New Series 700 AV/T-S Power Conditioner - Transtector · 2019. 3. 15. · 1402-012 2.1.2 LISTINGS...
Transcript of New Series 700 AV/T-S Power Conditioner - Transtector · 2019. 3. 15. · 1402-012 2.1.2 LISTINGS...
Series 700 AV/T-S Power ConditionerDesigned for Varian NovalisTM TX, TrilogyTM IX with ExacTRACTM and OBI or TruebeamTM STX, TruebeamTM with ExacTRACTM and OBI or any system with a high energy accelerator, ExactracTM and OBI
Input Voltages: 208 VAC, 240 VAC, 480 VAC or 600 VAC (60 Hz)Output Voltages: 208/120 VAC, 480/277 VAC and 120 VAC
▪ Integrated Input and Output Breakers
▪ One Input Breaker - Four Output Breakers
▪ Intelligent Voltage Regulation (+ 2.5% Output Typical)
▪ Output Voltage Monitoring
▪ Internal Bypass Switch
▪ Triple Shielded Isolation Transformer
▪ Internal TVSS
▪ Front Access “Zero Clearance” Cabinet
Quadruple Output Power Conditioner with Voltage RegulationSubmittal Package and Specifications
112283
2Quadruple Output Power Conditioner l A&E Specs/Submittal Package
TRANSTECTOR SERIES 700 AV/T-S
Specifications for Quadruple Output 60 Hz Power Conditioner, designed for Varian NovalisTM TX, TrilogyTM IX with ExacTRACTM and OBI or TruebeamTM STX, TruebeamTM with ExacTRACTM and OBI or any system with a high energy accelerator, ExactracTM and OBI.
1.0 SCOPE
This specification covers the electrical characteristics of the Transtector Power Conditioner which provides clean regulated power for the entire NovalisTM TX, TrilogyTM IX with ExacTRACTM and OBI or TruebeamTM STX, TruebeamTM with ExacTRACTM and OBI or any system with a high energy accelerator, ExactracTM and OBI.
2.0 GENERAL
The Power Line Conditioner consists of a front access power cabinet incorporating an all copper, multiple tapped, triple shield isolation/regulation transformer. The ultra low output impedance of the transformer in conjunction with the electrostatic shields assures precision hospital grade performance with excellent noise and transient attenuation. Independently controlled inverse parallel electronic switches for each of the 7 taps per phase provide tight regulation over a wide input range. Linear devices are used for line synchronization to prevent phase shift errors normally associated with simple CT zero current crossing acquisition. The microprocessor control accurately selects the correct tap to maintain the output no greater than + 2.5% of nominal in a typical installation, correcting for voltage disturbances within one cycle. Digital processing technique provides fast and accurate regulation without output voltage over or undershoots.
2.01 MODEL NUMBERSMODEL INPUT VOLTAGE OUTPUT VOLTAGESStandard Models - other configurations are available including 50 Hz
Model Input Voltage Output Voltages8BLNX-160 K (i) -700AV/T-S 208 VAC nominal 208/120 VAC, 480/277 VAC and 120 VAC8CLNX-160 K (i) -700AV/T-S 240 VAC nominal 208/120 VAC, 480/277 VAC and 120 VAC8DLNX-160 K (i) -700AV/T-S 480 VAC nominal 208/120 VAC, 480/277 VAC and 120 VAC8ELNX-160 K (i) -700AV/T-S-C 600 VAC nominal 208/120 VAC, 480/277 VAC and 120 VAC
2.1 AGENCIES
2.1.1 STANDARDS
The systems shall be designed in accordance with:
▪ American National Standards Institute
▪ Institute of Electrical and Electronic Engineers
▪ National Electric Code (NEC)
▪ National Fire Protection Association (NFPA Article 70)
▪ Underwriters Laboratories (UL) 1449, 1012
▪ FCC Article 15, Section J, Class A
▪ ISO 9001
3
1402-012
2.1.2 LISTINGS
▪ The system shall be listed to C-UL, UL standard UL1012.
▪ The system shall comply to: FCC Article 15, Section J, Class A and ANSI C62.14 (electromagneticcompatibility).
▪ The SPD shall be UL 1449 3rd Edition listed/recognized.
