New Tower Start-Up
-
Upload
sreedhar-patnaikm -
Category
Documents
-
view
213 -
download
0
Transcript of New Tower Start-Up
-
7/31/2019 New Tower Start-Up
1/2
Chemical Solution, Inc. Technical Data Sheet
CLEANING, PASSIVATION and STARTUP of NEW COOLING SYSTEMS
Prior to hydraulic testing or putting a new system into service, it must
be cleaned to remove oil, grease, new pipe mill scale, silts and organicdebris, and general rust accumulations. It is then chemically
passivated to inhibit corrosion of the various metallurgies involved.
Since the system may also contain microbiological contamination,
disinfection should be provided prior to allowing any aerosol
emissions from any wet-type heat rejection device (WTHRD), e.g.,
cooling towers, and evaporative condensers. Accordingly, the
cleaning and disinfection procedures presented herein also incorporate
the procedural concepts and disinfection guidelines for system start-up
as endorsed by The Centers for Disease Control and Prevention
(CDC) and as published in the "1987 Wisconsin Guidelines" entitled,
Control of Legionella in Cooling Towers, Summary Guidelines.
NACE publication item number 21027 may serve as an additional
reference for the initial conditioning of cooling water equipment.
NOTES: This procedure cannot nor can any of the CDC/Wisconsin
cleaning/disinfection procedures guarantee elimination of Legionella
bacteria or any other pathogen from cooling systems. Workers should
be instructed and trained in protective procedures to minimize
exposure to biological and chemical agents which may occur during
system cleaning.
Contaminants referenced above and a poor passivation program can
cause a wide variety of operating problems. Oil can aggravate
corrosion by hindering the ability of chemical corrosion inhibitors to
function and by contributing to the formation of corrosion cells. Siltdeposits and organic debris can retard heat transfer, restrict water
flow, initiate formation of corrosion cells, and enhance the corrosive
actions at existing corrosion cells. This leads to additional localized
corrosion and subsequent leaks. These deposits also hinder the
protective action of corrosion inhibitors, and can provide a "protective
home" for many types of micro-organisms including corrosive ones
such as the acid producing, sulfate reducing bacteria.
Open recirculating water systems are typically constructed of mild
steel, zinc-galvanized steel, copper, and brass metallurgies. Some may
contain stainless steel, admiralty, and/or aluminum metallurgies.
Thus, highly alkaline "boil out" procedures typically prescribed by
boiler manufacturer's operating manuals for "all steel" boilers areNOT acceptable.
Cleaning procedures based on strong, inhibited mineral acids can be
risky for some metallurgies, are hazardous to handle, and are much
more difficult to dispose of. The cleaning and passivation procedures
employed in systems containing a zinc-galvanized WTHRD is most
important to aid initial formation of a proper zinc oxide barrier. After
start-up and concentration of
makeup water impurities, system operation at moderately alkaline
conditions (pH 8 - 9) and with water containing highconcentrations of carbonate alkalinity could lead to formation of
zinc carbonate (i.e. "White Rust") if the zinc galvanize is not
initially passivated. The combination of cleaning and passivation
chemical formulations and procedures described below function
at pH neutral to very mildly alkaline conditions, contain
phosphates to aid initial passivation of the zinc, and have been
proven quite successful.
Initial Flushing of Newly Constructed Systems
New systems must be first filled with water to check for leaks and
flushed to remove construction debris and loose deposits. Dead
ends and low velocity areas should be flushed/drained until allsediment has been removed. The system volume (water holding
capacity) should be established to effectively estimate cleaning
chemical and treatment requirements. An alternate to any initial
calculation/estimation of system capacity from design data is to
perform a traced ion study during the initial system filling and
circulation just prior to flushing. Once flushed, the system should
not be allowed to sit idle for more than a day or two before all
observed leaks are repaired and the chemical cleaning,
passivation, and disinfection program is performed.
Additional tasks prior to circulating any water over the cooling
tower or other WTHRD should include:
Turn off (lock out) the tower fans to avoid formation and
emission of any contaminated aerosols; i.e. water mist. Close
nearby building air intakes; say intakes within 30 meters
(100 feet) of the cooling tower. This step is also very
important prior to conducting any high dosage chemical
cleaning, passivation, and disinfection in order to protect
building occupants from high levels of chlorine or bromine
gas and other biologic agents that would otherwise be
aerosolized during this process.
Remove all loose construction materials. Inspect the tower
fill, drift eliminators, and fan belts. Repair or properly install
as deemed necessary.
Ascertain that the makeup water fill line is positioned so that
the chemically treated circulating water cannot "backup" or
siphon into the water supply lines. Make sure there are no
system cross connections with the potable water supply.
(continued on other side)
Cleaning of Newly Constructed Systems
ALL RIGHTS RESERVED. Do not duplicate this document by any method without prior
written permission from Chemical Solution, Inc.
