NG40 120 Vac 60 Hz · NG40 120 Vac 60 Hz Blower for gas-premix heating systems SIT S.p.A. Viale...
Transcript of NG40 120 Vac 60 Hz · NG40 120 Vac 60 Hz Blower for gas-premix heating systems SIT S.p.A. Viale...
NG40 120 Vac 60 HzBlower for gas-premix heating systems
SIT S.p.A. Viale dell’Industria, 31-33 35129 PADOVA - ITALYTel. +39/049/829.31.11, Fax +39/049/807.00.93 - www.sitgroup.it - e-mail: [email protected]
gas-premix heating systemOutput Curve
Airflow/Pressure
0
600
1200
1800
2400
3000
3600
4200
4800
0 20 40 60 80 100 120 140 160 180 200 220
[Nm3/h]
[Pa]
This new electronically commutated centrifugal brushless fan has been developed for premix condensing gas boilers and other gas appliances in the range up to 150 kBTU/h. Advanced design and engineering tools such as FEM, CFD, DOE testing routines, and Design for Assembly principles were used in developing this product.NG40 is CSA approved and its main features are:
• High “pressure vs. airflow” characteristics with overall blower efficiency maintained above average industry levels
• Wide modulation ratio up to 10:1• Flexibility for various applications - The blower electronics are equipped with a programmable
microcontroller managing several functional curves allowing the NG40 to easily be applied to a wide range of applications
Weight
Wire insulation
Housing
Impellermaterial
4.89 lbs
Class F
Die-cast aluminium
Plastic antistatic
1-4 kHz
Power supply voltage
Frequency
Max. nominalpower consumption
Max.Air flow
Max. pressure
Max. fan speed
PWM voltage
PWM frequency
120 Vac
60 Hz
90 W
64.7 CFM
12.4 inch WC
9,600 rpm
18-30 Vdc
Technical dataPower supply voltage
Frequency
Max. nominalpower consumption
Max.Air flow
Max. pressure
Max. fan speed
Mass
Wire insulation
Housing
Impellermaterial
230V
50Hz
200W
210m3/h
4500 Pa
8000 rpm
1990g
Class F (EN 60730-1)
Die-cast aluminium
Plastic antistatic
Technical data
PRODUCT TECHNICAL DATA
MOD. REV.: 2 DATE: 20/05/2015 CUSTOMER: Project N°
FAN TYPE: PREMIX FAN – NG40 CODE: W940111230
2
Performances At constant voltage
At constant rpm
Curves are indicative
0
2
4
6
8
10
12
0 10 20 30 40 50 60 70
[in.WC]
[CFM]
AIR FLOW / PRESSURE
120V
0
0,5
1
1,5
2
2,5
3
3,5
4
4,5
5
0 10 20 30 40 50 60
[in.WC]
[CFM]
AIR FLOW / PRESSURE
7000rpm
5000rpm
3000rpm
All dimensions are indicative.
NG
40N
G40
Reference standards:- C22.2 NO. 113-UL 507
C US
SIT S.p.a.EVDC NG40 XXXCode W940xxxxxxAC 120V 60Hz 90W 1.3A CL.Fn XXXXXXXX dd/mm/yy
Made in EU
Dimensions are in millimeters. Dimensions between [...] are in inches.
C US
SIT S.p.a.EVDC NG40 XXXCode W940xxxxxxAC 120V 60Hz 90W 1.3A CL.Fn XXXXXXXX dd/mm/yy
Made in EU
Blower for gas-premix heating systems
Power supply voltage 230V
Frequency 50Hz
Max. nominalpower consumption 200W
Max.Air flow 210m3/h
Max. pressure 4500 Pa
Max. fan speed 8000 rpm
Mass 1990g
Wire insulationclass F ( EN 60730-1 )
Housing Die-cast aluminium
Impellermaterial Plastic antistatic
NG
150
NG
150
Reference standards :- EN60335-1- LVD 2006/95EC (ex 73/23/EC) - EMC 2004/108/EC (ex 89/336/EC)- ATEX (94/9/CE)
Technical data
- ErP lot11 (327/2011)
Use only 3 screws for mounting
C US
SIT S.p.a.EVDC NG40 XXXCode W940xxxxxxAC 120V 60Hz 90W 1.3A CL.Fn XXXXXXXX dd/mm/yy
Made in EU