NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity...

16
Asset: ADULT BASIC EDUCATION - QUEENS, 27-35 JACKSON AVENUE, New York, 11101 Inspection Id Inspection Type Time In Last Edited SA : Q972 Architectural - Senior 2018-12-21 7:37 AM 2019-06-06 3:19 PM AA : Q972 Architectural - Associate 2018-12-21 9:01 AM 2019-03-14 4:32 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment Facades B, C, and D, and Roof Structure were not accessible for visual inspection. Principal(s) Information Principal Name Mariza Cerff Organization Pre-K Center @ 27-35 Jackson Avenue - Queens Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal's comments are as follows: 1. There are leaks into classrooms and offices. 2. Room 236 is consistently too cold. Principal Name Christine Britton Organization P.S. 384 - Queens Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal commented that there are no security cameras at exits and exit stairwells. Principal Name Olga Nelson Organization Adult Basic Education Center - Queens Did you meet with this Principal? No Did this Principal provide feedback? No Custodian Was not present Fireman Angel Torres Building Square Footage 38000 Comments on the Area 52,000sf Building (38,000sf leased) Comments on the Stories (Floors) plus Basements 4+B Comments on the Number of Classrooms 23 Comments on the Year Built 1965 Student Population 343 Staff Population 64 Weather Fair Facade Photo NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2018 - 2019 Q972 PB/A&W Print Date: 6/21/2019 Page 1 of 16

Transcript of NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity...

Page 1: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Asset: ADULT BASIC EDUCATION - QUEENS, 27-35 JACKSON AVENUE, New York, 11101

Inspection Id Inspection Type Time In Last Edited

SA : Q972 Architectural - Senior 2018-12-21 7:37 AM 2019-06-06 3:19 PM

AA : Q972 Architectural - Associate 2018-12-21 9:01 AM 2019-03-14 4:32 PM

Asset Data

Question Answer

Was the building fully accessible for inspection No

Inspection Access Comment Facades B, C, and D, and Roof Structure were not accessible for visualinspection.

Principal(s) Information

Principal Name Mariza Cerff

Organization Pre-K Center @ 27-35 Jackson Avenue - Queens

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal's comments are as follows: 1. There are leaks intoclassrooms and offices. 2. Room 236 is consistently too cold.

Principal Name Christine Britton

Organization P.S. 384 - Queens

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal commented that there are no security cameras at exitsand exit stairwells.

Principal Name Olga Nelson

Organization Adult Basic Education Center - Queens

Did you meet with this Principal? No

Did this Principal provide feedback? No

Custodian Was not present

Fireman Angel Torres

Building Square Footage 38000

Comments on the Area 52,000sf Building (38,000sf leased)

Comments on the Stories (Floors) plus Basements 4+B

Comments on the Number of Classrooms 23

Comments on the Year Built 1965

Student Population 343

Staff Population 64

Weather Fair

Facade Photo

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 1 of 16

Page 2: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Jackson Avenue - Northwest View

Main Entrance Photo

Facade A - Jackson Avenue

Roof Photo

Roof 1 - View

Have any Systems/Major Building Components been upgraded? Yes

Systems: Renovation of Leased Space to Pre-K Center

Year: 2017

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? Yes

Year Leased 2013

Inspection Partial Inspection

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 2 of 16

Page 3: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes

If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings No No

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies Yes

Interior Elevators Yes Yes

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms No

Auditorium No

Cafeteria No

Classrooms 1st and 2nd Floors Yes Yes

Computer Rooms Rooms 314, 316, 318, 320, and 322 Yes Yes

Gymnasium No

Library No

Main Office Rooms 218, 236 Yes Yes

Multi-purpose Room Rooms 208, 216 Yes Yes No Yes

Nurse's Room Room 236 Yes Yes

Pool No

Science Lab No

Toilet Rooms (Boys) 2nd Floor Yes Yes

Toilet Rooms (Girls) 2nd Floor Yes Yes

Toilet Rooms (Staff) 2nd and 3rd Floors Yes Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 3 of 16

Page 4: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Does not Exist

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Not Required

COPING Inspected

Condition 2 - Between Good and Fair

Deficiency TERRA COTTA: CRACKED/BROKEN PIECES

Roof Plan reference

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action REPLACE-IN-KIND

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 4 of 16

Page 5: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

EXTERIOR

COPING

Roof 1

Violations No violations recorded.

CORNICE Does not Exist

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

DOOR HARDWARE Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 6,500

Replacement Uom S.F.

InspectedInstance on Facades A and C1

Instance Condition 3 - Fair

Instance Quantity 2,200

Instance Quantity Uom S.F.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Elevation

Deficiency Quantity 220

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 5 of 16

Page 6: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo1

Facade A

Violations No violations recorded.

InaccessibleInstance on Facades B, C, D

Instance Quantity 4,300

Instance Quantity Uom S.F.

EXTERIOR SOFFITS Does not Exist

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 800

Replacement Uom C.F.

