NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design...
Transcript of NMSU NEW ART BUILDING LAS CRUCES, NEW MEXICO · project modeled by rmkm project no. scale design...
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
MARKROHDE
NO. 1465
ST
ATE
OF NEW MEXI C
O
RE
GI S
TER E D ARCHI T
EC
T
Copyright © RMKM Architecture, P.C. 2018
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
G-000
NEW ARTBUILDINGAiM #3035
NMSU LAS CRUCES, NM
COVER SHEET
A01508
RMKM
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS1/5/2018
MYO
SHEET LISTSHEET NO. SHEET NAMEM-801B BASE BID & BID LOT 1 1ST LEVEL SPACE PRESSURIZATION PLAN - STUDIO WINGM-802B BASE BID 2ND LEVEL SPACE PRESSURIZATION PLAN - STUDIO WINGM-901 MECHANICAL 3D REPRESENTATIONS
MECHANICAL CONTROLSMI-001 MECHANICAL CONTROLS LEGENDMI-601 MECHANICAL CONTROLS DIAGRAMSMI-602 MECHANICAL CONTROLS DIAGRAMSMI-603 MECHANICAL CONTROLS DIAGRAMSMI-604 MECHANICAL CONTROLS DIAGRAMSMI-605 SEQUENCE OF OPERATIONSMI-606 SEQUENCE OF OPERATIONS (CONT.)
ELECTRICALE-001 ELECTRICAL LEGENDES-101 ELECTRICAL DEMO SITE PLANES-102 ELECTRICAL SITE PLANEL-101A BASE BID & BID LOT 1 1ST LEVEL LIGHTING FLOOR PLAN - GALLERY WINGEL-101B BASE BID & BID LOT 1 1ST LEVEL LIGHTING FLOOR PLAN - STUDIO WINGEL-102B BASE BID 2ND LEVEL LIGHTING FLOOR PLAN - STUDIO WINGEP-101A BASE BID & BID LOT 1 1ST LEVEL POWER FLOOR PLAN - GALLERY WINGEP-101B BASE BID & BID LOT 1 1ST LEVEL POWER FLOOR PLAN - STUDIO WINGEP-102B BASE BID 2ND LEVEL POWER FLOOR PLAN - STUDIO WINGEP-121A BASE BID 1ST LEVEL ELECTRICAL ROOF PLAN - GALLERY WINGEP-122B BASE BID 2ND LEVEL ELECTRICAL ROOF PLAN - STUDIO WINGFA-101A BASE BID & BID LOT 1 1ST LEVEL FIRE ALARM FLOOR PLAN - GALLERY WINGFA-101B BASE BID & BID LOT 1 1ST LEVEL FIRE ALARM FLOOR PLAN - STUDIO WINGFA-102B BASE BID 2ND LEVEL FIRE ALARM FLOOR PLAN - STUDIO WINGE-501 ELECTRICAL DETAILSE-601A ELECTRICAL DIAGRAMSE-601B ELECTRICAL DIAGRAMSE-602 GROUNDING DIAGRAME-603 LIGHTING CONTROL DIAGRAMSE-604 ELECTRICAL LIGHTING DIAGRAMSE-701 ELECTRICAL LUMINAIRE SCHEDULESE-702 ELECTRICAL LUMINAIRE SCHEDULESE-703 ELECTRICAL PANEL SCHEDULESE-704 ELECTRICAL PANEL SCHEDULESE-705 ELECTRICAL PANEL SCHEDULESE-706 ELECTRICAL PANEL SCHEDULESE-707 ELECTRICAL PANEL SCHEDULESE-708 ELECTRICAL PANEL SCHEDULESE-801 LABORATORY EQUIPMENT ELECTRICAL SCHEDULE
TECHNOLOGYT-001 TECHNOLOGY LEGENDTS-102 TECHNOLOGY SITE PLANT-101A BASE BID & BID LOT 1 1ST LEVEL TECH SYSTEMS FLOOR PLAN - GALLERY WINGT-101B BASE BID & BID LOT 1 1ST LEVEL TECH SYSTEMS FLOOR PLAN - STUDIO WINGT-102B BASE BID 2ND LEVEL TECH SYSTEMS FLOOR PLAN - STUDIO WINGT-401 ENLARGED TECHNOLOGY PLANST-501 TECHNOLOGY DETAILST-502 TECHNOLOGY DETAILST-503 AUDIO-VISUAL DETAILST-601 TECHNOLOGY DIAGRAMS
SHEET LISTSHEET NO. SHEET NAMEFX-102B BASE BID 2ND LEVEL & PENTHOUSE FIRE PROTECTION FLOOR PLAN - STUDIO
WINGFX-501 FIRE PROTECTION DETAILSFX-601 FIRE PROTECTION DIAGRAMS
PLUMBINGP-001 PLUMBING LEGENDPS-102 PLUMBING SITE PLANPL-101A BASE BID & BID LOT 1 1ST LEVEL WASTE & VENT FLOOR PLAN - GALLERY WINGPL-101B BASE BID & BID LOT 1 1ST LEVEL WASTE & VENT FLOOR PLAN - STUDIO WINGPL-102B BASE BID 2ND LEVEL WASTE & VENT FLOOR PLAN - STUDIO WINGPL-122B BASE BID PENTHOUSE LEVEL WASTE & VENT FLOOR PLANPP-101A BASE BID & BID LOT 1 1ST LEVEL PRESSURE PIPING FLOOR PLAN - GALLERY WINGPP-101B BASE BID & BID LOT 1 1ST LEVEL PRESSURE PIPING FLOOR PLAN - STUDIO WINGPP-102B BASE BID 2ND LEVEL & PENTHOUSE PRESSURE PIPING FLOOR PLANS - STUDIO
WINGPG-101B BASE BID & BID LOT 1 1ST LEVEL PIPED GASES FLOOR PLAN - STUDIO WINGPG-102B BASE BID 2ND LEVEL PIPED GASES FLOOR PLAN - STUDIO WINGP-401 ENLARGED PLUMBING PLANSP-501 PLUMBING DETAILSP-502 PLUMBING DETAILSP-503 PLUMBING DETAILSP-701 PLUMBING SPECIFICATIONSP-702 PLUMBING SCHEDULES
MECHANICALM-001 MECHANICAL LEGENDMS-101 MECHANICAL DEMOLITION SITE PLANMS-102 MECHANICAL SITE PLANMH-101A BASE BID & BID LOT 1 1ST LEVEL HVAC FLOOR PLAN - GALLERY WINGMH-101B BASE BID & BID LOT 1 1ST LEVEL HVAC FLOOR PLAN - STUDIO WINGMH-102B BASE BID 2ND LEVEL HVAC FLOOR PLAN - STUDIO WINGMH-121A BASE BID 1ST LEVEL MECHANICAL ROOF PLAN - GALLERY WINGMH-122B BASE BID 2ND LEVEL MECHANICAL ROOF PLAN - STUDIO WINGMP-101A BASE BID & BID LOT 1 1ST LEVEL MECHANICAL PIPING FLOOR PLAN - GALLERY
WINGMP-101B BASE BID & BID LOT 1 1ST LEVEL MECHANICAL PIPING FLOOR PLAN - STUDIO WINGMP-102B BASE BID 2ND LEVEL MECHANICAL PIPING FLOOR PLAN - STUDIO WINGM-301 MECHANICAL SECTIONSM-302 MECHANICAL SECTIONSM-401 ENLARGED MECHANICAL PLANSM-402 ENLARGED MECHANICAL PLANSM-403 ENLARGED MECHANICAL PLANSM-501 MECHANICAL DETAILSM-502 MECHANICAL DETAILSM-503 MECHANICAL DETAILSM-504 MECHANICAL DETAILSM-505 MECHANICAL DETAILSM-601 MECHANICAL DIAGRAMSM-602 MECHANICAL DIAGRAMSM-603 MECHANICAL DIAGRAMSM-604 MECHANICAL DIAGRAMSM-701 MECHANICAL SCHEDULESM-702 MECHANICAL SCHEDULESM-703 MECHANICAL SCHEDULESM-704 MECHANICAL SCHEDULESM-801A BASE BID & BID LOT 1 1ST LEVEL SPACE PRESSURIZATION PLAN - GALLERY WING
SHEET LISTSHEET NO. SHEET NAMEARCHITECTURALA-101A BASE BID & BID LOT 1 1ST LEVEL FLOOR & DIMENSION PLANS - GALLERY WINGA-101B BASE BID & BID LOT 1 1ST LEVEL FLOOR & DIMENSION PLANS - STUDIO WINGA-102 BASE BID & BID LOT 1 2ND LEVEL FLOOR & DIMENSION PLANS - STUDIO WINGA-111A BASE BID & BID LOT 1 1ST LEVEL REFLECTED CEILING PLANS - GALLERY WINGA-111B BASE BID & BID LOT 1 1ST LEVEL REFLECTED CEILING FLOOR PLAN - STUDIO WINGA-112 BASE BID 2ND LEVEL & PENTHOUSE REFLECTED CEILING PLANA-121 BASE BID & BID LOT 1 1ST LEVEL ROOF PLANS - GALLERY WINGA-122 BASE BID 2ND LEVEL & PENTHOUSE ROOF PLANSAE-100A EQUIPMENT INVENTORYAE-100B EQUIPMENT INVENTORYAE-101A EQUIPMENT & CASEWORK PLAN 1ST LEVEL - GALLERY WINGAE-101B EQUIPMENT & CASEWORK PLAN 1ST LEVEL - STUDIO WINGAE-102 EQUIPMENT & CASEWORK PLAN 2ND LEVEL- STUDIO WINGA-200 BASE BID BUILDING ELEVATIONSA-201 BASE BID & BID LOT 1 BUILDING ELEVATIONSA-301 BUILDING SECTIONSA-302 BUILDING SECTIONSA-303 BUILDING SECTIONSA-304 BUILDING SECTIONSA-310 WALL SECTIONSA-311 WALL SECTIONSA-312 WALL SECTIONSA-313 WALL SECTIONSA-314 WALL SECTIONSA-315 WALL SECTIONSA-401 ENLARGED PLANS & ELEVATIONSA-410 INTERIOR ELEVATIONS - HALLSA-411 INTERIOR ELEVATIONS - HALLSA-420 STAIR & ELEVATOR ENLARGED PLANS, SECTIONS AND DETAILSA-421 VERTICAL CIRCULATION SECTIONSA-423 STAIR ENLARGED PLAN, SECTIONS & DETAILSA-501 SECTION DETAILSA-502 SECTION DETAILSA-503 SECTION DETAILSA-511 PLAN DETAILSA-512 PLAN DETAILSA-513 PLAN DETAILSA-514 PLAN DETAILSA-515 PLAN DETAILS & PIVOT WALL ENLARGED PLANS & DETAILSA-600 DOOR SCHEDULE & DETAILSA-601 EXTERIOR FRAME TYPES & GLAZING SCHEDULESA-602 EXTERIOR FRAME TYPES & GLAZING SCHEDULESA-603 EXTERIOR FRAME & GLAZING SCHEDULESA-610 ROOM FINISH SCHEDULES & DETAILSA-622 CASEWORK ELEVATIONSA-623 CASEWORK ELEVATIONSA-624 CASEWORK ELEVATIONSA-625 CASEWORK SECTIONS & DETAILSA-626 CASEWORK SECTIONS & DETAILSA-701 PARTITION TYPE LEGEND & DETAILS
FIRE PROTECTIONFX-001 FIRE PROTECTION LEGENDFX-101A BASE BID & BID LOT 1 1ST LEVEL FIRE PROTECTION FLOOR PLAN - GALLERY WINGFX-101B BASE BID & BID LOT 1 1ST LEVEL LEVEL FIRE PROTECTION FLOOR PLAN - STUDIO
WING
SHEET LISTSHEET NO. SHEET NAMEGENERALG-000 COVER SHEETG-001 ABBREVIATIONS, SYMBOLS, & SPECIAL INSPECTIONSG-100A OVERALL 1ST & 2ND LEVEL FLOOR PLANSG-100B OVERALL ROOF PLANG-101 CODE PLAN - FIRST LEVELG-102 CODE PLAN - SECOND & PENTHOUSE LEVELSG-105 TYPICAL MOUNTING HEIGHTS
CIVILC-001 GENERAL NOTES, VICINITY MAP, F.I.R.M. AND LEGENDC-101 SITE PAVING PLAN - BASE BIDC-101A SITE PAVING PLAN - ALTERNATEC-102 GRADING PLAN - BASE BIDC-102A GRADING PLAN - ALTERNATEC-103 PAVING AND DRAINAGE SECTIONS AND DETAILSC-104 WATER AND SANITARY SEWER PLAN - BASE BIDC-104A WATER AND SANITARY SEWER PLAN - ALTERNATEC-105 WATER AND SANITARY SEWER SECTIONS AND DETAILS
LANDSCAPEL-100 IRRIGATION PLANL-101 IRRIGATION NOTES, DETAILS, SCHEDULEL-200 LANDSCAPE PLANL-201 LANDSCAPE NOTES, DETAILS, SCHEDULE
ARCHITECTURAL SITEAS-100 SITE SURVEYAS-101 DEMOLITION ARCHITECTURAL SITE PLANAS-102 ARCHITECTURAL SITE PLANAS-103 SITE DETAILSAS-104 SITE DETAILS
STRUCTURALS001 STRUCTURAL GENERAL NOTESS101-A FOUNDATION PLANS - GALLERY WINGS101-B FOUNDATION PLAN - STUDIO WINGS102-A LEVEL 2 FLOOR & LOW ROOF FRAMING PLAN - GALLERY WINGS102-B LEVEL 2 FRAMING - STUDIO WINGS103-B LEVEL 2 ROOF & PENTHOUSE FLOOR FRAMING - STUDIO WINGS104-A HIGH ROOF FRAMING PLANS201 BRACED FRAME ELEVATIONSS202 BRACED FRAME ELEVATIONSS203 BRACED FRAME DETAILSS301 SECTIONS & DETAILSS302 SECTIONS & DETAILSS303 SECTIONS & DETAILSS304 SECTIONS & DETAILSS305 SECTIONS & DETAILSS306 SECTIONS & DETAILSS401 ENLARGED STAIR FRAMING PLANS - SECTIONS AND DETAILSS701 TYPICAL DETAILSS702 TYPICAL DETAILSS703 TYPICAL DETAILS
NMSU NEW ART BUILDINGLAS CRUCES, NEW MEXICO
100% CONSTRUCTION DOCUMENTS 05 JANUARY 2018
OWNER PROJECT DIRECTORY
A & E TEAM PROJECT DIRECTORYTEAM MEMBER CONTACT PHONEARCHITECT: RMKM ARCHITECTURE, P.C. MILDRED ORTIZ 505.243.5454
STRUCTURALENGINEERING: RME ABQ STRUCTURAL ENGINEERS JIM KREIS 505.889.3004
CIVILENGINEERING: HIGH MESA CONSULTING GROUP J. GRAEME MEANS 505.345.4250
MEPTENGINEERING: BRIDGERS & PAXTON CONSULTING ENGINEERS ABBAS SHIRIAN 505.883.4111
LANDSCAPEARCHITECT: RICHARD BORKOVETZ LANDSCAPE ARCHITECTURE RICHARD BORKOVETZ 505.266.8506
CONSTRUCTIONCOST ESTIMATING: BALIS & COMPANY JON BALIS 505.883.7990
PROJECT MANAGER: ROBERT HERRERAASSISTANT DIRECTOR: JOSE LOERA
EXECUTIVE DIRECTOR: ALTON LOONEY
VICINITY MAP
PROJECT LOCATION:1308 University AveLas Cruces, NM
NEW ART BUILDINGPROJECT LOCATION
NO. ISSUE DATE1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
UP
P
P
P P R/FR/F R/F
P
F
F
P
/1
FA
102-
A
/1
FA
102 -
A
EXTERIORYARD
140
ELEVATOR/STAIRLOBBY
200F
DIGITALOUTPUT
221
GRADUATESTUDIO
220A
GRADUATESTUDIO
220B
GRADUATESTUDIO
220C
GRADUATESTUDIO
220D
GRADUATESTUDIO
220E
GRADUATESTUDIO
220F
GRADUATESTUDIO
220G
GRADUATESTUDIO
220H
HALLH201E
FACULTYSTUDIO
(SAFETY)242
GRAD STUDIOHUDDLE
240
FILM LOADING222D
GANG DARKRM
222B
PHOTO DOC. &STORAGE
210
PHOTOSTUDIO
222
FILMPROCESSING
RM222E
DESIGNSTUDIO
224
WOMENSR223A
MENSR223B
HALLH201F
STUDY/RESOURCE RM
229TR
T225AELEC. RM
M225B
COMPUTERLAB231
TECHNOLOGYLAB233
JEWELRYFACULTYSTUDIO
234
JANITORJ227
WASH OUT224A DARKROOM
224B
ETCHING RM224C
PAINTINGSTUDIO
230
STILL LIFESTORAGE
230ADRESSING
230BDRESSING
232A
DRAWINGSTUDIO
232
STUDENTCOLLABORATION
236
HALLH201G
DWG/PAINTINGFACULTYSTUDIO
238A
PHOTO.FACULTYSTUDIO
238B
DESIGNFACULTYSTUDIO
238C
CONFERENCERM235
DESIGNFACULTYSTUDIO
238D
FILM LOADING222C
C F G
8
2
ED
3
5
7
10
9
11
4
6.1
9.5
6.6
D.8 E.5 E.8 F.4 G.4
2.3
2.6
2.7
5.1
B.8
11.2
6
D.3
2.4
E.6 F.7 H
2.2
10.9
9.6
8.9
2.9
3.5
4.4
5.3
6.4
6.9
7.8
8.8
E.4D.45 D.9D.4
2.65
4.5
FS TS
1
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
1/8" = 1'-0"
FA-102B
NEW ARTBUILDINGNMSU LAS CRUCES, NM
BASE BID 2ND LEVEL FIRE ALARM FLOORPLAN - STUDIO WING
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB
OU
1/8" = 1'-0"FA-102B
1 BASE BID 2ND LEVEL FIRE ALARM FLOOR PLAN - STUDIO WING
NORTH
KEY PLAN
GALLERY
WING
STUDIO
WING EXTERIOR
YARD
MA
TC
H L
INE
RECEIVING
BID LOT 1
0' 8' 16' 32' 64'
1. COORDINATE FLOW AND TAMPER SWITCH LOCATION IN CEILING SPACE WITH PLUMBING DRAWINGS. PROVIDE INDICATOR LIGHT TO INDICATE LOCATION OF FLOW AND TAMPER SWITCHES THAT ARE ABOVE THE CEILING.
A. SEE SHEET E-604 FOR FIRE ALARM RISER DIAGRAM.B. ALL STROBES IN CORRIDORS AND COMMON AREAS WILL FLASH AT THE
SAME TIME.C. COORDINATE ALL DEVICES WITH ARCHITECTURAL AT WHITEBOARDS AND
PANEL LOCATIONS.D. REFER TO SPECIFICATION 28 3111 FOR VOICE EVACUATION SYSTEM
REQUIREMENTS AND ADDITIONAL INFORMATION. E. SEE SPECIFICATION SECTION 013100 FOR COORDINATION DRAWING
REQUIREMENTS.
GENERAL SHEET NOTES
KEYNOTES
IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASICREPRESENTATION OF THE FIRE ALARM SYSTEM. DEVICES INDICATED ONTHESE DOCUMENTS ARE IN NO WAY IMPLIED TO BE COMPREHENSIVE OF
THE FINAL DESIGN. IT IS THE RESPONSIBILITY OF THE FIRE ALARMCONTRACTOR TO PROVIDE A DESIGN/BUILD FIRE ALARM SYSTEM BASEDUPON A THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE
RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THEFIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OFTHE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY
PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSTEMSIMPACTING THE FIRE ALARM SYSTEM. NO CHANGE ORDERS SHALL BE
APPROVED FOR THE BASE SCOPE OF WORK.
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:06:09-07'00'
2" GRAVEL AT BOTTOM
WIDE SWEEP BEND
POLYMER CONCRETESTACKABLE BOX,WITH OPEN BOTTOM
EXTEND CONDUITS4" ABOVE BOTTOM,(2" ABOVE GRAVEL)
TYPE SIZE BOX
A 48WX48LX48D
COVER
PULL BOX SCHEDULE
B
6" DEEP LAYER OF CRUSH STONE BASE (3/4" CLEANCRUSHED STONE - 2B CLEAN)
BACK FILL
12-18" DEEPSEE SCHEDBELOW
PG4848BA48 PG4848HH0017
C 11Wx18Lx18D
D 12Wx12Lx12D
PC1118BA18 PC1118HAXX-17
PC1212BA12 PC1212HAXX-17
24W-36L-30D PG2436BA30 PG2436CA0017
- ALL PULL BOXES ARE TYPE "A" UNLESS NOTED OTHERWISE- COVER TO BE SECURED WITH MIN. OF TWO TAMPER-PROOF
FIVE-SIDED-HEAD STAINLESS STEEL BOLTS.- BOX WITH NO BASE.- LID TO DISPLAY "ELECTRIC" (QUAZITE OPTION #17)- BASIS OF DESIGN QUAZITE "PC" STYLE BOX.- BOX AND LID COLOR TO BE "LIGHT TAN".
NOTE:
CEILING
HANGER WIRES (TYP.)CEILING SYSTEM
MEMBERS. SUSPEND FROM EACHBUILDING FRAMING OR STRUCTURALNO. 12 GAUGE WIRE HANGER TO
END OF FIXTURE.
SUSPENSIONSYSTEM (TYP.)
18" BELOW CEILING
(TYP.)HANGER WIRES
CORNERS OF FIXTURE.
NO. 12 GAUGE WIRE HANGER TOBUILDING FRAMING OR STRUCTURALMEMBERS). SUSPEND FROM ALL FOUR
CEILING SYSTEM
LAY-IN LUMINAIRE
SEISMIC FIXTURE CLAMPS: REQUIRED AT ALL (4) LUMINAIRE CORNERS WITH (2) #10 SELF-TAPPING SCREWS. AGI SEISMIC PRODUCTS OR EQUAL. AC 184 COMPLIANT.
(TYP.)HANGER WIRESCEILING SYSTEM
BOLT CONNECTION WITHCOMPRESSION SPADE LUGFITTING (TYPICAL)
TO SERVICE ENTRANCE GROUND
2700V INSULATORS
STAND-OFFS
COPPER BUS BAR(REFER TO DIAGRAM ANDKEYED NOTE ON SHEET E602.)
DUCTBANK SIDEVIEW
RED CONCRETE
WARNING TAPE
WARNING TAPE
GRADE12"
30"MIN.
ONLY ONE CONDUIT SHOWN FOR CLARITY.
4"3"
3" 3"
3"
12"
SIMILAR FOR LOCATIONSWHERE MORE OR LESS CONDUITS ARE REQUIRED
PROVIDE CONCRETE DUCT BANK FOR PROTECTION ATDRIVEWAYS, STREETS, PARKING AREAS, OR OTHER LOCATIONS
WHERE VEHICULAR USE IS PRESENT.
CONDUIT SIZED AS INDICATED ON PLANS AND/OR FEEDER SCHEDULE
COUPLING
RED CONCRETEENCASED DUCT
RGS CONDUIT SIZE WHERE APPLICABLE
PVC CONDUIT SIZEWHERE APPLICABLE
TRENCHING
3"
SPARE
#4/0 GROUND
4" CONDUIT (TYP.)
3"3"
FINISHED GRADE OR SURFACE. REPAIRSURFACES TO MATCH EXISTING.
UNDISTURBED EARTH.
COMPACTED TO 90% RELATIVE DENSITY.FREE FROM LARGE ROCKS AND DEBRIS.(COMPACTED IN 6" LAYERS).
WARNING TAPE. (DETECTABLE)
PVC SCHEDULE 40 CONDUIT. NUMBERAND SIZE PER ONE-LINE DIAGRAM.FEEDER RUNS WILL BE GALVANIZED RIGIDSTEEL (GRS) FOR BENDS AND WHERETHEY ENTER A BUILDING.
CONCRETE DUCTBANK. CONCRETE TO BECOLORED RED.
6" SAND BED.
42"
MIN
.
24" MIN.
*
2
3
1
4
5
6
7
1
2
3
4
5
6
7
12"
SPARE4"4"4"
G
G
GG
GROUND LUG
BUSH CONDUIT ENDS
#6 BARE COPPER BONDED TO REBAR AND CONNECTED TOPOLE GROUND LUG
FINISH GRADE
BRANCH CIRCUIT INPVC CONDUIT. SEEELECTRICAL SITE PLANFOR ROUTING.
FIXTURE POLE AND BASEPLATE FURNISHED ASINTEGRAL PART OF PIXTURE
CHAMFER AND FINISHAS DIRECTED BYARCHITECT
4 #7 REBAR OPPOSITEEACH OTHER
GALVANIZED BOLTS FURNISHEDAS PART OF FIXTURE.QUANTITY AS REQUIRED BYMANUFACTURER. INSTALLBOLTS PER MANUFACTURER'SBOLT PATTERN
BRANCH CIRCUIT INPVC CONDUIT. SEEFOR ROUTING.
#3 REBAR TIESAT 12" O.C. 30"
6'-0
"
2'-0
"
MIN
.
6"
TO FIXTURE. LIGHTING FIXTURE IS EXISTING AND WILL BE REUSED IN NEW POLE.
G
G
GG
GROUND LUG
BUSH CONDUIT ENDS
#6 BARE COPPER BONDED TO REBAR AND CONNECTED TOPOLE GROUND LUG
FINISH GRADE
BRANCH CIRCUIT INPVC CONDUIT. SEEELECTRICAL SITE PLANFOR ROUTING.
TO FIXTURE. LIGHTING FIXTURE IS EXISTING AND WILL BE REUSED IN NEW POLE.
FIXTURE POLE AND BASEPLATE FURNISHED ASINTEGRAL PART OF PIXTURE
CHAMFER AND FINISHAS DIRECTED BYARCHITECT
4 #7 REBAR OPPOSITEEACH OTHER
GALVANIZED BOLTS FURNISHEDAS PART OF FIXTURE.QUANTITY AS REQUIRED BYMANUFACTURER. INSTALLBOLTS PER MANUFACTURER'SBOLT PATTERN
BRANCH CIRCUIT INPVC CONDUIT. SEEFOR ROUTING.
#3 REBAR TIESAT 12" O.C. 30"
6'-0
"
2'-0
"
MIN
.
DEVICE AND OUTLET BOX TYPES PER PLANS
CORD INSULATIONAND CONDUCTORSPER PLANS
CORD REEL
BALL STOP
CHANNEL
THREADED ROD ORAPPROVED EQUIVALENT
CORD GRIP
7'-0" AFF(MIN)
SUSPENDEDCEILING
CORD & PLUG
NEMA 5-20RTWISTLOCK CEILING OUTLET
ASSEMBLY TO CONSIST OF THE FOLLOWING COMPONENTS(BASIS OF DESIGN):- HUBBELL #HBLC40123--REEL W/MOUNTING BASE AND 12/3 WIRE LEADS- HUBBELL #3059H--PORTABLE OUTLET BOX- HUBBELL #3061H--LIFTING COVER WITH GFCI DEVICE PLATE- HUBBELL #074011335--STAINLESS STEEL CORD GRIP
BACK TO BACK DUPLEX RECEPTACLE (4 OUTLETS TOTAL)
VACANCY/OCCUPANCYSENSOR
SWITCHED OUTLET SHALL BE COLOR CODED: LIGHT BROWN
SWITCHED OUTLET SHALL BE COLOR CODED: LIGHT BROWN
GENERAL NOTE:1. AT LEAST 50% OF ALL 120V, 20A RECEPTACLES MUST BE AUTOMATICALLY CONTROLLED PER
ASHRAE 90.1: SECTION 8.4.2. THIS STANDARD ONLY APPLIES TO PRIVATE OFFICES, AND COMPUTER CLASSROOMS.
2. BOTH A TIME CLOCK AND OCCUPANCY SENSOR TO CONTROL RECEPTACLE'S SWITCHED OUTLETS. DURING “ON” HOURS ALL SWITCHED RECEPTACLES WILL REMAIN ON. DURING CLOCK OFF HOURS, SWITCHED RECEPTACLES WILL ONLY BE ON WHEN ROOM IS OCCUPIED. DURING “OFF” HOURS RECEPTACLES WILL SHUT OFF AFTER 20 MINUTES OF ROOM VACANCY.
3. SPLIT-WIRE RECEPTACLES SHALL BE USED THROUGH-OUT THE DESIGNATED SPACES. THIS INCLUDES WALL MOUNTED, FLOOR MOUNTED AND CEILING MOUNTED RECEPTACLES AS NOTED IN PLANS. COMPUTER PC SHALL BE CONNECTED TO UNSWITCHED RECEPTACLE FOR CONTINUOUS POWER.
4. COORDINATE WITH NMSU TIME CLOCK SETTINGS FOR THESE DEVICES.
(TIME CLOCK DIALOG)
REFER TO E-603
RELAYPACK
ELEVATION
SECTION "A-A"
RIGID STEEL 3/4"CONDUIT FOR WIRING
RIGID STEEL CONDUITFOR SUPPORT PER
N.E.C. ART. 314
CAST METAL"WHILE-IN-USE"WATERPROOF
COVER(S) &RECEPTACLE(S)
CAST METAL, 2-GANG,NEMA 3R JUNCTION BOXWITH THREADED HUBS
12"
MA
X
3/4" CONDUIT
NOTE: REFER TO STRUCTURAL AND ARCHITECTURAL DRAWINGS FORSECURELY ATTATCHING TO ROOF STRUCTURE AND FLASHING
2-GANG JUNCTION BOX
ELEVATION
SECTION "A-A"
RIGID STEEL 3/4"CONDUIT FOR WIRING
RIGID STEEL 2" STRUT SUPPORT
PERN.E.C. ART. 314
DISCONNECT. REFER TO PLANS
FOR SIZE.
12"
MA
X
3/4" CONDUIT
NOTE: REFER TO STRUCTURAL AND ARCHITECTURAL DRAWINGS FORSECURELY ATTATCHING TO ROOF STRUCTURE AND FLASHING
2-GANG JUNCTION BOX
A
A
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
NO SCALE
E-501
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL DETAILS
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB
OU
SCALE: NO SCALE1 LINEAR DIRECT-INDIRECT SUPPORT DETAIL
SCALE: NO SCALE2 LUMINAIRE SUPPORT DETAIL
SCALE: NO SCALE3 MAIN GROUNDING ELECTRODE BUS BARSCALE: NO SCALE6 DUCTBANK DETAILS - PRIMARY POWER
SCALE: NO SCALE5 208V SECONDARY DUCT BANK DETAILSCALE: NO SCALE8 POLE BASE DETAIL (PARKING LOT LIGHTS)
SCALE: 1/8" = 1'-0"4 PULL BOX/HAND HOLE DETAIL
SCALE: NO SCALE9 POLE BASE DETAIL (WALKWAY LIGHTS)
SCALE: NO SCALE7 POWER CORD REEL DETAILSCALE: N.T.S.10 PLUG LOAD CONTROL
SCALE: NO SCALE12 RECEPTACLE ROOF MOUNTING DETAIL
SCALE: NO SCALE11 UNISTRUT MOUNTED DISCONNECT DETAIL
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:25:29-07'00'
"S25-133"
1 2 3 4
4
TO LOAD BREAK SECTIONALIZER
100E
20E
SP
AR
E
100E
TO WILLIAMS VAULT
TO HILTON HALL
23.9 KV
208Y/120
EX. T25-423750 kVA(H & SS)
EX. H & SS
EX
EX. 3#4/0 W/ 1/3 NEUTRAL
AND #1/0 GND
23.9 KV
208Y/120
6
"J1"
1000/3P
EX. 1200A, 208Y/120V, 50 KAIC
EX. (3) - 4#500 KCMIL(3) 4" CONDUIT
EX. WILLIAMS HALL EX. ANNEX(NORMAL)
800 Y 50 Y
EX. EX.EX. EX.
METERED DEMAND LOAD:
140KW @ .895 PF = 156.5 KVA
1000 Y
9
NEC DEMAND LOAD: 192.5 KVA
"T1" XFMR BY NMSU
1600 YEX.
4
1600/3P4
15
EX. FIRE PUMP
4
250 YEX.
4
4
4
1 2 3
600/
3P
800/
3P
SP
AC
E
1000
/3P
4
50/3
P
11
EX. SITE POLE
LUMINAIRES
EX
12
14
EX. NMSU EMERGENCY SYSTEM @ BUSINESS VAULT (4160Y / 2400V)
2.4KV
240/120V
50/3P
PANEL "EM" - 480Y/277V, 3PH, 4W 100A
50/3P
M
100/3P
EX
NEW XFMR"T3"
NMSU 25 KV SYSTEM(NEW WORK)
NMSU "CONTINUOUS LIGHTING"
EMERGENCY SYSTEM(NEW WORK)
WORK WITHIN DASHED LINES IS BY NMSU. SHOWN HERE FOR REFERENCE ONLY.
50/3P 20/3P
SP
AC
E
SP
AC
E
PANEL "EM1" PANEL "EM2"
EX. MSB
"DB1" - FREE-STANDING GEAR
600 Y
"J3""J2"
"HH-1"
"HH-2" "HH-3"
"J4"
4
125/
3P
1000
/3P
EX. ANNEX(EMERG.)
EX. ANNEX
AIC RATING: 14 kAIC
208Y/120V, 3PH, 4W 1000A, AIC RATING: 22 kAIC
PHASE IIIPHASE I
1
1
1
1
125 Y
125 Y
8
8
8
"D1"100E
50 Y 50 Y
XXA
P5-350
EXIST. BUSINESS ADM VAULT SWITCH: "S5-200"
1 2 3 4
65A
P5-355
4
2
2
TO GARDINER VAULT
TO BUSINESS ADMINISTRATION
15A
EX. SWITCH
EX. NMSU EMERGENCY SYSTEM (4160Y / 2400V)
208Y/120V
2.4KV
120/240V
50/2P
EX. PANEL "E"
50/2P
M
100/2P
EX. ANNEX(EMERG.)
EX. WILLIAMS HALL
85A
1#2 15kV1#2 600V(1) 2" CONDUIT
3#1, 1#6 GND IN(1) 1-1/4" CONDUIT
EX
EX. XFMR25 kVA
50A
/2P
EX.3#4, 1#10 GND IN(1) 1" CONDUIT
EX. T5-815(3) 50 kVA
1000/3P
5KV
EX. ANNEX(NORMAL)
5 KV
208Y/120
EX. T5-810300 kVA
1200A, 208Y/120V, 50 KAIC
3#2 15kV1#2 600V(1) 4" CONDUIT
(3) - 4#500 KCMIL(3) 4" CONDUIT
EX.
500 KCMIL SET
EX. WILLIAMS HALL
800/3PEX
800A, 208Y/120V
EXISTING ABOVE-GRADE ELECTRICAL VAULT. EQUIPMENT SHOWN WITHIN DASHED LINES IS INSIDE OF VAULT
208V120/240V
10 KVA 3#6, 1#10 GND IN3/4" CONDUIT
3#4, 1#10 GND IN1" CONDUIT
50A
/2P
EX. PANEL "E1"NEC DEMAND
LOAD: 3.96 KVA
3#4, 1#10 GND IN(1) 1" CONDUIT
EX. ATS80A/3P
SINGLE- PHASE
NMSU 5 KV SYSTEM(EXISTING/DEMO WORK)
NMSU "CONTINUOUS LIGHTING"
EMERGENCY SYSTEM(EXISTING/DEMO WORK)
2
2
2
2
22
2
2 2
2
2 22 2
2
2
2
3
4
4
4
4
5
NEC DEMAND LOAD: 13.96
KVA
EX. EMERGENCY PANEL
NEC DEMAND LOAD: 10 KVA
15
2
METERED DEMAND LOAD:
140KW @ .895 PF = 156.5 KVA
EX. SITE POLE
LUMINAIRES
EX
12
13
EX. PANEL (AT SCULPTURE YARD)
2
800/3P 400/3P 125/3P EX EX
22
2
"J3"
2
PHASE II
PHASE II
7
2
2
5 "J1"
EX.EX.
25
40
35
30
45
50
60
70
90
80
125
100
200
175
225
250
150
300
350
450
400
700
600
800
1000
500
1200
1600
2500
2000
3000
NOTE:
NOTESDESIGNATION
THREE PHASE THREE WIRE & GROUND FEEDER
FEEDER SCHEDULE
20
4000
CONDUCTORS GROUND CONDUIT
(6) 3-600 KCMIL
(8) 3-500 KCMIL
(10) 3-600 KCMIL
(5) 3-600 KCMIL
(2) 3-600 KCMIL
(4) 3-600 KCMIL
(3) 3-600 KCMIL
(3) 3-400 KCMIL
(2) 3-250 KCMIL
(2) 3-500 KCMIL
(2) 3-350 KCMIL
3-600 KCMIL
(2) 3#4/0
3#1
3#2
3#2/0
3#1/0
3#4/0
3#3/0
3-250 KCMIL
3-500 KCMIL
3-350 KCMIL
3#10
3#8
3#10
3#8
3#8
3#6
3#4
3#8
3#2
3#4
3#12
(8)400 KCMIL
(6)350 KCMIL
(10)500 KCMIL
2
(2) 2
(2) 1
(2) 1
(2) 2
(5)250 KCMIL
(4) 4/0
(3) 3/0
(3) 2/0
(2) 1/0
4
2
4
4
6
6
6
6
8
10
10
10
10
10
10
10
8
8
8
12
(6) 4"
(8) 4"
(10) 4"
4"
(2) 4"
(2) 3"
(2) 3"
(3) 3"
(5) 4"
(4) 4"
(3) 4"
(2) 4"
(2) 2 1/2"
1 1/2"
1 1/4"
1 1/2"
2 1/2"
2"
3"
4"
3"
2"
3/4"
1 1/4"
1 1/4"
1 1/4"
1"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
ALL CONDUCTORS ARE COPPER, TYPE THWN/THHN UNLESS OTHERWISE NOTED.
35Y
40Y
30Y
45Y
50Y
60Y
70Y
80Y
90Y
125Y
100Y
175Y
200Y
225Y
250Y
150Y
300Y
350Y
450Y
400Y
600Y
700Y
800Y
1000Y
500Y
1200Y
1600Y
2000Y
2500Y
3000Y
25Y
20Y
4000Y
5000Y
4#6
(3) 4-600 KCMIL
(4) 4-600 KCMIL
(5) 4-600 KCMIL
(8) 4-500 KCMIL
(6) 4-600 KCMIL
(10) 4-600 KCMIL
(12) 4-600 KCMIL
(2) 4-250 KCMIL
(2) 4-350 KCMIL
(2) 4-500 KCMIL
(2) 4-600 KCMIL
(3) 4-400 KCMIL
4-250 KCMIL
(2) 4#4/0
4-350 KCMIL
4-500 KCMIL
4-600 KCMIL
4#4
4#4
4#2
4#2
4#1/0
4#2/0
4#3/0
4#4/0
4#1
4#10
4#10
4#12
4#8
4#8
4#8
4#8
(3) 3/0
(4) 4/0
(5) 250 KCMIL
(6) 350 KCMIL
(8) 400 KCMIL
(10) 500 KCMIL
(12) 700 KCMIL
4
(2) 2
(2) 1
(2) 1
(2) 2
(2) 1/0
(3) 2/0
2
4
2
6
6
4
6
6
8
8
8
8
10
10
12
10
10
10
10
10
(3) 4"
(4) 4"
(5) 4"
(6) 4"
(8) 4"
(10) 4"
(12) 4"
3"
(2) 3"
(2) 4"
(2) 4"
(3) 3"
(2) 3"
(2) 2 1/2"
4"
3"
4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
2 1/2"
1 1/2"
2"
2"
2"
3/4"
3/4"
1"
3/4"
3/4"
3/4"
3/4"
3/4"
THREE PHASE FOUR WIRE & GROUND FEEDER
NOTE:
NOTESDESIGNATION
FEEDER SCHEDULE (CONT.)
