Nortel iBTS Indoor2 Site Spec
-
Upload
kevinnight -
Category
Documents
-
view
131 -
download
1
Transcript of Nortel iBTS Indoor2 Site Spec
Pkgid: 0000003 PROPRIETARY INFORMATION: The information contained in this document is the property of Nortel Networks. Except as specifically authorized in writing, the holder of this document shall keep all information contained herein confidential and shall protect same in whole or in part from disclosure and dissemination to third parties.
Nortel Networks 2003 All Rights Reserved
Univity UMTS iBTS Indoor 2 Site Specifications
Installation Method – 06-9434
July 25, 2003
Issue Number: 3.01
Univity UMTS iBTS Indoor 2 Site Specifications / 1
July 25, 2003 Method 06-9434
Table of Contents1.0 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61.2 Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61.3 Reason for Reissue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.0 Material Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82.1 Required Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82.2 Tools & Test Sets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.0 Precautions and Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.1 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.2 Preparations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.0 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104.2 iBTS Indoor 2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.2.1 Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104.2.2 Equipment Packaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144.2.3 Dimensions and Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.2.3.1 iBTS Indoor 2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154.2.3.2 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164.2.3.3 Configurations Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.2.4 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174.2.4.1 Acoustic Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174.2.4.2 Transportation and Storage Requirements . . . . . . . . . . . . . . . . . . . . . . . . 184.2.4.3 Operating Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.2.5 Optional Modules Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194.2.5.1 External Alarms Module (Optional). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194.2.5.2 LPPCM Module (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214.2.5.3 TMA Equipment (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234.2.5.4 DC/DC Converter Module (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264.2.5.5 The NAM (3-Slot Passport 7420 Switch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.3 Co-Location Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374.3.1 Co-Location Particularities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374.3.2 Sharing Particularity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.4 Site Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 384.4.1 Site Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.4.1.1 Easy Access Site Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 394.4.1.2 Difficult Access Site Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.4.2 Cabinet Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 394.4.2.1 Lifting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 394.4.2.2 Horizontal Moving. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 404.4.2.3 Moving a Depopulated Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4.4.3 Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414.4.3.1 Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414.4.3.2 Floor Flatness. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4.4.4 Site Dimensioning Rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 424.4.4.1 Cabinets Positions and Distance Constraints. . . . . . . . . . . . . . . . . . . . . . . . . 424.4.4.2 Cabinets Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 454.4.4.3 Input Constraint of Coaxial Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
2 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.5 Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 494.5.1 iBTS Indoor Anchoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4.5.1.1 iBTS Indoor Installed on the Concrete floor . . . . . . . . . . . . . . . . . . . . . . . . . 544.5.1.2 iBTS Indoor Installed on a Raised Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 554.5.1.3 iBTS Indoor secured by the wall or the top . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4.5.2 Cable Tray and Cable Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 564.5.3 Earth Plate Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 594.5.4 DC Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4.5.4.1 iBTS Indoor Customer DC Power Supply Box . . . . . . . . . . . . . . . . . . . . . . . 614.5.5 -48Vdc Solution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4.5.5.1 DC Electrical Distribution System of the iBTS Indoor 2 (-48Vdc) . . . . . . . . . 624.5.5.2 Consumption According to Configurations (-48V Solution) . . . . . . . . . . . . . . 634.5.5.3 DC Power Supply -48Vdc Solution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 644.5.5.4 DC -48Vdc Power Supply Distribution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
4.5.6 +24Vdc Solution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 664.5.6.1 DC Electrical Distribution System of the DC/DC Converter (+24Vdc). . . . . . 664.5.6.2 Consumption According to Configurations with the DC/DC Converter (+24V Solution) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
4.5.6.3 DC Power Supply +24Vdc Solution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 674.5.6.4 DC +24Vdc Power Supply Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
4.5.7 DF for PCM Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 704.5.8 DF for External Alarm Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 724.5.9 Lighting and Service Socket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 734.5.10 Ventilation or Air Conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 734.5.11 High-Voltage Protector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 744.5.12 Lightning Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 744.5.13 Feeders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 754.5.14 Antennas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
4.6 Site Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 764.6.1 iBTS Indoor External Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 764.6.2 iBTS Indoor External Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
4.6.2.1 Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 784.6.2.2 Alarm Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 784.6.2.3 PCM Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 794.6.2.4 RF Jumpers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
4.6.3 Connection to the Aerial RF Part . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 804.6.4 External Cables Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
4.7 Final State of Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
5.0 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
6.0 Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86Appendix A – Equivalent between AWG and mm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86Appendix B – Cable Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87Appendix C – Abbreviations and Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88Last Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Univity UMTS iBTS Indoor 2 Site Specifications / 3
July 25, 2003 Method 06-9434
FiguresFigure 1 – .UTRAN - UMTS Terrestrial Radio Access Network . . . . . . . . . . . . . . . . . . . . . 11Figure 2 – iBTS Indoor 2 - General View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Figure 3 – iBTS Indoor 2 - Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Figure 4 – iBTS Indoor 2 Shipped in Vertical Position on its Wooden Pallet . . . . . . . . . . . . . 14Figure 5 – iBTS Indoor 2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Figure 6 – External Alarm Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Figure 7 – LPPCM Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Figure 8 – LPPCM Module Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Figure 9 – The LPPCM Module Location Above the Top iBTS Indoor 2 . . . . . . . . . . . . . . . 22Figure 10 – Pole Fixing System and UMTS Double TMA 2100MHz Module . . . . . . . . . . . . 23Figure 11 – Pole Fixing System and UMTS Single TMA 1900MHz Module . . . . . . . . . . . . . 24Figure 12 – TMAs Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Figure 13 – Double TMA 2100 MHz or Single TMA 1900MHz on Site . . . . . . . . . . . . . . . . . 25Figure 14 – The User/Option Rack 19" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Figure 15 – DC/DC Converter Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Figure 16 – User/Option Rack Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Figure 17 – Rear DC/DC Converter Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Figure 18 – Dipswitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Figure 19 – Power Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Figure 20 – Relay Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Figure 21 – The NAM - 3-slot Passport Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Figure 22 – Example of Mounting Configurations of the NAM . . . . . . . . . . . . . . . . . . . . . . . 34Figure 23 – Example of 13" Termination Panel Mounted on the Rear of the NAM . . . . . . . . 34Figure 24 – Example of GSM – UMTS Co-location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Figure 25 – Access Within the Building . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Figure 26 – iBTS Indoor 2 - Footprint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Figure 27 – iBTS Indoor 2 - Clearance View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Figure 28 – Example of iBTS Indoor 2 Alone - Layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46Figure 29 – Example of iBTS Indoor 2 with User/Option Rack and DC/DC Converter - Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Figure 30 – Jumper Bending Radius . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Figure 31 – iBTS Indoor 2 - Adaptation Foot Print Panel (Optional) . . . . . . . . . . . . . . . . . . . 51Figure 32 – Adaptation Foot Print Panel General View (Optional) . . . . . . . . . . . . . . . . . . . . 51Figure 33 – Example of the Adaptation Foot Print Panel Used with an IBN Solution . . . . . 52Figure 34 – iBTS Indoor 2 Drilling Template . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Figure 35 – iBTS Indoor 2 - Anchor Hole Template . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Figure 36 – iBTS Indoor 2 - 1/4 Anchor Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Figure 37 – Example of Raised Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Figure 38 – iBTS Indoor 2 - Top Holes Securing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Figure 39 – Example of Wall or Top Securing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Figure 40 – Cable Tray Equipotential . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Figure 41 – Cable Tray Cross Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57Figure 42 – DC Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Figure 43 – Bonding and Grounding Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Figure 44 – DC Electrical Distribution System of the iBTS Indoor 2 (-48Vdc) . . . . . . . . . . . 62Figure 45 – DC Electrical Distribution System of the DC/DC Converter (+24Vdc) . . . . . . . . 66Figure 46 – Example of Distribution Frame Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71Figure 47 – Example of Adaptation 120/75Ohms with Balun and LPPCM Box . . . . . . . . . 72Figure 48 – Example of Balun Adaptor 120/75 Ohms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
4 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 49 – Example of DF for PCM and Alarm Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73Figure 50 – Lightning Protection on Feeders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75Figure 51 – External Top Connection of the iBTS Indoor 2 . . . . . . . . . . . . . . . . . . . . . . . . . 77Figure 52 – Example of RF Link with UMTS 2100MHz Double TMA . . . . . . . . . . . . . . . . . . 81Figure 53 – Example of RF Link with UMTS 1900MHz Single TMA . . . . . . . . . . . . . . . . . . 81Figure 54 – Example of RF Link without UMTS TMA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82Figure 55 – Cable Size Graph for 0.25 Voltage Drop (One way) . . . . . . . . . . . . . . . . . . . . . 87
Univity UMTS iBTS Indoor 2 Site Specifications / 5
July 25, 2003 Method 06-9434
TablesTable 1 – Packaging Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Table 2 – iBTS Indoor 2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Table 3 – iBTS Indoor 2 Weight Fully Equipped . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Table 4 – iBTS Indoor 2 Weight with DC/DC Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Table 5 – Acoustic Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Table 6 – Transportation and Storage Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Table 7 – Operating Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Table 8 – Input Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Table 9 – Site Acquisition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Table 10 – DC/DC Converter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Table 11 – DC/DC Converter Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Table 12 – DC/DC Converter General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Table 13 – Status/Alarm Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Table 14 – Relay Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Table 15 – Relay Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Table 16 – NAM Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Table 17 – NAM Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Table 18 – iBTS Indoor 2 Alone Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Table 19 – iBTS Indoor 2 with DC/DC Converter Clearance . . . . . . . . . . . . . . . . . . . . . . . . 43Table 20 – Anchor Kit - List of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Table 21 – Raised Floor Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Table 22 – Cable Quantity for the Maximum Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 58Table 23 – Maximum Consumption According to Configurations (-48V Solution) . . . . . . . . 63Table 24 – Cable’s Section According to the DC Power Supply Mode (-48Vdc) . . . . . . . . . 64Table 25 – Protection Requirements for the iBTS Indoor 2 (-48V solution) . . . . . . . . . . . . . . 65Table 26 – Maximum Consumption According to Configurations with the DC/DC Converter (+24V Solution) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Table 27 – Cable’s Section According to the DC Power Supply Mode (+24Vdc) . . . . . . . . 68Table 28 – Maximum input Current (with 2 converters modules). . . . . . . . . . . . . . . . . . . . . . 70Table 29 – Protection Requirements for DC/DC Converter used for the +24V solution . . . . 70Table 30 – Maximum Distance Between the Cabinet and the DDF . . . . . . . . . . . . . . . . . . . 71Table 31 – Blowers speed set-point values of the iBTS Indoor 2 . . . . . . . . . . . . . . . . . . . . . 74Table 32 – The Maximal Dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74Table 33 – Example of the Feeders Characteristics For the Radio Link Optimized . . . . . . . 76Table 34 – Type of External Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77Table 35 – Example of the DC (-48Vdc) Power Cables (if IRM kit - CE Compliant used) . 78Table 36 – Example of the DC (+24Vdc) Power Cables (if IRM kit - CE Compliant used) . 78Table 37 – External Alarms Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78Table 38 – The PCM Cable With LPPCM Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79Table 39 – Example of the Jumpers Characteristics For the Radio Link Optimized . . . . . . 79Table 40 – Peculiarities of RF Links for Jumpers or Feeders (Connectors + Cables) . . . . . 80Table 41 – External Cables Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83Table 42 – AWG and mm² . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
6 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
1.0 General Information
1.1 DescriptionPurpose: This document covers the specifications for the selection and preparation of iBTS Indoor 2 sites.
Equipment: Univity iBTS Indoor 2 products.
Application: This document applies to the deployment of iBTS Indoor 2, which characteristics follow:
• The UMTS 2100MHz or UMTS 1900MHz with their specifics TRM or iTRM, MCPA, DDM or DDM2.
• The -48Vdc Power Supply Solution.
• The +24Vdc Power Supply Solution
• The Digital shelf (main functions are: network interface, call and signal processing, frequency up/down conversion) with the modules alpha (CEM, CCM, TRM) or the imodules (iCEM, iCCM, iTRM),
• The RF block which contains the front-end RF modules (TX splitter(s) in OTSR configuration for UMTS, 1 to 6 MCPAs, 3 to 6 DDMs),
• The number of CEM Module or iCEM64 or iCEM128,
• The Cooling Unit (ICU),
• The standard network interface of the iBTS is a maximum of 8 PCM E1/T1 (E1 PCM 120 Ω / 75 Ω, T1 PCM 100 Ω).
The following units are optional:
• The External Alarms module,
• The LPPCM Module (PCM Lightning protection),
• The DC/DC Converter (+24Vdc/-48Vdc)
• The NAM Passport 7420 (3-slot Passport switch)
• The Double UMTS 2100MHz TMA,
• The Single UMTS 1900MHz TMA,
Service Impact: None.
1.2 SequenceThis specification is to be used before Method 08-9432 "Univity UMTS iBTS Indoor 2 Handling and Securing".
Installation Methods can be found at: http://gis.us.nortel.com
This is a stand-alone method.
