This product should be installed only by competent personnel trained in good safety practices involving high voltageelectrical equipment. These instructions are not intended as a substitute for adequate training or experience in such safety practices. These instructions do not attempt to provide for every possible contingency.Failure to follow these instructions could result in damage to the product and serious or fatal injury.IMPORTANT : Cable and associated apparatus must be de-energised, locked out, and tagged prior to product installation.
a Nexans company
Optionally supplied :
CAUTION: Read instructions thoroughly and completely prior to beginning installation.
Installation instructions for slip-on indoor termination
AIN 30U max. 36 kV
Contents :
Installation instructions
3 x Stress control mastic strips, type
MFC (Hi-K)
Glove
Roll adhesive tape Emery cloth
WiperSilicone grease3 x Tinned copper wire
3 x Earth braid
3 x Semi-conductive tape
3 x Conductorcable lug
or
3 x Termination housing
Table 1
Terminationsize
1 50 - 70
95 - 240
240 - 400
23,5
27,0
32,0
29,0
38,0
43,0
2
3
Conductorcross section
(mm²)[for information only]
Cable coreinsulationdiameter
(mm)
min. max.
For copper tape screened cable with:- extruded easy strip semi-conductive screen- bonded extruded semi-conductive screen
Page 1 of 6IS94018-ENG - AIN 30-2618 September 2013 - Revision 5 - Supersedes edition of 18 March 2013
IS94
018-
ENG
- AI
N 3
0-26
- Re
visio
n 5
B
A
1 Temporarily install the cable lug on to the equipment and hold the cable next to it.
2 Mark the bottom of the cable lug on the cable (reference point A).
3 Measure the depth of the cable lug bore (length L) and mark this distance above the reference point A on the cable (reference point B).
4 Cut the cable at the reference point B.
EQUIPMENT
L
cable
temporarilyfixed cable lug
IS94
018-
ENG
- AI
N 3
0-26
- Re
visio
n 5
Page 2 of 6
extruded semi- conductivescreen
outersheath
coreinsulation
20
CABLE PREPARATION
1 Remove the outer cable sheath for a distance X + L + 30 mm. L = depth of the cable lug bore X = see table 22 Remove the copper tape screen to a point 20 mm above the cut edge of the outer sheath.3 Remove the semi-conductive screen up to 45 - 50 mm above the cut edge of the outer sheath. Check if the cable insulation diameter is in accordance with the termination range. See table 2. 4 Bare the conductor for a distance L + 30 mm. IMPORTANT : To ensure the termination slips on easily, the edge of the core insulation should be rounded and slightly roughened using the supplied emery cloth.
L
!
!
Table 2
L + 30
X +
L +
30
copper tapescreen
45 - 50
conductor
bevelledandrounded
!
removeall sharpedges
123,5 - 26
26 - 29
27 - 30,6
30,6 - 34,1
34,1 - 38
32 - 38
38 - 43
255
250
250
245
240
255
245
2
3
Terminationsize
Cable coreinsulationdiameter
(mm)
X(mm)
Page 3 of 6IS
9401
8-EN
G -
AIN
30-
26 -
Revis
ion
5
5 Using a tinned copper wire, cleat the earth braid onto the copper tape screen.
6 Using adhesive tape, secure the earth braid approx. 60 mm below the edge of the outer sheath.
7 Completely overtape the cleating with semi-conductive tape. All sharp edges must be covered. Make a step at 20 mm from the edge of the outer sheath.
8 For cables with extruded easy strip semi-conductive screen (see detail) - Apply one layer of field control mastic, type MFC (Hi-K) on the core insulation, flush with the extruded semi- conductive screen. - Squeeze it tightly in place using the coated side of the paper.
!
extruded semi-conductive screen
extruded semi-conductive screen
cleating
adhesive tape
!
60
semi-conductivetape
cleating
!
20
20
field control mastic,type MFC (Hi-K)
semi-conductivetape
DETAIL
For cables with extruded easy strip semi-conductive screen
earth braidearth braid
earth braid
IS94
018-
ENG
- AI
N 3
0-26
- Re
visio
n 5
Page 4 of 6
!
1 Remove burrs from the conductor and as a protection, wrap a few turns of adhesive tape around the conductor end.
2 Remove any traces of conductive residue from the core insulation.
3 Lubricate core insulation and the inner surface of the termination (use only the silicone lubricant supplied).
4 Push the termination on the cable, until the internal step in the bottom part of the termination butts against the step made by the cleating and taping. Remove protective tape from the conductor.
5 - Crimp contacts : crimp according specification. - Bolted contacts : tighten the screws, refer to the installation instruction included with the contact.
6 Remove any burrs after crimping/tightening and wipe off excess inhibitor.
!
!
INSTALLATION OF THE TERMINATION HOUSING AND CABLE LUG
Hexagonalcable lug
deep indentcable lug
boltedcable lug
protectiveadhesivetape
terminationhousing
internal step
Page 5 of 6IS
9401
8-EN
G -
AIN
30-
26 -
Revis
ion
5
a Nexans company
Nexans Network Solutions NV - div. EUROMOLDZuid III - Industrielaan 12
B-9320 EREMBODEGEM-AALST – BELGIUMTel: +32 (0)53/85 02 11 – Telefax: +32 (0)53/83 10 13
1 Connect earth braid to the system earth.
2 Clamp the cable as close as possible to the termination.
CABLE SCREEN EARTHING
to thesystemearth
cable lug
cableclamp
IS94
018-
ENG
- AI
N 3
0-26
- Re
visio
n 5
Page 6 of 6