3.0 DYNAMIC ELECTRICAL CHARACTERISTICS
3.1 OPERATING VOLTAGE AND OUTPUTS
The input voltage shall be 208 VAC, 240 VAC or 480 VAC, Delta, three phase, 60Hz. Each unit will be pre-wired at the factory to accommodate the nominal input voltage selected. Units with other input voltages (i.e. 380, 400, 415, 600 VAC) and/or frequencies (50 Hz) are produced upon request.
3.2 LINE VOLTAGE REGULATION Usable Input Line Voltage +15%, -23%.Nominal Input Line Voltage +10% to -15%
3.2.1 OUTPUT VOLTAGE REGULATION + 2.0% to + 2.5% typical.
The design of the system shall indicate that with an input voltage of -10% of nominal, increasing the load to 1000% shall cause the output voltage to fall no lower than -6%.
3.3 OUTPUT VOLTAGES Two (2) separate WYE configured, 3 phase voltage outputs shall be provided as follows:Output #1 shall be 208/120 VAC.Output #2 shall be 208/120 VAC or 480/277 VAC.Output #3 shall be 480/277 VAC.A single (1) phase voltage output shall be provided as follows:Output #4 shall be 120 VAC.
3.4 OUTPUT CONNECTIONSOutput #1: 150 Amp, three (3) pole circuit breaker for Linear Accelerator or a 175 Amp three (3) pole circuit
breaker for TrueBeamTM.Output #2: 100 Amp, three (3) pole circuit breaker if 208 VAC, or a 70 Amp three (3) pole 480 VAC circuit breaker
for the BrainLAB ExacTRACTM generator.Output #3: 60 Amp, three (3) pole circuit breaker for OBI or a 90 Amp three (3) pole circuit breaker for
TrueBeamTM.Output #4: 30 Amp, single (1) pole circuit breaker for power peripherals.
** The TrueBeamTM STx will use either the 175 Amp 208 VAC output or the 90 Amp 480 VAC output.
Refer to chart on page #8 for output configurations.
4Quadruple Output Power Conditioner l A&E Specs/Submittal Package
3.5 INPUT/OUTPUT WIRINGThe input/output wiring sizes are dependant upon the terminals provided by the circuit breakers.
Input wiring sizes: 208 VAC 300 Amp breaker #1 AWG to #600 KCMIL
240 VAC 250 Amp breaker #3/0 AWG to #350 KCMIL480 VAC 150 Amp breaker #14 AWG to #3/0 AWG600 VAC 100 Amp breaker #14 AWG to #3/0 AWG
Output wiring sizes:208/120 VAC 175 Amp breaker #4 AWG to #4/0 AWG
208/120 VAC 150 Amp breaker #14 AWG to #3/0 AWG208/120 VAC 100 Amp breaker #14 AWG to #3/0 AWG480/277 VAC 90 Amp breaker #14 AWG to #3/0 AWG480/277 VAC 70 Amp breaker #14 AWG to #3/0 AWG480/277 VAC 60 Amp breaker #14 AWG to #3/0 AWG120 VAC 30 Amp breaker #14 AWG to #2 AWG
Refer to chart on page #8 for output configurations.
The ILSCO TA-2/0 terminal allows wire sizes from #14 to 2/0 to be connected to the ground.
3.6 RESPONSE TIME Response time is less than 1/2 cycle.
3.7 CORRECTION TIME The output voltage is corrected within 1 cycle.
3.8 LOAD REGULATION The output is maintained to within 2% of nominal or less, from no load to full load.
3.9 IMPEDANCEOutput #1 and Output #2: impedance shall be less than 2.33% (Measured with the linear accelerator in beam on state @45 KVA with the OBI and ExacTracTM @ 5 KVA continuous) Output #3: impedance shall be less than 1.45% (45.9 mOhms) (Measured with the linear accelerator in ready state @ 20 KVA, ExacTracTM in standby state @ 5 KVA and OBI @ 45.7 KVA (55 A) momentary)
3.10 OPERATING FREQUENCY 60 Hertz + 3 Hertz.
3.11 HARMONIC DISTORTIONLess than 1% THD added to the output waveform under any dynamic linear loading conditions presented to the line regulator.
3.12 TURN-ON CHARACTERISTICS When energized the voltage overshoot is 5% or less of the nominal voltage for less than 1 cycle.
3.13 OVERLOAD RATING 200% for ten seconds. 1000% for one cycle.
5
1402-012
3.14 NOISE ATTENUATION Common mode noise attenuation is typically 140 dB or greater.Transverse mode noise attenuation is 3 dB down at 1000 Hertz, 40 dB down per decade to below 50 dB with a resistive load.