CONDUCTORS GROUND CONDUIT
ALL CONDUCTORS ARE COPPER, TYPE THWN/THHN UNLESS OTHERWISE NOTED.
EQUIPMENT BONDING JUMPER FOR SEPARATELY DERIVED SYSTEMS PERNEC 250.66 (PROVIDE CONDUCTOR GROUND BELOW INSTEAD OF FEEDER GROUND FOR
THREE PHASE,4-WIRE SYSTEMS INDICATED ABOVE)
8
6
100Y-E
THREE PHASE FOUR WIRE 200% NEUTRAL & GROUND FEEDER
150Y-E
225Y-E
350Y-E
500Y-E
400Y-E
3-250 KCMIL,2-250 KCMIL NEUT.(2) 3#3/0,(2) 2#3/0 NEUT.(2) 3#4/0,(2) 2#4/0 NEUT.(2) 3-350 KCMIL,(2) 2-350KCMIL NEUT.
3#2, 1#4/0 NEUTRAL
3#2/0, 2#2/0 NEUT.
(2) 2
(2) 2
8
(2) 2
4
6 2"
2 1/2"
2"
(2) 3"
(2) 2 1/2"
(2) 2 1/2"
20YS THRU 100YS
125YS THRU 150YS
4175YS THRU 200YS
2225YS THRU 300YS
1/0350YS THRU 500YS
2/0600YS THRU 700YS
GROUNDDESIGNATION
800YS THRU 5000YS 3/0
800Y-E(2) 3-600 KCMIL,(2) 2-600KCMIL NEUT.
(2) 1/0 (2) 4"
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
As indicated
E-601A
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL DIAGRAMS
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB
OU
1/8" = 1'-0"E-601A
1 ELECTRICAL ONE LINE DIAGRAM (NEW WORK--EXISTING WILLIAMS HALL AND ANNEX)
1/8" = 1'-0"E-601A
2 ELECTRICAL ONE LINE DIAGRAM (DEMOLITION--EXISTING WILLIAMS HALL AND ANNEX)
NO SCALEE-601A
3 COPPER SCHEDULE.
1. NEW ELECTRICAL EQUIPMENT AND/OR FEEDER TO BE PROVIDED AND INSTALLED BY NMSU.
2. EXISTING ELECTRICAL EQUIPMENT AND/OR FEEDERS TO BE REMOVED IN ITS ENTIRETY.
3. DISCONNECT FROM EXISTING CIRCUIT AND REMOVE CONDUITS AND CONDUCTORS FROM VAULT.
4. EXISTING ELECTRICAL EQUIPMENT TO REMAIN AS PRESENTLY INSTALLED.5. EXISTING PANEL WILL BE RE-FED FROM "DB1". COORDINATE LOCATION OF
SPLICE WITH FIELD CONDITIONS.6. NMSU WILL PROVIDE AND INSTALL TRANSFORMER. STUB-UP CONDUITS UP
THROUGH CONCRETE PAD. COORDINATE WITH NMSU PRIOR TO ENERGEZING CONDUCTORS.
7. EXISTING LOADS ARE NOT BEING USED ANYMORE. REMOVE BRANCH CIRCUIT UP TO LOAD/DEVICE.
8. EXTEND UNDERGROUND RACEWAY PATHS AND CONDUCTORS FROM "DB1" TO EACH EXISTING FEEDER AS SHOWN. SPLICE CONDUCTORS IN NEW HANDHOLE. REFER TO SITE PLAN FOR ADDITIONAL INFORMATION.
9. 3#4/0 25 KV ALUMINUM, 100% INSULATION WITH 1/3 NEUTRAL AND 1#1/0 COPPER GROUND, IN ONE 4" PVC CONDUIT. EXTEND CONDUCTORS FROM EX. XFMT "T25-423" TO NEW "T1". COORDINATE WITH NMSU TERMINATIONS AT THE TRANSORMER(S). REFER TO SHEET ES-101 FOR TRANSFORMER LOCATIONS.
10. NOT USED.11. OVERCURRENT PROTECTION DEVICE SHALL BE ADJUSTED PER
COORDINATION STUDY.12. REFER TO SHEET ES-101 AND ESD-101 FOR SITE POLE LUMINAIRES
LOCATIONS AND ADDITIONAL INFORMATION.13. EXISTING PHOTOCELL SYSTEM IS MOUNTED AT THE VAULT. DISCONNECT
FROM EXISTING CIRCUIT AND PROTECT UNTIL RE-INSTALL.14. EXISTING PHOTOCELL SYSTEM SHALL BE RELOCATED AND MOUNTED TO
"DB1" AS SHOWN IN ES-101. 15. REMOVE EXISTING "ATS" AND SPLICE CONDUCTORS TO ASSURE CIRCUIT
CONTINUITY TO EX. PANEL "E1". MINIMIZE WORK AT THIS AREA AS MUCH AS POSSIBLE. COORDINATE WITH NMSU SHUTDOWN TIME TO THE EXISTING BUILDING.
A. PANELBOARD AIC RATINGS FOR PANELBOARDS ARE INDICATED ON THE PANEL SCHEDULES.
B. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO REPRESENT PHYSICAL ARRANGEMENTS, LOCATIONS, ROUTING ORCONNECTIONS. PHYSICAL LAYOUTS ARE TO BE PER FIELD CONDITIONS AND AS INDICATED ELSEWHERE IN THE ELECTRICAL PLANS.
C. REFERENCE THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTSREGARDING EQUIPMENT AND INSTALLATION.
D. CONTRACTOR WILL MEASURE AND TORQUE ALL PANEL FEEDERS, MEASURE RESISTANCE TO GROUND AT SERVICE GROUND AND PROVIDE WRITTEN DOCUMENTATION OF TEST RESULTS.
E. CONTRACTOR WILL LABEL ALL DISTRIBUTION EQUIPMENT PRIOR TO FINAL OBSERVATION WALKTHROUGH.
GENERAL SHEET NOTES
KEYNOTES
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:11:21-07'00'
"T2"PADMOUNTED
TRANSFORMER3
1600 Y
1600AMCB
GFP
7
5
23.9 KV 480/277Y
M
"MSB"
480Y/277V, 3PH, 4W 1200A MAIN SWITCHBOARD
DEVICES MINIMUM
BUS BRACING MINIMUM
42KAIC
42KA
SPD
GROUND BUS
8
60A3P6
400A3P
60 Y
SECOND LEVEL
FIRST LEVEL
PENTHOUSE
225A3P
2
100 Y
PANEL"H2A"
100A
MLO
"T2DB"225KVA480-208Y/120V
400
10
100A3P
9
800 Y
400A3P
PANEL"1LP4"
PANEL"1LP3
PANEL"1LP2"
PANEL"1LP1"
225A3P6
225A3P6
225 Y 225 Y
225A3P6
225 Y
225A3P6
225 Y
"L1DB"
208Y/120V, 3PH, 4W 800A DIST. BOARD
DEVICES MINIMUM
BUS BRACING MINIMUM
22KAIC
22KA
PANEL"2LP4"
PANEL"2LP3"
PANEL"2LP2"
PANEL"2LP1"
100A3P6
225A3P6
225 Y 100 Y
100A3P6
100 Y
100A3P6
100 Y
"L2DB"
208Y/120V, 3PH, 4W 800A DIST. BOARD
DEVICES MINIMUM
BUS BRACING MINIMUM
14KAIC
14KA
PANEL"1LP5"
450A3P6
450 Y
PANEL"1LP6"
225A3P6
225 Y
PANEL"1LP7"
225A3P6
225 Y
PANEL"1LP8"
225A3P6
225 Y
600A3P
225 Y
225A
"TP"75KVA480-208Y/120V
600Y
100A3P
600A3P
85A3P
60A3P6
60 Y
SPD
60A3P6
60 Y
SPD
5
5
100 Y
1 E-602
TYP.
1 E-602
TYP.
1 E-602
1
"T1DB"300KVA480-208Y/120V
TYP.
1 E-602
400
800AMCB
800AMCB
800 Y
PANEL "LP"
150A3P
150A3P
16
15
3P150A
150
12
13
11
14
ELEVATORCONTROLLER
40
150A
G
ELEVATOR
SPARE SPACE
PANEL"M2A"
100A
MLO
150A
PANEL "MP"
600A
150 Y
SPARE SPACE SPARE
225A
MLO
225A
MLO
225A
MLO
225A
MLO
600A
MLO
225A
MLO
225A
MLO
225A
MLO
100A
MLO
100A
MLO
225A
MLO
100A
MLO
PANEL"L1A"
100A3P6
100 Y
100A
MLO
PANEL"L2A"
225A3P6
225 Y
225A
MLO
150A3P
150A3P
SPARE SPACE
70A3P6
"T-LT"45KVA480-208Y/120V
TYP.
1 E-602
70
PANEL"LT"
225A
MLO
150AD1
M
M
M
12,470 V
R
EXISTING MANHOLE
EXISTING MANHOLE R
PAD MOUNTED SWITCH
WORK WITHIN DASHED LINES IS BY NMSU.SHOWN HERE FOR INFORMATION ONLY.
M
M
M
M
M
4
LSIG LSIG LSIG LSIG LSIG
PANEL"LT2"
100A
MLO
225 Y
PANEL"H1B"
100A
MLO
225A3P
100A3P
100 Y
PANEL"M1"
225A
MLO
LSIG LSIG
PANEL"H1A"
100A
MLO
100A3P
100 Y
LSIG
16 17
PANEL"L1B"
225A3P6
225 Y
225A
MLO SPD
SPD
150 Y
100 Y
(2 SEC.) (2 SEC.)
(2 SEC.) (2 SEC.) (2 SEC.) (2 SEC.) (2 SEC.) (3 SEC.)
(2 SEC.)
25
40
35
30
45
50
60
70
90
80
125
100
200
175
225
250
150
300
350
450
400
700
600
800
1000
500
1200
1600
2500
2000
3000
NOTE:
NOTESDESIGNATION
35Y
40Y
30Y
45Y
50Y
60Y
70Y
80Y
90Y
125Y
100Y
175Y
200Y
225Y
250Y
150Y
300Y
350Y
450Y
400Y
600Y
700Y
800Y
1000Y
500Y
1200Y
1600Y
2000Y
2500Y
3000Y
THREE PHASE THREE WIRE & GROUND FEEDER
FEEDER SCHEDULE
25Y
20Y
EQUIPMENT BONDING JUMPER FOR SEPARATELY DERIVED SYSTEMS PERNEC 250.66 (PROVIDE CONDUCTOR GROUND BELOW INSTEAD OF FEEDER GROUND FOR
THREE PHASE,4-WIRE SYSTEMS INDICATED ABOVE)
20
4000
4000Y
5000Y
CONDUCTORS
4#6
(3) 4-600 KCMIL
(4) 4-600 KCMIL
(5) 4-600 KCMIL
(8) 4-500 KCMIL
(6) 4-600 KCMIL
(10) 4-600 KCMIL
(12) 4-600 KCMIL
(2) 4-250 KCMIL
(2) 4-350 KCMIL
(2) 4-500 KCMIL
(2) 4-600 KCMIL
(3) 4-400 KCMIL
4-250 KCMIL
(2) 4#4/0
4-350 KCMIL
4-500 KCMIL
4-600 KCMIL
4#4
4#4
4#2
4#2
4#1/0
4#2/0
4#3/0
4#4/0
4#1
4#10
4#10
4#12
4#8
4#8
4#8
4#8
GROUND
(3) 3/0
(4) 4/0
(5) 250 KCMIL
(6) 350 KCMIL
(8) 400 KCMIL
(10) 500 KCMIL
(12) 700 KCMIL
4
(2) 2
(2) 1
(2) 1
(2) 2
(2) 1/0
(3) 2/0
2
4
2
6
6
4
6
6
8
8
8
8
10
10
12
10
10
10
10
10
CONDUIT
(3) 4"
(4) 4"
(5) 4"
(6) 4"
(8) 4"
(10) 4"
(12) 4"
3"
(2) 3"
(2) 4"
(2) 4"
(3) 3"
(2) 3"
(2) 2 1/2"
4"
3"
4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
2 1/2"
1 1/2"
2"
2"
2"
3/4"
3/4"
1"
3/4"
3/4"
3/4"
3/4"
3/4"
(6) 3-600 KCMIL
(8) 3-500 KCMIL
(10) 3-600 KCMIL
(5) 3-600 KCMIL
(2) 3-600 KCMIL
(4) 3-600 KCMIL
(3) 3-600 KCMIL
(3) 3-400 KCMIL
(2) 3-250 KCMIL
(2) 3-500 KCMIL
(2) 3-350 KCMIL
3-600 KCMIL
(2) 3#4/0
3#1
3#2
3#2/0
3#1/0
3#4/0
3#3/0
3-250 KCMIL
3-500 KCMIL
3-350 KCMIL
3#10
3#8
3#10
3#8
3#8
3#6
3#4
3#8
3#2
3#4
3#12
(8)400 KCMIL
(6)350 KCMIL
(10)500 KCMIL
2
(2) 2
(2) 1
(2) 1
(2) 2
(5)250 KCMIL
(4) 4/0
(3) 3/0
(3) 2/0
(2) 1/0
4
2
4
4
6
6
6
6
8
10
10
10
10
10
10
10
8
8
8
12
(6) 4"
(8) 4"
(10) 4"
4"
(2) 4"
(2) 3"
(2) 3"
(3) 3"
(5) 4"
(4) 4"
(3) 4"
(2) 4"
(2) 2 1/2"
1 1/2"
1 1/4"
1 1/2"
2 1/2"
2"
3"
4"
3"
2"
3/4"
1 1/4"
1 1/4"
1 1/4"
1"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
8
6
THREE PHASE FOUR WIRE & GROUND FEEDER
ALL CONDUCTORS ARE COPPER, TYPE THWN/THHN UNLESS OTHERWISE NOTED.
100Y-E
THREE PHASE FOUR WIRE 200% NEUTRAL & GROUND FEEDER
150Y-E
225Y-E
350Y-E
500Y-E
400Y-E
3-250 KCMIL,2-250 KCMIL NEUT.(2) 3#3/0,(2) 2#3/0 NEUT.(2) 3#4/0,(2) 2#4/0 NEUT.(2) 3-350 KCMIL,(2) 2-350KCMIL NEUT.
3#2, 1#4/0 NEUTRAL
3#2/0, 2#2/0 NEUT.
(2) 2
(2) 2
8
(2) 2
4
6 2"
2 1/2"
2"
(2) 3"
(2) 2 1/2"
(2) 2 1/2"
20YS THRU 100YS
125YS THRU 150YS
4175YS THRU 200YS
2225YS THRU 300YS
1/0350YS THRU 500YS
2/0600YS THRU 700YS
GROUNDDESIGNATION
800YS THRU 5000YS 3/0
800Y-E(2) 3-600 KCMIL,(2) 2-600KCMIL NEUT.
(2) 1/0 (2) 4"
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
As indicated
E-601B
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL DIAGRAMS
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB
OU
SCALE: NONEA3 PHASE 3. ELECTRICAL ONE LINE DIAGRAM1
SCALE: NO SCALEA1 COPPER SCHEDULE1
ELECTRICAL CALCULATIONSScale: NOT TO SCALE
C2
1. SOLID STATE, ELECTRONIC TRIP CIRCUIT BREAKER WITH LONG-TIME, SHORT-TIME, INSTANTANEOUS AND GROUND FAULT FUNCTIONS. 100% RATED WITH ADJUSTABLE SETTINGS.
2. MEDIUM VOLTAGE SYSTEM TO BE PROVIDED BY NMSU. REFER TO SHEET ES-101 FOR ADDITIONAL INFORMATION.
3. SERVICE TRANSFORMER TO BE PROVIDED BY NMSU.4. SUBMETERS FOR FEEDER. BASIS OF DESIGN IS SQUARE D POWER LOGIC
ION 7300 METER WITH BACNET COMPABILITY OUTPUT.5. SPD MOUNTED EXTERNALLY TO SWITCHBOARD/PANELBOARD. WHERE
EQUIPMENT IS INSTALLED EXTERIOR TO THE BUILDING, THE EQUIPMENT WILL BE IN A NEMA 3R ENCLOSURE, LOCKABLE AND HINGED DOOR. SIZE OF ENCLOSURE WILL BE LARGE ENOUGH TO ACCOMMODATE MANUFATURER;S CLEARANCE REQUIREMENTS OF SPD DEVICE.
6. MOLDED CASE, THERMAL-MAGNETIC CIRCUIT BREAKERS, 100% RATED AND LOCKABLE.
7. INTEGRAL POWER MONITOR MOUNTED INTERNALLY TO SWITCHBOARD. REFER TO SPECIFICATIONS FOR METERING INSTRUMENTATION REQUIREMENTS.
8. REFER TO DETAIL 1 ON SHEET E-602 FOR GROUNDING INFORMATION FOR THIS EQUIPMENT.
9. METER TO BE PROVIDED BY OWNER.. PROVIDE CT'S AND PR'S AS REQUIRED. SIZE CT'S FOR FULL LOAD OF TRANSFORMER. PROVIDE (1) 1" CONDUIT FROM MSB TO NEAREST I/T ROOM.
10. ETHERNET OUTLET ADJACENT TO EACH METER. INCLUDE CONNECTION TO SERVER.
11. ELEVATOR CONTROL MODULE.12. GROUND CONDUCTOR FOR THIS ELEVATOR FEEDER WILL BE RATED FOR
100% OF THE PHASE CONDUCTORS AND NOT AS CALLED FOR IN FEEDER TAG/SCHEDULE.
13. CIRCUIT BREAKER WITH SHUNT TRIP COIL PROVIDED IN CONTROLLER BY ELEVATOR MANUFACTURER.
14. CONNECT FIRE ALARM AND ELEVATOR RECALL PER ELEVATOR INSTALLER'S RECOMMENDATIONS.
15. PROVIDE GFP FOR ELEVATOR.16. PROVIDE (3)2" UNDERGROUND SPARE CONDUITS FROM ELECTRICAL - M150
TO ELEC M125B. 17. PROVIDE (2)1" CONDUITS FROM ELECTRICAL - M150 TO PENTHOUSE FOR
FUTURE PV SYSTEM.
A. PANELBOARD AIC RATINGS FOR PANELBOARDS ARE INDICATED ON THE PANEL SCHEDULES.
B. INFORMATION SHOWN IS DIAGRAMMATIC AND IS NOT INTENDED TO REPRESENT PHYSICAL ARRANGEMENTS, LOCATIONS, ROUTING ORCONNECTIONS. PHYSICAL LAYOUTS ARE TO BE PER FIELD CONDITIONS AND AS INDICATED ELSEWHERE IN THE ELECTRICAL PLANS.
C. REFERENCE THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTSREGARDING EQUIPMENT AND INSTALLATION.
D. CONTRACTOR WILL MEASURE AND TORQUE ALL PANEL FEEDERS, MEASURE RESISTANCE TO GROUND AT SERVICE GROUND AND PROVIDE WRITTEN DOCUMENTATION OF TEST RESULTS.
E. CONTRACTOR WILL LABEL ALL DISTRIBUTION EQUIPMENT PRIOR TO FINAL OBSERVATION WALKTHROUGH.
GENERAL SHEET NOTES
KEYNOTES
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:16:51-07'00'
~ ~
M
25 kV SYSTEM BY NMSU
<5'-0"
#4/0
#4/0
METER &BACKFLOWPREVENTER(S)
#4/0
#4/0
METER &BACKFLOWPREVENTER(S)
NEUTRALGROUND
COLDWATER
PIPE
GROUND NEUTRAL
"MSB"SERVICEENTRANCEEQUIPMENT
"T1DB"TRANSFORMER FORSEPARATELY DERIVEDSYSTEM (SIMILAR FORALL SEPARATELYDERIVED DRY-TYPETRANSFORMERS)
GROUND NEUTRAL
GROUND NEUTRALMAIN GROUNDINGELECTRODEGROUND BAR
TELECOMM ROOM
CW HW
WATERHEATER(TYPICAL)
NEUTRALGROUND
GROUND NEUTRAL
BUILDINGSTRUCTURALSTEEL
COLDWATER
PIPE
H1A, H1B, M1A
GROUND
#4/0
"LT" & "LT2"
#4/0WITH 600VINSULATION
GRADE
GROUND NEUTRAL
"T2"OUTDOORTRANSFORMERBY NMSU
#6
PIPE/CONDUIT
CABLE TRAY
#6
NOTE: ALL CONDUCTORS ARE COPPER.
SIZE OF LARGEST UNGROUNDED SERVICE-ENTRANCE
CONDUCTOR OR EQUIVALENT AREA FOR PARALLEL
CONDUCTORS.(AWG OR kCMIL)
SIZE OF GROUNDING ELECTRODE
CONDUCTOR (AWG)
<= #2
#1 OR 1/0
2/0 OR 3/0
OVER 3/0THROUGH 350
OVER 350THROUGH 600
OVER 600THROUGH 1100
OVER 1100
8
6
4
2
1/0
2/0
SEE KEYED NOTE 16
GROUNDING ELECTRODECONDUCTOR SCHEDULE
1010
10
2
1
7
10
9
6
5
4
14
10
10 1
16
10
10
16
10
3
1
11
20'-0" MINIMUM
12 13
15
METALLIC PIPE
14
BY NMSU
BY CONTRACTOR
#4/0
NEUTRALGROUND
GROUND NEUTRAL
"T2DB"TRANSFORMER FORSEPARATELY DERIVEDSYSTEM (SIMILAR FORALL SEPARATELYDERIVED DRY-TYPETRANSFORMERS)
NEUTRALGROUND
10
10 1
1610
SECONDARY GROUNDINGELECTRODEGROUND BAR
GROUND NEUTRALGROUND NEUTRAL
H2A, M2A
10
10
GROUND NEUTRALGROUND NEUTRAL
MP
10
"L2DB"
NEUTRALGROUND NEUTRALGROUND
10
10 1
TYPICAL FOR ALL 2LPX PANELS AND L2A
BUILDINGSTRUCTURAL
STEEL
NEUTRALGROUND
COLDWATER
PIPE
GROUND NEUTRAL
"TP"TRANSFORMER FORSEPARATELY DERIVEDSYSTEM
NEUTRALGROUND
4
14
10
10 1
1610
"LP"
BUILDINGSTRUCTURAL
STEEL
COLDWATER
PIPE
4
14
"L2DB"
NEUTRALGROUND NEUTRALGROUND
10
10 1
TYPICAL FOR ALL 1LPX PANELS AND L1A/L1B
GROUND NEUTRAL
"T2DB"TRANSFORMER FORSEPARATELY DERIVEDSYSTEM (SIMILAR FORALL SEPARATELYDERIVED DRY-TYPETRANSFORMERS)
10
1
1610
BUILDINGSTRUCTURAL
STEEL
COLDWATER
PIPE
4
14
NEUTRALNEUTRAL
GROUND NEUTRAL
"T3"OUTDOORTRANSFORMERBY NMSU
1010
10
2
"EM"GROUND NEUTRAL
16
10
GROUND NEUTRALGROUND NEUTRAL
EM1
10
GROUND NEUTRALGROUND NEUTRAL
EM2
10
5 kV EMERGENCY SYSTEM BY NMSU
"DB1"OUTDOOR SWITCHGEAR
GROUND NEUTRAL
GROUND NEUTRAL
"T1"OUTDOORTRANSFORMERBY NMSU
1010
10
2
1
16
10
1
"J1"
1
EX. WILLIAMS
HALL
"J2" "J3" "J4"
EX. ANNEX (NORMAL)
EX. ANNEX (EMERG.)
EX. SITE POLE
LUMINAIRES
PHASE II & III
PHASE I
P
TTB
FACP
MDF134
120VAC
120VAC
DC
SUP.RET.
12
7
2
11
3
TYP.
6
8
4
TYP.
1
MM
13
R
FSTS
FTS
14
L1C1-95
15
HOT BOX
1"C
PIV
FAA9
L1C1-XX
1"C
GENERAL SHEET NOTES
KEYNOTES
1. XXXX.
A. XXXX.A. INSTALL GROUNDING CONNECTIONS TO BUILDING STRUCTURE AND WATER PIPES AT LOCATIONS THAT ARE VISIBLE AND ACCESSIBLE FOR INSPECTION, MAINTENANCE, AND TESTING.
B. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC SERVICE ENTRANCE CONDUIT. BOND TO SERVICE ENTRANCE EQUIPMENT GROUND BUS USING NEC TABLE 250.102 (C)(1).
C. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH METALLIC FEEDER CONDUIT. BOND TO GROUND BUS USING CONDUCTOR THAT IS SIZED EQUAL TO EQUIPMENT GROUNDING CONDUCTOR.
D. BOND ELECTRICAL EQUIPMENT ENCLOSURES TO GROUND BAR USING SAME SIZE CONDUCTOR AS FEEDER EQUIPMENT GROUND CONDUCTOR OR FACTORY PROVIDED GREEN SCREW.
E. CLEAN COATED RE-BAR PRIOR TO PERFORMING ELECTRICAL CONNECTIONS.
1. REFER TO ONE-LINE DIAGRAM AND FEEDER SCHEDULE FOR GROUNDED CONDUCTOR SIZE.
2. CONNECT GROUNDING ELECTRODE CONDUCTOR TO GROUND ROD.3. FOR EQUIPMENT GROUNDING CONDUCTOR SIZE REFER TO ONE-LINE
DIAGRAM AND FEEDER SCHEDULE.4. PROVIDE GROUNDING ELECTRODE CONDUCTOR SIZE BASED ON THE
CONDUCTOR SIZE OF THE SECONDARY OF THE TRANSFORMER. SIZE PER NEC 250.66 AND PER SCHEDULE ON THIS SHEET.
5. PROVIDE A CONCRETE-ENCASED MAIN GROUNDING ELECTRODE IN THE BUILDING FOUNDATION AROUND THE ENTIRE PERIMETER OF THE BUILDING. LOCATE ELECTRODE IN THE BOTTOM ONE-THIRD OF THE FOUNDATION WITH AT LEAST 3 INCHES OF CONCRETE COVER. USE EITHER #4/0 BARE COPPER CABLE OR #6 OR LARGER STEEL REINFORCING BARS MADE ELECTRICALLY CONTINUOUS USING EXOTHERMICALLY WELDED #4/0 JUMPERS.
6. BOND EACH PERIMETER STRUCTURAL STEEL COLUMN TO THE CONCRETE-ENCASED MAIN GROUNDING ELECTRODE. USE EXOTHERMIC WELDS.
7. PROVIDE A 1/4" X 4" X 12" "MAIN GROUNDING ELECTRODE GROUND BAR" FOR SINGLE POINT GROUNDING. LOCATE AT AN ACCESSIBLE POINT NEAR THE SERVICE ENTRANCE EQUIPMENT. MAKE OTHER CONNECTIONS TO THE GROUND BAR USING TWO-HOLE COMPRESSION SPADE LUGS THAT MEET IEEE 837 REQUIREMENTS. LABEL EACH CONNECTION.
8. XX9. INSTALL A 1/4" X 4" COPPER "TELECOMMUNICATIONS GROUNDING
BUSBAR" IN EACH TELECOMMUNICATIONS ROOM. CONNECT CABLES TO THE "TELECOMMUNICATIONS GROUNDING BUSBAR" USING COMPRESSION SPADE LUGS. LABEL CONDUCTORS PER ANSI-J-STD-607-A. LABEL EACH CONNECTION. SEE PLAN FOR BAR LENGTH AND LOCATIONS.
10. BONDING JUMPER SIZED PER GROUNDING ELECTRODE CONDUCTOR SCHEDULE THIS SHEET.
11. BOND HOT WATER PIPE TO COLD WATER PIPE AT EACH WATER HEATER WITH A #8 BARE COPPER CONDUCTOR.
12. PROVIDE A GROUND RING PER NEC 250.52 A.4.13. PROVIDE A GROUND ROD PER NEC 250.52 A.514. BOND ALL METALLIC PIPING SYTEMS WITHIN STRUCTURE.15. PROVIDE A GROUNDING ELECTRODE SYSTEM PER 2014 NMEC.16. MAIN BONDING JUMPER AND/OR SYSTEM BONDING JUMPER SIZE BASED
ON UNGROUNDED CONDUCTOR SIZE AND GROUNDING ELECTRODE CONDUCTOR SCHEDULE ON THIS SHEET UNLESS UNGROUNDED CONDUCTOR SIZE OR EQUIVALENT IS GREATER THAN 1100 KCMIL. IF GREATER THAN 1100 KCMIL (OR 1750 KCMIL FOR ALUMINUM) SIZE JUMPER PER NEC TABLE 250.102 (C)(1).
17. LIGHTNING PROTECTION COUNTERPOISE - #4/0 BARE COPPER.18. BOND EACH CORNER STRUCTURAL STEEL AND PERIMETER
STRUCTURAL STEEL AT NO MORE THAN 50 FOOT SPACING TO THE LIGHTNING PROTECTION COUNTERPOISE.
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
As indicated
E-602
NEW ARTBUILDINGNMSU LAS CRUCES, NM
GROUNDING DIAGRAM
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB
OU
SCALE: NO SCALEA4 FIRE ALARM RISER DIAGRAM1
GENERAL SHEET NOTES
KEYNOTES
1. XXXX.
A. XXXX.1. MINIMUM 3/4" CONDUIT AND FIRE ALARM CABLING AS REQUIRED BY THE FIRE ALARM MANUFACTURER.
2. INDEPENDENTLY SUPERVISE EACH FLOW AND TAMPER SWITCH WITH AN ADDRESSABLE MODULE. REFER TO FIRE PROTECTION/PLUMBING PLANS FOR LOCATION OF EACH LOCATION.
3. DIGITAL COMMUNICATOR FOR CENTRAL STATION MONITORING. 4. CONDUIT AND COMMUNICATIONS CABLING FOR CENTRAL STATION
REPORTING. 5. FIRE ALARM TERMINAL CABINETS (FATC) WILL BE FACTORY
MANUFACTURED, UL LABELED PANELS. THE FATC WILL ENCLOSE ALL TERMINATIONS FOR DEVICES ON THE FLOOR OR AREA IT SERVES. INTELLIGENT CARDS AS REQUIRED OR INDEPENDENT OPERATION, POWER SUPPLIES AND STANDBY BATTERIES WILL BE PROVIDED AT EACH LOCATION.
6. DUCT SMOKE DETECTOR, FURNISHED BY DIVISION 28. INSTALLED IN DUCT BY DIVISION 23. CONNECTED, WIRED AND TESTED BY DIVISION 28. REFERENCE MECHANICAL CONTROL DIAGRAMS FOR MECHANICAL INTERCONNECTIONS. PROVIDE DUCT DETECTORS IN NEW AND EXISTING UNITS WHERE 2000CFM AND ABOVE EXIST. INSTALL PER CODE.
7. FIRE SMOKE DAMPER. ROUTE 120VAC VIA FIRE ALARM ADDRESSABLE RELAY.
8. TELEPHONE TERMINAL BOARD. 9. PROVIDE NEW ANNUNCIATOR PANEL. FIELD COORDINATE EXACT
LOCATION.10. PROVIDE RACEWAY PATH OVERHEAD OR UNDERGROUND TO FATC. 11. NEW FIRE ALARM SYSTEM. LOCATION OF FACT AS SHOWN ON PLANS.12. PROVIDE SURGE PROTECTION FOR CIRCUIT TO FIRE ALARM PANEL.13. RELAY MODULES FOR SHUNT TRIP, AUTO RECALL, ALTERNATE RECALL,
AND FIRE CAP.14. TAMPER SWITCH IN HOT BOX. TERMINATE AS REQUIRED FOR
NOTIFICATION OF TAMPERING OF EQUIPMENT.PROVIDE SEPERATE DROP FOR ANALOG CONNECTION TO FIRE ALARM CONTROL PANEL, SHOULD DPS WISH TO HAVE FACP COMMUNICATION IN THIS FASHION.
A. FIRE ALARM DIAGRAM INDICATES GENERAL DIAGRAMMATIC CONNECTIONS ONLY. ALL CONNECTIONS AND INSTALLATION WILL BE PER FIRE ALARM SYSTEM MANUFACTURER'S SHOP DRAWINGS.
B. DEVICE QUANTITIES ARE NOT INDICATED ON THIS DRAWING. REFER TO FLOOR PLANS FOR QUANTITIES AND LOCATIONS.
C. REFER TO SPECIFICATION SECTION 283111 FOR FIRE ALARM SYSTEM REQUIREMENTS.
D. FIRE ALARM WIRING AND CABLING SHALL BE IN CONFORMANCE WITH NEC AND TYPE SHALL BE AS RECOMMENDED BY FIRE ALARM SYSTEM MANUFACTURER.
E. SEAL ALL PENETRATIONS THROUGH WALLS, FLOOR, CEILINGS AND ROOF PER ARCHITECTURAL SPECIFIED REQUIREMENTS. SEAL WILL MATCH THE FIRE RATING OF EACH PENETRATION LOCATION.
F. IT IS THE INTENT OF THESE DOCUMENTS TO SHOW A BASIC PRESENTATION OF THE MINIMUM FIRE ALARM SYSTEM REQUIREMENTS. DEVICES INDICATED ON THESE DOCUMENTS ARE IN NO WAY IMPLIED TO BE COMPREHENSIVE OF THE FINAL DESIGN. IT IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO PROVIDE A COMPLETE FIRE ALARM SYSTEM BASED UPON THOROUGH REVIEW OF ALL CONTRACT DOCUMENTS. IT IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR TO ENSURE THAT THE FIRE ALARM SYSTEM IS CODE COMPLIANT, MEETS THE REQUIREMENTS OF THE AHJ AND COMPREHENSIVELY COVERS AND INCLUDES ALL NECESSARY PARTS AND LABOR ASSOCIATED WITH OTHER TRADES AND SYSTEMS IMPACTING THE FIRE ALARM SYSTEM.
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:17:04-07'00'
Local Room Dataline
REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION
SEE INSTALLATION INSTRUCTIONSFOR TERMINATION TYPE.QUANTITY AS SHOWN ON PLAN.
LIGHTING CONTROL DESCRIPTIONAll room luminaires - Manual-ON/Manual or Auto-OFF
ADDITIONAL SWITCHES WILL BE CONNECTED FROM THE NEXT SWITCH. PROVIDE CABLE AS NECESSARY FOR COMPLETE CONTROLLABILITY.
RELAY 4
RELAY 3
RELAY 2
RELAY 1 DIM 1
DIM 2
DIM 3
DIM 4
ROOM CONTROLLER#WRC-3160
DATALINE
ROOMLUMINAIRES
Hot
120/277
0-10V CONTROL
ONE BUTTON DIMMING SWITCH
TYPE "D"#WSD-3501
EM. EXPANSION
TOPOLOGY/POLARITY FREE
BACK TO DIALOG PANEL
ONE BUTTON DIMMING SWITCH
TYPE "D"#WSD-3501
(ZONES AS NOTED ON DRAWINGS)
REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION
RELAY 4
RELAY 3
RELAY 2
RELAY 1 DIM 1
DIM 2
DIM 3
DIM 4
ROOM CONTROLLER#WRC-3160
DATALINE
LightingLoad(a)
LightingLoad(a)
Hot
120/277
0-10V CONTROL
EM. EXPANSION
Local Room Dataline18AWG / 2-Wire
Non-Polarized
VACANCY SENSOR TYPE "DCDT"#WORSDG1
DAYLIGHT SENSOR#WPS-3711-P-N
TOPOLOGY/POLARITY FREE
ADDITIONAL SWITCHES WILL BE CONNECTED FROM THE NEXT SWITCH. PROVIDE CABLE AS NECESSARY FOR COMPLETE CONTROLLABILITY.
BACK TO DIALOG PANEL
DRIVER
Line
White
Green
Black
Neutral
Ground
Gray
120V/230V/277V Ground
Violet
YellowTraveler
Red
0-10V
0-10V
OCC
LIGHTING CONTROL DESCRIPTION
All room luminaires - Auto-ON/Manual or Auto-OFF
REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION
VACANCY SENSOR TYPE "DCDT"#WORSDG1
SEE INSTALLATION INSTRUCTIONSFOR TERMINATION TYPE.
LIGHTING CONTROL DESCRIPTIONMain Scene (1) (Dimming Switches will control all lights in room) Manua-ON/Auto-OFF. Note: If two or more main dimmers exist within same room, last dimmer setting will override
the other dimmer status to that same dimmed level
Scene (1) (100% lumen output of all LED luminaires) Manual-ON/Auto-OFFScene (2) (50% lumen output of all LED luminaires) Manual-ON/Auto-OFFScene (3) (turn off front of room luminaires and 50% lumen output of back of
room LED luminaires. If there is an odd number of luminaire rows, include the middle row as part of the back room luminares (50%)) Manual-ON/Auto-OFF
THREE BUTTON SWITCHTYPE "3"
#WSW-3513
ADDITIONAL SWITCHES/SENSORS WILL BE CONNECTED FROM THE NEXT SWITCH/SENSOR.
PROVIDE CABLE AS NECESSARY FOR COMPLETE CONTROLLABILITY.
100% LIGHT LEVEL
50% = 50% LIGHT LEVEL
A/V=FRONT OFF/BACK 50%
LIGHTING CONTROL DESCRIPTION PLACARD
MOUNT ADJACENT TO SWITCH(ES)
RELAY 4
RELAY 3
RELAY 2
RELAY 1 DIM 1
DIM 2
DIM 3
DIM 4
ROOM CONTROLLER#WRC-3160
DATALINE
BACK OF ROOMLUMINAIRES
FRONT OF ROOMLUMINAIRES
Hot
120/277
0-10V CONTROL
ONE BUTTON DIMMING SWITCH
TYPE "D"#WSD-3501
DAYLIGHT SENSOR#WPS-3711-P-N
EM. EXPANSIONREFER TO E-603 FOR
ADDITIONAL INFORMATION
Dimmer UpDimmer Down
All Lights On
Local Room Dataline18AWG / 2-Wire
Non-Polarized
100%
50%
A/VTOPOLOGY/POLARITY FREE
BACK TO DIALOG PANEL
Local Room Dataline
REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION
SEE INSTALLATION INSTRUCTIONSFOR TERMINATION TYPE.QUANTITY AS SHOWN ON PLAN.
LIGHTING CONTROL DESCRIPTIONAll room luminaires - Manual-ON/Manual or Auto-OFF
ADDITIONAL SWITCHES WILL BE CONNECTED FROM THE NEXT SWITCH. PROVIDE CABLE AS NECESSARY FOR COMPLETE CONTROLLABILITY.
