    M/S McNALLY BHARAT LIMITED

    C&A SYSTEM FOR 9000TPD CEMENT PLANT FOR

    ACC-JAMUL

    PCS CONFIGURATION DIAGRAM

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    2/14

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    3/14

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    4/14

    PCS CONFIGURATION DIAGRAM - LIU PORT USAGE

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    5/14

    Please confirm that is it Matrion or Matricon ?

    Please indicate the location

    room of server cabinet, networkcabinet, CPU of various work

    station & LVS, etc.

    HAC shall be

    L64-1T3, pleasecheck & correct.

    Please check the connectivity

    with Weigh Bridge, EMS, LoadManager, etc.

    Please indicate the

    connectivity of packing plantPS.

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    6/14

    Following Profibus-DP shall also be

    considered in each load centre:-1. UPS.

    2. Battery & Battery charger

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    7/14

    These SCS shallbe considered in

    LC-4

    Following SCS

    shall also beconsidered :-

    1. 364-FM1.C1

    2. 364-FM2.C13.364-AD1.U14. 364-Ad2.U1

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    8/14

    Following shall beconsidered in

    Profibus-DP:-1. VFD drive

    compressor.2. Water treatment

    Plant

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    9/14

    4D4-FM1.C1 and

    4D4-FM2.C1 shallalso be considered

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    10/14

    Maximum DP nodes

    shall be limited to 40

    Nos. and PA nodes

    shall be limited to18

    Nos.

    Repeating

    Minimum speed of communication

    for the profibus should greater

    than 2 MBPS

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    11/14

    454-PF1, 454-PF2and 484-BU1 shall

    be considered

    Repeating

    Please provide the calculation

    communication speed and loadingfor profibus PA networks.

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    12/14

    Following shall beconsidered in

    Profibus -DPnode :-

    1. L64-RF2.U12. L64-GB1.C1

    3. L24-3B4.W14. L94-BI1.W1

    5. L94-BI2.W1

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    13/14

  • 7/23/2019 NJP-MBE-E501-000000-0001_A

    14/14

    Profibus PA deviceshall be limited to

    maximum of 18

    number in onenode

    Following PA dviceshall be considered

    1. 51A-BF1.P2

    2. 51A-BF2.P23. 51A-BF3.P2

    4. 51A-BF4.P2

    Following DPdevices shall be

    considered :-1. K94-3B1.W1

    2. K94-3B2.W13. 624-LA1.C1

    4. 624-LA2.C1