3.15 AUDIBLE NOISE Not to exceed 55dB measured @1 meter.
3.16 EFFICIENCY Efficiency shall be > 96% typical at full load. Excitation losses shall be less than 1.5% of KVA rating.
3.17 BTU The Power Line Conditioner shall generate no more than 10,230 BTU/Hour in typical use.
3.18 POWER FACTORInput power factor shall be greater than .95 with a resistive load and reflect no triplen harmonics to the utility under non-linear loads.
3.19 LINE TO LINE BALANCE The Power Line Conditioner shall not produce more than a 2% phase to phase unbalance.
3.20 MTBFThe system shall exhibit a MTBF > 10,000Hr.
3.21 ENHANCED TRANSIENT OVER VOLTAGE SURGE SUPPRESSIONAn enhanced surge protection device (SPD) shall be installed parallel to the secondary output of the power line conditioner to provide all mode, bi-directional and bi-polar surge protection. The SPD is rated for 100 KA per phase, 50 KA per mode capacity. (L-L, L-N, L-G, N-G) The surge suppressor shall be listed to UL 1449 3rd edition ratings when subjected to ANSI/IEEE 62.41-1991 category 3 waveforms. Unit shall conform to UL 1283 requirements for electromagnetic interference. Unit shall provide attenuation against EMI/RFI noise up to 50 dB at 1MHz. The surge suppressor is installed on the load side of the transformer, connected in parallel.
4.0 MAIN TRANSFORMER
4.1 BASIC CONSTRUCTION The transformer windings are of all copper conductor construction with separate primary and secondary isolated windings.
4.2 MAGNETICGrain oriented, stress relieved silicon transformer steel is utilized to minimize losses and provide maximum efficiency. Flux density will not exceed 14k gauss.
4.3 INSULATION Class N (200° C) insulation is utilized throughout.
4.4 SHIELDING The transformer has multiple (three) copper shields to minimize inner winding capacitance, transient and noise coupling between primary and secondary windings. Inner winding capacitance is limited to .001 pf or less.
4.5 COOLING The transformer is designed for natural convection cooling. Fans are inside the unit.
6Quadruple Output Power Conditioner l A&E Specs/Submittal Package
4.6 OPERATING TEMPERATURE The system operating range: 0 to 40 degrees Celsius, 32 to 104 degrees Fahrenheit.
4.7 OPERATING HUMIDITY0-95% relative humidity, non-condensing.
5.0 MAIN INPUT BREAKER
A main input molded case thermal magnetic circuit breaker, rated at 125 % of the full load input current, is furnished as an integral part of the unit. For example, a 300 Amp input breaker will be provided for 208 VAC input, a 250 Amp input breaker will be provided for a 240 VAC input, or a 150 Amp input breaker will be provided for 480 VAC input. A 100 Amp input breaker will be provided for 600 VAC input.
6.0 BY-PASS SWITCH
A manually operated rotary bypass switch provides bypassing of the SCR controlled voltage regulator portion of the Power Line Conditioner. The Power Line Conditioner can be operated in either the on-line or bypassed mode with one turn of the switch. The transformer and surge suppression circuitry remains in the circuit when in the bypass mode. All nominal output voltages, 208/120 and 480/277 VAC three (3) phase 4 wire, and 120 VAC single (1) phase will remain available in the bypass mode. The bypass switch is located on the front of the unit.
7.0 MONITORING
7.1 ALERT LIGHT An indicator light shall annunciate that the output has been disabled by one of the following conditions. (1) Transformer over-temperature.(2) SCR thermal over-temperature.
7.2 INPUT OUT OF RANGE LEDs
Input “Out of Range” red indicating LEDs shall be provided for each phase. If any phase of the input voltage source exceeds the specified +10%, -15% from nominal, the appropriate phase LED shall be illuminated.
7.3 INDICATING LAMPS Output “ON” indicating lamps shall provided for each phase.
7.4 OUTPUT VOLTAGE METERS
Two (2) digital output meters shall be provided. One shall monitor the 208/120 VAC output and the other shall monitor the 480/277 VAC output. Each meter shall monitor and display Line-to-Line and Line-to-Neutral voltages.
Minimum and maximum voltage values shall be recorded in EPROM. High and low output voltage limit alarms shall be programmable and a visual indication given if limits are exceeded.