RELAY 2
RELAY 1 DIM 1
DIM 2
ROOM CONTROLLER#WRC-3260
DATALINE
ROOMLUMINAIRES
Hot
120/277
0-10V CONTROL
ONE BUTTON DIMMING SWITCH
TYPE "D"#WSD-3501
EM. EXPANSION
DAYLIGHT SENSOR#WPS-3711-P-N
TOPOLOGY/POLARITY FREE
DATALINE BACK TO DIALOG PANEL
REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION
Neutral
LANTERNLUMINAIRES
DMX CONDUCTORDMX CONTROLLER
STICK-DE3
Hot
120/277
POWER4M
TO LIGHTING CONTROL UNIT
6-7VDC
POWER SUPPLY(DRIVER)
120/277
Hot
DATA BOX
REFER TO SHEET SERIES "EL" FOR ADDITIONAL INFORMATION
TRACK LIGHTING SYSTEM
LUMINAIRES
36 CIRCUITRELAY BOX
120/277
Hot
DIMMER BOXDOUGLAS #DLS-RP
1LP70-10V
LCPBACK TO DIALOG PANEL
LCP SHALL PROVIDESEPARATE DIMMING CONTROL FOR EACH ZONES (TRACK ROW)
a,b,c,d,e,f,g
WRC-LCD
Hot
120/277
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
As indicated
E-603
NEW ARTBUILDINGNMSU LAS CRUCES, NM
LIGHTING CONTROL DIAGRAMS
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
Checker
Author
NO SCALEE-603
2 DOUGLAS CONTROL WIRING DIAGRAM
NO SCALEE-603
5 DOUGLAS CONTROL WIRING DIAGRAM
GENERAL SHEET NOTES
A. CONTRACTOR WILL PROVIDE ENGRAVED SWITCHES AND A PLACARD WITH CONTROL DESCRIPTION. PLACARD WILL BE PER ARCHITECTURAL REQUIREMENTS, PLACARD WILL BE NO LARGER THAN A SWITCH COVER PLATE.
B. DIAGRAMS ARE FOR INFORMATION ONLY AND DO NOT REFLECT THE CORRECT NUMBER OF DEVICES. REFER TO "EL" SHEETS FOR QUANTITIES AND TO MANUFACTURERS RECOMMENDATIONS FOR LOCATION OF LIGHTING CONTROL DEVICES.
1/8" = 1'-0"E-603
3 WALL OCC SENSOR 0-10V DIMMING SINGLE LOAD
LIGHTING SEQUENCE: TYPE "E" (CONFERENCE ROOM)
LIGHTING SEQUENCE: TYPE "H" (LABS W/O PROJECTOR)
NO SCALEE-603
6 DOUGLAS CONTROL WIRING DIAGRAMLIGHTING SEQUENCE: TYPE "G" (LABS W/ PROJECTOR)
NO SCALEE-603
4 DOUGLAS CONTROL WIRING DIAGRAM
NO SCALEE-603
1 DMX CONTROL WIRING DIAGRAM
LIGHTING SEQUENCE: TYPE "D" (OFFICES)
LIGHTING SEQUENCE: (LANTERN DMX)
LIGHTING SEQUENCE: TYPE "A" (RESTROOMS)
LIGHTING SEQUENCE OF OPERATION
A. RESTROOMS (MEN & WOMEN):a. DUAL TECHNOLOGY (ULTRASONIC/INFRARED) SENSORS WILL CONTROL
ENTIRE ROOM. • OCCUPIED MODE: OCCUPANCY SENSOR WILL TURN LIGHTS IN
RESTROOM UPON MOTION DETECTION, AUTO-ON, AUTO-OFF.• UNOCCUPIED MODE: ALL LIGHT SHALL BE DISABLED IN RESTROOM
BY OCCUPANCY SENSOR(S) AFTER 10 MINUTES OF NO MOTION DETECTION.
B. FAMILY RESTROOMS (SMALL):a. SMALL: THE WALL-MOUNTED SENSOR WILL CONTROL LUMINAIRES.
MANUAL ON/ AUTO OFF. WALKTHROUGH FEATURE IS DESIRED.C. UTILITY ROOMS (STORAGE, JANITORS AND THE LIKE): WALL-MOUNTED
OCCUPANCY SENSOR WILL CONTROL THE LUMINAIRE(S) IN THE ROOM. MANUAL ON/ AUTO OFF.
D. OFFICES, SMALL/LARGE:a. WALL-MOUNTED DIMMING SWITCHES WILL CONTROL LUMINAIRES. MANUAL
ON/ AUTO OFF. b. WHEN ROOM IS UNOCCUPIED, ALL LIGHTING SHALL BE DISABLED AND DE-
ENERGIZED BY OCCUPANCY SENSOR(S) IN ROOM CEILING E. CONFERENCE ROOMS
a. WALL-MOUNTED DIMMING SWITCHES WILL CONTROL LUMINAIRES. MANUAL ON/ AUTO OFF.
b. WHEN ROOM IS UNOCCUPIED, ALL LIGHTING SHALL BE DISABLED AND DE-ENERGIZED BY OCCUPANCY SENSOR(S) IN ROOM CEILING
c. REFER TO FLOOR PLAN FOR LIGHTING ZONES.F. UNDERCABINETS LIGHT (APPLIES TO ALL UNDER CABINET LIGHT)
a. DEDICATED-TO-CABINET TOGGLE SWITCHES WILL CONTROL UNDERCABINET TASK LUMINAIRES.
b. OCCUPANCY SENSOR ON ROOM/SPACE WILL ALSO DE-ENERGIZE UNDERCABINET TASK LIGHTING WHEN SENSOR TIMES OUT.
c. LOCATE HARDWIRE POWER SUPPLY (DRIVER) INSIDE OF CABINET AND COORDINATE WITH CABINET INSTALLER. COORDINATE NUMBER OF POWER SUPPLY BASED ON THE NUMBER OF FIXTURES IT CAN POWER (BASIS OF DESIGN IS 100W POWER SUPPLY).
d. COORDINATE LENGTH OF LUMINAIRE WITH CABINET ACTUAL LENGTH DIMENSIONS.
G. LABORATORY WITH PROJECTOR/PRESENTATION SCREEN (VARIOUS ROOMS WILL HAVE DIFFERING CONTROL LOADS. SEE DIAGRAMS AND ROOMS FOR ADDITIONAL INFORMATION. INFORMATION BELOW IS TYPICAL.)a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY MAIN DIMMING
SWITCHES IN ROOM. NO LUMINAIRE WILL AUTOMATICALLY ENERGIZZE.b. IN ADDITION, THREE-BUTTON WALL MOUNTED SWITCHES BY THE
INSTRUCTORS DESK WILL PROVIDE OVERRIDE SETTINGS AS SHOWN ON DETAIL DIAGRAM.
H. LABORATORY WITHOUT PROJECTOR/PRESENTATION SCREEN (VARIOUS ROOMS WILL HAVE DIFFERING CONTROL LOADS. SEE DIAGRAMS AND ROOMS FOR ADDITIONAL INFORMATION. INFORMATION BELOW IS TYPICAL.)a. LIGHTING CONTROL IN ROOM WILL BE ENABLED BY MAIN DIMMING
SWITCHES IN ROOM. NO LUMINAIRE WILL AUTOMATICALLY ENERGIZED.b. IN ADDITION, THREE-BUTTON WALL MOUNTED SWITCHES BY THE
INSTRUCTORS WORKING DESK WILL PROVIDE OVERRIDE SETTINGS AS SHOWN ON DETAIL DIAGRAM.
I. ART GALLERYa. WALL-MOUNTED SWITCHES WILL CONTROL TRACK LIGHTING. MANUAL ON/
AUTO OFF. REFER TO FLOOR PLAN FOR LIGHTING ZONES.b. A SEPARATE SWITCH WILL CONTROL AMBIENT LIGHT FOR CLEANING AND
MAINTENANCE PURPOSES.J. PHOTOGRAPHY LAB
a. WALL-MOUNTED DIMMING SWITCHES WILL CONTROL LUMINAIRES. MANUAL ON/ MANUAL OFF. REFER TO FLOOR PLAN FOR LIGHTING ZONES.
b. TUNNABLE WHITE LIGHT WILL BE PROVIDED FOR LAB FLEXIBILITY GIVING THE USERS THE ABILITY TO CHANGE THE COLOR TEMPERATURE OF THE LIGHTS.
K. FILM PROCESSING LAB - DARK ROOMa. WALL-MOUNTED SWITCHES WILL CONTROL LUMINAIRES. MANUAL ON/
MANUAL OFF. REFER TO FLOOR PLAN FOR LIGHTING ZONES.b. SPECIALTY TYPE LIGHT WILL BE PROVIDED TO AVOID FILM DAMAGE.
L. EXTERIOR BUILDING LIGHTING:a. ALL EXTERIOR BUILDING LIGHTING WILL BE PROGRAMMED TO COME ON A
1/2 HOUR BEFORE DUSK AND OFF A 1/2 HOUR AFTER DAWN.M. DAYLIGHT SENSORS:
a. DAYLIGHT SENSORS WILL CONTROL LUMINAIRES WITHIN 15 FT OF LOBBY VERTICAL FENESTRATION AND WINDOW WIDTH PLUS 2 FT ON EACH SIDE. DAYLIGHT SENSOR WILL MAINTAIN 20 FOOTCANDLES AT ALL TIMES.
b. DAYLIGHT SENSOR WILL OVERRIDE ANY LIGHT LEVEL SET BY THE LUMINAIRE SWITCH.
N. SITE LIGHTING:1. ALL ROADWAY LIGHTING WILL BE PROGRAMMED TO COME ON A 1/2
HOUR BEFORE DUSK AND OFF A 1/2 HOUR AFTER DAWN.2. PARKING LOT AREA LIGHTING WILL BE PROGRAMMED TO COME ON A 1/2
HOUR BEFORE DUSK AND OFF AT 11 PM.3. ALL WALKWAY LIGHTING, EXCEPT THOSE NOTED, WILL COME ON A 1/2
HOUR BEFORE DUSK AND OFF AT 11 PM.4. DESIGNATED WALKWAY LIGHTING WILL BE ON A 1/2 HOUR BEFORE
DUSK AND OFF A 1/2 HOUR AFTER DAWN.
NO SCALEE-603
7 DOUGLAS CONTROL WIRING DIAGRAM
NO. ISSUE DATE1 DESIGN DEVELOPMENT - PRELIMINARY SUBMITTAL 05/03/2017
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:17:14-07'00'
FIRST FLOOR SECOND FLOOR
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ZONE 6
ZONE 9
ZONE 5
H101B
HALL
H101A
HALL
100B
ENTRANCELOBBY
H101
EXHIBITIONHALL
H101D
HALL
H101F
HALL
100F
ELEVATORLOBBY
120
STUDENTCOLLABORATION
H101E
HALL
140A
RECEIVINGYARD
140
EXTERIORYARD
H201E
HALL
120
STUDENTCOLLABORATION
H201F
HALL
H201F
HALL
ST101B
SOUTHSTAIR
ST101B
SOUTHSTAIR
H201D
HALL
ZONE 10
D
J127
JANITOR
DMX
D
D
DOUGLAS LIGHTING
CONTROL UNIT
EXTERIOR LTG -NORTH/WEST)
ETHERNET OUTLET ADJACENT TO RELAY PANEL. INCLUDE CONNECTION TO SERVER
H1B-7
277 V
LCP-BROOM: ELEC-M125B
LIGHTING CONTROL
UNIT
277 V
WLC-3150
LIGHTING RELAY PANEL
WRD-3408
LCP-CROOM: ELEC-T225B
LIGHTING RELAY PANEL
WRD-3408
1ST LEVEL HALLWAY
SOUTH/EASTDM. 0-10V
LCU
K
DATA LINEOS OCCUPANCY SENSORS ARE
USED IN HALLWAYS FOR AFTER HOUR USE
DATA LINEOS OCCUPANCY SENSORS ARE
USED IN HALLWAYS FOR AFTER HOUR USE
PC
1ST LEVEL HALLWAY
SOUTH/EASTDM. 0-10V
K
K
H1B-4
EM1-1
SPAREK
SPAREK
SPAREK
SPAREK
ETHERNET OUTLET ADJACENT TO RELAY PANEL. INCLUDE CONNECTION TO SERVER
PANEL EM1
"H" PANEL
"H" PANEL
2ND LEVEL HALLWAY
DM. 0-10V
K
2ND LEVEL HALLWAY
DM. 0-10V
K
LANTERN LIGHTSDMX
H2A-9"H" PANEL
H2A-5
EM2-5
SPAREK
SPAREK
SPAREK
SPARE
"H" PANEL
EXHIBITION HALL
DM. 0-10V
K
EXHIBITION HALL
DM. 0-10V
K
H2A-7
EM2-11
"H" PANEL
E-RELAY
E-RELAY
1ST LEVEL HALLWAY
NORTH/EASTDM. 0-10V
K
1ST LEVEL HALLWAY
NORTH/EASTDM. 0-10V
K
H1B-9
EM1-3PANEL
EM1
"H" PANEL
PANEL EM2
PANEL EM2
E-RELAY
E-RELAY
DOUGLAS LIGHTING
CONTROL UNIT
ETHERNET OUTLET ADJACENT TO RELAY PANEL. INCLUDE CONNECTION TO SERVER
277 V
LCP-AROOM: ELEC-M150
LIGHTING RELAY PANEL
WRD-3408LCU
PC
SPAREK
SPAREK
SPAREK
SPAREK
EXTERIOR YARD (PHOTOCELL
CONTROLLED)DM. 0-10V
K
DM. 0-10V
K
H1A-3
EM-1PANEL
EM1
"H" PANEL
E-RELAY
EXTERIOR LIGHTING -
SOUTH AND YARD
K
EXTERIOR LIGHTING -
SOUTH
K
H1A-5
EM-3PANEL
EM1
"H" PANEL
E-RELAY
EXTERIOR YARD (PHOTOCELL
CONTROLLED)
SPAREK
SPAREK
1ST LEVEL HALLWAY
WESTDM. 0-10V
K
1ST LEVEL HALLWAY
WESTDM. 0-10V
K
H1B-10
EM1-5PANEL
EM1
"H" PANEL
E-RELAY
EXTERIOR WALL
PACKSDM. 0-10V
K
EXTERIOR WALL
PACKS SOUTH
DM. 0-10V
K
H2A-4
EM2-1
"H" PANEL
E-RELAY
PANEL EM2
EXTERIOR WALL
PACKS NORTH
DM. 0-10V
KEM2-3
E-RELAY
PANEL EM2
120V
120V
120V
120V120V
120V
120V
120V
120V
277V
277V
277V
277V
277V
277V
277V
277V
277V
277V
MOUNT PHOTOCELL ON EXTERIOR YARD
CANOPY ROOF ROOF MOUNTED
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
NO SCALE
E-604
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL LIGHTING DIAGRAMS
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB
OU
NO SCALEE-604
1 LIGHTING HALLWAY CONTROL
1. ZONE 1 (EXHIBITION HALL & ENTRANCE LOBBY): a. OVERALL CONTROL WILL BE PROGRAMMED ON AT 5 AM AND OFF AT 11 PM.b. FROM 11 PM TO 5 AM. OCCUPANCY SENSORS WILL OVERRIDE CLOCK AND
TURN LIGHTS ON FOR 30 MINUTE INCREMENTS. LIGHTING WILL SIGNAL A BLINK OF THE LIGHTS (5) FIVE MINUTES BEFORE SHUT DOWN.
c. OVERRIDE HALLWAY CONTROL WILL BE SET THROUGH DIMMER SWITCHES LOCATED AT THE ART GALLERY - 105.
2. ZONE 2 (HALL H101B & H101A), ZONE 3 (ROOMS 118, 1180G & 118H), ZONE 4 (HALL H101F, H101F, H101E) & ZONE 9 (HALL H201E, H201D, H201F, H201F)a. OVERALL CONTROL WILL BE PROGRAMMED ON AT 5 AM AND OFF AT 11 PM.b. FROM 11 PM TO 5 AM. OCCUPANCY SENSORS WILL OVERRIDE CLOCK AND
TURN LIGHTS ON FOR 30 MINUTE INCREMENTS. LIGHTING WILL SIGNAL A BLINK OF THE LIGHTS (5) FIVE MINUTES BEFORE SHUT DOWN.
3. ZONE 5 (SOUTH STAIR - ST101B)a. LUMINAIRES WILL OPERATE 24/7.b. FROM 11 PM TO 5 AM. OCCUPANCY SENSORS IN HALLWAYS/CORRIDOR
WILL DIM THE LIGHTS DOWN UPON NO DETECTION (DAMP DOWN/RAMP UP).
4. ZONE 6 (STUDENT COLLABORATION - 120)a. OVERALL CONTROL WILL BE PROGRAMMED ON AT 5 AM AND OFF AT 11 PM.b. FROM 5 AM TO 11 PM. OVERRIDE DIMMING SWITCHES, LOCATED AT THE
FIRST FLOOR AREA, WILL OVERRIDE ZONE 6 LUMINAIRES.c. AFTER HOURS: OVERRIDE DIMMING SWITCHES WILL CONTROL AND TURN
LIGHTS ON FOR 1 HOURS ONLY. IF LIGHTING WAS ON BEFORE CLOCK OFF SETPOINT, LIGHTS WILL STAY ON FOR 1 HOUR AFTER THAT TIME. LIGHTING WILL SIGNAL A BLINK OF THE LIGHTS (5) FIVE MINUTES BEFORE SHUT DOWN.
5. ZONE 7 (EXTERIOR YARD - 140)a. LUMINAIRES WILL BE CONTROLLED BY A PHOTOCELL MOUNTED ON TOP OF
THE CANOPY. LUMINAIRES WILL BE OFF DURING THE DAY AND ON DURING NIGHT/DARK TIME.
b. OVERRIDE SWTICHES LOCATED AT FACULTY STUDIO (SAFETY)-242 WILL OVERRIDE LUMINAIRES IN ZONE 7.
6. ZONE 8 (RECIEVING AREA - 140A)a. EXTERIOR LIGHTING WILL BE ON 1/2 HOUR BEFORE DUSK AND OFF 1/2
HOUR AFTER DAWN.b. OVERRIDE SWITCHES WILL TURN LIGHTS ON FOR 2 HOURS.
7. ZONE 10 (CUPULA) RGB EXTERIOR LUMINAIRES - DMX CONTROLa. OVERALL CONTROL WILL BE PROGRAMMED ON AT 5 AM AND OFF AT 11 PM.
COORDINATE FINAL SETTINGS WITH NMSU REPRESENTATIVE/USERS.b. CONTROLLER WILL PROVIDE AUTOMATED SELECTION OF MULTIPLE
SCENES WITH PROGRAMMING CAPABILITIESc. CONTROLLER WILL PROVIDE SCENES OF DIFFERENT COLORS THAT CAN
BE SELECTED MANUALLY AT CONTROL KEYPAD OR AUTOMATICALLY THOUGH A BACNET ENABLED FMS SYSTEM.
d. DMX CONTROLLER WILL BE LOCATED IN FIRST FLOOR JANITOR CLOSET.
LIGHTING SEQUENCE OF OPERATIONFOR PROGRAMMABLE CONTROL SETTINGS
NO SCALEE-604
2 LIGHTING RELAY PANEL DIAGRAM2
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:17:25-07'00'
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
E-701
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL LUMINAIRE SCHEDULES
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB
OU
ELECTRICAL LUMINAIRE SCHEDULE
TYPE DESCRIPTION VOLTS MOUNTINGLAMPS (NEED TO BE ENERGY STAR
OR DLC LISTED) LED DRIVERINPUTWATTS EM. BAT. PK. LENS MANUFACTURER/MODEL NOTES
A2 2' x 2' X 3 1/4" RECESSED LED VOLUMETRIC LUMINAIRE, COLD ROLLED STEELHOUSING, BAKED WHITE ENAMEL FINISH WITH MODULAR FIELD UPGRADEABLE LEDSAND DRIVERS. WHITE FINISH STANDARD
277 0R 120MULTI TAP
(UNV.)
RECESSED T-BAR LED3500K4400 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC METALUX #22CZ
AR 2' x 4' ARCHITECTURAL/DECORATIVE LED LUMINAIRE. HIGH ENERGY EFFICIENCY. LOWPROFILE, WIDE DISTRIBUTION WITH 0-10V DIMMING CONTROL. BAKED MATTE WHITEENAMEL FINISH.
277 OR 120MULTI-TAP
(UNV.)
CEILING RECESSED (LAY-IN GRID) LED3500K3000 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC METALUX # 24CZ 1
AR2 2' x 2' X 3 1/4" RECESSED LED VOLUMETRIC LUMINAIRE, COLD ROLLED STEELHOUSING, BAKED WHITE ENAMEL FINISH WITH MODULAR FIELD UPGRADEABLE LEDSAND DRIVERS. WHITE FINISH STANDARD
277 0R 120MULTI TAP
(UNV.)
RECESSED T-BAR LED3500K3000 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC METALUX #22CZ
AR2E 2' x 2' X 3 1/4" RECESSED LED VOLUMETRIC LUMINAIRE, COLD ROLLED STEELHOUSING, BAKED WHITE ENAMEL FINISH WITH MODULAR FIELD UPGRADEABLE LEDSAND DRIVERS. EMERGENCY THROUGH LIGHTING INVERTER. WHITE FINISH STANDARD
277 0R 120MULTI TAP
(UNV.)
RECESSED T-BAR LED3500K3000 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING
CIRCUIT
WHITE ACRYLIC METALUX #22CZ 1,2
ARD 2' x 4' ARCHITECTURAL/DECORATIVE LED LUMINAIRE. HIGH ENERGY EFFICIENCY. LOWPROFILE, WIDE DISTRIBUTION WITH 0-10V DIMMING CONTROL. BAKED MATTE WHITEENAMEL FINISH.
277 OR 120MULTI-TAP
(UNV.)
CEILING RECESSED (LAY-IN GRID) 4500 LUMEN LED,3500° K,85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC METALUX # 24CZ 1
ARE 2' x 4' ARCHITECTURAL/DECORATIVE LED LUMINAIRE. HIGH ENERGY EFFICIENCY. LOWPROFILE, WIDE DISTRIBUTION WITH 0-10V DIMMING CONTROL. BAKED MATTE WHITEENAMEL FINISH.
277 OR 120MULTI-TAP
(UNV.)
CEILING RECESSED (LAY-IN GRID) LED3500K3000 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING
CIRCUIT
WHITE ACRYLIC METALUX # 24CZ 1,3,4
Bl 4' LONG LIFE LED, HIGH ENERGY EFFICIENT LINEAR STRIP LUMINAIRE. BAKED MATTEWHITE ENAMEL FINISH.
277 OR 120MULTI-TAP
(UNV.)
CEILING SURFACE OR BOTTOM OFJOIST OR WALL MOUNTED AT 8'-0"
LED3500K3700 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE SEMI-FROST METALUX # 4SNLED 1,2
BlE 4' LONG LIFE LED, HIGH ENERGY EFFICIENT LINEAR STRIP LUMINAIRE. BAKED MATTEWHITE ENAMEL FINISH.
277 OR 120MULTI-TAP
(UNV.)
CEILING SURFACE OR BOTTOM OFJOIST OR WALL MOUNTED AT 8'-0"
LED3500K3700 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING
CIRCUIT
SEMI-FROST METALUX # 4SNLED 1,2
C1 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING. LISTED FOR DAMP LOCATION.
277 OR 120MULTI-TAP
(UNV.)
CEILING RECESSED LED3500K1500 LUMEN80 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE NO LENS (OPENOPTICS)
ATLANTIC # LED6 1
C1E 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING. LISTED FOR DAMP LOCATION.
277 OR 120MULTI-TAP
(UNV.)
CEILING RECESSED LED3500K1500 LUMEN80 CRI MIN.
0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING
CIRCUIT
NO LENS (OPENOPTICS)
ATLANTIC # LED6 1
C2 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING. WALL WASH OPTION.
277 OR 120MULTI-TAP
(UNV.)
CEILING RECESSED LED3500K1500 LUMEN80 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE NO LENS (OPENOPTICS)
ATLANTIC # LED6 1
C6 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING.
277 OR 120MULTI-TAP
(UNV.)
CEILING RECESSED LED3500K1500 LUMEN80 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE NO LENS (OPENOPTICS)
ATLANTIC # LED6 1
C6E 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING.
277 OR 120MULTI-TAP
(UNV.)
CEILING RECESSED LED3500K1500 LUMEN80 CRI MIN.
0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING
CIRCUIT
NO LENS (OPENOPTICS)
ATLANTIC # LED6 1
CA 6" ROUND LED CYLINDER TYPE DOWN LIGHT FIXTURE, CLEAR OPTICS, BLACK FINISH. 277 OR 120MULTI-TAP
(UNV.)
SURFACE MOUNTED TO DECK LED3000K1500 LUMEN80 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE CLEAR OPTIC ATLANTIC # SLED 610 1
CAE 6" ROUND LED CYLINDER TYPE DOWN LIGHT FIXTURE, CLEAR OPTICS, BLACK FINISH. 277 OR 120MULTI-TAP
(UNV.)
SURFACE MOUNTED TO DECK LED3000K1500 LUMEN80 CRI MIN.
0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING
CIRCUIT
CLEAR OPTIC ATLANTIC # SLED 610 1
E LED SINGLE FACED EXIT SIGN, EMERGENCY, DIE CAST ALUMINUM HOUSING WITHGREEN CHARACTERS, BLACK HOUSING AND BRUSHED ALUMINUM FACE (DIRECTIONALARROWS AS INDICATED ON LIGHTING PLANS). MEETS UL LISTINGS FOR THIS TYPE OFLUMINAIRE. WITH SELF-CONTAINED, SELF DIAGNOSING, EMERGENCY BATTERY PACK.
277 OR 120MULTI-TAP
(UNV.)
UNIVERSAL MOUNTING TO CEILINGOR WALL SURFACE 8'-6" A.F.F. OR AS
DIRECTED BY ARCHITECT
LED LAMPS NONE NICKELCADIMUMPER MFG.
BRUSHEDALUMINUM FACE
SURE-LITES # CX 1,2
E2 LED DOUBLE FACED EXIT SIGN, EMERGENCY, DIE CAST ALUMINUM HOUSING WITHGREEN CHARACTERS, BLACK HOUSING AND BRUSHED ALUMINUM FACE (DIRECTIONALARROWS AS INDICATED ON LIGHTING PLANS). MEETS UL LISTINGS FOR THIS TYPE OFLUMINAIRE. WITH SELF-CONTAINED, SELF DIAGNOSING, EMERGENCY BATTERY PACK.
277 OR 120MULTI-TAP
(UNV.)
CEILING SURFACE OR WALLSURFACE AT 8'-6" A.F.F. OR AS
DIRECTEDBY ARCHITECT
LED LAMPS NONE NICKELCADIMUMPER MFG.
BRUSHEDALUMINUM FACE
SURE-LITES # CX72S 1,2
F1 FLOODLIGHT IP66 RATED LUMINAIRE, HEAVY-DUTY, DIE CAST ALUMINUM HOUSING,ADJUSTED 5 DEGREE INCREMENTS, DISTRIBUTION 6 X 6 WIDE. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.
277 OR 120MULTI-TAP
(UNV.)
WALL SURFACE 9'-0" AFF OR ASINDICATED ON PLANS
LED4000K10,530 LUMEN
0-10V DIMMABLE LED DRIVER NONE IMPACTRESISTANTTEMPERED
LENS
LUMARK #NFFLD-C25 1
F1E FLOODLIGHT IP66 RATED LUMINAIRE, HEAVY-DUTY, DIE CAST ALUMINUM HOUSING,ADJUSTED 5 DEGREE INCREMENTS, DISTRIBUTION 6 X 6 WIDE. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.
277 OR 120MULTI-TAP
(UNV.)
WALL SURFACE 9'-0" AFF OR ASINDICATED ON PLANS
LED4000K10,530 LUMEN
0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING
CIRCUIT
IMPACTRESISTANTTEMPERED
LENS
LUMARK #NFFLD-C25 1
Fb EXTERIOR RECESSED DIE-CAST STEP LIGHT WITH STAINLESS STEEL FACE PLATE.9.5"H x 2"W x 3"D. IP65, MARINE GRADE, CORROSION RESISTANT, HEAVY WALLED,ALUMINUM CONSTRUCTION. WHITE FINISH STANDARD
277 0R 120MULTI TAP
(UNV.)
RECESSED ON WALL, 2 FT A.F.F. ORAS NOTED ON PLANS
LED4000K360 LUMENS
0-10V DIMMABLE LED DRIVER NONE 1/4" THICKTEMPERED
LENS
FC LIGHTING #FCSL902 1,3
FL2 8"H x 7"W x4"D, SLIM, LOW PROFILE ONE PIECE DIE CAST HOUSING. SILICONE SEALEDOPTICAL CHAMBER WITH IMPACT RESISTANT TEMPERED GLASS LENS, FULL CUT-OFF.WHITE FINISH STANDARD
277 OR 120MULTI-TAP
(UNV.)
WALL SURFACE 9'-0" AFF OR ASINDICATED ON PLANS
LED4000K2103 LUMEN
0-10V DIMMABLE LED DRIVER NONE IMPACTRESISTANTTEMPERED
LENS
LUMARK #XTOR 1
FL2E 8"H x 7"W x4"D, SLIM, LOW PROFILE ONE PIECE DIE CAST HOUSING. SILICONE SEALEDOPTICAL CHAMBER WITH IMPACT RESISTANT TEMPERED GLASS LENS, FULL CUT-OFF.WHITE FINISH STANDARD
277 OR 120MULTI-TAP
(UNV.)
WALL SURFACE 9'-0" AFF OR ASINDICATED ON PLANS
LED4000K2103 LUMEN
0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING
CIRCUIT
IMPACTRESISTANTTEMPERED
LENS
LUMARK #XTOR 1
Fo1 WALL MOUNTED 4' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING,INDIRECT/DIRECT, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.
277 0R 120MULTI TAP
(UNV.)
EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).
LED4000K1061 LUMEN/FT85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE DIFFUSE LENS A-LIGHT #D2 SERIES 1,2
Fo1E WALL MOUNTED 4' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING,INDIRECT/DIRECT, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.
277 0R 120MULTI TAP
(UNV.)
EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).
LED4000K1061 LUMEN/FT85 CRI MIN.
0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING
CIRCUIT
DIFFUSE LENS A-LIGHT #D2 SERIES 1,2
Fo2 WALL MOUNTED 4' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING, INDIRECTCOMPONENT ONLY, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.
277 0R 120MULTI TAP
(UNV.)
EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).
LED4000K1061 LUMEN/FT85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE DIFFUSE LENS A-LIGHT #D2 SERIES 1,2
Fo3 WALL MOUNTED 4' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING,INDIRECT/DIRECT, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.
277 0R 120MULTI TAP
(UNV.)
EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).
LED4000K530 LUMEN/FT85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE DIFFUSE LENS A-LIGHT #D2 SERIES 1,2
Fo3E WALL MOUNTED 4' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING,INDIRECT/DIRECT, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.
277 0R 120MULTI TAP
(UNV.)
EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).
LED4000K530 LUMEN/FT85 CRI MIN.
0-10V DIMMABLE LED DRIVER NMSUCONTINUOUS LIGHTING
CIRCUIT
DIFFUSE LENS A-LIGHT #D2 SERIES 1,2
Fo4 WALL MOUNTED 2' LONG X 3.5" DEPTH X 5.0" HEIGHT, SQUARE HOUSING,INDIRECT/DIRECT, LED LUMINAIRE WITH INTEGRAL POWER SUPPLY, AND ALUMINUMEXTRUDED HOUSING. SYMMETRIC NARROW DISTRIBUTION. COORDINATE FINISHCOLOR WITH ARCHITECT AT SUBMITTAL REVIEW.
277 0R 120MULTI TAP
(UNV.)
EXTERIOR WALL MOUNTED (REFERTO ARCHITECTURAL ELEVATIONS).
LED4000K1061 LUMEN/FT85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE DIFFUSE LENS A-LIGHT #D2 SERIES 1,3
LUMINAIRE SCHEDULE NOTES:1. MANUFACTURERS CATALOG NUMBERS REPRESENT MANUFACTURER SERIES. SHOP DRAWING SUBMITTALS WILL INCLUDE ALL PART NUMBERS REPRESENTING ALL ITEMS OF THIS LUMINAIRE SCHEDULE. IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO ORDER LUMINAIRES TO INCLUDE ALL PARTS INDICATED ON SCHEDULE FOR EACH LUMINAIRE. SUBMITTAL WILL CALL OUT EACH PART CLEARLY.2. LUMINAIRE REQUIRES MOUNTING COORDINATION WITH ARCHITECT PRIOR TO COMMENCEMENT OF ANY WORK. THIS LUMINAIRE MAY REQUIRE A HIGHER OR LOWER MOUTING FROM THAT PROVIDED ON THIS
SCHEDULE OR NOTES ON PLAN DUE TO ARCHITECTURAL REQUIREMENTS OR CONSTRUCTION CONDITIONS.
1,2
1,2
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:17:35-07'00'
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
E-702
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL LUMINAIRE SCHEDULES
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
Checker
Author
ELECTRICAL LUMINAIRE SCHEDULE (CONT.)
TYPE DESCRIPTION VOLTS MOUNTINGLAMPS (NEED TO BE ENERGY STAR
OR DLC LISTED) LED DRIVERINPUTWATTS
EM. BAT.PK. LENS MANUFACTURER/MODEL NOTES ADD. ALTER
L4 4' LONG HEAVY DUTY STEEL HOUSING, ONE – EXTRUDED LINEAR RIBBEDPOLYCARBONATE LENS, VANDAL RESISTANT, FINISHED IN MATTE WHITE STANDARD.
277 OR 120MULTI-TAP
(UNV)
PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”
AFF OR SURFACE MOUNTED TOCEILING.
LED3500K3503 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC FAILSAFE #HVSL 1,2
L8 8' LONG HEAVY DUTY STEEL HOUSING, ONE – EXTRUDED LINEAR RIBBEDPOLYCARBONATE LENS, VANDAL RESISTANT, FINISHED IN MATTE WHITE STANDARD.
277 OR 120MULTI-TAP
(UNV)
PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”
AFF OR SURFACE MOUNTED TOCEILING.
LED3500K3503 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC FAILSAFE #HVSL 1,2
L8E 8' LONG HEAVY DUTY STEEL HOUSING, ONE – EXTRUDED LINEAR RIBBEDPOLYCARBONATE LENS, VANDAL RESISTANT, FINISHED IN MATTE WHITE STANDARD.
277 OR 120MULTI-TAP
(UNV)
PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”
AFF OR SURFACE MOUNTED TOCEILING.
LED3500K3503 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NMSUCONTINUO
USLIGHTINGCIRCUIT
WHITE ACRYLIC FAILSAFE #HVSL 1,2
L83 8' LONG HEAVY DUTY STEEL HOUSING, ONE – EXTRUDED LINEAR RIBBEDPOLYCARBONATE LENS, VANDAL RESISTANT, FINISHED IN MATTE WHITE STANDARD.
277 OR 120MULTI-TAP
(UNV)
PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”
AFF OR SURFACE MOUNTED TOCEILING.
LED3000K3503 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE WHITE ACRYLIC FAILSAFE #HVSL 1,2 LITHONIA #LBL
L83E 8' LONG HEAVY DUTY STEEL HOUSING, ONE – EXTRUDED LINEAR RIBBEDPOLYCARBONATE LENS, VANDAL RESISTANT, FINISHED IN MATTE WHITE STANDARD.
277 OR 120MULTI-TAP
(UNV)
PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”
AFF OR SURFACE MOUNTED TOCEILING.
LED3000K3503 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NMSUCONTINUO
USLIGHTINGCIRCUIT
WHITE ACRYLIC FAILSAFE #HVSL 1,2 LITHONIA #LBL
LDMX HIGH PERFORMANCE, COLOR CHANGING, LINEAR SURFACE MOUNT LED LUMINAIREWITH EXTRUDED ALUMINUM HOUSING. PROVIDE WITH ADJUSTABLE BRACKETS ANDSNAP-IN CONNECTORS FOR DAISY CHAINING. (4) ROWS OF 7 FT NOMINAL LENGHT.
277 OR 120MULTI-TAP
(UNV.)
TOP MOUNT TO STRUCTURE ON THEINTERIOR OF LANTERN
LED4000K553 LM/FT85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE CLEARTEMPERED
GLASS COVERLENS
GVA LIGHTING #STR9-LITE RGB 1,2 METALUX #SNLED LENSED
LG 4' LONG X 6”W X 4”D SEMI-DIRECT ALUMINUM SQUARE HOUSING LED PENDANTLUMINAIRE WITH 0-10V DIMMING CAPABILITY. SUSPENDED WITH AIRCRAFT CABLETHAT IS FIELD ADJUSTABLE. COLOR TO BE MATTE WHITE.
277 OR 120MULTI-TAP
(UNV)
PROVIDE 24” ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”
AFF. REFER TO ARCHITECTURALSECTIONS FOR ADDITIONAL
INFORMATION.
LED3500K8078 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE CLEAR LINEARPRISMATIC
CORELITE #RZL-WB 1,2
LP 8' EXTRUDED ALUMINUM AND WELDED HOUSING LED DIRECT OUTPUT, PENDANTLUMINAIRE. LUMINAIRE WITH (2)0-10V DIMMING CAPABILITY FOR COLORS WHITE ANDRED COLOR. PROVIDE WITH 2 ROW FOR HIGUER LUMEN CAPACITY.
277 OR 120MULTI-TAP
(UNV)
PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”
AFF OR SURFACE MOUNTED TOCEILING.
LED3500K1020 LM/FT
0-10V DIMMABLE LED DRIVER(DUAL)
NONE WHITE ACRYLIC PMC LIGHTING #ES66-LED 1,2 LITHONIA #LBL
LP4 4' EXTRUDED ALUMINUM AND WELDED HOUSING LED DIRECT OUTPUT, PENDANTLUMINAIRE. LUMINAIRE WITH (2)0-10V DIMMING CAPABILITY FOR COLORS WHITE ANDRED COLOR. PROVIDE WITH 2 ROW FOR HIGUER LUMEN CAPACITY.
277 OR 120MULTI-TAP
(UNV)
PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”
AFF OR SURFACE MOUNTED TOCEILING.
LED3500K1020 LM/FT
0-10V DIMMABLE LED DRIVER(DUAL)
NONE WHITE ACRYLIC PMC LIGHTING #ES66-LED 1,2 LITHONIA #LBL
LPE 8' EXTRUDED ALUMINUM AND WELDED HOUSING LED DIRECT OUTPUT, PENDANTLUMINAIRE. LUMINAIRE WITH (2)0-10V DIMMING CAPABILITY FOR COLORS WHITE ANDRED COLOR. PROVIDE WITH 2 ROW FOR HIGUER LUMEN CAPACITY.
277 OR 120MULTI-TAP
(UNV)
PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”
AFF OR SURFACE MOUNTED TOCEILING.
LED3500K1020 LM/FT
0-10V DIMMABLE LED DRIVER(DUAL)
NMSUCONTINUO
USLIGHTINGCIRCUIT
WHITE ACRYLIC PMC LIGHTING #ES66-LED 1,2 LITHONIA #LBL
N1 FLAT LINEAR, LED CONTINUOUS RUN LUMINAIRE. IP68 RATED, WHITE FINISHSTANDARDS WITH REMOTE DRIVER. PROVIDE COMPATIBLE ALUMINUM, SUAREMOUNTING LOW PROFILE CHANNEL WITH LENS. .1.39" WIDE X 1.39" HEIGHT. (2) ROWS27' INDIVIDUAL LENGTH (VERIFY EXACT LENGHTS WITH CONSTRUCTIONCOORDINATION DRAWINGS)
277 0R 120MULTI TAP
(UNV.)
SURFACE MOUNTED TO CASEWORK LED3000K371 LM/FT
0-10V DIMMABLE LED DRIVER NONE FROSTED LENS OPTIC ARTS #FLEX DC 44, CHW 1,2 --
N2 EXTRUDED ALUMINUM 2" RECESSED LINEAR LED SLOT LUMINAIRE. FLANGED,CUSTOM TOTAL LENGTH = 146 FT WITH ONE 90 DEGREE RECESSED CORNER (VERIFYEXACT LENGHTS WITH CONSTRUCTION COORDINATION DRAWINGS). WHITE FINISHSTANDARD
277 0R 120MULTI TAP
(UNV.)
