NLDC Petition regarding inadequate FGMO response
Transcript of NLDC Petition regarding inadequate FGMO response
Annexure-1
Fig.1
Fig.2
49.00
49.40
49.80
50.20
50.60
51.00H
z --
>
Date -->
ER / NEW GRID MAXIMUM AND MINIMUM FREQUENCY JANUARY'2013 ONWARDS
MAXIMUM MINIMUM
0.3
0.5
0.7
0.9
1.1
1.3
De
c-1
2
Ma
r-1
3
Ju
n-1
3
Oc
t-1
3
Jan
-14
Ap
r-1
4
Ju
l-1
4
No
v-1
4
Hz
MONTH -->
ER/NEW GRID FREQUENCY FLUCTUATIONS (MAXIMUM-MINIMUM) JANUARY'2013 ONWARDS
31
Annexure-I
Fig.3
Fig.4
49.80
50.00
50.20
De
c-1
2
Mar-
13
Ju
n-1
3
Oc
t-1
3
Ja
n-1
4
Ap
r-1
4
Ju
l-1
4
No
v-1
4
Hz -
->
MONTH -->
EASTERN REGION / NEW GRID AVERAGE FREQUENCY SCATTER PLOT January'2013 ONWARDS
48.50
49.00
49.50
50.00
50.50
51.00
51.50
52.00
52.50
53.00
Ja
n-9
8
Ju
l-9
8
Ja
n-9
9
Ju
l-9
9
Ja
n-0
0
Ju
l-0
0
Ja
n-0
1
Ju
l-0
1
Ja
n-0
2
Ju
l-0
2
Ja
n-0
3
Ju
l-0
3
Ja
n-0
4
Ju
l-0
4
Ja
n-0
5
Ju
l-0
5
Ja
n-0
6
Ju
l-0
6
Jan
-07
Ju
l-0
7
Ja
n-0
8
Ju
l-0
8
Ja
n-0
9
Ju
l-0
9
Ja
n-1
0
Ju
l-1
0
Ja
n-1
1
Ju
l-1
1
Ja
n-1
2
Ju
l-1
2
Ja
n-1
3
Ju
l-1
3
Ja
n-1
4
Ju
l-1
4
Hz -
->
MONTH -->
EASTERN REGION / NEW GRID AVERAGE FREQUENCY SCATTER PLOT JANUARY'98 ONWARDS
32
Annexure-I
Fig.5
Fig.6
0.3
0.8
1.3
1.8
2.3
2.8
3.3
3.8
4.3
4.8
5.3
5.8J
an
-98
Ju
l-9
8
Jan
-99
Ju
l-9
9
Jan
-00
Ju
l-0
0
Jan
-01
Ju
l-0
1
Jan
-02
Ju
l-0
2
Jan
-03
Ju
l-0
3
Jan
-04
Ju
l-0
4
Jan
-05
Ju
l-0
5
Jan
-06
Ju
l-0
6
Jan
-07
Ju
l-0
7
Jan
-08
Ju
l-0
8
Jan
-09
Ju
l-0
9
Jan
-10
Ju
l-1
0
Jan
-11
Ju
l-1
1
Jan
-12
Ju
l-1
2
Jan
-13
Ju
l-1
3
Jan
-14
Ju
l-1
4
Hz
MONTH -->
ER/NEW GRID FREQUENCY FLUCTUATIONS (MAXIMUM-MINIMUM) JANUARY'98 ONWARDS
47
48
49
50
51
52
53
54
Hz -
->
Date -->
ER / NEW GRID MAXIMUM AND MINIMUM FREQUENCY JANUARY'98 ONWARDS
MAXIMUM MINIMUM
33
Annexure-I
Fig.7
Fig.8
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4D
ec
-12
Ju
n-1
3
Dec
-13
Ju
n-1
4
Dec
-14
HZ
--->
DAYS --->
SOUTHERN REGION FREQUENCY FLUCTUATIONS (MAXIMUM-MINIMUM) SCATTER PLOT
January'2013 ONWARDS
48.5
49.0
49.5
50.0
50.5
51.0
Dec-1
2
Ju
n-1
3
De
c-1
3
Ju
n-1
4
Dec-1
4
FR
EQ
UE
NC
Y I
N H
Z -
-->
DAY ---->
MAXIMUM, MINIMUM & AVERAGE FREQUENCY PLOT FROM January'2013 ONWARDS(Southern Region)
MAXIMUM MINIMUM AVERAGE
34
Annexure-I
Fig.9
Fig.10
48.5
49.0
49.5
50.0
50.5
51.0D
ec-1
2
Ju
n-1
3
Dec-1
3
Ju
n-1
4
Dec-1
4
FR
EQ
UE
NC
Y I
N H
Z -
-->
DAY ---->
MAXIMUM, MINIMUM FREQUENCY PLOT FROM January'2013 ONWARDS(Southern Region)
MAXIMUM MINIMUM
0.2
0.7
1.2
1.7
2.2
2.7
3.2
Ap
r-01
Oct-
01
Ap
r-02
Oct-
02
Ap
r-03
Oct-
03
Ap
r-04
Oct-
04
Ap
r-05
Oct-
05
Ap
r-06
Oct-
06
Ap
r-07
Oct-
07
Ap
r-08
Oct-
08
Ap
r-09
Oct-
09
Ap
r-10
Oct-
10
Ap
r-11
Oct-
11
Ap
r-12
Oct-
12
Ap
r-13
Oct-
13
Ap
r-14
Oct-
14
HZ
--->
DAYS --->
SOUTHERN REGION FREQUENCY FLUCTUATIONS (MAXIMUM-MINIMUM) SCATTER PLOT
APRIL-2001 ONWARDS
35
Annexure-I
Fig.11
Fig.12
47.5
48.0
48.5
49.0
49.5
50.0
50.5
51.0
51.5
Ap
r-01
Oct-
01
Ap
r-02
Oct-
02
Ap
r-03
Oct-
03
Ap
r-04
Oct-
04
Ap
r-05
Oct-
05
Ap
r-06
Oct-
06
Ap
r-07
Oct-
07
Ap
r-08
Oct-
08
Ap
r-09
Oct-
09
Ap
r-10
Oct-
10
Ap
r-11
Oct-
11
Ap
r-12
Oct-
12
Ap
r-13
Oct-
13
Ap
r-14
Oct-
14
Ap
r-15
FR
EQ
UE
NC
Y I
N H
Z -
-->
DAY ---->
MAXIMUM, MINIMUM & AVERAGE FREQUENCY PLOT FROM APRIL-01 ONWARDS(Southern Region)
MAXIMUM MINIMUM AVERAGE
47.5
48.0
48.5
49.0
49.5
50.0
50.5
51.0
51.5
Ap
r-01
Oct-
01
Ap
r-02
Oct-
02
Ap
r-03
Oct-
03
Ap
r-04
Oct-
04
Ap
r-05
Oct-
05
Ap
r-06
Oct-
06
Ap
r-07
Oct-
07
Ap
r-08
Oct-
08
Ap
r-09
Oct-
09
Ap
r-10
Oct-
10
Ap
r-11
Oct-
11
Ap
r-12
Oct-
12
Ap
r-13
Oct-
13
Ap
r-14
Oct-
14
Ap
r-15
FR
EQ
UE
NC
Y I
N H
Z -
-->
DAY ---->
MAXIMUM, MINIMUM FREQUENCY PLOT FROM APRIL-01 ONWARDS(Southern Region)
MAXIMUM MINIMUM
36
Annexure-I
Fig.13
49.70
49.80
49.90
50.00
50.10
50.20
50.300
:00
:00
1:0
0:0
0
2:0
0:0
0
3:0
0:0
0
4:0
0:0
0
5:0
0:0
0
6:0
0:0
0
7:0
0:0
0
8:0
0:0
0
9:0
0:0
0
10
:00
:00
11
:00
:00
12
:00
:00
13
:00
:00
14
:00
:00
15
:00
:08
16
:00
:00
17
:00
:00
18
:00
:00
19
:00
:00
20
:00
:00
21
:00
:00
22
:00
:00
23
:00
:00
24 hour Frequency Plot of a normal day(20th Jan'15)
37
Power System Control and Stability
Power Plant Testing
Process Control
Engineering Management
Nuclear Power Safety
Solvina International Annexure-2
38
Voltage stability research 1992-1995
Consultant since 1996
Focus: Dynamic behavior of Power systems
Introduction
0
2
Niclas Krantz Managing Director
Lic. Eng. Power Systems [email protected]
+46 31 709 6304
Annexure-2
39
1. Solvina Introduction
2. Methodology adopted for testing
3. Brief outcome of the testing of the units andcomments on FGMO/RGMO
4. International practices and regulatory provisionsregarding periodic testing of frequency control
5. Suggestions for Control strategies and RegulatoryInterventions reg. testing in India
Presentation outline Annexure-2
40
Holistic and dynamic approach to Process, Power and Control engineering is our speciality.
Core business Annexure-2
41
Nuclear Power
Power Plants (Thermal, Hydro)
Cogeneration/Captive plants
Pulp Mills
Steel Mills
Chemical sites
Electric grid utilities
Customers Annexure-2
42
”Generators are the pillars of power grid stability…”
Grid Stability
Dr. Prabha Kundur
To ensure power grid and power plant stability Solvina carry out and optimize:
Frequency control, Governors
Load control
Voltage control, AVR
Power System Stabilizers, PSS
Plant operation capabilities
Load rejection into House Load operation
System simulation studies
Annexure-2
43
During 2014, Solvina International has carried our test of primary response of five units in India, under a contract with Power Grid /POSOCO.
Reports for each test is under way and will be submitted in a final report shortly.
(Observe that this is a preliminary presentation and should not be taken in detail for implementation straight off.
Background to primary response testingAnnexure-2
44
Test method /SSPS function Annexure-2
45
By breaking up the control loop for frequency control, any test signal may be injected to study the response of the machine while still synchronized to the main grid (online testing!)
Tests may be carried out
- ”open loop”, with a predefined signal
- ”closed loop”, with a simulated signal depending on the unit output
Test principle Annexure-2
46
What is desired to know in normal operation in the large grid is the
- Magnitude of response (MW/Hz)
- Speed of response (Time constant)
Injecting a frequency step (open loop) gives both these variables in a very clear way.
FGMO ”primary response” Annexure-2
47
Example Dadri II, 100% load
-0.05, +0.13 Hz steps
Annexure-2
48
What is desired to know in Islanded conditions is the ability of the unit to respond to load changes and how it can maintain the stability of the system frequency following different contingencies.
Full scale tests can be made if allowed, but this is both costly and hazardous. Furthermore, rarely the load level may be chosen.
So, by simulating islanded conditions and giving the simulated frequency to the unit, islanded conditions can be evaluated.
FGMO ”Islanded systems” Annexure-2
49
Example Dadri II, 75 % load
± 23 MW
Annexure-2
50
Unit / Test FGMO RGMO Islanding (FMGO)
Chamera (180MW)
As Expected 60 MW/Hz, 10-60s
OK, meets grid code
Stable, can manage large load change (>10%)
Tehri, (250MW) Expected behavior but gate feedback causes nonlinear load response. 50-250MW/Hz, (125) 100-200s
Works but not as intended in some cases
Stable, can manage large load change (>10%)
Dadri II (490MW) Expected beavior 196MW/Hz, 15-85s
- Stable f-control but unstable process
Dadri I (210MW) Expected behavior, but maybe too reponsive 84MW/Hz, 3-8s
- Unstable f-control and process
Bawana (216MW) Expected behavior 110MW/Hz, 5-10s
- Not tested due to inability to arrange test input
Test results Annexure-2
51
Hydro power plants are generally well suited for frequency control, including islanding. Response is practically only limited by limit of the turbine. The process itself is quite simple and robust.
Thermal Power Plants (boilers) can provide a fast response, but the thermal process is complex and slow, which requires special attention.
Gas Turbines can usually respond very quickly, and are ideal both for fast primary response and for Islanding.
General comments Annexure-2
52
RGMO is implemented as per the Grid Code in both Chamera and Tehri but the interpretations are different. Hence, the Grid Code is not completely clear.
RGMO is not acting in proportion to the frequency deviation and is NOT strictly a frequency governing mode, rather a logic to increase the generated load at frequency drops.
RGMO is missing controller feedback and consequently, no stable dynamic equilibrium can be reached with this mode.
RGMO comments Annexure-2
53
FGMO is not an internationally used expression
FGMO seems to have different interpretations in India.
A combined Frequency / Load Control with Droop is commonly used internationally, and could be found in Dadri and Chamera for instance.
FGMO comments Annexure-2
54
Primary control – intends to maintain the power balance in the system and hence keep the frequency reasonably close to 50Hz.
Should be automatic and always present.
Response in seconds (0-60)
Secondary control – intends to control the average frequency level at 50.0 Hz.
Response in minutes - hours
Can be automatic or manual in combination with forecasting tools and scheduling
On Frequency Dynamics Annexure-2
55
Large units, when operating in FSM (Article 10): Response according to droop within certain limits
ENTSO-E Annexure-2
56
Large units, when operating in FSM (Article 10): Full response within 30 s, start within 2 s.
ENTSO-E Annexure-2
57
Testing of FSM (Article 39)
a) The Power Generating Module shall demonstrate its technical capability to continuously modulate Active Power over the full operating range between Maximum Capacity and Minimum Regulating Level to contribute to Frequency Control and shall verify the steady- state parameters of regulations, such as Droop and deadband and dynamic parameters, including robustness through Frequency step change response and large, fast Frequency changes.
b) The test shall be carried out by simulating Frequency steps and ramps big enough to activate the whole Active Power Frequency response range, taking into account the Droop settings, the deadband and the Real Power headroom or deload (margin to Maximum Capacity in operational timescale). Simulated Frequency deviation signals shall be injected simultaneously into the references of both the speed governor and the load controller of the unit or plant control system if required, taking into account the speed governor and load controller scheme. (Equipment Certificate may be used instead of part or all of the test)
ENTSO-E Annexure-2
58
LFSM-O (Article 8) Medium and large units must respond to severe overfrequency (threshold 50.2 .. 50.5 Hz) by reducing output according to droop.
ENTSO-E Annexure-2
59
Testing of LFSM-O (Article 38)
a) The Power Generating Module shall demonstrate its technical capability to continuously modulate Active Power to contribute to Frequency Control in case of large increase of Frequency in the system and shall verify the steady-state parameters of regulations, such as Droop and deadband, and dynamic parameters, including Frequency step change response.
b) The test shall be carried out by simulating Frequency steps and ramps big enough to activate at least 10 % of Maximum Capacity change in Active Power, taking into account the Droop settings and the deadband. Simulated Frequency deviation signals shall be injected simultaneously at both the speed and power control loops of the control systems if required, taking in account the scheme of these control system. (Equipment Certificate may be used instead of part or all of the test)
ENTSO-E Annexure-2
60
LFSM-U (Article 10) Large units must, if possible, respond to severe underfrequency (threshold 49.8 .. 49.5 Hz) by increasing output according to droop.
ENTSO-E Annexure-2
61
Testing of LFSM-U (Article 39)
a) The Power Generating Module shall demonstrate its technical capability to continuously modulate Active Power at operating points below Maximum Capacity to contribute to Frequency Control in case of large drop of Frequency in the system.
b) The test shall be carried out by simulating at appropriate Active Power load points (e.g. 80 %) with low Frequency steps and ramps big enough to activate at least 10 % of Maximum Capacity Active Power change, taking into account the Droop settings and the deadband. Simulated Frequency deviation signals shall be injected simultaneously into both the speed governor and the load controller references if required, taking into account the speed governor and the load controller scheme. (Equipment Certificate may be used instead of part or all of the test)
ENTSO-E Annexure-2
62
Testing
No details given on how simulating Frequency steps and ramps shall be done.
• Internal governor function?
• External equipment?
ENTSO-E Annexure-2
63
Grid code ’FIKS’ developed in a specific technical environment:
• Almost exclusively hydropower
• Mainly Francis and Pelton turbines – fast response possible
• Weak grid and long distances – large risk for islanding
Norway Annexure-2
64
Governor response testing (Appendix to FIKS)
1. Servo loop time constant Test during shutdown (dry unit) recommended. Test is specific for hydropower
2. Delay – from frequency rise to start of gate movement Breaker trip suggested
Norway Annexure-2
65
Governor response testing (Appendix to FIKS)
3. Droop Logging during interconnected operation.
4. Islanding Real life tests, single or multiple units
Norway Annexure-2
66
Primary control support is an ancillary service, and is purchased in blocks of XXMW/Hz
Time constant shall be <60s (Mostly Hydro)
Testing by step response is required to show compliance (common practice)
Island operation ability is contracted between the TSO and the plants, or regionally and utilize a combination of real tests and SSPS online method for evaluation.
Sweden Annexure-2
67
Require plants to have an external analog frequency test input, where the National Load Dispatch Center (EGAT) can inject a test signal and evaluate the primary response regularly. (Grid code does not clearly express
this but is based on discussions with system planning department)
Thailand Annexure-2
68
Phase out RGMO gradually
Implement PI(D) Frequency control (FGMO) with droop integrated with Load control.
”Power Feedback” in normal operation for predictible response
”Gate Feedback” in Islanding for best possible stability
Recommendations for Plants Annexure-2
69
For Primary response in normal operation, step response tests should be carried out to get the magnitude and time constant
For islanding, either online ”simulator testing” or real life full scale tests should be considered. Nothing else is sufficient.
For checking of the participation in frequency control, the generated power and frequency can be used for verification
Any testing should be carried out by an independent party
Recommendations for Testing Annexure-2
70
Work out clear Crid Code for Primary Control response and for testing of the same. The requirements should be based on the unique circumstances in India.
Grid topology
Grid bottlenecks
Generation mix, geograpical distribition
”Design base” contingencies
Market aspects
Recommendations for Grid Control Annexure-2
71
Thanks for your attention!
