Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

73
Novec 1230 SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid

Transcript of Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Page 1: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Novec 1230™

SYSTEM DESIGN

3M™ Novec 1230™ Fire Protection Fluid

Page 2: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Design Concepts

•Total Flooding Fire Protection System– Must have an enclosure

– Agent mixes with atmosphere to protect

entire volume– No local application

– Agent mixing performed by nozzles

Page 3: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Design Concepts

•Enclosure Integrity

– Air leaks effectively sealed

– Door fan test is used to determine

whether or not integrity exists

– Procedure in Appendix C of NFPA 2001

– Must be performed on all new installations

Page 4: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Design Concepts

•Duration of Protection– “...(Extinguishing concentration) shall be

maintained for the specified period of time

to allow effective emergency action by

trained personnel.” -NFPA 2001, Section 5.6

– Hold time is typically 10 minutes, but not

standard– Refer to local AHJ

Page 5: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Design Concepts

•Discharge Time– Must be 10 seconds or less

– Rapid extinguishment reduces production of

by-products (HF)

– Per NFPA 2001 5.7.1.2.1

– Software will issue a warning for less

than 6 seconds

Page 6: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

HAZARD SURVEY AND ANALYSIS

Page 7: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Perform Hazard Survey

•Define Hazard:

– Enclosure boundaries

– Enclosure integrity exists?

– Fuels

– Hazard type (Class A, B, C or D)

– MSDS for chemicals present

Page 8: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Required Data

– Dimensions

– Ambient Temperature Range

– Min. and Max.

– Occupancy Requirements

– Normally occupied?

Page 9: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Determine Novec 1230 Suitability

•Novec 1230 is suitable for:

– Class A: Fires in ordinary combustibles

– Class B: Flammable Liquid Fires

– Class C: Fires involving energized

electrical equipment

Page 10: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Determine Novec 1230 Suitability

•Novec 1230 is NOT suitable for use with:– Deep seated fire hazards

– Metal fires per NFPA 2001, par. 1.4.2.2

– Certain chemicals capable of rapid oxidation in

the absence of air: gunpowder,

– Reactive metals: sodium, magnesium, etc.

– Metal hydrides

– Chemicals capable of undergoing autothermal

decomposition

Page 11: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Determine Novec 1230 Suitability

•Operating temperature range for Novec 1230 equipment is 32°F to 130°F

Page 12: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

AGENT QUANTITY

Page 13: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Extinguishing Concentration

•NFPA 2001 5.4.2

– Class A extinguishing concentration

determined as part of witness testing

– UL 2166

– Class B extinguishing concentrations

determined by cup burner test

– Appendix B

Page 14: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Minimum Design Concentration

•NFPA 2001 5.4.2– Class A design concentration

– EC x 1.2

– Class B design concentration– MCB x 1.3

– Class C design concentration must be at least

that for Class A

– Manual-Only systems design concentration– EC x 1.3

Page 15: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Minimum Design Concentration

•Determined by Hazard Analysis:

– Class A Hazard: 4.2% (Minimum)

– Class C Hazard: At least that of Class A:

4.2%

– Manual-Only systems: 4.6%

Page 16: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Minimum Design Concentration

•Determined by Hazard Analysis:

– Class B Hazard:

– Reference list in manual or

call Kidde

Page 17: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Minimum Design Concentration•Class B Reference list

Page 18: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Minimum Design Concentration

•If multiple fuels and/or classifications are present, highest applicable concentration is used

Page 19: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Minimum Design Quantity (MDQ)

Equation

-or-

Table

Page 20: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

•Dimensions taken during hazard analysis

•OK to subtract permanent volume reductions– Columns– Platforms

•Do NOT subtract for equipment and moveable objects!

Calculate Volume

Page 21: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Design Temperature

•To calculate agent quantity, use minimum expected ambient temperature

•Agent concentration is proportional to air temperature– Same quantity of agent will result in a low

concentration at low temperatures and a high concentration at high temperatures

Page 22: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

MDQ Calculation Example

•Enclosure is 10 ft. W x 10 ft. L x 10 ft. H

•Min Ambient Temperature = 70°F

•Class A Surface Fire Hazard

Page 23: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

MDQ Calculation Example

Volume = 1000 ft.3

s = 0.9856 + (0.002441 x 70°F) = 1.1565

W = (1000 ft.3 / 1.1565 ) x (4.2% / 100% - 4.2%) = 37.9 lb.

- or -Flooding Factor(4.2%, 70°F) = 0.0379 lb./ft.3

W = 1000 ft.3 x 0.0379 lb./ft. 3 = 37.9 lb.

