New transformer-rated meter socket accepted by Hydro-Québec

2
www.tnb.ca Another innovative solution for Wire and Cable Management New transformer-rated meter socket accepted by Hydro-Québec Microlectric ® CT104-5SWLHQ meter socket replaces AB100 Series for 120/240 V services, above 200 A, that require current transformers. As of July 1, 2014, the new Microlectric ® CT104-5SWLHQ meter socket will replace the AB100 Series for all installations in Quebec exceeding 200 A that require instrument transformer metering. • Compact unit – smaller footprint than standard CT104 Series • Conductor range: 14-10 AWG • Transformer-rated – 20 A, 600 V maximum • Suitable for 120/240 V single-phase service entrance • Hydro-Québec-approved test switch included • Units are pre-wired from base to test switch • Lower test switch compartment cover securely held by upper cover and a catch at bottom • Weatherproof Type 3R enclosure • Designed and manufactured to Hydro-Québec specifications in Saint-Jean-sur-Richelieu, Quebec • CSA Certified Manufactured in Quebec to Hydro-Québec specifications Includes Hydro-Québec-approved test switch Pre-wired as per Hydro-Québec’s specifications Thomas & Betts. Your best connection for innovative solutions.

Transcript of New transformer-rated meter socket accepted by Hydro-Québec

Page 1: New transformer-rated meter socket accepted by Hydro-Québec

w w w . t n b . c a

Another innovat ive solut ion for Wire and Cable Management

New transformer-rated meter socket accepted by Hydro-Québec

Microlectric® CT104-5SWLHQ

meter socket replaces AB100 Series

for 120/240 V services, above 200 A,

that require current transformers.

As of July 1, 2014, the new Microlectric®

CT104-5SWLHQ meter socket will replace the

AB100 Series for all installations in Quebec

exceeding 200 A that require instrument

transformer metering.

• Compact unit – smaller footprint than standard CT104 Series

• Conductor range: 14-10 AWG

• Transformer-rated – 20 A, 600 V maximum

• Suitable for 120/240 V single-phase service entrance

• Hydro-Québec-approved test switch included

• Units are pre-wired from base to test switch

• Lower test switch compartment cover securely held by upper cover and a catch at bottom

• Weatherproof Type 3R enclosure

• Designed and manufactured to Hydro-Québec specifications in Saint-Jean-sur-Richelieu, Quebec

• CSA Certified

Manufactured in Quebec to Hydro-Québec specifications

Includes Hydro-Québec-approved test switch

Pre-wired as per Hydro-Québec’s specifications

Thomas & Betts. Your best connection for innovative solutions.

Page 2: New transformer-rated meter socket accepted by Hydro-Québec

w w w . t n b . c a

Microlectric® CT104-5SWLHQ meter socket – a utility-driven solution

Atlantic Provinces Quebec Ontario Manitoba/Saskatchewan Alberta British ColumbiaThomas & Betts Limited Tel.: (902) 450-1307 Toll Free: 1-877-862-4357 Fax: (902) 450-1309

Thomas & Betts Limited Tel.: (450) 466-1102 Toll Free: 1-800-465-1399 Fax: (450) 466-1163

Thomas & Betts Limited Tel.: (905) 858-1010 Toll Free: 1-877-291-7771 Fax: (905) 858-1080

Thomas & Betts Limited Tel.: (604) 598-9811 Toll Free: 1-866-540-8220 Fax: (604) 598-9840

Thomas & Betts Limited Tel.: (780) 424-7092 Toll Free: 1-888-664-5666 Fax: (780) 424-7093Toll Free: 1-866-424-4082

Thomas & Betts Limited Tel.: (604) 598-9811 Toll Free: 1-866-540-8220 Fax: (604) 598-9840

Microlectric® CT104-5SWLHQ – Hydro-Québec

CAT. NO. DESCRIPTIONDIMENSIONS (in.) WEIGHT PER EACH

H W D lb. kg

CT104-5SWLHQ Hydro-Québec-approved 20 A current transformer meter socket 18 8-1/4 4-1/2 11 lb. 5.4 kg

© 2014. Thomas & Betts Limited. All rights reserved. Printed in Canada. 05/15/250. Order No. MICROHQCT104-E

4-5/8 in.

6.625 in.

3.574 in.

18 in.

Ø 3/4, 1, 1-1/4 in. KO5 Sets

New Hydro-Québec requirementAs of July 1, 2014, the new CT104-5SWLHQ meter socket replaces the AB100 Series for all installations in Quebec above 200 A.

8-1/4 in.

TRANSFORMER-RATED METER SOCKET

A Service boxB Transformer cabinetC Distribution panelD Meter socket

Diameter*:≤ 15 meter = 27 mm> 15 meter = 35 mm

*Maximum conduit length is 30 m.

1200 mm min.1600 mm max.

300 mm min.

Finished floor

Reprinted with permission from Hydro-Québec. Reference: Hydro-Québec Blue Book, Articles 0.3, 7.3, 7.5.1 and 7.5.1.1. For installation instructions, refer to the July 1, 2014 edition of the Hydro-Québec Blue Book, Standard E.21-10, 10th edition, Chapter 7.

4-1/2 in.