0
35
Niclas Krantz [email protected]
+46 31 709 6304
Contact in India:
Mr. Shahzad Alam +91 99 10 611184
Welcome to contact us for clarifications!
Annexure-2
72
Solvina International AB Document template: Solvina International Report.dot. Last change made by VOl 20st of October 2010
Gruvgatan 37 Phone +46 031 - 709 63 00 Internet www.solvina.com Org no 556782-3280 SE-421 30 Västra Frölunda Location: Göteborg SWEDEN
Valid date
2014-11-23 Project (no - customer)
2014018- POSOCO Report No:
2014018-20 Page (no pages)
1 (39) Author
Shweta Tigga/Niclas Krantz Reviewed
Sven Granfors
Bengt Johansson
Approved
Niclas Krantz
Title
2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Distribution
Nodal officers NTPC, NHPC, THDC, PPCIL, POSOCO
SUMMARY
This document presents the results of primary response tests, including island operation tests of a
180 MW hydroelectric unit at Chamera I Power Plant, India, conducted from 13th
Oct – 15th
October 2014.
The report describes the test setup, conditions and results from the measurements made by
Solvina International. Tests show that both FGMO and RGMO work as expected and that
FGMO can be used to control the frequency both in interconnected mode and in islanded mode.
In the latter case power feedback should be set OFF.
The following tests were performed at Chamera-I unit 3:
- Step response tests with FGMO mode, power feedback ON: The step response tests
performed show a consistent behaviour in accordance with droop, with the expected
value of 60MW/Hz. However, the time constant varies vastly due to actuator
imperfection, i.e mechanical backlash.
- Step response tests with FGMO mode, power feedback OFF: The performed step
response tests show longer delay compared to power feedback ON and a varying
response of the generated load magnitude. This is according to expected behaviour due to
mechanical backlash in the actuator system. The tests in this mode show that the
generated load response is only approximately in accordance with the droop setting,
whereas the gate position response is in accordance with the droop, which can be
expected considering the mechanical backlash.
- Step response tests with RGMO mode: The tests conducted in RGMO mode show a
consistent behaviour and in line with the grid code. The generated load increases by 5 %
of the actual generated load for 5 min for a drop in frequency.
- Small Island test: From the tests it was concluded that the unit is able to control the
frequency in a stable way. Up to 20MW load changes were tested without any problems.
Due to mechanical backlash, continuous but stable oscillations in the generated load were
observed.
- Large Island test: The test shows that the power plant responds well to load steps on a
large grid as well. The oscillations on application of the load step are quite damped due to
the presence of inertia of other plants. In this case 30MW load changes were tested
successfully.
Annexure-3
73
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 2 of 39 Printed 2014-11-23 14:37
CONTENTS
1 INTRODUCTION .......................................................................................... 4 1.1 Background ....................................................................................................... 4 1.2 Tests performed ................................................................................................ 4
2 DESCRIPTION OF TESTED UNIT ............................................................ 5 2.1 Basic unit data .................................................................................................. 5 2.2 Governor ........................................................................................................... 5 2.3 Actuator system ................................................................................................ 6
3 DESCRIPTION OF TESTS PERFORMED ................................................ 7 3.1 Definitions ........................................................................................................ 7 3.2 Method for island operation testing .................................................................. 8 3.3 Test procedure .................................................................................................. 9
3.3.1 Test equipment/function/signal check ............................................................... 9 3.3.2 Step response tests ............................................................................................ 9 3.3.3 Small island tests .............................................................................................. 9 3.3.4 Large island test ............................................................................................. 10
4 TEST RESULTS ........................................................................................... 11 4.1 Executive summary ........................................................................................ 11 4.1.1 Primary frequency response ........................................................................... 11 4.1.2 Island operation .............................................................................................. 11 4.2 Primary frequency response, step response tests ............................................ 11 4.2.1 Step response tests in FGMO mode ................................................................ 11 4.2.2 Step response tests in RGMO mode ................................................................ 19 4.3 Island operation tests – Small island .............................................................. 27 4.3.1 Small island – generated load 10 %. .............................................................. 28
4.3.2 Small island – generated load 75% ................................................................ 31 4.4 Island operation tests – Large island .............................................................. 33
5 CONCLUSIONS ........................................................................................... 36 5.1 FGMO ............................................................................................................. 36 5.2 RGMO ............................................................................................................ 36 5.3 ISLAND OPERATION .................................................................................. 36 5.3.1 Small Island test: ............................................................................................ 36 5.3.2 Large island test ............................................................................................. 37
6 RECOMMENDATIONS ............................................................................. 38 6.1 Normal (grid connected) operation ................................................................ 38 6.2 Island operation .............................................................................................. 38
6.3 Mechanism ..................................................................................................... 38
7 REFERENCES ............................................................................................. 39
Annexure-3
74
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 3 of 39 Printed 2014-11-23 14:37
REVISION RECORD
Rev.
No.
Date Section Cause Revised
by
Distributed to
1.0 2014-11-23 All Draft report submitted NKr Nodal officers
Annexure-3
75
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 4 of 39 Printed 2014-11-23 14:37
1 INTRODUCTION
1.1 Background
After the large disturbance/outage in northern India in July 2012 it was concluded
that there is a need to verify the primary response of generating units in India. In
March 2013 it was decided that a pilot project to carry out primary frequency
response would be carried out, and this was then described in terms of reference
document (annexure to contract agreement) [1].
Solvina International was awarded this pilot project after a global tender process and
signed a contract agreement with Power Grid PGCIL/POSOCO in August 2014 [1].
The purpose of these tests was to record and verify the following capabilities on the
specified generating units:
Primary Frequency Response in normal operation under Restricted governor
mode (RGMO) and Free governor mode (FGMO).
Primary Response of the machine to a simulated frequency signal
corresponding to islanded conditions in small island (one unit) and large
island (2000MW system load).
The following units are included in the project:
490 MW thermal unit at Dadri NCTPS
210 MW thermal unit at Dadri NCTPS
216 MW gas turbine at Bawana GPS
180 MW hydro unit at Chamera-1 HPS
250 MW hydro unit at Tehri HPS
This report is for the tests at unit 3 (180MW) at Chamera, NHPC.
1.2 Tests performed
The following tests were carried out on Chamera-I unit 3 as per the test program [2]:
13th
Oct 2014 Test equipment/function/signal check
Connections completed with signal check and test equipment
function check.
14th
Oct 2014 Step Response tests
Step response tests at 10%, 75% and 100% of rated generated load
under FGMO and RGMO mode.
15th
Oct 2014 Small Island test: 10% and 75% of rated generated load.
Large Island test: 75% of rated generated load.
Annexure-3
76
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 5 of 39 Printed 2014-11-23 14:37
2 DESCRIPTION OF TESTED UNIT
Chamera hydro power station has three units of 180 MW each. The turbines are
Francis type.
2.1 Basic unit data
Table 1: Basic data Chamera unit 3
Turbine Make BHEL
Age 1994
Size 180MW
Speed 214.3 rpm
Generator Make BHEL
Age 1994
Size 200MVA
Governor Make ALSTOM
Age 2011
Type Digital
2.2 Governor
The governor is supplied by Alstom. It has two frequency control modes for normal
operation
1. FGMO (Free Governor Mode of Operation) is a linear power/frequency
control, based on a PI controller with droop. The feedback which is used for
forming the droop response can be taken from either the measured generated
active power (referred to as power feedback ON) or from the corresponding
wicket gate position (referred to as power feedback OFF). This is selected by
a switch in the control room. The normal condition is power feedback ON.
FGMO is also suitable for islanding.
2. RGMO (Restricted Governor Mode of Operation) is a non-linear control
especially adapted for the grid code requirements. Certain conditions of
decreasing grid frequency within the RGMO frequency band will cause the
governor to increase the generated load by 5 % of actual generated load for 5
minutes. If the grid frequency goes above the limit of the RGMO, the
governor will decrease the generated load by an amount calculated from
droop (which is in this case referred to rated generated load).
Annexure-3
77
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 6 of 39 Printed 2014-11-23 14:37
2.3 Actuator system
The wicket gate of each unit is controlled by a hydraulic actuator cylinder that rotates
a wicket gate ring in proportion to the governor output. The gate sections are linked
to this ring and are rotated by it, as indicated in the figure below. The sensor of the
wicket gate position is placed on the actuator piston rod, which means that it cannot
sense if there is any mechanical play or backlash in the link between the piston and
the ring or between the ring and the gate sections. The gate position in the figures in
this report is the position as measured by this sensor. The actual angle of the gate
sections may differ from this measured position in case of mechanical play or
backlash.
The hydraulic actuator has a pressure reserve that enables rapid movement of the
wicket gate. Repeated large movements could theoretically deplete this reserve faster
than it can be refilled, but no such problems were seen during the tests.
Figure 1. Simplified diagram of the wicket gate control mechanism.
The results from the tests indicate that there is in fact a significant play or backlash in
the mechanism. This is the case for both the step response tests and the island
operation tests, see section 5.
Sensor
ACTUATOR
CYLINDER
Piston rod
Ring
Gate
sections Links
Annexure-3
78
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 7 of 39 Printed 2014-11-23 14:37
3 DESCRIPTION OF TESTS PERFORMED
3.1 Definitions
Simulated frequency: This is the signal generated by the test
equipment, SSPS.
It can be used as input to the
frequency/speed controller instead of the
actual speed from the frequency/speed
sensor.
Actual frequency: Signal from generator frequency/speed
sensor.
Generated load: Active power of generating unit
[Active power (used in plots) ]
System load: Total active power consumption in the
grid
Simulated system load System load simulated in the test
equipment
System base load: Start value of simulated system load when
starting the island simulation test.
Annexure-3
79
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 8 of 39 Printed 2014-11-23 14:37
3.2 Method for island operation testing
Solvina has developed a test equipment to be used for evaluation of the island
operation capability of power turbines. The equipment is called SolvSim Power
Station, SSPS.
The test method uses the principle of “HardWare In the Loop”, i.e. a simulator
simulating that a small power system is connected to the speed governor of a turbine.
The speed controller will then act as if it is actually running in island operation. The
active power produced by the turbine is measured and summed up with simulated
contributions to calculate the active power balance of the simulated island.
Gen.
Grid
Turbine
Mea
sure
d Si
gnal
s
Governor
Simulated
island
Actual Frequency
Simulated
FrequencySSPS
Relay
Figure 2. Hardware-in-the-loop simulation of island operation.
Models of loads as well as other power producers can be included in the model of the
electric island.
Using the active power balance and the total moment of inertia of the island, the
island frequency can be calculated and fed back to the speed controller of the turbine
tested. In this way, the capability of running in island operation can be tested while
the turbine is still synchronized to a strong grid.
SSPS is also used to inject simulated frequency steps for primary response tests.
Annexure-3
80
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 9 of 39 Printed 2014-11-23 14:37
3.3 Test procedure
3.3.1 Test equipment/function/signal check
Before commencement of actual tests, all the values/scalings of the measured signals
and the installation of the test equipment were checked to ensure correct
measurements and safe operation. The switching between the actual and the
simulated frequency was tested several times to verify a bumpless transition. The
internal safety functions of the SSPS system were also verified.
3.3.2 Step response tests
With commencement of the test sequence, initially the simulated frequency was kept
at 50Hz. The primary response was tested by injecting a frequency step to the
governor frequency input. The frequency step was calculated from the droop settings,
to produce an generated load change of up to approx. 5% of rated load.
The step tests with RGMO/ FGMO engaged in governor were performed at 10%,
75% and 100% of rated generated load with positive and negative steps in frequency.
3.3.3 Small island tests
This test was performed to assess the ability of the turbine to control the frequency as
sole production on an island grid. Simulated load steps of different sizes were
applied (see section 4.3), which resulted in a change in simulated frequency.
For the tests at Chamera, Table 2 below summarizes the grid model with a total
simulated system base load of 18 and 135 MW respectively. The simulated system
load comprises frequency dependent and frequency independent loads.
Table 2 Simulator parameters for small island test.
System
Base load
Rated apparent
power (Sn) of
generator
System load with
linear frequency
characteristic
System load without
frequency
dependence, no inertia
Small
Island
@10%
18MW 200 MVA
(Inertia 4,07 s)
8 MW
(Inertia 0,70 s)
10 MW
Small
Island
@75%
135 MW
60 MW
(inertia 0,70 s)
65 MW
Annexure-3
81
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 10 of 39 Printed 2014-11-23 14:37
Simulated load steps were added to this base load as shown in section 4.3. After each
load step, the generated load and the simulated frequency were allowed to stabilize
(near to 50 Hz).
The tests were repeated at 10% and 75% generated load with FGMO engaged in
governor. The size of the acceptable system load steps was decided by increasing the
step size gradually until the simulated frequency limits or other limitations were
reached.
3.3.4 Large island test
This test was performed to assess the ability of the turbine to control the frequency
together with other power plants on a local grid. All other power plants were
simulated to act according to power control. Simulated load steps of different sizes
were applied (see section 4.4) to determine the size of the load changes that the
power plant could handle.
The summary of the total simulated base load was 2000 MW. Table 3 below
summarizes the grid model. The simulated load comprises frequency dependent and
independent loads.
Table 3 Simulator parameters for large island test
Total
system
base load
Rated
apparent
power (Sn) of
generator
System load with
linear frequency
characteristic
System load
without
frequency
dependence,
no inertia
Additional
simulated
power
plants
Large
island:
2000 MW
200 MVA
(inertia 4,07 s)
1000 MW
(Inertia 0,70 s) 1000 MW
2000 MVA
(Inertia 4,0 s)
1800 MW
Annexure-3
82
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 11 of 39 Printed 2014-11-23 14:37
4 TEST RESULTS
4.1 Executive summary
4.1.1 Primary frequency response
FGMO works as expected in both “power feedback ON” and “power feedback
OFF”. The magnitude of the response is as per the droop settings. However, the time
constant varies vastly, mainly because of mechanical backlash in the actuator system.
In “power feedback OFF” (meaning gate opening feedback), the gate opening
responds according to droop, but due to the mechanical backlash, the load responds
to various extent only. During the tests, both positive and negative frequency steps
up to 0.15 Hz were tested.
RGMO works as intended and in accordance with the Grid Code. Simulated
frequency steps were made to test functionality both within and outside the RGMO
frequency range 49.0-50.05 Hz.
4.1.2 Island operation
The unit is very capable of controlling the frequency both in small island grids and
large island grids. The capacity of handling load changes was tested up to ±20MW
(11%) with very moderate frequency variations (1,5Hz). It is believed that up to
±30MW should not be a problem in islanding.
Due to the mechanical backlash of the actuator there is a slow spontaneous frequency
oscillation of ±0.3-0.4 Hz that however does not at all tend to cause instability.
4.2 Primary frequency response, step response tests
4.2.1 Step response tests in FGMO mode
The step response tests are carried out to investigate how well the plant supports the
power system at frequency changes of the grid. The speed droop is the parameter that
decides the magnitude of response. The response has two characteristics that are
interesting to examine, the magnitude and the time constant (67% value, T67).
For the tests in FGMO mode the droop setting during test was 6%. Both power
feedback ON and power feedback OFF were tested.
Steps were carried out to give up to 5% load change, which is 9MW, and the
frequency step size giving that response would be 0.05*0.06*50 = 0.15 Hz.
Consequently 9MW is the expected response for the steps to be carried out.
Similarly, expressed in MW/Hz, the response is expected to be 60MW/Hz for any
step (9/0.15).
Annexure-3
83
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 12 of 39 Printed 2014-11-23 14:37
4.2.1.1 Step response in FGMO, generated load 10%, power feedback ON
The step response tests were carried out at 10% generated load with power feedback
ON.
Table 4 Frequency steps in FGMO, generated load 10 %, power feedback ON – part 1
Simulated
frequency (Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change , ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
50 50,1 20 14 -6 60 48
50,1 50 14 20 +6 60 59
5049,9
20 26 +6 60 25
49,9 50 26 20 -6 60 65
50 49,85 20 29 +9 60 42
49,85 50 30 20 -10 67 47
Figure 3. Frequency steps in FGMO, generated load 10 %, power feedback ON – part 1.
Annexure-3
84
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 13 of 39 Printed 2014-11-23 14:37
Table 5. Frequency steps in FGMO, generated load 10%, power feedback ON – part 2
Simulated
frequency (Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change , ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
Load setpoint changed from 20 25 MW @ 50 Hz
50 50,15 25 15 -10 67 30
50,1550 15 25 +10 67 45
Figure 4. Frequency steps in FGMO, generated load 10%, power feedback ON – part 2.
It can be concluded that the response is correct and in accordance with the droop
settings at all steps. The spread of time constant values mainly depends on
mechanical backlash of the actuator linkage as explained in section 2.3 and 5.1. It
can be seen from the above figure that the measured gate position opening varies
depending on step sequence whereas the load response is constant, which is expected
as power feedback is ON. The measured gate position is moved further to
compensate for the existing mechanical backlash (see section 5.1). For steps in the
same (decreasing) direction, the effect of mechanical backlash is reduced as the gate
position is already moving in upward direction so a shorter traveling distance is
required by the actuator piston rod.
Annexure-3
85
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 14 of 39 Printed 2014-11-23 14:37
4.2.1.2 Step response in FGMO, generated load 10%, power feedback OFF
The tests with power feedback OFF were carried at 10% generated load.
Table 6. Frequency steps in FGMO, generated load 10 %, power feedback OFF
Simulated
frequency
(Hz)
Initial
generated
load
(MW)
Post step
generated
load
(MW)
Gen. load
change ,
ΔP (MW)
MW
contribution
(MW/Hz)
Gate
position
change
(%)
Time
constant,
T67 (s)
5049,85 22 25 +3 20 5 57
49,8550 25 23 -2 13 5 78
50 50,15 23 13 -10 67 5 27
50,1550 13 14 +1 7 5 75
Figure 5. Frequency steps in FGMO, generated load 10 %, power feedback OFF.