Page 24: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

EXAMPLE PROBLEMS

Page 25: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Correct For Pressure Differentials

•Must correct if ±11% or more from normal

barometric pressure at sea level– Approximately ± 3000 feet from sea level

•Reference Table 5.5.3.3 in NFPA 2001

(also in manual)– Atmospheric correction

– Highly pressurized; keep dust out

– Highly depressurized; keep particles in

Page 26: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

EXAMPLE PROBLEMS

Page 27: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Minimum Design Concentration

vs. Adjusted Design Concentration•Minimum Design Concentration is the

minimum required per NFPA 2001

•Adjusted Design Concentration is the concentration used to calculate the quantity of agent in the cylinder– ADC >= MDC

Page 28: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

AGENT STORAGE CONTAINER LOCATION

Page 29: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

KIDDE

Agent Storage Container Location

•As close as possible to or within the protected enclosure– Per NFPA 2001

Page 30: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

KIDDE

Agent Storage Container Location

•Floor loading

– Container weight plus

agent weight

Page 31: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

KIDDE

Agent Storage Container Location

•Space requirements

– Single/Multiple cylinders

– Space for riser and attached controls

Page 32: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

KIDDE

Agent Storage Container Location

•Accessibility– Cylinder(s) accessible

for maintenance

Page 33: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

KIDDE

Agent Storage Container Location

•Storage temperature– Balanced or Single Hazard

Systems

= 32°F to130°F

– Unbalanced, Multi-Hazard

Systems

= 60°F to 80°F

Page 34: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

KIDDE

Agent Storage Container Location

•Storage temperature– If necessary, build an enclosure

and control temperature

– Does not reflect hazard

temperature(s)

Page 35: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

KIDDE

Agent Storage Container Location

•Classified areas– Explosion-proof equipment

needed/available?

Page 36: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Novec 1230™SERIES SYSTEMS

Page 37: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Nozzles

•Two nozzle types– 180° Nozzle– 360° Nozzle

•Nozzle sizes– 3/8” through 2”– 1/4” offered - Non UL and FM

•All nozzles must be pendant (hanging down)

Page 38: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Wid

th (

W)

Length (L)

1/3 L 1/3 L 1/3 L

1/3 W

1/3 W

1/3 W

Acceptable 180 degree nozzle location

NOVEC 1230 Nozzles

•180° Nozzle– Placed 6” ± 2” from a wall

– Orifices aimed away from the wall

– 6 - 19” ± 2” from ceiling to orifices

– As close to center of the wall as possible– At least 1/3

– No corner placement

Page 39: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Wid

th (

W)

Length (L)

1/3 L 1/3 L 1/3 L

1/3 W

1/3 W

1/3 W

Acceptable 360 degree nozzle location

NOVEC 1230 Nozzles

•360° Nozzle– Discharges agent in a

360° pattern

– Placed as close to center

of hazard as possible

– 6” to 19” from ceiling to

orifices

Page 40: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Novec 1230 Discharge

•Discharged as both liquid and vapor

•When near obstructions, liquid will “splash”

– Will effect the mixing of agent in the space due to reduced momentum in discharge.

Page 41: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Min 6' Min 6'

Min 6'

Min 6'

Min 6'

Min 6'

Min 6'

NOVEC 1230 Nozzle Locations

•Proximity of nozzles to significant obstructions– 6 ft. of clearance between

nozzle and wall

(or significant obstruction)

– Additional agent can be

discharged to

compensate for “losses”

on obstructions

Page 42: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Min 10'

Min 10' Min 10'

Min 10'

NOVEC 1230 Nozzle Locations

•Proximity of multiple nozzles– At least 10 ft. of clearance between

nozzles

Page 43: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

2' (Min 1')

Imaginary boundary

NOVEC 1230 Nozzle Locations

•Back-to-Back 180° Nozzles– 1 ft. to 2 ft. apart– Must face away from each other– Nozzles discharge equal quantities

Page 44: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Nozzle Locations

•For smaller enclosures

– Recommend using 180 nozzles in order

to meet 6 ft. clearance

– Recommend placing 180 nozzles along

longest wall to allow maximum

clearance in all directions

Page 45: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

d

d

NOVEC 1230 Nozzle Coverage

•Tested 35.6 ft. x 35.6 ft. Rectangle– (10.9 m x 10.9m)

•Actual coverage area defined as rectangle with diagonal, d

• 180°-d = 39.8 ft.(12.1m) 360°–d = 25.2 ft.(7.7 m)

Page 46: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Nozzle Height

•Maximum height for single nozzle is 16 ft.

•Minimum height– 1 ft. for UL Listed systems

Page 47: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Max 16’

Max 16’

Nozzle Tiering

•Use two rows of nozzles to protect enclosures greater than 16 ft. high (note max elevation difference limit)

Page 48: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Quantity of Nozzles

•Not always dictated by coverage area

•Coverage volume 35.6 ft. x 35.6 ft. x 12

ft. requires 574 lb. of Novec 1230– Will not discharge out of a single nozzle

within 10 seconds!

