New Tower Start-Up

download New Tower Start-Up

of 2

Transcript of New Tower Start-Up

  • 7/31/2019 New Tower Start-Up

    1/2

    Chemical Solution, Inc. Technical Data Sheet

    CLEANING, PASSIVATION and STARTUP of NEW COOLING SYSTEMS

    Prior to hydraulic testing or putting a new system into service, it must

    be cleaned to remove oil, grease, new pipe mill scale, silts and organicdebris, and general rust accumulations. It is then chemically

    passivated to inhibit corrosion of the various metallurgies involved.

    Since the system may also contain microbiological contamination,

    disinfection should be provided prior to allowing any aerosol

    emissions from any wet-type heat rejection device (WTHRD), e.g.,

    cooling towers, and evaporative condensers. Accordingly, the

    cleaning and disinfection procedures presented herein also incorporate

    the procedural concepts and disinfection guidelines for system start-up

    as endorsed by The Centers for Disease Control and Prevention

    (CDC) and as published in the "1987 Wisconsin Guidelines" entitled,

    Control of Legionella in Cooling Towers, Summary Guidelines.

    NACE publication item number 21027 may serve as an additional

    reference for the initial conditioning of cooling water equipment.

    NOTES: This procedure cannot nor can any of the CDC/Wisconsin

    cleaning/disinfection procedures guarantee elimination of Legionella

    bacteria or any other pathogen from cooling systems. Workers should

    be instructed and trained in protective procedures to minimize

    exposure to biological and chemical agents which may occur during

    system cleaning.

    Contaminants referenced above and a poor passivation program can

    cause a wide variety of operating problems. Oil can aggravate

    corrosion by hindering the ability of chemical corrosion inhibitors to

    function and by contributing to the formation of corrosion cells. Siltdeposits and organic debris can retard heat transfer, restrict water

    flow, initiate formation of corrosion cells, and enhance the corrosive

    actions at existing corrosion cells. This leads to additional localized

    corrosion and subsequent leaks. These deposits also hinder the

    protective action of corrosion inhibitors, and can provide a "protective

    home" for many types of micro-organisms including corrosive ones

    such as the acid producing, sulfate reducing bacteria.

    Open recirculating water systems are typically constructed of mild

    steel, zinc-galvanized steel, copper, and brass metallurgies. Some may

    contain stainless steel, admiralty, and/or aluminum metallurgies.

    Thus, highly alkaline "boil out" procedures typically prescribed by

    boiler manufacturer's operating manuals for "all steel" boilers areNOT acceptable.

    Cleaning procedures based on strong, inhibited mineral acids can be

    risky for some metallurgies, are hazardous to handle, and are much

    more difficult to dispose of. The cleaning and passivation procedures

    employed in systems containing a zinc-galvanized WTHRD is most

    important to aid initial formation of a proper zinc oxide barrier. After

    start-up and concentration of

    makeup water impurities, system operation at moderately alkaline

    conditions (pH 8 - 9) and with water containing highconcentrations of carbonate alkalinity could lead to formation of

    zinc carbonate (i.e. "White Rust") if the zinc galvanize is not

    initially passivated. The combination of cleaning and passivation

    chemical formulations and procedures described below function

    at pH neutral to very mildly alkaline conditions, contain

    phosphates to aid initial passivation of the zinc, and have been

    proven quite successful.

    Initial Flushing of Newly Constructed Systems

    New systems must be first filled with water to check for leaks and

    flushed to remove construction debris and loose deposits. Dead

    ends and low velocity areas should be flushed/drained until allsediment has been removed. The system volume (water holding

    capacity) should be established to effectively estimate cleaning

    chemical and treatment requirements. An alternate to any initial

    calculation/estimation of system capacity from design data is to

    perform a traced ion study during the initial system filling and

    circulation just prior to flushing. Once flushed, the system should

    not be allowed to sit idle for more than a day or two before all

    observed leaks are repaired and the chemical cleaning,

    passivation, and disinfection program is performed.

    Additional tasks prior to circulating any water over the cooling

    tower or other WTHRD should include:

    Turn off (lock out) the tower fans to avoid formation and

    emission of any contaminated aerosols; i.e. water mist. Close

    nearby building air intakes; say intakes within 30 meters

    (100 feet) of the cooling tower. This step is also very

    important prior to conducting any high dosage chemical

    cleaning, passivation, and disinfection in order to protect

    building occupants from high levels of chlorine or bromine

    gas and other biologic agents that would otherwise be

    aerosolized during this process.

    Remove all loose construction materials. Inspect the tower

    fill, drift eliminators, and fan belts. Repair or properly install

    as deemed necessary.

    Ascertain that the makeup water fill line is positioned so that

    the chemically treated circulating water cannot "backup" or

    siphon into the water supply lines. Make sure there are no

    system cross connections with the potable water supply.

    (continued on other side)

    Cleaning of Newly Constructed Systems

    ALL RIGHTS RESERVED. Do not duplicate this document by any method without prior

    written permission from Chemical Solution, Inc.