The test shows that the gate opening response is according to the droop setting. The
measured gate position change of 5% is in perfect accordance with the set droop
value of 6%. However, looking at load response to frequency, steps have a varying
magnitude. This is mainly because of the mechanical backlash, where certain gate
opening value causes different values in real gate value and hence generated load.
The generated load change after a step is dependent on the direction of the previous
step. For example, for two steps in the same consecutive directio, the response of the
active load is immediate with frequency steps in increasing direction and the effect of
the mechanical backlash is not there. This is because the movement of the gate
position is already in the downward direction and requires shorter piston traveling
distance.
Annexure-3
86
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 15 of 39 Printed 2014-11-23 14:37
4.2.1.3 Step response in FGMO, generated load 75%, power feedback ON
The same procedure as above tests is repeated. The power feedback being ON so the
response is expected to be faster as mentioned in section 4.1.1.
Table 7 Frequency steps in FGMO, generated load 75 %, power feedback ON.
Simulated
frequency (Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change , ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
50 49,85 Hz 133 142 +9 60 11
49,85 50 Hz 142 133 -9 60 42
50 50,15 Hz 133 122 -10 67 31
50,1550 Hz 122 133 +10 67 18
Figure 6. Frequency steps in FGMO, generated load 75 %, power feedback ON.
The test shows that the response to frequency steps has a consistent magnitude which
is in accordance with the droop setting. The response of the measured gate position
signal is immediate. The response of the active load is immediate for some steps but
delayed by 7-10 seconds for some steps, due to the mechanical backlash as described
in sections 2.3 and 5.1.
Annexure-3
87
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 16 of 39 Printed 2014-11-23 14:37
4.2.1.4 Step response in FGMO, generated load 75%, power feedback OFF
Tests were performed at 75% generated load with the same conditions as previous
tests mentioned in above sections.
Table 8 Frequency steps in FGMO, generated load 75 %, power feedback OFF.
Simulated
frequency
(Hz)
Initial
generated
load
(MW)
Post step
generated
load
(MW)
Gen. load
change ,
ΔP (MW)
MW
contribution
(MW/Hz)
Gate
position
change
(%)
Time
constant,
T67 (s)
50 50,15 136 127 -9 60 5 47
50,15 50 127 133 +9 60 5 79
Figure 7. Frequency steps in FGMO, generated load 75 %, power feedback OFF.
The test shows that the gate opening response is according to the droop setting. The
measured gate position change of 5% is in perfect accordance with the set droop
value of 6%.
However, the generated load response magnitude varies. This is mainly because of
the mechanical backlash, where certain measured gate opening value causes different
values in real gate value and hence load.
Annexure-3
88
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 17 of 39 Printed 2014-11-23 14:37
4.2.1.5 Step response in FGMO, generated load 100%, power feedback ON
Tests were performed at 100% generated load with the same conditions as for
previous tests.
Table 9 Frequency steps in FGMO, generated load 100 %, power feedback ON.
Simulated
frequency (Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change , ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
50 49,85 180 189 +9 60 29
49,85 50 189 179 -10 67 26
50 50,15 179 169 -10 67 14
50,1550 169 180 +10 67 30
Figure 8. Frequency steps in FGMO, generated load 100 %, power feedback ON.
The test shows that the generated load response to frequency steps has a consistent
magnitude in accordance with the droop setting. The response of the gate position
signal is immediate. The response of the active load is immediate for some steps but
delayed by 7-10 seconds for some steps, due to the mechanical backlash as described
in sections 2.3 and 5.1.
Annexure-3
89
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 18 of 39 Printed 2014-11-23 14:37
4.2.1.6 Step response in FGMO, generated load 100%, power feedback OFF
Tests were performed at 100% generated load with power feedback OFF and with
same conditions as for the previous tests.
Table 10 Frequency steps in FGMO, generated load 100 %, power feedback OFF.
Simulated
frequency
(Hz)
Initial
generated
load
(MW)
Post step
generated
load
(MW)
Gen. load
change ,
ΔP (MW)
MW
contribution
(MW/Hz)
Gate
position
change
(%)
Time
constant,
T67 (s)
50 50,15 179 170 -9 60 5 34
50,1550 170 177 +7 47 5 38
50 49,85 177 190 +13 87 5 24
49,85 50 190 186 -4 27 5 52
Figure 9. Frequency steps in FGMO, generated load 100 %, power feedback OFF.
The test shows that the gate opening response is according to the droop setting. The
measured gate position change of 5% is in perfect accordance with the set droop
value of 6%. However, looking at load response to frequency, steps have a varying
magnitude. This is mainly because of the mechanical backlash, where certain gate
opening value causes different values in real gate value and hence generated load.
Annexure-3
90
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 19 of 39 Printed 2014-11-23 14:37
4.2.2 Step response tests in RGMO mode
The purpose of this test is to elaborate the function of RGMO. Frequency steps of
different size and different levels are generated to excite the response of the RGMO.
The response in this mode should be in accordance with the grid code, which states
that, “There should not be any reduction in generation in case of improvement in
grid frequency below 50.05 Hz. Whereas for any fall in grid frequency, generation
from the unit should increase by 5 % limited to 105% of the MCR of the unit
subject to machine capability”.
In Chamera, the RGMO frequency band is 49-50.05 Hz. The droop setting kept
during these tests in RGMO was 6%. The following sections give the results of the
tests performed.
Annexure-3
91
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 20 of 39 Printed 2014-11-23 14:37
4.2.2.1 Step response in RGMO, generated load 10%
For the tests at 10% generated load in RGMO mode, it is expected that for any
decrease in frequency below the RGMO upper band limit of 50.05 Hz, the generated
load should increase by 5%.
Table 11 Frequency steps in RGMO mode, generated load 10%, part 1of 2.
Simulated frequency
(Hz)
Initial generated
load (MW)
Post step generated
load (MW)
Generated load
change, ΔP (MW)
50 49,95 24 22 -2
49,95 50 22 23 +1
50 50,10 23 16 -7
50,10 50 16 23 +7
50 50,15 23 13 -10
50,1550 13 23 +10
Figure 10. Frequency steps in RGMO mode, generated load 10%, part 1of 2
Annexure-3
92
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 21 of 39 Printed 2014-11-23 14:37
Figure 11: Frequency steps in RGMO, generated load 10 % - part 2 of 2.
From the above figure, it can be seen that for a decrease in frequency, the generated
load increases by 5% of the actual value which is 1MW at that level. With increase in
frequency to 50 Hz, no change in generated load is seen. For a step change in
frequency outside the RGMO frequency band 50.05 Hz, the generated load is
decreased in accordance with the droop setting referred to the rated load. The
behavior is correct and in accordance with the grid code.
Annexure-3
93
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 22 of 39 Printed 2014-11-23 14:37
4.2.2.2 Step response in RGMO, generated load 75%
The same procedure is repeated as per the above tests were performed at 75%
generated load.
Table 12 Frequency steps in RGMO, generated load 75 % - part 1 of 2
Simulated
frequency (Hz)
Initial generated
load (MW)
Post step generated
load (MW)
Generated load
change, ΔP (MW)
50 49,85 133 140 and ramp back to
133 MW after 5 min
+7
49,85 50 133 133 0
50 49,80 133 141 +8
49,80 50 141 No initial response. Ramps back to 134
MW after 5 min
Figure 12. Frequency steps in RGMO, generated load 75 % - part 1 of 2
From the above figure, it can be seen that for a decrease in frequency, the generated
load increases by 5% of the actual value which is 7 MW at that level. With increase
in frequency to 50 Hz, no change in generated load is seen. The behavior is in
accordance with the grid code.
Annexure-3
94
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 23 of 39 Printed 2014-11-23 14:37
Table 13 Frequency steps in RGMO, generated load 75 % Part 2 of 2
Simulated
frequency (Hz)
Initial generated
load (MW)
Post step generated
load (MW)
Generated load
change, ΔP
(MW)
50 50,15 134 124 -10
50,15 50 124 134 +10
50 49,95 135 141 +6
49,9550 141 141 0
Figure 13. Frequency steps in RGMO, generated load 75 % Part 2 of 2
The test shows that when the frequency goes above 50.05 Hz, the generated load is
decreased in accordance with the droop setting. When the frequency decreases, the
generated load is increased by 5 % of actual generated load for 5 minutes. This is in
accordance with the grid code.
Annexure-3
95
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 24 of 39 Printed 2014-11-23 14:37
4.2.2.3 Step response in RGMO, generated load 100%
The same procedure is repeated for tests carried out at 100% generated load. The
behavior is expected to be according to grid code.
Table 14 Frequency steps in RGMO, generated load 100 % - part 1 of 2.
Note: generated load changes after 5350 s are caused by water head
oscillations due to starting of another unit.
Simulated frequency
(Hz)
Initial generated
load (MW)
Post step generated
load (MW)
Generated load
change, ΔP
(MW)
50 49,85 Hz 179 188 +9
49,85 50Hz 188 179 -9
50 50,15 Hz 179 168 -11
50,15 50 Hz 168 187 +19 *)
*)Simulated frequency going in and out of RGMO band, so result is not taken
into account.
Figure 14. Frequency steps in RGMO, generated load 100 % - part 1 of 2. Note:
generated load changes after 5350 s are caused by water head oscillations due
to starting of another unit.
From the above figure, it can be seen that for a decrease in frequency, the generated
load increases by 5% of the actual generated load which is 9MW at that level. With
increase in frequency to 50 Hz, no change in generated load is seen. The behavior is
in accordance with grid code.
Annexure-3
96
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 25 of 39 Printed 2014-11-23 14:37
Table 15 Frequency steps in RGMO, generated load 100 % - part 2 of 2
Simulated frequency
(Hz)
Initial generated
load (MW)
Post step generated
load (MW)
Generated load
change, ΔP
(MW)
50 50,10 Hz 178 171 -7
50,10 50 Hz 171 187 +16
50 50,2 Hz 178 164 -14
50,20 50 Hz 164 186 +22
50 49,98 Hz 178 178 0
49,98 50 Hz 178 178 0
5050,02 Hz 178 178 0
50,0250 Hz 178 178 0
5049,99 Hz 178 178 0
49,9950 Hz 178 178 0
50 50,04 Hz 178 178 0
50,0450 Hz 176 186 +10
5050,05 Hz 186 176* -10
50,0550 Hz 176 186* +10
*Simulated frequency going in and out of RGMO band
Annexure-3
97
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 26 of 39 Printed 2014-11-23 14:37
Figure 15. Frequency steps in RGMO, generated load 100 % - part 2 of 2
The test shows that when the frequency goes above 50.05 Hz, the generated load is
decreased in accordance with the droop setting. When the frequency decreases, the
generated load is increased by 5 % of actual generated load.
Annexure-3
98
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 27 of 39 Printed 2014-11-23 14:37
4.3 Island operation tests – Small island
This test shows the ability of the plant to control the frequency when the tested unit
is the only generating source of the system. By simulating system load changes of the
simulated island, the simulated frequency will change. The tested unit will try to
control the simulated frequency. This way, it can be seen if the unit is stable. The
island operation tests were performed with power feedback off.
Droop setting was 6 %.
It was decided that the testing would be made at 10% and 75% load.
For the following figures, the legend is as below:
Blue Simulated frequency. This denotes the grid frequency in
real Island operation.
Red Generated load (= measured active power). This denotes
the mechanical turbine load in real island operation.
Green Gate position feedback. Please note that this is measured on
the actuator piston, see section 2.3.
Purple Simulated system load. This denotes the actual system load
in real island operation.
Annexure-3
99
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 28 of 39 Printed 2014-11-23 14:37
4.3.1 Small island – generated load 10 %.
The tests were carried out at only 10% of generated load. Simulated system load
steps were applied and the frequency deviations were recorded.
Table 16 Simulated island operation, generated load 10 %, all applied load steps.
Total range of
generated load (MW)
Simulated system load
step (MW)
Max. frequency deviation,
Δf (Hz)*
23-40 MW
+6 MW -0,8
-6 MW +0,4
+8 MW -0,9
-8 MW +1,0
+10 MW -1,2
-10 MW +0,5
+12 MW -0,8
-12 MW +0,8
+14 MW -1,4
-14 MW +0,7
+16 MW -1,5
-16 MW +1,2
+18 MW -1,2
-18 MW +1,3
+20 MW -1,3
-20 MW +1,1
*Please note: All frequency deviations are measured from the instant the step is
applied.
Annexure-3
100
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 29 of 39 Printed 2014-11-23 14:37
Figure 16. Simulated island operation, generated load 10 %, load step ±16 MW.
Figure 17. Simulated island operation, generated load 10 %, load step ±18 MW.
Annexure-3
101
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 30 of 39 Printed 2014-11-23 14:37
Figure 18. Simulated island operation, generated load 10 %, load step ±20 MW.
The test shows that the unit is able to control the frequency in a stable way. There is
a continuous slow oscillation while in island operation, due to mechanical backlash
as earlier described, causing frequency deviations of around ±0.3-0.4 Hz. (The cause
of the oscillation is further described in section 5.) Nevertheless, the unit responds
well to system load steps and the frequency stabilizes quickly. The largest simulated
load steps were ±20 MW. It is likely that the unit can handle even larger steps but the
test was halted after ±20 MW to avoid overstressing of the turbine.
Annexure-3
102
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 31 of 39 Printed 2014-11-23 14:37
4.3.2 Small island – generated load 75%
The tests were carried out at only 75% of rated generated load. Simulated system
load steps were applied and the frequency deviations were recorded.
Table 17 Simulated island operation, generated load 10 %, all applied load steps.
Total range of
generated load
(MW)
Simulated system load step
(MW)
Max. frequency deviation, Δf
(Hz)*
134-155 MW
+4 MW -0,4
-4 MW +0,6
+8 MW -0,5
-8 MW +0,7
+12 MW -0,5
-12 MW +1,0
+16 MW -1,2
-16 MW +1,0
+20 MW -1,3
-20 MW +1,0
Annexure-3
103
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 32 of 39 Printed 2014-11-23 14:37
Figure 19. Simulated island operation, generated load 75%, load step ±16 MW.
Figure 20. Simulated island operation, generated load 10 %, load step ±20 MW.
The test shows that the unit is able to control the frequency in a stable way. There is
a continuous slow oscillation while in island operation, due to mechanical backlash
as earlier described, causing frequency deviations of around ±0.3-0.4 Hz.
Nevertheless, the unit responds well to load steps and the frequency stabilizes
quickly. The largest simulated load steps were ±20 MW. It is likely that the unit can
handle even larger steps but the test was halted after ±20 MW to avoid overstressing
of the turbine.
Annexure-3
104
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 33 of 39 Printed 2014-11-23 14:37
4.4 Island operation tests – Large island
This test was performed to assess the ability of the turbine to control the frequency
together with other power plants on a local grid. The summary of the simulated base
load is described in section 3.3.4. The large island tests were performed at 75% of
rated generated load. Simulated system load steps were applied and the frequency
deviations were recorded. The droop setting during test was 6%.
Table 18 Simulated large island operation, generated load 75 %, all applied steps.
Total range of
generated load
(MW)
Simulated system load
step (MW)
Max. frequency
deviation, Δf (Hz)*
134-168 MW
+12 MW -0,33
-12 MW +0,26
+20 MW -0,32
-20 MW +0,40
+25 MW -0,40
-25 MW +0,56
+30 MW -0,63
-30 MW +0,62
Annexure-3
105
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 34 of 39 Printed 2014-11-23 14:37
Figure 21. Simulated large island operation, generated load 75 %, load steps ±25, ±30
MW. Simulated frequency and simulated system load are shown.
Figure 22. Simulated large island operation, generated load 75 %, load steps ±25, ±30
MW. Generated load (active power) and gate position along with simulated
frequency are shown.
Annexure-3
106
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 35 of 39 Printed 2014-11-23 14:37
The test shows that the power plant responds well to load steps on a large grid. The
largest simulated system load steps were ±30 MW. It is likely that the unit can
handle even larger steps but the test was halted after ±30 MW to avoid overstressing
of the turbine.
From the above figure it can be seen that the load follows the same profile as the
frequency because of the inertia and linear frequency dependency characteristic of
the load model described in section 3.3.4. Together with the inertia of the other
simulated power plants, this has a stabilizing effect of the grid frequency.
Annexure-3
107
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 36 of 39 Printed 2014-11-23 14:37
5 CONCLUSIONS
5.1 FGMO
The results for step response tests in FGMO mode show a consistent behavior. Tests
were performed both with power feedback ON and OFF.
Test performed with power feedback ON, show that response of load for a step
change was as per droop, but with a variation in time constant.
Tests with power feedback OFF show that the response with regard to gate opening
value was as per droop. However, a longer delay compared to power feedback ON
was noticed, as well as a varying response of the load magnitude depending on the
character of the step sequence.
The delay in response is attributed to mechanical backlash of the actuator system.
This cause shows in several ways. The measured gate position is seen to increase by
3-4% before the load actually starts to increase. It was also observed that this
phenomenon was not so pronounced when consecutive steps in frequency were
applied in the same direction (either positive or negative), because the backlash at the
second step then is zero.
In the case of power feedback is ON, the control compensates for this mechanical
backlash by further moving the gate position. The tests with power feedback OFF
show a larger time delay for the response of the load. Here the delay is longer as the
governor does not compensate for the existing mechanical backlash as there is no
feedback of generated load (active power).
5.2 RGMO
The grid code states that, “There should not be any reduction in generation in case
of improvement in grid frequency below 50.05 Hz. Whereas for any fall in grid
frequency, generation from the unit should increase by 5 % limited to 105% of the
MCR of the unit subject to machine capability”.
All tests show that the behavior is in accordance with the grid code. The time delays
caused by mechanical backlash has not been considered here because it is not part of
the requirements, but the same variation in delay is present in RGMO.
5.3 ISLAND OPERATION
5.3.1 Small Island test:
The unit could handle the ±20MW system load steps very well, with very moderate
frequency variations. The tested load changes correspond to 11% of rated load, and
that is considered being very good.