RECESSED CEILING. SEE ARCHPLANS FOR CEILING TYPE.
LED3500K1580 LUMENS
0-10V DIMMABLE LED DRIVER NONE FLUSH-SATINLENS
ZUMTOBEL SLOTLIGHT LED II 1,2 --
N3 EXTRUDED ALUMINUM 2" RECESSED LINEAR LED SLOT LUMINAIRE. FLANGED,CUSTOM TOTAL LENGTH = 146 FT WITH ONE 90 DEGREE RECESSED CORNER (VERIFYEXACT LENGHTS WITH CONSTRUCTION COORDINATION DRAWINGS). WHITE FINISHSTANDARD
277 0R 120MULTI TAP
(UNV.)
RECESSED CEILING. SEE ARCHPLANS FOR CEILING TYPE.
LED3500K1580 LUMENS
0-10V DIMMABLE LED DRIVER NONE FLUSH-SATINLENS
ZUMTOBEL SLOTLIGHT LED II 1,2
N6 FLAT LINEAR, LED CONTINUOUS RUN LUMINAIRE. IP68 RATED, WHITE FINISHSTANDARDS WITH REMOTE DRIVER. PROVIDE COMPATIBLE ALUMINUM, SUAREMOUNTING LOW PROFILE CHANNEL WITH LENS. .92" WIDE X .39" HEIGHT. 16'INDIVIDUAL LENGTH (VERIFY EXACT LENGHTS WITH CONSTRUCTION COORDINATIONDRAWINGS)
277 0R 120MULTI TAP
(UNV.)
SURFACE MOUNTED TO CANOPY LED4000K813 LM/FT
0-10V DIMMABLE LED DRIVER NONE FROSTED LENS OPTIC ARTS #FLEX DC 88, CHW 1,2 --
N12 EXTRUDED ALUMINUM 2" RECESSED LINEAR LED SLOT LUMINAIRE. FLANGED, 12'INDIVIDUAL LENGTH (VERIFY EXACT LENGHTS WITH CONSTRUCTION COORDINATIONDRAWINGS). WHITE FINISH STANDARD
277 0R 120MULTI TAP
(UNV.)
RECESSED CEILING. SEE ARCHPLANS FOR CEILING TYPE.
LED3500K1580 LUMENS
0-10V DIMMABLE LED DRIVER NONE FLUSH-SATINLENS
ZUMTOBEL SLOTLIGHT LED II 1,2 --
P8 3" ROUND LED, CYLINDER TYPE DOWN LIGHT FIXTURE. COORDINATE FINISH COLORWITH ARCHITECT AT SUBMITTAL REVIEW.
277 OR 120MULTI-TAP
(UNV.)
PENDANT CYLINDER (DOWN TOCEILING LEVEL)
LED3500K1360 LUMEN80 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE DIFFUSE LENS BRUCK #112 1 --
P8E 6" ROUND LED DOWN LIGHT FIXTURE, OPEN OPTICS, SEMI-SPECULAR CLEARREFLECTOR, WHITE TRIM RING. WHITE FINISH STANDARD
277 OR 120MULTI-TAP
(UNV.)
CEILING RECESSED LED3500K1500 LUMENS
LED DRIVER VIAGENERAT
OR
NO LENS (OPENOPTICS)
ATLANTIC # LED6OR APPROVED EQUAL.
1,2 --
P44 4" ROUND AND 4 FT LONG PENDANT CYLINDER LED DOWNLIGHT. MATTE WHITEALRYLIC DIFFUSER. WHITE FINISH STANDARD
277 0R 120MULTI TAP
(UNV.)
PENANT CYLINDER - COORDINATEFINAL MOUNTING WITH
ARCHITECTURAL DRAWINGS.
LED3500K6000 LUMENS
0-10V DIMMABLE LED DRIVER NONE NONE DELRAY #6300-4 1 KIRLING #LSR-12381-25L-MFL-ABS-87
P44E 4" ROUND AND 4 FT LONG PENDANT CYLINDER LED DOWNLIGHT. MATTE WHITEALRYLIC DIFFUSER. WHITE FINISH STANDARD
277 0R 120MULTI TAP
(UNV.)
PENANT CYLINDER - COORDINATEFINAL MOUNTING WITH
ARCHITECTURAL DRAWINGS.
LED3500K6000 LUMENS
0-10V DIMMABLE LED DRIVER NMSUCONTINUO
USLIGHTINGCIRCUIT
NONE DELRAY #6300-4 1 KIRLING #LSR-12381-25L-MFL-ABS-87
PD1 EXTRUDED ALUMINUM 4" PENDANT MOUNTED LINEAR LED SLOT LUMINAIRE. FLANGEDAT THE LENS TO ACCEPT THE CEILING PANELS, SINGLE LONG RUN - 8' INDIVIDUALLENGTH (VERIFY EXACT LENGHTS WITH CONSTRUCTION COORDINATION DRAWINGS).WHITE FINISH STANDARD
277 OR 120MULTI-TAP
(UNV)
PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”
AFF. REFER TO ARCHITECTURALSECTIONS FOR ADDITIONAL
INFORMATION.
LED3500K4136 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NONE FLUSH-SATINLENS
NEORAY #PDRS124 1,2 --
PDE EXTRUDED ALUMINUM 4" PENDANT MOUNTED LINEAR LED SLOT LUMINAIRE. FLANGEDAT THE LENS TO ACCEPT THE CEILING PANELS, SINGLE LONG RUN - 8' INDIVIDUALLENGTH (VERIFY EXACT LENGHTS WITH CONSTRUCTION COORDINATION DRAWINGS).WHITE FINISH STANDARD
277 OR 120MULTI-TAP
(UNV)
PROVIDE ADJUSTABLE AIR CRAFTCABLE. BOTTOM OF LUMINAIRE 9’-6”
AFF. REFER TO ARCHITECTURALSECTIONS FOR ADDITIONAL
INFORMATION.
LED3500K4136 LUMEN85 CRI MIN.
0-10V DIMMABLE LED DRIVER NMSUCONTINUO
USLIGHTINGCIRCUIT
FLUSH-SATINLENS
NEORAY #PDRS124 1,2 --
SB POLE MOUNTED WALKWAY LUMINAIRE, SINGLE HEAD, DIE CAST ALUMINUM HOUSING,GASKETED DOOR, FOUR INSET QUICK RELEASE FASTENERS FOR EASY RELAMPING,TYPE V DISTRIBUTION, HORIZONTAL FULL CUT OFF, ROUND STRAIGHT POLE. DARKSKY COMPLIANT. COORDINATE FINISH COLOR WITH ARCHITECT AT SUBMITTAL OFLUMINAIRES. PROVIDE FUSES AT BOTTOM OF POLE.
277 OR 120MULTI-TAP
(UNV)
12'-0" POLE LED4000K9000 LUMENS
LED DRIVER NONE FLAT, CLEAR,HIGH IMPACT,
TEMPEREDGLASS
IINVUE #MSA-E05LED-E1-5WQ-BK /SRX4A16-XXX-5
1,2
T1 ARCHITECTURAL STYLE LED WITH HIGH PERFORMANCE ENERGY EFFICIENT TRACKLUMINAIRE. 0-10V DIMMING CONTROL. EXTRUDED ALUMINUM, ANODIZED FINISH, TWOCIRCUIT, COMMERCIAL GRADE SYSTEM. COORDINATE FINISH COLOR WITHARCHITECT AT SUBMITTAL OF LUMINAIRES AND TRACK.
120 DOUBLE CIRCUIT TRACK MOUNTEDTO STRUCTURE
SURFACE MOUNT TO CEILING
DOUBLE CIRCUIT TRACK 0-10V DIMMABLE LED DRIVER NONE NONE ERCO 2-CIRCUIT TRACK 1 HALO #TEK4
TH CYLINDRICAL CAST ALUMINUM, POWDER COATED LED HEAD WITH FULL 360 DEGREETILT ADAPTER. .COORDINATE FINISH COLOR WITH ARCHITECT AT SUBMITTAL OFLUMINAIRES AND TRACK.
120 TRACK MOUNTEDSURFACE MOUNT TO CEILING
LED3000K1126 DELIVERED LUMENS PER HEAD90 CRI (MIN)
0-10V DIMMABLE LED DRIVER0-10V DIMMING
NONE SPHEROLITLENS FLOOD
ERCO #OPTECT SPOTLIGHT 1
U3 3' LONG X 1.5" WIDE X ".3 -.8" DEPTH,THIN PROFILE UNDERCABINET, LED LUMINAIREWITH EXTRUDED ALUMINUM HOUSING AND 0-10V DIMMING CONTROL. COORDINATEFINISH COLOR WITH ARCHITECT AT SUBMITTAL REVIEW. WHITE FINISH STANDARD.PROVIDE AND MOUNT POWER SUPPLY ADJACENT TO FIXTURE UNDER CABINET.
277 0R 120MULTI TAP
(UNV.)
UNDERCABINET SURFACE MOUNTED LED4000K300 LUMENS
0-10V DIMMABLE LED DRIVER NONE WHITE LENS SSL #UNL-36"-4K-WL 1,2 --
W2l UL LISTED CAST ALUMINUM HOUSING WITH WIRE GUARD. WHITE FINISH STANDARD 120 SURFACE 6" BELOW LOWER FLOORLEVEL IN ELEVATOR PIT
LED 0-10V DIMMABLE LED DRIVER NONE WIREGUARD LURALINE #LVB43 1,2 --
LUMINAIRE SCHEDULE NOTES:1. MANUFACTURERS CATALOG NUMBERS REPRESENT MANUFACTURER SERIES. SHOP DRAWING SUBMITTALS WILL INCLUDE ALL PART NUMBERS REPRESENTING ALL ITEMS OF THIS LUMINAIRE SCHEDULE. IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO ORDER LUMINAIRES TO INCLUDE ALL PARTS INDICATED ON SCHEDULE FOR EACH LUMINAIRE. SUBMITTAL WILL CALL OUT EACH PART CLEARLY.2. LUMINAIRE REQUIRES MOUNTING COORDINATION WITH ARCHITECT PRIOR TO COMMENCEMENT OF ANY WORK. THIS LUMINAIRE MAY REQUIRE A HIGHER OR LOWER MOUTING FROM THAT PROVIDED ON THIS
SCHEDULE OR NOTES ON PLAN DUE TO ARCHITECTURAL REQUIREMENTS OR CONSTRUCTION CONDITIONS.
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:17:47-07'00'
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
E-703
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL PANEL SCHEDULES
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB
OU
Notes:
Total Est. Demand Current: 6 ATotal Conn. Current: 5 A
Total Est. Demand: 4881 VALTG-EXT 2070 VA 125.00% 2588 VA Total Conn. Load: 3905 VALTG 1846 VA 125.00% 2308 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 3 A 5 A 7 ATotal Load: 720 VA 1388 VA 1815 VA
29 Spare 20 A 1 0 VA 0 VA -- -- Space 30
27 Spare 20 A 1 0 VA 0 VA -- -- Space 28
25 Spare 20 A 1 0 VA 0 VA -- -- Space 26
23 Spare 20 A 1 0 VA 0 VA -- -- Space 24
21 Spare 20 A 1 0 VA 0 VA -- -- Space 22
19 Spare 20 A 1 0 VA 0 VA -- -- Space 20
17 Spare 20 A 1 0 VA 0 VA -- -- Space 18
15 Spare 20 A 1 0 VA 0 VA -- -- Space 16
13 Spare 20 A 1 0 VA 0 VA -- -- Space 14
11 Spare 20 A 1 0 VA 0 VA -- -- Space 12
9 Spare 20 A 1 0 VA 0 VA -- -- Space 10
7 Spare 20 A 1 0 VA 0 VA -- -- Space 8
5 LTG EXTERIOR, STUDIO WING 20 A 1 1815... 0 VA -- -- Space 6
3 LTG LOCKERS 130G 20 A 1 861 VA 542 VA 1 20 A LTG TOP CORRIDOR STUDIO WING 4
1 Space -- -- 0 VA 720 VA 1 20 A LTG EXTERIOR YARD-1 140-1 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: MSB Phases: 3 Mains Type:Location: ELECTRICAL M150 Volts: 480/277 Wye A.I.C. Rating: 35000
Branch Panel: H1A
Notes:
Total Est. Demand Current: 10 ATotal Conn. Current: 8 A
Total Est. Demand: 8209 VALTG 6567 VA 125.00% 8209 VA Total Conn. Load: 6567 VAOther 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 10 A 5 A 9 ATotal Load: 2658 VA 1511 VA 2401 VA
29 Spare 20 A 1 0 VA 0 VA -- -- Space 30
27 Spare 20 A 1 0 VA 0 VA -- -- Space 28
25 Spare 20 A 1 0 VA 0 VA -- -- Space 26
23 Spare 20 A 1 0 VA 0 VA -- -- Space 24
21 Spare 20 A 1 0 VA 0 VA -- -- Space 22
19 Spare 20 A 1 0 VA 0 VA -- -- Space 20
17 Spare 20 A 1 0 VA 0 VA -- -- Space 18
15 Spare 20 A 1 0 VA 0 VA -- -- Space 16
13 Spare 20 A 1 0 VA 0 VA -- -- Space 14
11 LTG CLAY MIXING 122C 20 A 1 918 VA 0 VA -- -- Space 12
9 LTG ELEVATOR/STAIR LOBBY-1 100F-1 20 A 1 329 VA 324 VA 1 20 A LTG ROOM H101B, H101C, H101-1 10
7 LTG EXTERIOR, GALLERY WING 20 A 1 493 VA 756 VA 1 20 A LTG ROOM 124-1, 123-1, 122E, 122,... 8
5 LTG ROOM M125C, R123C, 130C, 130-... 20 A 1 726 VA 758 VA 1 20 A LTG STU.COLB & GRAD STUDIOS 6
3 LTG ROOM ST101AAAA, 108 20 A 1 290 VA 578 VA 1 20 A LTG ROOM 130-1, 130A 4
1 LTG ROOM105 20 A 1 52 VA 1366... 1 20 A LTG ROOM R112, 105, R108, 113, 107,... 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: MSB Phases: 3 Mains Type:Location: ELEC M125B Volts: 480/277 Wye A.I.C. Rating: 14000
Branch Panel: H1B
Notes:
Total Est. Demand Current: 7 ATotal Conn. Current: 6 A
Total Est. Demand: 5949 VALTG-EXT 600 VA 125.00% 750 VA Total Conn. Load: 4759 VALTG 4162 VA 125.00% 5202 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 7 A 5 A 5 ATotal Load: 1969 VA 1454 VA 1340 VA
29 Spare 20 A 1 0 VA 0 VA -- -- Space 30
27 Spare 20 A 1 0 VA 0 VA -- -- Space 28
25 Spare 20 A 1 0 VA 0 VA -- -- Space 26
23 Spare 20 A 1 0 VA 0 VA -- -- Space 24
21 Spare 20 A 1 0 VA 0 VA -- -- Space 22
19 Spare 20 A 1 0 VA 0 VA -- -- Space 20
17 Spare 20 A 1 0 VA 0 VA -- -- Space 18
15 Spare 20 A 1 0 VA 0 VA -- -- Space 16
13 Spare 20 A 1 0 VA 0 VA -- -- Space 14
11 Spare 20 A 1 0 VA 0 VA -- -- Space 12
9 LTG 20 A 1 82 VA 0 VA -- -- Space 10
7 LTG STUDY/ RESOURCE RM-1 229-1 20 A 1 336 VA 0 VA -- -- Space 8
5 LTG TOP CORRIDOR - STUDIO WING 20 A 1 826 VA 515 VA 1 20 A LTG GRADUATE STUDIO-1 220A-1 6
3 LTG - BOTTOM RIGHT STUDIO WING 20 A 1 434 VA 945 VA 1 20 A LTG 4
1 LTG-LEFT STUDIO WING 20 A 1 1098... 539 VA 1 20 A LTG - TOP RIGHT STUDIO WING 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: MSB Phases: 3 Mains Type:Location: ELEC. RM-1 M225B-1 Volts: 480/277 Wye A.I.C. Rating: 14000
Branch Panel: H2A
KEY NOTE
H1A H1B
H2A EM
EM1 EM2
Notes:
Total Est. Demand Current: 1 ATotal Conn. Current: 1 A
LTG 26 VA 125.00% 33 VA Total Est. Demand: 213 VANC 180 VA 100.00% 180 VA Total Conn. Load: 206 VAOther 0 VA 0.00% 0 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 2 A 0 ATotal Load: 180 VA 26 VA
29 Space -- -- 0 VA 0 VA -- -- Space 30
27 Space -- -- 0 VA 0 VA -- -- Space 28
25 Space -- -- 0 VA 0 VA -- -- Space 26
23 Space -- -- 0 VA 0 VA -- -- Space 24
21 Space -- -- 0 VA 0 VA -- -- Space 22
19 Space -- -- 0 VA 0 VA -- -- Space 20
17 Space -- -- 0 VA 0 VA -- -- Space 18
15 Space -- -- 0 VA 0 VA -- -- Space 16
13 Space -- -- 0 VA 0 VA -- -- Space 14
11 Other FABRICATION LAB-1 129-1 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 NC-FACP 20 A 1 180 VA 0 VA 1 20 A Spare 10
7 Other CONSERVATION LAB 115 20 A 1 26 VA 0 VA 1 20 A Spare 8
5 Other 20 A 1 0 VA 0 VA 1 20 A Spare 6
3 Other HALL H101F 20 A 1 0 VA 0 VA 1 20 A Spare 4
1 Other HALL H101F 20 A 1 0 VA 0 VA 1 20 A Spare 2
CKT Circuit Description Notes Trip Poles A B Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84Mounting: Surface Wires: 3 Mains Rating: 100 A
Supply From: EM Phases: 1 Mains Type:Location: ELEC M125B Volts: 120/240 Single A.I.C. Rating:
Branch Panel: EM1
Notes:
Total Est. Demand Current: 2 ATotal Conn. Current: 2 A
LTG 73 VA 125.00% 91 VA Total Est. Demand: 391 VANC 180 VA 100.00% 180 VA Total Conn. Load: 373 VAOther 120 VA 100.00% 120 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 2 A 1 ATotal Load: 227 VA 146 VA
29 Space -- -- 0 VA 0 VA -- -- Space 30
27 Space -- -- 0 VA 0 VA -- -- Space 28
25 Space -- -- 0 VA 0 VA -- -- Space 26
23 Space -- -- 0 VA 0 VA -- -- Space 24
21 Space -- -- 0 VA 0 VA -- -- Space 22
19 Space -- -- 0 VA 0 VA -- -- Space 20
17 Space -- -- 0 VA 0 VA -- -- Space 18
15 Space -- -- 0 VA 0 VA 1 20 A Spare 16
13 Space -- -- 0 VA 0 VA 1 20 A Spare 14
11 120 VA 0 VA 1 20 A Spare 12
9EM2 50 A 2
47 VA 0 VA 1 20 A Spare 10
7 26 VA 0 VA 1 20 A Spare 8
5EM1 50 A 2
180 VA 0 VA 1 20 A Spare 6
3 Other 20 A 1 0 VA 0 VA 1 20 A Spare 4
1 Other EXTERIOR YARD-1 140-1 20 A 1 0 VA 0 VA 1 20 A Spare 2
CKT Circuit Description Notes Trip Poles A B Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 30Mounting: Surface Wires: 3 Mains Rating: 100 A
Supply From: Phases: 1 Mains Type:Location: ELECTRICAL M150 Volts: 120/240 Single A.I.C. Rating: 10000
Branch Panel: EM
Notes:
Total Est. Demand Current: 1 ATotal Conn. Current: 1 A
Total Est. Demand: 179 VALTG 47 VA 125.00% 59 VA Total Conn. Load: 167 VAOther 120 VA 100.00% 120 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 0 A 1 ATotal Load: 47 VA 120 VA
29 Space -- -- 0 VA 0 VA -- -- Space 30
27 Space -- -- 0 VA 0 VA -- -- Space 28
25 Space -- -- 0 VA 0 VA -- -- Space 26
23 Space -- -- 0 VA 0 VA -- -- Space 24
21 Space -- -- 0 VA 0 VA -- -- Space 22
19 Space -- -- 0 VA 0 VA -- -- Space 20
17 Space -- -- 0 VA 0 VA -- -- Space 18
15 Space -- -- 0 VA 0 VA -- -- Space 16
13 Space -- -- 0 VA 0 VA -- -- Space 14
11 Other EXHIBITION HALL-1 H101-1 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 Other HALL-1 H201D-1 20 A 1 0 VA 0 VA 1 20 A Spare 10
7 Other DESIGN STUDIO-1 224-1 20 A 1 0 VA 0 VA 1 20 A Spare 8
5 Other HALL H201E 20 A 1 47 VA 0 VA 1 20 A Spare 6
3 Other 20 A 1 120 VA 0 VA 1 20 A Spare 4
1 Other 20 A 1 0 VA 0 VA 1 20 A Spare 2
CKT Circuit Description Notes Trip Poles A B Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 30Mounting: Surface Wires: 3 Mains Rating: 100 A
Supply From: EM Phases: 1 Mains Type:Location: ELEC. RM-1 M225B-1 Volts: 120/240 Single A.I.C. Rating:
Branch Panel: EM2
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:18:22-07'00'
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
E-704
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL PANEL SCHEDULES
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB
OU
Notes:
Total Est. Demand Current: 4 ATotal Conn. Current: 4 A
REC 720 VA 100.00% 720 VA Total Est. Demand: 1440 VAMTR 360 VA 100.00% 360 VA Total Conn. Load: 1440 VANC 360 VA 100.00% 360 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 9 A 3 A 0 ATotal Load: 1080 VA 360 VA 0 VA
29 Space -- -- 0 VA 0 VA -- -- Space 30
27 Space -- -- 0 VA 0 VA -- -- Space 28
25 Space -- -- 0 VA 0 VA -- -- Space 26
23 Space -- -- 0 VA 0 VA -- -- Space 24
21 Space -- -- 0 VA 0 VA -- -- Space 22
19 Space -- -- 0 VA 0 VA -- -- Space 20
17 Spare 20 A 1 0 VA 0 VA -- -- Space 18
15 Spare 20 A 1 0 VA 0 VA -- -- Space 16
13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 MTR ELECTRICAL M150 20 A 1 180 VA 0 VA 1 20 A Spare 10
7 REC ELECTRICAL M150 20 A 1 540 VA 0 VA 1 20 A Spare 8
5 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 6
3 MTR-HEATED ENCLOSURE 20 A 1 180 VA 0 VA 1 20 A Spare 4
1 REC LOCKERS 130G 20 A 1 540 VA 0 VA 1 20 A Spare 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: L1DB Phases: 3 Mains Type:Location: ELECTRICAL M150 Volts: 120/208 Wye A.I.C. Rating: 14000
Branch Panel: L1A
Notes:
Total Est. Demand Current: 102 ATotal Conn. Current: 152 A
REC 46680 VA 60.71% 28340 VA Total Est. Demand: 36590 VAMTR 1440 VA 100.00% 1440 VA Total Conn. Load: 54930 VANC 6810 VA 100.00% 6810 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 154 A 165 A 143 ATotal Load: 18250 VA 19580 VA 17100 VA
125 Spare 20 A 1 0 VA 0 VA -- -- Space 126
123 Spare 20 A 1 0 VA 0 VA -- -- Space 124
121 Spare 20 A 1 0 VA 0 VA -- -- Space 122
119 Spare 20 A 1 0 VA 0 VA -- -- Space 120
117 Spare 20 A 1 0 VA 0 VA -- -- Space 118
115 Spare 20 A 1 0 VA 0 VA -- -- Space 116
113 Spare 20 A 1 0 VA 0 VA -- -- Space 114
111 Spare 20 A 1 0 VA 0 VA -- -- Space 112
109 Spare 20 A 1 0 VA 0 VA -- -- Space 110
107 Spare 20 A 1 0 VA 0 VA -- -- Space 108
105 Spare 20 A 1 0 VA 0 VA -- -- Space 106
103 MTR MECHANICAL ROOM M125C 20 A 1 360 VA 0 VA -- -- Space 104
101 REC Room ST101O, 120K 20 A 1 540 VA 0 VA -- -- Space 102
99 REC Room ST101O, 120K 20 A 1 540 VA 0 VA 1 20 A Spare 100
97 REC Room ST101O, 120K, 120L 20 A 1 540 VA 0 VA 1 20 A Spare 98
95 REC Room ST101O, 120L, 120K 20 A 1 540 VA 0 VA 1 20 A Spare 96
93 REC GRADUATE STUDIO 120L 20 A 1 540 VA 0 VA 1 20 A Spare 94
91 REC GRADUATE STUDIO 120L 20 A 1 540 VA 0 VA 1 20 A Spare 92
89 REC DROP-CORD, LAB 129 20 A 1 180 VA 0 VA 1 20 A Spare 90
87 REC DROP-CORD, LAB 129 20 A 1 180 VA 0 VA 1 20 A Spare 88
85 REC DROP-CORD, LAB 129 20 A 1 180 VA 0 VA 1 20 A Spare 86
83 REC DROP-CORD, LAB 129 20 A 1 180 VA 0 VA 1 20 A Spare 84
81 REC VENDING MACHINE, HALL H101F 20 A 1 1200... 600 VA 1 20 A REC DIGITAL SIGNAGE, LOBBY-1... 82
79 REC VENDING MACHINE, HALL H101F 20 A 1 1200... 300 VA 1 20 A NC PROJECTION SCREEN, STUDY 106 80
77 REC VENDING MACHINE, HALL H101F 20 A 1 1200... 360 VA 1 20 A REC RECEIVING YARD-1 140A-1 78
75 REC RETABLOS GALLERY 110 20 A 1 540 VA 1200... 1 20 A NC HANDICAP DOOR, VEST. 100E 76
73 REC RETABLOS GALLERY 110 20 A 1 540 VA 600 VA 1 20 A NC HANDICAP DOOR, H101E 74
71 NC SUPPORT EXTRACTOR,... 20 A 1 400 VA 600 VA 1 20 A REC WATER COOLER, HALL H101D 72
69 REC ROOM 100B-1, H101-1 20 A 1 660 VA 360 VA 1 20 A REC WATER COOLER, HALL H101F 70
67 REC CORRIDOR 20 A 1 780 VA 540 VA 1 20 A REC STUDENT COLLABORATION-1... 68
65 REC CORRIDOR 20 A 1 960 VA 540 VA 1 20 A REC STUDENT COLLABORATION-1... 66
63 DRINKING FOUNTAING - REC HALL... 20 A 1 360 VA 720 VA 1 20 A REC HALL 101F 64
61 REC ROOM 106-1 20 A 1 360 VA 1080... 1 20 A REC HALL 101E, 101F J131 62
59 REC UAG COLLECTION STUDY-1 106-1 20 A 1 540 VA 1080... 1 20 A REC HALL 101E, 101F 60
57 REC ROOM 109, 111 20 A 1 720 VA 540 VA 1 20 A REC GRADUATE STUDIO 120H 58
55 REC ROOM 109, 111 20 A 1 720 VA 540 VA 1 20 A REC GRADUATE STUDIO 120H 56
53 DWH-1-REC MECHANICAL ROOM... 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120G 54
51 WS-1-REC MECHANICAL ROOM M125C 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120G 52
49 REC ELEVATOR/STAIR LOBBY-1 100F-1 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120F 50
47 NC ELEVATOR/STAIR LOBBY-1 100F-1 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120F 48
45 FSD-MTR RETABLOS GALLERY 110 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO 120E 46
43 FSD-MTR RETABLOS GALLERY 110 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO 120E 44
41 FACP 20 A 1 500 VA 540 VA 1 20 A REC GRADUATE STUDIO 120D 42
39 PROJECTOR SCREEN FABRICATION... 20 A 1 500 VA 540 VA 1 20 A REC GRADUATE STUDIO 120D 40
37 30N PAINT BOOTH LIGHTING 20 A 1 250 VA 540 VA 1 20 A REC GRADUATE STUDIO 120C 38
35 REC REFRIGERATOR 20 A 1 900 VA 540 VA 1 20 A REC GRADUATE STUDIO 120C 36
33 REC ART GALLERY 105 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120B 34
31 REC ART GALLERY 105 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120B 32
29 REC ROOM 118H, 118G 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120A 30
27 REC ROOM 118H, 118G, H101C 20 A 1 180 VA 540 VA 1 20 A REC GRADUATE STUDIO 120A 28
25 REC ROOM 118H, 118F 20 A 1 540 VA 600 VA 1 20 A REC REFR, GRADUATE STUDIO 120L 26
23 REC ROOM 118H, 118F 20 A 1 720 VA 540 VA 1 20 A REC SPACE ST101O 24
21 REC ROOM 118E, 118D, 118C 20 A 1 1080... 720 VA 1 20 A REC SPACE ST101O 22
19 REC ROOM 118E, 118D, 118C 20 A 1 1080... 1080... 1 20 A REC ROOM 120K, 120L 20
17 REC ROOM 118A, 118B 20 A 1 900 VA 900 VA 1 20 A REC ROOM 120K, 120L 18
15 REC ROOM 118A, 118B 20 A 1 1080... 1200... 1 20 A REC VENDING MACHINE , HALL H101E 16
13 REC RETABLOS 110 20 A 1 540 VA 180 VA 1 20 A REC HALL H101F 14
11 REC RETABLOS 110 20 A 1 360 VA 720 VA 1 20 A REC FABRICATION LAB-1 129-1 12
9 REC GALLERY STORAGE 108 20 A 1 600 VA 720 VA 1 20 A REC FABRICATION LAB-1 129-1 10
7 REC GALLERY STORAGE 108 20 A 1 540 VA 180 VA 1 20 A NC IRRIGATION 8
5 REC CEILING PROJECTOR, STUDY 106 20 A 1 600 VA 600 VA 1 20 A REC CEILING PROJECTOR, LAB129 6
3 NC HANDICAP DOOR, 100A 20 A 1 1200... 540 VA 1 20 A REC JEWELRY FACULTY 130D-1 4
1 NC HANDICAP DOOR, H101 20 A 1 1200... 720 VA 1 20 A REC JEWELRY FACULTY 130D-1 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 126 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type:Location: ELEC M125B Volts: 120/208 Wye A.I.C. Rating: 14000
Branch Panel: L1B
KEY NOTE
L1A L2A
LPL1B
Notes:
Total Est. Demand Current: 81 ATotal Conn. Current: 128 A
Total Est. Demand: 29105 VAREC 43770 VA 61.42% 26885 VA Total Conn. Load: 45990 VANC 2220 VA 100.00% 2220 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 129 A 134 A 122 ATotal Load: 15420 VA 15910 VA 14660 VA
125 Space -- -- 0 VA 0 VA -- -- Space 126
123 Space -- -- 0 VA 0 VA -- -- Space 124
121 Space -- -- 0 VA 0 VA -- -- Space 122
119 Space -- -- 0 VA 0 VA -- -- Space 120
117 Space -- -- 0 VA 0 VA -- -- Space 118
115 Space -- -- 0 VA 0 VA -- -- Space 116
113 Space -- -- 0 VA 0 VA -- -- Space 114
111 Space -- -- 0 VA 0 VA -- -- Space 112
109 Space -- -- 0 VA 0 VA -- -- Space 110
107 Space -- -- 0 VA 0 VA -- -- Space 108
105 Space -- -- 0 VA 0 VA -- -- Space 106
103 Space -- -- 0 VA 0 VA -- -- Space 104
101 Space -- -- 0 VA 0 VA -- -- Space 102
99 Space -- -- 0 VA 0 VA 1 20 A Spare 100
97 Space -- -- 0 VA 0 VA 1 20 A Spare 98
95 Space -- -- 0 VA 0 VA 1 20 A Spare 96
93 Space -- -- 0 VA 0 VA 1 20 A Spare 94
91 Space -- -- 0 VA 0 VA 1 20 A Spare 92
89 Space -- -- 0 VA 0 VA 1 20 A Spare 90
87 Space -- -- 0 VA 0 VA 1 20 A Spare 88
85 Space -- -- 0 VA 0 VA 1 20 A Spare 86
83 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 900 VA 0 VA 1 20 A Spare 84
81 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 1080... 0 VA 1 20 A Spare 82
79 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 1080... 0 VA 1 20 A Spare 80
77 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 1830... 0 VA 1 20 A Spare 78
75 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 1080... 0 VA 1 20 A Spare 76
73 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 1080... 0 VA 1 20 A Spare 74
71 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 72
69 REC DIGITAL OUTPUT/ PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 70
67 REC PRINTER, DIGITAL PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 68
65 REC PRINTER, DIGITAL PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 66
63 REC PRINTER, DIGITAL PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 64
61 REC PRINTER, DIGITAL PRINTING-1... 20 A 1 750 VA 0 VA 1 20 A Spare 62
59 REC SCANNER, DIGITAL PRINTING-1... 20 A 1 750 VA 500 VA 1 20 A SCREEN CONFERENCE RM-1 235-1 60
57 REC SCANNER, DIGITAL PRINTING-1... 20 A 1 750 VA 360 VA 1 20 A REC COMPUTER LAB-1 231-1 58
55 REC SCANNER, DIGITAL PRINTING-1... 20 A 1 750 VA 360 VA 1 20 A REC COMPUTER LAB-1 231-1 56
53 REC TECHNOLOGY LAB-1 233-1 20 A 1 540 VA 360 VA 1 20 A REC COMPUTER LAB-1 231-1 54
51 REC CEILING PROJECTOR,... 20 A 1 1100... 360 VA 1 20 A REC COMPUTER LAB-1 231-1 52
49 REC MAC LAB-1 231-1 20 A 1 540 VA 720 VA 1 20 A REC DESIGN STUDIO-1 224-1 50
47 REC MAC LAB-1 231-1 20 A 1 720 VA 180 VA 48
45 REC CEILING PROJECTOR, LAB-1... 20 A 1 1100... 180 VA2 20 A REC TECHNOLOGY LAB-1 233-1
46
43 REC HALL-1 H201F-1 20 A 1 720 VA 360 VA 1 20 A REC COMPUTER LAB-1 231-1 44
41 REC TECHNOLOGY LAB-1 233-1 20 A 1 360 VA 360 VA 1 20 A REC COMPUTER LAB-1 231-1 42
39 REC TECHNOLOGY LAB-1 233-1 20 A 1 900 VA 540 VA 1 20 A REC HALL H201E 40
37 REC TECHNOLOGY LAB-1 233-1 20 A 1 720 VA 900 VA 1 20 A REC Room T225A-1, H201F-1, H201E,... 38
35 REC LASER CUTTER, LAB-1 233-1 20 A 1 180 VA 1080... 1 20 A REC Room R223A-1, T225A-1, H201D,... 36
33 REC TECHNOLOGY LAB-1 233-1 20 A 1 600 VA 1080... 1 20 A REC Room R223B-1, H201G-1, H201F-... 34
31 REC SCANNER, TECHNOLOGY LAB-1... 20 A 1 750 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220A-1 32
29 REC 3D PRINTER, TECHNOLOGY LAB... 20 A 1 360 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220A-1 30
27 REC TECHNOLOGY LAB-1 233-1 20 A 1 360 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220B-1 28
25 REC JEWELRY FACULTY STUDIO-1... 20 A 1 360 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220B-1 26
23 REC JEWELRY FACULTY STUDIO-1... 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220C-1 24
21 REC PROJECTOR , RM 236 20 A 1 600 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220C-1 22
19 REC CONFERENCE RM-1 235-1 20 A 1 720 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220D-1 20
17 REC CONFERENCE RM-1 235-1 20 A 1 720 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220D-1 18
15 REC PAINTING FACULTY STUDIO-1... 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220E-1 16
13 REC PAINTING FACULTY STUDIO-1... 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220E-1 14
11 REC PHOTO FACULTY STUDIO-1... 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220F-1 12
9 REC PHOTO FACULTY STUDIO-1... 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220F-1 10
7 REC PRTN FACULTY STUDIO-1 238C-1 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220G-1 8
5 REC PRTN FACULTY STUDIO-1 238C-1 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220G-1 6
3 REC PRNT FACULTY STUDIO-1 238D-1 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220H-1 4
1 REC PRNT FACULTY STUDIO-1 238D-1 20 A 1 540 VA 540 VA 1 20 A REC GRADUATE STUDIO-1 220H-1 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 126Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: L2DB Phases: 3 Mains Type:Location: ELEC. RM-1 M225B-1 Volts: 120/208 Wye A.I.C. Rating: 14000
Branch Panel: L2A
Notes:
Total Est. Demand Current: 64 ALTG 696 VA 125.00% 870 VA Total Conn. Current: 63 AREC 3600 VA 100.00% 3600 VA Total Est. Demand: 22909 VAMTR 4687 VA 100.00% 4687 VA Total Conn. Load: 22735 VANC 13752 VA 100.00% 13752 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 82 A 42 A 74 ATotal Load: 9321 VA 5005 VA 8409 VA
41 Space -- -- 0 VA 0 VA -- -- Space 42
39 Space -- -- 0 VA 0 VA -- -- Space 40
37 IP-1 20 A 1 997 VA 0 VA -- -- Space 38
35 IP-3 20 A 1 1696 VA 0 VA -- -- Space 36
33 Spare 20 A 1 0 VA 0 VA -- -- Space 34
31 AHU LTS/POW 20 A 1 500 VA 0 VA -- -- Space 32
29 AHU-1 LTS/POW 20 A 1 500 VA 0 VA 1 20 A Spare 30
27 AHU-2 LTS/POW 20 A 1 500 VA 0 VA 1 20 A Spare 28
25 REC PENTHOUSE 20 A 1 1260 VA 0 VA 1 20 A Spare 26
23 REC 20 A 1 900 VA 0 VA 1 20 A Spare 24
21 REC 2ND FLOOR ROOF S 20 A 1 720 VA 0 VA 1 20 A Spare 22
19 2028 VA 0 VA 1 20 A Spare 20
17CU-5 20 A 2
2028 VA 0 VA 1 20 A Spare 18
15 1560 VA 0 VA 1 20 A Spare 16
13CU-4 20 A 2
1560 VA 0 VA 1 20 A Spare 14
11 728 VA 0 VA 1 20 A Spare 12
9CU-3 15 A 2
728 VA 0 VA 10
7 1560 VA 0 VA2 20 A Spare
8
5CU-2 20 A 2
1560 VA 997 VA 1 20 A MTR-IP-3 6
3 NC 20 A 1 500 VA 997 VA 1 20 A MTR-IP-2 4
1 REC LOWER ROOF 20 A 1 720 VA 696 VA 1 20 A EF-2 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: TP Phases: 3 Mains Type:Location: MECH. PENTHOUSE M300 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: LP225A
30
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:18:37-07'00'
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
E-705
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL PANEL SCHEDULES
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
Checker
Author
SKIRT: TOP & BOTTOMNotes:
Total Est. Demand Current: 56 ATotal Conn. Current: 63 A
REC 14802 VA 83.78% 12401 VA Total Est. Demand: 20161 VANC 7760 VA 100.00% 7760 VA Total Conn. Load: 22562 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 76 A 77 A 43 ATotal Load: 8593 VA 8773 VA 5197 VA
83 Spare 20 A 1 0 VA 0 VA -- -- Space 84
81 Spare 20 A 1 0 VA 0 VA -- -- Space 82
79 Spare 20 A 1 0 VA 0 VA -- -- Space 80
77 Spare 20 A 1 0 VA 0 VA -- -- Space 78
75 Spare 20 A 1 0 VA 0 VA -- -- Space 76
73 Spare 20 A 1 0 VA 0 VA -- -- Space 74
71 Spare 20 A 1 0 VA 0 VA -- -- Space 72
69 Spare 20 A 1 0 VA 0 VA -- -- Space 70
67 Spare 20 A 1 0 VA 0 VA -- -- Space 68
65 Spare 20 A 1 0 VA 0 VA -- -- Space 66
63 Spare 20 A 1 0 VA 0 VA -- -- Space 64
61 Spare 20 A 1 0 VA 0 VA -- -- Space 62
59 Spare 20 A 1 0 VA 0 VA -- -- Space 60
57 Spare 20 A 1 0 VA 0 VA -- -- Space 58
55 Spare 20 A 1 0 VA 0 VA -- -- Space 56
53 Spare 20 A 1 0 VA 0 VA -- -- Space 54
51 Spare 20 A 1 0 VA 0 VA -- -- Space 52
49 Spare 20 A 1 0 VA 0 VA -- -- Space 50
47 Spare 20 A 1 0 VA 0 VA -- -- Space 48
45 Spare 20 A 1 0 VA 0 VA -- -- Space 46
43 Spare 20 A 1 0 VA 0 VA -- -- Space 44
41 Spare 20 A 1 0 VA 0 VA -- -- Space 42
39 Spare 20 A 1 0 VA 0 VA -- -- Space 40
37 Spare 20 A 1 0 VA 0 VA -- -- Space 38
35 Spare 20 A 1 0 VA 0 VA -- -- Space 36
33 Spare 20 A 1 0 VA 0 VA -- -- Space 34
31 Spare 20 A 1 0 VA 0 VA -- -- Space 32
29 REC DROP-CORD, WOOD SHOP-1 126-1 20 A 1 180 VA 0 VA -- -- Space 30
27 2184 VA 0 VA -- -- Space 28
25 20E SAW TABLE LAB UNIT, WOODEQUIPMENT SHOP-1 126-1 30 A 2
2184 VA 0 VA -- -- Space 26
23 REC WOOD EQUIPMENT SHOP-1 126-1 20 A 1 360 VA 0 VA -- -- Space 24
21 REC WOOD EQUIPMENT SHOP-1 126-1 20 A 1 720 VA 0 VA -- -- Space 22
19 REC WOOD EQUIPMENT SHOP-1 126-1 20 A 1 540 VA 0 VA -- -- Space 20
17 REC MITER SAW, SHOP-1 126-1 20 A 1 1800 VA 0 VA -- -- Space 18
15 22E REC DRILL PRESS SHOP-1 126-1 20 A 1 1800 VA 0 VA -- -- Space 16
13 27E REC BANDSAW, SHOP-1 126-1 30 A 1 1800 VA 0 VA -- -- Space 14
11 24E REC DISC SANDER SHOP-1 126-1 20 A 1 1680 VA 0 VA -- -- Space 12