Univity UMTS iBTS Indoor 2 Site Specifications / 7
July 25, 2003 Method 06-9434
1.3 Reason for ReissueCloses Alert(s): None.
Closes CR(s): None.
• Reason for update:
• 3.01 update the Aerial RF part and add the 1900Mhz, the iModules, the TMA 1900MHz Single, the NAM, the T1 and the converter DC/DC (+24Vdc/-48Vdc).
• 2.03 update the new acoustic noise value, the TMA environment and removed the triplexor.
• 2.02 Method released with a new required document number IM-45-9389 instead of the bad number IM 45-9386.
• 2.01: New template and the new name includes "Univity".
• The iBTS Indoor 2 is the result of an evolution of the iBTS Indoor.
Replaces Method 06-9434 dated: January 21, 2003.
8 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
2.0 Material Requirements
2.1 Required DocumentsRegional Installation Safety Manuals (ISM) can be found at:
http://navigate.us.nortel.com/imds?pg=/ops/qual/inst
For example:
• Americas - Field Operations Safety Manual (SOP 030)
• EMEA Environmental Health & Safety
• Asia-Pacific Environmental Health & Safety
IM 45-9389 Univity UMTS iBTS Indoor 2 Product Safety Installation Requirements.
IM 10-9400 Univity UMTS iBTS Indoor 2 IRM Kits (Ancillaries) Definition - CE Compliant Only.
IM 04-9405 Univity UMTS iBTS Indoor 2 Cabling Referential
IM 53-9404 Univity UMTS iBTS Indoor 2 Depopulation, Repopulation Procedure
Project Document: iBTS Indoor 2 Packaging Specification.
2.2 Tools & Test SetsNone.
Univity UMTS iBTS Indoor 2 Site Specifications / 9
July 25, 2003 Method 06-9434
3.0 Precautions and Preparations
3.1 PrecautionsObserve the general safety precautions against personal injury and equipment damage outlined in the regional Installation Safety Manual at all times.
Appropriate precautions must be taken to guarantee the staff and equipment safety.
Refer to IM 45-9389 Univity UMTS iBTS Indoor 2 Product Safety Installation Requirements.
The site which receives the iBTS Indoor 2 must comply with national standard rules of installation, refer to [R6].
3.2 PreparationsPrior to starting the operations presented in this method, arrange all materials, tools, and test equipment at the work location so as to minimize fatigue and inconvenience.
10 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.0 Specifications
4.1 OverviewThe information presented in this specification covers the following topics:
• iBTS Indoor 2 description,
• Co-location issues
• Site requirements,
• Site preparation,
• Site wiring requirements,
• Final state of site preparation.
4.2 iBTS Indoor 2 Description
4.2.1 Presentation
The iBTS Indoor 2 is one component of the UTRAN (for UMTS refer to Figure 2) and supports the following fonctions:
• Radio access and modem (modulation, frequency conversion, amplification, reception, digitizing and radio signal demodulation),
• Call processing (channel setup and management for both common and dedicated channels),
• Performance monitoring (performing and reporting radio measurements),
• Network interface (managing interface with iRNC on the layer 1 for configuration and alarm reporting and on the layer 2 for IMA, switching..),
• Configuration and supervision (configuring and supervising internal modules as well as insuring inventory information reporting and plug and play management),
• The iBTS Indoor 2 can be used in DROP and INSERT configuration in the UTRAN Access Network.
Univity UMTS iBTS Indoor 2 Site Specifications / 11
July 25, 2003 Method 06-9434
Figure 1 – .UTRAN - UMTS Terrestrial Radio Access Network
Radio siteNode Bs
Radio siteNode Bs
NMS
OMC-R
OMC-B
Drop andInsert
12 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 2 – iBTS Indoor 2 - General View
Univity UMTS iBTS Indoor 2 Site Specifications / 13
July 25, 2003 Method 06-9434
Figure 3 – iBTS Indoor 2 - Overview
DC/DC Converter
DC Module
MCA Module
IEA Module
GPSAM Module
TRM or iTRM
CEM or iCEM
DDM Modules
DDM Modules
RF
MCPA Modules
CEM or iCEM
TRM or iTRM
CCM or iCCM
Cooling Unit
4 Hoisting RingLocation
Control Board
1 2 3
4 5 6
1 2 3 4 5 6
1 2 1 2 31 2 34
SIM IC1 IC2
Interco Breaker
Cooling Unit
Digital Breaker
Breaker
Interconnect
(Optional)
LPPCM Location(Optional)
User/Option Rack(Optional)
(Tools)
(Optional)
Modules
Modules
Module
Module
Modules
14 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.2.2 Equipment Packaging
The iBTS Indoor 2 cabinet is fully assembled in conventional delivery conditions and is shipped on its wooden pallet.
This wooden pallet weights around 23 kg (50, 7lb) the table hereafter gives its dimensions:
The cabinets can be delivered without cosmetic panel for manual handling; in this case only the modules and internal cabling are housed in the cabinet, but without cooling unit and cosmetic panel (door, side panel...).
For sites with difficult access, the iBTS Indoor 2 cabinet can be ordered and delivered depopulated. The modules that have to be inserted in the cabinet on site are then delivered in a specific protective packaging.
(refer to the iBTS Indoor 2 Packaging Specification)
Until the BTS was disassembly from its wooden pallet, the packaging increase the BTS’s weight and dimensions during installation phase (moving).
Figure 4 – iBTS Indoor 2 Shipped in Vertical Position on its Wooden Pallet
Table 1 – Packaging Description
iBTS Indoor 2 Vertically Position iBTS Indoor 2 Horizontally Position
Europe (Corrugated fiberboard) Export (Folding crate plywood)
900x800x1700 (mm) 1700x940x840 (mm)
iBTS Indoor 2
Wooden Pallet
Without itsCorrugatedFiberboard
Wooden Pallet
CorrugatedFiberboard
Univity UMTS iBTS Indoor 2 Site Specifications / 15
July 25, 2003 Method 06-9434
4.2.3 Dimensions and Weight
4.2.3.1 iBTS Indoor 2 Dimensions
Figure 5 – iBTS Indoor 2 Dimensions
Table 2 – iBTS Indoor 2 Dimensions
iBTS Indoor 2Alone
iBTS Indoor 2 With User/Option Rack
(mm) (in) (mm) (in)
Width 600 23.6 600 23.6
Depth 600 23.6 600 23.6
Height 1670 65.7 1940 76.4
600
1670
92
400
1940
482.6
600
4U177,8
iBTS Indoor 2Alone
iBTS Indoor 2With
User/OptionRack
DC/DCConverter
User/OptionRack
600
Front view
iBTS Indoor 2Side view
16 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.2.3.2 Weight
The Table 3 gives the weight of an iBTS Indoor 2 in STSR3-D radio configuration fully equipped with all the options and with the DC/DC Converter in Table 4. As a consequence, an iBTS shipped "fully equipped" on site weights about 320,3 kg (706 lb) up to 342kg (753 lb) with the DC/DC Converter and its wooden pallet.
The weight of iTRM = 4.5Kg/9.9Ib , iCCM =3.7Kg/8.16Ib , iCEM=3.3Kg/7.27Ib
Table 3 – iBTS Indoor 2 Weight Fully Equipped
Modules Unit (kg) Unit (lb) Qty Total (kg) Total (lb)Bare cabinet 79 174 1 79 174
Fixed Part105.8 Kg
233 Ib
Interco 1.3 2.9 1 1.3 2.9MCA 0.5 1.1 1 0.5 1.1
Cables 25 55 1 25 55Pallet 23 50.7 1 23 50.7
Removable PartMaximum
Configuration214.5 Kg
473 Ib
iBTS Door 13 28.6 1 13 28.6Lateral Panel 10 22 2 20 44
ICU Door 2 4.4 1 2 4.4Cooling Unit 15 33 1 15 33
CEM* 4.5 9.9 4 18 39.7TRM* 6.3 13.8 3 18.9 41.6CCM* 4.5 9.9 2 9 19.8
GPSAM* 3.5 7.7 1 3.5 7.7IEA* 1.5 3.3 1 1.5 3.3
MCPA** 11.3 24.9 6 67.8 149.5DDM** 7.6 16.7 3 22.8 50.2
iBTS Indoor 2 Fully Equipped with Pallet 320.3 706
Table 4 – iBTS Indoor 2 Weight with DC/DC Converter
Modules Unit (kg) Unit (lb) Qty Total (kg) Total (lb)
iBTS Indoor 2 Fully Equipped 1 320,3 706
Shelf 9.4 20.7 1 9.4 20.7
Converter 3 6.6 4 12 26.4
iBTS Indoor 2 with DC/DC Converter 342 753
Univity UMTS iBTS Indoor 2 Site Specifications / 17
July 25, 2003 Method 06-9434
4.2.3.3 Configurations Descriptions
There are two different configurations names for OTSR, OTBR, OTOR, BTBR and STSR.
• The first example is: OTSR1-D, which means Omni-Transmission Split-Reception with 1 carrier/sector and transmission redundancy. Or STSR3-D which means Sector-Transmission Split-Reception with 3 carrier/sector and transmission redundancy.
The second one is: (STSR) Sa-b-xxx-c, "a" is the number of sectors, "b" is the number of carriers/sector, "xxx" is the type of CEM (64,128,192,256 ...), "c" is the number of MCPA.
4.2.4 Environment
UMTS iBTS Indoor 2 should meet the requirements of [R7],[R8],[R9]&[R2]
Once fully installed, the iBTS Indoor 2 will meet the requirements of [R3] (Earthquake Vibration & Shock) class 3M3., for level 3 seismic events.
Note: Level 3 seismic events are equivalent to top floor Zone 4 (NEBS) seismic events specified by Bellcore.
4.2.4.1 Acoustic Noise
The maximum noise power emitted by the iBTS Indoor 2, when measured in accordance with [R4]&[R9], will not exceed:
Note: The bel is standard unit to express sound intensity or loudness level. Sound power can be defined as the sound loudness level of a sound source (in the case of iBTS Indoor 2), independent of distance or surrounding environment.
Table 5 – Acoustic Noise
iBTS Indoor 2 Sound Power (Max)
Normal speed operation 6.12 bels 61.2dbAI
Maximum speed operation 6.84 bels 68.4dbAI
18 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.2.4.2 Transportation and Storage Requirements
4.2.4.3 Operating Requirements
Table 6 – Transportation and Storage Requirements
iBTS Indoor 2
Temperature (long term) -40°C < TEMP < + 75°C-40°F < TEMP < +167°F
Temperature gradient < 30°C/hour < 86°F/hour
Relative humidity (non condensing) 5% < Hr < 95 %
Absolute humidity 1 g/m3 to 29g/m3
Air pressure 70<kPa<106
Storage recommendation [R7] Class 1.2
Transportation recommendation [R8] Class 2.2
Table 7 – Operating Requirements
iBTS Indoor 2
Temperature (long term) - 5°C < TEMP < + 45°C+ 23°F < TEMP < + 113°F
Temperature gradient < 30°C/hour< 86°F/hour
Relative humidity (non condensing) 5%<RH<95%
Air pressure 70<kPa<106
Operating recommendation [R1],[R2],[R9] Class 3.2
Univity UMTS iBTS Indoor 2 Site Specifications / 19
July 25, 2003 Method 06-9434
4.2.5 Optional Modules Characteristics
4.2.5.1 External Alarms Module (Optional)
A specific Alarm distribution frame should be considered. It must be grounded.
The external alarm kit provides up to 16 external alarms and up to 6 remote control. This kit consists of one module (IEA) equipped with 2 digital cables and one ground cable. This external alarm module is located in the MCPA shelf on the right hand side slot when viewed from the front of the cabinet (see Figure 3) to adapt the alarm 2 remote control loops to the internal alarm bus.
The 16 external alarms and 6 remote control are shared on 2 cables (8 external alarms and 3 remote control per cables). The normal state (no alarm) is a closed loop. That means when the loop is open, an alarm appears at OMC. As a consequence, each equipment connected to the external alarms should be "closed" in a normal state.
Regarding the remote control, when the contact is closed, the maximum current is 150 mA and the serial resistor is 10 Ohms. When the contact is open, the maximum switching voltage is 60V.
Table 8 – Input Characteristics
Loop Output Current 0 - 7mA
Max Output Voltage 8V
Max Loop Resistance 1KOhms
Electrically Isolated Inputs
20 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 6 – External Alarm Kit
D-Sub 25 Pin Female
IN
OUT
Ground
ExternalAlarm 1
ExternalAlarm 2
InternalAlarmBus
ExternalAlarm 1
ExternalAlarm 2
Univity UMTS iBTS Indoor 2 Site Specifications / 21
July 25, 2003 Method 06-9434
4.2.5.2 LPPCM Module (Optional)
The LPPCM Module (PCM Lightning protection) protects up to 8 PCM. This Kit consists of one module (LPPCM module), equipped with one cable. This module is located above the iBTS Indoor 2.