Annexure-3
108
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 37 of 39 Printed 2014-11-23 14:37
5.3.2 Large island test
For the large island test, the highest system load step of ±30 MW was applied which
generated a frequency deviation of approx. ±0.63 Hz. From Figure 22, it can be seen
that there is a delay in the response of the load but there exists no continuous
oscillations. This delay in the response is again caused by the mechanical backlash.
As the system inertia is higher in a large island, the plant can more easily keep the
frequency in a large island than in a small island. It is most likely that the unit can
handle much bigger system load changes in such a large island, at least double the
tested amount, i.e 60MW.
Annexure-3
109
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 38 of 39 Printed 2014-11-23 14:37
6 RECOMMENDATIONS
The results from the tests were analyzed to see what could further be done to
improve the performance. In this section some recommendations are presented.
6.1 Normal (grid connected) operation
FGMO is useful for providing frequency control to the national grid. While
connected to the national grid, the governor should be set to power feedback ON for
best accuracy of generated load and fastest possible response.
RGMO has a consistent response which is according to the settings. No actions are
recommended regarding this function.
6.2 Island operation
FGMO is also useful for frequency control while in island operation, either with one
unit as sole production on the grid or together with other units which may operate in
frequency or load control. The unit responds well to load changes in the grid and can
handle load changes of at least ±20 MW as sole production, and more if operating
together with other units. While operating on an island grid, the governor should be
set to power feedback OFF for best stability.
While operating on a small island grid, there may be some slow continuous
oscillations, caused by mechanical backlash in the wicket gate control mechanism.
This oscillation does not impede the ability of the unit to respond to load changes in
the grid. It could however cause some difficulty or delay in the synchronization of
the island grid to another grid.
RGMO should not be used while in island operation.
6.3 Mechanism
It is likely that a reduced mechanical backlash between the gate position sensor and
the angle of the gate sections will provide less continuous oscillations in island
operation, as well as faster load control in grid connected operation.
One way of compensating for the backlash could be to move the gate position
feedback sensor so that it senses the angle of the gate section rather than the position
of the piston that rotates the wicket gate ring.
Annexure-3
110
C:\Temp\2014018 - INT, POSOCO, Testing of Primary Response\2014018-20-1.0 Testing of Primary Response of Chamera I Unit 3.docx
Page 39 of 39 Printed 2014-11-23 14:37
7 REFERENCES
[1] Contract Agreement No.: CC-CS/422-CC/CON-2241/3/G8/CA/5002 dated
19/08/2014
[2] Test Program - Chamera : 2014 018-14-1.0
Annexure-3
111
Solvina International AB Document template: Solvina International Report.dot. Last change made by VOl 20st of October 2010
Gruvgatan 37 Phone +46 031 - 709 63 00 Internet www.solvina.com Org no 556782-3280 SE-421 30 Västra Frölunda Location: Göteborg SWEDEN
Valid date
2015-01-12 Project (no - customer)
2014018- POSOCO Report No:
2014018-28 Page (no pages)
1 (61) Author
Shweta Tigga
Bengt Johansson
Reviewed Niclas Krantz
Approved Niclas Krantz
Title
2014018-28-1.0 Testing of Primary Response of Dadri I Unit 4
Distribution
Nodal officer NTPC; POSOCO
SUMMARY
This document presents the results of primary response tests, including island operation tests of a
210 MW thermal unit at Dadri Power Plant, India, conducted from 20th
- 22nd
November 2014.
The report describes the test setup, conditions and results from the measurements made by
Solvina International. Tests show that the droop of the FGMO works as intended, but the
response is very fast which makes the unit unable to achieve stable operation on a small island
grid.
The following tests were performed at Dadri (Stage I), unit 4:
- Step response tests in FGMO mode: The step tests were performed at 75%, 90% and
100% generated load levels with a droop setting of 5%. Steps corresponding to a
generated load change of up to 5 % were tested. The generated load response corresponds
well to the droop setting. The response time T67 is very fast, in the range of 2-8 seconds,
and it has a distinct overshoot. This is due to the settings of the load controller.
- Small Island tests: The unit was unable to operate in small island tests at 75% and 90%
load levels with 5% droop. A continuously growing oscillation occurred as soon as the
island simulation was started, and the simulation had to be stopped. The tests were also
performed with droop setting of 8% but with the same result.
- Large Island test: The large inertia of the simulated grid made it possible for the unit to
achieve stable island operation. The response to a simulated system load change was
oscillatory but reasonably well damped. Simulated system load changes of ±14 MW were
tested successfully.
It was observed during the tests that the boiler control had problems responding to the load
changes and large steam pressure fluctuations were seen. This caused, at different times, both
operation of the HP bypass valve due to overpressure and load reduction due to underpressure.
The load control system itself started oscillating under certain conditions when the IP valve was
active.
Annexure-3
112
Page 2 of 61 Printed 2015-01-15 09:29
CONTENTS
1 INTRODUCTION .......................................................................................... 4 1.1 Background ....................................................................................................... 4 1.2 Tests performed ................................................................................................ 4
2 DESCRIPTION OF TESTED UNIT ............................................................ 5 2.1 Basic unit data .................................................................................................. 5 2.2 Operation principle of Thermal power plants................................................... 6 2.4 Governor ........................................................................................................... 9
3 DESCRIPTION OF TESTS PERFORMED .............................................. 12 3.1 Definitions ...................................................................................................... 12 3.2 Method for island operation testing ................................................................ 13
3.3 Test procedure ................................................................................................ 14 3.3.1 Test equipment/function/signal check ............................................................. 14 3.3.2 Step response tests .......................................................................................... 14 3.3.3 Small island tests ............................................................................................ 14 3.3.4 Large island test ............................................................................................. 15 3.4 Recorded signals ............................................................................................. 16
4 TEST RESULTS ........................................................................................... 17 4.1 Executive summary ........................................................................................ 17 4.1.1 Primary frequency response ........................................................................... 17 4.1.2 Island operation .............................................................................................. 17 4.2 Primary frequency response, step response tests in FGMO ........................... 18 4.2.1 Step response in FGMO, generated load 75%, droop 5% ............................. 19 4.2.2 Step response in FGMO, generated load 90%, droop 5% ............................. 34
4.2.3 Step response in FGMO, generated load 100%, droop 5% ........................... 37 4.3 Island operation tests – Small island .............................................................. 41 4.3.1 Small Island test, generated load 75%, droop 5% ......................................... 42 4.3.2 Small Island test, generated load 75%, droop 8% ......................................... 44 4.3.3 Small island – generated load 90%, droop 5% .............................................. 46 4.3.4 Small island – generated load 90%, droop 8% .............................................. 47 4.4 Island operation tests – Large island .............................................................. 50
5 CONCLUSIONS ........................................................................................... 57 5.1 FGMO ............................................................................................................. 57
5.2 ISLAND OPERATION .................................................................................. 57 5.2.1 Small Island test: ............................................................................................ 57 5.2.2 Large island test ............................................................................................. 57
6 RECOMMENDATIONS ............................................................................. 58 6.1 Normal (grid connected) operation ................................................................ 58 6.2 Island operation .............................................................................................. 58
7 REFERENCES ............................................................................................. 61
Annexure-3
113
Page 3 of 61 Printed 2015-01-15 09:29
REVISION RECORD
Rev.
No.
Date Section Cause Revised by Distributed to
1.0 2015-01-12 All Document created BJo POSOCO
Annexure-3
114
Page 4 of 61 Printed 2015-01-15 09:29
1 INTRODUCTION
1.1 Background
After the large disturbance/outage in northern India in July 2012 it was concluded
that there is a need to verify the primary response of generating units in India. In
March 2013 it was decided that a pilot project to carry out primary frequency
response would be carried out, and this was then described in terms of reference
document (annexure to contract agreement) [1].
Solvina International was awarded this pilot project after a global tender process and
signed a contract agreement with Power Grid PGCIL/POSOCO in August 2014 [1].
The purpose of these tests was to record and verify the following capabilities on the
specified generating units:
Primary Frequency Response in normal operation under Free governor mode
(FGMO).
Primary Response of the machine to a simulated frequency signal
corresponding to islanded conditions in small island (one unit) and large
island (2000MW system load).
The following units are included in the project:
490 MW thermal unit at Dadri NCTPS
210 MW thermal unit at Dadri NCTPS
216 MW gas turbine at Bawana GPS
180 MW hydro unit at Chamera-1 HPS
250 MW hydro unit at Tehri HPS
This report is for the tests at unit 4 (210MW) at Dadri I, NTPC
1.2 Tests performed
The following tests were carried out on unit 4 of Stage-I Dadri as per the test
program [2]:
20th
Nov 2014 Test equipment/function/signal check
Connections completed with signal check and test equipment
function check.
Step Response tests
Step response tests at 75% of rated generated load under FGMO
mode.
21st Nov 2014 Step Response tests: Step response tests at 90% and 100% of
rated generated load under FGMO mode.
Small Island test: 75% and 90 % of rated generated load.
Large Island test: 90% of rated generated load.
Annexure-3
115
Page 5 of 61 Printed 2015-01-15 09:29
2 DESCRIPTION OF TESTED UNIT
The total installed capacity of NTPC Dadri power plant is 2642 MW. The plant
comprises six thermal units with a total capacity of 1820 MW; four units of 210 MW
each and two units of 490 MW. In addition to the thermal plants, NTPC Dadri also
has 817 MW gas based thermal plant and 5 MW solar plant.
2.1 Basic unit data
Table 1: Basic data Dadri I Unit 4
Turbine Type KWU
Speed 3000 rpm
Generator Rating 247 MVA, 210 MW
Governor Make BHEL
Type Analog
Figure 1. Interior of power plant
Annexure-3
116
Page 6 of 61 Printed 2015-01-15 09:29
2.2 Operation principle of Thermal power plants
The thermal power plant is based on the principle of Rankine cycle. Figure shows the
processes involved in a Rankine cycle. The water is first pumped from step 12,
thereby increasing the pressure, which requires some input energy. From step 23,
the water at high pressure is heated in a boiler at constant pressure by an external
heat source which turns it into steam. The steam is then allowed to expand in a
turbine, thereby generating power (step 34). The steam is finally allowed to
condense to water in a condenser at constant pressure (step 41), thereby removing
heat from the cycle. The same process repeats continuously.
Figure 2: Rankine cycle
In thermal power plants, however, different applications of the Rankine cycle exist.
Various stages of turbines can be added for the expansion of steam so as to maximize
the efficiency of the cycle.
Figure 3 below shows the schematic of a basic thermal power plant. The pulverized
coal from the coal mill enters the furnace where combustion takes place. The heat
generated turns the water into steam which is used to rotate the steam turbine which,
in turn, drives the generator. After the steam passes through the steam turbine, it is
heated again.
Vaporizer
Condenser
P
ExpanderPump
1
2
3
4
Annexure-3
117
Page 7 of 61 Printed 2015-01-15 09:29
Figure 3: Schematic of a general thermal power plant
The plant can be divided into four main circuits, namely:
Fuel and Ash circuit
The coal from the storage is fed to the boiler via coal handling plant. The
Ash produced after the combustion process is collected and moved to the
ash handling plant.
Air and Gas circuit
Air from the atmosphere is supplied to the furnace via induced draught
fans (ID) and/or forced draught (FD) fans. The air before passing to the
furnace is preheated in the Air preheater using the heat of the flue gases.
The flue gases first pass through the boiler tubes in the furnace, next
through a precipitator or dust collector and then through the economizer.
Finally, the flue gases are released through the chimney.
Feed water and steam circuit
The condensate leaving the condenser is first heated through extracted
steam from the turbine. The feed water then passes through a deaerator
and HP heaters before it goes into the boiler through the economizer. The
wet steam from the boiler drum is further heated in the superheater before
it is sent to the high pressure turbine. After the expansion of steam in the
HP turbine, it is retaken to the boiler for reheating before it passes through
the intermediate pressure turbine and low pressure turbine. From the LP
turbine, the steam after expansion condenses to water in the condenser.
Cooling water circuit
A continuous flow of cooling water is required to condense the steam in
the condenser and also to maintain a low pressure in it.
LP Turbine
Furnace
Deaerator
HP
heaters
IP
TurbineHP
Turbine Generator
Condenser
Boiler
Drum
LP
heaters
Chimney
Dust
collector
Coal
hopper
Pulveriser
Air
Hot airPulverised
Coal
Flue
gases
Annexure-3
118
Page 8 of 61 Printed 2015-01-15 09:29
Unlike hydro power plants, where water is always available for load changes, a
thermal power plant has limited ability to handle large load changes. It is commonly
known that boiler response is rather slow, that drum level variations may be critical
etc. However, by designing and tuning for optimal dynamic performance,
improvements can usually be achieved.
2.3 Details of tested unit
Some additional information is required to understand the operation of the tested
unit. Figure 4 shows a simplified schematic of the steam system diagram above, but
with some additional details that are explained below.
LP Turbine
Furnace
HP
heaters
IP
Turbine
HP
Turbine Generator
Condenser
Boiler
Drum
LP
heaters
Air
Pulverised
Coal
Flue
gases
HP
Valve
HP
Bypass
IP
Valve
LP
Bypass
Feed
water
Figure 4: Schematic diagram of the steam system of the tested unit.
HP bypass = valve for shunting steam past the HP turbine. The HP bypass increases
the steam consumption from the boiler without increasing the generated load and is
used for reducing the steam pressure in case of overpressure, which may occur when
the turbine is using less steam than the boiler produces. This valve is normally closed
but opened partially during one of the tests performed.
LP bypass = valve for shunting steam past the IP and LP turbines. This valve was
closed during all of the tests performed.
IP valve = IP turbine steam inlet valve, which is used for controlling the pressure in
the reheater. The valve normally fully open but closes partially in case of high HP
steam pressure and small HP valve opening, which occured during some of the tests
performed.
Annexure-3
119
Page 9 of 61 Printed 2015-01-15 09:29
2.4 Governor
The governor has the following control modes/functions for normal operation
1. FGMO (Free Governor Mode of Operation) is a power/frequency control
mode in which a load offset is calculated from the measured frequency using
an adjustable gain function which is set to produce the desired droop, which
in this case is 5 % (the adjustment range is 2.5 to 8 %). The frequency
dependent load offset is limited to ± 5 % of rated load, which consequently
limits the frequency range for the response in FGMO operation. (It can be
noted that for other types of units, for example hydro power, there is usually
no such limitation for the frequency dependent load adjustment.) The load
offset is added to the load setpoint and the resulting load value is used as
setpoint by the load controller, which in turn is a PI controller which controls
the generated load by adjusting the HP valve position. The load controller
uses the measured active power as feedback. Figure 5 shows a simplified
block diagram for this control mode and Figure 6 shows the load/frequency
characteristic for the stationary condition in this mode. The load offset is zero
when the frequency is exactly 50 Hz. FGMO is suitable for islanding but
requires some adjustments for optimal performance.
2. Co-ordinated mode control (CMC). In this mode, the HP valve opening is
coordinated with the boiler to keep the steam pressure stable. The generated
load is basically according to the steam production.
3. RGMO is implemented on this unit but, on request fron NTPC, this mode was
not tested by Solvina. The implementation is made in the Co-ordinated mode
control and increases the fuel infeed to the boiler depending on the grid
frequency and with a certain droop and deadband. The generated load
changes with the steam production. This makes the response very slow
(several minutes) but the method ensures that the unit operation remains
stable. Though being slow, it will have a beneficial effect on the long term
frequency stability of the national grid.
There is also a separate speed controller but it is only used for idling and
syncronization purposes.
Furthermore, the governor contains a number of additional functions for ensuring
safe operation, for example:
1. The pressure controller may take over the control of the HP valve in case of
large HP steam pressure deviations, typically by reducing the generated load
in case the steam pressure becomes too low.
2. The over pressure limiter will open the HP bypass valve in case the HP steam
pressure becomes too high.
3. The IP valve is controlled together with the HP valve for maintaining the
pressure in the reheater.
Annexure-3
120
Page 10 of 61 Printed 2015-01-15 09:29
Figure 5. Simplified block diagram for FGMO.
Figure 6. Load/frequency characteristic in FGMO mode. The slope is adjusted
according to the droop.
Generator
frequency
Droop
setting
P(f)
Lim
±5%
Load
setpoint
Active
power
Load
controller
To HP
valve Selector
Pressure
controller
x
Frequency
sensitivity
on/off
Generator
frequency
Load setpoint +5%
50.00
Hz
Load setpoint -5%
Load setpoint
49.87
Hz
50.13
Hz
Annexure-3
121
Page 11 of 61 Printed 2015-01-15 09:29
Figure 7. Parts of governor front panel: Speed controller (upper) and load controller
including FGMO circuitry (lower). The location of the droop control knob is
indicated with an arrow.
Annexure-3
122
Page 12 of 61 Printed 2015-01-15 09:29
3 DESCRIPTION OF TESTS PERFORMED
3.1 Definitions
Simulated frequency: This is the signal generated by the test
equipment, SSPS.
It can be used as input to the
frequency/speed controller instead of the
actual speed from the frequency/speed
sensor.
Actual frequency: Signal from generator frequency/speed
sensor.
Generated load: Active power of generating unit
System load: Total active power consumption in the
grid
Simulated system load System load simulated in the test
equipment
System base load: Start value of simulated system load when
starting the island simulation test.
Annexure-3
123
Page 13 of 61 Printed 2015-01-15 09:29
3.2 Method for island operation testing
Solvina has developed a test equipment to be used for evaluation of the island
operation capability of power turbines. The equipment is called SolvSim Power
Station, SSPS.
The test method uses the principle of “HardWare In the Loop”, i.e. a simulator
simulating that a small power system is connected to the speed governor of a turbine.
The speed controller will then act as if it is actually running in island operation. The
active power produced by the turbine is measured and summed up with simulated
contributions to calculate the active power balance of the simulated island.
Gen.