9 1177 VA 0 VA -- -- Space 10
7 1177 VA 0 VA -- -- Space 8
525E MTR WOOD EQUIPMENT SHOP-1126-1 20 A 3
1177 VA 0 VA -- -- Space 6
3 1196 VA 1696 VA 1 20 A 50N AIR FILTER WOOD SHOP-1 126-1 4
1 26E REC WOOD EQUIPMENT SHOP-1126-1 20 A 2
1196 VA 1696 VA 1 20 A 50N AIR FILTER WOOD SHOP-1 126-1 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: L1DB Phases: 3 Mains Type:Location: WOOD SHOP-1 126-1 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 1LP2
SKIRT: TOP & BOTTOMNotes:
Total Est. Demand Current: 93 ATotal Conn. Current: 145 A
REC 48157 VA 60.38% 29079 VA Total Est. Demand: 33331 VANC 4252 VA 100.00% 4252 VA Total Conn. Load: 52409 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 138 A 154 A 147 ATotal Load: 16558 VA 18384 VA 17468 VA
83 REC ROOM 122B-1, 122C 20 A 1 720 VA 0 VA -- -- Space 84
81 REC CERAMICS FACULTY STUDIO 122A 20 A 1 540 VA 0 VA -- -- Space 82
79 REC CERAMICS FACULTY STUDIO 122A 20 A 1 540 VA 0 VA -- -- Space 80
77 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 78
75 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 76
73 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 74
71 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 72
69 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 70
67 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 68
65 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 66
63 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 64
61 REC DROP-CORD, CERAMICS 122 20 A 1 180 VA 0 VA -- -- Space 62
59 REC CERAMICS 122 20 A 1 540 VA 0 VA -- -- Space 60
57 REC CERAMICS 122 20 A 1 720 VA 0 VA -- -- Space 58
55 REC CERAMICS 122 20 A 1 900 VA 0 VA -- -- Space 56
53 REC CEILING PROJECTOR, CERAMICS... 20 A 1 600 VA 0 VA 1 20 A Spare 54
51 1560 VA 0 VA 1 20 A Spare 52
4939E REC CLAY MIXING 122C 20 A 2
1560 VA 0 VA 1 20 A Spare 50
47 40E REC PUGMILL, CLAY MIXING 122C 30 A 1 3000 VA 0 VA 1 20 A Spare 48
45 720 VA 0 VA 1 20 A Spare 46
43 720 VA 0 VA 1 20 A Spare 44
41
42E REC CLAY MIXING 122C 20 A 3
720 VA 0 VA 1 20 A Spare 42
39 1141 VA 0 VA 1 20 A Spare 40
37 1141 VA 0 VA 1 20 A Spare 38
35
37E REC CLAY MIXING 122C 20 A 3
1141 VA 0 VA 1 20 A Spare 36
33 540 VA 0 VA 1 20 A Spare 34
31 540 VA 0 VA 1 20 A Spare 32
29
43E REC CLAY MIXING 122C 20 A 3
540 VA 0 VA 1 20 A Spare 30
27 REC AIR CLEANER, GLAZE LAB-1 122B-1 25 A 1 1656 VA 1696 VA 1 20 A 41E AIR FILTER 28
25 NC EXHAUST, GLAZE LAB-1 122B-1 20 A 1 180 VA 500 VA 1 20 A PROJECTOR SCREEN CERAMICS 122 26
23 32E REC LAMAN SLIP MIXER, CERAMICS... 20 A 1 1176 VA 600 VA 1 20 A PROJECTOR CERAMICS 122 24
21 REC AIR COMPRESSOR, CERAMICS 122 30 A 1 1920 VA 180 VA 1 20 A REC DROP-CORD, MOLD RM-1 123-1 22
19 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 180 VA 1 20 A REC DROP-CORD, MOLD RM-1 123-1 20
17 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 720 VA 1 20 A REC MOLD RM-1 123-1 18
15 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 720 VA 1 20 A REC MOLD RM-1 123-1 16
13 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 540 VA 1 20 A REC WET ROOM 122E 14
11 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 900 VA 1 20 A REC WASOUT SINK, ROOM 122C, 122B-1 12
9 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 180 VA 1 20 A NC EYE WASH, CERAMICS 122 10
7 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 2520 VA 8
5 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 2520 VA 6
3 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 2520 VA
3 20 A REC CLAY MIXING 122C
4
1 REC POTTER WHEEL, CERAMICS 122 30 A 1 1250 VA 1696 VA 1 20 A 36E HEPA AIR FILTER 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: L1DB Phases: 3 Mains Type:Location: CERAMICS 122 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 1LP4
Notes:
Total Est. Demand Current: 74 ATotal Conn. Current: 111 A
REC 37188 VA 63.45% 23594 VA Total Est. Demand: 26534 VANC 2940 VA 100.00% 2940 VA Total Conn. Load: 40128 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 105 A 108 A 123 ATotal Load: 12570 VA 12882 VA 14676 VA
83 84
81 82
79 80
77 78
75 76
73 74
71 72
69 70
67 68
65 66
63 64
61 62
59 60
57 REC METALS/JEWELRY-1 130-1 20 A 1 1440 VA 58
55 REC METALS/JEWELRY-1 130-1 20 A 1 1440 VA 56
53 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 54
51 REC METALS/JEWELRY-1 130-1 20 A 1 360 VA 52
49 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 50
47 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 48
45 1040 VA 46
43REC ENAMEL 130A 20 A 2
1040 VA 44
41 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 42
39 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 540 VA 1 20 A REC METALS/JEWELRY-1 130-1 40
37 REC METALS/JEWELRY-1 130-1 20 A 1 720 VA 180 VA 1 20 A REC METALS/JEWELRY-1 130-1 38
35 REC METALS/JEWELRY-1 130-1 20 A 1 360 VA 540 VA 1 20 A REC METALS/JEWELRY-1 130-1 36
33 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 540 VA 1 20 A NC METALS/JEWELRY-1 130-1 34
31 REC METALS/JEWELRY-1 130-1 20 A 1 540 VA 1260 VA 1 20 A NC ENAMEL 130A 32
29 99E REC METALS/JEWELRY-1 130-1 20 A 1 720 VA 360 VA 1 20 A REC ENAMEL 130A 30
27 200 VA 540 VA 1 20 A REC RAISING ROOM 130B 28
25 REC PUK 4 MICRO WELDER,METALS/JEWELRY STUDIO-1 130-1 30 A 2
200 VA 540 VA 1 20 A REC RAISING ROOM 130B 26
23 REC METALS/JEWELRY-1 130-1 20 A 1 1656 VA 1980 VA 1 20 A REC METALS/JEWELRY STUDIO-1 130-1 24
21 98E REC KILN, ENAMEL 130A 20 A 1 1440 VA 1620 VA 1 20 A REC METALS/JEWELRY STUDIO-1 130-1 22
19 REC BAND SAW, STUDIO-1 130-1 30 A 1 1920 VA 1440 VA 1 20 A REC METALS/JEWELRY STUDIO-1 130-1 20
17 REC BELT SANDER, STUDIO-1 130-1 20 A 1 864 VA 1440 VA 1 20 A REC METALS/JEWELRY STUDIO-1 130-1 18
15 REC SANDER, STUDIO-1 130-1 20 A 1 1176 VA 720 VA 1 20 A REC METALS/JEWELRY STUDIO-1 130-1 16
13 REC SCROLL SAW, STUDIO-1 130-1 20 A 1 80 VA 900 VA 1 20 A REC Room 130A, 130-1 14
11 REC METAL MATHE, STUDIO-1 130-1 25 A 1 1656 VA 900 VA 1 20 A REC Room 130A, 130-1 12
9 REC METAL MATHE, STUDIO-1 130-1 25 A 1 1656 VA 180 VA 1 20 A NC FUME HOOD, STUDIO-1 130-1 10
7 REC DRILL PRESS, STUDIO-1 130-1 20 A 1 240 VA 180 VA 1 20 A NC FUME HOOD, STUDIO-1 130-1 8
5 REC DRILL PRESS, STUDIO-1 130-1 35 A 1 2400 VA 180 VA 1 20 A 27N NC FUME HOOD, STUDIO-1 130-1 6
3 REC SLOW COOKER, STUDIO-1 130-1 20 A 1 250 VA 100 VA 1 20 A NC SUPPORT EXTRACTOR, JEWELRY-1... 4
1 REC SLOW COOKER, STUDIO-1 130-1 20 A 1 250 VA 1100 VA 1 20 A REC CEILING PROJECTOR , STUDIO-1... 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: L1DB Phases: 3 Mains Type:Location: METALS/JEWELRY-1 130-1 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 1LP1
KEY NOTE
1LP1 1LP2
1LP41LP3
SKIRT: TOP & BOTTOMNotes:
Total Est. Demand Current: 72 ATotal Conn. Current: 114 A
REC 40632 VA 62.31% 25316 VA Total Est. Demand: 25846 VANC 530 VA 100.00% 530 VA Total Conn. Load: 41162 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 113 A 98 A 137 ATotal Load: 13264 VA 11720 VA 16178 VA
83 Spare 20 A 1 0 VA 0 VA -- -- Space 84
81 Spare 20 A 1 0 VA 0 VA -- -- Space 82
79 Spare 20 A 1 0 VA 0 VA -- -- Space 80
77 Spare 20 A 1 0 VA 0 VA -- -- Space 78
75 Spare 20 A 1 0 VA 0 VA -- -- Space 76
73 Spare 20 A 1 0 VA 0 VA -- -- Space 74
71 REC HYDRAULIC PRESS, SCULPTURE-1... 20 A 1 600 VA 0 VA -- -- Space 72
69 REC BENCH GRINDER, SCULPTURE-1... 20 A 1 600 VA 0 VA -- -- Space 70
67 NC SUPPORT EXTRACTOR, SCULPTURE... 20 A 1 50 VA 0 VA -- -- Space 68
65 0 VA -- -- Space 66
63 0 VA -- -- Space 64
61 REC DROP-CORD SCULPTURE-1 124-1 20 A 1 180 VA 0 VA -- -- Space 62
59 REC DROP-CORD SCULPTURE-1 124-1 20 A 1 180 VA 0 VA -- -- Space 60
57 REC DROP-CORD SCULPTURE-1 124-1 20 A 1 180 VA 0 VA -- -- Space 58
55 REC DROP-CORD SCULPTURE-1 124-1 20 A 1 180 VA 0 VA -- -- Space 56
53 REC DROP-CORD SCULPTURE-1 124-1 20 A 1 180 VA 0 VA -- -- Space 54
51 0 VA -- -- Space 52
49 REC SCULPTURE FACULTY STUDIO 124A 20 A 1 540 VA 0 VA -- -- Space 50
47 REC SCULPTURE FACULTY STUDIO 124A 20 A 1 720 VA 0 VA -- -- Space 48
45 0 VA -- -- Space 46
43 0 VA -- -- Space 44
41 REC SCULPTURE STUDIO-1 124-1 20 A 1 1080 VA 0 VA -- -- Space 42
39 REC SCULPTURE STUDIO-1 124-1 20 A 1 900 VA 0 VA -- -- Space 40
37 NC PROJECTION SCREEN , STUDIO-1... 20 A 1 300 VA 0 VA -- -- Space 38
35 REC CEILING PROJECTOR , STUDIO-1... 20 A 1 600 VA 0 VA -- -- Space 36
33 NC EYE WASH, STUDIO-1 124-1 20 A 1 180 VA 0 VA -- -- Space 34
31 0 VA -- -- Space 32
29 0 VA -- -- Space 30
27 0 VA 0 VA 1 20 A Spare 28
2512E WELDER 30 A 2
0 VA 0 VA 1 20 A Spare 26
23 5200 VA 0 VA 1 20 A Spare 24
21GEN WELDER REC 2 30 A 2
5200 VA 0 VA 1 20 A Spare 22
19 2418 VA 0 VA 1 20 A Spare 20
1713E WELDER REC 50 A 2
2418 VA 0 VA 1 20 A Spare 18
15 2740 VA 0 VA 1 20 A Spare 16
13REC SCULPTURE STUDIO-1 124-1 50 A 2
2740 VA 0 VA 1 20 A Spare 14
11 0 VA 0 VA 1 20 A Spare 12
9GEN WELDER REC 50 A 2
0 VA 0 VA 1 20 A Spare 10
7 5200 VA 0 VA 1 20 A Spare 8
53E REC SCULPTURE STUDIO-1 124-1 70 A 2
5200 VA 0 VA 1 20 A Spare 6
3 REC DRILL PRESS STUDIO-1 124-1 30 A 1 1920 VA 0 VA 1 20 A Spare 4
1 REC SPAY BOOTH, STUDIO-1 124-1 25 A 1 1656 VA 0 VA 1 20 A Spare 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: L1DB Phases: 3 Mains Type:Location: SCULPTURE-1 124-1 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 1LP3
Spare 20 A 1
Spare 20 A 1
Spare 20 A 1
Spare 20 A 1
Spare 20 A 1
Spare 20 A 1
Spare 20 A 1
Spare 20 A 1
Spare 20 A 1
Spare 20 A 1
Spare 20 A 1
Spare 20 A 1
Spare 20 A 1
Spare1 20 A
Spare1 20 A
Spare1 20 A
Spare1 20 A
Spare1 20 A
Spare1 20 A
Spare1 20 A
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
Space
84
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:19:02-07'00'
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
E-706
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL PANEL SCHEDULES
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
Checker
Author
KEY NOTE
1LP-5 1LP-6
1LP-81LP-7
SKIRT: TOP & BOTTOMNotes:
Total Est. Demand Current: 364 ATotal Conn. Current: 498 A
REC 106972 VA 54.67% 58486 VA Total Est. Demand: 130978 VAMTR 0 VA 0.00% 0 VA Total Conn. Load: 179464 VANC 72492 VA 100.00% 72492 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 440 A 527 A 551 ATotal Load: 52854 VA 61825 VA 64785 VA
83 Space -- -- 0 VA 0 VA -- -- Space 84
81 REC ROOM 142, 122F 20 A 1 720 VA 0 VA -- -- Space 82
79 REC ROOM 140-1, 130F 20 A 1 540 VA 0 VA -- -- Space 80
77 REC ROOM 140-1, 130F, M150 20 A 1 540 VA 0 VA -- -- Space 78
75 1463 VA 0 VA -- -- Space 76
73 1463 VA 0 VA -- -- Space 74
71
NC COMPRESSOR RM 142 30 A 3
1463 VA 0 VA -- -- Space 72
69 7176 VA 0 VA -- -- Space 70
67REC SKUTT KILN, KILN ROOM 122F 30 A 2
7176 VA 0 VA -- -- Space 68
65 REC DOLL KILN, KILN ROOM 122F 20 A 1 6000 VA 0 VA -- -- Space 66
63 REC DOLL KILN, KILN ROOM 122F 20 A 1 6000 VA 0 VA -- -- Space 64
61 REC DOLL KILN, KILN ROOM 122F 20 A 1 6000 VA 0 VA -- -- Space 62
59 REC DOLL KILN, KILN ROOM 122F 20 A 1 6000 VA 0 VA -- -- Space 60
57 409 VA 0 VA -- -- Space 58
55 409 VA 0 VA -- -- Space 56
53
NC KILN ROOM 122F 30 A 3
409 VA 0 VA -- -- Space 54
51 REC EXHAUST, KILN ROOM 122F 20 A 1 360 VA 0 VA 1 20 A Spare 52
49 7904 VA 0 VA 1 20 A Spare 50
47REC SKUTT KILN, KILN ROOM 122F 100 A 2
7904 VA 0 VA 1 20 A Spare 48
45 2777 VA 0 VA 1 20 A Spare 46
43REC SKUTT KILN, KILN ROOM 122F 100 A 2
2777 VA 0 VA 1 20 A Spare 44
41 4992 VA 0 VA 1 20 A Spare 42
39REC SKUTT KILN, KILN ROOM 122F 100 A 2
4992 VA 0 VA 1 20 A Spare 40
37 2777 VA 0 VA 1 20 A Spare 38
35RECSKUTT KILN, KILN ROOM 122F 100 A 2
2777 VA 0 VA 1 20 A Spare 36
33 4992 VA 0 VA 1 20 A Spare 34
31REC SKUTT KILN, KILN ROOM 122F 100 A 2
4992 VA 180 VA 1 20 A AD-1 COMPRESSOR RM 142 32
29 3120 VA 4800 VA 1 20 A REC CASTING 130F 30
27 REC MIG WELDER, EXTERIOR YARD-1140-1 30 A 2
3120 VA 2080 VA 28
25 3120 VA 2080 VA 26
23 REC MIG WELDER, EXTERIOR YARD-1140-1 30 A 2
3120 VA 2080 VA
3 20 A REC
24
21 7176 VA 720 VA 1 20 A REC KILN ROOM 122F 22
19 REC MIG WELDER, EXTERIOR YARD-1140-1 30 A 2
7176 VA 200 VA 20
17 16640 VA 200 VA 18
15REC WELDER, EXTERIOR YARD-1 140-1 30 A 2
16640 VA 200 VA
3 20 A NC EXTERIOR YARD-1 140-1
16
13 REC CASTING, CASTING AREA 130F 20 A 1 2400 VA 1680 VA 14
11 REC KILN, CASTING AREA 130F 20 A 1 2400 VA 1680 VA 12
9 REC WAX INJECTOR, CASTING AREA 130F 20 A 1 660 VA 1680 VA
3 20 A NC EXTERIOR YARD-1 140-1
10
7 REC CRUCIBLE. CASTING AREA 130F 20 A 1 1680 VA 0 VA 1 20 A Spare 8
5 REC PRESS, CASTING AREA 130F 20 A 1 660 VA 0 VA 1 20 A Spare 6
3 REC WAX INJECTOR CASTING AREA 130F 20 A 1 660 VA 0 VA 1 20 A Spare 4
1 REC CLEANER, CASTING AREA 130F 20 A 1 300 VA 0 VA 1 30 A MTR-EF-1 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: L1DB Phases: 3 Mains Type:Location: EXTERIOR YARD-1 140-1 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 1LP5
SKIRT: TOP & BOTTOMNotes:
Total Est. Demand Current: 68 ATotal Conn. Current: 104 A
REC 36020 VA 63.88% 23010 VA Total Est. Demand: 24563 VAMTR 1373 VA 100.00% 1373 VA Total Conn. Load: 37573 VANC 180 VA 100.00% 180 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 115 A 102 A 98 ATotal Load: 13675 VA 12167 VA 11731 VA
83 Space -- -- 0 VA 0 VA -- -- Space 84
81 Space -- -- 0 VA 0 VA -- -- Space 82
79 Space -- -- 0 VA 0 VA -- -- Space 80
77 Space -- -- 0 VA 0 VA -- -- Space 78
75 Space -- -- 0 VA 0 VA -- -- Space 76
73 Space -- -- 0 VA 0 VA -- -- Space 74
71 Space -- -- 0 VA 0 VA -- -- Space 72
69 Space -- -- 0 VA 0 VA -- -- Space 70
67 Space -- -- 0 VA 0 VA -- -- Space 68
65 Space -- -- 0 VA 0 VA -- -- Space 66
63 Space -- -- 0 VA 0 VA -- -- Space 64
61 Space -- -- 0 VA 0 VA -- -- Space 62
59 Space -- -- 0 VA 0 VA -- -- Space 60
57 Space -- -- 0 VA 0 VA -- -- Space 58
55 Space -- -- 0 VA 0 VA -- -- Space 56
53 Space -- -- 0 VA 0 VA -- -- Space 54
51 PLASMA TABLE 20 A 1 600 VA 0 VA -- -- Space 52
49 REC EXTERIOR YARD-1 140-1 20 A 1 540 VA 0 VA -- -- Space 50
47 REC EXTERIOR YARD-1 140-1 20 A 1 360 VA 0 VA -- -- Space 48
45 REC POWDER COATING 130H 20 A 1 540 VA 0 VA -- -- Space 46
43 REC MACHINERY 130J 20 A 1 1728 VA 0 VA -- -- Space 44
41 REC MACHINERY 130J 20 A 1 1728 VA 0 VA -- -- Space 42
39 REC BENCH GRINDER, EXTERIOR YARD... 20 A 1 600 VA 0 VA -- -- Space 40
37 1040 VA 0 VA 1 20 A Spare 38
35REC EXTERIOR YARD-1 140-1 40 A 2
1040 VA 0 VA 1 20 A Spare 36
33 REC BLAST CABINET, EXTERIOR YARD 35 A 1 2400 VA 0 VA 1 20 A Spare 34
31 REC PANEL SAW, EXTERIOR YARD-1... 20 A 1 1800 VA 0 VA 1 20 A Spare 32
29 668 VA 0 VA 1 20 A Spare 30
27 668 VA 0 VA 1 20 A Spare 28
25
REC EXTERIOR YARD-1 140-1 20 A 3
668 VA 0 VA 1 20 A Spare 26
23 458 VA 0 VA 1 20 A Spare 24
21 458 VA 0 VA 1 20 A Spare 22
19
MTR EXTERIOR YARD-1 140-1 30 A 3
458 VA 180 VA 1 20 A REC EXTERIOR YARD-1 140-1 20
17 REC POWDER COATING 130H 35 A 1 2400 VA 360 VA 1 20 A REC EXTERIOR YARD-1 140-1 18
15 REC BENCH GRINDER, MACHINERY 130J 20 A 1 864 VA 180 VA 1 20 A REC EXTERIOR YARD-1 140-1 16
13 REC MACHINERY 130J 20 A 1 720 VA 2773 VA 14
11 REC POLISHER & DUST COLLECTION... 20 A 1 864 VA 2773 VA 12
9 REC MACHINERY 130J 20 A 1 360 VA 2773 VA
3 50 A11E PLASMA TABLE REC EXTERIORYARD-1 140-1
10
7 REC MACHINERY 106E 20 A 1 864 VA 360 VA 1 20 A REC EXTERIOR YARD-1 140-1 8
5 REC EXTERIOR YARD-1 140-1 20 A 1 180 VA 900 VA 1 20 A REC EXTERIOR YARD-1 140-1 6
3 2184 VA 540 VA 1 20 A REC ROOM 140-1, M150 4
1REC EXTERIOR YARD-1 140-1 30 A 2
2184 VA 360 VA 1 20 A REC ROOM 140-1, 130H 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: L1DB Phases: 3 Mains Type:Location: EXTERIOR YARD-1 140-1 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 1LP6
Notes:
Total Est. Demand Current: 31 ATotal Conn. Current: 30 A
LTG 1110 VA 125.00% 1388 VA Total Est. Demand: 11047 VAREC 9600 VA 100.00% 9600 VA Total Conn. Load: 10780 VANC 120 VA 100.00% 120 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 37 A 39 A 19 ATotal Load: 4107 VA 4392 VA 2281 VA
41 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 42
39 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 40
37 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 38
35 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 36
33 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 34
31 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 32
29 LTG ART GALLERY 105 20 A 1 15 VA 0 VA 1 20 A Spare 30
27 LTG ART GALLERY 105 20 A 1 105 VA 0 VA 1 20 A Spare 28
25 LTG ART GALLERY 105 20 A 1 105 VA 0 VA 1 20 A Spare 26
23 LTG ART GALLERY 105 20 A 1 90 VA 0 VA 1 20 A Spare 24
21 LTG ART GALLERY 105 20 A 1 120 VA 0 VA 1 20 A Spare 22
19 LTG ART GALLERY 105 20 A 1 105 VA 0 VA 1 20 A Spare 20
17 LTG ART GALLERY 105 20 A 1 105 VA 0 VA 1 20 A Spare 18
15 REC ART GALLERY-1 105-1 20 A 1 1440 VA 75 VA 1 20 A LTG RETABLOS GALLERY 110 16
13 REC ART GALLERY-1 105-1 20 A 1 1800 VA 30 VA 1 20 A LTG RETABLOS GALLERY 110 14
11 REC ART GALLERY-1 105-1 20 A 1 900 VA 60 VA 1 20 A LTG MODERN & CONTEMPORARY ART... 12
9 REC ART GALLERY-1 105-1 20 A 1 1080 VA 60 VA 1 20 A LTG MODERN & CONTEMPORARY ART... 10
7 REC ART GALLERY-1 105-1 20 A 1 960 VA 60 VA 1 20 A LTG MODERN & CONTEMPORARY ART... 8
5 REC ART GALLERY-1 105-1 20 A 1 1080 VA 15 VA 1 20 A LTG ART GALLERY 105 6
3 REC MODERN ART GALLERY 105A 20 A 1 900 VA 600 VA 1 20 A REC CEILING PROJECTOR, GALLERY... 4
1 REC MODERN ART GALLERY 105A 20 A 1 960 VA 75 VA 1 20 A LTG 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Recessed Wires: 4 Mains Rating: 225 A
Supply From: L1DB Phases: 3 Mains Type:Location: ART GALLERY 105 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 1LP7
Notes:
Total Est. Demand Current: 25 ATotal Conn. Current: 25 A
LTG 0 VA 0.00% 0 VA Total Est. Demand: 9180 VAREC 8700 VA 100.00% 8700 VA Total Conn. Load: 9180 VANC 480 VA 100.00% 480 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 24 A 28 A 25 ATotal Load: 2880 VA 3360 VA 2940 VA
41 Space -- -- 0 VA 0 VA -- -- Space 42
39 Space -- -- 0 VA 0 VA -- -- Space 40
37 Space -- -- 0 VA 0 VA -- -- Space 38
35 Spare 20 A 1 0 VA 0 VA -- -- Space 36
33 Spare 20 A 1 0 VA 0 VA -- -- Space 34
31 Spare 20 A 1 0 VA 0 VA -- -- Space 32
29 Spare 20 A 1 0 VA 0 VA -- -- Space 30
27 Spare 20 A 1 0 VA 0 VA -- -- Space 28
25 Spare 20 A 1 0 VA 0 VA -- -- Space 26
23 Spare 20 A 1 0 VA 0 VA -- -- Space 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20
17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18
15 PROJECTINO SCREEN RM 115 20 A 1 300 VA 0 VA 1 20 A CEF-2 16
13 REC ROOM 115 20 A 1 540 VA 0 VA 1 20 A CEF-1 14
11 REC PREP + FRAMING ROOM 113 20 A 1 360 VA 600 VA 1 20 A REC CEILING PROJECTOR, LAB 115 12
9 REC PREP + FRAMING ROOM 113 20 A 1 900 VA 180 VA 1 20 A NC FUME HOOD, CONSERVATION LAB 115 10
7 REC GALLERY PREP ROOM (DIRTY) 107 20 A 1 360 VA 900 VA 1 20 A REC ROOM 115 8
5 REC PREP + FRAMING ROOM 113 20 A 1 1080 VA 900 VA 1 20 A REC CONSERVATION LAB 115 6
3 REC GALLERY PREP ROOM (DIRTY) 107 20 A 1 900 VA 1080 VA 1 20 A REC CONSERVATION LAB 115 4
1 REC GALLERY PREP ROOM (DIRTY) 107 20 A 1 720 VA 360 VA 1 20 A REC PREP + FRAMING ROOM 113 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Recessed Wires: 4 Mains Rating: 225 A
Supply From: L1DB Phases: 3 Mains Type:Location: FRAME PREP ROOM 113 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 1LP8
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:19:37-07'00'
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
E-707
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL PANEL SCHEDULES
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
Checker
Author
KEY NOTE
2LP1 2LP2
2LP42LP3
SKIRT: TOP & BOTTOMNotes:
Total Est. Demand Current: 25 ATotal Conn. Current: 25 A
Total Est. Demand: 8840 VAREC 8340 VA 100.00% 8340 VA Total Conn. Load: 8840 VANC 500 VA 100.00% 500 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 28 A 23 A 23 ATotal Load: 3360 VA 2760 VA 2720 VA
41 Space -- -- 0 VA 0 VA -- -- Space 42
39 Space -- -- 0 VA 0 VA -- -- Space 40
37 Space -- -- 0 VA 0 VA -- -- Space 38
35 Space -- -- 0 VA 0 VA -- -- Space 36
33 Space -- -- 0 VA 0 VA -- -- Space 34
31 Spare 20 A 1 0 VA 0 VA -- -- Space 32
29 Spare 20 A 1 0 VA 0 VA -- -- Space 30
27 Spare 20 A 1 0 VA 0 VA -- -- Space 28
25 Spare 20 A 1 0 VA 0 VA -- -- Space 26
23 REC Room 224B-1, 224A-1, 224C-1 20 A 1 540 VA 0 VA 1 20 A Spare 24
21 REC Room 224B-1, 224A-1, 224C-1 20 A 1 540 VA 0 VA 1 20 A Spare 22
19 REC WASH OUT-1 224A-1 20 A 1 1350 VA 0 VA 1 20 A Spare 20
17 REC CEILING PROJECTOR, DESIGN... 20 A 1 1100 VA 0 VA 1 20 A Spare 18
15 REC DESIGN STUDIO-1 224-1 20 A 1 1080 VA 0 VA 1 20 A Spare 16
13 REC DESIGN STUDIO-1 224-1 20 A 1 1080 VA 0 VA 1 20 A Spare 14
11 REC DESIGN STUDIO-1 224-1 20 A 1 900 VA 0 VA 1 20 A Spare 12
9 REC DESIGN STUDIO-1 224-1 20 A 1 900 VA 0 VA 1 20 A Spare 10
7 REC LARGE PRINTER, WORKSHOP-1... 20 A 1 750 VA 0 VA 1 20 A Spare 8
5 REC VALAD HOT PLATE, WORKSHOP-1... 20 A 1 180 VA 0 VA 1 20 A Spare 6
3 REC EXPOSURE TABLE, WORKSHOP-1... 20 A 1 240 VA 0 VA 1 20 A Spare 4
1 REC LIGHT TABLE, WORKSHOP-1 224-1 20 A 1 180 VA 0 VA 1 20 A Spare 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: L2DB Phases: 3 Mains Type:Location: DESIGN STUDIO-1 224-1 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 2LP2
SKIRT: TOP & BOTTOMNotes:
Total Est. Demand Current: 18 ATotal Conn. Current: 18 A
Total Est. Demand: 6307 VAREC 5307 VA 100.00% 5307 VA Total Conn. Load: 6307 VANC 1000 VA 100.00% 1000 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 16 A 27 A 11 ATotal Load: 1874 VA 3154 VA 1280 VA
41 Space -- -- 0 VA 0 VA -- -- Space 42
39 Space -- -- 0 VA 0 VA -- -- Space 40
37 Space -- -- 0 VA 0 VA -- -- Space 38
35 Space -- -- 0 VA 0 VA -- -- Space 36
33 REC DROP-CORD, DRAWING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 34
31 REC DROP-CORD, DRAWING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 32
29 REC DROP-CORD, DRAWING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 30
27 REC DROP-CORD, DRAWING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 28
25 Spare 20 A 1 0 VA 0 VA -- -- Space 26
23 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 24
21 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 22
19 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 20
17 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 18
15 REC CEILING PROJECTOR, PAINTING-1... 20 A 1 1100 VA 0 VA 1 20 A Spare 16
13 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 14
11 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 12
9 REC DRAWING/PAINTING-1 232-1 20 A 1 1080 VA 0 VA 1 20 A Spare 10
7 REC DRAWING/PAINTING-1 232-1 20 A 1 1080 VA 0 VA 1 20 A Spare 8
5 REC CEILING PROJECTOR, PAINTING-1... 20 A 1 1100 VA 0 VA 1 20 A Spare 6
3 614 VA 0 VA 1 20 A Spare 4
1 REC GAS KILN, DRAWING/PAINTING-1232-1 30 A 2
614 VA 0 VA 1 20 A Spare 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: L2DB Phases: 3 Mains Type:Location: DRAWING STUDIO-1 232-1 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 2LP4
SKIRT: TOP & BOTTOMNotes:
Total Est. Demand Current: 46 ATotal Conn. Current: 62 A
Total Est. Demand: 16513 VAREC 21666 VA 73.08% 15833 VA Total Conn. Load: 22346 VANC 680 VA 100.00% 680 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 77 A 55 A 54 ATotal Load: 9180 VA 6636 VA 6530 VA
83 Space -- -- 0 VA 0 VA -- -- Space 84
81 Space -- -- 0 VA 0 VA -- -- Space 82
79 Space -- -- 0 VA 0 VA -- -- Space 80
77 Space -- -- 0 VA 0 VA -- -- Space 78
75 Space -- -- 0 VA 0 VA -- -- Space 76
73 Space -- -- 0 VA 0 VA -- -- Space 74
71 Spare 20 A 1 0 VA 0 VA -- -- Space 72
69 Spare 20 A 1 0 VA 0 VA -- -- Space 70
67 Spare 20 A 1 0 VA 0 VA -- -- Space 68
65 Spare 20 A 1 0 VA 0 VA -- -- Space 66
63 Spare 20 A 1 0 VA 0 VA -- -- Space 64
61 Spare 20 A 1 0 VA 0 VA -- -- Space 62
59 Spare 20 A 1 0 VA 0 VA -- -- Space 60
57 Spare 20 A 1 0 VA 0 VA -- -- Space 58
55 Spare 20 A 1 0 VA 0 VA -- -- Space 56
53 Spare 20 A 1 0 VA 0 VA -- -- Space 54
51 Spare 20 A 1 0 VA 0 VA -- -- Space 52
49 Spare 20 A 1 0 VA 0 VA -- -- Space 50
47 Spare 20 A 1 0 VA 0 VA -- -- Space 48
45 Spare 20 A 1 0 VA 0 VA -- -- Space 46
43 Spare 20 A 1 0 VA 0 VA -- -- Space 44
41 REC Room 222C-1, 222D-1 20 A 1 360 VA 0 VA -- -- Space 42
39 REC Room 222C-1, 222D-1 20 A 1 360 VA 0 VA -- -- Space 40
37 REC GANG DARK RM. 222B 20 A 1 540 VA 0 VA -- -- Space 38
35 REC Room 210-1, 222A 20 A 1 540 VA 0 VA -- -- Space 36
33 REC REFRIGERATOR, STORAGE 222A 20 A 1 600 VA 0 VA 1 20 A Spare 34
31 REC VENDING MACHINE , HALL H101E 20 A 1 1200 VA 0 VA 1 20 A Spare 32
29 REC DROP-CORD FILM PROCESSING... 20 A 1 180 VA 0 VA 1 20 A Spare 30
27 REC DROP-CORD FILM PROCESSING... 20 A 1 180 VA 0 VA 1 20 A Spare 28
25 NC EYE WASH, FILM PROCESSING RM-1... 20 A 1 180 VA 360 VA 1 20 A REC FACULTY STUDIO (SAFETY)-1 242-1 26
23 REC FILM PROCESSING RM-1 222E-1 20 A 1 360 VA 600 VA 1 20 A REC GANG DARK RM 222B 24
21 REC FILM PROCESSING RM-1 222E-1 20 A 1 360 VA 600 VA 1 20 A REC GANG DARK RM 222B 22
19 REC PHOTO STUDIO-1 222-1 20 A 1 900 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 20
17 REC PHOTO STUDIO-1 222-1 20 A 1 1080 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 18
15 REC EXPOSURE TABLE, PHOTO STUDIO... 20 A 1 1800 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 16
13 REC LIGHT TABLE, PHOTO STUDIO-1... 20 A 1 1680 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 14
11 REC CEILING PROJECTOR, PHOTO... 20 A 1 1100 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 12
9 REC PRESS, PROCESSING RM-1 222E-1 20 A 1 996 VA 600 VA 1 20 A REC BESELER ENLARGER, GANG DARK... 10
7 REC REFRIGERATOR, PROCESSING RM-... 20 A 1 600 VA 360 VA 1 20 A REC FACULTY STUDIO (SAFETY)-1 242-1 8
5 REC DRUM DRYER, PROCESSING RM-1... 20 A 1 750 VA 360 VA 1 20 A REC FACULTY STUDIO (SAFETY)-1 242-1 6
3 REC FILM PROCESSING RM-1 222E-1 20 A 1 180 VA 360 VA 1 20 A REC GRAD STUDIO HUDDLE-1 240-1 4
1 REC COPY STAND, PROCESSING RM-1... 20 A 1 1800 VA 360 VA 1 20 A REC GRAD STUDIO HUDDLE-1 240-1 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 84Mounting: RECESSED Wires: 4 Mains Rating: 225 A
Supply From: L2DB Phases: 3 Mains Type:Location: PHOTO STUDIO-1 222-1 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 2LP3
SKIRT: TOP & BOTTOMNotes:
Total Est. Demand Current: 12 ATotal Conn. Current: 12 A
Total Est. Demand: 4340 VATotal Conn. Load: 4340 VA
REC 4340 VA 100.00% 4340 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 16 A 14 A 8 ATotal Load: 1760 VA 1620 VA 960 VA
41 Spare 20 A 1 0 VA 0 VA -- -- Space 42
39 Spare 20 A 1 0 VA 0 VA -- -- Space 40
37 Spare 20 A 1 0 VA 0 VA -- -- Space 38
35 Spare 20 A 1 0 VA 0 VA -- -- Space 36
33 Spare 20 A 1 0 VA 0 VA -- -- Space 34
31 Spare 20 A 1 0 VA 0 VA -- -- Space 32
29 Spare 20 A 1 0 VA 0 VA -- -- Space 30
27 Spare 20 A 1 0 VA 0 VA -- -- Space 28
25 Spare 20 A 1 0 VA 0 VA -- -- Space 26
23 Spare 20 A 1 0 VA 0 VA -- -- Space 24
21 Spare 20 A 1 0 VA 0 VA -- -- Space 22
19 REC FLAT SCREEN, METALS/JEWELRY-1... 20 A 1 500 VA 0 VA -- -- Space 20
17 REC DROP-CORD, PAINTING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 18
15 REC DROP-CORD, PAINTING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 16
13 REC DROP-CORD, PAINTING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 14
11 REC DROP-CORD, PAINTING STUDIO-1... 20 A 1 180 VA 0 VA -- -- Space 12
9 REC ROOM 230B-1, 230-1 20 A 1 540 VA 0 VA 1 20 A Spare 10
7 REC WASHER, PAINTING-1 230-1 20 A 1 180 VA 0 VA 1 20 A Spare 8
5 REC REFRIGERATOR, PAINTING-1 230-1 20 A 1 600 VA 0 VA 1 20 A Spare 6
3 REC PAINTING-1 230-1 20 A 1 900 VA 0 VA 1 20 A Spare 4
1 REC PAINTING-1 230-1 20 A 1 900 VA 0 VA 1 20 A Spare 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: L2DB Phases: 3 Mains Type:Location: PAINTING STUDIO-1 230-1 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: 2LP1
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:20:03-07'00'
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
E-708
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ELECTRICAL PANEL SCHEDULES
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
Checker
Author
Notes:
LTG 1093 VA 125.00% 1366 VA Total Est. Demand Current: 547 AREC 3600 VA 100.00% 3600 VA Total Conn. Current: 547 AMTR 322759 VA 100.00% 322759 VA Total Est. Demand: 455031 VANC 116130 VA 100.00% 116130 VA Total Conn. Load: 454760 VAOther 11185 VA 100.00% 11185 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 553 A 542 A 548 ATotal Load: 152924 VA 150213 VA 151623 VA
125 Space -- -- 0 VA 0 VA -- -- Space 126
123 Space -- -- 0 VA 0 VA -- -- Space 124
121 Space -- -- 0 VA 0 VA -- -- Space 122
119 Space -- -- 0 VA 0 VA -- -- Space 120
117 Space -- -- 0 VA 0 VA -- -- Space 118
115 Space -- -- 0 VA 0 VA -- -- Space 116
113 Space -- -- 0 VA 0 VA -- -- Space 114
111 Spare 20 A 1 0 VA 0 VA -- -- Space 112
109 Spare 20 A 1 0 VA 0 VA -- -- Space 110
107 Spare 20 A 1 0 VA 0 VA 108
105 Spare 20 A 1 0 VA 0 VA 106
103 Spare 20 A 1 0 VA 0 VA
3 80 A Spare
104
101 Spare 20 A 1 0 VA 0 VA 102
99 Spare 20 A 1 0 VA 0 VA 100
97 Spare 20 A 1 0 VA 0 VA
3 50 A Spare
98
95 Spare 20 A 1 0 VA 0 VA 96
93 7479... 0 VA 94
91 7479... 0 VA
3 30 A Spare
92
89
VFD-16 - AHU-2 SF(2) 50 A 3
7479... 0 VA 90
87 7479... 0 VA 88
85 7479... 0 VA
3 20 A Spare
86
83
VFD-15 - AHU-2 SF(2) 50 A 3
7479... 5817... 84
81 2105... 5817... 82
79 2105... 5817...