-
7/31/2019 New Tower Start-Up
2/2
CLEANING, PASSIVATION and STARTUP of NEW COOLING SYSTEMS (continued)
Additional preparations after system flushing, repair of any leaks
encountered, and estimation of system holding capacity include:
Shut down the system's bleedoff conductivity controller and close
bleedoff valve.
Verify that the chemically treated system bleedoff water will
comply with proper regulatory agency discharge requirements;
i.e. an EPA/State NPDES permit for discharges to a surfacestream or, if required, a local POTW permit regulating discharges
into a public sanitary sewer system.
Add the cleaning, passivation, and disinfection chemical formulations
in accordance with the specific product selections and dosage
instructions provided by the water treatment specialist serving the
facility. A two step process is outlined in the following paragraphs.
Circulate this initial cleaning-passivation solution for 24 to 48 hours at
a cleaning temperature of 50oF to 100
oF. The warmer temperatures
will be more effective and permit more rapid cleaning. After the
initial cleaning solutions are flushed from the system, the subsequent
passivation chemical program should ideally be circulated for an
additional one to two weeks to optimize the passivation process.During this period of time the system may be operated at low heat
load and low cycles. Microbiocides should be added in accordance
with the program selected for the on-going treatment program. The
chemical formulations required for this two step process are generally
described in the following paragraphs.
Initial Cleaning and Passivation
SERIES 1960 Formulations are concentrated mixtures of
chelating agents, sequestrants, and metal passivators with
polymeric dispersants, an azole yellow metal inhibitor, and
surfactants. These products are mildly alkaline as necessary to
maintain product stability. If the system being cleaned containszinc galvanize, the pH of the circulating water needs to be
adjusted downward to pH neutral or very slightly alkaline; pH of
7.0 to 7.5. This can be best accomplished by using an organic
acid-based formulation. This mild organic acid serves to lower
the pH to the desired range and has mild cleaning properties to
aid removal of metal oxides such as mill scale and rust.
NOTE: The cleaners and surfactant contained in the SERIES 1960
Formulations are NOT designed for systems heavily fouled with oil.
An alternate cleaner or supplemental addition of a SERIES 1335 or
1340 Formulation may be required. The water treatment specialist
serving the facility should be consulted.
FORMULA 3218 and FORMULA 3214 are two different
organic acid-based formulations available to accomplish the
above mentioned objectives. FORMULA 3218 is a concentrated
liquid also containing a phosphonate sequestrant. FORMULA
3214 is a powdered formulation that would be most cost-effective
for large systems.
ALL RIGHTS RESERVED. Do not duplicate this document by any method without prior written
FORMULAs DL-1542 through DL-1547 are glutaraldehyde
based microbiocides. These non-oxidizing-type biocides are
preferred for disinfection of new systems as they would not
adversely effect the new, un-passivated metallurgies as would
high dosages of chlorine. Once diluted in the system's waters,
they are compatible with the above referenced
cleaning/passivation formulations.
Oxidizing chlorine based disinfectants such as sodium
hypochlorite liquid (FORMULA 1582) or chlorinated
isocyanurate powder (FORMULA 1588-G) are both good
sources of chlorine that can be used prudently with the above
referenced products. Maintenance of chlorine residuals at 1-
2 ppm free chlorine should be quite sufficient to compliment
the above cleaning-passivation program without necessarily
hindering initial system passivation.
NOTE: The CDC/Wisconsin guidelines for start-up of existing
systems and emergency disinfection of systems containing
objectionable concentrations of Legionella specify chlorine
dosages of 25 and 50 ppm and maintenance of 10 ppm for 24
hours.
After circulating the above solution for 24 to 48 hours, drain and
flush the system by procedures described above and in
accordance with specific system characteristics learned during
initial system flushing. IMMEDIATELY refill the system with
clean water and add the final passivation and disinfection
formulations specified by the water treatment specialist and as
generally described below.
Final Passivation and Disinfection
SERIES 1930 Formulations are concentrated mixtures of
molybdate, complex polyphosphates, orthophosphate, and azole
yellow metal-based corrosion inhibitors ideal for passivation of
cooling systems. The formulations also contain phosphonates and
multi-functional polymer dispersants to aid product performance
during initial one to two weeks of system operation provided the
system only experiences moderate heat loads and is operated atlow cycles to aid in maintaining operation at pH 7.0 to 7.5.
Feed microbiocides as deemed necessary and specified by the
water treatment specialist serving the facility. This program
could utilize the same products referenced above and selected for
the initial cleaning process.
The SERIES 1930 passivation program may not require system
flushing. At start-up, simply initiate the automated bleedoff valve
to regulate desired cycles of concentration. The SERIES 1930
passivation formulation will be removed by normal system
bleedoff and replaced by the specific corrosion/scale inhibitor and
dispersant formulation specified by the facility's water treatmentspecialist for use during the on-going treatment program
permission from Chemical Solution, Inc.