Figure 7 – LPPCM Module
Figure 8 – LPPCM Module Connection
Top iBTS Indoor 2
LPPCM Module
DC/DC Converter location if used
LPPCMBox
iBTS Indoor 2Cabinet
Towards DDF customer side
LPPCM Box
22 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 9 – The LPPCM Module Location Above the Top iBTS Indoor 2
Top view
Air Exit
Univity UMTS iBTS Indoor 2 Site Specifications / 23
July 25, 2003 Method 06-9434
4.2.5.3 TMA Equipment (Optional)
The basic function of this equipment is to amplify the received RF signals in the early stages of the reception path before going through the feeders where a big amount of noise is added.
The TMA is designed to be a low noise amplifier and to be mounted as near as possible from the antenna system, it is made of 2 independent subassemblies:
• A pole fixing system providing securing to the mast designed for one-man easy-installation requirements, compatible with pole diameters between 48 and 110 mm for the Double TMA 2100 MHz or between 50 and 140 mm for the Single TMA 1900 MHz.
• A wall fixing system.
A TMA module providing interconnection of electrical and radio functionalities.
Figure 10 – Pole Fixing System and UMTS Double TMA 2100MHz Module
24 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 11 – Pole Fixing System and UMTS Single TMA 1900MHz Module
For site acquisition, the dimensions to take in account are the following:
The external connections are located at the bottom side of the TMA module, the RF connectors are standard male 7/16.
The TMA location should permit a sufficient space for installation (for easy key mounting on site), for example, refer to Figure 12 – TMAs Connections.
Figure 12 – TMAs Connections
Table 9 – Site Acquisition
Type of TMA Height Width Depth Weight
Simple TMA 1900MHz 272,5 mm (10,72 in) 190 mm (7,48 in) 135 mm (5,314 in) 6Kg
(13.2Ib)
Double TMA2100MHz 368 mm (14,488 in) 229.5 mm ( 9.035 in) 135 mm (5,314 in) 8.5Kg
(18.7Ib)
UMTS DoubleTMA 2100MHz
UMTS SingleTMA 1900MHz
Univity UMTS iBTS Indoor 2 Site Specifications / 25
July 25, 2003 Method 06-9434
IMPORTANT: In terms of lightning protection, when TMAs are employed on site, the iBTS should be equipped with gaz tub at the place of ¼ wave stubs.
Figure 13 – Double TMA 2100 MHz or Single TMA 1900MHz on Site
Jumpers
Feeders
Ground
Jumpers
Main earthiBTS
Double
Antennae
iBTS
TMA TMA19001900
Single Single
Antennaemain anddiversity
Jumpers
Feeders
Ground
Main earth
Jumpers
TMA2100
26 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.2.5.4 DC/DC Converter Module (Optional)
The DC/DC converter module is to be used in conjunction with the iBTS Indoor 2 to provide a DC/DC (+24Vdc/-48Vdc) power solution.
The DC/DC converter is inside a User/Option Rack 19" independent and is mounted above the iBTS Indoor 2 cabinet without interfere the rear exit air flow.
Figure 14 – The User/Option Rack 19"
Figure 15 – DC/DC Converter Module
Air Deflector
User/Option Rack 19"
iBTS Indoor 2Door
iBTS Indoor 2Top
482.6mm
177,8mm= 4U101,6mm
2iBTS Indoor 2
DC/DCConverter
User/Option Rack 19"
394.6mm15.5"
3.5"
90mm304.6mm
12"
19"
Univity UMTS iBTS Indoor 2 Site Specifications / 27
July 25, 2003 Method 06-9434
Figure 16 – User/Option Rack Support
Table 10 – DC/DC Converter Dimensions
Height 177.8 mm (6.9 in)
Depth 400 mm (15.7 in)
Width 482.6 mm (19in)
Table 11 – DC/DC Converter Weight
Shelf without DC/DC Converter 9.5 Kg (21 Ib)
Equipped with 2 Converter Module 15.5 Kg (34 Ib)
Equipped with 3 Converter Module 18.5 Kg (41 Ib)
Equipped with 4 Converter Module 21.5 Kg (47.4 Ib)
Table 12 – DC/DC Converter General Specifications (Page 1 of 2)
DC Input +20Vdc ~ +31Vdc
DC Output Default -55Vdc+/- 1%
System Capacity 7.8KW (6.5KW N+1 redundancy)
Operating Temperature 14°F ~ 122°F / -10°C ~ +50°C
Storage Temperature -40°F ~ +158°F / -40°C ~ +70°C
Efficiency >88%, Typical
177.8mm =4U
DC/DC ConverterLeft side view
User/Option Rack Support
92mm
1
1
Top Left iBTS Indoor 2
394.6mm15.5"
3.62"
7"
Air Deflector
28 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Input/Output Interface
This power shelf provides input and output connection copper bus bars as interfaces.
The DC/DC power system provides M8 thread holes with 25.4mm pitch on both +24V and 0V Bus in input side, and on both -55V and 0V Bus in output side.
For earth connection, the DC/DC Power System provides M8 thread holes (see Figure 17).
Current sharing +/- 5% of rated output current
Humidity 95% Relative Humidity, Non Condensing
Altitude -500 ~ 10,000 Feet (-152 ~ 3048m)
Voltage Accuracy </= +/- 1V
Acoustic Module: <35°C 60dBA>35°C 65dBA (sound power level)System (with 3 Modules)<35°C 61dBA>35°C 66dBA (sound power level)
Transportation ETS 300 019-1-1 class 1.2ETS 300 019 1-2 class 2.2
Vibration / Shock IEC 721-3-3, Class 3M5
IP IP20 according to IEC 529
Earthquake BellCore GR-63-CORE, Zone 4ETS 300 019-1-4, Zone 4 (requirements)ETS 300 019-2-4, Zone 4 (Testing Methods)
Safety UL/CUL, TUV, CE mark, CB report
Table 12 – DC/DC Converter General Specifications (Page 2 of 2)
Univity UMTS iBTS Indoor 2 Site Specifications / 29
July 25, 2003 Method 06-9434
Figure 17 – Rear DC/DC Converter Connection
Module Installation
In order to minimize the weight of system, all DC-DC converter modules can be removed from the system shelf and re-installed after the system shelf has been mounted to the rack.
Note: The converters will work in any slot of the shelf. The Alarm Board requires a converter in slot #1 to be fully functional. For proper system operation always equip slot 1 with a converter module.
Note: The Dipswitch shown in Figure 18 is for input alarm setting and controller recognition of modules. When slots #3, #4 are both empty, please switch pin1 to OFF position. When slots #5, #6 are both empty, please switch pin2 to OFF position.
Figure 18 – Dipswitch
Power Module Description
I/P 0VBus
I/P 0VBus
I/P 0VBus
I/P 24VBus
I/P 24VBus
I/P 24VBus
O/P -55VBus
O/P 0VBus
30 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
The DC/DC modules are rated at 1300W max output. The modular design provides flexibility to configure and expand the system as the load demand increases. Every power module is hot-swappable with front access for ease of maintenance without system shutdown providing uninterrupted service.
System Relay Output
The DC/DC Power System provides 4 alarm relay output positions via a 9-pin terminal (European type). These alarms use Normal Closed (N.C.) Form C Dry contact type.
Table 13 – Status/Alarm Indicators
Input OK This is a green LED to indicate whether the DC input is within operating range. It is ON whenever the DC input is within operating range from 20Vdc to 31Vdc.
Figure 19 – Power Module
Output Fail This is a red LED to indicate whether the output voltage is normal. It is ON whenever the output voltage is higher than 57V±1V or lower than 50Vdc±1V.
Fan Fail This is a red LED to indicate whether the fans are operating normally. It is ON whenever one or both of the fans are out of service. When the fan fail condition occurs, the converter continues to supply output power normally unless the over temperature protection is triggered.
Table 14 – Relay Specifications
Items Specifications Figure 20 – Relay Output
Rating (Resistive) 0.5A 120Vac or 1A 24Vdc
Maximum Switching Voltage 120Vac/60Vdc
Maximum Switching Current 1A
Univity UMTS iBTS Indoor 2 Site Specifications / 31
July 25, 2003 Method 06-9434
Note: When the FAN FAIL LED on the converter is on, it means one or both of the fans are out of service. When the fan fail condition occurs, the converter continues to supply output power normally unless the over temperature protection is triggered.
System Ventilation
Mount the rack with a distance no less than 4 inches from the rear of the shelf to the wall. This will provide adequate ventilation for the DC/DC converter. The front of the system should be clear of all obstruction and allow room for proper ventilation.
Table 15 – Relay Output
Pin Alarm Event Definition Description
1 Input +24VdcFault
The relay releases if DC Input voltage over 31 Vdc or under 20 Vdc.
The system will detect the input voltage from input landing bus bar and execute this alarm.
2 Output -55VdcFault
The relay releases if DC Output voltage over 60 Vdc or under 42 Vdc.
The system will detect the output voltage from output bus bar and execute this alarm.
4 Major Alarm
2 or more than 2 converters are fault. or the converter is fault when the system equipped only 1 converter.
The red LED of OUTPUT FAIL on the faulty converters will emit and major alarm is triggered.
5 Minor Alarm
Only 1 converter is fault. (This function is void when the system equipped only 1 converter.)
The red LED of OUTPUT FAIL on the faulty converter will emit and minor alarm is triggered.
32 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.2.5.5 The NAM (3-Slot Passport 7420 Switch)
Main Function of the NAM
NAM/iCCM with cascaded stars ATM case:
• Regular CCM/iCCM is used for remote sites
• NAM + iCCM is used for intermediate hubs
NAM as Cell Aggregator.
NAM in a multi-service environment.
List of Interface Available
• MSA 32 providing:
• 2 optional STM-1
• 32 E1 ports for 24 E1 IMA or 30 E1 without IMA
• 8 E1 IMA
• 4 E1 CES
• 3 E3 / DS3
• 2 STM-1
Possible Configuration
• 2 STM-1 / 24 E1 IMA or 30 E1 without IMA
• 24 E1 IMA or 30 E1 without IMA
• 8 E1 IMA / 3 E3
• 8 E1 IMA / 4 E1 CES
Shelf Assembly
A fully-installed 3-slot Passport switch consists of a CP (Control Processor card) installed in slot 0 of a three-slot chassis and an integrated dc power supply. The remaining two slots support function processors. The Passport 7420 supports all CPs and FPs (Function Processor card) offered with the Passport 7400 family with the exception of VSP1, VSP2 and the VPN extender card.
All hardware modules for power conversion, cooling, and cable management integrate into its chassis. See Figure 21.
Univity UMTS iBTS Indoor 2 Site Specifications / 33
July 25, 2003 Method 06-9434
Figure 21 – The NAM - 3-slot Passport Switch
Dimensions and Weights
Table 16 – NAM Dimensions and Weights
Equipment Height x width x depth Weight ChassisEmpty
Fully-configured, 1 chassis, 1CP, 2 functionprocessors, 2 termination panels (excludingcables), with 4 feet in a desktop mount installation
15.8 x 40.6 x 52.4 cm(6.22 x 16 x 20.63 inches)
16.82kg(37Ib)
11.48 kg(25.3 Ib)
Fully-configured, 1 chassis, 1CP, 2 functionprocessors, 2 termination panels (excludingcables), in a rack-mount installation
13.3 x 49.2 x 52.4 cm(5.23 x 19.37 x 20.63 inches)
17.05 kg(37.5 Ib)
12.18 kg(26.8 Ib)
Fully-configured, 1 chassis, 1CP, 2 functionprocessors, 2 termination panels (excludingcables), in a seismic cabinet
14.1 x 49.2 x 52.4 cm(5.55 x 19.37 x 20.63 inches)
17.73 kg(39Ib)
12.18 kg(26.8 Ib)
Fully-configured, 1 chassis, 1CP, 2 functionprocessors, 2 termination panels (excludingcables), in a vertical mount installation
51.7 x 18.8 x 51.7 cm(20.35 x 7.4 x 20.35 inches)
17.27 kg(38 Ib)
12.2 kg(26.8 Ib)
PowerControl and functionprocessor cards
Slot 2
Slot 1
Slot 0
switch
FRONT VIEW REAR VIEW
GND Connection
DCTerminalBlock
Localoperatorport
34 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Hardware Configurations Figure 22 – Example of Mounting Configurations of the NAM
Cables guides route the cables from the FPs at the front to the termination panels at the rear.
Figure 23 – Example of 13" Termination Panel Mounted on the Rear of the NAM
If you install the NAM in a cabinet or rack, you can use 19" termination panels.
For installation instructions see 241-7401-240 Passport 7400 Hardware Installation, Maintenance and Upgrade.