3 20 A VFD-14 - DOAS-1
80
77
VFD-17 - AHU-2 RF 40 A 3
2105... 1108... 78
75 7479... 1108... 76
73 7479... 1108...
3 80 A VFD-8 - LED-1(1)
74
71
VFD-16 - AHU-2 SF 50 A 3
7479... 1108... 72
69 7479... 1108... 70
67 7479... 1108...
3 80 A VFD-7 - LED-1(2)
68
65
VFD-15 - AHU-2 SF 50 A 3
7479... 3878... 66
63 FCU-2/3 20 A 1 1994... 3878... 64
61 LTG PENTHOUSE 20 A 1 410 VA 3878...
3 30 A VFD-8 - MAU-1(4)
62
59 9418... 3728... 60
57 9418... 3728... 58
55
LEF1 FAN 2 75 A 3
9418... 3728...
3 30 A Other
56
53 9418... 3878... 54
51 9418... 3878... 52
49
LEF1 FAN 1 75 A 3
9418... 3878...
3 30 A VFD-8 - MAU-1(3)
50
47 831 VA 3878... 48
45 831 VA 3878... 46
43
EF-3 15 A 3
831 VA 3878...
3 30 A VFD-9 - MAU-1(2)
44
41 582 VA 3878... 42
39 582 VA 3878... 40
37
EF-4 15 A 3
582 VA 3878...
3 30 A VFD-9 - MAU-1(1)
38
35 1329... 2105... 36
33 1329... 2105... 34
31
EF-5 15 A 3
1329... 2105...
3 20 A VFD-13 - AHU-1 RF
32
29 2105... 5817... 30
27 2105... 5817... 28
25
EF-6 20 A 3
2105... 5817...
3 40 A VFD-10 - MAU-1 SF
26
23 2105... 5817... 24
21 2105... 5817... 22
19
EF-7 20 A 3
2105... 5817...
3 40 A VFD-11 - MAU-1 SF
20
17 3878... 2105... 18
15 3878... 2105... 16
13
RTU-2 20 A 3
3878... 2105...
3 20 A VFD-12 - AHU-1 RF
14
11 3878... 2105... 12
9 3878... 2105... 10
7
RTU-1 30 A 3
3878... 2105...
3 20 A VFD-18 - AHU-2 RF
8
5 1248... 8409... 6
3 1248... 5005... 4
1
C-1 60 A 3
1248... 9321...
3 20 A TP
2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 126 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 600 A
Supply From: MSB Phases: 3 Mains Type:Location: MECH. PENTHOUSE M300 Volts: 480/277 Wye A.I.C. Rating: 25000
Branch Panel: MP
KEY NOTE
MP
Notes:
Total Est. Demand Current: 23 ATotal Conn. Current: 23 A
Total Est. Demand: 19200 VATotal Conn. Load: 19200 VA
MTR 19200 VA 100.00% 19200 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 26 A 45 A 4 ATotal Load: 6480 VA 11520 VA 1200 VA
29 Space -- -- 0 VA 0 VA -- -- Space 30
27 Spare 20 A 1 0 VA 0 VA -- -- Space 28
25 Spare 20 A 1 0 VA 0 VA -- -- Space 26
23 Spare 20 A 1 0 VA 0 VA -- -- Space 24
21 Spare 20 A 1 0 VA 0 VA -- -- Space 22
19 Spare 20 A 1 0 VA 0 VA -- -- Space 20
17 Spare 20 A 1 0 VA 0 VA -- -- Space 18
15 Spare 20 A 1 0 VA 0 VA -- -- Space 16
13 Spare 20 A 1 0 VA 0 VA -- -- Space 14
11 Spare 20 A 1 0 VA 0 VA -- -- Space 12
9 Spare 20 A 1 0 VA 0 VA -- -- Space 10
7 Spare 20 A 1 0 VA 0 VA -- -- Space 8
5 MTR TU2-201-TU2-208 20 A 1 1200... 0 VA -- -- Space 6
3 MTR ECV 20 A 1 1152... 0 VA -- -- Space 4
1 MTR ECV 20 A 1 6480... 0 VA -- -- Space 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: MSB Phases: 3 Mains Type:Location: ELEC. RM-1 M225B-1 Volts: 480/277 Wye A.I.C. Rating: 22000
Branch Panel: M2A
KEY NOTE
M2A
Notes:
Total Est. Demand Current: 19 ATotal Conn. Current: 19 A
Total Est. Demand: 7020 VATotal Conn. Load: 7020 VA
REC 7020 VA 100.00% 7020 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 29 A 12 A 19 ATotal Load: 3330 VA 1485 VA 2205 VA
29 Space -- -- 0 VA 0 VA -- -- Space 30
27 Space -- -- 0 VA 0 VA -- -- Space 28
25 Space -- -- 0 VA 0 VA -- -- Space 26
23 Space -- -- 0 VA 0 VA -- -- Space 24
21 Space -- -- 0 VA 0 VA -- -- Space 22
19 Space -- -- 0 VA 0 VA -- -- Space 20
17 Space -- -- 0 VA 0 VA -- -- Space 18
15 Space -- -- 0 VA 0 VA 1 20 A Spare 16
13 Space -- -- 0 VA 0 VA 1 20 A Spare 14
11 REC ROOM T125A, M125B, M127 20 A 1 1080... 0 VA 1 20 A Spare 12
9 REC MDF T125A 20 A 1 360 VA 0 VA 1 20 A Spare 10
7 1125... 0 VA 1 20 A Spare 8
5REC MDF T125A 30 A 2
1125... 0 VA 1 20 A Spare 6
3 1125... 0 VA 1 20 A Spare 4
1REC MDF T125A 30 A 2
1125... 1080... 1 20 A REC ROOM T125A, M125B, R123C 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 30 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: T-LT Phases: 3 Mains Type:Location: MDF T125A Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: LT
Notes:
Total Est. Demand Current: 17 ATotal Conn. Current: 17 A
Total Est. Demand: 6300 VATotal Conn. Load: 6300 VA
REC 6300 VA 100.00% 6300 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 16 A 25 A 12 ATotal Load: 1845 VA 2970 VA 1485 VA
29 Space -- -- 0 VA 0 VA -- -- Space 30
27 Space -- -- 0 VA 0 VA -- -- Space 28
25 Space -- -- 0 VA 0 VA -- -- Space 26
23 Space -- -- 0 VA 0 VA -- -- Space 24
21 Space -- -- 0 VA 0 VA -- -- Space 22
19 Space -- -- 0 VA 0 VA -- -- Space 20
17 Space -- -- 0 VA 0 VA -- -- Space 18
15 Space -- -- 0 VA 0 VA 1 20 A Spare 16
13 Space -- -- 0 VA 0 VA 1 20 A Spare 14
11 REC TR-1 T225A-1 20 A 1 360 VA 0 VA 1 20 A Spare 12
9 REC TR-1 T225A-1 30 A 1 2250... 0 VA 1 20 A Spare 10
7 1125... 0 VA 1 20 A Spare 8
5REC TR-1 T225A-1 30 A 2
1125... 0 VA 1 20 A Spare 6
3 REC TR-1 T225A-1 20 A 1 720 VA 0 VA 1 20 A Spare 4
1 REC TR-1 T225A-1 20 A 1 720 VA 0 VA 1 20 A Spare 2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: Phases: 3 Mains Type:Location: TR-1 T225A-1 Volts: 120/208 Wye A.I.C. Rating: 10000
Branch Panel: LT2
M1 LT
Notes:
Total Est. Demand Current: 125 ATotal Conn. Current: 125 A
Total Est. Demand: 103916 VAMTR 49780 VA 100.00% 49780 VA Total Conn. Load: 103916 VANC 54136 VA 100.00% 54136 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:Total Amps: 157 A 121 A 102 ATotal Load: 42787 VA 32923 VA 28207 VA
41 Space -- -- 0 VA 0 VA -- -- Space 42
39 Space -- -- 0 VA 0 VA -- -- Space 40
37 Space -- -- 0 VA 0 VA -- -- Space 38
35 Space -- -- 0 VA 0 VA -- -- Space 36
33 Spare 20 A 1 0 VA 0 VA -- -- Space 34
31 Spare 20 A 1 0 VA 0 VA -- -- Space 32
29 Spare 20 A 1 0 VA 0 VA -- -- Space 30
27 5533 VA 696 VA 1 20 A MTR MECHANICAL ROOM M125C 28
25 5533 VA 2533 VA 26
23
AC-1-COMPRESSOR RM 142 40 A 3
5533 VA 2533 VA 24
21 3878 VA 2533 VA
3 20 A NC EXTERIOR YARD-1 140-1
22
19 3878 VA 3878 VA 20
17
NC MECHANICAL ROOM M125C 20 A 3
3878 VA 3878 VA 18
15 3878 VA 3878 VA
3 30 A MTR EXTERIOR YARD-1 140-1
16
13 3878 VA 6480 VA 1 20 A MTR CERAMICS FACULTY STUDIO 122A 14
11
NC MECHANICAL ROOM M125C 20 A 3
3878 VA 3878 VA 12
9 MTR ECV 20 A 1 4320 VA 3878 VA 10
7 MTR ECV 20 A 1 7200 VA 3878 VA
3 20 A NC MECHANICAL ROOM M125C
8
5 MTR TU2-103 - 105, STUDIO WING 20 A 1 750 VA 3878 VA 6
3 MTR TU1-10 - TU1-12, BID LOT 1 20 A 1 450 VA 3878 VA 4
1 MTR TU1-1 - TU1-9, GALLERY WING 20 A 1 1650 VA 3878 VA
3 20 A NC MECHANICAL ROOM M125C
2
CKT Circuit Description Notes Trip Poles A B C Poles Trip Notes Circuit Description CKT
Notes:
Enclosure: Type 1 Spaces: 42 MCB Rating:Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: MSB Phases: 3 Mains Type:Location: ELEC M125B Volts: 480/277 Wye A.I.C. Rating: 22000
Branch Panel: M1
LT2
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:20:15-07'00'
ENJAM N E. BOSSE
19418
GIN
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
E-801
NEW ARTBUILDINGNMSU LAS CRUCES, NM
LABORATORY EQUIPMENT ELECTRICALSCHEDULE
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB
OU
LABORATORY EQUIPMENT - ELECTRICAL SCHEDULEEQUIPMENT
NO. EQUIPMENT DESCRIPTION VOLTAGE PHASEEQUIPMENT LOAD BRANCH CIRCUIT
CONDUCTORCONDUIT
SIZEEQUIPMENT
TERMINATIONKEYEDNOTESCHARATERISTICS
1E 208 1 3#6 & 1#10 GND 1" RECEPTACLE2E 208 1 3#6 & 1#10 GND 1" RECEPTACLE3E MILLERMATIC 250 MIG PORTABLE WELDER 208 1 50A 3#4 & 1#8 GND 1" RECEPTACLE3N MILLERMATIC WELDER 208 1 31A 3#6 & 1#10 GND 1" RECEPTACLE4E MILLER ECONOTIG TIG WELDER 208 1 52A 3#4 & 1#8 GND 1-1/4" RECEPTACLE5E MILLER PLASMA CUTTER 208 1 60A 3#4 & 1#8 GND 1-1/4" RECEPTACLE5N MILLERMATIC WELDER 208 1 31A 3#6 & 1#10 GND 1" RECEPTACLE6E POWERMATIC DRILL PRESS 120 1 15.7A 2#12 & 1#12 GND 3/4" RECEPTACLE7E BALDOR GRINDER 120 1 3.8 2#12 & 1#12 GND 3/4" RECEPTACLE8E PIPE BENDER 208 3 6.2A 3#10 & 1#10 GND 3/4" NFSS
10E METAL PLANISHER NA NO ELEC11E PLASMA-CAM CUTTING TABLE 208 1 40A 3#6 & 1#10 GND 1" RECEPTACLE12E MILLER MIG WELDER 208 1 30A 3#6 & 1#10 GND 1" RECEPTACLE13E MILLER MIG WELDER 208 1 30A 3#6 & 1#10 GND 1" RECEPTACLE14E MILLER MIG WELDER 208 1 69A 3#6 & 1#10 GND 1" RECEPTACLE15E 1/2 TON CRANE 208 3 2A 4#12 & 1#12 GND 3/4" NFSS17E MCENGEL HI SPEED MELT FURNACE 208 3 XX 4#12 & 1#12 GND 3/4" RECEPTACLE18E BEAD BLAST CABINET 120 1HP 2#12 & 1#12 GND 3/4" RECEPTACLE19E COFFING HOIST DOWN PILLER JIB CRANE NA20E SAW STOP 10" TABLE 208 1 19.7A 3#10 & 1#10 GND 3/4" RECEPTACLE21E DEWALT 12" COMPOUND 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE22E DELTA DRILL PRESS 120 1 12A 2#12 & 1#12 GND 3/4" RECEPTACLE23E MILWAUKEE PANEL SAW 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE23N REAR DRAFT MEASURING TABLE NA NO ELEC24E POWERMATIC DISC SANDER 120 1 14A 2#12 & 1#12 GND 3/4" RECEPTACLE25E POWERMATIC DISC SANDER 208 3 9.8A 4#12 & 1#12 GND 3/4" RECEPTACLE26E ROCKWELL BANDSAW 208 1 11.5 3#12 & 1#12 GND 3/4" RECEPTACLE26N FUME HOOD 120 1 2.5A 2#12 & 1#12 GND 3/4" HARD WIRE27E DELTA BANDSAW 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE27N FUME HOOD 120 2.5 2#12 & 1#12 GND 3/4" HARD WIRE30E BRENT CXC POTTERS WHEELS 120 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE30N WALK-IN SPRAY BOOTH NA 3/4" RECEPTACLE31E THOMAS STUART POTTERS WHEELS 120 1 10.4A 2#12 & 1#12 GND 3/4" RECEPTACLE31N STAINLESS STEEL QUAD RECEP OVER
CENTRAL BENCHES120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE
32E LAMAN SLIP MIXER 120 1 7.3A 2#12 & 1#12 GND 3/4" RECEPTACLE33E AIR COMPRESSOR 120 1 1HP 2#12 & 1#12 GND 3/4" RECEPTACLE33N SNORKLE OVER RESIN PREP NA NO ELEC34E REAR DRAFT MEASURING TABLE 120 1 XX 2#12 & 1#12 GND 3/4" RECEPTACLE35E LAGUNA WET GLAZE SPRAY BOOTH NA NO ELEC35N PROJECTION SCREEN 120 1 3A 2#12 & 1#12 GND 3/4" RECEPTACLE36E BAILEY HEPA AIR FILTER 120 1 3/4 HP 3/4" RECEPTACLE37E SOLDNER CLAY MIXER 208 3 9.1A 3#12 & 1#12 GND 3/4" RECEPTACLE38E UPDRAFT EXHAUST 120 1 12A 2#12 & 1#12 GND 3/4" RECEPTACLE39E PETTER PUGGER PUGMILL 208 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE40E PETER PUGGER PUGMILL 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE41E BAILEY HEPA AIR FILTER 120 1 3/4 HP 2#12 & 1#12 GND 3/4" SWITCH42E SMALL SOLDNER CLAY MIXER 208 3 6A 3#10 & 1#10 GND 3/4" RECEPTACLE43E BLUEBIRD CLAY MIXER 208 3 4.5A 3#12 & 1#12 GND 3/4" RECEPTACLE45E SKUTT ELECTRIC KILN 208 3 76A 3#1 & 1#6 GND 1-1/2" NFSS46E SKUTT 1227PK ELECTRIC KILN 208 1 69A 2#4 & 1#8 GND 1" NFSS47E SKUTT ELECTRIC KILN 208 3 48A 3#6 & 1#10 GND 1" RECEPTACLE48E SKUTT ELECTRIC KILN 208 3 26.7A 3#10 & 1#10 GND 3/4" RECEPTACLE49E SKUTT ELECTRIC KILN 208 3 26.7A 3#10 & 1#10 GND 3/4" RECEPTACLE50E SKUTT ELECTRIC KILN 208 3 48A 3#6 & 1#10 GND 1" RECEPTACLE50N BAILEY HEPA FILTER 120 1 3/4 HP 2#12 & 1#12 GND 3/4" SWITCH51E SKUTT DOLL KILN 120 1 50A 2#4 & 1#8 GND 1" RECEPTACLE52E SKUTT DOLL KILN 120 1 50A 2#4 & 1#8 GND 1" RECEPTACLE52N 20 GALLON PARTS WASHER 120 1 F 2#12 & 1#12 GND 3/4" RECEPTACLE53E SKUTT DOLL KILN 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE54E LAGUNA DOLL KILN 120 1 50A 2#6 & 1#8 GND 1" RECEPTACLE54N PIANO BOX STORAGE NA NO ELEC55E ENVIRO-VENT EXHAUST 120 1 F 2#12 & 1#12 GND 3/4" RECEPTACLE56E PROGRAMMABLE GAS KILN 208 1 5.9A 3#10 & 1#10 GND 3/4" RECEPTACLE56N SPRAY BOOTH NA NO ELEC64E OLSEN UPDRAFT GAS KILN NA65E OLSEN UPDRAFT GAS KILN NA66E OLSEN UPDRAFT GAS KILN NA66N OLSEN UPDRAFT GAS KILN NA67E LAGUNA RAKU KILN NA68E SPENCER CENTRAL VACUUM SYSTEM 208 3 21.1A 3#10 & 1#10 GND 3/4" RECEPTACLE70N SCREEN WASHOUT SINK W/ VERTICAL
LIGHT BOX120 1 2A 2#12 & 1#12 GND 3/4" RECEPTACLE
75E WILTON DRILL PRESS 120 1 8A 2#12 & 1#12 GND 3/4" RECEPTACLE76E FOREDOM-RIO GRANDE FLEX DRILL PRESS 120 1 1.7A 2#12 & 1#12 GND 3/4" RECEPTACLE77E HAMILTON SLOW COOKER 120 1 2A 2#12 & 1#12 GND 3/4" RECEPTACLE78E FORDOM-RIO GRANDE FLEX SHAFT 120 1 1.2A 2#12 & 1#12 GND 3/4" RECEPTACLE79E CRAFTSMAN BENCH GRINDER 120 1 2.1A 2#12 & 1#12 GND 3/4" RECEPTACLE80E PROGRAMMABLE GAS KILN 120 1 2A 2#12 & 1#12 GND 3/4" RECEPTACLE81E REF 120 1 9A 2#12 & 1#12 GND 3/4" RECEPTACLE85E VULCANIZING PRESS 120 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE86E HAMILTON BEACH SLOW COOKER (PICKLE
POTS)120 1 XX 2#12 & 1#12 GND 3/4" RECEPTACLE
87E WAX INJECTOR 120 1 9A 2#12 & 1#12 GND 3/4" RECEPTACLE89E GESSWEIN ULTRASONIC CLEANER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE90E ELECTRIC MELT CRUCIBLE 120 1 11.3A 2#12 & 1#12 GND 3/4" RECEPTACLE91E ARBE POLISHER 120 1 9A 2#12 & 1#12 GND 3/4" RECEPTACLE92E HEGNER SCROLL SAW 120 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE93E BELT SANDER 120 1 5.4A 2#12 & 1#12 GND 3/4" RECEPTACLE94E DISC SANDER 120 1 14A 2#12 & 1#12 GND 3/4" RECEPTACLE95E LAMPERT-PUK 4 MICRO WELDER 120 1 6A 2#12 & 1#12 GND 3/4" RECEPTACLE96E GRIZZLY MINI LATHE 120 1 9A 2#12 & 1#12 GND 3/4" RECEPTACLE97E AMACO ENAMEL KLINN 208 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE98E PARAGON ENAMEL KILNS ON SS CART 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE99E LITTLE GIANT PUMP AND SPRAY ETCHING
TANK120 1 2.1A 2#12 & 1#12 GND 3/4" RECEPTACLE
101E WILTON BAND SAW 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE102E DAYTON BENCH GRINDER 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE103E PARAGON INVESTMENT AND DEWAX KILN 208 1 22A 2#10 & 1#10 GND 3/4" RECEPTACLE104E VIC 12 CASTING MACHINE 120 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE106E BEAD BLAST CABINET 120 1 XX 2#12 & 1#12 GND 3/4" RECEPTACLE107E DONALDSON DUST COLLECTOR 208 1 10A 2#12 & 1#12 GND 3/4" RECEPTACLE109E POWDER COATING OVEN 120 1 XX 2#12 & 1#12 GND 3/4" RECEPTACLE200E RABBIT LASER CUTTER 208 1 12A 3#10 & 1#10 GND 3/4" RECEPTACLE202E DELL OPTIPLEX COMPUTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE203E EPSON FLATBED SCANNER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE204E CUBE 3D PRINTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE205E SEWING MACHINE 120 1 5A 2#12 & 1#12 GND 3/4" RECEPTACLE210E GE REFRIGERATOR 120 1 9A 2#12 & 1#12 GND 3/4" RECEPTACLE225E KAISER COPY STAND 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE226E PREMIER ROTO DRUM DRYER 120 1 2.7A 2#12 & 1#12 GND 3/4" RECEPTACLE227E LIGHT TABLE 120 1 1A 2#12 & 1#12 GND 3/4" RECEPTACLE228E BRETFORD LIGHT TABLE 120 1 1A 2#12 & 1#12 GND 3/4" RECEPTACLE229E DRY MOUNTING PRESS 120 1 11.7A 2#12 & 1#12 GND 3/4" RECEPTACLE230E ABSOCOLD CUBE REFRIGERATOR 120 1 1.1A 2#12 & 1#12 GND 3/4" RECEPTACLE231E AMERGRAPH EXPOSURE TABLE 120 1 15A 2#12 & 1#12 GND 3/4" RECEPTACLE232E CHEM SINK NA NO ELEC233E GE REFRIGERATOR 120 1 5A 2#12 & 1#12 GND 3/4" RECEPTACLE235E BESELER ENLARGER 120 1 5A 2#12 & 1#12 GND 3/4" RECEPTACLE236E PVC CHEMICAL PROCESS SINK NA NO ELEC243E LIGHT TABLE 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE245E EXPOSURE TABLE W/ VACUUM PRESS 120 1 XX 2#12 & 1#12 GND 3/4" RECEPTACLE246E VALAD HOT PLATE 120 1 13.8A 2#12 & 1#12 GND 3/4" RECEPTACLE247E LARGE FORMAT PRINTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE250E PVC PROCESS SINK NA NO ELEC253E IMAC COMPUTERS 120 1 2A 2#12 & 1#12 GND 3/4" RECEPTACLE254E LARGE FORMAT EPSON PRINTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE255E LARGE FORMAT EPSON PRINTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE256E LARGE FORMAT EPSON PRINTER 120 1 1.5A 2#12 & 1#12 GND 3/4" RECEPTACLE257E FLATBED SCANNER 120 1 0.5A 2#12 & 1#12 GND 3/4" RECEPTACLE263E IMAC COMPUTERS 120 1 2A 2#12 & 1#12 GND 3/4" RECEPTACLE
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.05 09:20:28-07'00'
TECHNOLOGY SYMBOL LEGEND
T4T3
A
DRAWING NUMBER WHERE TAKEN
DRAWING NUMBER WHERE DETAILED
SECTION/ELEVATION LETTER OR DETAIL NUMBER
A
T4
6
T4 DRAWING NUMBER WHERE DETAILED
SECTION/ELEVATION LETTER OR DETAIL NUMBER
NORTH ARROW OR MATCH ARCHITECT'S
SCALE BAR OR MATCH ARCHITECT'S
GENERAL DRAWING SYMBOLS
DEFINITIONABBREV.
ABBREVIATIONS
NORTH
T3 T4
6
0 10' 20' 40' 80'
1" = 40'-0"
IC
S
W
B
SC
WAP
FLUSH
+84"UON
CEILING
WALL
FLOOR
FLOOR BOX WITH POWER AND VOICE\DATA. "#" DENOTES NUMBER OF DATA PORTS.
VOICE\DATA OUTLET ABOVE COUNTER TOP
FLOOR BOX WITH A/V. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS.
CEILING SPEAKER: LOCAL SOUND SYSTEM
INTERCOM WALL SPEAKER
INTERCOM CALL SWITCH
CABLE TRAY FOR COMMUNICATIONS
VARIESSEE
PLANS
SPECIAL SYSTEMS
+44"UONWALL
TELEPHONE OUTLET WALL MOUNTED
COMMUNICATION HORN
COMMUNICATION BELL
COMBINATION CLOCK/SPEAKER. MOUNTEDABOVE AND CENTER TO WRITING/TACK BOARD
SEEPLANSWALL
WIRELESS ACCESS POINT
J-HOOK ROUTING PATH
S
J
Jxx
S
WALL +96"UON
ABOVE CEILING
xS IC CEILING SPEAKER: INTERCOM SYSTEM
J Jx A/V JUNCTION BOX. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS.
SEEPLANSWALL
JJx
J JJx Jx A/V J- BOXES STACKED VERTICALLY. REFER TO
J-BOX SCHEDULE ON 600 SERIES SHEETS.
SEEPLANS
+18"UONWALL
VOICE\DATA OUTLET (WITH QTY. (3) PORTS UON)
AC
DURESS ALARM PUSHBUTTON
LOCK DOWN PUSHBUTTON
DA
LDSEE
PLANSWALL
DSVD DIGITAL SIGNAGE VIDEO DISPLAY
CEILING VOICE/DATA"#" DENOTES NUMBER OF DATA PORTS.
VP VIDEO PROJECTOR
REFER TO PLANS
SEEPLANSWALL
ICM INTERCOM MASTER STATION
+44"UON
WALL
J JxCEILING MOUNTED A/V JUNCTION BOX. REFER TO J-BOX SCHEDULE ON 600 SERIES SHEETS.
CR
KP
G
DS
CARD READER
SECURITY CAMERA (BOX, FIXED)
WALL +44"UONKEY PAD
GLASS BREAK DETECTORSEE
PLANS
DOOR SWITCH
DOORSEE
PLANS
WINDOW
SECURITY CAMERA (DOME, FIXED OR PTZ)
SECURITY
SEE PLANS
VARIESSECURITY CAMERA 180°
SECURITY CAMERA 360°
M CEILING MOTION DETECTOR SEEPLANSCEILING
ES ELECTRIC STRIKE
ML MAGNETIC LOCK
MOUNTINGHT.LOC.SYMBOL DESCRIPTION
SYMBOL DESCRIPTION MOUNTINGHT.LOC.
R
EX
DEMOLITION
DASHED SYMBOL INDICATES EXISTING DEVICE OR EQUIPMENT TO BE REMOVED
SOLID SYMBOL, LIGHTER IN COLOR INDICATES EXISTING DEVICE OR EQUIPMENT TO REMAIN
EXISTING CONDUIT TO BE REUSED
REMOVE EXISTING RACEWAY IN ALL ACCESSIBLE AREAS. CAPPED AND ABANDONED IF IN UNACCESSIBLE AREA
REFER TO DEMOLITION PLANS FOR ADDITIONAL
INFORMATION
SYMBOL DESCRIPTION NOTES
GROUND BAR
SYMBOL
EQUIPMENTDESCRIPTION
ELECTRICAL PANELBOARD. DASHED LINES INDICATE CLEARANCES. (SEE ELECTRICAL DRAWINGS.)L1A
T1A
UNINTERRUPTABLE POWER SUPPLY. DASHED LINES INDICATE CLEARANCES.
DRY TYPE TRANSFORMER (15kVA OR ABOVE), WITH EQUIPMENT TAG (SEE ELECTRICAL DRAWINGS.)
UPS-A
G
DRY TYPE TRANSFORMER (LESS THAN 15kVA), WITH NO EQUIPMENT TAG.(SEE ELECTRICAL DRAWINGS.)T
CONCEALED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT IN WALLS OR IN CEILING SPACE
UNDERGROUND RACEWAY BETWEEN DEVICES AND OR EQUIPMENT
EXPOSED RACEWAY BETWEEN DEVICES AND OR EQUIPMENT ON WALLS OR CEILINGS
CONDUIT TURNSDOWN UP
B BUSWAYGROUNDING CONDUCTORG
CABLE TRAY - POWER AND TELECOMMUNICATIONS
T TELECOMMUNICATIONS RACEWAYD DATA RACEWAY
FA FIRE ALARM RACEWAY
CONDUIT STUBBED AND CAPPED
VOICE/DATA COMBINATION RACEWAYV/D
RACEWAY & CONDUCTORSDESCRIPTIONSYMBOL
(NOT ALL SYMBOLS APPLY TO THIS PROJECT)
+44"
VAV-9
SYMBOL DEFINITION
REFERENCE TAGS
KEYED NOTE REFERENCE
MECHANICAL EQUIPMENT REFERENCE
DENOTES MOUNTING HEIGHT AFF
KITCHEN EQUIPMENT REFERENCE
MEDICAL EQUIPMENT REFERENCE
VR POLYCARBONITE VANDAL RESISTANT COVER
LD LOCK DOWN
DISTRIBUTION POLE FOR OVERHEAD ELECTRICAL OR COMMUNICATIONS AS INDICATED ON PLAN.
OVERHEAD UTILITY AND OR SYSTEM DISTRIBUTION.XX
3PH = THREE PHASE (SEE ELECTRICAL DRAWINGS.)
XX
UT UTILITY OR FACILITY TRANSFORMER (SEE ELECTRICAL DRAWINGS.)
MHMANHOLE - POWER OR COMMUNICATIONAS INDICATED ON PLANS
HH HAND HOLE - POWER OR COMMUNICATIONAS INDICATED ON PLANS
1PH = SINGLE PHASE (SEE ELECTRICAL DRAWINGS.)
S = ELECTRICAL SECONDARY (SEE ELECTRICAL DRAWINGS.)P = ELECTRICAL PRIMARY (SEE ELECTRICAL DRAWINGS.)
T = TELECOMMUNICATIONTV = TELEVISIONE = EMERGENCY POWERATSC=AUTOMATIC TRANSFER SWITCH CONTROL(SEE ELEC. DRAWINGS.)
TP TELECOMMUNICATION PEDESTAL
TVP TELEVISION PEDESTAL
UTILITIESDESCRIPTIONSYMBOL
UNDERGROUND UTILITY AND OR SYSTEM DISTRIBUTION.
X
X
N = NEWEX = EXISTING MULTI-OULET ASSEMBLY (SURFACE MOUNTED
RACEWAY)
COMBINATION POWER/COMMUNICATION POLE.CONFIGURATION AS NOTED ON PLANS
O/H = OVER HEADU/G = UNDERGROUND
MAIN SWITCHBOARD. DASHED LINES INDICATE CLEARANCES.(SEE ELECTRICAL DRAWINGS.)MSB
DISTRIBUTION BOARD. DASHED LINES INDICATE CLEARANCES.(SEE ELECTRICAL DRAWINGS.)
DB
MCC
MOTOR CONTROL CENTER. DASHED LINES INDICATE CLEARANCES.(SEE ELECTRICAL DRAWINGS.)
WALL MOUNTED CODE SIZE J-BOXJ
J CODE SIZE JUNCTION BOX
M WALL MOUNTED MOTION DETECTOR WALL+84"UON
S INTERCOM SPEAKER HORNIC
IC
FLAT PANEL OR PROJECTION SCREEN
TV TELEVISION OUTLET
DC DOOR CONTACT
KS KEY SWITCH
F FIBER RACEWAY
AMPS, AMPEREAMPLIFIERABOVE COUNTERALTERNATING CURRENTAMERICANS WITH DISABILITIES ACTABOVE FINISHED FLOORABOVE FINISHED GRADEAVAILABLE INTERRUPTING CURRENTALUMINUMAMERICAN NATIONAL STANDARDS INSTITUTEAUTOMATIC TRANSFER SWITCH CONTROLAUTOMATIC TRANSFER SWITCHAUDIO-VISUAL OR AUDIO-VIDEOAMERICAN WIRE GAUGEBELOW FINISHED GRADECONDUITCIRCUIT BREAKERCLOSED CIRCUIT TELEVISIONCONTRACTOR FURNISHED CONTRACTOR
INSTALLEDCIRCUITCLOCKCURRENT LIMITING FUSECONDUIT ONLYCOPPERDIMMINGDIRECT CURRENTDAY-LIGHTINGDIAMETERDIGITAL SIGNAGE VIDEO DISPLAYEMERGENCYEMERGENCY, CRITICALENGINE GENERATOREQUIPMENT & GROUNDING CONDUCTOREMERGENCY, LIFE SAFETYELECTRICAL METALLIC TUBINGELECTRIC WATER COOLEREXISTINGFUTUREFIRE ALARMFIRE ALARM ANNUNCIATORFIRE ALARM CONTROL PANELFIRE ALARM POWER SUPPLYFIRE ALARM MASS NOTIFICATION CONTROL
PANELFIRE ALARM MASS NOTIFICATION TERMINAL
PANELFEEDERFIBER DISTRIBUTION UNITGENERATORGROUND FAULT INTERRUPTERGROUND FAULT CIRCUIT INTERRUPTERGROUND FAULT PROTECTIONGROUNDHANDHOLEHAND-OFF-AUTOMATICHORSEPOWERINSTITUTE OF ELECTRICAL AND ELECTRONICS
ENGINEERSINTERCOMINTERCOM MASTERISOLATED GROUNDTHOUSAND CIRCULAR MILSKNOCK-OUTKILOVOLTKILOVOLT AMPSKILOVOLT AMPS REACTIVEKILOWATTKILOWATT HOURLIGHT INTERFACE UNITLONG TIME, SHORT TIME, INSTANTANEOUS,
AND GROUNDMAXIMUMMOTOR CONTROL CENTERMANHOLEMICROPHONEMINIMUMMIXED MEDIAMANUAL TRANSFER SWITCHMEGAVOLT AMPSNEWNOT APPLICABLENORMALLY CLOSEDNATIONAL ELECTRICAL CODENATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATIONNEUTRALNATIONAL FIRE PROTECTION ASSOCIATIONNOT IN CONTRACTNORMALNEW MEXICONORMALLY OPENOWNER FURNISHED CONTRACTOR INSTALLEDOWNER FURNISHED OWNER INSTALLEDOVERHEADPOLEPUBLIC ADDRESSPHOTOCELLPHASEPOWER MONITORING AND CONTROL SYSTEMPOWER OVER ETHERNETRIGID STEEL CONDUITSECURITYSURGE PROTECTIVE DEVICESWITCHTEMPORARYTELECOMMUNICATIONS MAIN GROUNDING
BUS BARTELEPHONE TERMINAL BOARDTELEVISIONTRANSIENT VOLTAGE SURGE SUPPRESSERTYPICALUNDER COUNTERUNDERGROUNDUNDERGROUND ELECTRICUNDERWRITERS' LABORATORIESUNLESS OTHERWISE NOTEDUNINTERRUPTIBLE POWER SUPPLYVOLTS, VOLTAGEVARIABLE FREQUENCY DRIVEVANDAL RESISTANTWIREWEATHERPROOF AND GFCIWEATHERPROOFTRANSFERTRANSFORMER
AAMPACA/CADAAFFAFGAICALANSIATSCATSAV, A/VAWGBFGCCBCCTVCFCI
CKTCLCLFCOCUDDCDLDIADSVDEECEGEGCELEMTEWCEXFUTFAFAAFACPFAPSFAMNCP
FAMNTC
FDRFDUGENGFIG,GFCIGFPGNDHHHOAHPIEEE
ICICMIGKCMILKOKVKVAKVARKWKWHLIULSIG
MAXMCCMHMICMINMMMTSMVANNANCNECNEMA
NEUTNFPANICNLNMNOOFCIOFOIOH (O/H)PPAPCPHPMCSPOERSCSECSPDSWTEMPTMGB
TTBTVTVSSTYPUCU/GUGEULUONUPSVVFDVRWWGWPXFERXFMR (TRANSF)
#
#
#
ADA AUTOMATIC DOOR ACTUATOR PUSH PLATE FOR HANDICAP ACCESSIBILITY
EN
JAM N E. BOSSE
19418
GI N
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
NO SCALE
T-001
NEW ARTBUILDINGNMSU LAS CRUCES, NM
TECHNOLOGY LEGEND
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB/SPO
CSK/JEB/SDR
ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND
INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS
AND TESTING OF ALL NETWORK CABLING.