8.0 CABINET
8.1 TERMINATIONTerminations is front access with input and output connections to the input and output circuit breakers. A ground terminal will also be provided, Ilsco TA-2/0.
The unit is constructed using an isolation transformer and is considered to be a “separately derived system”. It should be grounded in accordance with the NFPA 70 article 250.20 “Alternating-Current Circuits and Systems to be Grounded”, article 250.20 (D) “Separately Derived Systems” and article 250.30 “Grounding Separately Derived Alternating-Current Systems”.
The Output Neutral and Ground connection points are common to both WYE outputs (208/120 VAC & 480/277 VAC).Therefore, it is considered a single, separately derived, power source and should be wired accordingly.
7
1402-012
8.2 VENTILATIONVentilation originates from the front of the cabinet, exiting through the top and/or sides.
8.3 MOBILITYThe Power Line Conditioner cabinets are equipped with angle iron supports that allow for transport by pallet jack or fork lift. These can be used for mounting unit to the floor in seismic zones.
8.4 ACCESSIBILITYThe Power Line Conditioner will have front access. Access to all wiring inputs, outputs, and breakers will be accessible through the front access door or panels. The output meters and bypass switch will be located on the front of the unit. The back of the unit may be set next to a wall without impeding access. It will also incorporate lift off side panels.
8.5 WEIGHTUnit weight: Approximately 2,194 lbs. (995.18 kg.).
8.6 DIMENSIONS76” Height x 34.5” Wide x 35.875” Deep (193.04 cm. x 87.63 cm. x 91.12 cm.).
9.0 CONTROLS
The control portion of the cabinet containing the circuit boards and connection to the semi-conductor devices is separate from the transformer section and apart from the input/output power connections.
10.0 WARRANTY
Units shall include a comprehensive warranty for the first year, covering all parts and workmanship, inclusive of on site labor and travel expenses in geographical areas covered. Consult factory for details. All units are provided with a standard two (2) year warranty covering parts and workmanship.
11.0 SERVICE
Transtector shall provide immediate phone support/consultation and if possible, same day parts shipment. (contact must be prior to 12:00 PM PST). If necessary, on site service shall be scheduled the same day for service to be conducted within 24 to 48 hours, based on customer requirements. Typical service hours are 8 AM to 5 PM Monday through Friday.
12.0 CONTACT
Rick Ribbeck
Phone: (O) 208-635-6400 Ext. 5867 | (M) 208-762-6112
E-mail: [email protected]
E-mail: [email protected]
Transtector Systems
10701 Airport Dr.
Hayden Lake ID 83835
8Quadruple Output Power Conditioner l A&E Specs/Submittal Package
OUTPUT KVA INPUT BREAKER SIZE
160 K(I)
300 A @ 208 VAC 250 A @ 240 VAC
150 A @ 480 VAC
100 A @ 600 VAC
WEIGHTS, BTU AND DIMENSIONS UNIT SIZE IN
KVA (I)WEIGHT OPERATIONAL
BTU/HR TYPICALMAXIMUM
BTU/HRDIMENSIONS
160 K(I) 2,194 lbs. 995.18 kg.
5,115* 10,230 76” H x 34.5” W x 35.875” D(193.04 cm. x 87.63 cm. x 91.12 cm.2)
* Stated BTU’s / Hr is at 100% rated load, 100% duty cycle. Operational BTU’s / Hr is typically at 50% of ratedload. Input over current protection provided by others.
INPUT AND OUTPUT CONFIGURATION
INPUT
OUTPUT
NovalisTM TX - TrilogyTM with ExacTRACTM Output Breaker Configurations
TrueBeamTM STx - TrueBeamTM with ExacTRACTM Output Breaker Configurations
BRL #1 BRL #2 (Varian preferred breakers) BRL #6150 A 208 VAC CB for the Linear Accelerator 150 A 208 VAC CB for the Linear Accelerator 150 A 208 VAC for the Linear Accelerator
100 A 208 VAC CB for the BL Generator 70 A 480 VAC CB for the BL Generator 70 A 480 VAC CB for the BL Generator
60 A 480 VAC CB for the OBI 60 A 480 VAC CB for the OBI 60 A 480 VAC CB for the OBI
30 A 120 VAC CB for the BL Computers 30 A 120 VAC CB for the BL Computers 30 A 120 VAC CB for the BL Computers
30 A 120 VAC CB for the VMS Computers
BRL #4 BRL #5150 A 208 VAC CB (Not Used) 175 A 208 VAC CB for the TrueBeam
TM
70 A 480 VAC CB for the BL Generator 70 A 480 VAC CB for the BL Generator
90 A 480 VAC CB for the TrueBeamTM
60 A 480 VAC CB (Not Used)
30 A 120 VAC CB for the BL Computers 30 A 120 VAC CB for the BL Computers
9
1402-012
SEISMIC CALCULATIONS
Coastal California, Zone 4 Z = 0.4
Equipment Anchorage I = 1.5
Uniform Building Code, Table 160 Cp = 0.75
Cabinet Weight 2100 lbs.
