Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Table of contents
Page
Safety notes/ Technical support 2
---------------------------------------------------------------------------------------------------------------------------
Introduction 3
---------------------------------------------------------------------------------------------------------------------------
Dimensions 4
---------------------------------------------------------------------------------------------------------------------------
Technical data Electrical Data 7 Mechanical Data 8 Operating conditions 9 Transport and Storage 9 Approvals 10 Sensor weight guide 11
---------------------------------------------------------------------------------------------------------------------------
Options 12
---------------------------------------------------------------------------------------------------------------------------
Mounting 13
---------------------------------------------------------------------------------------------------------------------------
Electrical installation 15
---------------------------------------------------------------------------------------------------------------------------
Signal overview 20
---------------------------------------------------------------------------------------------------------------------------
Programming Quickset menu 22 Output adjustment menu 25 Diagnostics menu 28 Communication menu 30 Modbus register 31
---------------------------------------------------------------------------------------------------------------------------
Commissioning Interface measurement 33
---------------------------------------------------------------------------------------------------------------------------
Maintenance General items 34 Diagnostics Maintenance 35 Diagnostics Failure 37
---------------------------------------------------------------------------------------------------------------------------
Notes for use in Hazardous Locations 38
---------------------------------------------------------------------------------------------------------------------------
Disposal 40
Subject to technical change. We assume no liability for typing errors.
All dimensions in mm (inches). Different variations to those specified are possible.Please contact our technical consultants.
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 1
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Safety notes / Technical support
Notes • Installation, maintenance and commissioning must be carried out only by qualified technical personnel. • The product must be used only in the manner outlined in this instruction manual.
Special attention must be paid to warnings and notes as follows:
WARNING
Relates to a caution symbol on the product and means, that a failure to observe the necessary precautions can result in death, serious injury and/ or considerable material damage.
WARNING
Relates to a caution symbol on the product and means, that a failure to observe the necessary precautions can result in death, serious injury and/ or considerable material damage.
This symbol is used, when there is no corresponding caution symbol on the product.
A failure to observe the necessary precautions can result in considerable material damage.
CAUTION
Safety symbols
In manual and on product
Description
CAUTION: refer to related documents (manual) for details.
Earth (ground) Terminal
Protective Conductor Terminal
Technical support
Please contact your local supplier (see www.uwt.de for address). Otherwise you can contact:
UWT GmbH Tel. 0049 (0)831 57123-0Westendstr. 5 Fax. 0049 (0)831 7687987488 Betzigau [email protected] www.uwt.de
WARNING
Relates to a caution symbol on the product: Risk of electric shock
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi0201162
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Introduction
The Nivobob® NB 3000 is an electromechanic level measuring instrument for continuous measuring of level or volumes in silos, hoppers or tanks.
Applications• Powder, granulate, small or coarse bulk goods• Interface measurement (solids in water)
Available for industries such as• Chemistry• Food• Cement• Mining• Plastics• others
Features
Process
• Suitable for most types of bulk goods• Independent of bulk material properties, such as: Dielectricity and conductivity of the bulk good Dusty atmosphere in the silo Changing humidity inside the product Products that tend to stick • No mechanical load on the silo roof, the sensor weight just touches the surface of the material• Very accurate measurement
Service
• Simple installation and commissioning• Measurement principle easy to understand• Rope, tape and (optional) motor with increased service life• Low maintenance
Approvals
• Approval for use in Hazardous Locations
Mechanic
• Measurement range up to 50 m (164 ft)• 11/2" process connection possible• Different sensor weights, suitable for every application• Internal tape cleaner for difficult materials• Window in lid and external start button (optional)• Robust cast housing, ingress protection IP66
Electronic
• Micro processor controlled measurement• Comprehensive diagnostics possibilities• Output 0/4-20 mA/ Modbus/ Profibus DP/ counting pulses• Programmable relais (can be used as level limit switch outputs)• Measurement start with external signal or integrated timer
Function The Nivobob® NB 3000 is mounted on the top of the silo. A sensor weight is driven down into the silo. It is mounted at the end of a rope or tape which is wound on a motor driven roller. Upon contact with bulk material, the motor changes the winding direction and the sensor weight is driven back to the upper stop position.
During downwards movement of the sensor weight the distance is electronically measured by the rotations of the internal rope / tape roller. The microcontroller converts the measured distance into an output signal, which is a volumetric signal based on the silo geometry. The output signal is updated, when the sensor weight touches the bulk material.
DiagnosticsComprehensive diagnostics possibilities are present:
• Measurement control is done by comparing the moved distance between up and downward movement and checking for discrepancy. In case of discrepancy, the sensor weight is pulled to the upper stop position to ensure, that the sensor weight is not inside the silo.
• Service interval after a certain amount of measurements and running time.
• Internal control of motor, motor driver electronic and smooth movement of rope/ tape rollers.
Diagnostics is in accordance with NAMUR recommendation NE107.
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 3
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Dimensions
X
Flange versionDN100/ 4"
Basic typeThread versionFlange version 2"/ 3"
Flange version, bottom view
X
A A
C CB
B
B = Diameter of socket pipe
Rope version with Flange DN100/ 4"
ø60 mm (ø2.36")
All other versions ø40 mm (ø1.57")
Socket pipe
Socket pipe
Flange
Thread
HousingHousing
Housing extension Housing
extension
Housing outside Aluminium, powder coated
Housing inside Aluminium
Housing extension
Aluminium, powder coated or 1.4305 (303)
Flange 80°C/ 150°C: Aluminium, powder coated 250°C: 1.4305 (303)
Thread 1.4301 (304)
Socket pipe Flange version DN100/ 4", 80°C/ 150°C: AluminiumAll other versions: 1.4301 (304)
Rope 1.4401 (316)
Tape 1.4310 (301)
X = Length to bottom of sensor weight (in upper stop position): see next page
A = Lenght of socket pipe
200 mm (7.9")Optional 500 mm (19.7")/ 1,000 mm (39.4")
C = Housing extension
Flange versionDN100/ 4"
80°C/ 150°C 95 mm (3.74")
250°C 340 mm (13.4")
All other versions 80°C/ 150°C 160 mm (6.3")
250°C 340 mm (13.4")
Rope/ tape Rope/ tape
Dimensions
Materials
Rope ø1.0 mm (ø0.04")
Tape 12 x 0.2 mm (0.47 x 0.008")
With option "Increased corrosion resistance":All metal parts in contact with the process are coated.The rope is plastic coated with PA.The internal bearings are made of stainless steel.
Lk d2
Flanges
fitting to:DN100 PN16/ 4" 150lbs
Lk = ø180 - 190.5 mm (ø7.1 - 7.5") slotd2 = ø19 mm (ø0.75")
fitting to:2" /3" 150 lbs
Lk = ø120.7 - 152.4 mm (ø4.75 - 6.0") slotd2 = ø19 mm (ø0.75")
Flange
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi0201164
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Dimensions
PVC without pin
Sensor weights
PVC with pin
Stainless steel Claw
Folding cover
Spider
Bag
Float
Solids measurement: Rope version All weights ca. 1,0 kg (2.2 lbs)
X
ø81 mm (ø3.2" )X = 137 mm (5.4")Material: PVC
Version with Flange DN100/ 4"ø75 mm (ø3.0")X = 25 mm (1.0")Pin: 130 mm (5.1")
ø95 mm (ø3.7")X = 71 mm (2.80")Material: 1.4305 (303)
ø81 mm (ø3.2")X = 137 mm (5.4")Pin: 130 mm (5.1")Material: PVC (pin POM)
X
X
X
X
X
X
X
X
380 x 380 mm (15 x 15")X = 150 mm (5.9")Material: 1.4310 (301)/ 1.4305 (303) PA canvas
ø600 mm (ø23.6")X = 160 mm (6.3")Material: 1.4301 (304)/ 1.4305 (303) 1.4310 (301)
Options and Accessories
pos.28Compressed air connector
pos.25Window in lid andoutside start button
Window in lid
Outside start button
Compressed air connector
All other versionsø42 mm (ø1.65")X = 81 mm (3.19")Pin: 130 mm (5.1")
Material: 1.4305 (303)
ø190 mm (ø7.5" )X = 175 mm (6.9")Material: Float PP, Cone: aluminium
ø95 mm (ø3.7")X = 460 mm (18.1")Material: PA canvas,Chain: 1.4305 (303)Cone: aluminium
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 5
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Dimensions
Solids measurement: Tape version All weights ca. 2.1 kg (4.6 lbs)
Interface measurement: Rope version Weight ca. 1.0 kg (2.2 lbs)
PVC with pin
Stainless steel
Claw Folding cover
Spider
Bag
Float
X ø42 mm (ø1.65")X = 320 mm (12.6")Pin: 130 mm (5.1")Material: 1.4305 (303)
ø95 (ø3.7")X = 236 mm (9.3")Material: 1.4305 (303)
ø81 mm (ø3.2")X = 465 mm (18.3")Pin: 130 mm (5.1")Material: PVC (pin POM)
X
X
X
X
X
X
380 x 380m m (15 x 15")X = 430 mm (16.9")Material: 1.4310 (301)/ 1.4305 (303) PA canvas
ø600 mm (ø23.6")X = 345 mm (13.6")Material: 1.4301 (304)/ 1.4305 (303) 1.4310 (301)
ø190 mm (ø7.5" )X = 285 mm (11.2")Material: Float PP
ø95 mm (ø3.7")X = 575 mm (22.6")Material: PA canvas
Aluminium
1.4305 (303)
ø81 mm (ø3.2" )X = 82 mm (3.22")Material: PVC with plastic/ metal disks
X
Interface measurement: Tape version Weight ca. 2.1 kg (4.6 lbs)
ø42 mm (ø1.65")X = 320 mm (12.6")Pin: 130 mm (5.1")Material: 1.4305 (303)
X
including additional disks to adjust to the application
Aluminium Aluminium Aluminium
Aluminium Aluminium
Aluminium
1.4305 (303)
1.4305 (303)Aluminium
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi0201166
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Technical data
Electrical data
Power supply AC version 98 .. 253 V 50 - 60 HzDC version 20 .. 28 V(voltages incl. 10% of EN 61010)
Installed load AC version: 150 VA (including internal heater (80 W))
DC version:One unit: 150 W (with or without internal heater) *Further units which are connected to the same power supply: 25 W per unit (without internal heater, motor off) ** 50 W per unit (without internal heater, motor running) 80 W per unit (with internal heater, supply voltage 20 V DC) 100 W per unit (with internal heater, supply voltage 24 V DC) 120W per unit (with internal heater, supply voltage 28 V DC) * Considers the max. motor traction which is needed in a failure condition. A failure condition is assumed for max. one unit at the same time. ** This value can be considered, if the controlling PLC starts the measurement for max. one unit at the same time.
Signal output:0/4-20 mA
Max. 500 Ohms (active, isolated) Linearity ±0.1 mA
Signal output: Relay
4x Relay SPST:max. 250 V AC, 2 A, 500 VA non inductive
Signal output:Electronic counting pulse
Optocoupler max. 30 V DC, max. 25 mA
Communication:Modbus RTU
Physical layer: RS 485 and Ground, isolatedMode: RTU, Type: SlaveDevice number range: 1 - 247 (selectable in menu), Baudrate: 1,200 to 57,600 Baud, Data bits: 8, Stop Bits: 1Parity: NoneMulti-drop configuration possible. Factory setting of adress is 31. Each unit which is connected to the network must be set to an individual adress.Supported commandsReading: All diagnostics and parameters using command 03HEX: Read Holding RegisterWriting: All parameters using command 06HEX: Write Single Register (not supported is command 10HEX: Write Multiple Register).
Communication:Profibus DP
Physical layer: RS 485, isolatedType: SlaveDevice number range: 0 - 126 (selectable in menue), Baudrate: 9.6 kbps to 12 MbpsAvailable communication by GSD file, Read only (Sensor weight bottom to material (in mm))
Accuracy of measurement Output Setting AccuracyCounting pulse 10 cm (1/3 ft)/ pulse 1 pulse
5 cm (1/6 ft)/ pulse 1 pulse2,5 cm (1/10 ft)/ pulse 2 pulses1 cm (1/20 ft)/ pulse 4 pulses
0/4-20 mA 1% of max. range
Modbus RTU/ Profibus
0.5% of max. range
Display LCD display: 2 line x 16 digit
Indication light Status by build in LED: Power On, Relais, Maintenance and Failure
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 7
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Technical data
Mechanical data
Ingress protection IP66, Type 4
Process connection Threads: R 11/2" EN 10226 tapered, NPT 11/2" or 3" ANSI B1.20.1 tapered Flanges: DN100 PN16 EN 1092-1 (unit fits to this flange) 2" or 3" or 4" 150lbs ANSI B16.5 (unit fits to this flange)
Colour Housing, Flange RAL 5010 (gentian blue)Lid RAL 9006 (aluminium silver)
Material See detail specifications on page 4 - 6
Measuring range Rope version max. 30 m (100 ft)Tape version max. 50 m (164 ft)
Measuring speed Sensor weight speed in average:Standard version: ca. 0.25 m/s (0.8 ft/sec) Version with brushless motor: ca. 0.33 m/s (1.0 ft/sec)
Sound level max. 50 dBA
Weight Rope version with flange: ca. 11 kg (24.2 lbs) with thread: ca. 12 kg (26.4 lbs)Tape version with flange: ca. 12 kg (26.4 lbs) with thread: ca. 13 kg (28.6 lbs)
Deviation of vertical mounting
max. 2° max. 1° for tape version with extended socket pipe (see page 4)
Compressed air connector(Option)
Quick coupling incl. opposite part, for hose diameter 9 mm (0.35“), female at housingMax. operating pressure 0.2 bar (2.9 psi)
Memory Non-volatile (no backup battery required) > 10 years data retention
Connection terminals 0.14 .. 2.5 mm2 (AWG 26 .. 14)
Cable entry According to selection:Screwed cable gland: 2x M20 x 1.5 and 1x M25 x 1.5 Blindplug: 2x M20 x 1.5 orConduit ANSI B1.20.1: 1x NPT 3/4" and 2x NPT 1/2" Blindplug: 2x NPT 1/2"
Clamping range (diameter) of the factory provided cable glands:M20 x 1.5: 6 .. 12 mm (0.24 .. 0.47") M25 x 1.5: 8 .. 17 mm (0.31 .. 0.67")
Extension cables for Profibus DP/ Modbus
Use common recommended cables
Isolation Power supply to all other outputs/ inputs: AC version 2,210 Vrms DC version: 1,000 VDCRelay to relay: 2,210 Vrms
Protection class I
Overvoltage category II
Pollution degree 2 (inside housing)
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi0201168
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Operating conditions
Process overpressure -0.3 .. +0.3 bar (-4.4 .. +4.4 psi)-0.5 .. + 1.7 bar (-7.3 .. +25 psi) optional for CE + ATEX-0.5 .. + 1.1 bar (-7.3 .. +16 psi) optional for FM general purpose
Process temperature -40°C .. +80/ 150/ 250°C (-40 .. +176/ 302/ 482°F)
Ambient temperature -20°C .. +60°C (-4 .. +140°F) -40°C .. +60°C (-40 .. +140°F) CE, FM General Purpose with internal heater-40°C .. +60°C (-40 .. +140°F) ATEX, FM Class II on request possiblemax. +40°C (104°F) Version with Process temp. 150°C (302°F)
Ventilation Ventilation is not required
Min. powder density see "Sensor weight guide" on next page
Minimum time between measuring starts
measuring height 5 m (16 ft )-> 3 minmeasuring height 10 m (33 ft) -> 6 minmeasuring height 20 m (66 ft) -> 12 minmeasuring height 30 m (98 ft) -> 18 minmeasuring height 40 m (131 ft) -> 24 minmeasuring height 50 m (164 ft) -> 30 min
Rope/ tape operating time see page 36
Max. permitted tractive force
Tape version: with brushless motor: ca. 3,000 N standard motor: ca. 800 N Rope version: with brushless motor: ca. 1,000 N standard motor: ca. 800 N with increased corrosion resistance: ca. 700 N
Relative humidity 0 - 100%, suitable for outdoor
Altitude max. 2,000 m (6,562 ft)
Expected product lifetime Following parameters have a negative influence on the expected product lifetime: High ambient- and process temperature, corrosive environment, high vibration, high flow rate of abrassive bulk material passing the sensor element, high amount of measurement cycles.
Technical data
Transport and Storage
Transport Observe the instructions as stated on the transport packaging, otherwise the products may get damaged.
Transport temperature: -40 .. +80°C (-40 .. +176°F)Transport humidity: 20 .. 85%
Transport incoming inspections must be caried out to check for possible transport damage.
Storage Products must be stored at a dry and clean place. They must be protected from influence of corrosive environment, vibration and exposure to direct sunlight.
Storage temperature: -40 .. +80°C (-40 .. +176°F)Storage humidity: 20 .. 85%
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 9
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Approvals
Hazardous Locations* ATEX II 1/2 DFM Class. II, III Div.1 Gr. E-GTR-CU Ex ta/tb IIIC T! Da/Db X
General purpose * CE EN 61010-1FM General purposeTR-CU
EMC EN 61326 - A1 (industrial standard)
RoHS conform According to directive 2011/65/EU
* Depending on selected version in selection list
Technical data
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011610
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Sensor weight guide (solids measurement)
Technical data
Sensor weight Application Note Fits through mounting hole
* Material densitiy
g/l (lb/ft3)
Material consistence
Angle of repose
Max. process temp.
Thread Flange
11/2" 3" 2" 3" DN100/ 4"
PVC without pin
>300(18)
granulate flat 80°C (176°F)
Standard weight •
PVC with pin
>300(18)
granulate, powder
steep 80°C (176°F)
The pin penetrates into the material and avoids slipping or tilting of the sensor weight on the steep bulk surface.
•
Stainl. steel >300(18)
granulate, powder
flat, steep
250°C (482°F)
The pin penetrates into the material and avoids slipping or tilting of the sensor weight on the steep bulk surface.
• • • • •
Claw >200(12)
coarse (e.g. stones)
steep 250°C (482°F)
Avoids slipping or tilting on the steep bulk surface.
•
Folding cover >20(1.2)
light powder flat, steep
80°C (176°F)
Big surface prevents the sensor weight from sinking into the material.
• • • • •
Spider >40(1.4)
light powder flat, steep
250°C (482°F)
Big surface prevents the sensor weight from sinking into the material.
•
Bag >300(18)
granulate, powder
flat 80°C (176°F)
Prevents damage of the conveying screw. To be filled with bulk material.
•
Float - liquids only - 80°C (176°F)
To be filled with material.
PVC without pin
Stainless steel
Claw
Folding cover
Spider
BagFloat
PVC with pin
* The above mentioned data is a guideline and is valid for material which has settled after filling.During the filling the bulk density can change (e. g. for fluidised material).
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 11
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Options
Window in lid andexternal start button
Enables to see the display through the closed lid and to start a measurement without opening the lid.
Material of the window: break-proof glass.Drawing see page 5
Weather protection cover
If the unit is used outdoors, the use of the weather protection cover is recommended. It protects the device from all atmospheric influences such as• rain water• condensation water• excessively high temperatures • excessively low temperatures in winterMaterial: PE, weather and temperature stable
For use in Hazardous Locations only permitted for Zone 22 or Division 2.
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011612
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Mounting
General Safety Instructions
Process pressure Improper installation may result in loss of process pressure.
Chemical resistance against the medium
Materials of construction are chosen based on their chemical compatibility (or inertness) for general purposes. For exposure to specific environments, check with chemical compatibility charts before installing.
Mounting location The right mounting place is significant for a proper function. Observe mounting instructions.
Vibrations Avoid mounting in applications with strong vibration. Use rubber mounts for absorption in case of light vibrations.
Mounting instructions
Mounting position • The unit is mounted vertically on the silo. Max. deviation is 2°.
• There must be at least 200 mm (7.87“) space for the sensor weight to move down in case of a full silo. Observe the bottom of the sensor weight at "upper stop position" (dimensions see page 4 - 6). With overfilling the rope/tube may break.
Additional Safety Instructions for Hazardous Locations
Installation regulations For devices to be used in Hazardous Locations the respective valid installation regulations must be observed.
Sparks The installation has to be done in a way, that mechanical friction or impact does not cause sparks between the aluminium enclosure and steel.
• The socket pipe of the unit must protude at least 50 mm (2") into the silo. A version with longer socket pipe is available.
• Proper movement of the sensor weight must be guaranteed, even if the sensor weight oscillates. Observe enough distance to the silo wall, stanchions and built-in fittings.
• For measurements through a long pipe in a double chamber silo we recommend the use of NB 3200 (tape version).
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 13
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Mounting
Measurement during filling of the silo
Filling of the silo while measuring might cover the sensor weight with bulk material. Measurements during filling are possible, if there is enough distance to the infeed, so that no material can fall on the sensor weight.
Sensor weight "Bag" and "Float"
• The weights are filled with plastic granulate or sand. They shall be filled on site with bulk material or liquid, which is not critical if mixed with the material stored in the silo. Consider ageing of the material.
• When filling, observe the total weigth of the sensor: rope version 1.0 kg (2.2 lbs), tape version 2.1 kg (4.6 lbs)
Sealing • A rubber seal must be used to tighten the flange.• Close both lids of the enclosure tightly.
Sensor weight which does not fit through the mounting hole
The sensor weight must be removed before placing the unit on the silo. An inlet close to the fixing loacation and a hook is needed.
See installation manual for more details. Hook
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011614
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Electrical installation
Handling In case of improper handling or handling malpractice, the electric safety of the device cannot be guaranteed.
Installation regulations The local regulations or VDE 0100 (Regulations of German Electrotechnical Engineers) must be observed.
Fuse Use a fuse as stated in the connection diagrams.
RCCB protection In case of a fault, the supply voltage must be automatically switched off by a RCCB protection switch to protect against indirect contact with dangerous voltages.
Power supply switch A voltage disconnection switch must be provided near the device.
Wiring diagram The electrical connections are made in accordance with the wiring diagram.
Supply voltage Compare the supply voltage applied with the specifications given on the name plate before switching the device on.
Cable gland The screwed cable gland and closing element must have following specifications: Ingress protection IP66, temperature range from -40°C to +70°C, UL or VDE or INMETRO certified (depending on the country where the unit is installed), pull relief. Make sure that the screwed cable gland safely seals the cable and that it is tight (danger of water intrusion). Cable glands that are not used have to be sealed with a blanking element.The diameter of the field wiring cable has to match to the clamping range of the used cable gland.
Conduit system In case of using a conduit system (with NPT thread) instead of a cable gland the regulations of the country, where the unit is installed, must be observed. The conduit must have a tapered thread either NPT 1/2“ or NPT 3/4” in accordance with the unit and ANSI B 1.20.1. Not used inlets must be closed tight with a metal blanking element.
Field wiring cables • The diameter has to match to the clamping range of the used cable gland.• The cross section has to match with the clamping range of the connection terminals and consider the max. current. • All field wirings must have insulation suitable for at least 250 V AC. • The temperature rating must be at least 90°C (194°F).• If higher immunity interferences as specified in the stated EMC standards are present (see chapter approval), a shielded cable is required, otherwise an unshielded instrumentation cable is satisfactory.
Guiding the cables in the terminal box
Cut the field wiring cables to appropriate length to fit properly into the terminal box.
Relay protection Provide protection for relay contacts to protect the device against inductive load surges.
Protection against static charging
The housing of the unit must be grounded to avoid static charging of the unit. This is particularly important for applications with pneumatic conveying and non-metallic containers.
General Safety Instructions
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 15
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
External equipotential bonding terminal
Field wiring A strain relief must be provided for the field wiring cables, if the device is installed with the factory provided cable glands.
Cable glands for ATEX/ TR-CU Hazardous Locations
The used entry devices and blanking elements must have an adequate type approval and a temperature range as defined in the technical data of the unit. In addition they shall be suitable for the conditions and correctly installed. Where available the provided original parts of the manufacturer must be used.
Conduit system for FMHazardous Locations
In addition the regulations of the country must be observed. The used flameproof seals and blanking elements must have an adequate type approval and a temperature range as defined in the technical data of the unit. In addition they shall be suitable for the conditions and correctly installed. Where available the provided original parts of the manufacturer must be used.
Comissioning/ opening the lid
Comissioning only, when there are no dust deposits or swirls present.
Additional Safety Instructions for Hazardous Locations
Connect to equipotential bonding of the plant
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011616
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Electrical installation
Relais
Power supply
0/4-20 mA
Modbus RTUProfibus DP
Start input
El. counting pulse
Terminal location
Power supply and Signal input/ output
Display
Protective conductor terminal
Full detector input
Power supply
Signal input:Start of measurement
98 .. 253 V 50 - 60 Hz 20 .. 28 V DC
AC or DC supply depending on ordered version
DC versionAC version
Start contact Start +24 V
alternative
Signal description:See page 20
Measurement interruption in case of filling. If used, remove factory provided connection.
0.14 .. 2.5 mm2 (AWG 26 .. 14)
Internal fuse AC version: 1.25 A, slow, HBC, 250 VDC version: 4 A, slow, HBC, 250 V
1.5 .. 2.5 mm2 (AWG 15 .. 13)
0.75 .. 2.5 mm2 (AWG 18 .. 13)
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 17
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Electrical installation
Signal input:Full detector
Signal output:0/4-20 mA
Signal output:Relay
Signal output:Electronic counting pulse
max. 500 Ohm
Relay1
max. 250 V AC, 2 A, 500 VA, non inductive
Fuse: max. 2 A, fast or slow, HBC, 250 V
max. 30 V DC, max. 25 mA
Fuse: max. 63 mA fast and slow
Optocoupler Note: Reset pulse is done with Relay 2
Signal description:See page 20
Signal description:See page 20
Relay2 Relay3 Relay4
Signal description:See page 21
active, isolated *
Signal description:See page 20
0.14 .. 2.5 mm2 (AWG 26 .. 14)
0.14 .. 2.5 mm2 (AWG 26 .. 14)
0.14 .. 2.5 mm2 (AWG 26 .. 14)
0.14 .. 2.5 mm2 (AWG 26 .. 14)
* CAUTION: If connecting to a PLC with isolated (floating) 4-20 mA input, the "-" line must be connected to ground of the PLC. See user manual of the PLC.
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011618
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Electrical installation
Modbus network Profibus DP network
Wiring according to Profibus DP standards
Setting Biasing and Termination Resistor
For use of NB 3000 units in a external Modbus or Profibus network, it is possible to set Biasing and Termination Resistor on each unit as required.
*factory provided
Biasing OFF* OFF ON
Termination Resistor
OFF* ON ON
Version with Jumper
Version with DIP switch
Biasing OFF* OFF ON ON
Termination Resistor
OFF* ON OFF ON
Wiring according to Modbus standards
DIP Switch position:
Side viewTop view
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 19
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Signal input: Start of measurement
• Floating contact (terminal 24, 25) or• 24 V DC voltage (terminal 25, 27), current consumption approx. 25 mA, observe the polarity.
Duration of starting signal: 0.7 to 5 sThe contact must be closed or the 24 V signal must be present to start.
Measurement interruptionUsed to avoid a measurement in case of filling and to interrupt a running measurement when filling starts. When the terminal 24 und 26 are opened, the sensor weight returns to the upper stop position. If required, remove factory provided wire between terminal 24 and 26 and connect to the filling coupling. The contact must be closed to enable a measurement.
Signal input:Full detector
Enables to implement a full detector signal in the Modbus or Profibus.When the signal is present (terminal 24 - 28 closed) the yellow LED next to the display in on.
Signal output: 0/4-20 mA
Programmable to indicate a level or a volume signal. The output is updated, when the sensor weight touches the surface of the bulk good. It stays until the next measurement is done.
Signal output: Relay
Relais can be setted as shown in the following table:
Relay 1 Relay 2 Relay 3 Relay 4
Factory settings Counting pulse Reset pulse Failure Upper stop positionProgrammable Limit switch 1 Limit switch 2 Maintenance Maintenance
Relais 1/2 set to Counting/ Reset pulse:
The counting pulse output is used to connect an external digital counter or a PLC with counting input.
Reset pulse (terminal 6 and 7):After start of measurement, a reset pulse is given. It is used to reset the connected evaluation device (counter/ PLC, ...).
Counting pulse (terminal 5 and 6):The counting pulse communicates the measured value to the connected evaluation device. During the downward movement of the sensor weight, this pulse is generated according to the following table:
Relais 1/2 set to Limit switch:
It is possible to indicate two independent level limit switches. The limit switch signal is derivated from the analogue measurement signal (details see Programming page 26)
Relay 3 - set to "Failure"
The relay indicates a failure (see also programming on page 27 and diagnostics "Failure" on page 37)
Relay 3 - set to "Maintenance"
The relay indicates a necessary maintenance (see also programming on page 27 and diagnostics "Maintenance" on page 35)
Signal overview
Start
Reset
Counting
Timing
Signal input / output
Counting pulseprogrammed to: ON OFF
10cm (1/3ft) / pulse 0.13s 0.13..0.3s5cm (1/6 ft) / pulse 0.07s 0.07..0.15s
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011620
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Signal overview
Diagnostics signals
Failure Result is a non valid measurement.Red LED is on. Relay 3 indicates Failure.The signal indicates critical situations. Evaluation can help to avoid losing the sensor weight inside the silo.
If Failure is indicated, the unit must be checked on site.
Failure codes description see page 37.
Maintenance Result is an indication for the user with still valid measurement.Red LED is blinking. Relay 4 indicates Maintenance (programmable).The signal enables a preventive maintenance. Evaluating can help to avoid loosing the sensor weight inside the silo.
If Maintenance is indicated, the measurement process can be continued.
Maintenance codes description see page 35.
Relay 4 - set to "Upper stop postition"
The signal allows the user to determine whether the measurement has come to its end. In this case the sensor weight is in its upper stop position, relay contacts are closed.
Relay 4 - set to "Maintenance"
The relay indicates a necessary maintenance (see also programming on G27 and diagnostics "Maintenance" on G35)
Signal output: Electronic counting pulse
Counting pulse (terminal 3 and 4):The electronic counting pulse enables a high amount of pulses to receive a high resolution of the measurement signal.
Note: The reset pulse is done with relay 2.
LED statusLED StatusLED`s next to the Display Green is on Power On
Red is on FailureRed is blinking MaintenanceYellow in on Full detector input present
LEDs next to relais terminals Yellow is on Relay is energised
Counting pulseprogrammed to: ON OFF
2,5 cm (1/10 ft)/ pulse
25 ms 25 .. 70 ms
1 cm (1/20 ft)/ pulse 10 ms 10 .. 30 ms
Start
Reset
Counting
Timing
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 21
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Quickset menu
Max. adjustable length of 30/ 50 m depending on ordered version.* Factory-provided
The Quickset menu is used for fast and easy start-up of the system.If the unit is working in normal operation (measurement mode), the SETUP button brings up the Quickset menu.
Press to return to measurement mode
Measurement mode0.0m (0.0ft)
Max. move distance M
Silo height H
Air distance A
Cone height C
Language
*Deutsch English Francais Russian
Unit
Programming
0 .. 30/ 40/ 50 m (0 .. 100/ 133/ 164 ft)*1 m (3 ft)
0 .. 30/ 40/ 50 m (0 .. 100/ 133/ 164 ft)*0 m (0 ft)
0 .. 30/ 40/ 50 m (0 .. 100/ 133/ 164 ft)*0 m (0 ft)
0 .. 30/ 40/ 50 m(0 .. 100/ 133/ 164 ft)*0 m (0 ft)
*Meter, Distance Meter, Empty Level Meter, Level Feet, Distance Feet, Empty Level Feet, Level
100%
0%
Leve
lE
mp
ty L
evel
Dis
tanc
e
Display
Unit - Defines if units are meter or feet.- Defines what shall be stated on the display of the unit. This is not related to the signal output.
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011622
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Con
e he
ight
C
A
ir d
ista
nce
A
Max
. mov
e d
ista
nce
M
Silo
hei
ght H
100%
0%
Max. move distance M Ensures that the weight does not enter into the silo outlet.
Silo height H Definition of 0% level output.Note: If the maximum move distance M is smaller than the silo height H, the measured value will always be more than 0%.
Air distance A Definition of 100% level output.
Cone height C Enables to set the current output as volume.C =0 Current output indicates material levelC >0 Current output indicates material volume
Note:When using the digital pulse output (terminal 5/ 6/ 7, see page 18/ 21) the parameters silo height H, air distance A and cone height C have no influence on the measurement value.
see page 4 - 6
X+A
Programming
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 23
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Programming
Advanced menus(use only if necessary)
With the advanced menues it is possible to set the outputs and to display the actual state of the unit.
Entering the advanced menues: If the unit is working in normal operation (measurement mode), press both "arrow" buttons together for approx. 2 seconds.
Measurement mode0.0 m (0.0 ft)
Output Adjustment menu
Press both buttons together
for 2 secondsDiagnostics menu
Communication menu
Press to return to measurement mode
Entering into the Output Adjustment menu(see page 25)
Entering into the Diagnostics menu(see page 28)
Entering into the Communication menu(see page 30)
To reset all programmed parameters to factory setting (default values), press the buttons ARROW UP, ARROW DOWN and SETUP together for approx. 10 seconds.
Programming buttons
Continues with next adjustment item
Continues with measurement display after parameter adjustmentStarts measurementCancels a Failure or Maintenance message
Increases the value to be adjusted
Decreases the value to be adjusted
Factory settings
Runtime messagesDuring measurement mode, following runtime indications are given:
* Upper Stop Position is reached
Motor is moving the sensor weight downwards resp. upwards (fast mode)
Motor is moving in slow mode (shortly after motor start and before Upper Stop Position is reached)
Measurement interruption is active (terminal 24-26 not connected, see page 20)
Measurement interruption is active (signal is set via Modbus)
Note: Pressing the ARROW DOWN button in measurement mode brings up more service information (not described in this manual
Blocked 24 - 26 open
Blocked Modbus
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011624
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Programming
Output Adjustment menuThe Output Adjustment menu is used for setting the 0/4-20mA, relais and internal timer
Current output mode
* Factory provided
Current at error
Relay 1/2*Pulse/ Reset Limit switch
Pulse distance
*10 cm (2.5 cm) 5 cm (1 cm) 1/3 ft (1/10 ft) 1/6 ft (1/20 ft)
After selecting Pulse/ Reset:
After selecting Limit switch:
Relay1 L1
Relay1 EN/DEN
Relay1 L2
0 .. 30/ 40/ 50 m0 .. 100/ 133/ 164 ft(*0 m)
0 .. 30/ 40/ 50 m0 .. 100/ 133/ 164 ft(*0 m)
*DEN EN
Relay 3
*Upper stop position Maintenance
*DEN EN
Relay 4
DEN*EN
Timer*OFF 0.05 h/ 0.1 h .. 99.9 h
Relay2 L1
Relay2 EN/DEN
Relay2 L2
0 .. 30/ 40/ 50 m0 .. 100/ 133/ 164 ft(*0 m)
0 .. 30/ 40/ 50 m0 .. 100/ 133/ 164 ft(*0 m)
*DEN EN
Press 2x to return to
measurement mode
*0mA 3.6mA 4mA 20mA 22mA Remain
*4-20mA 0-20mA 20-4mA 20-0mA
*Failure Maintenance Both
Current error when
Failure Maintenance*Both
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 25
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Current output mode
Current at error In case of error (Failure, Maintenance) the current output shows the adjusted value.It can also be adjusted, whether the current output shall indicate Failure or Maintenance or both situations.
Relay 1/2 Selects, if Relay 1 and 2 shall work as Counting/ Reset pulse output or as two independently programmable limit switches.
Selecting Pulse/ Reset:Relay 1 works as Counting pulse output with selected pulse rate (the values in brackets are valid for the version with Electronic counting pulse). Relay 2 works as Reset pulse. Details see Signal Overview on page 20.
Selecting Limit switch:The relais are programmed with the distance from the sensor weight bottom to the required material surface switching point. The relais can be set to energise or de-energise. The relay logic is as follows:
DEN The relay is normally de-energised and is energised when the product rises above the L1 level. It remains energised until the product falls below the L2 level.
EN The relay is normally energised and is denergised when the product rises above the L1 level. It remains denergised until the product falls below the L2 level.
L1 L1 is the upper switching point.
L2 L2 is the lower switching point. Note: L2 must always be greater than L1.
Note: The limit switch outputs are updated after a measurement cycle.
Mode Mode
LED at relay
Relay
OFF De-energised
ON Energised
Programming
SettingCurrent output at
level
0% 100%
4-20 mA
0-20 mA
20-4 mA
20-0 mA
4 mA
0 mA
20 mA
20 mA
20 mA
20 mA
4 mA
0 mA
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011626
100%
0%
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Programming
Relay 3 Selects, if relay 3 shall indicate Failure, Maintenance or both situations.
Relay 4 Selects, if relay 4 shall indicate "Upper stop position" or Maintenance.
Timer Automatic start of measurement with timer function.
The timing interval between two measurements can be adjusted between 0.05 h (3 minutes) for the version with brushless motor (otherwise 0.1h (6 minutes)) and 99.9 hours. Position „off“ causes no automatic measurement start.
The timer will be reset:• after finishing a measurement• after linking the terminals 24/ 26 (measurement interruption during filling)
For automatic measurement at a predetermined time of day, an external start unit connected to terminals 24/ 25/ 27 is necessary.
To avoid needless wear and tear, the unit should not be started more often than necessary.
Mode Mode
Not present
Failure/ Maintenance
Present
Mode Mode
Not present
Upper stop position/ Maintenance
Present
* factory provided
* factory provided
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 27
DEN *
DEN EN *
EN
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Diagnostics menuThe Diagnostics menu is used to diagnostics the unit status and for manual motor driving mode
Failure/ Maintenancehistory
Manual motor control
Rope/ tape maintenance
Total run time
Current output check
Firmware version
Sensor weight moves up or down while pressing
Scrolls through the messages
Press 2x to return to measurement mode
Motor maintenance
Total cycles
Cycles left
Reset
Cycles leftxxx
Run time left
Reset
Run time leftxxx
Actual current: 10 mA
Programming
SD card*Disable Enable
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011628
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Programming
Firmware version States the firmware version of the unit.
Manual motor control The motor moves the sensor weight upwards while the "ARROW UP" button is beeing pushed.The motor moves the sensor weight downwards while the "ARROW DOWN" button is beeing pushed.
Note: If the sensor weight is in the upper stop position or touching the bulk material surface or after the max. move distance, the motor is automatically stopped.
CAUTION: Avoid the sensor weight reaching the outlet position of the silo.
Failure / Maintenance history
Indicates the last 93 error messages related to the motor run time after switching on the power supply for the first time. Messages can be scrolled up and down with the "ARROW" buttons. If "None" is indicated, there is no message filed. The messages and the time information are permanently filed even when the power supply is switched off. Details of the messages see page 35 - 37
Examples of indicating a Failure:
Hist. 0512h 1350s0348h 2400s +F11Meaning: Actual motor run time is 512 hours and 1,350 seconds after first power on. At 348 hours and 2,400 seconds the Failure F11 came up
Hist. 0512h 1350s0356h 1920s -F11Meaning: Actual motor run time is 512 hours and 1,350 seconds after first power on. At 356 hours and 1,920 seconds the Failure F11 was resetted
Total cycles Indicates how many measurement cycles have been performed up to now.
Rope/tape maintenance Cycles left: Indicates how many measurement cycles are left until the next rope/ tape failure message F16 will appear and the unit will stop working.
Reset: Can be done after a rope/tape change, if the Maintenance message was not yet present. It sets the internal counter to zero to have the full amount of measurement cycles until the next maintenance message will appear.
Note 1: After a Maintenance message is reset with the "START" button, the rope/tape maintenance counter is automatically set to zero.Note 2: The number of preset cycles to the next maintenance message depends on the use of rope or tape version.
Total run time Indicates, how long the motor has been runnning up to now (in hours).
Motor maintenance Run time left: Indicates, how much motor run time (in hours) is left, until the motor failure message F17 will appear and the unit will stop working.
Reset: Can be done after a motor change, if the Maintenance message was not yet present. It sets the internal counter to zero to have the full amount of motor run time until the next maintenance message will appear.
Note 1: After a Maintenance message is reset with the "START" button, the motor maintenance counter is automatically set to zero.
Current output check Enables to check, if the current output is working proper. The current output is forced to 10 mA. This can be evaluated by an external connected multimeter.
SD card Optional use for service aspects (not explained in this manual).After connecting a SD card to the electronics, this parameter shall be set to "Enable". Before removing the SD card, it shall be set back to "Disable".
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 29
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Programming
Communication menuThe Communication menu is used for setting parameters of Modbus RTU and Profibus DP
Protocol
Baudrate**
*Modbus RTU Profibus DP
1,200 2,400 4,800 9,600*19,200 38,400 57,600
1 .. 247(*31)
* Factory provided** Displayed only with Modbus. With Profibus Baudrate is set automatically.
Press 2x to return to measurement mode
Protocol Selects if Modbus RTU or Profibus DP protocol is used.
Adress Selects the used communication adress.
Baudrate Selects the used baudrate.
Address
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011630
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Programming
40051 M_START Start of a measurementStart 1
W
40046 M_DISTANCE Actual measured distance, in mmNote: After the unit has finished the measurement, the M_STATUS register states “Ready, measurement valid” (the Modbus master must read the M_STATUS register). Then the data on the register M_DISTANCE is valid.
R
40055 M_VOLUME Actual measured volume (considering the programmed cone height, air distance and silo height), in ‰See note on register M_DISTANCE
R
40052 M_INHIBIT Block command (allows to block the unit, so that no measurement can be started)No block 0Block 1The unit will remain blocked as long as the register has the value “Block”.Note: Unit states the blocked status through the M_ STATUS register.
W 0
40045 M_STATUS States the functional status of the unitBlocked 1 Ready, measurement not valid 2Ready, measurement valid 6 Busy 8Failure present 16 Temporary not ready 32 -> Explanation see next page
R
Measurement
Modbus RegisterThe following registers describe the communication via Modbus.
CAUTIONWriting to the registers different from what is stated will cause a miss function of the unit
Setup
Register address
Register name
Register description
Register use
Default value
40001 M_LANGUAGE Language on the menuDEUTSCH 0ENGLISH 1FRANCAIS 2RUSSIAN 3
R/W 0
40002 M_UNIT Unit used for distance visualisationMETER 0FEET 1
R/W 0
40003 M_MAX_MOVE_DIST Max. move distance mm R/W 1000
40004 M_SILO_HEIGHT Silo height mm R/W 0
40005 M_AIR_DIST Air distance mm R/W 0
40006 M_CONE_HEIGHT Cone height mm R/W 0
40022 M_TIMER Timer interval (for automatic start of measurements), in 1/100 hours (Off = 0)Notes: 1/100 hour = 36 secMinimum time for standard motor: 0.10 hours (value =10) Minimum time for brushless motor: 0.05 hours (value = 5)
R/W 0
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 31
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Programming
Total measured cycles up to now = “M_TOTAL_CYCLES” + 65536 * “M_TOTAL_CYCLES_H”
40026 M_TOTAL_CYCLES Total measured cycles up to now, in cycles R
40044 M_TOTAL_CYCLES_H Total measured cycles up to now, in 65536 cycles R
Measurement cycles left until failure message F16 will appear= “M_CYCLES_LEFT” + 65536 * “M_CYCLES_LEFT_H”
40028 M_CYCLES_LEFT Measurement cycles left until F16 will appear, in cycles R
40050 M_CYCLES_LEFT_H Measurement cycles left until F16 will appear, in 65536 cycles R
Total motor run time up to now = “M_TOTAL_RUN_TIME” hours + “M_TOTAL_RUN_TIME_S” seconds
40029 M_TOTAL_RUN_TIME Total motor run time up to now, in hours R
40048 M_TOTAL_RUN_TIME_S
Total motor run time up to now, in seconds R
40031 M_RUN_TIME_LEFT Motor run time left until F17 will appear, in hours R
40053 M_FAILURE Failure status of the unit (stated on a bit basis)F10 – Motor or motor-driver-electronic defect b0 = 1F11 – Sensor weight is buried b1 = 1F12 – Rope/tape broken b2 = 1F13 – Rope/tape too short or jammed in the rope roller b3 = 1F15 – Not enough current from power supply b4 = 1F16 – Service interval rope/tape b5 = 1F17 – Service interval motor b6 = 1
R
40054 M_MAINTENANCE Maintenance status of the unit (stated on a bit basis)M10 – Deflection pulley moves not smooth b0 = 1M11 – Sensor weight blocked inupper position b1 = 1M16 – Service interval rope/tape b3 = 1M17 – Service interval motor b4 = 1
R
Diagnostics
40034 M_PROTOCOL Bus protocol used for communicationModbus 0
R/W 0
40035 M_ADDRESS Device address 1 to 247 R/W 31
40036 M_BAUDRATE Communication speed1,200 baud 02,400 baud 14,800 baud 29,600 baud 319,200 baud 438,400 baud 557,600 baud 6
R/W 4
Communication
R/W: read/write R: read only W: write only
Explanation:Blocked: No measurement can be started.Ready: A new measurement can be started.Measurement valid: Indicates a valid measurement.Measurement not valid: Indicates a maintenance condition (details see M_MAINTENANCE)Busy: A measurement is actually running.Failure present: No new measurement can be started (details see M_FAILURE)Temporary not ready: No measurement can be started due to internal actions (usually during upwards movement of the sensor weight).
R
40057 M_FULL_DETECTOR States the full detector input status Contact open (24-28) 0Contact close (24-28) 1
R
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011632
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Commissioning: Interface measurement
Deflection-pulley-bar
Sensor weight
Stainless steel or plastic discs
Lid
Adjustment nut
Applications Measurement of solids in water like mud, sand, bed ash, sediment, stones etc.Rope version: The material surface can be soft/ muddy or compact. Sensitivity adjustment possible.Tape version: The material surface must be compact (the sensor weight cannot sink in). No sensitivity adjustment possible.
Principle The sensor weight penetrates into the water and stops when touching the solid surface.
General items
Sensitivity adjustment (rope version)
General The sensitivity (needed release force for the sensor weight when touching the solid surface) can be set to the requirements of the application.Sensitivity adjustment is done by lowering the sensor weight into the water by using the "Manual motor control" (see page 28).
1. Coarse adjustment Coarse adjustment is done to avoid the detection of the water surface.
When penetrating into the water, the weight must not float. This can be checked by watching the deflection-pulley-bar. If the deflection-pulley-bar will move briefly upwards while penetrating into the water, the sensor weight floats and needs to be heavier. This is achieved by unscrewing the lid of the sensor weight and replacing one or more plastic discs by stainless steel discs. For soft/ muddy surfaces the sensor weight shall be as light as possible to keep it from sinking into the bulk material surface (see step 2).
Note: It is important that the sensor weight is completely filled with discs to avoid intrusion of air.
2. Fine adjustment Fine adjustment is done to keep the sensor weight from sinking into a soft/ muddy material surface.
• Turn adjustment nut anti clockwise: measurement becomes more sensitive (for soft/ muddy surface)• Turn adjustment nut clockwise: measurement becomes less sensitive (for more compact surface)• Fix the adjustment nut with the counter nut
The adjustment was sucessful if the sensor weight penetrates the water surface easily and detects the material surface without sinking in.
cw
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 33
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Maintenance
Opening the lid (cover) Before opening the lid for maintenance reasons observe following items: • Do not remove the lid while circuits are alive.• No dust deposits or whirlings are present.• No rain can enter into the housing
Frequent check of the unit
To ensure durable safety in hazardous locations and with electrical safety, following items must be checked frequently depending on the application:• Mechanical damage or corrosion of any components (housing side and sensor side) and of the field wiring cables.• Thight sealing of the process connection, cable glands and enclosure lid.• Properly connected external PE cable (if present).
Cleaning If cleaning is required by the application, following must be observed:• Cleaning agent must comply with the materials of the unit (chemical resistance). Mainly the lid sealing, cable gland and the surface of the unit must be considered.
The cleaning process must be done in a way, that:• The cleaning agent cannot enter into the unit through the lid sealing or cable gland.• No mechanical damage of the lid sealing, cable gland or other parts can happen.
A possible accumulation of dust on the unit does not increase the maximum surface temperature and must therefore not be removed for purposes of maintaining the surface temperature in hazardous locations.
Production date The production date can be traced by the serial number on the typeplate. Please contact the manufacturer or your local distrubutor.
Spare parts All available spare parts are stated in the selection list
General items
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011634
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Maintenance
Diagnostics: MaintenanceResult is an indication for the user with still valid measurement.Red LED is blinking. Relay 4 indicates Maintenance (programmable).The signal enables a preventive maintenance. Evaluating the signal can help to avoid losing the sensor weight inside the silo.If Maintenance was indicated, the measurement process can be continued.
Mainte-nance code
Description Performance of the device Solution
M10 Deflection pulley moves not smooth/ regular
Message is shown, measurement can be continued.If the following 5 measurement cycles after indication are okay, the message will automatically disappear.
Check for proper movement of the pulley.Check for possible slipping of the rope/ tape on the pulley.
M11 Sensor weight blocked in "upper stop position" or block distance of sensor weight to short
The unit tries to start 5 times. If the sensor weight is not released during this time, the message is shown. If after a new measurement start the sensor weight is released, the message will automatically disappear.
Release sensor weight. Ensure, that the min. moving distance (block distance) is > 200 mm (7.87“)
M12 SD card not working properly
In the diagnostics menu the setting "SD card Enable" is done but SD card is not present or not working properly
Set the menu to "SD card Disable" or change SD card
M16 Service interval: rope/ tape
The amount of measurement cycles has reached 70% of the rope/ tape lifetime.
To further guarantee faultless performance, it is strongly recommended to change the rope/tape.
After resetting the message, the internal counter for the rope/ tape cycles is reset to zero.
If the message is not reset, the unit will continue measuring, until 90% of the rope/tape lifetime is reached. Then Failure F16 will come up.
Change rope/ tape.
M17 Service interval:motor
The actual run time has reached 70% of the motor lifetime.
To further guarantee faultless performance, it is strongly recommended to change the motor.
After resetting the message, the internal counter for the motor run time is reset to zero.
If the message is not reset, the unit will continue measuring, until 90% of the motor lifetime is reached. Then Failure F17 will come up.
Change motor
Deflection- pulley
Upper stop position Sensor
weight
By pushing the START button the actual stated messages shown on the display can be reset.
If more than one message is present, the one with a lower code is shown on the display. After reset with the START button, the next one will be stated.
Possibilities to see a maintenance history: see page G28. Rope/ tape roller
Before removing the rope/ tape roller, remount the unit from the silo to avoid, that the sensor weight can fall into the silo.
CAUTION
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 35
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Rope
Measurements per dayLi
fe t
ime
in y
ears
Maintenance
Rope/ Tape lifetimeThe expected life time (measurement cycles) for the rope/ tape is:Rope version: approx. 200,000 Tape version: approx. 500,000
Note: These values refer to lifetime tests under the following conditions: No excessive material influence. The sensor weight meets an inclined surface, so that an oscillating movement of the sensor weight during upwards movement is caused.
The maintenance message is displayed at 70%, the failure message at 90% of the expected lifetime to provide some safety. For further information see message M16 and F16.
See figure on right hand for the operating time depending on the measurement cycles per day.
For applications with adverse conditions it is recommended to change the rope/tape more frequently.
Motor lifetimeThe expected life time (run time) for the motor is:
Version for high measurement frequency (brushless motor): approx. 60,000 hours
Version with standard motor (brush motor): approx. 3,500 hours
The maintenance message is displayed at 70%, the failure message at 90% of the expected lifetime to consider some safety. For further informations see message M17 and F17.
See figure on right hand for the operating time depending on the measurement cycles per day.
Brush motor10 m*
*average measurement distance
Measurements per day
Life
tim
e in
yea
rs
Brush motor20 m*
Tape
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011636
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Maintenance
Failure code
Describtion Indication Performance of the device Solution
F10 Motor or motor-driver-electronic defect
Motor does not rotate when it is actuated. Evaluation by the hallsensor on the rope/tape roller.
If possible, the sensor weight will be moved up to the "Upper stop position".
Check motor connection. Motor or electronic change.
F11 Sensor weight is buried or jammed
Difference of distance between down and up movement too big. Evaluation by the hallsensor on the rope/ tape roller.
Motor moves 4 seconds upwards, then waits 10 seconds. After that motor moves shortly downwards and then upwards again. If the sensor weight is still jammed, this cycle is repeated 5 times. After that the cycle goes on with a delaytime of one hour.
Release the sensor weight. Make sure, that the sensor weight can move freely.
F12 Rope/ tape broken
Motor is running but the upper stop position is not reached. Evaluation by the hallsensor on the rope/tape roller on the deflection pulley bar.
Motor moves upwards. If after a certain time the upper stop position is not reached, the motor stops.
Repair of rope/ tape break.Check, if rope/tape maintenance was properly done. Check possibility of buried sensor weight.
F13 Rope/ tape too short or rope jammed in the rope roller
The deflection pulley and the rope/tape roller move in different directions. Evaluation by the Hall sensors on the pulley and the rope/tape roller.
Motor direction is selected so the sensor weight moves upwards until upper stop position is reached.
Check if the rope/ tape is too short compared to the adjusted minimum safety setting.Check if the rope is jammed in the rope roller and wound in the wrong direction.
F15 Not enough current available from DC power supply (DC version only)
Supply voltage drops during function.
Sensor weight is moved to the upper stop position.
Enable enough supply current according to the technical data specification.
F16 Service interval: rope/ tape
The amount of measurement cycles is 90% of the rope/tape lifetime. See also maintenance message M16.
The measurement cannot be restarted.
Change rope or tape.
F17 Service interval: motor
The actual run time is 90% of the motor lifetime. See also maintenance message M17.
The measurement cannot be restarted.
Change motor.
Deflection- pulley
Upper stop position Sensor
weight
Diagnostics: FailureResult is an invalid measurement.Red LED is on. Relay 3 indicates Failure.The signal indicates critical situations. Evaluating the signal can help to avoid losing the sensor weight inside the silo.If Failure is indicated, the unit must be checked on site.
By pushing the START and SETUP button together for 2 seconds, the message shown on the display can be reset.
Possibilities to see a failure history: see page G28.
CAUTIONResetting F16 or F17 without changing the rope/ tape respective the motor will cause material damage by a broken rope/ tape.
Rope/ tape roller
Before removing the rope/ tape roller, remount the unit from the silo to avoid, that the sensor weight can fall into the silo.
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 37
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Notes for use in Hazardous Locations
Zone classification
* in case of conductive dust, additional requirements for installation are necessary.
Silo wall
inside silo
outsidesilo
Zone 22(Category 3)
Zone 21(Category 2)
Zone 20(Category 1)
General notes
Marking Devices with Ex-approval are marked on the type plate.
Process pressure The device construction allows process over-pressure up to 0.3 bar (4.4 psi) (option 1.7 bar (25 psi)). These pressures are allowed for test purposes. The definition of the Ex approvals are only valid for a silo-over-pressure between -0.2 .. +0.1 bar (-2.9 .. +1.45 psi).Out of these pressures the approvals are not valid.
Process and ambient temperature
The permitted temperature ranges are marked on the type plate.
Category useable in zone
1 D 20, 21, 222 D 21, 223 D* 22
Permitted zones (categories) for mounting in partition wall
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011638
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Notes for use in Hazardous Locations
Maximum Surface Temperature
The temperature marking on the name plate wrefers to the instruction manual.On the following table the relevant temperature ratings are shown.
The maximum surface temperature and the temperature class refer to the warmest area outside on the unit which can occur in failure case (according to EX definition).
Static discharge of the material surfaceIt must be ensured that no static discharge can occur when the grounded metal sensor weight or rope/ tape touches the surface of the bulk material. If this can not be ensured, the safe use of the unit is NOT guaranteed. The responsibility for this rests with the user. In case of inclarity an assessment from a notified body is necessary.
From the manufacturer side a version with a plastic sensor weight and additional plastic rope insulation part is available on request. This keeps a 500 mm (19.7") distance from the material surface to the grounded rope/ tape.
Max. ambienttemperature
Max. processtemperature
Max. surfacetemperature
Temp.class
60°C (140°F) 80°C (176°F) 130°C (266°F) T4
40°C (104°F) 90°C (194°F) 130°C (266°F) T4
100°C (212°F) 130°C (266°F) T4
110°C (230°F) 130°C (266°F) T4
120°C (248°F) 130°C (266°F) T4
130°C (266°F) 130°C (266°F) T4
135°C (275°F) 135°C (275°F) T4
140°C (284°F) 140°C (284°F) T3C
150°C (302°F) 150°C (302°F) T3C
Ambient
Process
Max. ambienttemperature
Max. processtemperature
Max. surfacetemperature
Temp.class
60°C (140°F) 80°C (176°F) 130°C (266°F) T4
130°C (266°F) 130°C (266°F) T4
135°C (275°F) 135°C (275°F) T4
140°C (284°F) 140°C (284°F) T3C
150°C (302°F) 150°C (302°F) T3C
160°C (320°F) 160°C (320°F) T3C
165°C (329°F) 165°C (329°F) T3B
170°C (338°F) 170°C (338°F) T3A
180°C (356°F) 180°C (356°F) T3A
190°C (374°F) 190°C (374°F) T3
200°C (392°F) 200°C (392°F) T3
210°C (410°F) 210°C (410°F) T2D
215°C (419°F) 215°C (419°F) T2D
220°C (428°F) 220°C (428°F) T2C
230°C (446°F) 230°C (446°F) T2C
240°C (464°F) 240°C (464°F) T2B
250°C (482°F) 250°C (482°F) T2B
Ambient
Process
Version for process temperature max. 80°C (176°F)/ max. 150°C (302°F)
Version for process temperature max. 250°C (482°F)
Nivobob® 1
2
3
4
5
6
7
8
9
10
11
12NB 3000 b gi020116 39
Continuous level measuring systemNB 3000Technical information / Instruction manual
page
Disposal
The product consists of materials which can be recycled, details of the used materials see chapter "Technical data - mechanical data". Recycling must be done by a specialised recycling company. Since the product is not subject to the WEEE directive 2002/96/EG, it is not permitted to bring it to a public recycling station.
Nivobob®1
2
3
4
5
6
7
8
9
10
11
12NB 3000 bgi02011640