    SITE TEST REPORT

    Replacement of 132/11kV Transformer, TransformerProtection Panels and 110V DC Batteries at W13 Substation

    CONTRACT No. N-6399

    Consultant ENERGOEquipment : 11kV Neutral Grounding Reactor T201

    Main

    Contractor Circuit: 11 KV NGR-1 Page 1 of 3

    Test Report for Neutral Grounding Reactor

    Name Plate Details-:-

    Make Power Economy Rated Voltage 12kV

    Reactor Type NGR Insulation Class 50/125 kV/KVP

    Frequency 50 hz Rated Impedance 0.36 Ohm

    Cooling Natural air cooled Thermal class of Insulation FThermal rating 15kA for 10 Sec Cont Rated Current 450A

    Standard IEC 60289 Year of Manufacturer 2008

    Application Outdoor Serial No 1381/70/08

    No of Phases One Total Weight 375 kG

    Tested by Witnessed by Approved byABB Transmission &

    DistributionENERGO TRANSCO

    Signature

    Name Ganesan K Mohammad Rasheed

    Date 18.02.2013 18.02.2013

  • 7/30/2019 NGR Winding Res. Inductance

    2/3

    SITE TEST REPORT

    Replacement of 132/11kV Transformer, TransformerProtection Panels and 110V DC Batteries at W13 Substation

    CONTRACT No. N-6399

    Consultant ENERGOEquipment : 11kV Neutral Grounding Reactor T201

    Main

    Contractor Circuit: 11 KV NGR-1 Page 2 of 3

    1. INSULATION RESISTANCE TESTS (M):

    DescriptionMeasured Insulation Resistance in M @ 60Sec Applied Voltage

    Coil Earth 420 5000 V

    2. MEASUREMENT OF DC WINDING RESISTANCE

    Coil SerialNo.

    Measured DCResistance@ 28.0 C

    Calculated DCResistance@75 C ()

    REMARKS

    1381-70-08

    29.597 m 34.886 m (Omicron Test sheetattached)

    R = Ramb *(225+75) / (225+Tamb)

    3. MEASUREMENT OF WINDING IMPEDANCE

    COIL

    SIERIALNO.

    Measured DCImpedance

    Given atName

    plate

    REMARKS

    1381-70-08 363.44 m 0.36 (Omicron Test sheet attached)

    4. INSULATION AND POWER FREQUENCY WITHSTAND TESTVoltage applied for 60 secbet terminal and earth

    WITHSTANDSTATUS

    INSULATION ESISTANCE (G)

    AC 30kV 14mABefore Test After Test

    420 M 500 M

    Note: Insulation resistance measured by 5kV DC insulation tester.

    Tested by Witnessed by Approved byABB Transmission &

    DistributionENERGO TRANSCO

    Signature

    Name Ganesan K Mohammad Rasheed

    Date 18.02.2013 18.02.2013

    1. Testing instrument details

    Particulars Make Type Sr. No. Cal. due date

    InsulationResistance meter

    Megger BM11D AETAD/ST/00203 27.11.2013

    CPC100 Omicron CPC100 AETAD/ST/13002 13.05.2013

    HV Test Phenix BK130 AETAD/ST/00103 16.01.2014

  • 7/30/2019 NGR Winding Res. Inductance

    3/3

    SITE TEST REPORT

    Replacement of 132/11kV Transformer, TransformerProtection Panels and 110V DC Batteries at W13 Substation

    CONTRACT No. N-6399

    Consultant ENERGOEquipment : 11kV Neutral Grounding Reactor T201

    Main

    Contractor Circuit: 11 KV NGR-1 Page 3 of 3

    Remarks:- OK

    Tested by Witnessed by Approved byABB Transmission &

    DistributionENERGO TRANSCO

    Signature

    Name Ganesan K Mohammad Rasheed

    Date 18.02.2013 18.02.2013