SITE TEST REPORT
Replacement of 132/11kV Transformer, TransformerProtection Panels and 110V DC Batteries at W13 Substation
CONTRACT No. N-6399
Consultant ENERGOEquipment : 11kV Neutral Grounding Reactor T201
Main
Contractor Circuit: 11 KV NGR-1 Page 1 of 3
Test Report for Neutral Grounding Reactor
Name Plate Details-:-
Make Power Economy Rated Voltage 12kV
Reactor Type NGR Insulation Class 50/125 kV/KVP
Frequency 50 hz Rated Impedance 0.36 Ohm
Cooling Natural air cooled Thermal class of Insulation FThermal rating 15kA for 10 Sec Cont Rated Current 450A
Standard IEC 60289 Year of Manufacturer 2008
Application Outdoor Serial No 1381/70/08
No of Phases One Total Weight 375 kG
Tested by Witnessed by Approved byABB Transmission &
DistributionENERGO TRANSCO
Signature
Name Ganesan K Mohammad Rasheed
Date 18.02.2013 18.02.2013
-
7/30/2019 NGR Winding Res. Inductance
2/3
SITE TEST REPORT
Replacement of 132/11kV Transformer, TransformerProtection Panels and 110V DC Batteries at W13 Substation
CONTRACT No. N-6399
Consultant ENERGOEquipment : 11kV Neutral Grounding Reactor T201
Main
Contractor Circuit: 11 KV NGR-1 Page 2 of 3
1. INSULATION RESISTANCE TESTS (M):
DescriptionMeasured Insulation Resistance in M @ 60Sec Applied Voltage
Coil Earth 420 5000 V
2. MEASUREMENT OF DC WINDING RESISTANCE
Coil SerialNo.
Measured DCResistance@ 28.0 C
Calculated DCResistance@75 C ()
REMARKS
1381-70-08
29.597 m 34.886 m (Omicron Test sheetattached)
R = Ramb *(225+75) / (225+Tamb)
3. MEASUREMENT OF WINDING IMPEDANCE
COIL
SIERIALNO.
Measured DCImpedance
Given atName
plate
REMARKS
1381-70-08 363.44 m 0.36 (Omicron Test sheet attached)
4. INSULATION AND POWER FREQUENCY WITHSTAND TESTVoltage applied for 60 secbet terminal and earth
WITHSTANDSTATUS
INSULATION ESISTANCE (G)
AC 30kV 14mABefore Test After Test
420 M 500 M
Note: Insulation resistance measured by 5kV DC insulation tester.
Tested by Witnessed by Approved byABB Transmission &
DistributionENERGO TRANSCO
Signature
Name Ganesan K Mohammad Rasheed
Date 18.02.2013 18.02.2013
1. Testing instrument details
Particulars Make Type Sr. No. Cal. due date
InsulationResistance meter
Megger BM11D AETAD/ST/00203 27.11.2013
CPC100 Omicron CPC100 AETAD/ST/13002 13.05.2013
HV Test Phenix BK130 AETAD/ST/00103 16.01.2014
-
7/30/2019 NGR Winding Res. Inductance
3/3
SITE TEST REPORT
Replacement of 132/11kV Transformer, TransformerProtection Panels and 110V DC Batteries at W13 Substation
CONTRACT No. N-6399
Consultant ENERGOEquipment : 11kV Neutral Grounding Reactor T201
Main
Contractor Circuit: 11 KV NGR-1 Page 3 of 3
Remarks:- OK
Tested by Witnessed by Approved byABB Transmission &
DistributionENERGO TRANSCO
Signature
Name Ganesan K Mohammad Rasheed
Date 18.02.2013 18.02.2013