Center of Gravity Height 33 in.
Wp (max) 2,415.0 lbs.
Wp (min) 1,785.0 lbs.
Vertical Force Fp = 0.45 x 2415 = 1,086.8 lbs.
Moment Fp = 0.15 x 2415 = 1,086.8 lbs.
Mo = 33 x 1086 = 35,863 in. lbs.
Corners (a,b) 43.1 in
V1 = V4 = 21.6
Tension = Fp x Cg / V4 = 3,213.6 lbs.
Shear = Wp(max)Fp/4 lbs., each anchor = 603.8
EXAMPLE: <Rawl Power Bolt # 6913>
3/8” embedded 2.5”in minimum 2000 psi concrete
Tension rating of bolt: 5,200 lbs.
Shear rating of bolt: 7,270 lbs.
Interaction = (T/Tbolt) + (S/Sbolt)
Interaction = 0.70
Interaction = < 1 (OK)
10Quadruple Output Power Conditioner l A&E Specs/Submittal Package
CABINET OUTLINE
8.00
0
T.SZW
AST
REVI
SED
OUTP
UT B
REAK
ER, A
DDED
KNO
CK-O
UTS I
NTO
P, R
ECRE
ATED
IN C
ADRA
FOR
POW
ERW
AY D
ATA
BASE
3/30
/090
84 3
ADDE
D OU
TPUT
MET
ERS A
ND M
OVED
125A
OUT
PUT
BREA
KER
4/28
/200
8D.
CAR
LSON
2UP
DATE
D PR
INT T
O RE
FLEC
T ONL
Y NE
UTRA
L AND
GROU
ND O
UTPU
T BUS
.2/
1/20
08D.
CAR
LSON
1CH
ANGE
D IN
PUT G
ROUN
D LU
G AN
D CH
ANGE
D (1
)20
8V O
UTPU
T CIR
CUIT
BRE
AKER
TO 15
0A.
D. C
ARLS
ON1/
21/2
008
REV.
DESC
RIPT
ION
DATE
BY
REVI
SIONS
OU
TPU
T M
ETER
S
(4)Ø
.875
KN
OC
K-O
UTS
4
BOTT
OM
VIE
W
R
36" C
LEA
RAN
CE
REQ
UIR
ED O
N F
RON
T SI
DE
FOR
SERV
ICE
OF
REG
ULA
TOR
SEC
TIO
NLI
FT O
FF A
CC
ESS
PAN
ELS
REQ
UIR
E C
OM
MO
N H
AN
D T
OO
L FO
R A
CC
ESS.
REA
R PA
NEL
S M
AYB
E RE
MO
VED
TO
DEC
REA
SE D
EPTH
. MU
ST B
E RE
INST
ALL
ED.
NO
TE:
.060
= 1
6GA
. .1
35 =
10G
A.
.048
= 1
8GA
. .1
05 =
12G
A.0
36 =
20G
A.
.075
= 1
4GA
.
Hay
den
Lake
, ID
838
35SU
PERI
OR
SURG
E SU
PPRE
SSIO
N
OU
TPU
T VO
LTA
GES
: 120
/208
VA
C &
277
/480
VA
CIN
PUT
VOLT
AG
ES: 2
08, 2
40, 4
80, O
R 60
0VA
C8(
BCD
E)LN
X-16
0K(i)
-700
AV/
T-S
SERI
ES 7
00A
FRO
NT
AC
CES
S C
ABI
NET
OU
TLIN
E
COPP
ER B
US
OU
TPU
T TE
RMIN
ATI
ON
S
WIR
E RA
NG
E: 2
/0-#
14 S
TR.