Grid
Turbine
Mea
sure
d Si
gnal
s
Governor
Simulated
island
Actual Frequency
Simulated
FrequencySSPS
Relay
Figure 8: Hardware-in-the-loop simulation of island operation.
Models of loads as well as other power producers can be included in the model of the
electric island.
Using the active power balance and the total moment of inertia of the island, the
island frequency can be calculated and fed back to the speed controller of the turbine
tested. In this way, the capability of running in island operation can be tested while
the turbine is still synchronized to a strong grid.
SSPS is also used to inject simulated frequency steps for primary response tests.
On this particular unit, the connection of the simulated frequency was different from
the normal case shown above. Instead of switching between actual and simulated
frequency, the switching was made between a fixed signal corresponding to 50.00 Hz
and the simulated frequency.
Annexure-3
124
Page 14 of 61 Printed 2015-01-15 09:29
3.3 Test procedure
3.3.1 Test equipment/function/signal check
Before commencement of actual tests, all the values/scalings of the measured signals
and the installation of the test equipment were checked to ensure correct
measurements and safe operation. The switching between the actual and the
simulated frequency was tested several times to verify a bumpless transition. The
internal safety functions of the SSPS system were also verified.
3.3.2 Step response tests
Initially, before beginning the test sequence, the simulated frequency was kept at
50Hz. The primary response was tested by injecting a frequency step to the governor
frequency input. The frequency step was calculated from the droop settings, to
produce an generated load change of up to approx. 5% of rated load.
The step tests with FGMO engaged in governor were performed at 75%, 90% and
100% of rated generated load with positive and negative steps in frequency.
3.3.3 Small island tests
This test was performed to assess the ability of the turbine to control the frequency as
sole production on an island grid. Simulated load steps of different sizes were
intended to be applied but this could not be done since the island operation was
unstable (see section 4.3). The tests were repeated at 75% and 90% generated load
with FGMO engaged in governor.
For the tests at Dadri Unit -4, Table 2 below summarizes the grid model with a total
simulated system base load of 155 and 190 MW respectively. The simulated system
load comprises frequency dependent and frequency independent loads.
Table 2 Simulator parameters for small island test.
System
Base load
Rated apparent
power (Sn) of
generator
System load with
linear frequency
characteristic
System load without
frequency
dependence, no inertia
Small
Island
@75%
155 MW 247 MVA
(Inertia 3.52 s)
70 MW
(Inertia 0.70 s)
85 MW
Small
Island
@90%
190 MW
85 MW
(inertia 0.70 s)
105 MW
Annexure-3
125
Page 15 of 61 Printed 2015-01-15 09:29
3.3.4 Large island test
This test was performed to assess the ability of the turbine to control the frequency
together with other power plants on a local grid. All other power plants were
simulated to act according to power control. Simulated load steps of different sizes
were applied (see section 4.4) to determine the size of the load changes that the
power plant could handle.
The summary of the total simulated base load was 2000 MW. Table 3 below
summarizes the grid model. The simulated load comprises frequency dependent and
independent loads.
Table 3 Simulator parameters for large island test
Total
system
base load
Rated
apparent
power (Sn) of
generator
System load with
linear frequency
characteristic
System load
without
frequency
dependence,
no inertia
Additional
simulated
power
plants
Large
island:
2000 MW
247 MVA
(Inertia 3.52 s)
1000 MW
(Inertia 0.70 s) 1000 MW
2000 MVA
(Inertia 4.0 s)
2000 MW
Annexure-3
126
Page 16 of 61 Printed 2015-01-15 09:29
3.4 Recorded signals
The following signals were recorded during the tests for analysis of the unit
performance, including the boiler and steam system:
Simulated frequency = the frequency signal injected into the governor from the test
equipment SSPS (switched between simulated signal and a fixed signal
corresponding to 50 Hz).
Active power = generated load of the unit, as measured by a transducer from PT and
CT outputs.
Frequency correction = output from limiter in Figure 5, corresponding to the load
offset added to the load setpoint
HP valve position = opening position of HP turbine steam inlet valve, which is the
main valve for controlling the steam flow to the turbine and hence also the generated
load.
IP valve position = opening position of IP turbine steam inlet valve, which is used
for controlling the pressure in the reheater. This valve is normally fully open but
closed partially during some of the tests performed (Step response 75/900/100%).
HP pressure = steam pressure before HP valve, corresponding to pressure at
overheater outlet.
IP pressure = steam pressure before IP valve, corresponding to pressure at reheater
outlet.
Feed water flow = flow of feed water into boiler. This is controlled to keep the
boiler drum level within limits.
Boiler drum level = level of water in the steam drum, should ideally be kept
constant by the feed water control.
HP bypass = opening position of valve for shunting steam past the HP turbine. The
HP bypass increases the steam consumption from the boiler without increasing the
generated load and is used for reducing the steam pressure in case of overpressure.
This valve is normally closed but opened partially during one of the tests performed
(Step response 75%).
LP bypass = opening position of valve for shunting steam past the IP and LP
turbines. This valve was closed during all of the tests performed.
Reactive power = reactive output of generator, positive corresponding to lagging
system load.
Generator voltage = AC voltage measured at generator terminal PTs.
Actual frequency = frequency of the voltage measured at generator terminal PTs.
Total Load = Simulated system load on island grid (only for island test).
Additionally, some signals were monitored for safety reasons and for facilitating
trouble shooting in case of unexpected problems. These are omitted from the list
above.
Annexure-3
127
Page 17 of 61 Printed 2015-01-15 09:29
4 TEST RESULTS
4.1 Executive summary
4.1.1 Primary frequency response
Step response tests were performed at 75%, 90% and 100% of rated generated load.
FGMO works as expected and the magnitude of response is according to the droop
settings. The generated load response in the step tests corresponds to 5% droop. The
response time T67 is very fast, in the range 2-8 seconds, and it has a distinct
overshoot, all due to the settings of the load controller.
Due to slow boiler control, the changes in generated load cause a slow but large
variation in the HP steam pressure. The upper limit of steam pressure was reached
and the HP bypass valve operated during the step response tests at 75%.
4.1.2 Island operation
The small island tests were performed at 75% and 90% load levels respectively with
a droop setting of 5% initially. The unit was unable to handle islanding operation at
both load levels. As soon as the simulated frequency was switched in, growing
oscillations occurred and the simulation was aborted. The tests were repeated with
droop setting of 8% at both load levels of 75% and 90%. The results, however,
remained unchanged. It was concluded that the unit is unable to operate during
islanding operation as sole production on the grid. This is all due to the settings of
the load controller.
The unit was capable of keeping the frequency stable on a large island grid while
using the inertia of other units for stability. System load steps of up to ±14 MW were
applied, which caused frequency deviations of only up to ±0.2 Hz.
Annexure-3
128
Page 18 of 61 Printed 2015-01-15 09:29
4.2 Primary frequency response, step response tests in FGMO
The step response tests are carried out to investigate how well the plant supports the
power system at frequency changes of the grid. The speed droop is the parameter that
decides the magnitude of response. The response has two characteristics that are
interesting to examine, the magnitude and the time constant (67% value, T67).
For the tests in FGMO mode the droop setting during test was 5%.
Steps were carried out to give up to 5% load change, which is approx. 10.5 MW, and
the frequency step size giving that response would be 0.05*0.05*50 = 0.125 Hz.
Consequently 10.5 MW is the expected response for the steps to be carried out.
Similarly, expressed in MW/Hz, the response is expected to be 84 MW/Hz for any
step (10.5/0.125), given a rated generated load of 210 MW.
For the following figures, the legend is as below:
Blue Simulated frequency.
Light blue Grid frequency (equal to the generator frequency) during
test.
Red Generated load (= measured active power).
Purple HP pressure.
Green Frequency correction voltage, corresponding to the setpoint
offset sent to the load controller from the droop circuitry.
Dark blue HP valve position.
Pink IP valve position.
Orange HP bypass valve position. This signal is only seen in the
figures where the valve is active.
Annexure-3
129
Page 19 of 61 Printed 2015-01-15 09:29
4.2.1 Step response in FGMO, generated load 75%, droop 5%
The step response tests were carried out at 75% generated load with 5 % droop.
Initially, some smaller steps were tested to determine the behaviour of the unit and to
check that the steps expected to cause 5 % generated load change could be handled
safely.
Table 4 Frequency steps in FGMO, generated load 75 %, droop 5%, part 1
Simulated
frequency
(Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
50 50.05 154 149 Approx.
-4.5
Approx.
90
2
(oscillating)
50.05 50 149.5 153.6 +4.1 82 3
5049.95 153.6 158 +4.4 88 3
49.9550 158 153.5 -4.5 90 4
With a droop setting of 5 %, a 0.05 Hz step is expected to cause a generated load
change of approx. 4 MW (84 MW/Hz).
Figure 9: Frequency steps in FGMO, generated load 75 %, part 1
Annexure-3
130
Page 20 of 61 Printed 2015-01-15 09:29
Figure 10: Frequency steps in FGMO, generated load 75 %, part 1. The frequency
correction signal, corresponding to the load setpoint offset, is proportional to
the deviation in simulated frequency.
Figure 11: Frequency steps in FGMO, generated load 75 %, part 1. The operation of the
HP, IP valve and the HP bypass valve is shown.
The test shows that the response of the generated load to a step change in frequency
is approximately in accordance with the droop settings. The response is very fast and
there is a small overshoot in the generated load. A small oscillation in the generated
load is seen in the beginning of the figures, this coincides with the IP valve being
partially closed.
Annexure-3
131
Page 21 of 61 Printed 2015-01-15 09:29
The test was continued with further steps.
Table 5 Frequency steps in FGMO, generated load 75 %, droop 5%, part 2
Simulated
frequency
(Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
5049.95 153.4 157.8 +4.4 88 2
49.9550 158.2 153.9 -4.3 86 2
5050.1 153.9 145.3 Approx.
-8.6
Approx.
86
3
The steam pressure increases to 136 bar and the HP bypass opens, but is closed by
manual intervention. Severe oscillations in the generated load occur. The output is
then manually increased for a short time to reduce the oscillations.
With a droop setting of 5 %, a 0.05 Hz step is expected to cause a generated load
change of approx. 4 MW, and, correspondingly, a 0.1 Hz step is expected to cause a
generated load change of approx. 8 MW (84 MW/Hz).
Figure 12: Frequency steps in FGMO, generated load 75 %, part 2
Annexure-3
132
Page 22 of 61 Printed 2015-01-15 09:29
Figure 13: Frequency steps in FGMO, generated load 75 %, part 2. The frequency
correction signal, corresponding to the load setpoint offset, is proportional to
the deviation in simulated frequency.
Figure 14: Frequency steps in FGMO, generated load 75 %, part 2. The operation of the
HP, IP valve and the HP bypass valve with increase in steam pressure is
shown.
Annexure-3
133
Page 23 of 61 Printed 2015-01-15 09:29
The test shows that the response of the generated load is in accordance with the
droop settings. The response is very fast and there is a certain overshoot in the
generated load.
The generated load depends on the HP steam pressure and the HP valve opening. As
a result, the HP valve opening varies in proportion to the generated load and in
reverse proportion to the HP steam pressure.
A small oscillation in the the HP and IP valves, and consequently also in the
generated load, in the beginning of the figures. This coincides with the IP valve
being partially closed. Later on, an larger oscillation is seen. The oscillation is
probably related to the tuning of the load controller. Frequency steps are seen by the
load controller as load setpoint steps since the droop calculation is a simple gain
function. The load controller has a very fast step response with a distinct overshoot in
the and a response time T67 of only a few seconds, to be compared to Dadri II unit 6
which has a response time T67 of 15-85 seconds and no overshoot. The overshoot
indicates a small stability margin and in that situation an increased total closed loop
gain or an additional delay can make the system unstable. It appears that the
operation if the IP valve causes either one (or possibly both) of these. The gain in the
load controller will have to be reduced significantly to ensure stable operation also in
a situation when the IP valve is active.
After the step 5050.1 Hz, the steam pressure increases steadily due to the slow
boiler control and reaches the upper limit. At approx. 136 bar, the HP bypass valve
operates to reduce the excess pressure. When the bypass is closed through manual
intervention, the oscillation grows drastically. Figure 15 shows the sequence in more
detail. The oscillation does not stop until the load is increased manually.
Figure 15: Zoom-in on previous figure. The operation of the HP, IP valve and the HP
bypass valve with increase in steam pressure is shown.
Annexure-3
134
Page 24 of 61 Printed 2015-01-15 09:29
When the generated load oscillated, severe oscillations were seen also in reactive
power and generator voltage, which were being monitored during the tests. Most
likely, it is the power system stabiliser (PSS) that causes these effects. The PSS
cannot sufficiently filter out the load changes caused by variations in the turbine
torque and therefore respond to these in a similar way as it responds to the power
oscillations that it is intended to counteract.
Figure 16: Active and reactive power during the oscillation of generated load shown in
previous figure.
Annexure-3
135
Page 25 of 61 Printed 2015-01-15 09:29
After the oscillations have been successfully stopped, the steam pressure decreases
steadily. The generated load depends on the HP steam pressure and the HP valve
opening. As a result, the HP valve opening varies in proportion to the generated load
and in reverse proportion to the HP steam pressure. Consequently, the HP valve
keeps opening to maintain the generated load. After around 10 minutes, the pressure
is so low that the HP valve has opened fully, and the generated load drops slightly.
As soon as the pressure starts increasing the HP valve begins to close to balance the
load at 154 MW. The sequence is shown in Figure 18. During all this time the
simulated frequency is kept at 50.1 Hz.
Figure 17: Frequency steps in FGMO, generated load 75 %. The 50.1 step is maintained
between part 2 and 3. The operation of the HP, IP valve and the HP bypass
valve with decrease in steam pressure is shown.
Annexure-3
136
Page 26 of 61 Printed 2015-01-15 09:29
The test was continued with further steps.
Table 6 Frequency steps in FGMO, generated load 75 %, droop 5%, part 3
Simulated
frequency
(Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
50.150 155 163 +8 80 3
5050.1 163 155 -8 80 2
50.150 154 163 +9 90 2
Load setpoint changed back to 154 MW.
5049.90 155 164 +9 90 6
49.9050 165 156 -9 90 7
With a droop setting of 5 %, a 0.1 Hz step is expected to cause a generated load
change of approx. 8 MW (84 MW/Hz).
Figure 18: Frequency steps in FGMO, generated load 75 %, part 3. At 10200 s the load
setpoint is increased manually.
Annexure-3
137
Page 27 of 61 Printed 2015-01-15 09:29
Figure 19: Frequency steps in FGMO, generated load 75 %, part 3. The frequency
correction signal, corresponding to the load setpoint offset, is proportional to
the deviation in simulated frequency.
Figure 20: Frequency steps in FGMO, generated load 75 %, part 3. The operation of the
HP and IP valve along with steam pressure and the generated load is shown.
The test shows that the response of the generated load is in accordance with the
droop settings. The response is very fast and there is a certain overshoot in the
generated load.
Annexure-3
138
Page 28 of 61 Printed 2015-01-15 09:29
The test was continued with further steps. With a droop setting of 5 %, a 0.125 Hz
step is expected to cause a generated load change of approx. 11 MW (84 MW/Hz).
For practical reasons the magnitude of the applied frequency step was rounded to
0.13 Hz.
Table 7 Frequency steps in FGMO, generated load 75%, droop 5%, part 4
Simulated
frequency (Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
5050.13 156 145 -11 85 3
The steam pressure increases to 125 bar and the HP bypass opens, but is the closed
by manual intervention. Severe oscillations in the generated load occur. The output
is then manually increased to reduce the oscillations.
With a droop setting of 5 %, a 0.125 Hz step is expected to cause a generated load
change of approx. 11 MW. For practical reasons the magnitude of the applied
frequency step was rounded to 0.13 Hz.
Figure 21: Frequency steps in FGMO, generated load 75 %, part 4
Annexure-3
139
Page 29 of 61 Printed 2015-01-15 09:29
Figure 22: Frequency steps in FGMO, generated load 75 %, part 4. The frequency
correction signal, corresponding to the load setpoint offset, is proportional to
the deviation in simulated frequency.
Figure 23: Frequency steps in FGMO, generated load 75 %, part 4. The operation of the
HP,IP and HP bypass valve during the excess steam pressure is shown.
Annexure-3
140
Page 30 of 61 Printed 2015-01-15 09:29
The generated load depends on the HP steam pressure and the HP valve opening. As
a result, the HP valve opening varies in proportion to the generated load and in
reverse proportion to the HP steam pressure. The step change from 5050.13 Hz
causes the HP valve to close in order to reduce the generated load according to the
droop settings. However, the closing of the HP valve and the slow boiler control
causes an increase in the steam pressure, which in turn makes the HP valve close
even more. On reaching the upper limit at approx. 124 bar, the HP bypass opens to
lower the excess steam pressure. During the operation of the bypass valve, an
oscillation is seen in the the HP and IP valves, and consequently also in the generated
load. The oscillation is shown in detail in Figure 24.
The occurence of the oscillation at the time the bypass valve opens does not
automatically imply that it is the bypass valve that causes the oscillation. More
likely, it is related to the IP valve operation together with the the load controller, as
discussed previously (for example, see Figure 15).
The bypass valve is closed through manual intervention and the oscillation is
stopped. The steam pressure still continues to increase and reaches approx. 127 bar.
To control the pressure, the generated load is increased manually for a few minutes
(seen as repeated steps in the figures above).
Figure 24: Zoom-in on previous figure. The operation of the HP, IP valve and the HP
bypass valve with increase in steam pressure is shown.
Once again, when the generated load oscillated, severe oscillations were seen also in
reactive power and generator voltage, which were being monitored during the tests.
the magnitude was simlar to that in Figure 16.
Annexure-3
141
Page 31 of 61 Printed 2015-01-15 09:29
The test was continued with further steps.
