Posts Does not Exist

Football Goal Posts Does not Exist

Tennis Net Posts Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SEATING Inspected

Benches Inspected

Concrete Does not Exist

Metal/Wood/Plastic Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Bleachers Inspected

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency CRACKS/SPALLING - MAJOR

Deficiency Location/Instance 5th row Center

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

5th row Center

Violations No violations recorded.

Metal/Wood/Plastic Does not Exist

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Concrete Covering Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 21 of 29

Page 22: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

SITE

Drainage System for Soil Inspected

Catch Basins/Manhole - Surrounded by Soil Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Soil Covering Does not Exist

DRINKING FOUNTAINS Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

FENCES Inspected

Condition 4 - Between Fair and Poor

Deficiency CHAIN LINK: DAMAGED/DETERIORATED

Deficiency Location/Instance South side

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

South side

Violations No violations recorded.

Deficiency CHAIN LINK: RUST - MAJOR

Deficiency Location/Instance Near Bleachers north Entrance, Tennis Court 2, near Field House

Deficiency Quantity 700

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Bleachers north Entrance

Violations No violations recorded.

Deficiency WROUGHT IRON: DAMAGED/DETERIORATED

Deficiency Location/Instance Dekalb Avenue

Deficiency Quantity 80

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 22 of 29

Page 23: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

SITE

FENCES

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Dekalb Avenue

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Parking Lot, Dekalb Avenue Driveway

Deficiency Quantity 400

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Dekalb Avenue Driveway

Violations No violations recorded.

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Dekalb Avenue Driveway

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 23 of 29

Page 24: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

SITE

PAVING

Student Non-Use

Concrete

Deficiency Photo1

Dekalb Avenue Driveway

Violations No violations recorded.

Pavers Does not Exist

Student Use Inspected

Gravel Exists? No

Asphalt Does not Exist

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Inspected

Condition 2 - Between Good and Fair

Deficiency HEAVING

Deficiency Location/Instance Near the flagpole

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near the flagpole

Violations No violations recorded.

Site Sidewalks & Walkways Inspected

Asphalt Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance East of track

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 24 of 29

Page 25: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

SITE

PAVING

Site Sidewalks & Walkways

Asphalt

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

East of track

Violations No violations recorded.

Concrete Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Near Field House

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Field House

Violations No violations recorded.

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 4 - Between Fair and Poor

Deficiency HEAVING

Deficiency Location/Instance Willoughby Avenue

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 25 of 29

Page 26: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency Photo1

Willoughby Avenue

Violations No violations recorded.

Deficiency DAMAGED CURBS

Deficiency Location/Instance Dekalb Avenue, Willoughby Avenue

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Dekalb Avenue

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Dekalb Avenue, Willoughby Avenue

Deficiency Quantity 800

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Dekalb Avenue

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 26 of 29

Page 27: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

SITE

PAVING Inspected

DOT Sidewalk

Concrete Inspected

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Does not Exist

RETAINING WALLS Inspected

Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?

Yes

Condition 3 - Fair

Deficiency CAST IN PLACE CONCRETE: DETERIORATED EXPANSIONJOINT

Deficiency Location/Instance Handball Court

Deficiency Quantity 10

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Handball Court

Violations No violations recorded.

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance Near Tennis Courts, Handball Court, near Field House Exit 4, Southside

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Tennis Courts

Violations No violations recorded.

SEATING Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 27 of 29

Page 28: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

SITE

SEATING

Benches Inspected

Concrete Does not Exist

Metal/Wood/Plastic Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SITE WALLS (NOT RETAINING WALLS) Inspected

Condition 3 - Fair

Deficiency BRICK: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance Dekalb Avenue

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Dekalb Avenue

Violations No violations recorded.

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance Handball Court

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Handball Court

Violations No violations recorded.

STAIRS/RAMPS: EXTERIOR Inspected

Railings Inspected

Condition 4 - Between Fair and Poor

Deficiency MISSING

Deficiency Location/Instance East,west of Bleachers

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 28 of 29

Page 29: NYC Department of EducationSK Violations No violations recorded. STAIRS/RAMPS: EXTERIOR Inspected RAILINGS Inspected Condition 2 - Between Good and Fair Deficiency No deficiencies

Question Response

SITE

STAIRS/RAMPS: EXTERIOR

Railings

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

East of Bleachers

Violations No violations recorded.

Site Cheek/flank Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs/ramps Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2019 - 2020

Q488

PB/A&W Print Date: 9/14/2020Page 29 of 29