In a standard 19-inchrack or cabinet(rack-mount)
Free-standing verticallyunder a desk(vertical mount)
Free-standing horizontallyon a desk(desktop mount)
Cable guides
19" Termination Panels
CablesGuides
Example of 13" Termination
Brackets
Panel kit
Univity UMTS iBTS Indoor 2 Site Specifications / 35
July 25, 2003 Method 06-9434
Environmental Requirements
Ventilation and Access Clearances
Total heat dissipation of a fully populated 3-slot Passport switch is approximately 200 W.
Desktop mount NAM placed on a table and vertically-mounted switches need the following clearances:
• Top: 5 cm (2 inches)
• Front and sides: 2.5 cm (1 inch)
• Rear: 5 cm (2 inches)
A rack-mounted NAM needs 5 cm (2-inch) clearance on all sides. The maximum depth of the rack-mounting bracket must not exceed 20 cm (8 inches).
Noise Levels
The noise level for the NAM is 44 dBA (for a front-facing switch in an open frame with no cover or door).
Table 17 – NAM Environmental Requirements
Environmental Factor Mode SpecificationTemperature Operating Air Inlet
• Maximum 40° C for long term reliability
• Maximum 55° C for short term functionality
Air outlet
• Maximum 60° C for long term reliability
• Maximum 75° C for short term functionality
Rate of change <10°C/hrStorage -40 to +70°CRate of change <100°C/hr
Relative Humidity Operating 10% to 80% non condensing(5.2kPa pressure maximum)
Storage 10% to 80% non condensing(5.2kPa pressure maximum)
Altitude Operating 61m (200ft) below sea level to 2000m (6600ft) above sea level
Particulate atmosphere Class 100,000(Fed. Std. No.209B)
36 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Dc Power Source Requirements
The NAM has an integrated 300W power supply. The terminal block for the -48V dc power input is located on the rear panel of the shelf.
In -48 V dc installations (typically North American), power feeds into the system require a 60 V dc rated circuit breaker or fuse.
In -60 V dc installations (typically European), power feeds into the system require an 80 V dc rated circuit breaker or fuse.
In all cases the circuit breaker or fuse must be rated for 10 A dc and have appropriate regulatory approvals.
Dc Power Input and Wiring Requirements
You must supply your own 12 AWG or 14 AWG dc power wiring. Wiring must be
• approved for use in the country of installation
• rated for 10 A dc
• protected with a 10 A circuit breaker or fuse
The nominal input voltage can be -48/-60 V with an input operational range of -39 to -72 V. The maximum output power for each dc supply is 300 W.
Input voltage under minimum battery operating conditions must supply a minimum of -36.0 V to the power supply. The maximum dc wire length for a voltage drop of 1 V using 14 AWG wire is 12.2 m (39 ft) and for 12 AWG wire is 19.6 m (62 ft).
Note: A length of 12.2 m is the distance from the power source to the unit. Total loop length (battery and battery return) is double this length.
North American installations must use plain crimp ring lugs (insulated) with a #8 stud size and either a 12 AWG or 14 AWG wire to connect to the power supply terminal strip.
European installations must use plain double crimp ring lugs (insulated) approved for European requirements with a #8 stud size and either a 12 AWG or 14 AWG wire.
Note: Ring lugs must be insulated to prevent accidental electric shock.
Univity UMTS iBTS Indoor 2 Site Specifications / 37
July 25, 2003 Method 06-9434
Grounding Requirements
Passport is grounded to protect both personnel and equipment and contains a separate ground stud located on the rear housing.
For further information on grounding, see 241-7401-240 Passport 7400 Hardware Installation, Maintenance and Upgrade.
Cabling Requirements
If you have a fully-configured switch with 13” rear-mounted termination panels, you will get the best cable routing between the lower cable organizer and the cable-support guide if:
• cable diameters do not exceed 0.8 cm (5/16 inch)
• cable flexibility allows for a bend radius of 2.5 cm (1 inch).
For more information see 241-7401-200 Passport 7400 Hardware Description "cables."
Compliance to Electrical and Safety Standards
Passport switches comply with both North American and international regulatory safety requirements.
4.3 Co-Location Issues
4.3.1 Co-Location Particularities
As the UMTS network is a new coming system, the operators might be looking for solutions of co-location between GSM BTS and new UMTS BTS on the same site for different reasons: Difficulty of finding new sites, cost reduction, environmental issues...
In the analysis of co-location, different interferences occur (like spurious emissions, wideband noise, blocking, intermodulation products, or electromagnetic problems). For each type of interference, the necessary isolation between different systems should be achieved to avoid any disturbance. The isolation can be obtained by different ways (antenna decoupling, use of filters…).
CAUTION/WARNING:Damage to equipment by electromagnetic interferenceTo meet electromagnetic interference (EMI) regulatoryrequirements and thermal specifications, all blank slotsmust be fitted with a blank function processor faceplate.
38 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Some co-siting phenomena must be studied concerning the existing GSM sites which are in compliance with GSM specification fixed before the arrival of UMTS. As the spurious emissions from GSM BTS within the UMTS receiving band have not been specified at a controlled level, the potential interference risks from GSM BTS to UMTS BTS in co-location case exist: Anyway, these problems cannot be forecasted and must be treated on site, case by case. For more information, refer to your site engineering prime.
Figure 24 – Example of GSM – UMTS Co-location
4.3.2 Sharing Particularity
The iBTS Indoor 2 could be divided between two (or several) different operators (customer) with intend to optimize the site.
4.4 Site Requirements
4.4.1 Site Access
Once a site has been selected, access conditions should be evaluated to determine whether the cabinet should be delivered populated (easy-access site) or depopulated (difficult-access site).
The access conditions must comply with cabinet dimensions and the available moving equipment.
The packaging can be remove to get over an obstacle (door or staircase...) but keep some protection of the iBTS Indoor 2 (Antistatic bag or vapor barrier or blanket...)
iBTS Indoor 2 UMTS
Univity UMTS iBTS Indoor 2 Site Specifications / 39
July 25, 2003 Method 06-9434
The iBTS Indoor 2, the User/Option Rack 19" and the DC/DC Converter with its Shelf are delivered separately.
4.4.1.1 Easy Access Site Characteristics
• The site access conditions allow the mechanical handling of a populated cabinet throughout the distance separating the delivery point from the mounting location without manual carrying.
• The mechanical means used to carry and/or hoist the fully populated cabinet (e.g. dolly system, elevator, ...) must be qualified to bear the fully populated cabinet weight (about 320 kg/ 706 lb) in compliance with standard security requirements.
4.4.1.2 Difficult Access Site Characteristics
• For this type of site mechanical means cannot cover the entire delivery to mounting location distance; part of the way (as small as it might be) requires manual carrying. As a consequence, the cabinet can be depopulated to reduce its weight and height (by swinging).
• Even though the cabinet can be carried manually, the maximum use of mechanical means is encouraged to enhance the safety and security of both staff and equipment.
4.4.2 Cabinet Handling
Otherwise specified the term ‘the cabinet’, in this chapter, refers to an iBTS Indoor 2 cabinet without User/Option Rack 19" and DC/DC Converter option.
The iBTS Indoor 2 cabinets are delivered upright with a corrugated cardboard sleeve on a wooden pallet in case of road transport. They are delivered lying in plywood crates in case of air and sea transports. In all cases, the specific packing allows their handling by means of a fork-lift truck.
The equipment should be unpacked as close as possible to their precise mounting location.
The path from the delivery point to the mounting location should be clear of any obstacle.
The cabinet can be carried either in vertical or horizontal position (in populated or depopulated configuration (refer to IM 53-9404 Univity UMTS iBTS Indoor 2 Depopulation, Repopulation Procedure).
4.4.2.1 Lifting
The populated iBTS cabinet must be handled with mechanical devices (the cabinet may only be guided manually during lift-off or during final
40 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
positioning, provided that basic safety rules are observed by the personnel).
All other handling methods must be specified and validated if required by the project. The cabinets are hoisted with 4 hoisting rings type, by a lifting vehicle suited to the cabinet weight and to the site characteristics (height...).
• No specific tool to lift the iBTS Indoor 2.
• 4 hoisting rings (M10) with strap (useful load 500kg/1102Ib) are the tools for the top of the iBTS Indoor 2 cabinet.(see Figure 51 and Figure 3).
• A specific manual carrying by 4 installers (mover profile) or a specific mechanical carrying by 2 installers means is needed to install this iBTS Indoor 2.
4.4.2.2 Horizontal Moving
• A standard forklift/dolly is used to move the cabinet, secured to its wooden pallet.
• The path should be clear of obstacle (gravel’s, cableway, conduits ...).
4.4.2.3 Moving a Depopulated Cabinet
The access to reach the building entrance from the truck should respect the following minimum dimensions are given under. :
Note: Lift / Elevator: Capacity of 650 kg for a populated cabinet. Capacity of 400 kg for a depopulated cabinet. Check that the lift / elevator max. load is sufficient to lift the cabinet, its means of handling and personnel simultaneously.
Layout Height Width Comment
Doors 1.80 m (5.9 ft) 0.80 m (2.6 ft)
Corridor 1.80 m (5.9 ft) 1.00 mm (3.3 ft) Case of way in straight line.
Corridor 1.80 m (5.9 ft) 1.00 mm (3.3 ft) Case of way with right angle turn.
Staircase 1.80 m (5.9 ft) 1.40 mm (4.6 ft)
Staircase 1.80 m (5.9 ft) 1.40 mm (4.6 ft) Half floor (to turn).
Spiral staircase
1.80 m (5.9 ft) 1.40 m (4.6 ft) Minimal interior diameter 2.80 m (9.2 ft)
Univity UMTS iBTS Indoor 2 Site Specifications / 41
July 25, 2003 Method 06-9434
Figure 25 – Access Within the Building
4.4.3 Floor
The iBTS Indoor 2 cabinet can be installed either on a concrete floor or on a raised floor.
The floor covering must be antistatic (about 1MOhms) or the technician must use an antistatic bracelet.
In case of raised floor installation, all raised floor supports must be earth equipotentialized.
In seismic regions, where raised floors are mandatory, cabinets are installed on the same metallic support with additional vibration absorbers.
The site which receives the iBTS Indoor 2 must comply with standard rules for installation in indoor premises (refer to [R1], [R2], [R5], [R6]).
4.4.3.1 Resistance
iBTS cabinet: In accordance to cabinet weight, the minimum floor resistance should be: 700 kg/m², 123 lb./ft².
Note: In case of floor resistance value close to the previous one, an additional securing point to the wall or a load spreading structure on the floor is advised.
Staircase
Corridor
Door
0.80m 1.80m
1.4 m 1m
1.40m
2.80m
Spiral Staircase
42 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.4.3.2 Floor Flatness
The iBTS Indoor must be installed on a level floor surface. The maximum tolerance for floor flatness is 5mm over 2m (~ 0.2’’ over 78’’). In other words, the vertical tolerance shall not exceed 5mm over a 2m horizontal length.
If the BTS pad does not respect this maximum tolerance, the cabinet once installed may be ‘twisted’ and the cabinet door might be impossible to open. The adjustable feet can be used for taking up of play.
4.4.4 Site Dimensioning Rules
The criteria governing the size of the site are:
• The cabinet dimensions and the distance constraint,
• The relative positions of cabinets,
• The input constraint of coaxial cables,
• The use of the User/Option Rack 19" with the DC/DC Converter.
4.4.4.1 Cabinets Positions and Distance Constraints
Each site can be constituted of one iBTS cabinet plus one optional User/Option Rack 19" with the DC/DC Converter. The clearances considers the clean surface which is the minimum surface required to install the cabinet and allow the different field technicians to move along the cabinet when installing or servicing it. The clean surface is described in the given sample layouts.A minimum clearance is required around the cabinet.
Table 18 – iBTS Indoor 2 Alone Clearance
iBTS Indoor 2 Alone (m) (in) Comments
Minimum distance
Ceiling 2.17 85.4 Between the floor and the ceiling
Height 1.97 77.5 Between the floor and the cable tray.
Front/Door 1.20 47.2 Between the cabinet front side and the opposite wall to allow access for moving.
Space on either side 0 0 To allow the right and the left panel to be taken off for the installation/removal of the side outer skin.
Rear 0 0 To allow radio cabinets securing, the supporting wall must be flat and more or less vertical (maxi-
mum tilt of 5%)
Univity UMTS iBTS Indoor 2 Site Specifications / 43
July 25, 2003 Method 06-9434
Table 19 – iBTS Indoor 2 with DC/DC Converter Clearance
iBTS Indoor 2 with DC/DC Converter
(m) (in) Comments
Minimum distance
Ceiling 2.44 96 Between the floor and the ceiling
Height 2.24 88.2 Between the floor and the cable tray.
Front/Door 1.20 47.2 Between the cabinet front side and the opposite wall to allow access for moving.