•Rule of Thumb:– Approximately 200 lb. per nozzle

Page 49: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Novec 1230™Engineered System Limits

Page 50: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Engineered Systems

•Hydraulic flow calculations used as basis of design– Allows for unbalanced systems

– Allows designer to use smaller pipe

– Use computer software to run flow

calculations

Page 51: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Piping Network: Tees

•Tee Parameters:

– Tee Orientation

– Flow Splits

– Bull Tees

– Side Tees

– “10 Pipe Diameters”

Page 52: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Piping Network: Tees

•Orientation

– 1 inlet

– May be horizontal or vertical (bull head tee

only)

– 2 outlets

– Both must be horizontal

Page 53: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

IN

OUT OUT

NOVEC 1230 Piping Network: Tees

•Bull tee flow split

– Minimum imbalance: 50/50

– Maximum imbalance: 75/25

Page 54: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

SIDE OUTLET(10 - 35)

INRUN OUTLET

(90 - 65)

NOVEC 1230 Piping Network: Tees

•Side tee flow split– Minimum imbalance: 65/35

– Maximum imbalance: 90/10

Page 55: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Piping Network: Tees

•“10 Pipe Diameters” Rule:– Length of pipe between a tee and a

change in direction must be equal to 10 times the nominal diameter of the pipe– A change in direction is defined as either

an elbow or another tee

– Must be adhered to before and after the tee

– Only necessary if the tee feeds agent to

separate hazards

Page 56: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

KIDDE KIDDE KIDDE

NOVEC 1230 Piping Network: Layout

•Keep network as simple, balancedand short as possible

•Consider structural members for hanging/bracing

•Avoid obstructions

Page 57: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Max 20’

NOVEC 1230 Piping Network: Layout

•Maximum allowable elevation difference in system piping (outlet and furthest horizontal pipe run/nozzle, or nozzles) is 20 ft.

Page 58: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Piping Network: Layout

•Percent of Agent in Pipe

– Percentage of the available agent that is

required to fill the pipe network

– Maximum 100%

– Affected by agent quantity, pipe lengths

and pipe diameters

Page 59: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Piping Network: Layout

•Percent of Agent Before 1st Tee is 2%

– Percentage of the available agent that is

required to fill the pipe network between

the cylinder outlet and the first tee

Page 60: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Piping Network: Layout

•Arrival Time Imbalance– Difference in time between when the agent

reaches the first nozzle and when it reaches the last nozzle

– Max 1.0 seconds (Subject to change)

•Runout Time Imbalance– Similar to Arrival Time Imbalance, but refers to

when agent runs out at each nozzle

– Max 3.2 seconds (Subject to change)

Page 61: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Piping Network: Pipe Sizes

•Pipe sizes are estimated by the software based on quantity of agent designated to each nozzle– Flow rate = lb. of Novec 1230 in branch /

10 seconds– Pipe estimating table in DIOM manual

(Table 3-6)

•Some manual changes may be required

Page 62: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Piping Network: Pipe Sizes

•Pipe sizes 1/2” through 6” are listed/approved– Largest Nozzle Size is 2”

•Smaller than 1/2” is available in software, but not listed/approved– Smallest Nozzle Size is 3/8”

– 1/4” nozzle is available (Unapproved

systems only)

Page 63: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Piping Network: Nozzles

•Minimum Nozzle Pressure– 91 psig (per UL 2166 Requalification)

Page 64: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

NOVEC 1230 Piping Network: Hydraulic Calculation

•Enter:– Enclosure info– Agent quantity– Agent Source– Pipe network

•Run Main Calculations

•Verify system acceptance

Page 65: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Hints, Tips and Other Considerations

Page 66: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Multiple Systems / Single Hazard

•If enclosure is large, consider using:– Multiple, modular NOVEC 1230 systems,

which will discharge simultaneously,

located throughout the hazard

– However - With 100% Agent in Pipe limit

- Novec flows well in complex pipe

networks.

Page 67: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Single System / Multiple Hazards

•If protecting more than four enclosures that are not connected, consider:

– Separate NOVEC 1230 systems

Page 68: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Agent Migration

• If protecting a single space with multiple nozzles, each nozzle should discharge the quantity of agent required by the nozzle’s design coverage area

– Maximum of 5% of the required agent may be discharged by a nozzle protecting an adjacent area

Page 69: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Designing for Multiple Hazards

•For more than one hazard, design with an adjusted concentration of 4.2% or higher

– Extra agent will make flow splits a lot

easier

– NOTE: Still use 4.2% as minimum

Page 70: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Tee Design Factor

•NFPA 2001 5-5.3.1– Starting from each hazard, count:

– Every tee within the hazard that splits to a

separate hazard

– Each tee between entry point to hazard and

the agent source (not including tees in a

manifold)– Reference Table 5-5.3.1 in NFPA 2001

for additional agent required

Page 71: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Tee Design Factor Example

Page 72: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.

Tee Design Factor Example

– Maximum tee count is 6

– From NFPA 2001, Table 5-5.3.1, a tee

count of 6 requires a 0.02 (2%) safety

factor

Page 73: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid.