GETTING STARTED GUIDE NI 9202 16 AI, ±10 V, 24 bit, 10 kS/s/ch Simultaneous

Transcript of NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring...

Page 1: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

GETTING STARTED GUIDE

NI 920216 AI, ±10 V, 24 bit, 10 kS/s/ch Simultaneous

Page 2: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

This document explains how to connect to the NI 9202. In thisdocument, the NI 9202 with spring terminal and the NI 9202 withDSUB are referred to inclusively as the NI 9202.

Note Before you begin, complete the software andhardware installation procedures in your chassisdocumentation.

Note The guidelines in this document are specific tothe NI 9202. The other components in the system mightnot meet the same safety ratings. Refer to thedocumentation for each component in the system todetermine the safety and EMC ratings for the entiresystem.

Safety GuidelinesOperate the NI 9202 only as described in this document.

Caution This icon denotes a caution, which advisesyou to consult documentation where this symbol ismarked.

2 | ni.com | NI 9202 Getting Started Guide

Page 3: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

Caution Do not operate the NI 9202 in a manner notspecified in this document. Product misuse can result ina hazard. You can compromise the safety protectionbuilt into the product if the product is damaged in anyway. If the product is damaged, return it to NI forrepair.

Hazardous Voltage This icon denotes a warningadvising you to take precautions to avoid electricalshock with the NI 9202 with spring terminal.

Safety VoltagesConnect only voltages that are within the following limits:

Maximum voltage1

Channel-to-COM ±30 V DC maximum, up to 6channels at a time

1 The maximum voltage that can be applied or output between AI and COMwithout creating a safety hazard.

NI 9202 Getting Started Guide | © National Instruments | 3

Page 4: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

NI 9202 with Spring Terminal Isolation VoltagesChannel-to-channel NoneChannel-to-earth ground

Continuous 250 V RMS, MeasurementCategory II

Withstandup to 5,000 m 3,000 V RMS, verified by a 5 s

dielectric withstand test

Measurement Category II is for measurements performed oncircuits directly connected to the electrical distribution system.This category refers to local-level electrical distribution, such asthat provided by a standard wall outlet, for example, 115 V forU.S. or 230 V for Europe.

Caution Do not connect the NI 9202 with springterminal to signals or use for measurements withinMeasurement Categories III or IV.

4 | ni.com | NI 9202 Getting Started Guide

Page 5: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

NI 9202 with DSUB Isolation VoltagesChannel-to-channel NoneChannel-to-earth ground

Continuous 60 V DC, MeasurementCategory I

Withstandup to 2,000 m 1,000 V RMS, verified by a 5 s

dielectric withstand testup to 5,000 m 500 V RMS

Measurement Category I is for measurements performed oncircuits not directly connected to the electrical distribution systemreferred to as MAINS voltage. MAINS is a hazardous liveelectrical supply system that powers equipment. This category isfor measurements of voltages from specially protected secondarycircuits. Such voltage measurements include signal levels, specialequipment, limited-energy parts of equipment, circuits poweredby regulated low-voltage sources, and electronics.

NI 9202 Getting Started Guide | © National Instruments | 5

Page 6: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

Caution Do not connect the NI 9202 with DSUB tosignals or use for measurements within MeasurementCategories II, III, or IV.

Note Measurement Categories CAT I and CAT O areequivalent. These test and measurement circuits are forother circuits not intended for direct connection to theMAINS building installations of MeasurementCategories CAT II, CAT III, or CAT IV.

Safety Guidelines for Hazardous VoltagesYou can connect hazardous voltages only to the NI 9202 withspring terminal. Do not connect hazardous voltages to theNI 9202 with DSUB.

If hazardous voltages are connected to the device, take thefollowing precautions. A hazardous voltage is a voltage greaterthan 42.4 Vpk voltage or 60 V DC to earth ground.

Caution Ensure that hazardous voltage wiring isperformed only by qualified personnel adhering to localelectrical standards.

Caution Do not mix hazardous voltage circuits andhuman-accessible circuits on the same module.

6 | ni.com | NI 9202 Getting Started Guide

Page 7: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

Caution Ensure that devices and circuits connected tothe module are properly insulated from human contact.

Note When module terminals are hazardous voltageLIVE (>42.4 Vpk/60 V DC), you must ensure thatdevices and circuits connected to the module areproperly insulated from human contact. You must usethe NI 9940 connector backshell kit with the NI 9202with spring terminal to ensure that the terminals are notaccessible.

Safety Guidelines for Hazardous LocationsThe NI 9202 is suitable for use in Class I, Division 2, Groups A,B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC T4Gc and Ex nA IIC T4 Gc hazardous locations; and nonhazardouslocations only. Follow these guidelines if you are installing theNI 9202 in a potentially explosive environment. Not followingthese guidelines may result in serious injury or death.

Caution Do not disconnect I/O-side wires orconnectors unless power has been switched off or thearea is known to be nonhazardous.

NI 9202 Getting Started Guide | © National Instruments | 7

Page 8: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

Caution Do not remove modules unless power hasbeen switched off or the area is known to benonhazardous.

Caution Substitution of components may impairsuitability for Class I, Division 2, or Zone 2.

Caution The system must be installed in an enclosurecertified for the intended hazardous (classified)location, having a tool secured cover/door, where aminimum protection of at least IP54 is provided.

Electromagnetic Compatibility GuidelinesThis product was tested and complies with the regulatoryrequirements and limits for electromagnetic compatibility (EMC)stated in the product specifications. These requirements andlimits provide reasonable protection against harmful interferencewhen the product is operated in the intended operationalelectromagnetic environment.

This product is intended for use in industrial locations. However,harmful interference may occur in some installations, when theproduct is connected to a peripheral device or test object, or if the

8 | ni.com | NI 9202 Getting Started Guide

Page 9: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

product is used in residential or commercial areas. To minimizeinterference with radio and television reception and preventunacceptable performance degradation, install and use thisproduct in strict accordance with the instructions in the productdocumentation.

Furthermore, any changes or modifications to the product notexpressly approved by National Instruments could void yourauthority to operate it under your local regulatory rules.

Caution To ensure the specified EMC performance ofthe NI 9202 with DSUB, the length of all I/O cablesmust be no longer than 30 m (100 ft).

Caution To ensure the specified EMC performance,operate the NI 9202 with DSUB only with shieldedcables and accessories. Do not use unshielded cables oraccessories unless they are installed in a shieldedenclosure with properly designed and shielded input/output ports and connected to the product using ashielded cable. If unshielded cables or accessories arenot properly installed and shielded, the EMCspecifications for the product are no longer guaranteed.

NI 9202 Getting Started Guide | © National Instruments | 9

Page 10: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

Special Conditions for Marine ApplicationsSome products are Lloyd’s Register (LR) Type Approved formarine (shipboard) applications. To verify Lloyd’s Registercertification for a product, visit ni.com/certification and searchfor the LR certificate, or look for the Lloyd’s Register mark onthe product.

Caution In order to meet the EMC requirements formarine applications, install the product in a shieldedenclosure with shielded and/or filtered power andinput/output ports. In addition, take precautions whendesigning, selecting, and installing measurement probesand cables to ensure that the desired EMC performanceis attained.

10 | ni.com | NI 9202 Getting Started Guide

Page 11: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

EnvironmentalRefer to the manual for the chassis you are using for moreinformation about meeting these specifications.

Operating temperature(IEC 60068-2-1, IEC 60068-2-2)

-40 °C to 70 °C

Storage temperature(IEC 60068-2-1, IEC 60068-2-2)

-40 °C to 85 °C

Ingress protection IP40Operating humidity(IEC 60068-2-78)

10% RH to 90% RH,noncondensing

Storage humidity(IEC 60068-2-78)

5% RH to 95% RH,noncondensing

Pollution Degree 2Maximum altitude 5,000 m

Indoor use only.

NI 9202 Getting Started Guide | © National Instruments | 11

Page 12: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

NI 9202 Pinout

AI1-

AI0-

AI2-

AI4-

AI6-

AI8-

AI10-

AI12-

AI14-

COM

AI3-

AI5-

AI7-

AI9-

AI11-

AI13-

AI15-

NC

192021222324252627282930313233343536

AI0+AI1+

AI3+

AI5+

AI7+

AI9+

AI11+

AI13+

AI15+

NC

AI2+

AI4+

AI6+

AI8+

AI10+

AI12+

AI14+

COM

123456789

101112131415161718

AI0-AI1-AI2-AI3-AI4-AI5-AI6-AI7-

COMCOMAI8-AI9-

AI10-AI11-AI12-AI13-AI14-AI15-

AI0+AI1+AI2+AI3+AI4+AI5+AI6+AI7+COMCOMAI8+AI9+AI10+AI11+AI12+AI13+AI14+AI15+

123456789

10111213141516171819

202122232425262728293031323334353637

NC

12 | ni.com | NI 9202 Getting Started Guide

Page 13: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

Table 1. Signal Descriptions

Signal Description

AI+ Positive analog input signal connection

AI- Negative analog input signal connection

COM Common reference connection to isolated ground

NC No connection

Grounded Differential Connections

VoltageSource

+

AI+

AI–

COM

NI 9202

NI 9202 Getting Started Guide | © National Instruments | 13

Page 14: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

Floating Differential Connections

NI 9202

AI+

AI–

COM

VoltageSource

1 MΩResistor

+

Connect the negative lead to COM through a 1 MΩ resistor tokeep the signal source within the common-mode voltage range.The NI 9202 does not read data accurately if the signal source isoutside of the common-mode voltage range.