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.04 17:23:23-07'00'
DN
EV
ET
EV
DN
E
E
8'
CMU
8'
CMU
KENT HALLNEW ART BUILDING FOOTPRINT
BUSINESS COMPLEX BUILDING
HSS BUILDING
EN & SP BUILDINGS
NEW ART BUILDING FOOTPRINT
EXISTING TUNNEL(UNDERGROUND CHILLED WATER & STEAM, COMMUNICATIONS, FIRE PROTECTION)
NEW FIBER OPTIC & COPPER SERVICE ENTRANCE FROM GUTHRIE HALL BASEMENT. COORDINATE WITH NMSU ICT.
MDF T125A
EXISTING WILLIAMS HALL & ANNEX BUILDINGS
BID LOT 1
FIBER/COPPER ROUTE TEMPORARY COMMUNICATIONS PATHWAY FROM BUISNESS COMPLEX - UTILIZING EXISTING PATHWAY INTO BUILDING FROM TUNNEL. COORDINATE WITH NMSU ICT.
EXISTING POWER & FIBER TIE-IN
1
2
3
EN
JAM N E. BOSSE
19418
GI N
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
1" = 20'-0"
TS-102
NEW ARTBUILDINGNMSU LAS CRUCES, NM
TECHNOLOGY SITE PLAN
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB/SPO
CSK/JEB/SDR
GENERAL SHEET NOTES
1" = 20'-0"TS-102
1 TECHNOLOGY SITE PLAN
NORTH
0' 10' 20' 40' 80'
ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND
INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS
AND TESTING OF ALL NETWORK CABLING.
A. THE CONDUIT RUNS, AS SHOWN ON PLANS, INDICATE APPROXIMATE ROUTING. EXACT LOCATION OF CONDUIT RUNS SHALL BE AS FIELD CONDITIONS DICTATE.
B. ALL LOW VOLTAGE CONDUCTORS SHALL BE RUN IN SEPARATE RACEWAYS FROM POWER CONDUCTORS (120VAC OR HIGHER PHASE TO NEUTRAL). NO EXCEPTIONS.
C. ALL UNDERGROUND CONDUITS LOCATED UNDER ROADWAYS AND PARKING LOTS SHALL BE CONCRETE ENCASED PATHWAYS TRAFFIC RATED TIER 22.
D. ALL HANDHOLES AND MANHOLES LOCATED IN ROADWAYS AND PARKING LOTS SHALL BE TRAFFIC RATED H20.
E. ALL UNDERGROUND CABLING TO BE OSP RATED.F. ALL CONDUIT TURNS SHALL BE "SWEEP" TYPE, NO 90 DEGREE BEND FITTINGS ARE
PERMITTED.G. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL
BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.
KEYNOTES
1. FIBER/COPPER ROUTE COMMUNICATIONS PATHWAY FROM TUNNEL. COORDINATE EXACT PATH WITH NMSU ICT AND ALL OTHER TRADES. PROVIDE (3) 4" UNDERGROUND CONDUITS TO MDF. PROVIDE HANDHOLES AT LOCATIONS IN CONDUIT PATHWAYS WITH NO MORE THAN (2) 90 DEGREE BENDS TOTAL. FIBER AND COPPER TO FEED FROM GUTHRIE HALL BASEMENT. REFER TO SHEET T-401 FOR ONE-LINE DIAGRAM. REFER TO DETAILS D3 AND E5 ON SHEET T-502 FOR DUCTBANK AND HANDHOLE REQUIREMENTS.
2. KEEP EXISTING WILLIAMS HALL AND ANNEX OPERATIONAL. FIBER/COPPER ROUTE COMMUNICATIONS PATHWAY FROM TUNNEL. COORDINATE EXACT PATH WITH NMSU ICT AND ALL OTHER TRADES. PROVIDE 4" UNDERGROUND CONDUITS TO EXISTING TIE-IN. PROVIDE HANDHOLES AT LOCATIONS IN CONDUIT PATHWAYS WITH NO MORE THAN (2) 90 DEGREE BENDS TOTAL. FIBER AND COPPER TO FEED FROM BUSINESS COMPLEX. COORDINATE FIBER AND COPPER CONNECTIONS TO WILLIAMS HALL AND ANNEX WITH NMSU ICT.
3. INTERCEPT EXISTING FIBER PATHWAY TO WILLIAMS HALL AND ANNEX.
REFER TO PHASING SEQUENCE PROGRAM IN SPEC SECTION 01 1000 FOR DETAIL INFORMATION FOR SITE PROGRAM
PHASING SEQUENCE:• PHASE I. UTILITIES TO KEEP EXISTING WILLIAMS HALL
AND ANNEX OPERATIONAL.
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.04 17:23:35-07'00'
2
2
2
2
2
2
2
2
JJ
JJ
DSVD
CR
DS
DS
WAP
WAP
WAP WAP
VP
2
2 2
2
2
2
2
S
2
S
AD
A
ADA
AD
A
KP
CR
DS DS
KP
2
2
CR
CR
CR
CR
M
M
M
M
M
M
M
M
M
M
M
M
M
RFB4E-OG RFB4E-OG RFB4E-OG
RFB4E-OGRFB4E-OGRFB4E-OG
RFB4E-OG RFB4E-OG RFB4E-OG
CR
VP
2
J
J
WAP
2
2
S
2
S
2
2
2
2
2
2
M
M
CR
AD
A
2
2
2
2
2
22
2
2
2
2
2
KP
222
WAP
2
2
DS DSCR
2
2
M
M
CR
CR
AD
A
/1
T-1
01B
/1
T-1
01B
ART GALLERY105
UAGCOLLECTION
STUDY106
STAFF TOILETFEMALE
R108
GALLERYWORK RM
107
A.G. OFFICE109
MODERN &CONTEMPORARY
ART GALLERY105A
HALLH101B
FRAME PREPROOM
113
A.G. OFFICE111
STAFF TLTMALER112
CONSERVATIONLAB115
GALLERYSTORAGE
108
HALLH101A
TYP.
1
2
TYP.
3
TYP.
4
TYP.
9
TYP.
8
TYP.
16
TYP.
15
TYP.
5
10
TYP.
16
CONSERVATIONLAB OFFICE
115A
RETABLOSGALLERY
110
ENTRYVESTIBULE
100D
ENTRYVESTIBULE
100A
C
2
B
1
D
3
5
4
A
J1J3
J1J3
B.6 D.8
1.5
2.3
2.6
2.7
5.1
B.8
6
D.3
1.2
1.4
1.6
STORAGE115B
2.4
2.2
2.9
3.5
4.4
5.3
A.8 D.45D.4
2.65
4.5
J1
J3
TYP.
19
2
2
12
TYP.
11
TYP.
11
18
21
21
21
22
23
22
22
TYP.
22
23
23
23
23
23
23
23
23
AC ACENTRY
VESTIBULE100D
RECEPTION &ADMIN.
ASSISTANT118A
WAITING118
DEPT. HEADOFFICE
118X
A.H. OFFICE118C
A.H. OFFICE118D
A.H. OFFICE118E
A.H. OFFICE118F
WORKRM/STORAGE
118H
ENTRYVESTIBULE
100D
GALLERYSTORAGE
108
CONSERVATIONLAB OFFICE
115A
CB D
5
A
6.1
6.6
B.6
5.1
B.8
6
4.4
5.3
6.4
A.8
4.5
TYP.
12
23
22
23
22
TYP.
22
23
EN
JAM N E. BOSSE
19418
GI N
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
1/8" = 1'-0"
T-101A
NEW ARTBUILDINGNMSU LAS CRUCES, NM
BASE BID & BID LOT 1 1ST LEVEL TECHSYSTEMS FLOOR PLAN - GALLERY WING
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB/SPO
CSK/JEB/SDR
1/8" = 1'-0"T-101A
1 BASE BID 1ST LEVEL TECHNOLOGY SYSTEMS FLOOR PLAN - GALLERY WING
GENERAL SHEET NOTES
KEYNOTES
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF
BOX) UNLESS OTHERWISE NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.
H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS.
I. NUMBER ADJACENT TO TELECOMMUNICATIONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.
J. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE PERMITTED.
K. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.
L. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.
M. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS.
N. CONTRACTOR IS PROVIDE AND TERMINATE CABLING FOR THE BLACKBOARD SYSTEM AND T0 “FUTURE” CARD READERS.
O. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.
P. ANY ON-GRADE FLOOR BOX APPLICATIONS, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET-RATED" CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.
ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND
INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS
AND TESTING OF ALL NETWORK CABLING.
1/8" = 1'-0"T-101A
2
BID LOT 1 ADMINISTRATION1ST LEVEL TECHNOLOGY SYSTEMS FLOOR PLAN
NORTH
0' 8' 16' 32' 64'
NORTH
KEY PLAN
GALLERY
WING
STUDIO
WING EXTERIOR
YARD
MA
TC
H L
INE
RECEIVING
BID LOT 1
0' 8' 16' 32' 64'
1. STANDARD TELECOMMUNICATIONS OUTLET. CONSISTS OF CATEGORY 6 CABLES. QUANTITY AS SHOWN. REFER TO DETAILS D1 AND D2 ON SHEET T-502.
2. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. CO-LOCATE WITH CEILING POWER OUTLET. QUANTITY AS SHOWN.
3. WIRELESS ACCESS POINT LOCATION. PROVIDE A CLEAR LABEL FOR LOCATION OF WIRELESS ACCESS POINT ON ACCESSIBLE CEILING TILE OR WALL NEAR ACCESSIBLE CEILING TILE. WIRELESS ACCESS POINT HARDWARE FURNISHED AND INSTALLED BY OWNER.
4. 12" X 4" WIRE BASKET STYLE CABLE TRAY FOR HORIZONTAL TELECOMMUNICATIONS CABLING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
5. CEILING SPEAKERS FOR LOCAL SOUND SYSTEM. COORDINATE WITH OWNER FOR EXACT LOCATIONS AND QUANTITIES. REFER TO DETAILS A6 AND B6 ON SHEET T503
6. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAILS A2, B1, AND B2 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES. COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.
7. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.
8. CEILING MOUNTED PROJECTOR LOCATION. REFER TO DETAILS A2 AND B2 ON SHEET T503 FOR ROUGH-IN REQUIREMENTS. PROVIDE 120V POWER RECEPTACLE MOUNTED PER DETAILS A2 AND B2 ON SHEET T503. DISTANCE FROM DISPLAY SURFACE IS CRITICAL, COORDINATE EXACT LOCATION / THROW DISTANCE WITH ARCHITECT AND OWNER.
9. MOTORIZED PROJECTION SCREEN LOCATION FOR LOCAL A/V SYSTEM. FOR 120V SCREEN SWITCH REQUIREMENTS REFER TO ELECTRICAL SHEETS. COORDINATE WITH OWNER FOR SCREEN ROUGH-IN REQUIREMENTS.
10. WALL MOUNTED DIGITAL SIGNAGE VIDEO DISPLAY LOCATION. PROVIDE STRUCTURAL BACKING, BACK BOXES, AND POWER/ VOICE/DATA OUTLETS AS SHOWN ON DETAIL C4 AND C5 ON SHEET T-503.
11. PULL BOXES FOR A/V CABLING. REFER TO DIAGRAMS AND A/V J-BOX SCHEDULE ON SHEET T-601 FOR REQUIREMENTS.
12. BOX AND CONDUIT ROUGH-IN FOR ACCESS CONTROL. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE FOR ADDITIONAL REQUIREMENTS.
13. 12" X 4" WIRE BASKET STYLE CABLE TRAY BLACK POWDER COATED FOR HORIZONTAL TELECOMMUNICATIONS CABLING. PROVIDE CABLE TRAY LINER TO PROTECT CABLES IN OPEN CEILING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
14. TELECOMMUNICATIONS OUTLETS IN OPEN CEILING AREAS TO HOMERUN CONDUITS TO NEAREST CABLE TRAY.
15. BOX AND CONDUIT ROUGH-IN FOR INTRUSION ALARM SYSTEM KEYPAD. 16. AUTOMATIC DOOR ACTUATOR LOCATION FOR PUSH PLATE HANDICAP ACCESS.
REFER TO ELECTRICAL FLOOR PLANS FOR ADDITIONAL REQUIREMENTS, PATHWAYS, AND POWER.
17. 2-WAY COMMUNICATION SYSTEM CALLING STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO BASE STATION. PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND TO BASE STATION. LOCATE BASE STATION . REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.
18. 2-WAY COMMUNICATION SYSTEM BASE STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO MDF ROOM #125A.PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND ON 110 FIELD FOR PHONE TERMINATION. REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.
19. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.
20. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAIL A1 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.
21. BOX AND CONDUIT ROUGH-IN FOR FUTURE CARD READER EQUIPMENT INSTALLATION. PROVIDE BLANK COVER PLATE. STUB CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE ON SHEET A-600, AND SPECIFICATION 08 7100 DOOR HARDWARE FOR ADDITIONAL REQUIREMENTS.
22. 2" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.
23. 4" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.
NOT ALL NOTES USED
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.04 17:23:53-07'00'
Table
CR
2
2
2
2
2
222
DS
DS DS
CR
CR
CR
EFB8S-OG
4
2
2
2 2
222
2
2
2
WAP
WAP
WAP WAP
WAP
WAP
WAP
VP
VP
DS
DS
CR
2
2
2
2
2
2
2
2
2
VP
VP
2
2
J
J
J J
J
2
J
J2
2
2
S2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
CR
DS
DS DS
2
2
EFB8S-OG
4
M
M
M
M
M
M
M
M
M
M
M
M
M
2
2
WAP
2
WAP
2 2 2
2 2 22
2
2
2
2 4
2
2
2
WAP
CR
CR
J
J
J
J
J
2
2
2 2
2
2 2
CR
J
AD
A
2
2
2
J
2
J
2
2
2
J
/1
T-1
01A
/1
T-1
01A
WOMENSR123A
MENSR123B
HALLH101D
MDFT125A
ELECM125B
UNIVERSALTLT
R123C
MECHANICALROOMM125C
FABRICATIONLAB129
JANITORJ131
JEWELRYSTORAGE
130C
JEWELRYFACULTYSTUDIO
130D
VEST.100E
METALS/JEWELRY130
ENAMEL130A
RAISING ROOM130B
WOOD SHOP126
SCULPTURE124
WET ROOM122E
SCULPTUREFACULTYSTUDIO
124A
MOLD RM123
CERAMICS122
CERAMICSFACULTYSTUDIO
122A GLAZE LAB122B
HALLH101E
GRADUATESTUDIO
120A
GRADUATESTUDIO
120B
GRADUATESTUDIO
120C
GRADUATESTUDIO
120D
GRADUATESTUDIO
120E
GRADUATESTUDIO
120F
GRADUATESTUDIO
120G
GRADUATESTUDIO
120H
CLAY MIXING122C
EXTERIORYARD
140
KILN ROOM122F
TYP.
1
TYP.
7
TYP.
4
TYP.
3
TYP.
9
TYP.
8
TYP.
5
T-4011
EXTERIORYARD
140
CASTING130F
LOCKERS130G
ENTRYVESTIBULE
100D
F G
8
2
ED
3
5
7
10
9
11
4
6.1
9.5
6.6
ELEVEL101
J3
J1
TYP.
12
J1
J1
J3
J1 J3
6
D.8 E.5 E.8 F.4 G.4
2.3
2.6
2.7
5.1
6
D.3
AC
AC AC
AC
AC
ADMINISTRATION118A
DEPT. HEADOFFICE
118B
WORK ROOM118C
2.4 2.4
E.6 F.7 H
2.2
10.9
2.9
3.5
4.4
5.3
6.4
6.9
7.8
8.8
E.4D.45 D.9D.4
2.65
4.5
2
2
2
2
12
TYP.
11
TYP.
11
12
J3
13
14
13
14
14
13
TYP.
4
4
18
12
21
21
21
21
21
23
23
23
23 22
22
23
23
WP
WP
WP
WP
WP
WP WP
WP
WP
GRADUATESTUDIO
120L
GRADUATESTUDIO
120K
GRADUATESTUDIO
120J
ED
3
D.8
2.7
D.3
2.9
3.5
D.45 D.9
23
23
21
23
EN
JAM N E. BOSSE
19418
GI N
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
1/8" = 1'-0"
T-101B
NEW ARTBUILDINGNMSU LAS CRUCES, NM
BASE BID & BID LOT 1 1ST LEVEL TECHSYSTEMS FLOOR PLAN - STUDIO WING
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB/SPO
CSK/JEB/SDR
1/8" = 1'-0"T-101B
1 BASE BID 1ST LEVEL TECHNOLOGY SYSTEMS FLOOR PLAN - STUDIO WING
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF
BOX) UNLESS OTHERWISE NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.
H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS.
I. NUMBER ADJACENT TO TELECOMMUNICATIONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.
J. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE PERMITTED.
K. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.
L. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.
M. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS.
N. CONTRACTOR IS PROVIDE AND TERMINATE CABLING FOR THE BLACKBOARD SYSTEM AND T0 “FUTURE” CARD READERS.
O. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.
P. ANY ON-GRADE FLOOR BOX APPLICATIONS, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET-RATED" CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.
1/8" = 1'-0"T-101B
2
BID LOT 1 GRAD STUDIOS 1ST LEVELTECHNOLOGY SYSTEMS FLOOR PLAN
ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND
INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS
AND TESTING OF ALL NETWORK CABLING.
NORTH
KEY PLAN
GALLERY
WING
STUDIO
WING EXTERIOR
YARD
MA
TC
H L
INE
RECEIVING
BID LOT 1
0' 8' 16' 32' 64'
NORTH
GENERAL SHEET NOTESKEYNOTES
1. STANDARD TELECOMMUNICATIONS OUTLET. CONSISTS OF CATEGORY 6 CABLES. QUANTITY AS SHOWN. REFER TO DETAILS D1 AND D2 ON SHEET T-502.
2. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. CO-LOCATE WITH CEILING POWER OUTLET. QUANTITY AS SHOWN.
3. WIRELESS ACCESS POINT LOCATION. PROVIDE A CLEAR LABEL FOR LOCATION OF WIRELESS ACCESS POINT ON ACCESSIBLE CEILING TILE OR WALL NEAR ACCESSIBLE CEILING TILE. WIRELESS ACCESS POINT HARDWARE FURNISHED AND INSTALLED BY OWNER.
4. 12" X 4" WIRE BASKET STYLE CABLE TRAY FOR HORIZONTAL TELECOMMUNICATIONS CABLING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
5. CEILING SPEAKERS FOR LOCAL SOUND SYSTEM. COORDINATE WITH OWNER FOR EXACT LOCATIONS AND QUANTITIES. REFER TO DETAILS A6 AND B6 ON SHEET T503
6. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAILS A2, B1, AND B2 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES. COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.
7. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.
8. CEILING MOUNTED PROJECTOR LOCATION. REFER TO DETAILS A2 AND B2 ON SHEET T503 FOR ROUGH-IN REQUIREMENTS. PROVIDE 120V POWER RECEPTACLE MOUNTED PER DETAILS A2 AND B2 ON SHEET T503. DISTANCE FROM DISPLAY SURFACE IS CRITICAL, COORDINATE EXACT LOCATION / THROW DISTANCE WITH ARCHITECT AND OWNER.
9. MOTORIZED PROJECTION SCREEN LOCATION FOR LOCAL A/V SYSTEM. FOR 120V SCREEN SWITCH REQUIREMENTS REFER TO ELECTRICAL SHEETS. COORDINATE WITH OWNER FOR SCREEN ROUGH-IN REQUIREMENTS.
10. WALL MOUNTED DIGITAL SIGNAGE VIDEO DISPLAY LOCATION. PROVIDE STRUCTURAL BACKING, BACK BOXES, AND POWER/ VOICE/DATA OUTLETS AS SHOWN ON DETAIL C4 AND C5 ON SHEET T-503.
11. PULL BOXES FOR A/V CABLING. REFER TO DIAGRAMS AND A/V J-BOX SCHEDULE ON SHEET T-601 FOR REQUIREMENTS.
12. BOX AND CONDUIT ROUGH-IN FOR ACCESS CONTROL. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE FOR ADDITIONAL REQUIREMENTS.
13. 12" X 4" WIRE BASKET STYLE CABLE TRAY BLACK POWDER COATED FOR HORIZONTAL TELECOMMUNICATIONS CABLING. PROVIDE CABLE TRAY LINER TO PROTECT CABLES IN OPEN CEILING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
14. TELECOMMUNICATIONS OUTLETS IN OPEN CEILING AREAS TO HOMERUN CONDUITS TO NEAREST CABLE TRAY.
15. BOX AND CONDUIT ROUGH-IN FOR INTRUSION ALARM SYSTEM KEYPAD. 16. AUTOMATIC DOOR ACTUATOR LOCATION FOR PUSH PLATE HANDICAP ACCESS.
REFER TO ELECTRICAL FLOOR PLANS FOR ADDITIONAL REQUIREMENTS, PATHWAYS, AND POWER.
17. 2-WAY COMMUNICATION SYSTEM CALLING STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO BASE STATION. PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND TO BASE STATION. LOCATE BASE STATION . REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.
18. 2-WAY COMMUNICATION SYSTEM BASE STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO MDF ROOM #125A.PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND ON 110 FIELD FOR PHONE TERMINATION. REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.
19. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.
20. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAIL A1 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.
21. BOX AND CONDUIT ROUGH-IN FOR FUTURE CARD READER EQUIPMENT INSTALLATION. PROVIDE BLANK COVER PLATE. STUB CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE ON SHEET A-600, AND SPECIFICATION 08 7100 DOOR HARDWARE FOR ADDITIONAL REQUIREMENTS.
22. 2" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.
23. 4" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.
NOT ALL NOTES USED
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.04 17:24:20-07'00'
UP
22
2
2
2
2
2
2
2
2
2
222
2
2
2
JJ
J J
2
2J
J
2J
J
J
8ATC
2
2
2
8ATC
8ATC
JJ
44
4 4
4
2
2 2
2
2 2
2 2
2
2 2
2 2
2
2
VP
VP
VP
VP
WAP
WAP
WAP
WAP
WAP
WAP
WAP WAP
DSCR
DS
CR
2
2
2
2
2
2
2
2
2
2
2 2
2
2
2
2
8ATC
8ATC
J
J
J
J
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
2
S
CR
DS
VP
2
J
VP
VP
CR
CR
M
M
M
M
M
CR
M
M
M
2 2 2 2
2 2 2 2
WAP
2
CR
J
J
J
2
2
2 2
2 2
2
2
J J
8ATC 8ATC
8ATC8ATC
2
8ATC
8ATC
ELEVATOR/STAIRLOBBY
200F
DIGITALOUTPUT
221
GRADUATESTUDIO
220A
GRADUATESTUDIO
220B
GRADUATESTUDIO
220C
GRADUATESTUDIO
220D
GRADUATESTUDIO
220E
GRADUATESTUDIO
220F
GRADUATESTUDIO
220G
GRADUATESTUDIO
220H
HALLH201E
FACULTYSTUDIO
(SAFETY)242
GRAD STUDIOHUDDLE
240GANG DARK
RM222B
PHOTO DOC. &STORAGE
210
PHOTOSTUDIO
222
FILMPROCESSING
RM222E
DESIGNSTUDIO
224WOMENS
R223AMENSR223B
STUDY/RESOURCE RM
229TR
T225AELEC. RM
M225B
COMPUTERLAB231
TECHNOLOGYLAB233
JEWELRYFACULTYSTUDIO
234
JANITORJ227
WASH OUT224A DARKROOM
224B
ETCHING RM224C
PAINTINGSTUDIO
230
STILL LIFESTORAGE
230A
DRAWINGSTUDIO
232
STUDENTCOLLABORATION
236
HALLH201G
DWG/PAINTINGFACULTYSTUDIO
238A
PHOTO.FACULTYSTUDIO
238B
DESIGNFACULTYSTUDIO
238C
CONFERENCERM235
DESIGNFACULTYSTUDIO
238D
TYP.
1
TYP.
3
TYP.
7
TYP.
4
TYP.
8
TYP.
9
TYP.
12
TYP.
5
TYP.
9
T-4012
20
DRESSING232A
DRESSING230B
SOUTH STAIRST101B
STORAGE222A FILM LOADING
222D
FILM LOADING222C
C F G
8
2
ED
3
5
7
10
9
11
4
6.1
9.5
6.6
J1 J3
J4
J1
J3
J1
J2
J3
J3J1
J1J3
J3
J1
J1
J3
D.8 E.5 E.8 F.4
2.3
2.6
2.7
5.1
11.2
6
D.3
2.4
E.6 F.7 H
2.2
10.9
9.6
8.9
2.9
3.5
4.4
5.3
6.4
6.9
7.8
8.8
E.4D.45 D.9D.4
2.65
4.5
2
2
7
2
2
2
2
2
TYP.
11
J3 J1
13
14
13
14
13
14
13
14
13
4
17
20
20
20
TYP.
6
21
21
21
23
23
23
23
23
23
23
22
23
23
EN
JAM N E. BOSSE
19418
GI N
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
1/8" = 1'-0"
T-102B
NEW ARTBUILDINGNMSU LAS CRUCES, NM
BASE BID 2ND LEVEL TECH SYSTEMSFLOOR PLAN - STUDIO WING
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB/SPO
CSK/JEB/SDR
1/8" = 1'-0"T-102B
1 BASE BID 2ND LEVEL TECHNOLOGY SYSTEMS FLOOR PLAN - STUDIO WING
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF
BOX) UNLESS OTHERWISE NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.
H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS.
I. NUMBER ADJACENT TO TELECOMMUNICATIONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.
J. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE PERMITTED.
K. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.
L. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.
M. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS.
N. CONTRACTOR IS PROVIDE AND TERMINATE CABLING FOR THE BLACKBOARD SYSTEM AND T0 “FUTURE” CARD READERS.
O. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.
P. ANY ON-GRADE FLOOR BOX APPLICATIONS, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET-RATED" CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.
ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND
INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS
AND TESTING OF ALL NETWORK CABLING.
NORTH
KEY PLAN
GALLERY
WING
STUDIO
WING EXTERIOR
YARD
MA
TC
H L
INE
RECEIVING
BID LOT 1
0' 8' 16' 32' 64'
GENERAL SHEET NOTESKEYNOTES
1. STANDARD TELECOMMUNICATIONS OUTLET. CONSISTS OF CATEGORY 6 CABLES. QUANTITY AS SHOWN. REFER TO DETAILS D1 AND D2 ON SHEET T-502.
2. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. CO-LOCATE WITH CEILING POWER OUTLET. QUANTITY AS SHOWN.
3. WIRELESS ACCESS POINT LOCATION. PROVIDE A CLEAR LABEL FOR LOCATION OF WIRELESS ACCESS POINT ON ACCESSIBLE CEILING TILE OR WALL NEAR ACCESSIBLE CEILING TILE. WIRELESS ACCESS POINT HARDWARE FURNISHED AND INSTALLED BY OWNER.
4. 12" X 4" WIRE BASKET STYLE CABLE TRAY FOR HORIZONTAL TELECOMMUNICATIONS CABLING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
5. CEILING SPEAKERS FOR LOCAL SOUND SYSTEM. COORDINATE WITH OWNER FOR EXACT LOCATIONS AND QUANTITIES. REFER TO DETAILS A6 AND B6 ON SHEET T503
6. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAILS A2, B1, AND B2 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES. COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.
7. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.
8. CEILING MOUNTED PROJECTOR LOCATION. REFER TO DETAILS A2 AND B2 ON SHEET T503 FOR ROUGH-IN REQUIREMENTS. PROVIDE 120V POWER RECEPTACLE MOUNTED PER DETAILS A2 AND B2 ON SHEET T503. DISTANCE FROM DISPLAY SURFACE IS CRITICAL, COORDINATE EXACT LOCATION / THROW DISTANCE WITH ARCHITECT AND OWNER.
9. MOTORIZED PROJECTION SCREEN LOCATION FOR LOCAL A/V SYSTEM. FOR 120V SCREEN SWITCH REQUIREMENTS REFER TO ELECTRICAL SHEETS. COORDINATE WITH OWNER FOR SCREEN ROUGH-IN REQUIREMENTS.
10. WALL MOUNTED DIGITAL SIGNAGE VIDEO DISPLAY LOCATION. PROVIDE STRUCTURAL BACKING, BACK BOXES, AND POWER/ VOICE/DATA OUTLETS AS SHOWN ON DETAIL C4 AND C5 ON SHEET T-503.
11. PULL BOXES FOR A/V CABLING. REFER TO DIAGRAMS AND A/V J-BOX SCHEDULE ON SHEET T-601 FOR REQUIREMENTS.
12. BOX AND CONDUIT ROUGH-IN FOR ACCESS CONTROL. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE FOR ADDITIONAL REQUIREMENTS.
13. 12" X 4" WIRE BASKET STYLE CABLE TRAY BLACK POWDER COATED FOR HORIZONTAL TELECOMMUNICATIONS CABLING. PROVIDE CABLE TRAY LINER TO PROTECT CABLES IN OPEN CEILING. MOUNT CABLE TRAY 10'-6" ABOVE FINISHED FLOOR, BOTTOM OF TRAY. COORDINATE WITH ALL OTHER TRADES AND ARCHITECT PRIOR TO COMMENCEMENT OF WORK. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
14. TELECOMMUNICATIONS OUTLETS IN OPEN CEILING AREAS TO HOMERUN CONDUITS TO NEAREST CABLE TRAY.
15. BOX AND CONDUIT ROUGH-IN FOR INTRUSION ALARM SYSTEM KEYPAD. 16. AUTOMATIC DOOR ACTUATOR LOCATION FOR PUSH PLATE HANDICAP ACCESS.
REFER TO ELECTRICAL FLOOR PLANS FOR ADDITIONAL REQUIREMENTS, PATHWAYS, AND POWER.
17. 2-WAY COMMUNICATION SYSTEM CALLING STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO BASE STATION. PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND TO BASE STATION. LOCATE BASE STATION . REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.
18. 2-WAY COMMUNICATION SYSTEM BASE STATION. PROVIDE 1" EMT CONDUIT, HOME RUN TO MDF ROOM #125A.PROVIDE PULL BOXES AS NEEDED. CABLING TO LAND ON 110 FIELD FOR PHONE TERMINATION. REFER TO SPECIFICATION SECTION 28 3200 FOR ADDITIONAL REQUIREMENTS.
19. STANDARD TELECOMMUNICATIONS OUTLET IN CEILING WITH CATEGORY 6 CABLES. QUANTITY AS SHOWN.
20. COMBINATION POWER AND DATA FLOOR BOX. DO NOT DAISY CHAIN FLOOR BOXES, PROVIDE A SEPARATE CONDUIT HOME RUN FOR EACH BOX. REFER TO DETAIL A1 ON SHEET T-502 FOR ADDITIONAL FLOOR BOX INFORMATION. ANY ON-GRADE APPLICATION, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET" RATED CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.COORDINATE FINAL MOUNTING LOCATIONS WITH EP SERIES SHEETS AND FURNITURE PRIOR TO COMMENCEMENT OF ANY WORK.
21. BOX AND CONDUIT ROUGH-IN FOR FUTURE CARD READER EQUIPMENT INSTALLATION. PROVIDE BLANK COVER PLATE. STUB CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE. REFER TO DOOR HARDWARE DETAILS ON SHEET T-501 AND ARCHITECTURAL DOOR HARDWARE SCHEDULE ON SHEET A-600, AND SPECIFICATION 08 7100 DOOR HARDWARE FOR ADDITIONAL REQUIREMENTS.
22. 2" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.
23. 4" CONDUIT SLEEVE THROUGH WALL AND/OR SOFFIT FOR VOICE, DATA, AND INTERCOM CABLING. PROVIDE PLASTIC BUSHINGS ON BOTH ENDS TO PROTECT CABLES. QUANTITY AS SHOWN.
NOT ALL NOTES USED
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.04 17:24:32-07'00'
CR
DS
DS
CR
2
MDFT125A
13
12
15
16
17
18
11 11
11
11
D
6.1
6
5.3
3' - 1 7/8" 3' - 0"
16
4
T-401
3
T-401
TYP.
19
20
21
TRT225A
14
15
16
17
11
11
11
11
D
6.1
6
5.3
7' - 10 1/8"
12' -
6 3
/4"
16
16
3
T-4015
T-401
2' - 5 1/8" 2' - 6"
TYP.
19
20
21
1ST LEVEL0' - 0"
2ND LEVEL15' - 6"
PENTHOUSELEVEL
30' - 8 1/2"
AFF48"
24"
MDFT125A
TRT225A
AFF48"
24"
7' -
6"
7' -
6"
GROUNDING BUS BAR
110 PUNCH BLOCK
GROUNDING BUS BAR
110 PUNCH BLOCK
4"ø
4"ø
4"ø
4"ø
4"ø
CONDUIT RISER
STRUCTURAL DECK
LADDER RACK
VERTICAL LADDER RACK
0' -
4"
3/4" AC PLYWOOD
0' -
4"
VERTICAL LADDER RACK
3/4" AC PLYWOOD
STRUCTURAL DECK
LADDER RACK
8' -
4"
8' -
4"
13
12
11
10
9
8
7
6
5
4
3
2
1
45
44
43
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
45
44
43
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
45
44
43
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
344
7
TYP.
8
TYP.
6
212
TYP.
5
9
13
12
11
10
9
8
7
6
5
4
3
2
1
45
44
43
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
43 1
9
UPS (OFOI)
RACK 3RACK 2RACK 1 RACK 4
RACK 3RACK 2RACK 1 RACK 4
FDU (BUILDING) 10
FDU (CAMPUS) 10
NETWORK SWITCH(OFOI)
NETWORK SWITCH(OFOI)
NETWORK SWITCH(OFOI)
NETWORK SWITCH(OFOI)
TYP.
9
13
12
11
10
9
8
7
6
5
4
3
2
1
45
44
43
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
42
9
13
12
11
10
9
8
7
6
5
4
3
2
1
45
44
43
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
43 1
RACK 2RACK 1
RACK 2RACK 1
FDU (BUILDING)10
TYP.
9
UPS (OFOI) TYP.
6
NETWORK SWITCH(OFOI)
NETWORK SWITCH(OFOI)
NETWORK SWITCH(OFOI)
NETWORK SWITCH(OFOI)
7
TYP.
8
TYP.
5
GUTHRIE HALL
MDF T125A
IDF T225A
48 STRAND OS2 SM OSP50 PAIR VOICE GRADE COPPER OSP
24 STRAND OS2 SM 25 PAIR VOICE GRADE COPPER
EN
JAM N E. BOSSE
19418
GI N
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
As indicated
T-401
NEW ARTBUILDINGNMSU LAS CRUCES, NM
ENLARGED TECHNOLOGY PLANS
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB/SPO
CSK/JEB/SDR
1/2" = 1'-0"T-401
1
TECHNOLOGY SYSTEMS ENLARGED1ST FLOOR PLAN - MDF T125A
1/2" = 1'-0"T-401
2
TECHNOLOGY SYSTEMS ENLARGED2ND FLOOR PLAN - TR T225A
GENERAL SHEET NOTES
KEYNOTES
1. 4 POST 84" TALL QUADRARACK TELECOMMUNICATIONS EQUIPMENT RACK. CPI# 50120-703.
2. 2 POST 84" TALL UNIVERSAL TELECOMMUNICATIONS EQUIPMENT RACK. CPI# 46353-703.
3. 6" WIDE VERTICAL WIRE MANAGERS. CPI #35571-703.4. 8" WIDE VERTICAL WIRE MANAGERS. CPI #35572-703.5. HORIZONTAL WIRE MANAGEMENT. CPI #35441-702.6. GROUND BUS BAR MOUNTED TO RACK.7. 48 PORT VOICE GRADE PATCH PANEL WITH 50 PAIR COPPER TO 110 BLOCK ON
WALL.8. 48 PORT CAT6 DATA PATCH PANEL.9. OWNER FURNISHED, OWNER INSTALLED ACTIVE NETWORK EQUIPMENT.10. FIBER DISTRIBUTION UNIT.11. 3/4" AC GRADE FIRE RESISTANT PLYWOOD WITH 2 COATS OF FIRE RESISTANT
PAINT ON ALL WALLS. LEAVE WINDOW WITH GRADE STAMP UNPAINTED.12. COPPER OSP PROTECTOR BLOCK ON WALL.13. 100 PAIR 110 STYLE PUNCHDOWN BLOCK ON WALL.14. 50 PAIR 110 STYLE PUNCHDOWN BLOCK ON WALL.15. TELECOMMUNICATIONS GROUND BUS BAR MOUNTED 24" BELOW CABLE TRAY.16. 4" FIRE-RATED CONDUIT PATHWAY. QTY AS SHOWN. REFER TO T SERIES
FLOOR PLANS FOR PATHWAY.17. (2) 4" FIRE RATED CONDUIT RISER PATHWAY. STUB UP FOR MDF 115 TO
SECOND FLOOR 6" AFF IN IT 252.18. (3) 4" UNDERGROUND CONDUIT PATHWAY. REFER TO SITE PLAN TS-102 FOR
ADDITIONAL INFORMATION.19. 18" WIDE CABLE TRAY LADDER RACK RUNWAY. PROVIDE MOUNTS,
GROUNDING, AND ACCESSORIES FOR FULL INSTALATION. CPI #10250-71820. 18" WIDE ADJUSTABLE CABLE TRAY LADDER RACK RUNWAY. PROVIDE MOUNTS,
GROUNDING, AND ACCESSORIES FOR FULL INSTALATION. CPI #14300-71821. 18" WIDE VERTICAL CABLE TRAY LADDER RACK RUNWAY. PROVIDE MOUNTS,
GROUNDING, AND ACCESSORIES FOR FULL INSTALATION.
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF
BOX) UNLESS OTHERWISE NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.
H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS.
I. NUMBER ADJACENT TO TELECOMMUNICATIONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.
J. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE PERMITTED.
K. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.
L. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.
M. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS.
N. CONTRACTOR IS PROVIDE AND TERMINATE CABLING FOR THE BLACKBOARD SYSTEM AND T0 “FUTURE” CARD READERS.
O. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.
P. ANY ON-GRADE FLOOR BOX APPLICATIONS, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET-RATED" CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.
NO SCALET-401
3 TECHNOLOGY SYSTEMS WALL ELEVATION: MDF T125A, IT T225A
ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND
INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS
AND TESTING OF ALL NETWORK CABLING.
GENERAL SHEET NOTES
NO SCALET-401
4
TECHNOLOGY SYSTEMS RACKELEVATION: MDF T125A
NO SCALET-401
5
TECHNOLOGY SYSTEMS RACKELEVATION: IT T225A
NO SCALET-401
6 TELECOMMUNICATIONS BACKBONE ONE-LINE DIAGRAM
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.04 17:24:44-07'00'
SOLID WOOD DOOR
HOLLOW METAL DOOR
WOOD BLOCK
MAGNET
MAGNET
SWITCH
MAGNET
DW
2/3 DW 1/3 DW
FLOOR
CEILING
1/2" EMT3 PAIR 22AWG
CR
DOORPOSITIONSWITCH
J
1" EMT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE.
4" SQ BOX WITH BLANK FACEPLATE (OPPOSITE SIDE OF DOOR FROM CARD READER)
DOORPOSITIONSWITCH
1/2" EMT4 CONDUCTOR 22AWG
4" SQ BOX FOR CARD READER.