  • 7/31/2019 New Tower Start-Up

    2/2

    CLEANING, PASSIVATION and STARTUP of NEW COOLING SYSTEMS (continued)

    Additional preparations after system flushing, repair of any leaks

    encountered, and estimation of system holding capacity include:

    Shut down the system's bleedoff conductivity controller and close

    bleedoff valve.

    Verify that the chemically treated system bleedoff water will

    comply with proper regulatory agency discharge requirements;

    i.e. an EPA/State NPDES permit for discharges to a surfacestream or, if required, a local POTW permit regulating discharges

    into a public sanitary sewer system.

    Add the cleaning, passivation, and disinfection chemical formulations

    in accordance with the specific product selections and dosage

    instructions provided by the water treatment specialist serving the

    facility. A two step process is outlined in the following paragraphs.

    Circulate this initial cleaning-passivation solution for 24 to 48 hours at

    a cleaning temperature of 50oF to 100

    oF. The warmer temperatures

    will be more effective and permit more rapid cleaning. After the

    initial cleaning solutions are flushed from the system, the subsequent

    passivation chemical program should ideally be circulated for an

    additional one to two weeks to optimize the passivation process.During this period of time the system may be operated at low heat

    load and low cycles. Microbiocides should be added in accordance

    with the program selected for the on-going treatment program. The

    chemical formulations required for this two step process are generally

    described in the following paragraphs.

    Initial Cleaning and Passivation

    SERIES 1960 Formulations are concentrated mixtures of

    chelating agents, sequestrants, and metal passivators with

    polymeric dispersants, an azole yellow metal inhibitor, and

    surfactants. These products are mildly alkaline as necessary to

    maintain product stability. If the system being cleaned containszinc galvanize, the pH of the circulating water needs to be

    adjusted downward to pH neutral or very slightly alkaline; pH of

    7.0 to 7.5. This can be best accomplished by using an organic

    acid-based formulation. This mild organic acid serves to lower

    the pH to the desired range and has mild cleaning properties to

    aid removal of metal oxides such as mill scale and rust.

    NOTE: The cleaners and surfactant contained in the SERIES 1960

    Formulations are NOT designed for systems heavily fouled with oil.

    An alternate cleaner or supplemental addition of a SERIES 1335 or

    1340 Formulation may be required. The water treatment specialist

    serving the facility should be consulted.

    FORMULA 3218 and FORMULA 3214 are two different

    organic acid-based formulations available to accomplish the

    above mentioned objectives. FORMULA 3218 is a concentrated

    liquid also containing a phosphonate sequestrant. FORMULA

    3214 is a powdered formulation that would be most cost-effective

    for large systems.

    ALL RIGHTS RESERVED. Do not duplicate this document by any method without prior written

    FORMULAs DL-1542 through DL-1547 are glutaraldehyde

    based microbiocides. These non-oxidizing-type biocides are

    preferred for disinfection of new systems as they would not

    adversely effect the new, un-passivated metallurgies as would

    high dosages of chlorine. Once diluted in the system's waters,

    they are compatible with the above referenced

    cleaning/passivation formulations.

    Oxidizing chlorine based disinfectants such as sodium

    hypochlorite liquid (FORMULA 1582) or chlorinated

    isocyanurate powder (FORMULA 1588-G) are both good

    sources of chlorine that can be used prudently with the above

    referenced products. Maintenance of chlorine residuals at 1-

    2 ppm free chlorine should be quite sufficient to compliment

    the above cleaning-passivation program without necessarily

    hindering initial system passivation.

    NOTE: The CDC/Wisconsin guidelines for start-up of existing

    systems and emergency disinfection of systems containing

    objectionable concentrations of Legionella specify chlorine

    dosages of 25 and 50 ppm and maintenance of 10 ppm for 24

    hours.

    After circulating the above solution for 24 to 48 hours, drain and

    flush the system by procedures described above and in

    accordance with specific system characteristics learned during

    initial system flushing. IMMEDIATELY refill the system with

    clean water and add the final passivation and disinfection

    formulations specified by the water treatment specialist and as

    generally described below.

    Final Passivation and Disinfection

    SERIES 1930 Formulations are concentrated mixtures of

    molybdate, complex polyphosphates, orthophosphate, and azole

    yellow metal-based corrosion inhibitors ideal for passivation of

    cooling systems. The formulations also contain phosphonates and

    multi-functional polymer dispersants to aid product performance

    during initial one to two weeks of system operation provided the

    system only experiences moderate heat loads and is operated atlow cycles to aid in maintaining operation at pH 7.0 to 7.5.

    Feed microbiocides as deemed necessary and specified by the

    water treatment specialist serving the facility. This program

    could utilize the same products referenced above and selected for

    the initial cleaning process.

    The SERIES 1930 passivation program may not require system

    flushing. At start-up, simply initiate the automated bleedoff valve

    to regulate desired cycles of concentration. The SERIES 1930

    passivation formulation will be removed by normal system

    bleedoff and replaced by the specific corrosion/scale inhibitor and

    dispersant formulation specified by the facility's water treatmentspecialist for use during the on-going treatment program

    permission from Chemical Solution, Inc.