Table 8 Frequency steps in FGMO, generated load 75%, droop 5%, part 5
Simulated
frequency (Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
50.1350 145 156 +11 85 4
5050.13 155 145 -10 77 6
50.1350 145 156 +11 85 3
5049.87 156 167 +11 85 5
49.8750 167 156 -11 85 6
With a droop setting of 5 %, a 0.125 Hz step is expected to cause a generated load
change of approx. 11 MW. For practical reasons the magnitude of the applied
frequency step was rounded to 0.13 Hz (84 MW/Hz).
Figure 25: Frequency steps in FGMO, generated load 75 %, part 5
Annexure-3
142
Page 32 of 61 Printed 2015-01-15 09:29
Figure 26: Frequency steps in FGMO, generated load 75 %, part 5. The frequency
correction signal, corresponding to the load setpoint offset, is proportional to
the deviation in simulated frequency.
Figure 27: Frequency steps in FGMO, generated load 75 %, part 5.The operation of the
HP and IP valves is shown along with the generated load.
Annexure-3
143
Page 33 of 61 Printed 2015-01-15 09:29
The test shows that the response of the generated load is in accordance with the
droop settings. The response is very fast and there is a certain overshoot in the
generated load.
It can be concluded that despite the slow response from the boiler, the unit is still
able to maintain the level of the generated load and the results are in accordance with
the droop settings.
The overshoot in the response of the generated load for the last two steps is shown in
detail in Figure 28. As seen in Figure 26, the frequency correction signal that
corresponds to the load setpoint offset has no overshoot. The overshoot is instead
caused by a very high proportional gain setting in the load controller.
Figure 28: Zoom-in on previous figure. The operation of the HP valve is shown along
with the generated load.
Annexure-3
144
Page 34 of 61 Printed 2015-01-15 09:29
4.2.2 Step response in FGMO, generated load 90%, droop 5%
The tests in FGMO mode were carried at 90% generated load with droop 5%. The
result is shown in Figure 29 and Figure 30.
Table 9 Frequency steps in FGMO, generated load 90 %, droop 5%, part 1
Simulated
frequency
(Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant,
T67 (s)
5050.05 190 185.4 -4.6 92 5
50.0550 185.5 190 +4.5 90 4
5049.87 190 200 +10 77 6
49.8750 200 190 -10 77 8
With a droop setting of 5 %, a 0.05 Hz step is expected to cause a generated load
change of approx. 4 MW and a 0.13 Hz step is expected cause a generated load
change of approx. 11 MW (84 MW/Hz).
The test was continued with further steps. The result is shown in Figure 31 and
Figure 32.
Table 10 Frequency steps in FGMO, generated load 90 %, droop 5%, part 2
Simulated
frequency
(Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant,
T67 (s)
5050.13 190 179 -11 85 4
50.1350 179 190 +11 85 3
With a droop setting of 5 %, a 0.13 Hz step is expected cause a generated load
change of approx. 11 MW.
The response of the frequency correction signal is similar to the one seen at 75%
generated load and is therefore omitted here.
Annexure-3
145
Page 35 of 61 Printed 2015-01-15 09:29
Figure 29: Frequency steps in FGMO, generated load 90 %, part 1.
Figure 30: Frequency steps in FGMO, generated load 90 %, part 2. The operation of the
HP and IP valves is shown along with the generated load.
The test shows that the response of the generated load is in accordance with the
droop settings. The response is very fast and there is a certain overshoot in the
generated load. No major problems related to the steam pressure are seen.
Annexure-3
146
Page 36 of 61 Printed 2015-01-15 09:29
Figure 31: Frequency steps in FGMO, generated load 90 %, part 2.
Figure 32: Frequency steps in FGMO, generated load 90 %, part 2. The operation of the
HP and IP valves is shown along with the generated load.
The test shows that the response of the generated load is in accordance with the
droop settings. The response is very fast and there is a certain overshoot in the
generated load. No major problems related to the steam pressure are seen.
Annexure-3
147
Page 37 of 61 Printed 2015-01-15 09:29
4.2.3 Step response in FGMO, generated load 100%, droop 5%
The same procedure as above tests is repeated at 100 % generated load. The result is
shown in Figure 33 and Figure 34.Figure 33: Frequency steps in FGMO,
generated load 100 %, part 1.
Table 11 Frequency steps in FGMO, generated load 100 %, droop 5%, part 1.
Simulated
frequency (Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
5050.05 211.2 207.3 -3.9 78 6
50.0550 207.6 211.8 +4.2 84 5
50 50.13 211.5 201 -11 85 6
50.1350 201 211 +11 85 5
With a droop setting of 5 %, a 0.05 Hz step is expected to cause a generated load
change of approx. 4 MW and a 0.13 Hz step is expected cause a generated load
change of approx. 11 MW (84 MW/Hz).
The test was continued with further steps. The result is shown in Figure 35 and
Figure 36.
Table 12 Frequency steps in FGMO, generated load 100 %, droop 5%, part 2.
Simulated
frequency (Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
5049.87 211 218 +7* 54 -
49.8750 218 211 -7* 54 -
5049.87 211.9 222.4 +10.5 80 7
49.8750 222 211 +10.5 80 8
*) Due to insufficient steam pressure
The generated load depends on the HP steam pressure and the HP valve opening. As
a result, the HP valve opening varies in proportion to the generated load and in
reverse proportion to the HP steam pressure. At the first step 5049.87 Hz, the
steam pressure is low and drops further as the generated load is being increased.
Since the steam pressure is insufficient to produce the desired generated load, the HP
valve opens to its maximum, but still without fully reaching 105 % generated load.
At the instant of the step back to 50 Hz, the HP valve takes some time to close from
the fully open position, causing a delayed response.
The steam pressure is allowed to increase before the second attempt.
The response of the frequency correction signal is similar to the one seen at 75%
generated load and is therefore omitted here.
Annexure-3
148
Page 38 of 61 Printed 2015-01-15 09:29
Figure 33: Frequency steps in FGMO, generated load 100 %, part 1.
Figure 34: Frequency steps in FGMO, generated load 100 %, part 1. The operation of
the HP and IP valves is shown along with the generated load.
The test shows that the response of the generated load is in accordance with the
droop settings. The response is very fast and there is a certain overshoot in the
generated load. No major problems related to the steam pressure are seen.
Annexure-3
149
Page 39 of 61 Printed 2015-01-15 09:29
Figure 35: Frequency steps in FGMO, generated load 100 %, part 2.
Figure 36: Frequency steps in FGMO, generated load 100 %, part 2. The operation of
the HP and IP valves is shown along with the generated load.
The test shows that the response of the generated load is in accordance with the
droop settings, provided that there is sufficient steam production. The response is
very fast and there is a certain overshoot in the generated load.
Annexure-3
150
Page 40 of 61 Printed 2015-01-15 09:29
4.2.4 Notes concering island operation
The different effects seen in the step response tests above could have serious effects
if they occured during island operation.
The intervention of the pressure controller makes the load/frequency controller
unable to control the frequency. The island grid would most likely collapse in this
case and the unit trip unless immediate (within seconds) load shedding of correct size
is made. The same goes for the case when the HP valve opens fully due to
insufficient steam pressure.
The opening of the HP bypass valve would however not have such dramatic
consequences. Since the HP valve is still controlled by the load/frequency controller,
the frequency of the grid would only suffer a minor disturbance.
The oscillations seen in some situations would in themselves not be a big problem as
long as they are sufficiently small, although the island grid frequency would
fluctuate. Large oscillations would cause excessive grid frequency deviations and
the island grid would most likely collapse in this case and the unit would trip. It
must be remembered that it will not be possible to manually adjust the generated
load at the power plant during island operation as sole production. The generated
load will then always be equal to the system load in the island grid.
Annexure-3
151
Page 41 of 61 Printed 2015-01-15 09:29
4.3 Island operation tests – Small island
This test shows the ability of the plant to control the frequency when the tested unit
is the only generating source of the system. By simulating system load changes of the
simulated island, the simulated frequency will change. The tested unit will try to
control the simulated frequency. This way, it can be seen if the unit is stable. Ideally,
balance between generated load and system load will be reached quickly and the
frequency will stabilise.
However, for this unit, the frequency control was not stable enough for the unit to
operate as the only generating source of the system. As soon as the simulation was
started, a quickly growing oscillation started and the simulation had to be aborted
before any simulated system load steps could be applied.
It was decided that the tests would be made at 75% and 90% load. The tests were
made with droop settings of 5%, but also a droop of 8% was tested to determine
whether this would improve the stability due to a lower total system gain. This was
not the case. It was, for safety reasons, not possible to test any other governor
settings to improve the performance while the power plant was running.
For the following figures, the legend is as below:
Blue Simulated frequency. This denotes the grid frequency in
real Island operation.
Light blue Grid frequency (equal to the generator frequency) during
test.
Red Generated load (= measured active power). This denotes
the mechanical turbine load in real island operation.
Purple HP pressure
Green Frequency correction voltage, corresponding to the setpoint
offset sent to the load controller from the droop circuitry.
Dark blue HP valve position
Pink IP valve position
Dark green Simulated system load
Note that the time scale of the island test figures is zoomed in compared to the
figures for step response tests.
Since the simulated load is partially frequency dependent, it will deviate from the
final value when the frequency is not equal to 50 Hz. This has a small stabilizing
effect on the simulated island grid, although in this case far from enough to keep the
operation stable.
Annexure-3
152
Page 42 of 61 Printed 2015-01-15 09:29
4.3.1 Small Island test, generated load 75%, droop 5%
The test was carried out at 75% of rated generated load and with 5% droop. As soon
as the simulation was started, a growing oscillation began. The simulation was
aborted to avoid excessive load swings and no simulated system load steps were
applied.
Figure 37: Small Island test, generated load 75%, droop 5%. The simulation is started at
A and aborted at B.
A B
Annexure-3
153
Page 43 of 61 Printed 2015-01-15 09:29
Figure 38: Small Island test, generated load 75%, droop 5%. The frequency correction,
corresponding to the load setpoint offset, is proportional to the deviation in
simulated frequency but is limited at 0.4 volts.
Figure 39: Small Island test, generated load 75%, droop 5%. The operation of the HP
and IP valves is shown along with the generated load.
It was concluded that the unit could not handle islanding operation as the sole
production on the grid.
Annexure-3
154
Page 44 of 61 Printed 2015-01-15 09:29
4.3.2 Small Island test, generated load 75%, droop 8%
The test above was repeated with 8% droop. Also in this case, a growing oscillation
began a soon as the simulation was started, but at a somewhat slower rate. The
simulation was aborted to avoid excessive load swings and no simulated system load
steps were applied.
Figure 40: Small Island test, generated load 75%, droop 8%. The simulation is started at
A and aborted at B.
A B
Annexure-3
155
Page 45 of 61 Printed 2015-01-15 09:29
Figure 41: Small Island test, generated load 75%, droop 8%. The frequency correction,
corresponding to the load setpoint offset, is proportional to the deviation in
simulated frequency but is limited at 0.4 volts.
Figure 42: Small Island test, generated load 75%, droop 8%. The operation of the HP
and IP valves is shown along with the generated load.
It was concluded that an increased droop to 8 % was not sufficient to achieve stable
island operation.
Annexure-3
156
Page 46 of 61 Printed 2015-01-15 09:29
4.3.3 Small island – generated load 90%, droop 5%
The test was carried out also at 90% of rated generated load and with 5% droop. As
soon as the simulation was started, a growing oscillation began. The simulation was
aborted to avoid excessive load swings and no simulated system load steps were
applied.
Figure 43: Small Island test, generated load 90%, droop 5%. The simulation is started at
A and aborted at B, after which the simulated frequency is ramped back.
A B
Annexure-3
157
Page 47 of 61 Printed 2015-01-15 09:29
Figure 44: Small Island test, generated load 75%, droop 5%. The frequency correction,
corresponding to the load setpoint offset, is proportional to the deviation in
simulated frequency but is limited at 0.4 volts.
Figure 45: Small Island test, generated load 90%, droop 5%. The operation of the HP
and IP valves is shown along with the generated load.
It was concluded that the unit could not handle islanding operation as the sole
production on the grid.
Annexure-3
158
Page 48 of 61 Printed 2015-01-15 09:29
4.3.4 Small island – generated load 90%, droop 8%
The test above was repeated with 8% droop. Also in this case, a growing oscillation
began a soon as the simulation was started. The simulation was aborted to avoid
excessive load swings and no simulated system load steps were applied.
Figure 46: Small Island test, generated load 90%, droop 8%. The simulation is started at
A and aborted at B.
A B
Annexure-3
159
Page 49 of 61 Printed 2015-01-15 09:29
Figure 47: Small Island test, generated load 90%, droop 8%. The frequency correction,
corresponding to the load setpoint offset, is proportional to the deviation in
simulated frequency.
Figure 48: Small Island test, generated load 90%, droop 8%. The operation of the HP
and IP valves is shown along with the generated load.
It was concluded that an increased droop to 8 % was not sufficient to achieve stable
island operation.
Annexure-3
160
Page 50 of 61 Printed 2015-01-15 09:29
4.4 Island operation tests – Large island
This test was performed to assess the ability of the turbine to control the frequency
together with other power plants on a local grid with a total production of approx.
2000 MW. The summary of the simulated base load is described in section 3.3.4. The
large island tests were performed at 90% of rated generated load. Simulated system
load steps were applied and the frequency deviations were recorded. The droop
setting during test was 5%. Figures for all steps except the two first are presented
below.
Table 13 Simulated large island operation, generated load 90 %, all applied steps.
Total range of
generated load
(MW)
Simulated system load
step (MW)
Max. frequency
deviation, Δf (Hz)*
190-202 MW
+5 MW -0.06
-5 MW +0.06
+10 MW -0.12
-10 MW +0.12
+12 MW -0.15
-12 MW +0.15
+14 MW -0.18
-14 MW +0.20
*Please note: All frequency deviations are measured from the instant the step is
applied.
For convenience, the simulated system load is shown using the same scale as the
generated load. For this reason, an offset of 1840 MW (being the total output of the
other simulated power plants) has been subtracted from the simulated system load
curve.
Annexure-3
161
Page 51 of 61 Printed 2015-01-15 09:29
Figure 49: Simulated large island operation, generated load 90 %, load steps ±10 MW.
The simulated system load has an offset of 1840MW subtracted.
Figure 50: Simulated large island operation, generated load 90 %, load steps ±10 MW.
The frequency correction, corresponding to the load setpoint offset, is
proportional to the deviation in simulated frequency. No limit is reached.
Annexure-3
162
Page 52 of 61 Printed 2015-01-15 09:29
Figure 51: Simulated large island operation, generated load 90 %, load steps ±10 MW.
HP pressure, HP bypass valve, HP valve are shown together with the
generated load.
Annexure-3
163
Page 53 of 61 Printed 2015-01-15 09:29
Figure 52: Simulated large island operation, generated load 90 %, load steps ±12 MW.
The simulated system load has an offset of 1840MW subtracted.
Figure 53: Simulated large island operation, generated load 90 %, load steps ±12 MW.
The frequency correction, corresponding to the load setpoint offset, is
proportional to the deviation in simulated frequency but is limited at 0.4 volts.
Thie limit is reached only briefly.
Annexure-3
164
Page 54 of 61 Printed 2015-01-15 09:29
Figure 54: Simulated large island operation, generated load 90 %, load steps ±12 MW.
HP pressure, HP bypass valve, HP valve are shown together with the
generated load.
Annexure-3
165
Page 55 of 61 Printed 2015-01-15 09:29
Figure 55: Simulated large island operation, generated load 90 %, load steps ±14 MW.
The simulated system load has an offset of 1840MW subtracted.
Figure 56: Simulated large island operation, generated load 90 %, load steps ±14 MW.
The frequency correction, corresponding to the load setpoint offset, is
proportional to the deviation in simulated frequency but is limited at 0.4 volts.
The signal is at the limit as long as the load step is maintained.
Annexure-3
166
Page 56 of 61 Printed 2015-01-15 09:29
Figure 57: Simulated large island operation, generated load 90 %, load steps ±14 MW.
HP pressure, HP bypass valve, HP valve are shown together with the
generated load.
The test shows that the unit responds well to a load steps on a large grid, and thanks
to the large total inertia it is able to keep the frequency stable. The stability margin is
however relatively small. This is seen in the oscillatory behaviour when the
frequency correction signal is not in limitation. The largest simulated load steps
applied were ±14 MW, causing a maximum frequency deviation of ±0.2 Hz. The test
was halted after these steps as they were estimated to be at the limit of what the unit
could handle.
The response of the unit is limited to around 5 % of rated generated load. This
limitation is seen clearly in the figures showing the frequency correction signal after
the +12 and +14 MW steps. After the step of +14 MW, the generated load is held
back continuously by this limit and it is the frequency denendence of the simulated
grid that prevents the frequency form dropping further. A slightly larger load step
would have caused a significantly larger frequency deviation, as was seen during the
tests at Dadri II unit 6 which has a similar type of limitation.
The steam pressure fluctations were relatively small during the test.
Annexure-3
167
Page 57 of 61 Printed 2015-01-15 09:29
5 CONCLUSIONS
5.1 FGMO
FGMO works as expected and the magnitude of response is approx. according to the
droop settings. The generated load response in the step tests corresponds to 5 %
droop. The response time T67 is very fast, in the range 2-8 seconds, and it has a
distinct overshoot. This is due to the settings of the load controller. The load
controller is also the cause for that the load control system itself started oscillating
under certain conditions when the IP valve was active.
Due to slow boiler control, the changes in generated load cause a slow but large
variation in the HP steam pressure. The upper limit of steam pressure was reached
and the HP bypass valve operated during the step response tests at 75%. The load
control system itself started oscillating under certain conditions when the IP valve
was active.
In order to safely operate the plant in FGMO while connected to the national grid and
without manual interventions, the boiler control will have to be revised and the load
controller will require improved tuning.