InspectedInstance on Roof 1

Instance Condition 3 - Fair

Instance Quantity 800

Instance Quantity Uom C.F.

Deficiency BRICK: MINOR CRACKS, SPALLING

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 6 of 16

Page 7: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

EXTERIOR

PARAPETS

Deficiency Photo1

Roof 1

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 11,000

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Does not Exist

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Does not Exist

ROOF BARRIER Does not Exist

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 7 of 16

Page 8: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

InspectedInstance on Modified Bitumen: Roof 1

Instance Condition 3 - Fair

Instance Quantity 11,000

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

Yes

Installation Year 2000

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

ROOFING DRAINS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Specialties Inspected

BULKHEAD/PENTHOUSE Not Required

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Inspected

Condition 3 - Fair

Deficiency HEIGHT LESS THAN 18"

Roof Plan reference

Deficiency Quantity 40

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 1

Deficiency Photo1

Roof 1

Violations No violations recorded.

Deficiency MINOR RUSTING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 8 of 16

Page 9: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

EXTERIOR

ROOF

Specialties

DUNNAGE STEEL

Roof Plan reference

Deficiency Quantity 40

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

SKYLIGHT/ROOF VENT Does not Exist

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Does not Exist

WINDOWS Inspected

Replacement Quantity 1,300

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Other: Facades A, C, D

Instance Condition 3 - Fair

Instance Quantity 1,300

Instance Quantity Uom S.F.

Installation Year 2017

Source of Installation Custodial Staff

Deficiency ALUMINUM - OTHER: AIR/WATER INFILTRATION

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 9 of 16

Page 10: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

EXTERIOR

WINDOWS

WINDOWS

Elevation

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action REPLACE TRIM, SILLS OR WEATHERSTRIPPING

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A - Room 320

Violations No violations recorded.

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 3 - Fair

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING

Deficiency Location/Instance Basement

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 10 of 16

Page 11: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS

Fire Alarm Service Room

Violations No violations recorded.

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED MASONRYFIREPROOFING

Deficiency Location/Instance Stair B/3

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Stair B/3

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Basement

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Basement Corridor

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 3 - Fair

Deficiency CONCRETE: WATER INFILTRATION IN ELECTRICAL PANELROOM

Deficiency Location/Instance Electrical Panel Room

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 11 of 16

Page 12: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Electrical Panel Room

Violations No violations recorded.

ROOF STRUCTURE Inaccessible

VAULTS-BUNKERS Does not Exist

AUDITORIUM Does not Exist

CAFETERIA Does not Exist

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Room 226

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 226

Violations No violations recorded.

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 12 of 16

Page 13: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DETERIORATED

Deficiency Location/Instance Corridor near Room 319, 228

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 319

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Does not Exist

INTERIOR DOOR HARDWARE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Does not Exist

KITCHEN Inspected

InspectedInstance on 2nd Floor

Ceiling

InspectedInstance on 2nd Floor

Condition 1 - Good

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 2nd Floor

Condition 1 - Good

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 2nd Floor

Condition 1 - Good

Deficiency No deficiencies recorded

Walls

InspectedInstance on 2nd Floor

Condition 1 - Good

Deficiency No deficiencies recorded

LIBRARY Does not Exist

LOCKER ROOM Does not Exist

MULTI-PURPOSE ROOM Inspected

InspectedInstance on Rooms 208, 216

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 13 of 16

Page 14: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Ceiling

InspectedInstance on Rooms 208, 216

Condition 1 - Good

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Rooms 208, 216

Condition 1 - Good

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on Rooms 208, 216

Floor Finish

InspectedInstance on Rooms 208, 216

Condition 1 - Good

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on Rooms 208, 216

Stage

Does not ExistInstance on Rooms 208, 216

Walls

InspectedInstance on Rooms 208, 216

Condition 1 - Good

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on Rooms 208, 216

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Yes

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Partition Does not Exist

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 14 of 16

Page 15: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

INTERIOR

TOILET ROOMS - STAFF

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Does not Exist

Drainage System for Concrete Does not Exist

Drainage System for Soil Does not Exist

DRINKING FOUNTAINS Does not Exist

FENCES Does not Exist

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Does not Exist

Student Use Does not Exist

Site Sidewalks & Walkways Does not Exist

DOT Sidewalk Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 15 of 16

Page 16: NYC Department of Education · 2019-06-21 · Roof Plan reference Deficiency Quantity 100 Quantity Uom S.F. Potential Action REPOINT Urgency of Action PRIORITY 3 Purpose of Action

Question Response

SITE

PAVING

DOT Sidewalk

Asphalt Does not Exist

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Does not Exist

PLAYGROUNDS Does not Exist

PLAYING SURFACE Does not Exist

RETAINING WALLS Does not Exist

SEATING Does not Exist

SITE WALLS (NOT RETAINING WALLS) Does not Exist

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q972

PB/A&W Print Date: 6/21/2019Page 16 of 16