Space on Left side 0.30 11.8 To allow the left access to the RF connection (only above the cabinet respectively the RF Zone con-nection) the minimum can be 0 mm / 0" under the
top cabinet level (see Figure 27)
Space on Right side 0.60 23.6 To allow the right access to the RF and DC connec-tion. (only above the cabinet respectively the DC and RF Zone connection) the minimum can be 0 mm / 0" after final cabling, under the top cabinet
level (see Figure 27)
Rear 0 0 To allow radio cabinets securing, the supporting wall must be flat and more or less vertical (maxi-
mum tilt of 5%)
44 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 26 – iBTS Indoor 2 - Footprint
All dimension are expressed in millimeters
600
600
1200
TOP VIEW
1200Maximum
Removable Door
900minimum
0.9m² (9.7ft²)
1.08m² (11.6ft²)
minimum
Maximum
Univity UMTS iBTS Indoor 2 Site Specifications / 45
July 25, 2003 Method 06-9434
Figure 27 – iBTS Indoor 2 - Clearance View
4.4.4.2 Cabinets Layout
Different types of layout are defined in order to have a larger number of cabinets in the premises in case of a scheduled extension for example (see Figure 27, Figure 28 and Figure 29). The following possibilities are available:
• To attach them at the bottom,
• To secure the cabinets back to back, (It is recommended to secure them together)
• To secure the cabinets side by side, (No space between each) is always possible (see Figure 28).
• To invert the opening of the door.
1670
CABLE TRAY
iBTSIndoor 2
iBTSIndoor 2
Cooling Unit
Front view Side View
200
CEILING
Minimum
WALL
300
200 Minimum
Minimum
600
With DC/DCConverter
WithoutUser/Option
Rack
400
19402240
1970
Doo
r
300 Minimum92
DC and RF Zone Connection DC/DCConverter
User/OptionRack
46 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 28 – Example of iBTS Indoor 2 Alone - Layout
900
600
1200
600
600
700
V VV000
600 600 600
>0
800
iBTS Id 2iBTS Id 2
iBTS Id 2
iBTS Id 2
iBTS Id 2
23.6in
31.5in
35.4in
47.2in
23.6in
23.6in 23.6in 23.6in
23.6in
27.5iniBTS Id 2
Minimum
Minimum
WA
LL
WALL
Minimum
Wall orOther
Equipment
Univity UMTS iBTS Indoor 2 Site Specifications / 47
July 25, 2003 Method 06-9434
Figure 29 – Example of iBTS Indoor 2 with User/Option Rack and DC/DC Converter - Layout
4.4.4.3 Input Constraint of Coaxial Cables
The position and length of the antenna feeders should respect the bending radius of the jumpers on both sides (antenna and iBTS side). Refer Table 33 for the feeders and Table 39 for the jumpers characteristics.
900
600
1200
600
600
300 600 600
>0
800
iBTS Id 2
23.6in
31.5in
35.4in
47.2in
23.6in
11.8in 23.6in 23.6in
23.6in
Minimum
Or minimum
Wall orOther
Equipment
WALL
WA
LL
RF
Zone
Con
nect
ion
DC and RF
ConnectionZone
with a Five-treadstepladders
DC and RF
ConnectionZone
with a Five-treadstepladders
Minimum Minimum
With DC/DCConverter
iBTS Id 2With DC/DCConverter
iBTS Id 2With DC/DCConverterR
F Zo
neC
onne
ctio
n
60023.6in
RF
Zone
Con
nect
ion
70027.5in
Minimum
DC and RF
ConnectionZone
with a Five-treadstepladders
90035.4in
Ideally
duringfirst connection
48 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 30 – Jumper Bending Radius
Univity UMTS iBTS Indoor 2 Site Specifications / 49
July 25, 2003 Method 06-9434
4.5 Site PreparationThis section describes the preparatory work which should be carried out on site prior to the iBTS Indoor installation. The iBTS Indoor cabinets are installed in premises which are equipped with:
• Cable tray,
• Grounding and equipotential circuits,
• Customer DC Electrical power supply (with a surge protection),
• Digital Distribution Frame for PCM connection (with a surge protection) and DF for external alarms connection (with a surge protection),
• Lighting and service sockets,
• Ventilation or air conditioning,
• Where necessary, an anti seismic system.
• Feeders and Antennas,
4.5.1 iBTS Indoor Anchoring
The iBTS Indoor 2 cabinet is secured to the floor using the following floor anchoring hole pattern or with an iBTS Indoor 1 adapter plate (Option supplied by Nortel) if used to upgrade an iBTS Indoor 1 site into an iBTS Indoor 2 (see Figure 31 and Figure 32).
50 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
CAUTION/WARNING:For isolated bonding network (IBN) the cabinet must be isolated from the floor by the use of rubber shims or groundsheet and isolated anchoring system (Isolated bushing washer)
CAUTION/WARNING:For the common bonding network (CBN): there is no specific recommendation to secure the cabinet.
7 mm 0.27"4 mm 0.15"
20 mm / 0.78"
15 mm / 0.59"
40 mm / 1.57" Maxi
BushingWasher
SpecificIBNIsolated
01 02 03
05
AdjustableFoot (isolated)
FrameBase
Specific
BushingWasher
Isolated
Univity UMTS iBTS Indoor 2 Site Specifications / 51
July 25, 2003 Method 06-9434
Figure 31 – iBTS Indoor 2 - Adaptation Foot Print Panel (Optional)
All dimension are expressed in millimeters.Figure 32 – Adaptation Foot Print Panel General View (Optional)
600 mm
102.
5
24.8
566.5
BACK
FRONT
0
497.
5
492
108
00
99
183
343
427
500.75
566.5
32.5
567.
5
32
38
50892
8838
M10x40
52 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 33 – Example of the Adaptation Foot Print Panel Used with an IBN Solution
The anchor template of the main frame is given in the Figure 34 and Figure 35.
Isolated
100mmCONCRETE FLOOR
M10M12
4"
5
6
7
8
3
1 24
For the numberrefer to the table: Anchor kit - List of Materiels
Univity UMTS iBTS Indoor 2 Site Specifications / 53
July 25, 2003 Method 06-9434
Figure 34 – iBTS Indoor 2 Drilling Template
Figure 35 – iBTS Indoor 2 - Anchor Hole Template
The iBTS Indoor 2 is secured with 4 bolts M12 or 4 anti-seismic bolt.(Figure 36).
There are 4 adjustable feet (with hexagonal key).
600
395102.524.8
476 600
535
BACK
FRONT
32.5
Anchorhole
2 adjustable feet
2 adjustable feet
54 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
A specific anchor kit is an option of the cabinet and is defined in the IM 10-9400 Univity UMTS iBTS Indoor 2 IRM Kits (Ancillaries) Definition - CE Compliant Only.
This anchor kit requires drilling into the concrete floor to a depth of 100mm (3.9in). Refer to Figure 36.
4.5.1.1 iBTS Indoor Installed on the Concrete floor
If the iBTS is installed on the floor, holes are drilled in the floor using the Hold-down given below (see Figure 36), then the iBTS is positioned in its final location and anchored to the floor.
Figure 36 – iBTS Indoor 2 - 1/4 Anchor Kit
Table 20 – Anchor Kit - List of Materials
ITEM QTY/ iBTS DESCRIPTION
01 4 Threaded Full Bolt M12x150
02 4 Nut Hex Head M12
03 4 Flat Washer
04 4 Square Plate
05 4 Anchor Sleeve M12 x 38
06 4 Collapsible Sleeve for M12
07 4 Anchor Expanding Sleeve M12
08 4 Anchor Cone M12
01 02 0304
05
07
08
FrameBase
O 17mm
CONCRETEFLOOR
100mm
AdjustableFoot (isolated)
06
Univity UMTS iBTS Indoor 2 Site Specifications / 55
July 25, 2003 Method 06-9434
4.5.1.2 iBTS Indoor Installed on a Raised Floor
If the iBTS is installed on a frame support it is absolutely necessary to place a support under the foot step in order to avoid overhang problem (see Figure 37) and if necessary reinforce the cabinet’s bottom.
Figure 37 – Example of Raised Floor
Only in case of a raised floor installation, the installer must supplies these following parts to the initial Anchor Kit (See Table 21).
4.5.1.3 iBTS Indoor secured by the wall or the top
The iBTS Indoor 2 cabinet can be secured on the wall or by the top with a metallic bar or a threaded rod.(see Figure 38 and Figure 39).
Table 21 – Raised Floor Supplies
PEC/CPC Qty. Description
4 Threaded Rods (M12) according to the raised floor
8 Hex Nuts (M12)
8 Plate Washers
01 02 0304iBTS Indoor 2 Adjustable
Foot (Isolated) Frame
Raised floor Plate washerHex Nut
Access floor Pedestal
Only in case of raised
must supplythese parts to the initial Anchor Kit (see Table 20)
floor, the installer
07
08 O 17mm
CONCRETEFLOOR
100mm06
05
56 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 38 – iBTS Indoor 2 - Top Holes Securing
Figure 39 – Example of Wall or Top Securing
4.5.2 Cable Tray and Cable Routing
The cable distribution in the cable tray is shown in the Figure 40, Figure 41 & Figure 42.
The cable tray is dimensioned according to the site configuration.
The cable tray allows the cables routing, PCM, - 48V or +24V if used, ground cables, feeder jumpers, inter-cabinet cables and ensures the equipotentiality with 35mm² (2AWG) braids.
The cable tray is located under the ceiling. It is connected to the ground plate (see Figure 40 & Figure 41).
CAUTION/WARNING:Only in case of IBN installation the iBTS Indoor 2 must be isolated from the floor and from the wall or Top.
Top holes securing O 11mm1630mm
200mmmiddle
Not supply
By the top with metallic bar or with threaded rod
Univity UMTS iBTS Indoor 2 Site Specifications / 57
July 25, 2003 Method 06-9434
Figure 40 – Cable Tray Equipotential
Figure 41 – Cable Tray Cross Section
The power supply and the ground connections are wired on the top of the cabinets (see Figure 42).
35mm² (2AWG)
Warning:Metallic partition between RF, low current (data) and high current (power supply)
Cable tray
Feeders Jumpers
AC cables &
(if required)GND cables
PCM &Alarmcables
-48V cables &GND cables
58 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 42 – DC Power Supply
The inter-cabinet data cables routing is also performed at the top of the cabinets.
The separation between low and high voltages cables is performed as follows:
• By using different cable trays,
• Or by using one cable tray with partition separator (see Figure 40 and Figure 41),
• Or by using one cable tray and shielded cables connected to the ground at both sides.
(Refer to "4.6 Site Wiring")
Table 22 – Cable Quantity for the Maximum Configuration
Items Quantity / Cabinet Type of Voltage
8 twisted pairs PCM cable 1 Telecommunication network voltage
Alarm cable 1 or 2 Extra low voltage
DC Power supply cable 2 (if -48Vdc)or 4 (if +24Vdc) Primary voltage DC
Ground cable 1 Ground
RF jumpers (according to site configuration). 2 to 6 RF signal
2 cabinet
35mm² (2AWG)
Univity UMTS iBTS Indoor 2 Site Specifications / 59
July 25, 2003 Method 06-9434
All the external cables (except the PCM cable) are defined in an optional kit.
• PCM cable T1 or E1 could be delivered with the iBTS Indoor 2.
• External Alarms cables are delivered with the optional External Alarms kit.
• DC and Ground cables can be delivered as an option. For more detail, refer to IM 10-9400 Univity UMTS iBTS Indoor 2 IRM Kits (Ancillaries) Definition - CE Compliant Only.
• RF Jumper can be ordered separately. For more detail, refer to Table 39 – Example of the Jumpers Characteristics For the Radio Link Optimized.
4.5.3 Earth Plate Preparation
The earth plate is installed systematically on each site, all the site grounding circuits are connected to it:
• Cabinet to grounding via a 35mm² (2 AWG - green/yellow)
• Antenna feeder grounding kitsFigure 43 – Bonding and Grounding Requirements
A ground plate, available in the room, is directly connected to the earth plate of the building. Its dimension must allow 10 or 20 ground connections respectively according to the compression lug with 1 or 2 holes.
-48Vdc
0V
Earth
ElectronicEquipment
EMI compartment
CABINET
Mains Distribution
0V -48V
DC
FILTERS
60 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
A direct connection from the building earth plate electrode and the ground plate has to be performed with a 50mm² (0.077in².1/0 AWG (with length< 50m otherwise 95mm² (0.14 in².4/0 AWG)) bar. This connection must be continuous and not removable.
The building earth plate is continuously linked to the ground electrode. The maximum impedance of the ground electrode must be less than 10 Ohms from the earth plate.
The green/yellow ground cables must be routed to the ground plate to provide the equipotentiality between each iBTS 2 cabinet and metallic part with a section of 35mm² (2 AWG) each. (See Figure 42, Figure 40 & Figure 41).
Option: For the shelters, a flat copper belt can be considered at the low level.
For isolated bonding network (IBN) the cabinet must be grounded only by one unique ground cable directly connected to the SPC site; no strap should be connected between the cabinet RTN (0V) connection and the cabinet ground.