5.2 ISLAND OPERATION
5.2.1 Small Island test:
The small island tests were performed at 75% and 90% load levels respectively with
a droop setting of 5% initially. The unit was unable to handle islanding operation at
both load levels. As soon as the simulated frequency was switched in, growing
oscillations occurred and the simulation was aborted.
The tests were repeated with droop setting of 8% at both load levels of 75% and
90%. The results, however, remained unchanged and the simulation was aborted.
Unfortunately, it was for safety reasons not possible to test any other governor
settings to improve the performance while the power plant was running.
It was concluded that the unit is unable to operate during islanding operation as sole
production on the grid.
5.2.2 Large island test
The unit was capable of keeping the frequency stable on a large island grid while
using the inertia of other units to for stability. System load steps of up to ±14 MW
were applied, which caused frequency deviations of only up to ±0.2 Hz.
Annexure-3
168
Page 58 of 61 Printed 2015-01-15 09:29
6 RECOMMENDATIONS
The results from the tests were analyzed to see what could further be done to
improve the performance. In this section some recommendations are presented.
6.1 Normal (grid connected) operation
The tuning of the load controller will have to be revised for stable operation in
FGMO. At present, the gain is very high and severe oscillations have been observed
in conditions when the IP valve is active. The gain should be reduced at least as
much as is necessary to provide stable load control in all steam system conditions,
which probably means a reduction by 50 % or more. The integration time and other
parameters may also need adjustment. Normally, the gain set to give a moderately
slow response with a time constant T67 being tens of seconds or even a few minutes.
The boiler control is in its present state ill fitted running the unit in FGMO or any
other control mode in which anything else than the steam pressure controls the HP
valve. The pressure fluctuates severely just from load changes of 5 %. Boiler control
is slow by nature but it should be possible to improve stability by using
1. a feed-forward function so that the fuel input is increased already when the
generated load is increased, instead of when the pressure has dropped.
2. improved control parameter tuning.
Also the governor limit of ±5 % affects the ability to operate in FGMO. With a droop
of 5 %, the generated load will be at its upper limit for a grid frequency of 49.87 Hz
and at its lower limit at 50.13 Hz. The grid frequency, however, is at present varying
between 49.7 and 50.3 Hz. With a droop of 5 %, this corresponds to load variations
of ±12.5 %, which would very difficult for the steam system to handle if the
variations are fast. The governor limit is thus probably necessary to limit the stress
on the steam system, but if the boiler control is improved it could probably be
extended somewhat. Nevertheless, for successful FGMO operation, assuming that a
quick response is required, it may be a good idea to increase the droop. The response
for a given frequency change would be smaller but the response would be present in
a larger frequency range.
It should however be considered that thermal units such as this should not participate
in the short term frequency control of the grid (using FGMO) other than in grid
emergency situations, but rather in the long term frequency control (using RGMO in
combination with Co-ordinated mode control such as it is implemented here), for
which the unit is better adapted.
6.2 Island operation
Load controller tuning is necessary also if island operation as sole production on a
grid is desired. The present parameters make it impossible to achieve stable island
operation. The gain reduction required can be determined for example by simulated
island tests as the one performed, or by simulations provided that sufficient model
data can be obtained. The best path would however be to perform this tuning at the
time of commissioning of the new control system that is scheduled in a year.
Annexure-3
169
Page 59 of 61 Printed 2015-01-15 09:29
Furthermore, a digital controller makes it possible to arrange a special control mode
for islanding which can be tuned without affecting the load control of normal
operation. This mode may, but does not have to be, the same as the FGMO for grid
connected operation.
The same issues with the boiler control that are described above apply also during
islanding conditions, but the consequences of being unable to maintain the steam
pressure will be much worse. The most important issue during island operation as the
sole prodution on a grid is that the steam pressure must never be allowed to drop so
low that the generated load is reduced by the pressure control. In that case the island
grid will collapse and the unit will probably trip. When operating in islanding
together with other units on a large island grid, the task of frequency control would
be placed on the other units. Overpressure, on the other hand, can be handled by the
bypass valves and is not such a big problem in itself, provided that the steam system
remains stable.
If load controller tuning (or FGMO/island mode implementation) is successful, it
will be the steam system that puts the limit for how large island loads that can be
connected at a time. The frequency control itself would be capable of handling
relatively large load changes on an island grid, provided that the governor limit of ±5
% is sufficiently extented. It can anyway be assumed that the controller will have be
significantly slower to enable stable island operation. It is therefore estimated that the
limit should be at least in the order of ±10 % during island operation to handle a grid
load change of ±5 % well.
As always during island operation, it will be the responsibility of the grid operator to
keep the size of the load connections sufficiently small for the power plant to handle,
and communication between the grid operator and the power plant operator will be
necessary to ensure that the power plant, especially considering the steam system
conditions, is ready each time more load is to be connected to the island grid.
After a load is connected to (or disconnected from) the island grid, and the frequency
has stabilised, the stationary frequency will be different from 50 Hz due to the droop.
It will then be necessary to bring the frequency back to 50 Hz by adjusting the load
setpoint to be equal to the generated load at the time, thereby ensuring that the
stationary frequency does not get too close to the governor limit, outside which there
is no further response to frequency variation. The wider the limit is, the easier this
handling will be.
In an emergency situation requiring island operation, one possible way of keeping
the steam system parameters within limits could be to manually set the boiler output
slightly higher than the steam flow required for a generated load equal to the highest
expected island grid load at the time, thereby ensuring that the steam pressure never
drops too low to provide the required generated load. The resulting overproduction of
steam would then have to be handled by the bypass valves to keep the pressure
within limits, which of course requires stable bypass control. This way of operating a
unit has been successfully tested at simulated island tests on at least one thermal unit
in Sweden.
For best frequency stability during islanding, especially in a situation where the unit
is the sole production on an island grid, the feedback signal to the load controller
should not be the measured active power, but a signal corresponding to the active
power but calculated from the HP valve position (with adjustment for HP steam
Annexure-3
170
Page 60 of 61 Printed 2015-01-15 09:29
pressure and possibly other parameters). This applies for islanding only and is best
handled by a software function that automatically changes the feedback type in case
of islanding, and possibly also the governor limit from ±5 % to a suitable higher
value. This will however require a digital governor.
Finally, it is recommended that the PSS is disabled during island operation. It is not
useful in island operation but instead causes unnecessary voltage fluctuation that
could disturb the grid.
Annexure-3
171
Page 61 of 61 Printed 2015-01-15 09:29
7 REFERENCES
[1] Contract Agreement No.: CC-CS/422-CC/CON-2241/3/G8/CA/5002 dated
19/08/2014
[2] Test Program – 2014 018-11-1.0 Dadri II
Annexure-3
172
Solvina International AB Document template: Solvina International Report.dot. Last change made by VOl 20st of October 2010
Gruvgatan 37 Phone +46 031 - 709 63 00 Internet www.solvina.com Org no 556782-3280 SE-421 30 Västra Frölunda Location: Göteborg SWEDEN
Valid date
2014-01-12 Project (no - customer)
2014018- POSOCO Report No:
2014018-29 Page (no pages)
1 (23) Author
Shweta Tigga, Niclas Krantz
Reviewed Niclas Krantz
Bengt Johansson
Approved Niclas Krantz
Title
2014018-29-1.0 Testing of Primary Response of Bawana.docx
Distribution
Nodal officers PPCL, POSOCO
SUMMARY
This document presents the results of primary response tests of a 216 MW gas turbine unit #2 at
Bawana Power Plant, India, conducted on 24th
November 2014. The tests were carried out with a
built in step response function by GE and witnessed by Solvina, and the signals were recorded as
decided in the meeting held on 24.10.2014 [3].
The report describes the test setup, conditions and results from the measurements made by
Solvina International. Tests show that FGMO works as expected and that FGMO can be used to
support the control of grid frequency in interconnected mode.
The following tests were performed:
Step response tests in FGMO mode: The steps tests were performed at 75%, 90% and 100% of
rated generated load with a droop setting of 4%. The generated load response in the step tests
corresponds well to the droop setting. The response time T67 is in the range 3-10 seconds. The
frequency control in itself operates in a stable manner.
Annexure-3
173
Page 2 of 23 Printed 2015-01-15 11:05
CONTENTS
1 INTRODUCTION .......................................................................................... 4 1.1 Background ....................................................................................................... 4 1.2 Tests performed ................................................................................................ 5
2 DESCRIPTION OF TESTED UNIT ............................................................ 6 2.1 Basic unit data .................................................................................................. 6 2.2 Operation principle of Gas based plants ........................................................... 7
3 DESCRIPTION OF TESTS PERFORMED .............................................. 10 3.1 Definitions ...................................................................................................... 10 3.2 Method for step response tests ....................................................................... 10 3.3 Test procedure ................................................................................................ 11 3.3.1 Test equipment/function/signal check ............................................................. 11
3.3.2 Step response tests .......................................................................................... 11
4 RECORDED SIGNALS ............................................................................... 12
5 TEST RESULTS ........................................................................................... 13 5.1 Executive summary ........................................................................................ 13 5.1.1 Primary frequency response ........................................................................... 13 5.1.2 Island operation .............................................................................................. 13 5.2 Primary frequency response, step response tests in FGMO ........................... 13 5.2.1 Step response in FGMO, generated load 70%, droop 4% ............................. 14 5.2.2 Step response in FGMO, generated load 90%, droop 4% ............................. 16 5.2.3 Step response in FGMO, generated load 100%, droop 4% ........................... 18
6 CONCLUSIONS ........................................................................................... 21 6.1 Step response in FGMO ................................................................................. 21 6.2 Island Operation ............................................................................................. 21
7 RECOMMENDATIONS ............................................................................. 22 7.1 Normal (grid connected) operation ................................................................ 22 7.2 Island operation .............................................................................................. 22
8 REFERENCES ............................................................................................. 23
Annexure-3
174
Page 3 of 23 Printed 2015-01-15 11:05
REVISION RECORD
Rev.
No.
Date Section Cause Revised
by
Distributed to
1.0 2014-01-12 All Report submitted. NKr POSOCO, Pragati Power
Annexure-3
175
Page 4 of 23 Printed 2015-01-15 11:05
1 INTRODUCTION
1.1 Background
After the large disturbance/outage in northern India in July 2012 it was concluded
that there is a need to verify the primary response of generating units in India. In
March 2013 it was decided that a pilot project to carry out primary frequency
response would be carried out, and this was then described in terms of reference
document (annexure to contract agreement) [1].
Solvina International was awarded this pilot project after a global tender process and
signed a contract agreement with Power Grid PGCIL/POSOCO in August 2014 [1].
The purpose of these tests was to record and verify the following capabilities on the
specified generating units:
Primary Frequency Response in normal operation under Free Governor Mode
of Operation (FGMO).
Primary Response of the machine to a simulated frequency signal
corresponding to islanded conditions in “small island” (one unit) and “large
island” (2000MW system load).
The following units are included in the project:
490 MW thermal unit at Dadri NCTPS
210 MW thermal unit at Dadri NCTPS
216 MW gas turbine at Bawana GPS
180 MW hydro unit at Chamera-1 HPS
250 MW hydro unit at Tehri HPS
This report is for the primary frequency response tests conducted on a 216 MW gas
turbine unit-2, at Bawana Power station.
Due to the inability of the plant OEM, GE, to prepare a software switch in the
governor for connection of a simulated signal as agreed, the test equipment SSPS
could not be connected, and the tests could not be carried out as agreed.
Hence, on request from POSOCO, Solvina agreed to still carry out the step response
tests using the governor built-in function for step responses.
Annexure-3
176
Page 5 of 23 Printed 2015-01-15 11:05
1.2 Tests performed
The following tests were carried out at Bawana as per the test program [2]:
24th
Nov 2014 Test equipment/function/signal check
Connections completed with signal check and test equipment
function check.
Step Response tests
Step response tests at 75%, 90% and 100% of rated generated load
under FGMO mode.
Annexure-3
177
Page 6 of 23 Printed 2015-01-15 11:05
2 DESCRIPTION OF TESTED UNIT
The total installed capacity of Bawana is 1500 MW. It comprises 4 gas turbine units
of 250 MW each. The power plant also has 2 steam turbine units of 250 MW each.
2.1 Basic unit data
Table 1: Basic data Bawana power ststation
Turbine Type BHEL, 9 FA advance class GT
Speed 3000 rmp
Generator Make BHEL
Rating 216 MW (250MVA)
Governor Make Mark VI, GE
Type Digital
Annexure-3
178
Page 7 of 23 Printed 2015-01-15 11:05
2.2 Operation principle of Gas based plants
A Gas power plant is based on the principle of Brayton cycle. Figure 1 show the
processes involved in a Brayton cycle. In a simple gas turbine plant the main
components are namely; compressor, combustion chamber and the turbine. The
ambient air is first compressed in a compressor from Step 12, thereby increasing
the pressure, which requires some input energy. From step 23, the compressed air
is mixed with the fuel and combustion takes place in a combustion chamber at
constant pressure. The resulting hot gases after combustion are allowed to pass
through a turbine, thereby generating power (step 34). In the case of an open
system, the exhaust gases are not reused and released to the atmosphere (step 41).
Figure 1: The principle of gas based plants (open cycle)
The efficiency of the plant can further be increased by utilizing the high temperature
of the exhaust gases coming out of the turbine in a gas turbine-steam turbine cycle,
known as a combined cycle arrangement. In the case of combined cycle plants (see
Figure 2), the exhaust gases from the outlet of the turbine are used further to generate
steam in a heat recovery boiler. The steam is then used to drive a turbine, thereby
generating electricity.
Combustion
Chamber
CompressorGas
Turbine
FuelFuel
Ambient airAmbient air
GasesGases
AmbientAmbient
AirAir2
2
11
33
44
~
Exhaustgases
Exhaustgases
Annexure-3
179
Page 8 of 23 Printed 2015-01-15 11:05
Figure 2: Principle of combined cycle plants.
This combination of gas turbine- steam turbine utilizes two thermodynamic cycles;
gas turbine operating by the Brayton cycle (as explained for open cycle) and steam
turbine operating by the Rankine cycle. The main difference between these two
cycles is that the working medium in a gas turbine is air and in a steam turbine, the
working fluid is steam.
A steam turbine in a thermal power plant is based on the principle of Rankine cycle.
Figure 3 shows the processes involved in a Rankine cycle. The water is first pumped
from Step12 which requires little input energy. From step 23, the water at high
pressure is heated in a boiler at constant pressure by an external heat source which
turns it into steam. The steam is then allowed to expand in a turbine, thereby
generating power (step 34). The steam is then allowed to condense to water in a
condenser at constant pressure (step 41) and the same process repeats.
Combustion
Chamber
CompressorGas
Turbine
FuelFuel
Ambient airAmbient air
GasesGases
ExhaustGases
ExhaustGases
AirAir2
2
11
33
44
~
Heat
recovery
boiler~
Steam
Turbine
Steam
Annexure-3
180
Page 9 of 23 Printed 2015-01-15 11:05
Figure 3: Principle of thermal power plants with steam turbines.
Vaporizer
Condenser
P
ExpanderPump
1
2
3
4
Annexure-3
181
Page 10 of 23 Printed 2015-01-15 11:05
3 DESCRIPTION OF TESTS PERFORMED
3.1 Definitions
Simulated frequency: This is the signal generated by the test
equipment, SSPS.
It can be used as input to the
frequency/speed controller instead of the
actual speed from the frequency/speed
sensor.
Grid frequency: Signal from generator frequency/speed
sensor.
Generated load: Active power of generating unit
3.2 Method for step response tests
The Step response tests were executed by GE on the system and the signals were
provided to Solvina for recording as per the signal list given in section 4.
For performing the step tests, the grid frequency signal was replaced with the GE
simulated frequency signal. After application of each step, the simulated frequency
was switched back to the grid frequency.
The test was carried out in the same manner as in the previous units tested, with
frequency steps giving around 5% generated load change, at 70%, 90% and 100%
generated load.
The built-in test function is described in [4].
Annexure-3
182
Page 11 of 23 Printed 2015-01-15 11:05
3.3 Test procedure
3.3.1 Test equipment/function/signal check
Before commencement of actual tests, all the values/scaling of the measured signals
and the connections to the test equipment were checked to ensure correct
measurements. The frequency steps were applied using a built-in tests function of the
governor by GE and the same were verified with the recorded signals.
3.3.2 Step response tests
Initially, before beginning the test sequence, the GE simulated frequency was kept
same as the grid frequency. The primary response was then tested by applying a
simulated frequency step to the governor frequency input. The frequency step was
calculated from the droop settings, to produce a generated load change of up to
approx. 5% of rated load.
The step tests with FGMO engaged in governor were performed at 70%, 90% and
100% of rated generated load with positive and negative steps in frequency.
Annexure-3
183
Page 12 of 23 Printed 2015-01-15 11:05
4 RECORDED SIGNALS
The following signals were recorded during the tests for analysis of the power plant
performance:
Simulated frequency = the frequency signal injected into the governor from the test
equipment SSPS.
Active power = generated load of the unit, as measured by a transducer from PT and
CT outputs.
Generator voltage = AC voltage measured at generator terminal PTs.
Generator frequency = frequency of the voltage measured at generator terminal
PTs. This is equal to the grid frequency.
Annexure-3
184
Page 13 of 23 Printed 2015-01-15 11:05
5 TEST RESULTS
5.1 Executive summary
5.1.1 Primary frequency response
Step response tests were performed at 70%, 90% and 100% of rated generated load.
The tests were conducted according to the built-in tests function of the governor. The
frequency steps were carried out as per the GE test procedure [4]
FGMO works as expected and the magnitude of response is approx. according to the
droop settings. The generated load response in the step tests corresponds to 4%
droop. The response time T67 is in the range 3-10 seconds, measured for steps
causing a change in generated load equal to 5 % of rated load.
5.1.2 Island operation
The islanding operation tests were not performed as discussed in minutes of the
meeting [2] and [3].
Although the unit is able to maintain stable operation during primary frequency
response tests, it can however, not be concluded that it can operate during islanding
conditions without specific testing.