14 | ni.com | NI 9202 Getting Started Guide

Page 15: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

Single-Ended Connections

+

AI+

AI–

COM

VoltageSource

NI 9202

Connect the ground signal to COM to keep the signal sourcewithin the common-mode voltage range.

NI 9202 Getting Started Guide | © National Instruments | 15

Page 16: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

Differential Connections with Common ModeVoltage

VoltageSource

+

AI+

AI–

COM

NI 9202

Common Mode Voltage

NI 9202 Connection Guidelines• Make sure that devices you connect to the NI 9202 are

compatible with the module specifications.• You must use 2-wire ferrules to create a secure connection

when connecting more than one wire to a single terminal onthe NI 9202 with spring terminal.

16 | ni.com | NI 9202 Getting Started Guide

Page 17: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

• For the NI 9202 with spring terminal, push the wire into theterminal when using a solid wire or a stranded wire with aferrule.

• For the NI 9202 with spring terminal, open the terminal bypressing the push button when using stranded wire without aferrule.

High-Vibration Application ConnectionsIf your application is subject to high vibration, NI recommendsthat you use the NI 9940 backshell kit to protect connections tothe NI 9202 with spring terminal.

Overvoltage ProtectionThe NI 9202 provides overvoltage protection for each channel.

Note Refer to the device datasheet on ni.com/manualsfor more information about overvoltage protection.

NI 9202 Getting Started Guide | © National Instruments | 17

Page 18: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

Where to Go Next

RELATED INFORMATION

C Series Documentation& Resourcesni.com/info cseriesdoc

Servicesni.com/services

CompactRIO

Located at ni.com/manuals Installs with the software

CompactDAQ

NI 9202 Datasheet

NI-RIO Help

LabVIEW FPGA Help

NI 9202 Datasheet

NI-DAQmx Help

LabVIEW Help

18 | ni.com | NI 9202 Getting Started Guide

Page 19: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

Worldwide Support and ServicesThe NI website is your complete resource for technical support.At ni.com/support, you have access to everything fromtroubleshooting and application development self-help resourcesto email and phone assistance from NI Application Engineers.

Visit ni.com/services for NI Factory Installation Services, repairs,extended warranty, and other services.

Visit ni.com/register to register your NI product. Productregistration facilitates technical support and ensures that youreceive important information updates from NI.

A Declaration of Conformity (DoC) is our claim of compliancewith the Council of the European Communities using themanufacturer’s declaration of conformity. This system affords theuser protection for electromagnetic compatibility (EMC) andproduct safety. You can obtain the DoC for your product byvisiting ni.com/certification. If your product supports calibration,you can obtain the calibration certificate for your product at ni.com/calibration.

NI 9202 Getting Started Guide | © National Instruments | 19

Page 20: NI 9202 Getting Started Guide - National Instruments · 2010. 8. 1. · NI 9202 with Spring Terminal Isolation Voltages Channel-to-channel None Channel-to-earth ground Continuous

NI corporate headquarters is located at11500 North Mopac Expressway, Austin, Texas, 78759-3504. NIalso has offices located around the world. For telephone supportin the United States, create your service request at ni.com/supportor dial 1 866 ASK MYNI (275 6964). For telephone supportoutside the United States, visit the Worldwide Offices section of ni.com/niglobal to access the branch office websites, whichprovide up-to-date contact information, support phone numbers,email addresses, and current events.

Information is subject to change without notice. Refer to the NI Trademarks and Logo Guidelinesat ni.com/trademarks for information on NI trademarks. Other product and company namesmentioned herein are trademarks or trade names of their respective companies. For patentscovering NI products/technology, refer to the appropriate location: Help»Patents in your software,the patents.txt file on your media, or the National Instruments Patent Notice at ni.com/patents. You can find information about end-user license agreements (EULAs) and third-partylegal notices in the readme file for your NI product. Refer to the Export Compliance Information atni.com/legal/export-compliance for the NI global trade compliance policy and how to obtainrelevant HTS codes, ECCNs, and other import/export data. NI MAKES NO EXPRESS ORIMPLIED WARRANTIES AS TO THE ACCURACY OF THE INFORMATION CONTAINEDHEREIN AND SHALL NOT BE LIABLE FOR ANY ERRORS. U.S. Government Customers: Thedata contained in this manual was developed at private expense and is subject to the applicablelimited rights and restricted data rights as set forth in FAR 52.227-14, DFAR 252.227-7014, andDFAR 252.227-7015.