For the common bonding network (CBN) the cabinet must be grounded by the ground cable and equipotentiality braids; the strap should be connected between the cabinet RTN (0V) connection and the cabinet ground.
Univity UMTS iBTS Indoor 2 Site Specifications / 61
July 25, 2003 Method 06-9434
4.5.4 DC Power Supply
The cabinet can be connected to 2 types of power network:
• -48Vdc: Nominal DC voltage range: -57Vdc< V < -40.5Vdc.
• +24Vdc: Nominal DC voltage range: +20Vdc< V < +31Vdc.(iBTS Indoor 2 with a DC/DC Converter)
4.5.4.1 iBTS Indoor Customer DC Power Supply Box
For a site with several cabinets, one protected power supply branch is required for each equipment installed on the site.
The DC customer box is not provided by Nortel. The location of the DC customer box must take into account the length of the cables connected to the BTS (max 16 m / 52.5ft for the cables provided with the ancillaries kit).
The DC boxes must contain an appropriate disconnect device, easily accessible by the service personnel and marked as the disconnect device for the equipment.
The cables used for powering each BTS cabinet must be able to hold at least 50 Amps (AWG 1/0), and are dimensioned according to the distance between the cabinet and the customer DC box.
The voltage drop due to cable resistance must be so that the voltage at the cabinet level is in the window given in the power supply paragraph.
The DC boxes must be dimensioned according to the connected systems characteristics. The insulated earth conductor for the product must be green/yellow.
The DC box feeding one cabinet must be dimensioned to feed one fully equipped BTS cabinet in the worst case configuration (cooling / heating on, all equipment broadcasting, max current drawn on DC plug, dc input voltage variation).
During the start-up of the climatic system, the current drawn by the BTS may be higher for a short period of time. This is why the site breaker must be time delayed.
4.5.5 -48Vdc Solution
In the -48Vdc Solution, the iBTS Indoor 2 power connection are directly connected to the DC Customer power supply box.
62 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.5.5.1 DC Electrical Distribution System of the iBTS Indoor 2 (-48Vdc)Figure 44 – DC Electrical Distribution System of the iBTS Indoor 2 (-48Vdc)
DDMDDMDDMDDMDDMDDM
FANSDIGITAL
RACK
Circuit
100A
CircuitBreaker25A
CircuitBreaker10A
EMI filtersGround Stud
Bus Bar ICO
Breaker
PA PA PA PA PA PA
Fuses
iBTS Indoor 2
-48Vdc0VGND
Univity UMTS iBTS Indoor 2 Site Specifications / 63
July 25, 2003 Method 06-9434
4.5.5.2 Consumption According to Configurations (-48V Solution)
(1) Theoretical Worst case: All transmitted powers at the maximum level and with -40.5V.
Table 23 – Maximum Consumption According to Configurations (-48V Solution)
Configurations(1) Max DC Power(W)
(-48V solution)
MCPA 30W MCPA 45W
OTOR 1 954 1136
OTSR
1 1086 1268
1R 1156 1338
2 1156 1338
BTBR 1 1333 1697
OTSR1D 1449 1883
2D 1519 1883
STSR
1 2067 2613
1R 2137 2683
2 2137 2683
3 2207 2923
1D 3226 4318
2D 3226 4318
3D 3296 4388
64 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.5.5.3 DC Power Supply -48Vdc Solution
The power supply of the iBTS Indoor 2 is -48VDC.
• iBTS Indoor in DC feed mode uses 2 cables 2AWG minimum (Safety limit according to the maximum length of 10m).
For other length or section, refer to Table 24 to choose the right cable.
*Maximum length between the DC customer power supply connection and the iBTS DC terminal power connection. Calculation based on a 1.5V voltage drop.
Location: Top of the cabinet (see Figure 51).
4.5.5.4 DC -48Vdc Power Supply Distribution
Site Without - 48 V Availability:
A specific DC power cabinet including the rectifier, the storage and the distribution functions has to be foreseen for - 48 V supply.
A 0V reference cable (RTN Cable) should link the (+) terminal of the power supply to the ground.
Site With - 48 V Availability:
The iBTS Indoor 2 is not provided with a main disconnect device. Therefore, an appropriate disconnect device has be provided as part of the building installation by the operator.
The location of this customer connecting box and the length of the cables (max 16m (52.5ft) for the cables provided with the IRM kit, see Table 24 and IM 10-9400 Univity UMTS iBTS Indoor 2 IRM Kits (Ancillaries) Definition - CE Compliant Only) should be taken into account.
Table 24 – Cable’s Section According to the DC Power Supply Mode (-48Vdc)
Cable Section
Maximum Length* (meter/foot)
-48Vdc Protection: 1x120A
AWG mm² m ft
4 25 Not allowed (Minimum Safety Limit)
2 35 11 36
1/0 50 15 49
2/0 70 23 75
Univity UMTS iBTS Indoor 2 Site Specifications / 65
July 25, 2003 Method 06-9434
Note: If IRM kit is used the cabling path distance between the power supply box and the cabinet (4.6 Site Wiring) should not exceed 16 m (52.5ft), otherwise a deported power supply box must be installed or refer to Table 24.
The disconnect device should be near the equipment, easily accessible by the service personnel, and clearly identified.
The acceptable variations in the input voltage of the equipment, under normal operation, range from - 40.5Vdc to - 57Vdc.
In the DC power cabinet dedicated to the site, one output supply is required for each equipment installed on the site. Each protection has to identify the unit that is protected by fuse or breaker unipolar.
Power supply cables must be labeled (see "4.6.4 External Cables Marking").
Table 25 – Protection Requirements for the iBTS Indoor 2 (-48V solution)
iBTS Indoor 2 Radio cabinet OTSR 1/2/1D/2D STSR 1/2/3 STSR1D/2D/3D
Fuse rate (Slow Blow) protection(Standard Value) 65A 80A 120A (worst case)
number of fuse per cabinet 1
66 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.5.6 +24Vdc Solution
The +24Vdc Solution use a DC/DC Converter (+24Vdc/-48Vdc) connected between the iBTS Indoor 2 power connection and the DC customer power supply box.
4.5.6.1 DC Electrical Distribution System of the DC/DC Converter (+24Vdc)Figure 45 – DC Electrical Distribution System of the DC/DC Converter (+24Vdc)
DC/DC1
DC/DC2
DC/DC2
DC/DC2
DC/DC1
DC/DC1
Ala
rm B
oard
+24VGNDFG
+24VGNDFG
+24VGNDFG
+24VGNDFG
+24VGNDFG
+24VGNDFG
GND
-55V
GND
-55V
GND
-55V
GND
-55V
GND
-55V
GND
-55V
GND BUS
-55V BUS
DC
/DC
She
lf B
oard
Vin 1+Vin 1-Vin 2+Vin 2-Vin 3+Vin 3-
DC
out+
DC
out-
Input Range+20Vdc to +31Vdc
Input Range+20Vdc to +31Vdc
Input Range+20Vdc to +31Vdc
Input +24Vdc FaultOutput -55Vdc Fault
Major AlarmMinor Alarm
Slot 1
Slot 2
Slot 3
Slot 4
Slot 5
Slot 6
iBTS
Indo
or 2
Sid
e
DC
Cus
tom
er P
ower
Sup
ply
Side
DC/DC Converter
iBTS
Indo
or 2
Sid
e
Univity UMTS iBTS Indoor 2 Site Specifications / 67
July 25, 2003 Method 06-9434
4.5.6.2 Consumption According to Configurations with the DC/DC Con-verter (+24V Solution)
(1) Theoretical Worst case: All transmitted powers at the maximum level and with +20V.
4.5.6.3 DC Power Supply +24Vdc Solution
The power supply of the iBTS Indoor 2 with a DC/DC converter is +24VDC.
• iBTS Indoor in "Dual" DC feed mode uses 4 cables 2AWG minimum (Safety limit according to the maximum length of 8m for the DC/DC Converter with 2 Converters Modules).
Table 26 – Maximum Consumption According to Configurations with the DC/DC Con-verter (+24V Solution)
Configurations
(2) Theoretical Max DC Power(W) with The DC/DC Converter (+24V solution)
MCPA 30W MinimumNumber ofConverter
MCPA 45W MinimumNumber ofConverter
OTOR 1 1477 1 1477 1
OTSR
1 1477 1 1477 1
1R 1477 1 1477 1
2 1477 1 1477 1
BTBR 1 1477 1 2954 2
OTSR1D 1477 1 2954 2
2D 2954 2 2954 2
STSR
1 2954 2 2954 2
1R 2954 2 2954 2
2 2954 2 2954 2
3 2954 2 2954 2
1D 4432 3 4432 3
2D 4432 3 4432 3
3D 4432 3 4432 3
CAUTION/WARNING:It is a dual feed without customer DC power redundancy, only intended to reduce the section and to route the cable easily.
68 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
For other length or section, refer to Table 27 to choose the right cable or Appendix B – Cable Size.
*Maximum length between the DC customer power supply connection and the DC/DC Converter terminal power connection. Calculation based on a 1.5V voltage drop.
Location: Behind the DC/DC converter (see Figure 17).
Table 27 – Cable’s Section According to the DC Power Supply Mode (+24Vdc)
DC/DC Converter with 2 Converters Modules
Dual feed (2 x 24Vdc and 2 x 0V)Cable Section
Maximum Length* (meter/foot)
+24Vdc Protection: 1x150A
AWG mm² m ft
4 25 Not allowed
2 35 8 26.2
1/0 50 12 39.4
2/0 70 18 59
DC/DC Converter with 3 Converters Modules
Dual feed (2 x 24Vdc and 2 x 0V)Cable Section
Maximum Length* (meter/foot)
+24Vdc Protection: 1x250A
AWG mm² m ft
2 35 Not allowed
1/0 50 8 26.2
2/0 70 12 39.4
DC/DC Converter with 3+1 (redundancy) Converters Modules
Dual feed (2 x 24Vdc and 2 x 0V)Cable Section
Maximum Length* (meter/foot)
+24Vdc Protection: 1x250A
AWG mm² m ft
4 50 Not allowed
2/0 70 11 36
Univity UMTS iBTS Indoor 2 Site Specifications / 69
July 25, 2003 Method 06-9434
4.5.6.4 DC +24Vdc Power Supply Distribution
Site Without +24 V Availability:
A specific DC power cabinet including the rectifier, the storage and the distribution functions has to be foreseen for +24 V supply.
The DC/DC converter above the iBTS Indoor 2 is used in case of +24Vdc supply.
A 0V reference cable (RTN Cable) should link the terminal of the power supply to the ground.
Site With +24 V Availability:
The iBTS Indoor 2 is not provided with a main disconnect device. Therefore, an appropriate disconnect device has be provided as part of the building installation by the operator.
The location of this customer connecting box and the length of the cables (max 16m (52.5ft) for the cables provided with the IRM kit, see Table 27, Appendix B – Cable Size and IM 10-9400 Univity UMTS iBTS Indoor 2 IRM Kits (Ancillaries) Definition - CE Compliant Only) should be taken into account.
Note: If IRM kit is used the cabling path distance between the power supply box and the cabinet (4.6 Site Wiring) should not exceed 16 m (52.5ft), otherwise a deported power supply box must be installed or refer to Table 27.
The disconnect device should be near the equipment, easily accessible by the service personnel, and clearly identified.
The acceptable variations in the input voltage of the equipment, under normal operation, range from +20Vdc to +31Vdc.
In the DC power cabinet dedicated to the site, one output supply is required for each equipment installed on the site. Each protection has to identify the unit that is protected by 1 fuse or 1 breaker bipolar.
Here it’s a dual feed without customer DC power redundancy, only intended to reduce the section and to route the cable easily, then there is only one breaker dedicated to this iBTS Indoor 2 cabinet.
Inform the project supervisor if DC power engineering does not conform to these specifications.
70 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Power supply cables must be labeled (see "4.6.4 External Cables Marking").
4.5.7 DF for PCM Connection
The iBTS Indoor 2 is not connected directly to the telecommunication network, but by means of a DF. This DF is a connection point between the PCM cable from the iBTS, and the transmission network. Refer to Figure 49 – Example of DF for PCM and Alarm Cables. A DDF must be grounded.
For isolated bonding network (IBN) the PCM screens cable and pairs are connected to the ground on one end only (equipment side).
For the common bonding network (CBN) the PCM screens cable and pairs are connected to ground on both ends (equipment and DDF sides).
There are two major cases for the connection to the PCM link:
• Or the telecommunication network is 120 Ω E1 or 100 Ω T1, in that case the only equipment necessary to ensure the PCM connection between the DF and the iBTS is the PCM cable.
• Or the telecommunication network is E1 75 Ω, in that case, as the iBTS works in 120Ω, it is necessary to ensure an adaptation from the iBTS’s 120 Ω to the customer network’s 75 Ω. As a consequence, the PCM cable should be equipped with Mini-Baluns male, and the DF should be able to receive it.