5.2 Primary frequency response, step response tests in FGMO
The step response tests are carried out to investigate how well the plant supports the
power system at frequency changes of the grid. The speed droop is the parameter that
decides the magnitude of response. The response has two characteristics that are
interesting to examine, the magnitude and the time constant (67% value, T67).
For the tests in FGMO mode the droop setting during test was 4%.
Steps were carried out to give up to 5% load change, which is approx. 11 MW, and
the frequency step size giving that response would be 0.05*0.04*50 = 0.1 Hz.
Consequently 11 MW is the expected response for the steps to be carried out.
Similarly, expressed in MW/Hz, the response is expected to be 110 MW/Hz for any
step.
Annexure-3
185
Page 14 of 23 Printed 2015-01-15 11:05
5.2.1 Step response in FGMO, generated load 70%, droop 4%
The step response tests were carried out at 70% generated load with 4 % droop.
With a droop setting of 5 %, a 0.1 Hz step is expected to cause a generated load
change of approx. 11 MW.
Table 2 Frequency steps in FGMO, generated load 70 %, droop 4%, Part 1
Simulated
frequency
(Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change , ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
5049.90 149.3 161.2 +11.9 119 9
49.9050 161.2 149.6 -11.6 116 3
Figure 4: Frequency steps in FGMO, generated load 70%, droop 4%, Part 1
Annexure-3
186
Page 15 of 23 Printed 2015-01-15 11:05
Table 3 Frequency steps in FGMO, generated load 70%, droop 4%, Part 2
Simulated
frequency
(Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change , ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
5050.1 149.4 137.3 -12.1 121 5
50.150 137.1 149.6 +12.5 125 6
Figure 5: Frequency steps in FGMO, generated load 70%, droop 4%, Part 2
In the simulated step tests conducted by GE, the simulated frequency was switched
back to the grid frequency after reaching 50 Hz.
From the above figure we can see that with the application of the frequency steps, the
response of the generated load is immediate. The response is also in approx.
accordance with the droop setting.
Annexure-3
187
Page 16 of 23 Printed 2015-01-15 11:05
5.2.2 Step response in FGMO, generated load 90%, droop 4%
The tests in FGMO mode were carried at 90% generated load with droop 4%. As
before, with a droop setting of 4 %, a 0.1 Hz step is expected to cause a generated
load change of approx. 11 MW.
Table 4 Frequency steps in FGMO, generated load 90 %, droop 4%, Part 1
Simulated
frequency
(Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change ,
ΔP (MW)
MW
contribution
(MW/Hz)
Time
constant,
T67 (s)
5049.90 194.3 206.5 +12.2 122 6
49.9050 206 193.7 -12.3 123 4
Figure 6: Frequency steps in FGMO, generated load 90 %, droop 4%, Part 1
Annexure-3
188
Page 17 of 23 Printed 2015-01-15 11:05
Table 5 Frequency steps in FGMO, generated load 90 %, droop 4%, Part 2
Simulated
frequency
(Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change ,
ΔP (MW)
MW
contribution
(MW/Hz)
Time
constant,
T67 (s)
50 50.1 194.2 182.6 -11.6 116 3
50.150 182 194.8 +12.8 128 5
Figure 7: Frequency steps in FGMO, generated load 90 %, droop 4%, Part 2
It can be seen that with the application of the frequency steps, the response of the
generated load is immediate. The response is also approximately in accordance with
the droop setting.
Annexure-3
189
Page 18 of 23 Printed 2015-01-15 11:05
5.2.3 Step response in FGMO, generated load 100%, droop 4%
The same procedure as above tests was repeated at 100 % load. As before, with a
droop setting of 4 %, a 0.1 Hz step is expected to cause a generated load change of
approx. 11 MW.
Table 6 Frequency steps in FGMO, generated load 100 %, droop 4%, Part 1
Simulated
frequency (Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change , ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
50 49.90 215.4 224.5 +9.1 91 7
49.90 50 224.6 215.1 -9.5 95 5
50 50.1 214.5 203.3 -11.2 112 10
50.150 203.2 215.1 +11.9 119 7
Figure 8: Frequency steps in FGMO, generated load 100 %, droop 4%, Part 1
Annexure-3
190
Page 19 of 23 Printed 2015-01-15 11:05
Figure 9: Frequency steps in FGMO, generated load 100 %, droop 4%, Part 1 (Showing
the interval 370 – 470 seconds)
Figure 10: Results received from GE show the interval of during oscillations.
For the step change in frequency from 50 49.90 Hz, certain oscillations are seen in
the generated load response. The oscillations in the generated load as shown in
Figure 9 and Figure 10 are likely caused due to the power system stabiliser (PSS)
Annexure-3
191
Page 20 of 23 Printed 2015-01-15 11:05
that causes these effects. The PSS cannot sufficiently filter out the load changes
caused by variations in the turbine torque and therefore responds to these in a similar
way as it responds to the power oscillations that it is intended to counteract.
Table 7 Frequency steps in FGMO, generated load 100 %, droop 4%, Part 2
Simulated
frequency (Hz)
Initial
generated
load (MW)
Post step
generated
load (MW)
Gen. load
change , ΔP
(MW)
MW
contribution
(MW/Hz)
Time
constant
T67 (s)
50 50.1 214.5 203.3 -11.2 112 10
50.150 203.2 215.1 +11.9 119 7
Figure 11: Frequency steps in FGMO, generated load 100 %, droop 4%, Part 2
The overall response of the unit is approximately in accordance with droop.
Annexure-3
192
Page 21 of 23 Printed 2015-01-15 11:05
6 CONCLUSIONS
6.1 Step response in FGMO
FGMO works as expected and the magnitude of response is according to the droop
settings. The generated load response in the step tests corresponds to 4 % droop. The
response time T67 is in the range 3-10 seconds, measured for steps causing a change
in generated load approx. equal to 5 % of rated load.
6.2 Island Operation
The island operation tests were not performed as agreed and discussed in the
meetings 24/10/2014 [2] and 25/11/2014 [3].
Annexure-3
193
Page 22 of 23 Printed 2015-01-15 11:05
7 RECOMMENDATIONS
The results from the tests were analysed to see what could further be done to improve
the performance. In this section some recommendations are presented.
7.1 Normal (grid connected) operation
No recommendations.
7.2 Island operation
The island operation tests were not performed as mention in the meeting [2] and [3].
However, for a stable operation of the unit during islanding operation, island
operation tests are recommended to verify the performance.
Annexure-3
194
Page 23 of 23 Printed 2015-01-15 11:05
8 REFERENCES
[1] Contract Agreement No.: CC-CS/422-CC/CON-2241/3/G8/CA/5002 dated
19/08/2014
[2] Minutes of the meeting held on 24.10.2014.
[3] Minutes of the meeting held on 25.11.2014 for primary frequency response
testing at Bawana Gas station Unit-2.
[4] GE Test procedure: Testing of governor response (Fuel gas)
Annexure-3
195
1 Punjab 13.3 1 Maharashtra 7.6
2 Haryana 23.5 2 Gujarat 2.4
3 Rajasthan 18.4 3 MP 2.3
4 Delhi 12.4 4 Chhattisgarh -3.6
5 Uttar Pradesh 5.5 5 DNH 0
6 Uttarakhand* 147.6 6 DD 0
7 Chandigarh* 135.1 7 Goa* 312.7
8 HP 6.8
9 J&K* -63.4
1 AP 30 1 WB 19.22 TN 21 2 BSEB -54.23 KAR 21 3 OPTCL 6.94 KER 70 4 JSEB 11.65 Telangana 45 5 DVC 14.26 Pondi* 343 6 Sikkim 18.2
1 Assam 23.4
2 Meghalaya -0.2
3 Tripura 16
4 Manipur 31
5 Mizoram 38.4
6 Nagaland* -270.3
7Arunachal
Pradesh*-170.4
** the constituent with highest positive value of FRC contributes maximum to frequency response and that with highest
–negative value severely aggravates the frequency deviation.
* For smaller states, small error in Telemetry can cause large impact in calculation result.Data pertaining to these states
can be interpreted accordingly
TABLE 1 Control Area wise - Percentage of Ideal Response** (%)
Control AreaPercentage of Ideal
Response (%)
Sl. No. Control AreaPercentage of Ideal
Response (%)
ER
Sl. No. Control AreaPercentage of Ideal
Response (%)
NR WR
SR
Sl. No. Control AreaPercentage of Ideal
Response (%)Sl. No.
NER
Sl. No. Control AreaPercentage of Ideal
Response (%)
Annexure-4
196
1 Sri Cement 5.4 18 Pong 17.8 1 Korba 0
2 Jhajjar-MGTPS -10.3 19 Singrauli 0.3 2 Vindhyachal 2.5
3 Chamera-I -3 20 Rihand -6.3 3 Sipat -35.1
4 Chamera-II -22.1 21 Dadri -13.8 4 NTPC-SAIL 8.2
5 URI 0 22 Dadri-Gas 2.4 5 JINDAL -8.9
6 Salal 1.2 23 Unchahar 0 6 LANCO -1.7
7 Bairasul 9.9 24 ANTA 2.7 7 KAWAS 0
8 Tanakpur 0 25 Auraiya 0 8 SSP 9.8
9 Dhauliganga 0 26 Narora 0 9 UMPP-Mundra 0.6
10 Dulhasti -3.2 27 RAPPB 0 10 Tarapur -32.8
11 SEWA2 0 28 RAPP C 0 11 KSK Mahanadi 4.1
12 Karcham -8.2 29 Jhajjar-PG 5.8 12 Balco -24.4
13 Malana 0 30 ADHydro 0 13 Mouda 25.3
14 TEHRI 0 31 Koteshwar -5.2 14 Emco -25.2
15 Naphtha 0 15 Sasan 0
16 Bhakra 6.4 16 Essar -26.8
17 DEHAR 0.9
Sl. No.Generating
Station
Percentage of
Ideal Response
(%)
TABLE 2 Generating Station- Percentage of Ideal Response* (%)
NR WR
Sl. No.Generating
Station
Percentage of
Ideal Response
(%)
Sl. No.Generating
Station
Percentage of
Ideal
Response (%)
Annexure-4
197
1 Ramagundam 0.2 1 Farraka -0.8 1 KAITHALGURI -6.2
2 Simhadari 34 2 Kahalgaon 2.4 2 AGARTALA -24.2
3 Neyveli-II 13.2 3 TSTPS-I 5.4 3 KHANDONG -18.1
4 Neyveli Exp 0 4 MPL 9.1 4 KOPILI -3.7
5 Kaiga 1.8 5 Sterlite 57.9 5 DOYAN 3.7
6 MAPS -3.2 6 Adhunik 54.2 6 RANGANADI 3.8
7 KNPP 0 7 Teesta -31.2 7 LOKTAK 2.8
8 Vallur 0 8 RHEP -2.5 8 PALATANA 0
9 CHEP 0
*generating station with highest –negative value of FRC is contributing maximum to frequency response and generating station with
highest positive value of FRC is aggravating the frequency deviation.
Sl. No.Generating
Station
Percentage of
Ideal Response
(%)
ER
Sl. No.Generating
Station
Percentage of
Ideal
Response (%)
Sl. No.Generating
Station
Percentage of
Ideal Response
(%)
SR NER
Annexure-4
198
Sl. No. Control AreaPercentage of Ideal
Response (%)Sl. No. Control Area
Percentage of
Ideal Response
(%)1 Haryana 23.5 1 Maharashtra 7.6
2 Rajasthan 18.4 2 Gujarat 2.4
3 Punjab 13.3 3 MP 2.3
4 Delhi 12.4 4 Chhattisgarh -3.65 Uttar Pradesh 5.5
1 KER 70 1 WB 19.2
2 Telangana 45 2 DVC 14.2
3 AP 30 3 OPTCL 6.9
4 TN 21 4 BSEB -54.2
5 KAR 21
Percentage of Ideal
Response (%)Sl. No. Control Area
Percentage of
Ideal Response
(%)
Sl. No. Control Area
TABLE 3 Ranking Control Area wise (Demand Met 2000MW and Above) Based on
Percentage of Ideal Response (%)
NR WR
SR ER
Annexure-4
199
1 Chamera-II -22.1 1 Sipat -35.1 1 MAPS -3.2
2 Dadri -13.8 2 Tarapur -32.8 2 Neyveli Exp 0
3 Jhajjar-MGTPS -10.3 3 Essar -26.8 3 KNPP 0
4 Karcham -8.2 4 Emco -25.2 4 Vallur 0
5 Rihand -6.3 5 Balco -24.4 5 Ramagundam 0.2
6 Koteshwar -5.2 6 JINDAL -8.9 6 Kaiga 1.8
7 Dulhasti -3.2 7 LANCO -1.7 7 Neyveli-II 13.2
8 Chamera-I -3 8 Korba 0 8 Simhadari 34
9 URI 0 9 KAWAS 0
10 Tanakpur 0 10 Sasan 0
11 Dhauliganga 0 11 UMPP-Mundra 0.6
12 SEWA2 0 12 Vindhyachal 2.5
13 Malana 0 13 KSK Mahanadi 4.1
14 TEHRI 0 14 NTPC-SAIL 8.2
15 Naphtha 0 15 SSP 9.8
16 Unchahar 0 16 Mouda 25.3
17 Auraiya 018 Narora 019 RAPPB 020 RAPP C 021 ADHydro 0
22 Singrauli 0.323 DEHAR 0.9 1 Teesta -31.2 1 AGARTALA -24.224 Salal 1.2 2 RHEP -2.5 2 KHANDONG -18.125 Dadri-Gas 2.4 3 Farraka -0.8 3 KAITHALGURI -6.226 ANTA 2.7 4 CHEP 0 4 KOPILI -3.7
27 Sri Cement 5.4 5 Kahalgaon 2.4 5 PALATANA 0
28 Jhajjar-PG 5.8 6 TSTPS-I 5.4 6 LOKTAK 2.8
29 Bhakra 6.4 7 MPL 9.1 7 DOYAN 3.7
30 Bairasul 9.9 8 Adhunik 54.2 8 RANGANADI 3.8
31 Pong 17.8 9 Sterlite 57.9
ER NER
Sl. No.Generating
Station
Percentage of
Ideal Response
(%)
Sl. No.Generating
Station
Percentage of
Ideal Response
(%)
TABLE 4 Ranking of Generating Station Based on Percentage of Ideal Response (%)NR WR SR
Sl. No.Generating
Station
Percentage of
Ideal Response
(%)
Sl. No.Generating
Station
Percentage of
Ideal Response
(%)
Sl. No.Generating
Station
Percentage of
Ideal Response
(%)
Annexure-4
200
Annexure-V
Over Fluxing of Transformers
In normal operation, if an electrical power transformer is subjected to carry more than specified
flux density as per its design limitations, the transformer is said to have faced over
fluxing problem and consequent bad effects towards its operation and life. The magnetic
flux density is proportional to the quotient of voltage and frequency (V/f). Over fluxing can,
therefore, occur either due to increase in voltage or decrease in-frequency or both. Over fluxing
in transformer has sufficient harmful effect towards its life.
In the normal Grid Operations it is observed that frequency keeps varying throughout the day. In
the events of sudden large Generation Loss such as that of CGPL Outage, frequency plunged to a
very low value and thereby posed as severe threat to system operation. Such sudden Generation
Loss causing frequency to plunge to a low value can eventually lead to over fluxing operation of
transformers. Therefore it is very important to check this sudden fall of frequency by
implementation of FGMO. The Voltage and Frequency scatter plots of important stations across
the Grid for the month of January 2015 is given below as Fig.1 to Fig.8 for better understanding.
In the plots it is observed that second quadrant operation is present in almost all the stations. The
second quadrant operation indicates that voltage is high and frequency is low in the system.
Therefore the condition for overfluxing of transformers is satisfied during such operation.
201
Annexure-V
Fig:1
Fig:2
750
760
770
780
790
800
810
820
830
49.6 49.8 50 50.2 50.4 50.6 50.8
Vol
tage
(kV
)
Frequency(Hz)
V/F Plot for Wardha(765kV) (For the month of Jan'15)
730
740
750
760
770
780
790
800
49.60 49.80 50.00 50.20 50.40 50.60 50.80
Vo
ltag
e(k
V)
Frequency(Hz)
V/F Plot for Seoni (765kV) ( For the month of Jan'15)
202
Annexure-V
Fig:3
Fig:4
735
740
745
750
755
760
765
770
775
780
49.60 49.80 50.00 50.20 50.40 50.60 50.80V
olta
ge(k
V)
Frequency(Hz)
V/F plot for Sipat (765kV) ( For the month of Jan'15)
730
740
750
760
770
780
790
800
810
49.60 49.80 50.00 50.20 50.40 50.60 50.80
Volta
ge(k
V)
Frequency(Hz)
V/F plot for Agra (765kV) ( For the month of Jan'15)
203
Annexure-V
Fig:5
Fig:6
720
730
740
750
760
770
780
790
800
49.60 49.80 50.00 50.20 50.40 50.60 50.80Vo
ltag
e(kV
)Frequency(Hz)
V/F plot for Fatehpur (765kV) ( For the month of Jan'15)
395
400
405
410
415
420
425
430
435
440
49.60 49.80 50.00 50.20 50.40 50.60 50.80
Volt
age(
kV)
Frequency(Hz)
V/F plot for Kurnool (400kV) ( For the month of Jan'15)
204
Annexure-V
Fig:7
Fig:8
395
400
405
410
415
420
425
430
435
440
49.60 49.80 50.00 50.20 50.40 50.60 50.80
Vo
ltag
e(k
V)
Frequency(Hz)
V/F plot for Malkaram (400kV) ( For the month of Jan'15)
395
400
405
410
415
420
425
430
435
49.60 49.80 50.00 50.20 50.40 50.60 50.80
Vo
ltag
e(k
V)
Frequency(Hz)
V/F plot for Hyderabad (400kV) ( For the month of Jan'15)
205