DRILL HOLE THROUGH DOOR FRAME FOR CABLE PATHWAY. FOR ELECTRIFIED HINGE, OR POWER TRANSFER DEVICE.
P
POWER
OPTIONAL HORNPROVIDE 4"sq. BOX FOR FUTURE USE.
1/2" EMT
1/2" EMT4 CONDUCTOR 22AWG
1/2" EMT4 CONDUCTOR 22AWG
4 CONDUCTOR 18AWG; SHIELDED/3 PAIR 22AWG;SHIELDED/2 CONDUCTOR 22AWG;SHIELDED/4 CONDUCTOR 22AWG;FROM BLACKBOARD CONTROLLER AT NEAREST TELCOM ROOM.
DRILL HOLE THROUGH DOOR FRAME FOR CABLE
PATHWAY. FOR ELECTRIFIED HINGE, OR
POWER TRANSFER DEVICE.
2 CONDUCTOR 12AWG
2 CONDUCTOR 12AWG
FLOOR
CEILING
ADA
DOOR OPERATOR
HANDICAP PUSH BUTTON BOTH SIDES VERIFY EXACT LOCATION WITH ARCHITECT PRIOR TO INSTALL
CR
DOORPOSITIONSWITCH
J
1-1/4" EMT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE.
4" SQ BOX WITH BLANK FACEPLATE (OPPOSITE SIDE OF DOOR FROM CARD READER)
DOORPOSITIONSWITCH
DRILL HOLE THROUGH DOOR FRAME FOR CABLE PATHWAY. FOR ELECTRIFIED HINGE, OR POWER TRANSFER DEVICE.
P
POWER
OPTIONAL HORNPROVIDE 4"sq. BOX FOR FUTURE USE.
1/2" EMT
4 CONDUCTOR 18AWG; SHIELDED/3 PAIR 22AWG;SHIELDED/2 CONDUCTOR 22AWG;SHIELDED/4 CONDUCTOR 22AWG;4 CONDUCTOR 22AWG;FROM BLACKBOARD CONTROLLER AT NEAREST TELCOM ROOM.
3/4" EMT3 PAIR 22AWG;4 CONDUCTOR 22AWG
1/2" EMT4 CONDUCTOR 22AWG
1/2" EMT4 CONDUCTOR 22AWG
DRILL HOLE THROUGH DOOR FRAME FOR CABLE PATHWAY. FOR FUTURE ELECTRIFIED HINGE, OR
POWER TRANSFER DEVICE.
2 CONDUCTOR 12AWG
2 CONDUCTOR 12AWG
1/2" EMT4 CONDUCTOR 22AWG
1/2" EMT4 CONDUCTOR 18AWG;4 CONDUCTOR 22AWG
FLOOR
CEILING
CR
DOORPOSITIONSWITCH
J
1" EMT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE.
4" SQ BOX FOR CARD READER.
4" SQ BOX WITH BLANK FACEPLATE (OPPOSITE SIDE OF DOOR FROM CARD READER)
DRILL HOLE THROUGH DOOR FRAME FOR CABLE PATHWAY. FOR ELECTRIC STRIKE.
1/2" EMT3 PAIR 22AWG
1/2" EMT4 CONDUCTOR 22AWG
4 CONDUCTOR 18AWG; SHIELDED/3 PAIR 22AWG;SHIELDED/2 CONDUCTOR 22AWG;SHIELDED/4 CONDUCTOR 22AWG;FROM BLACKBOARD CONTROLLER AT NEAREST TELCOM ROOM.
P
2 CONDUCTOR 12AWG
POWER
1/2" EMT4 CONDUCTOR
22AWG
1/2" EMT
OPTIONAL HORNPROVIDE 4"sq. BOX FOR FUTURE USE.
FLOOR
CEILING
CR
DOORPOSITIONSWITCH
J
1-1/4" EMT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE.
4" SQ BOX FOR CARD READER.
4" SQ BOX WITH BLANK FACEPLATE (OPPOSITE SIDE OF DOOR FROM CARD READER)
DRILL HOLE THROUGH DOOR FRAME FOR CABLE PATHWAY. FOR ELECTRIC STRIKE.
1/2" EMT4 CONDUCTOR 22AWG
4 CONDUCTOR 18AWG; SHIELDED/3 PAIR 22AWG;SHIELDED/2 CONDUCTOR 22AWG;SHIELDED/4 CONDUCTOR 22AWG;FROM BLACKBOARD CONTROLLER AT NEAREST TELCOM ROOM.
P
2 CONDUCTOR 12AWG
POWER
1/2" EMT4 CONDUCTOR
22AWG
1/2" EMT
OPTIONAL HORNPROVIDE 4"sq. BOX FOR FUTURE USE.
DOOR OPERATOR
1/2" EMT4 CONDUCTOR 18AWG; 4 CONDUCTOR 22AWG
ADA
HANDICAP PUSH BUTTON BOTH SIDES VERIFY EXACT LOCATION WITH ARCHITECT PRIOR TO INSTALL
3/4" EMT3 PAIR 22AWG;4 CONDUCTOR 22AWG
EXIT EXIT
PB IC
CEILING
FLOOR
EQ.
EQ.
DOOR
EQ.
12"
48"UON
(BACKSPLASH)
COUNTER
2" ABOVE BACKSPLASH(COORDINATE WITH ARCH)
18"
80"MIN
FIRE ALARM NOTIFIER(STROBE/HORN/SPEAKER)
NOTES:
1. HEIGHTS SHOWN ARE TYPICAL TO CENTER OF BACKBOX / DEVICE UNLESS NOTED OTHERWISE.2. DEVICES ABOVE DOORS SHALL BE CENTERED BETWEEN TOP OF DOOR TRIM AND CEILING LINE.3. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE.4. NOT ALL DEVICES SHOWN ARE USED IN THIS PROJECT.
96"MAX
6"MIN
LIGHT SWITCH (OR OCCUPANCY SENSOR/SWITCH)
PUSHBUTTON (DOOR ACTUATOR)
WALL PHONE JACK
INTERCOM SWITCH
18"
4" MAX
VOICE/DATA OUTLET
POWER OUTLET
Jx
4" MAX
AUDIO-VISUAL INPUT JACK
Jx
AUDIO-VISUAL CONTROL KEYPAD
CR
SECURITY CARD READER
80"MIN
CLOCK/SPEAKER
96"MAX
6"MIN
C S
8'-6"MAX
39"UON
FLOOR
CEILING
DOOR OPERATOR
DS DS
JUNCTION BOX
POWER SUPPLY
ADAADACR
KEYED NOTES1. 4 CONDUCTOR 18AWG2. 3 PAIR 22AWG3. 2 CONDUCTOR 22AWG4. 4 CONDUCTOR 22AWG5. 2 CONDUCTOR 12AWG6. BLACKBOARD DOOR CONTROLLER WITH
ENCLOSURE7. APPROVED POWER SUPPLY8. APPROVED JUNCTION BOX9. APPROVED ADA COMPLIANT SWING
OPERATOR10. APPROVED DOOR POSITION SWITCH11. APPROVED HC OPERATOR BUTTON12. BLACKBOARD CARD READER 13. APPROVED POWER TRANSFER14. APPROVED EXIT DEVICE WITH REQUIRED
TRIM15. APPROVED DOOR CLOSER16. OPTIONAL HORN. PROVIDE 4"sq. BOX
FOR FUTURE USE.17. 1, 120 VAC. CONNECT TO EMERGENCY
POWERED CIRCUIT WHERE AVAILABLE.
42
5 5
44
17 1 4
4
17
9
10 15
14
1313
12 11 11
7
8INSIDEOUTSIDE
CONTROLLER
617
INSTALL CONTROLLER IN LOCAL TELCOM ROOM
INTERNET CONNECTION
HORN
16
PLENUM RATED CONTROL CABLES4 CONDUCTOR 18AWG; SHIELDED/3 PAIR 22AWG;SHIELDED/2 CONDUCTOR 22AWG;SHIELDED/4 CONDUCTOR 22AWG;4 CONDUCTOR 22AWG;
PROVIDE BY DIVISION 27 AND INSTALLED BY DIVISION 27
PROVIDED BY NMSU ANDINSTALLED BY DIVISION 25
PROVIDED BY NMSU ANDINSTALLED BY DIVISION 26
PROVIDED BY DIVISION 25 ANDINSTALLED BY DIVISION 25
PROVIDED BY NMSU ANDINSTALLED BY DIVISION 25 PROVIDED BY NMSU AND
INSTALLED BY DIVISION 25
IRRIGATION
SERIAL CABLE
CAT 6
PROVIDED BY CONTRACTOR
ONICON SYSTEM-10CHW BTU METER
BACNET IP
MAIN ELECTRIC METERMODBUS TCP
MECHANICAL SYSTEMSELECTRIC SUB-METER
MODBUS TCP
LIGHTING SYSTEMSELECTRIC SUB-METER
MODBUS TCP
METRON FARNIERSPECTRUM (AMR)
DOMESTIC WATER METER
CADILLAC CMAGCONDENSATE METER
MODBUS RTU
*RED-DESIGNATES NMSUSUPPLIED METERS AND
COMMUNICATION GATEWAYS
AMRGATEWAY
PROTONODEGATEWAY
CAT-5/6ETHERNET CABLE
CAT-5/6ETHERNET CABLE
CAT-5/6ETHERNET CABLE
CAT-5/6ETHERNET CABLE
CAT-5/6ETHERNET CABLE
NETWORKSWITCH
CAT-5/6ETHERNET CABLE
QTY (2) RS-485SERIAL CABLES(BELDEN 88723)
MODBUS RTU TO BAC NET IPCOMMUNICATION GATEWAY
*RED
*RED *RED
*RED
*RED
EN
JAM N E. BOSSE
19418
GI N
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
As indicated
T-501
NEW ARTBUILDINGNMSU LAS CRUCES, NM
TECHNOLOGY DETAILS
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB/SPO
CSK/JEB/SDR
SCALE: NO SCALED5
SECURITY ALARM SYSTEM:DOOR SWITCHES
SCALE: NO SCALEA4
DOOR ROUGH-IN: CONTROLLEDACCESS ENTRY PAIRED DOORS - DETAIL D
SCALE: NO SCALEB4
DOOR ROUGH-IN: ADA CONTROLLEDACCESS ENTRY PAIRED DOORS - DETAIL B
SCALE: NO SCALEA5
DOOR ROUGH-IN: CONTROLLEDACCESS ENTRY - DETAIL C
SCALE: NO SCALEB5
DOOR ROUGH-IN: ADA CONTROLLEDACCESS ENTRY - DETAIL A
SCALE: NO SCALEA1 ELECTRICAL COMPONENT MOUNTING HEIGHTS (TYPICAL)
SCALE: NO SCALEB2 DOOR ROUGH-IN: WIRE PATHWAY DIAGRAM
ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND
INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS
AND TESTING OF ALL NETWORK CABLING.
SCALE: NO SCALED1 DATA METERING DETAIL
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.04 17:24:54-07'00'
J-BOX #7 TEL CONDUIT #1 TR1-ER
TEL CONDUIT #2 TR1-ER
TEL CONDUIT #3 TR1-TR2
TEL CONDUIT #1 TR1-ER
TEL CONDUIT #2 TR1-ER
TEL CONDUIT #3 TR1-TR2
NOTE: COORDINATE WITH NMSU-ICT FOR LABELING SCHEME
U-089-1-202A
CABLE #ORIGIN (TR NAME)DESTINATION (OUTLET NAME)
CABLE TYPE: C = COPPER F = FIBER CX = COAX CABLE U = UTP
LABEL WITHIN 6"OF CABLE BREAKOUT
NOTE: COORDINATE WITH NMSU-ICT FOR LABELING SCHEME
END VIEWSECTION A
PLAN VIEW
8" SUMP
34"
6"
SPRING ASSISTED GALVANIZED DIAMONDPLATE COVER W/ LOCKING LATCH
4-3/4" DIA. RNDKNOCKOUTS 4 PER SIDE
1" DIA. GROUND ROD KNOCKOUTS 2 PLACES ON FLOOR (OPTIONAL)
GALVANIZED PULLING IRON 2 EACH END, 2 ENDS
4-3/4" DIA. RND KNOCKOUTS4 PER SIDE
(4)- 5/8" DIA. LIFTING INSERTS
2'-0"ALL AROUND
PROVIDECOPPER #6 TO ALL METALLIC PARTS
24" DRAIN
COMPACTED TO 95% RELATIVE DENSITY. FREE FROM LARGE ROCKS AND DEBRIS.(COMPACTED IN 6" LAYERS).
SPLICE ENCLOSURE BOND AS REQUIRED
8" GRAVEL BED
CONDUIT DUCTBANK
A ACOMMUNICATIONS
HH-T12
HANDHOLE IDENTIFICATION.
BOTTOM FEED.SIDE-MOUNT HOUSING ASSEMBLY FOR POWER.ACCEPTS (1)3/4" CONDUIT.WIREMOLD CAT #575CHA (TYPICAL OF 2)
TOP VIEW(COVER) ISOMETRIC VIEW
SIDE VIEW (SIDE MOUNT
HOUSING ONLY)
SIDE VIEW(ALL BOTTOM HOUSINGS)
FLANGED COVER FOR CARPET FLOOR
9 1/4"
16 3/4"BOTTOM FEED.CENTER-MOUNT HOUSING ASSEMBLY FOR TELECOM & A/V.ACCEPTS (1)1-1/4" CONDUIT.WIREMOLD CAT #1125CHA(TYPICAL OF 3)
2700V INSULATORS
STAND-OFFS
COPPER BUS BAR.
BOLT CONNECTION WITHCOMPRESSION SPADE LUGFITTING (TYPICAL)PROVIDE BONDING TO
CONNECTIONS TOCABLE TRAY SYSTEMSAND EQUIPMENT RACKS(TYPICAL)
STRUCTURE
THREADED ROD
UNISTRUT SUPPORTS
CABLE TRAY -VOICE DATA CABLING ONLY
J-HOOKS FOR NON VOICE / DATA CABLING MOUNTED TO THREADED ROD.
#6 AWG BOND. BOND ALL ENDS OF CONDUIT TO CABLE TRAYS AS PER MANUFACTURER RECOMMENDATIONS.
EMT CONDUIT SLEEVES PATHWAYS (REFER TO PLANS)
CABLE TRAY
THREADED DROP ROD
CABLE TRAY
CABLE RUNWAY RADIUS DROP
NOTE: PROVIDE CABLE TRAY LINER WHEREVER CABLE TRAY IS IN EXPOSED CEILING. VERIFY COLOR WITH OWNERAND ARCHITECT BEFORE ANY COMMENCEMENT OF WORK
SLACK LOOP
COMMUNICATIONCABLING
WALL
CONDUIT THROUGH WALL TO OUTLET
4-11/16" SQUARE,2-1/8" DEEP JUNCTIONBOX WITH 1-DEVICERAISED MUD RING
COVER PLATE
SLACK LOOP
COMMUNICATIONCABLING
WALL
CONDUIT THROUGH WALL TO OUTLET
4-11/16" SQUARE,2-1/8" DEEP JUNCTIONBOX WITH 1-DEVICERAISED MUD RING
COVER PLATE
J-HOOK
FINISHED GRADE
12"
36" MIN.
4"
3"
3" 3" 3"3"
4" PVC SCHEDULE 40 CONDUIT, QTY AS NOTED ON PLANS. PROVIDE PULLSTRINGS IN EACH.
NOTE:REFER TO SHEETS TS102 AND T-401 FOR ADDITIONAL INFORMATION REGARDING TELECOMMUNICATIONS CABLING.
FINISHED GRADE OR SURFACE REPAIR SURFACES TO MATCH EXISTING
COMPACTED TO 95% RELATIVE DENSITY. FREE FROM LARGE ROCKS AND DEBRIS.(COMPACTED IN 6" LAYERS).
UNDISTURBED EARTH
WARNING TAPE
CONCRETE DUCTBANK.
1 # 4/0 BARE COPPER
8" SAND BED.
BOTTOM FEED.SIDE-MOUNT HOUSING ASSEMBLY FOR POWER.ACCEPTS (1)3/4" CONDUIT.WIREMOLD CAT #575CHA (TYPICAL OF 2)
TOP VIEW(COVER) ISOMETRIC VIEW
SIDE VIEW (SIDE MOUNT
HOUSING ONLY)
SIDE VIEW(ALL BOTTOM HOUSINGS)
FLANGED COVER FOR CARPET FLOOR
7 1/4"
16 3/4"BOTTOM FEED.CENTER-MOUNT HOUSING ASSEMBLY FOR TELECOM & A/V.ACCEPTS (1)1-1/4" CONDUIT.WIREMOLD CAT #1125CHA(TYPICAL OF 1)
2 PORT DATA W/ 3 SLOT A/V LOCATION FOR EXTRON MAAP PLATES. WIREMOLD CAT #6MAAP2A
POWER DUPLEX 20AMP WIREMOLD CAT #68REC
(BOTH SIDES)
PROVIDE BLANK CENTER PLATE WIREMOLD CAT #6B WHEN DEVICES NOT IN USE.
1" CONDUIT & CONNECTOR.
4-11/16" SQUARE, 2-1/8" DEEPJUNCTION BOX WITH KNOCKOUTS.
4-11/16" SQUARE1-DEVICE RAISEDMUD RING.
CABLE LENGTH 12"COIL IN BACK BOX
MODULAR JACK ORBLANK AS NEEDED
FACEPLATE
CATEGORY CABLES(QTY AS INDICATEDON PLANS)
181
123-A
01-20:01
BLANK
TELECOM ROOM #
SERVICING CLOSET
PORT LABEL
OUTLET ID
OUTLET IDOUTLET ROOM #
01-20:02
01-20:03
PORT LOCATIONRACK UNIT #
EQPT. RACK ID #
12 3/4"
13 13/16"
17 5/16" 15 3/8"
6 1/8"
4 11/16"
4 13/16"
11 7/8"
A/V
POWER
DATA
RELOCATABLEDIVIDER
TUNNELEFB810-TUN
MODULE
A: 2" K.O.B: 1-1/4" K.O.C: 1" K.O.
B A,CBB
C
C
C
C
C
C
C
C
A,C
BOTTOM FEED.SIDE-MOUNT HOUSING ASSEMBLY FOR POWER.ACCEPTS (1)3/4" CONDUIT.WIREMOLD CAT #575CHA
TOP VIEW(COVER) ISOMETRIC VIEW
SIDE VIEW (SIDE MOUNT
HOUSING ONLY)
SIDE VIEW(ALL BOTTOM HOUSINGS)
FLANGED COVER FOR CARPET FLOOR
9 1/4"
16 3/4"
BOTTOM FEED.CENTER-MOUNT HOUSING ASSEMBLY FOR TELECOM.ACCEPTS (1)1-1/4" CONDUIT.WIREMOLD CAT #1125CHA
MOUNTING PLATE FOR STANDARD DUPLEX RECEPTACLE.
CONTROLLED POWER DUPLEX 20AMP
WIREMOLD CAT #68REC-CTRL(BOTH SIDES)
MOUNTING PLATE FOR DATA.PROVIDE VOLTAGE BARRIER BETWEEN DEVICES.
CO
NT
RO
LLE
D
CO
NT
RO
LLE
D
WIREMOLD 8" POKE-THRU #8STC (INCLUDES, QTY. (1) 1/2-GANG 3/4" CONDUIT HOUSING ASSEMBLY #575CHA, QTY. (1) 8" DIVIDER #8DIV, AND QTY. (1) BOTTOM HOUSING ASSEMBLY #5BLH).
PROVIDE THE FOLLOWING FOR EACH BOX:QTY. (1) BLANK HOUSING COVER #1BLHQTY. (1) BOTTOM HOUSING (DATA) #1125CHAQTY. (1) BOTTOM HOUSING (POWER) #175CHAQTY. (2) CONTROLLED RECEPTACLES #68REC-CTRLQTY. (1) DEVICE MOUNTING PLATE FOR DATA #8ATC6AQTY. (2) STANDARD DUPLEX DEVICE MOUNTING PLATE #8DPQTY. (1) FINISHING COVER ASSEMBLY AS FOLLOWS:• PROVIDE (1) FINISHING COVER ASSEMBLY AS FOLLOWS:• FOR CARPETED OR VINYL TILE FLOORING, PROVIDE SURFACE STYLE
COVER ASSEMBLY, CATALOG # 8CTC2xx.• FOR BARE/POLISHED CONCRETE OR TERRAZZO FLOORING, PROVIDE
FLUSH STYLE COVER ASSEMBLY, CATALOG # 8CT2xx. PROVIDE BARE CONCRETE/TERRAZZO TRIM RING, PROVIDE TILE SHIMS AS REQUIRED, CATALOG #8TS.
• VERIFY STYLE AND COLOR "xx" (NICKEL, BLACK, GRAY, BRASS OR BRONZE) WITH ARCHITECT PRIOR TO PURCHASE ORDER.
BOTTOM FEED.CENTER-MOUNT HOUSING ASSEMBLY FOR POWER.ACCEPTS (1)3/4" CONDUIT.WIREMOLD CAT #175CHA
EN
JAM N E. BOSSE
19418
GI N
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
As indicated
T-502
NEW ARTBUILDINGNMSU LAS CRUCES, NM
TECHNOLOGY DETAILS
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB/SPO
CSK/JEB/SDR
SCALE: NO SCALEC6
TELECOMMUNICATIONS CONDUITIDENTIFICATION SCHEME
SCALE: NO SCALED6 TYPICAL CABLE IDENTIFICATION SCHEME
SCALE: NO SCALEE5 TYPICAL HANDHOLE DETAILS
SCALE: NO SCALEB2
WIREMOLD EVOLUTION POKE THROUGHFLOOR BOX DETAILS (8ATCNK)
SCALE: NO SCALEB6
TELECOMMUNICATIONSGROUNDING BUS BAR (TYPICAL)
SCALE: NO SCALEE4 CABLE TRAY DETAILSCALE: NO SCALEE2
CABLE TRAY / CONDUIT SLEEVEBONDING AND GROUNDING
SCALE: NO SCALEE1
TELECOMMUNICATIONSCABLE TRAY RUNWAY RADIUS DROP
SCALE: NO SCALEA6 TELECOMMUNICATIONS OUTLET CONDUIT ROUTING
SCALE: NO SCALED3 TELECOM CONDUIT DUCTBANK SECTION
ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND
INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS
AND TESTING OF ALL NETWORK CABLING.
SCALE: NO SCALEB1
WIREMOLD EVOLUTION POKE THROUGHFLOOR BOX DETAILS (6ATC)
SCALE: NO SCALED1
TELECOMMUNICATIONSOUTLET BOX DETAILS (TYPICAL)
SCALE: NO SCALED2
STANDARD TELECOM OUTLETIDENTIFICATION SCHEME (TYPICAL)
SCALE: NO SCALEA2 WIREMOLD EFB8-OG
REFER TO NMSU ICT STANDARDS FOR TELECOMMUNICATIONS LABLING
STANDARD PER TIA-606
SCALE: NO SCALEA1
WIREMOLD EVOLUTION POKE THROUGHFLOOR BOX DETAILS (8STC)
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.04 17:25:04-07'00'
1/16" STRANDED AIRCRAFT CABLE.LOUDSPEAKER ASSEMBLY W/TILEBRIDGE APPROX. 10LBS
LOCKING WINGS
SUSPENDED CEILINGCEILING RECESSED LOUDSPEAKER
REFER TO AUDIO-VISUALPATHWAY DIAGRAMS
SPEAKER WIRE PULL BOX(REFER TO PLANS)
LAY-IN CEILING T-GRID SYSTEMWHERE APPLICABLE
DECK
A/V & DATA EMT CONDUITS PERROOM CONDUIT PATHWAY DIAGRAMS
DOUBLE-GANG DATA WORKBOX(DOWNWARD FACING)
SINGLE-GANGELECTRICAL WORKBOX WITH
DUPLEX POWER RECEPTACLE(DOWNWARD FACING).
SCREENWALL
VIDEO PROJECTOR (O.F.O.I.)
1.5" NPT SUSPENSION COLUMN(O.F.O.I.)
DECK
!!! CRITICAL DISTANCE !!!
COORDINATE WITH OWNER AND ARCHITECT
P TO
UNISTRUT GRID MOUNTED TO DECK. CONTRACTOR TO FURNISH AND INSTALL
1.5" NPT THREADED POLE. CONTRACTOR PROVIDED.
VIDEO PROJECTORMOUNTING BRACKET (O.F.O.I.)
1.5" NPT THREADED PIPE COUPLER WITH SET SCREWS.CHIEF CMA270 OR EQUAL. CONTRACTOR PROVIDED.
1.5" NPT CEILING MOUNTED PLATE.CHIEF CMA110 OR EQUAL. CONTRACTOR PROVIDED.
OUTLINE OF SUPPORT PIPE ABOVE PROJECTOR
PROJECTION SCREEN (O.F.C.I.)
DOUBLE-GANG JUNCTION BOX WITH TELECOM OUTLET
DUPLEX POWERRECEPTACLE
VIDEO PROJECTOR(O.F.O.I.)
!!! CRITICAL DISTANCE !!!
COORDINATE WITH OWNER AND ARCHITECT
32"
DATA
60" O.C.AFF
O.U.N.
48"
NOTES:1. SPAN BACKING SEGMENTS BETWEEN STUDS.2. VERIFY LOCATIONS OF BACKING MATERIAL WITH
ARCHITECT/OWNER PRIOR TO ROUGH-IN3. FASTEN MATERIAL FLUSH TO FACE OF STUDS READY TO
ACCEPT FINISH WALLBOARD.4. TELECOM OUTLET (T.O.) FURNISHED WITH QTY(2) CAT6 DATA
DROPS. NETWORK CABLING IS O.F.C.I.
3/4" PLYWOOD BLOCKINGSPAN BETWEEN (3) STUDS
PWR
T-503C4
6 11
/16"
6 3/
32"
4 7/
32"
6"
3 15
/16"
3 13
/16"
5 3/16"
VOLTAGE BARRIER INSIDE BOX.
MODEL # TVBS505 AS MFD. BY ARLINGTON INDUSTRIES.
PROVIDE SUPPORT CABLE TAIL LENGTH SUFFICIENT TO REACH TO 8FT AFF.
AV CONTRACTOR WILL CUT SUPPORT CABLE TO CORRECT HANGING LENGTH AND
PROVIDE CONNECTION TO LOUDSPEAKER ASSEMBLY. PRIMARY & SECONDARY SUPPORT CABLES
USE 1/16" DIA. STRANDED AIRCRAFT CABLEWITH MIN. 180LB LOAD LIMIT AND BREAKINGLOAD LIMIT OF 900LB (GRIPPLE OR EQUAL)
EYE-BOLT OR SIMILAR ANCHOR TOUNDERSIDE OF DECK SUFFICIENTTO SUPPORT WEIGHT OF 10LBLOUDSPEAKER PLUS HARDWARE WITHMIN. SAFETY FACTOR OF 5X.
SPEAKER WIRE
SPEAKER WIRE PULL BOX(REFER TO PLANS)
PRIMARY SUPPORT CABLE SECURE TOLOUDSPEAKER HANGING BRACKET WITHCARIBINER PROVIDED WITH LOUDSPEAKER.
SECONDARY SUPPORT CABLE SECURED TOLOUDSPEAKER HANGING BRACKET W/#10BOLT BY AV CONTRACTOR.
TERMINALWEATHER BOOT
SIDE VIEW
WIRE CONNECTOR
HANGING BRACKET
PENDANT LOUDSPEAKER(TYPICAL)
SIDE
BOTTOM TOP
STRUCTURAL DECK
DECK
A/V & DATA EMT CONDUITS PERROOM CONDUIT PATHWAY DIAGRAMS
DOUBLE-GANG DATA WORKBOX
(DOWNWARD FACING)
SINGLE-GANGELECTRICAL WORKBOX WITH
DUPLEX POWER RECEPTACLE(DOWNWARD FACING).
SCREENWALL
VIDEO PROJECTOR (O.F.O.I.)
1.5" NPT SUSPENSION COLUMN(O.F.O.I.)
DECK
!!! CRITICAL DISTANCE !!!
COORDINATE WITH OWNER AND ARCHITECT
PTO
UNISTRUT GRID MOUNTED TO DECK. CONTRACTOR TO FURNISH AND INSTALL
1.5" NPT THREADED POLE. CONTRACTOR PROVIDED
VIDEO PROJECTORMOUNTING BRACKET (O.F.O.I.)
1.5" NPT CEILING MOUNTED PLATE.CHIEF CMA110 OR EQUAL. CONTRACTOR PROVIDED.
1.5" NPT THREADED PIPE COUPLERWITH SET SCREWS. CHIEF CMA270OR EQUAL. CONTRACTOR PROVIDED.
EN
JAM N E. BOSSE
19418
GI N
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
As indicated
T-503
NEW ARTBUILDINGNMSU LAS CRUCES, NM
AUDIO-VISUAL DETAILS
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB/SPO
CSK/JEB/SDR
SCALE: NO SCALEB6 RECESSED CEILING LOUDSPEAKER
SCALE: NO SCALEA2
CEILING MOUNTED PROJECTOR DETAIL FOR SUSPENDED LAY-IN CEILING
SCALE: NO SCALEB2 PROJECTION SYSTEM PLAN
SCALE: NO SCALEC5
ROUGH-IN AND STRUCTUAL BACKING FOR WALLMOUNTED DIGITAL SIGNAGE DISPLAY
ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND
INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS
AND TESTING OF ALL NETWORK CABLING.
SCALE: NO SCALEC4
MULTISERVICE OUTLET BOX FORWALL MOUNTED DIGITAL SIGNAGE
SCALE: NO SCALEA6 PENDANT MOUNTED LOUDSPEAKERSCALE: NO SCALEA1
CEILING MOUNTED PROJECTOR DETAILFOR OPEN CEILING
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.04 17:25:14-07'00'
TELECOM OUTLET (VOICE/DATA)
AUDIOVISUAL JUNCTION/PULL BOX
POWER OUTLETS W/ RECEPTACLE
CONDUIT STUB
J
TO
S LOUDSPEAKER RECESSED FLUSH IN CEILING
P
A/V PATHWAY DIAGRAMSYMBOLS LEGEND
LAY-INCEILINGWHERE
INDICATED
STRUCTURALDECK
FLOOR
MOTORIZED PROJECTION SCREEN(O.F.C.I.)
P
P
CONDUIT ANDWIRING TO 120V
CONTROL SWITCH IN LECTERN.
S2
CEILING MOUNTED SPEAKERS (OFCI)
S2S2TO REMAINING
SPEAKERS
J
PULL BOX
TO BLDG LAN
COIL SECOND SPEAKER CABLE
(4) DATA CABLE-OFCI(BLUE & WHITE)
(2) SPEAKER CABLES (2X18AWG PLENUM) OFCI
2' SLACK LOOP
(2) DATA CABLE-(BLUE & WHITE)
JJ1LECTERNA/V CONNECTION PANEL
(2) DATA CABLES FOR LAN (IN 1" EMT)(4) DATA CABLES FOR A/V (IN 1" EMT)(2) SPEAKER CABLES IN (3/4") EMT)
J3
VIDEO PROJECTOR(OFOI)
P TO
POWER DUPLEX MOUNTED FLUSH IN CEILING.
T.O. PLATE MOUNTED IN FLUSH IN CEILING.
(2) DATA CABLE(BLUE & WHITE)
TO BLDGLAN
UNISTRUTGRID
LAY-INCEILINGWHERE
INDICATED
STRUCTURALDECK
FLOOR
VIDEO PROJECTOR(OFOI)
MOTORIZED PROJECTION SCREEN(O.F.C.I.)
P
P
P TO
POWER DUPLEX MOUNTED FLUSH IN CEILING.
(1)1/2" FLEX
T.O. PLATE MOUNTED IN FLUSH IN CEILING.
CONDUIT TO 120V CONTROL SWITCH
IN LECTERN
(2) 1" EMTAND
(1) 3/4" EMT
(1) 1" EMT
S2
CEILING MOUNTED SPEAKERS (OFCI)
S2S2TO REMAINING
SPEAKERS
(1) 1" EMT
(1) 3/4" EMT
J
PULL BOX
(1) 1" EMT
DATA
TO CABLE TRAY
J3
JJ1LECTERNA/V CONNECTION PANEL
UNISTRUTGRID
STRUCTURALDECK
FLOOR
VIDEO PROJECTOR(OFOI)
MOTORIZED PROJECTION SCREEN(O.F.C.I.)
P
P
P TO
CONDUIT AND WIRING TO 120V CONTROL
SWITCH IN LECTERN
(4) DATA CABLE-(BLUE & WHITE)
(2) DATA CABLE-(BLUE & WHITE)
2' SLACK LOOP
JJ1LECTERNA/V CONNECTION PANEL
(2) DATA CABLES FOR LAN (IN 1" EMT)(4) DATA CABLES FOR A/V (IN 1" EMT)(2) SPEAKER CABLES IN (3/4") EMT)
S2
PENDANT MOUNTED SPEAKERS (OFCI)
S2S2
(1) 1" EMTJ
PULL BOX
(1) 1" EMT
DATA
J3
J J J
UNISTRUTGRID
STRUCTURALDECK
FLOOR
MOTORIZED PROJECTION SCREEN(O.F.C.I.)
P
P(1)1/2" FLEX
CONDUIT TO 120V CONTROL
SWITCH INLECTERN
(2) 1" EMTAND
(1) 3/4" EMT
S2
PENDANT MOUNTED SPEAKERS (OFCI)
S2S2
(1) 1" EMT
(1) 3/4" EMT
J
PULL BOX
(1) 1" EMT
DATA
J3
JJ1LECTERNA/V CONNECTION PANEL
J J J
(4) DATA CABLE-OFCI(BLUE & WHITE)
2' SLACK LOOP
VIDEO PROJECTOR(OFOI)
P TO
(2) DATA CABLE-(BLUE & WHITE)
UNISTRUTGRID
EN
JAM N E. BOSSE
19418
GI N
EE
R
ON L
E
A
N
SROFES
D
PI
CLI
ENSE
NE
WME X I COB
I
400 Gold Ave SW Studio 1100 Albuquerque, NM 87102 505.243.5454 www.rmkmarch.com
Copyright © RMKM Architecture, P.C. 2017
SHEET TITLE
SHEET NUMBER
PROJECT
MODELED BY
RMKM PROJECT NO.
SCALE
DESIGN PHASE
PROJECT MANAGER
1 100% CONSTRUCTION DOCUMENTS / BID SET 01/05/2018
NO SCALE
T-601
NEW ARTBUILDINGNMSU LAS CRUCES, NM
TECHNOLOGY DIAGRAMS
A01508
Replacement of Dan W. Williams Hall
CONSTRUCTION DOCUMENTS
BEB/SPO
CSK/JEB/SDR
ALL NETWORK CABLING IS CONTRACTOR FURNISHED AND
INSTALLED (CFCI) AND CONTRACTOR IS RESPONSIBLE FOR TERMINATIONS
AND TESTING OF ALL NETWORK CABLING.
SCALE: NO SCALEB2 A/V CABLE RISER DIAGRAM: TYPICAL CLASSROOM
SCALE: NO SCALEA2 A/V PATHWAY DIAGRAM: TYPICAL CLASSROOM
GENERAL SHEET NOTES
SHEET KEYNOTES
1. MOUNT BOX AT 12"-18" ABOVE SUSPENDED CEILING IN PARTITION WALL WITH ACCESS COVER/DEVICE SIDE FACING AWAY FROM WALL. IN LOCATIONS WITHOUT SUSPENDED CEILINGS MOUNT BOX IN PARTIITION WALL AT 12" - 18" BELOW STRUCTURAL DECK. COORDINATE FINAL LOCATION WITH ALL OTHER DISCIPLINES PRIOR TO INSTALLATION.
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL OTHER TRADES.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END WARRANTED SOLUTION FOR THE HORIZONTAL CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.E. ALL COMMUNICATIONS CABLING TO MEET OR EXCEED CAT6 STANDARDS.F. TELECOMMUNICATIONS OUTLETS TO BE MOUNTED AT +18" A.F.F. (BOTTOM OF
BOX) UNLESS OTHERWISE NOTED. FOR EXAMPLE, DEVICES SPECIFIED AT +18" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR POWER RECEPTACLES AND TELECOMMUNICATIONS OUTLETS. DEVICES SPECIFIED AT + 48" A.F.F. SHALL MATCH THE STANDARD MOUNTING HEIGHT FOR LIGHT SWITCHES ETC.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL, THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR PATHWAYS INDICATED ON THIS SHEET. ALL CONDUITS ARE TO BE, AT A MINIMUM, 1” TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL.
H. CABLE TRAY SYSTEMS SHOWN ON THIS SHEET SHALL BE USED FOR VOICE AND DATA CABLING ONLY. ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, SECURITY, HVAC CONTROL, ETC. SHALL BE SUPPORTED BY OTHER MEANS. J-HOOKS ATTACHED TO THE CABLE TRAY SUPPORTS WILL BE PERMITTED. LIKEWISE, ANY CONDUITS PROVIDED FOR VOICE AND DATA CABLING IS NOT TO BE USED BY ANY OTHER SYSTEM, HENCE, SEPARATE CONDUITS MAY NEED TO BE PROVIDED FOR THE SUPPORT OF THESE SYSTEMS.
I. NUMBER ADJACENT TO TELECOMMUNICATIONS OUTLET SYMBOL REPRESENTS NUMBER OF CAT 6 CABLES TO BE INSTALLED AND TERMINATED AT THAT LOCATION. A "B" ADJACENT TO AN OUTLET LOCATION REPRESENTS A ROUGH-IN ONLY LOCATION, PROVIDE BOX, CONDUIT, AND BLANK FACEPLATE.
J. ALL CONDUIT TURNS FOR A/V AND IT CONDUITS SHALL BE "SWEEP" TYPE, NO BEND FITTINGS ARE PERMITTED.
K. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE OR JUNCTION BOX.
L. CONTRACTOR TO VERIFY ALL CABLE COUNTS AND NUMBER OF PATCH PANELS REQUIRED.
M. GROUP DATA OUTLETS TOGETHER WITH POWER OUTLETS (WHERE APPLICABLE). REFER TO "EP" SERIES SHEETS FOR POWER OUTLET LOCATIONS.
N. CONTRACTOR IS PROVIDE AND TERMINATE CABLING FOR THE BLACKBOARD SYSTEM AND T0 “FUTURE” CARD READERS.
O. DURING VOICE/DATA CABLE INSTALLATION, PROPER COORDINATION AND CARE SHALL BE TAKEN TO ENSURE CABLING DOES NOT GET PAINTED, TEXTURED OR OTHERWISE CONTAMINATED. PER MANUFACTURERS INSTALLATION GUIDELINES.
P. ANY ON-GRADE FLOOR BOX APPLICATIONS, CONTRACTOR SHALL INSTALL "WET-RATED" CABLE, AS PER NEC 2014 ARTICLE 100. CONTRACTOR TO TRANSITION FROM "WET-RATED" CABLE TO "PLENUM" RATED CABLE AS PER BICSI GUIDELINES AND INDUSTRY BEST PRACTICES.
SCALE: NO SCALEB1 A/V CABLE RISER DIAGRAM: TYPICAL CLASSROOM WITHOUT CEILING
SCALE: NO SCALEA1 A/V PATHWAY DIAGRAM: TYPICAL CLASSROOM WITHOUT CEILING
NO. ISSUE DATE
Digitally signed by Benjamin E BosseDate: 2018.01.04 17:25:23-07'00'