1 type of cable is supplied according to the site configuration E1 or T1 :
• 8 Twisted pairs 120Ohms E1 PCM cable (+ balun 75Ω if E1 75Ω ).
• or 8 Twisted pairs 100Ohms T1 PCM cable.
Table 28 – Maximum input Current (with 2 converters modules)
+24Vdc / -55VdcConverter
@ +20Vdc @ +31Vdc
150 Amps 100 Amps
Table 29 – Protection Requirements for DC/DC Converter used for the +24V solution
+24V/-55V DC/DC Converter OTSR 1/2 OTSR 1D/2DSTSR 1/2/3 STSR1D/2D/3D
Number of Converters Modules 1 2 3 3+1(redundancy)
Converter Feeder +24V Breaker Size Protection
(Standard Value)80 Amp 150 Amp 250 Amp 250 Amp
Number of breaker per cabinet 1
Univity UMTS iBTS Indoor 2 Site Specifications / 71
July 25, 2003 Method 06-9434
The maximum recommended cabling path distance between the iBTS Indoor 2 cabinet and the DDF is < 16m (52.5ft) with the IRM kit.
(Standard length of the cables provided with the cabinet)
The maximum distance of the cabling path between the cabinet and the transmission equipment should not exceed the value listed in Table 30:
Note: For an E1 75Ohms configuration, the adaptation 120/75Ohms (balun 75Ohms, see Figure 48) should be secured as close as possible to the specific distribution frame (see Figure 46 and Figure 47) and with heat shrink (customer supply).
A surge arrestor must equip each input.Figure 46 – Example of Distribution Frame Installation
Table 30 – Maximum Distance Between the Cabinet and the DDF
D max (m) (ft) Section
E1 120Ohms 150 492 24AWG
T1 100Ohms 150 492 24AWG
E1 75Ohms 70 229 Not used
72 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 47 – Example of Adaptation 120/75Ohms with Balun and LPPCM Box
There are 3 types of mini Balun connector described in Figure 48.Figure 48 – Example of Balun Adaptor 120/75 Ohms
4.5.8 DF for External Alarm Connection
The iBTS Indoor 2 is not connected directly to the supervised equipment, but by means of a DF. This DF is a connection point between the alarm cable from the iBTS, and the supervised equipment (for example smoke detector). Refer to Figure 49 – Example of DF for PCM and Alarm Cables.
A specific Alarm distribution frame should be considered. It should be grounded.
For isolated bonding network (IBN) the alarm screens cable and pairs are connected to the ground on one end only (equipment side).
For the common bonding network (CBN) the alarm screens cable and pairs are connected to the ground on both ends (equipment and DDF sides).
TX1
RX2
BalunConnectorMale
Towards DDFiBTS Indoor 2
Example of adaptation120/75 Ohms with balun
RXnLPPCM box
......
..
Customer DDFExample ofNortel Supplies
Heat shrinkCable 120Ohms16 pairs 16m (52.5ft)
D-SubConnector
BNC 1.6-5.6 SMZ Type 43
75 OHMS/BNC 75 OHMS/1.6-5.6 75 OHMS/ SMZ TYPE 43Ref PEC / Ref CPC Ref PEC / Ref CPC Ref PEC / Ref CPCNTQG41GA / A0830902 NTUM98LA / A0841462 NTUM98YA / A0853655
Univity UMTS iBTS Indoor 2 Site Specifications / 73
July 25, 2003 Method 06-9434
Figure 49 – Example of DF for PCM and Alarm Cables
4.5.9 Lighting and Service Socket
The lighting in the room must have intensity, measured before the equipment installation, of 300 Lux at 1 m (3.3ft) above the floor. The maximum acceptable value is 500 Lux. The lamps should be electronic ballast.
A service socket network should be provided with the room. An outlet should be available about every 3 m (9.8ft).
The sockets equipped with 2 poles and a ground pin equipotentialized to the site ground and dimensioned according to the local rules, are located at 0.30 m (11.8in) from the floor.
The ground of the sockets is the same as the ground of the equipment network.
4.5.10 Ventilation or Air Conditioning
A forced convection system will be used to cool the iBTS Indoor 2, with a cooling unit pushing air through the shelves. The iBTS Indoor 2 can operate reliably when the ambient temperature is between O°C and 40°C.
Blowers shall have 2 speed set-point values either "nominal" or "maximum," dependant on operational environmental temperature conditions.
PCM Part
Alarm Part
74 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
The worst-case thermal load occurs when 45W RF PAs are used, and when the digital and MCPA shelves are fully populated. In this case, the expected total heat dissipation in the flow path is 3860W.
In case of dusty premises, the ventilation system must be equipped with a filter which complies with [R2] and for which maintenance is periodically performed.
The temperature gradient inside the premises must comply with the recommendation for operating conditions (refer to [R2]).
The minimum air exchange with iBTS Indoor 2: 1250m3/hour (44143ft²/hour) per iBTS Indoor 2.
4.5.11 High-Voltage Protector
The external ports of the equipment (power supply, data, antennas, etc.) must be protected according to the current safety instructions.
4.5.12 Lightning Protection
All the site must be protected against direct lightning strikes.
The site must be equipped with a lightning conductor on top.
Table 31 – Blowers speed set-point values of the iBTS Indoor 2
Inlet air temperature
T<35°C T>35°C
No fan failed 550m3/hNominal speed
700m3/hMaximal speed
1 fan failed 700m3/h Maximal speed
Table 32 – The Maximal Dissipation
PA Shelf (6 x 45W RF PAs) 3000W
Digital Shelf (fully populated) 810W
Cooling unit 50W
DDMs dissipation (6x25W) 150W
Cables & other dissipation in working (miscellaneous frame) 440W
Total iBTS dissipation (max theoretical) 4300W 5200VA
Univity UMTS iBTS Indoor 2 Site Specifications / 75
July 25, 2003 Method 06-9434
For lightening protection it is important that the radio lines from the antennas to the cabinet are regularly grounded with dedicated grounding kits. (refer to Figure 50).
Figure 50 – Lightning Protection on Feeders
Note: In case of TMA are employed, the site should be equipped with specific surge arrestor as "gaz tub" in order to avoid short circuit between the inner and outer connector of feeder (the TMA is supplied in DC voltage thanks to its RF cables).
4.5.13 Feeders
Feeders are used to establish the link between the iBTS Indoor 2 cabinets and the antennas or TMAs.
The feeders are located on the top left or right of the radio cabinet, ready to be connected to the jumpers.
It is recommended to use the jumpers between the iBTS and feeders.
A female 7/16 connector equips each feeder end.
In case of site with dual band configuration, label the feeders with a specific marking for each frequency band.
The position of the antenna feeders must respect the bending radius of the cable and of the antenna jumpers.
On the iBTS side, the feeders should arrive as close as possible to the iBTS Indoor 2 cabinet mounting location.
The number of feeders depends on the configuration type. (refer to IM 04-9405 Univity UMTS iBTS Indoor 2 Cabling Referential) in order:
• To allow an easier installation: depends on the size of feeder used, it might be very difficult to position correctly the feeder in front of the RF connector on BTS side.
76 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
• To avoid excessive efforts on the RF connector on the BTS side: risk to damage the connector and potential waterproofing issue with the time.
• To allow easier maintenance operation.
The Cable used for feeder should have a maximum attenuation of 6.99dB/100m at 2300Mhz. Couple connector losses = 0.2dBmax.
In all cases, network designer must be informed about the end to end attenuation measured at the end of the installation: it might be necessary to modify parameters at the OMC-R.
4.5.14 Antennas
The customer must foresee and install the antennas and the feeders. The antennae are installed in compliance with the radio engineering studies by trained staff.
The UMTS iBTS Indoor 2 could used TMA, refer to "4.2.5.3 TMA Equipment (Optional)".
4.6 Site Wiring
4.6.1 IBTS Indoor External Connectors
The external connections are done on the top of the iBTS cabinet:
• on the top right: -48V; 0V Return; GND; Equipotentiality, External Alarms 1 and 2.
• on the top left: RF jumpers, Iub link (IUB1).
The PCM cable (E1 120Ohms or T1 100Ohms) is always delivered with the iBTS Indoor 2.
All the other external cables required to connect the iBTS Indoor 2 are provided in an optional's kit delivered separately.(see IM 10-9400 Univity UMTS iBTS Indoor 2 IRM Kits (Ancillaries) Definition - CE Compliant Only, Figure 48 and Figure 51).
Table 33 – Example of the Feeders Characteristics For the Radio Link Optimized
Length Maximum Feeders (50 Ohms) Characteristics Minimum Single
BendingAttenuation Max.
(connector included)
35 m (114.83 ft)LDF5P-5A-42 or the
equivalent 6.99dB/100m at 2300Mhz
7/8 " 250 mm (9.8 in)
at 2300Mhz2.44+0.2 = 2.64dB
at 2000Mhz2.24+0.2 = 2.44dB
Univity UMTS iBTS Indoor 2 Site Specifications / 77
July 25, 2003 Method 06-9434
Figure 51 – External Top Connection of the iBTS Indoor 2
Table 34 – Type of External Connectors
Terminal Number Type of connector (BTS side)
Equipotentiality point 2 Top holes wall securing ∅ 11mm
-48Vdc DC Power 1 Stud ∅ M8
0V Return DC Power 1 Stud ∅ M8
GND 1 Stud ∅ M8
PCM (IUB1 and IUB2) 1 or 2 D-Sub 37 pin (female contact)
External Alarms (1 and 2) 2 D-Sub 25 pin (female contact)
RF 2 up to 12 7/16 female
On the DC/DC Converter if used
Terminal Number Type of connector (BTS side)
+24Vdc DC Power 2 +24Vdc Terminal Lugs Double holes ∅ M8
0V Return DC Power 2 Terminal Lugs Double holes ∅ M8
GND 1 Stud ∅ M8
LPPCM (optional)
PCM PCMOut
PCMOutIn
GND
GND 0V -48V
Fiber
IUB 1
IUB 2
RFExtensionRF
D
M
D
M
M
D
D
D
Div.
Main
M
M
External Alarms 1
4x hoisting rings (M10)
Internal Alarm Bus Out
Internal Alarm Bus InExtension PRIVATE ALARM
GPSAMGPS 2
GPSAMGPS 1
External Alarms 2
BUS
Alpha
Alpha
Beta
Beta
Gamma
Gamma Delta
Zeta
Epsilon
Epsilon
Delta
Zeta
78 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.6.2 iBTS Indoor External Cables
4.6.2.1 Power Cables
For the physical installation and wiring of the iBTS Indoor 2, all the cables, except the PCM cable are defined in an optional kit.
Ground plate must be supplied by the customer.
• The DC (-48Vdc) power cables are optional. (refer to Table 35 and IM 10-9400 Univity UMTS iBTS Indoor 2 IRM Kits (Ancillaries) Definition - CE Compliant Only)
Note: *-48Vdc and 0V Return (example: type H07 RN)
• The DC (+24Vdc) power cables are optional. (refer to Table 36 and IM 10-9400 Univity UMTS iBTS Indoor 2 IRM Kits (Ancillaries) Definition - CE Compliant Only)
The site ground cable shall have the same size as the input cables.
4.6.2.2 Alarm Cables
• The 2 External Alarms cables (NTBY6102) are supplied with the optional External Alarm kit. (refer to Table 37 and Figure 6)
Table 35 – Example of the DC (-48Vdc) Power Cables (if IRM kit - CE Compliant used)
PROVIDING CABLES mm² AWG Length (ft) CABLES CONNECTORS
DC CABLE DC Standard (2 cables)* 50 1/016m 52.5
Pre-connectorized on BTS side with lugs
8mmGROUNDING
CABLE green/yellow (1cable) 50 1/0
Table 36 – Example of the DC (+24Vdc) Power Cables (if IRM kit - CE Compliant used)
PROVIDING CABLES mm² AWG Length (ft) CABLES CONNECTORS
DC CABLE DC Standard (4 cables) 70 2/016m 52.5
Pre-connectorized on BTS side with lugs
8mmGROUNDING
CABLE green/yellow (1cable) 70 2/0
Table 37 – External Alarms Cables
PROVIDING CABLES mm² AWG Length (ft) CABLES CONNECTORS
2 x Alarm CABLES 12 Twisted pairs (ex: SYT1) 0.25 24 16m 52.5 D-sub 1x25 pins male
Univity UMTS iBTS Indoor 2 Site Specifications / 79
July 25, 2003 Method 06-9434
4.6.2.3 PCM Cables
• The PCM cable is always supplied with the iBTS indoor and has always these characteristics (refer to Table 38).
For PCM cable and Alarm cable: the symmetrical pair will be screened. The screen or the outer conductor of the coaxial cable shall be connected to the earth at the output port of the iBTS and provision shall be made for connecting the screen to earth at the input port if required and according the IBN or CBN network (refer 4.5.7 DF for PCM Connection and 4.5.8 DF for External Alarm Connection).