INPU
T G
ROU
ND
LU
G (1
) TA
2/0
TO T
OP)
(CU
STO
MER
'S IN
PUT
CO
NN
ECTS
INPU
T C
IRC
UIT
BRE
AKE
R
TERM
INA
TIO
N A
CC
ESS
ARE
ATO
P IN
PUT/
OU
TPU
T
OU
TPU
T FI
LTER
, OU
TPU
T TE
RMIN
ATI
ON
S A
ND
CU
RREN
T TR
AN
SFO
RMER
S.RE
MO
VABL
E TO
P PA
NEL
PRO
VID
ES A
CC
ESS
TO T
RAN
SFO
RMER
,
TERM
INA
TIO
N A
CC
ESS
ARE
AO
PTIO
NA
L SI
DE
OU
TPU
T
TERM
INA
TIO
N A
CC
ESS
ARE
ABO
TTO
M IN
PUT/
OU
TPU
T
DET
AIL
A
AIR
FLO
W
1/18
/200
8D
.CA
RLSO
N
76.0
00
3.00
0
BYPA
SS S
WIT
CH
AIR
INLE
T
14.0
006.
895
23.0
00
15.8
75
3.71
6
5.69
0
FRO
NT
VIEW
4.85
0
8.25
0
4.50
02.
810
35.5
00
RIG
HT
SID
E VI
EWLE
FT S
IDE
VIEW
6.89
5
30.2
71
2.73
9
30.7
50
Ø.5
62 x
1.0
00
2.46
9
3.87
5
34.5
00
REA
R VI
EW
AIR
FLO
W
OU
T O
F RA
NG
E &
MO
NIT
OR
ALE
RTLI
GH
TS
: 1:8
SCA
LETO
LERA
NCE
3O
F1
SHEE
T
PRO
HIB
ITED
.TR
AN
STEC
TOR
IS
WIT
HO
UT
THE
WRI
TTEN
PER
MIS
SIO
N O
FRE
PRO
DU
CTI
ON
IN P
ART
OR
AS
A W
HO
LETR
AN
STEC
TOR.
AN
Y D
RAW
ING
IS T
HE
SOLE
PRO
PERT
Y O
FTH
E IN
FORM
ATI
ON
CO
NTA
INED
IN T
HIS
.
.
MA
TERI
AL:
REV
DW
G.
NO
.
DA
TE
CHEC
KED
DRA
WN
PRO
PRIE
TARY
AN
D C
ON
FID
ENTI
AL
"
SEE D
ETAI
L A
SEE D
ETAI
L A INPU
T BR
EAKE
R SI
ZE30
0 A
@ 2
08 V
AC25
0 A
@ 2
40 V
AC15
0 A
@ 4
80 V
AC10
0 A
@ 6
00 V
AC
BR
L #1
BR
L #2
(Var
ian
pref
erre
d br
eake
rs)
BR
L #6
150
A 20
8 VA
C C
B fo
r the
Lin
ear A
ccel
erat
or15
0 A
208
VAC
CB
for t
he L
inea
r Acc
eler
ator
150
A 20
8 VA
C fo
r the
Lin
ear A
ccel
erat
or10
0 A
208
VAC
CB
for t
he B
L G
ener
ator
70
A 4
80 V
AC C
B fo
r the
BL
Gen
erat
or70
A 4
80 V
AC C
B fo
r the
BL
Gen
erat
or60
A 4
80 V
AC C
B fo
r the
OBI
60 A
480
VAC
CB
for t
he O
BI60
A 4
80 V
AC C
B fo
r the
OBI
30 A
120
VAC
CB
for t
he B
L C
ompu
ters
30 A
120
VAC
CB
for t
he B
L C
ompu
ters
30 A
120
VAC
CB
for t
he B
L C
ompu
ters
30 A
120
VAC
CB
for t
he V
MS
Com
pute
rs
BR
L #4
BR
L #5
150
A 20
8 VA
C C
B (N
ot U
sed)
175
A 20
8 VA
C C
B fo
r the
Tru
eBea
mTM
70 A
480
VAC
CB
for t
he B
L G
ener
ator
70 A
480
VAC
CB
for t
he B
L G
ener
ator
90 A
480
VAC
CB
for t
he T
rueB
eam
TM60
A 4
80 V
AC C
B (N
ot U
sed)
30 A
120
VAC
CB
for t
he B
L C
ompu
ters
30 A
120
VAC
CB
for t
he B
L C
ompu
ters
Nov
alis
TM T
X - T
rilog
yTM w
ith E
xacT
RAC
TM O
utpu
t Bre
aker
Con
figur
atio
ns
True
Bea
mTM
STx
- Tr
ueB
eam
TM w
ith E
xacT
RAC
TM O
utpu
t Bre
aker
Con
figur
atio
ns
11
1402-012
CABINET OUTLINE
8.00
0
Ø.8
75 K
NO
CK-
OU
TS
4
R
TOP
INPU
T/O
UTP
UT
TERM
INA
TIO
N A
CC
ESS
ARE
A
REM
OVA
BLE
TOP
PAN
EL
OPT
ION
AL
SID
E O
UTP
UT
TERM
INA
TIO
N A
CC
ESS
ARE
A
BOTT
OM
INPU
T/O
UTP
UT
TERM
INA
TIO
N A
CC
ESS
ARE
A
SERI
ES 7
00A
FRO
NT
AC
CES
S C
ABI
NET
OU
TLIN
E8(
BCD
E)LN
X-16
0K(i)
-700
AV/
T-S
INPU
T VO
LTA
GES
: 208
, 240
, 480
, OR
600V
AC
OU
TPU
T VO
LTA
GES
: 120
/208
VA
C &
277
/480
VA
C
SUPE
RIO
R SU
RGE
SUPP
RESS
ION
Hay
den
Lake
, ID
838
35
.036
= 2
0GA
. .0
75 =
14G
A.
.048
= 1
8GA
. .1
05 =
12G
A.0
60 =
16G
A.
.135
= 1
0GA
.
AIR
FLO
WRI
GH
T SI
DE
VIEW
4.75
0
2.81
24.
500
8.25
0
FRO
NT
AIR
OU
TLET
35.5
15
15.8
75
3.71
6
5.75
034
.389
23.0
00
1.87
5
3.36
4
6.89
514
.000
FRO
NT
Ø.562 X 1.000
3.72
36.
895
2.46
9
30.2
501.
954
30.7
50
2.73
9
D.C
ARL
SON
1/18
/200
8
BOTT
OM
VIE
W
TOP
VIEW
: 1:4
SCA
LETO
LERA
NCE
THE
INFO
RMA
TIO
N C
ON
TAIN
ED IN
TH
ISD
RAW
ING
IS T
HE
SOLE
PRO
PERT
Y O
FTR
AN
STEC
TOR.
AN
Y RE
PRO
DU
CTI
ON
IN P
ART
OR
AS
A W
HO
LEW
ITH
OU
T TH
E W
RITT
EN P
ERM
ISSI
ON
OF
TRA
NST
ECTO
R IS
PRO
HIB
ITED
.
SHEE
TO
F
"
PRO
PRIE
TARY
AN
D C
ON
FID
ENTI
AL
DRA
WN
CHEC
KED
DA
TE
DW
G.
NO
.RE
V
MA
TERI
AL:
.
.
12Quadruple Output Power Conditioner l A&E Specs/Submittal Package
CABINET OUTLINE
4
R
SERI
ES 7
00A
FRO
NT
ACC
ESS
CABI
NET
OU
TLIN
E8(
BCD
E)LN
X-16
0K(i)
-700
AV/
T-S
INPU
T VO
LTA
GES
: 208
, 240
, 480
, OR
600V
AC
OU
TPU
T VO
LTA
GES
: 120
/208
VA
C &
277
/480
VA
C
SUPE
RIO
R SU
RGE
SUPP
RESS
ION
Hay
den
Lake
, ID
838
35
.036
= 2
0GA
. .0
75 =
14G
A.
.048
= 1
8GA
. .1
05 =
12G
A.0
60 =
16G
A.
.135
= 1
0GA
.
TOP
VIEW
FRO
NT
D.C
ARL
SON
1/18
/200
8
: 1:4
SCA
LETO
LERA
NCE
THE
INFO
RMA
TIO
N C
ON
TAIN
ED IN
TH
ISD
RAW
ING
IS T
HE
SOLE
PRO
PERT
Y O
FTR
AN
STEC
TOR.
AN
Y RE
PRO
DU
CTIO
N IN
PA
RT O
R A
S A
WH
OLE
WIT
HO
UT
THE
WRI
TTEN
PER
MIS
SIO
N O
FTR
AN
STEC
TOR
IS P
ROH
IBIT
ED.
SHEE
TO
F
"
PRO
PRIE
TARY
AN
D C
ON
FID
ENTI
AL
DRA
WN
CHEC
KED
DAT
E
DW
G.
NO
.RE
V
MA
TERI
AL:
.
.