4.6.2.4 RF Jumpers
The RF jumpers are optional. The iBTS Indoor 2 should be connected to the feeders via RF jumpers, the minimum bending radius must comply with the height of the space available above the iBTS Indoor 2 cabinet.
The jumper connector to plug into the iBTS Indoor 2 radio bulkhead must be straight, Male, DIN 7/16 for a key 32mm (hexagonal head).
Example of available jumpers lengths: these Jumpers are orderable.
Table 38 – The PCM Cable With LPPCM Module
PROVIDING CABLES mm² AWG Length (ft) CABLES CONNECTORS
PCM CABLE
8 Twisted pair120Ohms(ex: L904) 0.25 24 16m 52.5
Pre-connectorized on the LPPCM side with
a 37 pins D-Sub8 Twisted pair100Ohms
Table 39 – Example of the Jumpers Characteristics For the Radio Link Optimized (Page 1 of 2)
Length/Reference Jumpers (50 Ohms) Characteristics
Minimum Single
Bending
Attenuation Max. (connector included)
1.5 m (4.9 ft)NTUM97JA
LDF4-50A-42 or the equivalent 12.2dB/100m at 2300Mhz rigid foam 125 mm (5 in)
at 2300Mhz0.183+0.2 = 0.382dB
at 2000Mhz0.168+0.2 = 0.368dB
80 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.6.3 Connection to the Aerial RF Part
The use of jumpers on each side of the feeder (BTS/feeder and Feeder/antenna or Double TMA 2100 MHz or Single TMA 1900 MHz) is recommended when using LDF or FSJ type of feeder.
2 m (6.5 ft)NTUM97MA
FSJ4-50B or the equivalent18.8dB/100m at 2300Mhz
½" superflex
32 mm (1.26 in)
at 2300Mhz0.376+0.2 = 0.576dB
at 2000Mhz0.346+0.2 = 0.546dB
3 m (9.8 ft)NTUM97KA
FSJ4-50B or the equivalent18.8dB/100m at 2300Mhz 32 mm (1.26 in)
at 2300Mhz0.564+0.2 = 0.764dB
at 2000Mhz0.519+0.2 = 0.719dB
Table 40 – Peculiarities of RF Links for Jumpers or Feeders (Connectors + Cables)
Characteristics Specifications
Frequency Range DC - 2300 Mhz
Impedance 50 Ohms
Return Loss -25dB
Isolation From 880 Mhz to 2200 Mhz: -100 dB
IMD -120 dB for two tones at +43 dBm
Table 39 – Example of the Jumpers Characteristics For the Radio Link Optimized (Page 2 of 2)
Univity UMTS iBTS Indoor 2 Site Specifications / 81
July 25, 2003 Method 06-9434
Figure 52 – Example of RF Link with UMTS 2100MHz Double TMA
Figure 53 – Example of RF Link with UMTS 1900MHz Single TMA
MainAntenna
DivAntenna
Feeder 7/8" (35m)
Jumper1.5m
Jumper1.5m
Jumper2m
MAIN PATH DIV PATH
Double TMAUMTS 2100 MHz
Hatch
Plate
Minimum singlebending radius
125mm
125mm
250mm
32mm
50Ohms
Double TMADouble TMA
S1 S2 S3Univity UMTS iBTS Indoor 2
MainAntenna
DivAntenna
Feeder 7/8" (35m)
Jumper1.5m
Jumper1.5m
Jumper2m
MAIN PATH DIV PATH
Hatch
Plate
Minimum singlebending radius
125mm
125mm
250mm
32mm
50Ohms
SingleTMA
SingleTMA
SingleTMA
SingleTMA
SingleTMA
SingleTMA
UMTS 1900MHz
S1 S2 S3Univity UMTS iBTS Indoor 2
82 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Figure 54 – Example of RF Link without UMTS TMA
S1 S2 S3
Univity UMTS iBTS Indoor 2
Feeder 7/8" (35m)
Jumper1.5m
Jumper2m
MAIN PATH DIV PATH
DoubleUMTS TMA
DoubleUMTS TMA
DoubleUMTS TMA
DivAntenna
MainAntenna
Hatch
Plate
Minimum singlebending radius
125mm
250mm
32mm
50Ohms
Univity UMTS iBTS Indoor 2 Site Specifications / 83
July 25, 2003 Method 06-9434
4.6.4 External Cables Marking
Note: Each sector is identified by a map label (Main 1 or A, Div 1 or A, Main "n", Div "n"), and the feeders available close to the iBTS Indoor 2 by a RED (1), a BLUE (2) or a GREEN (3) sticker.
They should be marked: Tx/Rx Main, Tx/Rx/Div, Tx, Rx.
Note: In the US, each sector is identified by a Greek letter (Alpha, Beta, Gamma), and the feeders available close to the BTS bear a RED (Alpha), a BLUE (Beta) or a GREEN (Gamma) sticker.
They should be marked : Tx/Rx Main, Tx/Rx/Div, Tx, Rx.
Table 41 – External Cables Marking
Function Labeling
PCM 120Ohms Base cab. / PCM 120Ohms
PCM 120/75Ohms Base cab. / PCM 120/75Ohms
PCM 100Ohms Base cab. / PCM 100Ohms
Sector j Main Reception / Transmission Antenna / type of band (UMTS)
Sect j Main Tx/Rx / UMTS
Sector j Diversity Reception Antenna / type of band (UMTS)
Sect j Div Rx / UMTS
Sector j Diversity Reception / Transmission Antenna / type of band (UMTS)
Sect j Div Tx/Rx / UMTS
Cabinet k DC Standard -48V or 0V Cab k DC -48V or 0V
Cabinet k DC Standard +24V or 0V Cab k DC +24V or 0V
Cabinet k Protective Ground Cab k GND
84 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
4.7 Final State of PreparationThe site preparation does not include the aerial system installation.
The different external interfaces to the equipment (ground plate, -48V or +24V power supply cabinet, transmission distribution frame) are installed and dimensioned in compliance with iBTS Indoor 2 site specification.
The installation plan (cabinets layout, physical interfaces location, cable trays) as well as the conditions to access the site are defined in the site preparation and installation document.
The following operations in compliance with iBTS Indoor 2 site specification have been performed:
• A well-dimensioned cable tray is installed and grounded.
• A ground plate is connected to the earth skins.
• The circuit impedance and the continuity are checked and recorded.
• A power supply output is available for each cabinet (breaker off).
• A PCM distribution frame is installed and grounded.
• An alarm distribution frame is installed and grounded.
• The BTS premises are equipped with lighting and service socket.
All external cables are ready to be connected to the cabinet and labeled.
Univity UMTS iBTS Indoor 2 Site Specifications / 85
July 25, 2003 Method 06-9434
5.0 References
Document Number Title
[R1] IEC 364 Electrical installation of buildings
[R2] IEC 721-3-3 Classification of groups of environmental parameters and their severity. Stationary use at weather protected locations: classes 3
[R3] IEC 721-2-6 Classification of Environmental Conditions. Part2 : Environmental Conditions Appearing in Nature-Earthquake Vibration and Shock : Level 3
[R4] ISO 7779 Acoustics - Measurement of Airborne Noise Emitted by Computer and Business Equipment
[R5] Bellcore GR 63-CORE
Network Equipment - Building System (NEBS) requirements. Physical protection.
[R6] UL 1950 CSA C22.2 950 IEC 60950
Safety of information technology equipment including electrical business equipment
[R7] ETS 300 019-1-1 Classification of environmental conditions – Storage: Class 1.2
[R8] ETS 300 019-1-2 Classification of environmental conditions Transportation: Class 2.2
[R9] ETS 300 019-1-3 Classification of environmental conditions Acoustic Noise: Class 3.2
IM 08-9307 UMTS Instruction for Installation of 2100MHz
IM 08-9297 UMTS Instruction for Installation of 1900MHz Single TMA
241-7401-240 Passport 7400 Hardware Installation, Mainte-nance and Upgrade
241-7401-200 Passport 7400 Hardware Description
241-7401-242 Passport 7400 Cabling Specification
86 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
6.0 Appendices
Appendix A – Equivalent between AWG and mm
Table 42 – AWG and mm²
Standard American Size Equivalent Metric Nearest Standard Metric Size
24 0.205 0.2
22 0.324 0.35
20 0.519 0.5
18 0.823 1
16 1.31 1.5
14 2.08 2.5
12 3.31 4
10 5.26 6
8 8.37 10
6 13.3 16
4 21.15 25
2 33.62 35
1/0 53.49 50
2/0 67.43 70
3/0 85.01 95
4/0 107.22 120
Univity UMTS iBTS Indoor 2 Site Specifications / 87
July 25, 2003 Method 06-9434
Appendix B – Cable SizeFigure 55 – Cable Size Graph for 0.25 Voltage Drop (One way)
88 / Univity UMTS iBTS Indoor 2 Site Specifications
Method 06-9434 July 25, 2003
Appendix C – Abbreviations and Terms
AbbreviationsA Ampere ISO International Standard Organization
ATM Asynchronous Transfer Mode MDM Multi-service Device Management
AWG American Wire Gauge MCPA MultiCarrier Power Amplifier
BIP Breaker Interface Panel NEBS Networks Equipment Building System
BTBR Bisector Tx Bisector Rx OMC-B Operation & Maintenance Center for Node B
BTS Base Station Transceiver Subsystem OMC-R Operation & Maintenance Center for Radio
BNC Bayonet Neil Councilman connector OTBR Omnisector Tx Bisector Rx
CEC Canadian electrical code part I OTOR Omnisector Tx Omnisector Rx
CEM Channel Element Module OTSR Omnisector Tx Sector Rx
DDM Dual Duplexer Module PA Power Amplifier
DC Direct Current PCM Pulse Code Modulation
DDF Dedicated Distribution Frame RNC Radio Network Controller
E1 PCM Standard European PCM link RF Radio Frequency
EMC Electro-Magnetic Compatibility STSR Split Transmission Split Reception
GND GrouND STM Synchronous Transport Module
GPSAM GPS/Alarm Module T1 PCM Pulse Code Modulation at 1.544 MHz
GRM GSM Radio Module also called TRM in all the document
TMA Tower Masthead Equipment
TRM Transceiver Module
GSM Global System for Mobile TxRx
TransmitterReceiver
HDSL High-Bit-Rate Digital Subscriber Line UL Underwriters Laboratories
iBTS Internet Base Station Transceiver Subsystem
UMTS Universal Mobile Telecom. System
IEC International Electro-technical Committee
UTRAN UMTS Terrestrial Radio Access Network
IP Interco Panel V Volt (Vdc with DC) or (Vac with AC)
IRM Installation Rating Material Vrms Volt root mean square
Univity UMTS iBTS Indoor 2 Site Specifications / 89
July 25, 2003 Method 06-9434
Terms
Last Page
Commissioner Person in charge of equipment commissioning
Coordinator Person in charge of coordinating the project installation
Supervisor Person in charge of supervising a site installation
Optimized operational temperature range
The temperature range prevailing in most populated areas of the world. Temperatures above and below this range, fall into areas of low population, or into the category of single time recorded extremes.
Populated Fully equipped cabinet
Depopulated Cabinet partially equipped
Total operational temperature range
The BTS operates in extreme temperatures, however:In the lower range, the electrical supply requirements of the BTS site increase.In the upper range, operating for more than 5 hours par day and for more than 72 hours per year may result in early failure of temperature dependent modules and/or components. The acoustic sound power emitted by the BTS will increase by 0.5 bels per 5°C rise above the optimized temperature upper extreme.
E1 A digital E1 PCM link carries 32 time slots at 64 Kbits/sec i.e. 2.048 Mbits/sec
T1 A digital T1 PCM link (1.544 Mbits/sec)
Node B Radio Base Station (equivalent iBTS)
lub Standard logical interface between RNC and Node B
lur Standard logical interface between RNCs
lu Standard logical interface between RNC and Core Network
Sub-D Type of connector
IBN Isolated Bonding Networks: A bonding network that has a single point of connection (SPC) to either the common bonding network or another isolated bonding network. All IBNs have a unique connection to earth via SPC.
CBN Common Bonding Network: The CBN is the principal means of performing bonding and earthing inside a telecommunication building. It is the set of metallic components that are intentionally or incidentally interconnected to form the principal BN in a building. The CBN always has a mesh topology and is connected to the grounding electrode system.
CCM CCM in this document, can indicate CCM or iCCM
CEM CEM in this document, can indicate CEM or iCEM64 or iCEM128
DDM DDM in this document, can indicate DDM2100 or DDM1900 or DDM2
MCPA MCPA in this document, can indicate MCPA2100 or MCPA1900
TMA TMA in this document, can indicate UMTS 2100MHz Double TMA or UMTS 1900MHz Single TMA.
TRM TRM in this document, can indicate TRM2100 or TRM1900 or iTRM